principles of smoke management - printed

Upload: chidi-henry

Post on 02-Jun-2018

255 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/10/2019 Principles of Smoke Management - Printed

    1/383

    PRINCIPLESOF SMOKEMANAGEMENT

  • 8/10/2019 Principles of Smoke Management - Printed

    2/383

    This publicationwas made possible by funds from ASHRAE research.

    Principles of Smoke Managementby John and James Milke is an exhaustive treatment of man-

    agement, including pressurized stairwells, pressurized elevators, zoned smoke control, and smoke manage-

    ment in atria and other large spaces. Recent advancements include heat release rate, toxicity ofnatural atrium venting, minimum depth of an atrium smoke layer, smoke stratification,

    detection, tenability systems, and computer analysis. The book includes numerous example calculations.

    Methods of analysis include equations, network flow models, zone fire models, scale and hazard

    analysis. Computational fluid dynamics (CFD) is also addressed. The book includes a CD of computer soft-

    ware for of smoke management systems.

    This publication was prepared under ASHRAE Research Project

    Cognizant TC: TC5.6, Fire and Control.

    ABOUT THE AUTHORS

    John H. P.E., Fellow ASHRAE, is a consulting engineer specializing in the design and

    review of smoke management systems, as well as code consulting and teaching private management

    courses. He conducted research for 19 years at the National Institute of Standards and Technology (NIST)

    and has published over 80 papers and articles on smoke management and other aspects of fire protection.

    Dr. Klote headed the Building Fire Physics Group at NIST, which conducted research in smoke

    ment in buildings. The tools used for this research included full-scale fire experiments, scale fire

    experiments, network airflow models, zone fire models, and computational fluid dynamics (CFD).

    acted as a consultant in the area of smoke movement for the investigations of the MGM Grand fire and the

    First Interstate Bank fire. research was the basis of the 1997 revision to the NFPA Life Safety Code

    (section allowing elevators to be used as a second means of egress from towers.

    In he e arned a Doctor of S cience degree in mechanical from George W ashington Uni-versity. He is a member of the National Fire Protection Association (NFPA). a fellow of SFPE, and a fellow

    of ASHRAE. He has extensive participation in ASHRAE and NFPA committees, including being a past

    of ASHRAETC Fire and SmokeControl. Dr. is a registered professionalengineer in the

    District of Columbia, North Carolina, California, and Delaware.

    James A. is an associate professor and chair of the Department of Fire Protec-

    tion Engineering at the University of Maryland. Dr. has been a member of thefaculty and staff of the

    department since 1977. He received his in aerospace engineering from the University of Maryland,

    with an in structures. He received an M.S. degree in mechanicalengineering and a B.S. degreei n

    fire protection engineering, both from the University of Maryland. In addition. he has a B.S. degreei n phys-

    ics from College.

    Dr. has served as a research fire prevention engineer at the Building and Fire Research Labora-

    tory, National Institute of Standards and Technology, as the fire protection engineer for County, Vir-

    ginia, and consultant to numerous organizations. Dr. Milke is a fellow of theSFPE and is a of the National Fire Protection Association. the International Association of Fire Safety Science. and the Amer-

    ican Society of Civil Engineers. He is the chairman of the NFPA Technical Committee on Smoke Manage-

    ment and the ASCWSFPE committee on Structural Design for Fire Conditions. He on the

    Fire Council of Underwriters Laboratories.

  • 8/10/2019 Principles of Smoke Management - Printed

    3/383

    PRINCIPLES OF

    SMOKE

    MANAGEMENT

    JohnH.Klote

    JamesA.Milke

    American Society of Heating, Refrigerating

    and Air-conditioning Engineers, Inc.

    Society of Fire Protection Engineers

  • 8/10/2019 Principles of Smoke Management - Printed

    4/383

    ISBN 13-99-0

    American Society of Heating, Refrigerating

    and Air-conditioning Engineers, Inc.

    1791 Circle, N.E.Atlanta,GA 30329

    rights reserved.

    Printed in the United States of America

    ASHRAE has compiled this publication with care, but has not investigated, and ASHRAE expressly disclaims any duty

    to investigate, any product, service, process, procedure, design, or the like that may be described herein. The appearance'of any

    technical data or editorial material in .this publication does not endorsement, warranty, or guaranty byASHRAE of any

    product, service, process, procedure, design, or the like.ASHRAE not warrant that the information in the publication is free

    of errors, and ASHRAE does not necessarily agree with any statement or opinion in this publication. The entire risk of the use ofany information in this publication is assumed by the user.

    No part of this book may be reproduced without permission in writing fromASHRAE, except by a reviewerwho may brief

    or reproduce illustrations in a with appropriate nor may any part of this book be reproduced, stored in a

    retrieval system, or transmitted in any way or by any means--electronic.photocopying. recording, or other-without permission

    in writing fromASHRAE.

    ASHRAE STAFF

    Editor

    Howard

    Editor

    Christina

    Editorial Ass

    Barry Kurian

    Jayne

    Assistant

    PUBLISHER

    Cornstock

  • 8/10/2019 Principles of Smoke Management - Printed

    5/383

    DEDICATION

    This book is dedicated to the memory of George Tamura, who conducted pioneering research in smoke control atthe National Research Council of Canada.

  • 8/10/2019 Principles of Smoke Management - Printed

    6/383

  • 8/10/2019 Principles of Smoke Management - Printed

    7/383

    TABLE OF CONTENTS

    Chapter Page

    Preface ix

    Acknowledgments

    Chapter I-Introduction

    Chapter 2-Fire and Heat Release

    Chapter 3

    -

    Smoke and Tenability 27

    Chapter Analysis 49

    Chapter 5-Effective Areas and Smoke Movement 63

    Chapter of Smoke Management 87

    Chapter 7-Air Moving Equipment and Systems

    Chapter 119

    Chapter 9-Hazard Analysis 129

    Chapter 10

    -

    Stainvell Pressurization 139

    Chapter l-

    Elevator Smoke Control 157

    Chapter 12-Zoned Control 171

    Chapter 13-Fundamental Concepts for Atria 181

    Chapter 14-Atrium Systems 199

    Chapter 15-Physical 217

    Chapter 16-Computational Fluid Dynamics 225

    Chapter 17-Commissioning and Routine Testing 235

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nomenclature 243

    References 247

    A-Units of and Physical Data 259

  • 8/10/2019 Principles of Smoke Management - Printed

    8/383

    AppendixB-Bibliography 271

    Appendix of Elevator Evacuation Time 277

    Appendix D-Applicationof CONTAMW 289

    Appendix E-ASMET Documentation

    .................................Appendix F

    -

    ASET-C: A Room Fire Program for Personal Computers 329

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix G-Data and Computer Output for Stairwell Example

    . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix H-Data and Computer Output for Zoned Smoke Control Example 349

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix I-Inspection Procedures for Smoke Control Systems 355

    Appendix J-Test Procedures for Stairwell Pressurization Systems 361

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix K-Test Procedures for Zoned Smoke Control Systems 365

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix L-Inspection Procedures for Atria Smoke Exhaust 369

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix M-

    Test Procedures for Atria Smoke Exhaust Systems 371

    Index 373

  • 8/10/2019 Principles of Smoke Management - Printed

    9/383

    PREFACE

    In 1983, ASHRAE published Design of Smoke Control Systems for Buildings, written by myself and John

    This book was the first attempt to consolidate and present practical information about smoke control

    design. Judging by the many favorable comments and suggestions about this first book, I feel that it was a success.

    The first publication was limited to systems that control smoke by means of the physical mechanisms of pressuriza-

    tion and airflow.

    In 1992, ASHRAE and SFPE jointly publishedDesign of Smoke Management written by myself and

    James Milke. The term smoke management was used in the title of this publication to indicate that the physical mech-

    anisms were expanded from pressurization and airflow to include compartmentation, dilution, and buoyancy. Based

    on heightened about supplying combustion air to the fire, a caution was added about the use of airflow for

    smoke management.This new publication addresses the material of the two earlier books plus people movement in fire, hazard analy-

    sis, scale modeling, and computational fluid 'dynamics. In addition, the material about tenability and atrium smoke

    management has been extensively revised. As with the other books, this new book is primarily intended for designers,

    but it is expected that it will be of interestto other professionals (code researchers, etc.).

    This book and its predecessors are different from other design books in a number of respects. This book is writ-

    ten in both English units (also called for inch-pound) and units so that it can be used by a wide audience. To the

    extent practical, equations are accompanied by derivations and physical descriptions of the mechanisms involved.

    The physical descriptions are worked into the text as simple explanations of how particular mechanisms, processes,

    or events happen. The goal of the derivations and physical descriptions is to provide information and understanding

    so that readers can apply the material of this book in creative and insightful ways.

    As with the first two publications, I hope that this book is of value to the engineering community. Further, I

    invite readers to mail their suggestions and comments to me at the address below:

    JohnH. Klote, P.E.I I I I Street

    VA 22 l

  • 8/10/2019 Principles of Smoke Management - Printed

    10/383

    ACKNOWLEDGMENTS

    This project would not have been possible without the support of theAmericanSociety of Heating, Refrigerating

    and Air -conditioning Engineers (ASHRAE). Acknowledgment is made to the members of the ASHRAE Smoke

    Control Monitoring Committee for their generous support and constructive criticism. The members of this subcom-

    mittee are:

    A. Webb, Chairman (Performance Technology Consulting, Ltd., Lake Bluff,

    John A. Minn.)

