    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    DESIGN CALCULATIONS

    BEAM FORCES

    BEAM 102

    Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 68.60kNm @ 10.6m

    -40.0

    -60.0

    -80.0

    m)

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    2/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    002PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Envelope for Load Cases:

    Y-Shear Envelope Shear Force max = 108.0kN @ 7.86m

    -80.0

    -60.0

    -40.0

    -20.0

    20.0

    40.0

    60.0

    80.0

    100

    .500

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    12

    .0

    12

    .5

    Shear

    Force

    (kN)

    Distance (m) Shear Force min = -84.3kN @ 12.7m

    94 86 80 75 69

    D, L, LC1, LC2,

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    3/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    003PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    BEAM 104Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 86.42kNm @ 5.98m

    80.0

    60.0

    40.0

    20.0

    -20.0

    -40.0

    -60.0

    -80.0

    -100

    -120

    .500

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    Ben

    ding

    Momen

    t(kNm

    )

    Distance (m) Bending Moment min = -130kNm @ 3.50m

    117 113 100 93

    Envelope for Load Cases:D, L, LC1, LC2,

    Y-Shear Envelope Shear Force max = 170.2kN @ 3.50m

    -100

    -50.0

    50.0

    100

    150

    .500

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    Shear

    Force

    (kN)

    Distance (m) Shear Force min = -134kN @ 8.73m

    117 113 100 93

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    4/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    004PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    BEAM 105Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 86.50kNm @ 10.5m

    80.0

    60.0

    40.0

    20.0

    -20.0

    -40.0

    -60.0

    -80.0

    -100

    .5

    00

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    12

    .0

    12

    .5

    Ben

    ding

    Momen

    t(kNm

    )

    Distance (m) Bending Moment min = -103kNm @ 5.20m

    92 79 74 68

    Envelope for Load Cases:D, L, LC1, LC2,

    Y-Shear Envelope Shear Force max = 133.9kN @ 7.87m

    -120

    -100

    -80.0

    -60.0

    -40.0

    -20.0

    20.0

    40.0

    60.0

    80.0

    100

    120

    140

    .500

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    12

    .0

    12

    .5

    Shear

    Force

    (kN

    )

    Distance (m) Shear Force min = -128kN @ 5.20m

    92 79 74 68

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    5/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    005PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    BEAM 107Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 62.90kNm @ 7.92m

    60.0

    40.0

    20.0

    -20.0

    -40.0

    -60.0

    -80.0

    -100

    .200

    .400

    .600

    .800

    1.0

    0

    1.2

    0

    1.4

    0

    1.6

    0

    1.8

    0

    2.0

    0

    2.2

    0

    2.4

    0

    2.6

    0

    2.8

    0

    3.0

    0

    3.2

    0

    3.4

    0

    3.6

    0

    3.8

    0

    4.0

    0

    4.2

    0

    4.4

    0

    4.6

    0

    4.8

    0

    5.0

    0

    5.2

    0

    5.4

    0

    5.6

    0

    5.8

    0

    6.0

    0

    6.2

    0

    6.4

    0

    6.6

    0

    6.8

    0

    7.0

    0

    7.2

    0

    7.4

    0

    7.6

    0

    7.8

    0

    8.0

    0

    8.2

    0

    8.4

    0

    8.6

    0

    8.8

    0

    9.0

    0

    9.2

    0

    9.4

    0

    9.6

    0

    9.8

    0

    Ben

    ding

    Momen

    t(kNm

    )

    Distance (m) Bending Moment min = -97.7kNm @ 5.33m

    91 78 73

    Envelope for Load Cases:D, L, LC1, LC2,

    Y-Shear Envelope Shear Force max = 124.1kN @ 5.33m

    -80.0

    -60.0

    -40.0

    -20.0

    20.0

    40.0

    60.0

    80.0

    100

    120

    .200

    .400

    .600

    .800

    1.0

    0

    1.2

    0

    1.4

    0

    1.6

    0

    1.8

    0

    2.0

    0

    2.2

    0

    2.4

    0

    2.6

    0

    2.8

    0

    3.0

    0

    3.2

    0

    3.4

    0

    3.6

    0

    3.8

    0

    4.0

    0

    4.2

    0

    4.4

    0

    4.6

    0

    4.8

    0

    5.0

    0

    5.2

    0

    5.4

    0

    5.6

    0

    5.8

    0

    6.0

    0

    6.2

    0

    6.4

    0

    6.6

    0

    6.8

    0

    7.0

    0

    7.2

    0

    7.4

    0

    7.6

    0

    7.8

    0

    8.0

    0

    8.2

    0

    8.4

    0

    8.6

    0

    8.8

    0

    9.0

    0

    9.2

    0

    9.4

    0

    9.6

    0

    9.8

    0

    Shear

    Force

    (kN

    )

    Distance (m) Shear Force min = -96.1kN @ 9.92m

    91 78 73

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    6/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    006PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    BEAM 109Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 90.33kNm @ 7.28m

    80.0

    60.0

    40.0

    20.0

    -20.0

    -40.0

    -60.0

    -80.0

    -100

    -120

    -140

    .500

    1.0

    0

    1.5

    0

    2.0

    0

    2.5

    0

    3.0

    0

    3.5

    0

    4.0

    0

    4.5

    0

    5.0

    0

    5.5

    0

    6.0

    0

    6.5

    0

    7.0

    0

    7.5

    0

    8.0

    0

    8.5

    0

    9.0

    0

    9.5

    0

    10

    .0

    10

    .5

    11

    .0

    11

    .5

    12

    .0

    12

    .5

    13

    .0

    Ben

    ding

    Momen

    t(kNm

    )

