March 2014 PKGP-PRC006-EN
Product Catalog
Koolman Air-Cooled Chiller and Heat PumpCGAK cooling only /CGAR heat pumpModel:030~200R410A, 50Hz
2
Contents
Features and Benefi t 3
Mechanical Specifi cations 4
Model Nomenclature 5
Performance Data 6
Dimensions 8
Service and Maintenance Space Requirement 12
Electrical Specifi cations 13
Water Pressure Drop Curve 14
3
Features and Benefi ts
IntroductionUsing the leading high-effi ciency ermetic scroll compressor and evaporator technology, Koolman provides you a stable, reliable and highly effi cient operation. Matched with a large variety of fan coils of different sizes it can be widely used in top grade apartments, luxury villas, offi ce buildings, small-sized restaurants, retail stores and hotels to create a comfortable and delightful indoor environment.
State-of-the-art appearanceKoolman boasts of its state-of-the-art appearance. The contemporary appearance, designed by expert designers, will be naturally integrated with the surrounding environment and will defi nitely display your prominent taste.
Small footprintAs a result of the particular slim design (standard type is 500mm thick while mini type is only 393mm thick), the unit can be installed directly on the veranda, rooftop or ground without the need to have aplant room.
Available optionsUnit with pressurized water tank is available to meet various requirements.
Noise levelKoolman uses low noise fans and components to achieve its low noise evel.
Easy installationEach chiller has factory charged oil and refrigerant for reducing fi eld labor and materials costs. All units are factory run tested. Only power supply and water piping are required to be connected on the jobsite.
Environmentally friendly refrigerantAll models are charged with R410A refrigerant.
Free of Cooling TowerHeat dissipation in the way of air cycle eliminates the need for cooling water tower. Thus, not only does it save the cost and space for cooling tower it also eliminates water shortage concerns.
4
Mechanical Specifi cations
GeneralKoolman air-cooled liquid chiller is designed to couple with fan coil units and air handling units for residential and light commercial air conditioning applications. Units are composed of scroll compressor (s), plate type evaporator, fi nned-coppertube and aluminum condenser, axial fan assembly, expansion valve, four-way reversal valve (heat pump only), indoor Cooling/Heating control switch, water fl ow switch, fi lter dryer, sight-glass, built-in water pump, galvanized sheet metal housing with powder paint and factory mounted controls. Optional fi ttings include pressurized water tank system.
CompressorDepending on capacity range, units come with single or double scroll compressors to cater for changing demand and effi cient part load operations.
EvaporatorEvaporator is a compact brazed plate heat exchanger with AISI 316 stainless plates and adapters. A 20-mesh strainer is installed at the water inlet to protect the evaporator and unit against fouling. The strainer (factory provided, fi eld installed) can be removed for cleaning.
HousingAll parts are fabricated to precision by state-of-the-art CNC machines. The frame design allows all panels to be removed for service without affecting the structure of the unit. The panels are made of galvanized steel plate with powder paint. All panels are internally insulated with single layer foam cell in order to reduce noise and vibration.
Water pumpPump is Rotodynamic pumps and adopts a mechanical shaft seal. Motor is fan cooled (TEFC), 2-pole induction type. Pump is installed in the unit to save installation space and also to reduce noise level.
Controls and protection devicesThe controller contains all the basic electrical protection devices including electromagnetic switches, relays and current overload protectors. The automatic control devices consist of high and low pressure switches, thermostatic and anti-freeze cutouts, which improve and protect the unit's normal operation.In addition, the preset low temperature protection command can start the machine automatically to protect the water pipes from freezing.
LCD microprocessor-based controllerPrecise temperature control of inlet chilled water, operation modes and system protection are provided by the long-range controller. In addition, the password can be set and any abnormal condition will be monitored and captured to facilitate quick repair and normal operation. In addition, the interlocking function of the two-way valve is available.
