procontrol p14 83sr52/r1210 control module for … · procontrol p14 . 83sr52r1210 . module and...

30
Procontrol P14 83SR52R1210 Module and Application Description Control Module for Analog Control Functions with Continuous Output, Speed Inputs

Upload: lamnguyet

Post on 07-Sep-2018

366 views

Category:

Documents


9 download

TRANSCRIPT

Procontrol P14

83SR52R1210 Module and Application Description Control Module for Analog Control Functions with Continuous Output, Speed Inputs

Procontrol P14

83SR52R1210 Control Module for Analog Control Functions with Continuous Output, Speed Inputs

NOTICE This document contains information about one or more ABB products and may include a description of or a reference to one or more standards that may be generally relevant to the ABB products. The presence of any such description of a standard or reference to a standard is not a representation that all of the ABB products referenced in this document support all of the features of the described or referenced standard. In order to determine the specific features supported by a particular ABB product, the reader should consult the product specifications for the particular ABB product. ABB may have one or more patents or pending patent applications protecting the intellectual property in the ABB products described in this document. The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. This product meets the requirements specified in EMC Directive 2014/30/EC.

TRADEMARKS Procontrol is a registered trademark of ABB AG. All rights to copyrights, registered trademarks, and trademarks reside with their respective owners. Copyright © 2016 ABB. All rights reserved. Release: July 2016 Document number: 2VAA007467

TABLE OF CONTENTS

1. APPLICATION ................................................................................................. 8

2. FEATURES ...................................................................................................... 8

3. DESIGN OF THE MODULE ............................................................................. 9

3.1 Process Interface .................................................................................................. 9

3.2 Station-Bus Interface ............................................................................................ 9

3.3 Processing Section .............................................................................................. 9

4. STRUCTURING ............................................................................................. 10

5. ADRESSING .................................................................................................. 10

5.1 General ................................................................................................................ 10

5.2 Address Formation ............................................................................................. 10

5.3 Address List for Module Inputs ......................................................................... 10

5.4 Address List for Module Outputs ...................................................................... 11

6. PARAMETER LIST ........................................................................................ 11

7. EVENT GENERATION .................................................................................. 11

8. SIMULATION ................................................................................................. 12

9. DISTURBANCE BIT EVALUATION, RECEIVE MONITORING .................... 12

10. DIAGNOSIS AND ANNUNCIATION FUNCTIONS ........................................ 12

10.1 Disturbance Annunciations on the Module ................................................... 12

10.2 Disturbance Annunciation Signals to the Annunciation System ................ 12

10.3 Diagnosis ......................................................................................................... 12

11. OPERATING STATES OF THE MODULE .................................................... 14

11.1 Initialization and Bootstrapping with User Lists........................................... 14

11.2 Normal Operation ............................................................................................ 14

11.3 Changing the User Program ........................................................................... 14

11.4 Changing Fixed Values ................................................................................... 14

11.5 Changing Parameters ..................................................................................... 14

11.6 Simulation ........................................................................................................ 14

12. PROCESS INPUTS AND OUTPUTS ............................................................. 15

12.1 Output of Commands to the Process Interface ............................................ 15

12.2 Process inputs ................................................................................................. 15

13. CONFIGURATION OF INPUTS/OUTPUTS ................................................... 15

13.1 Setting of the system hum filter ..................................................................... 15

13.2 Setting of the analog inputs and outputs ...................................................... 15

13.3 Setting of the jumpers ..................................................................................... 15

13.4 Configuration of the speed inputs ................................................................. 15

14. APPLICATION OF FUNCTION BLOCKS ..................................................... 16

14.1 Overview .......................................................................................................... 16

15. FUNCTION DIAGRAM ................................................................................... 19

16. CONNECTION DIAGRAM ............................................................................. 21

17. MODULE DESIGN ......................................................................................... 22

18. SYSTEM DATA .............................................................................................. 25

19. TECHNICAL DATA ........................................................................................ 25

19.1 Power supply ................................................................................................... 25

19.2 Process Interface............................................................................................. 25

19.2.1 Binary inputs BI1..BI8 ..................................................................................... 25

19.2.2 Transmitter power supply for binary inputs UB1, UB2 .................................... 26

19.2.3 Binary outputs BO1...BO8 .............................................................................. 26

19.2.4 Speed inputs FI11...FI13 ................................................................................ 26

19.2.5 Transmitter power supply for speed inputs..................................................... 26

19.2.6 Analog inputs AI1...AI4 ................................................................................... 26

19.2.7 Accuracy of input values ................................................................................ 27

19.2.8 Transducer power supply for analog inputs.................................................... 27

19.2.9 Analog outputs AO1...AO8 ............................................................................. 27

19.2.10 Accuracy of the output values .................................................................. 27

83SR50R1210

TABLE OF CONTENTS

19.2.11 Initialization time ...................................................................................... 28

19.3 Interference immunity (of process inputs and outputs) .............................. 28

20. ORDERING DATA ......................................................................................... 28

21. REVISION HISTORY ..................................................................................... 29

Process Interface APPLICATION

1. APPLICATION The module is used for stored-program control of process parameters. For communicating with the process, the module has several continuous inputs and outputs as well as several binary inputs and outputs. For recording speed data, pulse/speed inputs are provided. It is possible to activate the following type of actuators:

