Building TechnologiesFire Safety & Security Products

FD720 Cerberus® PRO, Synova, AlgoRex Detector system

Equipment overview

Page 2: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Liefermöglichkeiten und technische Änderungen vorbehalten. Data and design subject to change without notice. / Supply subject to availability. Sous réserve de modifications techniques et de la disponibilité. © 2009 Copyright by Siemens Schweiz AG Wir behalten uns alle Rechte an diesem Dokument und an dem in ihm dargestellten Gegenstand vor. Der Empfänger anerkennt diese Rechte und wird dieses Dokument nicht ohne unsere vorgängige schriftliche Ermächtigung ganz oder teilweise Dritten zugänglich machen oder außerhalb des Zweckes verwenden, zu dem es ihm übergeben worden ist. We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him. Nous nous réservons tous les droits sur ce document, ainsi que sur l'objet y figurant. La partie recevant ce document reconnaît ces droits et elle s'engage à ne pas le rendre accessible à des tiers, même partiellement, sans notre autorisation écrite préalable et à ne pas l'employer à des fins autres que celles pour lesquelles il lui a été remis.

Page 3: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

3

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

1 About this document ..............................................................................7

2 Automatic fire detectors in C-NET ........................................................9 2.1 Point detectors with detection algorithms .................................................9 2.1.1 Accessories for point detectors...............................................................11 2.2 Detector bases........................................................................................11 2.2.1 Accessories for detector bases...............................................................12 2.3 Linear smoke detector FDL241-9 with ASAtechnology™.......................13 2.3.1 Accessories for FDL241-9 ......................................................................14 2.4 Infrared flame detector FDF221-9 with detection algorithms..................15 2.5 Infrared flame detector FDF241-9 with ASAtechnology™......................16 2.5.1 Accessories for FDF221-9, FDF241-9....................................................17

3 Alarm indicators for C-NET devices....................................................18 3.1 Door frame version DJ1191 ....................................................................18 3.2 Wall version DJ1192 ...............................................................................18 3.2.1 Accessory for DJ1192.............................................................................18

4 Manual call points in C-NET.................................................................19 4.1 Manual call point FDM221 with direct operation.....................................19 4.1.1 Accessories for FDM221.........................................................................20 4.1.2 Spare parts for FDM221 .........................................................................20 4.2 Manual call points FDM225/226 with direct operation............................21 4.2.1 Accessories for FDM225, FDM226.........................................................22 4.2.2 Spare parts for FDM225, FDM226..........................................................23 4.3 Manual call point FDM224 with direct operation.....................................24 4.4 Manual call point 'Heavy Duty' FDM224H with direct operation .............25 4.4.1 Accessories for FDM224, FDM224H ......................................................25 4.4.2 Spare parts for FDM224, FDM224H.......................................................26 4.5 Manual call point FDM223 complete with indirect operation ..................27 4.6 Manual call point FDM223 with indirect operation ..................................28 4.7 Manual call point 'Heavy Duty' FDM223H with indirect operation ..........29 4.7.1 Accessories for FDM223, FDM223H ......................................................29 4.7.2 Spare parts for FDM223, FDM223H.......................................................30

5 Alarm devices in C-NET .......................................................................31 5.1 Alarm sounders FDS221.........................................................................31 5.2 Alarm sounder beacons FDS229............................................................32 5.2.1 Accessories for FDS221, FDS229..........................................................32 5.3 Sounder base DBS720 ...........................................................................35 5.3.1 Accessories for DBS720 .........................................................................35

6 Line separator, Input/output modules in C-NET................................36 6.1 Line separator FDCL221.........................................................................36 6.2 Multi line separator FDCL221-M.............................................................37 6.2.1 Accessories for FDCL221 / FDCL221-M ................................................37 6.3 Input modules FDCI221, FDCI222..........................................................38 6.4 Input/output modules FDCIO22x ............................................................39 6.4.1 Accessories for FDCI22x, FDCIO22x .....................................................41 6.4.2 Spare part for FDCI22x, FDCIO22x........................................................41

7 Special detectors in C-NET ..................................................................42 7.1 Aspirating smoke detectors.....................................................................42

8 Conventional and collective devices ..................................................43 8.1 Point detectors Synova conventional/SynoLINE300 ..............................43 8.1.1 Detector base and accessories...............................................................45

Page 4: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

4

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.2 Manual call points FDM1101A conventional/SynoLINE300 ...................46 8.2.1 Accessories for FDM1101A ....................................................................47 8.2.2 Spare parts for FDM1101A .....................................................................47 8.3 Alarm indicators for conventional/SynoLINE300 devices .......................48 8.3.1 Accessory for AI322 ................................................................................48 8.4 Point detectors AlgoRex collective/SynoLINE600 ..................................49 8.4.1 Accessories for detector base.................................................................50 8.5 Manual call points FDM1101 collective/SynoLINE600 ...........................53 8.5.1 Accessories for FDM1101.......................................................................54 8.5.2 Spare parts for FDM1101........................................................................54 8.6 Manual call point DM1101 collective/SynoLINE600 ...............................55 8.6.1 Accessories for DM1101 .........................................................................55 8.6.2 Spare parts for DM1101..........................................................................56 8.7 Manual call points DM1103/04 collective/SynoLINE600 ........................57 8.7.1 Accessories for DM1103/04 ....................................................................58 8.7.2 Spare parts for DM1103/04.....................................................................59 8.8 Air sampling smoke detection kit FDBZ292 ............................................60 8.8.1 Accessories FDBZ292 ............................................................................60 8.9 Alarm indicators for collective/SynoLINE600 devices.............................62 8.9.1 Accessory AI340 .....................................................................................62 8.9.2 Accessories for DJ1193 ..........................................................................63 8.10 Conventional alarm devices ....................................................................64 8.10.1 Alarm devices AGN24.6, AGT24.1, AGS24.5.........................................64 8.10.2 Flashing signal lamps ALB24.1R, ALB24.1OR.......................................66 8.11 Devices for explosion-hazard area of zones 1 and 2..............................67 8.11.1 Interface for connection of the 'Ex' devices to C-NET ............................67 8.11.2 Interface for connection of 'Ex' devices to SynoLINE600 .......................67 8.11.3 Shunt Zener diode barrier SB3 ...............................................................68 8.11.3.1 Accessories for SB3...............................................................................68 8.11.4 Point detectors AlgoRex Serie 'Ex' .........................................................69 8.11.4.1 Accessories for DB1101A ......................................................................70 8.11.5 Infrared flame detector DF1101-Ex.........................................................71 8.11.5.1 Accessories for DF1101-Ex ...................................................................72 8.11.6 Manual call points DM1103(Ex), DM1104(Ex)........................................73 8.11.6.1 Accessories for DM1103(Ex), DM1104(Ex) ...........................................73 8.11.6.2 Spare parts for DM1103(Ex), DM1104(Ex)............................................74 8.11.7 Alarm indicators DJ1191-Ex, DJ1192-Ex, AJUT24-Ex ...........................75 8.11.7.1 Accessory for DJ1192-Ex.......................................................................75 8.11.7.2 Accessories for AJUT24-Ex ...................................................................76 8.11.8 Alarm device DB3 for explosion-hazard areas........................................77

9 Test equipment and accessories ........................................................78 9.1 Detector exchanger for FD720 point detectors .......................................78 9.2 Detector tester RE6, RE6T, RE7T ..........................................................78 9.2.1 Accessories for RE6................................................................................78 9.2.2 Accessories for RE7T .............................................................................79 9.2.3 Spare parts for RE7T ..............................................................................80 9.2.4 Accessories for DX791, RE6, RE6T, RE7T ............................................80 9.2.4.1 Spare parts for FDUM291.......................................................................81 9.2.4.2 Spare parts for FDUM292.......................................................................81 9.3 Detector base tester DZB1191................................................................82 9.4 Test equipment for linear smoke detectors.............................................82 9.4.1 Adjustment device set FDLU291 ............................................................82 9.4.2 Detector tester RE10...............................................................................82 9.5 Line tester FDUL221 ...............................................................................83 9.5.1 Accessories for FDUL221 .......................................................................83 9.5.2 Spare parts for FDUL221........................................................................84

Page 5: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

5

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9.6 Test lamps for flame detectors................................................................84 9.6.1 Spare part for LE3...................................................................................84 9.7 Adapter for C-NET devices .....................................................................85

10 Index.......................................................................................................86

Page 6: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

6

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

Page 7: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

About this document

7

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

1 About this document

Purpose This document is an overview about following detector products: Cerberus PRO FD720 Synova conventional/SynoLINE300 AlgoRex collective/SynoLINE600

All available conventional Synova and collective AlgoRex devices are contained in this overview, therefore the equipment overview 009252 is not applicable.

This document is continuously revised and extended.

Scope The document contains information about all available devices.

Target groups This document arranges itself to all persons.

Reference documents You can find the detailed information in the product data sheets and technical de-scriptions.

Conventions (...) Additional information bold letters Definitions of designations see Cross-reference

Document identification Place Signification Title page – System names

– Product type – Document purpose

Last page bottom left – Document number – Version date

Last page bottom right – Manual – Register

Modification index Version Date Brief description A6V10225323_a_en 05.2009 Initial edition A6V10225323_b_en 07.2009 VdS Approval DBS720, DBZ1195A. DLA/DLB1191A deleted.

Label 'avoid electrostatic charging' BPZ:5358470001 is enclosed with DMA1103D/04D it cannot be ordered separately, replace AX1204 by FA2003-A1, insert DC1192, minor changes.

A6V10225323_c_en 12.2009 Correction of the Ex-classification DM1103(Ex), DM1104 (Ex), DJ1191-Ex, DJ1192-Ex, AJUT24-Ex; FDCL221-M (new); FDMH293-O (new); VdS Approval for FDM226-RG/RP, FDM1101A-RG/RP, FDM1101-RG/RP; DB721 (new)

Page 8: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

About this document

8

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

Download The current issue documentation and photos can be found in the Siemens Intranet. https://workspace.sbt.siemens.com/content/00001123/default.aspx (STEP, Web-Client)

Page 9: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

9

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

2 Automatic fire detectors in C-NET

2.1 Point detectors with detection algorithms

OH720 Multi sensor smoke detector Part no. S54310-F2-A1 Documents Product data sheet A6V10202198

Technical description A6V10212047 Scope of delivery Detector and dust cap

Application For the detection of flaming fires caused by the combustion of liquid and solid matters, as well as smol-dering fires. For reliable fire detection in environments with deceptive phenomena. Addressable applicable. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. An additional heat sensor increases the fire detector’s immunity to deceptive phenomena. Selectable detection behavior by different parameter sets. Immunity against transient false alarm causes Technical data Communication protocol C-NET Operating voltage (modulated) 12... 33 VDC Operating current (quiescent) ~230 μA Ext. alarm indicator 2 Permissible air speed max. 5 m/s Operating temperature -10... +50 °C Storage temperature -30... +70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards CEA4021 / EN54-7 / EN54-17 Dimensions (detector with base) Ø117 x 59 mm

Approvals VdS G209064, LPCB request

Page 10: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

10

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

OP720 Smoke detector Part no. S54310-F1-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application For the detection of smoke-generating flaming and smoldering fires. Addressable applicable. Function Works according to the scattered light principle with one sensor, optical forward scattering. Opto-electronic sampling chamber holds off disturbing extraneous light but optimally detects smoke particles. Selectable detection behavior thanks different parameter sets. Technical data Communication protocol C-NET Operating voltage (modulated) 12... 33 VDC Operating current (quiescent) ~220 μA Ext. alarm indicator 2 Permissible air speed max. 5 m/s Operating temperature -10... +50 °C Storage temperature -30... +70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 – with detector base seal RS720

IP40 IP42

System compatibility C-Net FS720 Standards EN54-7 / EN54-17 Dimensions (detector with base) Ø117 x 56 mm

Approvals VdS G209068, LPCB request

HI720 Heat detector (static + RoR) Part no. S54310-F4-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application Suitable in areas in which occur different environment temperatures. Where high dust or dirt developments or large humidity which can the impact of conventional alarm units to impair. Addressable applicable. Function Equipped with one heat sensor. For high requirements. Certain response behavior with slow and fast temperature increases, also by depth temperature. Selectable detection behavior by different parameter sets. Technical data Communication protocol C-NET Operating voltage (modulated) 12... 33 VDC Operating current (quiescent) ~200 μA Ext. alarm indicator 2 Operating temperature -10... +50 °C Storage temperature -30... +70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN54-5 / EN54-17 Dimensions (detector with base) Ø117 x 59 mm

Approvals VdS G209065, LPCB request

Page 11: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

11

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

HI722 Heat detector (static) Part no. S54310-F3-A1 Documents Product data sheet A6V10202198

Techn. description A6V10212047 Scope of delivery Detector and dust cap

Application Suitable in areas, in which temporary high variations in temperature arise. Where high dirt and heat fluctuation which can the impact of conventional alarm units to impair. Addressable applicable. Function Equipped with one heat sensor. Measures permanent the ambient temperature, with exceeding of the maximum temperature, the detec-tor sends a danger signal to control panel, at short term exceeding no alarming takes place. Technical data Communication protocol C-NET Operating voltage (modulated) 12... 33 VDC Operating current (quiescent) ~200 μA Ext. alarm indicator 2 Operating temperature -10... +50 °C Storage temperature -30... +70 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 – with detector base seal RS720

IP40 IP42

System compatibility C-NET FS720 Standards EN54-5 / EN54-17 Dimensions (detector with base) Ø117 x 59 mm

Approvals VdS request, LPCB request

2.1.1 Accessories for point detectors

LP720 Detector locking device Part no. S54319-F9-A1

Application Threaded pin M3 x 12 to protect detector against theft. Scope of delivery 2 hexagonal wrenches, 100 threaded pins Technical data Threaded pin M3 x 12 Hexagonal wrench 1.5 mm

2.2 Detector bases

DB720 Detector base Part no. S54319-F4-A1

Application For all point detectors of the series Cerberus PRO FD720. Technical data Color white, ~RAL 9010

Dimensions Ø117 x 23 mm

Page 12: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

12

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DB721 Detector base with loop contact Part no. S54319-F11-A1

Application For all point detectors of the series Cerberus PRO FD720. Technical data Color white, ~RAL 9010

Dimensions Ø117 x 23 mm

DBS720 Sounder base Part no. S54319-F5-A1 Details see chapter 5.3

2.2.1 Accessories for detector bases

FDBZ291 Designation plate Part no. A5Q00002621

Application To identify the location address. Compatibel to bases FDB221, FDB222, DB720, base attachment FDB291 and sounder base DBS720. Technical data Color transparent

10 pieces

Dimensions 62 x 35 mm

RS720 Detector base seal Part no. S54319-F8-A1

Application For higher protection category. Compatible with base DB720 and sounder base DBS720. Note: Not usable together with the designation plate FDBZ291. Technical data Color transparent

10 pieces

Dimensions Ø119 x 6.5 mm

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001

Application As cross-connection point for T branches, external alarm indicators (AI), cable shielding, or for the con-nection of a power supply. Technical data DBZ1190-AA for conductors 0.28... 0.5 mm2 / 4-pole Dimensions 7 x 10 x 10 mm DBZ1190-AB for conductors 1.0... 2.5 mm2 / 3-pole

DBZ1190-AA

50 pieces DBZ1190-AB

50 pieces Dimensions 13.5 x 9.5 x 19.5 mm

Page 13: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

13

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

2.3 Linear smoke detector FDL241-9 with ASAtechnology™

FDLB291 Base for linear smoke detector Part no. A5Q00003941 FDL241-9 Linear smoke detector Part no. A5Q00002298 Documents Product data sheet 007017