Air-cooled condenserThe unit comes with air-cooled fi n-tube U or V shaped condensers. Copper tubes are of the 3/8" diameter, seamless type. Fins are aluminum with effi cient Wavy fi n. Copper tubes are expanded mechanically to bond with the fi ns for effective heat transfer. Light-weight axial fl ow fan(s) is (are) driven by high effi ciency, low speed, low noise motor(s) to ensure quiet and reliable operations.
Operating limitsCooling mode Heating mode
mini 21℃ -7℃
max 43℃ 21℃
Leaving water temperature
Cooling mode Heating mode
mini 5℃ 40℃
max 15℃ 50℃
5
Digit 1,2,3 CGA = Air-Cooled Chiller and Heat Pump
Digit 4 Model
K = Cooling Only
R = Heat Pump
Digit 5,6,7 Model
030 100
050 120
060 150
075 200
Digit 8 Power Supply
5 = 380V/50Hz/3ph (For Model 030,050,060,075,100,120,150,200)
6 = 220V/50Hz/1ph (For 030 with single compressor and 060 with double compressors)
Digit 9 Manufacturing Code (defaulted by factory)
R = R410A
Digit 10 Controller
B=Microprocessor-based adjustable water temperature controller
Digit 11 Water Side Electric Heater
N=None
Digit 12 Service Sequence
A=The fi rst time
Digit 13 Water Pump for Unit
R=With Pump inside (standard)
N=Without Pump
Digit 14 Applicable Ambient Temperature
R = Standard ambinent temperature/Blue-fi n
Digit 15 Fitting Options
N = None (Standard Unit)
Digit 16 Other option
B = Export
N15
A16
R14
R13
A12
N11
B10
R9
58
07
56
05
R4
A3
G2
C1
Model Nomenclatures
6
Mmodel CGAR/K0305R CGAR/K0306R CGAR/K0505R CGAR/K0605R CGAR/K0606R
Cooling Capacity Kal/Hr 9040.5 9557.1 11193 14809.2 19114.2
kW 10.5 11.1 13 17.2 22.2
Heating Capacity Kal/Hr 9901.5 10418.1 12570.6 15584.1 21352.8
kW 11.5 12.1 14.6 18.1 24.8
Power Supply V 380-415V/50Hz/3 220-240V/50Hz/1 380-415V/50Hz/3 380-415V/50Hz/3 220-240V/50Hz/1
Compressor
Number 1 1 1 1 2
Rated Current(C/H) A 6.01/6.39 18.78/20.4 7.97/8.35 10.02/9.93 20/20.95
Locked Rotor Current A 60 130 82 100 130
Power Input(C/H) KW 3.32/3.43 3.58/3.78 4.16/4.26 5.65/5.2 3.63/3.65
Fan
Type Hermetic Scroll compressor
Number 2 1
Rated Current A 0.5 4.8
Power Input kW 0.1 0.6
Water Pump
Number 1
Rated Current A 1.45 3.65 1.45 1.45 3.65
Power Input kW 0.74
Discharge Head m 25.05 24.65 23.55 17.89 22.05
EvaporatorType Plate type heat exchanger
Water Flow (C/H) m3/h 1.79/1.91 1.91/2.02 2.24/2.45 2.96/3.11 3.82/4.14
Protective Device Overheat protection, High and Low Pressure Protection
LubricantType 320HV 320HV 320HV 320HV 320HV
Charge L 1.57 1.57 1.57 1.57 1.57+1.57
RefrigerantType R410a
Charge kg 2.8 2.7 3.3 3.7 2.8+2.8
Unit Dimensions mm 950*393*1285 1290*500*1900
Water Connection (FPT) inch 1“ 1“ 1“ 1“ 1-1/4"
Direction of Connection Right Right Right Right Right or Left
Operation Weight Kg 130 131 141 149 320
Note:1.Cooling Mode Conditions (Evap. 12℃/7℃ - Air. 35℃).2.Heating Mode Condition (Evap. 40℃/45℃ - Air. DB/WB 7℃/6℃).3.The unit is tested under GB18430.1-2007and GB18430.2-2008.
