principles of smoke management - printed
TRANSCRIPT
-
8/10/2019 Principles of Smoke Management - Printed
1/383
PRINCIPLESOF SMOKEMANAGEMENT
-
8/10/2019 Principles of Smoke Management - Printed
2/383
This publicationwas made possible by funds from ASHRAE research.
Principles of Smoke Managementby John and James Milke is an exhaustive treatment of man-
agement, including pressurized stairwells, pressurized elevators, zoned smoke control, and smoke manage-
ment in atria and other large spaces. Recent advancements include heat release rate, toxicity ofnatural atrium venting, minimum depth of an atrium smoke layer, smoke stratification,
detection, tenability systems, and computer analysis. The book includes numerous example calculations.
Methods of analysis include equations, network flow models, zone fire models, scale and hazard
analysis. Computational fluid dynamics (CFD) is also addressed. The book includes a CD of computer soft-
ware for of smoke management systems.
This publication was prepared under ASHRAE Research Project
Cognizant TC: TC5.6, Fire and Control.
ABOUT THE AUTHORS
John H. P.E., Fellow ASHRAE, is a consulting engineer specializing in the design and
review of smoke management systems, as well as code consulting and teaching private management
courses. He conducted research for 19 years at the National Institute of Standards and Technology (NIST)
and has published over 80 papers and articles on smoke management and other aspects of fire protection.
Dr. Klote headed the Building Fire Physics Group at NIST, which conducted research in smoke
ment in buildings. The tools used for this research included full-scale fire experiments, scale fire
experiments, network airflow models, zone fire models, and computational fluid dynamics (CFD).
acted as a consultant in the area of smoke movement for the investigations of the MGM Grand fire and the
First Interstate Bank fire. research was the basis of the 1997 revision to the NFPA Life Safety Code
(section allowing elevators to be used as a second means of egress from towers.
In he e arned a Doctor of S cience degree in mechanical from George W ashington Uni-versity. He is a member of the National Fire Protection Association (NFPA). a fellow of SFPE, and a fellow
of ASHRAE. He has extensive participation in ASHRAE and NFPA committees, including being a past
of ASHRAETC Fire and SmokeControl. Dr. is a registered professionalengineer in the
District of Columbia, North Carolina, California, and Delaware.
James A. is an associate professor and chair of the Department of Fire Protec-
tion Engineering at the University of Maryland. Dr. has been a member of thefaculty and staff of the
department since 1977. He received his in aerospace engineering from the University of Maryland,
with an in structures. He received an M.S. degree in mechanicalengineering and a B.S. degreei n
fire protection engineering, both from the University of Maryland. In addition. he has a B.S. degreei n phys-
ics from College.
Dr. has served as a research fire prevention engineer at the Building and Fire Research Labora-
tory, National Institute of Standards and Technology, as the fire protection engineer for County, Vir-
ginia, and consultant to numerous organizations. Dr. Milke is a fellow of theSFPE and is a of the National Fire Protection Association. the International Association of Fire Safety Science. and the Amer-
ican Society of Civil Engineers. He is the chairman of the NFPA Technical Committee on Smoke Manage-
ment and the ASCWSFPE committee on Structural Design for Fire Conditions. He on the
Fire Council of Underwriters Laboratories.
-
8/10/2019 Principles of Smoke Management - Printed
3/383
PRINCIPLES OF
SMOKE
MANAGEMENT
JohnH.Klote
JamesA.Milke
American Society of Heating, Refrigerating
and Air-conditioning Engineers, Inc.
Society of Fire Protection Engineers
-
8/10/2019 Principles of Smoke Management - Printed
4/383
ISBN 13-99-0
American Society of Heating, Refrigerating
and Air-conditioning Engineers, Inc.
1791 Circle, N.E.Atlanta,GA 30329
rights reserved.
Printed in the United States of America
ASHRAE has compiled this publication with care, but has not investigated, and ASHRAE expressly disclaims any duty
to investigate, any product, service, process, procedure, design, or the like that may be described herein. The appearance'of any
technical data or editorial material in .this publication does not endorsement, warranty, or guaranty byASHRAE of any
product, service, process, procedure, design, or the like.ASHRAE not warrant that the information in the publication is free
of errors, and ASHRAE does not necessarily agree with any statement or opinion in this publication. The entire risk of the use ofany information in this publication is assumed by the user.
No part of this book may be reproduced without permission in writing fromASHRAE, except by a reviewerwho may brief
or reproduce illustrations in a with appropriate nor may any part of this book be reproduced, stored in a
retrieval system, or transmitted in any way or by any means--electronic.photocopying. recording, or other-without permission
in writing fromASHRAE.
ASHRAE STAFF
Editor
Howard
Editor
Christina
Editorial Ass
Barry Kurian
Jayne
Assistant
PUBLISHER
Cornstock
-
8/10/2019 Principles of Smoke Management - Printed
5/383
DEDICATION
This book is dedicated to the memory of George Tamura, who conducted pioneering research in smoke control atthe National Research Council of Canada.
-
8/10/2019 Principles of Smoke Management - Printed
6/383
-
8/10/2019 Principles of Smoke Management - Printed
7/383
TABLE OF CONTENTS
Chapter Page
Preface ix
Acknowledgments
Chapter I-Introduction
Chapter 2-Fire and Heat Release
Chapter 3
-
Smoke and Tenability 27
Chapter Analysis 49
Chapter 5-Effective Areas and Smoke Movement 63
Chapter of Smoke Management 87
Chapter 7-Air Moving Equipment and Systems
Chapter 119
Chapter 9-Hazard Analysis 129
Chapter 10
-
Stainvell Pressurization 139
Chapter l-
Elevator Smoke Control 157
Chapter 12-Zoned Control 171
Chapter 13-Fundamental Concepts for Atria 181
Chapter 14-Atrium Systems 199
Chapter 15-Physical 217
Chapter 16-Computational Fluid Dynamics 225
Chapter 17-Commissioning and Routine Testing 235
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Nomenclature 243
References 247
A-Units of and Physical Data 259
-
8/10/2019 Principles of Smoke Management - Printed
8/383
AppendixB-Bibliography 271
Appendix of Elevator Evacuation Time 277
Appendix D-Applicationof CONTAMW 289
Appendix E-ASMET Documentation
.................................Appendix F
-
ASET-C: A Room Fire Program for Personal Computers 329
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix G-Data and Computer Output for Stairwell Example
. . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix H-Data and Computer Output for Zoned Smoke Control Example 349
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix I-Inspection Procedures for Smoke Control Systems 355
Appendix J-Test Procedures for Stairwell Pressurization Systems 361
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix K-Test Procedures for Zoned Smoke Control Systems 365
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix L-Inspection Procedures for Atria Smoke Exhaust 369
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Appendix M-
Test Procedures for Atria Smoke Exhaust Systems 371
Index 373
-
8/10/2019 Principles of Smoke Management - Printed
9/383
PREFACE
In 1983, ASHRAE published Design of Smoke Control Systems for Buildings, written by myself and John
This book was the first attempt to consolidate and present practical information about smoke control
design. Judging by the many favorable comments and suggestions about this first book, I feel that it was a success.
The first publication was limited to systems that control smoke by means of the physical mechanisms of pressuriza-
tion and airflow.
In 1992, ASHRAE and SFPE jointly publishedDesign of Smoke Management written by myself and
James Milke. The term smoke management was used in the title of this publication to indicate that the physical mech-
anisms were expanded from pressurization and airflow to include compartmentation, dilution, and buoyancy. Based
on heightened about supplying combustion air to the fire, a caution was added about the use of airflow for
smoke management.This new publication addresses the material of the two earlier books plus people movement in fire, hazard analy-
sis, scale modeling, and computational fluid 'dynamics. In addition, the material about tenability and atrium smoke
management has been extensively revised. As with the other books, this new book is primarily intended for designers,
but it is expected that it will be of interestto other professionals (code researchers, etc.).
This book and its predecessors are different from other design books in a number of respects. This book is writ-
ten in both English units (also called for inch-pound) and units so that it can be used by a wide audience. To the
extent practical, equations are accompanied by derivations and physical descriptions of the mechanisms involved.
The physical descriptions are worked into the text as simple explanations of how particular mechanisms, processes,
or events happen. The goal of the derivations and physical descriptions is to provide information and understanding
so that readers can apply the material of this book in creative and insightful ways.
As with the first two publications, I hope that this book is of value to the engineering community. Further, I
invite readers to mail their suggestions and comments to me at the address below:
JohnH. Klote, P.E.I I I I Street
VA 22 l
-
8/10/2019 Principles of Smoke Management - Printed
10/383
ACKNOWLEDGMENTS
This project would not have been possible without the support of theAmericanSociety of Heating, Refrigerating
and Air -conditioning Engineers (ASHRAE). Acknowledgment is made to the members of the ASHRAE Smoke
Control Monitoring Committee for their generous support and constructive criticism. The members of this subcom-
mittee are:
A. Webb, Chairman (Performance Technology Consulting, Ltd., Lake Bluff,
John A. Minn.)
