Page 1: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

S W I S S

05.2006Eternit (Schweiz) AG

Facade System SIGMA 12

www.swisspearl.ch IIIII CH 8867 Niederurnen

®

PROV

ISIO

NAL

Design + Installation Manual

Page 2: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

2S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Table of contents

Table of contents..........

Page 3: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

3S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

This design�installation manual(DIM) contains basic informationfor planning and execution purpo-ses.

Refer to your local distributor forfurther information such as :• general sales conditions• prices, panel size optimising

process• product program and colors• maintenance and cleaning• ecological aspects

General information External wall designArchitect / consultant / contractorare to assume responsibility for thecorrect design and execution of theexternal wall and its cladding - in-cluding all thermal, water, vapourand wind insulation layers - all inaccordance with good buildingpractice.

Facade engineeringThis DIM has been based uponSwiss building standards. For anyproject abroad, the structural engi-neer must verify compliance withlocal building codes, standards andregulations. Structural engineer /contractor are to assume overallresponsibility for the facade engi-neering, including• to determine material and sizes

of all sub framing members• to determine all fastening details

to sub framing and panels

Project specific orderingThe characteristics of the raw ma-terials determine properties andappearance of the SWISSPEARLpanels. Subtile visual differencesmay occur between production bat-ches. Orders should make allowancefor this by itemising quantities ac-cordingly, so that panels for adja-cent surfaces on the same job canbe supplied from the same produc-tion batch.

General information

Marketing Phone +41 (0) 55 617 13 07Technical application Phone +41 (0) 55 617 13 19Fax +41 (0) 55 617 12 [email protected]

Page 4: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

4S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

4

5

6

7

8

910

1 2

4

3

System Description

CharacteristicsThe SWISSPEARL SIGMA 12 sys-tem consists of large size fiber ce-ment panels, with concealed me-chanical fasteners for high endarchitectural, rear ventilated faca-des.System descriptionThe SIGMA 12 rain screen facadesystem consists out of 12 mm thickSWISSPEARL panels with a maxi-mum net size of 3040�1220 mm(10�4 feet). At the factory, the pa-nels are cut to the required size, theedges slightly chamfered and im-pregnated. Still at the factory, un-dercut holes are drilled into the rearside of the panels. On building site,the cleats are fixed to the rear sideof the panels. After installation ofthe horizontal support rails onto ver-tical sub frame, the panels are hungby the rear attached cleats into thehorizontal support rails. Subse-quently each panel is levelled outby 2 adjusting screws and a loca-ting pin is inserted to prevent thepanel from horizontal wandering.

1 Undercut drill hole to panel rear side

2 SWISSPEARL undercut anchor

3 Stainless steel socket head screw

4 Cleat

5 Double cleat

6 Thermal insulation layer with dark finish

7 Wall bracket with thermal insulation pad

8 Vertical support profile (painted black at

panel joints)

9 Horizontal support profile

(black at panel joints)

10 SWISSPEARL panel 12 mm thick

Isometric scheme of SIGMA 12 system

Page 5: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

5S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

1

3

2

1

2

Planning I Panel and anchor details

SWISSPEARL panel technicaldata• Panel thickness 12 mm

(15/32 inch)• Gross density 1.8 g/cm3

22 kg/m2 (4.5 lbs/sqft.)• Modulus of elasticity

15’000 N/mm2

• Bending stress design value8.0 N/mm2

• Thermal expansion 0.01 mm/m/K• Fire performance A2-s1,d0

non inflammable• Frost resistance to EN 12467

SWISSPEARL panels 12 mm areavailable in product ranges Carat,Natura, TecturaPlease refer to „program�colors“.

Anchor components

1 Undercut dowel anchor

2 Stainless steel socket head screw M6�12 mm

Undercut anchorUndercut hole is drilled at thefactory at positions as per pro-ject specific requirements [1].

Insert dowel anchor. The squareshaped collar (10/10 mm) standsproud of the panel surface andcorresponds to the square cut outin the cleat to be attached [2].