Performance Data
7
Note:1.Cooling Mode Conditions (Evap. 12℃/7℃ - Air. 35℃).2.Heating Mode Condition (Evap. 40℃/45℃ - Air. DB/WB 7℃/6℃).3.The unit is tested under GB18430.1-2007and GB18430.2-2008..
Performance Data
Mmodel CGAR/K0755R CGAR/K1005R CGAR/K1205R CGAR/K1505R CGAR/K2005R
Cooling Capacity Kal/Hr 20405.7 24280.2 33148.5 42275.1 47355
kW 23.7 28.2 38.5 49.1 55
Heating Capacity Kal/Hr 21266.7 25571.7 34870.5 46063.5 51487.8
kW 24.7 29.7 40.5 53.5 59.8
Power Supply V 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3
Compressor
Number 1 2 2 2 2
Rated Current(C/H) A 13.77/13.43 8.2/8.3 11.2/11.1 14.9/15.2 17/17.1
Locked Rotor Current A 110 82 100 110 140
Power Input(C/H) KW 7.85/7.1 4.43/4.25 5.85/5.7 6.95/7.2 8.48/8.15
Fan
Type Hermetic Scroll compressor
Number 3 1 2 2 2
Rated Current A 0.5 1.6 1.6 4.2 4.2
Power Input kW 0.1 0.6 0.6 1.5 1.5
Water Pump
Number 1
Rated Current A 1.45 1.45 3.26 2.4 3.8
Power Input kW 0.74 0.74 1.44 1.41 1.92
Discharge Head m 18.99 16.07 18.05 16.28 26.18
EvaporatorType Plate type heat exchanger
Water Flow (C/H) m3/h 4.08/4.25 4.85/5.11 6.62/6.96 8.45/9.2 9.46/10.28
Protective Device Overheat protection, High and Low Pressure Protection
LubricantType 320HV 320HV 320HV 320HV 320HV
Charge L 1.57 1.57+1.57 1.57+1.57 2.66+2.66 2.66+2.66
RefrigerantType R410a
Charge kg 4.4 3.0+3.0 3.8+3.8 4.0+4.0 4.5+4.0
Unit Dimensions mm 950*393*1590 1290*500*1900 1990*500*1900
Water Connection (FPT) inch Inlet1-1/4" outlet1" 1-1/4" 1-1/4" 1-1/4" 1-1/2"
Direction of Connection Right Right or Left Right or Left Front Front
Operation Weight Kg 202 449 530 540 540
8
Dimensions
Mini casingCGAK/R-0305R/0306R/0505R/0605R (Unit: mm)
CGAK/R-0705 R (Unit: mm)
Ø1"Water outlet
Ø1"Water inlet
90
740
950670
1285
402
393
Mini-Koolman
186
647
90
402
393
1590
670
950
824
Mini-Koolman
732
186
1 1/4Water outlet
1 1/4Water inlet
9
Dimensions
Standard casingCGAK/R-0606R/1005R (Unit: mm)
500
50
1290
FPT 1 1/4"B Water inletPower cable inletØ40
Water outlet
500
1900
900
1000
580
Drain waterFPT 1/2" B
99
75
FPT 1 1/4"B
120
155
TM
50
FPT 1-1/4"B
75
FPT 1/2" B
500
1990 580
1000
900
1900
500Drain water Water outlet
Power cable inletØ40Water inletFPT 1-1/4"B
TM TM
120
155
99
CGAR/K-1205R(Unit:mm)
10
Dimensions
CGAR/K-2005R (Unit: mm)
50
FPT 1-1/2"B
FPT 1/2" B
490.0000
1990
580
1000
900
1900
500.0000
Water outlet
Drain waterØ40
Water inletFPT 1-1/2"B
TM TM
125
120
90 985
500
1990
CGAR/K-1505R (Unit: mm)
50
FPT 1-1/4"B
FPT 1/2" B
500
1990 580
1000
900
1900
500
Water outlet
Drain waterØ40
Water inletFPT 1-1/4"B
TM TM
125
120
90 985
11
Pressure water tank (Option Unit:mm)
Dimensions
Installation Example
P
P
Makeup water valve
Drain Valve
Shut-off Electric heater
Fan coil X4
Tapwater
Water drainage
Direct return Reversed
return
Shockproof hose
Thermometer
Automaticair vent
Primary Unit pressurisedwater tank
water strainer
flowswitch
Description of the principle of the pressurized water tank:1. In order to avoid the pipe cracking due to the system over pressure resulting from the change of
ambient temperature and also to avoid the water hammer in the pipes, a pressurized water tank shall be installed for system.