Dave Elovitz (Energy Economics, Inc., Natick, Mass.)
Gary Lougheed (National Research Council Canada, Ottawa, Ontario)
The support and advice of the staff of the Building and Fire Research Laboratory (BFRL) at the National Insti-tute of Standards and Technology (NIST) in Gaithersburg, Md., was invaluable. Particular appreciation is expressed
to Richard Bukowski, Glen and Richard Peacock. Special thanks are due to Daniel Madrzykowski for his
advice regarding oxygen consumption calorimetry and heat release rate. The authors are indebted to Kevin
tan of BFRL for his valuable advice and constructive criticism regarding computational fluid dynamics.
Richard Gann and Barbara Levin of and Braun of Hughes Associates, Baltimore, Md., provided valu-
able information and insight concerning the evaluation of the effects of toxic exposures. Creg Beyler of Hughes
Associates provided constructive criticism in a number of areas. Special thanks are due to Gary Lougheed for his con-
criticism and for bodyof relevant research conducted by him and associates at the National Research
Council of Canada.
Students of fire engineering at the University of Maryland have provided insightful comments on
drafts of several chapters of this book In particular, the students and Naviaser developed the
information about CONTAMW that is included as Appendix D.
content of book is heavily dependent upon work of researchers, design engineers, and other
professionals around the world. So many of these people provided experimental research results, system con-cepts, and analytical methods that it is impossible to thank them all individually. Appreciation is expressed to all
those have to advancement of smoke technology directly or indirectly by their con-
tributions to fire science and fire protection engineering.
-
8/10/2019 Principles of Smoke Management - Printed
11/383
CHAPTER1
Introduction
Smoke is recognized as the major killer in fire situa-
tions. Smoke often migrates to building locationsremote from the fire space, threatening life and
damaging property. Stairwells and elevator shafts
quently become smoke-logged, thereby
and inhibiting rescue and fire fighting. The MGM
Grand Hotel fire (Best and Demers 1982) is an
of the smoke problem. The fire was limited to the first
floor, but smoke spread throughout the building. Some
occupants on upper floors were exposed to smoke for
hours before rescue. The death toll was 85, and the
of the deaths were on floors far above the fire.
23
22
2
20
17
MGM Grand HotelFireLas Vegas, NVNov 21,1980
Note: Renumberedfor
The MGM Grand is not unique in this respect, a s is
illustrated by the fires at the Roosevelt Hotel1964) and Johnson City Retirement (Steckler et
al. 1990). All of these fires were located on the first
floor, but the majority of deaths were on upper floors
(Figure l).'
During the intensive activity of fire fighting andrescue, the locations of some of the bodies are notrecorded. Thus Figure 1. 1 is limited to the deaths forwhich the locations were known.
Retirement8 Fire
L7 Johnson City. TNDec 24,1989
2
I
0 1 2 3
Deaths
2
I
0 3 4 5 6 7 8 9 1 0 1 1 1 2 1 3 1 4 1 5 1 6 1 7 1 8
Deaths 0 1 2 3 4 5 6 7 8
Deaths
Figure I.I Deaths for fires was
-
8/10/2019 Principles of Smoke Management - Printed
12/383
Chapterl-Introduction
Figure Floor plan of Health Care Test the Annex.
The general public is unaware of how fast a fire can
grow and of how much smoke can be produced by a fire.
This unawareness extends to many designers and other
related professionals. Because such an awareness i s nec-
essary to the evaluation of design parameters for smokemanagement systems, the following example is pro-
vided.
This example is fire test N-54, performed at the
Health Care Test Facility at the National Institute of
Standards and Technology Annex in Gaithersburg, Md.
For technical details of this unsprinklered fi re test, the
reader is referred to a report by et al. 980). T he
floor plan of the test facility is shown in Figure 1.2.
In this test, various fabrics representing common
clothing materials were hung on wire coat hangers and
arranged loosely in a wooden wardrobe. A cardboard
box containing crumpled newspaper was placed on the
floor of the wardrobe. The test started when the crum-pled newspaper was ignited by a match. Following igni-
tion, the left-hand door of the wardrobe was closed
tightly while the right-hand door was partially open
resulting in a 3 in. (76 mm) opening along the vertical
edge of thedoor.
At one second after ignition, no flame or smoke
was visible. At 80 seconds, flames were visible flowing
from the top of the wardrobe, a layer of smoke was cov-
ering the ceiling of the burn room, and smoke had
flowed into the corridor forming a one-foot-thick layer
just below the corridor ceiling. At seconds, flames
were flowing from the top two-thirds of the wardrobe
opening, and the smoke flowing out of the burn roomdoorway had increased significantly. At seconds
after ignition, flames were flowing from the entire open-
ing of the wardrobe door, and the layer of smoke in the
corridor and lobby had descended to approximately 4 ft
(1.2 m) below the ceiling.
Such very rapid fire growth and accompanying
smoke production represent a real possibility in
wardrobe fires and perhaps even closet fires. Many
other fire scenarios are possible. For example, a latex or
a polyurethane filled mattress ignited by an adjacentwastebasket fire would reach about the same stage of
development in six minutes that wardrobe test N-54
reached in two minutes.
Full-scale fire tests by et al. (1997) and
Lougheed et al. (2000, 2001) have shown that success-
fully sprinklered fires can continue to bum and produce
enormous amounts of dense buoyant smoke after sprin-
kler activation. While it appears this smoke production
is greatest for fires that are shielded from sprinkler
spray, some unshielded fires still produced considerable
amounts of buoyant smoke.
The concept of smoke management has developed
as a solution to the smoke migration Smoke
movementcan be managed by use of one or more of the
following mechanisms: compartmentation, dilution, air-
flow, pressurization, or buoyancy. These
are discussed in detail in Chapter 4. The use of pressur-
ization produced by mechanical fans is referred to as
controlby NFPA 92A (NFPA 2000). By this def-
inition, stairwell pressurization (Chapter 7), elevator
pressurization (Chapter and zoned smoke control
(Chapter 9) are all types of smoke control systems.
The primary emphasis of this book is on
that cse pressurization produced by mechanical fans.
The use of pressurization to control the flow of undes-
ired airborne matter has been practiced for at least 50
years. For example, it has been used in buildings, suchas experimental laboratories, where there is dangerof
2. As discussed later in Design Con-siderations,"smoke management is only one of manytechniques available to protection engineers.
-
8/10/2019 Principles of Smoke Management - Printed
13/383
Principlesof
poison gas, flammable gas, or bacteriological material
migrating one area to another; it has been used to
control the entrance of contaminants where a dust-free
environment is necessary; it has been used
tion migration and contamination could occur; and it has
been used hospitals to prevent the migration of bacte-
ria to sterile areas. However, the use of airflow and pres-surization to control smoke flow from a building fire is a
fairly recent adaptation.
INTENT
The primary intent of this book is to provide practi-
cal state-of-the-art to engineers who have
been charged with design of smoke management sys-
tems. The book is also intended to provide information
for the review of designs and development of codes and
standards,. This chapter contains general background
Chapter2 deals with fire development and
the heat :release rate of fires. Chapter 3 discusses the
nature including toxicity, heat exposure, andvisibility through smoke. Chapter 4 people
movement during fire evacuation.
methods are employed to minimize the possibility
doors being proppedopen.
While advances in tenability analysis have
engineering analysis smoke feasible, these sys-
tems are not included in this book. The idea of smoke
shafts is that smoke flows up the shaft due to
where the smoke flows away from the building, but the
authors have concerns about the fundamental effective-
ness of smoke shafts. Further, there seems to be little
interest in smoke
The stair systems known as towers
are misnomers, in that there is nothing about them that
ensures no smoke migration into stairs. Originally, these
towers were separate from the building and were con-
nected to it only by walkways open to the outside. Some
versions of these towers used relatively small openings
in exterior vestibule walls in place of the separate walk-
ways. In the absence of an engineering analysis of these
systems, it can only be stated that the benefits of these
systems are questionable. For these reasons, separatedstair towers are not included in this book, and it is rec-
ommended that the term towers not be
Chapter 5 is devoted to smoke movement in build-
and the individual driving forces of smoke move-
ment are discussed in detail. Chapter 6 contains a EQUATIONS AN D UNITS
discussion of topics that are essential forOF MEASUREMENT
the design of systems to manage smoke movement. It
discusses the mechanisms of compartmentation, dilu-
tion, airflow, pressurization, and buoyancy, which are
used by themselves or in combination to manage
conditions in fire situations.