    Dave Elovitz (Energy Economics, Inc., Natick, Mass.)

    Gary Lougheed (National Research Council Canada, Ottawa, Ontario)

    The support and advice of the staff of the Building and Fire Research Laboratory (BFRL) at the National Insti-tute of Standards and Technology (NIST) in Gaithersburg, Md., was invaluable. Particular appreciation is expressed

    to Richard Bukowski, Glen and Richard Peacock. Special thanks are due to Daniel Madrzykowski for his

    advice regarding oxygen consumption calorimetry and heat release rate. The authors are indebted to Kevin

    tan of BFRL for his valuable advice and constructive criticism regarding computational fluid dynamics.

    Richard Gann and Barbara Levin of and Braun of Hughes Associates, Baltimore, Md., provided valu-

    able information and insight concerning the evaluation of the effects of toxic exposures. Creg Beyler of Hughes

    Associates provided constructive criticism in a number of areas. Special thanks are due to Gary Lougheed for his con-

    criticism and for bodyof relevant research conducted by him and associates at the National Research

    Council of Canada.

    Students of fire engineering at the University of Maryland have provided insightful comments on

    drafts of several chapters of this book In particular, the students and Naviaser developed the

    information about CONTAMW that is included as Appendix D.

    content of book is heavily dependent upon work of researchers, design engineers, and other

    professionals around the world. So many of these people provided experimental research results, system con-cepts, and analytical methods that it is impossible to thank them all individually. Appreciation is expressed to all

    those have to advancement of smoke technology directly or indirectly by their con-

    tributions to fire science and fire protection engineering.

  • 8/10/2019 Principles of Smoke Management - Printed

    11/383

    CHAPTER1

    Introduction

    Smoke is recognized as the major killer in fire situa-

    tions. Smoke often migrates to building locationsremote from the fire space, threatening life and

    damaging property. Stairwells and elevator shafts

    quently become smoke-logged, thereby

    and inhibiting rescue and fire fighting. The MGM

    Grand Hotel fire (Best and Demers 1982) is an

    of the smoke problem. The fire was limited to the first

    floor, but smoke spread throughout the building. Some

    occupants on upper floors were exposed to smoke for

    hours before rescue. The death toll was 85, and the

    of the deaths were on floors far above the fire.

    23

    22

    2

    20

    17

    MGM Grand HotelFireLas Vegas, NVNov 21,1980

    Note: Renumberedfor

    The MGM Grand is not unique in this respect, a s is

    illustrated by the fires at the Roosevelt Hotel1964) and Johnson City Retirement (Steckler et

    al. 1990). All of these fires were located on the first

    floor, but the majority of deaths were on upper floors

    (Figure l).'

    During the intensive activity of fire fighting andrescue, the locations of some of the bodies are notrecorded. Thus Figure 1. 1 is limited to the deaths forwhich the locations were known.

    Retirement8 Fire

    L7 Johnson City. TNDec 24,1989

    2

    I

    0 1 2 3

    Deaths

    2

    I

    0 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8

    Deaths 0 1 2 3 4 5 6 7 8

    Deaths

    Figure I.I Deaths for fires was

  • 8/10/2019 Principles of Smoke Management - Printed

    12/383

    Chapterl-Introduction

    Figure Floor plan of Health Care Test the Annex.

    The general public is unaware of how fast a fire can

    grow and of how much smoke can be produced by a fire.

    This unawareness extends to many designers and other

    related professionals. Because such an awareness i s nec-

    essary to the evaluation of design parameters for smokemanagement systems, the following example is pro-

    vided.

    This example is fire test N-54, performed at the

    Health Care Test Facility at the National Institute of

    Standards and Technology Annex in Gaithersburg, Md.

    For technical details of this unsprinklered fi re test, the

    reader is referred to a report by et al. 980). T he

    floor plan of the test facility is shown in Figure 1.2.

    In this test, various fabrics representing common

    clothing materials were hung on wire coat hangers and

    arranged loosely in a wooden wardrobe. A cardboard

    box containing crumpled newspaper was placed on the

    floor of the wardrobe. The test started when the crum-pled newspaper was ignited by a match. Following igni-

    tion, the left-hand door of the wardrobe was closed

    tightly while the right-hand door was partially open

    resulting in a 3 in. (76 mm) opening along the vertical

    edge of thedoor.

    At one second after ignition, no flame or smoke

    was visible. At 80 seconds, flames were visible flowing

    from the top of the wardrobe, a layer of smoke was cov-

    ering the ceiling of the burn room, and smoke had

    flowed into the corridor forming a one-foot-thick layer

    just below the corridor ceiling. At seconds, flames

    were flowing from the top two-thirds of the wardrobe

    opening, and the smoke flowing out of the burn roomdoorway had increased significantly. At seconds

    after ignition, flames were flowing from the entire open-

    ing of the wardrobe door, and the layer of smoke in the

    corridor and lobby had descended to approximately 4 ft

    (1.2 m) below the ceiling.

    Such very rapid fire growth and accompanying

    smoke production represent a real possibility in

    wardrobe fires and perhaps even closet fires. Many

    other fire scenarios are possible. For example, a latex or

    a polyurethane filled mattress ignited by an adjacentwastebasket fire would reach about the same stage of

    development in six minutes that wardrobe test N-54

    reached in two minutes.

    Full-scale fire tests by et al. (1997) and

    Lougheed et al. (2000, 2001) have shown that success-

    fully sprinklered fires can continue to bum and produce

    enormous amounts of dense buoyant smoke after sprin-

    kler activation. While it appears this smoke production

    is greatest for fires that are shielded from sprinkler

    spray, some unshielded fires still produced considerable

    amounts of buoyant smoke.

    The concept of smoke management has developed

    as a solution to the smoke migration Smoke

    movementcan be managed by use of one or more of the

    following mechanisms: compartmentation, dilution, air-

    flow, pressurization, or buoyancy. These

    are discussed in detail in Chapter 4. The use of pressur-

    ization produced by mechanical fans is referred to as

    controlby NFPA 92A (NFPA 2000). By this def-

    inition, stairwell pressurization (Chapter 7), elevator

    pressurization (Chapter and zoned smoke control

    (Chapter 9) are all types of smoke control systems.

    The primary emphasis of this book is on

    that cse pressurization produced by mechanical fans.

    The use of pressurization to control the flow of undes-

    ired airborne matter has been practiced for at least 50

    years. For example, it has been used in buildings, suchas experimental laboratories, where there is dangerof

    2. As discussed later in Design Con-siderations,"smoke management is only one of manytechniques available to protection engineers.

  • 8/10/2019 Principles of Smoke Management - Printed

    13/383

    Principlesof

    poison gas, flammable gas, or bacteriological material

    migrating one area to another; it has been used to

    control the entrance of contaminants where a dust-free

    environment is necessary; it has been used

    tion migration and contamination could occur; and it has

    been used hospitals to prevent the migration of bacte-

    ria to sterile areas. However, the use of airflow and pres-surization to control smoke flow from a building fire is a

    fairly recent adaptation.

    INTENT

    The primary intent of this book is to provide practi-

    cal state-of-the-art to engineers who have

    been charged with design of smoke management sys-

    tems. The book is also intended to provide information

    for the review of designs and development of codes and

    standards,. This chapter contains general background

    Chapter2 deals with fire development and

    the heat :release rate of fires. Chapter 3 discusses the

    nature including toxicity, heat exposure, andvisibility through smoke. Chapter 4 people

    movement during fire evacuation.

    methods are employed to minimize the possibility

    doors being proppedopen.

    While advances in tenability analysis have

    engineering analysis smoke feasible, these sys-

    tems are not included in this book. The idea of smoke

    shafts is that smoke flows up the shaft due to

    where the smoke flows away from the building, but the

    authors have concerns about the fundamental effective-

    ness of smoke shafts. Further, there seems to be little

    interest in smoke

    The stair systems known as towers

    are misnomers, in that there is nothing about them that

    ensures no smoke migration into stairs. Originally, these

    towers were separate from the building and were con-

    nected to it only by walkways open to the outside. Some

    versions of these towers used relatively small openings

    in exterior vestibule walls in place of the separate walk-

    ways. In the absence of an engineering analysis of these

    systems, it can only be stated that the benefits of these

    systems are questionable. For these reasons, separatedstair towers are not included in this book, and it is rec-

    ommended that the term towers not be

    Chapter 5 is devoted to smoke movement in build-

    and the individual driving forces of smoke move-

    ment are discussed in detail. Chapter 6 contains a EQUATIONS AN D UNITS

    discussion of topics that are essential forOF MEASUREMENT

    the design of systems to manage smoke movement. It

    discusses the mechanisms of compartmentation, dilu-

    tion, airflow, pressurization, and buoyancy, which are

    used by themselves or in combination to manage

    conditions in fire situations.

    Background information is provided about ducts,

    fans, fire dampers, smoke dampers, and fan-powered

    ventilation systems in Chapter 7. Chapter8 is a descrip-tion of the computer programs that are used for the anal-

    ysis of smoke management systems.