    Distance (m) Bending Moment min = -137kNm @ 4.81m

    120 112 99 90

    Envelope for Load Cases:

    Y-Shear Envelope Shear Force max = 180.8kN @ 4.81m

    -100

    -50.0

    50.0

    100

    150

    .500 1.00 1.50 2.00 2.50 3.00 3.50 4.00 4.50 5.00 5.50 6.00 6.50 7.00 7.50 8.00 8.50 9.00 9.50 10.0 10.5 11.0 11.5 12.0 12.5 13.0

    ShearF

    orce

    (kN)

    Distance (m) Shear Force min = -139kN @ 9.96m

    120 112 99 90

    D, L, LC1, LC2,

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    7/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    007PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    BEAM 111Envelope for Load Cases:D, L, LC1, LC2,

    X-Moment Envelope Bending Moment max = 87.82kNm @ 2.34m

    80.0

    60.0

    40.0

    20.0

    -20.0

    -40.0

    -60.0

    -80.0

    -100

    -120

    .200

    .400

    .600

    .800

    1.0

    0

    1.2

    0

    1.4

    0

    1.6

    0

    1.8

    0

    2.0

    0

    2.2

    0

    2.4

    0

    2.6

    0

    2.8

    0

    3.0

    0

    3.2

    0

    3.4

    0

    3.6

    0

    3.8

    0

    4.0

    0

    4.2

    0

    4.4

    0

    4.6

    0

    4.8

    0

    5.0

    0

    5.2

    0

    5.4

    0

    5.6

    0

    5.8

    0

    6.0

    0

    6.2

    0

    6.4

    0

    6.6

    0

    6.8

    0

    7.0

    0

    7.2

    0

    7.4

    0

    7.6

    0

    7.8

    0

    8.0

    0

    8.2

    0

    8.4

    0

    8.6

    0

    8.8

    0

    9.0

    0

    9.2

    0

    9.4

    0

    9.6

    0

    9.8

    0

    Ben

    ding

    Momen

    t(kNm

    )

    Distance (m) Bending Moment min = -126kNm @ 5.20m

    89 77 70

    Envelope for Load Cases:D, L, LC1, LC2,

    Y-Shear Envelope Shear Force max = 120.6kN @ 0.00m

    -140

    -120

    -100

    -80.0

    -60.0

    -40.0

    -20.0

    20.0

    40.0

    60.0

    80.0

    100

    120

    .200

    .400

    .600

    .800

    1.0

    0

    1.2

    0

    1.4

    0

    1.6

    0

    1.8

    0

    2.0

    0

    2.2

    0

    2.4

    0

    2.6

    0

    2.8

    0

    3.0

    0

    3.2

    0

    3.4

    0

    3.6

    0

    3.8

    0

    4.0

    0

    4.2

    0

    4.4

    0

    4.6

    0

    4.8

    0

    5.0

    0

    5.2

    0

    5.4

    0

    5.6

    0

    5.8

    0

    6.0

    0

    6.2

    0

    6.4

    0

    6.6

    0

    6.8

    0

    7.0

    0

    7.2

    0

    7.4

    0

    7.6

    0

    7.8

    0

    8.0

    0

    8.2

    0

    8.4

    0

    8.6

    0

    8.8

    0

    9.0

    0

    9.2

    0

    9.4

    0

    9.6

    0

    9.8

    0

    Shear

    Force

    (kN

    )

    Distance (m) Shear Force min = -149kN @ 5.20m

    89 77 70

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    8/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    008PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    C11COLUMN C1

    0 100

    200

    200

    100

    0

    X X

    Y

    Y

    Rectangular column design by PROKON. (RecCol Ver W2.5.13 - 19 Apr 2012)

    Design code : BS8110 - 1997

    General design parameters:Given: h = 230 mm b = 230 mm d'x = 23 mm d'y = 23 mm Lo = 3.400 m fcu = 25 MPa fy = 410 MPa

    Column design chart (X-X)

    Momen

    tmax=

    121

    .1kNm

    @2

    91kN

    -1000

    -800

    -600

    -400

    -200

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    10

    .0

    20

    .0

    30

    .0

    40

    .0

    50

    .0

    60

    .0

    70

    .0

    80

    .0

    90

    .0

    100

    110

    120

    130

    Ax

    ialloa

    d(kN)

    Bending moment (kNm)

    6%5%4%3%2%1%0%

    Design chart for bending about the X-X axis:

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    9/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    009PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Column design chart (Y-Y)

    Momen

    tmax=

    121

    .1kNm

    @2

    91kN

    -1000

    -800

    -600

    -400

    -200

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    10

    .0

    20

    .0

    30

    .0

    40

    .0

    50

    .0

    60

    .0

    70

    .0

    80

    .0

    90

    .0

    100

    110

    120

    130

    Ax

    ialloa

    d(kN)

    Bending moment (kNm)

    6%5%4%3%2%1%0%

    Design chart for bending about the Y-Y axis:

    Therefore:

    =Ac b h.

    = .23 .2301

    = 0.0529 m

    =h' h d' x-

    = . 2301 .023-

    = 0.2071 m

    =b' b d' y-

    = .23 .023-

    = 0.2070 m

    Assumptions: (1) The general conditions of clause 3.8.1 are applicable. (2) The section is symmetrically reinforced. (3) The specified design axial loads include the self-weight of the column. (4) The design axial loads are taken constant over the height of the column.

