protection of hvdc transmission line based on distributed...

7
2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC) 978-1-4799-3826-1/14/$31.00©2014 IEEE Protection of HVDC Transmission Line based on Distributed Parameters using Transient Energy Miss D.A Suryawanshi Prof. Y.N Bhosale Department of Electrical Engineering Department of Electrical Engineering Rajarambapu Institute of Technology Rajarambapu Institute of Technology Islampur, Maharashtra, India Islampur, Maharashtra, India [email protected] [email protected] AbstractProtection of the HVDC transmission line is one of the major concerns in the present power system as HVDC is preferred more than HVAC due to its leading advantages over HVAC system. In this paper a novel transient energy protection principle is proposed. Behaviour of the HVDC system during internal and external fault is studied. And according to that the variation of the transient energy and the relation between the parameters of the dc transmission is analyzed during internal and external fault conditions, based on that the transient energy protective principle is developed. It is based on distributed parameters of the transmission line model and the transient energy distributed over the line is obtained by measuring voltage and current at both the terminals and fault can be identified from the calculated value of transient energy. The test system is modeled in MATLAB software and it is based on CIGRE (Counseil International des Grands Reseaux Electriques) benchmark by considering distributed parameters of the transmission line. Index Terms-HVDC, Transient energy, Transmission line. I. INTRODUCTION HVDC transmission system has advantages over HVAC system such as long distance, flexible and fast control, low losses, large capability of power transmission [1]-[3]. Due to the rapid development of power electronics and encouraging means for improving the stability, HVDC transmission system plays a vital role in the complex power systems. The older protective system for the HVDC transmission line uses the voltage and its rate of change to identify ground fault in the dc line. It is found that it is sensitive to fault impedance. Due to the increasing advance of microelectronics technology and microcomputer, traveling wave theory has been implemented in the HVDC transmission lines protection [4].Traveling wave methods has disadvantage such as it is easily affected by noise lacking mathematical tools to represent the traveling wave [5]-[7]. A novel protection scheme was proposed for UHVDC based on the characteristics of low frequency differential transient energy at the two terminals of dc transmission line. But this paper considered lumped parameters of the transmission line. We know that the characteristic of HVDC transmission system is the long distance, distributed parameter effect cannot be neglected and that may cause the mis-operation of relay protection [8]- [10]. A new transient energy protection principle is proposed in this paper considering the steady state transmission line equations, the distributed parameters of the transmission line are taken into account. The increase in the transient energy in dc line is used to identify internal and external fault. Based on the distributed parameters of the transmission line, the test system is modeled. This paper is organized as follows. In section II CIGRE HVDC benchmark test system is given. In section III the protection principle used is proposed. Test results are given in section IV and conclusion is given in section V. II. CIGRE HVDC BENCHMARK SYSTEM Fig. 1. CIGRE HVDC benchmark system. The system is monopolar 500kv, 1000MW HVDC link. It has 12 pulse converters on both rectifier and inverter side and is connected to weak ac system. Damping filters and capacitive reactive compensators are provided on both sides. The power circuit consists of the following subcircuits [11], [12]. A. AC side AC side of the HVDC system consists of Supply source, converter transformer, AC filters. i) Supply Voltage source: Three phase ac voltage source is supplied to rectifier and inverter side. 81

Upload: others

Post on 20-Mar-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)

978-1-4799-3826-1/14/$31.00©2014 IEEE

Protection of HVDC Transmission Line based on

Distributed Parameters using Transient Energy

Miss D.A Suryawanshi Prof. Y.N Bhosale

Department of Electrical Engineering Department of Electrical Engineering

Rajarambapu Institute of Technology Rajarambapu Institute of Technology

Islampur, Maharashtra, India Islampur, Maharashtra, India

[email protected] [email protected]

Abstract—Protection of the HVDC transmission line is one

of the major concerns in the present power system as HVDC

is preferred more than HVAC due to its leading advantages

over HVAC system. In this paper a novel transient energy

protection principle is proposed. Behaviour of the HVDC

system during internal and external fault is studied. And

according to that the variation of the transient energy and

the relation between the parameters of the dc transmission is

analyzed during internal and external fault conditions, based

on that the transient energy protective principle is

developed. It is based on distributed parameters of the

transmission line model and the transient energy distributed

over the line is obtained by measuring voltage and current at

both the terminals and fault can be identified from the

calculated value of transient energy. The test system is

modeled in MATLAB software and it is based on CIGRE

(Counseil International des Grands Reseaux Electriques)

benchmark by considering distributed parameters of the

transmission line.