    Chapters 9 through 14 address hazard analysis,

    stairwell pressurization, elevator smoke control, zoned

    smoke and atrium smoke management. For

    applications for which these conventional methods are

    inappropriate, the methods of scale and

    putational'fluid dynamics (CFD) can be used (Chapters

    and 16). Chapter 17 addresses the important topic of

    commissioning and routine testing.

    It may be noted that pressurized corridors have

    been omitted. The presented in this book can

    Considering that this book is primarily intended for

    design, it seems most appropriate that units should be

    specified for every equation. However, the topic of

    smoke management is relatively new, and there is no

    test to refer to for the derivation of many of the equa-

    tions used. Further, it was desired that the text be in both

    Inch-Pound (IP) units and the International System

    units. It would be unacceptably to present

    derivations using both commonly used English units

    and units. The equations used for derivations are

    homogeneous, and they can be used with

    the system, the slug pound system, and the pound

    mass poundal system (Appendix A). These dimension-ally homogeneous equations are easily identified

    because no units are specified for them in the text.

    all of the equations the reader is to use

    for design analysis are given in both English and

    units. These equations are easily identified because the

    appropriate units for the equation are specifically indi-

    catedi n the text.

    applied to pressurized corridors in a manner similarto their application to other pressurization systems. The

    HISTORY OF SMOKE VENTING.

    concern with pressurized corridors is that if a fire room Smoke venting has been used extensively todoor is blocked open, the corridor pressurization system age smoke flow during fires. The acceptance of

    can force smoke into other rooms off the corridor. For such venting resulted from several major fires,

    this reason, pressurized corridors are not generally rec- including those at the Brooklyn which killed

    except for applications where practical 283 in 1877; Vienna Ring which killed 449

  • 8/10/2019 Principles of Smoke Management - Printed

    14/383

    Chapter l

    AreAreas2 and4on 10 Tower

    I I

    ........................3 on................ Floor....................................

    Figure1.3 Typical floor plan of the office at

    30Church Street.

    in 1881; the Royal, which killed 186 in 1887;

    and the Iroquois which killed 571 in All

    of these fires started on the stage and resulted inmajor loss of life in the audience. The Palace fire

    in Edinburgh in 1911 was an exception. In this fire,

    smoke venting through the stage roof was credited for

    helping to prevent any loss of life. The buoyancy of the

    hot smoke forced the smoke flow through the vent open-

    ings, and this venting is called natural venting or gravity

    venting.

    Over the past few decades, fan-powered smoke

    exhaust has become the standard for almost all atria in

    North America. In other areas, such as Europe, Austra-

    lia, and New Zealand, both natural venting systems and

    fan-powered exhaust systems have become for

    atria. Modem atria smoke management designs are

    based on engineering analysis developed over the last

    few decades. These analytical methods are primarily

    based on research in smoke plumes fire model-

    ing. Information about these analytical methods is pro-

    vided in Chapters and 14.

    HISTORY OF PRESSURIZATIONSMOKE CONTROL

    The idea of smoke protection by pressurization sys-

    tems is restrict the movement of smoke a build-

    ing fire. To study the effectiveness of pressurization

    smoke control, the Brooklyn Polytechnic Institute con-ducted a series of fire experiments at a 22-story office

    building at 30 Church street in New YorkCityThis building was scheduled for demolition.

    Materials representative of fuels that would be in an

    were burned on floors 7 and 10, as shown in Fig-

    ure 1.3. This project demonstrated that pressurization

    could provide "smoke free" exits during large unsprin-

    Experimental Tower

    34 LobbySupply

    Figure 1.4Typicalfloor plan of NRCCexper-hen-

    klered fires. The term"smoke free" is used to mean

    essentially free of smoke, with the possibility of such

    insignificant amounts ofcombustion products that tena-bility is maintained.

    Other full-scale fire tests also demonstrated thatpressurization could provide "smoke free" exits during

    large unsprinklered fires (Koplon

    Butcher et al. 1976). Cresci (1973) describes visualiza-

    tion experiments using a model of the stair shaft at the

    Church Street building, where stationary vortices

    observed at open doonvays. These vortices are the rea-

    son that the flow coefficient through an open

    door is about half of i t be otherwise. This

    significant effect on airflow is discussed in Chapter

    The Research Tower near Ottawa (Figure 1.4) was

    used for a joint National Instituteof Standards and Tech-

    nology (NIST) and National Research Council Canada(NRCC) study of elevator smoke control. Again, i t was

    demonstrated that pressurization could control smoke

    from large unsprinklered fires (Tamura and Klote

    1988; Klote and Tamura 1987).

    In the spring of 1989, NIST conducted a series ofexperiments of zoned smoke control at the Plaza Hotel

    in Washington as shown in Figure 1.5 (Klote

    1990). A zoned smoke control is a system that

    uses pressurization to restrict migration to the

    zone of fire origin. Once again, it was demonstrated that

    pressurization could control smoke from unsprin-

    klered fires.

    An analysis based on first principles of engineering

    was made of the pressure differences produced thesmoke during the fires at the Plaza Hotel.As is done with zone fire modeling, the pressures

    rooms were considered hydrostatic. The general trendsof calculated values were i n agreement with thesurements (Figure and this indicates a of

  • 8/10/2019 Principles of Smoke Management - Printed

    15/383

    Principles of Smoke Management

    applicability o f z one fire for analysis o f pres-surization smoke control systems.

    OBJECTIVES O FSMOKE MANAGEMENT

    Some objectives of a smoke management system

    are to reduce deaths and injuries from smoke, reduce

    property loss from smoke damage, and to aid firefight-ers. Many designers feel that life safety is the primary

    objective of smoke management; however, systemshave been built with the primary objective of protecting

    property--especially high-value equipment. Regardlessof the objective, the methods of design analysis pre-sented in book are applicable.

    Theoretically, a smoke management system can be

    designed to provide a safe escape route, a safe

    area,or both. However, a pressurization control)

    system can meet its objectives even if a small amount ofsmoke infiltrates protected areas. For this book, pressur-ization systems are designed on the basis that no smoke

    infiltration will occur. Hazard analysis (Chapter 9) can

    be used for the design of systems that maintain tenabil-ity even when people come into contact with some

    smoke.

    PERFORMANCE-BASEDDESIGN

    recent years, performance-based codes havebecome a topic of considerable attention. Traditional

    codes prescribe requirements, while performance-basedcodes require a level of performance. A

    based design is developed to meet the level of perfor-mance stipulated in the code.

    This book uses a performance-based approach,where the kind of performance is based on the type of

    system. Pressurization smoke control systems aredesigned to maintain specific levels of pressurization at

    barriers, such as partitions and closed doors. Atrium

    smoke exhausts often are designed to keep smoke

    descending below a specific level. Further, various

    of smoke management systems can be designed to

    maintain tenable conditions within specific spaces.

    PRELIMINARY DESIGNCONSIDERATIONS

    Smoke management should be viewed as only one

    part of the overall building fire protection systems. Two

    basic approaches to fire protection are to prevent fire

    ignition and to manage fire impact. Figure 1.7 shows a

    simplified decision tree for fire protection. The building

    occupants and managers have the role in pre-venting fire ignition. The building design team may

    incorporate features into the building to assist the occu-pants and managers in this effort. Because it is impossi-ble to prevent fire ignition completely, managing fire

    impact has assumed a significant role in fire protection

    design. Compartmentation, suppression, control of con-struction materials, exit systems, and smoke manage-ment are examples. The NFPA Fire Protection

    Handbook(NFPA SFPEHandbook of Fire Pro-

    tection Engineering (SFPE and NFPA 550(NFPA 1995) contain detailed about fire

    safety.

    S 20 25(minutes)

    (a)Pressure Difference Near Ceiling

    00 5 15 20 25 30

    lime (minutes)

    (b) Near Floor

    Figure 1.5 Figure 1.6 and

    Plaza Hotel

    tests.

  • 8/10/2019 Principles of Smoke Management - Printed

    16/383

    Chapter1

    Objectives

    Ignition Impact

    Heat-Energy Source-FuelThreat' Exposure'

    Sources Interactions

    'Note: Smoke managementis one of many fireprotectiontools that can beusedto help manage the threat of fire and manage the exposure of fire.

    1.7 decisiontree.

    Many factors will affect the design of a man-

    agement system. Before the actual mechanical design of

    the system can proceed, the potential constraints on the

    system should be determined and the design criteria

    established. This section introduces some considerations

    peculiar to smoke management system design, some of

    which are merely listed below, since detailed discussion

    is beyond the scope of this book. However. published

    works on some of these subjects are cited in the bibliog-

    raphy in AppendixB.

    Occupancy type and characteristics

    Evacuation plan

    Refuge areas

    Distribution of occupant density

    Human life support requirements

    Form of detection and alarm

    Fire service response-to-alarm

    Fire suppression system characteristics

    Type of heating, ventilating, and air-conditioning

    (HVAC) system

    Energy

    Building security provisions

    Controls

    Status of doors during potential fire condition

    Potential threatsInternal compartmentation and charac-

    teristics

    leakage

    Exterior

    Wind

    FLEXIBILITY AN D RESILIENCY

    To help ensure smoke management system perfor-

    mance, the approaches of flexibility and resiliency can

    be employed. The concept of flexibility consists of

    using design features that allow for easy adjustment of a

    smoke management system in order to achieve accept-

    able performance. A resilient system is one that resists

    serious adverse effects due to pressure fluctuations.

