Benefits• Maximize the lifetime of outdoor lighting
applications• Lower maintenance costs• Easy to apply in new or existing installations• Supporting all common power grid varieties
Features• Xtreme standard: long lifetime,
robust protection against vibration andtemperature
• Provides high surge protection of up to10 kV / 10 kA for all lighting technologies
• Optical failure indicator
Application• Highways• Rural roads• Industrial zones• Open space parking areas
Insulation Class Supported grids
TN TNC TNS TNCS TT ITClass I ✓ ✓ ✓ ✓ ✓ ✓
Datasheet
Protect your outdoor luminaires against damaging spikes and transientsOutdoor SPD - Xtreme Surge Protector I The unique solution for Outdoor lighting systems offering full protection against high surges in insulation Class I installations.
March 2019
Outdoor SPD
XtremeSurge Protector I
2 - 4 Datasheet - Xtreme Surge Protector I
Specification item Value
Product name Xtreme Surge Protector I
European order code 871829175031400
Logistic code 12NC 9290 008 86906
20
Specifications Parameter Value Unit Condition
Certifications CE, Kema Keur
Designation Type 2 & 3 Acc. EN61643-11
Classification Class III Acc. IEC61643-11
Protection mode Diff. mode & Comm. mode
Rated input voltage Un (L-N) 230 VAC 50 … 60 Hz, max. +10%
Max. continuous operating voltage Uc (L-N) 255 VAC 50 … 60 Hz
Max. continuous operating voltage Uc (L-GND) 255 VAC 50 … 60 Hz
Max. continuous operating voltage Uc (N-GND) 255 VAC 50 … 60 Hz
Temporary overvoltage TOV UT 1455 V MV system fault: 1200 V + 255 V, at tt = 200 ms, TT and
IT power grid
Temporary overvoltage TOV UT 337 V LV system fault: 255 V x 1.32 at tt = 120m, TT and IT power grid
Temporary overvoltage TOV UT 442 V LV system fault: 255 V x √3 at tt = 5 s, TT and IT power grid
Supported power grids TN, TT, IT Incl. all TN varieties TN-C, TN-C-S, TN-S
Rated discharge current In (L-N) 5 kA 8/20 µs
Rated discharge current In (L-GND) 5 kA 8/20 µs
Rated discharge current In (N-GND) 5 kA 8/20 µs
Max. voltage protection level at In Up (L-N) 1.5 kV See separate protection level table for other In values
Max. voltage protection level at In Up (L-GND) 2 kV See separate protection level table for other In values
Max. voltage protection level at In Up (N-GND) 2 kV See separate protection level table for other In values
Open-circuit voltage Uoc 10 kV
Backup fuse 20 A max., gG fuse
End of life indication yes Optical, light ON: SPD is functional. Light OFF: SPD has reached end-of-life
Servicability n/a No user servicable parts inside
Max earth leakage current at Uc 50 µA
Specifications Parameter Value Unit Condition
Surge withstand capability 1 strike Max. 10 kA, 8/20µs
Surge withstand capability 50 strikes Max. 5 kA, 8/20µs
Surge withstand capability 100 strikes Max. 3 kA, 8/20µs
Rated load current (max) 4 A
Power consumption (max) 0.01 W At Uc = 255 VAC at 4A load current
Insulation Class I only Insulation Class acc. IEC60598
Logistical data
Pieces per box
Electrical specifications
Other specifications
Xtreme Surge Protector I
IC 8/20 µs Differential mode U2 Common mode U1/U21 kA 1100 V 1100 V / 1050 V
3 kA 1250 V 1700 V / 1300 V
IC 8/20 µs Differential mode U2 Common mode U1/U25 kA 1350 V 1800 V / 1450 V
10 kA 1500 V 1900 V / 1850 V
Suitable for luminaires
Protection levels Up
u2
t2
Differential mode L-N
u1
u2
t1
t2
Common mode (L/N - GND, L+N - GND)
3 - 4 Datasheet - Xtreme Surge Protector I
45
37.5
90
11
35
16.5
70
M8
4.3
4
Product dimensions
dimensions in mm
Specification item Value Unit
Mounting length 70 mm
Overall length 90 mm
Case Width 45 mm
Case Height 37.5 mm
Mounting screw M4
Mounting stud M8
Mounting torque M4 screw/M8 stud (max) 0.8 Nm
Weight 66 gr
Specification item Value Unit Condition
Ambient temperature -40…70 °C
Max. allowable surface temperature 80 °C
Storage temperature -40…85 °C
Relative humidity 5…95 % Non-condensing
Suitable for outdoor luminaires Yes Built-in only
Specification item Value Unit Condition
Lifetime 100,000 hours At max. surface temperature, min. 90% survival rate
Environmental conditions
Lifetime
Specification item Value Unit Condition
Connector type Push-in Single wire only
Wire diameter 0.5…2.5 mm2 Solid and stranded
Wire strip length 10…11 mm
Wiring
Connection diagram and recommended wiring layout
Electrical connections
Signal Description Color
L-Out Line output connection Black
L-Mains Line input connection Black
N-Mains Neutral input connection White
N-Out Neutral output connection White
GND Protective Earth connection Green
GND Protective Earth connection Green
©2019 Signify Holding, IBRS 10461, 5600 VB, NL. All rights reserved.
The information provided herein is subject to change without notice. Signify does not give any representation or warranty as to the accuracy or completeness of the information included herein and shall not be liable for any action in reliance thereon. The information presented in this document is not intended as any commercial offer and does not form part of any quotation or contract, unless otherwise agreed by Signify.
Philips and the Philips Shield Emblem are registered trademarks of Koninklijke Philips N.V. All other trademarks are owned by Signify Holding or their respective owners.
Date of release: March 22, 2019 v10
www.philips.com/oem
Warning: Connect the SPD GND connector to Protective Earth only. Do not connect the SPD GND connector to ungrounded accessible (luminaire) parts.
System DisposalWe recommend that the Surge Protector is disposed of in an appropriate way at the end of its (economic) lifetime. The Surge Protector is in effect a normal piece of electronic equipment containing components that are currently not considered to be harmful to the environment. We therefore recommend that this part is disposed of as normal electronic waste, in accordance with local regulations.