• Electrohydraulic actuators • Electropneumatic actuators • Electric-motor-driven actuators

The positioning of the actuators takes place at the local transformer or, in the case of electric motor-driven actuators, in continuously operating power electronics system. In addition to the single-variable analog control functions, a super-ordinated master control function can be implemented. The module includes the function blocks needed for continuous single-variable control. For signal handling, further function blocks are available. The module is intended to be used with the Process Operator Station (POS30). The module uses 2 process interfaces for the power controllers and for the process.

2. FEATURES The module can be plugged into any station of the PROCONTROL bus system. It incorporates a standard interface for the PROCONTROL station bus. The module address is set automatically when the module is plugged into the PROCONTROL station. The telegrams received over the bus are checked by the module for error-free transmission based on their parity bits. The telegrams sent from the module to the bus are provided with parity bits, in order to ensure error-free transmission. The user program is stored on a nonvolatile memory (Flash–PROM). Loading and changing of the user program is done from the PDDS over the bus. The module is ready for operation as soon as a valid user program has been loaded. For communicating with the process and with the power controller units, the module requires the following voltages: USA/USB, branched internally into the following voltages:

• UB1 Supply for contacts, process interface 1 • UB2 Supply for contacts, process interface 2 • UA1/UA2/UF1 Supply for transducers, process interface 1 • UA3/UA4/UF2 Supply for transducers, process interface 2 • UF3 Supply for transducers, process interface 3

The voltages are short-circuit-proof and non-interfering. The operating voltages and the external logic signals are related to reference conductor Z. In case the internal monitoring circuits or the input signal monitor respond, disturbance annunciation ST (general disturbance) will be indicated on the front panel of the module. Response of the internal monitoring circuits is indicated as disturbance annunciation SG (module disturbance) on the front panel of the module.

8 2VAA007467

DESIGN OF THE MODULE Process Interface

3. DESIGN OF THE MODULE The module essentially consists of:

• Process interfaces • Station-bus interface • Processing section

3.1 Process Interface In the process interfaces, the process signals are adapted to the signal levels.

3.2 Station-Bus Interface In the station-bus interface, the module signals are adapted to the bus. Mainly a parallel/serial conversion takes place. The module transfers the data telegrams through a standard interface to the station bus. Data transfer is serial.

3.3 Processing Section For processing the signals coming from the process and from the bus, the module is equipped with a microprocessor which cooperates with the following memory areas:

Contents Storage medium

Operating program Flash PROM

Function blocks Flash PROM

User program (structure, address and simulation list)

Flash PROM

History values RAM

Current module input and output signals (shared memory)

RAM

The operating program enables the microprocessor to perform the elementary operations of the module. The memory for the function blocks contains standard programs for implementing the different functions. All the function blocks, their inputs and outputs, can be called by the user via the Programming, Diagnosis and Display System (PDDS). The memory for the user program contains information on:

• how the function blocks are interconnected, • which module inputs and outputs are assigned to which inputs and outputs of the function blocks, • which fixed values are specified at the individual inputs of the function blocks, • which parameters are specified at the individual inputs of the function blocks, • which plant signals are assigned to which module inputs and outputs, • which function blocks support the process interfaces, • which function results, module input and output signals are simulated.

These information are defined by the user depending on the plant conditions. The entire user program is stored in a flash PROM. The settings (mainly for analog control) can be preset directly by the user at the respective function block inputs in the form of values (fixed values) or be specified as parameters. Fixed values and parameters can be modified at any time during operation (on-line). In this case they are changed and stored in the Flash PROM. The exchange of information between the module and the bus system takes place via the memory for the module's input and output signals (shared memory). This memory is used for buffering the signals.

2VAA007467 9

General STRUCTURING

4. STRUCTURING For structuring, the neutral inputs and outputs of the individual function blocks are assigned certain logic combinations. Inputs of function blocks can be connected to a module input, an output of another function block on the module (function results), or to fixed values and parameters. Outputs of function blocks can be logically combined with module outputs and function blocks on the module. For structuring, the following limit values of the module need to be taken into consideration:

• max. number of module inputs (EG) 510 • max. number of simulatable signals 32 • max. number of module outputs (AG) 255 • max. number of function results (AF) 255 • max. number of timers 256 • max. number of parameters 80 • max. number of lines in structure list 2886 • length of history value list (bytes) 2048 • dimensioning of the shared memory (cf. ”Addressing”)

A line is understood as one entry on the PDDS. For the precise procedure of structuring the function blocks please refer to the respective function block descriptions.