Background information is provided about ducts,
fans, fire dampers, smoke dampers, and fan-powered
ventilation systems in Chapter 7. Chapter8 is a descrip-tion of the computer programs that are used for the anal-
ysis of smoke management systems.
Chapters 9 through 14 address hazard analysis,
stairwell pressurization, elevator smoke control, zoned
smoke and atrium smoke management. For
applications for which these conventional methods are
inappropriate, the methods of scale and
putational'fluid dynamics (CFD) can be used (Chapters
and 16). Chapter 17 addresses the important topic of
commissioning and routine testing.
It may be noted that pressurized corridors have
been omitted. The presented in this book can
Considering that this book is primarily intended for
design, it seems most appropriate that units should be
specified for every equation. However, the topic of
smoke management is relatively new, and there is no
test to refer to for the derivation of many of the equa-
tions used. Further, it was desired that the text be in both
Inch-Pound (IP) units and the International System
units. It would be unacceptably to present
derivations using both commonly used English units
and units. The equations used for derivations are
homogeneous, and they can be used with
the system, the slug pound system, and the pound
mass poundal system (Appendix A). These dimension-ally homogeneous equations are easily identified
because no units are specified for them in the text.
all of the equations the reader is to use
for design analysis are given in both English and
units. These equations are easily identified because the
appropriate units for the equation are specifically indi-
catedi n the text.
applied to pressurized corridors in a manner similarto their application to other pressurization systems. The
HISTORY OF SMOKE VENTING.
concern with pressurized corridors is that if a fire room Smoke venting has been used extensively todoor is blocked open, the corridor pressurization system age smoke flow during fires. The acceptance of
can force smoke into other rooms off the corridor. For such venting resulted from several major fires,
this reason, pressurized corridors are not generally rec- including those at the Brooklyn which killed
except for applications where practical 283 in 1877; Vienna Ring which killed 449
-
8/10/2019 Principles of Smoke Management - Printed
14/383
Chapter l
AreAreas2 and4on 10 Tower
I I
........................3 on................ Floor....................................
Figure1.3 Typical floor plan of the office at
30Church Street.
in 1881; the Royal, which killed 186 in 1887;
and the Iroquois which killed 571 in All
of these fires started on the stage and resulted inmajor loss of life in the audience. The Palace fire
in Edinburgh in 1911 was an exception. In this fire,
smoke venting through the stage roof was credited for
helping to prevent any loss of life. The buoyancy of the
hot smoke forced the smoke flow through the vent open-
ings, and this venting is called natural venting or gravity
venting.
Over the past few decades, fan-powered smoke
exhaust has become the standard for almost all atria in
North America. In other areas, such as Europe, Austra-
lia, and New Zealand, both natural venting systems and
fan-powered exhaust systems have become for
atria. Modem atria smoke management designs are
based on engineering analysis developed over the last
few decades. These analytical methods are primarily
based on research in smoke plumes fire model-
ing. Information about these analytical methods is pro-
vided in Chapters and 14.
HISTORY OF PRESSURIZATIONSMOKE CONTROL
The idea of smoke protection by pressurization sys-
tems is restrict the movement of smoke a build-
ing fire. To study the effectiveness of pressurization
smoke control, the Brooklyn Polytechnic Institute con-ducted a series of fire experiments at a 22-story office
building at 30 Church street in New YorkCityThis building was scheduled for demolition.
Materials representative of fuels that would be in an
were burned on floors 7 and 10, as shown in Fig-
ure 1.3. This project demonstrated that pressurization
could provide "smoke free" exits during large unsprin-
Experimental Tower
34 LobbySupply
Figure 1.4Typicalfloor plan of NRCCexper-hen-
klered fires. The term"smoke free" is used to mean
essentially free of smoke, with the possibility of such
insignificant amounts ofcombustion products that tena-bility is maintained.
Other full-scale fire tests also demonstrated thatpressurization could provide "smoke free" exits during
large unsprinklered fires (Koplon
Butcher et al. 1976). Cresci (1973) describes visualiza-
tion experiments using a model of the stair shaft at the
Church Street building, where stationary vortices
observed at open doonvays. These vortices are the rea-
son that the flow coefficient through an open
door is about half of i t be otherwise. This
significant effect on airflow is discussed in Chapter
The Research Tower near Ottawa (Figure 1.4) was
used for a joint National Instituteof Standards and Tech-
nology (NIST) and National Research Council Canada(NRCC) study of elevator smoke control. Again, i t was
demonstrated that pressurization could control smoke
from large unsprinklered fires (Tamura and Klote
1988; Klote and Tamura 1987).
In the spring of 1989, NIST conducted a series ofexperiments of zoned smoke control at the Plaza Hotel
in Washington as shown in Figure 1.5 (Klote
1990). A zoned smoke control is a system that
uses pressurization to restrict migration to the
zone of fire origin. Once again, it was demonstrated that
pressurization could control smoke from unsprin-
klered fires.
An analysis based on first principles of engineering
was made of the pressure differences produced thesmoke during the fires at the Plaza Hotel.As is done with zone fire modeling, the pressures
rooms were considered hydrostatic. The general trendsof calculated values were i n agreement with thesurements (Figure and this indicates a of
-
8/10/2019 Principles of Smoke Management - Printed
15/383
Principles of Smoke Management
applicability o f z one fire for analysis o f pres-surization smoke control systems.
OBJECTIVES O FSMOKE MANAGEMENT
Some objectives of a smoke management system
are to reduce deaths and injuries from smoke, reduce
property loss from smoke damage, and to aid firefight-ers. Many designers feel that life safety is the primary
objective of smoke management; however, systemshave been built with the primary objective of protecting
property--especially high-value equipment. Regardlessof the objective, the methods of design analysis pre-sented in book are applicable.
Theoretically, a smoke management system can be
designed to provide a safe escape route, a safe
area,or both. However, a pressurization control)
system can meet its objectives even if a small amount ofsmoke infiltrates protected areas. For this book, pressur-ization systems are designed on the basis that no smoke
infiltration will occur. Hazard analysis (Chapter 9) can
be used for the design of systems that maintain tenabil-ity even when people come into contact with some
smoke.
PERFORMANCE-BASEDDESIGN
recent years, performance-based codes havebecome a topic of considerable attention. Traditional
codes prescribe requirements, while performance-basedcodes require a level of performance. A
based design is developed to meet the level of perfor-mance stipulated in the code.
This book uses a performance-based approach,where the kind of performance is based on the type of
system. Pressurization smoke control systems aredesigned to maintain specific levels of pressurization at
barriers, such as partitions and closed doors. Atrium
smoke exhausts often are designed to keep smoke
descending below a specific level. Further, various
of smoke management systems can be designed to
maintain tenable conditions within specific spaces.
PRELIMINARY DESIGNCONSIDERATIONS
Smoke management should be viewed as only one
part of the overall building fire protection systems. Two
basic approaches to fire protection are to prevent fire
ignition and to manage fire impact. Figure 1.7 shows a
simplified decision tree for fire protection. The building
occupants and managers have the role in pre-venting fire ignition. The building design team may
incorporate features into the building to assist the occu-pants and managers in this effort. Because it is impossi-ble to prevent fire ignition completely, managing fire
impact has assumed a significant role in fire protection
design. Compartmentation, suppression, control of con-struction materials, exit systems, and smoke manage-ment are examples. The NFPA Fire Protection
Handbook(NFPA SFPEHandbook of Fire Pro-
tection Engineering (SFPE and NFPA 550(NFPA 1995) contain detailed about fire
safety.
S 20 25(minutes)
(a)Pressure Difference Near Ceiling
00 5 15 20 25 30
lime (minutes)
(b) Near Floor
Figure 1.5 Figure 1.6 and
Plaza Hotel
tests.
-
8/10/2019 Principles of Smoke Management - Printed
16/383
Chapter1
Objectives
Ignition Impact
Heat-Energy Source-FuelThreat' Exposure'
Sources Interactions
'Note: Smoke managementis one of many fireprotectiontools that can beusedto help manage the threat of fire and manage the exposure of fire.
1.7 decisiontree.
Many factors will affect the design of a man-
agement system. Before the actual mechanical design of
the system can proceed, the potential constraints on the
system should be determined and the design criteria
established. This section introduces some considerations
peculiar to smoke management system design, some of
which are merely listed below, since detailed discussion
is beyond the scope of this book. However. published
works on some of these subjects are cited in the bibliog-
raphy in AppendixB.