2. In order to avoid the excessively high or low pressure in the pipe, an automatic feed water valve and an automatic drain valve are included in the pressurized water tank. The feed water pressure can be adjusted based on the fi eld situation.
3. An open expansion tank shall be installed at the highest position of system.
Note: the automatic exhaust valve shall be set at the highest point of the piping
SizeModel
A B C D E F G H
WTANK-5 470 263 230 182 254 435 415 455
WTANK-12 620 400 324 162 356 569 440 475
Water Inlet(φ12.7mm)Water Outlet(φ12.7mm)
Water Drainage(φ12.7mm)
H
G
FAB
DC E
12
Unit: mm
Service and Maintenance Space Requirement
300
500
1500
300
500
Mini-Koolman
4030
1630
450 730
1630
850
496
640 740
4030
640
740
450
496
2330
640
150
640
640
950
402 393
Installation dimensions
CGAR(K)0606R/1005R
Air Direction
CGAR(K)0305R/0306R/0505R/0605R/0755R
CGAR(K)1205R/1505R/2005R
13
MODELPower supply
(V/Hz/Ph)
Full load current of
water pumpFLA(A)
Full load current of chiller unit
FLA(A)
Rated current of the fan RLA(A)
Minimum current of the
water unit circuitMCA(A)
Recommended fuse
specifi cation REC(A)
Maximum specifi cation of the fuse
FMS(A)
Minimum specifi cation of the power
supply copper core wire
diameter (mm2)
0305R 380-415/50/3 1.1 8.6 1 12.85 15 21.45 4
0306R 220/50/1 2.4 25.6 1 35.4 41.8 61 10
0505R 380-415/50/3 1.1 9.6 1 14.1 16.5 23.7 4
0605R 380-415/50/3 1.1 13 1 18.35 21.6 31.85 6
0755R 380-415/50/3 1.4 14 1.5 20.4 23.9 34.4 6
0606R 220/50/1 2.4 51.2 4.8 63.5 71.2 85.6 16
1005R 380-415/50/3 1.4 16.4 1.6 23.5 27.6 39.9 6
1205R 380-415/50/3 3.26 22.4 3.2 34.46 40.06 58.5 10
1505R 380-415/50/3 2.6 24.6 8.4 41.75 47.9 61.15 10
2005R 380-415/50/3 3.2 26.6 8.4 44.85 51.5 68.7 16
• The difference between the power voltage and the standard voltage shall not exceed 10 percent of the
standard value.
• Rated current(RLA)=the current of the machine under the ARI or UL standard conditions
• Minimum circuit current(MCA)=maximum loadx1.25+sum of the extra load (to decide the diameter of
the wire)
• Recommended fuse specifi cation(REC)=maximum loadx1.5+sum of the extra load (to select the fuse
closest in specifi cation)
• Maximum fuse specification(MFS)=maximum loadx2.25+sum of the extra load (to select the fuse
same or smaller in specifi cation)
