PRESENTATION ON
PROCONTROL SYSTEM PROCONTROL SYSTEM ARCHITECTURE
BY E.K.C. ARORA & AJAY GIRI
70FV01 70FV0170FV05 70FV05
70FA01
70FA01
WSPOSE
SERVER 1 SERVER 2
HUB 1 HUB 2
OWS 1 OWS 1 OWS 1 OWS 1��������������� ������������ ���������
70FA01
70FA01
DIAGNOSTICSTATION
70FA01
70FA01
XV
XV
IPB # 1
IPB # 2
INDIVIDUAL CONTROL
MCC
~
ANALOGINPUT
ANALOG OUTPUT
BINARYINPUT
BINARY OUTPUT
EP
BUS ENDMODULE70BA01
BUSCOUPLER70BK02
BUSCOUPLER70BK02
BUS TRAFFIC DIRECTOR
70BV05
PROCESSOR70PR05
LOCAL BUSSTATION
PROCONTROL
PROCONTROL IS MICROPROCESSOR BASED INTELLIGENT REMOTE
MULTIPLEXED SYSTEM DESIGNED MULTIPLEXED SYSTEM DESIGNED ON
MODULAR BASIS.
FEATURES
� SIGNAL CONDITIONING AND TRANSMISSION.
� MODULATING CONTROL.� MODULATING CONTROL.� ON/OFF LOGICAL/SEQUENTIAL CONTROL.� INDIVIDUAL AND PROCESS PROTECTION.� MAN PROCESS INTERFACE.
DESIGN CONCEPT
PROCONTROL UTILISED SERIAL DATA BUS TECHNIQUE WHICH PROVIDES
� VERY HIGH DATA TRANSMISSION SPEED FOR REAL TIME CONTROL.TIME CONTROL.
� PURELY CYCLIC MODE OF OPERATION.� REDUNDANT,FAULT TOLERENT,MULTI CHANNEL
STRUCTURE.� DISTRIBUTED CONTROL SYSTEM CONFIGURATION
FOR� FUNCTIONAL DISTRIBUTION OF CONTROL FUNCTION� GEOGRAPHICAL DISTRIBUTION OF CONTROL FUNCTION.
MAIN CHARACTERITICS
� MODULAR HARDWARE AND SOFTWARE.� EXTENDED POSSIBILITIES.� SIMPLE SYSTEM CONFIGURATION AND � SIMPLE SYSTEM CONFIGURATION AND
PROGRAMMING. � EXTENDED MONITORING FUNCTION.� HOT REPAIRE CAPABILITY.
PROGRAMMABLE CONTROLLER
INPUT/OUTPUT
BUS
PROCESS CONTROL SYSTEM
BUS CONTROLLER
OUTPUTINPUT
FROM FIELD TO FIELD
DATA TRANSMISSION
THE DATA TRANSMISSION OF PROCONTROL P IS PERFORMED WITH TWO LEVEL SERIAL BUS WITH TWO LEVEL SERIAL BUS SYSTEMS
� LOCAL BUS P-13� INTRAPLANT BUS P-42
LOCAL BUS
� TRANSMISSION RELIABILITY
LOCAL BUS IS A HEART OF EVERY STATION ANDCONNECT ALL THE MODULES WITHIN THE STATION
� PARITY BIT� CYCLIC TRANSMISSION� DATA VALENCY� CLOCK SIGNAL� REDUNDANCY � GEOGRAPHICAL STRUCTURE
LOCAL BUS PCB (70BL01) HAS SEVEN LINES
� AD : ADDRESS � DN : DATA OR INFORMATION � DI : INVERTED DATA OR INFORMATION
LOCAL BUS
� DI : INVERTED DATA OR INFORMATION� CK : CLOCK SIGNAL� US : 24V DC POWER SUPPLY� ZD : REFERENCE CONDUCTOR FOR BUS SIGNAL� Z : FOR REFERENCE CONDUCTOR
70BV05
70BV05
70BV05