Occupancy type and characteristics
Evacuation plan
Refuge areas
Distribution of occupant density
Human life support requirements
Form of detection and alarm
Fire service response-to-alarm
Fire suppression system characteristics
Type of heating, ventilating, and air-conditioning
(HVAC) system
Energy
Building security provisions
Controls
Status of doors during potential fire condition
Potential threatsInternal compartmentation and charac-
teristics
leakage
Exterior
Wind
FLEXIBILITY AN D RESILIENCY
To help ensure smoke management system perfor-
mance, the approaches of flexibility and resiliency can
be employed. The concept of flexibility consists of
using design features that allow for easy adjustment of a
smoke management system in order to achieve accept-
able performance. A resilient system is one that resists
serious adverse effects due to pressure fluctuations.
During the design of a new building, the leakage
paths throughout the building can only be estimated.
Therefore, the smoke management design calculations
constitute only an approximate representation of the
pressures and airflows that will occur as a result of the
smoke management system in the actual building. The
introduction of flexibility into a smoke management
system allows for variations in leakage from the origi-
nally estimated values. Because it is to measure
leakage paths in existing buildings, the concept of flexi-
bility is also useful for retrofit of smoke management i n
existing buildings. In many systems, flexibility can be
achieved by the use of fans with sheaves3 to allow sev-
eral flow rates, a variable flow fan for the same purpose,
or by dampers that can be manually adjusted to obtain
desired pressure differences.
Pressure fluctuations often occur during a fire when
doors are opened and closed and when windows are
opened, closed, or broken. To resist such fluctuations,
resiliency can, be incorporated in a system by use of
A sheave is with aa By exchanging a sheave for
of rotational of the fan
and its flow changed.
-
8/10/2019 Principles of Smoke Management - Printed
17/383
Principles of Smoke
automatic control to reduce the pressure fluctuations.
For example, in pressurized stairwells, automatic con-
trol can be used in the supply fan bypass system to
reduce the effect of opening and closing stairwell doors.
An alternative keep the exterior stairwell door open
during pressurization. This eliminates what is probably
the major source of fluctuations; that the opening and
closing of the exterior stairwell door. The concepts of
flexibility and resiliency are discussed further where
they apply to specific smoke management applications.
SAFETY FACT R S
Smoke management is still a relatively new field,
and it should come as no surprise that there is no -
sensus concerning safety factors, which are commonly
used in many branches of engineering to provide a level
of assurance of system performance. Further, the topic
of factors has attracted little attention in smoke
control design.
Safety factors for sizing fans of pressurization sys-
tems are very different from those intended to maintaina tenable environment in an atrium or other application
based on a hazard analysis. If a pressurization fan is
undersized, it will not maintain acceptable pressure dif-
ferences. This should be apparent and corrected during
commissioning.
Ideally, an analysis of a system intended to maintain
a tenable environment would be based on detailed and
accurate capabilities of simulating smoke transport,
physiological effects of fire-related exposures, human
response to fire, and evacuation analysis. However, this
technology is not so advanced, and these calculations
are of necessity based on a number of conservative
assumptions with conservativedesign parameters. It can
be argued that such conservative calculations may resultin conservative designs even in the absence of any
safety factors. The specifics of the design and the meth-
of analysis would be expected to have a significant
impact on any approach to safety factors.
of the absence of any accepted approaches
to safety factors, this topic is not included in the meth-
ods of analysis of this book.
FIRE SUPPRESSIONSYSTEMS
Automatic suppression systems are an integral part
of many fire protection designs, and the efficacy of such
systems in controlling building fires is well docu-
mented. However, it is important to recognize that whilethe functions of fire suppression and smoke manage-
ment are both desirable fire safety features, they should
not be readily substituted for each other. One of the best
ways to deal with the smoke problem is to stop smoke
production. To the extent that a suppression system
slows down the burning rate, it reduces the smoke prob-
lem. From fires that are suppressed rather than extin-
guished, smoke is produced. This smoke can move
through the building due to various driving forces dis-
cussed in Chapter5. the other hand, well-designed
smoke management systems can maintain tolerable con-
ditions along critical egress routes but will have littleeffect on the fire.
In addition to the fact that the systems dif -
ferent functions, it is important that the designer con-
sider the interaction between smoke management and
fire suppression. For example, in the case of a
sprinklered building, the pressure difference needed to
control smoke movement is probably less than in an
unsprinklered building, due to the likelihood that the
maximum fire size will be significantly smaller than in
an unsprinklered building.
A pressurization (smoke control) system can
adversely affect performance of a gaseous agent (such
as halon, or suppression system when the sys-tems are located in a common space. In the event that
both systems are activated concurrently, the smoke
exhaust system may exhaust the suppressant gas from
the room, replacing it with outside air. Because gas sup-
pression systems commonly provide a single application
of the agent, the potential arises for renewed growth of
the fire.
A general guideline would be that the gaseous agent
suppression system should take precedence over the
smoke control system. An extremely desirable feature in
such spaces would be the ability to purge the residual
smoke and the suppressant gas after the fire is com-
pletely extinguished and to replace them with fresh air.This ability to replace the atmosphere in these spaces in
the post-fire period is very important from a life-safety
viewpoint, since some gas suppressants are asphyxiants
at normal design concentrations.
ENERGY CONSERVATION
The smoke management system must be designed
to override the local controls in a variable air volume
HVAC system so that the air supply necessary to pres-
surize spaces is supplied. Also, if there is an
energy management system or a 24-hour clock
the designer must ensure that the smoke management
system will take precedence over the local control sys-tem so that the necessary air is supplied or exhausted
according to the design approach. It is a good general
rule that smoke management should take precedence
over energy conservation features in both new designs
and retrofits.
-
8/10/2019 Principles of Smoke Management - Printed
18/383
Chapterl-Introduction
SYSTEM ACTIVATION
System activationisprobably the major area of dis-agreement in the field of smoke control. Primarily, this
disagreement is about automatic activation versus man-
ual activation. In the early days of smoke control, there
was general agreement that activationof"pressure sand-wich" systems should be automatic upon alarm from
smoke detectors. Automatic activation by smoke detec-tors located in building spaces has the clear advantage
of fast response.
Some building designers and fire service officials
began to realize that smoke detectors could go into
alarm on a floor far away the fire. Thus, automatic
activation by smoke detectors could result in pressuriza-tion of the zone in which the fire occurred. This would
result in the opposite of the desired operation; that is,
smoke would be forced into other zones. As a result, a
vocal minority of feel that smoke control
should only be activated manually by fire fighters after
they are sure of the fire location. However, many
involved professionals are concerned that such manualactivation could be so late in the fire development that
significant hazard to life and damage to property would
result. Such delayed activation can suddenly transport a
body of smoke that is highly charged with unbumed
hydrocarbons, carbon monoxide, and other toxic gases
and depleted of oxygen to remote locations. This can
result in a wave-like movement of toxic gases or flame
to remote areas.
The most recent view on the subject is that zoned
smoke control should be automatically activated by an
from either heat detectors or sprinkler water flow.
This can only be accomplished if the detector or sprin-
kler zones are compatible with the smoke control zones.
Using heat detector or sprinkler flow signals for activa-tion increases the likelihood of proper identification of
the fire zone. For smoldering fires, this approach would
result in a significantly longer response time, and smoke
detectors would probably be better suited for applica-
tions where smoldering fires are of particular
However, for flaming fires, it is believed that the
response time with this approach would be short enough
so that significant benefit would be realized by the oper-
ation of the smoke control system. It is hoped that
advances in smoke detector technology and application
will significantly improve the ability of these detectors
to positively identify the fire zone.
Throughout all of this controversy, there has been
complete agreement that zoned smoke control should
not be activated by from manual stations (pull
boxes). The reason can be illustrated by the scenario ofa
man who, while observing a fire on an upper floor of a
building, decides that the first thing he should do is to
get out of the building. On the way down the stairs, he
thinks of his responsibility to the other occupants. He
stops on a lower floor long enough to actuate a manual
station. If that alarm activated thesmoke control system,
the wrong zone would be identifiedas the fire zone.
Because of the long response time and the mainte-
nance problem of clogging with airborne particles, it is
generally agreed that smoke detectors located in HVACducts should not be the primary means of smoke control
system activation. A means of activationof higher
ability and quicker response time is needed. However,
an alarm from a duct-located detector can be used in
addition to such a primary means of activation. A signal
only this secondary means might be unusual, but it
should be able to activate the smoke control system.
Most stairwell pressurization systems operate in the
same manner regardless of where the fire is located.
Therefore, it generally is agreed that most stairwell pres-
surization systems can be activated by the alarm of any
fire alarm-initiating device located within the building.A possible exception to this is large buildings with hori-
zontal separations, such that smoke is not expected tohave an impact on some stairwells remote from the fire.
