Page 1: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

ATTACHMENTB

MARKED-UPTECHNICALSPECIFICATIONS

Remove Pa e Insert Pa e

3/4 3-323/4 3-333/4 3-343/4 3-358 3/4 3-1a

3/4 3-323/4 3-333/4 3-343/4 3-35B 3/4 3-1a

9411230090 94k l i4PDR AOOCK 05000275PDR,

Page 2: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

I

Page 3: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

TAB .3-2

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION

FUNCTIONAL UNIT

1. Safety Injection (Reactor TripFeedwater Isolat/on StartDiesel Generators, kontainmentFan Cooler Units, and ComponentCooling Water)

CHANNELCHECK

CHANNELCALI-BRATION

.CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MODES FORMASTER SLAVE WHICH

ACTUATION RELAY RELAY SURVEILLANCELOGIC TEST TEST TEST ~IS IIE LIIOEO

a. Manual Initiationb. Automatic Actuation

Logic and Actuation Relays

c. Containment Pressure-High

N.A.

N.A.

N.A.

N.A.

N.A.

N.A. N.A.

N.A.

N.A.

M(1)

N.A.

N.A.

M(1)

N.A.

N.A. 1, 2, 3, 4

1, 2, 3, 4

R.N.A. 1, 2, 3, 4

d. Pressurizer Pressure-Low

e. DELETED

N.A. N.A. N.A. N.A. 1, 2, 3

f. Steam LinePressure-Low

2. Containment Spray

N.A. N.A. N.A. N.A. 1, 2, 3

a. Manual In)tiationb. Automatic Actuation

Logic and ActuationRelays

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

R

N.A.

N.A.

M(1)

N.A. N.A. 1E 2O 3, 4 ~M(1) 1, 2, 3, 4

c. Conta'inment Pressure-High-High

N.A. N.A. N.A. N.A. 1, 2, 3, 4"-"-a I

DIABLO CANYON — UNITS 1 5 2

«fj « .rT«W

OE

3(4 3-32 d nt N ~ 84- -83- -6-86 9 8f ctiv nit CyclI

Page 4: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

7W

K

LI

IJ

t

X

I.(t

b'

Page 5: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

=TABLE 4.3-2 Continued

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATIONRVEILLA E E IREMENTS

FUNCTIONAL UNITCHANNELCHECK

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FORSLAVE WHICHRELAY SURVEILLANCE

. TERT ~IR RE IITRE

3. Containment Isolationa. Phase "A" Isolation

1) Manual2) Automatic Actuation

Logic and ActuationRelays

3) Safety Injectionb. Phase "B" Isolation

1) Manual2) Automatic Actuation

Logic and ActuationRelays

3) ContainmentPressure-High-High

c. Containment Ventilation Isol1) Automatic Actuation

Logic and ActuationRelays

2) Plant Vent Noble GasActivit -High (RH-14Aand 14B (a)

3) Safety njection4) Containment Ventilation

Exhaust Radiation-High(RH-44A and 44B)(b)

N.A.N.A.

N.A.N.A.

ationN.A.

N.A.N.A.

N.A.N.A.

RN.A.

N.A.M(1)

N.A.M(1)

s,z,3,%

N.A.N.A.

N.A.N.A.

RN.A.

N.A. N.A. .A. 1, 2, 3, 4H(1) H(1) 1, 2, 3, 4

N.A. N.A. N.A.R.

N.A. 1, 2, 3, 4 (

N.A. N.A.

M(2)

N.A.

N.A.

M(1)

N.A.

H(l)

N.A.

1 , 2, 3, 4IZ.

N.A. 1, 2, 3, 4

See Item 1. above for all Safety Injection Surveillance Requirements.

M(2) N.A. N.A. N.A. N.A. 1, 2, 3, 4

I'eeItem 1. above for all Safety Injection Surveillance Requirements.

a e requ rements for ant Vent Noble Gas Activity-High (RH-14A and 14B) are not applicable following installation ofRH-44A and 44B.

(b)The requirements for Containment Ventilation Exhaust Radiation-High (RH-44A and 44B) are applicable followinginstallation of RH-44A and 448.