    During the design of a new building, the leakage

    paths throughout the building can only be estimated.

    Therefore, the smoke management design calculations

    constitute only an approximate representation of the

    pressures and airflows that will occur as a result of the

    smoke management system in the actual building. The

    introduction of flexibility into a smoke management

    system allows for variations in leakage from the origi-

    nally estimated values. Because it is to measure

    leakage paths in existing buildings, the concept of flexi-

    bility is also useful for retrofit of smoke management i n

    existing buildings. In many systems, flexibility can be

    achieved by the use of fans with sheaves3 to allow sev-

    eral flow rates, a variable flow fan for the same purpose,

    or by dampers that can be manually adjusted to obtain

    desired pressure differences.

    Pressure fluctuations often occur during a fire when

    doors are opened and closed and when windows are

    opened, closed, or broken. To resist such fluctuations,

    resiliency can, be incorporated in a system by use of

    A sheave is with aa By exchanging a sheave for

    of rotational of the fan

    and its flow changed.

  • 8/10/2019 Principles of Smoke Management - Printed

    17/383

    Principles of Smoke

    automatic control to reduce the pressure fluctuations.

    For example, in pressurized stairwells, automatic con-

    trol can be used in the supply fan bypass system to

    reduce the effect of opening and closing stairwell doors.

    An alternative keep the exterior stairwell door open

    during pressurization. This eliminates what is probably

    the major source of fluctuations; that the opening and

    closing of the exterior stairwell door. The concepts of

    flexibility and resiliency are discussed further where

    they apply to specific smoke management applications.

    SAFETY FACT R S

    Smoke management is still a relatively new field,

    and it should come as no surprise that there is no -

    sensus concerning safety factors, which are commonly

    used in many branches of engineering to provide a level

    of assurance of system performance. Further, the topic

    of factors has attracted little attention in smoke

    control design.

    Safety factors for sizing fans of pressurization sys-

    tems are very different from those intended to maintaina tenable environment in an atrium or other application

    based on a hazard analysis. If a pressurization fan is

    undersized, it will not maintain acceptable pressure dif-

    ferences. This should be apparent and corrected during

    commissioning.

    Ideally, an analysis of a system intended to maintain

    a tenable environment would be based on detailed and

    accurate capabilities of simulating smoke transport,

    physiological effects of fire-related exposures, human

    response to fire, and evacuation analysis. However, this

    technology is not so advanced, and these calculations

    are of necessity based on a number of conservative

    assumptions with conservativedesign parameters. It can

    be argued that such conservative calculations may resultin conservative designs even in the absence of any

    safety factors. The specifics of the design and the meth-

    of analysis would be expected to have a significant

    impact on any approach to safety factors.

    of the absence of any accepted approaches

    to safety factors, this topic is not included in the meth-

    ods of analysis of this book.

    FIRE SUPPRESSIONSYSTEMS

    Automatic suppression systems are an integral part

    of many fire protection designs, and the efficacy of such

    systems in controlling building fires is well docu-

    mented. However, it is important to recognize that whilethe functions of fire suppression and smoke manage-

    ment are both desirable fire safety features, they should

    not be readily substituted for each other. One of the best

    ways to deal with the smoke problem is to stop smoke

    production. To the extent that a suppression system

    slows down the burning rate, it reduces the smoke prob-

    lem. From fires that are suppressed rather than extin-

    guished, smoke is produced. This smoke can move

    through the building due to various driving forces dis-

    cussed in Chapter5. the other hand, well-designed

    smoke management systems can maintain tolerable con-

    ditions along critical egress routes but will have littleeffect on the fire.

    In addition to the fact that the systems dif -

    ferent functions, it is important that the designer con-

    sider the interaction between smoke management and

    fire suppression. For example, in the case of a

    sprinklered building, the pressure difference needed to

    control smoke movement is probably less than in an

    unsprinklered building, due to the likelihood that the

    maximum fire size will be significantly smaller than in

    an unsprinklered building.

    A pressurization (smoke control) system can

    adversely affect performance of a gaseous agent (such

    as halon, or suppression system when the sys-tems are located in a common space. In the event that

    both systems are activated concurrently, the smoke

    exhaust system may exhaust the suppressant gas from

    the room, replacing it with outside air. Because gas sup-

    pression systems commonly provide a single application

    of the agent, the potential arises for renewed growth of

    the fire.

    A general guideline would be that the gaseous agent

    suppression system should take precedence over the

    smoke control system. An extremely desirable feature in

    such spaces would be the ability to purge the residual

    smoke and the suppressant gas after the fire is com-

    pletely extinguished and to replace them with fresh air.This ability to replace the atmosphere in these spaces in

    the post-fire period is very important from a life-safety

    viewpoint, since some gas suppressants are asphyxiants

    at normal design concentrations.

    ENERGY CONSERVATION

    The smoke management system must be designed

    to override the local controls in a variable air volume

    HVAC system so that the air supply necessary to pres-

    surize spaces is supplied. Also, if there is an

    energy management system or a 24-hour clock

    the designer must ensure that the smoke management

    system will take precedence over the local control sys-tem so that the necessary air is supplied or exhausted

    according to the design approach. It is a good general

    rule that smoke management should take precedence

    over energy conservation features in both new designs

    and retrofits.

  • 8/10/2019 Principles of Smoke Management - Printed

    18/383

    Chapterl-Introduction

    SYSTEM ACTIVATION

    System activationisprobably the major area of dis-agreement in the field of smoke control. Primarily, this

    disagreement is about automatic activation versus man-

    ual activation. In the early days of smoke control, there

    was general agreement that activationof"pressure sand-wich" systems should be automatic upon alarm from

    smoke detectors. Automatic activation by smoke detec-tors located in building spaces has the clear advantage

    of fast response.

    Some building designers and fire service officials

    began to realize that smoke detectors could go into

    alarm on a floor far away the fire. Thus, automatic

    activation by smoke detectors could result in pressuriza-tion of the zone in which the fire occurred. This would

    result in the opposite of the desired operation; that is,

    smoke would be forced into other zones. As a result, a

    vocal minority of feel that smoke control

    should only be activated manually by fire fighters after

    they are sure of the fire location. However, many

    involved professionals are concerned that such manualactivation could be so late in the fire development that

    significant hazard to life and damage to property would

    result. Such delayed activation can suddenly transport a

    body of smoke that is highly charged with unbumed

    hydrocarbons, carbon monoxide, and other toxic gases

    and depleted of oxygen to remote locations. This can

    result in a wave-like movement of toxic gases or flame

    to remote areas.

    The most recent view on the subject is that zoned

    smoke control should be automatically activated by an

    from either heat detectors or sprinkler water flow.

    This can only be accomplished if the detector or sprin-

    kler zones are compatible with the smoke control zones.

    Using heat detector or sprinkler flow signals for activa-tion increases the likelihood of proper identification of

    the fire zone. For smoldering fires, this approach would

    result in a significantly longer response time, and smoke

    detectors would probably be better suited for applica-

    tions where smoldering fires are of particular

    However, for flaming fires, it is believed that the

    response time with this approach would be short enough

    so that significant benefit would be realized by the oper-

    ation of the smoke control system. It is hoped that

    advances in smoke detector technology and application

    will significantly improve the ability of these detectors

    to positively identify the fire zone.

    Throughout all of this controversy, there has been

    complete agreement that zoned smoke control should

    not be activated by from manual stations (pull

    boxes). The reason can be illustrated by the scenario ofa

    man who, while observing a fire on an upper floor of a

    building, decides that the first thing he should do is to

    get out of the building. On the way down the stairs, he

    thinks of his responsibility to the other occupants. He

    stops on a lower floor long enough to actuate a manual

    station. If that alarm activated thesmoke control system,

    the wrong zone would be identifiedas the fire zone.

    Because of the long response time and the mainte-

    nance problem of clogging with airborne particles, it is

    generally agreed that smoke detectors located in HVACducts should not be the primary means of smoke control

    system activation. A means of activationof higher

    ability and quicker response time is needed. However,

    an alarm from a duct-located detector can be used in

    addition to such a primary means of activation. A signal

    only this secondary means might be unusual, but it

    should be able to activate the smoke control system.

    Most stairwell pressurization systems operate in the

    same manner regardless of where the fire is located.

    Therefore, it generally is agreed that most stairwell pres-

    surization systems can be activated by the alarm of any

    fire alarm-initiating device located within the building.A possible exception to this is large buildings with hori-

    zontal separations, such that smoke is not expected tohave an impact on some stairwells remote from the fire.