Technical description 007016

Application Large storerooms and production workshops. Areas with complex roof structures or historically valuable ceilings. Covered courtyards. Atrium-type buildings. Reception halls. Can be used as an addressable or collective, conventional device. Function The detector consists of a light emitter and a light receiver. The light emitter emits a bundled infrared ray, which is scattered back by the prism-shaped reflector to the light emitter. The receiver converts the received infrared signal in an electric signal, which is evaluated by the microprocessor-controlled elec-tronics. Smoke penetrating the measuring section attenuates the infrared signal. When the signal reaches pre-defined measuring values, the detector transmits the corresponding danger level to the control unit. Distance measurement for the recognition of foreign matters. The built-in alarm indicator signals the alarm status locally. Max. Detection distance 5 – 100m. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional

12... 33 VDC / 18... 28 VDC

Operating current addressable, collective, conven-tional

1.5 mA

Ext. alarm indicator 1 Operating temperature -25... +60 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 IP65 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN54-12, EN54-17 Dimensions 135 x 135 x 115 mm

FDLB291

FDL241-9

Approvals VdS G204063, LPCB 126ag/01

Page 14: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

14

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

2.3.1 Accessories for FDL241-9

DLR1191 Long distance reflector (Prism) Part no. BPZ:4787710001 DLR1192 Middle distance reflector (400cm2) Part no. BPZ:4788490001 DLR1193 Short distance reflector (100cm2) Part no. BPZ:4787840001

Application Reflectors to the linear smoke detector incl. detector heating. Function Light rays arriving are reflected parallel. Any extraneous light is also reflected in its own direction and consequently does not reach the receiver. The retro reflecting prism in the DLR1191 has the shape of a pyramid that's lateral faces are formed by isosceles orthogonal triangles. Light beams entering through the base are completely reflected twice on the lateral faces and reflected back through the base. In principle, the reflector foil has the same effect (function) as the prism. Technical data Long distance reflector (Prism) for 20-100 m Supply for detector heater 24 VDC Dimensions 135 x 135 x 65 mm Middle distance reflector (400 cm2) for 30-65 m Dimensions 200 x 200 x 2.5 mm Short distance reflector (100 cm2) for 10-30 m Dimensions 100 x 100 x 2.5 mm

DLR1191

DLR1192

DLR1193

DLF1191-AA Short distance filter 7-10m Part no. BPZ:4933030001 DLF1191-AB Short distance filter 5-8m Part no. BPZ:4933160001 DLF1191-AC Extraneous light filter Part no. BPZ:5221480001

Application The short distance filter is required for short distance of 5-10 m. The extraneous light filter is required at powerful external light causes interference Only one filter possible.

DLF1191-AA

DLF1191-AB, DLF1191-AC

DLH1191A Detector heating element Part no. BPZ:4787970001

Application In the event of danger of condensation of the linear smoke detector. Technical data Operating voltage 20... 30 VDC Operating current 30… 50 mA

Resistance 600 Ω

Page 15: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

15

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478

Application For surface cable entry. Technical data Material Ms nickel-plated

10 pieces

Dimensions M20 x 1.5

2.4 Infrared flame detector FDF221-9 with detection algorithms

FDFB291 Base for infrared flame detector Part no. A5Q00003310 FDF221-9 Infrared flame detector (1 Sensor) Part no. A5Q00003902 Documents Product data sheet 007012

Technical description 007011

Application For simple applications, additional to smoke detectors. Detection of smokeless combustible liquid and gas fires, as well as smoke-forming open fire involving carbonaceous materials as contained in wood, plastics, gases, oil products etc. Only used without source of interference as sun, halogen light, and blackbody radiation. Can be used as an addressable, collective or conventional device. Function 1 infrared sensor with detection algorithms. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional (quiescent)

12... 33 VDC / 16... 28 VDC

Operating current addressable / collective, conven-tional (quiescent)

0.7 mA / 0.5 mA

Ext. alarm indicator 2 Connection terminals 0.2… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -40... +75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 IP44 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN54-10, EN54-17 Dimensions 135 x 135 x 77 mm

FDFB291

FDF221-9

Approvals VdS G204009, LPCB 126af/02

Page 16: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

16

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

2.5 Infrared flame detector FDF241-9 with ASAtechnology™

FDFB291 Base for infrared flame detector Part no. A5Q00003310 FDF241-9 Infrared flame detector (3Sensors) Part no. A5Q00003006 Documents Product data sheet 007012

Technical description 007011

Application Detects smokeless liquid and gas fires as well as smoke-generating open fires resulting from the com-bustion of carbonaceous materials such as wood, synthetics, gases, oil products, etc. Large industrial warehouses, Hangars for military and civil aircraft, Underground tunnels etc. Can be used as an addressable, collective or conventional device. Function 3 infrared sensors with ASAtechnology™. Technical data Communication protocol C-NET, collective, conventional Operating voltage addressable / collective, conven-tional (quiescent)

12... 33 VDC / 14... 28 VDC

Operating current addressable / collective, conven-tional (quiescent)

0.7 mA / 0.5 mA

Ext. alarm indicator 2 Anschlussklemmen 0.2… 1.5 mm2 Operating temperature -35... +70 °C Storage temperature -40... +75 °C Humidity ≤95 % rel. Color white, ~RAL 9010 Protection category EN60529/IEC529 IP67 System compatibility C-NET FS720 System compatibility collective, conventional CZ10, BC10, FC10, XC10, CS11, FC700A,

FC330A, SIGMASYS, BMS, SM80/88/D100 Standards EN54-10, EN54-17 Dimensions 135 x 135 x 77 mm

FDFB291

FDF241-9

Approvals VdS G204010, LPCB 126af/01

Page 17: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Automatic fire detectors in C-NET

17

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

2.5.1 Accessories for FDF221-9, FDF241-9

MV1 Mounting bracket Part no. BPZ:3950450001 MWV1 Ball and socket joint Part no. BPZ:3674840001 DFZ1190 Rain hood Part no. BPZ:5302660001 Document Product data sheet 007012

Application MV1 The mounting bracket for volumetric surveillance, fixed the detector in the right angle. MWV1 Ball and socket joint for the flame detector for the orientation to a defined object. DFZ1190 Rain hood for the flame detector for outdoor applications. Technical data Mounting bracket Dimensions 136 x 120 x 120 mm Ball and socket joint Dimensions 120 x 164 x 118 mm Rain hood Dimensions 150 x 165 x 130 mm

MV1

MWV1

DFZ1190

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 For details, see chapter 2.3.1

Page 18: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm indicators for C-NET devices

18

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

3 Alarm indicators for C-NET devices

3.1 Door frame version DJ1191

DJ1191 Alarm indicator (door frame), resistor 75 Ω Part no. BPZ:4783280001 Documents Product data sheet A6V10229141

Technical description A6V10212047 Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 5... 8 VDC Operating current, permanent max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 62 x 37 x 17 mm

3.2 Wall version DJ1192

DJ1192 Alarm indicator (wall mounting), resistor 75 Ω Part no. BPZ:4783310001 Documents Product data sheet A6V10229141

Technical description A6V10212047 Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 5... 8 VDC Operating current, permanent max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 85 x 85 x 25 mm

3.2.1 Accessory for DJ1192

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different makes of box. Technical data Color white, ~RAL 9010

Dimensions 85 x 85 x 16 mm

Page 19: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

19

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4 Manual call points in C-NET

4.1 Manual call point FDM221 with direct operation

FDMH291-R Housing red with key Part no. A5Q00002217 FDMH291-Y Housing yellow with key Part no. A5Q00004979 FDMH291-B Housing blue with key Part no. A5Q00004980 FDMH291-G Housing green with key Part no. A5Q00004981 FDME221 Switching unit Part no. A5Q00002451 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN60529/IEC529 IP44 System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 87 x 87 x 46.6 mm Approvals VdS G203059, LPCB 126ac/01

Page 20: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

20

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.1.1 Accessories for FDM221

FDMC291 Protective cover Part no. A5Q00001644

Application Protects the manual call point from unintentional glass break. Technical data

5 pieces Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479

Application For surface-mounted feed lines. Technical data Cable gland Dimensions M20 x 1.5 Back nut

10 pieces

10 pieces

Dimensions M20

4.1.2 Spare parts for FDM221

FDMG291 Glass Part no. A5Q00002122

Application Use as spare part. Technical data

10 pieces Color transparent

FDMK291 Cover with key Part no. A5Q00001643

Application Use as spare part. Technical data Color red, ~RAL 3000

Page 21: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

21

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.2 Manual call points FDM225/226 with direct operation

FDM225-RG Manual call point with glass plate Part no. A5Q00013434 FDM225-RP Manual call point with plastic element Part no. A5Q00012020 FDM226-RG Manual call point with glass plate incl. housing

base Part no. A5Q00013435

FDM226-RP Manual call point with plastic element incl. housing base

Part no. A5Q00013436

Documents Product data sheet 009023 Technical description 009757

Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application. FDM225 for surface and recess mounting in easily accessible places. FDM226 for surface mounting for IP67 applications Addressable applicable. Function FDM225/226-RG – Direct alarm actuation by pushing in the glass plate. – By replacing the glass plate the push button is set back and the device is ready for operation again. FDM225/226-RP – Direct alarm actuation by pushing on the plastic element. – The switch is set back with the key and the device is ready for operation again. An additional protective cover FDMC295 protects the manual call point from unintentional glass break. Technical data Communication protocol C-NET Operating voltage 13... 33 VDC Operating current (quiescent) 180 μA Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN60529/IEC529 – FDM225 – FDM226

IP44 IP66

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions – FDM225 – FDM226

87 x 87 x 20 mm 87 x 87 (113) x 57 mm

FDM225-RG, FDM225-RP

FDM226-RG, FDM226-RP

Approvals – FDM225-RG – FDM225-RP – FDM226-RG – FDM226-RP

VdS G207092, LPCB 126ap/02 VdS G207092, LPCB 126ap/01 VdS G209194, LPCB 126ap/04 VdS G209194, LPCB 126ap/03

Page 22: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

22

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438

Application Housing base for manual call points FDM225, FDM1101 and FDM1101A for surface mounting. Technical data Color red, ~RAL 3000 Dimension (WxHxD) 87 x 87 x 33 mm FDMH295-S With 2 holes and 2 sockets for cable up to Ø5 mm

FDMH295-R

10 pieces FDMH295-S

10 pieces

4.2.1 Accessories for FDM225, FDM226

FDMC295 Protective cover Part no. A5Q00013440

Application Protects the manual call point from unintentional glass break. Technical data

10 pieces Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

Page 23: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

23

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.2.2 Spare parts for FDM225, FDM226

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445

Application Use as spare part.

FDMG295

5 pieces FDMP295

5 pieces

FDMK295 Key Part no. A5Q00013448

Application Use as spare part.

5 pieces

Page 24: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

24

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.3 Manual call point FDM224 with direct operation

FDMH293-R Housing red with glass and key Part no. A5Q00004023 FDMH293-Y Housing yellow with glass and key Part no. A5Q00004908 FDMH293-B Housing blue with glass and key Part no. A5Q00004909 FDMH293-G Housing green with glass and key Part no. A5Q00004911 FDMH293-O Housing orange with glass and key Part no. S54311-F2-A1 FDME224 Switching unit Part no. A5Q00009392 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000,

yellow, ~RAL 1023, blue, ~RAL 5005, green, ~RAL 6024, orange, ~RAL 2011

Protection category EN60529/IEC529 – with seal DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 134,3 x 134,3 x 43,2 mm Approvals VdS G206123

Page 25: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

25

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.4 Manual call point 'Heavy Duty' FDM224H with direct operation

FDMH292-R Housing Heavy Duty red Part no. A5Q00005525 FDME224 Switching unit Part no. A5Q00009392 Documents Product data sheet 008345

Technical description 007002 Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. Only for surface mounted feed lines in easily accessible places, Tunnels, Industry. Addressable. The housing is equipped with one opening at the top and two openings at the bottom for nipples (en-closed) and for M20 metal screwed cable glands –> see accessory. For IP66 applications the unused openings must be locked with the V-plug –> see accessory. Function Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN60529/IEC529 – with seal DMZ1197-AD and V-plug

IP44 IP64

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 134.3 x 134.3 x 43.2 mm

FDMH292-R

FDME224

Approvals VdS G206124

4.4.1 Accessories for FDM224, FDM224H

DMZ1197-AC Protective cover Part no. BPZ:5223550001

Application Protects the manual call point from unintentional glass break. Technical data

5 pieces Color transparent

DMZ1197-AD Seal for wet areas Part no. BPZ:5470680001

Application Protects the manual call point in wet applications. Technical data

5 pieces Color transparent

Page 26: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

26

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

– V-plug PA M20 x 1.5 Part no. A5Q00008131

Application For locked the unused openings at the housing FDMH292-R. Technical data Color black

Dimensions M20 x 1.5 mm

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055

Application For surface-mounted feed lines. For the application in dry rooms. Technical data Color red

Locking plug 1 hole (10 pcs.)

Locking plug 2 holes (10 pcs.)

Dimensions M20 x 1.5

4.4.2 Spare parts for FDM224, FDM224H

DMZ1196-AC Glass Part no. BPZ:4942050001

Application Use as spare part.

10 pieces

DMZ1195 Key Part no. BPZ:4851910001

10 pieces

Application Only for housing FDMH293-x Use as spare part.

Page 27: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

27

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.5 Manual call point FDM223 complete with indirect operation

FDM223 Manual call point complete, housing red with

glass , key, switching unit and locking plug Part no. A5Q00008098

Documents Product data sheet 007001 Technical description 007002

Consists of: – Housing red – Glass – Key – Switching unit – 2 locking plugs (2 holes)

– 2 labels standard with house and Feuerwehr/Brandmelder Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN60529/IEC529 – mit Dichtung DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 134.3 x 134.3 x 43.2 mm

Approvals VdS G204002, LPCB 126ac/02

Page 28: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

28

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.6 Manual call point FDM223 with indirect operation

FDMH293-R Housing red with glass and key Part no. A5Q00004023 FDMH293-Y Housing yellow with glass and key Part no. A5Q00004908 FDMH293-B Housing blue with glass and key Part no. A5Q00004909 FDMH293-G Housing green with glass and key Part no. A5Q00004911 FDME223 Switching unit Part no. A5Q00003087 Documents Product data sheet 007001

Technical description 007002

Application For the immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. Addressable applicable. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005, yellow,

~RAL 1023, green, ~RAL 6024 Protection category EN60529/IEC529 – with seal DMZ1197-AD

IP44 IP64

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 134.3 x 134.3 x 43.2 mm Approvals VdS G204002, LPCB 126ac/02

Page 29: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

29

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

4.7 Manual call point 'Heavy Duty' FDM223H with indirect opera-tion

FDMH292-R Heavy Duty housing red with glass, hexagon wrench key, 3 nipples and plate fire brigade / fire detector

Part no. A5Q00005525

FDME223 Switching unit Part no. A5Q00003087 Documents Product data sheet 008345

Technical description 007002

Application For the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. Only for surface mounted feed lines in easily accessible places, Tunnels, Industry etc. Addressable. The housing is equipped with one opening at the top and two openings at the bottom for nipples (en-closed) and for M20 metal screwed cable glands –> see accessories. For IP66 applications the unused openings must be locked with the V-plug –> see accessories. Function Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back be-fore closing the door again. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current (quiescent) 200 μA Ext. alarm indicator 2 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN60529/IEC529 – with seal DMZ1197-AD and V-plug

IP44 IP64

System compatibility C-NET FS720 Standards EN54-11, EN54-17 Dimensions 134.3 x 134.3 x 43.2 mm

FDMH292-R

FDME223

Approvals VdS G205014, LPCB 126ac/03

4.7.1 Accessories for FDM223, FDM223H

DMZ1197-AC Protective cover Part no. BPZ:5223550001 Details see chapter 4.4.1

DMZ1197-AD Seal for wet areas Part no. BPZ:5470680001 Details see chapter 4.4.1

Page 30: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Manual call points in C-NET