DIABLO CANYON — UNITS 1 & 2 3/4 3-33 Am men os 4- 9- -5-8 -89 8feet e U t 1 ycl 7

Page 6: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

l

I( *

Page 7: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

0TABLE 4.3-2 Continued

ENGINEERED SAFETY EM INSTRUMENTATION

FUNCTIONAL UNIT

4. Steam Line Isolation

CHANNELCHECK

CHANNELCALI-BRATION

ACTUATINGCHANNEL DEVICEOPERA- OPERA-TIONAL TIONALTEST

,TEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FORSLAVE WHICHRELAY SURVEILLANCETEST I5 REISUIREO

a. Manual

b. Automatic Actuation Logicand Actuation Relays

c. Containment Pressure-High-High

d. Steam Line Pressure-Low

N.A.

N.A.

e. Negative Steam Line Pressure SRate-High

5. Turbine Trip and FeedwaterIsolation

N.A.

N.A.

N.A.

N.A.

Q

N.A.

N.A.

N.A.

N.A.

N.A.

M(1)

N.A.

N.A.

N.A.

N.A.

M(1)

N.A.

N.A.

N.A.

N.A. 1, 2, t3

1, 2,

N.A. 1, 2, 3

N.A. 1, 2, 3

N.A. 3(3)

a. Automatic ActuationLogic and Actuation Relays

b. Steam Generator WaterLevel-High-High

6. Auxiliary Feedwater

a. Manual

b. Automatic ActuationLogic and Actuation Relays

c. Steam Generator WaterLevel-Low-Low

1) Steam GeneratorWater Level-Low-Low

2) RCS Loop hT

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A

M(1)

N.A.

N.A.

M(1)

N.A.

N.A

M(1)

N.A.

N.A.

M(1)

N.A.

N.A

N.A. 1, 2

N.A. 1, 2, 3

1, 2,'3

N.A. 1, 2, 3

N.A 1,2,3DIABLO CANYON — UNITS 1 5 2 3/4 3-34 e ent os. -and 8 8

ect Uni 1 C e 7

Page 8: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

/

~,

)

I

f

0

Page 9: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

I

TABLE 4.3-2 Continued

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATIONRVEI A RE UIREMENTS

FUNCTIONAL UNIT

6. Auxiliary Feedwater (Continued)

CHANNELCHECK

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATING

, DEVICEOPERA-

: TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FORSLAVE WHICHRELAY SURVEILLANCETERT IIIRIEIIIIIIIRIEIII

d. Undervoltage — RCP

e. Safety Infection

N.A. R N.A. ', R N.A. N.A.

See Item 1. above for all Safety Injection Surveillance Requirements.

N.A. 1

7. Loss of Power

a. 4.16 kV Emergency BusLevel 1

b. 4.16 kV Emergency BusLevel 2

S. Engineered Safety FeatureActuation System Interlocks

a. Pressurizer Pressure,P-11

b. DELETED

c. Reactor Trip, P-4

N.A.

N.A.

N.A.

N.A. N.A.

N.A.

N.A.

N.A.

TABLE NOTATIONS

'.R

N.A.

N.A.

N.A.

N.A.

N.A.

. N.A.

N.A.

N.A.

N.A.

N.A. 1, 2, 3, 4

N.A. 1, 2, 3, 4

N.A. 1, 2, 3

N.A. 1, 2, 3

1 Each train shall be tested at least every 62 days on a STAGGERED TEST BASIS.2 For the Plant Vent Activity-High monitor only, a CHANNEL FUNCTIONAL TEST shall be performed at least once every 31 days.3 Trip function automatically blocked above P-11 (Pressurizer Pressure Interlock) setpoint and is automatically blocked

elow P- when Safet Injecti n on Steam e P su — ow is not blocked(4) or ts nd, e a a:. xc relays 12A, K6, K615, d K615 which all be t ed, at

mi mum, ce per month durin refue g and d ng each old;Shutd unles hey ha been te ed withi herevio 92 days

DIABLO CANYON — UNITS 1 84 2 3(4 3-35 Am ment os. -end- 84- BB 8feet Uni 1 C e 7

Page 10: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

f

Ih

I

t

j

e

l"A>

Page 11: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

INSTRUMENTATION

BASES

REACTOR PROTECTION SYSTEM and ENGINEERED SAFETY FEATURES ACTUATION SYSTEMINSTRUMENTATION (Continued)

To accommodate the instrument drift that may occur between operational testsand the accuracy to which setpoints can be measured and calibrated, Allowable Valuesfor the setpoints have been specified in Table 3.3-4. Operation with setpoints lessconservative than the Trip Setpoint, but within the Allowable Value, is acceptable.

