Promistyl 3005T - roofing
120A - Metal Cladding
N° H001 - Key Plan (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Metal Cladding Arval Globalroof Promistyl 3005T ribbed face fix composite fire rated roofing panels
Panel reference Arval Promistyl 3005T
Manufacturer
R
R
ArcelorMittalLammerdries82440 GeelBelgiumweb site: www.arcelormittal.com/arval
H003
H002
H011
H004
H009
H010
H008
H005
H006
Direction Of Lay Panel Width Module 1000mm
Ma
xim
um
Pa
ne
lLe
ng
th12
00
0M
axi
mu
m
H002
H002
H002
H007
H012
H013
120A - Metal Cladding
N° H002 - Panel Arrangement (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
External facing material 0.63mm or 0.75mm gauge galvanized cold rolled steel sheetgrade S320 G to EN10326 & En10346
Finish/colour Colorissme range (we recommend using light colours) to EN10169
Internal facing material 0.5mm or 0.63mm gauge galvanized cold rolled steel sheetgrade S320 G to EN10326 & EN10346
Finish/colour Interior 912 to EN10169
Core insulation Rockwool, density 100kg/m ( 15kg/m )giving Uc [W/(m.K)] :60mm - 0.61; 80mm - 0.46; 100mm - 0.39; 120mm - 0.33;150mm - 0.26
3 3+
Roof steelwork purlin indicative Main panel fixing in accordance to the specification of panel thickness
Direction of layEnd lap detail
200
50
50
10mm nominal 20mm maximum
job specific calculationsMain panel fixing screw as per
10mm minimum
End lap stitcher screwto every crown
3 Rows of 6 x 5mm butyl rubbersealant (site applied)
1000 Cover width
333.3mm
Pa
ne
lth
ickn
ess
Promistyl 3005T roof panel
Promistyl 3005T roof panel
End lap detail
Promistyl 3005T roof panelPromistyl 3005T roof panel
Main panel fixing screw as perjob specific calculations
maximum 450mm centresEnd lap stitcher screw at
6mm diameter butyl rubber sealantVapour seal when required (site applied)
6x5mm butyl rubber sealant (site applied)
Promistyl 3005T roof panel
Fire resistance A2-S1, do to Euronorms
Promistyl 3005T - roofing
120A - Metal Cladding
N° H003 - Primary Fasteners (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Primary cladding fasteners Self tapping and self drilling screws (galvanized carbon steel) .
Number and location offasteners
1 N° fastener at every support rail fixed through panel trough plus side lap fasteners at 450mmminimum centers or as required by project specific calculations. For alternative crown fixing(applicable to certain territories only) please consult.
Fixing Cladding210G Structure Check that the structure is in a suitable state to receive the cladding before commencing fixing. Subcontractor must
confirm acceptance to main contractor.
215 Structure Do not fix cladding until final coats of paint have been applied to all contact surfaces of supporting structure, andremove all dust and foreign matter before finally fixing panels into position.
Drill all holes and install fasteners at regular intervals in straight lines, centered on support bearings.
Install fastners to correct tightness using special tools recommended by the fastener manufacturer. When used,screw guns must be fitted with depth sensitive devices and be used at the correct speed.
Check fasteners on completion and adjust as necessary to ensure that they are watertight and sheeting is securebut not buckled or distorted.
Promistyl 3005T - roofing
Direction of layscrew as per
screw as perjob specific calculations
Main panel fixing
(Applies to certain territories- please consult)
Alternative end lap detail
Promistyl 3005T roof panel
6mm diameter butyl rubber sealantVapour seal when required (site applied)
6x5mm butyl rubber
Promistyl 3005T roof panel
sealant (site applied)
Direction of layMain panel fixing
job specific calculations
Promistyl 3005T roof panel
6x5mm butyl rubber sealant (site applied)
Vapour seal when required (site applied)6mm diameter butyl rubber sealant
End lap stitcher screw atmaximum 450mm centres
Promistyl 3005T roof panel
Preferred end lap detail
N° H004 - Sealing Joints (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Sealing Cladding550A Seals Horizontal - Rolled steel full interlocking male/female edges giving weather tight overlap joint.