30

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

– V-plug PA M20 x 1.5 Part no. A5Q00008131 Details see chapter 4.4.1

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Details see chapter 4.4.2

4.7.2 Spare parts for FDM223, FDM223H

DMZ1196-AC Glass Part no. BPZ:4942050001 Details see chapter 4.4.2

DMZ1195 Key Part no. BPZ:4851910001 Details see chapter 4.4.2

Page 31: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm devices in C-NET

31

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

5 Alarm devices in C-NET

5.1 Alarm sounders FDS221

FDS221-R Alarm sounder red Part no. A5Q00004117 FDS221-W Alarm sounder white Part no. A5Q00006711 Documents Product data sheet A6V10203095

Technical description 008109

Application Only applicable with addressable detector base FDB221 or FDB222. For recess supply line. For surface supply line with FDB221 until cable 6 mm in diameter, otherwise use base attachment FDB291. Along escape routes, corridors, staircases and is mounted on the wall or on the ceiling. Function Loud alarming in case of fire alarm, clearly recognizable as danger signal. Synchronized of acoustic signals with all other alarm sounder devices and sounder bases in the same detector line (C-NET). Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current quiescent condition Operating current ton activated

250 μA 3.5 mA

Ext. alarm indicator 2 Connection terminals according to the detector base Number of sounds 11; 2 activation levels, 3 sound intensities Sound intensity 80... 99 dBA Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, white, ~RAL 9010 Protection category EN60529/IEC529 with – Base FDB221 or FDB222 – Base attachment FDB291 – Base FDB221 and sealing element FDBZ295 – Base attachment wet FDB293

mounting on the wall with cable feed from bottom –> IP43, otherwise IP40 IP44 IP54

System compatibility C-NET FS720 Standards EN54-3, EN54-17 Dimensions Ø100 x 43 mm

FDS221-R

FDS221-W

Approvals VdS G204073, LPCB request

Page 32: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm devices in C-NET

32

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

5.2 Alarm sounder beacons FDS229

FDS229-R Alarm sounder beacon, red Part no. A5Q00023093 FDS229-A Alarm sounder beacon, orange Part no. A5Q00023092 Documents Product data sheet A6V10229545

Technical description 010095 Application Only applicable with addressable detector base FDB221 or FDB222. For recess supply line. For surface supply line with FDB221 until cable 6 mm in diameter, otherwise use base attachment FDB291. Along escape routes, corridors, staircases and is mounted on the wall or on the ceiling. Function Acoustic and optical alarming in case of fire alarm, clearly recognizable as danger signal. Synchronized of acoustic signals with all other alarm sounder devices and sounder bases in the same detector line (C-NET). Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current quiescent condition – Operating current ton activated – Operating current beacon activated – Operating current ton and beacon activated

250 μA 3.5 mA 3.5 mA 7.0 mA

Sounds 11; 2 activation levels, 3 sound intensities Sound intensity 80... 99 dBA Number of flashing pattern 1 (intermittent) Light intensity (unit: candela, cd) at 32 VDC (depending of viewing angle -30… +30 °): – with hood red – with hood orange

1.27… 3.2 cd 1.1… 2.8 cd

Ext. alarm indicator 2 Connection terminals according to the detector base Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color transparent red, transparent orange Protection category EN60529/IEC529 with – Base FDB221 or FDB222 – Base attachment FDB291 – Bsse FDB221 and sealing element FDBZ295 – Base attachment wet FDB293

mounting on the wall with cable feed from bottom –> IP43, otherwise IP40 IP44 IP54

System compatibility C-NET FS720 Standards EN54-3, EN54-17 Dimensions Ø100 x 43 mm

FDS229-R

FDS229-A

Approvals VdS G207156, LPCB 126ar/01, LPCB 126ar/02

5.2.1 Accessories for FDS221, FDS229

FDB221 Detector base addressable Part no. A5Q00001664 FDB222 Detector base addressable, flat Part no. S54319-F1-A1

Application For alarm sounders and alarm sounder beacons. For recess supply line. Only FDB221for surface supply line until cable 6 mm in diameter. Technical data Screwless connecting terminals 'orange' wire cross-sectional area from 0.2 … 1.5 mm2 Color white, ~RAL 9010 Dimensions – FDB221 – FDB222

Ø100 x 22 mm Ø100 x 17 mm

FDB221

FDB222

Page 33: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm devices in C-NET

33

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDBZ295 Sealing element Part no. S54319-F10-A1

Application For higher protection category. Use only with base FDB221 and for recess supply wiring. Note: Not usable together with the designation plate FDBZ291. Technical data

Dimensions Ø106 x 28 mm

FDBZ293 Detector locking device Part no. A5Q00005035

Application Threaded pin M3 x 6 for protection against theft. Scope of delivery 2 hexagonal wrenches 100 threaded pins Technical data Threaded pin M3 x 6

Hexagonal wrench 1.5 mm

FDBZ291 Designation plate (10x) Part no. A5Q00002621 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

FDB291 Base attachment Part no. A5Q00001603

Application For the supply of surface-mounted lines > ∅6 mm. Breakouts for surface supply line. Technical data Color white, ~RAL 9010

Dimensions Ø120 x 25 mm

Page 34: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm devices in C-NET

34

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDB293 Base attachment wet with seal Part no. A5Q00003945

Application For mounting in humid or wet environments, and when the detector-heating unit is used. For higher protection category (IP54 applications). Technical data Color white, ~RAL 9010

Dimensions 135 x 135 x 49 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

DBZ1193A Designation plate (10x) Part no. BPZ:4864330001

Application To identify the location address. For base attachment wet FDB293. Technical data Color transparent

10 pieces

Dimensions 62 x 52 mm

DBZ1194 Protective cage Part no. BPZ:4677110001

Application For the protection of the detector against damage. Can only be used together with the base attachment wet FDB293. Technical data Dimensions Ø160 x 126 mm

Page 35: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Alarm devices in C-NET

35

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

5.3 Sounder base DBS720

DBS720 Sounder base Part no. S54319-F5-A1 Documents Product data sheet A6V10203095

Technical description A6V10218037

Application Compatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter. The signal base and the detector compose a unity, which already has a base and is mounted on ceil-ings, e.g. in hotel rooms, hospitals and nursing homes. Function The sounder base serves for acoustic alarming in the addressed FS720 fire detection system. In case of a fire alarm, the signal base triggers an acoustic signal in parallel to the flashing of the detec-tor LED. Synchronized of acoustic signals with all other alarm sounder and sounder beacon devices in the same detector line (C-NET). Technical data Communication protocol detector / ton element C-NET / EAI-Link Operating voltage 12... 33 VDC Operating current quiescent condition Operating current ton activated

150 μA 1.2 mA

Ext. alarm indicator 2 Number of sounds 11; 2 activation levels, 2 sound intensities Sound intensity 80... 88 dBA Operating temperature -25... +70 °C (follow data from detector) Storage temperature -30... +70 °C Humidity ≤95 % rel. Connection terminals Wire cross-sectional area from 0.2... 1.6 mm2 Color white, ~RAL 9010 Protection category EN60529/IEC529 – with detector base seal RS720

IP41 IP42

System compatibility C-NET FS720 Standards EN54-3 Dimensions 153 x 93 x 27 mm

Approvals VdS G209133

5.3.1 Accessories for DBS720

FDBZ291 Designation plate Part no. A5Q00002621 Details see chapter 2.2.1

RS720 Detector base seal Part no. S54319-F8-A1 Details see chapter 2.2.1

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

Page 36: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

36

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

6 Line separator, Input/output modules in C-NET

6.1 Line separator FDCL221

FDCL221 Line separator Part no. A5Q00004011 Documents Product data sheet 007065

Technical description 007063

Application To avoid the breakdown of several stub lines in case of a short circuit, line separators may be inserted. The line separator is used where several stub lines are connected to the C-NET at one point. Retrofitting of existing, collective systems to the addressed Cerberus PRO FS720 fire detection system. Function The separator is an electronic switch, which is integrated in the C-NET and separates the negative conductor in case of a short circuit, so that the short circuit-free side can continue to be operated. The separator has 2x2 connectors for the detector line. Yellow LED for the status indication signals the short circuit separation. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current 250 μA Operating temperature -25... +70 °C Storage temperature -30... +80 °C Humidity ≤95 % rel. Color transparent Protection category EN60529/IEC529 IP44 System compatibility C-NET FS720 Standards EN54-17 Dimensions 44 x 47,5 x 10 mm

Approvals VdS G204030, LPCB 126ae/01

Page 37: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

37

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

6.2 Multi line separator FDCL221-M

FDCL221-M Line separator Part no. S54312-F6-A1 Documents Product data sheet A6V10230308

Technical description A6V10224006

Application To avoid the breakdown of several stub lines in case of a short circuit, line separators may be inserted. The multi line separator is used where several stub lines are connected to the C-NET at one point. The module can also be connected to 2 separate loops Retrofitting of existing, collective systems to the addressed Cerberus PRO FS720 fire detection system. Function The module has total 9 separators. Each separator is an electronic switch, which is integrated in the C-NET and separates the negative conductor in case of a short circuit, so that the short circuit-free side can continue to be operated. The separator has connections for the detector lines, connections for the stub lines (T taps), jumpers for programming of operation mode (1 loop or 2 loop mode), yellow LED for the status indication signals the short circuit separation. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current 2.25 mA (9 x 250 μA) or

2 x 1 mA (4 x 250 μA) Number of separators 9 with 1 loop

2 x 4 with 2 loops Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color – Housing – Cover – Aux. housing FDCH221

white, ~RAL 9010 Transparent, matt white, ~RAL 9010

Protection category EN60529/IEC529 – With ext. Housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN54-17

Approvals VdS G209162

6.2.1 Accessories for FDCL221 / FDCL221-M

– U-rail TS35, L=122 mm Part no. BPZ:5644780001 – U-rail TS35, L=288 mm Part no. BPZ:5644230001

Application For the mounting of the line separator. For the series mounting of input/output modules together with mounting feet.

Page 38: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

38

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

6.3 Input modules FDCI221, FDCI222

FDCI221 Input module Part no. S54312-F1-A1 Documents Product data sheet A6V10202196

Technical description A6V10211122

Application For the connection of 1 independent, potential-free make or break contact for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). Addressable applicable. Function 1 input for potential-free contact. Status indication by LED. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current max. 0.3 mA Connection terminals 0.2... 2.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN54-17, EN54-18 Dimensions 95 x 71 x 23 mm

FDCI221

2 Resistors 1 x 3k3; 1 %; 0.25 W 1 x 680 Ω; 1 %; 0.25 W 2 Mounting feet

Approvals VdS G209066, LPCB request

FDCI222 Input module Part no. A5Q00001984 Documents Product data sheet 007024

Technical description 007023

Application For the connection of 4 independent, potential-free make or break contacts for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). Addressable applicable. Function 4 inputs for potential-free contacts. Status indication by LED. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current 0.25... 0.35 mA Connection terminals 0.2... 1.5 mm2 (2.5 mm2) Operating temperature -25... +60 °C Storage temperature -30... +65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN54-17, EN54-18 Dimensions 130 x 90 x 20 mm

FDCI222

8 Resistors 4 x 3k01; 1 %; 0.25 W 4 x 1k15; 1 %; 0.25 W 2 Mounting feet

Approvals VdS G204028, LPCB 126ad/01

Page 39: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

39

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

6.4 Input/output modules FDCIO22x

FDCIO221 Input/output module Part no. S54312-F2-A1 Documents Product data sheet A6V10202196

Technical description A6V10211122

Application For the connection of 1 independent, potential-free make or break contact for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors, ventilation, air conditioning, etc. Addressable applicable. Function 1 input for potential-free contact. 1 output configurable via jumper – not monitored –> 1 potential-free relay contact (30 VAC, 2 A / 30 VDC, 2 A) – monitored –> 1 relay contact (30 VDC, 2 A) Status indication by LED. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current max. 0.4 mA Relay output (ohm) 30 VAC, 2 A, max. 60 VA

30 VDC, 2 A, max. 60 W Anschlussklemmen 0.2... 2.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color Gehäuse / Deckel white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards EN54-17, EN54-18 Dimensions 95 x 71 x 23 mm

FDCIO221

3 Resistors 2 x 3k3; 1 %; 0.25 W 1 x 680 Ω; 1 %; 0.25 W 2 Mounting feet

Approvals VdS G209067, LPCB request

FDCIO222 Input/output module Part no. A5Q00002369 Documents Product data sheet 007024

Technical description 007023

Application For the connection of 4 independent, potential-free make or break contacts for the acknowledgement of technical states (e.g. door or ventilation control) or for alarm actuation (e.g. sprinkler alarm). For the decentralized control of fire doors, ventilation, air conditioning, etc. Addressable applicable. Function 4 inputs for potential-free contacts. 4 outputs with 4 potential-free relay contacts for fire control installations. Status indication by LED. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current 0.6... 0.75 mA Relay output (ohm) 250 VAC, 4 A, max. 1000 VA

30 VDC, 4 A, max. 120 W Connection terminals 0.2... 1.5 mm2 (2.5 mm2) Operating temperature -25... +60 °C Storage temperature -30... +65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN54-17, EN54-18 Dimensions 130 x 90 x 20 mm

FDCIO222

8 Resistors 4 x 3k01; 1 %; 0.25 W 4 x 1k15; 1 %; 0.25 W 2 Mounting feet

Approvals VdS G204029, LPCB 126ad/02

Page 40: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

40

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDCIO223 Transponder Part no. S24218-B102-A1 Documents Product data sheet 009168

Technical description 009122

Application For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-Zener-diode barrier (SB3) for explosion-hazard areas). For monitored controls of e.g. smoke dampers, alarm devices, door magnets and extinguishing activa-tion devices (adhere to country-specific instructions). Monitored signal input for status and alarm messages or for acknowledging technical status. Addressable applicable. Function The 2 inputs/outputs can be parameterized autonomously in each case as detector line collective, con-tact input, control output, control output and input as acknowledgement with selectable monitoring time frame. Technical data Operating voltage C-NET 12... 33 VDC External power supply: Input voltage 18... 32 VDC In-/outputs as collective detector line GMT Siemens/Cerberus, Synova 300 or similar Collective line factor (KLK) / end of line 32 / 20 V Transzorb diode Control output 24 VDC ±5 % / 2 A (fuse on site) Contact input End of line combinations

3,3k Ω/680 Ω, 2,7k Ω/560 Ω, 3,3k Ω

Operating temperature -25... +60 °C Storage temperature -30... +65 °C Humidity ≤95 % rel. Communication protocol C-NET Connection terminals 0.2... 1.5 mm2 (Auxiliary terminal 2.5 mm2) Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN54-17, EN54-18 Dimensions 132 x 90 x 24 mm

FDCIO223

2 Transzorb diode 20 V 2 x 560 Ω 1 %; 0.25 W 2 x 680 Ω 5 %; 0.25 W 2 x 2,7k Ω 1 %; 0.35 W 2 x 3,3k Ω 5 %; 0.25 W 2 Mounting feet

Approvals VdS G206054

FDCIO224 Input/output module Part no. A5Q00018689 Documents Product data sheet 007024

Technical description 007023

Application For the VdS interface for extinguishing activating devices. Addressable applicable. Function 4 inputs for potential-free contacts. 4 outputs with 4 potential-free relay contacts (230 VAC / 4 A) for the VdS interface for extinguishing controls. Status indication by LED. Technical data Communication protocol C-NET Operating voltage 12... 33 VDC Operating current 0,6... 0,75 mA Relay output (ohm) 250 VAC, 4 A, max. 1000 VA

30 VDC, 4 A, max. 120 W Connection terminals 0.2... 1.5 mm2 (2.5 mm2) Operating temperature -25... +60 °C Storage temperature -30... +65 °C Humidity ≤95 % rel. Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN54-17, EN54-18 Dimensions 130 x 90 x 20 mm

FDCIO224

8 Resistors 4 x 2k7; 1 %; 0.35 W 4 x 560 Ω; 1 %; 0.25 W 2 Mounting feet

Approvals VdS G207001

Page 41: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Line separator, Input/output modules in C-NET

41

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

6.4.1 Accessories for FDCI22x, FDCIO22x

– U-rail TS35, L=122 mm Part no. BPZ:5644780001 – U-rail TS35, L=288 mm Part no. BPZ:5644230001 Details see chapter 6.2

FDCH221 Housing for input/output modules Part no. S54312-F3-A1

Application For the mounting of the input/output modules and transponder for humid, wet applications. Technical data Protection category EN60529/IEC529 IP65 Color housing / cover white, ~RAL 9010 / transparent matt Dimensions 207 x 119 x 48 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

6.4.2 Spare part for FDCI22x, FDCIO22x

FDCM291 Mounting feet for input/output modules Part no. A5Q00003855

25 pieces

Application Installation in range of the input/output modules with mounting feet onto top U-rail TS35. Use as spare part.

