HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a conventional CRAC unit www.airedale.com In Row IT Cooling InRak 10 – 63kW BRITISH MANUFACTURER ENERGY EFFICIENCY CONTROLS SERVICE TRAINING AIR COOLED DX AIR HFC R410A HFC R410A CHILLED WATER CW EC FAN EC EC EC INVERTER COMPRESSOR

Upload: others

Post on 04-Oct-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

HIGH PERFORMANCE IN-ROW COOLER:

+ EER up to 108.03

+ 17 – 100% variable capacity control

+ Up to 83% more cooling/m2* * Compared with a conventional CRAC unit

www.airedale.com

In RowIT Cooling

InRak™

10 – 63kW

BRITISHMANUFACTURER

ENERGY EFFICIENCY

CONTROLS SERVICE TRAINING

AIR COOLED

DX AIR

HFC R410A

HFCR410A

CHILLED WATER

CWEC FAN

ECEC

EC INVERTER COMPRESSOR

Page 2: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

more cooling per square metre

Up to83%

Targeting IT coolingVia the shortest, direct route

01

The InRak™ is a high performance in-row

cooling solution which precisely cools

and conditions air in close proximity to

the servers and provides industry-leading

cooling for its footprint.

Advanced air flow management within the InRak™ innovatively transmits cooled air horizontally across the front of the server racks. This acts as a curtain, providing even cooling over the full height of the server rack whilst managing the aisle static pressure. Single circuit models of the InRak™ are available in DX or chilled water (CW) units and dual circuit in CW.

Flexible, scalable application

The compact, modular InRak™ is an ideal solution for:

EC fans

Up to 70% more

efficient*

EC electronically commutated centrifugal fans give increased performance for reduced power input; the fan assembly can be replaced while the unit is still running.

Efficient ‘A’ frame coil design

Maximum heat

exchange areaThe A-Frame heat exchanger can give a large increase in heat exchanger face area facilitating larger cooling capacities and more efficient cooling.

EC inverter scroll compressor

17 – 100% variable

capacity controlEC 20 – 120rps compressor quietly and exactly matches cooling demand, reacting to load fluctuations and saving substantial energy at part load.

Electronic expansion valve

EER increased by

up to 30%*

An EEV allows for perfect refrigeration control whilst operating at part load and lower ambient conditions with a reduced condensing pressure.

Typically offered by the InRak™ compared with a

conventional CRAC unit

Page 3: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

Up to 70% less energy used

0 20 40 60 80 100

20

0

40

60

80

100

EC Fan

EC fan: Up to 70% more efficient than an AC fan at part load

AC Fan

Fan speed %

Inpu

t pow

er %

02

EER up to108.0

Optional n+1 fan configuration enhanced by smart control logic and EC fan technology, gives the InRak™ built-in redundancy and excellent part load efficiencies. During part load operation, the unit’s Energy Efficiency Ratio (EER) increases from 72.5 to 108.0, significantly contributing to reduced operating costs and carbon emissions.

0.1

0.2

0.3

0.4

0.5

0.7

0.8

0.9

1.0

0.6

01020

30

40

50

70

80

90100110

60

0

InRak™: Excellent part load efficiencyN (47.1kW of cooling), N+1 (38.9kW of cooling)

N N+1EERCooling Capacity

Fan configuration

Powe

r Inp

ut (k

W)

EER

EER108.0

EER72.50

47kW 39kW

Up to 70% energy savings*

The InRak™ has been engineered withvery low air flow resistance; its four centrifugal fans utilise the latest EC fan technology which responds seamlessly to load fluctuations and delivers greatly enhanced fan efficiency particularly at part load* compared with an AC fan at part load.

EC FAN

EC

Time

Tem

pera

ture

Supply air temperature is closer to setpoint. Zone temperature is kept tightly near setpoint at all times by continuous load-matching operation.

Zone temperature Setpoint

With variable speed

Time

Tem

pera

ture

Supply air temperature will be colder than needed due to excess capacity.Zone setpoint is maintained by on-off cycling.