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    10/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    010PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Design approach:The column is designed using the following procedure: (1) The column design charts are constructed. (2) The design axis and design ultimate moment is determined . (3) The steel required for the design axial force and moment is read from the

    relevant design chart. (4) The area steel perpendicular to the design axis is read from the relevant design chart. (5) The procedure is repeated for each load case. (6) The critical load case is identified as the case yielding the largest steel area about the design axis.

    Through inspection: Load case 1 is critical.

    Check column slenderness:End fixity and bracing for bending about the X-X axis: At the top end: Condition 1 (fully fixed).

    At the bottom end: Condition 1 (fully fixed). The column is braced.x = 0.75 Table 3.21

    End fixity and bracing for bending about the Y-Y axis: At the top end: Condition 1 (fully fixed). At the bottom end: Condition 1 (fully fixed). The column is braced.y = 0.75 Table 3.21

    Effective column height:

    =lex x Lo.

    = .75 3.4= 2.550 m

    =ley y Lo.

    = .75 3.4

    = 2.550 m

    Column slenderness about both axes:

    =xlex

    h

    =2.55

    .2301

    = 11.082

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    11/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    011PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    =yley

    b

    =2.55

    .23

    = 11.087

    Minimum Moments for Design:Check for mininum eccentricity: 3.8.2.4 For bi-axial bending, it is only necessary to ensure that the eccentricity exceeds the minimum about one axis at a time.

    For the worst effect, apply the minimum eccentricity about the minor axis:

    =eminx 0.05 h.

    = 0.05 .2301

    = 0.0115 m

    =eminy 0.05 b.

    = 0.05 .23

    = 0.0115 m

    =Mmin emin N.

    = .0115 734.09

    = 8.442 kNm

    Check if the column is slender: 3.8.1.3

    x = 11.1 < 15

    y = 11.1 < 15

    The column is short.

    Initial moments:The column is bent in single curvature about the X-X axis: M1 = Smaller initial end moment = 0.2 kNm M2 = Larger initial end moment = 2.3 kNm

    The initial moment near mid-height of the column : 3.8.3.2

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    12/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    012PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    =Mi 0.4 M1 0.6 M2. .- +

    = 0.4 -.17 0.6 2.3 - +

    = 1.448 kNm

    =Mi2 0.4 M2.

    = 0.4 2.3

    = 0.9200 kNm

    Mi 0.4M2 = 2.3 kNm

    The column is bent in single curvature about the Y-Y axis: M1 = Smaller initial end moment = 0.3 kNm M2 = Larger initial end moment = 3.3 kNm

    The initial moment near mid-height of the column : 3.8.3.2

    =Mi 0.4 M1 0.6 M2. .- +

    = 0.4 -.28 0.6 3.33 - +

    = 2.110 kNm

    =Mi2 0.4 M2.

    = 0.4 3.33

    = 1.332 kNm

    Mi 0.4M2 = 3.3 kNm

    Design ultimate load and moment:Design axial load: Pu= 734.1 kN

    Design of column section for ULS:Through inspection: The critical section lies at the top end of the column.

    The column is bi-axially bent. The moments are added vectoriallyto obtain the design moment: Mx/h = 40.8 < My/b = 40.8

    The effective uniaxial design moment about the Y-Y axis:

    = 1

    7

    6N

    b h fcu. .

    .

    -

    = 1

    7

    6734090

    .23 .2301 2500104

    -

    = 0.3527

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    13/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    013PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    =M'y My b dcy

    h dcxMx

    -( )

    -

    ..+

    = 8442 .35269 .23 .023.2301 .023

    8 445.7-( )-

    +

    = 11.41103

    kNm

    For bending about the design axis:

    Column design chart (Y-Y)

    Momen

    tmax=

    121

    .1kNm

    @2

    91kN

    -1000

    -800

    -600

    -400

    -200

    200

    400

    600

    800

    1000

    12001400

    1600

    10

    .0

    20

    .0

    30

    .0

    40

    .0

    50

    .0

    60

    .0

    70

    .0

    80

    .0

    90

    .0

    100

    110

    120

    130

    Ax

    ialloa

    d(kN)

    Bending moment (kNm)

    6%5%4%3%2%1%0%

    Minimum reinforcement required for bending about the Y-Y axis only: From the design chart, Asc = 662 mm = 1.25%

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    14/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    014PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    For bending about the design axis - use the Y-axis:

    Column design chart (Y-Y)

    Momen

    tmax=

    121

    .1kNm

    @2

    91

    kN

    -1000

    -800

    -600

    -400

    -200

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    10

    .0

    20

    .0

    30

    .0

    40

    .0

    50

    .0

    60

    .0

    70

    .0

    80

    .0

    90

    .0

    100

    110

    120

    130

    Ax

    ialloa

    d(kN)

    Bending moment (kNm)

    6%5%4%3%2%1%0%

    Summary of design calculations:

    Design results for all load cases:

    Load case Axis N (kN) M1 (kNm) M2 (kNm) Mi (kNm) Madd (kNm) Design M (kNm) M' (kNm) Asc (mm)

    LC1_35-291

    LC2_35-291

    X-XY-Y 734.1

    -0.2-0.3

    2.33.3

    2.33.3

    0.00.0

    Y-YTop

    8.48.4 11.4

    662 (1.25%)745 (1.41%)

    X-XY-Y 619.9

    -0.1-0.2

    1.92.8

    1.92.8

    0.00.0

    Y-YTop

    7.17.1 10.4

    290 (0.55%)381 (0.72%)

    Load case 1 is critical.