Page 42: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Special detectors in C-NET

42

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

7 Special detectors in C-NET

7.1 Aspirating smoke detectors

LaserFOCUS VLF-250 Aspirating smoke detector with display Part no. VLF-250-SIE

see footnote 1) LaserFOCUS VLF-500 Aspirating smoke detector with display Part no. VLF-500-SIE

see footnote 1) Document Product data sheet A6V10221433

Application VLF-250 The LaserFOCUS detector is a very early warning smoke detector (Aspirating Smoke Detector ASD) designed to protect small, business-critical environments of less than 250 sqm. VLF-500 The LaserFOCUS detector is a very early warning smoke detector (Aspirating Smoke Detector ASD) designed to protect small, business-critical environments of less than 500 sqm. Function The detector works by continually drawing air into sample holes in a pipe network. The air is filtered and passed into a detection chamber where light scattering technology detects the presence of very small amounts of smoke. Detector status information is communicated on the detector display. The C-NET interface card is integrated. Technical data Communication protocol C-NET Operating voltage 18… 30 VDC Quiescent current 220 mA Alarm current 295 mA Display 4 Alarm state indicators, Fault and disabled indi-

cators, Smoke level indicator Area coverage – VLF-250 – VLF-500

up to 250 m2

up to 500 m2

Alarm threshold 0.025 - 2.00 %/m / Info alarm, Pre-alarm 0.025 - 20.00 %/m / Fire 1, Fire 2

Air inlet pipe Accepts both metric and American standard pipe sizes, External diameter 25 mm, Internal diameter 21 mm

Pipe length – VLF-250 – – VLF-500

max. 1 x 25 m (max. 12 holes), max. 2 x 15 m per branch (max. 6 holes per branch) max. 1 x 50 m (max. 24 holes), max. 2 x 30 m per branch (max. 12 holes per branch)

Relay output 3x 2 A / 30 V (Pre-alarm, Alarm, Fault) Terminals 0.2… 2.5 mm2 (30… 12 AWG) Dimensions (WxHxD) 255 x 185 x 90 mm Operating temperature 0... +40 °C Humidity ≤95 % rel. (no condensation) Protection category IP30

Approval VdS, LPCB 1) Delivery time and ordering approximately 14 working days from date of order from:

EMEA Xtralis (UK) Ltd. Focus 31, Mark Road Hemel Hempstead, Hertfordshire HP2 7BW United Kingdom Tel: + 44 1442 242330 Fax: +44 1442 249327

APAC Xtralis Pty Ltd. 4 North Drive, Virginia Park 236-262 East Boundery Road (PO Box 102) Bentleigh East, Victoria, Australia, 3165 Tel: +61 3 9936 7200 Fax: +61 3 9936 7201

Warranty for all Xtralis products is 24 months. Contact Xtralis (UK) for information about warranty, replacement parts, repair and return items.

Page 43: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

43

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8 Conventional and collective devices

8.1 Point detectors Synova conventional/SynoLINE300

OP320C Optical smoke detector Part no. BPZ:5081460001 Documents Product data sheet 006801

Technical description 1704 Application The Optical detector OP320C is an excellent all-round detector. It is particularly suitable anywhere where there are normal environmental conditions. Function The Optical detector OP320C has an excellent good all-round performance within the Synova 300 range. It has a completely new optical chamber and the latest electronics which opens up new dimen-sions in safety and functionality. The base SO320 must be ordered separately. Technical data Communication protocol conventional/SynoLINE300 Operating voltage 16... 28 VDC Operating current without smoke with smoke

max. 100 μA max. 170 μA

Operating temperature -10... +55 °C Storage temperature -20... +65 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-7 Color white, ~RAL 9010 (can be sprayed a different

color) Dimensions Ø100 x 44 mm (incl. base)

Approvals VdS G298039, LPCB 531c/04

OH320C Multi-sensor detector Part no. BPZ:5364190001 Documents Product data sheet 006886

Technical description 1917 Application The OH320C is an extremely sensitive smoke detector. It is the right detector for anywhere where early detection of smoke or fire is important (e.g. in timbered and half-timbered houses, museums, galleries etc.). Function The OH320C is the most sensitive detector in the Synova 300 product range. It has a completely new optical and latest electronic system, which opens up new dimensions with regard to safety and function. The base SO320 must be ordered separately. Technical data Communication protocol conventional/SynoLINE300 Operating voltage 16... 28 VDC Operating current ohne Rauch mit Rauch

max. 100 μA max. 170 μA

Operating temperature -10... +55 °C Storage temperature -20... +65 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-7 Color white, ~RAL 9010 (can be sprayed a different

color) Dimensions Ø100 x 52 mm (incl. base)

Approvals VdS G200109, LPCB 531c/02

Page 44: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

44

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

HI320C Heat detector (rate of rise and maximum) Part no. BPZ:5081590001 Documents Product data sheet 006885

Technical description 1703 Application The HI320C is best suited for locations in which different ambient temperatures occur (e.g. mechanical workshops, tool rooms etc.). Furthermore, its innovative design makes it particularly suitable anywhere where dust, dirt (e.g. sawmills) or high humidity (e.g. wet cells) could affect the operation of traditional detectors. Function The HI320C is an extremely reliable rate of rise and maximum temperature detector for demanding applications. It is characterized by reliable response behavior, not only in the event of temperature rises which are slow, but also where the temperature rises are fast. The base SO320 must be ordered separately. Technical data Communication protocol conventional/SynoLINE300 Operating voltage 16... 28 VDC Quiescent current max. 100 μA Operating temperature -10... +50 °C Storage temperature -20... +65 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-5: A1R Color white, ~RAL 9010 (can be sprayed a different

color) Dimensions Ø100 x 36 mm (incl. base)

Approvals VdS G298040, LPCB 531b/03

HI322C Heat detector (maximum) Part no. BPZ:5316470001 Documents Product data sheet 006885

Techn. description 1703 Application The HI322C is a reliable heat detector for locations in which there are large fluctuations in temperature. It continuously measures the ambient temperature and reacts if there is a sustained overshoot of de-fined maximum values. Function The HI322C is a reliable heat detector for locations in which there are large fluctuations in temperature. It continuously measures the ambient temperature and reacts if there is a sustained overshoot of de-fined maximum values. The base SO320 must be ordered separately. Technical data Communication protocol conventional/SynoLINE300 Operating voltage 16... 28 VDC Quiescent current max. 100 μA Operating temperature -10... +50 °C Storage temperature -20... +65 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-5: A1R Color white, ~RAL 9010 (can be sprayed a different

color) Dimensions Ø100 x 36 mm (incl. base)

Approvals VdS G298040, LPCB 531b/03

Page 45: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

45

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.1.1 Detector base and accessories

SO320 Base Part no. BPZ:5085990001

Application Base made of impact, scratch-proof plastic and environmentally safe materials. The base is completely covered by the detector. It fits all Synova 300 series detectors, conventional and addressable. Standard click-concept, with screwless terminals for easy installation. Click-in connection for alarm indicators is standard on the base. Fits all standard flush mounting boxes from 55 to 80 mm. Technical data Cable capacity 0.2... 1.5 mm² Color white, ~RAL 9010

SOA322 Base attachment Part no. BPZ:5358340001

Application Base attachment for feeding in surface wiring and to provide more wire space. It may also be used as a junction box where up to 30 wires can be connected. Up to 10 connection terminals DBZ1190-AB can be clicked into to the base attachment SOA322. The base SO320 is mounted using a spring-loaded catch. Technical data Dimensions Ø100 x 20 mm Cable capacity 0.2... 2.5 mm²

Color white, ~RAL 9010

TP320 Detector locking device Part no. BPZ:5093100001

Application To protect the detector from theft. Mounts on the detector base SO320.

50 pieces

DBZ1190-AB Connection terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

Page 46: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

46

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.2 Manual call points FDM1101A conventional/SynoLINE300

FDM1101A-RG Manual call point with glass plate Part no. S54371-F6-A3 FDM1101A-RP Manual call point with resettable plastic element Part no. S54371-F6-A4 Documents Product data sheet A6V10206486

Technical description A6V10201152 Application For immediate manual actuation of a fire alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. For surface mounting the housing base FDMH295-x must be ordered separately. Function FDM1101A-RG Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. FDM1101A-RP Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. Technical data Communication protocol conventional/SynoLINE300 Operating voltage max. 28 VAC or VDC Operating current 100 mA… max. 1 A Terminal block 0.28… 1.5 mm² Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-11 Color red, ~RAL 3000 Dimensions 87 x 87 x 20 mm

Approvals – FDM1101A-RG – FDM1101A-RP

VdS 209149, LPCB 126as/03 VdS 209149, LPCB 126as/04

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438 Details see chapter 4.2

FDMH295-R

FDMH295-S

Page 47: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

47

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.2.1 Accessories for FDM1101A

FDMC295 Protective cover Part no. A5Q00013440 Details see chapter 4.2.1

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.2.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.2.2 Spare parts for FDM1101A

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445 Details see chapter 4.2.2

FDMK295 Key Part no. A5Q00013448 Details see chapter 4.2.2

Page 48: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

48

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.3 Alarm indicators for conventional/SynoLINE300 devices

AI320 Alarm indicator Part no. BPZ:5163030001 Document Product data sheet 007267

Application The AI320 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE300 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI320 is suitable for door frames. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 6... 28 VDC Operating current max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 62 x 37 x 17 mm

AI322 Alarm indicator Part no. BPZ:5163160001 Document Product data sheet 007267

Application The AI320 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE300 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI322 is suitable for surface wall mounting. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 6... 28 VDC Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 85 x 85 x 25 mm

8.3.1 Accessory for AI322

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different makes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

Page 49: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

49

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.4 Point detectors AlgoRex collective/SynoLINE600

DO1101A Smoke detector Part no. BPZ:4930020001 Documents Product data sheet 001578

Technical description 1001 Application For the early warning of smoke-forming flaming fires and smoldering fires. The base DB1101A must be ordered separately. Function The DO1101A has a new, high performance opto-electronic sensor system. It has uniform response behavior for different types of fire. It has a high resistance to soiling and temperature fluctuation. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 24 VDC Quiescent current max. 100 μA Operating temperature -25... +60 °C Protection category EN60529/IEC529 IP44 Standard EN54-7 Dimensions Ø115 x 51 mm (incl. base) Color white, ~RAL 9010

Approvals VdS G294005, LPCB 126a/08

DT1101A Heat detector Part no. BPZ:4931700001 DT1102A Heat detector Part no. BPZ:4931830001 Documents Product data sheet 001578

Technical description 1039 Application DT1101A: For the monitoring of rooms and installations where in the event of fire, a rapid increase in temperature can be expected, or other types of detector cannot be used due to operational reasons. DT1102A: For the monitoring of rooms and installations in which high ambient temperatures can be expected (up to + 70 °C). The base DB1101A must be ordered separately. Function Precise maximum temperature alarm activation with quality thermo sensor. Response behavior immune to deceptive phenomena with rapid and slow increases in temperature. Intelligently designed differential characteristics. DT1101A: Heat detector with wide application range (up to +50 °C) DT1102A: Heat detector for high ambient temperatures (up to +70 °C) Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 24 VDC Quiescent current max. 100 μA Operating temperature -25... +50 °C Protection category EN60529/IEC529 IP44 Standard – DT1101A – DT1102A

EN54-5: A1R EN54-5: B

Dimensions Ø115 x 54.5 mm (inkl. Sockel) Color white, ~RAL 9010

Approvals – DT1101A – DT1102A

VdS G294017, LPCB 126b/03 VdS G294018, LPCB 126c/03

Page 50: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

50

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DB1101A Detector base Part no. BPZ:4931830001 Document Product data sheet 001035

Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught, dirt and dripping water from above. Screwless terminals for easy installation. Space for auxiliary terminals as micro terminals (0.5 mm²) and connection terminals (2.5 mm²). Fits all standard flush-mounted boxes from 55 to 80 mm. Technical data Cable capacity 0.2... 2.5 mm² Dimensions Ø115 x 21 mm

Color white, ~RAL 9010

8.4.1 Accessories for detector base

DBZ1191 Base attachment, surface mounting Part no. BPZ:4540830001

Application For surface wiring feed and provision of more wire loop space. Bases DB1101A are mounted using a spring-loaded catch. Technical data Dimensions Ø116 x 22 mm

5 pieces Color white, ~RAL 9010

DBZ1191A-AA Base attachment flat, surface mounting Part no. BPZ:5011270001

Application For surface-mounted applications with cables up to Ø6 mm and to use for existing mounting holes. Bases DB1101A are mounted using a spring-loaded catch. Technical data Dimensions Ø116 x 11 mm

10 pieces Color white, ~RAL 9010

DBZ1192 Base attachment humid Part no. BPZ:4588140001

Application For installation in damp and corrosive environments. M20 x 1.5 cable entries are located on the side of the base attachments for easy access. Technical data Dimensions 135 x 135 x 45 mm

Color white, ~RAL 9010

DBZ1194 Protective cage Part no. BPZ:4677110001

Application To protect the detector from damage. Can only be used together with the base attachment humid. Technical data Dimensions Ø160 x 126 mm

Page 51: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

51

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DBZ1192-AA Base attachment wet Part no. BPZ:5355590001

Application As DBZ1192 but for IP55 protection for heat detectors DT110xA only. Technical data Dimensions 135 x 135 x 45 mm Color white, ~RAL 9010

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

DBZ1195A Acoustic base Part no. BPZ:4940140001 Document Product data sheet 001444

Application The base DBZ1195A has an integrated base sounder. It is mainly used for hotel rooms or wherever it is sensible to have an acoustic warning when a detector is activated. The sounder is operated when the detector LED is lit. The base DB1101A is mounted in the acoustic base using a spring-loaded catch. The acoustic base is connected to the external output of the detector alarm indicator direct. Technical data Sound level ≥75 dB / 1 m Operating temperature -10... +60 °C Dimensions Ø128.5 x 32 mm (without detector) Color white, ~RAL 9010 Protection category EN60529/IEC529 IP44 Humidity ≤95 % (no condensation) Standard EN54-3

Approvals VdS G209137

DBC1191A-AA Relay base Part no. BPZ:5017870001 Document Product data sheet 001566

Application The base DBC1191A-AA has an integrated relay. It enables the connection of a simple fire control output facility. The contact is activated when the detector LED is lit. The base DB1101A is mounted using a spring-loaded catch. Technical data Operating voltage external supply 10... 48 VDC Operating current 12... 24 mA Quiescent current 3.5... 7 mA Relay output 30 VDC / 1 A Operating temperature -10... +60 °C Dimensions Ø128.5 x 32 mm (without detector) Color white, ~RAL 9010 Protection category EN60529/IEC529 IP44

Humidity ≤95 % (no condensation)

Page 52: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

52

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

DBZ1190 Locking device Part no. BPZ:4585260001

Application To protect the detector from theft.