Index Terms-HVDC, Transient energy, Transmission

line.

I. INTRODUCTION

HVDC transmission system has advantages over

HVAC system such as long distance, flexible and fast

control, low losses, large capability of power transmission

[1]-[3]. Due to the rapid development of power

electronics and encouraging means for improving the

stability, HVDC transmission system plays a vital role in

the complex power systems.

The older protective system for the HVDC

transmission line uses the voltage and its rate of change to

identify ground fault in the dc line. It is found that it is

sensitive to fault impedance. Due to the increasing

advance of microelectronics technology and

microcomputer, traveling wave theory has been

implemented in the HVDC transmission lines protection

[4].Traveling wave methods has disadvantage such as it is

easily affected by noise lacking mathematical tools to

represent the traveling wave [5]-[7].

A novel protection scheme was proposed for

UHVDC based on the characteristics of low frequency

differential transient energy at the two terminals of dc

transmission line. But this paper considered lumped

parameters of the transmission line. We know that the

characteristic of HVDC transmission system is the long

distance, distributed parameter effect cannot be neglected

and that may cause the mis-operation of relay protection

[8]- [10].

A new transient energy protection principle is

proposed in this paper considering the steady state

transmission line equations, the distributed parameters of

the transmission line are taken into account. The increase

in the transient energy in dc line is used to identify

internal and external fault. Based on the distributed

parameters of the transmission line, the test system is

modeled.

This paper is organized as follows. In section II

CIGRE HVDC benchmark test system is given. In section

III the protection principle used is proposed. Test results

are given in section IV and conclusion is given in section

V.

II. CIGRE HVDC BENCHMARK SYSTEM

Fig. 1. CIGRE HVDC benchmark system.

The system is monopolar 500kv, 1000MW HVDC

link. It has 12 pulse converters on both rectifier and

inverter side and is connected to weak ac system.

Damping filters and capacitive reactive compensators are

provided on both sides.

The power circuit consists of the following subcircuits

[11], [12].

A. AC side

AC side of the HVDC system consists of Supply source,

converter transformer, AC filters.

i) Supply Voltage source:

Three phase ac voltage source is supplied to rectifier and

inverter side.

81

Page 2: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

D.A SURYAWANSHI, et.al.: PROTECTION OF HVDC TRANSMISSION LINE BASED ON DISTRIBUTED PARAMETERS

ii) Converter Transformer:

Two transformers are connected on rectifier side. They

are three phase, two winding transformers. One is with

grounded Wye-Wye connection and other with grounded

Wye-delta connection. Similar transformers are connected

to inverter side.

iii) AC Filters:

Damped filters are provided to reduce harmonics and

compensate reactive power.

B. DC Side

Smoothing reactors are connected at both rectifier and

inverter side. The dc transmission is represented by T

network.

C. Converters

Converters are of 12 pulse configuration. Two six pulse

converters are connected in series and configuration of 12

pulses is obtained. It consists of built in RC snubber

circuits for each thyristor.

i) Rectifier Control:

Constant Current Control technique is used for

rectifier control. The reference for current limit is taken

from inverter side. This is done to ensure the protection of

the converter during fault when inverter does not have

sufficient dc voltage support and during load rejection it

does not have sufficient load requirement. The reference

current used for rectifier control depends on inverter side

voltage. DC current on the rectifier side is passed through

filters before they are compared to produce the error

signal. Further the error signal is passed through PI

controller that produces firing order α.

ii) Inverter Control:

On the inverter side both extinction angle control (γ

control) and current control have been implemented. The

constant current control has been used with Voltage

dependent Current Order Limiter (VDCOL) through PI

controller. The reference limit for the current control is

obtained by comparing the external reference and

VDCOL (implemented by lookup table) output. Further

the measured current is subtracted from reference limit to

produce an error signal which is sent to the PI controller

to produce the required angle order. In order to produce

gamma angle order for the inverter the γ control uses

another PI controller. The two angle orders are compared

with each other and the minimum of two is used to

calculate the firing instant.

