price bid/ boq - vol-iii is replaced with revised price...

89
Engineering Projects (India) Limited Contracts Division, CO. New Delhi DLI/CON/753/541 19.07.2016 Sub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLE POWER PLANT OF OTPC. Ref: NIT No. DLI/CON/753/541 dated 30.06.2016 Addendum No. – 4 Price Bid/ BOQ - Vol-III is replaced with Revised Price Bid/BOQ -Vol-III (R). The Revised Price Bid/BOQ - Vol-III (R) is enclosed as annexure “A”. All other terms and conditions shall remain unchanged. GGM (Contracts)

Upload: others

Post on 27-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Engineering Projects (India) Limited Contracts Division, CO. New Delhi

DLI/CON/753/541 19.07.2016

Sub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLE POWER PLANT OF OTPC.

Ref: NIT No. DLI/CON/753/541 dated 30.06.2016

Addendum No. – 4

Price Bid/ BOQ - Vol-III is replaced with Revised Price Bid/BOQ -Vol-III (R). The Revised Price Bid/BOQ - Vol-III (R) is enclosed as annexure “A”.

All other terms and conditions shall remain unchanged.

GGM (Contracts)

Page 2: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Annexure‐A

SL. NO

Description

Civil Works

a. Annexure-AA

b.Type-IV Quarter

c. Type-V Quarter

d. Club House

2 Sanitary/Plumbing Supply Installation Total Price

a.Type-IV Quarter

b. Type-V Quarter

a.Club House

3 Internal Electrification

a.Type-IV Quarter

b. Type-V Quarter

a.Club House

Signature & Stamp of Bidder

Name of Work: CONSTRUCTION OF TYPE‐IV, TYPE‐V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OFTOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLE POWER PLANT OFOTPC.

SUMMARY OF PRICE BID

Total Quoted Price

Total Quoted Price (in Figures)

Total Quoted Price (in Words)

1

Page 3: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Category -Piling Work1 Vertical load testing of piles in accordance with IS 2911 (Part IV)

including installation of loading platform and preparation of pilehead or construction of test cap and dismantling of test cap aftertest etc. complete as per specification & the direction of EngineerinA-charge:-

Single pile above 50 tonne and upto 100 tonne capacity pile:-

Initial test.18 Mtrs Piles Per Test 2.0024 Mtrs Piles Per Test 11.00Routine test.18 Mtrs Piles Per Test 2.0024 Mtrs Piles Per Test 11.00

2 Lateral load testing of single pile in accordance with IS Code ofpractice IS : 2911 (Part IV) for determining safe allowable lateralload on pile as per specification & the direction of Engineer inA-charge :-Above 50 tonne and upto 100 tonne capacity pile.18 Mtrs Piles Per Test 2.0024 Mtrs Piles Per Test 11.00

3 Integrity testing of Pile using Low Strain/ Sonic Integrity Test/Sonic Echo Test method in accordance with IS 14893 includingsurface preparation of pile top by removing soil, mud, dust &chipping lean concrete lumps etc. and use of computerisedequipment and high skill trained personal for conducting the test &submission of results, all complete as per direction of Engineer-in-charge.

18 Mtrs Piles Per Test 14.0024 Mtrs Piles Per Test 80.00

Additional items for Plumbing works31 Providing and fixing C.P. brass bib cock of approved quality

conforming to IS:893115 mm nominal bore each 60

32 Providing and fixing C.P. brass long nose bibcock of approvedquality conforming to IS standards and weighing not less than 810gms.15 mm nominal bore each 60TOTAL 0.00

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT“CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASEDCOMBINED CYCLE POWER PLANT OF OTPC.

Annexure-AACIVIL WORKS

2 of 88

Page 4: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6C TYPE-IV

Category -Carriage of MaterialsCarriage of materials by mechanical transport including loading,unloading and stackingEarth upto 1 Km Cum 1973.40

Category - Earth WorkEarth work in excavation over areas (exceeding 30cm in depth,1.5m in width as well as 10 sqm on plan) including disposal ofexcavated earth, lead upto 50m and lift upto 1.5m, disposed earthto be levelled and neatly dressed. All kinds of soil

By mechanical means Cum 2400.00Earth work in excavation in foundation trenches or drains (notexceeding 1.5 m in width or 10 sqm on plan) including dressing ofsides and ramming of bottoms, lift upto 1.5 m, including gettingout the excavated soil and disposal of surplus excavated soil asdirected, within a lead of 50 m. All kinds of Soil

By mechanical means Cum 600.00Extra rates for quantities of works, executed:In or under water and/ or liquid mud, including pumping out wateras required.

Cum 960.00

Filling available excavated earth (excluding rock) in trenches,plinth, sides of foundations etc. in layers not exceeding 20cm indepth, consolidating each deposited layer by ramming andwatering, lead up to 50 m and lift upto 1.5 m. All kinds of soil

Cum 1973.40

Extra for additional lift of 1.5m or part thereof All kinds of soil Cum 1973.40

Supplying and filling in plinth, under floor, foundations etc. withsand (fine) from local quarry with all lifts including spreading inhorizontal layers, watering, grading to required slope, ramming,consolidating and compacting each layer by using platecompactor or by any suitable method complete.

Cum 100.38

Supplying chemical emulsion in sealed containers includingdelivery as specified.Chlorpyriphos/Lindane emulsifiable concentrate of 20% Ltr 279.22Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite treatment (excluding the cost ofchemical emulsion) and continuous chemical barrier under andalround the column pits, wall trenches, basement excavation, topsurface of plinth filling, junction of wall and floor, along theexternal perimeter of building, expansion joints, over the topsurface of consolidated earth of which apron is to be laid,surroundings of pipes and conduits etc. complete as perspecification. The work should be carried out as per IS: 6313(Part II)- Latest revision [Plinth area of the building at ground flooronly shall be measured for payment] :

With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. Sqm 1116.88

Category - Concrete WorkProviding and laying in position cement concrete of specifiedgrade excluding the cost of centring and shuttering -

1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mmnominal size)

Cum 92.35

Centering shuttering including strutting, propping etc. and removalof form work for :Foundations, footings, bases for columns Sqm 15.08

CIVIL WORKS

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTIONOF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLEPOWER PLANT OF OTPC.

3 of 88

Page 5: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Extra for providing and mixing water proofing material in cementconcrete work @ 1 kg per 50 kg of cement.

per 50kg of bag

171.00

Extra for laying concrete in or under water and/or liquid mudincluding cost of pumping or bailing out water and removing slushetc. complete.Note [Item No. 4.5.5]: The quantity will becalculated by multiplying the depth measured from the sub-soilwater level up to the centre of gravity of concrete under sub-soilwater lebel with the quantity of concrete in cubic meter executedunder sub-soil water. The depth of centre of gravity shall bereckoned correct to 0.1m, 0.05m or more shall be taken as 0.1mand less than 0.05m ignored. No extra payment shall be made forplacing centering and shuttering under sub-soil water conditions.[unit of measuement = per cun per meter depth]

Cum/m depth

75.28

Making plinth protection 50mm thick of cement concrete 1:3:6 (1cement : 3 fine sand : 6 graded well burnt brick aggregate 20 mmnominal size) over 75mm bed of dry brick ballast 40mm nominalsize well rammed and consolidated and grouted with fine sandincluding finishing the top smooth.

Sqm 150.82

Category - RCCCentering shuttering including struttings, propping etc. andremoval of form work for:Foundations, footings, bases for columns etc. for mass concretewith steel formwork

Sqm 113.12

Walls (any thickness) including attached pilasters, buttresses,plinth and string courses etc. using shuttering ply with all leads &lifts complete for all floors.

Sqm 1112.40

Suspended floors, roofs, landings, balconies and access platformwith MS Plates and props with all leads & lifts complete for allfloors.

Sqm 4486.82

Lintels, beams, plinth beams, girders, bressumers and cantileverswith shuttering ply with all leads & lifts complete for all floors.

Sqm 6792.31

Columns, Pillars, Piers, Abutments, Posts and Struts with M.S.shutters with all leads & lifts complete for all floors.

Sqm 5363.32

Stairs (excluding landings) except spiral-staircases with woodenplank with all leads & lifts complete for all floors.

Sqm 145.53

Edges of slabs and breaks in floors and walls under 20 cm. wide Mtr 1659.02

Reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto all floorlevel including all leads and lifts.Thermo-Mechanically Treated bars/ Cold twisted deformed steelbars

Kg 428755.45

Extra for laying reinforced cement concrete in or under foulpositions.

Cum 462.84

Providing and laying in position ready mixed concretemanufactured in fully automatic batching plant and transported tosite of work in transit mixer for a lead upto 10kms havingcontinuous agitated mixer, manufactured as per mix design ofspecified grade for reinforced cementconcrete work includingpumpingof RMC from transit mixerto site of laying butexcludingthe cost of centring, shuttering, finishing andreinforcement, including admixtures in recommended proportionsas per IS 9103 to accelerate, retard setting of concrete, improveworkability without impairing strength and durability as per thedirection of Engineer-in-Charge.

All works upto plinth levelReinforced cement concrete grade M-35 using 440 kg of cementper cum

Cum 462.84

All works upto all floor level including all leads and lifts .Reinforced cement concrete grade M-25 using 410 kg of cementper cum

Cum 2018.52

Category - Brick Work

4 of 88

Page 6: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

First class brick work in superstructure above plinth level & uptoall floor level including all leads and lifts including cost of allmaterials as required complete:-

In cement mortar 1:4 ( 1 cement : 4 fine sand ). Cum 1381.83Half brick masonry work with first class bricks in superstructureupto floor five level including cost of all materials as requiredcomplete:-

In cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 2371.25Extra for half brick masonry work in superstructure above floor-Vlevel for each four floors or part thereof by mechanical means bylifting material using mobile crane as required complete.

Sqm 4742.50

Extra for providing and placing in position 2 Nos. 6mm dia. M.S.bars at every third course of half brick masonryIn cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 2371.25Cinder Filling Cum 211.02

Category - Marble WorkProviding and fixing 18 mm thick plain marble stone, mirrorpolished, machine cut for, kitchen platforms, vanity counters,facias and similar locations of required size of approved shade,colour and texture laid over 20 mm thick base of cement mortar1:4 ( 1 cement : 4 fine sand ) with joints treated with white cement,mixed with matching pigment, epoxy touch ups, including rubbing, curing etc. complete at all levels as required:-

Granite of any colour and shade duly approved:-Area of slab over 0.50 sqm. Sqm 195.25Providing and fixing 8mm mirror polished marble tile work for walllining over 12mm thick bed of cement mortar 1:3 (1 cement : 3fine sand) and cement slurry @ 3.3 kg/sqm including pointing inwhite cement complete including rubbing, curing etc. complete atall levels as required:-

Granite of any colour and shade duly approved . Sqm 541.70

Flamed Granite Sqm 95.70

Granite stone flooring with 18mm thick Granite of any colour(sample of granite stone shall be approved by Engineer-incharge)over 20 mm (average) thick base of cement mortar 1:4 (1 cement: 4 coarse sand) laid and jointed with grey cement slurry includingrubbing and polishing complete with : (Basic Cost of Granite stoneRs- 150/ per sqm)

Sqm 564.54

Category - Wood and PVC WorkProviding wood work in frames of doors, windows, clerestorywindows and other frames, wrought framed and fixed in position :

Local Teak Wood Cum 8.82

Providing and fixing ISI marked flush door shutters conforming toIS: 2202 (Part I) decorative type, core of block board constructionwith frame of 1st class hard wood and well matched teak 3 plyveneering with vertical grains or cross bands and face veneers onboth faces of shutters.

35 mm thick including ISI marked Stainless Steel butt hinges withnecessary screws.

Sqm 315.00

Providing and fixing curtain rods of 1.25 mm thick chromiumplated brass plate, with two chromium plated brass brackets fixedwith C.P. brass screws and wooden plugs, etc., wherevernecessary complete :25 mm dia Mtr 791.40

5 of 88

Page 7: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Providing and fixing special quality bright finished brass cupboardor ward robe locks with four levers including necessary screwsetc. complete (best make of approved quality):

50 mm No. 240.00Providing and fixing 50 mm bright finished brass cup board orwardrobe knob with necessary screws (best make of approvedquality)

No. 240.00

Providing and fixing bright finished brass handles with screws etc.complete :75 mm No. 240.00Providing and fixing aluminium sliding door bolts ISI markedanodised (anodic coating not less than grade AC 10 as per IS :1868) transparent or dyed to required colour or shade with nutsand screws etc. complete :300 X 16 mm No. 880.00Providing and fixing aluminium tower bolts ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868 )transparent or dyed to required colour or shade with necessaryscrews etc. complete :

300 X 10 mm No. 880.00Providing and fixing aluminium handles ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour or shade with necessaryscrews etc. complete :

125 mm No. 880.00Providing and fixing aluminium hanging floor door stopper ISImarked anodised (anodic coating not less than grade AC 10 asper IS : 1868) transparent or dyed to required colour and shadewith necessary screws etc. complete.

Single rubber stopper No. 880.00Providing and fixing factory made UPVC door frame made ofUPVC extruded, section having an overall dimension, as below(tolerance +/- 1mm) with wall thickness 2.0mm+/- 02mm. cornersof the door frame to be jointed with galvanized brackets andstainless screws, joint mitred and plastic wilded. The hinge sidevertical of the frames reinforced by galvanized MS tube of size 19A— 19 mm and 1 mm +/- 0.1 mm wall thickness and 3 nosstainless steel hinges fixed to the frame complete as permanufacturers specification and direction of Engineer-In-Charge.

Extruded section Profile size 48x40 mm. Mtr 2437.20Providing and fixing cup board shutters with 25mm thick veneeredparticle board IS : 3097 marked exterior grade (Grade I) ofapproved make including IInd class teak wood lipping of 25mmwide x 12 mm thick with necessary screws and bright finishedstainless steel piano hinges complete as per direction of Engineer-in-Charge.

With decorative veneering on one side and commercial veeringon other side.

Sqm 214.00

UPVC door/window/ventilator shutter Sqm 810.60UPVc Wire Gauge Shutter Sqm 348.60Fire Door Sqm 21.00Providing and fixing stainless steel (SS-304 grade) friction hingesto the side/ top hung uPVC windows, of approved quality withnecessary stainless steel screws etc. as per direction of Engineer-in-charge.250 x 19 x 1.9 mm No. 800.00Providing and fixing casement handle made of zinc alloyed (whitepowder coated) for uPVC casement window with necessaryscrews etc. complete.

No. 800.00

Category -Steel Work

6 of 88

Page 8: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Providing and fixing 1mm thick M.S. sheet door with frame of40x40x6mm angle iron and 3mm M.S. gusset plates at thejunctions and corners, & with cleats with bolts & nuts, rivets,locking arrangement, handles, hooks & eyes, pinlets includingembedding in cement concrete of required grade for fixing inposition, all necessary fittings, including applying a priming coat of approved steel primer etc. complete as required:-

Using M.S. angels 40x40x6 mm for diagonal braces. Sqm 8.40Steel work welded in built up section/framed work includingcutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer using steel etc. complete as required:-

In grating, frames, guard bar, railing, brackets, gates and similarworks, all complete.

Kg 23240.70

Providing and fixing stainless steel ( Grade 304) railing made ofHollow tubes, channels, plates etc. including welding, grinding,buffing, polishing and making curvature (wherever required) andfitting the same with necessary stainless steel nuts and boltscomplete i/c fixing the railing with necessary accessories &stainless steel dash fasteners , stainless steel bolts etc., ofrequired size, on the top of the floor or the side of waist slab withsuitable arrangement as per approval of Engineer-in-charge. (forpayment purpose only weight of stainless steel members shall beconsidered excluding fixing accessories such as nuts, bolts,fasteners etc.)

Kg 3156.28

Category - FlooringExtra for prefinished nosing to treads of steps of marble stones. Mtr 494.90

Extra for marble flooring complete in treads of steps and risersusing single length upto 2.00 metre.

Sqm 215.28

Providing and fixing 25 mm thick wooden planking, tongued andgrooved in floors including fixing with iron screws complete.

With teak wood local Sqm 482.40Providing and fixing 1st quality ceramic glazed wall tilesconforming to IS : 15622 ( thickness to be specified by themanufacturer ) of approved make in all colours, shades exceptburgundy, bottle green, black of any size as approved by Engineer-in-charge in skirting, risers of steps and dados over 12 mm thickbed of cement mortar 1 : 3 ( 1 cement : 3 fine sand ) jointed withordinary cement slurry including pointing with white cement mixedwith pigment of matching shade complete.

Sqm 2197.56

Providing and laying polished vitrified floor tiles in different sizes(thickness to be specified by the manufacturer ) with waterabsorption less than 0.08 % and conforming to IS : 15622 ofapproved make in all colours, shades over 20 mm thick bed ofcement mortar 1 : 4 ( 1 cement : 4 fine sand ) jointed with ordinarycement slurry including pointing with white cement mixed withpigment of matching shade complete.

Size of tile 60x60 cm Sqm 2416.72Providing and laying Vitrified tiles in different sizes (thickness tobe specified by manufacturer) with water absorption less than0.08 % and conforming to I.S. 15622, of approved make in allcolours & shade in skirting, riser of steps, over 12 mm thick bed ofcement mortar 1:3 (1 cement: 3 coarse sand), including groutingthe joint with white cement & matching pigments etc. complete.

Size of Tile 600x600 mm Sqm 263.40

7 of 88

Page 9: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Providing and laying 60mm thick factory made cement concreteinterlocking paver block of M -30 grade made by block makingmachine with strong vibratory compaction, of approved size,design & shape, laid in required colour and pattern over andincluding 50mm thick compacted bed of fine sand, filling the jointswith fine sand etc. all complete as per the direction of Engineer-in-charge.

Sqm 436.52

Providing and laying Non-Skid Ceramic glazed floor tiles 600x600mm (thickness to be specified by the manufacturer) of 1st qualityconforming to IS :15622 of approved make in colours such asWhite, Ivory, Grey, Fume Red Brown, laid on 20 mm thickCement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointingthe joints with white cement and matching pigment etc., complete.( Cost of basic tiles Rs 35/- per sft )

Sqm 1294.72

Category - RoofingMaking khurras 45x45 cm with average minimum thickness of 5cm cement concrete 1:2:4 (1 cement : 2 fine sand : 4 gradedstone aggregate of 20 mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1cement : 3 fine sand) and a coat of neat cement rounding theedge and making and finishing the outlet complete.

No. 24.00

Extra for any sunk or raised mouldings in the plaster of Paris(Gypsum anhydrous) ceiling.

Sqm 2682.80

Providing and fixing on wall face unplasticised Rigid PVC rainwater pipes (working pressure 4 kg / cm2) conforming to IS :13592 Type A including jointing with seal ring conforming to IS :5382 leaving 10 mm gap for thermal expansion:

Single socketed pipe - 110 mm OD Mtr 852.00Providing and fixing on wall face unplasticised - PVC mouldedfittings/ accessories for unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A including jointing with seal ringconforming to IS : 5382 leaving 10 mm gap for thermal expansion:

Coupler110 mm No. 24.00Single equal tee with door110x110x110mm No. 48.00Bend 87.5A°110mm No. 48.00Plain shoe110mm No. 24.00Providing and fixing to the inlet mouth of rain water pipe PTMTgrating with thickness of 8mm and weighing not less than 100gm.complete.

100mm No. 24.00

Category - Finishing12 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.

In cement mortar 1 6 ( 1 cement : 6 fine sand ) Sqm 6007.9615 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.In cement mortar 1 6 ( 1 cement : 6 fine sand ) Sqm 6007.9620 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing complete.

In cement mortar 1 4 ( 1 cement : 4 fine sand ) Sqm 3212.476 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.

8 of 88

Page 10: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

In cement mortar 1 : 3 ( 1 cement : 3 fine sand ) Sqm 4142.08Extra for plastering exterior walls of height more than 10 m fromGL for every additional height of 3 m or part thereof complete.

Sqm 25699.73

Providing and applying plaster of paris putty of 2 mm thicknessover plastered surface to prepare the surface even and smoothwith all leads & lifts complete for all floors..

Sqm 3711.43

Distempering with oil bound washable distemper of approvedbrand and manufacture and of required shade on new work ( twoor more coats ), over and including a priming coat of cementprimer to give an even shade with all leads & lifts complete for allfloors.

Sqm 4300.13

Finishing walls with water proofing cement paint of required shadeof approved brand and manufacture on new work ( two or morecoats applied @ 3.84 kg/10 sqm) with all leads & lifts completefor all floors.

Sqm 1608.89

Finishing walls with premium acrylic smooth exterior paint ofrequired shade of approved brand and manufacture on new work (two or more coats applied @ 1.43 kg/10 sqm ) over and includingbase coat water proofing cement paint applied @ 2.20 kg/10 sqmwith all leads & lifts complete for all floors.

Sqm 3212.47

Applying priming coat:With ready mixed red oxide zinc chromate primer of approvedbrand and manufacture on steel, galvanised iron / steel work.

Sqm 16.80

Wall painting with plastic emulsion paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 12015.91

Painting with synthetic enamel paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 16.80

Wall painting with Textured paint ( two or more coats ) of requiredcolour of approved brand and manufacture on new work to give aneven shade with all leads & lifts complete for all floors.

Sqm 7667.51

Unistone Wall Cladding Sqm 1412.23

Category - Piling WorkBoring, providing and installing bored cast-in-situ reinforcedcement concrete pile of specified diameter and length below thepile cap, to carry a safe working load not less than specified,excluding the cost of steel reinforcement and including the cost ofboring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of thepile to be embedded in the pile cap etc. all complete, includingremoval of excavated earth with all lifts and leads along withbreaking of pile head as per specification & the direction ofEngineer in- charge(Length of pile for payment shall be measuredupto bottom of pile cap), Note:(Depth of pile to be 18 mts to 25mtrs). Inclusive of all labour, materials enabling, mobilisation,demoblisation all costs included.