The methodology to derive the Trip Setpoints is based upon'ombining all of theuncertainties in the channel. Inherent to the determination of the Trip Setpointsare the magnitudes of these channel uncertainties. Sensor and rack instrumentationutilized in these channels are expected to be capable of operating within theallowances of these uncertainty magnitudes.

ESF response times specified in Table 3.3-5, which include sequential operationof the RMST and VCT valves (Table Notations 4 and 5), are based on values assumed inthe non-LOCA safety analyses. These analyses take credit for injection of borated

—-water from-the RMST. - Injection- of- borated water is assumed not to occur until theVCT charging pump suction isolation valves are closed following opening of the'RMSTcharging pump suction isolation valves. When the sequential operation of the RWST andVCT valves is not included in the response times (Tahle Notation 7), the valuesspecified are based on the LOCA analyses. The LOCA analyses takes credit forinjection flow regardless of the source. Verification of the response timesspecified in Table 3.3-5 will assure that the assumptions used for the LOCA and non-LOCA analyses with respect to the operation of the VCT and RMST valves are valid.

Undervoltage protection will generate a loss of power diesel generator start inthe event a loss of voltage or degraded voltage condition occurs. The dieselgenerators provide a source of emergency power when offsite power is either availableor is insufficiently stable to allow safe unit operation. The first levelundervoltage relays (FLURs) detect the loss of bus voltage (less than 69K busvoltage). The second level undervoltage relays (SLURs) provide a second level ofundervoltage protections which protects all Class 1E loads from short or long termdegradation in the offsite power system. The SLUR allowable value is the minimumsteady state voltage needed on the 4160 volt vital bus to ensure adequate voltage isavailable for safety related equipment at the 4160 volt, 480 volt, and 120 voltlevels.

IVER.<~ A

DIABLO CANYON — UNITS 1 & 2 B 3/4 3-la nt os. H8-84 -83—6 and

Mare , 1994

Page 12: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

pl

Page 13: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

Insert APage B 3/4 3-1a

For slave relays in the ESF actuation system circuit that are Potter 8 Brumfield typeMDR relays, the SLAVE RELAYTEST is performed on a refueling frequency. The testfrequency is based on relay reliability assessments presented in WCAP-13878,"ReliabilityAssessment of Potter and Brumfield MDR Series Relays," WCAP-1 3900,"Extension of Slave Relay Surveillance Test Intervals," and WCAP-14117, "ReliabilityAssessment of Potter and Brumfield MDR Series Relays." These reliabilityassessments are relay specific and apply only to Potter and Brumfield MDR seriesrelays. Note that for normally energized applications, the relays may have to bereplaced periodically in accordance with the guidance given in WCAP-13878 for MDRrelays.

Page 14: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage
Page 15: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

ATTACHMENTC

PROPOSED TECHNICALSPECIFICATION PAGES

6688S

Page 16: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage
Page 17: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

TABLE 4.3-2

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATIONSURVEILLANCE RE UIREMENTS

FUNCTIONAL UNIT

1. Safety Injection, (Reactor TripFeedwater Isolation, StartDiesel Generators, ContainmentFan Cooler Units, and ComponentCooling Water)

CHANNELCHECK

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FOR

SLAVE WHICHRELAY SURVEILLANCETERT ~IE RI IIIRER

a. Hanual Initiation N.A. - N.A. N.A. N.A. N.A. N.A. 1, 2, 3, 4

b. Automatic ActuationLogic and Actuation Relays

c. Containment Pressure-High

d. Pressurizer Pressure-Low

e. DELETED

f. Steam LinePressure-Low

2. Containment Spray

a. Hanual Initiation

b. Automatic ActuationLogic and ActuationRelays

c. Containment Pressure-High-High

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

H(l)

N.A.

N.A.

N.A.

N.A.

H(l)

N.A.

H(l)

N.A.

N.A.

N.A.

N.A.

H(1)

N.A.

1 2 3 4l

N.A. 1, 2, 3, 4

N.A. 1, 2,3

N.A. 1, 2, 3

N.A. 1, 2, 3, 4

R 1,2,3,4I

N.A. 1, 2, 3, 4

DIABLO CANYON — UNITS 1 & 2 3/4 3-32 Amendment Nos. 8

Page 18: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

0

Page 19: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

TABLE 4.3-2 Continued

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATIONSURVEILLANCE RE UIREMENTS

FUNCTIONAL UNITCHANNELCHECK

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

NODES FORSLAVE WHICHRELAY SURVEILLANCEIEEI ~IE RE IIIRER

N.A.N.A.