By inserting the socket screw thedowel anchor expands into theundercut zone of the drill hole.Thus the anchor gets held backand anchoring effect results [3]

Principle of undercut anchoring

SIGMA 12 fiber cement panels

Page 6: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

6S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

> 1

0

> 40

PlanningThe SIGMA 12 system calls for ca-reful planning of all facade compo-nents, starting at the very beginningof the project. Based thereupon, allcomponents of the facade systemcan be manufactured according toprecise requirements and can beinstalled on building site the mostefficient way.

ResponsibilityThe architect, engineer, specialconsultant, contractor - as the casemay be - assumes full responsibili-ty for the planning and execution ofthe cladding system, including de-sign and calculations of buildingphysicist and structural engineer,water and vapour management de-sign, construction details, tenderdocuments, specifications, as wellas for all measurements and di-mensioning on building and clad-ding.

Fiber cement panelsSWISSPEARL panels 12 mm forSIGMA 12 cladding systems aremanufactured as ordered accordingto list of panels. At the factory, pa-nels are cut to size, panel edgesslightly chamfered and impregna-ted; undercut holes are drilled intopanel rear side.

Other componentsAnchors, socket head screws, cle-ats, double cleats and horizontalsupport rails and pertaining rivetswill be delivered as ordered per listof components.

Panel jointsWhen needful, it must be possibleto replace a panel in mid facadearea. Therefore provide sufficientjoint width to allow sliding in andout of the panels. Minimum jointwidth is 10 mm (13/32 inch). As pa-nel joints are open, paint supportprofiles black at joints and usethermal insulation with UV resis-tant black top layer.

Ventilation cavityNet cavity thickness is minimum40 mm (1 9/16"). The thermal insula-tion layer must be well fastened tothe wall as not to obstruct the airflow within the cavity.

Ventilation opening at bottomProvide perforated screen at bottomof cavity to keep out rodents/vermin.

Planning I Various aspects

Page 7: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

7S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Sub framingSub framing consists generally outof brackets and vertical supportprofiles provided locally, and hori-zontal support rail, to be suppliedby SWISSPEARL.

Architect, engineer, special consul-tant, contractor - as the case maybe – assumes responsibility for thedesign, specification and executionof all sub frame members includingall pertaining fasteners.

Butt joints within vertical sub fra-me profiles must coincide with pa-nel joints. Vertical profile lengthgenerally from storey to storey.

CleatsCleats and double cleats are at-tached to the panel rear face onbuilding site. Both double cleats inthe top row at each panel end bearthe panel dead load and are adjus-table in height by adjustment screwin order to level out the panel. Onedouble cleat per panel shall have alocating pin. All other cleats aresingle cleats and are bearing windload only. EPDM U-sections arefitted to the cleats in order to pre-vent rattling noise from wind.

SealantNo sealant shall be used in con-junction with the SIGMA 12 clad-ding system. Where the use is una-voidable, best suitable would behybrid polymer, poly urethane oracrylic sealant, do not use silico-ne, poly sulphide or Thiokol mate-rial.

Planning I Various aspects

Page 8: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

8S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Planning I Calculation values

Determine dimensions on buil-Determine dimensions on buil-Determine dimensions on buil-Determine dimensions on buil-Determine dimensions on buil-ding siteding siteding siteding siteding siteReference level and grid lines tothe facade must be defined in orderto determine what follows :• Arrangement and setting out of

sub frame profiles• Position of cladding outer

face line• Window reveal alignments• Window sill and head levels• Top, bottom and vertical

finish lines• Dimensions of SWISSPEARL

panels (list of panels)

DimensioningThe sub frame and claddingconstruction is to be calculated bythe structural engineer on the pro-ject, employing FEM (finite ele-ments method) or special facadecalculation programs.

The number of anchors depends onpanel sizes, sub frame design andthe exposure to stresses; and mustbe calculated for each individualproject. Wall brackets and supportprofiles are assumed to be bend-proof.