In M35 reinforced cement concrete:-500 mm dia piles. Mtr 5568.00

Category - ALUMINIUM WORKProviding and fixing aluminium work for doors, windows,ventilators, stair railings, including hand rail..For fixed portions of approved qualityAnodised aluminium.. Kg 6720.00

Category -Water Proofing

9 of 88

Page 11: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Providing and laying APP (Atactic Polypropylene Polymer)modified prefabricated five layer 3 mm thick water proofingmembrane, black finished reinforced with non-woven polyestermatt consisting of a coat of bitumen primer for bitumen membrane@ 0.40 ltr/sqm. by the same membrane manufacturer of densityat 25A°C, 0.87 a€" 0.89 kg/ltr and viscocity 70 a€" 160 cps. Overthe primer coat the layer of membrane shall be laid using butanetorch and sealing all joints etc. and preparing the surfacecomplete. The vital physical and chemical parameters of themembrane shall be: Joint strength in longitudinal and transversedirection at 23A°C 650/450 N/ 5 cm. Tear strength in longitudinaland transverse direction as 300/250 N. Softening point ofmembrane not less than 150A°C. Cold flexibility shall be upto -2A°C when tested in accordance with ASTM, D a€" 5147. Thelaying of membrane shall be got done through the authorisedapplicator of the manufacturer of membrane as required as perdirection of the Engineer-in-charge.

Sqm 562.72

Providing and laying integral cement based water proofingtreatment including preparation of surface as required fortreatment of roofs, balconies, terraces etc consisting of followingoperations: a) Applying a slurry coat of neat cement using 2.75kg/sqm. of cement admixed with water proofing compoundconforming to IS. 2645 and approved by Engineer-incharge overthe RCC slab including adjoining walls upto 300mm heightincluding cleaning the surface before treatment. b) Laying brickbats with mortar using broken bricks/brick bats 25 mm to 115mmsize with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)admixed with water proofing compound conforming to IS : 2645and approved by Engineer-incharge over 20 mm thick layer ofcement mortar of mix 1:5 (1 cement :5 coarse sand ) admixedwith water proofing compound conforming to IS : 2645 andapproved by Engineer-in-charge to required slope and treatingsimilarly the adjoining walls upto 300 mm height includingrounding of junctions of walls and slabs c) After two days ofproper curing applying a second coat of cement slurry using2.75kg/ sqm of cement admixed with water proofing compoundconforming to IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement mortar ofmix

1:4 (1 cement :4 coarse sand) admixed with water proofingcompound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in toplayer of plaster and finally finishing the surface with trowel withneat cement slurry and making pattern of 300x300 mm square3mm deep. e) The whole terrace so finished shall be flooded withwater for a minimum period of two weeks for curing and for finaltest. All above operations to be done in order and as directed andspecified by the Engineer-in-Charge :

With average thickness of 120mm and minimum thickness atkhurra as 65 mm.

Sqm 501.88

TOTAL FOR CIVIL WORKS TYPE-IV

10 of 88

Page 12: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

Carriage of materials by mechanical transport including loading,unloading and stackingEarth upto 1 Km Cum 759.95

Category - Earth WorkEarth work in excavation over areas (exceeding 30cm in depth,1.5m in width as well as 10 sqm on plan) includingdisposal ofexcavated earth, lead upto 50m and lift upto 1.5m, disposed earthto be levelled and neatly dressed. All kinds of soil

By mechanical means Cum 1474.25Earth work in excavation in foundation trenchesordrains(notexceeding 1.5min width or 10 sqm on plan) includingdressingof sides and ramming of bottoms, lift upto 1.5 m, including gettingout the excavated soil and disposal of surplus excavated soil asdirected, within a lead of 50 m. All kinds of Soil

By mechanical means Cum 600.00Extra rates for quantities of works, executed:In or under water and/ or liquid mud, including pumping out wateras required.

Cum 589.70

Filling available excavated earth (excluding rock) in trenches,plinth, sides of foundations etc. in layers not exceeding 20cm indepth, consolidating each deposited layer by ramming andwatering, lead up to 50 m and lift upto 1.5 m. All kinds of soil

Cum 1314.30

Extra for additional lift of 1.5m or part thereof All kinds of soil Cum 1474.25

Supplying and filling in plinth, underfloor, foundations etc. withsand (fine) from local quarry with all lifts including spreading inhorizontal layers, watering, gradingto required slope, ramming,consolidatingand compactingeach layer by using platecompactoror by any suitable method complete.

Cum 79.39

Supplying chemical emulsion in sealed containers includingdelivery as specified.Chlorpyriphos/Lindane emulsifiable concentrate of 20% Ltr 228.53Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite treatment (excluding the cost ofchemical emulsion) and continuous chemical barrier under andalround the column pits, wall trenches, basement excavation, topsurface of plinth filling, junction of wall and floor, along theexternal perimeter of building, expansion joints, over the topsurface of consolidated earth of which apron is to be laid,surroundingsof pipes and conduits etc. complete as perspecification. The work should be carried out as per IS: 6313(Part II)- Latest revision [Plinth area of the building at ground flooronly shall be measured for payment] :

With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. Sqm 914.12

Category - Concrete WorkProviding and laying in position cement concrete of specifiedgrade excluding the cost of centring and shuttering -

1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mmnominal size)

Cum 79.23

Centering shuttering including strutting, propping etc. and removalof form work for :Foundations, footings, bases for columns Sqm 15.03Extra for providing and mixing water proofing material in cementconcrete work @ 1 kg per 50 kg of cement.

per 50kg of bag

269.00

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTIONOF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLEPOWER PLANT OF OTPC.CIVIL WORKS

11 of 88

Page 13: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Extra for laying concrete in or under water and/or liquid mudincluding cost of pumping or bailing out water and removing slushetc. complete.Note [Item No. 4.5.5]: The quantity will becalculated by multiplying the depth measured from the sub-soilwater level up to the centre of gravity of concrete under sub-soilwater lebel with the quantity of concrete in cubic meter executedunder sub-soil water. The depth of centre ofgravityshall bereckoned correctto 0.1m, 0.05m or more shall be taken as 0.1mand less than 0.05m ignored. No extra payment shall be made forplacing centering and shuttering under sub-soil water conditions.[unit of measuement = per cun per meter depth]

Cum/m depth

59.54

Making plinth protection 50mm thick of cement concrete 1:3:6 (1cement : 3 fine sand : 6 graded well burnt brick aggregate 20 mmnominal size) over 75mm bed of dry brick ballast 40mm nominalsize well rammed and consolidated and grouted with fine sandincluding finishing the top smooth.

Sqm 150.32

Category - RCCCentering shuttering including struttings, propping etc. andremoval of form work for:Foundations, footings, bases for columns etc. for mass concretewith steel formwork

Sqm 120.26

Walls (any thickness) including attached pilasters, buttresses,plinth and string courses etc. using shuttering ply with all leads &lifts complete for all floors.

Sqm 906.40

Suspended floors, roofs, landings, balconies and access platformwith MS Plates and props with all leads & lifts complete for allfloors.

Sqm 3731.79

Lintels, beams, plinth beams, girders, bressumers and cantileverswith shuttering ply with all leads & lifts complete for all floors.

Sqm 5117.27

Columns, Pillars, Piers, Abutments, Posts and Struts with M.S.shutters with all leads & lifts complete for all floors.

Sqm 4301.28

Stairs (excluding landings) except spiral-staircases with woodenplank with all leads & lifts complete for all floors.

Sqm 142.56

Edges of slabs and breaks in floors and walls under 20 cm. wide Mtr 1653.52

Reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto all floorlevel including all leads and lifts.Thermo-Mechanically Treated bars/ Cold twisted deformed steelbars

Kg 268047.11

Extra for laying reinforced cement concrete in or under foulpositions.

Cum 219.05

Providing and laying in position ready mixed concretemanufactured in fully automatic batching plant and transported tosite of work in transit mixer for a lead upto 10kms havingcontinuous agitated mixer, manufactured as per mix design ofspecified grade for reinforced cementconcrete work includingpumpingof RMC from transit mixerto site of laying butexcludingthe cost of centring, shuttering, finishing andreinforcement, including admixtures in recommended proportionsas per IS 9103 to accelerate, retard setting of concrete, improveworkability without impairing strength and durability as per thedirection of Engineer-in-Charge.

All works upto plinth levelReinforced cement concrete grade M-35 using 440 kg of cementper cum

Cum 219.05

All works upto all floor level including all leads and lifts .Reinforced cement concrete grade M-25 using 410 kg of cementper cum

Cum 2047.86

Category - Brick Work

12 of 88

Page 14: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

First class brick work in superstructure above plinth level & uptoall floor level including all leads and lifts including cost of allmaterials as required complete:-

In cement mortar 1:4 ( 1 cement : 4 fine sand ). Cum 966.71Half brick masonry work with first class bricks in superstructureupto floor five level including cost of all materials as requiredcomplete:-In cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 2410.04

Extra for half brick masonry work in superstructure above floor-Vlevel for each four floors or part thereof by mechanical means bylifting material using mobile crane as required complete.

Sqm 4820.08

Extra for providing and placing in position 2 Nos. 6mm dia. M.S.bars at every third course of half brick masonryIn cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 2410.04

Cinder Filling Cum 197.70

Category - Marble WorkProviding and fixing 18 mm thick plain marble stone, mirrorpolished, machine cut for, kitchen platforms, vanity counters,facias and similar locations of required size of approved shade,colour and texture laid over 20 mm thick base of cement mortar1:4 ( 1 cement: 4 fine sand ) withjointstreated with white cement,mixed with matching pigment, epoxy touch ups, including rubbing,curing etc. complete at all levels as required:-

Granite of any colour and shade duly approved:-Area of slab over 0.50 sqm. Sqm 162.19Providing and fixing 8mm mirror polished marble tile work for walllining over 12mm thick bed of cement mortar 1:3 (1 cement: 3 finesand) and cementslurry @ 3.3 kg/sqm including pointing in whitecement complete including rubbing, curing etc. complete at alllevels as required:-

Granite of any colour and shade duly approved . Sqm 541.70Flamed Granite Sqm 119.06Granite stone flooring with 18mm thick Granite of any colour(sample of granite stone shall be approved by Engineer-in-charge) over 20 mm (average) thick base of cement mortar 1:4 (1cement : 4 coarse sand) laid and jointed with grey cement slurryincluding rubbing and polishing complete with : (Basic Cost ofGranite stone Rs- 150/ per sqm)

Sqm 316.41

Category - Wood and PVC WorkProviding wood work in frames of doors, windows, clerestorywindows and other frames, wrought framed and fixed in position :

Local Teak Wood Cum 8.79Providing and fixing ISI marked flush door shutters conforming toIS: 2202 (Part I) decorative type, core of block board constructionwith frame of 1st class hard wood and well matched teak3plyveneeringwith vertical grainsorcross bands and face veneerson both faces of shutters.

35 mm thick including ISI marked Stainless Steel butt hinges withnecessary screws.

Sqm 310.80

Providing and fixing curtain rods of 1.25 mm thick chromiumplated brass plate, with two chromium plated brass brackets fixedwith C.P. brass screws and wooden plugs, etc., wherevernecessary complete :25 mm dia Mtr 862.60Providing and fixing special quality brightfinished brass cupboardor ward robe locks with four levers including necessary screwsetc. complete (best make of approved quality):

50 mm No. 160.00

13 of 88

Page 15: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and fixing 50 mm bright finished brass cup board orwardrobe knob with necessary screws (best make of approvedquality)

No. 160.00

Providing and fixing bright finished brass handles with screws etc.complete :75 mm No. 160.00Providing and fixing aluminium sliding door bolts ISI markedanodised (anodic coating not less than grade AC 10 as per IS :1868) transparent or dyed to required colour or shade with nutsand screws etc. complete :300 X 16 mm No. 800.00Providing and fixing aluminium tower bolts ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868 )transparent or dyed to required colour or shade with necessaryscrews etc. complete :

300 X 10 mm No. 800.00Providing and fixing aluminium handles ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868)transparentor dyed to required colour or shade with necessaryscrews etc. complete :

125 mm No. 800.00Providing and fixing aluminium hanging floor door stopper ISImarked anodised (anodic coating not less than grade AC 10 asper IS : 1868) transparent or dyed to required colour and shadewith necessary screws etc. complete.

Single rubber stopper No. 800.00Providing and fixing factory made UPVC door frame made ofUPVC extruded, section having an overall dimension, as below(tolerance +/- 1mm) with wall thickness 2.0mm+/- 02mm. cornersofthe doorframe to be jointedwith galvanized brackets andstainless screws, joint mitred and plasticwilded. The hinge sidevertical ofthe frames reinforced by galvanized MS tube of size 19A— 19 mm and 1 mm +/- 0.1 mm wall thickness and 3 nosstainless steel hinges fixed to the frame complete as permanufacturers specification and direction of Engineer-In-Charge.

Extruded section Profile size 48x40 mm. Mtr 2496.40Providing and fixing cup board shutters with 25mm thick veneeredparticle board IS : 3097 marked exterior grade (Grade I) ofapproved make including IInd class teak wood lipping of 25mmwide x 12 mm thick with necessary screws and bright finishedstainless steel piano hinges complete as per direction of Engineer-in-Charge.

With decorative veneering on one side and commercial veeringon other side.

Sqm 361.20

UPVC door/window/ventilator shutter Sqm 842.10UPVc Wire Gauge Shutter Sqm 173.04Fire Door Sqm 21.00Providing and fixing stainless steel (SS-304 grade) friction hingesto the side/ top hung uPVC windows, of approved quality withnecessary stainless steel screws etc. as per direction of Engineer-in-charge.250 x 19 x 1.9 mm No. 1280.00Providing and fixing casement handle made of zinc alloyed (whitepowder coated) for uPVC casement window with necessaryscrews etc. complete.

No. 1280.00

Category -Steel WorkProviding and fixing 1mm thick M.S. sheet door with frame of40x40x6mm angle iron and 3mm M.S. gusset plates at thejunctions and corners, & with cleats with bolts & nuts, rivets,locking arrangement, handles, hooks & eyes, pinlets includingembedding in cement concrete of required grade for fixing inposition, all necessary fittings, including applying a priming coat of approved steel primer etc. complete as required:-

14 of 88

Page 16: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Using M.S. angels 40x40x6 mm for diagonal braces. Sqm 8.40Steel work welded in built up section/framed work includingcutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer using steel etc. complete as required:-

In grating, frames, guard bar, railing, brackets, gates and similarworks, all complete.

Kg 8089.20

Providing and fixing stainless steel ( Grade 304) railing made ofHollow tubes, channels, plates etc. includingwelding, grinding,buffing, polishing and making curvature (wherever required) andfitting the same with necessary stainless steel nuts and boltscomplete i/c fixing the railing with necessary accessories &stainless steel dash fasteners , stainless steel bolts etc., ofrequired size, on the top of the floor orthe side of waist slab withsuitable arrangementas per approval of Engineer-in-charge. (forpayment purpose only weight of stainless steel members shall beconsidered excluding fixing accessories such as nuts, bolts,fasteners etc.)

Kg 867.98

Category - FlooringExtra for prefinished nosing to treads of steps of marble stones. Mtr 594.00

Extra for marble flooring complete in treads of steps and risersusing single length upto 2.00 metre.

Sqm 251.79

Providing and fixing 1st quality ceramic glazed wall tilesconforming to IS : 15622 (thickness to be specified by themanufacturer) of approved make in all colours, shades exceptburgundy, bottle green, black of any size as approved by Engineer-in-charge in skirting, risers of steps and dados over 12 mm thickbed of cement mortar 1:3(1 cement: 3 fine sand ) jointed withordinary cement slurry including pointing with white cement mixedwith pigment of matching shade complete.

Sqm 2166.51

Providing and laying polished vitrified floor tiles in different sizes(thickness to be specified by the manufacturer) with waterabsorption less than 0.08 % and conformingto IS : 15622 ofapproved make in all colours, shades over 20 mm thick bed ofcement mortar 1:4(1 cement : 4 fine sand ) jointed with ordinarycement slurry including pointing with white cement mixed withpigment of matching shade complete.

Size of tile 60x60 cm Sqm 2038.47Providing and laying Vitrified tiles in different sizes (thickness tobe specified by manufacturer)with waterabsorption less than 0.08% and conformingto I.S. 15622, ofapproved make in all colours &shade in skirting, riser of steps, over 12 mm thick bed of cementmortar 1:3 (1 cement: 3 coarse sand), including grouting the jointwith white cement & matching pigments etc. complete.

Size of Tile 600x600 mm Sqm 224.44Providing and laying 60mm thickfactory made cement concreteinterlocking paver block of M -30 grade made by block makingmachine with strong vibratory compaction, of approved size,design & shape, laid in required colour and pattern over andincluding 50mm thick compacted bed of fine sand, filling the jointswith fine sand etc. all complete as per the direction of Engineer-in-charge.

Sqm 333.68

Providing and laying Non-Skid Ceramic glazed floor tiles 600x600mm (thickness to be specified by the manufacturer) of 1st qualityconforming to IS : 15622 of approved make in colours such asWhite, Ivory, Grey, Fume Red Brown, laid on 20 mm thickCement Mortar 1:4 (1 Cement : 4 Coarse sand) including pointingthe joints with white cement and matching pigment etc., complete.( Cost of basic tiles Rs 35/- per sft )

Sqm 835.36

Category - Roofing

15 of 88

Page 17: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Making khurras 45x45 cm with average minimum thickness of 5cm cement concrete 1:2:4 (1 cement: 2 fine sand : 4 graded stoneaggregate of 20 mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1cement: 3 fine sand) and a coat of neat cement rounding the edgeand making and finishing the outlet complete.

No. 24.00

Extra for any sunk or raised mouldings in the plaster of Paris(Gypsum anhydrous) ceiling.

Sqm 2491.80

Providing and fixing on wall face unplasticised Rigid PVC rainwater pipes (working pressure 4 kg / cm2) conformingto IS :13592 TypeA including jointing with seal ring conforming to IS :5382 leaving 10 mm gap for thermal expansion:

Single socketed pipe - 110 mm OD Mtr 852.00Providing and fixing on wall face unplasticised - PVC mouldedfittings/ accessories for unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A including jointing with seal ringconforming to IS : 5382 leaving 10 mm gap for thermal expansion:

Coupler110 mm No. 24.00Single equal tee with door110x110x110mm No. 48.00Bend 87.5A°110mm No. 48.00Plain shoe110mm No. 24.00Providing and fixing to the inlet mouth of rain water pipe PTMTgrating with thickness of 8mm and weighing not less than 100gm.complete.100mm No. 24.00

Category - Finishing12 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete forall floors.

In cement mortar 1 6 ( 1 cement : 6 fine sand ) Sqm 4203.0815 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.In cement mortar 1 6 ( 1 cement : 6 fine sand ) Sqm 4203.0820 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing complete.

In cement mortar 1 4 ( 1 cement : 4 fine sand ) Sqm 3201.826 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.In cement mortar 1 : 3 ( 1 cement : 3 fine sand ) Sqm 3731.79Extra for plastering exterior walls of height more than 10 m fromGL for every additional height of 3 m or part thereof complete.

Sqm 28816.34

Providing and applying plaster of paris putty of 2 mm thicknessover plastered surface to prepare the surface even and smoothwith all leads & lifts complete for all floors..

. Sqm 3731.79

Distempering with oil bound washable distemper of approvedbrand and manufacture and of required shade on new work ( twoor more coats ), over and including a priming coat of cementprimer to give an even shade with all leads & lifts complete for allfloors.

Sqm 3731.79

Finishing walls with water proofing cement paint of required shadeof approved brand and manufacture on new work ( two or morecoats applied @ 3.84 kg/10 sqm) with all leads & lifts completefor all floors.

Sqm 5672.84

16 of 88

Page 18: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Finishing walls with premium acrylic smooth exterior paint ofrequired shade of approved brand and manufacture on new work (two or more coats applied @ 1.43 kg/10 sqm ) over and includingbase coat water proofing cement paint applied @ 2.20 kg/10 sqmwith all leads & lifts complete for all floors.

Sqm 3201.82

Applying priming coat:With ready mixed red oxide zinc chromate primer of approvedbrand and manufacture on steel, galvanised iron / steel work.

Sqm 239.52

Wall painting with plastic emulsion paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 8406.17

Painting with synthetic enamel paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 239.52

Wall painting with Textured paint ( two or more coats ) of requiredcolour of approved brand and manufacture on new work to give aneven shade with all leads & lifts complete for all floors.

Sqm 8213.70

Unistone Wall Cladding Sqm 27.45

Category - Piling WorkBoring, providing and installing bored cast-in-situ reinforcedcement concrete pile of specified diameter and length below thepile cap, to carry a safe working load not less than specified,excludingthe cost of steel reinforcement but including the cost ofboring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of thepile to be embedded in the pile cap etc. all complete, includingremoval of excavated earth with all lifts and leads as perspecification & the direction of Engineer inA-charge (Length ofpile for payment shall be measured upto bottom of pile cap) :-

In M35 reinforced cement concrete:-500 mm dia piles. Mtr 4608.00

Category - ALUMINIUM WORKProviding and fixing aluminium work for doors, windows,ventilators, stair railings, including hand rail..For fixed portions of approved qualityAnodised aluminium.. Kg 9618.00

Category -Water ProofingProviding and laying APP (Atactic Polypropylene Polymer)modified prefabricated five layer 3 mm thick water proofingmembrane, black finished reinforced with non-woven polyestermatt consisting of a coat of bitumen primer for bitumen membrane@ 0.40 ltr/sqm. by the same membrane manufacturerof density at25A°C, 0.87 a€" 0.89 kg/ltrand viscocity 70 «€" 160 cps. Over theprimer coat the layer of membrane shall be laid using butanetorch and sealing all joints etc. and preparing the surfacecomplete. The vital physical and chemical parameters of themembrane shall be: Joint strength in longitudinal and transversedirection at 23A°C 650/450 N/ 5 cm. Tear strength inlongitudinaland transverse direction as 300/250 N. Softeningpointof membrane not lessthan 150A°C. Cold flexibilityshall beupto -2A°C when tested in accordance with ASTM, D a€" 5147.The laying of membrane shall be got done through the authorisedapplicator of the manufacturer of membrane as required as perdirection of the Engineer-in-charge.