    It is recommended that zoned smoke control sys-

    tems be equipped with a remote control from

    which the smoke control system can be manually over-ridden. This should be easily identifiable and

    accessible to the fire department. Such a remote control

    allows fire fighters to change the mode of smoke

    control system operation in addition to system shut-down. Activation of smoke management systems for

    atria and other large spaces is addressed in Chapter

    RELIABILITY OF SMOKE MANAGEMENT

    The intent of this section is to provide insight intothe need for acceptance testing and routine testing and

    the relative importance of system simplicity: The fol-

    lowing should not be thought of as an exhaustive treat-ment of smoke management reliability. Due to the

    of obtaining data about the reliability of com-ponents of smoke management systems, the simple cal-

    culations that follow are only very rough estimates.

    However, it is believed that the insight gained justifies

    this treatment despite these limitations. Further, the

    same reliability concerns that apply to smoke manage-

    ment systems apply to all life safety systems, and the

    following discussion may be of general interest beycnd

    smoke management.

    The discussion is limited to series systems, which

    are systems that operate only if all the components oper-ate, as is true of many smoke management system

    designs. Redundancies (such as backup power) are not

    included in this analysis. The reliability, R, a series

  • 8/10/2019 Principles of Smoke Management - Printed

    19/383

    Principles ofSmoke Management'

    Table1.1:

    EstimatedSystem Reliabilityfor NewSmokeManagement

    SystemThat Has Not Been Commissioned

    No. of HVAC No. of Other of

    System System Fans Components Before Commissioning System (months)

    1 0 0.97 162 0 3 0.83 46

    3 3 9 0.56 14

    4 5 18 0.31 8

    5 5 54 0.03 3

    1. Systemreliabilities calculated Equation For purposesof these calculations, the of fansof a forced airHVAC system weretaken as 0.99, andother components were taken as 0.94.

    2. Mean lives calculatedfrom Equation(1.3). For purposesof thesecalculations. the failure rates of fans of a forcedairHVAC system were takenas

    per hour, and other components were taken as per hour.

    system is the product of the of

    ponents.

    Usually, discussions of reliability progress from this point

    with the assumption that all components operate initially

    and that failures occur with time after system installation.

    For this assumption to be appropriate, a program of accep-

    tance testing and defect correction is necessary. Such com-

    missioning must include an installation check of all

    components, tests of system during all modes

    of operation, repairof defects, and retestinguntil all defects

    are corrected. Current construction practices are such that

    system commissioning is not always this exhaustive. For

    this reason, attention is first given to reliability of systems

    without commissioning followed by a discussion of reli-

    ability of systems for which all components operate after

    commissioning.

    RELIABILITY BEFORECOMMISSIONING

    For newly installed components, the reliability can

    be thought of as the likelihood that the component will

    both be installed properly and be in good working con-

    dition when it is delivered to the construction site. There

    are an enormous number of errors that can occur during

    manufacture, transportation, storage, and installation

    that can cause a component to fail to operate.

    such as motors wired for the wrong voltage, not

    connected to power, dampers failing to close, fans run-

    ning backward, holes i n walls, and automatic doors fail-

    ing to close have been observed in newly built smoke

    management systems. Based on experience

    testing of smoke management systems, it is estimated

    that the reliability of components i n noncommissioned

    systems is0.90 or An consideration

    regarding the of a component in a

    missioned system is if that component is part of an

    HVAC system. In hot or cold weather, building occu-

    pants demand that the HVAC system provide comfort

    conditions. Thus, for a new building in extreme weather,

    it can be considered that the reliability of the HVAC sys-tem fan will approach unity. Based on field observa-

    tions, it is believed that other components will have a

    lower reliability. The following reliabilities were chosen

    for example calculations for new systems that have not

    been commissioned:

    Fans of a forced air HVACsystem 0.99

    Other components 0.94

    These values were arbitrarily selected, but the rela-

    tive values between them are based on the discussion

    above. Table I . lists calculated reliabilities of such sys-

    tems made up of many components. It can be observed

    from this table that the more components a system has,the less likely the system is to operate before it has been

    commissioned. The most reliable new system would be

    one that only uses the HVAC system fans. A large com-

    plicated system consisting of many components (Table

    1.1, system 5) has very little chance of operating before

    commissioning. The trend of lower reliability for com-

    plicated systems agrees with observations of the author

    during field tests of systems of various

    degrees of complexity. Probably the most important

    point to be made from this discussion is the need for

    commissioning of new systems.

    MEAN LIFE OF COMMISSIONED SYSTEMS

    For this discussion, all system components are con-

    sidered to operate-at the end of the commissioning pro-

    cess. A commonly used relation for the reliability of

    components is the distribution,

    = .

  • 8/10/2019 Principles of Smoke Management - Printed

    20/383

    Chapterl-Introduction

    I I " ICircuit Breakers

    IMechanical

    Large

    IEq

    Figure 1.8 Typical ranges rates Lees[ I

    where is the failure rate of the component. The mean

    life, L, of a system is

    Some typical ranges of failure rates of some

    ponents and systems are shown in Figure It can be

    seen that failure rates vary over large ranges and that

    failure rates vary considerably with equipment type. It

    seems that the failure rate of HVAC system fans would

    be lower than those of other components. If these fans

    fail, building desiring heating o r cooling tend

    to put pressure on maintenance personnel to get fans

    repaired quickly. Smoke management systems are only

    needed for a short time over the life of a building. Thus,

    when an HVAC system fan is called for smoke

    management duty, it seems that it will be more likely to

    operate than other components. To account for this, the

    effective failure rate of HVAC system fans can be

    thought of as being much smaller than other compo-

    nents. The following failure rates were arbitrarily

    selected for example calculations, but their relative val-

    ues are based on the above discussion:

    Fans of a forced air I-[VAC system per hr

    Other components per hr

    Table 1. 1 shows mean lives of systems composed of

    various numbers of components. It can be observed that

    systems composed of a fewcomponents have long

    lives, while those made up of very components

    have short lives. This tends to support the view that sim-

    ple systems are more reliable, and this view is supported

    by in the field. However, it should be cau-tioned that systems should not be overly simple; that is,

    they should have the features needed to achieve desired

    performance at likely conditions during a fire. Further,

    the above simple analysis did not include the beneficial

    effects of redundancies. However, it is safe to conclude

    that unnecessary system complexities should be

    avoided. The mean lives listed in Table also indicate

    that routine testing and repair of smoke management

    is needed so that the systems will probably be

    in good working order when they are needed. A similar

    statement can be made concerning all life safety sys-

    tems.

  • 8/10/2019 Principles of Smoke Management - Printed

    21/383

    CHAPTER2

    Fire and Heat Release

    Probably the most important aspect of a building quences of a fireafter ignition but not with the causes of

    fire is the heat release rate (HRR). The tempera- Ignition.

    ture and amount of gases produced by a fire are Growth: After ignition, fire growth is determinedthe burning, with influence from

    models use the HRR as input. When characterized by an

    of air for the fire. Figure 2.2 shows an officefire starting in a corner of an upholstered chair andabout the size of a fire or how big a fire is, they almost

    always are referring to the HRR. Other indicators of fire

    size are the fire area and fire perimeter, but neither of

    these is commonly used to depict how big a fire is in the

    predictive models that have gained a high level of

    acceptance in recent years. For these reasons, the term

    size is used in this book to HRR.

    The intent of this chapter is to provide basic

    i about fire size and development that should be

    helpful concerning evaluation and ofI design fires. A design fire is the challenge that a smoke

    management system is designed to withstand. Because

    the presence of sprinklers often plays a role in the

    mination of a design fire, sprinklers are also included.

    The design fire can be a steady fire or an unsteady one.

    While the steady fire is not physically realistic, it can

    result in very conservative designs and it can simplify

    design analysis.

    STAGES OF FIRE DEVELOPMENT

    Fires in rooms or other compartments are oftendescribed in terms of the stages of fire development,

    shown in Figure 2.1. These stages are useful in discuss-

    ing fires, but many fires do not go through all of thesestages due to lack of fuel or the action of a suppression

    system.

    Ignition: Ignition is the period during which thefire begins. management deals with the

    growing until it spreads to other objects. As the firegrows, the temperature in the room rises. A fire with

    sufficient combustion air is called a fuel fire,and such a fire is also referred to as burning a ir .

    Flashover: In engineering, most processes of inter-est consist of gradual changes, but flashover is an excep-tion. is a sudden change from an apparentsteady fire confined to a relatively small space to a fire

    that involves a much larger space, such as the entireroom.For the office fire of Figure (c), materials

    throughout the room are subject to thermal radiation

    from the Flames and the smoke layer under the ceiling.When this radiation is sufficiently high, some of thesematerials ignite. This is followed by other materials

    I I I

    I Post FlashoverI II I

    I II I

    Dewy

    Time

    Figure

  • 8/10/2019 Principles of Smoke Management - Printed

    22/383

    Chapter2-Fire and Heat Release

    (a)Fire restricted to inside corner of chair and resulting in smoke layer under ceiling

  • 8/10/2019 Principles of Smoke Management - Printed

    23/383

    Principles of Smoke Management

    Table 2.1:ApproximateValues of CO

    Yield for Room

    CO

    Flamingfires in"free air" 0.04

    Fully involved fire (in a roomwithout 0.2materialson ceiling or upper portionof walls)***

    These estimates are based onand (2002).

    is in CO produced per of fuel burned (org ofCO

    produced pergof fuel burned).Fully involvedfires in rooms withcellulosic materials (wood,paper, cardboard, etc.)on ceilingor upper of wallsareexpected to have COyieldsseveraltimes higher

    igniting, and then the entire room is involved in fire.Once a fire gets to the stage depicted in Figure 2.2 (c), itonly takes a few seconds for a room to flashover.