Consider the following values for structural calculations

egdelenapotecnatsiD d ep mm051-07

rohcnarepdaolrepelisnetelbissimdA F .mda N414

rohcnarepdaoLraehselbissimdA Q .mda N008

srohcnaneewtebgnicapS d � mm057

nihtiwsrohcnaneewtebgnicapStaelcelbuod d cd mm54

taelcnituotucerauqS h×l mm2,01×mm2,01

taelcelbuodnituotucralugnatceR h×l mm2,01×mm0,51

Page 9: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

9S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Planning I Calculation values

Max. distances betweenanchor pointsBased upon Swiss building stan-dards, i. e. wind speed up to 140km/h or 0.9 kN/m2, (building fringezones with increase wind load), forpreliminary planning purpose thehorizontal distance between anchorsmay be determined according to thetable as follows:

thgiehgnidliuB enozlamron enozegnirf

m8otpu mm057 mm056

m22otpu mm057 mm045

m05otpu mm086 mm064

Horizontal rails at 750 mm centers.

For final determination of anchorquantities, the structural engineerwill take into consideration:• factor applicable wind speed• factor location in the field and

building height• factor building shape

Distance anchors to paneledgesHorizontally 70–150 mmVertically 70–150 mmRecommendation 100 mm

Distances for anchors must be cal-culated for each project individually.Maximum distance between an-chors is 750 mm.

Facade normal and fringe zoneParticularly concerning negativewind loads it is essential to diffe-rentiate between normal zone(mid field facade) and fringe zone(at building corners and on top) asshown on scheme.

The extent of the fringe zone is 1/10of the building length and height(minimum 1 m, maximum 2 m).

Fringe zone

Frin

ge z

one

Frin

ge z

one

Normal zone

Page 10: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

10S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

1 2 1 1 2 1

1

2

1

70-150 w w 70-150

70-1

5070

-150

70-150www70-150

70-1

50h

h70

-150

70-150w70-150

70-1

50h

70-1

50

hh

h

Planning I Anchor positions

Anchor configurationProvide double anchor cleats to up-per anchor row at both panel ends.These double cleats bear the paneldead load. All the other cleats aresingle anchor cleats.

1 Double cleat (bearing panel dead load)

2 Single cleat (bearing wind load)

Max. distances between anchor points w = 750 mm, h = 750 mm

Page 11: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

11S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

> 50

10.2

10.2

80

15 10.2

10.2

45

Planning I Cleats

Double cleat Single cleat

Double cleat with two anchors, 1 square cut out and 1rectangular (rectangular hole allows some play for theinstallation) 1 level adjustment screw 1 locating pin

Single cleat with one anchor, 1 square cut out

Cleat as supplied by SWISSPEARL

Page 12: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

12S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

1 2 3

4

5

Execution I Panel installation

Installation procedure1Insert SWISSPEARL dowel anchorinto undercut hole, drilled at thefactory.

2Fit square anchor collar exactlyinto cleat cut out, then fasten cleatwith socket head screw and washer,adjusting torque spanner tomax. 4.0 Nm.

3After attaching the cleats, hangthe panel directly into horizontalrails. The installation proceeds frombottom to top of the facade.

4Level out panel with adjustmentscrews on both double cleats.

5Install locating pin systematically toleft side double cleat.

Page 13: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

13S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

abc

5050 30 70 70 30

d = 80 d = 80

a b c

7030

50

d =

80

Dimensions on site –tolerancesVariations between theoretical andactual building site dimensions canbe taken up by adaptor panels. Ifvariations are anticipated, adaptorpanels should be included in thePO to avoid delays and additionalcosts.Horizontal dimensionaltolerancesTolerance variations from the nomi-nal panel size may be taken up byadaptor panel from -60 to +100 mm.Order adaptor panels 100 mm widerthan nominal size. The distance fromedge to anchor shall be 150 mm forthe adaptor panel. This allows oneach side 80 mm of play i. e. thetotal panel width may vary 160 mm.