Zone temperature Setpoint

Without variable speed

Exact capacity match with

17 – 100% variable coolingEC latest technology 20 – 120rps compressor offering 17 – 100% modulation

The InRak™ features two scroll compressors in one circuit comprising an EC latest technology 20 – 120rps inverter compressor and the opportunity to add a fixed speed compressor for larger capacities. The quietly operating EC inverter driven scroll compressor offers substantial energy savings at part load and with a starting current equivalent to just 10% that of a traditional fixed speed scroll compressor.

EC FAN

ECEC

EC INVERTER COMPRESSOR

Page 4: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

The InRak™ can be positioned next to a single rack; within a row of six 10kW server cabinets for example or sit between two 30kW racks in a higher density area.

The InRak™ can be integrated into a traditional hot or cold aisle system, but when applied with aisle containment, the performance of the InRak™ is significantly enhanced. In hot aisle containment, the fans draw in hot air rejected by the servers. Due to the minimum distance that the hot air has to travel, the risk of cold air mixing with rejected hot air is greatly decreased. This in turn reduces the need for low supply air temperatures, enabling the data centre to operate at higher temperature, which improves efficiency.

Even more efficient In aisle containment

03

y heth

s,

Example hot aisle containment: Each pod

includes two InRak™ units; the CW InRak™ units

control the supply temperate of air into the servers at

22°C ±2°C; hot aisle temperature is 36°C

20.0

24.3

28.5

32.8

37.0

Temperature (C)

The InRak™ fans

draw in through the

rear of the unit, hot

air rejected by the

servers

Page 5: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

04

With a free-cooling chillerFree-cooling for up to 95% p.a.

Integration with a free-cooling chiller

Chilled water models of the InRak™ deliver even greater efficiency when integrated with one or more Airedale free-cooling chillers. Free-cooling saves vast amounts of energy, particularly when room temperatures are high. For free-cooling to operate, the temperature difference between the ambient air and return water can be as little as 1°C.

Concurrent free-cooling

Airedale chillers offer concurrent free-cooling which enables free-cooling to be captured whenever the ambient is below the return water temperature. The system controls constantly monitor the temperature differences and will only switch on the mechanically-driven compressor when extra cooling is needed, introducing concurrent free-cooling - a mixture of free-cooling and mechanical cooling.

A higher water supply temperature of up to 17°C raises the free-cooling threshold of all Airedalefree-cooling chillers including the more compact variants. When an Airedale free-cooling chiller is linked with the InRak™ in a 24/7 data centre with a typical room temperature of 24°C, free-cooling will be active for more than 95% of the year (London, UK).

50%

One kilowatt of power saved every hour 24/7, represents a saving of £876* a year, equivalent to over 4 tonnes of CO

2* £0.10/kWh

0

700

400

300

200

100

500

-5 0 20 25 305 10 1530% Free-cooling only

Up to 95% of the year spent in free-cooling

65% Concurrent free-cooling5% Mechanical cooling

Ambient temperature (°C)

Cum

ulat

ive

hour

s Lo

ndon

(UK)

Up to95%

65%

Concurrent free-cooling maximises total free-cooling

FREE-COOLING

FREE

COOL

Using heat

to increase

free-cooling

energysavings

when the InRak™ is integrated with

a concurrent free-cooling chiller*

*compared with a conventional chiller

Page 6: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

05

The control centre of each of our cooling systems is a sophisticated electronic microprocessor with control logic specially developed by Airedale.

The microprocessor uses sensors to send and receive messages to and from active components such as compressors, fans and pumps so they interact with each other, balancing cooling duty, temperature, air flow and pressure to exactly match the application.

By integrating intelligent components, the controller manages and optimises the system’s performance and reduces power draw.

Smart networking solutions:

Fully-programmable via the control panel’s user-friendly display, the microprocessor can be linked with all standard BMS protocols to:

Intelligent controlsSeamlessly managing your system

Trigger alarm

messages

Operate time

scheduling

Send alarm/service

messages via email or

SMS using an interface

Allow adjustment of

temperature setpoints

Integration protocols

24/7 total confidence

Resilience is designed into InRak™ units from day one and is managed by advanced controls logic to give you complete confidence that your data centre is never put at risk and to help you achieve data centre tier classification.

