Protection & Control Relay (IED)

Page 2: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Protection relay evolution

6/12/2015 | Slide 2© ABB Group

Electromechanical relay :

- Induction disc type

- Electromagnetic forcecauses mechanicaloperation of relay

- Fixed operatingcharacteristic

Static relay :

- Doesn’t have moving parts- Trip output is of attracted

armature type- Operating qty is generated

by discrete analog(generally) electroniccomponents

- Selectable operatingcharacteristic

Numeric relay, IED :

- Analog input is sampled andconverted to digital format.

- The digital quantity is managedfurther by microprocessor withmathematical algorithm to generatethe operating quantities andimplement the protection functions.

- Operating characteristic isadjustable.

- Having sophisticatedcommunication features.

Page 3: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Protection function

6/12/2015 | Slide 3© ABB Group

Detectfaults

Isolate faults selectively andquickly from the network

To limit consequences, i.e.damaged equipment or loss ofproduction

Protection requirementLV MV 70kV…150kV 275kV…500kV

Fuse,MCB

Overcurrentrelays

- Main prot- Backup prot

- Main 1- Main 2

Shorter operating time

Protection applicationSystem topologyand characteristic

Protection zones, Fault detection,Suitable protection scheme andalgorithm

Protection relayselection & settings

Higher CT requirement

Page 4: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Fault clearing time

6/12/2015 | Slide 4© ABB Group

Fault clearing time according to Aturan Jaringan PLN (Grid Code) :

1. For main protection

- 500 kV system ≤ 90 ms

- 275kV system ≤ 100 ms

- 150kV system ≤ 120 ms

- 70 kV system ≤ 150 ms

2. For backup protection ± 500 ms

3. Fault clearing time consists of :

- Relay operating time

- Circuit breaker break time

- Teleprotection transfer time

- CT performance

Page 5: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Example 1 : Unit protection zones

6/12/2015 | Slide 5© ABB Group

OHL

Bus1

Bus2

Line protection :- Distance- Line diff.

Transformer prot. :- Diff.- REF

Busbar prot. :- Busbar Diff.

Page 6: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Example 2 : Unit protection zones

6/12/2015 | Slide 6© ABB Group

OHL

Bus1 Bus2

Line protection :- Distance- Line diff.

Transformer prot. :- Diff.- REF

Busbar prot. :- Busbar Diff.

Page 7: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Example 3 : Unit protection zones

6/12/2015 | Slide 7© ABB Group

OHL

Bus1 Bus2

Line protection :- Distance, or- Line diff.

Transformer prot. :- Diff.- REF

Busbar prot. :- Busbar Diff.

Tee zone prot :- Circulating

current

Page 8: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Fault detection :

6/12/2015 | Slide 8© ABB Group

500 ohm

Ground fault currenttoo small…practicallynot feasible

Make use of open deltaVT to detect ground faultfor :- Neutral displacementprotection relay

Page 9: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Challenging areas :

6/12/2015 | Slide 9© ABB Group

§ CT accuracy class

§ CT saturation

§ Transformer inrush

§ Zero-sequence block by deltawinding or ungrounded wye

§ Power swing

§ Communication scheme forline protection

§ Short zone/dead zone

§ High impedance differentialprotection

§ Asynchronous closing ofcapacitor or transformer

Page 10: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

CT classes :

6/12/2015 | Slide 10© ABB Group

§ Metering : 0.2S, 0.2, 0.5, 1

§ Protection : Class P, Class PX, TPX, TPY, TPZ

Page 11: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Power swing :

6/12/2015 | Slide 11© ABB Group

Communication scheme for protection :

Page 12: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Short zone/dead zone :

6/12/2015 | Slide 12© ABB Group

Page 13: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

High impedance differential protection:

6/12/2015 | Slide 13© ABB Group

Page 14: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Capacitor bank energization :

6/12/2015 | Slide 14© ABB Group

§ High frequency inrush currentà protection failure§ Overvoltageà flashover

Page 15: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

Transformer energization :

6/12/2015 | Slide 15© ABB Group

§ V=L.di/dtà assymetrical inrush current for closing at zero crossing§ Voltage drop

Page 16: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 16© ABB Group

Page 17: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 17© ABB Group

Page 18: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 18© ABB Group

Page 19: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 19© ABB Group

Page 20: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 20© ABB Group

Page 21: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 21© ABB Group

Page 22: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group

6/12/2015 | Slide 22© ABB Group

Contact PersonName : Ustika Anggono

Division : Power System

Position : Engineering Manager

Email : [email protected]

Mobile : 081514271512

Page 23: Protection & Control Relay (IED) - ABB Groupfile/Protection+Control+IED-+Ustika.pdf · Protection & Control Relay (IED) Protection relay evolution 6/12/2015 | Slide 2 © ABB Group