Horizontal dimensionaltolerances

a minimal panel size

b nominal panel size

c max. panel size (to order)

d 80 mm play (each side)

Vertical dimensional tolerances

Vertical dimensionaltolerancesTolerance variations from the nomi-nal panel size may be taken up byadaptor panel from -30 to +50 mm.Adaptor panels to be provided forbottom or top of facade. Order ad-aptor panels 50 mm higher than no-minal size. This allows a play of 80mm for the top or bottom panel ofthe facade.

a minimal panel size

b nominal panel size

c max. panel size (to order)

d 80 mm play

Execution I Dimensional Tolerances

Page 14: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

14S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

left

top

bottom

rig

ht

TYP Avertikal

Typ Bhorizontal

76

54

32

1

1 2 3 4 top

bottom

left

rig

ht

Wl Wr

Hu

Ho

H

W

45 45

Wl Wr

Ho

Hu

W

H7654321

12

34 45 45

Execution I Panel configuration

Vertikal panel type A and Horizontal panel type B

Panel front elevation

Page 15: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

15S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Execution I List of Panels - Example

Fill out Panel number, quantity, panel sizes, edge distances and applicable wind load. The program will define anchor spacing.

lenaPrebmun

ytitnauQ ezislenaPsretemillimni

epytlenaP ecnatsidegdE[tfel WWWWWlllll]

ecnatsidegdEthgir [WWWWWrrrrr ]

ecnatsidegdEmottob [HHHHHuuuuu]

ecnatsidegdEpot [HHHHHooooo]

forebmuNsgnicaps

htdiW [WWWWW]

forebmuNsgnicaps

[thgieH HHHHH]

]eceip[ htdiW WWWWW thgieH HHHHH epytAAAAA ro BBBBB ]mm[ ]mm[ ]mm[ ]mm[ ]mm[ ]mm[

Page 16: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

16S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

1

2 3

5

4

6

7

8 9

10

Execution I Construction Detail

Outer building corner detail1 External wall installation base

2 Thermal insulation with black top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Double cleat (by SWISSPEARL)

7 Angle profile for corner

8 Undercut anchor (by SWISSPEARL)

9 Locating pin (by SWISSPEARL)

10 SWISSPEARL SIGMA 12 panel

Page 17: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

17S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL1

2 3

5

4

6

78

9

Inner building corner detail

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Double cleat (by SWISSPEARL)

7 Undercut anchor (by SWISSPEARL)

8 Locating pin (by SWISSPEARL)

9 SWISSPEARL SIGMA 12 panel

Page 18: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

18S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

1

2

5

4

6

7

8

9

10

3

Window reveal detail

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Double cleat (by SWISSPEARL)

7 Angle profile

8 Undercut anchor (by SWISSPEARL)

9 Locating pin (by SWISSPEARL)

10 SWISSPEARL SIGMA 12 panel

Page 19: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

19S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

1

2

5

4

6

7

8

9

10

3

Window sill detail

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Level adjustment screw to double cleat

(by SWISSPEARL)

7 Undercut anchor with socket head screw

(by SWISSPEARL)

8 Window sill by others

9 Window reveal

10 SWISSPEARL SIGMA 12 panel

Page 20: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

20S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

12

5

4

6

7

8

9

10

3

11

12

Execution I Construction Detail

Window head detail1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Single cleat (by SWISSPEARL)

7 Undercut anchor with socket head screw

(by SWISSPEARL)

8 Angle (by others)

9 Window reveal

10 SWISSPEARL 8 mm panel

11 Window connection U channel (by others)

12 SWISSPEARL SIGMA 12 panel

Page 21: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

21S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

1

2

5

46

7

8

9

10

3

Window head with shutter

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Single cleat (by SWISSPEARL)

7 Undercut anchor with socket head screw

(by SWISSPEARL)