5. ADRESSING

5.1 General Signal exchange between the module and the bus system takes place via a shared memory. In this shared memory, incoming telegrams that the module is to receive and function results that are to leave the module are buffered. For this purpose, the shared memory includes send registers for telegrams to be sent and receive registers for telegrams to be received.

Dimensioning of the shared memory:

• Receive register: register numbers 0 - 254 • Send register: register numbers 0 - 199 • System register: register numbers 200 - 255

The allocations of the module's input and output signals to the registers of the shared memory are defined as specified by the user via the PDDS. The user data are contained in address lists.

5.2 Address Formation System address and station address are set at the station-bus coupling module or at the station-bus control module and are transferred by that module to all the modules of the relevant PROCONTROL station. The module addresses are defined through the connections on the backplane so that the modules are adjusted automatically when being plugged into a slot.

5.3 Address List for Module Inputs In the address list for module inputs, each module input is assigned the send-location address or the process interface of the signal to be received. In the case of module inputs which receive their signals over the bus, the addressing is effected by allocating the send-location address to EGn, e.g.:

10 2VAA007467

PARAMETER LIST Address List for Module Outputs

Input Address EG1 1, 32, 24, 8, 7 Bit no. (0 – 15) Register no. (0 – 255) Module no. (1 – 58) Station no. (1 – 249) System no. (0 – 3) In the case of module inputs that receive their signals from the Process Operator Station (POS30), addressing is done by allocating L,m to EGn, m being the register no. (0 - 199) of the module. This register number is no longer available for module outputs. For example: Input Address EG1 L,10

Destination telegram from the POS30

The address list for inputs is translated by the PDDS into two internal lists, i.e. into the ”Bus address list” and the ”Module inputs allocation list”. The bus address list contains, for all telegrams to be used by the module, the send-location address and the receive register number. Incoming telegrams, whose addresses are contained in the bus address list, are registered in the receive register of the shared memory. The module ignores incoming telegrams, whose addresses are not part of the bus address list. The "Module inputs allocation list" contains for each module input the associated receive register number and, in the case of binary values, the bit position.

5.4 Address List for Module Outputs In the address list for module outputs, a send register is defined for each signal that is to leave the module and, additionally, a send bit in the case of binary signals, e.g.:

6. PARAMETER LIST The parameter list contains up to 80 parameters for function blocks. Parameter values can be changed on-line on the PDDS anytime.

7. EVENT GENERATION For each system cycle, the module is prompted once by the PROCONTROL system to send the information stored in the send registers of the shared memory. If values change within one cycle time, this will be treated as an event. The module recognizes the following conditions as an event:

• a change of the status in the case of binary values • a change of an analog value by a fixed threshold of 0.39 % and the expiration of a time-out of 200 msec after the

last transmission activity (cyclically or per event).

Function block EZS can be used to set these response values separately for each analog value (cf. Function block description). When an event occurs, the cyclic mode is interrupted, and the new values are given priority and transmitted over the bus.

Output Address

AG1 1, 5

Bit no.Register no.

(1 - 15)(0 - 199)

2VAA007467 11

Disturbance Annunciations on the Module SIMULATION

8. SIMULATION With the PDDS, a maximum of 32 module signals (function results, module inputs and outputs) can be overwritten with constant values (”simulated”). Simulation values can be changed on-line on the PDDS anytime. When a simulation is cancelled on the PDDS, a simulation data record is deleted and the module will go on operating with the data received from the bus or with the values formed inside the module.

9. DISTURBANCE BIT EVALUATION, RECEIVE MONITORING The telegrams received over the bus may be provided with a fault flag on bit position 0. This fault flag is generated by the sending module based on plausibility checks and is set to ”1” if certain disturbances occur (cf. the respective Module or Function Block Descriptions). In order to be able to detect errors occurring during signal transmission, the module is provided with a monitoring function for the cyclic renewal of the input telegrams. If a signal is not renewed for a certain amount of time (e.g. caused by a failure of the sending module), in the assigned receive register of the shared memory, the bit of position 0 will be set to ”1”. At the same time, in the case of binary value telegrams, all binary values will be set to ”0”. For analog values, the old value is maintained. A set disturbance bit does not automatically cause a reaction in the module. If the disturbance bit of a telegram is to be evaluated, this must be taken into consideration in the structuring process. Disturbance bits from telegrams received can be used inside the module only. They are not included in telegrams to be sent. Function blocks with processing functions for measured values do include disturbance bits in the telegrams to be sent. Further information on disturbance bit evaluation is given in the respective function block descriptions.

10. DIAGNOSIS AND ANNUNCIATION FUNCTIONS

10.1 Disturbance Annunciations on the Module On the module front, light-emitting diodes indicate the following conditions:

LED designation

• Disturbance ST • Module disturbance SG

The LED ST signals all disturbances of the module and disturbances in the data communication with the module. The LED SG signals module disturbances only.

