product catalog - trane hk-home 032014.pdf · march 2014 pkgp-prc006-en product catalog koolman...

16
March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A, 50Hz

Upload: doanduong

Post on 23-Nov-2018

269 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

March 2014 PKGP-PRC006-EN

Product Catalog

Koolman Air-Cooled Chiller and Heat PumpCGAK cooling only /CGAR heat pumpModel:030~200R410A, 50Hz

Page 2: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

2

Contents

Features and Benefi t 3

Mechanical Specifi cations 4

Model Nomenclature 5

Performance Data 6

Dimensions 8

Service and Maintenance Space Requirement 12

Electrical Specifi cations 13

Water Pressure Drop Curve 14

Page 3: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

3

Features and Benefi ts

IntroductionUsing the leading high-effi ciency ermetic scroll compressor and evaporator technology, Koolman provides you a stable, reliable and highly effi cient operation. Matched with a large variety of fan coils of different sizes it can be widely used in top grade apartments, luxury villas, offi ce buildings, small-sized restaurants, retail stores and hotels to create a comfortable and delightful indoor environment.

State-of-the-art appearanceKoolman boasts of its state-of-the-art appearance. The contemporary appearance, designed by expert designers, will be naturally integrated with the surrounding environment and will defi nitely display your prominent taste.

Small footprintAs a result of the particular slim design (standard type is 500mm thick while mini type is only 393mm thick), the unit can be installed directly on the veranda, rooftop or ground without the need to have aplant room.

Available optionsUnit with pressurized water tank is available to meet various requirements.

Noise levelKoolman uses low noise fans and components to achieve its low noise evel.

Easy installationEach chiller has factory charged oil and refrigerant for reducing fi eld labor and materials costs. All units are factory run tested. Only power supply and water piping are required to be connected on the jobsite.

Environmentally friendly refrigerantAll models are charged with R410A refrigerant.

Free of Cooling TowerHeat dissipation in the way of air cycle eliminates the need for cooling water tower. Thus, not only does it save the cost and space for cooling tower it also eliminates water shortage concerns.

Page 4: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

4

Mechanical Specifi cations

GeneralKoolman air-cooled liquid chiller is designed to couple with fan coil units and air handling units for residential and light commercial air conditioning applications. Units are composed of scroll compressor (s), plate type evaporator, fi nned-coppertube and aluminum condenser, axial fan assembly, expansion valve, four-way reversal valve (heat pump only), indoor Cooling/Heating control switch, water fl ow switch, fi lter dryer, sight-glass, built-in water pump, galvanized sheet metal housing with powder paint and factory mounted controls. Optional fi ttings include pressurized water tank system.

CompressorDepending on capacity range, units come with single or double scroll compressors to cater for changing demand and effi cient part load operations.

EvaporatorEvaporator is a compact brazed plate heat exchanger with AISI 316 stainless plates and adapters. A 20-mesh strainer is installed at the water inlet to protect the evaporator and unit against fouling. The strainer (factory provided, fi eld installed) can be removed for cleaning.

HousingAll parts are fabricated to precision by state-of-the-art CNC machines. The frame design allows all panels to be removed for service without affecting the structure of the unit. The panels are made of galvanized steel plate with powder paint. All panels are internally insulated with single layer foam cell in order to reduce noise and vibration.

Water pumpPump is Rotodynamic pumps and adopts a mechanical shaft seal. Motor is fan cooled (TEFC), 2-pole induction type. Pump is installed in the unit to save installation space and also to reduce noise level.

Controls and protection devicesThe controller contains all the basic electrical protection devices including electromagnetic switches, relays and current overload protectors. The automatic control devices consist of high and low pressure switches, thermostatic and anti-freeze cutouts, which improve and protect the unit's normal operation.In addition, the preset low temperature protection command can start the machine automatically to protect the water pipes from freezing.

LCD microprocessor-based controllerPrecise temperature control of inlet chilled water, operation modes and system protection are provided by the long-range controller. In addition, the password can be set and any abnormal condition will be monitored and captured to facilitate quick repair and normal operation. In addition, the interlocking function of the two-way valve is available.