N.A.N.A.

lationN.A.

3. Containment Isolationa. Phase "A" Isolation

1) Manual2) Automatic Actuation

Logic and ActuationRelays

3) Safety Injectionb. Phase "B" Isolation

1) Manual2) Automatic Actuation

Logic and ActuationRelays

3) ContainmentPressure-High-High

c. Containment Ventilation Iso1) Automatic Actuation

Logic and ActuationRelays

2) Plant Vent Noble GasActivity-High (RN-14Aand 14B)(a)

3) Safety Injection4) Containment Ventilation

Exhaust Radiation-High(RN-44A and 44B)(b)

N.A.N.A.

N.A.N.A.

RN.A.

N.A.N(1)

N.A.N(l)

N.A. 1, 2, 3,R 1,2,3,4~

See Item l. above for all Safety Injection Surveillance Requirements.

N.A.N.A.

N.A.N.A.

R

N.A.N.A. N.A. N.A. 1, 2, 3, 4N(l) N(l) R 1 2 3. 4 I

N.A. N.A. N.A. N.A. 1, 2, 3, 4

N.A. N.A.

N(2)

N.A.

N.A.

N(l)

N.A.

N(l)

N.A.

R 1, 2, 3, 4 I

N.A. 1, 2, 3, 4

N(2) N.A. N.A. N.A. N.A. 1, 2, 3, 4

See Item l. above for all Safety Injection Surveillance Requirements.

(a)The requirements for Plant Vent Noble Gas Activity-High (RN-14A and 14B) are not applicable following installation ofRN-44A and 44B.

(b)The requirements for Containment Ventilation Exhaust Radiation-High (RN-44A and 44B) are applicable followinginstallation of RM-44A and 44B.

DIABLO CANYON — UNITS 1 & 2 3/4 3-33 Amendment Nos. &

Page 20: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage
Page 21: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

TABLE 4.3-2 Continued

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION

FUNCTIONAL UNIT

4. Steam Line Isolation

CHANNELCHECK

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FORSLAVE WHICHRELAY SURVEILLANCETE I ~IRE IIIREE

a. Manual

b. Automatic Actuation Logicand Actuation Relays

c. Containment Pressure-High-High

N.A.

N.A.

N.A.

N.A.

N.A.

N.A. N.A.

N.A.

N.A.

M(l)

N.A.

N.A.

M(1)

N.A.

N.A. 1, 2,3R 1, 2, 3

N.A. 1,2,3

d. Steam Line Pressure-Low S

e. Negative Steam Line Pressure SRate-High

5. Turbine Trip and FeedwaterIsolation

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A. 1, 2, 3

N.A. 3(3)

a. Automatic ActuationLogic and Actuation Relays

b. Steam Generator WaterLevel-High-High

6. Auxiliary Feedwater

a. Manual

b. Automatic ActuationLogic and Actuation Relays

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

M(l)

N.A.

N.A.

M(1)

M(l)

N.A.

N.A.

M(1)

R 1, 2

N.A. 1, 2

N.A. 1, 2, 3

R 1, 2, 3

c. Steam Generator WaterLevel-Low-Low

1) Steam GeneratorWater Level-Low-Low

2) RCS Loop hT

DIABLO CANYON - UNITS 1 L 2

N.A.

3/4 3-34

N.A.

N.A N.A N.A

N.A. N.A. N.A. 1, 2, 3

N.A 1, 2, 3

Amendment Nos.

Page 22: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage
Page 23: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

TABLE 4.3-2 Continued

ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATIONSURVEILLANCE RE UIREMENTS

CHANNELFUNCTIONAL UNIT CHECK6. Auxi 1 i ary Feedwater (Continued)

CHANNELCALI-BRATION

CHANNELOPERA-TIONALTEST

TRIPACTUATINGDEVICEOPERA-TIONALTEST

MASTERACTUATION RELAYLOGIC TEST TEST

MODES FORSLAVE WHICHRELAY SURVEILLANCETERT ~IE RE EIRER

d. Undervoltage — RCP

e. Safety Injection

7. Loss of Power

N.A. R N.A. R N.A. '.A.See Item l. above for all Safety Injection Surveillance Requirements.

N.A. 1

a. 4.16 kV Emergency BusLevel 1

b. 4. 16 kV Emergency BusLevel 2

8. Engineered Safety FeatureActuation System Interlocks

a. Pressurizer Pressure,P-11

b. DELETED

c. Reactor Trip, P-4

N.A.

N.A.