Electrical specifi cations -50Hz
LCD microprocessor-based controller
1. System function
• Cooling/heating switch
• Compressor and pump protection
• Two-way valve interlock
• Refrigerant high pressure protection
for the plate heat exchanger
• EWT display/setting
• Timing on/off time
2. The factory provides standard length of 10 meters for the LCD controller.
• Refrigerant system high/low pressure protection
• Anti-freeze protection of water system and plate
heat exchanger in winter
• Malfunction alarm
• System operating statuse
• Defrosting interval/operation time setting
Electrical Specifi cations
14
Water Pressure Drop Curve
CGAR0305
0
5
10
15
20
25
30
35
1.07 1.25 1.43 1.61 1.79 1.97 2.15 2.33 2.51
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
CGAR0306
0
5
10
15
20
25
30
35
1.146 1.337 1.528 1.719 1.91 2.101 2.292 2.483 2.674
CGAR0505
0
5
10
15
20
25
30
1.344 1.568 1.792 2.016 2.24 2.464 2.688 2.912 3.136
CGAR0605
0
5
10
15
20
25
30
1.68 1.96 2.24 2.52 2.8 3.08 3.36 3.64
CGAR0606
0
5
10
15
20
25
30
2.292 2.674 3.056 3.438 3.82 4.202 4.584 4.966 5.348
CGAR0755
0
5
10
15
20
25
30
2.31 2.70 3.08 3.47 3.85 4.24 4.62 5.01 5.39
CGAR1005
0
5
10
15
20
25
30
2.74 3.19 3.65 4.10 4.56 5.02 5.47 5.93
CGAR1205
0
5
10
15
20
25
30
35
4.03 4.70 5.37 6.04 6.71 7.38 8.05
Water Flow:m3/h Water Flow:m3/h
Water Flow:m3/h Water Flow:m3/h
Water Flow:m3/hWater Flow:m3/h
Water Flow:m3/h Water Flow:m3/h
15
Wat
er P
ress
ure
Dro
p (
mH
2O)
Wat
er P
ress
ure
Dro
p (
mH
2O)
CGAR1505
0
5
10
15
20
25
30
35
4.76 5.56 6.35 7.15 7.94 8.73 9.53
Water Flow:m3/h
CGAR2005
5
10
15
20
25
30
35
40
45
50
55
5.47 6.38 7.29 8.20 9.11 10.02 10.93 11.84
Water Flow:m3/h
Pump Head Internal Pressure Drop Allowable External Pressure Drop
Type Lower limit of fl ow Rated fl ow Upper limit of fl ow Connection Dimension
CGAR0305 1.16 1.79 2.33 1"
CGAR0306 1.24 1.91 2.48 1"
CGAR0505 1.45 2.24 2.90 1"
CGAR0605 1.93 2.96 3.85 1"
CGAR0755 4.08 4.08 5.30 1 1/4"
CGAR0606 2.50 3.82 4.96 1 1/4"
CGAR1005 3.17 4.85 0.91 1 1/4"
CGAR1205 4.33 6.62 8.60 1 1/4"
CGAR1505 5.53 8.45 10.99 1 1/4"
CGAR2005 6.19 9.46 12.31 1 1/2"
Water pressure drop
To measure the water pressure difference between the water inlet and outlet of the unit (including
pump), pump head at a particular water flow rate may be read off from the pump head curve.
Refer to curves to design piping system for standard models with pumps.
The inner water pressure drop of the unit without a pump (the pump is installed outside of the
unit) should basically follow the graphs shown in the Water pressure drop curve section. Refer to
curves to design piping system for models without pumps.
Water fl owThe chilled water fl ow through the unit shall be rated between the upper and lower limit listed
in the table. If the chilled water fl ow is below the lower limit, the discontinuous water fl ow will
reduce the evaporator heat transfer and make the expansion valve out of control or exceptional
low-pressure shutdown. Contrarily, the inner parts of the evaporator will be eroded if the water
fl ow is higher than the upper limit.
Water fl ow rateunit: m3/h
Water Pressure Drop Curve
© 2011 Trane All rights reserved
PKGP-PRC006-EN March 2014
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy effi cient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifi cations without notice.