Sqm 300.40

17 of 88

Page 19: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and laying integral cement based water proofingtreatment including preparation of surface as required fortreatment of roofs, balconies, terraces etc consistingof followingoperations: a) Applyinga slurry coat of neat cement using 2.75kg/sqm. of cement admixed with water proofing compoundconforming to IS. 2645 and approved by Engineer-in-chargeoverthe RCC slab including adjoining walls upto 300mm heightincludingcleaningthe surface before treatment. b) Laying brickbats with mortar using broken bricks/brickbats 25 mm to 115mmsize with 50% of cement mortar 1:5 (1 cement: 5 coarse sand)admixed with water proofing compoundconformingto IS : 2645and approved by Engineer-in-chargeover 20 mm thick layer ofcement mortar of mix 1:5 (1 cement :5 coarse sand ) admixedwith water proofing compound conforming to IS : 2645 andapproved by Engineer-in-charge to required slope and treatingsimilarly the adjoining walls upto 300 mm height includingrounding of junctions of walls and slabs c) After two days oo daysof proper curing applying a second coat of cement slurry using2.75kg/ sqm of cement admixed with water proofing compoundconforming to IS : 2645 and approved by Engineer-in-charge. d)Finishing the surface with 20 mm thick jointless cement

1:4 (1 cement :4 coarse sand) admixed with water proofingcompound conforming to IS : 2645 and approved by Engineer-in-charge including laying glass fibre cloth of approved quality in toplayer of plaster and finally finishing the surface with trowel withneat cement slurry and making pattern of 300x300 mm square3mm deep. e) The whole terrace so finished shall be flooded withwaterfor a minimum period of two weeks for curing and for finaltest. All above operations to be done in order and as directed andspecified by the Engineer-in Charge :

With average thickness of 120mm and minimum thickness atkhurra as 65 mm.

Sqm 396.93

TOTAL FOR CIVIL WORKS TYPE-V

18 of 88

Page 20: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Sr. No Description of Item Unit Qty Rate Amount1 3 4 5 6 7 = 5 x 6

E CLUB HOUSECategory -CARRIAGE OF MATERIALSCarriage of materials by mechanical transport including loading,unloading and stackingEarth upto 1 Km Cum 2272.00

Category - EARTH WORKClearing grass and removal of the rubbish upto a distance of 50 moutside the periphery of the area cleared

sqm 1420.00

Earth work in excavation over areas (exceeding 30cm in depth,1.5m in width as well as 10 sqm on plan) including disposal ofexcavated earth, lead upto 50m and lift upto 1.5m, disposed earthto be levelled and neatly dressed. All kinds of soil

By mechanical means Cum 2840.00Earth work in excavation in foundation trenches or drains (notexceeding 1.5 m in width or 10 sqm on plan) including dressing ofsides and ramming of bottoms, lift upto 1.5 m, including gettingout the excavated soil and disposal of surplus excavated soil asdirected, within a lead of 50 m. All kinds of Soil

By mechanical means Cum 194.00Filling available excavated earth (excluding rock) in trenches,plinth, sides of foundations etc. in layers not exceeding 20cm indepth, consolidating each deposited layer by ramming andwatering, lead up to 50 m and lift upto 1.5 m. All kinds of soil

Cum 2615.01

Extra for additional lift of 1.5m or part thereof All kinds of soil Cum 2615.01

Supplying and filling in plinth, underfloor, foundations etc. withsand (fine) from local quarry with all lifts including spreading inhorizontal layers, watering, grading to required slope, ramming,consolidating and compacting each layer by using platecompactor or by any suitable method complete.

Cum 568.00

Supplying chemical emulsion in sealed containers includingdelivery as specified.Chlorpyriphos/Lindane emulsifiable concentrate of 20% Liter 88.80Diluting and injecting chemical emulsion for PRE-CONSTRUCTIONAL anti-termite treatment (excluding the cost ofchemical emulsion) and continuous chemical barrier under andalround the column pits, wall trenches, basement excavation, topsurface of plinth filling, junction of wall and floor, along theexternal perimeter of building, expansion joints, over the topsurface of consolidated earth of which apron is to be laid,surroundings of pipes and conduits etc. complete as perspecification. The work should be carried out as per IS: 6313(Part II)- Latest revision [Plinth area of the building at ground flooronly shall be measured for payment] :

With Chlorpyriphos/Lindane E.C. 20% with 1% concentration. Sqm 355.20

Category - CONCRETE WORKProviding and laying in position cement concrete of specifiedgrade excluding the cost of centring and shuttering -

1:4:8 ( 1 Cement: 4 fine sand : 8 graded stone aggregate 40 mmnominal size)

cum 123.44

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTIONOF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASED COMBINED CYCLEPOWER PLANT OF OTPC.CIVIL WORKS

19 of 88

Page 21: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Centering shuttering including strutting, propping etc. and removalof form work for :Foundations, footings, bases for columns Sqm 240.00Extra for providing and mixing water proofing material in cementconcrete work @ 1 kg per 50 kg of cement.

50 Kg of Ce 426.42

Extra for laying concrete in or under foul positions. cum 100.00Making plinth protection 50mm thick of cement concrete 1:3:6 (1cement: 3 fine sand : 6 graded well burnt brick aggregate 20 mmnominal size) over 75mm bed of dry brick ballast 40mm nominalsize well rammed and consolidated and grouted with fine sandincluding finishing the top smooth.

Sqm 216.00

Category - RCCCentering shuttering including struttings, propping etc. andremoval of form work for:Foundations, footings, bases for columns etc. for mass concretewith steel formwork

Sqm 201.60

Suspended floors, roofs, landings, balconies and access platformwith MS Plates and props with all leads & lifts complete for allfloors.

Sqm 3420.47

Lintels, beams, plinth beams, girders, bressumers and cantileverswith shuttering ply with all leads & lifts complete for all floors.

sqm 2939.04

Columns, Pillars, Piers, Abutments, Posts and Struts withshuttering ply

sqm 880.00

Stairs (excluding landings) except spiral-staircases with woodenplank with all leads & lifts complete for all floors.

sqm 122.62

Vertical and horizontal fins individually or forming box louversband, facias and eaves boards.

sqm 195.55

Extra for additional height in centring, shuttering where everrequired with adequate bracing, propping etc. including cost ofdeshuttering and decentring at all levels, over a height of 3.5 m,for every additional height of 1 metre or part thereof: Suspendedfloors, roofs, landing, beams and balconies (Plan area to bemeasured).

sqm 846.32

Providing, hoisting and fixing upto floor five level precastreinforced cement concrete work in vertical & horizontal finsindividually or forming box louvers including setting in cementmortar 1:2(1cement: 2 fine sand), cost of required centring,shuttering, finishing smooth with 6mm thick cement plaster1:3(1cement : 3 fine sand) on exposed surfaces complete, butexcluding cost of reinforcement with cement concrete 1:2:4(1cement : 2 fine sand : 4 graded stone aggregate 20mm nominalsize).

cum 16.28

Reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete upto all floorlevel including all leads and lifts.Thermo-Mechanically Treated bars/ Cold twisted deformed steelbars

kg 256833.05

Extra for laying reinforced cement concrete in or under foulpositions.

Cum 1000.00

Providing and laying in position ready mixed concretemanufactured in fully automatic batching plant and transported tosite ofwork in transit mixer for a lead upto 10kms havingcontinuous agitated mixer, manufactured as per mix design ofspecified grade for reinforced cement concrete work includingpumping of RMC from transit mixer to site of laying but excludingthe cost of centring, shuttering, finishing and reinforcement,including admixtures in recommended proportions as per IS 9103to accelerate, retard setting of concrete, improve workabilitywithout impairing strength and durability as per the direction ofEngineer-in-Charge.

All works upto plinth levelReinforced cement concrete grade M-35 using 440 kg of cementper cum

cum 551.72

20 of 88

Page 22: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and laying in position ready mixed concretemanufactured in fully automatic batching plant and transported tosite ofwork in transit mixer for a lead upto 10kms havingcontinuous agitated mixer, manufactured as per mix design ofspecified grade for reinforced cement concrete work includingpumping of RMC from transit mixer to site of laying but excludingthe cost of centring, shuttering, finishing and reinforcement,including admixtures in recommended proportions as per IS 9103to accelerate, retard setting of concrete, improve workabilitywithout impairing strength and durability as per the direction ofEngineer-in-Charge.

All works upto all floor level including all leads and lifts .

Reinforced cement concrete grade M-25 using 410 kg of cementper cum

cum 435.20

Category - Brick WorkFirst class brick work in superstructure above plinth level & uptoall floor level including all leads and lifts including cost of allmaterials as required complete:-In cement mortar 1:4 ( 1 cement : 4 fine sand ). Cum 459.76Half brick masonry work with first class bricks in superstructureupto floor five level including cost of all materials as requiredcomplete:-In cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 258.08Extra for providing and placing in position 2 Nos. 6mm dia. M.S.bars at every third course of half brick masonryIn cement mortar 1:3 ( 1 cement : 3 fine sand ). Sqm 258.08

Category - GRANITE WORKProviding and fixing 18 mm thick plain granite stone, mirrorpolished, machine cutfor, kitchen platforms, vanity counters,facias and similar locations of required size of approved shade,colour and texture laid over 20 mm thick base of cement mortar1:4 ( 1 cement : 4 fine sand ) with joints treated with white cement,mixed with matching pigment, epoxy touch ups, including rubbing, curing etc. complete at all levels as required:-

Rajnagar Plain white marble/ Udaypur green marble/ Zebra blackmarble or equivalent duly approved:-Area of slab upto 0.50 sqm. Sqm. 20.00Granite of any colour and shade duly approved:-Area of slab over 0.50 sqm. Sqm 63.13Extra for providing edge moulding to 18 mm thick marble stonecounters, vanities etc. including machine polishing to edge to givehigh gloss finish etc. Complete at all levels as required as perdesign approved by the Engineer-in-charge:-

Granite Work Mtr 63.13Extra for providing opening of required size & shape for washbasin/ kitchen sink in kitchen platform, vanity counter and similarlocation in marble/Granite/stone work, including necessary holesfor pillar taps etc. including moulding, rubbing and polishing of cutedges etc. complete

Each 15.00

Providing and fixing 2100mm high granite stone strips 8mm thk,mirrior polished with (20mm cement mortar with 1 cement :4 finesand or equivalent), in facia and drops of width upto 150 mm withepoxy resin based adhesive including cleaning etc. at all levels asrequired.

Mtr 229.11

Mirror polishing on Granite work wherever, required to give highgloss finish complete at all levels as required as per direction ofthe Engineerin- Charge.

Sqm 63.13

Providing and fixing 8mm mirror polished marble tile work for walllining over 12mm thick bed of cement mortar 1:3 (1 cement : 3fine sand) and cement slurry @ 3.3 kg/sqm including pointing inwhite cement complete including rubbing, curing etc. complete atall levels as required:-

Granite of any colour and shade duly approved . Sqm. 20.00

21 of 88

Page 23: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and laying flamed finish Granite stone flooring inrequired design and patterns, in linear as well as curvilinearportions of the building all complete as perthe architecturaldrawings with 18 mm thick stone slab over 20 mm (average) thickbase of cement mortar 1:4 (1 cement : 4 coarse sand) laid andjointed with cement slurry and pointing with white cement slurryadmixed with pigment of matching shade including rubbing, curingand polishing etc. all complete as specified and as directed by theEngineer-in Charge :

Flamed finish granite stone slab Jet Black, Cherry Red, EliteBrown, Cat Eye or equivalent.

sqm 199.46

Providing and laying Granite stone flooring in required design andpatterns, in linear as well as curvilinear portions of the building allcomplete as per the architectural drawings with 18 mm thick stoneslab over 20 mm (average) thick base of cement mortar 1:4 (1cement : 4 coarse sand) laid and jointed with cement slurry andpointing with white cement slurry admixed with pigment ofmatching shade including rubbing, curing and polishing etc. allcomplete as specified and as directed by the Engineer-in-Charge: There will be no extra payment for change of design

Sqm 440.48

Category - WOOD AND PVC WORKProviding wood work in frames of doors, windows, clerestorywindows and other frames, wrought framed and fixed in position :

Local Teak Wood Cum 3.75Providing and fixing glazed shutters for doors, windows andclerestory windows using 4 mm thick float glass (weight not lessthan 10ks/Sqm) panes including black enamelled ISI marked MSbutt hinges with necessary screws.

Local Teak wood35 mm thick Sqm 118.49Extra for providing heavy sheet float glass panes instead ofordinary float glass in glazed doors, window and clereslorywindow shutters (Area of opening of glass panes excludingportion inside rebate shall be measured)

5.5mm thick instead of 4mm thick. Sqm 71.10Providing and fixing ISI marked flush door shutters conforming toIS: 2202 (Part I) decorative type, core of block board constructionwith frame of 1st class hard wood and well matched teak 3 plyveneering with vertical grains or cross bands and face veneers onboth faces of shutters.

35 mm thick including ISI marked Stainless Steel butt hinges withnecessary screws.

Sqm 32.68

Providing and fixing fly proof galvanised M.S. wire gauge towindows and clerestory windows using galvanised M.S. wiregauge with average width of aperture 1.4 mm in both directionswith wire of dia. 0.63 mm.

With 12 mm mild steel U beading. Sqm 116.88

Providing and fixing ISI marked oxidised M.S. single acting springhinges with necessary screws etc. complete :

150 mm No 15.00

Providing and fixing bright finished brass towerbolts (barreltype)with necessary screws etc. complete

250 x 10 mm No 43.00Providing and fixing bright finished brass 100 mm mortice latchand lock with 6 levers and a pair of lever handles with necessaryscrews etc. complete (best make of approved quality)

No 30.00

22 of 88

Page 24: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and fixing aluminium sliding door bolts ISI markedanodised (anodic coating not less than grade AC 10as per IS :1868) transparent or dyed to required colour or shade with nutsand screws etc. complete :

300 X 16 mm Nos 27.00

Providing and fixing aluminium tower bolts ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868 )transparent or dyed to required colour or shade with necessaryscrews etc. complete :300 X 10 mm Nos 36.00Providing and fixing aluminium handles ISI marked anodised(anodic coating not less than grade AC 10 as per IS : 1868)transparent or dyed to required colour or shade with necessaryscrews etc. complete :125 mm Nos 52.00Providing and fixing aluminium hanging floor door stopper ISImarked anodised (anodic coating not less than grade AC 10 asper IS : 1868) transparent or dyed to required colour and shadewith necessary screws etc. complete.Single rubber stopper Nos 34.00Providing and fixing factory made UPVC door frame made ofUPVC extruded, section having an overall dimension, as below(tolerance +/- 1mm) with wall thickness 2.0mm+/- 02mm. cornersof the door frame to be jointed with galvanized brackets andstainless screws, joint mitred and plastic wilded. The hinge sidevertical of the frames reinforced by galvanized MS tube of size 19A— 19 mm and 1 mm +/- 0.1 mm wall thickness and 3 nosstainless steel hinges fixed to theframe complete as permanufacturers specification and direction of Engineer-In-Charge.

Extruded section Profile size 48x40 mm. Mtr 48.90UPVC door/window/ventilator shutter Sqm 116.97Providing and Fixing, uPVC factory made, white colourcasement/sliding window and door made of extruded profiles.Profiles of frames and sash will be mitered cut and fusion weldedat all corners including drilling of holes for fixing hardware anddrainage of water etc., making arrangement for fixing of hardware,EPDM gasket, 1.2 ± 0.2mm thick galvanised steel profile to beinserted in required profile, frame will be fixed to the wall with 8mm x 100 mm long fasteners, all complete as per direction ofEngineer-incharge. (Glazing, hardware hinges and fitting etc. tobe paid separately.)

Note :- Each member of window to be measured separately withclear length.Casement Window (With friction hinge & outward opening)

Casement Frame (67mm x 62mm) metre 143.88Casement Window Sash/Mullion (67mm x 75mm ) (style, rail andintermediate section)

metre 25.62

Casement Glazing bead (35mm x 18 mm) Mtr 234.62Providing and fixing panelling or panelling and glazing in panelledor panelled and glazed shutters for doors, windows and clerestorywindows (Area of opening for panel inserts excluding portioninside grooves or rebates to be measured). Panelling for panelledor panelled and glazed shutters 25 mm to 40 mm thick :

Float glass panes5.5 mm thick glass panes sqm 70.18Providing and fixing stainless steel (SS-304 grade) friction hingesto the side/ top hung uPVC windows, of approved quality withnecessary stainless steel screws etc. as per direction of Engineer-in-charge.250 x 19 x 1.9 mm Nos 52.00Providing and fixing casement handle made of zinc alloyed (whitepowder coated) for uPVC casement window with necessaryscrews etc. complete.

Nos 20.00

Category - STEEL WORKS

23 of 88

Page 25: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Steel work welded in built up sections/ framed work, includingcutting, hoisting, fixing in position and applying a priming coat ofapproved steel primer using structural steel etc. as required.

In gratings, frames, guard bar, ladder, railings, brackets, gatesand similar works

kg 50.00

Providing and fixing hand rail of approved size by welding etc. tosteel ladder railing, balcony railing, staircase railing and similarworks, including applying priming coat of approved steel primer.

M.S. tube kg 364.63Providing and fixing stainless steel ( Grade 304) railing made ofHollow tubes, channels, plates etc. including welding, grinding,buffing, polishing and making curvature (wherever required) andfitting the same with necessary stainless steel nuts and boltscomplete i/c fixing the railing with necessary accessories &stainless steel dash fasteners , stainless steel bolts etc., ofrequired size, on the top of the floor or the side of waist slab withsuitable arrangement as per approval of Engineer-in-charge. (forpayment purpose only weight of stainless steel members shall beconsidered excluding fixing accessories such as nuts, bolts,fasteners etc.)

Kg 355.61

Category - FLOORINGProviding and fixing designer inter locking floor tiles of makeEurocon/ Ultra/ Unistone as per all specification and approval ofEngineer -Incharge

Sqm 140.02

Providing and fixing Kota stone in floors over 20 mm thick bed ofcement mortar 1:4(1 cement: 4 fine sand ) jointed with ordinarycement slurry including pointing with ordinary cement mixed withpigment of matching shade, including rubbing and polishingcomplete.

Kota stone slab 25 mm thick Sqm 146.90Kota stone slabs 25 mm thick in risers of steps, skirting, dado andpillars laid on 12 mm (average) thick cement mortar 1:3(1 cement: 3 fine sand ) and joined with ordinary cement slurry mixed withpigment to match the shade of slabs, including rubbing andpolishing complete.

Sqm 5.95

Providing and fixing 1st quality ceramic glazed wall tilesconforming to IS : 15622 (thicknessto be specified by themanufacturer) of approved make in all colours, shades exceptburgundy, bottle green, black of any size as approved by Engineer-in-charge in skirting, risers of steps and dados over 12 mm thickbed of cement mortar 1 : 3 ( 1 cement : 3 fine sand ) jointed withordinary cement slurry including pointing with white cement mixedwith pigment of matching shade complete.

Sqm 508.47

Providing and laying polished vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with waterabsorption less than 0.08 % and conforming to IS : 15622 ofapproved make in all colours, shades over 20 mm thick bed ofcement mortar 1:4(1 cement: 4 fine sand ) jointed with ordinarycement slurry including pointing with white cement mixed withpigment of matching shade complete.

Size of tile 60x60 cm Sqm 119.50Providing and fixing Glass mossaic tiles at finished plain wallsurface of size 20 mm x 20 mm x 4 mm in all colour, design ,fixing in customize design as per direction of Engineer-in- Charge.The glass mosaic tiles to be fixed on the wall surface with the helpof approved adhesive applied at the rate of 2.5 kg per sqm andgrouting of the same. The rate is inclusive of all operation,material and required pattern approved by Engineer-in-Charge:

sqm 500.00

24 of 88

Page 26: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

38mm thick wood block flooring of first class teak wood laid over25mm thick leveling layer of cement concrete 1:2:4 (1 cement: 2coarse sand : 4 graded stone aggregate 10mm nominal size) tobe paid separately coated with a thin layer of hot bitumenpenetration 80/25 (blown type) @ 2.45 kg per sqm. includingfixing blocks in position after dipping in hot bitumen (blown type)upto half depth, planed, levelled smooth and finished complete.

sqm 252.91

Providing and laying Vitrified tiles in different sizes (thickness tobe specified by manufacturer) with water absorption less than0.08 % and conforming to I.S. 15622, ofapproved make in allcolours & shade in skirting, riser ofsteps, over 12 mm thick bed ofcement mortar 1:3 (1 cement: 3 coarse sand), including groutingthe joint with white cement & matching pigments etc. complete.

Size of Tile 600x600 mm Sqm 19.79Providing and fixing antiskid tiles of size 600X600 mm ofapproved make in flooring

Sqm 202.14

Providing and fixing 100 mm antiskid tile skirting. Sqm 25.49Providing and fixing wooden skirting Sqm 8.95Providing and fixing of Granite stone skirting Sqm 45.08Providing and fixing of ‘Unistone’ or equivalent Glass ReinforcedConcrete (G.R.C) Wall Cladding Tiles of 15mm thk. On roughplaster surface (1:3, (1 cement: 3 coarse sand) )with adhesive inapproved design, size, texture, thickness, pattern and color.