Air-cooled condenserThe unit comes with air-cooled fi n-tube U or V shaped condensers. Copper tubes are of the 3/8" diameter, seamless type. Fins are aluminum with effi cient Wavy fi n. Copper tubes are expanded mechanically to bond with the fi ns for effective heat transfer. Light-weight axial fl ow fan(s) is (are) driven by high effi ciency, low speed, low noise motor(s) to ensure quiet and reliable operations.

Operating limitsCooling mode Heating mode

mini 21℃ -7℃

max 43℃ 21℃

Leaving water temperature

Cooling mode Heating mode

mini 5℃ 40℃

max 15℃ 50℃

Page 5: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

5

Digit 1,2,3 CGA = Air-Cooled Chiller and Heat Pump

Digit 4 Model

K = Cooling Only

R = Heat Pump

Digit 5,6,7 Model

030 100

050 120

060 150

075 200

Digit 8 Power Supply

5 = 380V/50Hz/3ph (For Model 030,050,060,075,100,120,150,200)

6 = 220V/50Hz/1ph (For 030 with single compressor and 060 with double compressors)

Digit 9 Manufacturing Code (defaulted by factory)

R = R410A

Digit 10 Controller

B=Microprocessor-based adjustable water temperature controller

Digit 11 Water Side Electric Heater

N=None

Digit 12 Service Sequence

A=The fi rst time

Digit 13 Water Pump for Unit

R=With Pump inside (standard)

N=Without Pump

Digit 14 Applicable Ambient Temperature

R = Standard ambinent temperature/Blue-fi n

Digit 15 Fitting Options

N = None (Standard Unit)

Digit 16 Other option

B = Export

N15

A16

R14

R13

A12

N11

B10

R9

58

07

56

05

R4

A3

G2

C1

Model Nomenclatures

Page 6: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

6

Mmodel CGAR/K0305R CGAR/K0306R CGAR/K0505R CGAR/K0605R CGAR/K0606R

Cooling Capacity Kal/Hr 9040.5 9557.1 11193 14809.2 19114.2

kW 10.5 11.1 13 17.2 22.2

Heating Capacity Kal/Hr 9901.5 10418.1 12570.6 15584.1 21352.8

kW 11.5 12.1 14.6 18.1 24.8

Power Supply V 380-415V/50Hz/3 220-240V/50Hz/1 380-415V/50Hz/3 380-415V/50Hz/3 220-240V/50Hz/1

Compressor

Number 1 1 1 1 2

Rated Current(C/H) A 6.01/6.39 18.78/20.4 7.97/8.35 10.02/9.93 20/20.95

Locked Rotor Current A 60 130 82 100 130

Power Input(C/H) KW 3.32/3.43 3.58/3.78 4.16/4.26 5.65/5.2 3.63/3.65

Fan

Type Hermetic Scroll compressor

Number 2 1

Rated Current A 0.5 4.8

Power Input kW 0.1 0.6

Water Pump

Number 1

Rated Current A 1.45 3.65 1.45 1.45 3.65

Power Input kW 0.74

Discharge Head m 25.05 24.65 23.55 17.89 22.05

EvaporatorType Plate type heat exchanger

Water Flow (C/H) m3/h 1.79/1.91 1.91/2.02 2.24/2.45 2.96/3.11 3.82/4.14

Protective Device Overheat protection, High and Low Pressure Protection

LubricantType 320HV 320HV 320HV 320HV 320HV

Charge L 1.57 1.57 1.57 1.57 1.57+1.57

RefrigerantType R410a

Charge kg 2.8 2.7 3.3 3.7 2.8+2.8

Unit Dimensions mm 950*393*1285 1290*500*1900

Water Connection (FPT) inch 1“ 1“ 1“ 1“ 1-1/4"

Direction of Connection Right Right Right Right Right or Left

Operation Weight Kg 130 131 141 149 320

Note:1.Cooling Mode Conditions (Evap. 12℃/7℃ - Air. 35℃).2.Heating Mode Condition (Evap. 40℃/45℃ - Air. DB/WB 7℃/6℃).3.The unit is tested under GB18430.1-2007and GB18430.2-2008.