50 pieces

DBZ1190A-AC Detector heating Part no. BPZ:5167850001

Application Allows the AlgoRex series smoke detectors to operate under critical environmental conditions, for ex-ample where there is a danger of icing, moisture or condensation, in refrigeration plants, cold storage rooms, attics, loading ramps etc. Fits in DB1101A. Technical data Operating voltage 20... 30 VDC Operating current 35... 55 mA

Operating temperature -30... +40 °C

DBZ1193A Detector designation plate (10x) Part no. BPZ:4864330001

Application To indicate the location address. For DB1101A, DBZ1192, DBZ1192-AA.. Technical data Color transparent

10 pieces

Dimensions 62 x 52 mm

Page 53: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

53

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.5 Manual call points FDM1101 collective/SynoLINE600

FDM1101-RG Manual call point with glass plate Part no. S54371-F6-A1 FDM1101-RP Manual call point with resettable plastic element Part no. S54371-F6-A2 Documents Product data sheet A6V10206486

Technical description A6V10201150 Application For immediate manual actuation of a fire alarm. For indoor and outdoor application. For surface- and recess-mounted feed lines in easily accessible places. For surface mounting the housing base FDMH295-x must be ordered separately. Function FDM1101-RG Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is reset and the device is ready for operation again. FDM1101-RP Direct alarm actuation by pushing on the plastic element. The switch is reset with the key and the device is ready for operation again. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16… 28 VDC Operating current 60… 100 mA Terminal block 0.28… 1.5 mm² Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. (no condensation) Protection category EN60529/IEC529 IP44 Standard EN54-11 Color red, ~RAL 3000 Dimensions 87 x 87 x 20 mm

Approvals – FDM1101-RG – FDM1101-RP

VdS 209148, LPCB 126as/01 VdS 209148, LPCB 126as/02

FDMH295-R Back box Part no. A5Q00013437 FDMH295-S Back box with holes and socket Part no. A5Q00013438 Details see chapter 4.2

FDMH295-R

FDMH295-S

Page 54: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

54

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.5.1 Accessories for FDM1101

FDMC295 Protective cover Part no. A5Q00013440 Details see chapter 4.2.1

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.2.1

DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.5.2 Spare parts for FDM1101

FDMG295 Glass palte 'neutral' Part no. A5Q00013442 FDMP295 Plastic element 'neutral' Part no. A5Q00013445 Details see chapter 4.2.2

FDMK295 Key Part no. A5Q00013448 Details see chapter 4.2.2

Page 55: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

55

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.6 Manual call point DM1101 collective/SynoLINE600

FDMH291-R Housing red with key Part no. A5Q00002217 FDMH291-Y Housing yellow with key Part no. A5Q00004979 FDMH291-G Housing blue with key Part no. A5Q00004981 FDMH291-B Housing green with key Part no. A5Q00004980 DMA1101 Switching unit collective Part no. A5Q00005578 Document Product data sheet 007980

Application Collective manual call point for the immediate manual actuation of a fire alarm. For the connection on the collective/SynoLINE600 detector line. An integral LED provides visual indication of alarm. The housing FDMH291-x and the electronic unit DMA1101 must be ordered separately. Function Direct alarm actuation by pushing in the glass plate. By replacing the glass plate the push button is set back and the device is ready for operation again. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 26 VDC Operating current 60... 100 mA Anschlussklemmen 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN60529/IEC529 IP44 Standard EN54-11 Dimensions 87 x 87 x 46.6 mm Approvals LPCB 126w/02

8.6.1 Accessories for DM1101

FDMC291 Protective cover Part no. A5Q00001644

Application Protects the manual call point from unintentional glass break. Technical data

5 pieces Color transparent

Page 56: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

56

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 – Back nut Part no. A5Q00004479 Details see chapter 4.1.1

8.6.2 Spare parts for DM1101

FDMG291 Replacement glass Part no. A5Q00002122

Replacement glass for manual call point housings FDMH291-x.

10 pieces

FDMK291 Cover with key Part no. A5Q00001643

Spare key with call point front for manual call point housings FDMH291-x.

Page 57: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

57

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.7 Manual call points DM1103/04 collective/SynoLINE600

DMA1192-AA Housing red with glass and key Part no. BPZ:5222870001 DMA1192-AB Housing yellow with glass and key Part no. BPZ:5464250001 DMA1192-AC Housing blue with glass and key Part no. BPZ:5464120001 DMA1192-AD Housing green with glass and key Part no. BPZ:5090190001 DMA1103D Switching unit collective Part no. A5Q00004470 DMA1104D Switching unit collective Part no. A5Q00005925 Document Product data sheet 007980

Application Collective manual call point for the immediate manual actuation of a fire alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. For the connection on the collective/SynoLINE600 detector line. An LED always indicates the status of the manual call point. The housing DMA1192-xx and the electronic unit DMA1103D must be ordered separately. Function DM1103 Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be set back before closing the door again. DM1104 Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 26 VDC Operating current 60... 100 mA Anschlussklemmen 0,28… 1,5 mm2 Einsatztemperatur -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color red, ~RAL 3000, blue, ~RAL 5005,

yellow, ~RAL 1023, green, ~RAL 6024 Protection category EN60529/IEC529 – mit Dichtung DMZ1197-AD

IP54 IP65

Standard EN54-11 Dimensions 134 x 134 x 43 mm Approvals – DM1103 – DM1104

VdS G295036 VdS G299068, LPCB 126w/06

DMA1103D

DMA1104D

Page 58: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

58

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DM1103-L Manual release button complete Part no. A5Q00017630 Document Product data sheet 007980

Application Manual release button DM1103-L for the immediate manual actuation of a gas extinguishing system. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface-mounted feed lines to the DM1103-L the housing is equipped with opening at the top and bottom, with sealing studs for M20 cable glands or locking plug (2 locking plugs, 2 holes enclosed). Function For indirect extinguishing release by smashing in the glass plate and pressing the push button. To re-place the glass plate, open the housing door with the key. The push button must be set back before closing the door again. Technical data Communication protocol collective/SynoLINE600 Connection terminals 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color yellow, ~RAL 1023 Protection category EN60529/IEC529 – with seal DMZ1197-AD

IP54 IP65

Standard EN12094-3 Dimensions 134 x 134 x 43 mm

Approvals VdS G206029

DM1103-S Emergency stop button complete Part no. A5Q00014486 Document Product data sheet 007980

Application Emergency stop button DM1103-S for the stop function of a gas extinguishing system. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface-mounted feed lines to the DM1103-S, the housing is equipped with openings at the top and bottom, with sealing studs for M20 cable glands or locking plug (2 locking plugs, 2 holes enclosed). Function Indirect stop function by smashing in the glass plate and pressing the push button. As soon as the but-ton is not pressed any longer (self reset), the stopped extinguishing release will continue. To replace the glass plate, open the housing door with the key. Technical data Communication protocol collective/SynoLINE600 Anschlussklemmen 0.28… 1.5 mm2 Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color blue, ~RAL 5005 Protection category EN60529/IEC529 – with seal DMZ1197-AD

IP54 IP65

Standard EN12094-3 Dimensions 134 x 134 x 43 mm

Approvals VdS G206030

8.7.1 Accessories for DM1103/04

DMZ1197-AC Protective cover Part no. BPZ:5223550001

Application Protects the manual call point from unintentional glass break. Technical data

5 pieces Color transparent

Page 59: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

59

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DMZ1197-AD Protection seal Part no. BPZ:5470680001

Application Protects the manual call point in wet applications. Technical data

5 pieces Color transparent

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 4.2.1

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055

Application Für die Aufputz-Kabeleinführung. Für die Anwendung in trockenen Räumen. Technical data Color red

Locking plug 1 hole (10 pcs.)

Locking plug 2 holes (10 pcs.)

Dimensions M20 x 1.5

8.7.2 Spare parts for DM1103/04

DMZ1196-AC Spare glass Part no. BPZ:4942050001

Application Use as spare part.

10 pieces

DMZ1195 Key Part no. BPZ:4851910001

10 pieces

Application For housings DMA1192-xx. Use as spare part.

Page 60: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

60

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.8 Air sampling smoke detection kit FDBZ292

FDBZ292 Air sampling smoke detection kit Part no. A5Q00021362 Documents Product data sheet 009728

Installation 009726 Application Reliable monitoring of fresh air, used air and air re-circulation ducts for smoke in air conditioning and ventilation systems. The smoke detector DO1104A and the base DB1101A must be ordered separately. Function The air sampling smoke detection kit is mounted in the ventilation system where air flow measuring devices are usually installed, i.e. where there is no air vortex, change of direction, duct branching, duct narrowing or duct extensions. The distance to the branching, bracket or bend must have 5 x the duct diameter. In order to guarantee smoke detection, mount on the outside of the air duct sampling, after the last air inlet. Accessories for all shapes of duct. Technical data Smoke detector DO1104A Detector base DB1101A System compatibility collective/SynoLINE600, in C-NET via Trans-

ponder FDCIO223 Min. duct diameter 100 mm Permissible air speed 1... 20 m/s Air flow indicator ≥1 m/s Ambient temperature -20… +50 °C Dimensions (WxHxD) 146 x 235 x 183 mm Color grey, ~RAL 7001 Protection category IP54

Humidity ≤95 % rel.

8.8.1 Accessories FDBZ292

DO1104A Smoke detector, collective wide spectrum Part no. BPZ:5090640001 Documents Product data sheet 001578

Technical description 1001 Application Automatic fire detector with higher response sensitivity for the early warning of smoke-forming, flaming fires and smoldering fires. The base DB1101A must be ordered separately. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16… 24 VDC Quiescent current max. 100 μA Operating temperature -25… +60 °C Sensitivity typ. 1.8 %/m Protection category IP44 Color white, ~RAL 9010 Dimensions (ØxH) 115 x 51 mm (incl. base) Standard EN54-7

Approval VdS G297038

DB1101A Base for collective detector series Part no. BPZ:4863650001 Document Product data sheet 001035

Application Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught, dirt and dripping water from above. Screwless terminals for easy installation. Space for auxiliary terminals as micro terminals (0.5 mm²) and connection terminals (2.5 mm²). Fits all standard flush-mounted boxes from 55 to 80 mm. Technical data Cable capacity 0.2… 2.5 mm² Dimensions (ØxH) 115 x 21 mm

Color white, ~RAL 9010

Page 61: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

61

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDBZ292-AA Air flow tube 0.6 m Part no. A5Q00021363 FDBZ292-AB Air flow tube 1.5 m Part no. A5Q00021364 FDBZ292-AC Air flow tube 2.8 m Part no. A5Q00021366

Application The air flow tube is introduced through a hole drilled into the duct and shortened according to the diame-ter of the duct.

FDBZ292-AD Sealing kit for air flow tubes Part no. A5Q00021367

Application One sealing kit is necessary for – applications using the mounting bracket – applications using air flow tubes longer than 1 m Two sealing kits are necessary for – applications using the mounting bracket and air flow tubes longer than 1 m

FDBZ292-AF Mounting bracket Part no. A5Q00021369

Application The mounting bracket is used for uneven, round and insulated ducts.

Page 62: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

62

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.9 Alarm indicators for collective/SynoLINE600 devices

AI300 Alarm indicator Part no. BPZ:4930280001 Document Product data sheet 007162

Application The AI300 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE600 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI300 is suitable for door frames. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 5... 8 VDC Operating current max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 62 x 37 x 17 mm

AI340 Alarm indicator Part no. BPZ:4930440001 Document Product data sheet 007162

Application The AI340 alarm indicator is the visual parallel indication for fire detectors used on the SynoLINE600 detector line. The alarm indicators are an ideal supplement to fire detectors, where the detectors are mounted in positions which are difficult to reach (e.g. in switching cabinets) or difficult to see (e.g. in hotel rooms) and enable the triggered detector to be quickly located. The AI340 is suitable for surface wall mounting. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Technical data Operating voltage 5... 8 VDC Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Color white, ~RAL 9010

Dimensions 85 x 85 x 25 mm

8.9.1 Accessory AI340

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different makes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

Page 63: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

63

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DJ1193 Alarm indicator incl. insulating cap Part no. BPZ:4876360001 Document Product data sheet 007162

Application Made of transparent plastic, the alarm indicator is suitable for installation in door frames, switching panels, ceiling voids or special housings. The 23 mm Ø mounting hole is drilled by the system owner. The holder must be fitted with an insulating cap for safety. Function Indicator lamp to connect in parallel to automatic fire detectors. Technical data Operating voltage 6... 8 VDC Operating current max. 35 mA Humidity ≤95 % rel. Color transparent Protection category EN60529/IEC529 – with DCA1191 – with DJZ1193

IP56 IP65

Dimensions Ø22 x 51 mm

– Insulating cap Part no. BPZ:3048160001

Application Use as spare part.

8.9.2 Accessories for DJ1193

DCA1191 Housing with cover Part no. BPZ:4588560001 – Washer Part no. BPZ:2473130001

Application For surface mounting in humid, wet areas. Up to 4 alarm indicators DJ1193 can be built into the housing. Technical data Housing with cover Protection category EN60529/IEC529 IP56 Dimensions 135 x 135 x 65 mm Color white, ~RAL 9010 Washer

DCA1191

Washer

Dimensions Ø23 x 1 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

Page 64: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

64

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DJZ1193 Alarm indicator housing incl. washer Part no. BPZ:5302950001

Application For surface mounting in dry areas. 1 alarm indicator DJ1193 in can be built into the housing. Technical data Protection category EN60529/IEC529 IP65 Color white, ~RAL 9010

Dimensions 87 x 87 x 64 mm

MVH1 Mounting arm Part no. BPZ:3496190001

Application For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors. Technical data Pipe clamp ½"

Dimensions 20 x 20 x 290... 420 mm

8.10 Conventional alarm devices

8.10.1 Alarm devices AGN24.6, AGT24.1, AGS24.5

AGN24.6 Alarm device Part no. BPZ:5371170001 Document Product data sheet 001790

Application For fire detection and extinguishing systems. For inside and outdoor applications, although under roof or canopy. Removable base for simple surface mounting. Adapter base for cable entry with screwed cable gland. The adapter base ZS/AGN24.5 for IP65 must be ordered separately. Function Powerful alarm - recognizable as a danger signal even against a high background noise level. 28 differ-ent tones programmable. Remote-controlled switchover to continuous tone for two-stage alarm. Line monitoring possible by changing the polarity. Technical data Operating voltage 9... 30 VDC Alarmstrom 18 mA Operating temperature -25... +80 °C Tones 28 Frequency range 500... 4000 Hz Sound level at 24 V and 1 m 92.. 111 dB Cable capacity 0,28... 1,5 mm² Protection category EN60529/IEC529 – with ZS/AGN24.5

IP54 IP65

Approvals VdS G296013, LPCB 378b/01 Dimensions Ø93 x 63 mm

Color white, ~RAL 9003

ZS/AGN24.5 Adapter base Part no. BPZ:4242620001

Application Adapter base for AGN24.6, ALB24.1x for higher protection category. Technical data Protection category EN60529/IEC529 IP65 Color white, ~RAL 9003