Sqm 755.31

Category - ROOFING & CLADDINGMaking khurras 45x45 cm with average minimum thickness of 5cm cement concrete 1:2:4 (1 cement: 2 fine sand : 4 graded stoneaggregate of20mm nominal size) over P.V.C. sheet1mx1mx400micron, finished with 12mm cement plaster 1:3 (1cement: 3 fine sand) and a coat of neat cement rounding the edgeand making and finishing the outlet complete.

Nos 10.00

Providing and fixing at all height false ceiling including providingand fixing of frame work made of special sections power pressedfrom M.S. sheet and galvanised in accordance with zinc coating ofgrade 350 as per IS : 277 and consisting of angle cleats of size25mm wide x 1.6mm thick with flanges of 22mm and 37mm at1200mm centre to centre one flange fixed to the ceiling with dashfastener 12.5mm diax40mm long with 6mm dia bolts to the anglehangers of 25x25x0.55mm of required length, and other end ofangle hanger being fixed with nut and bolts to G.I. channels45x15x0.9mm running at the rate of 1200mm centre to centre towhich the ceiling section 0.5mm thick button wedge of 80mm withtapered flanges of 26mm each having clips of 10.5mm at 450mmcentre to centre shall be fixed in a direction perpendicular to G.I.channel with connecting clips made out of 2.64mm diax230mmlong G.I. wire at every junction including fixing the gypsum boardwith ceiling section and perimeter channels 0.5mm thick 27mmhigh having flanges of 20mm and 30mm long,the perimeter ofceiling fixed to wall/partition with the help of rawl plugs at 450mmcentre to centre with 25mm long drive-all screws @ 230mminterval including jointing and fixing to a flush finish of tapered andsquare edges of the board with recommended filler, jointing tapes,finisher and two coats of primer suitable for board as permanufactures specification and also including the cost of makingopenings for light fittings, grills, diffusers, cutouts made with frameof perimeter channels suitably fixed all complete as per drawingand specification and direction of the Engineer in Charge but12.5 mm thick tapered edge gypsum board conforming to IS:2095- Part I

Sqm 769.75

Providing and fixing on wall face unplasticised Rigid PVC rainwater pipes (working pressure 4 kg / cm2) conforming to IS :13592 Type A including jointing with seal ring conforming to IS :5382 leaving 10 mm gap for thermal expansion:

Single socketed pipe - 110 mm OD Mtr 100.00

25 of 88

Page 27: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing and fixing on wall face unplasticised - PVC mouldedfittings/ accessories for unplasticised Rigid PVC rain water pipesconforming to IS : 13592 Type A including jointing with seal ringconforming to IS : 5382 leaving 10 mm gap for thermal expansion:

Coupler110 mm No. 10.00Single equal tee with door110x110x110mm No. 20.00Bend 87.5A°110mm No. 20.00Plain shoe110mm No. 10.00Providing and fixing to the inlet mouth of rain water pipe PTMTgrating with thickness of 8mm and weighing not less than 100gm.complete.100mm No. 10.00

Category - FINISHING15 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.In cement mortar 1 6 ( 1 cement : 6 fine sand ) Sqm 2907.4520 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing complete.

In cement mortar 1 4 ( 1 cement : 4 fine sand ) Sqm 1170.406 mm cement plaster in single layer including cost of materialsrequired and finishing even and smooth and curing with all leads& lifts complete for all floors.In cement mortar 1 : 3 ( 1 cement : 3 fine sand ) Sqm 1493.13Neat cement punning. Sqm 0Providing and applying plaster of paris putty of 2 mm thicknessover plastered surface to prepare the surface even and smoothwith all leads & lifts complete for all floors..

Sqm 4400.58

Distempering with oil bound washable distemper of approvedbrand and manufacture and of required shade on new work ( twoor more coats ), over and including a priming coat of cementprimer to give an even shade with all leads & lifts complete for allfloors.

Sqm 3469.35

Finishing walls with premium acrylic smooth exterior paint ofrequired shade of approved brand and manufacture on new work (two or more coats applied @ 1.43 kg/10 sqm ) over and includingbase coat water proofing cement paint applied @ 2.20 kg/10 sqmwith all leads & lifts complete for all floors.

Sqm 101.78

Wall painting with plastic emulsion paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 1983.01

Painting with synthetic enamel paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 50.00

Finishing walls with textured exterior paint of required shade ofapproved brand and manufacture on new work (two or more coatsapplied @ 3.28 kg/10 sqm) over and including base coat waterproofing cement paint applied @ 2.20 kg/10 sqm complete.

Sqm 35.92

Wall painting with plastic emulsion paint ( two or more coats ) ofrequired colour of approved brand and manufacture on new workto give an even shade with all leads & lifts complete for all floors.

Sqm 35.92

POP Cornices /Pattern on Ceiling Sqm 232.93

Category - PILING WORK

26 of 88

Page 28: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Boring, providing and installing bored cast-in-situ reinforcedcement concrete pile of specified diameter and length below thepile cap, to carry a safe working load not less than specified,excluding the cost of steel reinforcement but including the cost ofboring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of thepile to be embedded in the pile cap etc. all complete, includingremoval of excavated earth with all lifts and leads as perspecification & the direction of Engineer inA-charge (Length ofpile for payment shall be measured upto bottom of pile cap) :-

In M35 reinforced cement concrete:-500 mm dia piles. Metre 3240.00

Aluminium WorkProviding and fixing anodised aluminium grill (anodisedtransparent or dyed to required shade according to IS: 1868 withminimum anodic coating of grade AC 15) of approveddesign/pattern, with approved standard section and fixed to theexisting window frame with C.P. brass/ stainless steel screws @200 mm centre to centre, including cutting the grill to properopening size for fixing and operation of handles and fixingapproved anodised aluminium standard section around theopening, all complete as per requirement and direction ofEngineer-in-charge. (Only weight of grill to be measured forpayment).

kg 736.32

Category - WATER PROOFINGProviding and laying APP (Atactic Polypropylene Polymer)modified prefabricated five layer 3 mm thick water proofingmembrane, black finished reinforced with non-woven polyestermatt consisting of a coat of bitumen primer for bitumen membrane@ 0.40 ltr/sqm. by the same membrane manufacturer of densityat 25A°C, 0.87 0.89 kg/ltr and viscocity 70 a€" 160 cps. Over theprimer coat the layer of membrane shall be laid using butanetorch and sealing all joints etc. and preparing the surfacecomplete. The vital physical and chemical parameters of themembrane shall be: Joint strength in longitudinal and transversedirection at 23A°C 650/450 N/ 5 cm. Tear strength in longitudinaland transverse direction as 300/250 N. Softening point ofmembrane not less than 150A°C. Cold flexibility shall be upto -2A°C when tested in accordance with ASTM, D a€" 5147. Thelaying of membrane shall be got done through the authorisedapplicator of the manufacturer of membrane as required as perdirection of the Engineer-incharge.

Sqm 178.16

Providing and laying water proofing treatment in sunken portion ofWCs, bathroom etc., by applying cement slurry mixed with waterproofing cement compound consisting of applying : a) First layerof slurry of cement @ 0.488 kg/sqm mixed with water proofingcement compound @ 0.253 kg/sqm. This layer will be allowed toair cure for 4 hours. b) Second layer of slurry of cement @ 0.242kg/sqm mixed with water proofing cement compound @ 0.126kg/sqm. This layer will be allowed to air cure for 4 hours followedwith water curing for 48 hours. The rate includes preparation ofsurface, treatment and sealing of all joints, corners, junctions ofpipes and masonry with polymer mixed slurry.

Sqm 529.54

Providing and laying brick tiles over mumty roofs, grouted withcement mortar 1:3 (1 cement : 3 fine sand) mixed with 2% ofintegral water proofing compound by weight of cement, over 12mm layer of cement mortar 1:3 (1 cement : 3 fine sand) andfinished neat :

Sqm 826.54

With common burnt clay F.P.S. (non modular) brick tiles of classdesignation 10

27 of 88

Page 29: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SWIMMING POOL EQUIPMENT & ACCESSOARIESFILTERATION EQUIPMENTFilter:FRP Multigrade filter with adequate dirt holding capacity. the filtershall be complete having PVC frontal piping with 6 way2.5”multiport valves including all supporting structure with initialcharge filter sand media as per require quantity. The filter shall beprovided with set of internals for raw water inlet and bottomcollecting system. Velocity in frontal piping and valves shall be 50m3/h/m2

Dia-011OOmm.Flow rate:-43 m3/h on Max. Filtration Velocity:-50m3/h/m2 , Make: Pentair U.S.A/

Nos 3

Pump For Filter :Supplying, installing, testing and commissioning of Self primingpumps with inbuilt hair strainer. Each pump shall have TEFC 2850RPM three phase electric motor. The pump shall have body,prefilter & basket made of polypropylene, shaft made of AISI 316and impeller made of noryl fibre glass. Pump shall be providedwith mechanical seal. Motor IP-55 protection rated The pumpshall be suitable for auto/ manual operation. The installation shallbe complete with all necessary ancillaries & accessories includingbase plate complete as required Make :Pentair U.S.A or ESPA Spain, Pump Type: -Flow@ 34000 L/h, 10Mtr head 2.2 kW(3 HP 230 V.)

Nos 3

CHEMICAL DOSINGDosing Pump:Supplying, installing, testing and commissioning of pH dosingsystem and for Chlorine dosing system consisting of one HDPEtank of 100 liters capacity with a positive displacement diaphragmdosing pump having variable flow rate of 0-5 lph. The motor shallbe suitable for operation at 240 V/Single phase/50 Hz. Supply.The pump shall be supplied complete with necessarypolypropylene piping, valves, strainers, low level switch andinjection fittings. Make:Pentair U.S.A/ EMAC ITALY

Nos 2

POOL BASINE ITEMSInlet Nozzle:Providing &, fixing & commissioning of White ABS plastic Floorinlet with SS screws and Adjustable flow. Max flow 5cum/hr.connection outside 50mm thread and inside diameter 50mm.Make : Pentair U.S.A

Nos 20

Drain Plate :Providing & fixing & commissioning of Main Drain Grates 300 mmx 300 mm ABS, support frame & grate made of SS fixing screwsin. Made in White ABS.Make : Pentair U.S.A/ Certikin U.K

Nos 2

POOL LADDERS/GRATINGPool Ladder:Providing, fixing & commissioning of stainless steel AISI304ladders, width 500mm, handles, non-slip3steps.

Nos 2

Providing, fixing & commissioning of stainless steel AISI-304ladders, width 500mm, handles, non-slip 4 steps.Make : Pentair U.S.A/

Nos 2

Grating:Providing & Fixing of Over flow channel grating Size-12” Made inWhite ABS. Single lock & stabilized Against UV Rays.Make : Pentair U.S.A/

Mtr 80

Grating Profile:Providing & Fixing of channel grating Profile Size-26mm” Made inWhite ABS. Single lock & stabilized Against UV Rays. For GratingSupport.

Mtr 80

POOL LIGHTSLight:

28 of 88

Page 30: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Providing, fixing, testing & commissioning of, 12V 100W Halogenwith IP 68 pool light fixture, in ABS plastic with cable of suitablelength. Make : Pentair U.S.A/ Certikin U.K

Nos 24

Junction BoxProviding, fixing & commissioning of deck box / junction box andflexible conduits for the Pool lights. Made in ABS

Nos 24

Transformer: Providing, fixing, & testing of Transformerwith panelbox for underwater lights to provide sufficient load up to 3 K.Wand electrical voltage to light with integrated voltage meter andM.C.B having three inputs for different voltage 200/220/240v andthree outputs according to the distance variation 12/15/18v.

POOL CLEANING & MAINTENANCE KITPool Cleaning Kit:Supply, Installation & testing of Pool Maintenance kit withcomplete Accessories including the following items: SS 304Vacuum head with wheels & rope angle size 600mm, 30 mtrsVacuum hose Pipe, Wall brush, Deep net, Leaf net, Telescopichandle 4.8 Mtr long and test kit for chlorine & pH level. And 50 kgTcca- 90% chemical, Each items 01.No.

Set 1.00

Suction Pump With Trolley:Supply, Installation & testing of self priming pump for Pool

cleaning with manual 4 wheel drive mounted MS trolley for pumpwith starter & 15 mtrs 3 core cable. Model SP01HM/ 2 H.P PumpMake: Kriloskar.

Set 1.00

PLUMBIN G & ELECTRI CAL & COMMIS SIONING WORK

Electrical Work for Pool Light Pool Light WiringProviding, fixing, testing and of copper cabling 2.5 mm2 for pool

under water lights. Cable shall be flexible, 2 core black seethedcover copper conductor doctor enclosed in conduit voltage at lightshall be between 11.8-12v. For above lights up to the plant room.As per ISI make.

Lot 1.00

Plumbing & Commissioning WorkPool Floor Inlet Line: Supply, installation & testing of pool inter connecting PVC pipe

reduce Dia 160/110/ mm to 90 to 75 to 63mm with 2 No’s ofparallel line & fixing for floor inlet nozzle with all fittings. Line FromPool Floor to Pump Room.

Pool Drain Line:Supply, Installation & testing of pool drain line pvc pipe dia110

mm/ 10 kg. And reduce the 110mm to 160 mm 06 kg. From pooledge to balancing tank. With Providing & fixing 6” Sluice Valvemade in CI body ISI on drain pipe in balancing tank.

Pool Over Flow Line: Supply, Installation & testing of over flow channel pipe with

fittings, Pipe dia 110 mm/ 06 Kg From pool channel edge toBalancing tank

29 of 88

Page 31: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

Pool Plant Room Commissioning: Installation &Commissioning offiltration plant. To make common header for all Pumps & filter andfix the NRV & butter fly valve with flange & all fitting. On suction &delivery line.Electrical wiring with wall conduit in plant room forpump to electric panel, light transformer panel, & connect to thepanel. Back wash line from filter to drain chamber, dia 110mmPvc Pipe. Fixing of U/W Light inside of the pool and allaccessories surround the pool ( Grating, S.S Ladder, Nozzle) (AllPvc pipes and fitting should be Make of Prince/ Supreme/ Finolexin 10kg/ cm2 pressure tested and valve as per ISI. Make Cepax orequivalent. And electrical wire fitting (MCV/ Switches) makesFinolex/ Havel’s, or equivalent as per ISI. And work will be doneaccording to plumbing drawing. ( The estimated cost and materialfor plumbing and electrical work on assuming the distance of plantroom not more than 30’from either end of pool)

TOTAL of Electrical & Plumbing work for swimming pool Lot 1.00

POOL TILING WORK, POOL GLASS MOSAIC TILING WORK

Pool TilesSupply , Installation & testing Pool glass mosaic tiles random mixglass mosaic tiles 20’ x 20’ mm with fixing Latticrete/ Balenduraadhesive and epoxy grout, as per approved sample(includesfixing and adhesive and epoxy grout cost). Make of tile: Opio orequivalent as per Approved Sample.( Aqua Blue Color RandomMix)

Sqm 418.00

TOTAL CLUB HOUSE CIVIL

30 of 88

Page 32: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

TYPE-IV QUARTERSANITARY & PLUMBING WORKS

1.0 Providing & fixing wall hung type white/coloured vitreous china European wall hung water closet ofapproved make syphonic wall mounting with concealed `P' or ‘S’ trap, seat & lid white or as approved with(heavy duty) with Two Way Bib Cock with Health fuacet 1.0 Meter Long PVC Tube & Wall Hook having allinternal fittings, dual flushing cistern , C.P. brass hinges & rubber buffer with fittings C.I. / M.S. bracktes40mm diameter flush bend with fitting & clamps, overflow arrangment with special and mosquito proofcoipling of approved municipal design complete including painting of fittings & brackts cutting & makinggood the wall or direction of engineer incharge.

Each 36

2.0 Providing & fixing white/coloured vitreous china floor mounting type one piece / two piece ( WC+dualflushing Cistern) EWC of approved make with concealed `P' or ‘S’ trap , Two Way Bib Cock with Healthfuacet 1.0 Meter Long PVC Tube & Wall Hook having all internal fittings including 110mm dai WCconnector Bend, Brackets, C.P bolts, nuts, solid plastic seat lid white or as approved. C.P brass hinges andrubber buffer, 32 mm dia flush pipe with clamp and adapter rubber joint, painting of fittings & brackets,C.P brass screws and washer complete including cutting & making good the walls/floor/slab whererequired. or direction of engineer incharge.

Each 36

3.0 P & F vitreous china oval below counter wash basin size 550x480mm of approved make with C.I. / M.S.brackets, 15mm C.P. brass single lever basin mixer with 450mm long copper connection and piller tap pipeand brass nuts of approved make, 32mm C.P. brass waste coupling of standard pattern of approvedmake including C.P. cast brass bottle trap 40 mm with extension piece, rubber adaptor, wall flange,union, C.P. brass chainrubber plug painting of fitting and brackets, cutting and making good the wallwherever required.

Each 72

4.0 SITC of 1.0 mm thick Salem stainless steel AISI -304 kitchen sink of approved make (Nirali, Neel – kanth,Jaina, Faber-Castell ) with C.I. brackets (duly painted with 2 coats of paint over a coat of primer) with largewaste coupling, C.P. sink mixer with swinging spout J-pipe . complete including cutting & making good thewall/counter etc.:

Overall Size Bowl Size45" x 20" x 8" 20"x16"x8" (with drain board) Each 36

5.0 Providing and fixing 600x450 mm bevelled edge mirror of superior glass (of approved quality)complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws andwashers complete.

Each 72

SANITARY, PLUMBING, INTERNAL ELECTRICAL WORKS

Name of Work:CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASEDCOMBINED CYCLE POWER PLANT OF OTPC

31 of 88

Page 33: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

6.0 Providing and fixing 600x120x5mm glass shelf with edges round of supported on anodised aluminiumangle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugsetc., complete.

Each 72

7.0 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brassscrews with concealed fitting arrangement of approved 450mm long towel rail with total length of495mm, 78mm wide and effective height quality and colour.600mm long towel rail with total length of 645mm, width 78mm and effective height of 88mm, weighing notless than 190gms.

Each 72

8.0 Providing fixing SS Towel Rack 600mm Long 200mm wide of approved make with LowerHangers CP brackets fixed to wooden cleats, PVC rawl plug with CP brass screws etc. including cuttingand making good the wall wherever required.

Each 72

9.0 P & F C. P. brass Toilet Paper Holder with rod of approved quality/make, with CP brass screws &rowlplugs as approved

Each 72

10.0 P & F Inlet Connection (Angle Valves) Superior quality, of approved make, with CP wall flange, Nut andWasher etc complete as required for Wash basin, Gyser etc. complete including cutting & making good thewall/counter etc.

C.P. Inlet connection 15mm.Brass (IS : 8931 marked) Each 432

11.0 SITC of Superior quality of approved make CP Brass fittings complete as per direction of EI

Wall mixer 3 in 1 system with tetephonic bath shower with bend pipe Each 72

12.0 Providing and fixing Shower Superior quality of approved make CP Brass fittings complete as per directionof engineer incharge.

Each 72

13.0 Providing and fixing PTMT (Polytetra Methylene Terephthalate) soap Dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fitting arrangements weighing not less than 106 gms.

Each 72

14.0 Providing fixing satin finish stainless steel AISI 316 grade wall mounted coat hooks/peg rag (makedline or equivalent) on door with complete fittings complete.

Each 72

32 of 88

Page 34: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

15.0 Providing and fixing PolyetheleneAluminiumPolyethelene (PEALPE) Composite Pressure Pipes conforming toIS 15450 U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capableto withstand temperature up to 800 C including all special fittings of composite material (engineeringplastic blend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connectors etc.with clamps at 1.00 metre spacing. This includes testing of joints complete as per direction of theEngineer in charge.

Internal work - Exposed on wall15.1 1216 (16 mm OD) pipe Mtr 10015.2 1620 (20 mm OD) pipe Mtr 44815.3 2025 (25 mm OD) pipe Mtr 70015.4 2532 (32 mm OD) pipe Mtr 25215.5 3240 (40 mm OD) pipe Mtr RO15.6 4050 (50 mm OD) pipe Mtr 28015.7 5065 (65 mm OD) pipe Mtr 15015.8 6580 (80 mm OD) pipe Mtr 10

16.0 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL- PE) Composite Pressure Pipesconforming to IS - 15450 U.V. stabilized with carbon black having thermal stability for hot & coldwater supply, capable to withstand temperature up to 800 C including all special fittings of compositematerial (engineering plastic blend and brass inserts wherever required) e.g. elbows, tees, reducers,couplers & connectors etc. with clamps at 1.00 metre spacing. This includes the costs of cutting chasesand including testing of joints complete as per direction of the engineer in charge. Concealed work includingcutting chases and making good the wall etc.

Concealed work including cutting chases and making good the wall etc.16.1 1216 (16 mm OD) pipe Mtr 79216.2 1620 (20 mm OD) pipe Mtr 21616.3 2025 (25 mm OD) pipe Mtr RO16.4 2532 (32 mm OD) pipe Mtr RO

17 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL- PE) Composite Pressure Pipesconforming to IS - 15450 - 2004 U.V. stabilized with carbon black having thermal stability for hot & coldwater supply, capable to withstand temperature up to 800 C including all special fittings of composite material(engineering plastic blend and brass inserts wherever required ) e.g. elbows ,tees ,reducers, couplers &connectors etc. with trenching, refilling and testing of joints complete as per direction of the engineer incharge.