It is recommended that zoned smoke control sys-
tems be equipped with a remote control from
which the smoke control system can be manually over-ridden. This should be easily identifiable and
accessible to the fire department. Such a remote control
allows fire fighters to change the mode of smoke
control system operation in addition to system shut-down. Activation of smoke management systems for
atria and other large spaces is addressed in Chapter
RELIABILITY OF SMOKE MANAGEMENT
The intent of this section is to provide insight intothe need for acceptance testing and routine testing and
the relative importance of system simplicity: The fol-
lowing should not be thought of as an exhaustive treat-ment of smoke management reliability. Due to the
of obtaining data about the reliability of com-ponents of smoke management systems, the simple cal-
culations that follow are only very rough estimates.
However, it is believed that the insight gained justifies
this treatment despite these limitations. Further, the
same reliability concerns that apply to smoke manage-
ment systems apply to all life safety systems, and the
following discussion may be of general interest beycnd
smoke management.
The discussion is limited to series systems, which
are systems that operate only if all the components oper-ate, as is true of many smoke management system
designs. Redundancies (such as backup power) are not
included in this analysis. The reliability, R, a series
-
8/10/2019 Principles of Smoke Management - Printed
19/383
Principles ofSmoke Management'
Table1.1:
EstimatedSystem Reliabilityfor NewSmokeManagement
SystemThat Has Not Been Commissioned
No. of HVAC No. of Other of
System System Fans Components Before Commissioning System (months)
1 0 0.97 162 0 3 0.83 46
3 3 9 0.56 14
4 5 18 0.31 8
5 5 54 0.03 3
1. Systemreliabilities calculated Equation For purposesof these calculations, the of fansof a forced airHVAC system weretaken as 0.99, andother components were taken as 0.94.
2. Mean lives calculatedfrom Equation(1.3). For purposesof thesecalculations. the failure rates of fans of a forcedairHVAC system were takenas
per hour, and other components were taken as per hour.
system is the product of the of
ponents.
Usually, discussions of reliability progress from this point
with the assumption that all components operate initially
and that failures occur with time after system installation.
For this assumption to be appropriate, a program of accep-
tance testing and defect correction is necessary. Such com-
missioning must include an installation check of all
components, tests of system during all modes
of operation, repairof defects, and retestinguntil all defects
are corrected. Current construction practices are such that
system commissioning is not always this exhaustive. For
this reason, attention is first given to reliability of systems
without commissioning followed by a discussion of reli-
ability of systems for which all components operate after
commissioning.
RELIABILITY BEFORECOMMISSIONING
For newly installed components, the reliability can
be thought of as the likelihood that the component will
both be installed properly and be in good working con-
dition when it is delivered to the construction site. There
are an enormous number of errors that can occur during
manufacture, transportation, storage, and installation
that can cause a component to fail to operate.
such as motors wired for the wrong voltage, not
connected to power, dampers failing to close, fans run-
ning backward, holes i n walls, and automatic doors fail-
ing to close have been observed in newly built smoke
management systems. Based on experience
testing of smoke management systems, it is estimated
that the reliability of components i n noncommissioned
systems is0.90 or An consideration
regarding the of a component in a
missioned system is if that component is part of an
HVAC system. In hot or cold weather, building occu-
pants demand that the HVAC system provide comfort
conditions. Thus, for a new building in extreme weather,
it can be considered that the reliability of the HVAC sys-tem fan will approach unity. Based on field observa-
tions, it is believed that other components will have a
lower reliability. The following reliabilities were chosen
for example calculations for new systems that have not
been commissioned:
Fans of a forced air HVACsystem 0.99
Other components 0.94
These values were arbitrarily selected, but the rela-
tive values between them are based on the discussion
above. Table I . lists calculated reliabilities of such sys-
tems made up of many components. It can be observed
from this table that the more components a system has,the less likely the system is to operate before it has been
commissioned. The most reliable new system would be
one that only uses the HVAC system fans. A large com-
plicated system consisting of many components (Table
1.1, system 5) has very little chance of operating before
commissioning. The trend of lower reliability for com-
plicated systems agrees with observations of the author
during field tests of systems of various
degrees of complexity. Probably the most important
point to be made from this discussion is the need for
commissioning of new systems.
MEAN LIFE OF COMMISSIONED SYSTEMS
For this discussion, all system components are con-
sidered to operate-at the end of the commissioning pro-
cess. A commonly used relation for the reliability of
components is the distribution,
= .
-
8/10/2019 Principles of Smoke Management - Printed
20/383
Chapterl-Introduction
I I " ICircuit Breakers
IMechanical
Large
IEq
Figure 1.8 Typical ranges rates Lees[ I
where is the failure rate of the component. The mean
life, L, of a system is
Some typical ranges of failure rates of some
ponents and systems are shown in Figure It can be
seen that failure rates vary over large ranges and that
failure rates vary considerably with equipment type. It
seems that the failure rate of HVAC system fans would
be lower than those of other components. If these fans
fail, building desiring heating o r cooling tend
to put pressure on maintenance personnel to get fans
repaired quickly. Smoke management systems are only
needed for a short time over the life of a building. Thus,
when an HVAC system fan is called for smoke
management duty, it seems that it will be more likely to
operate than other components. To account for this, the
effective failure rate of HVAC system fans can be
thought of as being much smaller than other compo-
nents. The following failure rates were arbitrarily
selected for example calculations, but their relative val-
ues are based on the above discussion:
Fans of a forced air I-[VAC system per hr
Other components per hr
Table 1. 1 shows mean lives of systems composed of
various numbers of components. It can be observed that
systems composed of a fewcomponents have long
lives, while those made up of very components
have short lives. This tends to support the view that sim-
ple systems are more reliable, and this view is supported
by in the field. However, it should be cau-tioned that systems should not be overly simple; that is,
they should have the features needed to achieve desired
performance at likely conditions during a fire. Further,
the above simple analysis did not include the beneficial
effects of redundancies. However, it is safe to conclude
that unnecessary system complexities should be
avoided. The mean lives listed in Table also indicate
that routine testing and repair of smoke management
is needed so that the systems will probably be
in good working order when they are needed. A similar
statement can be made concerning all life safety sys-
tems.
-
8/10/2019 Principles of Smoke Management - Printed
21/383
CHAPTER2
Fire and Heat Release
Probably the most important aspect of a building quences of a fireafter ignition but not with the causes of
fire is the heat release rate (HRR). The tempera- Ignition.
ture and amount of gases produced by a fire are Growth: After ignition, fire growth is determinedthe burning, with influence from
models use the HRR as input. When characterized by an
of air for the fire. Figure 2.2 shows an officefire starting in a corner of an upholstered chair andabout the size of a fire or how big a fire is, they almost
always are referring to the HRR. Other indicators of fire
size are the fire area and fire perimeter, but neither of
these is commonly used to depict how big a fire is in the
predictive models that have gained a high level of
acceptance in recent years. For these reasons, the term
size is used in this book to HRR.
The intent of this chapter is to provide basic
i about fire size and development that should be
helpful concerning evaluation and ofI design fires. A design fire is the challenge that a smoke
management system is designed to withstand. Because
the presence of sprinklers often plays a role in the
mination of a design fire, sprinklers are also included.
The design fire can be a steady fire or an unsteady one.
While the steady fire is not physically realistic, it can
result in very conservative designs and it can simplify
design analysis.
STAGES OF FIRE DEVELOPMENT
Fires in rooms or other compartments are oftendescribed in terms of the stages of fire development,
shown in Figure 2.1. These stages are useful in discuss-
ing fires, but many fires do not go through all of thesestages due to lack of fuel or the action of a suppression
system.
Ignition: Ignition is the period during which thefire begins. management deals with the
growing until it spreads to other objects. As the firegrows, the temperature in the room rises. A fire with
sufficient combustion air is called a fuel fire,and such a fire is also referred to as burning a ir .
Flashover: In engineering, most processes of inter-est consist of gradual changes, but flashover is an excep-tion. is a sudden change from an apparentsteady fire confined to a relatively small space to a fire
that involves a much larger space, such as the entireroom.For the office fire of Figure (c), materials
throughout the room are subject to thermal radiation
from the Flames and the smoke layer under the ceiling.When this radiation is sufficiently high, some of thesematerials ignite. This is followed by other materials
I I I
I Post FlashoverI II I
I II I
Dewy
Time
Figure
-
8/10/2019 Principles of Smoke Management - Printed
22/383
Chapter2-Fire and Heat Release
(a)Fire restricted to inside corner of chair and resulting in smoke layer under ceiling
-
8/10/2019 Principles of Smoke Management - Printed
23/383
Principles of Smoke Management
Table 2.1:ApproximateValues of CO
Yield for Room
CO
Flamingfires in"free air" 0.04
Fully involved fire (in a roomwithout 0.2materialson ceiling or upper portionof walls)***
These estimates are based onand (2002).
is in CO produced per of fuel burned (org ofCO
produced pergof fuel burned).Fully involvedfires in rooms withcellulosic materials (wood,paper, cardboard, etc.)on ceilingor upper of wallsareexpected to have COyieldsseveraltimes higher
igniting, and then the entire room is involved in fire.Once a fire gets to the stage depicted in Figure 2.2 (c), itonly takes a few seconds for a room to flashover.