    In a very large room, such as an open floor

    plan, only a portion of the room may flashover. The

    smoke layer temperature at which flashover occurs is

    generally in the range of 930F to 1300F (500C to700C). The criteria for flashover is sometimes taken to

    be a smoke layer temperature of (600C) or a

    radiant heat flux of 1.8 (20 at the floor

    of the fire (Peacock et al. 1999).

    Fully Developed Fire: This stage of fire develop-

    ment has the highest temperatures. For small and

    medium rooms, the HRR of a fully developed fire

    depends on the amount of air that reaches the fire. Such

    a fully developed fire is ventilation

    In a ventilation controlled fire, more volatile gases

    are produced by the burning materials than can be

    bumed in the room with the oxygen available, and the

    fire can be characterized by flames consisting of burn-ing volatile gases extending from open doonvays of the

    fire room. For very rooms, as in an open office

    floor plan, the fire may not ever become ventilation con-

    trolled. Fully developed fires are characterized by

    cient combustion and high production of CO (Table

    2.1).

    Decay: As the fuel is consumed, the HRR of the

    fire and the temperature of the room drop. The fire may

    change from ventilation controlled to fuel controlled.

    Strictly speaking, the term post-flashover

    includes both fully developed and decay stages, but the

    is often used to mean a fully developed fire.

    MEASUREMENTOFHEAT RELEASE RATEIn the early days of fire research, of

    the HRR during a fire was very crude. Typically, materi-

    als were burned on a load cell (scale), and the HRR was

    estimated from the mass loss and the heat of combustion

    of the material. If the load cell became too hot, mass

    MeasureTemperature,Flow Rate, GasConcentrations.

    Figure2.3 Open air calorimeter:

    measurements would be meaningless. Various schemes .

    to keep the load cell from heating up were devised, but

    they all interfered to some extent with the measure-

    ments. The situation was even worse when pieces of

    burning material would fall from the load cell.To further exacerbate the difficulties with such

    HRR determinations, many items burned are composites

    of several different materials, each with its own heat of

    combustion. For example, a desk might be made of

    wood, fiberboard, sheet plastic and molded plastic

    doors, and drawer fronts. Not only do these materials

    have different heats of combustion, but they burn at dif-

    ferent times during the course of a fire. For these rea-

    sons, an HRR estimated from measured mass losses is

    often unreliable.

    Oxygen Consumption

    In the fire research laboratories around theworld worked to develop a method of calorimetry that

    was not subject to the problems of the old method dis-

    cussed above. The new method is based on the osygen

    used upin the fire and is called

    (and sometimes depletion

    While oxygen consumption calorimeters often have

    load cells, the measurements from these cells are for

    information and not for calculation of the HRR.

    The key to this technology is that the heat released

    per unit oxygen consumed is almost a constant for most

    materials. Huggctt (1980) found that this heat release

    constant is 5,630 Btu per Ib of oxygen

    MJ per kg of oxygen consumed). For most materials

    involved in building fires, this constant has an uncer-tainty of about 6%.

    Figure 2.3 shows a calorimeter where furniture is

    burned under a hood connected to an exhaust, such that

    all the is drawn into the exhaust. From measure-

    ments of the mass flow of exhaust and the content of

  • 8/10/2019 Principles of Smoke Management - Printed

    24/383

    2- and Heat Release

    MeasureTemperature. Flow Rate,and GasConcentrations.

    SmokePlume

    Front View

    Figure2.4 Room calorimeter:

    the exhaust, the time rate of consumption can be cal-

    culated. From this, the HRRcan be calculated. Because

    some of the is not completely consumed, gas mea-

    surements also include CO and Parker (1982) pre-

    sents equations for calculation of the for various

    applications.

    consumption calorimeters are calibrated by

    burning a gaseous fuel (methane, propane, etc.) at a

    measured flow rate. The uncertainty of the calorimeter

    depends on the uncertainties of (1) the operation of the

    calorimeter, (2) the calorimeter calibration process, and

    (3) the heat release constant. Calorimeter operation is

    not always as intended. Some of the smoke may not be

    captured by the hood, or burning materials may fall off

    the fire and away from the calorimeter. With such unin-

    tended operation, uncertainties in excess of 20% could

    result. For a well-calibrated calorimeter operated as

    intended, the uncertainty of measured HRR may be in

    the neighborhood of 10%. For more information about

    the uncertainty of consumption calorimeters, see

    et al. (2000).

    Open air calorimeters (Figure 2.3) are sometimes

    called furniture calorimeters because theyare often used

    for furniture. However, they can be used for any fuel

    package provided that all of the smoke from the fire

    is collected, and (2) the heat released does not damage

    the calorimeter including the pollution control equip-

    ment. Typically, these calorimeters are located indoors

    to protect the fire from the wind. The hoods are usually

    to 20 (3 to G m) square, but the size is only con-

    strained by the practicalities of construction.Other types of consumption calorimeters are the

    room calorimeter and the cone calorimeter. The room

    calorimeter (Figure 2.4) is used when the effects of the

    walls and ceiling on the HRR are to be

    Section View

    Time

    Figure2.5 Three kiosk

    of materials (data

    [I

    cant. The cone calorimeter is a"bench scale" laboratoryinstrument developed at NIST (Babrauskas 1990).

    HRROF SOME OBJECTS

    When duplicate objects are burned, there are devia-

    tions in HRR as illustrated with the three kiosk fires of

    Figure 2.5. These kiosks are for selling T shirts. The

    deviations of HRR are due to a number of factors,

    including (I ) minor variationsi n arrangement of the T-

    shirts, (2) variations in composition of T-shirts, (3) vari-

    ations in the dimensions of the kiosk, (4) variations in

    materials of the kiosk, and (5) variations in the air cur-

    rents near the kiosk. However, the shapes and peak

    HRRs of kiosk curves are similar.

    Figures 2.6 to 2.19 show HRRs of other objects. The

    peak HRR of Scotch pine Christmas trees burned byStroupet al. (1999) were in the range of' to 5000

    (1900 to 5300 kW), as shown in Ahonen et

  • 8/10/2019 Principles of Smoke Management - Printed

    25/383

  • 8/10/2019 Principles of Smoke Management - Printed

    26/383

    Chapter2-Fire and Heat Release

    looc

    0360

    l ime

    Figure2.11 Upholstered chair with

    padding and weighing 25 (11.5 kg)

    (datafroni et

    00 300 600 900 1200 1500 1800

    lime

    Figure2.1 2 foam

    and 62 (28.3

    et al. 9841).

    Figure 2.13Sofa padding

    et al.

    Figure2.14 Metal wardrobe cotton

    (data al.

    Time(S)

    Figure Wardrobe of 0.5in. (12.7

    et al.

    8000

    Unfinished

    Fire Retardant 6000. Paint:

    4000 2Coats 4000

    KI

    2000

    ., .

    Figure2.16 of in.(3.2

    cotton

    et al.

  • 8/10/2019 Principles of Smoke Management - Printed

    27/383

    Principlesof Smoke Managemerit

    20 W

    15001500.

    m,I

    500 I

    500

    01200 1800 2400

    lime Time(min)

    Figure2.17Two-divider workstation with Figure2.19Automobiles(data from Joyeux

    tional desk and credenza (data from

    Madrzykowski and Vettori

    lime

    Figure2.18Three-divider with an open

    top and shelf (data from

    tion from other spaces. The workstation(Figure 2.17) has a peak HRR of 1700 (1800 kW)at The three-divider workstation (Figure 2.18) has

    a peak HRR of 6400 (6800 kW) at 550 A

    reason for the higher HRR of the three-sided

    tion is probably the increased radiation feedback from

    the additional divider and the shelves. For further infor-mation about the HRRs of workstations, readers arereferred to Madrzykowski

    Figure shows HRR data of automobiles mea-sured by Joyeux 997). Joyeux showed that cars made

    in the had a higher HRR than those made earlier,and this may be due to increased use of polymers and

    other materials.-Because of these higher

    HRRs, a car fire in a parking garage can ignite an adja-cent car.

    Cribs and piles of wood pallets are used in research

    and testing when reproducible solid fuel fires are needed(Figures 2.20 and 2.21). Cribs are geometrically

    arranged piles of sticks. The crib shown in Figure 2.20

    Figure2.20Crib of geometrically arranged

    was used for tests of the smoke management system atthe Plaza Hotel (Klote 1990). This crib was made of

    wood sticks, in. (38 mm) by 1.5 in. (38 mm) by 2 ft(0.61 long, and it had a peak HRR of aboet 1400

    (l kW) when burned in free air. The stack of

    nine wood pallets shown in Figure has a peak HRR

    of about 3,500 (3,700 kW) when burned in free

    air. Gross ( 1 Block( 197 and Walton (1988)burned cribs of various sizes and stick

    Babrauskas (2002) provides heat release data of cribsand pallets.