10.2 Disturbance Annunciation Signals to the Annunciation System The annunciation system or the Control Diagnosis System CDS receives disturbance messages from the control module over the bus.

10.3 Diagnosis In the processing section of the module the received telegrams, the generation of the telegrams to be transmitted and the internal signal processing are monitored for errors (self-diagnosis). If a disturbance occurs, the type of the disturbance is stored in the diagnosis register and a disturbance signal is transmitted to the PROCONTROL system at the same time. When requested, the module transmits a telegram which contains the data stored in the diagnosis register (register 246) The contents of the diagnosis register, the signals on the general disturbance lines, the messages on the CDS, and lamps ST and SG are shown in Fig. 1. If message ”Process channel fault” is indicated in the diagnosis register, this may be due to the following causes:

• Short-circuit at supply outputs UA1, UA2, UA3, UA4, UB1, UB2, UF1, UF2 and UF3 • Short-circuit at binary outputs BO1 .. BO4 or BO5 .. BO8 • Analog input value not plausible, i.e. the values are smaller than -6.25% or greater than 150 %. • Wire break at analog outputs AO1 .. AO4 or AO5 .. AO8 in a configuration for 4 ... 20 mA.

12 2VAA007467

DIAGNOSIS AND ANNUNCIATION FUNCTIONS Diagnosis

If message ”Processing fault” is indicated in the diagnosis register, this may be due to the following causes:

• Invalid structuring. • Analog section for analog outputs AO1 . .AO4 or AO5 .. AO8 defective. • Internal module voltages disturbed. • Disturbance of the internal reference values for the analog inputs and analog outputs.

Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Type S S S S 0 S D S 0 0 0 S 0 S 0 0

Parameter fault Process channel fault Processing fault Checksum error detected

Timer defective Module restart executed Bus deactivation defective

Receive monitoring responded

Event mode fault

Wrong firmware PROM Hardware defect of processing section EEPROM not valid Processing initialization active

by bus control module Module address not within 1 - 58 Hardware defect of bus interface

Module not operating

Module not accessible from bus

Module operating Diagnosis register 246

6615 6600 6601 6602

6604 6605 6606

6610

6612

CDS messages *)

ST

SST ≥ 1 ≥ 1

D = Dynamic annunciations are cancelled after the contents of the diagnosis register has been transmitted S = Static annunciations disappear automatically upon deactivation

SG

SSG ≥ 1

0 = Not used

Module transmitter disconnected

Figure 1: Diagnosis messages of 83SR52R1210 *) The control diagnosis system (CDS) provides a description for every message number. This description comprises:

• Information about cause and effect of the disturbance • Recommendations for elimination.

Thus, fast disturbance elimination is ensured

2VAA007467 13

Initialization and Bootstrapping with User Lists OPERATING STATES OF THE MODULE

11. OPERATING STATES OF THE MODULE

11.1 Initialization and Bootstrapping with User Lists The initialization is effected either upon plugging-in of the module or after the voltage is connected. By initialization, the module is put into a defined initial state. During initialization, disturbance light-emitting diodes ST and SG are on. There is no user program available when the module is first started. The module signals ”Processing fault” and disturbance light-emitting diodes ST and SG are on. First, the user program of the PDDS has to be transmitted via bus into the RAM of the module. The procedure will start with the structure list, and the PDDS will call up the other lists automatically. The PDDS checks locations and addresses for each transmission activity in order to avoid wrong lists. The module checks each list received for plausibility. Now, the complete user program can be transferred per PDDS command into the Flash-PROM. After this procedure, the module is ready for operation and the disturbance light-emitting diodes ST and SG will go off.

11.2 Normal Operation The initialization is effected either upon plugging-in of the module or after the voltage is connected. By initialization, the module is put into a defined initial state. During initialization, disturbance light-emitting diodes ST and SG are on. There is no user program available when the module is first started. The module signals ”Processing fault” and disturbance light-emitting diodes ST and SG are on. First, the user program of the PDDS has to be transmitted via bus into the RAM of the module. The procedure will start with the structure list, and the PDDS will call up the other lists automatically. The PDDS checks locations and addresses for each transmission activity in order to avoid wrong lists. The module checks each list received for plausibility. Now, the complete user program can be transferred per PDDS command into the Flash-PROM. After this procedure, the module is ready for operation and the disturbance light-emitting diodes ST and SG will go off.

11.3 Changing the User Program User programs (structure, address, parameter and simulation list) can be transferred from the module into the PDDS or can be taken over from the data base. Changed user programs can be transferred back to the module. This may be done as described below:

• The changed user program is transferred by the PDDS into the RAM of the module. • Then, the module checks the user program in the background. If no faults are detected, the new list is activated

and transferred into the nonvolatile Flash-PROM.