    A A

    AA

    4T16-A17R8-(

    B)-200

    Double set of links

    3R8-C Tie links3400

    0

    R8-B

    R8-C

    SECTION

    Cover on links = 30 mm

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    15/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    015PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    16/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    016PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Column Base Design : FOOTING F1C15

    Input Data

    Base length A (m)

    Base width B (m)

    Column(s)

    C (m)

    D (m)

    E (m)

    F (m)

    Stub column height X (m)

    Base depth Y (m)

    Soil cover Z (m)

    Concrete density (kN/m3)

    Soil density (kN/m3)

    Soil friction angle ()

    Base friction constantRebar depth top X (mm)

    Rebar depth top Y (mm)

    Rebar depth bottom X (mm)

    Rebar depth bottom Y (mm)

    ULS ovt. LF: Self weight

    ULS LF: Self weight

    Max. SLS bearing pr. (kN/m)

    S.F. Overturning (ULS)

    S.F. Slip (ULS)

    fcu base (MPa)

    fcu columns (MPa)

    fy (MPa)

    1.60

    1.90

    Col 1 Col 2

    0.230

    0.230

    1.5

    0.3

    0.3

    24.0

    18

    27

    0.550

    50

    75

    75

    1

    1.4

    200

    1

    1

    25

    25

    410

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    17/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    017PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Load Data

    Unfactored Loads

    LoadCase

    Colno.

    LFULSovt

    LFULS

    P(kN)

    Hx(kN)

    Hy(kN)

    Mx(kNm)

    My(kNm)

    D_291 1 1 1 461.92 -0.89 -1.29 -1.45 -2.10

    L_291 1 1 1 54.63 -0.11 -0.15 -0.17 -0.24

    LC1_291 1 1 1.40 461.92 -0.89 -1.29 -1.45 -2.10

    1 1 1.60 54.63 -0.11 -0.15 -0.17 -0.24

    LC2_291 1 1 1.20 461.92 -0.89 -1.29 -1.45 -2.10

    1 1 1.20 54.63 -0.11 -0.15 -0.17 -0.24

    A

    X

    Y

    Y

    B

    C1

    D1

    P

    Mx

    Z

    Hx

    Y

    X

    Sketch of Base

    Output for Load Case D_291

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    18/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    018PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_291

    Soil pressure (ULS) (kN/m) 178.69

    Soil pressure (SLS) (kN/m) 173.44

    SF overturning (SLS) 83.39

    SF overturning (ULS) 83.39Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 36.44

    Reinforcement X (mm/m) 478

    Design moment Y (kNm/m) 54.36

    Reinforcement Y (mm/m) 714

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.309vc (MPa) 0.410

    Linear Shear Y (MPa) 0.421

    vc (MPa) 0.468

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.404

    vc (MPa) 0.467

    Cost 119.65

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    173.44 kN/m

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    178.69 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_291

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    19/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    019PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_291

    Output for Load Case L_291

    Soil pressure (ULS) (kN/m) 37.34

    Soil pressure (SLS) (kN/m) 32.09

    SF overturning (SLS) >100SF overturning (ULS) >100

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 4.47

    Reinforcement X (mm/m) 59

    Design moment Y (kNm/m) 6.66

    Reinforcement Y (mm/m) 87

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.038

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.052

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.050

    vc (MPa) 0.388

    Cost 94.68

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    32.09 kN/m

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    37.34 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_291

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    20/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    020PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_291

    Output for Load Case LC1_291

    Soil pressure (ULS) (kN/m) 273.14

    Soil pressure (SLS) (kN/m) 192.39

    SF overturning (SLS) 82.74SF overturning (ULS) 82.74

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 57.81

    Reinforcement X (mm/m) 762

    Design moment Y (kNm/m) 86.24

    Reinforcement Y (mm/m) 1173

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.491

    vc (MPa) 0.478

    Linear Shear Y (MPa) 0.668

    vc (MPa) 0.552

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.642

    vc (MPa) 0.548

    Cost 137.38

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    192.39 kN/m

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    273.14 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_291

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    21/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    021PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_291

    Output for Load Case LC2_291

    Soil pressure (ULS) (kN/m) 233.49

    Soil pressure (SLS) (kN/m) 192.39

    SF overturning (SLS) 82.74SF overturning (ULS) 82.74

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 48.84

    Reinforcement X (mm/m) 641

    Design moment Y (kNm/m) 72.86

    Reinforcement Y (mm/m) 976

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.415

    vc (MPa) 0.452

    Linear Shear Y (MPa) 0.564

    vc (MPa) 0.520

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.542

    vc (MPa) 0.516

    Cost 129.79

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    192.39 kN/m

    1.60

    X

    Y

    Y

    1.9

    00.23

    0.23

    P

    Mx

    0.3

    0

    Hx

    0.30

    1.50

    233.49 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_291

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    22/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    022PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Schematic reinforcement of Base

    8T16-A-250 (B1)

    A

    7T20-B-250 (B2)

    col1

    PLAN

    SECTION

    B B B B B B B

    3R8-SA

    R8-SA

    4T16-E

    E

    E

    E

    E

    SECTION: col1

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    23/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    023PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Column Base Design : FOOTING F2C15

    Input Data

    Base length A (m)

    Base width B (m)

    Column(s)

    C (m)

    D (m)

    E (m)

    F (m)

    Stub column height X (m)

    Base depth Y (m)

    Soil cover Z (m)

    Concrete density (kN/m3)

    Soil density (kN/m3)

    Soil friction angle ()

    Base friction constantRebar depth top X (mm)

    Rebar depth top Y (mm)

    Rebar depth bottom X (mm)

    Rebar depth bottom Y (mm)

    ULS ovt. LF: Self weight

    ULS LF: Self weight

    Max. SLS bearing pr. (kN/m)

    S.F. Overturning (ULS)

    S.F. Slip (ULS)

    fcu base (MPa)

    fcu columns (MPa)

    fy (MPa)

    1.5

    1.5

    Col 1 Col 2

    0.230

    0.230

    1.6

    0.3

    1.5

    25

    18

    27

    0.550

    50

    75

    75

    1

    1.4

    200

    1

    1

    25

    30

    410

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    24/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    024PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Load Data

    Unfactored Loads

    LoadCase

    Colno.