554A Vapour seals
Vertical - Extended top profile with foam core and bottom profile cut back to give a fully sealedoverlap joint (200mm) complete with 3 continuous rows of 6mm x 5mm butyl rubber sealant.
Sealant tape: 20mm x 5mm closed cell foam vapour strip positioned in straight unbroken lines at panelsupports, parallel to and slightly back from end of panel. Do not allow tape to be stretched into position.
Ensure continuity and effectiveness of seal, especially at sheet corners. Ensure adequate over-compressionto achieve required vapour seal.
.
120A - Metal CladdingPrimary cladding fasteners Self tapping and self drilling screws (galvanized carbon steel) .
Number and location offasteners
1 N° fastener at every support rail fixed through panel trough plus intermediate fastenersat 450mm centers or as required by project specific calculations.
Promistyl 3005T roof panel
sealant (site applied)3 Rows of 6 x 5mm butyl rubber
to every crownEnd lap stitcher screw
10mm minimum
Main panel fixing screw as perjob specific calculations
10mm nominal 20mm maximum
50
50
200
End lap detail
Promistyl 3005T - roofing
120A - Metal Cladding
N° H005 - Eaves Gutter 1 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Accessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Eaves galv support angle by others
Air Seal - 6mm diameter bead of gun grade sealant by others
Air seal - 8mm diameter butyl rubber sealant by others
Promistyl 3005T roof panel
Profiled filler sealed top andbottom with gun grade mastic
Main panel fixing (rigime as per job specific calculations)
Downpipe by others
Wall panel
Steelwork by others
Trimline Gutter by others
75
Gutter support bracket
Stitcher fixing at 900mm centres
Promistyl 3005T - roofing
N° H006 - Eaves Gutter 2 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Parapet galv support zed by others
Main panel fixing (rigime as per job specific calculations)
Downpipe by others
Wall panel
Steelwork by others
Insulated membrane lined composite gutter by others
Promistyl 3005T roof Panel
Air seal - 8mm diameter butyl rubber sealant by others
Steelwork by others
Parapet capping by others75
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
N° H007 - Eaves Overhangs (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Main panel fixing (rigime as per
Steelwork by others
Promistyl 3005T roof panel
75
Stitcher fixing at 900mm centres
Air Seal - 6mm diameter bead of
Air Seal - 8mm diameter butyl rubber sealant by others
Steelwork by others
Eaves flashing by others
Eaves Flashing by others
Snow guard unit by others
job specific calculations)
job specific calculations)Main panel fixing (rigime as per
gun grade sealant by others
Eaves galv support angle by others
Wall panel
bottom with gun grade masticProfiled filler sealed top and
(if required)
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
N° H008 - Verge - parapet (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Steelwork by others
Cill closure flashing by others
Air seal - 6mm diameter butyl
Galv support angle by others
rubber sealant by others
applied insulation to fill any gaps if requiredto maintain continunity of insulation
PIR board insulation with alfasbond FR canister
Verge zed support by others forsite cut panel applications
Wall panel
9 x 3mm butylrubber sealant
1000mm To next panel module
Direction of lay
Main panel fixing (rigime as per job specific calculations)
Wall panel
Steelwork by others
Promistyl 3005T roof panel
Air Seal - 8mm diameter butyl rubber sealant by others
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H009 - Verge (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Wall Panel
Parapet capping flashing by others
Direction of lay
Steelwork by others
Cleader angle by others
Air seal - 6mm diameter butyl rubber sealant by others
Profiled filler sealed top andbottom with gun grade sealant
rubber sealant9 x 3mm butyl
site cut panel applicationsVerge zed support by others forPIR board insulation with alfasbond FR canister applied insulation
to fill any gaps if required to maintain continuity of insulation
Air Seal - 8mm diameter butyl rubber sealant by others
Promistyl 3005T roof panel
Main panel fixing (rigime as per job specific calculations)
1000mm to next panel module
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H010 - Ridge (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Air seal - 8mm diameter butyl
Promistyl 3005T Roof Panel
Main panel fixing (rigime as per
Steelwork by others
Internal ridge flashing with 150mm overlap sealed withair seal vapourflex or gun grade sealant by others
job specific calculations)
sealed overlaps or butt strapsRidge flashing by others with a 150mm
Profiled filler sealed top and bottomwith gun grade sealant
Profile filler set back 80mm to
100mm to prevent bird attack
rubber sealant by others
Mineral fibre insulation site applied
Promistyl 3005T Roof Panelto be turned up on site
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