    VENTILATION-CONTROLLED FIRES

    As already stated, the HRR of a

    trolled fire depends on the amount of air that reaches thefire. Further, the HRR can be expressed as a function of

    the openings to the fire room as

    where

  • 8/10/2019 Principles of Smoke Management - Printed

    28/383

    Chapter2-Fire and Heat Release

    Q = heat release rate of fire, kW

    A, area of ventilation opening, f? (m2);

    H, = height of ventilation opening, (m);

    =

    Equation (2. l )appiies to rooms of construc-

    tion and size with only one rectangular opening. Figure2.22 shows the ofa ventilation-controlled fire as a

    function of width of the door or other opening. Equation

    (2.1) provides useful estimates for rooms made with

    normal construction materials concrete, wood,

    etc.), but it is not appropriate for metal rooms, such as

    on a ship with steel decks and bulkheads. For large

    rooms (over 300 [30 the appropriateness of

    Equation (2.1) is questionable. For information about

    the effects of construction materials and room sizes, see

    Walton and 995).

    For a number of rectangular openings with the same

    bottom and top elevations, the heights are the same, and

    the effective area is the sum of the individual areas.

    where

    A , effective area of all the ventilationopenings,ft2

    area of ventilation opening from = to

    (m').

    This is illustrated for two openings in Figure 2.23.

    Figure2.2 Stacko f

    Example 2.1 Ventilation-Controlled Fire

    For a roomwith a single doorway opening that is fullyinvolved in how big will the fire be? The doorway open-ing is 3 (0.914m)wideby7 (2.13 high.H,=7 (213 m);A, = =21

    thetire is ventilation controlled, Equation (2.1) isapplicable.

    Q

    SPRINKLERS

    Figure illustrates t-squared fire growth with

    the three possible responses to sprinkler spray: (a) sprin-

    klers overpowered by fire, (b) constant and (c)

    reduction ofHRR. Sprinklers can be overpowered by an

    extremely fast growing fire due to burning materials that

    exceed the sprinkler design. Sprinklers can also be over-

    powered when the smoke reaching the sprinklers has

    cooled due to plume entrainment, happen with

    fires in spaces with ceilings that are relatively high com-

    pared to the arrangement of fuel. For this to happen, the

    Door

    DoorWidth

    Figure 2.22 HRR a

    medium-sizedroom

    Foropenings with the same andbottom elevations.A,

    Figure2.23Combining openings

    of sizeo f

  • 8/10/2019 Principles of Smoke Management - Printed

    29/383

    Principles of Smoke Management

    Time

    (a) SprinklersOverpowered by Fire

    I

    Conservative Estimate

    of Constant HRR

    Time

    (b) Conservative Estimate of ConstantHRR After Sprinkler Activation

    Time

    (c) Fire Decay After Sprinkler Activation

    Figure2.24 Interaction between and sprinklers.

    flame height is typically less than the ceiling height, androom air cools the gases in the

    plume. Methods of calculating the plume temperature

    are in Chapter 13. If the sprinklers do activate, the spray

    could evaporate before the droplets reach the fuel.

    DECAY DU ETOSFRINKLERS

    A constant HRR after sprinkler actuation is a con-

    servative estimate for many applications. Fire

    after sprinkler actuation is more realistic. Fire decay can

    be expressed as

    where

    = post sprinkler actuation HRR, kW

    = sprinkler actuation, kW

    t = time from ignition,

    = time of sprinkler actuation,

    = time constant fire suppression,

    For a number of fuel likely to be found in

    offices, and (1992) conducted

    sprinklered fire experiments with a spray density of

    (0.07 of water. They determined that a

    fire decay curve with a time constant of 435 had ahigher HRR than most of the sprinklered fires (Figure

    2.25). Evans (1993) used these data and data for wood

    crib fires with sprinkler spray densities of

    (0.041 and 0.097 (0.066 from

    (1976) to develop the following correlation:

    where

    = spray density,

    C, = 6.15

    While Equation (2.4) has not been experimentally

    verified, it does allow us to adjust the decay for

    sprinkler densities other than those of

    Sprinkler Response

    While the information in this section is primarily

    about sprinklers, it also applies to vents actuated by fus-

    ible links and fixed temperature detectors.

    The responsiveness of sprinklers is tested by the

    plunge test, where a sprinkler is into a heated

    in which heated air is circulated. The of

    the plunge test is mathematically the as that o f a

    small piece of hot metal suddenly quenched in a cool

    fluid, as described in heat transfer textsand This analysis is based on

    the assumptions that (I ) the internal resistance of the

    sprinkler is negligible, (2) the sprinkler is instanta-

    neously put the oven, (3) the convective heat transfer

    is constant, (4) the gas temperature i n

  • 8/10/2019 Principles of Smoke Management - Printed

    30/383

    Chapter 2-Fire and Heat Release

    oven is constant, and the only heat transfer is from

    the sprinkler to the gas.

    The temperature of the sprinkler increases

    as shown in Figure The time constant, of

    the sprinkler is

    where

    =

    m =

    C =

    h, =

    A =

    time constant,

    mass of the sprinkler, (kg);

    specific heat of the sprinkler, "F "C);

    convective heat transfer "F

    surface area of the sprinkler, (m2).

    . The time constant, is the time at which the tem-

    perature of the sprinkler has reached 63% of the way to

    thegas temperature. The convective heat transfer

    cient varies with velocity, so that the time constant alsovaries with the velocity at which it is measured.

    The response time index (RTI) was developed as a

    measure of sprinkler responsiveness that is independent

    of velocity.

    where is the velocity,

    In the plunge test, the to actuation and the gas

    velocity are measured. Then the time constant can be

    calculated from the to actuation, and the RTI is

    calculated from Equation The RTI of standsrd

    sprinklers varies from about 140 to 280

    to 155 and the RTI of quick-response sprin-

    klers (QRS) varies from about 50 to 100 (28 .

    to 55

    The response time index does not account for con-

    ductive heat transfer from the sprinkler. To account for

    conduction, a virtual RTI can be calculated as

    RTI,

    where

    RTI, = virtual RTI,

    = conductivity factor,

    . .

    'I:is time constant

    Time

    Figure2.26

    Paper Cart Fuel PackageSecretarial Desk Fuel PackageExecutiveDesk Fuel Package

    . Office Fuel PackageI Fuel Package

    Sofa Fuel. Work Station I Fuel Package-- Work Station Fuel Package

    Wood Cribs

    0 200 400 600 800

    Time, t-

    Figure 2.25 to a of

    (0.07

  • 8/10/2019 Principles of Smoke Management - Printed

    31/383

    Principlesof SmokeManagement

    Actuation

    Actuation depends on gas temperature and velocity

    near the sprinkler. In a fire, a jet of hot gases flows

    ally from where the smoke plume intersects the ceiling.

    Computer programs have been developed that use corre-

    lations for such a ceiling jetto predict actuation time.

    The program DETACT-QS (Evans and Stroup

    1986) assumes that the thermal device is located ina rel-

    atively large area, that only the ceiling jet heats the

    device, and that there is no heating from the accumu-

    lated hot gases in the room. The required program inputs

    are the height of the ceiling the fuel, the distance

    of the thermal device from the axis of the fire, the actua-

    tion temperature of the thermal device, the response

    time index (RTI) for the device, and the rate of heat

    release of the fire. The program outputs are the ceiling

    gas and the device temperature, both as a

    function of time and the time required for device actua-

    tion. DETACT-T2 (Evans et al. 1986) is similar to

    DETACT-QS, except it is specifically for t-squaredfires. Several zone fire models (such as FAST,

    and JET) are capable of calculating ceiling jet

    temperatures and predicting actuation (Chapter 8).

    DESIGN FIRES

    A design fire curve is the description of the devel-

    opment of a design fire that can be used in a fire sce-

    nario. The curve is for HRR as a function of time. This

    curve can be as simple as a constant, and it can also be a

    simple function of The design fire curve can also

    be a complicated sequence of lesser for some or

    all of the stages of tire development described at the

    beginning of this chapter.

    A fire scenario includes more than just the design

    fire curve. The word means an outline of

    events, asi n a play or other theatrical production. A fire

    scenario can be thought of as the outline of events and

    conditions that are critical to the outcome

    of alternative designs. In addition to the HRR and fire

    location, a scenario could include the type of materials

    burned, airborne toxicants and soot produced, and peo-ple movement during fire.

    are not intended to be located in the space are referred to

    as

    A few examples of transient fuels are Christmas

    decorations, paint and solvents in stairwells during

    redecorating, unpacked foam cups in cardboard boxes

    after delivery, cut up cardboard boxes awaiting removal,

    and closely stacked upholstered furniture after delivery.Sometimes, transient fuels remain in place for long peri-ods. Some examples are a number of polyurethane

    mattresses delivered to a dormitory and waiting for dis-tribution in the next school year, (2) automobiles on dis-

    play in a shopping mall, (3) boats and campers on

    display in an arena, and (4) a two-story colonial house

    built for display inside a shopping mall.

    Transient fuels must not be overlooked when select-

    ing a design fire. One approach to incorporating tran-

    sient fuels in a design fire is to consider the fire

    occurring over 100 (9.3 m2) of floor space with a

    heat release rate density of 20 Btuls ft2

    (225

    This amounts to an allowance for transient of 2000

    (2100 kW).