When the new lists are activated, the old user program is compared to the new one. Only in the case of a discrepancy, an initialization phase will be carried out in the new user program. This means, all controllers and binary group control systems will enter ”Manual” mode, memory and timer elements are reset, and the commands present at the process interface are deactivated. In the case of changed addresses at module inputs (EGn), the respective shared-memory entries are set to zero until new data is received for the first time. If the lists are identical, the processing will not be interrupted by an initialization phase.

11.4 Changing Fixed Values Some fixed values in the structure list can be changed online via the PDDS. The changes made are stored in the Flash–PROM.

11.5 Changing Parameters Some parameters in the parameter list can be changed on-line via the PDDS. The changes made are stored in the Flash–PROM.

11.6 Simulation Via the PDDS, module signals can be specified and deleted. The simulation data is stored in the Flash-PROM

14 2VAA007467

PROCESS INPUTS AND OUTPUTS Output of Commands to the Process Interface

12. PROCESS INPUTS AND OUTPUTS

12.1 Output of Commands to the Process Interface The module incorporates interfaces for analog and binary signal output to the process. The signal output to the process interface takes place via function block AP08.

12.2 Process inputs The module incorporates interfaces for analog and binary signal input. For recording speed data, 3 mutually independent differential inputs are available. The speeds are determined on the basis of pulses, using function block EDZ. For the analog and binary signals of the process interface, signal input takes place via function block EP08.

13. CONFIGURATION OF INPUTS/OUTPUTS

13.1 Setting of the system hum filter The system hum filter is defined in the first EP04 function block for both analog inputs.

Indication PDDS

Input PDDS

Filtering

FIL 0 16 50 60

No filter active 16 2/3 Hz

50 Hz (default setting) 60 Hz

13.2 Setting of the analog inputs and outputs The configuration is defined by means of function blocks EP08 and AP08 (cf. Function block descriptions).

13.3 Setting of the jumpers Jumpers X300....X330 are used to set the type of analog value transmitter connected to the analog input. When X3x0 is plugged in, analog input AIx is non-floating and can be used for connecting 2-wire measuring transducers which are supplied from the module. When X3x0 is not plugged in, analog input AIx is floating and can be used for connecting 2-wire measuring transducers which are either externally supplied or supplied from the module.

13.4 Configuration of the speed inputs The speed inputs are configured using function block EDZ. The value range of the entries for nominal speed and detail function is limited to a range within 0...4095 if integer values are used. If parameters are used, a range within 0...16383 is possible.

2VAA007467 15

Overview APPLICATION OF FUNCTION BLOCKS

14. APPLICATION OF FUNCTION BLOCKS

14.1 Overview Function block Abbrev.

BINARY FUNCTIONS

Switch-off delay element ASV

2-out-of-3 selection, binary B23

2-out-of-4 selection, binary B24

out-of-N selection BMN

Bit marshalling BRA2

Dual-BCD-converter DBC1

Dual-decimal-converter DDC

Dynamic OR element DOD

Switch-on delay element ESV

Monostable flip-flop, break MOA

Monostable flip-flop, constant MOK

OR element ODR

RS flip-flop RSR

AND element AND

Counter ZAE

BINARY GROUP CONTROL

Group control function for sequential control GSA2

Group control function for logic control GSV

Criteria call KRA1

Criteria call without time monitoring KRA3

Step function for multifunction SCH1

Preselection function, two-fold VW2

Preselection function, three-fold VW3

Preselection function, four-fold VW4

Selector switch, two-fold to four-fold WS41

DRIVE CONTROL

Drive control function, unidirectional drive ASE1

Drive control function, incremental output ASI2

Drive control function, solenoid valve ASM1

Drive control function, proportional output ASP2

Drive control function, actuator ASS1

Drive control function, reversible drive ASW

16 2VAA007467

APPLICATION OF FUNCTION BLOCKS Overview

Function block Abbrev.

LIMIT SIGNAL ELEMENTS

Limit signal for upper limit value GOG

Limit signal for lower limit value GUG

Limit signal generation GRE1

ANALOG FUNCTIONS

Absolute value generator ABS

Limiter BEG

Divider DIV

Function generator FKG

ANALOG FUNCTIONS

Integrator INT1

Factor variation KVA

Maximum value selector MAX

Minimum value selector MIN

Multiplier MUL

Monitoring and select function MVN

Differentiator PDT

Dead-time element PT0

Delay element, 1st order PT1

Delay element, 2nd order PT2

Delay element, Nth order PTN

Square-root extractor RAD

Summing multiplier SMU

Time variation TVA

Change-over switch UMS

SIGNAL CONDITIONING FUNCTIONS

Enthalpy function ENT1

Correcting element for water level measurement NIV1

Non-linear filter FIL1

Correcting function, steam flow measurement KOD

Correcting function, gas flow measurement KOG

Calculation of saturated steam pressure SDD

Calculation of saturated steam temperature SDT

2VAA007467 17

Overview APPLICATION OF FUNCTION BLOCKS

Function block Abbrev.