    LFULSovt

    LFULS

    P(kN)

    Hx(kN)

    Hy(kN)

    Mx(kNm)

    My(kNm)

    D_294 1 1 1 296.23 -0.43 0.29 -0.69 0.51

    L_294 1 1 1 27.29 -0.11 0.06 -0.17 0.11

    LC1_294 1 1 1.40 296.23 -0.43 0.29 -0.69 0.51

    1 1 1.60 27.29 -0.11 0.06 -0.17 0.11

    LC2_294 1 1 1.20 296.23 -0.43 0.29 -0.69 0.51

    1 1 1.20 27.29 -0.11 0.06 -0.17 0.11

    A

    X

    Y

    Y

    B

    C1

    D1

    P

    Mx

    Z

    Hx

    Y

    X

    Sketch of Base

    Output for Load Case D_294

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    25/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    025PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_294

    Soil pressure (ULS) (kN/m) 184.95

    Soil pressure (SLS) (kN/m) 171.03

    SF overturning (SLS) >100

    SF overturning (ULS) >100Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 27.02

    Reinforcement X (mm/m) 355

    Design moment Y (kNm/m) 26.90

    Reinforcement Y (mm/m) 353

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.250vc (MPa) 0.388

    Linear Shear Y (MPa) 0.249

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.225

    vc (MPa) 0.394

    Cost 80.00

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    171.03 kN/m

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    184.95 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_294

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    26/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    026PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_294

    Output for Load Case L_294

    Soil pressure (ULS) (kN/m) 61.93

    Soil pressure (SLS) (kN/m) 48.01

    SF overturning (SLS) >100SF overturning (ULS) >100

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 2.63

    Reinforcement X (mm/m) 34

    Design moment Y (kNm/m) 2.59

    Reinforcement Y (mm/m) 34

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.024

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.024

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.021

    vc (MPa) 0.388

    Cost 68.71

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    48.01 kN/m

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    61.93 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_294

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    27/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    027PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_294

    Output for Load Case LC1_294

    Soil pressure (ULS) (kN/m) 260.56

    Soil pressure (SLS) (kN/m) 184.23

    SF overturning (SLS) >100SF overturning (ULS) >100

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 41.86

    Reinforcement X (mm/m) 549

    Design moment Y (kNm/m) 41.63

    Reinforcement Y (mm/m) 546

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.388

    vc (MPa) 0.429

    Linear Shear Y (MPa) 0.385

    vc (MPa) 0.428

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.347

    vc (MPa) 0.456

    Cost 86.85

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    184.23 kN/m

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    260.56 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_294

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    28/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    028PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_294

    Output for Load Case LC2_294

    Soil pressure (ULS) (kN/m) 228.04

    Soil pressure (SLS) (kN/m) 184.23

    SF overturning (SLS) >100SF overturning (ULS) >100

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 35.45

    Reinforcement X (mm/m) 465

    Design moment Y (kNm/m) 35.27

    Reinforcement Y (mm/m) 463

    Top

    Design moment X (kNm/m) 0.00

    Reinforcement X (mm/m) 0

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.328

    vc (MPa) 0.406

    Linear Shear Y (MPa) 0.327

    vc (MPa) 0.405

    Linear Shear Other (MPa) 0.000

    Punching Shear (MPa) 0.294

    vc (MPa) 0.431

    Cost 83.89

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    184.23 kN/m

    1.50

    X

    Y

    Y

    1.5

    00.23

    0.23

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    228.04 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_294

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    29/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    029PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Schematic reinforcement of Base

    5T16-A-350 (B1)

    A

    5T16-B-350 (B2)

    col1

    PLAN

    SECTION

    B B B B B

    3R8-SA

    R8-SA

    4T16-E

    E

    E

    E

    E

    SECTION: col1

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    30/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    030PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Column Base Design : COMBINED FOOTING F3C15

    Input Data

    Base length A (m)

    Base width B (m)

    Column(s)

    C (m)

    D (m)

    E (m)

    F (m)

    Stub column height X (m)

    Base depth Y (m)

    Soil cover Z (m)

    Concrete density (kN/m3)

    Soil density (kN/m3)

    Soil friction angle ()

    Base friction constantRebar depth top X (mm)

    Rebar depth top Y (mm)

    Rebar depth bottom X (mm)

    Rebar depth bottom Y (mm)

    ULS ovt. LF: Self weight

    ULS LF: Self weight

    Max. SLS bearing pr. (kN/m)

    S.F. Overturning (ULS)

    S.F. Slip (ULS)

    fcu base (MPa)

    fcu columns (MPa)

    fy (MPa)

    2.5

    1.5

    Col 1 Col 2

    0.230 0.230

    0.230 0.230

    0.715 -0.715

    0.3

    0.30

    0.3

    25

    18

    27

    0.550

    50

    75

    75

    1

    1.4

    200

    1

    1

    25

    25

    410

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    31/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    031PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Load Data

    Unfactored Loads

    LoadCase

    Colno.