LOCAL BUS
70BL01
70BL01
70BL0170BL02
BUS TRAFFIC
DIRECTOR
LOCAL BUS PCB
BUS CABLE
70BV05
70BA01
70BL01
70BL01
70BL01
70BL02
70BL02
BUS END MODULE
BUS TRAFFIC
DIRECTOR
BUS ISOLATION AMPLIFIER
BUS ACCESS MODULE
CUBICAL 1 CUBICAL 2
LOCAL BUS B/N CUBICALS
DIRECTOR AMPLIFIER
BUS END
MODULE
MODULE
BUS END
MODULE
LOCAL BUS
PROCESSOR I/O
MODULE
LOCAL/ IPB COUPLER
BUS
TRAFFIC
DIRECTOR
LOCAL BUS
LOCAL BUSPROCESSOR DRIVE
CONTROLI/O
MODULE
DRIVE CONTROL
I/O
MODULE
BUS END
MODULE
I/O
MODULE
DRIVE CONTROL
1.CONFIGURATION A) LENGTH OF LOCAL BUS LINEB) WITH ADITIONAL MODULEC) NO OF MODULES PER LOCAL
BUS D) DISTANCE B/N IPB BUS ACCESS
COUPLER AND LOCAL BUS/IPBCOUPLER
MAX. 3 MTRMAX. 30 MTRMAX. 64
MAX. 3 MTR
SYSTEM DATA
LOCAL BUS
2. DATA TRANSMISSION
A) SERVICE ADDRESSB) USEFUL ADDRESSES PER CYCLE
(CYCLE TIME 40 ms)C) INFORMATION RATE D) TYPE OF MODULATIONE) DATA SECURITY
F) TRANSMISSION MEANSWITHIN SUBRACKB/N TWO SUBRACKB/N TWO CUBICLES
2 EVERY 10 ms256
204. 8 KBAUDPULSE MODULATIONPARITY BIT,CLOCK MONITORING
P.C.B 70BL01ROUND CABLE 70BL02ROUND CABLE 70BL03
INTRA-PLANT BUS
INTRA- PLANT BUS LINK ALLSTATION WITH LOCAL BUS ,PROCESS COMPUTER ANDPROCESS COMPUTER ANDDIAGNOSTIC STATION WITHREDUNDANT LINE
INTRA PLANT BUS
IPBTRAFFIC
IPBTRAFFIC
DIRECTOR
IPBTRAFFIC
DIRECTORTRAFFIC
DIRECTOR
IPBTRAFFIC
DIRECTOR
IPBTRAFFIC
DIRECTOR
IPB IPB IPB # 1 IPB # 2
IPB 1
IPB 2
LOCAL BUS LOCAL BUS
INTRA PLANT BUS
IPB ACCESS COUPLER
IPB ACCESS COUPLER
LOCAL BUS LOCAL BUS
IPB ACCESS COUPLER
IPB ACCESS COUPLER
LOCAL BUS LOCAL BUS
IPB ACCESS COUPLER
IPB ACCESS COUPLER
STATION STATION STATION STATION
LOCAL BUSIPB COUPLER
LOCAL BUSIPB COUPLER
LOCAL BUSIPB COUPLER
LOCAL BUSIPB COUPLER
LOCAL BUSIPB COUPLER
LOCAL BUSIPB COUPLER
DATA EXCHANGE B/N LOCAL BUS AND IPB
LOCAL/IPB BUS
COUPLER
70 FK01
70 FK01
70 FA01
IPB
LOCAL
BUS
LOCAL/IPB BUS
COUPLER
70 FK01
70 FK01
LINE#A LINE#B
S
LOCAL
BUS
70 FV01
70 FV01
XV
XV
LOCAL / INTRA-PLANT BUS
PROCESSOR I/O
MODULE
LOCAL BUS
LOCAL BUSINT
RA
PLA
NT B
US
STATION -1LOCAL/ IPB COUPLER
BUS
TRAFFIC
DIRECTOR70FA01 70FV01
XV1
LOCAL BUS
INT
RA
PLA
NT B
US
PROCESSOR DRIVE CONTROL
I/O
MODULE
LOCAL/ IPB COUPLER
BUS
TRAFFIC
DIRECTOR
PROCESSOR DRIVE CONTROL
I/O
MODULE
LOCAL/ IPB COUPLER
BUS
TRAFFIC