III. TRANSIENT ENERGY PROTECTIVE

PRINCIPLE

Fig. 2. Diagram of the HVDC transmission system.

Fig. 2 is the main structure diagram of the typical

HVDC transmission system. Mi , Ni and Mu , Nu are dc

currents and dc voltages. The positive directions of the

mentioned electrical vectors are defined in the diagram

[13]-[15].

The transient energy from 1t to 2t is

dttPE

t

t

mM 2

1

)(

(1)

dttPE

t

t

nN 2

1

)(

The increase in the transient energy is described as

ME dttP

t

t

m )(2

1

(2)

NE dttP

t

t

n )(2

1

Where )(tPm and )(tPn are the instantaneous power

and their increments are dttPm )( nP )(t .Converting

equation (2) to discrete time form by substituting tn. for

continuous period from 1t to 2t . As shown in equation

(3) t is the sampling interval and n is the time index.

Further the increase in dc voltage and dc current is

expressed as Mu , Mi , Nu , Ni so the increase in

transient energy is given as follows :

ME = tPn

i

mi1

(3)

tEE

n

i

niN 1

That means

n

i

MiMiM tiuE1

(4)

n

i

NiNiN tiuE1

Therefore the increase of transient energy in the dc

transmission line is

NM EEE

(5) In steady state operating condition,

0 NM EE

(6)

82

Page 3: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)

Transient energy difference is negative during steady

state.

A. External fault

Fig. 3. Demonstration of line model. (a) Distributed parameter model.

(b) Lumped parameter model with shunt capacitance.

Where 0R is the series resistance Ω/km, 0L is the

series

inductance (H/km), 0G is the shunt leakage conductance

(S/km) .

Equations of the transmission line are

t

iLRi

x

u

(7)

t

uCGu

x

i

For simplicity the impact of leakage conductance is

neglected in this paper. The dc line that has to be

protected is replaced by a lumped parameter model

considering the influence of shunt capacitance. The

increase of voltage and current due to distributed

parameters of the transmission line can be expressed as:

dt

diL

dt

diLiRiRu NM

NML 2121

(8)

dt

duCi c

c

(9)

Where NML uuu

Fig. 3(a) shows that the series inductance of the dc

transmission line is affected during external fault at the

inverter side. The system impedance decreases with fault

1F and becomes smaller than normal operation. Hence the

voltage at both the ends of the transmission line drops

down rapidly.

Fig. 3(b) shows superimposed fault current fi from

that we get transient current at both ends of dc

transmission line during fault 1F .

fMM iii 1

(10)

fNN iii 1

(11)

Substituting the relations of (10) and (11) in equation (8)

We get

dt

diL

dt

diLiRiRu NM

NML1

21

11211

(12)

And

LNM uuu 11

(13)

Fig. 4. External fault at the inverter side considering the series

inductance of the dc transmission line. (a) Diagram of the external fault.

(b) Superimposed circuit for the external fault.

Before the fault has occurred, we have

NMNM iRiRuu 21

(14)

It means

dt

diL

dt

diLiRRuu NM

fNM1

21

121 )(

(15)

Hence there are

0 Mu and 0 Nu

(16)

NM uu

Shunt capacitance of the dc transmission line affects

the dc protection of the dc line. Shunt capacitance

between the overhead dc line and ground is present during

normal operating conditions.

Therefore, with the fault 1F the capacitance current is

discharged from the shunt capacitance. Equivalent

capacitance C and the discharging current ci are

represented in Fig. 4(a), and an equivalent current source

that is used to substitute for the discharging current under

the transient state condition is shown in Fig. 4(b).

According to (9) the equivalent discharge current of

the dc line is

dt

duci C

C

(17) Hence the transient current of the dc line

during the fault 1F is obtained as,

CfMM iiii2

11

(18)

CfNN iiii2

11

and increase in two transient currents are

83

Page 4: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

D.A SURYAWANSHI, et.al.: PROTECTION OF HVDC TRANSMISSION LINE BASED ON DISTRIBUTED PARAMETERS

CfM iii2

1

(19)

CfN iii2

1

We know, fi Ci (20)

Fig. 5. External fault at the inverter side considering the shunt

capacitance of the dc transmission line. (a) Diagram of the external fault.

(b) Superimposed circuit for the external fault.