External work17.1 1216 (16 mm OD) pipe Mtr RO17.2 1620 (20 mm OD) pipe Mtr RO17.3 2025 (25 mm OD) pipe Mtr RO17.4 2532 (32 mm OD) pipe for flushing water tank Mtr RO17.5 3240 (40 mm OD) pipe Mtr 50

33 of 88

Page 35: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

17.6 4050 (50 mm OD) pipe for domestic water tank Mtr 50

18.0 Supply & Wrapping of Hot water pipes with 9 mm thick nitrial foam type tube foam for hot water concealedpiping raping work including jointing treatment. (Rate to be coated per meter of pipe length).( Superloan/Accoflex / Armaflex Make)

18.1 15 mm dia pipes Mtr 36018.2 20 mm dia pipes Mtr 22418.3 25 mm dia pipes Mtr 25218.4 32 mm dia pipes Mtr RO18.5 40 mm dia pipes Mtr RO18.6 50 mm dia pipes Mtr 150

19.0 SITC of Ball Cock (IS :1703 Mark) with Rod & P.V.C. Ball complete :19.1 Brass wt.400 gm,15mm. In shaft Each 10819.2 Brass wt.750 gm, 20mm. In shaft Each 10819.3 (-do-) wt.1000 gm, 25mm. At terrace Each 4819.4 (-do-) wt.1000 gm, 32mm At terrace Each 3619.5 (-do-) wt.1200 gm 40mm at tarrece Each 219.6 (-do-) wt.2000 gm 50mm at tarrece Each 2

20.0 P & F Full-way Gun-metal Valve (IS:778 Mark) or wheel valve of approved make :20.1 Gun-metal 65mm nominal bore. Each 120.2 Gun-metal 80mm nominal bore. Each 1

21.0 Providing, fixing & testing uPVC SWR pipes confirming to IS 13592 (Type B) alongwith all required fittingslike tees, bends, offsets, 'Y', crosses with or without access doors jointed with approved solvent cementas per manufacturer's recommendations, fixed to walls and ceilings with clamps complete includingcutting and making good the floors and walls where required complete of outer diameter.

21.1 50 mm dia (for wash basin & balcony drainage) Mtr 36021.2 75 mm dia Mtr 14421.3 110 mm dia (Soil Waste 190mtr Horizontal+770mtr in shaft+60mtr in

Ground )+(Rain Water 462 m in shaft+50 mtr in ground)Mtr 1470

21.4 160 mm dia (in ground level) Mtr 80

22.0 Providing and laying 150 mm thick cement concrete 1:5:10 mix ( 1 cement : 5 coarse Sand : 10 gradedstone aggregate 40 mm nominal size) alround UPVC pipe including bed concrete 150 mm as perstandard design.

Mtr 190

34 of 88

Page 36: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

23.0 SITC of Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes fittings type B for sciland waste dischargesystem (IS:13592 : 1992 Marked) of approved quality /make, including complete including cutting andmaking good the wall/Floor:

23.1 Multi floor trap110mmx75mm dia Each 72

23.2 Nahni Trap with Jali110x110mm dia Each 36

23.3 Nahni Trap with Jalia) 110x75 mm dia Each ROb) 75x50mm dia Each 72

24.0 Providing and fixing square mouth (S.W) gully trap grade `A' complete with C.I. grating brick masonrychamber with bricks of class designation 75 and water tight double seal C.I. cover with frame of 300 x300 mm internal size. The weight of cover to be not less than 4.5 kg and frame to be not less than 2.70 kg. asper standard design.

a) 150 x 100 mm size ‘P’ type. Each 12

25.0 Construction of chamber in all type of soil with 230 mm thick masonry in CM 1:6 m 10 cm thick C.C. 1:5:10 infoundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 20mm external plaster1:4 ( 1 cement:4 course sand), 50 mm thick M-15 grade C.C. flooring , earthwork etc. complete as per designincluding disposal of surplus earth within a lead of 50 mtr.

25.1 300x300x300 mm size (inside) chamber with precast cover or 5Kg. C.I. frame to with stand 3 MTcenter point load & minimum unfractured load of 1 MT. (Light duty)

Each 12

25.2 450x450x450 mm size (inside) chamber with precast cover or 12Kg. C.I. frame to with stand 15 MTcenter point load & minimum unfractured load of 1 MT. (medium duty)

Each 5

25.3 600x450x600 mm size chamber with precast cover or 22Kg. C.I. frame to with stand 22 MT center point load& minimum unfractured load of 1 MT. (heavy duty)

Each 5

26.0 Construction of grease trap chamber 900x450mm( clear size depth to invert upto 1200mm) with 230mmthk. Brick work in 1:5 CM and 230mm thk. PCC 1:2:4 beddign 20mm thk. Cement water proof plastersmooth finish inside and rough outside 100mm thk. RCC baffle about 450mm away from inlet with 1 no.900x450mm heavy duty water tight CI cover and frame (weight not less then 125 Kg). includingexcavation in all soil, loose boulder etc. as per specifictions, back filling, ramming and consolidation andremoveing surplus earth as directed, including making smooth rendering for floor in cement finish towards inlet as per drawing.

Each 2

35 of 88

Page 37: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

27.0 Design and construction of RCC terrace tank including RCC M-25 grade concrete, relevant shuttering,steel reinforcement, foundation, puddle flange, level indicator, level controller, manholes, MS rungs,ventilators complete & comissioning as per specification & including waterproofing of the tank aginst anyleakage, the design of the tank to be got approved from the consultant before execution.

27.1 15001 litres capacity for Domestic Water Supply Each 127.2 5001 litres capacity for Flushing Water Supply Each 1

500 litres capacity Each 8

Supplying, installation, testing and commissioning of solar hot water generator with collectors,collector stands and frame. Technical specification as below for 500 litre capacity.Type of COLLECTOR : Cu-Cu, ultrasonically welded. Size of collector: 2600 X 1450 X 100 mmAbsorber area: 3.70 sqm Absorber coating: selective coated black chrome Nelson collectors absorvity>0.95 Collectors emissivity:<0.20 Collector box material: extruded aluminium frame 1.4 mmFin width :120 mm, Insulating material: Rockwool Thcikness of bottominsulation: 50 mm Thicknessof side insulation: 25 mm Thermal conductivity:0.029 W/mk, Density:40 kg/cum, Collectors glazing materials: Material: Toughenedclear glass thickness :4.0mm transitivity: 88% Glass beeding:EPDM,Supplying,installation, testing and commissioning of 500 litres insulated hot water storage tank of following specs,Capacity:500 litres,Material: SS-304, Insulating material for tank: Glasswool, Thermal conductivity ofinsulation:0.028 to 0.033 W/mk, Density of insulation material:48 kg/cum, Thickness of insulation material:100mm, Cladding material:Al 22 SWG, Supply,installation,testing and commissioning of 500 litre insulated hotwater storage tank of following specs: Capacity: 500 litres, Material:SS-304, Insulating material fortank:glasswool,thermal conductivity of insulation :0.028 to 0.033 W/mk,density of insultaion material;48kg/cum, thickness of insulation material:100 mm,cladding material:Al-22 SWG, hot water primary circulationpump, centifugal type with mechanical seal having flow rate of 0.5 LPS at 25m head (1W+1S), hot waterreturn pump, centrifugal type with mechanical seal having flow rate of 0.5LPS at 25m head (1W+1S),providing and fixing of 25 mm NB water flow meter on the pipes complete with Y-type strainer, bypass valveand full way ball valves on each side with flanged joints. Providing and fixing of 100 mm dia Pressure Gauge,syphon and cock valve, providing and fixing of 25 mm NB, 220 V AC water line solenoid valves screwed.Providing and fixing of flaot type level switches in mixing tank. Electrical panel in sheet metal enclosure(3phase) comprising of TPN MCB, overload relay with single phase protection features, ON/OFF and Tripindication lamps, contractors, contcts for automation system interlocking etc suitable for 9 nos DOL strteersfor pump motors and 6 nos feeders for 9kW heat paumps. The electrical panel in sheet metal enclosure (3phase) comprising of TPN MCB, overload relay with single phasing protection features,ON/OFF and Tripindiation lamps, contractors contacts for automation system interlocking etc suitable for 9 nos DOL starters forpump motors and 6 nos feeders for 9kW Heat pumps.Power and control cable and termination, 4C X 4.0

1100 V d PVC i l t d d bl 3CX2 5 1100 V d PVC i l t d

28.0

36 of 88

Page 38: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

29.0 SITC Stailness steel (SS) Tanks 1000 ltr capacity are made from SS304 2BA mirror finish imported sheets(0.5 mm to 1.00 mm thickness) and light weight.Chemical composition corrosion and heat resisting as per AISI Inlet and Outlet are threaded (BSP)connections,Inlet 3/4" - PVC fittings, except loft where connc. Size = ½" Outlet 1" - SS fittings, except loft where connc.Size = ½"There are two nozzles at the top, of ¾" size. (One for inlet and other for vent)There are two nozzles also at bottom, of 1" size. (One for outlet and other for cleaning)DD - Dish Top & Dish BottomDF - Dish Top & Flat Bottom

Each 4

30.0 Providing and fixing of Hot Water Geysers complete with fitting & testing, colour or approved make withrespect including connection with the line with geyser connector pipes copper/CP coated, connection in pipesetc for 25 litre capacity15 to 25 LTR. Cap. Each 108

Total C/f to Summary of Price Bid

INTERNAL ELECTRICAL WORKS

1.00Wiring for light/fan/exhaust fan/call bell point with 1.5sq.mm PVC insulated copper conductor cable in PVCconduit etc. as required.Short point:- Cudm 135Medium point:- Cudm 280Long point:- Cudm 965

2.00Wiring for 3/5 pin 5/6 amps plug point with 1.5 sq.mmPVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 650Medium point:- Cudm 125Long point:- Cudm 70

3.00Wiring for 3/6 pin 15/16 amps plug point with 4sq.mm PVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 10Medium point:- Cudm 15Long point:- Cudm 275

4.00Wiring for circuit/sub-main wiring with the followingsizes PVC insulated copper conductor cable in PVCconduit etc. as required.1 x 1.5 sq.mm:- mtr 40002 x 2.5 sq.mm:- mtr 4000

37 of 88

Page 39: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 x 2.5 sq.mm:- (for Ac Point) mtr 22502 x 4 sq.mm:- (for Ac Point) mtr 2250

5Supplying and drawing co-axial TV cable RG-6grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected withPVC sheath in the existing surface/ recessed steel/ PVC conduit as required.

mtr 4000

Supplying and fixing of the following PVC conduit i/call accessories as required:-19 mm:- mtr 875025 mm:- mtr 3500

6 Supplying and fixing of 12 way metal enclosure for 240/415 volts MCB (SP/SPN/DP) or Isolator,complete with necessary bus bar, earth bar, neutral link, din rail etc i/c connection as required.Category B:- each 21

7 Supplying and fixing of 3x6 way metal enclosure for 240/415 volts MCB (SP/SPN/DP/FP) or Isolator, completewith necessary bus bar, earth bar, neutral link, din rail etc i/c connection as required.Category B:- each 40

8 Supplying and fixing of 5 to 32 amps rating 240 volts 'G' series MCB of single pole in the existing MCB DBcomplete with connection etc. as required.Category B:- each 732

9 Supplying and fixing of 63 amps rating 415 volts 'G' series MCB of four pole in the existing MCB DBcomplete with connection etc. as requiredCategory B:- each 61

10Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DBcomplete with connections, testing and commissioning etc. as required.40 amps each 185

11 P & F double ball bearing capacitor start, aluminium body & blade ceiling fan with down rod up to 30 cm with3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. each 216

12 Supplying and fixing of 230 mm sweep Exhaust fan in the exisisting hole i/c necessary connection etc. asrequired. each 72

13 Supplying and fixing of 300 mm sweep/ 900 r.p.m Exhaust fan in the exisisting hole i/c necessaryconnection etc. as required. each 36

38 of 88

Page 40: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

14 Supplying and fixing of necessary shutter for 230 mm Exhaust fan in the exisisting hole i/c necessarypainting etc. as required. each 72

15 Supplying and fixing of necessary shutter for 300 mm Exhaust fan in the exisisting hole i/c necessarypainting etc. as required. each 36

16 Supplying and fixing of Ding Dong call bell i/c necessary connection etc. as required. each 36

17 Supplying and fixing of Holder (Angel/Batten)/ ceiling rose i/c necessary connection etc. as required. each 36

18 S.P. 5/6 amps, two way modular switch, ISI marked each 23619 Stepped type Modular Fan regulator (2 module) each 21620 Telephone Socket outlet modular type each 14421 T.V. Socket outlet modular type each 10822 Modular blanking plate each 10023 Modular base & cover plate for 1 module each 25524 Modular base & cover plate for 2 module each 145

25 Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable sizeof phenolic laminated sheet cover in front including painting etc as required.

26 75 mm X 75 mm X 60 mm deep (for Tel .& TV socket) each 25527 100 mm X 100 mm X 60 mm deep (for DP Switch AC.) each 14528 Supplying and fixing of 32 amps DP switch (kit kat) i/c necessary connection etc. as required. each 145

Telecomunication

29P & F Krone module with base frame in the recess / surface made out of 16 SWG sheet steel box, frontopenable, having locking arrangements duly powder painted.,including dressing, ferruling and punching oftelephone cable with krone tool etc. as required.20 Pairs Each 9

30

Supply, installation, testing and commissioning of out door type lockable Main field distribution panel withswivel input stub and splice chamber as required, for the lines. The panel shall have provision for bottomcable feeding. The conductors in the swivel stub and splice chamber shall have 24 AWG conductors andsatisfy the fuse link requirement.200 Pairs Each 1

31 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.

4 Pair Metre 288020 Pair Metre 250

39 of 88

Page 41: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

32

Supplying & erecting Delton or approved make Telephone Cable electrolytic grade annealed copperconductor insulated with PE insulation twisted in to pairs with colour combination bunched together inconcentric layers so as to minimizes cross-talk & wrapped with FR PVC tape & sheathed with FR PVC orHFFR outer Jacket suitable for indoor telephone wiring & confirming to C-DOT S/WS - 113/ IEC 60189-2,UL-1581 SECTION 1080 V W-1 erected in existing pipe of following size of conductor & nos. of pairs. withnecessary connections.100 Pair Metre 400

Lighting Fixtures

33

P & F strip type fluorscent tube fitting fabricated from (CRCA sheet and finished with powder coating /stove enamelled paint) / (extruded non corrosive UV resist EP channel) complete with accessories (Low LossCopper Choke, starter, starter seat) / Electronic Choke with terminal block duly prewired with copperconductor including making connection, testing etc. as required( without tube).1 X 28 Watts with EB each 266

34 T5 lamps28 Watts each 266

35.00

P & F of surface mounting 2 X 9/11 watt CFL luminaire made from engineering plastic with aluminiumreflector assembly electrochemicaly brightened and anodized cross louvers, complete with accessoriescopper ballast,starter,holder,terminal blockduly prewired with copper conductor including making connections,testing etc. as required (with lamp) Philips, Bajaj, Wipro

each 72.0

36.00P & F 9/11/13/ Watt CFL mirror light with CRCA powder coated housing, diffuser, end covers, copperballast, holder prewired upto terminal block including making connection testing etc. as required(with tube)Make Philips, Bajaj, Wipro

each 72.0

37.00 P & F energy efficient / energy saving direct fit (Retrofit) composite self ballasted compact fluorscentlamp (CFL) with PF >0.85 in existing holder / fixture as required. (Make Philips, Bajaj, Wipro)

14/15 Watt each 1018/20 Watt each 40

38.00P & F of decorative round/square shape surface mounting ceilng fitting complete with holder,aluminiumanodized back plate glass globe of approved design,prewired terminal block making connection,testing etc.as required as approved by Engineer in charge .150 mm each 144

39.00P & F of IP 65 protected LED down lighter luminaire with housing made of Die Cast aluminium housing withpowder coated finish and toughened glass diffuser, 1W LED, supply accessories(220 V, 50 HZ/12 V DC)complete in all respect. Available with 5 color option Make Philips (Green LED),Equivalent Bajaj , Wipro.

each 106

40 of 88

Page 42: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

40.00P & F' L' type fancy wall bracket suitable for GLS lamp with back plate of size 150mm x 40mm x 3mm glassshade of dia150/100 mm,brass holder duly prewired with pvc copper wire including making connection testingetc. as required & approved by Engineer in Charge

each 180.0

41.00 P & F of bed Light including making connection testing etc. as required & approved by Engineer inCharge . each 108.0

Solar PV Sytem42.00 Supply, Installation, Testing & Commissioning of solar photo voltaic Module (210 Wp+/-2%) Each 3043.00 Supply & Installation of Module Mounting Structure Each 144.00 Supply & Installation of Array Junction Box (4 In-1 Out) Each 145.00 Supply, Installation, Testing & Commissioning of 1 Core 4 sqmm. Poly ethelene Cu cable Sqmtr 10046.00 Supply, Installation, Testing & Commissioning of 1 Core 4 sqmm. Poly ethelene Cu cable Sqmtr 3047.00 Supply, Installation, Testing & Commissioning of 1 Core 25 sqmm. Poly ethelene Cu cable Sqmtr 10048.00 Supply, Installation, Testing & Commissioning of 3-1/2 Core 10 sqmm. Poly ethelene AL cable Sqmtr 8

49.00 Supply, Installation, Testing & Commissioning of power conditioning Unit-SCC:2 KVA, and Inverter andcharges: 2 KVA, 03 Phase 415 V Each 1

50.00 Supply, Installation, Testing & Commissioning of Battery Bank 500 Ah @ 240 V VRLA AGM Each 251.00 Supply & Installation of DC distribution board Each 152.00 Supply & Installation of AC distribution board Each 153.00 Supply & Installation of Lighting Arrestors Mtr. 554.00 Supply & Installation of Electrical Accessories Each 155.00 Supply & Installation of Earthing Kit Each 2

Panel & AccessoriesMetering Panel Normal (QTR. Type-IV)

56.00

Supply, installation, testing and commissioning of surface/ recessed mounted 16 SWG CRCA sheetsteel fabricated double door type powder coated MCB Distribution board complete with tinned copperchannel, neutral & earth link, interconnection as required, with suitable nos. of knockout holes for 25 mm dia.conduit, including cutting of wall and making good of the same, complete with the following.

INCOMER1 No. 800A TP MCCB +INDICATION+ METERING

41 of 88

Page 43: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

42 of 88

Page 44: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

43 of 88

Page 45: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

44 of 88

Page 46: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

45 of 88

Page 47: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

46 of 88

Page 48: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleeves

47 of 88

Page 49: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.800A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 800/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 800/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 800/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 800A, TPN Aluminum bus bars with colour coded PVC sleevesOUTGOINGS41 Nos. 6-40A DP MCBSupply, Receiving, Fixing, testing &commissioning of Capacitor panel as described above Sets 1

Metering Panel Emergency Panel (QTR. Type-IV)

57.00

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

48 of 88

Page 50: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

57.00

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

57

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

57

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

57

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

49 of 88

Page 51: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

58.00

P&F of IP51 direct or CT operated, 1x240 / 3x240volts , 50 Hz static watt-hour meter (kwh) having resolution 0.1 / 0.01 kwh , 1/ 0.5 accuracy class , LEDindicators for tamper operation ( Reverse &/or earth connection) , pulsating LED indicator for meterology ,electromechanical counter , LCD Display, cover plate for body and terminal sealing , including makingconnection ,testing etc. as required. up to 60 ampere three phase meter

Each 20

L.T. Cables & Trays

59.00

Providing & erecting XLPE(IS:7098) (I)-88 ISI markedarmoured cable multistrand Aluminium conductor for1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road corssing or floor offollowing size of cables.XLPE insulated Al. Ar.Cable

a 3.5C x 400 sq.mm. RM 200b 3.5C x 300 sq.mm. RM 200c 3.5C x 240 sq.mm. RM 200d 3.5C x 25 sq.mm. RM 600e 4C x 16 sq.mm. RM 300

60.00

Laying of one number PVC insulated and PVCsheathed / XLPEpower cable of 1.1 KV grade of following size direct in groundincluding excavation, sand cushioning, protective covering andrefilling the trench etc as required.

a Upto 35 sq. mm Metre 400b Above 185 sq. mm and upto 400 sq. mm Metre 200

61Supply and laying ,testing & commissioning offollowing sizes of Copper conductor power cables including earthing with tray including fixing clamps &effecting proper termination to equipment etc.complete as required.

a 4C x 16 Sq. mm ( Armoured ) RMT 150

CABLE JOINTING & END TERMINATION

62.00

Supplying and making end termination with brasscompressiongland and aluminium lugs for following size of PVCinsulated andPVC sheathed / XLPE aluminium conductor cable of1.1 KV grade as required.

a 3½ X 25 sq. mm (28mm) Each 100b 3½ X 240 sq. mm (62mm) Each 8c 4 X 16 sq. mm (28mm) Each 40d 3½ X 300 sq. mm (70mm) Each 4e 3½ X 400 sq. mm (82mm) Each 8

50 of 88

Page 52: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5

6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

63.00Supplying and making outdoor end termination with cast resin compound including aluminium lugs andother jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required.

a 3½ X 185 sq. mm (57mm) Each 4b 3½ X 240 sq. mm Each 4c 3½ X 300 sq. mm Each 4d 3½ X 400 sq. mm Each 4

64.00 MS perforated cable tray painted with powder coating 300 X 50 X 1.6 mm Metre 100Total Amount For Internal Electrical Works (C/f to Summary)

51 of 88

Page 53: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

TYPE-V QUARTERSANITARY & PLUMBING WORKS

1.0 Providing & fixing wall hung type white/coloured vitreous china European wall hung water closet ofapproved make syphonic wall mounting with concealed `P' or ‘S’ trap, seat & lid white or as approved with(heavy duty) with Two Way Bib Cock with Health fuacet 1.0 Meter Long PVC Tube & Wall Hook having allinternal fittings, dual flushing cistern , C.P. brass hinges & rubber buffer with fittings C.I. / M.S. bracktes40mm diameter flush bend with fitting & clamps, overflow arrangment with special and mosquito proofcoipling of approved municipal design complete including painting of fittings & brackts cutting & makinggood the wall or direction of engineer incharge.