    LFULSovt

    LFULS

    P(kN)

    Hx(kN)

    Hy(kN)

    Mx(kNm)

    My(kNm)

    D_292 1 1 1 389.90 0.99 -1.07 1.64 -1.75

    L_292 1 1 1 42.82 0.13 -0.12 0.22 -0.20

    LC1_292 1 1 1.40 389.90 0.99 -1.07 1.64 -1.75

    1 1 1.60 42.82 0.13 -0.12 0.22 -0.20

    LC2_292 1 1 1.20 389.90 0.99 -1.07 1.64 -1.75

    1 1 1.20 42.82 0.13 -0.12 0.22 -0.20

    D_293 2 1 1 212.44 0.22 -0.36 0.38 -0.57

    L_293 2 1 1 13.13 0.07 -0.04 0.12 -0.06

    LC1_293 2 1 1.4 212.44 0.22 -0.36 0.38 -0.57 2 1 1.6 13.13 0.07 -0.04 0.12 -0.06

    LC2_293 2 1 1.2 212.44 0.22 -0.36 0.38 -0.57

    2 1 1.2 13.13 0.07 -0.04 0.12 -0.06

    A

    X

    Y

    Y

    B

    E1

    C1

    D1

    E2

    C2

    D2

    P

    Mx

    P

    Mx

    Z

    Hx

    Y

    X

    Sketch of Base

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    32/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    032PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_292

    Output for Load Case D_292

    Soil pressure (ULS) (kN/m) 323.27

    Soil pressure (SLS) (kN/m) 323.40

    SF overturning (SLS) 1.95SF overturning (ULS) 1.95

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 34.08

    Reinforcement X (mm/m) 447

    Design moment Y (kNm/m) 21.36

    Reinforcement Y (mm/m) 280

    Top

    Design moment X (kNm/m) -7.35

    Reinforcement X (mm/m) 87

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.254

    vc (MPa) 0.401

    Linear Shear Y (MPa) 0.197

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.249

    Punching Shear (MPa) 0.136

    vc (MPa) 0.426

    Cost 133.92

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    323.40 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    323.27 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_292

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    33/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    033PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_292

    Output for Load Case L_292

    Soil pressure (ULS) (kN/m) 49.63

    Soil pressure (SLS) (kN/m) 44.45

    SF overturning (SLS) 3.70SF overturning (ULS) 3.70

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 3.64

    Reinforcement X (mm/m) 48

    Design moment Y (kNm/m) 2.38

    Reinforcement Y (mm/m) 31

    Top

    Design moment X (kNm/m) -1.51

    Reinforcement X (mm/m) 18

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.026

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.022

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.031

    Punching Shear (MPa) 0.015

    vc (MPa) 0.388

    Cost 114.82

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    44.45 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    49.63 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_292

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    34/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    034PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_292

    Output for Load Case LC1_292

    Soil pressure (ULS) (kN/m) 510.14

    Soil pressure (SLS) (kN/m) 359.26

    SF overturning (SLS) 1.93SF overturning (ULS) 1.93

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 54.90

    Reinforcement X (mm/m) 722

    Design moment Y (kNm/m) 33.62

    Reinforcement Y (mm/m) 441

    Top

    Design moment X (kNm/m) -8.00

    Reinforcement X (mm/m) 94

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.408

    vc (MPa) 0.470

    Linear Shear Y (MPa) 0.310

    vc (MPa) 0.399

    Linear Shear Other (MPa) 0.378

    Punching Shear (MPa) 0.214

    vc (MPa) 0.500

    Cost 146.73

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    359.26 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    510.14 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_292

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    35/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    035PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_292

    Output for Load Case LC2_292

    Soil pressure (ULS) (kN/m) 430.67

    Soil pressure (SLS) (kN/m) 359.26

    SF overturning (SLS) 1.93SF overturning (ULS) 1.93

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 46.04

    Reinforcement X (mm/m) 604

    Design moment Y (kNm/m) 28.42

    Reinforcement Y (mm/m) 373

    Top

    Design moment X (kNm/m) -7.80

    Reinforcement X (mm/m) 92

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.342

    vc (MPa) 0.443

    Linear Shear Y (MPa) 0.262

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.324

    Punching Shear (MPa) 0.181

    vc (MPa) 0.471

    Cost 141.26

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    359.26 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    430.67 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_292

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    36/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    036PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_293

    Output for Load Case D_293

    Soil pressure (ULS) (kN/m) 176.63

    Soil pressure (SLS) (kN/m) 174.27

    SF overturning (SLS) 2.16SF overturning (ULS) 2.16

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 18.89

    Reinforcement X (mm/m) 248

    Design moment Y (kNm/m) 11.58

    Reinforcement Y (mm/m) 152

    Top

    Design moment X (kNm/m) -5.68

    Reinforcement X (mm/m) 67

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.133

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.107

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.148

    Punching Shear (MPa) 0.075

    vc (MPa) 0.388

    Cost 124.27

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    174.27 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    176.63 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_293

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    37/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    037PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_293

    Output for Load Case L_293

    Soil pressure (ULS) (kN/m) 27.64

    Soil pressure (SLS) (kN/m) 22.45

    SF overturning (SLS) 8.36SF overturning (ULS) 8.36

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 1.37

    Reinforcement X (mm/m) 18

    Design moment Y (kNm/m) 0.75

    Reinforcement Y (mm/m) 10

    Top

    Design moment X (kNm/m) -0.37

    Reinforcement X (mm/m) 4

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.008

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.007

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.010

    Punching Shear (MPa) 0.005

    vc (MPa) 0.388

    Cost 113.32

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    22.45 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    27.64 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_293