N° H011 - Rooflights 1 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
perimeter of opening
Promistyl 3005T roof panel
Roof ventilator
EPDM foam rubber taperubber sealant9 x 3mm butyl
site cut panel applicationsVerge zed support by others for
PIR board insulation with alfasbond FR canister applied insulationto fill any gaps if required to maintain continuity of insulation
Galv channel framing to
Steelwork by others Air Seal - 8mm diameter butyl rubber sealant by others
Promisol 1001B roof panel
Main panel fixing (rigime as per job specific calculations)
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H012 - Rooflights 2 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
Rooflight fitted off ridge
Vent opening
rubber sealant by othersAir seal - 8mm diameter butyl
Internal ridge flashing with 150mmoverlap sealed with Air seal
Ridge flashing with150mm sealed laps
EPDM foam rubber tape
Promistyl 3005T roof panel
EPDM foam rubber tape
Roof ventilator
perimeter of openingGalv channel framing to
to fill any gaps if required to maintain continuity of insulationPIR board insulation with alfasbond FR canister applied insulation
9 x 3mm butyl rubber sealant
rubber sealant by others
with gun grade sealantProfiled filler sealed top and bottom
Air seal - 8mm diameter butyl
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H013 - Rooflights 3 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
120A - Metal Cladding
Soaker unit with insulated upstand
4mm diameter butyl rubber sealant
PIR board insulation with alfasbond FR canister applied insulationto fill any gaps if required to maintain continuity of insulation
Galv channel framing to
Steelwork by others
Air Seal - 8mm diameter butyl rubber sealant by others
perimeter of opening
Promistyl 3005T roof panel
EPDM foam rubber tape
Steel trimmer
Air Seal - 8mm diameter butylrubber sealant by others
Promistyl 3005T roof panel
Rooflight
Single skin profiled sheet to ridge or to next end lap
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H014 - Rooflights 4 (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Note: These details are for guidance only.The individual building designer mustsatisfy him/herself of any and all coldbridging issues and adjust the finaldesign layout accordingly.
EPDM foam rubber tape
perimeter of opening
Main panel fixing (rigime as per job specific calculations)
Promistyl 3005T roof panel
Air Seal - 8mm diameter butyl rubber sealant by othersSteelwork by others
Galv channel framing to
to fill any gaps if required to maintain continuity of insulationPIR board insulation with alfasbond FR canister applied insulation
4mm diameter butylrubber sealant
Soaker unit with insulated upstand
Barrel rooflight
Correct width, length and upstand lip should be specifiedIsometric view of upstand
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
Rockwool
N° H015 - Penetrations (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Air Seal - 8mm diameter butyl
Ondatherm 1001T roof panel extractor detail high temperature
Ondatherm 1001T roof panel
Hole in panel cut to accommodatepipe/ducting etc
Moulded GRP pipe outlet(factory produced)
Note: Maximum hole size to be 300mm square or diameterPenetrations greater will require additional supporting steel
Pipe/ducting by othersGRP insitu weathering systembonded to external sheetcolour to match external panel
Site applied non combustibleinsulation by others
Ondatherm 1001T roof panel extractor detail high temperature
Ondatherm 1001T roof panel
Pipe/ducting by others
Penetrations greater will require additional supporting steelNote: Maximum hole size to be 300mm square or diameter
rubber sealant by others
Site applied non combustibleinsulation by others
Note: It is advisable to locate pipe/ducting withinthe mini-corrugations of outer sheet profile
"Dektite" (silicon) flexible pipeflashing or similar to suit hightemperature conditions by others
Galvanised soaker
Internal cover flashing tomatch liner material
Hole site cut to accommodatepipe/ducting etc
Penetrations greater will require additional supporting steelNote: Maximum hole size to be 300mm square or diameter
Note: It is advisable to locate pipe/ducting withinthe mini-corrugations of outer sheet profile
Air Seal - 8mm diameter butylrubber sealant by others
Ondatherm 1001T roof panel
Standard temperaturepipe/ducting by others
"Dektite" (EPDM) flexible pipeor similar by others
Internal cover flashing tomatch liner material
pipe/ducting etcHole site cut to accommodate
Ondatherm 1001T roof panel extractor flue (soaker to flue)
Flue
Weather skirt by others
Soaker unit
4mm diameter butylrubber sealant
Site applied PUR board
rubber sealant by othersAir Seal - 8mm diameter butyl
Closure flashingby others
Isometric view of upstand
Ondatherm 1001T roof panel
3005T
3005T
3005T
3005T
3005T
3005T
3005T
Promistyl 3005T - roofing
120A - Metal CladdingAccessories Matching flashings and support zeds.