8 Angle (by others)

9 Window reveal

10 SWISSPEARL SIGMA 12 panel

Page 22: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

22S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

1

2

5

4

6

7

8

9

3

>30

50

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Level adjustment screw to double cleat

(by SWISSPEARL)

7 Undercut anchor with socket head screw

(by SWISSPEARL)

8 Coping profile (by others)

9 SWISSPEARL SIGMA 12 panel

Top of facade detail

Page 23: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

23S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL1

2

5

4

6

7

8

9

10

3

Bottom of facade detail

Execution I Construction Detail

1 External wall installation base

2 Thermal insulation with dark top finish

3 Bracket mounted onto thermal isolator pad

4 Vertical support profile

5 Horizontal rail (by SWISSPEARL)

6 Cleat (by SWISSPEARL)

7 Undercut anchor with socket head screw

(by SWISSPEARL)

8 Perforated closure profile (by others)

9 SWISSPEARL 8 mm panel, without

rear ventilation

10 SWISSPEARL SIGMA 12 panel

Page 24: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

24S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Storage on building siteFor storage on building site the pa-nels must be protected from humi-dity and dirt. The plastic foil co-vering the pallets serves only asprovisional protection, and is notsufficient for storage.

Protecting the panelsStore the pallets under roof. Wherethis is not possible use tarpaulin.If panels are stored longer than 2months, stack the panels betweenbattens to allow air circulation.

On site storage

Danger during transportationand installationFor transportation, handling and in-stallation all measures must be ta-ken to avoid damage to persons,material or property. All local, state,federal and other applicable safetyregulations must always be com-plied with.

Wrong: Do not drag panels from stack Correct: Always lift panel off the stack

AccessoriesUse only SWISSPEARL SIGMA 12accessories, do not use any materialsupplied by others.

Fabricating SWISSPEARLpanels• Use power tools with dust

extraction• Avoid the use of tools which

produce fine dust• Always work out of the weather• To cut panel use circular saw

with straight edge• Apply impregnation liquid after

cutting panel• Remove dust from fabrication

immediately

Execution I Storage and handling

Page 25: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

25S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

CuttingFor long straight cuts use circularhand saw with pertaining straightedge. Use carbide metal or dia-mond tipped blade suitable for fibrecement. Use system with automaticdust extraction.For small cut out in panel use pen-dular jig saw with carbide metalblade.

Additional undercut drill holesIn case any additional drill holesare needed for additional cleats,undercut holes may be drilled onbuilding site with special drillingmachine KS-HV. This tool may berented from either SWISSPEARL orfrom anchor manufacturer. Instruc-tion for use of the tool to be follo-wed strictly.

Instruction for using hand applicatorfor LUKO impregnation liquid:

1 Panel edge must slightlychamfered, clean and dry

2 Remove protective cap3 Hold applicator with tank upwards4. Apply sponge at right angle to

panel edge and run with moderatepressure twice over panel edge(forth and back)

5 Caution, do not allow LUKO toflow onto panel front face,remove immediately

6 Check that LUKO has beenapplied over entire edge length

7 Put cap on when interruptingthe job

8 Replace sponge when worn9. Store and use LUKO at

min. +5°C (+41°F)

LUKO hand applicator

Screw fastenerwith slipping clutch

Allen key

Pendular jig saw

Adjustabletorque spanner

Work table with straight guidecircular saw and dust extraction

Tools

Impregnation to panel edges cut on site

Impregnation of edges out on site

Execution I Fabrication and tools

Page 26: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

26S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Execution I Cleaning

Fabrication dustRemove dust from cutting and dril-ling immediately

Dry dustRemove best with vacuum cleaner,or with a dry soft and clean cloth orbrush.

Wet dustLeaves stains on panel coating.Therefore wet dust must be remo-ved immediately with plenty of wa-ter and a sponge or soft brush. Toremove stains, use solution of ace-tic acid in water.

Cleaning of completedcladdingNon calcium based stainsUse water blaster to wash claddingwith cold water at 40-80 bars. Pri-or do test on inconspicuous part ofthe cladding.