DIRECTOR
STATION -2
STATION -3
70FA01
70FA01
1.CONFIGURATION A) NO. OF INTRA-PLANT BUS LINESB) LENTH FROM ADDRESS
TRANSMITTERC) NUMBER OF STATIONS PER
INTRAPLANT BUS LINE D) NUMBER OF STATIONS PER
ENTIRE CONTROL SYSTEM
MAX. 16MAX. 1000 MTR
MAX. 64
1024
SYSTEM DATAINTRA-PLANT BUS
2. DATA TRANSMISSION
A) NUMBER OF ADDRESS FORMAXIMUM OF 64 STATIONS
B) TIME REQUIRED TO TRANSMIT 1TELEGRAM
C) INFORMATION RATE D) SIGNAL CODEE) AMPLITUDEF) DATA SECURITYF) TRANSMISSION MEANS
COXIAL CABLE,TYPECHARACTERISTICS IMPEDANCE
256 X NO. OF STATIONS
60 MICRO SECONDS
204. 8 KBAUDDPDM+- 10VPARITY BIT
RG 213 U50 Ohm
F C3
ADDRESS ALLOCATION
BINARY SIGNAL
0 1F
ANALOG SIGNAL
LOCAL BUS
ADDRESS ON LOCAL BUS
POSITION OF INDIVIDUAL BIT ON DATA BUS
ADDRESS ON LOCAL BUS
NO BIT POSITIONFOR ANALOG VALUE
1 0A
ADDRESS ALLOCATION
0 17
INTRA PLANT BUS
STATION NUMBER
INTRA PLANT BUS SYSTEM NUMBER
ADDRESS ON LOCAL BUS
POSITION OF INDIVIDUAL BIT
CONTROL MODULESPROCONTROL HAVE TWO BASIC TYPES OF CONTROL MODULES
� INDIVIDUAL CONTROL MODULES�UNIVERSAL PROCESSING MODULES�UNIVERSAL PROCESSING MODULES
THESE MODULES ARE CONNECTED TO LOCALBUS,ONE OR SEVERAL OF THEM CAN BECONNECTED TO THE SAME BUS OR TO VARIOUSONES
INDIVIDUAL CONTROL MODULES
� IMPLEMENTED TO CONTROL SUPERVISE,MONITOR AND PROTECTONE INDIVIDUAL FINAL CONTROL ELEMENT
� FINAL CONTROL ELEMENT CAN BE VALVES , PUMPS, FANS� MODULE EQUIPED WITH MICROPROCESSOR WITH IN-BUILT INPUTS
OUTPUTSOUTPUTS� INPUT ALLOW TO GATHER DATA ON THE POSITION AND STATUS
OF CONTROL SYSTEM� OUTPUT PROVIDES POSITIONING OR ON/OFF ORDERS EITHER IN
CONTACT OR mA FORM� ADDITIONAL AND OPTIONAL I/O CAPABILITY TO INTERFACE
CONTROL ELEMENT WITH CCR VIA HARDWARE
Control Module
Interface
Optional hardware connection to control room
I/o
Microprocessor
I/o
Signal from/to process,final control element
UNIVERSAL PROCESS MODULE
� AUTOMATION UNIT,FUNCTIONALLY SUPERIMPOSED ON THE INDIVIDUAL CONTROL MODULE
� PERFORM COMBINED INDIVIDUAL AND AUTOMATIC FUNCTIONSFUNCTIONS
� PERFORM ARTHIMATIC AND LOGICAL OPEREATION� PROGRAM MEMORIES FOR BASIC FUNCTION ,
APPLICATION SPECIFIED INSTRUCTION LIST AND MULTIFUNCTION
� FACILITY TO SIMULATE DATA
PROCESSOR MODULE
SUPERVISION
LOCAL BUS
INTERFACESIMULATION
MEMORY