Fittings and accessories generally221 Accessories Cappings, closure pieces, flashings, trims cills, gutters, fillers, spacers, tapes, sealants, fixings etc, where not
specified, are to be types as recommended by ArcelorMittal - Arval.
223 Isolating Tape A type recommended for the purpose by ArcelorMittal - Arval. Apply to those surfaces of supports whichwould otherwise be in contact with cladding or accessories after fixing.
Material: Galvanized cold rolled steel sheet grade S220 GD.Thickness/gauge: 0.75mm minimum.Finish/colour: External - Colorissime range.
Internal -
/Structure with 4.8mm stitcher screws (or rivets) at multiplesof 333mm centers.
Interior 912
Workmanship as NBS Standard Section Z22.
Fix to Promistyl
310A Purpose madecold formedmetalaccessories
R
NBS - H31
120A - Metal Cladding
N° H016 - Fixing Generally (Note: All installations should comply with the recommendations contained in MCRMA Techinical Papers N° 12 & 14; BS3200 and other relevant national standards)
Accessories Matching flashings and support zeds.
410 Fixing Panels The use of Promistyl sandwich panels requires accurate setting out, with due allowance for buildingexpansion devices (these must not be built over).
Before fitting the panels, the cladding contractor must inspect the supporting structure using thecriteria below listed, to ensure that the panels do not take on any uneveness inherent in the supportsupport system, thereby causing the finished surface of the facade to be out of true.
The results of a bilateral inspection by the principal contractor and the supplier of the support systemshould be duly recorded in any inspection report.
In case of complaint in respect of ArcelorMittal - Arval products we will require production of theinspection report for the support structure.
Any roof panel system is aesthetically only as good as the framework to which it is fixed. It isessential therefore that the support system is true to line and plumb. We recommend that allsecondary steelwork to which Promistyl panels are fixed be designed to be capable of adjustmentduring erection. ArcelorMittal - Arval recommend steelwork tolerances as listed below:-
Vertical tolerance (full height of building) = 5mm maximumAlignment (adjacent vertical supports) = +/-2mmHorizontal tolerance (full length of building)
Promistyl panels are purpose-made to specific requirements. Site cutting is not normally required,if cutting is required the following should be observed:-
Before cutting, masking tape must be laid on the cutting line to protect coating from damage.Cutting must be carried out with a jigsaw, blades are to have fine metal cutting serrations.Note - Angle grinders or similar type tools must not be used.
Cut panels on suitable supports to avoid de-lamination of metal skins by vibration.
All exposed rockwool cut panel edges to be protected afterwards with self adhesive foil tape. Cut openingsin panels for outlets, vent pipes, flues, etc. to the minimum size necessary. Reinforce edges of openingswith support angles/flashings.
Drill all holes and install fasteners perpendicular to the surface of the panels. Position the fasteners atregular intervals in straight lines, centred on the support bearings. Remove dust and any other foreignmatter before finally fixing panels into position.
Protect panels adequately during fixing and up to Completion against mechanical damage/disfigurement.Rectify any defects as quickly as practicable to minimise damage and nuisance. Cladding panels andflashings must be cleaned down and swarf, rivet mandrels, debris, etc. must be removed on a day to daybasis as work proceeds.
Paint all cut edges to match face finish.
Accessories
Fixing panels generallyR
R
= +/-5mm
R
Promistyl 3005T - roofing