Dimensions Ø93 x 30 mm

Page 65: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

65

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

AGT24.1 Alarm device Part no. BPZ:5371040001 Document Product data sheet 001790

Application For fire detection and extinguishing systems. For small to medium size rooms with a low background noise level. Function 4 different tones with two sound intensities. Remote-controlled change of tone for two-stage alarm. Technical data Operating voltage 9... 30 VDC Alarm current 3... 15 mA Operating temperature -25... +85 °C Tones 4 Frequency range 510… 970 Hz Sound level at 24 V and 1 m 86... 97 dB Cable capacity 0,28... 1,5 mm² Protection category EN60529/IEC529 IP42 Dimensions Ø110 x 35 mm

Color white, ~RAL 9003

AGS24.5 Mallory buzzer Part no. BPZ:2785020001 Document Product data sheet 001790

Application For small dry rooms with a low background noise level. For incorporation in equipment, panels, etc. (for front panels with a maximum thickness of 5 mm, a drill hole of 29.5 mm is adequate). Function Summer mit Dauerton. Technical data Operating voltage 18... 36 VDC Alarm current 12 mA Operating temperature -20... +40 °C Tones 1 Frequency range 2900 Hz Sound level at 24 V and 1 m 80 dB Cable capacity 0,28... 1,5 mm² Protection category EN60529/IEC529 IP20 Color schwarz

Dimensions 56 x 52 mm

Page 66: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

66

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.10.2 Flashing signal lamps ALB24.1R, ALB24.1OR

ALB24.1R Flashing signal lamp, red Part no. BPZ:5154270001 Document Product data sheet 001570

Application To identify buildings, entrances and exits: help can be brought quickly in an emergency. For inside and outside application. The adapter base ZS/AGN24.5 for IP65 must be ordered separately. Function Powerful light intensity generated by electronic flash tube. Verrippte Ribbed dome with strong diffusion. Line monitoring possible by changing the polarity. Technical data Operating voltage 20... 30 VDC Alarm current 155 mA (3.7 W) Operating temperature -20... +55 °C Flash frequency ca. 1 Hz (60/min.) Discharge energy 2 Joule Cable capacity 0.28... 1.5 mm² Protection category EN60529/IEC529 – mit ZS/AGN24.5

IP54 IP65

Dimensions Ø93 x 63 mm

ALB24.1OR Flashing signal lamp, orange Part no. BPZ:5154140001 Document Product data sheet 001570

Application To identify buildings, entrances and exits: help can be brought quickly in an emergency. For inside and outside application. The adapter base ZS/AGN24.5 for IP65 must be ordered separately. Function Powerful light intensity generated by electronic flash tube. Verrippte Ribbed dome with strong diffusion. Line monitoring possible by changing the polarity. Technical data Operating voltage 20... 30 VDC Alarm current 155 mA (3.7 W) Operating temperature -20... +55 °C Flash frequency ca. 1 Hz (60/min.) Discharge energy 2 Joule Cable capacity 0.28... 1.5 mm² Protection category EN60529/IEC529 – mit ZS/AGN24.5

IP54 IP65

Dimensions Ø93 x 63 mm

ZS/AGN24.5 Adapter base Part no. BPZ:4242620001

Application Adapter base for AGN24.6, ALB24.1x for higher protection category. Technical data Protection category EN60529/IEC529 IP65 Color white, ~RAL 9003

Dimensions Ø93 x 30 mm

Page 67: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

67

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.11 Devices for explosion-hazard area of zones 1 and 2

8.11.1 Interface for connection of the 'Ex' devices to C-NET

FDCIO223 Transponder Part no. S24218-B102-A1 Documents Product data sheet 009168

Technical description 009122 Application For connection of collective fire detectors (GMT/conventional line, GMT/conventional line with shunt-Zener-diode barrier (SB3) for explosion-hazard areas). Accessories and spare parts for FDCIO223 see chapter 6.4.1 and 6.4.2. Technical data Operating voltage C-NET 12... 33 VDC Communication protocol C-NET External power supply: Input voltage 18... 32 VDC In-/outputs as collective detector line collective GMT Siemens/Cerberus, Synova

conventional/SynoLINE300, collec-tive/SynoLINE600 or similar

Collective line factor (KLK) 32 Operating temperature -25... +60 °C Storage temperature -30... +65 °C Humidity ≤95 % rel. Connection terminals 0.2... 1.5 mm2 (Auxiliary terminal 2.5 mm2) Color housing / cover white, ~RAL 9010 / transparent matt Protection category EN60529/IEC529 – with auxiliary housing FDCH221

IP30 IP65

System compatibility C-NET FS720 Standards CEA GEI I-084, EN54-17, EN54-18 Dimensions 132 x 90 x 24 mm

FDCIO223

Approvals VdS G206054

8.11.2 Interface for connection of 'Ex' devices to SynoLINE600

DCA1191 Housing with cover Part no. BPZ:4588560001 DCA1192A Electronic unit, SynoLINE600 Bestell-Nr. BPZ:4942630001 DCB1192A Terminal base Bestell-Nr. BPZ:4942760001 Documents Product data sheet 001571

Technical description 1519 Application The input/output module DC1192 for galvanic isolation (detection line coupler) between control unit of collective line SynoLINE600 and shunt Zener diode barrier with fire detectors for explosion-hazard areas (via SB3). The housing DCA1191, the terminal base DCB1192A and the electronic unit DCA1192A must be or-dered separately. Technical data Primary line -> collective/SynoLINE600 – Compatibility E3M080, CI1110/15, FC330A, FC10, FC700A,

CZ10, KB24, GF24 Secundary line -> collective/SynoLINE600 – Operating voltage 18... 22 VDC – Operating current max. 5 mA – Line resistance, depends on the type of line 50… 250 Ω – End-of-line unit EOL22 (Ex) – Line factor (KLK) 25 Connection terminals 0.2... 2.5 mm² (AWG24... 14) External supply: Operating voltage 18... 32 VDC Operating temperature -25... +70 °C Storage temperature -30... +75 °C Humidity ≤95 % rel. Color housing white, ~RAL 9010 Schutzart EN60529 / IEC529 mit DCA1191 IP56 Standards EN54-17, EN54-18 Dimensions 135 x 135 x 65 mm

DCA1191

DCA1192A

DCB1192A

Approvals VdS G298021, LPCB 126m/04

Page 68: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

68

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

EOL22(Ex) End-of-line Part no. BPZ:5162220001

Application

End-of-line unit for collective detection lines as well as generally as end-of-line unit within explosion-hazard areas of zones 1 and 2.

8.11.3 Shunt Zener diode barrier SB3

SB3 Shunt Zener diode barrier Part no. BPZ:4837400001 Document Product data sheet 001222

Application This barrier is needed for an intrinsically safe installation in explosion-hazard areas connected to the in-/output module. This barrier restricts the electrical energy between non-intrinsically safe and intrinsically safe circuits. The installation has to be done according to the national safety regulations. The SB3 has to be mounted into the housing DCA1191 together with the Z3I410 installation set. Always install shunt Zener diode barriers outside explosion-hazard areas. Technical data Operating voltage max. 28 VDC Operating current max. 100 mA Type Stahl 9001/00-280-100-101

Standard EN50014 (IEC60079-0)/EN50020 (IEC60079-11)

8.11.3.1 Accessories for SB3

DCA1191 Housing with cover Part no. BPZ:4588560001

Application For surface mounting in humid, wet areas. One Shunt Zener diode barrier SB3 can be built into the housing. Technical data Protection category EN60529/IEC529 IP56 Dimensions 135 x 135 x 65 mm

Color white, ~RAL 9010

Z3I410 Installation set Part no. BPZ:4837660001

Application One SB3 shunt Zener diode barrier may be mounted together with support plate Z3I410 in housing DCA1191 with protection category IP56.

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 Details see chapter 2.2.1

– Metall-Kabelverschraubung M20 x 1,5 Part no. A5Q00004478 Details see chapter 2.3.1

Page 69: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

69

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.11.4 Point detectors AlgoRex Serie 'Ex'

DO1101A-Ex Smoke detector, wide spectrum collective 'Ex' Part no. BPZ:5008010001 Documents Product data sheet 001469

Technical description 1485 Application For the early warning of smoke-forming, flaming fires and smoldering fires in explosion-hazard areas of zones 1 and 2. The base DB1101A must be ordered separately. Function Penetrating smoke scatters the light of an infrared beam in the detector. If the light scatter exceeds a certain value, the detector transmits a danger signal to the control unit. Technical data Communication protocol collective/SynoLINE600 Operating voltage 17... 24 VDC Quiescent current max. 100 µA Operating temperature -25... +60 °C Storage temperature -30... +75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤60 °C) Dimensions 115 x 51 mm (incl. base) Humidity ≤95 % Protection category EN60529/IEC529 IP44 Standard for fire detectors EN54-7

for explosion-hazard areas EN50014 (IEC60079-0)/ EN50020 (IEC60079-11)

Approvals PTB 02 ATEX 2135 VdS G296052, LPCB 126am/02

Color white, ~RAL 9010

System compatibility collective/SynoLINE600, in C-NET via Transpon-der FDCIO223

DT1101A-Ex Heat detector collective 'Ex' Part no. BPZ:4852140001 Documents Product data sheet 001469

Technical description 1485 Application For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 50 °C. It is characterized by reliable response behavior, not only in the event of slow temperature rises, but also where the temperature rises are fast. The base DB1101A must be ordered separately. Function The detector measures the ambient temperature with one NTC thermistor and the detector housing temperature with another NTC thermistor. In this way the detector can rapidly and differentially evaluate an increase in temperature independent of the starting temperature. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 24 VDC Quiescent current max. 100 µA Operating temperature -25... +50 °C Storage temperature -30... +75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤50 °C) Dimensions 115 x 54.5 mm (incl. base) Humidity ≤95 % rel. Protection category EN60529/IEC529 IP44 Standard for fire detectors EN54-5: A1R

for explosion-hazard areas EN50014 (IEC60079-0)/ EN50020 (IEC60079-11)

Approvals PTB 02 ATEX 2097 VdS G296019, LPCB 126an/02

Color white, ~RAL 9010

System compatibility collective/SynoLINE600, in C-NET via Transpon-der FDCIO223

Page 70: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

70

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DT1102A-Ex Heat detector collective 'Ex' Part no. BPZ:4852270001 Documents Product data sheet 001469

Technical description 1485 Application For the monitoring of explosion-hazard areas of zones 1 and 2 with a maximum ambient temperature of 70 °C. It is the right heat detector for locations where large temperature fluctuations and high tempera-tures occur. It continuously measures the ambient temperature and reacts if defined maximum values are exceeded. The base DB1101A must be ordered separately. Function The detector measures the ambient temperature with one NTC thermistor and the detector housing temperature with another NTC thermistor. In this way the detector can rapidly and differentially evaluate an increase in temperature independent of the starting temperature. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 24 VDC Quiescent current max. 100 µA Operating temperature -25... +70 °C Storage temperature -30... +75 °C Ex-classification II 2 G Ex ib IIC T4 (-25 °C ≤Ta ≤70 °C) Dimensions Ø115 x 54.5 mm (incl. base) Humidity ≤95 % rel. Protection category EN60529/IEC529 IP44 Standard for fire detectors EN54-5: B

for explosion-hazard areas EN50014 (IEC60079-0)/ EN50020 (IEC60079-11)

Approvals PTB 02 ATEX 2097 VdS G296019, LPCB 126an/04

Color white, ~RAL 9010

System compatibility collective/SynoLINE600, in C-NET via Transpon-der FDCIO223

DB1101A Detector base Part no. BPZ:4931830001 Document Product data sheet 001035

Base made of impact and scratch-proof plastic and environmentally safe materials. Integral rubber gasket to protect against draught, dirt and dripping water from above. Screwless terminals for easy installation. Space for auxiliary terminals as micro terminals (0.5 mm²) and connection terminals (2.5 mm²). Fits all standard flush-mounted boxes from 55 to 80 mm. Technical data Cable capacity 0.2... 2.5 mm² Dimensions Ø115 x 21 mm

Color white, ~RAL 9010

8.11.4.1 Accessories for DB1101A

DBZ1191 Base attachment, surface mounting Part no. BPZ:4540830001

Application For surface wiring feed and provision of more wire loop space. Bases DB1101A are mounted using a spring-loaded catch. Technical data Dimensions Ø116 x 22 mm

5 pieces Color white, ~RAL 9010

Page 71: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

71

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DBZ1190-AA Micro terminal Part no. BPZ:4677080001 DBZ1190-AB Auxiliary terminal Part no. BPZ:4942340001 Details see chapter 2.2.1

8.11.5 Infrared flame detector DF1101-Ex

DFB1190 Base for infrared flame detector Part no. BPZ:5165360001 DF1101-Ex Infrared flame detector collective 'Ex' Part no. BPZ:5166750001 Documents Product data sheet 001744

Technical description 1673

Application Infrared flame detector for explosion-hazard areas of zones 1 and 2, for inside and outside applications. It is suitable for chemical production plants, oil refineries, propane and butane filling installations, for all explosion-hazard areas in which flaming fires involving carbonaceous materials could be expected. The base DFB1190 must be ordered separately. Function One sensor measures the hot carbon dioxide in a specific flame wavelength; the two other sensors simultaneously measure the interference radiation in other wavelengths. With intelligent signal process-ing through fuzzy algorithms and wavelet analysis, the DF1101-Ex achieves excellent detection reliabil-ity while maintaining the highest immunity to interference radiation and sunlight. In order to safeguard against a possible decision emergency, the detector contains an additional emergency activation chan-nel. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 28 VDC Quiescent current 0.5 mA Operating temperature -35... +70 °C Storage temperature -40... +75 °C Ex-classification II 2 G Ex ib IIC T4 (-35 °C ≤Ta ≤70 °C) Dimensions 135 x 135 x 77 mm Humidity (no heavy condensation of window) ≤95 % rel. Protection category EN60529/IEC529 IP67 Standard EN54-10 for flame detectors

EN50014 (IEC60079-0), EN50020 (IEC60079-11) for explosion-hazard areas

Approvals VdS G299085, PTB 02 ATEX 2161, LPCB 126s/03

Color white, ~RAL 9010

DFB1190

DF1101-Ex

System compatibility collective/SynoLINE600, in C-NET via Trans-ponder FDCIO223

Page 72: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

72

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.11.5.1 Accessories for DF1101-Ex

MV1 Mounting bracket Part no. BPZ:3950450001 MWV1 Ball and socket joint Part no. BPZ:3674840001 DFZ1190 Rain hood Part no. BPZ:5302660001 Details see chapter 2.5.1

MV1

MWV1

DFZ1190

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

EOL22(Ex) End-of-line Part no. BPZ:5162220001 Details see chapter 8.11.4.1

Page 73: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

73

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.11.6 Manual call points DM1103(Ex), DM1104(Ex)

DMA1192-AA Housing red with glass and key Part no. BPZ:5222870001 DMA1103D Switching unit collective Part no. A5Q00004470 DMA1104D Switching unit collective Part no. A5Q00005925 Document Product data sheet A6V10236643

Application For immediate manual actuation of an alarm. For indoor and outdoor application, equally suited for wet, humid and dusty areas. For surface- and recess-mounted feed lines in easily accessible places. The housing DMA1192-AA and the electronic unit DMA110xD must be ordered separately. The label 'avoid electrostatic charging' is enclosed with switching unit DMA110xD. Function DM1103(Ex) Indirect alarm actuation by smashing in the glass plate and pressing the push button. To replace the glass plate, open the housing door with the key. The push button must be reset before closing the door again. DM1104(Ex) Direct alarm actuation by smashing in the glass plate. To replace the glass plate, open the housing door with the key, upon closing the door the button is reset. Technical data Communication protocol collective/SynoLINE600 Operating voltage 16... 26 VDC Operating current 60... 100 mA Anschlussklemmen 0.28… 1.5 mm2 Einsatztemperatur -25... +70 °C Storage temperature -30... +75 °C Ex-classification 'simple apparatus' acc. EN50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Color red, ~RAL 3000 Protection category EN60529/IEC529 – mit Dichtung DMZ1197-AD