N+1 fans

The InRak’s four fans run up to 75% capacity during normal operation. If one fan fails, the other three fans instantly speed up to 100% if required, to provide the same total amount of cooling and maintain temperature control. They then modulate back when a fourth fan is in operation again. All fans are ‘hot swappable’ as standard.

Pressure differential management

The InRak™ maintains pressure in the aisle containment system within the server design envelope, whilst still ensuring temperature is controlled.

Automatic transfer switch

In the event of a power failure, power supply is switched instantly to an alternative power supply and cooling continues, supporting redundancy power supply specifications in critical data centre builds.

Hot swappable fan management

Each of the unit’s centrifugal fans are ‘hot swappable’ allowing the fan assembly to be replaced while the unit is still running.

Future-proof, flexible, 24/7

As an intelligent stand-alone unit or when networked with up to eight units, the InRak™ adapts to your data centre’s particular requirement. Its compact, modular design makes it easy for multiple units of different size and capacity to be added as load increases or to eliminate hot spots. Smartly networked standby units ensure 24/7 availability.

Latest touch

screen technology:

Available as an option and

allowing the display to be

viewed in full colour and

in graphical format

CONTROLS

Page 7: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

06

ACIS™ building management system developed by Airedale, enables you to manage smart cooling and other building services, from any manufacturer, in a single, integrated system across multiple sites and communication protocols. ACIS™ sits at the front end of a building system, putting you in control of reducing operating costs.

With the click of a button on a PC, tablet or phone, valuable and intelligent information can be pulled back automatically for remote 24/7 monitoring and maintenance, enhanced system operation and improved decisions.

Data centre managementTaken to another level

Sequencer

Building lighting

Generator/UPS/Server

Energy Manager

ACIS

Integrated cooling solutions

As you grow your data centre

Designed to be stand-alone, Airedale units are even more efficient when integrated together, sharing intelligence and reducing your total lifecycle costs. Our systems give you the confidence to move from low to medium to high density cooling as you populate and grow your data centre – from small rooms with DX indoor units linked with condensers outside to larger rooms benefitting from the better heat transfer of chilled water coupled with a free-cooling chiller.

Page 8: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

07

InRak™ DX – cooling by compressor

InRak™ DX is part of a closed refrigerant circuit controlled by scroll compressor technology. The InRak™ fans draw hot return air across an evaporator, heat is transferred into the refrigerant and dispelled via an external air cooled condenser.

InRak™ CW - chilled water cooling

In a closed chilled water circuit, fans in the InRak™ CW pull hot return air across the heat exchanger, transferring heat to the cooling water, fed to a chiller located externally which removes the heat and returns chilled water back to the InRak.

Mechanical ResilienceEnergy saving Electrical &

Controls

Specifications at a glance

DX air cooled

InRak DX InRak CW

Chilled water

CHILLED WATER

CWAIR COOLED

DX AIR

Page 9: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

08

Unit (-) Nominal cooling 1,

2 (kW)

Nominal power

input 2 (kW)

EER

(-)

Part load EER 3

(-)

Dimensions

(H x W x D mm)

Mass (kg)

Single Circuit Direct Expansion

Single Circuit Chilled Water

Dual Circuit Chilled Water

X1 X2 C0 CC

Depth1344mm

Height1994mm

Width600mm

InRak™ standard case size

InRak™ technical specifications:

50 Hz and 60 Hz power supplies available as follows:

Unit height in U

Nominal cooling capacity in kW

Nomenclature explained --

42U

10 - 60

400V/3 + N 50Hz0

380V/3+N 60Hz1

Chilled water cooling, single circuitChilled water cooling, double circuitDX cooling, single circuit - tandem internal compressors (50Hz only)DX cooling, single circuit - single internal compressor

C0CCX2X1

LogiCoolInRak

LIR

Case width in centimetres60

C060 40LIR 42U 0 1

Page 10: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

A factor influencing selection of Airedale was its transparency and facility to witness test. We prefer working with a UK manufacturer who is carrying out product development work and can give us support and reassurance

throughout.