In a very large room, such as an open floor
plan, only a portion of the room may flashover. The
smoke layer temperature at which flashover occurs is
generally in the range of 930F to 1300F (500C to700C). The criteria for flashover is sometimes taken to
be a smoke layer temperature of (600C) or a
radiant heat flux of 1.8 (20 at the floor
of the fire (Peacock et al. 1999).
Fully Developed Fire: This stage of fire develop-
ment has the highest temperatures. For small and
medium rooms, the HRR of a fully developed fire
depends on the amount of air that reaches the fire. Such
a fully developed fire is ventilation
In a ventilation controlled fire, more volatile gases
are produced by the burning materials than can be
bumed in the room with the oxygen available, and the
fire can be characterized by flames consisting of burn-ing volatile gases extending from open doonvays of the
fire room. For very rooms, as in an open office
floor plan, the fire may not ever become ventilation con-
trolled. Fully developed fires are characterized by
cient combustion and high production of CO (Table
2.1).
Decay: As the fuel is consumed, the HRR of the
fire and the temperature of the room drop. The fire may
change from ventilation controlled to fuel controlled.
Strictly speaking, the term post-flashover
includes both fully developed and decay stages, but the
is often used to mean a fully developed fire.
MEASUREMENTOFHEAT RELEASE RATEIn the early days of fire research, of
the HRR during a fire was very crude. Typically, materi-
als were burned on a load cell (scale), and the HRR was
estimated from the mass loss and the heat of combustion
of the material. If the load cell became too hot, mass
MeasureTemperature,Flow Rate, GasConcentrations.
Figure2.3 Open air calorimeter:
measurements would be meaningless. Various schemes .
to keep the load cell from heating up were devised, but
they all interfered to some extent with the measure-
ments. The situation was even worse when pieces of
burning material would fall from the load cell.To further exacerbate the difficulties with such
HRR determinations, many items burned are composites
of several different materials, each with its own heat of
combustion. For example, a desk might be made of
wood, fiberboard, sheet plastic and molded plastic
doors, and drawer fronts. Not only do these materials
have different heats of combustion, but they burn at dif-
ferent times during the course of a fire. For these rea-
sons, an HRR estimated from measured mass losses is
often unreliable.
Oxygen Consumption
In the fire research laboratories around theworld worked to develop a method of calorimetry that
was not subject to the problems of the old method dis-
cussed above. The new method is based on the osygen
used upin the fire and is called
(and sometimes depletion
While oxygen consumption calorimeters often have
load cells, the measurements from these cells are for
information and not for calculation of the HRR.
The key to this technology is that the heat released
per unit oxygen consumed is almost a constant for most
materials. Huggctt (1980) found that this heat release
constant is 5,630 Btu per Ib of oxygen
MJ per kg of oxygen consumed). For most materials
involved in building fires, this constant has an uncer-tainty of about 6%.
Figure 2.3 shows a calorimeter where furniture is
burned under a hood connected to an exhaust, such that
all the is drawn into the exhaust. From measure-
ments of the mass flow of exhaust and the content of
-
8/10/2019 Principles of Smoke Management - Printed
24/383
2- and Heat Release
MeasureTemperature. Flow Rate,and GasConcentrations.
SmokePlume
Front View
Figure2.4 Room calorimeter:
the exhaust, the time rate of consumption can be cal-
culated. From this, the HRRcan be calculated. Because
some of the is not completely consumed, gas mea-
surements also include CO and Parker (1982) pre-
sents equations for calculation of the for various
applications.
consumption calorimeters are calibrated by
burning a gaseous fuel (methane, propane, etc.) at a
measured flow rate. The uncertainty of the calorimeter
depends on the uncertainties of (1) the operation of the
calorimeter, (2) the calorimeter calibration process, and
(3) the heat release constant. Calorimeter operation is
not always as intended. Some of the smoke may not be
captured by the hood, or burning materials may fall off
the fire and away from the calorimeter. With such unin-
tended operation, uncertainties in excess of 20% could
result. For a well-calibrated calorimeter operated as
intended, the uncertainty of measured HRR may be in
the neighborhood of 10%. For more information about
the uncertainty of consumption calorimeters, see
et al. (2000).
Open air calorimeters (Figure 2.3) are sometimes
called furniture calorimeters because theyare often used
for furniture. However, they can be used for any fuel
package provided that all of the smoke from the fire
is collected, and (2) the heat released does not damage
the calorimeter including the pollution control equip-
ment. Typically, these calorimeters are located indoors
to protect the fire from the wind. The hoods are usually
to 20 (3 to G m) square, but the size is only con-
strained by the practicalities of construction.Other types of consumption calorimeters are the
room calorimeter and the cone calorimeter. The room
calorimeter (Figure 2.4) is used when the effects of the
walls and ceiling on the HRR are to be
Section View
Time
Figure2.5 Three kiosk
of materials (data
[I
cant. The cone calorimeter is a"bench scale" laboratoryinstrument developed at NIST (Babrauskas 1990).
HRROF SOME OBJECTS
When duplicate objects are burned, there are devia-
tions in HRR as illustrated with the three kiosk fires of
Figure 2.5. These kiosks are for selling T shirts. The
deviations of HRR are due to a number of factors,
including (I ) minor variationsi n arrangement of the T-
shirts, (2) variations in composition of T-shirts, (3) vari-
ations in the dimensions of the kiosk, (4) variations in
materials of the kiosk, and (5) variations in the air cur-
rents near the kiosk. However, the shapes and peak
HRRs of kiosk curves are similar.
Figures 2.6 to 2.19 show HRRs of other objects. The
peak HRR of Scotch pine Christmas trees burned byStroupet al. (1999) were in the range of' to 5000
(1900 to 5300 kW), as shown in Ahonen et
-
8/10/2019 Principles of Smoke Management - Printed
25/383
-
8/10/2019 Principles of Smoke Management - Printed
26/383
Chapter2-Fire and Heat Release
looc
0360
l ime
Figure2.11 Upholstered chair with
padding and weighing 25 (11.5 kg)
(datafroni et
00 300 600 900 1200 1500 1800
lime
Figure2.1 2 foam
and 62 (28.3
et al. 9841).
Figure 2.13Sofa padding
et al.
Figure2.14 Metal wardrobe cotton
(data al.
Time(S)
Figure Wardrobe of 0.5in. (12.7
et al.
8000
Unfinished
Fire Retardant 6000. Paint:
4000 2Coats 4000
KI
2000
., .
Figure2.16 of in.(3.2
cotton
et al.
-
8/10/2019 Principles of Smoke Management - Printed
27/383
Principlesof Smoke Managemerit
20 W
15001500.
m,I
500 I
500
01200 1800 2400
lime Time(min)
Figure2.17Two-divider workstation with Figure2.19Automobiles(data from Joyeux
tional desk and credenza (data from
Madrzykowski and Vettori
lime
Figure2.18Three-divider with an open
top and shelf (data from
tion from other spaces. The workstation(Figure 2.17) has a peak HRR of 1700 (1800 kW)at The three-divider workstation (Figure 2.18) has
a peak HRR of 6400 (6800 kW) at 550 A
reason for the higher HRR of the three-sided
tion is probably the increased radiation feedback from
the additional divider and the shelves. For further infor-mation about the HRRs of workstations, readers arereferred to Madrzykowski
Figure shows HRR data of automobiles mea-sured by Joyeux 997). Joyeux showed that cars made
in the had a higher HRR than those made earlier,and this may be due to increased use of polymers and
other materials.-Because of these higher
HRRs, a car fire in a parking garage can ignite an adja-cent car.
Cribs and piles of wood pallets are used in research
and testing when reproducible solid fuel fires are needed(Figures 2.20 and 2.21). Cribs are geometrically
arranged piles of sticks. The crib shown in Figure 2.20
Figure2.20Crib of geometrically arranged
was used for tests of the smoke management system atthe Plaza Hotel (Klote 1990). This crib was made of
wood sticks, in. (38 mm) by 1.5 in. (38 mm) by 2 ft(0.61 long, and it had a peak HRR of aboet 1400
(l kW) when burned in free air. The stack of
nine wood pallets shown in Figure has a peak HRR
of about 3,500 (3,700 kW) when burned in free
air. Gross ( 1 Block( 197 and Walton (1988)burned cribs of various sizes and stick
Babrauskas (2002) provides heat release data of cribsand pallets.