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    38/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    038PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_293

    Output for Load Case LC1_293

    Soil pressure (ULS) (kN/m) 260.68

    Soil pressure (SLS) (kN/m) 184.70

    SF overturning (SLS) 2.13SF overturning (ULS) 2.13

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 29.01

    Reinforcement X (mm/m) 381

    Design moment Y (kNm/m) 17.34

    Reinforcement Y (mm/m) 228

    Top

    Design moment X (kNm/m) -6.59

    Reinforcement X (mm/m) 78

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.203

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.160

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.214

    Punching Shear (MPa) 0.112

    vc (MPa) 0.404

    Cost 130.40

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    184.70 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    260.68 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_293

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    39/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    039PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_293

    Output for Load Case LC2_293

    Soil pressure (ULS) (kN/m) 222.55

    Soil pressure (SLS) (kN/m) 184.70

    SF overturning (SLS) 2.13SF overturning (ULS) 2.13

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 24.45

    Reinforcement X (mm/m) 321

    Design moment Y (kNm/m) 14.75

    Reinforcement Y (mm/m) 193

    Top

    Design moment X (kNm/m) -6.25

    Reinforcement X (mm/m) 74

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.171

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.136

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.185

    Punching Shear (MPa) 0.095

    vc (MPa) 0.388

    Cost 127.64

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    184.70 kN/m

    2.50

    X

    Y

    Y

    1.5

    0

    0.71

    0.23

    0.23

    -0.71

    0.23

    0.23

    P

    Mx

    P

    Mx

    0.3

    0Hx

    0.30

    0.30

    222.55 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_293

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    40/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    040PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Column Base Design : COMBINED FOOTING F4C15

    Input Data

    Base length A (m)

    Base width B (m)

    Column(s)

    C (m)

    D (m)

    E (m)

    F (m)

    Stub column height X (m)

    Base depth Y (m)

    Soil cover Z (m)

    Concrete density (kN/m3)

    Soil density (kN/m3)

    Soil friction angle ()

    Base friction constantRebar depth top X (mm)

    Rebar depth top Y (mm)

    Rebar depth bottom X (mm)

    Rebar depth bottom Y (mm)

    ULS ovt. LF: Self weight

    ULS LF: Self weight

    Max. SLS bearing pr. (kN/m)

    S.F. Overturning (ULS)

    S.F. Slip (ULS)

    fcu base (MPa)

    fcu columns (MPa)

    fy (MPa)

    3.4

    1.6

    Col 1 Col 2

    0.23 0.23

    0.23 0.23

    -1.085 1.285

    1.6

    0.30

    1.5

    25

    18

    27

    0.550

    50

    75

    75

    1

    1.4

    200

    1

    1

    25

    30

    450

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    41/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    041PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Load Data

    Unfactored Loads

    LoadCase

    Colno.

    LFULSovt

    LFULS

    P(kN)

    Hx(kN)

    Hy(kN)

    Mx(kNm)

    My(kNm)

    D_319 1 1 1 222.20 -0.20 0.21 -0.34 0.35

    L_319 1 1 1 17.94 0.02 0.09 0.03 0.15

    LC1_319 1 1 1.40 222.20 -0.20 0.21 -0.34 0.35

    1 1 1.60 17.94 0.02 0.09 0.03 0.15

    LC2_319 1 1 1 222.20 -0.20 0.21 -0.34 0.35

    1 1 1 17.94 0.02 0.09 0.03 0.15

    D_315 2 1 1 180.07 0.00 -0.07 -0.01 -0.10

    L_315 2 1 1 25.43 0.00 -0.02 0.00 -0.03

    LC1_315 2 1 1.40 180.07 0.00 -0.07 -0.01 -0.10

    2 1 1.60 25.43 0.00 -0.02 0.00 -0.03LC2_315 2 1 1 180.07 0.00 -0.07 -0.01 -0.10

    2 1 1 25.43 0.00 -0.02 0.00 -0.03

    A

    X

    Y

    Y

    B

    E1

    C1

    D1

    E2

    C2

    D2

    P

    Mx

    P

    Mx

    Z

    Hx

    Y

    X

    Sketch of Base

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    42/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    042PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_319

    Output for Load Case D_319

    Soil pressure (ULS) (kN/m) 168.38

    Soil pressure (SLS) (kN/m) 154.76

    SF overturning (SLS) 2.89SF overturning (ULS) 2.89

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 18.46

    Reinforcement X (mm/m) 221

    Design moment Y (kNm/m) 9.81

    Reinforcement Y (mm/m) 117

    Top

    Design moment X (kNm/m) -16.20

    Reinforcement X (mm/m) 174

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.137

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.083

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.204

    Punching Shear (MPa) 0.065

    vc (MPa) 0.388

    Cost 177.64

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    154.76 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    168.38 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_319

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    43/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    043PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_319

    Output for Load Case L_319

    Soil pressure (ULS) (kN/m) 58.40

    Soil pressure (SLS) (kN/m) 44.52

    SF overturning (SLS) 18.26SF overturning (ULS) 18.26

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 2.88

    Reinforcement X (mm/m) 34

    Design moment Y (kNm/m) 0.96

    Reinforcement Y (mm/m) 11

    Top

    Design moment X (kNm/m) -0.86

    Reinforcement X (mm/m) 9

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.011

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.008

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.019

    Punching Shear (MPa) 0.006

    vc (MPa) 0.388

    Cost 165.16

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    44.52 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    58.40 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_319