N.A.

N.A. N.A.

N.A.

N.A.

N.A.

TABLE NOTATIONS

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A.

N.A. 1, 2, 3, 4

N.A. 1, 2, 3, 4

N.A. 1, 2, 3

N.A. 1, 2, 3

1 Each train shall be tested at least every 62 days on a STAGGERED TEST BASIS.2 For the Plant Vent Activity-High monitor only, a CHANNEL FUNCTIONAL TEST shall be performed at least once every 31 days.3 Trip function automatically blocked above P-11 (Pressurizer Pressure Interlock) setpoint and is automatically blocked

below P-11 when Safety Injection on Steam Line Pressure-Low is not blocked.I

DIABLO CANYON — UNITS 1 5 2 3/4 3-36 Amendment Nos. and

Page 24: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage
Page 25: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

INSTRUMENTATION

BASES

REACTOR PROTECTION SYSTEM and ENGINEERED SAFETY FEATURES ACTUATION SYSTEM INSTRUMENTATION

(Continued)

To accommodate the instrument drift that may occur between operational tests and theaccuracy to which setpoints can be measured and calibrated, Allowable Values for thesetpoints have been specified in Table 3.3-4. Operation with setpoints less conservativethan the Trip Setpoint, but within the Allowable Value, is acceptable.

The methodology to derive the Trip Setpoints is based upon combining all of theuncertainties in the channel. Inherent to the determination of the Trip Setpoints are themagnitudes of these channel uncertainties. Sensor and rack instrumentation utilized inthese channels are expected to be capable of operating within the allowances of theseuncertainty magnitudes.

ESF response times specified in Table 3.3-5, which include sequential operation ofthe RWST and VCT valves (Table Notations 4 and 5), are based on values assumed in the non-

LOCA safety analyses. These analyses take credit for injection of borated water from theRWST. Injection of borated water is assumed not to occur until the VCT charging pump

suction isolation valves are closed following opening of the RWST charging pump suctionisolation valves. When the sequential operation of the RWST and VCT valves is not includedin the response times Table Notation 7), the values specified are based on the LOCA

analyses. The LOCA analyses takes credit for injection flow regardless of the source.Verification of the response times specified in Table 3.3-5 will assure that theassumptions used for the LOCA and non-LOCA analyses with respect to the operation of theVCT and RWST valves are valid.

For slave relays, in the ESF actuation system circuit that are Potter and Brumfieldtype MDR relays, the SLAVE RELAY TEST is performed on a refueling frequency. The testfrequency is based on relay reliability assessments presented in WCAP-13878, "ReliabilityAssessment of Potter and Brumfield MDR Series Relays," and WCAP-13900, "Extension of SlaveRelay Surveillance Test Intervals." The reliability,assessments are relay specific and

apply only to Potter and Brumfield MDR series relays. Note that for normally energizedapplications, the relays may have to be replaced periodically in accordance with theguidance given in WCAP-13878 for MDR relays.

Undervoltage protection will generate a loss of power diesel generator start in theevent a loss of voltage or degraded voltage condition occurs. The diesel generatorsprovide a source of emergency power when offsite power is either available or isinsufficiently stable to allow safe unit operation. The first level undervoltage relays(FLURs) detect the loss of bus voltage (less than 69M bus voltage). The second levelundervoltage relays (SLURs) provide a second level of undervoltage protections whichprotects all Class 1E loads from short or long term degradation in the offsite powersystem. The SLUR allowable value is the minimum steady state voltage needed on the 4160

volt vital bus to ensure adequate voltage is available for safety related equipment at the4160 volt, 480 volt, and 120 volt levels.

DIABLO CANYON - UNITS 1 & 2 B,3/4 3-la Amendment Nos.

Page 26: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

7

Page 27: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage

ATTACHMENTD

~ Westinghouse Electric Corporation Application for Withholding ProprietaryInformation from Public Disclosure (N. J. Liparulo to Document Control Desk,Attention Mr. WilliamT. Russell), CAW-94-739, dated October 17, 1994

~ AffidavitCAW-94-739 of Henry A. Sepp, Manager, Regulatory and LicensingInitiatives, Westinghouse Electric Corporation, dated October 17, 1994

~ Proprietary Information Notice

~ Copyright Notice

6688S

Page 28: Proposed TS 3/4.3.2, 'ESFAS Instrumentation,' relaxing ... · The SLUR allowable value is the minimum steady state voltage needed on the 4160 volt vital bus to ensure adequate voltage