IP54 IP65

Standard EN54-11 Dimensions 134 x 134 x 43 mm Approvals – DM1103 – DM1104

VdS G295036 VdS G299068, LPCB 126w/06

DMA1103D

Label for manual call point in explosion-hazard area DMA1104D

Label for manual call point in explosion-hazard area

System compatibility collective/SynoLINE600, in C-NET via Trans-ponder FDCIO223

8.11.6.1 Accessories for DM1103(Ex), DM1104(Ex)

DMZ1197-AC Protective cover Part no. BPZ:5223550001 Details see chapter 8.7.1

Page 74: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

74

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DMZ1197-AD Protection seal Part no. BPZ:5470680001 Details see chapter 8.7.1

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 8.7.1

– Locking plug red, M20 x 1.5 (1 hole) Part no. A5Q00006735 – Locking plug red, M20 x 1.5 (2 holes) Part no. A5Q00010055 Details see chapter 8.7.1

EOL22(Ex) End-of-line Part no. BPZ:5162220001 Details see chapter 8.11.4.1

8.11.6.2 Spare parts for DM1103(Ex), DM1104(Ex)

DMZ1196-AC Spare glass Part no. BPZ:4942050001 Details see chapter 8.7.2

DMZ1195 Key Part no. BPZ:4851910001 Details see chapter 8.7.2

Page 75: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

75

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

8.11.7 Alarm indicators DJ1191-Ex, DJ1192-Ex, AJUT24-Ex

DJ1191-Ex Alarm indicator (door frame) Part no. BPZ:4783440001 Document Product data sheet 001679

Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Only one external alarm indicator may be connected to each detector. Technical data Operating voltage 4… 5 VDC Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25... +80 °C Ex-classification 'simple apparatus' acc. EN50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Approvals EECS, ESTI Color white, ~RAL 9010

Dimensions 62 x 37 x 17 mm

DJ1192-Ex Alarm indicator (wall mounting) Part no. BPZ:4783570001 Document Product data sheet 001679

Application Alarm indicators are connected in parallel to automatic fire detectors in order to indicate quickly the source of an alarm signal from detectors, which are not easily accessible or visible. For recess supply line. For surface supply line use adapter frame AI330. Function The LEDs in the alarm indicator are on, as soon as the appropriate detector is in alarm. Only one external alarm indicator may be connected to each detector. Technical data Operating voltage 4… 5 VDC Operating current, dauernd max. 35 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Ex-classification 'simple apparatus' acc. EN50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Protection category EN60529/IEC529 IP40 Approvals EECS, ESTI Color white, ~RAL 9010

Dimensions 85 x 85 x 25 mm

8.11.7.1 Accessory for DJ1192-Ex

AI330 Adapter frame Part no. BPZ:3169430001

Application For surface laid conduit or ducts, to increase the loop space or as an adapter for different makes of box. Technical data Color white, ~RAL 9010 Dimensions 85 x 85 x 16 mm

Page 76: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

76

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

AJUT24-Ex Alarm indicator incl. insulating cap Part no. BPZ:2785440001 Document Product data sheet 001679

Application Made of transparent plastic, the AJUT24-Ex alarm indicator is suitable for installation in door frames, switching panels, ceiling voids or special housings. The 23 mm Ø mounting hole is drilled by the system owner. The holder must be fitted with the insulating cap for safety. For installation in humid rooms the DCA1191, DJZ1193 housings as well as a washer are available (must be ordered separately). Up to 4 alarm indicators can be built into the housing DCA1191. Function Indicator lamp to connect in parallel to automatic fire detectors. Only one external alarm indicator may be connected to each detector. Technical data Operating voltage 1,5 VDC Operating current, dauernd max. 20… 30 mA Screwless connection terminals Wire cross-sectional area max. 1.5 mm2 Environmental temperature -25… +80 °C Ex-classification 'simple apparatus' acc. EN50020 § 5.4

Ex ib IIC T4 (Ta ≤70 °C) Humidity ≤95 % rel. Protection category EN60529/IEC529 – with DJZ1193 – with DCA1191

IP65 IP56

Approvals EECS, ESTI, PTB Color transparent plastic

Dimensions Ø26 x 51 mm

– Insulating cap Part no. BPZ:3048160001

Application Use as spare part.

8.11.7.2 Accessories for AJUT24-Ex

DCA1191 Housing with cover Part no. BPZ:4588560001 – Washer Part no. BPZ:2473130001

Application For surface mounting in humid, wet areas. Up to 4 alarm indicators AJUT24-Ex can be built into the housing. Technical data Housing with cover Protection category EN60529/IEC529 IP56 Dimensions 135 x 135 x 65 mm Color white, ~RAL 9010 Washer

DCA1191

Washer

Dimensions Ø23 x 1 mm

– Metal screwed cable gland M20 x 1.5 Part no. A5Q00004478 Details see chapter 2.3.1

Page 77: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Conventional and collective devices

77

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

DJZ1193 Alarm indicator housing incl. washer Part no. BPZ:5302950001

Application For surface mounting in dry areas. 1 alarm indicator AJUT24-Ex can be built into the housing. Technical data Protection category EN60529/IEC529 IP65 Color white, ~RAL 9010

Dimensions 87 x 87 x 64 mm

MVH1 Mounting arm Part no. BPZ:3496190001

Application For mounting of the alarm indicator housing DJZ1193 and detectors in hollow floors. Technical data Pipe clamp ½"

Dimensions 20 x 20 x 290... 420 mm

8.11.8 Alarm device DB3 for explosion-hazard areas

DB3 Alarm device for explosion-hazard areas for

zones 1 and 2 Part no. BPZ:5757970001

Document Product data sheet 009001 Application The flameproof audible alarm device is intended for the use in potentially explosive atmospheres. It has been designed with high ingress protection to cope with harsh environmental conditions. Technical data Operating voltage 12... 48 VDC Alarmstrom max. 380 mA Volume at 24V and 1m 101... 115 dB Anzahl Töne 27 Operating temperature -20... +55 °C Ex-classification II 2 G Ex d IIC T5 (-20 °C ≤Ta ≤55 °C) Cable capacity 6 x 2,5 mm² Dimensions 137 x 184 mm Color red, anti-static, UV stable, glass reinforced poly-

ester Approvals BAS 00ATEX2097X Standard CENELEC, EN 50014, 18

Protection category EN60529/IEC529 IP66/67

Page 78: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

78

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9 Test equipment and accessories

9.1 Detector exchanger for FD720 point detectors

DX791 Detector exchanger Part no. S54319-F6-A1 Document Product data sheet A6V10203222

Application For all Cerberus PRO FD720 point detectors and dust caps. Function Rational insertion and removal of point detectors. Equipped with a vacuum cup for insertion and removal of dust cap. Compatible with the telescope rods FDUM291/292 and the conventional extension rods VR10/11/12/13 and the MP/MT grab rods and extension rods. Technical data

Dimensions Ø30 x 35 x 160 mm

9.2 Detector tester RE6, RE6T, RE7T

RE6 Detector tester for smoke detectors Part no. BPZ:3680300001 Document Product data sheet A6V10203222

Application The detector tester (delivered with bellow DZZ1190) is placed over the detector and given a brief push to release the test gas and so simulate the presence of fire aerosols. The detector responds quickly and actuates an alarm. The test gas is free of halogenated chlorofluorocarbons (CFCs). It is not combustible.The extension rod FDUM291/292 and the test gas can REF8, REF8-S must be ordered separately.

9.2.1 Accessories for RE6

RG320 Bellow for RE6 Part no. BPZ:5166880001

Application The bellow is fitted to the RE6 to fit all Synova 300 point detectors in an ideal way.

REF8 Test gas can for smoke detectors Part no. A5Q00011687 REF8-S Test gas can for smoke detectors Part no. A5Q00011688

REF8 REF8-S

Application REF8 has been developed as an environmentally friendly test gas for the testing of smoke detectors. REF8 can be used in the temperature range of 0... +40 °C in dry or in humid environments. Complies with environmental laws. Protects atmosphere and ozone layer. REF8-S has been developed as environmentally friendly test gas for the testing of smoke detectors. REF8-S can be used in the temperature range of -20... +40 °C in dry or in humid environments. REF8-S remains measurable longer than REF8, and is used for detectors having a longer signal evaluation time. Complies with environmental laws. Protects atmosphere and ozone layer. Use only together with detector tester RE6.

Page 79: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

79

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

RE6T Detector tester for heat detectors Part no. BPZ:3680270001 Document Product data sheet A6V10203222

Application This detector tester contains a hot air generator. For the performance check, the tester is pushed over the detector. The hot air released, heats the detector and so actuates an alarm. The extension rod FDUM291/292 must be ordered separately.

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Mains voltage 220 VAC/50… 60 Hz, ~300 W Operating temperature 0… +40 °C

RE7T Solo461 Heat detector tester kit Part no. A54370-S3-A1 Document Product data sheet A6V10252901

Anwendung The detector tester contains a hot air generator. For the performance check, the tester is pushed over the detector. The hot air released, heats the detector and so actuates an alarm. The adaptor RE7T-A and the extension rod FDUM291/292 must be ordered separately. Kit consists of: – Tester – 2 Battery batons – Charger

Forbidden in electrical switching stations or areas where there is a danger of explosion!

Technical data Operating temperature 5... +45 °C Storage temperature -10… +50 °C Humidity ≤95 %

9.2.2 Accessories for RE7T

RE7T-A Solo719 Adaptor for FDUM29x Part no. S54370-N4-A1

Application Adaptor from heat detector tester RE7T to the telescope rods FDUM29x.

Page 80: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

80

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9.2.3 Spare parts for RE7T

RE7T-B Solo760 Battery for RE7T Part no. S54370-N5-A1

Application Use as spare part for RE7T heat detector tester.

RE7T-C Solo725 Charger for RE7T Part no. S54370-N6-A1

Application Use as spare part for charging of battery baton to the RE7T heat detector tester.

9.2.4 Accessories for DX791, RE6, RE6T, RE7T

FDUM291 Telescope rod Part no. A5Q00004996

Application The three-part telescope with tri-oval tubes serve as extensions for the detector exchanger and other applications up to 5 m. Technical data Color yellow, black Dimensions Ø34.5 mm x 1.6 m (drown out length= 4.2 m)

Page 81: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

81

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDUM292 Telescope rod Part no. A5Q00004997

Application The three-part telescope with tri-oval tubes serve as extensions for the detector exchanger and other applications up to 8 m. Technical data Color yellow, black Dimensions Ø44.5 mm x 2.1 m (drown out length = 7.3 m)

9.2.4.1 Spare parts for FDUM291

– Adapter with lever, screw and nut incl. attach-

ment and bushing screw Part no. A5Q00009786

– Lever with screw and nut Part no. A5Q00009787 – Small flap with screw and nut Part no. A5Q00009788 – Large flap with screw and nut Part no. A5Q00009789

Application Use as spare part.

9.2.4.2 Spare parts for FDUM292

– Adapter with lever, screw and nut incl. attach-

ment and bushing screw Part no. A5Q00009786

– Lever with screw and nut Part no. A5Q00009787

Application Use as spare part.

Page 82: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

82

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9.3 Detector base tester DZB1191

DZB1191 Detector base tester Part no. BPZ:4680660001 Document Product data sheet 001049

Application The DB1191 base tester is handy and simple means of testing the detection line and detector base connections.

Function The base tester is inserted in the detector base like a detector. Bases can be tested during installation either individually or consecutively after installation is completed. The DBZ1191 can test for open lines, short circuit, earth leakages, polarity and alarm indicator connec-tion.

9.4 Test equipment for linear smoke detectors

9.4.1 Adjustment device set FDLU291

FDLU291 Adjustment device set for linear smoke detector Part no. A5Q00004905 Documents Product data sheet 007017

Technical description 007016 Application The optics can be rationally adjusted to the reflector by single-handed alignment by means of the ad-justment device. Box with adjustment device, alarm test filter, visor, magnet, spiral cable, MC-link cable, and battery 9 V, 0.5 Ah. Technical data

Dimensions adjustment device 120 x 65 x 22 mm

FDLU291 Adjustment device Part no. A5Q00006540

Application Use as spare part.

9.4.2 Detector tester RE10

RE10 Detector tester Part no. BPZ:3685190001 Document Product data sheet A6V10203222

Application For performance check of linear smoke detector. In compliance with the type of detector to be tested, the alarm test filter is inserted in the detector tester. Alarm test filter contained in FDLU291 or TF04 must be ordered separately.

Function The detector tester is then held in front of the optical parts of the detector (i.e. into the infrared ray). The detector reacts after a few seconds.

TF04 Alarm test filter (Absorption 77 %) Part no. BPZ:4931090001

Application Alarm test filter for detector tester RE10.

Page 83: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

83

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9.5 Line tester FDUL221

FDUL221 Line tester Part no. A5Q00004397 Documents Product data sheet A6V10203222

Operation 008250 Application The line tester is a universal device for the final testing of completely installed C-NET fire detection lines, when no control unit has been connected yet. For troubleshooting for electricians, installers or service technicians. Line tester incl. line connection set FDUL221-A and power supply set FDUL221-B. Technical data Line tester Operating voltage – Battery or via – mains adapter

min. 10 VDC, max. 30 VDC 2 x 9 V 240 VAC/24 VDC, 625 mA

Current consumption during measuring depending on number of devices Detection line voltage – C-NET (FS720)

32 VDC

Max. connection factor (MK) per line – with mains adapter – with battery

min 550 min. 150

Operating temperature -25... +40 °C Storage temperature – with battery

-30... +75 °C -25... +60 °C

Humidity ≤95 % rel. (no condensation) Dimensions 190 x 135 x 45 mm Mains adapter AC/DC Input voltage 100... 240 VAC / 50... 60 Hz / 400 mA Output voltage 24 VDC / 625 mA

Dimensions 115 x 52 x 33 mm

9.5.1 Accessories for FDUL221

– Lithium brownstone battery 9 V / 1 Ah Part no. A5Q00004142

Application For the supply of the line tester and others. Technical data

10 pieces Dimensions 25 x 48 x 16 mm

Page 84: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

84

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

9.5.2 Spare parts for FDUL221

FDUL221-A Line connection set Part no. A5Q00008436 FDUL221-B Mains adapter set Part no. A5Q00008437 FDUL221-C PC cable (RS232) Part no. A5Q00008438

FDUL221-A A5Q00008436 Line Connection Set Application Use as spare part.

FDUL221-B A5Q00008437 Power Supply Set FDUL221-C A5Q00008438 PC Cabel (RS232)

9.6 Test lamps for flame detectors

LE3 Test lamp Part no. BPZ:3669510001 FA2003-A1 Battery (12 V, 7 Ah, VDS) Part no. A5Q00019353 Document Product data sheet A6V10203222

Application For checking the alarm function of all flame detector for distance up to 10 m. Technical data Test lamp Dimensions 178 x 180 x 369 mm Battery Dimensions 151 x 94 x 65 mm

Approval VdS G103032

9.6.1 Spare part for LE3

– Halogen lamp 12 V / 50 W Part no. BPZ:3679630001

Application Use as spare part.