    Steady Fires

    It is the nature of fires to be unsteady, but the steady

    fire is a very useful idealization. Steady fires have a con-stant heat release rate. In many applications, use of a

    steady design fire can lead to and con-

    servative designs.

    HRRper Unit Area

    Morgan (1979) suggests a typical rate of heat

    release per unit floor area for mercantile occupancies of

    44 (500 Fang and Breese (1980)determined about the same rate of heat release for resi-dential occupancies. Morgan and Hansell (1987) and

    Law (1982) suggest a heat release rate per unit floor

    area for office buildings of 20 f? (225

    For smoke management applications, a heat release rate

    per floor area of 20 Btuls ft2 (225 is suggested

    for restricted fuel spaces, and 44 Btuls ft2 (500

    is suggested for spaces with furniture, wood, or other

    combustible materials. A occurring over 100 (9.3

    m2) of floor space would result in 2000 Btuls kW)

    for restricted fuel space and 4600 kW (4400 Btuls) fora

    space with The heat release densities ofIn many spaces, the fuel loading is severely

    Table 2.2 can be useful in determining design fires.restricted with the intent of restricting fire size. Such

    spaces are characterized by interior finishes of metal,

    brick, stone, or gypsum board and furnished with Unsteady Fires

    objects of similar materials plus plants. Even for Fires frequently proceed through an incubation

    such a space, there can be an almost period of slow and uneven growth, followed by a period

    unlimited number of objects that are in the of established growth as illustrated in Figure 2.27 (a).

    space for short periods. Such combustible materials that Figure 2.27 (b) shows that established growth - is often

  • 8/10/2019 Principles of Smoke Management - Printed

    32/383

  • 8/10/2019 Principles of Smoke Management - Printed

    33/383

    wheretis considered the time from effective ignition. For

    I-Punits, the following form of Equation (2.9) is

    used:

    where

    Q = heat release rate of fire,

    time after effective ignition,

    = growth time,

    When = Equation (2.10) gives a value ofQ =

    Table 2.3 lists fire growth values from

    NFPA 92B (NFPA 2000) and NFPA 72 (NFPA 1999).

    The fire growths corresponding tothe NFPA values

    are shown on Figure 2.28. Unless otherwise stated in

    this book, the terms slow, fast, and fast

    fire growth refer to the NFPA 92B values.

    Fuel Package Approach

    The base fuel package is the maximum probable

    size of package that is likely to be involved in fire

    for a specific application. A fuel package can be made

    up of a number of fuel items (sofa, chair, bed, table, cur-

    Time,t

    (a) Typical HRR curve

    Time,t

    (b) Idealized Parabolic curve

    2.27 Fire

    Principles of Smoke Management

    tains, The key to selecting the items that make

    the base package is that the radiant flux bum-

    ing one of the items will lead ignition of the other

    items in the base package but not to ignition for

    items outside the base package.

    The point source radiant model (Figure 2.29) con-siders the flame as a small thermal source such that the

    intensity of thermal radiation is proportional to the

    inverse of the square of distance from the source. Ther-

    mal radiation also is calledradiant

    The intensity of thermal radiation is

    where

    intensityof thermal radiation,

    = radiant releaseofthe fire, (kW);

    R = distance from the of the fire, ft (m).

    Table 2.3:

    Fire Growth Constants for T-Squared Fires

    NFPA 92 8

    Slow

    Thin Plywood Corrugated Cardboard

    Cartons1.5 (4.6m)High -Various: Contents

    0 200 400 600 800

    Medium

    Fast

    Fast

    TimeFrom

    Figure2.28 of

    0.002778 0.002931

    0.01 0.01 127 300

    0.04444 0.04689

    0.1778 0.1878 75

    400

    150

    NI A

  • 8/10/2019 Principles of Smoke Management - Printed

    34/383

    Chapter2-Fireand Heat Release

    OrientedFire Normal

    The point source model is a goodapproximationprovided thatR

    Figure2.29Point sourceradiation model.

    The point source radiant model is appropriate pro-

    vided that the distance from the of the flame is

    greater than twice the diameter of the fire (R The

    radiant heat release of the fire is

    where

    Q heat releaserateof the fire, (kW);

    = radiativefraction.

    Heat transfer a is by conduction, con-vection, and radiation. For most fires, conductive heat

    transfer from the is negligible. The radiant frac-

    tion can be expressed as

    where is the convective fraction.

    The radiative fraction depends on the material

    burned and the diameter of the fire, and the radiative

    fraction varies from about 0.1 to 0.6. Low sooting fuels,such as methanol, have low radiative fractions, and high

    sooting materials, such as gasoline and polystyrene,

    have high radiative fractions. However, for design appli-

    cations, values of 0.3 and = 0.7 are common.

    The idea of separation distance is useful evalua-

    tion of what items should be in the base fuel package.Using the point source radiant model, the separation dis-

    tance is

    where

    = separation distance from the ofthe fire to

    a target, (m);

    = intensityof radiation needed for

    ignition,

    Fuel items less than away from the fire would

    be expected to ignite, and fuel items farther than

    away would not be expected to ignite. The radiant flux

    needed for nonpiloted ignition varies from about 0.9(10 for thin easy-to-ignite materials to

    1.8 (20 for thick materials.

    For a fire, the heat release rate, that results in

    ignition of an object at a distance ofR away is

    For radiant heat transfer where R is less than twicethe diameter of the fire, a method other than the point

    source model is needed. Several texts have general

    information about radiant heat transfer and

    1992; lncropera and 1985; Kreith 1965).

    For information about radiant heat transfer of fire, read-ers are referred to Quintiere

    and and Croce (1995).

  • 8/10/2019 Principles of Smoke Management - Printed

    35/383

  • 8/10/2019 Principles of Smoke Management - Printed

    36/383

    Chapter2 andHeat Release

    Sofa Sofa

    Chair2Note:R, m)

    Figure2.30 the of

    Example

    time(a) Draw curveforsofa 1,and ignitionpointof chair

    . .

    (b) Draw for chair

    4000

    Time(c) Locate ignition point and draw curve for sofa 2

    Time(d) Get base fuel package by adding the 3 othercurves

    Figure2.31Graphic of base

    package Examnple2.2.

  • 8/10/2019 Principles of Smoke Management - Printed

    37/383

    CHAPTER3

    Smoke and Tenability

    In this book, the term is used in accordance ard. Frequently, people become disoriented in fire

    the definition of NFPA 92A (2000) and NFPA tions because they cannot see through heavy smoke. If92B which states that smoke consists of the they remain in the building too long, they fall victim to

    airborne solid and liquid particulates and gases evolved exposure to toxic gases or elevated temperatures. Fur-

    when a material undergoes pyrolysis or combustion, ther, in buildings with balconies, smoke obscuration can

    together with the quantity of air that is entrained or result in fatal falls.

    mixed into the mass. The products of combustion

    usually include particulates, unburned fuel, water

    carbon dioxide, carbon monoxide, and some other toxic

    and corrosive gases. As smoke moves through a build-

    ing, air mixes into the smoke mass and the concentration

    of combustion products in the smoke decreases. Includ-

    ing air that is entrained or othenvise mixed facilitates

    discussions about fire smoke management in atriums

    and other spaces. Generally. smoke is thought ofas

    being visible, but the above definition includes

    Smoke management systems can be designed with

    the objective of providing a tenable environment in the

    means of egress or at other locations during evacuation.

    Such a tenability system needs to be designed to meet

    tenability criteria. Such criteria need to include expo-

    sure to toxic gases, heat, and thermal radiation. Further,

    the criteria often include visibility. As discussed at the

    end of this chapter, criteria for a tenability design

    depend on the specific application.

    ble produced by burning of materials that pro-

    duce little or no particulate matter, such as hydrogen,

    natural gas, and alcohol.

    Information about smoke hazards is useful in

    effects of small quantities of smoke migrating

    into "protected spaces," and it is useful in evaluating the

    consequences of smoke migration without smoke pro-

    tection. This chapter concentrates on hazards due

    to toxicity, temperature, and smoke obscuration. The

    hazards of temperature consist ofhear which

    can occur when a person comes into bodily contact with

    hot gases, and can

    occur a person receives thermal radiation from

    flames or hot smoke that are some distance away from

    the person.

    Many different methods of expressing smoke

    obscuration are used in fire science and fire protection

    engineering, and this section discusses the common

    methods. There is a lack of uniformity concerning

    smoke obscuration, and some engineering publications

    use different terminology or have different mathemati-

    cal definitions for the same terms. These differences

    could result in significant errors, and readers are

    ticned to take care to verify the exact meanings of

    obscuration terms used in other publications. The termi-

    nology that follows was selected with the intent of beingconsistent with technical publications in this field.

    Exposure to toxic gases, heat. and thermal radiation The fraction of light transmitted through the

    can be a direct hazard to life, and reduced visibility due length of smoke is called thetransniittance and is writ-

    to smoke obscuration can be a significant indirect haz- ten as

  • 8/10/2019 Principles of Smoke Management - Printed

    38/383

  • 8/10/2019 Principles of Smoke Management - Printed

    39/383

    Principles of Smoke Management

    Table 3.1:Comparison of Differ