Performance Data

Page 7: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

7

Note:1.Cooling Mode Conditions (Evap. 12℃/7℃ - Air. 35℃).2.Heating Mode Condition (Evap. 40℃/45℃ - Air. DB/WB 7℃/6℃).3.The unit is tested under GB18430.1-2007and GB18430.2-2008..

Performance Data

Mmodel CGAR/K0755R CGAR/K1005R CGAR/K1205R CGAR/K1505R CGAR/K2005R

Cooling Capacity Kal/Hr 20405.7 24280.2 33148.5 42275.1 47355

kW 23.7 28.2 38.5 49.1 55

Heating Capacity Kal/Hr 21266.7 25571.7 34870.5 46063.5 51487.8

kW 24.7 29.7 40.5 53.5 59.8

Power Supply V 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3 380-415V/50HZ/3

Compressor

Number 1 2 2 2 2

Rated Current(C/H) A 13.77/13.43 8.2/8.3 11.2/11.1 14.9/15.2 17/17.1

Locked Rotor Current A 110 82 100 110 140

Power Input(C/H) KW 7.85/7.1 4.43/4.25 5.85/5.7 6.95/7.2 8.48/8.15

Fan

Type Hermetic Scroll compressor

Number 3 1 2 2 2

Rated Current A 0.5 1.6 1.6 4.2 4.2

Power Input kW 0.1 0.6 0.6 1.5 1.5

Water Pump

Number 1

Rated Current A 1.45 1.45 3.26 2.4 3.8

Power Input kW 0.74 0.74 1.44 1.41 1.92

Discharge Head m 18.99 16.07 18.05 16.28 26.18

EvaporatorType Plate type heat exchanger

Water Flow (C/H) m3/h 4.08/4.25 4.85/5.11 6.62/6.96 8.45/9.2 9.46/10.28

Protective Device Overheat protection, High and Low Pressure Protection

LubricantType 320HV 320HV 320HV 320HV 320HV

Charge L 1.57 1.57+1.57 1.57+1.57 2.66+2.66 2.66+2.66

RefrigerantType R410a

Charge kg 4.4 3.0+3.0 3.8+3.8 4.0+4.0 4.5+4.0

Unit Dimensions mm 950*393*1590 1290*500*1900 1990*500*1900

Water Connection (FPT) inch Inlet1-1/4" outlet1" 1-1/4" 1-1/4" 1-1/4" 1-1/2"

Direction of Connection Right Right or Left Right or Left Front Front

Operation Weight Kg 202 449 530 540 540

Page 8: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

8

Dimensions

Mini casingCGAK/R-0305R/0306R/0505R/0605R (Unit: mm)

CGAK/R-0705 R (Unit: mm)

Ø1"Water outlet

Ø1"Water inlet

90

740

950670

1285

402

393

Mini-Koolman

186

647

90

402

393

1590

670

950

824

Mini-Koolman

732

186

1 1/4Water outlet

1 1/4Water inlet

Page 9: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

9

Dimensions

Standard casingCGAK/R-0606R/1005R (Unit: mm)

500

50

1290

FPT 1 1/4"B Water inletPower cable inletØ40

Water outlet

500

1900

900

1000

580

Drain waterFPT 1/2" B

99

75

FPT 1 1/4"B

120

155

TM

50

FPT 1-1/4"B

75

FPT 1/2" B

500

1990 580

1000

900

1900

500Drain water Water outlet

Power cable inletØ40Water inletFPT 1-1/4"B

TM TM

120

155

99

CGAR/K-1205R(Unit:mm)

Page 10: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

10

Dimensions

CGAR/K-2005R (Unit: mm)

50

FPT 1-1/2"B

FPT 1/2" B

490.0000

1990

580

1000

900

1900

500.0000

Water outlet

Drain waterØ40

Water inletFPT 1-1/2"B

TM TM

125

120

90 985

500

1990

CGAR/K-1505R (Unit: mm)