ANALOG CONTROL

Auto/Manual station HST1

PID controller PID3

PI controller PIR3

P controller PRE

Setpoint integrator SWI1

Differentiator with derivative-action time PTV

Setpoint adjuster SWV1

Disturbance bit suppression SZU

PUSHBUTTON SELECTION FUNCTIONS

Pushbutton selection TAW

Pushbutton selection with target value presetting TAZ

ORGANIZATION FUNCTIONS

Diagnosis DIA

Event time and threshold adjuster EZS

Text element TXT

Text element with input of the module cycle time TXT2

Date and time reception UHR1

Signal transmitter clock WEK

PROCESS INPUT AND OUTPUT FUNCTIONS

Output of analog and binary process signals AP08

Input of analog and binary process signals EP08

Speed input EDZ

The exact specification of the function blocks as well as the procedure of structuring is explained in the respective function block descriptions.

18 2VAA007467

FUNCTION DIAGRAM Overview

15. FUNCTION DIAGRAM

Terminal Designations The module consists of a printed circuit board (see “Module design”). The printed circuit board is equipped with connectors X21 and X11. Connector X21 contains all process inputs. Connector X11 incorporates the standard interface with the station bus and the operating voltages of the module.

+

stat

ion

bus

SS

SRA*

ZDZD

ZZD

ZUS

AUS

B

d30

d32

b32

z32

b02

b14

d26

d18

83SR

52 -

E/R

1210

SGST

proc

esso

rop

erat

ing

func

tions

func

tion

bloc

ksus

er fu

nctio

nsFl

ash-

PR

OM

RA

M

shar

edm

emor

y

para

llel/s

eria

lco

nver

sion

mon

itorin

g pr

oces

s in

terfa

ce 1

UA1/

UA2

BO1.

..4

UB1

UF1

X11

+ BO1

BO2

BO3

BO4

ZB1

z02

z04

z06

z08

z10

X21

X22

#=

z02

z04

AO1

+-

#=

z06

z08

AO2

+-

z16 BI

1BI

2BI

3BI

4

b02

b04

b06

b08

b10

+ UB1

#=

z10

z12

AO3

+-

#=

z14

AO4

+-

b10

b16

UA2

#=

b12

AI2

+-

ZA2

b14

b24

z22

z24

UF1

#n

b22

FI1

+-

ZF1

proc

ess

inte

rface

1

anal

og in

puts

anal

og o

utpu

tsbi

nary

inpu

tsbi

nary

outp

uts

spee

d in

put

X31

0

UA1

ZA1

b02

b08

#=

b04

AI1

+-b0

6

X30

0

* Fo

r pro

per f

unct

ioni

ng o

f the

mod

ule

the

conn

ecto

r X11

/d18

has

to b

e co

nnec

ted

to Z

D (o

nce

per s

ubra

ck).

* For proper functioning of the module, connector X11/d18 has to be connected to ZD (once per subrack)

2VAA007467 19

Overview FUNCTION DIAGRAM

Function diagram, continued

83SR

52 -

E/R

1210

cont

inue

d

+ BO5

BO6

BO7

BO8

ZB2

z12

z14

z16

z18

z20

X21

X22

#=

z18

z20

AO5

+-

#=

z22

z24

AO6

+-

z32 BI

5BI

6BI

7BI

8

b12

b14

b16

b18

b20

+ UB2

#=

z26

z28

AO7

+-

#=

z30

AO8

+-

#=

b20

AI3

+-b2

2b2

6b3

2

UA4

#=

b28

AI4

+-

ZA4

b30

b28

z26

z28

UF2

#n

b26

FI2

+-

ZF2

pro

cess

inte

rface

2

anal

og i

nput

san

alog

out

puts

bina

ryin

puts

bina

ryou

tput

ssp

eed

inpu

t

pro

cess

inte

rface

3

UF3z3

0z3

2#n

b30

FI3

+-

ZF3

b32

X32

0X

330

mon

itorin

g pr

oces

s in

terfa

ce 2

UA3/

UA4

BO5.

..8

UB2

UF2

mon

itorin

g pr

oces

s in

terfa

ce 3 UF

3

spee

d in

put

b18

b24

UA3

ZA3

20 2VAA007467

CONNECTION DIAGRAM Overview

16. CONNECTION DIAGRAM

EH

+US

AU

SB

stat

ion

bus

ZDZD

ZZD

ZS

RA

AOn-

AOn+

UBn

BIn

BIm

anal

og o

utpu

t0/

4-20

mA

pow

ered

bin

ary

inpu

tsan

alog

inp

ut0/

4-20

mA

50

2-w

iretra

nsdu

cerX3

x0AI

n+AI

n-UA

nZA

n

anal

og i

nput

0/4-

20 m

A

50 4-w

iretra

nsdu

cer

X3x0

AIn+

AIn-

UFn

ZFn

spee

d in

puts

150

leve

l con

verte

r89

EI3

0

FIn+

FIn-

RS42

2

spee

dpi

ck u

p's

toot

hed

whe

el

2VAA007467 21

Overview MODULE DESIGN

17. MODULE DESIGN Board size: 6 units, 2 division, 160 mm deep Connector: acc. to DIN 41 612 / IEC 60603-2

1 x for station-bus connection, 48-pin edge-connector, type F (connector X11) 2 x for process connection, 32-pin edge-connector, type F (connector X21, X22)