VENTILATION-CONTROLLED FIRES
As already stated, the HRR of a
trolled fire depends on the amount of air that reaches thefire. Further, the HRR can be expressed as a function of
the openings to the fire room as
where
-
8/10/2019 Principles of Smoke Management - Printed
28/383
Chapter2-Fire and Heat Release
Q = heat release rate of fire, kW
A, area of ventilation opening, f? (m2);
H, = height of ventilation opening, (m);
=
Equation (2. l )appiies to rooms of construc-
tion and size with only one rectangular opening. Figure2.22 shows the ofa ventilation-controlled fire as a
function of width of the door or other opening. Equation
(2.1) provides useful estimates for rooms made with
normal construction materials concrete, wood,
etc.), but it is not appropriate for metal rooms, such as
on a ship with steel decks and bulkheads. For large
rooms (over 300 [30 the appropriateness of
Equation (2.1) is questionable. For information about
the effects of construction materials and room sizes, see
Walton and 995).
For a number of rectangular openings with the same
bottom and top elevations, the heights are the same, and
the effective area is the sum of the individual areas.
where
A , effective area of all the ventilationopenings,ft2
area of ventilation opening from = to
(m').
This is illustrated for two openings in Figure 2.23.
Figure2.2 Stacko f
Example 2.1 Ventilation-Controlled Fire
For a roomwith a single doorway opening that is fullyinvolved in how big will the fire be? The doorway open-ing is 3 (0.914m)wideby7 (2.13 high.H,=7 (213 m);A, = =21
thetire is ventilation controlled, Equation (2.1) isapplicable.
Q
SPRINKLERS
Figure illustrates t-squared fire growth with
the three possible responses to sprinkler spray: (a) sprin-
klers overpowered by fire, (b) constant and (c)
reduction ofHRR. Sprinklers can be overpowered by an
extremely fast growing fire due to burning materials that
exceed the sprinkler design. Sprinklers can also be over-
powered when the smoke reaching the sprinklers has
cooled due to plume entrainment, happen with
fires in spaces with ceilings that are relatively high com-
pared to the arrangement of fuel. For this to happen, the
Door
DoorWidth
Figure 2.22 HRR a
medium-sizedroom
Foropenings with the same andbottom elevations.A,
Figure2.23Combining openings
of sizeo f
-
8/10/2019 Principles of Smoke Management - Printed
29/383
Principles of Smoke Management
Time
(a) SprinklersOverpowered by Fire
I
Conservative Estimate
of Constant HRR
Time
(b) Conservative Estimate of ConstantHRR After Sprinkler Activation
Time
(c) Fire Decay After Sprinkler Activation
Figure2.24 Interaction between and sprinklers.
flame height is typically less than the ceiling height, androom air cools the gases in the
plume. Methods of calculating the plume temperature
are in Chapter 13. If the sprinklers do activate, the spray
could evaporate before the droplets reach the fuel.
DECAY DU ETOSFRINKLERS
A constant HRR after sprinkler actuation is a con-
servative estimate for many applications. Fire
after sprinkler actuation is more realistic. Fire decay can
be expressed as
where
= post sprinkler actuation HRR, kW
= sprinkler actuation, kW
t = time from ignition,
= time of sprinkler actuation,
= time constant fire suppression,
For a number of fuel likely to be found in
offices, and (1992) conducted
sprinklered fire experiments with a spray density of
(0.07 of water. They determined that a
fire decay curve with a time constant of 435 had ahigher HRR than most of the sprinklered fires (Figure
2.25). Evans (1993) used these data and data for wood
crib fires with sprinkler spray densities of
(0.041 and 0.097 (0.066 from
(1976) to develop the following correlation:
where
= spray density,
C, = 6.15
While Equation (2.4) has not been experimentally
verified, it does allow us to adjust the decay for
sprinkler densities other than those of
Sprinkler Response
While the information in this section is primarily
about sprinklers, it also applies to vents actuated by fus-
ible links and fixed temperature detectors.
The responsiveness of sprinklers is tested by the
plunge test, where a sprinkler is into a heated
in which heated air is circulated. The of
the plunge test is mathematically the as that o f a
small piece of hot metal suddenly quenched in a cool
fluid, as described in heat transfer textsand This analysis is based on
the assumptions that (I ) the internal resistance of the
sprinkler is negligible, (2) the sprinkler is instanta-
neously put the oven, (3) the convective heat transfer
is constant, (4) the gas temperature i n
-
8/10/2019 Principles of Smoke Management - Printed
30/383
Chapter 2-Fire and Heat Release
oven is constant, and the only heat transfer is from
the sprinkler to the gas.
The temperature of the sprinkler increases
as shown in Figure The time constant, of
the sprinkler is
where
=
m =
C =
h, =
A =
time constant,
mass of the sprinkler, (kg);
specific heat of the sprinkler, "F "C);
convective heat transfer "F
surface area of the sprinkler, (m2).
. The time constant, is the time at which the tem-
perature of the sprinkler has reached 63% of the way to
thegas temperature. The convective heat transfer
cient varies with velocity, so that the time constant alsovaries with the velocity at which it is measured.
The response time index (RTI) was developed as a
measure of sprinkler responsiveness that is independent
of velocity.
where is the velocity,
In the plunge test, the to actuation and the gas
velocity are measured. Then the time constant can be
calculated from the to actuation, and the RTI is
calculated from Equation The RTI of standsrd
sprinklers varies from about 140 to 280
to 155 and the RTI of quick-response sprin-
klers (QRS) varies from about 50 to 100 (28 .
to 55
The response time index does not account for con-
ductive heat transfer from the sprinkler. To account for
conduction, a virtual RTI can be calculated as
RTI,
where
RTI, = virtual RTI,
= conductivity factor,
. .
'I:is time constant
Time
Figure2.26
Paper Cart Fuel PackageSecretarial Desk Fuel PackageExecutiveDesk Fuel Package
. Office Fuel PackageI Fuel Package
Sofa Fuel. Work Station I Fuel Package-- Work Station Fuel Package
Wood Cribs
0 200 400 600 800
Time, t-
Figure 2.25 to a of
(0.07
-
8/10/2019 Principles of Smoke Management - Printed
31/383
Principlesof SmokeManagement
Actuation
Actuation depends on gas temperature and velocity
near the sprinkler. In a fire, a jet of hot gases flows
ally from where the smoke plume intersects the ceiling.
Computer programs have been developed that use corre-
lations for such a ceiling jetto predict actuation time.
The program DETACT-QS (Evans and Stroup
1986) assumes that the thermal device is located ina rel-
atively large area, that only the ceiling jet heats the
device, and that there is no heating from the accumu-
lated hot gases in the room. The required program inputs
are the height of the ceiling the fuel, the distance
of the thermal device from the axis of the fire, the actua-
tion temperature of the thermal device, the response
time index (RTI) for the device, and the rate of heat
release of the fire. The program outputs are the ceiling
gas and the device temperature, both as a
function of time and the time required for device actua-
tion. DETACT-T2 (Evans et al. 1986) is similar to
DETACT-QS, except it is specifically for t-squaredfires. Several zone fire models (such as FAST,
and JET) are capable of calculating ceiling jet
temperatures and predicting actuation (Chapter 8).
DESIGN FIRES
A design fire curve is the description of the devel-
opment of a design fire that can be used in a fire sce-
nario. The curve is for HRR as a function of time. This
curve can be as simple as a constant, and it can also be a
simple function of The design fire curve can also
be a complicated sequence of lesser for some or
all of the stages of tire development described at the
beginning of this chapter.
A fire scenario includes more than just the design
fire curve. The word means an outline of
events, asi n a play or other theatrical production. A fire
scenario can be thought of as the outline of events and
conditions that are critical to the outcome
of alternative designs. In addition to the HRR and fire
location, a scenario could include the type of materials
burned, airborne toxicants and soot produced, and peo-ple movement during fire.
are not intended to be located in the space are referred to
as
A few examples of transient fuels are Christmas
decorations, paint and solvents in stairwells during
redecorating, unpacked foam cups in cardboard boxes
after delivery, cut up cardboard boxes awaiting removal,
and closely stacked upholstered furniture after delivery.Sometimes, transient fuels remain in place for long peri-ods. Some examples are a number of polyurethane
mattresses delivered to a dormitory and waiting for dis-tribution in the next school year, (2) automobiles on dis-
play in a shopping mall, (3) boats and campers on
display in an arena, and (4) a two-story colonial house
built for display inside a shopping mall.
Transient fuels must not be overlooked when select-
ing a design fire. One approach to incorporating tran-
sient fuels in a design fire is to consider the fire
occurring over 100 (9.3 m2) of floor space with a
heat release rate density of 20 Btuls ft2
(225
This amounts to an allowance for transient of 2000
(2100 kW).