50

FPT 1-1/4"B

FPT 1/2" B

500

1990 580

1000

900

1900

500

Water outlet

Drain waterØ40

Water inletFPT 1-1/4"B

TM TM

125

120

90 985

Page 11: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

11

Pressure water tank (Option Unit:mm)

Dimensions

Installation Example

P

P

Makeup water valve

Drain Valve

Shut-off Electric heater

Fan coil X4

Tapwater

Water drainage

Direct return Reversed

return

Shockproof hose

Thermometer

Automaticair vent

Primary Unit pressurisedwater tank

water strainer

flowswitch

Description of the principle of the pressurized water tank:1. In order to avoid the pipe cracking due to the system over pressure resulting from the change of

ambient temperature and also to avoid the water hammer in the pipes, a pressurized water tank shall be installed for system.

2. In order to avoid the excessively high or low pressure in the pipe, an automatic feed water valve and an automatic drain valve are included in the pressurized water tank. The feed water pressure can be adjusted based on the fi eld situation.

3. An open expansion tank shall be installed at the highest position of system.

Note: the automatic exhaust valve shall be set at the highest point of the piping

SizeModel

A B C D E F G H

WTANK-5 470 263 230 182 254 435 415 455

WTANK-12 620 400 324 162 356 569 440 475

Water Inlet(φ12.7mm)Water Outlet(φ12.7mm)

Water Drainage(φ12.7mm)

H

G

FAB

DC E

Page 12: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

12

Unit: mm

Service and Maintenance Space Requirement

300

500

1500

300

500

Mini-Koolman

4030

1630

450 730

1630

850

496

640 740

4030

640

740

450

496

2330

640

150

640

640

950

402 393

Installation dimensions

CGAR(K)0606R/1005R

Air Direction

CGAR(K)0305R/0306R/0505R/0605R/0755R

CGAR(K)1205R/1505R/2005R

Page 13: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

13

MODELPower supply

(V/Hz/Ph)

Full load current of

water pumpFLA(A)

Full load current of chiller unit

FLA(A)

Rated current of the fan RLA(A)

Minimum current of the

water unit circuitMCA(A)

Recommended fuse

specifi cation REC(A)

Maximum specifi cation of the fuse

FMS(A)

Minimum specifi cation of the power

supply copper core wire

diameter (mm2)

0305R 380-415/50/3 1.1 8.6 1 12.85 15 21.45 4

0306R 220/50/1 2.4 25.6 1 35.4 41.8 61 10

0505R 380-415/50/3 1.1 9.6 1 14.1 16.5 23.7 4

0605R 380-415/50/3 1.1 13 1 18.35 21.6 31.85 6

0755R 380-415/50/3 1.4 14 1.5 20.4 23.9 34.4 6

0606R 220/50/1 2.4 51.2 4.8 63.5 71.2 85.6 16

1005R 380-415/50/3 1.4 16.4 1.6 23.5 27.6 39.9 6

1205R 380-415/50/3 3.26 22.4 3.2 34.46 40.06 58.5 10

1505R 380-415/50/3 2.6 24.6 8.4 41.75 47.9 61.15 10

2005R 380-415/50/3 3.2 26.6 8.4 44.85 51.5 68.7 16

• The difference between the power voltage and the standard voltage shall not exceed 10 percent of the

standard value.

• Rated current(RLA)=the current of the machine under the ARI or UL standard conditions

• Minimum circuit current(MCA)=maximum loadx1.25+sum of the extra load (to decide the diameter of

the wire)

• Recommended fuse specifi cation(REC)=maximum loadx1.5+sum of the extra load (to select the fuse

closest in specifi cation)

• Maximum fuse specification(MFS)=maximum loadx2.25+sum of the extra load (to select the fuse

same or smaller in specifi cation)