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    44/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    044PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_319

    Output for Load Case LC1_319

    Soil pressure (ULS) (kN/m) 232.75

    Soil pressure (SLS) (kN/m) 164.80

    SF overturning (SLS) 2.79SF overturning (ULS) 2.79

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 26.95

    Reinforcement X (mm/m) 322

    Design moment Y (kNm/m) 14.98

    Reinforcement Y (mm/m) 179

    Top

    Design moment X (kNm/m) -24.87

    Reinforcement X (mm/m) 268

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.210

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.127

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.311

    Punching Shear (MPa) 0.100

    vc (MPa) 0.388

    Cost 184.61

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    164.80 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    232.75 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_319

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    45/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    045PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_319

    Output for Load Case LC2_319

    Soil pressure (ULS) (kN/m) 178.19

    Soil pressure (SLS) (kN/m) 164.80

    SF overturning (SLS) 2.79SF overturning (ULS) 2.79

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 19.91

    Reinforcement X (mm/m) 238

    Design moment Y (kNm/m) 10.62

    Reinforcement Y (mm/m) 127

    Top

    Design moment X (kNm/m) -17.51

    Reinforcement X (mm/m) 188

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.148

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.090

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.221

    Punching Shear (MPa) 0.071

    vc (MPa) 0.388

    Cost 178.79

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    164.80 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    178.19 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_319

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    46/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    046PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case D_315

    Output for Load Case D_315

    Soil pressure (ULS) (kN/m) 157.02

    Soil pressure (SLS) (kN/m) 143.61

    SF overturning (SLS) 2.71SF overturning (ULS) 2.71

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 7.05

    Reinforcement X (mm/m) 84

    Design moment Y (kNm/m) 7.94

    Reinforcement Y (mm/m) 95

    Top

    Design moment X (kNm/m) -24.86

    Reinforcement X (mm/m) 267

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.043

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.067

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.177

    Punching Shear (MPa) 0.052

    vc (MPa) 0.388

    Cost 170.85

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    143.61 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    157.02 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:D_315

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    47/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    047PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case L_315

    Output for Load Case L_315

    Soil pressure (ULS) (kN/m) 64.04

    Soil pressure (SLS) (kN/m) 50.12

    SF overturning (SLS) 11.11SF overturning (ULS) 11.11

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 2.21

    Reinforcement X (mm/m) 26

    Design moment Y (kNm/m) 1.25

    Reinforcement Y (mm/m) 15

    Top

    Design moment X (kNm/m) -3.15

    Reinforcement X (mm/m) 34

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.006

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.010

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.028

    Punching Shear (MPa) 0.008

    vc (MPa) 0.388

    Cost 164.97

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    50.12 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    64.04 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:L_315

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    48/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    048PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC1_315

    Output for Load Case LC1_315

    Soil pressure (ULS) (kN/m) 227.09

    Soil pressure (SLS) (kN/m) 159.85

    SF overturning (SLS) 2.54SF overturning (ULS) 2.54

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 10.47

    Reinforcement X (mm/m) 125

    Design moment Y (kNm/m) 12.82

    Reinforcement Y (mm/m) 153

    Top

    Design moment X (kNm/m) -39.33

    Reinforcement X (mm/m) 423

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.058

    vc (MPa) 0.418

    Linear Shear Y (MPa) 0.108

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.280

    Punching Shear (MPa) 0.084

    vc (MPa) 0.388

    Cost 175.09

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    159.85 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    227.09 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC1_315

  • 8/11/2019 Prokon - Andrew Tibeyalrwa Calculations

    49/49

    SheetJob Number

    Job Title

    Client

    Calcs by Checked by Date

    Software Consultants (Pty) Ltd

    Internet: http://www.prokon.com

    E-Mail : [email protected]

    049PC-146

    Proposed Residential Building to built on Plot 918 Block 249 Kyadondo County

    NKUNZIRE ANNETTE

    N.RONNIE ENG. A. KUSEMERERWA 12/6/2012

    Output for Load Case LC2_315

    Output for Load Case LC2_315

    Soil pressure (ULS) (kN/m) 172.34

    Soil pressure (SLS) (kN/m) 159.85

    SF overturning (SLS) 2.54SF overturning (ULS) 2.54

    Safety Factor slip (ULS) >100

    Safety Factor uplift (ULS) >100

    Bottom

    Design moment X (kNm/m) 7.85

    Reinforcement X (mm/m) 94

    Design moment Y (kNm/m) 9.04

    Reinforcement Y (mm/m) 108

    Top

    Design moment X (kNm/m) -28.43

    Reinforcement X (mm/m) 306

    Design moment Y (kNm/m) 0.00

    Reinforcement Y (mm/m) 0

    Linear Shear X (MPa) 0.049

    vc (MPa) 0.388

    Linear Shear Y (MPa) 0.076

    vc (MPa) 0.388

    Linear Shear Other (MPa) 0.202

    Punching Shear (MPa) 0.059

    vc (MPa) 0.388

    Cost 171.82

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    159.85 kN/m

    3.40

    X

    Y

    Y

    1.6

    0

    -1.08

    0.23

    0.23

    1.28

    0.23

    0.23

    P

    Mx

    P

    Mx

    1.5

    0

    Hx

    0.30

    1.60

    172.34 kN/m

    Soil Pressures at ULSSoil Pressures at SLS

    LegendMax M (+)

    Max M (-)

    Max Shear

    Load Case:LC2_315