0 Mi ,0 Ni

(21)

NM ii

Substituting (16) and (21) in to equation (4)

We get,

MM iu 0 and 0 NN iu

Substituting these relations in equations (5)

We get

0E

Depending on the aforementioned procedures,

analysis of the ac fault at the rectifier side can be done.

During external fault the difference of transient energy

between both ends of the dc line is positive.

B. Internal Fault

Fig. 6. Internal fault at the dc transmission line. (a) Internal fault in the

dc line. (b) Superimposed circuit for the internal fault

During internal fault as shown in Fig. 5(a), the dc

voltages at both ends of the dc line drops down rapidly.

Fig. 5(b) shows superimposed circuit of the HVDC

transmission system where fu is the additional fault

voltage sources and fi is the additional fault current.

During this condition the current Mi always ascends and

Ni descends. So increase of transient voltage and current

is

0 Mu

0 Nu

0 Mi

0 Ni Substituting these relations into (4)

0E

During internal fault the difference of transient

energy between both ends of the dc line is negative.

Fig. 7. Flowchart of the transient energy principle.

IV. TEST RESULTS

i) Results for the balanced fault at the

inverter side:

In Fig. (8) four curves of the system responses are

shown during L-L-L-G fault at the inverter side. Fault

occurs at 0.5s. Im and Um are the dc current and dc voltage

close to the rectifier. In and Un are the dc current and

voltage close to the inverter.

During ac fault at the inverter side the dc voltages Um

and Un suddenly drops down. But current Im and In

increase rapidly. During that time constant current (CC)

and constant extinction angle (CEA) activates and tries to

make the dc system stable.

84

Page 5: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)

But large disturbance of the ac system makes dc

current to

increase on greater extent during that transient process.

Due to

the impact of shunt capacitor in the dc line, the dc current

Im is

smaller than In. And Um is greater than Un at that time.

Hence, there is transient energy difference between

both the terminals of the dc transmission line. And its

value is positive. As a result external fault can be

identified by the new scheme.

(a)

(b)

Fig. 8. System response during inverter fault,(a) Current under the

inverter fault. (b) Voltage under the inverter fault.

Fig. 9. Angle order of the rectifier during balanced fault at inverter side.

Fig. 10. Angle order of the inverter during balanced fault at inverter

side.

ii) Results for the balanced fault at the

rectifier side:

In Fig. (11) four curves of the system responses are

shown during L-L-L-G fault at the rectifier side. Fault

occurs at 0.5 s.

During ac fault at the rectifier side, the dc voltage Um

and Un decrease suddenly and dc currents Im and In will

decline. During that transient process due to the impact of

the shunt capacitor in the dc line the current Im is smaller

than In. Considering the influence of the equivalent series

inductance at that time, the voltage Un decreases slowly

than Um.

Hence, there is transient energy difference between

both terminals of the dc transmission line. And its value is

positive. As a result external fault can be identified by the

new scheme.

(a)

(b)

Fig. 11. System response during the rectifier fault. (a) Current under the

rectifier fault. (b) Voltage under the rectifier fault.

Fig. 12. Angle order of the rectifier during balanced fault at the rectifier

side

Fig. 13. Angle order of the inverter during balanced fault at the rectifier

side.

85

Page 6: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

D.A SURYAWANSHI, et.al.: PROTECTION OF HVDC TRANSMISSION LINE BASED ON DISTRIBUTED PARAMETERS

iii) Results for the dc line fault:

In Fig (12) four curves of the system responses are

shown during L-L-L-G fault at the dc line fault occurs at

0.5 s.

During dc line fault, dc voltages Um and Un drops

down

suddenly and dc current In decreases and Im increases

rapidly.

So increase of transient energy at the rectifier side is

negative and that at the inverter side is positive. Hence

there is transient energy difference between both the

terminals of the dc transmission line. And its value is

negative so the internal fault is recognized by the

proposed scheme.

(a)

(b) Fig. 14. System response during the dc line fault. (a) Current under the

dc line fault. (b) Voltage under dc line fault.

Fig. 15. Angle order of the rectifier during dc line fault.

Fig. 16. Angle order of the inverter during dc line fault.