PROCESINGI/OREGISTER
POWER SUPPLY
ADDRESS BUSDATA BUS
SIM
DATAMEMORY
TESTMEMORY
INSTRUCTION LIST
MULTIFUNCTION LIST
PROCESINGUNIT
CONTROL UNIT
REGISTER
ADDRESS BUS
CODE BUS
INPUT/OUTPUT MODULES
� POWER SUPPLY FOR TRANSMITTER AND TRANSDUCERS
� SIGNAL VERIFICATION� DIGITALIZATION OF SIGNALS� DIGITALIZATION OF SIGNALS� ADDRESS ALLOCATION� SERIAL/PARALLEL CONVERSION� PROCESS INTERFACE
PROCONTROL MODULES
TYPE APPLICATION BRIEF DESCRIPTION
70 EA01 � INPUT MODULE FORANALOG SIGNAL(X4)
� 20mA TO 0 TO +20 Ma� -10V T0 0 TO +10V
� 4 IDENTICAL FUNCTIONAL UNIT� 4 BINARY I/P OF 24V FOR SIGNAL
VALUE DISTURBANCE� 2 CODE SWITCHES FOR ADDRESS
SETTING� 4 WIRE JUMPERS FOR SELECTION
ANALOG INPUT MODULES
� 4 WIRE JUMPERS FOR SELECTIONB/N 20mA AND 10V
70EA02 � INPUT MODULE FORANALOG SIGNAL(X4)0 TO 20 mA
� 4 IDENTICAL FUNCTIONAL UNIT� 4 STABILIZED VOLTAGE SOURCE
21 TO 26V D.C. TO SUPPLY TOTRANSDUCERS
� 2 CODE SWITCHES FOR ADDRESSSETTING
� ANNUNCIATION OF DISTURBANCE INTHE MEASUREMENT LINE AND SUPPLYSYSTEM
TYPE APPLICATION BRIEF DESCRIPTION
70 EA03 � INPUT MODULE FORRESISTANCE ( X4)
� MEASURE OF TEMPRATURE WITH PT100(UP TO 250 OHMS
� CONVERT RESISTANCE IN TOLOCAL BUS SIGNAL
� 4 IDENTICAL FUNCTIONAL UNIT� LINEARIZATION FOR MEASUREMENT� 2 CODE SWITCHES FOR ADDRESS
SETTING� ANNUNCIATION OF DISTURBANCE IN
THE MEASUREMENT LINE AND SUPPLYSYSTEM
70EA04 � INPUT MODULE FOR THERMOELECTRIC VOLTAGE(X8)
� 8 IDENTICAL FUNCTIONAL UNIT� LINEARIZATION FOR MEASUREMENTELECTRIC VOLTAGE(X8)
� NICR-NI� FE-CUNI� NICR-CUNI� PTRH-PT
� LINEARIZATION FOR MEASUREMENT� CORRECTION OF THERMOELECTRIC
VOLTAGE WITH COLD JUNCTIONTEMPRATURE
� 2 CODE SWITCHES FOR ADDRESSSETTING
� ANNUNCIATION OF DISTURBANCE INTHE MEASUREMENT LINE AND SUPPLYSYSTEM
� EPROM FOR SELECTION OFTHERMOELECTRIC VOLTAGE
BINARY INPUT MODULE
TYPE APPLICATION BRIEF DESCRIPTION
70EB01 � INPUT MODULE FOR 24V BINARYSIGNAL ( X 16)
� CONVERSION OF 0/24V BINARYSIGNAL IN TO LOCAL BUS SIGNAL
� 16 IDENTICAL FUNCTIONAL UNIT�2 CODE SWITCHES FOR ADDRESS
SETTING
70EB02 � INPUT MODULE FOR BINARYSIGNAL ( X 16)
� INTERROGATION VOLTAGE OF48VDC
� 16 IDENTICAL FUNCTIONAL UNIT� 2 CODE SWITCHES FOR ADDRESS
SETTING� SHORT CIRCUIT PROOF SUPPLY TO48VDC
� CONVERSION OF 0/24V BINARYSIGNAL IN TO LOCAL BUS SIGNAL