Electrical specifi cations -50Hz

LCD microprocessor-based controller

1. System function

• Cooling/heating switch

• Compressor and pump protection

• Two-way valve interlock

• Refrigerant high pressure protection

for the plate heat exchanger

• EWT display/setting

• Timing on/off time

2. The factory provides standard length of 10 meters for the LCD controller.

• Refrigerant system high/low pressure protection

• Anti-freeze protection of water system and plate

heat exchanger in winter

• Malfunction alarm

• System operating statuse

• Defrosting interval/operation time setting

Electrical Specifi cations

Page 14: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

14

Water Pressure Drop Curve

CGAR0305

0

5

10

15

20

25

30

35

1.07 1.25 1.43 1.61 1.79 1.97 2.15 2.33 2.51

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

CGAR0306

0

5

10

15

20

25

30

35

1.146 1.337 1.528 1.719 1.91 2.101 2.292 2.483 2.674

CGAR0505

0

5

10

15

20

25

30

1.344 1.568 1.792 2.016 2.24 2.464 2.688 2.912 3.136

CGAR0605

0

5

10

15

20

25

30

1.68 1.96 2.24 2.52 2.8 3.08 3.36 3.64

CGAR0606

0

5

10

15

20

25

30

2.292 2.674 3.056 3.438 3.82 4.202 4.584 4.966 5.348

CGAR0755

0

5

10

15

20

25

30

2.31 2.70 3.08 3.47 3.85 4.24 4.62 5.01 5.39

CGAR1005

0

5

10

15

20

25

30

2.74 3.19 3.65 4.10 4.56 5.02 5.47 5.93

CGAR1205

0

5

10

15

20

25

30

35

4.03 4.70 5.37 6.04 6.71 7.38 8.05

Water Flow:m3/h Water Flow:m3/h

Water Flow:m3/h Water Flow:m3/h

Water Flow:m3/hWater Flow:m3/h

Water Flow:m3/h Water Flow:m3/h

Page 15: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

15

Wat

er P

ress

ure

Dro

p (

mH

2O)

Wat

er P

ress

ure

Dro

p (

mH

2O)

CGAR1505

0

5

10

15

20

25

30

35

4.76 5.56 6.35 7.15 7.94 8.73 9.53

Water Flow:m3/h

CGAR2005

5

10

15

20

25

30

35

40

45

50

55

5.47 6.38 7.29 8.20 9.11 10.02 10.93 11.84

Water Flow:m3/h

Pump Head Internal Pressure Drop Allowable External Pressure Drop

Type Lower limit of fl ow Rated fl ow Upper limit of fl ow Connection Dimension

CGAR0305 1.16 1.79 2.33 1"

CGAR0306 1.24 1.91 2.48 1"

CGAR0505 1.45 2.24 2.90 1"

CGAR0605 1.93 2.96 3.85 1"

CGAR0755 4.08 4.08 5.30 1 1/4"

CGAR0606 2.50 3.82 4.96 1 1/4"

CGAR1005 3.17 4.85 0.91 1 1/4"

CGAR1205 4.33 6.62 8.60 1 1/4"

CGAR1505 5.53 8.45 10.99 1 1/4"

CGAR2005 6.19 9.46 12.31 1 1/2"

Water pressure drop

To measure the water pressure difference between the water inlet and outlet of the unit (including

pump), pump head at a particular water flow rate may be read off from the pump head curve.

Refer to curves to design piping system for standard models with pumps.

The inner water pressure drop of the unit without a pump (the pump is installed outside of the

unit) should basically follow the graphs shown in the Water pressure drop curve section. Refer to

curves to design piping system for models without pumps.

Water fl owThe chilled water fl ow through the unit shall be rated between the upper and lower limit listed

in the table. If the chilled water fl ow is below the lower limit, the discontinuous water fl ow will

reduce the evaporator heat transfer and make the expansion valve out of control or exceptional

low-pressure shutdown. Contrarily, the inner parts of the evaporator will be eroded if the water

fl ow is higher than the upper limit.

Water fl ow rateunit: m3/h

Water Pressure Drop Curve

Page 16: Product Catalog - Trane HK-Home 032014.pdf · March 2014 PKGP-PRC006-EN Product Catalog Koolman Air-Cooled Chiller and Heat Pump CGAK cooling only /CGAR heat pump Model:030~200 R410A,

© 2011 Trane All rights reserved

PKGP-PRC006-EN March 2014

Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy effi cient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.Trane.com.

Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifi cations without notice.