Each 40

2.0 Providing & fixing white/coloured vitreous china floor mounting type one piece / two piece ( WC+dualflushing Cistern) EWC of approved make with concealed `P' or ‘S’ trap , Two Way Bib Cock with Healthfuacet 1.0 Meter Long PVC Tube & Wall Hook having all internal fittings including 110mm dai WCconnector Bend, Brackets, C.P bolts, nuts, solid plastic seat lid white or as approved. C.P brass hinges andrubber buffer, 32 mm dia flush pipe with clamp and adapter rubber joint, painting of fittings & brackets,C.P brass screws and washer complete including cutting & making good the walls/floor/slab whererequired. or direction of engineer incharge.

Each 40

3.0 P & F vitreous china oval below counter wash basin size 550x480mm of approved make with C.I. / M.S.brackets, 15mm C.P. brass single lever basin mixer with 450mm long copper connection and piller tap pipeand brass nuts of approved make, 32mm C.P. brass waste coupling of standard pattern of approvedmake including C.P. cast brass bottle trap 40 mm with extension piece, rubber adaptor, wall flange,union, C.P. brass chainrubber plug painting of fitting and brackets, cutting and making good the wallwherever required.

Each 80

4.0 SITC of 1.0 mm thick Salem stainless steel AISI -304 kitchen sink of approved make (Nirali, Neel – kanth,Jaina, Faber-Castell ) with C.I. brackets (duly painted with 2 coats of paint over a coat of primer) with largewaste coupling, C.P. sink mixer with swinging spout J-pipe . complete including cutting & making good thewall/counter etc.:

Overall Size Bowl Size45" x 20" x 8" 20"x16"x8" (with drain board) Each 40

5.0 Providing and fixing 600x450 mm bevelled edge mirror of superior glass (of approved quality)complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws andwashers complete.

Each 80

6.0 Providing and fixing 600x120x5mm glass shelf with edges round of supported on anodised aluminiumangle frame with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugsetc., complete.

Each 80

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASEDCOMBINED CYCLE POWER PLANT OF OTPC

SANITARY, PLUMBING, INTERNAL ELECTRICAL WORKS

52 of 88

Page 54: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

7.0 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brassscrews with concealed fitting arrangement of approved 450mm long towel rail with total length of495mm, 78mm wide and effective height quality and colour.

7.0 600mm long towel rail with total length of 645mm, width 78mm and effective height of 88mm, weighing notless than 190gms.

Each 80

8.0 Providing fixing SS Towel Rack 600mm Long 200mm wide of approved make with Lower HangersCP brackets fixed to wooden cleats, PVC rawl plug with CP brass screws etc. including cutting and makinggood the wall wherever required.

Each 80

9.0 P & F C. P. brass Toilet Paper Holder with rod of approved quality/make, with CP brass screws &rowlplugs as approved

Each 80

10.0 P & F Inlet Connection (Angle Valves) Superior quality, of approved make, with CP wall flange, Nut andWasher etc complete as required for Wash basin, Gyser etc. complete including cutting & making good thewall/counter etc.

a) C.P. Inlet connection 15mm.Brass (IS : 8931 marked) Each 480

11.0 SITC of Superior quality of approved make CP Brass fittings complete as per direction of EI

a) Wall mixer 3 in 1 system with tetephonic bath shower with bend pipe Each 8012.0 Providing and fixing Shower Superior quality of approved make CP Brass fittings complete as per direction

of engineer incharge.Each 80

13.0 Providing and fixing PTMT (Polytetra Methylene Terephthalate) soap Dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fitting arrangements weighing not less than 106 gms.

Each 80

14.0 Providing fixing satin finish stainless steel AISI 316 grade wall mounted coat hooks/peg rag (makedline or equivalent) on door with complete fittings complete.

Each 80

15.0 Providing and fixing PolyetheleneAluminiumPolyethelene (PEALPE) Composite Pressure Pipes conforming toIS 15450 U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capableto withstand temperature up to 800 C including all special fittings of composite material (engineeringplastic blend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connectors etc.with clamps at 1.00 metre spacing. This includes testing of joints complete as per direction of the Engineerin charge.

Internal work - Exposed on wall15.1 1216 (16 mm OD) pipe Mtr RO15.2 1620 (20 mm OD) pipe Mtr 44815.3 2025 (25 mm OD) pipe Mtr 70015.4 2532 (32 mm OD) pipe Mtr 25215.5 3240 (40 mm OD) pipe Mtr RO15.6 4050 (50 mm OD) pipe Mtr 28015.7 5065 (65 mm OD) pipe Mtr 150

53 of 88

Page 55: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

15.8 6580 (80 mm OD) pipe Mtr 1016.0 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL- PE) Composite Pressure Pipes

conforming to IS - 15450 U.V. stabilized with carbon black having thermal stability for hot & coldwater supply, capable to withstand temperature up to 800 C including all special fittings of compositematerial (engineering plastic blend and brass inserts wherever required) e.g. elbows, tees, reducers,couplers & connectors etc. with clamps at 1.00 metre spacing. This includes the costs of cutting chases andincluding testing of joints complete as per direction of the engineer in charge. Concealed work includingcutting chases and making good the walletc.Concealed work including cutting chases and making good the wall etc.

16.1 1216 (16 mm OD) pipe Mtr 88016.2 1620 (20 mm OD) pipe Mtr 24016.3 2025 (25 mm OD) pipe Mtr RO16.4 2532 (32 mm OD) pipe Mtr RO17.0 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL- PE) Composite Pressure Pipes

conforming to IS - 15450 - 2004 U.V. stabilized with carbon black having thermal stability for hot & coldwater supply, capable to withstand temperature up to 800 C including all special fittings of composite material(engineering plastic blend and brass inserts wherever required ) e.g. elbows ,tees ,reducers, couplers &connectors etc. with trenching, refilling and testing of joints complete as per direction of the engineer in charge.

External work17.1 1216 (16 mm OD) pipe Mtr RO17.2 1620 (20 mm OD) pipe Mtr RO17.3 2025 (25 mm OD) pipe Mtr RO17.4 2532 (32 mm OD) pipe for flushing water tank Mtr RO17.5 3240 (40 mm OD) pipe Mtr 5017.6 4050 (50 mm OD) pipe for domestic water tank Mtr 5018.0 Supply & Wrapping of Hot water pipes with 9 mm thick nitrial foam type tube foam for hot water concealed

piping raping work including jointing treatment. (Rate to be coated per meter of pipe length).( Superloan/Accoflex / Armaflex Make)

18.1 15 mm dia pipes Mtr 400

18.2 20 mm dia pipes Mtr 224

18.3 25 mm dia pipes Mtr 252

18.4 32 mm dia pipes Mtr RO

18.5 40 mm dia pipes Mtr RO18.6 50 mm dia pipes Mtr 150

19.0 SITC of Ball Cock (IS :1703 Mark) with Rod & P.V.C. Ball complete :19.1 Brass wt.400 gm,15mm. In shaft Each 120

19.2 Brass wt.750 gm, 20mm. In shaft Each 120

54 of 88

Page 56: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

19.3 (-do-) wt.1000 gm, 25mm. At terrace Each 4819.4 (-do-) wt.1000 gm, 32mm At terrace Each 36

19.5 (-do-) wt.1200 gm 40mm at tarrece Each 219.6 (-do-) wt.2000 gm 50mm at tarrece Each 2

20.0 P & F Full-way Gun-metal Valve (IS:778 Mark) or wheel valve of approved make :a) Gun-metal 65mm nominal bore. Each 1b) Gun-metal 80mm nominal bore. Each 1

21.0 Providing, fixing & testing uPVC SWR pipes confirming to IS 13592 (Type B) alongwith all required fittingslike tees, bends, offsets, 'Y', crosses with or without access doors jointed with approved solvent cementas per manufacturer's recommendations, fixed to walls and ceilings with clamps complete including cuttingand making good the floors and walls where required complete of outer diameter.

21.1 50 mm dia (for wash basin & balcony drainage) Mtr 40021.2 75 mm dia Mtr 160

21.3 110 mm dia (Soil Waste 190mtr Horizontal+770mtr in shaft+60mtr in Ground )+(Rain Water 462 m inshaft+50 mtr in ground)

Mtr 1532

21.4 160 mm dia (in ground level) Mtr 8022.0 Providing and laying 150 mm thick cement concrete 1:5:10 mix ( 1 cement : 5 coarse Sand : 10 graded

stone aggregate 40 mm nominal size) alround UPVC pipe including bed concrete 150 mm as perstandard design.

Metre 190

23.0 SITC of Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes fittings type B for sciland waste dischargesystem (IS:13592 : 1992 Marked) of approved quality /make, including complete including cutting andmaking good the wall/Floor:

23.1 Multi floor trap110mmx75mm dia Each 80

23.2 Nahni Trap with Jali110x110mm dia Each 40

23.3 Nahni Trap with Jali110x75 mm dia Each RO

23.4 75x50mm dia Each 8024.0 Providing and fixing square mouth (S.W) gully trap grade `A' complete with C.I. grating brick masonry

chamber with bricks of class designation 75 and water tight double seal C.I. cover with frame of 300 x 300mm internal size. The weight of cover to be not less than 4.5 kg and frame to be not less than 2.70 kg. as perstandard design.

a) 150 x 100 mm size ‘P’ type. Each 1225.0 Construction of chamber in all type of soil with 230 mm thick masonry in CM 1:6 m 10 cm thick C.C. 1:5:10 in

foundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 20mm external plaster1:4 ( 1 cement:4 course sand), 50 mm thick M-15 grade C.C. flooring , earthwork etc. complete as per designincluding disposal of surplus earth within a lead of 50 mtr.

55 of 88

Page 57: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

25.1 300x300x300 mm size (inside) chamber with precast cover or 5Kg. C.I. frame to with stand 3 MTcenter point load & minimum unfractured load of 1 MT. (Light duty)

Each 12

25.2 450x450x450 mm size (inside) chamber with precast cover or 12Kg. C.I. frame to with stand 15 MTcenter point load & minimum unfractured load of 1 MT. (medium duty)

Each 5

25.3 600x450x600 mm size chamber with precast cover or 22Kg. C.I. frame to with stand 22 MT center point load &minimum unfractured load of1 MT. (heavy duty)

Each 5

26.0 Construction of grease trap chamber 900x450mm( clear size depth to invert upto 1200mm) with 230mmthk. Brick work in 1:5 CM and 230mm thk. PCC 1:2:4 beddign 20mm thk. Cement water proof plastersmooth finish inside and rough outside 100mm thk. RCC baffle about 450mm away from inlet with 1 no.900x450mm heavy duty water tight CI cover and frame (weight not less then 125 Kg). includingexcavation in all soil, loose boulder etc. as per specifictions, back filling, ramming and consolidation andremoveing surplus earth as directed, including making smooth rendering for floor in cement finish towards inletas per drawing.

Each 2

27.0 Design and construction of RCC terrace tank including RCC M-25 grade concrete, relevant shuttering,steel reinforcement, foundation, puddle flange, level indicator, level controller, manholes, MS rungs,ventilators complete & comissioning as per specification & including waterproofing of the tank aginst anyleakage, the design of the tank to be got approved from the consultant before execution.

27.1 15000 litres capacity for Domestic Water Supply Each 127.2 5000 litres capacity for Flushing Water Supply Each 1

56 of 88

Page 58: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

28.0 500 Ltr Cap. Each 8

Supplying, installation, testing and commissioning of solar hot water generator with collectors,collector stands and frame. Technical specification as below for 500 litre capacity. Type of COLLECTOR : Cu-Cu, ultrasonically welded. Size of collector: 2600 X 1450 X100 mm Absorber area: 3.70 sqm Absorber coating: selective coated black chrome Nelsoncollectors absorvity >0.95 Collectors emissivity:<0.20 Collector boxmaterial: extruded aluminium frame 1.4 mm Fin width :120 mm, Insulating material: RockwoolThcikness of bottom insulation: 50 mm Thicknessof side insulation: 25 mm Thermalconductivity:0.029 W/mk, Density: 40 kg/cum, Collectors glazing materials:Material: Toughened clear glass thickness :4.0mm transitivity: 88% Glassbeeding:EPDM,Supplying, installation, testing and commissioning of 500 litres insulated hot water storage tankof following specs, Capacity:500 litres,Material: SS-304, Insulating material for tank:Glasswool, Thermal conductivity of insulation:0.028 to 0.033 W/mk, Density of insulation material:48 kg/cum,Thickness of insulation material:100 mm, Cladding material:Al 22 SWG, Supply,installation,testing andcommissioning of 500 litre insulated hot water storage tank of following specs: Capacity: 500 litres, Material:SS-304, Insulating material for tank:glasswool,thermal conductivity of insulation :0.028 to 0.033 W/mk,density ofinsultaion material;48 kg/cum, thickness of insulation material:100 mm,cladding material:Al-22 SWG, hot waterprimary circulation pump, centifugal type with mechanical seal having flow rate of 0.5 LPS at 25m head(1W+1S), hot water return pump, centrifugal type with mechanical seal having flow rate of 0.5LPS at 25m head(1W+1S), providing and fixing of 25 mm NB water flow meter on the pipes complete with Y-type strainer,bypass valve and full way ball valves on each side with flanged joints. Providing and fixing of 100 mm diaPressure Gauge, syphon and cock valve, providing and fixing of 25 mm NB, 220 V AC water line solenoidvalves screwed. Providing and fixing of flaot type level switches in mixing tank. Electrical panel in sheet metalenclosure (3phase) comprising of TPN MCB, overload relay with single phase protection features, ON/OFFand Trip indication lamps, contractors, contcts for automation system interlocking etc suitable for 9 nos DOLstrteers for pump motors and 6 nos feeders for 9kW heat paumps. The electrical panel in sheet metalenclosure (3 phase) comprising of TPN MCB, overload relay with single phasing protection features,ON/OFFand Trip indiation lamps, contractors contacts for automation system interlocking etc suitable for 9 nos DOLstarters for pump motors and 6 nos feeders for 9kW Heat pumps.Power and control cable and termination, 4CX 4.0 sqmm 1100 V grade PVC insulated copper armoured cable,3CX2.5 sqmm 1100 V grade PVC insulatedcopper armoured cable, 3CX1.5 sqmm 1100V grade PVC insulated copper control cable, 3CX1.0 sqmm 650 Vgrade copper screened/shielded cable, providing and fixing of PT100 temperature sensor with 4-20 mA headmounted transmitter, SS 304 probe suitable for pipe and tank mounting.

28.0

57 of 88

Page 59: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

29.0 SITC Stailness steel (SS) Tanks 1000 ltr capacity are made from SS304 2BA mirror finish imported sheets(0.5 mm to 1.00 mm thickness) and light weight.Chemical composition corrosion and heat resisting as per AISI Inlet and Outlet are threaded (BSP)connections,Inlet 3/4" - PVC fittings, except loft where connc. Size = ½" Outlet 1" - SS fittings, except loft where connc. Size= ½"There are two nozzles at the top, of ¾" size. (One for inlet and other for vent)There are two nozzles also at bottom, of 1" size. (One for outlet and other for cleaning)DD - Dish Top & Dish BottomDF - Dish Top & Flat Bottom

Each 4

30.0 Providing and fixing of Hot Water Geysers complete with fitting & testing, colour or approval make withrespect.15 to 25 LTR. Cap. Each 108Total C/f to Summary of Price Bid

INTERNAL ELECTRICAL WORKSSub-Mains & Point Wiring

1 Wiring for light/fan/exhaust fan/call bell point with 1.5 sq.mm PVC insulated copper conductor cable in PVCconduit etc. as required.Short point:- Cudm 130Medium point:- Cudm 260Long point:- Cudm 910

2 Wiring for 3/5 pin 5/6 amps plug point with 1.5 sq.mm PVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 520Medium point:- Cudm 125Long point:- Cudm 40

3 Wiring for 3/6 pin 15/16 amps plug point with 4 sq.mm PVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 10Medium point:- Cudm 20Long point:- Cudm 255

4 Wiring for circuit/sub-main wiring with the following sizes PVC insulated copper conductor cable in PVCconduit etc. as required.1 x 1.5 sq.mm:- mtr 45002 x 2.5 sq.mm:- mtr 45001 x 2.5 sq.mm:- (for Ac Point) mtr 20002 x 4 sq.mm:- (for Ac Point) mtr 2000

58 of 88

Page 60: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

5Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated,shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/PVC conduit as required.

mtr 2000

6 Supplying and fixing of the following PVC conduit i/c all accessories as required:-19 mm:- mtr 700025 mm:- mtr 3500

7 Supplying and fixing of 12 way metal enclosure for 240/415 volts MCB (SP/SPN/DP) or Isolator,complete with necessary bus bar, earth bar, neutral link, din rail etc i/c connection as required.Category B:- each 21

8 Supplying and fixing of 3x6 way metal enclosure for 240/415 volts MCB (SP/SPN/DP/FP) or Isolator, completewith necessary bus bar, earth bar, neutral link, din rail etc i/c connection as required.Category B:- each 40

9 Supplying and fixing of 5 to 32 amps rating 240 volts 'G' series MCB of single pole in the existing MCB DBcomplete with connection etc. as required.Category B:- each 732

10 Supplying and fixing of 63 amps rating 415 volts 'G' series MCB of four pole in the existing MCB DBcomplete with connection etc. as requiredCategory B:- each 40

11Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DBcomplete with connections, testing and commissioning etc. as required.40 amps each 180

12 P & F double ball bearing capacitor start, aluminium body & blade ceiling fan with down rod up to 30 cm with3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. each 200

13 Supplying and fixing of 230 mm sweep Exhaust fan in the exisisting hole i/c necessary connection etc. asrequired. each 80

14 Supplying and fixing of 300 mm sweep/ 900 r.p.mExhaust fan in the exisisting hole i/c necessary connection etc. as required. each 40

15 Supplying and fixing of necessary shutter for 230 mmExhaust fan in the exisisting hole i/c necessary painting etc. as required. each 80

59 of 88

Page 61: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

16 Supplying and fixing of necessary shutter for 300 mmExhaust fan in the exisisting hole i/c necessary painting etc. as required. each 40

17 Supplying and fixing of Ding Dong call bell i/c necessary connection etc. as required. each 40

18 Supplying and fixing of Holder (Angel/Batten)/ ceiling rose i/c necessary connection etc. as required. each 40

19 S.P. 5/6 amps, two way modular switch, ISI marked each 4220 Stepped type Modular Fan regulator (2 module) each 20021 Telephone Socket outlet modular type each 12022 T.V. Socket outlet modular type each 8023 Modular blanking plate each 10024 Modular base & cover plate for 1 module each 20025 Modular base & cover plate for 2 module each 120

26 Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size ofphenolic laminated sheet cover in front including painting etc as required.

27 75 mm X 75 mm X 60 mm deep (for Tel .& TV socket) each 20028 100 mm X 100 mm X 60 mm deep (for DP Switch for AC.) each 120

29 Supplying and fixing of 32 amps DP switch (kit kat) i/c necessary connection etc. as required. each 120

Telecomunication

30P & F Krone module with base frame in the recess / surface made out of 16 SWG sheet steel box, frontopenable, having locking arrangements duly powder painted.,including dressing, ferruling and punching oftelephone cable with krone tool etc. as required.

a 20 Pairs Each 10

31

Supply, installation, testing and commissioning of out door type lockable Main field distribution panel withswivel input stub and splice chamber as required, for the lines. The panel shall have provision for bottomcable feeding. The conductors in the swivel stub and splice chamber shall have 24 AWG conductors andsatisfy the fuse link requirement.

a 200 Pairs Each 1

32 Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.

a 4 Pair Metre 2400b 20 Pair Metre 250

60 of 88

Page 62: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

33

Supplying & erecting Delton or approved makeTelephone Cable electrolytic grade annealed copper conductor insulated with PE insulation twisted in to pairswith colour combination bunched together in concentric layers so as to minimizes cross-talk & wrapped withFR PVC tape & sheathed with FR PVC or HFFR outer Jacket suitable for indoor telephone wiring &confirming to C-DOT S/WS - 113/ IEC60189-2, UL-1581 SECTION 1080 V W-1 erected in existing pipe of following size of conductor & nos. of pairs.with necessary connections.100 Pair Metre 400

Lighting Fixtures

34

P & F strip type fluorscent tube fitting fabricated from (CRCA sheet and finished with powder coating /stove enamelled paint) / (extruded non corrosive UV resist EP channel) complete with accessories (Low LossCopper Choke, starter, starter seat) / Electronic Choke with terminal block duly prewired with copper conductorincluding making connection, testing etc. as required( without tube).1 X 28 Watts with EB each 250

35 T5 lamps28 Watts each 250

36

P & F of surface mounting 2 X 9/11 watt CFL luminaire made from engineering plastic with aluminiumreflector assembly electrochemicaly brightened and anodized cross louvers, complete with accessoriescopper ballast,starter,holder,terminal blockduly prewired with copper conductor including making connections,testing etc. as required (with lamp) Philips, Bajaj, Wipro

each 80.0

37P & F 9/11/13/ Watt CFL mirror light with CRCA powder coated housing, diffuser, end covers, copperballast, holder prewired upto terminal block including making connection testing etc. as required(with tube)Make Philips, Bajaj, Wipro

each 80.0

38 P & F energy efficient / energy saving direct fit (Retrofit) composite self ballasted compact fluorscentlamp (CFL) with PF >0.85 in existing holder / fixture as required. (Make Philips, Bajaj, Wipro)14/15 Watt each 1018/20 Watt each 40

39P & F of decorative round/square shape surface mounting ceilng fitting complete with holder,aluminiumanodized back plate glass globe of approved design,prewired terminal block making connection,testing etc. asrequired as approved by Engineer in charge .