Weight: approx. 0.66 kg View of connector side:

Contact assignments of process connector X21 View of contact side

b z

02 BI1 BO1

04 BI2 BO2

06 BI3 BO3

08 BI4 BO4

10 UB1 ZB1

12 BI5 BO5

14 BI6 BO6

16 BI7 BO7

18 BI8 BO8

20 UB2 ZB2

22 FI1+ UF1

24 FI1- ZF1

26 FI2+ UF2

28 FI2- ZF2

30 FI3+ UF3

32 FI3- ZF3

X11

X22 X21

22 2VAA007467

MODULE DESIGN Overview

Contact assignments of process connector X22 View of contact side

b z

02 UA1 AO1+

04 AI1+ AO1-

06 AI1- AO2+

08 ZA1 AO2-

10 UA2 AO3+

12 AI2+ AO3-

14 AI2- AO4+

16 ZA2 AO4-

18 UA3 AO5+

20 AI3+ AO5-

22 AI3- AO6+

24 ZA3 AO6-

26 UA4 AO7+

28 AI4+ AO7-

30 AI4- AO8+

32 ZA4 AO8-

2VAA007467 23

Overview MODULE DESIGN

Side view and view of module front

83SR52

ST

X22

ST disturbanceSG module

disturbanceSG

ABB ABB

ABB ABB

X11

X300

X301

X302

X303

24 2VAA007467

SYSTEM DATA Power supply

18. SYSTEM DATA Kind of influence Environmental Parameter Standard Characteristic/Value Operating conditions Climatic environment Ambient temperature IEC/EN 60068-2-2 0°C to +70°C, 16h

Relative humidity IEC/EN 60068-2-78 5% to 95% RH Atmospheric pressure IEC/EN 60068-1 86 kPa to 106 kPa

Electromagnetic compatibility (EMC)

Electrostatic discharge immunity IEC/EN 61000-4-2 Class 3 Class 2

Air discharge 8 kV Contact discharge 4 kV

Radiated, radio-frequency, electromagnetic field immunity

IEC/EN 61000-4-3 Class 3

80 MHz to 3000 MHz, 10 V/m, 80 % AM (1 kHz)

Electrical fast transient/burst immunity

- Supply lines for AC 120/230 V (burst)

- Supply lines for DC 24 V - Signal lines (I/O and bus lines)

IEC/EN 61000-4-4 Class 3

5/50 ns 2 kV 2 kV 2 kV

Surge immunity - Supply lines for AC 120/230 V

(burst) - Supply lines for DC 24 V - Signal lines (I/O and bus lines)

IEC/EN 61000-4-5 Class 4/3 Class 1/1 Class 3

1.2/50 ns 4/2 kV 0.5/0.5 kV 2 kV

Immunity to conducted disturbances, induced by radio-frequency fields

IEC/EN 61000-4-6 Class 3

0.15 MHz to 80 MHz, 10 V, 80% AM (1 kHz), Source impedance 150 Ω

Radiated emission CISPR16 / EN 55016 Class A

30 MHz to 1000 MHz, Limit Class A, group 1

Conditions of storage and transport Climatic environment Ambient temperature IEC/EN 60068-2-2 -40°C to +85°C, 16h

Relative humidity IEC/EN 60068-2-30 5% to 100% RH +25°C to 40°C (6 cycles)

Atmospheric pressure IEC/EN 60068-1 70 kPa to 106 kPa

19. TECHNICAL DATA

19.1 Power supply Operating voltage USA/USB 19.5..30 V, typ. 24 V

Power consumption at USA/USB = 24V typ. 200 mA + output values

Power dissipation at USA/USB = 24V 4,8..10 W, depending on operating and signal status

Reference potential, process side Z = 0 V

Reference potential, bus side ZD = 0 V

19.2 Process Interface

19.2.1 Binary inputs BI1..BI8 "0" signal 0 ... 3 V

"1" signal 11.2 ... 60 V

Input resistance 10 kOhm ± 5 %

Input current at UBn = 48 V 4.8 mA

Line resistance ≤ 100 Ohm

Line length (supply and return line) ≤ 1000 m

2VAA007467 25

Process Interface TECHNICAL DATA

19.2.2 Transmitter power supply for binary inputs UB1, UB2 Output voltage 48 V ± 10 %

Output current ≤ 30 mA

Response time of the monitoring function ≤ 1 s

The outputs are short-circuit-proof, non-interfering,

and open-circuit-proof.