TABLE I

Performance Evaluation of Transient Energy Protection

Scheme under Different Faults

Fault type ∆EM

/kW.ms

∆EN

/kW.ms

∆E

/kW.ms Operation

Rectifier

fault 0.1713 0.1210 0.0503 -

Inverter

fault -0.1329 -0.1807 0.4662 -

Internal

fault 0.2629 0.2033 -0.4662 +

A. Effect of Fault Resistance

To check the sensitivity of the transient protection

scheme, simulation of the CIGRE benchmark test system

is carried out with a set of different fault resistances from

1 to 300 .Correct responses are given by the proposed

protection scheme during various fault conditions that

includes high ground resistance fault.

In table II the performance evaluation of the proposed

transient energy protection scheme under different fault

resistance is given.

TABLE II

Performance Evaluation of Transient Energy Protection

Scheme under Different Fault Resistance

Fault

type

Fault

resistance/Ω

∆EM

/kW.ms

∆EN

/kW.ms

∆E

/kW.ms

Operation

Rectifier

fault

1

20 100

300

0.1795

0.1075 0.0284

0.0063

0.1101

0.0566 0.0130

0.0023

0.0694

.0509 0.0155

0.0039

-

- -

-

Inverter

fault

1

20 100

300

-0.1086

-0.0581 -0.0360

-0.0002

0.1638

-0.1027 -0.0712

-0.0014

0.0551

0.0446 0.0352

0.0012

-

- -

-

DC line

fault

1 20

100

300

-0.2475 -0.1750

-0.0872

-0.0282

0.2400 0.1827

0.0810

0.0284

-0.4875 -0.3577

-0.1681

-0.0565

+ +

+

+

B. Effect of Transmission Distance

To check the sensitivity of the transient protection

scheme, simulation of the CIGRE benchmark test system

is carried out by locating the fault at different

transmission distances from 100 to 2000 km. Proposed

protection gives correct responses under different

transmission distances.

In table III the performance evaluation of the

proposed scheme under different transmission distance is

given.

86

Page 7: Protection of HVDC Transmission Line based on Distributed ...iccpeic2014.weebly.com/uploads/2/4/6/4/24643277/ps036.pdfmodeled in MATLAB software and it is based on CIGRE ... HVDC transmission

2014 INTERNATIONAL CONFERENCE ON COMPUTATION OF POWER, ENERGY, INFORMATION AND COMMUNICATION (ICCPEIC)

TABLE III

Performance Evaluation of Transient Energy Protection

Scheme under Different Transmission Distances during

Internal Fault

Transmission

Distance/Km

∆EM

/kW.ms

∆EN

/kW.ms

∆E

/kW.ms Operation

100

300 500

1000

1500 2000

-0.2853

-0.2477 -0.2628

-0.1750

-0.1429 -0.1558

0.3234

0.2295 0.2034

0.1827

0.1640 0.1263

-0.6087

-0.4743 -0.4661

-0.3070

-0.3070 -0.2821

+

+ +

+

+ +

V. CONCLUSION

A novel transient energy protection method for the HVDC transmission line is proposed. This method is better than traveling wave protection method. Modeling of the CIGRE HVDC benchmark system is done using MATLAB software and the system is tested under various faults. According to the transient energy protection scheme, during external fault the transient energy is positive and negative during internal fault. Repetitive test studies shows that transient energy protection scheme satisfactorily works during internal and external fault conditions also it can respond to high ground resistance fault. Also the proposed protection scheme is not affected by the transmission distance.

APPENDIX

Rectifier ac system SCR= [email protected] 354.0 kV 50 Hz. Rectifier Rr1= 261.87 , Rr2= 83.32 , Rr3 = 29.76 Lr1= 0.1364H, Lr2 = 0.136H Cr1= 6.685 F , Cr2= 6.685 F , Cr3= 3.342 F , Cr4= 0.1364 F

Inverter ac system SCR= [email protected] 230 kV 50 Hz. Inverter Ri1= 116.38 , Ri2 = 37.03 , Ri3= 13.23 Li1= 0.0606 H, Li2 = 0.0061 H Ci1= 15.04 F , Ci2 = 15.04 F

, Ci3 = 7.522 F ,

Ci4 = 167.2 F

Resistance of the transmission line is 0.04633 /km.

REFERENCES

[1] B. R. Andersen and X. Lie, “Hybrid HVDC system for power transmission to island networks,” IEEE Trans. Power Del., vol.