150 mm each 120

40P & F of IP 65 protected LED down lighter luminaire with housing made of Die Cast aluminium housing withpowder coated finish and toughened glass diffuser, 1W LED, supply accessories(220 V, 50 HZ/12 V DC)complete in all respect. Available with 5 color option Make Philips (Green LED),Equivalent Bajaj , Wipro.

each 76

61 of 88

Page 63: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

41P & F' L' type fancy wall bracket suitable for GLS lamp with back plate of size 150mm x 40mm x 3mm glassshade of dia150/100 mm,brass holder duly prewired with pvc copper wire including making connection testingetc. as required & approved by Engineer in Charge

each 165.0

42 P & F of bed Light including making connection testing etc. as required & approved by Engineer in Charge. each 80.0

Solar PV Sytem43 Supply, Installation, Testing & Commissioning of solar photo voltaic Module (210 Wp+/-2%) Each 3044 Supply & Installation of Module Mounting Structure Each 145 Supply & Installation of Array Junction Box (4 In-1 Out) Each 146 Supply, Installation, Testing & Commissioning of 1 Core 4 sqmm. Poly ethelene Cu cable Sqmtr 10047 Supply, Installation, Testing & Commissioning of 1 Core 4 sqmm. Poly ethelene Cu cable Sqmtr 3048 Supply, Installation, Testing & Commissioning of 1 Core 25 sqmm. Poly ethelene Cu cable Sqmtr 10049 Supply, Installation, Testing & Commissioning of 3-1/2 Core 10 sqmm. Poly ethelene AL cable Sqmtr 8

50 Supply, Installation, Testing & Commissioning of power conditioning Unit-SCC:2 KVA, and Inverter andcharges: 2 KVA, 03 Phase 415 V Each 1

51 Supply, Installation, Testing & Commissioning of Battery Bank 500 Ah @ 240 V VRLA AGM Each 252 Supply & Installation of DC distribution board Each 153 Supply & Installation of AC distribution board Each 154 Supply & Installation of Lighting Arrestors Mtr. 555 Supply & Installation of Electrical Accessories Each 156 Supply & Installation of Earthing Kit Each 2

Panel & AccessoriesMetering Panel Normal (QTR. Type-V)

57

Supply, installation, testing and commissioning of surface/ recessed mounted 16 SWG CRCA sheetsteel fabricated double door type powder coated MCB Distribution board complete with tinned copperchannel, neutral & earth link, interconnection as required, with suitable nos. of knockout holes for 25 mm dia.conduit, including cutting of wall and making good of the same, complete with the following.

INCOMER1 No. 630A TP MCCB +INDICATION+ METERING1 Nos.630A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each

62 of 88

Page 64: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each

63 of 88

Page 65: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each1 Nos.630A FP EDO ACB having microprocessorbased programmable trip setting for releases for the following integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 630/5A,15VA, 5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 630/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 630/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 630A, TPN Aluminum bus bars with colour coded PVC sleeves

64 of 88

Page 66: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 630/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 630/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 630A, TPN Aluminum bus bars with colour coded PVC sleeves3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 630/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 630/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 630A, TPN Aluminum bus bars with colour coded PVC sleeves3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 630/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 630/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 630A, TPN Aluminum bus bars with colour coded PVC sleeves3 Nos. Load Analyser cum digital Multifunction Meterwith 3 nos. 630/5A, CL-1 CTs for each analyser, as required.3 Sets of Breaker ON-OFF-TRIP, Spring chargedindication Lamps1 Sets of 630/5A, 15 VA, class-1 CTs for APFC relay

BUS BAR1Sets of 630A, TPN Aluminum bus bars with colour coded PVC sleevesOUTGOINGS40 Nos. 6-40A DP MCBSupply, Receiving, Fixing, testing &commissioning of Capacitor panel as described above Sets 1

Metering Panel Emergency Panel (QTR. Type-V)

65 of 88

Page 67: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

58

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

58

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

58

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

58

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

66 of 88

Page 68: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

58

Supply, installation, testing and commissioning ofsurface/ recessed mounted 16 SWG CRCA sheet steel fabricated double door type powder coatedMCB Distribution board complete with tinned copper channel, neutral & earth link, interconnection as required,with suitable nos. of knockout holes for 25 mm dia. conduit, including cutting of wall and making good of thesame, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING+BUSOUTGOINGS25 No. 6-63A DP MCB

Set 1

59

P&F of IP51 direct or CT operated, 1x240 / 3x240volts , 50 Hz static watt-hour meter (kwh) having resolution 0.1 / 0.01 kwh , 1/ 0.5 accuracy class , LEDindicators for tamper operation ( Reverse &/or earth connection) , pulsating LED indicator for meterology ,electromechanical counter , LCD Display, cover plate for body and terminal sealing , including makingconnection ,testing etc. as required. up to 60 ampere three phase meter

Each 20

L.T. Cables & Trays

60

Providing & erecting XLPE(IS:7098) (I)-88 ISI markedarmoured cable multistrand Aluminium conductor for1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road corssing or floor offollowing size of cables.XLPE insulated Al. Ar.Cable

a 3.5C x 400 sq.mm. RM 200b 3.5C x 300 sq.mm. RM 200c 3.5C x 25 sq.mm. RM 600d 4C x 16 sq.mm. RM 300

61Laying of one number PVC insulated and PVC sheathed / XLPEpower cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning,protective covering and refilling the trench etc as required.

a Upto 35 sq. mm Metre 400b Above 185 sq. mm and upto 400 sq. mm Metre 200

62Supply and laying ,testing & commissioning of following sizes of Copper conductor power cablesincluding earthing with tray including fixing clamps & effecting proper termination to equipment etc.completeas required.

a 4C x 16 Sq. mm ( Armoured ) RMT 150

CABLE JOINTING & END TERMINATION

63 Supplying and making end termination with brass compression gland and aluminium lugs for following sizeof PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.

a 3½ X 25 sq. mm (28mm) Each 100

67 of 88

Page 69: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

b 4 X 16 sq. mm (28mm) Each 40c 3½ X 300 sq. mm (70mm) Each 4d 3½ X 400 sq. mm (82mm) Each 8

64Supplying and making outdoor end termination with cast resin compound including aluminium lugs andother jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required.

a 3½ X 185 sq. mm (57mm) Each 4c 3½ X 300 sq. mm Each 4d 3½ X 400 sq. mm Each 4

65 MS perforated cable tray painted with powder coating 300 X 50 X 1.6 mm Metre 100

Total Amount For Internal Electrical Works

68 of 88

Page 70: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

CLUB HOUSE SANITARY & PLUMBING WORKS

SUB HEAD 1 PIPES & PIPE FITTINGS1.0 Providing & fixing wall hung type white/coloured vitreous china European wall hung water closet of approved

make syphonic wall mounting with concealed `P' or ‘S’ trap, seat & lid white or as approved with (heavy duty)with Two Way Bib Cock with Health fuacet 1.0 Meter Long PVC Tube & Wall Hook having all internal fittings,dual flushing cistern , C.P. brass hinges & rubber buffer with fittings C.I. / M.S. bracktes 40mm diameter flushbend with fitting & clamps, overflow arrangment with special and mosquito proof coipling of approved municipaldesign complete including painting of fittings & brackts cutting & making good the wall or direction of engineerincharge.

Each 6

2.0 Providing & fixing white/coloured vitreous china floor mounting type one piece / two piece ( WC+dual flushingCistern) EWC of approved make with concealed `P' or ‘S’ trap , Two Way Bib Cock with Health fuacet 1.0 MeterLong PVC Tube & Wall Hook having all internal fittings including 110mm dai WC connector Bend, Brackets,C.P bolts, nuts, solid plastic seat lid white or as approved. C.P brass hinges and rubber buffer, 32 mm dia flushpipe with clamp and adapter rubber joint, painting of fittings & brackets, C.P brass screws and washer completeincluding cutting & making good the walls/floor/slab where required. or direction of engineer incharge.

Each 3

3.0 P & F vitreous china oval type counter top wash basin size 550x480mm of approved make with C.I. / M.S.brackets, 15mm C.P. brass single lever basin mixer with 450mm long copper connection and piller tap pipe andbrass nuts of approved make, 32mm C.P. brass waste coupling of standard pattern of approved makeincluding C.P. cast brass bottle trap 40 mm with extension piece, rubber adaptor, wall flange, union, C.P. brasschainrubber plug painting of fitting and brackets, cutting and making good the wall wherever required.

Each 7

3.0 P & F vitreous china oval below counter wash basin size 550x480mm of approved make with C.I. / M.S.brackets, 15mm C.P. brass single lever basin mixer with 450mm long copper connection and piller tap pipe andbrass nuts of approved make, 32mm C.P. brass waste coupling of standard pattern of approved makeincluding C.P. cast brass bottle trap 40 mm with extension piece, rubber adaptor, wall flange, union, C.P. brasschainrubber plug painting of fitting and brackets, cutting and making good the wall wherever required.

Each 4

4.0 Fixing white vitreous china flat back half stall urinal of size 580x380x350mm with white PVCautomatic flushing cistern, with fittings, standard size C.P. brass flush pipe, spreaders with unions and clamps(all in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet grating and other couplings in C.P.brass including painting of fittings and cutting and making good the walls and floors wherever required :

a) Single half stall urinal with 5 litre P.V.C. automatic flushing cistern. Each 7

Name of Work: CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE FOR THE PROJECT “CONSTRUCTION OF TOWNSHIP AT KHILPARA, UDAIPUR, TRIPURA” FOR 2x363.3MW GAS BASEDCOMBINED CYCLE POWER PLANT OF OTPC

SANITARY, PLUMBING, INTERNAL ELECTRICAL WORKS

69 of 88

Page 71: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

5.0 P&F Marble Urinal Partition slab Makrana II quality marble having light spotsboth sides polished of approveddesign cut from marble size 20mm thick 900x600mm, including all fixing arrangement, cutting and making goodthe walls wherever required.

Each 8

6.0 Providing fixing fully automatic "No tough" hand drier suitable to operate on 230 volts, single phase, 50 Hz ACpower supply complete with brackets for fixing on wall including cutting and making good the walls whereverrequired.

Each 5

7.0 SITC of 1.0 mm thick Salem stainless steel AISI -304 kitchen sink of approved make (Nirali, Neel – kanth,Jaina, Faber-Castell ) with C.I. brackets (duly painted with 2 coats of paint over a coat of primer) with largewaste coupling, C.P. sink mixer with swinging spout J-pipe . complete including cutting & making good thewall/counter etc.:Overall Size Bowl Size45" x 20" x 8" 20"x16"x8" (with drain board) Each 1

8.0 Providing and fixing 600x450 mm bevelled edge mirror of superior glass (of approved quality) complete with 6mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.

Each 4

9.0 Providing fixing 6mm thick bevelled edge of approved make/quality 0.5" water proof ply backing with 3"x1.5"thick lvory coast teakwood frame all around spririt polished.

Sqm 5

10.0 Providing and fixing 600x120x5mm glass shelf with edges round of supported on anodised aluminium angleframe with C.P. brass brackets and guard rail complete fixed with 40 mm long screws, rawl plugs etc., complete.

Each 10

11.0 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screwswith concealed fitting arrangement of approved 450mm long towel rail with total length of 495mm, 78mm wideand effective height quality and colour.

11.0 600mm long towel rail with total length of 645mm, width 78mm and effective height of 88mm, weighing notless than 190gms.

Each 15

12.0 Providing fixing SS Towel Rack 600mm Long 200mm wide of approved make with Lower Hangers CP bracketsfixed to wooden cleats, PVC rawl plug with CP brass screws etc. including cutting and making good the wallwherever required.

Each 6

13.0 P & F C. P. brass Toilet Paper Holder with rod of approved quality/make,with CP brass screws & rowlplugs asapproved

Each 9

14.0 P & F Inlet Connection (Angle Valves) Superior quality, of approved make, with CP wall flange, Nut and Washeretc complete as required for Wash basin, Gyser etc. complete including cutting & making good the wall/counteretc.

C.P. Inlet connection 15mm.Brass (IS : 8931 marked) Each 4815.0 SITC of Superior quality of approved make CP Brass fittings complete as

per direction of EI15.0 Wall mixer 3 in 1 system with tetephonic bath shower with bend pipe Each 416.0 Providing and fixing Shower Superior quality of approved make CP Brass fittings complete as per direction of

engineer incharge.Each 4

17.0 Providing and fixing PTMT (Polytetra Methylene Terephthalate) soap Dish Holder having length of 138mm,breadth 102mm, height of 75mm with concealed fitting arrangements weighing not less than 106 gms.

Each 4

70 of 88

Page 72: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

18.0 Providing fixing satin finish stainless steel AISI 316 grade wall mounted coat hooks/peg rag (make dline orequivalent) on door with complete fittings complete.

Each 6

19.0 Providing and fixing PolyetheleneAluminiumPolyethelene (PEALPE) Composite Pressure Pipes conformingto IS 15450 U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capable towithstand temperature up to 800 C including all special fittings of composite material (engineering plasticblend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connectors etc. with clampsat 1.00 metre spacing. This includes testing of joints complete as per direction of the Engineer in charge.

Internal work - Exposed on wall19.1 1216 (16 mm OD) pipe Mtr RO19.2 1620 (20 mm OD) pipe Mtr 25

19.3 2025 (25 mm OD) pipe Mtr 3019.4 2532 (32 mm OD) pipe Mtr 1019.5 3240 (40 mm OD) pipe Mtr 16819.6 4050 (50 mm OD) pipe Mtr 11019.7 5065 (65 mm OD) pipe Mtr 1019.8 6580 (80 mm OD) pipe Mtr RO20.0 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL-PE) Composite Pressure Pipes conforming

to IS - 15450 U.V. stabilized with carbon black having thermal stability for hot & cold water supply, capable towithstand temperature up to 800 C including all special fittings of composite material (engineering plasticblend and brass inserts wherever required) e.g. elbows, tees, reducers, couplers & connectors etc. with clampsat 1.00 metre spacing. This includes the costs of cutting chases and including testing of joints complete as perdirection of the engineer in charge. Concealed work including cutting chases and making good the wall etc.

Concealed work including cutting chases and making good the wall etc.20.1 1216 (16 mm OD) pipe Mtr 12120.2 1620 (20 mm OD) pipe Mtr 2020.3 2025 (25 mm OD) pipe Mtr 15

20.4 2532 (32 mm OD) pipe Mtr RO

71 of 88

Page 73: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

21.0 Providing and fixing Polyethelene-Aluminium- Polyethelene (PE-AL-PE) Composite Pressure Pipes conformingto IS - 15450 - 2004 U.V. stabilized with carbon black having thermal stability for hot & cold water supply,capable to withstand temperature up to 800 C including all special fittings of composite material (engineeringplastic blend and brass inserts wherever required ) e.g. elbows ,tees ,reducers, couplers & connectors etc. withtrenching, refilling and testing of joints complete as per direction of the engineer in charge.

External work21.1 1216 (16 mm OD) pipe Mtr RO21.2 1620 (20 mm OD) pipe Mtr RO21.3 2025 (25 mm OD) pipe Mtr 3021.4 2532 (32 mm OD) pipe for flushing water tank Mtr 3021.5 3240 (40 mm OD) pipe Mtr RO21.6 4050 (50 mm OD) pipe for domestic water tank Mtr RO22.0 Supply & Wrapping of Hot water pipes with 9 mm thick nitrial foam type tube foam for hot water concealed

piping raping work including jointing treatment. (Rate to be coated per meter of pipe length).( Superloan/Accoflex / Armaflex Make)

22.1 15 mm dia pipes Mtr 5022.2 20 mm dia pipes Mtr 2522.3 25 mm dia pipes Mtr 1022.4 32 mm dia pipes Mtr RO22.5 40 mm dia pipes Mtr 8022.6 50 mm dia pipes Mtr RO23.0 SITC of Ball Cock (IS :1703 Mark) with Rod & P.V.C. Ball complete :23.1 Brass wt.400 gm,15mm. In shaft Each 1023.2 Brass wt.750 gm, 20mm. In shaft Each 1223.3 (-do-) wt.1000 gm, 25mm. At terrace Each 423.4 (-do-) wt.1000 gm, 32mm At terrace Each 223.5 (-do-) wt.1200 gm 40mm at tarrece Each 423.6 (-do-) wt.2000 gm 50mm at tarrece Each 224.0 P & F Full-way Gun-metal Valve (IS:778 Mark) or wheel valve of approved make :24.1 Gun-metal 65mm nominal bore. Each 124.2 Gun-metal 80mm nominal bore. Each RO25.0 Providing, fixing & testing uPVC SWR pipes confirming to IS 13592 (Type B) alongwith all required fittings like

tees, bends, offsets, 'Y', crosses with or without access doors jointed with approved solvent cement as permanufacturer's recommendations, fixed to walls and ceilings with clamps complete including cutting and makinggood the floors and walls where required complete of outer diameter.

25.1 50 mm dia (for wash basin & balcony drainage) Mtr 4525.2 75 mm dia Mtr 4025.3 110 mm dia Mtr 15025.4 160 mm dia (in ground level) Mtr 5026.0 Providing and laying 150 mm thick cement concrete 1:5:10 mix ( 1 cement : 5 coarse Sand : 10 graded stone

aggregate 40 mm nominal size) alround UPVC pipe including bed concrete 150 mm as per standard design.Metre 80

72 of 88

Page 74: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

27.0 SITC of Unplasticized Poly Vinyl Chloride (UPVC) SWR Pipes fittings type B for sciland waste dischargesystem (IS:13592 : 1992 Marked) of approved quality /make, including complete including cutting and makinggood the wall/Floor:

Multi floor trap110mmx75mm dia Each 12Nahni Trap with Jali110x110mm dia Each 8Nahni Trap with Jali110x75 mm dia Each 1575x50mm dia Each 11Providing and fixing square mouth (S.W) gully trap grade `A' complete with C.I. grating brick masonry chamberwith bricks of class designation 75 and water tight double seal C.I. cover with frame of 300 x 300 mm internalsize. The weight of cover to be not less than 4.5 kg and frame to be not less than 2.70 kg. as per standarddesign.150 x 100 mm size ‘P’ type. Each 5

29.0 Construction of chamber in all type of soil with 230 mm thick masonry in CM 1:6 m 10 cm thick C.C. 1:5:10 infoundation, 20mm thick insider plaster in Cm 1:6, finished with floating neat cement, 20mm external plaster1:4 ( 1 cement:4 course sand), 50 mm thick M-15 grade C.C. flooring , earthwork etc. complete as per designincluding disposal of surplus earth within a lead of 50 mtr.

29.1 300x300x300 mm size (inside) chamber with precast cover or 5Kg. C.I. frame to with stand 3 MT center pointload & minimum unfractured load of 1 MT. (Light duty)

Each 5

29.2 450x450x450 mm size (inside) chamber with precast cover or 12Kg. C.I. frame to with stand 15 MT centerpoint load & minimum unfractured load of 1 MT. (medium duty)

Each 4

29.3 600x450x600 mm size chamber with precast cover or 22Kg. C.I. frame to with stand 22 MT center point load &minimum unfractured load of 1 MT. (heavy duty)

Each 3

30.0 Construction of grease trap chamber 900x450mm( clear size depth to invert upto 1200mm) with 230mm thk.Brick work in 1:5 CM and 230mm thk. PCC 1:2:4 beddign 20mm thk. Cement water proof plaster smooth finishinside and rough outside 100mm thk. RCC baffle about 450mm away from inlet with 1 no. 900x450mm heavyduty water tight CI cover and frame (weight not less then 125 Kg). including excavation in all soil, loose boulderetc. as per specifictions, back filling, ramming and consolidation and removeing surplus earth as directed,including making smooth rendering for floor in cement finish towards inlet as per drawing.

Each 1

31.0 P & F PVC Storage Tank ISI Marked (IS : 12701) indicating the BIS license No), of approved make withcover, 25mm dia 1M long G.I. over- flow pipe & 25 Cm. long wash out pipe with plug & socket, including makinginlet & outlet connection etc., complete of approved design:

31.1 2000 litres capacity for Domestic Water Supply Each 231.2 1000 litres capacity for Flushing Water Supply Each 1

27.1

27.2

27.3

28.0

73 of 88

Page 75: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

500 Ltr Cap. Each 133.0 SITC Stailness steel (SS) Tanks 500 ltr capacity are made from SS 304

2BA mirror finish imported sheets(0.5 mm to 1.00 mm thickness) and light weight.Chemical composition corrosion and heat resisting as per AISI Inlet and Outlet are threaded (BSP) connections,Inlet 3/4" - PVC fittings, except loft where connc. Size = ½" Outlet 1" - SS fittings, except loft where connc. Size= ½"There are two nozzles at the top, of ¾" size. (One for inlet and other for vent)There are two nozzles also at bottom, of 1" size. (One for outlet and other for cleaning)DD - Dish Top & Dish BottomDF - Dish Top & Flat Bottom

Each 1

Supplying, installation, testing and commissioning of solar hot water generator with collectors,collector stands and frame. Technical specification as below for 500 litre capacity. Type of COLLECTOR : Cu-Cu, ultrasonically welded. Size of collector: 2600 X 1450 X100 mm Absorber area: 3.70 sqm Absorber coating: selective coated black chrome Nelsoncollectors absorvity >0.95 Collectors emissivity:<0.20 Collector boxmaterial: extruded aluminium frame 1.4 mm Fin width :120 mm, Insulating material: RockwoolThcikness of bottom insulation: 50 mm Thicknessof side insulation: 25 mm Thermalconductivity:0.029 W/mk, Density: 40 kg/cum, Collectors glazing materials:Material: Toughened clear glass thickness :4.0mm transitivity: 88% Glassbeeding:EPDM,Supplying, installation, testing and commissioning of 500 litres insulated hot water storage tankof following specs, Capacity:500 litres,Material: SS-304, Insulating material for tank:Glasswool, Thermal conductivity of insulation:0.028 to 0.033 W/mk, Density of insulation material:48 kg/cum,Thickness of insulation material:100 mm, Cladding material:Al 22 SWG, Supply,installation,testing andcommissioning of 500 litre insulated hot water storage tank of following specs: Capacity: 500 litres, Material:SS-304, Insulating material for tank:glasswool,thermal conductivity of insulation :0.028 to 0.033 W/mk,density ofinsultaion material;48 kg/cum, thickness of insulation material:100 mm,cladding material:Al-22 SWG, hot waterprimary circulation pump, centifugal type with mechanical seal having flow rate of 0.5 LPS at 25m head(1W+1S), hot water return pump, centrifugal type with mechanical seal having flow rate of 0.5LPS at 25m head(1W+1S), providing and fixing of 25 mm NB water flow meter on the pipes complete with Y-type strainer, bypassvalve and full way ball valves on each side with flanged joints. Providing and fixing of 100 mm dia PressureGauge, syphon and cock valve, providing and fixing of 25 mm NB, 220 V AC water line solenoid valvesscrewed. Providing and fixing of flaot type level switches in mixing tank. Electrical panel in sheet metalenclosure (3phase) comprising of TPN MCB, overload relay with single phase protection features, ON/OFF andTrip indication lamps, contractors, contcts for automation system interlocking etc suitable for 9 nos DOL strteersfor pump motors and 6 nos feeders for 9kW heat paumps. The electrical panel in sheet metal enclosure (3phase) comprising of TPN MCB, overload relay with single phasing protection features,ON/OFF and Tripindiation lamps, contractors contacts for automation system interlocking etc suitable for 9 nos DOL starters forpump motors and 6 nos feeders for 9kW Heat pumps.Power and control cable and termination, 4C X 4.0 sqmm1100 V grade PVC insulated copper armoured cable,3CX2.5 sqmm 1100 V grade PVC insulated copperarmoured cable, 3CX1.5 sqmm 1100V grade PVC insulated copper control cable, 3CX1.0 sqmm 650 V gradecopper screened/shielded cable, providing and fixing of PT100 temperature sensor with 4-20 mA head mountedtransmitter, SS 304 probe suitable for pipe and tank mounting.