19.2.3 Binary outputs BO1...BO8 Output voltage USA/USB -max. 4 V

Output current ≤ 100 mA

Line resistance ≤ 50 Ohm

Line length (supply and return line) ≤ 500 m

The outputs are short-circuit-proof, non-interfering, and open-circuit-proof

19.2.4 Speed inputs FI11...FI13 Standard RS422 incremental inputs

Bus terminating resistance in the 83SR52 150 Ohm ± 5 %

Input frequency: ≤ 40kHz

Line length (supply and return line) ≤ 1000 m

Inputs are short-time (<10s) surge-proof up to +-30V

19.2.5 Transmitter power supply for speed inputs Outputs UF1...UF3

Output voltage USA/USB -max. 4V

Output current ≤ 300 mA

Response time of the monitoring function ≤ 1 s

The outputs are short-circuit-proof, non-interfering,

and open-circuit-proof.

19.2.6 Analog inputs AI1...AI4 Input resistance 50 Ohm

Input current, nominal range (corresponding to 0...100 %) 0/4 ... 20 mA

Maximum range -1 ... 50 mA

Line resistance ≤ 50 Ohm

Line length (supply and return line) ≤ 500 m

Response time of the monitoring function (at 4...20 mA) ≤ 1 s

2-wire transducer Jumpers X300 .... X330 plugged in:

Input resistance (to Z)

4-wire transducer Jumpers X300 .... X330 not plugged in:

Input resistance (to AIx-)

26 2VAA007467

TECHNICAL DATA Process Interface

19.2.7 Accuracy of input values All data are based on 100 % of the input value 20 mA

Accuracy, in as-delivered condition (23°C) ≤ 0.1 %

over temperature range within 0...70 °C, ≤ 0.3 % aging, voltage range

Quantization error ≤ 0.02 %

Linearity error ≤ 0.1 %

Temperature sensitivity ≤ 50 ppm/K (typ. 30 ppm/K)

Errors due to digital linearization 1 LSB

Resolution 12 bits

Common-mode rejection towards potential Z 120 dB

Normal-mode rejection at 16 2/3, 50 and 60 Hz 50 dB

19.2.8 Transducer power supply for analog inputs Outputs UA1...UA4

Output voltage USA/USB -max. 4 V

Output current ≤ 50 mA

Line resistance ≤ 50 Ohm

Line length (supply and return line) ≤ 500 m

Response time of the monitoring function ≤ 60 s The outputs are short-circuit-proof, non-interfering, and open-circuit-proof.

19.2.9 Analog outputs AO1...AO8 Output current (impressed current) 0/4 ... 20 mA

Maximum output current 23 mA

Output voltage ≤ 13 V

Burden ≤ 500 Ohm

Line resistance ≤ 50 Ohm

Line length (supply and return line) ≤ 500 m

Response time of the monitoring function (at 4..20 mA) ≤ 60 s The outputs are short-circuit-proof, non-interfering, and open-circuit-proof.

19.2.10 Accuracy of the output values All data are based on 100 % of the output value 20 mA

Accuracy, in as-delivered condition (23°C) ≤ 0.1 %

over a temperature range within 0...70 °C, ≤ 0.4 % aging, voltage range

Quantization error ≤ 0.02 %

Linearity error ≤ 0.1 %

Temperature sensitivity ≤ 50 ppm/K (typ. 30 ppm/K)

Resolution 12 bits

2VAA007467 27

Interference immunity (of process inputs and outputs) ORDERING DATA

19.2.11 Initialization time Upon power connection or when the module is plugged in 2 … 22 s

19.3 Interference immunity (of process inputs and outputs) The product is in conformity with the provisions of the following European Directive: 2014/30/EC Directive of the European Parliament and of the Council of

26. Februar 2014 on the harmonization of the laws of member States relating to electromagnetic compatibility (EMC Directive)

Conformity to the stated Directive is assured through the application of the following harmonized standards:

Environment: Industry EMC, Emission: EN 61000-6-4: 2007/A1:2011 EMC, Immunity: EN 61000-6-2: 2005/AC:2005

See 2VAA002182R0301_CE-Conformity-P14.pdf for detailed technical data.

20. ORDERING DATA Order no. for complete module: Type designation: 83SR52R1210 Order number: GKWE858000R1210 Technical data are subject to change without notice!

28 2VAA007467

REVISION HISTORY Interference immunity (of process inputs and outputs)

21. REVISION HISTORY Rev. Date / Initial 1.0 Replaces 1KGF 100 474 2016-07-13

CG

2VAA007467 29

ABB Inc. Power Generation Wickliffe, Ohio, USA E-Mail: [email protected] www.abb.com/controlsystems ABB AG Power Generation Mannheim, Germany E-Mail: [email protected] www.abb.com/controlsystems ABB Pte. Ltd. Power Generation Singapore E-Mail: [email protected] www.abb.com/controlsystems

Doc

umen

t Num

ber 2

VA

A00

7467

30 MD_2VAA007467_83SR52R1210.docx