Steady Fires
It is the nature of fires to be unsteady, but the steady
fire is a very useful idealization. Steady fires have a con-stant heat release rate. In many applications, use of a
steady design fire can lead to and con-
servative designs.
HRRper Unit Area
Morgan (1979) suggests a typical rate of heat
release per unit floor area for mercantile occupancies of
44 (500 Fang and Breese (1980)determined about the same rate of heat release for resi-dential occupancies. Morgan and Hansell (1987) and
Law (1982) suggest a heat release rate per unit floor
area for office buildings of 20 f? (225
For smoke management applications, a heat release rate
per floor area of 20 Btuls ft2 (225 is suggested
for restricted fuel spaces, and 44 Btuls ft2 (500
is suggested for spaces with furniture, wood, or other
combustible materials. A occurring over 100 (9.3
m2) of floor space would result in 2000 Btuls kW)
for restricted fuel space and 4600 kW (4400 Btuls) fora
space with The heat release densities ofIn many spaces, the fuel loading is severely
Table 2.2 can be useful in determining design fires.restricted with the intent of restricting fire size. Such
spaces are characterized by interior finishes of metal,
brick, stone, or gypsum board and furnished with Unsteady Fires
objects of similar materials plus plants. Even for Fires frequently proceed through an incubation
such a space, there can be an almost period of slow and uneven growth, followed by a period
unlimited number of objects that are in the of established growth as illustrated in Figure 2.27 (a).
space for short periods. Such combustible materials that Figure 2.27 (b) shows that established growth - is often
-
8/10/2019 Principles of Smoke Management - Printed
32/383
-
8/10/2019 Principles of Smoke Management - Printed
33/383
wheretis considered the time from effective ignition. For
I-Punits, the following form of Equation (2.9) is
used:
where
Q = heat release rate of fire,
time after effective ignition,
= growth time,
When = Equation (2.10) gives a value ofQ =
Table 2.3 lists fire growth values from
NFPA 92B (NFPA 2000) and NFPA 72 (NFPA 1999).
The fire growths corresponding tothe NFPA values
are shown on Figure 2.28. Unless otherwise stated in
this book, the terms slow, fast, and fast
fire growth refer to the NFPA 92B values.
Fuel Package Approach
The base fuel package is the maximum probable
size of package that is likely to be involved in fire
for a specific application. A fuel package can be made
up of a number of fuel items (sofa, chair, bed, table, cur-
Time,t
(a) Typical HRR curve
Time,t
(b) Idealized Parabolic curve
2.27 Fire
Principles of Smoke Management
tains, The key to selecting the items that make
the base package is that the radiant flux bum-
ing one of the items will lead ignition of the other
items in the base package but not to ignition for
items outside the base package.
The point source radiant model (Figure 2.29) con-siders the flame as a small thermal source such that the
intensity of thermal radiation is proportional to the
inverse of the square of distance from the source. Ther-
mal radiation also is calledradiant
The intensity of thermal radiation is
where
intensityof thermal radiation,
= radiant releaseofthe fire, (kW);
R = distance from the of the fire, ft (m).
Table 2.3:
Fire Growth Constants for T-Squared Fires
NFPA 92 8
Slow
Thin Plywood Corrugated Cardboard
Cartons1.5 (4.6m)High -Various: Contents
0 200 400 600 800
Medium
Fast
Fast
TimeFrom
Figure2.28 of
0.002778 0.002931
0.01 0.01 127 300
0.04444 0.04689
0.1778 0.1878 75
400
150
NI A
-
8/10/2019 Principles of Smoke Management - Printed
34/383
Chapter2-Fireand Heat Release
OrientedFire Normal
The point source model is a goodapproximationprovided thatR
Figure2.29Point sourceradiation model.
The point source radiant model is appropriate pro-
vided that the distance from the of the flame is
greater than twice the diameter of the fire (R The
radiant heat release of the fire is
where
Q heat releaserateof the fire, (kW);
= radiativefraction.
Heat transfer a is by conduction, con-vection, and radiation. For most fires, conductive heat
transfer from the is negligible. The radiant frac-
tion can be expressed as
where is the convective fraction.
The radiative fraction depends on the material
burned and the diameter of the fire, and the radiative
fraction varies from about 0.1 to 0.6. Low sooting fuels,such as methanol, have low radiative fractions, and high
sooting materials, such as gasoline and polystyrene,
have high radiative fractions. However, for design appli-
cations, values of 0.3 and = 0.7 are common.
The idea of separation distance is useful evalua-
tion of what items should be in the base fuel package.Using the point source radiant model, the separation dis-
tance is
where
= separation distance from the ofthe fire to
a target, (m);
= intensityof radiation needed for
ignition,
Fuel items less than away from the fire would
be expected to ignite, and fuel items farther than
away would not be expected to ignite. The radiant flux
needed for nonpiloted ignition varies from about 0.9(10 for thin easy-to-ignite materials to
1.8 (20 for thick materials.
For a fire, the heat release rate, that results in
ignition of an object at a distance ofR away is
For radiant heat transfer where R is less than twicethe diameter of the fire, a method other than the point
source model is needed. Several texts have general
information about radiant heat transfer and
1992; lncropera and 1985; Kreith 1965).
For information about radiant heat transfer of fire, read-ers are referred to Quintiere
and and Croce (1995).
-
8/10/2019 Principles of Smoke Management - Printed
35/383
-
8/10/2019 Principles of Smoke Management - Printed
36/383
Chapter2 andHeat Release
Sofa Sofa
Chair2Note:R, m)
Figure2.30 the of
Example
time(a) Draw curveforsofa 1,and ignitionpointof chair
. .
(b) Draw for chair
4000
Time(c) Locate ignition point and draw curve for sofa 2
Time(d) Get base fuel package by adding the 3 othercurves
Figure2.31Graphic of base
package Examnple2.2.
-
8/10/2019 Principles of Smoke Management - Printed
37/383
CHAPTER3
Smoke and Tenability
In this book, the term is used in accordance ard. Frequently, people become disoriented in fire
the definition of NFPA 92A (2000) and NFPA tions because they cannot see through heavy smoke. If92B which states that smoke consists of the they remain in the building too long, they fall victim to
airborne solid and liquid particulates and gases evolved exposure to toxic gases or elevated temperatures. Fur-
when a material undergoes pyrolysis or combustion, ther, in buildings with balconies, smoke obscuration can
together with the quantity of air that is entrained or result in fatal falls.
mixed into the mass. The products of combustion
usually include particulates, unburned fuel, water
carbon dioxide, carbon monoxide, and some other toxic
and corrosive gases. As smoke moves through a build-
ing, air mixes into the smoke mass and the concentration
of combustion products in the smoke decreases. Includ-
ing air that is entrained or othenvise mixed facilitates
discussions about fire smoke management in atriums
and other spaces. Generally. smoke is thought ofas
being visible, but the above definition includes
Smoke management systems can be designed with
the objective of providing a tenable environment in the
means of egress or at other locations during evacuation.
Such a tenability system needs to be designed to meet
tenability criteria. Such criteria need to include expo-
sure to toxic gases, heat, and thermal radiation. Further,
the criteria often include visibility. As discussed at the
end of this chapter, criteria for a tenability design
depend on the specific application.
ble produced by burning of materials that pro-
duce little or no particulate matter, such as hydrogen,
natural gas, and alcohol.
Information about smoke hazards is useful in
effects of small quantities of smoke migrating
into "protected spaces," and it is useful in evaluating the
consequences of smoke migration without smoke pro-
tection. This chapter concentrates on hazards due
to toxicity, temperature, and smoke obscuration. The
hazards of temperature consist ofhear which
can occur when a person comes into bodily contact with
hot gases, and can
occur a person receives thermal radiation from
flames or hot smoke that are some distance away from
the person.
Many different methods of expressing smoke
obscuration are used in fire science and fire protection
engineering, and this section discusses the common
methods. There is a lack of uniformity concerning
smoke obscuration, and some engineering publications
use different terminology or have different mathemati-
cal definitions for the same terms. These differences
could result in significant errors, and readers are
ticned to take care to verify the exact meanings of
obscuration terms used in other publications. The termi-
nology that follows was selected with the intent of beingconsistent with technical publications in this field.
Exposure to toxic gases, heat. and thermal radiation The fraction of light transmitted through the
can be a direct hazard to life, and reduced visibility due length of smoke is called thetransniittance and is writ-
to smoke obscuration can be a significant indirect haz- ten as
-
8/10/2019 Principles of Smoke Management - Printed
38/383
-
8/10/2019 Principles of Smoke Management - Printed
39/383
Principles of Smoke Management
Table 3.1:Comparison of Differ