� SHORT CIRCUIT PROOF SUPPLY TOCONTACTS
70EB03 � INPUT MODULE FOR SUPERVISEDCONTACT( X 5)
� FIVE DOUBLE THOW CONTACT� INTERROGATION VOLTAGE OF
48VDC� NO EFFECT OF EARTH FAULT
� 5 IDENTICAL FUNCTIONAL UNIT� 2 CODE SWITCHES FOR ADDRESS
SETTING� SHORT CIRCUIT PROOF SUPPLY TO
CONTACTS�ANNUNCIATION OF DISTURBANCE IN
EATRH FAULT,WIRE BREAKAGE
TYPE APPLICATION BRIEF DESCRIPTION
70AA01 � OUTPUT MODULE FORVOLTAGE SIGNALS +-10V(X4)
� 4 IDENTICAL FUNCTIONAL UNIT� 4 BINARY IO/P OF 24V FOR SIGNAL
VALUE DISTURBANCE� 2 CODE SWITCHES FOR ADDRESS
ANALOG OUTPUT MODULES
� 2 CODE SWITCHES FOR ADDRESSSETTING
70AA02 � OUTPUT MODULE FORANALOG SIGNAL ( X 4)0 TO 20 mA
� CONVER OF DIGITAL BUSSIGNAL TO CURRENT SIGNAL
� 4 IDENTICAL FUNCTIONAL UNIT�2 CODE SWITCHES FOR ADDRESS
SETTING
TYPE APPLICATION BRIEF DESCRIPTION
70AB01 � OUTPUT MODULE FOR 24VBINARY SIGNAL ( X 16)
� CONVERSION OF 0/24V BINARYSIGNAL IN TO LOCAL BUSSIGNAL
� 16 IDENTICAL FUNCTIONAL UNIT�2 CODE SWITCHES FOR ADDRESS
SETTING
BINARY OUTPUT MODULES
SIGNAL
70AB02 � OUTPUT MODULE FOR BINARYSIGNAL UP TO 60V ( X 16)
� INTERROGATION VOLTAGE OF48VDC
� CONVERSION OF 0/24V LOCALBUS SIGNAL IN TO POTENTIALFREE CONTACT
� 16 IDENTICAL FUNCTIONAL UNIT� 2 CODE SWITCHES FOR ADDRESS
SETTING
LOCAL BUS MODULE
TYPE APPLICATION BRIEF DESCRIPTION
70BA01 � BUS END MODULEUSED AT THE END OF THELOCAL BUS FOR MATCHINGINE IMPEDANCE
�ADDITIONAL SUPPLY TO THE BUS LINE
70BA02 � BUS ACCES MODULE FORCONNECTING BUS CABLEWHEN THE LOCAL BUSCONNECTED FORM CUBICAL
� SOCKET ON THE FRONT FOR BUSCABLE
CONNECTED FORM CUBICALTO CUBICAL
70BL01 �BUS CIRCUIT BOARDBUS PCB WITH CONNECTOR
�BUS LINE�SOCKET FOR BUS CABLE �2 SUPPLY BUS�POSSIBILITY FOR FITTING SEVERAL
BUS SOCKET
70BL02 �BUS CABLE SUBTRACK/SUBTRACKLINK THE BUS PCB OF TWOSUBRACK
�CABLE UP TO 3M LONG
TYPE APPLICATION BRIEF DESCRIPTION
70BL03 � BUS CABLE CUBICAL/CUBICALLINK THE BUS PCB OF TWOCUBICALS
� CABLE UP TO 30M LONG
70BT01 � BUS ISOLATION AMPLIFIER � SOCKET ON THE FRONT FOR BUSCABLECABLE
70BV01 �BUS TRAFFIC DIRECTORCONTROL EXCHANGE B/NMODULE CONNECTED TOLOCAL BUS
�PLUG IN JUMPER SETTING FOR CYCLEPERIOD
� JACK FOR FORCE INTERRUPT ORADDRESS TRANSMISSION
�LED FOR INDICATION OFOPERATION
IPB MODULE