32.0

74 of 88

Page 76: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

Providing and fixing of Hot Water Geysers complete with fitting & testing, colour or approval make with respect.

15 to 25 LTR. Cap. Each 5

SUB-TOTAL 'A'SUB-HEAD -2 TUBE WELL

1.0

Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS:2800 (part I), including collecting samples from different strata, preparing and submitting strata chart/bore log, including hire & running charges of all equipments, tools, plants & machineries required for thejob, all complete as per direction of Engineer -in-charge, upto 90 metre depth below ground level.

Mtr. 50

1.1 All type soil1.2 300mm dia Mtr. 50

2.0

Boring/drilling bore well of required dia for casing/ strainer pipe, by suitable method prescribed in IS:2800 (part I), including collecting samples from different strata, preparing and submitting stratachart/bore log, including hire & running charges of all equipments, tools, plants & machineries requiredfor the job, all complete as per direction of Engineer -in-charge, beyond 90 metre & upto 150 metre depthbelow ground level.

2.1 All type soil2.2 300mm dia Mtr. 30

3.0

Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric ResistanceWelded) FE 410 mild steel screwed and socketed/ plain ended casing pipes of required dia, conforming to IS:4270, of reputed & approved make, including painted with outside surface with two coats of anticorrosive paintof approved brand and manufacture, including required hire & labour charges, fittings & accessories, allcomplete, for all depths, as per direction of Engineer- in-charge.

3.1 200 mm nominal size dia having minimum wall thickness 5.40 mm Mtr. 40

4.0

Supplying, assembling, lowering and fixing in vertical position in bore well, ERW (Electric Resistance Welded)FE 410 plain slotted (having slot of size 1.6/3.2 mm) mild steel threaded and socketed / plain bevel ended pipe(type A) of required dia, conforming to IS: 8110, of reputed and approved make, having wall thickness notless than 5.40 mm, including painted with outside surface with two coats of anticorrosive bitumestic paint ofapproved brand and manufacture, including hire & labour charges, fittings & accessories, all complete, for alldepths, as per direction of Engineer -in-charge.

4.1 200 mm nominal size dia Mtr. 40

5.0

Development of tube well in accordance with IS : 2800 (part I) and IS:11189, to establish maximum rate ofusable water yield without sand content (beyond permissible limit), with required capacity air compressor,running the compressor for required time till well is fully developed, measuring yield of well by "V" notchmethod or any other approved method, measuring static level & draw down etc. by step draw downmethod, collecting water samples & getting tested in approved laboratory, i/c disinfection of tubewell, allcomplete, including hire & labour charges of air compressor, tools & accessories etc., all as per requirementand direction of Engineer-in-charge.

Hrs. 6

6.0 Providing and fixing suitable size threaded mild steel cap or spot welded plate to the top of bore wellhousing/ casing pipe, removable as per requirement, all complete for borewell of:

6.1 200mm dia Nos 2

7.0 Providing and fixing M.S. clamp of required dia to the top of casing/ housing pipe of tubewell as per IS: 2800(part I), including necessary bolts & nuts of required size complete.

7.1 200mm dia Nos. 1

34.0

75 of 88

Page 77: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

8.0 Installation of submersible pump sets suitable for 150 mm dia borewell for discharge range 60lpm to 150lpmand head 120meter to 180 meter of specified make.

Cum 1

9.0 Providing & lowering of G.I. flange pipe including rubber washer and nuts of 8 mm dia complete in all respect.

9.1 B Class 50 mm dia RM 50

10.0Providing and laying ISI marked pvc insulated Submersible cable cofirming to IS 694 with flexiblecopper conductor including making connection etc. 2.5 sqmm 3 core make ICC, nicco /Gloster/tropondour

10.1 New Tube wells RM 100

11.0

P/Laying XLPE insulated / P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor Armoured ofIS:7098-I/1554-1 approved make in ground as per IS:1255 including excavation of 30cmx75cm sizetrench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth,making necessary connection, testing etc. asrequired of size.10.0 Sq.mm 4 core (Group-1)

RM 20

11.1 Making connection of G.I. Distribution with GI main including all fitting beyond 25mm & upto to 100mm Each 1

13.0Providing & installation of Electric feeder panel for submersible pumps as per the scope of work,drasings and specifications including mounting on masonry plaeform of size 1000 mm x 600 mm as perdetailed specifications with star-delta starter suitble upto 10 HP

Each 1

14.0

SITC of radial / mixed flow submersible motor pump sets ISI marked (IS:8034-1989) of approved make withrequired accessories including making connection suitable for T.W./ D.C.B./ Open well. The job includeslowering of riser pipe, G.I./ H.D.P.E. pipe with rope, cables, installation of complete fitting and accessories,jointing of electrical cables up to switch board. All labour for testing of submersible pumps set and supply ofwater to water mains, complete in all respect. 150 mm diameter Submersible pump shall have followingHP Rating, phase, Head, minimum Discharge respectively.

14.1 10 HP, 3-Ø, (65-135)Mtr, (240-115)LPM Each 1

15.0Supplying, filling, spreading & leveling gravels of size range 5 mm to 10 mm, in the recharge pit, over theexisting layer of boulders, in required thickness, for all leads & lifts, all complete as per direction of Engineer-in-charge.

Cum 3

16.0Supplying, filling, spreading & leveling coarse sand of size range 1.5 mm to 2 mm in recharge pit, in requiredthickness over gravel layer, for all leads & lifts, all complete as per direction of Engineer -in- charge.

Cum 4

17.0Providing and fixing enclosed type water meter (bulk type) conforming to IS : 2373 and tested by MunicipalBoard complete with bolts, nuts, rubber insertions etc. (The tail pieces if required will be paid separately):

17.1 100 mm dia nominal bore Each 1

SUB-TOTAL 'B'Total C/f to Summary of Price Bid (A+B)

INTERNAL ELECTRICAL WORKSSub-Mains & Point Wiring

1 Wiring for light/fan/exhaust fan/call bell point with 1.5 sq.mm PVC insulated copper conductorcable in PVC conduit etc. as required.Short point:- Cudm 25

76 of 88

Page 78: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

Medium point:- Cudm 50Long point:- Cudm 170

2 Wiring for 3/5 pin 5/6 amps plug point with 1.5 sq.mm PVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 35Medium point:- Cudm 5Long point:- Cudm 15

3 Wiring for 3/6 pin 15/16 amps plug point with 4 sq.mm PVC insulated copper conductor cable in PVCconduit i/c earthing the 3rd pin,etc. as required.Short point:- Cudm 2Medium point:- Cudm 2Long point:- Cudm 10

4 Wiring for circuit/sub-main wiring with the following sizes PVC insulated copper conductor cable in PVC conduitetc. as required.1 x 1.5 sq.mm:- mtr 7802 x 2.5 sq.mm:- mtr 7801 x 2.5 sq.mm:- (for Ac Point) mtr 3002 x 4 sq.mm:- (for Ac Point) mtr 300

5 Supplying and fixing of the following PVC conduit i/c all accessories as required:-19 mm:- mtr 95025 mm:- mtr 350

6 Supplying and fixing of 3x6 way metal enclosure for 240/415 volts MCB (SP/SPN/DP/FP) or Isolator,complete with necessary bus bar, earth bar, neutral link, din rail etc i/c connection as required.Category B:- each 8

7 Supplying and fixing of 5 to 32 amps rating 240 volts 'G' series MCB of single pole in the existing MCB DBcomplete with connection etc. as required.Category B:- each 96

8 Supplying and fixing of 63 amps rating 415 volts 'G' series MCB of four pole in the existing MCB DB completewith connection etc. as requiredCategory B:- each 8

9Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCBDB complete with connections, testing and commissioning etc. as required.40 amps each 24

10 P & F double ball bearing capacitor start, aluminium body & blade ceiling fan with down rod up to 30 cmwith 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. each 38

77 of 88

Page 79: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

11 Supplying and fixing of 230 mm sweep Exhaust fan in the exisisting hole i/c necessary connectionetc. as required. each 4

12 Supplying and fixing of 300 mm sweep/ 900 r.p.m Exhaust fan in the exisisting hole i/c necessaryconnection etc. as required. each 2

13 Supplying and fixing of necessary shutter for 230 mm Exhaust fan in the exisisting hole i/cnecessary painting etc. as required. each 4

14 Supplying and fixing of necessary shutter for 300 mm Exhaust fan in the exisisting hole i/cnecessary painting etc. as required. each 2

15 Supplying and fixing of Holder (Angel/Batten)/ ceiling rose i/c necessary connection etc. as required. each 30

16 Stepped type Modular Fan regulator (2 module) each 3817 Telephone Socket outlet modular type each 1018 Modular blanking plate each 3019 Modular base & cover plate for 1 module each 1020 Modular base & cover plate for 2 module each 18

21 Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size ofphenolic laminated sheet cover in front including painting etc as required.

22 75 mm X 75 mm X 60 mm deep (for Tel socket) each 1023 100 mm X 100 mm X 60 mm deep (for DP Switch for AC.) each 1824 Supplying and fixing of 32 amps DP switch (kit kat) i/c necessary connection etc. as required. each 18

Telecomunication

25P & F Krone module with base frame in the recess / surface made out of 16 SWG sheet steel box, frontopenable, having locking arrangements duly powder painted.,including dressing, ferruling and punching oftelephone cable with krone tool etc. as required.20 Pairs Each 1

26Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor,unarmored telephone cablein the existing surface/ recessed steel/ PVC conduit as required.4 Pair Metre 20020 Pair Metre 150

Lighting Fixtures

27

P & F strip type fluorscent tube fitting fabricated from (CRCA sheet and finished with powdercoating / stove enamelled paint) / (extruded non corrosive UV resist EP channel) complete withaccessories (Low Loss Copper Choke, starter, starter seat) / Electronic Choke with terminalblock duly prewired with copper conductor including making connection, testing etc. asrequired( without tube).1 X 28 Watts with EB each 10

28 T5 lamps

78 of 88

Page 80: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

28 Watts each 10

29

P & F of surface mounting 2 X 9/11 watt CFL luminaire made from engineering plastic with aluminiumreflector assembly electrochemicaly brightened and anodized cross louvers, complete with accessories copperballast,starter,holder,terminal blockduly prewired with copper conductor including making connections,testing etc. as required (with lamp) Philips, Bajaj, Wipro

each 25

30P & F 9/11/13/ Watt CFL mirror light with CRCA powder coated housing, diffuser, end covers, copperballast, holder prewired upto terminal block including making connection testing etc. as required(withtube) Make Philips, Bajaj, Wipro

each 11

31 P & F energy efficient / energy saving direct fit (Retrofit) composite self ballasted compact fluorscentlamp (CFL) with PF >0.85 in existing holder / fixture as required. (Make Philips, Bajaj, Wipro)

14/15 Watt each 518/20 Watt each 5

32

P & F of IP 65 protected LED down lighter luminaire with housing made of Die Cast aluminium housingwith powder coated finish and toughened glass diffuser, 1W LED, supply accessories(220 V, 50 HZ/ 12V DC) complete in all respect. Available with 5 color option Make Philips (Green LED),Equivalent Bajaj ,Wipro.

each 55

33P & F of IP 65 protected LED cabinet luminaire with 600mm length housing made of aluminium withunit boards of 6X 2W/ 12X1.1W LEDs, supply accessories(220 V, 50 HZ/ 24 V DC) complete in all respect.Available with 2 color options – white, warm white.

each 68

34P & F' L' type fancy wall bracket suitable for GLS lamp with back plate of size 150mm x 40mm x 3mm glassshade of dia150/100 mm,brass holder duly prewired with pvc copper wire including making connectiontesting etc. as required & approved by Engineer in Charge

each 2.0

35 P & F of IP 65 protected LED down lighter luminaire with housing made of Die Cast aluminium housing withpowder coated finish and toughened glass diffuser. Make Philips (Ledo) Equivalent Bajaj ,Wipro. each 24.0

Solar PV Sytem36 Supply, Installation, Testing & Commissioning of solar photo voltaic Module (210 Wp+/-2%) Each 3037 Supply & Installation of Module Mounting Structure Each 138 Supply & Installation of Array Junction Box (4 In-1 Out) Each 1

39 Supply, Installation, Testing & Commissioning of 1 Core 4sqmm. Poly ethelene Cu cable Sqmtr 100

40 Supply, Installation, Testing & Commissioning of 1 Core 4sqmm. Poly ethelene Cu cable Sqmtr 30

41 Supply, Installation, Testing & Commissioning of 1 Core 25sqmm. Poly ethelene Cu cable Sqmtr 100

42 Supply, Installation, Testing & Commissioning of 3-1/2Core 10 sqmm. Poly ethelene AL cable Sqmtr 8

43 Supply, Installation, Testing & Commissioning of power conditioning Unit-SCC:2 KVA, and Inverter andcharges: 2 KVA, 03 Phase 415 V Each 1

44 Supply, Installation, Testing & Commissioning of Battery Bank 500 Ah @ 240 V VRLA AGM Each 2

79 of 88

Page 81: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

45 Supply & Installation of DC distribution board Each 146 Supply & Installation of AC distribution board Each 147 Supply & Installation of Lighting Arrestors Mtr. 548 Supply & Installation of Electrical Accessories Each 149 Supply & Installation of Earthing Kit Each 2

Panel & AccessoriesMetering Panel Emergency

50

Supply, installation, testing and commissioning of surface/ recessed mounted 16 SWG CRCA sheet steelfabricated double door type powder coated MCB Distribution board complete with tinned copper channel,neutral & earth link, interconnection as required, with suitable nos. of knockout holes for 25 mm dia.conduit, including cutting of wall and making good of the same, complete with the following.

INCOMER1 No. 400A TP MCCB +INDICATION+ METERING1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

80 of 88

Page 82: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

81 of 88

Page 83: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

82 of 88

Page 84: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

83 of 88

Page 85: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

84 of 88

Page 86: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves

85 of 88

Page 87: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleeves1 Nos.400A FP EDO ACB having microprocessor based programmable trip setting for releases for thefollowing integral protection:Under voltage & Overvoltage protectionIDMTL Overload, instantaneous over current & Earth fault protectionPhase Sequence ProtectionThe ACB shall be complete with 1 nos. 400/5A, 15VA,5P10 CTs for protection.Metering & Indication3 Sets of R,Y,B phase indicating lamps3 Sets of Voltmeter (0-500V) with Built-in VSS each with 3 nos. 2A SP MCBs each3 Nos. Load Analyser cum digital Multifunction Meter with 3 nos. 400/5A, CL-1 CTs for each analyser, asrequired.

3 Sets of Breaker ON-OFF-TRIP, Spring charged indicationLamps1 Sets of 400/5A, 15 VA, class-1 CTs for APFC relayBUS BAR1Sets of 400A, TPN Aluminum bus bars with colour codedPVC sleevesOUTGOINGS6 Nos. 6-63A DP MCBSupply, Receiving, Fixing, testing & commissioning ofCapacitor panel as described above Sets 1

86 of 88

Page 88: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

51

P&F of IP51 direct or CT operated, 1x240 / 3x240 volts , 50 Hz static watt-hour meter (kwh) having resolution0.1 / 0.01 kwh , 1/ 0.5 accuracy class , LED indicators for tamper operation ( Reverse &/or earth connection) ,pulsating LED indicator for meterology , electromechanical counter , LCD Display, cover plate for body andterminal sealing , including making connection ,testing etc. as required. up to 60 ampere three phase meter

Each 1

L.T. Cables & Trays

52Providing & erecting XLPE(IS:7098) (I)-88 ISI marked armoured cable multistrand Aluminium conductor for1.1 KV to be laid on wall with necessary clamps or in existing cable trench / pipe at road corssing or floor offollowing size of cables.XLPE insulated Al. Ar.Cable

a 3.5C x 400 sq.mm. RM 200b 3.5C x 25 sq.mm. RM 150c 4C x 16 sq.mm. RM 100

53Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following sizedirect in ground including excavation, sand cushioning, protective covering and refilling the trench etc asrequired.

a Upto 35 sq. mm Metre 400b Above 185 sq. mm and upto 400 sq. mm Metre 200

54Supply and laying ,testing & commissioning of following sizes of Copper conductor power cablesincluding earthing with tray including fixing clamps & effecting proper termination to equipmentetc.complete as required.

a 4C x 16 Sq. mm ( Armoured ) RMT 150b 4C x 10 Sq. mm RM 80

CABLE JOINTING & END TERMINATION

55Supplying and making end termination with brass compressiongland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPEaluminium conductor cable of 1.1 KV grade as required.

a 3½ X 25 sq. mm (28mm) Each 12b 4 X 16 sq. mm (28mm) Each 40d 3½ X 400 sq. mm (82mm) Each 8

56Supplying and making outdoor end termination with cast resin compound including aluminium lugs andother jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminiumconductor cable of 1.1 KV grade as required.

a 3½ X 185 sq. mm (57mm) Each 4d 3½ X 400 sq. mm Each 4

57 MS perforated cable tray painted with powder coating 300 X 50 X 1.6 mm Metre 100Earthing

87 of 88

Page 89: Price Bid/ BOQ - Vol-III is replaced with Revised Price ...engineeringprojects.com/Tender/UploadFiles/3087_Addendum-4.pdfSub: Tender for CONSTRUCTION OF TYPE-IV, TYPE-V & CLUB HOUSE

SL. NO DESCRIPTION UNIT QTY RATE SUPPLY (75%) INSTALLATION (25%)

TOTAL AMOUNT

1 2 3 4 5.00 6 = 5 x 4x 0.75 7 = 5 x 4 x 0.25 9 = 6 + 7

58

Maintenance free Gel Earthing with Pipe in pipe / Pipe in strip technology filled with anti corrosiveconductive compound ( CPRI Tested ) below the ground in 150 - 200 mm dia. earth pit & surrounding filledwith required mineral filling compound ( MFC should have hygroscopic property to retain the moisture forlong time to create low resistance zone ) and C.C. finished chamber covered with hinged type withlocking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete testing of earth resistanceas required. of following sizes.With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating

a GI pipe 3000 mm long, 50 / 25mm, Terminal 14 mm GI Strip Sets 2

59 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosurewith cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. Each 4

60Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonryenclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but withoutcharcoal/ coke and salt ) as required.

Each 4

61 Providing and fixing 50mm x 6mm G.I. Strip in 80mm dia. heavy duty PVC Pipe in ground level upto earthelectrode, as required RM 50

62 Providing and erecting HOT Deep Galvanised Strip iron wire 8 to 16 S.W.G. Kg. 15063 Providing and erecting Annealed bare Copper wire 8 to 16 S.W.G. Kg. 20

64

Mains with ISI marked, 1.5KV grade electrolyte standard, annealed copper conductor with 105 C heatresistant PVC insulated conform to IS 964, IEC-227 erected in existing pipe of following size(Specifically for control panel, relays, power switchgears, motor starter & control wiring) with requiredsize of copper lugs, nuts and bolts if required.k) One wire 70.00 sq. mm.

Metre 20

65

Mains with ISI marked, 1.5KV grade electrolyte standard, annealed copper conductor with 105 C heatresistant PVC insulated conform to IS 964, IEC-227 erected in existing pipe of following size(Specifically for control panel, relays, power switchgears, motor starter & control wiring) with requiredsize of copper lugs, nuts and bolts if required.

Metre 20

66Providing and fixing of 20mm dia., 300mm long G.I. Rod lightning conductor final having single prongat top, with 150mm dia. 6mm thick G.I. base plate including holes etc. complete with all hardwares asrequired for fixing.

Each 2

67 Providing and fixing 25 mm x 3mm GI Strip on parapet or surface of wall for lightning conductor asrequired. (for horizontal run). Metre 2

68 Providing and fixing G.I. tape 25 x 3mm thick on surface of wall for lightning conductor as required. (Forvertical run). Metre 50

69 Providing and fixing of 25mm x 3mm thick G.I. strip, 125mm long test joint with G.I. bolts, nuts,check nuts and spring washers etc. complete as required. Sets 5

70 Providing and laying 25mm x 6mm G.I. strip for earth grid & from test joint to grid. Metre 50

88 of 88