Steve Vandyke Head of Technical Services National Gallery

09

Performance tested

InRak™ in action: EMIS data centre

Quality is assured by our on-site, world-class testing and production facilities and the application of the latest manufacturing techniques and continuous improvement.

The challenge

Egton Medical Information Systems Ltd (EMIS) is the UK’s leading supplier of healthcare software and related services to GP practices and is estimated to hold the data for around 39 million patient records. EMIS required a new 24/7 data centre as expansion to the existing facility in order to increase its secure and resilient capacity. The data centre incorporates a highly efficient, reliable cooling and monitoring solution designed by Airedale.

Airedale solution

The InRak™ units make the aisle containment far more efficient; they are very clever; they communicate with each other to maintain pressure and temperature consistent with the room. Their EC fans are great – they are all linked to the ACIS™ and ramp up and down according to demand. ACIS™ gives us 24/7 control of the operation and peace of mind. When the data centre is fully populated, the Airedale cooling solution should guarantee an annualised PUE of 1.3 for the room.

Mike Marchant, Data Centre Manager, EMIS

* CEEDA: Certified Energy Efficiency Data Centre Award

We are aiming for a Gold CEEDA* and PUE of 1.3

Via a touch screen interface,

the operator can monitor

room temperature and

pressure; the fresh air unit

and the UPS battery life, run

time and load

Page 11: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

10

Total support Whenever you need it

Learn more about your cooling

system by attending an air

conditioning and refrigeration

course in our purpose-built training

school. Train on high-tech cooling

systems and fully operational rigs in

our dedicated workshops. Industry

recognised courses also available.

Email [email protected] for

further details.

Find out how we design our

systems to reduce your whole life

costs. Our highly experienced

engineers are adept at tailoring our

systems to suit your requirements.

+44 (0)113 239 1000

Immediate help on hand to keep

your critical cooling system

operational. Realise the full

potential of your system; improve

its longevity and efficiency and be

F Gas compliant. Avoid downtime

with our fast, efficient spares

service.

Customers with critical sites can

benefit from our remote monitoring

facility. Aftersales services include

chiller sequencing, network setup

and integration as well as a live

demonstration and training centre

at our head office.

At Airedale, we don’t just manufacture

and supply cooling and refrigeration

products; we also provide a broad range

of supporting services to ensure our

customers receive the best possible

aftersales care.

With more than 40 years’ experience in

business critical cooling, investing in an

Airedale cooling or refrigeration solution

means that you can benefit from our

advice, expertise and technical support

too. From design and selection, through

to commissioning and beyond, we make

sure your system reduces your total cost

of ownership, whilst providing maximum

availability and longevity.

24/7 support; maintenance and spares

Develop your skills

Have complete control of your site

Talk directly with an experienced engineer

Service plans Maximising your system’s effectiveness 24/7

An Airedale service plan provides a planned, preventative

maintenance package to sustain the optimum efficiency

of your system, enabling the user to see real savings in

energy costs and reduced carbon emissions.

With Airedale, you can rest assured that help is never far

away. Our 24/7 emergency helpline and call out service

is available 365 days of the year, ensuring that we are

always on hand to provide expert advice and immediate

help, day or night.

A guaranteed emergency response time means that a

qualified Airedale engineer will be with you in no time,

therefore maximising your system’s uptime. Service

plans also ensure F Gas compliance and incorporate a

full parts and labour warranty for the first 12 months.

For more information visit www.airedale.com

Page 12: [product] InRak v16 interactive€¦ · HIGH PERFORMANCE IN-ROW COOLER: + EER up to 108.03 + 17 – 100% variable capacity control + Up to 83% more cooling/m 2* * Compared with a

Distributed by:

Airedale International Air Conditioning Limited | Leeds Road, Rawdon, Leeds LS19 6JY, EnglandTel: +44 (0) 113 239 1000 Fax: +44 (0) 113 250 7219 E-Mail: [email protected]

All specifications are subject to change without prior notice | ENG-IT-INRAK-06-14

ISO 14001EMS52086

ISO 9001FM00542

www.airedale.com