Page 85: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Test equipment and accessories

85

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

StabexHF Test lamp for flame detectors 'Ex' Part no. BPZ:4620910001 Document Product data sheet 000252, A6V10203222

Application The test lamp is used to carry out a performance check of intrinsically safe flame detectors in explosion-hazard areas of zones 1 and 2. Technical data Operating temperature -20... +40 °C Storage temperature -20... +40 °C Battery capacity 2 x Alkali battery 1.5 V, single-cell UM1 Ex-classification II 2 G Ex ib e IIC T4 Protection category EN60529/IEC529 IP65

Approvals PTB 98 ATEX 2062

9.7 Adapter for C-NET devices

FDUZ221 MCL USB adapter Part no. A5Q00020131 Documents Product data sheet A6V10203222

Installation 009854 Application The MCL USB adapter is an interface converter for USB to MC link. It can be used to connect C-NET devices to a PC using a serial protocol (MCL). The MC link cable, the USB cable (1.8 m) and a CD with USB driver software are included. Function The adapter is used for the firmware update or for operation. The adapter is used for floor repeater display FT2011-A1, floor repeater terminal FT2010-A1 and for line tester FDUL221 (in the future other C-NET devices possible). Technical data Power supply via USB Interface USB 2.0/1.1, MC link Operating temperature -10… +55 °C Storage temperature -20… +60 °C Humidity ≤95 % rel. Dimensions (WxHxD) 100 x 30 x 54 mm

Protection category IP30

Page 86: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

86

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

10 Index

A Acoustic base 51 Adapter base

for AGN24.6 64 for ALB24.1x 66

Adapter frame for AI322 48 for AI340 62 for DJ1192 18 for DJ1192-Ex 75

Adapter with lever for FDUM291 81 for FDUM292 81

Adjustment device as spare part 82

Adjustment device set for linear smoke detector 82 AGN24.6 64 AGS24.5 65 AGT24.1 65 AI300 62 AI320 48 AI322 48 AI330 18, 48, 62, 75 AI340 62 Air flow tube 0.6 m 61 Air flow tube 1.5 m 61 Air flow tube 2.8 m 61 Air sampling smoke detection kit 60 AJUT24-Ex 76 Alarm device

conventional 64, 65 Alarm device for explosion-hazard areas for zones

1 and 2 77 Alarm indicator (door frame)

for C-NET devices 18 for conventional/SynoLINE300 devices 48 for conventional/SynoLINE600 devices 62 for explosion-hazard area 75

Alarm indicator (wall mounting) for C-NET devices 18 for conventional/SynoLINE300 devices 48 for conventional/SynoLINE600 devices 62 for explosion-hazard area 75

Alarm indicator housing incl. washer for AJUT24-Ex 77 for DJ1193 64

Alarm indicator incl. insulating cap 63 for explosion-hazard area 76

Alarm sounder red 31

white 31 Alarm sounder beacon, orange 32 Alarm sounder beacon, red 32 Alarm test filter (Absorption 77 %) 82 ALB24.1OR 66 ALB24.1R 66 Aspirating smoke detector with display 42 Auxiliary terminal 12, 22, 33, 35, 47, 52, 54, 71

B Back box

for FDM1101A-Rx 46 for FDM1101-Rx 53 for FDM225-xx 22

Back nut for screwed cable gland 20, 22, 41, 47, 54, 56

Ball and socket joint for flame detector 17, 72

Base for Synova 300 detector series 45

Base attachment for SO320 45

Base attachment for FDB22x 33

Base attachment flat, surface mounting for DB1101A 50

Base attachment humid for DB1101A 50

Base attachment wet for DB1101A 51

Base attachment wet with seal for IP54 applications 34

Base attachment, surface mounting for DB1101A 50, 70

Base for collective detector series for DO1104A 60

Base for infrared flame detector for DF1191-Ex 71

Base for infrared flame detector 16 FDF2x1-9 15

Base for linear smoke detector FDL241-9 13

Battery (12 V, 7 Ah, VDS) for test lamp 84

Bellow for RE6 for Synova 300 detectors 78

C Connection terminal 45 Cover with key

for DM1101 56

Page 87: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

87

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

for FDM221 20

D DB1101A 50, 60, 70 DB3 77 DB720 11 DB721 12 DBC1191A-AA 51 DBS720 12, 35 DBZ1190 52 DBZ1190-AA 12, 33, 35, 52, 68, 71 DBZ1190A-AC 52 DBZ1190-AB 12, 22, 33, 35, 45, 47, 52, 54, 71 DBZ1191 50, 70 DBZ1191A-AA 50 DBZ1192 50 DBZ1192-AA 51 DBZ1193A 34, 52 DBZ1194 34, 50 DBZ1195A 51 DCA1191 63, 67, 68, 76 Designation plate

for DB720 12 for DBS720 35 for FDB221/222 33 for FDB293 34

Detector base for collective/SynoLINE600 detectors 50, 70

Detector base for FDS221, FDS229 32 for OH/OP/HI720 11

Detector base seal for DB720 and DBS720 12, 35

Detector base tester for base DB1101A 82

Detector base with loop contact for OH/OP/HI720 12

Detector base, flat for FDS221, FDS229 32

Detector designation plate for DB1101A, DBZ1192, DBZ1192-AA 52

Detector exchanger for FD720 point detectors 78

Detector heating for DO1101A 52

Detector heating element for FDL241-9 14

Detector locking device 11, 33 for Synova 300 detector series 45

Detector tester for heat detectors 79 for linear smoke detectors 82 for smoke detectors 78

DF1101-Ex 71 DFB1190 71 DFZ1190 17, 72

DJ1191 18 DJ1191-Ex 75 DJ1192 18 DJ1192-Ex 75 DJ1193 63 DJZ1193 64, 77 DLF1191-AA 14 DLF1191-AB 14 DLF1191-AC 14 DLH1191A 14 DLR1191 14 DLR1192 14 DLR1193 14 DM1103-L 58 DM1103-S 58 DMA1101 55 DMA1103D 57, 73 DMA1104D 57, 73 DMA1192-AA 57, 73 DMA1192-AB 57 DMA1192-AC 57 DMA1192-AD 57 DMZ1195 26, 30, 59, 74 DMZ1196-AC 26, 30, 59, 74 DMZ1197-AC 25, 29, 58, 73 DMZ1197-AD 25, 29, 59, 74 DO1101A 49 DO1101A-Ex 69 DO1104A 60 DT1101A 49 DT1101A-Ex 69 DT1102A 49 DT1102A-Ex 70 DX791 78 DZB1191 82

E Electronic unit, SynoLINE600 67 Emergency stop button complete

for extinguishing system 58 End-of-line

EOL22(Ex) 68, 72, 74 EOL22(Ex) 68, 72, 74 Extraneous light filter 14

F FA2003-A1 84 FDB221 32 FDB222 32 FDB291 33 FDB293 34 FDBZ291 12, 33, 35 FDBZ292 60 FDBZ292-AA 61 FDBZ292-AB 61

Page 88: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

88

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

FDBZ292-AC 61 FDBZ292-AD 61 FDBZ292-AF 61 FDBZ293 33 FDBZ295 33 FDCH221 41 FDCI221 38 FDCI222 38 FDCIO221 39 FDCIO222 39 FDCIO223 40, 67 FDCIO224 40 FDCL221 36 FDCL221-M 37 FDCM291 41 FDF221-9 15 FDF241-9 16 FDFB291 15, 16 FDL241-9 13 FDLB291 13 FDLU291 82 FDM1101A-RG 46 FDM1101A-RP 46 FDM1101-RG 53 FDM1101-RP 53 FDM223 27 FDM225-RG 21 FDM225-RP 21 FDM226-RG 21 FDM226-RP 21 FDMC291 20, 55 FDMC295 22, 47, 54 FDME221 19 FDME223 28, 29 FDME224 24, 25 FDMG291 20, 56 FDMG295 23, 47, 54 FDMH291-B 19, 55 FDMH291-G 19, 55 FDMH291-R 19, 55 FDMH291-Y 19, 55 FDMH292-R 25, 29 FDMH293-B 24, 28 FDMH293-G 24, 28 FDMH293-O 24 FDMH293-R 24, 28 FDMH293-Y 24, 28 FDMH295-R 22, 46, 53 FDMH295-S 22, 46, 53 FDMK291 20, 56 FDMK295 23, 47, 54 FDMP295 23, 47, 54 FDS221-R 31 FDS221-W 31 FDS229-A 32

FDS229-R 32 FDUL221 83 FDUL221-A 84 FDUL221-B 84 FDUL221-C 84 FDUM291 80 FDUM292 81 FDUZ221 85 Flashing signal lamp, orange

conventional 66 Flashing signal lamp, red

conventional 66

G Glass

for FDM221 20 for FDM223 30 for FDM224 26

Glass plate 'neutral' for FDM1101A-RG 47 for FDM1101-RG 54 for FDM1225/226 23

H Halogen lamp 12 V / 50 W

for LE3 84 Heat detector

collective/SynoLINE600 49 Heat detector (maximum)

conventional/SynoLINE300 44 Heat detector (rate of rise and maximum)

conventional/SynoLINE300 44 Heat detector (static + RoR) 10 Heat detector (static) 11 Heat detector collective 'Ex' 69, 70 Heavy Duty housing red with glass, hexagon

wrench key, 3 nipples and plate Feuerwehr/Brandmelder 29

HI320C 44 HI322C 44 HI720 10 HI722 11 Housing blue with glass and key

for DMA110xD 57 for FDME223 28 for FDME224 24

Housing blue with key for DMA1101 55 for FDME221 19

Housing for input/output modules 41 Housing green with glass and key

for DMA110xD 57 for FDME223 28 for FDME224 24

Housing green with key

Page 89: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

89

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

for DMA1101 55 for FDME221 19

Housing Heavy Duty red for FDME224 25

Housing orange with glass and key for FDME224 24

Housing red with glass and key for DMA110xD 57, 73 for FDME223 28 for FDME224 24

Housing red with key for DMA1101 55 for FDME221 19

Housing with cover for AJUT24-Ex 76 for DC1192 67 for DJ1193 63 for SB3 68

Housing yellow with glass and key for DMA110xD 57 for FDME223 28 for FDME224 24

Housing yellow with key for DMA1101 55 for FDME221 19

I Infrared flame detector (1 Sensor) 15 Infrared flame detector (3Sensors)

with ASAtechnology 16 Infrared flame detector collective 'Ex' 71 Input module

1 input 38 4 inputs 38

Input/output module 1 input, 1 output 39 4 inputs, 4 outputs 39 for extinguishing controls 40

Installation set for SB3 in DCA1191 68

Insulating cap for AJUT24-Ex 76 for DJ1193 63

K Key

for DMA1192-AA 74 for DMA1192-xx 59 for FDM1101A-Rx 47 for FDM1101-Rx 54 for FDM225/226 23 for FDMH293-x 26, 30

L Large flap

for FDUM291 81 LaserFOCUS VLF-250 42 LaserFOCUS VLF-500 42 LE3 84 Lever with screw and nut

for FDUM291 81 for FDUM292 81

Line connection set for FDUL221 84

Line separator 36 Line tester

for C-NET detector line 83 Linear smoke detector

with ASAtechnology 13 Lithium brownstone battery 9 V / 1 Ah 83 Locking device 52 Locking plug M20 x 1.5 (1 hole)

for DMA1192-AA 74 for DMA1192-xx 59 for FDMH293-x 26

Locking plug M20 x 1.5 (2 holes) for DMA1192-AA 74 for DMA1192-xx 59 for FDMH293-x 26

Long distance reflector (Prism) 14 LP720 11

M Mains adapter set

for FDUL221 84 Mallory buzzer

conventional 65 Manual call point complete

housing red with glass, key, switching unit and locking plug 27

Manual call point with glass plate collective/SynoLINE600 53 conventional/SynoLINE300 46

Manual call point with glass plate 21 Manual call point with glass plate incl. housing base

21 Manual call point with plastic element 21 Manual call point with plastic element incl. housing

base 21 Manual call point with resettable plastic element

collective/SynoLINE600 53 conventional/SynoLINE300 46

Manual release button complete for extinguishing system 58

MCL USB adapter for C-NET devices 85

Metal screwed cable gland M20 x 1.5 for DBZ1192/-AA 51 for DCA1191 63, 76 for DFB1190 72

Page 90: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

90

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

for DMA1192-AA 74 for DMA1192-xx 59 for FDCH221 41 for FDFB291 17 for FDFB293 34 for FDLB291, DLR1191 15 for FDMH291-x 20, 22, 56 for FDMH293-x 26, 30 for FDMH295-R 47, 54

Metall-Kabelverschraubung M20 x 1,5 zu DCA1191 68

Micro terminal 12, 33, 35, 52, 68, 71 Middle distance reflector (400cm2) 14 Mounting arm 64, 77 Mounting bracket 61

for flame detector 17, 72 Mounting feet for input/output modules 41 Multi line separator 37 Multi-sensor smoke detector 9

conventional/SynoLINE300 43 MV1 17, 72 MVH1 64, 77 MWV1 17, 72

O OH320C 43 OH720 9 OP320C 43 OP720 10 Optical smoke detector

conventional/SynoLINE300 43

P PC cable (RS232)

for FDUL221 84 Plastic element 'neutral'

for FDM1101A-RP 47 for FDM1101-RP 54 for FDM225/226 23

Protection seal for areas for DM1103/04 59 for DM1103/04(Ex) 74

Protective cage 50 for FDB293 34

Protective cover for DM1101 55 for DM1103/04 58 for DM1103/04(Ex) 73 for FDM1101A-Rx 47 for FDM1101-Rx 54 for FDM221 20 for FDM223 29 for FDM224 25 for FDM225/226 22

R Rain hood

for flame detector 17, 72 RE10 82 RE6 78 RE6T 79 RE7T 79 RE7T-A 79 RE7T-B 80 RE7T-C 80 REF8 78 REF8-S 78 Relay base 51 Replacement glass

for FDMH291-x 56 RG320 78 RS720 12, 35

S SB3 68 Seal for wet areas

for FDM223 29 for FDM224 25

Sealing element for FDS221-x/FDS229-x 33

Sealing kit for air flow tubes 61 Short distance filter 5-8m 14 Short distance filter 7-10 m 14 Short distance reflector (100cm2) 14 Shunt Zener diode barrier 68 Small flap

for FDUM291 81 Smoke detector

collective/SynoLINE600 49 Smoke detector 10 Smoke detector, collective wide spectrum

for FDBZ292 60 Smoke detector, wide spectrum collective 'Ex' 69 SO320 45 SOA322 45 Solo461 Heat detector tester kit 79 Solo719 Adaptor for FDUM29x 79 Solo725 Charger for RE7T

as spare part 80 Solo760 Solo760 Battery for RE7T

as spare part 80 Sounder base 35

for OH/OP/HI720 12 Spare glass

for DM1103/04 59 for DM1103/04(Ex) 74

StabexHF 85 Switching unit

for FDMH291-x 19 for FDMH292-R 25, 29

Page 91: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Index

91

Building Technologies 058_FD720_Equipment_overview_A6V10225323_c_en.doc

Fire Safety & Security Products 12.2009

for FDMH293-x 24, 28 Switching unit collective

direct alarm actuation 55, 57, 73 indirect alarm actuation 57, 73

T Telescope rod 80, 81 Terminal base

for DCA1192A 67 Test gas can for smoke detectors

for RE6 78 Test lamp 84 Test lamp for flame detectors 'Ex' 85 TF04 82 TP320 45 Transponder 40, 67 TS35, L=288 mm 37

U U-rail TS35, L=122 mm 37 U-rail TS35, L=122 mm 41 U-rail TS35, L=288 mm 41

V V-plug PA M20 x 1.5

for FDMH292-R 26, 30

W Washer

for DCA1191 63, 76

Z Z3I410 68 ZS/AGN24.5 64, 66

Page 92: PRO, Detector system Equipment overvie · 2016-06-23 · FD720 Cerberus® PRO, Synova, AlgoRex Detector system Equipment overview . Liefermöglichkeiten und technische Änderungen

Siemens Switzerland Ltd Industry Sector Building Technologies Division International Headquarters Fire Safety & Security Products Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 www.siemens.com/buildingtechnologies

Document no. A6V10225323_c_en_-- Manual FD720

Edition 12.2009 Section 1