19, no. 4, pp. 1884–1890, Oct. 2004.

[2] J. O’Reilly, A. R. Wood, and C. M. Osauskas, “Frequency domain based control design for an HVdc converter connected to a weak

AC network,” IEEE Trans. Power Del., vol. 18, no. 3, pp. 1028–

1033, Jul. 2003.

[3] R. S. Thallam, S. Mogri, and R. S. Burton, “Harmonic impedance

and harmonic interaction of an ac system with multiple dc in feeds, ” IEEE Trans. Power Del., vol. 3, no. 4, pp. 2064–2071, Oct. 1988

[4] P. F. Gale, P. V. Taylor, P. Naidoo, C. Hitchin, and D. Clowes,

“Travelling wave fault locator experience on Eskom’s transmission network,” in Proc. 7th Int. Conf. Develop. Power Syst. Protect.,

2001, vol. 4, no. 479, pp. 327–330.

[5] X. L. Liu, A. H. Osman, and O. P. Malik, “Hybrid traveling wave/

boundary protection for monopolar HVDC line,” IEEE Trans.

Power Del., vol. 24, no. 2, pp. 569–578, Apr. 2009.

[6] X. L. Liu, A. H. Osman, and O. P. Malik, “Real-time implementation

of a hybrid protection scheme for bipolar HVDC line using

FPGA,” IEEE Trans. Power Del., vol. 26, no. 1, pp. 101–108, Jan. 2011.

[7] Ying Zhang, ”Fault Analysis and Traveling Wave protection scheme

for bipolar HVDC lines” IEEE Trans. Power

Del,vol.27.3,July.2012.

[8] H.Takeda, H. Ayakawa, M. Tsumenaga, and M. Sanpei, “New protection method for HVDC lines including cables,” IEEE Trans.

Power Del., vol. 10, no. 4, pp. 2035–2039, Oct. 1995.

[9] B. Wang, X. Z. Dong, Z. Q. Bo, and A. Perks, “RTDS environment Development of ultra-high-voltage power system and relay

protection test,” IEEE Trans. Power Del., vol. 23, no. 2, pp. 618–

623, Apr. 2008. [10] B. Wang, X. Z. Dong, Z. Q. Bo, and A. Klimek, “Residual

compensation for ground impedance relay with applications in

UHV transmission lines,” IEEE Trans. Power Del., vol. 24, no. 3, pp. 1072–1078, Jul. 2009.

[11] M.Szechtman, T.Wess, and C.V.Thio, “First benchmark model for

HVDC control studies,” Electra, vol. 135, no. 4, pp. 54–73, April 1991.

[12] M. O. Faruque, Y. Zhang, and V. Dinavahi, “Detailed modeling of

CIGRE HVDC benchmark system using PSCAD/EMTDC and

PSB/ SIMULINK,” IEEE Trans. Power Del., vol. 21, no. 1, pp.

378–387,Jan. 2006.

[13] Z. Chen, Z. Q. Bo, F. Jiang, and G. Weller, “A fault generated high frequency current transients based protection scheme for series

compensated lines,” presented at the Proc IEEE Power Eng. Soc.

Winter Meeting, Singapore, Jan. 23–27, 2000. [14] Xiaodong Zheng, Tai Nengling, Yang Guangliang and Ding

HaoyinA, “Transient Protection Scheme for HVDC Transmission

Line,” IEEE Trans. Power Del., vol. 27, no. 2, April 2012. [15] T.Kase, Y. Kurosawa, and H.Amo, “Charging current

compensation for

distance protection,” in Proc. IEEE Power Eng. Soc. Genera Meeting, 2005, vol.3, pp. 2683–2688.

.

Deepali Suryawanshi was born in

Maharashtra, India, in 26 October 1990. Received B.E degree in Electrical Engineering

from Shivaji University in 2012 and pursuing

M.Tech(Power System) from Rajarambapu Institute of Technology, Maharashtra. Her

research interests are the HVDC transmission

system, Power system protection.

Yogini Bhosale received B.E (electrical) degree from Shivaji University and M.E

degree from Bharati Vidyapeeth College of

Engineering (BVCOE) Pune. Currently she is Assistant professor at Rajarambapu

Institute of Technology (R.I.T), affiliated by

Shivaji University. Her research interests

are Power system protection, Deregulated

Electricity Market.

87