TYPE APPLICATION BRIEF DESCRIPTION
70FA01 � IPB ACCESS COUPLERCONNECT NORMAL LOCAL BUSSTATION WITH INTRA PLANTBUS
�COUPLING BY THE WAY OFMULTICORE INTERCONNECTINGCABLE
� SERVE FOR TRANSFER DATA SIGNALIN TO INTRAPLANT BUS CABLE
� FOR TRANSFER OF ADDRES ANDDATA FROM INTRAPLANT BUS CABLETO LOCAL BUS CABLE TO LOCAL BUS CABLE
70FK01 �IPB COUPLER WITH ADDRESS I/PUSE TO CONNECT LOCAL BUSSTATION CONTAINING THE IPBTRAFFIC DIRECTOR
�USE TO TRANSMISSION ANDRECEPTION OF ADDRESS AND DATA SIGNAL TO FROM IPB CABLE
70FV01 �IPB TRAFFIC DIRECTORMANAGE THE SIGNALTRANSMISSION SEQUENCE
� OPERATE IN SINGAL ANDREDUNDANT MODE
� FITTED IN TO LOCAL BUS SUBRACK� GENERATE MAXIMUM 4000 ADDRESS
WORD TRANSMITTED CYCLIC IN 8DIFFERENT SEQUENCE
TYPE APPLICATION BRIEF DESCRIPTION
70PR05 � PROCESSING OF BINARY ANDANALOG SIGNAL FOR LOGICCONTROL ,MODULATING
� 2 SOCKET FOR OPERATION WITH SIMULATION AND PROGRAMMINGUNIT
PROGRAMMABLE PROCESSOR
PROCESS MODULES
CONTROL ,MODULATINGCONTROL AND COMPUTINGFUNCTION ACCORDING TOINSTRUCTION LIST
� PARAMETER CAN BE CHANGEDON LINE WITHOUT PROGRAMMODIFICATION
UNIT� 1CODE SWITCH FOR SETTING
MODULE ADDRESS� EPROMS AVAILABLE FOR BASIC
FUNCTIONS/INSTRUCTIONLINE/MULTIFUNCTION
� RAM FOR STARAGE OF PARAMETERVALUE IN THE EVENT OF POWERFAILURE
� SIMULATION CAN BE POSSIBLE FORLOCAL BUS DATA
TYPE APPLICATION BRIEF DESCRIPTION
70AS04 � DRIVE CONTROL MODULETO PROCESS CONTROL TASK PROGRAMMABLE IN
� 6 BINARY INPUTS, 9 CONTACT INPUTS, 2 COMMAND OUTPUTS AND 5 LAMPOUTUTS ARE PROVIDED
DRIVE CONTROL MODULE
PROGRAMMABLE INPROCONTROL P10 LANGUAGE
OUTUTS ARE PROVIDED� ANNUNCIATION AVAILABLE FOR
ELECTRONIC SYSTEM AND DRIVESYSTEM
� EPROM(2732) AVAILABLE FOR PROGRAMMNG
�IMPLEMENT SOFTWARE TYPE 70 AS40/41/42/45/46/47
TYPE APPLICATION BRIEF DESCRIPTION
70AS06 � DRIVE CONTROL MODULETO PROCESS CONTROL TASK PROGRAMMABLE IN
� 6 BINARY INPUTS, 10 CONTACTINPUTS, 2 COMMAND OUTPUTS, 5LAMP OUTUTS, 1 ANALOG INPUT, 3
DRIVE CONTROL MODULE
PROGRAMMABLE INPROCONTROL P10 LANGUAGE
LAMP OUTUTS, 1 ANALOG INPUT, 3 ANALOG OUTPUT ARE PROVIDED
� ANNUNCIATION AVAILABLE FORELECTRONIC SYSTEM AND DRIVESYSTEM
� EPROM(2732) AVAILABLE FOR PROGRAMMNG
OWS OWS OWS OWS
HUB
IPB 1
IPB 2
SERVER
2
WSPOSE PANEL
SERVER
1
LINE ALINE B
LINE ALINE B