Calcium based stains1 Apply a mist spray of a solution

of 10% acetic acid in water2 Allow to react a few minutes but

do not let dry out3 Use water blaster to rinse

cladding (as described)4 Repeat steps 1-3 on obstinate

stainsNever wash facades in direct sunNever wash facades in direct sunNever wash facades in direct sunNever wash facades in direct sunNever wash facades in direct sunlight with alkaline or acid clea-light with alkaline or acid clea-light with alkaline or acid clea-light with alkaline or acid clea-light with alkaline or acid clea-ners, as the detergent may causeners, as the detergent may causeners, as the detergent may causeners, as the detergent may causeners, as the detergent may causeirreversible stains.irreversible stains.irreversible stains.irreversible stains.irreversible stains.

Masking tapeFor the application of masking tapeonto surface of SWISSPEARL pa-nels, it should be noted that mostcommon masking tapes are not re-sistant to UV rays. Such tapes lea-ve residues behind, that can not beremoved from the panel surface wi-thout causing damage.

Therefore it is recommended to usethe following masking tapes• for 1-2 weeks temporary

application use masking tapeBlue 3M 2090

• for several months long term application use masking tapeGold 3M 244

Page 27: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

27S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Execution I Horizontal rail

components

1 SWISSPEARL SIGMA 12 panel

2 Undercut drill hole to panel rear side

3 Undercut dowel anchor

4 Stainless steel washer

5 Stainless steel socket head screw

6 Stainless steel level adjustment screw

7 [a] Double cleat

7 [b] Single cleat

8 EPDM U-section

9 Stainless steel rivet

10 Aluminium horizontal rail

11 Vertical support profile (by others)

12 Material separation layer

13

7b

5 6

1

3

7a

4 5

6

8

910

11

8

9 10

11

12

12

2

2

29.3

Page 28: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

28S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Execution I Horizontal rail

x

y

Fastening onto vertical support at double cleats with 4 rivets. Provideseparation layer if vertical support is different material.

Fastening onto vertical support at single cleats with 2 rivets. Provideseparation layer if vertical support is different material.

Ao = 319,8 mm ²Wx = 5,747 cm ³Wy = 1,213 cm ³Ix = 20,435 cm 4Iy = 2,287 cm 4

Real supporting Double cleads Real supporting Single cleads

Horizontal support rail in raw aluminium:Material AlMg Si 0,5, T66 (EN 515)Length of rail max. 4000 mmMin. distance between horizontal rails = 170 mm

Rivets:Type SSX 614 Ø 4,8�12,0 mm, stainless steel A2

Page 29: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

29S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Execution I CleatsCleatsCleatsCleatsCleats

Double cleat Double cleat

80 mm wide double cleat in aluminium with cut outs for two undercut an-chors, EPDM U-section level adjustment screw and hole for locating pin.

The double cleat is provided with a thread for the stainless steel level ad-justment screw M6�16 mm. There is a ∅ 3.8 mm drill hole for stainlesssteel locating pin of ∅ 3.6 mm. Install 1 pin per panel systematically inthe same position. Use 2 pins for narrow vertical panels.

50 mm wide single cleat with cut ont for one anchor, with EPDM U-section.

1962

16

10,2

12

19 45 16

4830

40 10 30

10,2

10,2

15

10,2

19

6216

50

3048

25 25

10,2

10,2

10,2

Page 30: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

30S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Execution I Swisspearl® REFLEXSwisspearl® REFLEXSwisspearl® REFLEXSwisspearl® REFLEXSwisspearl® REFLEX

AppearanceWith varying angles of viewing andchanging incidence of light, the iri-descent surface of REFLEX presentsa different aspect to the beholder.This effect is influenced by the di-rection the panels are manufactu-red. To achieve consistency in theaspect over an entire façade, fromwhatever angle it is viewed, thepanels must come from the samebatch and must be installed orien-ted aline.

IdentificationOn the back of every REFLEX panelarrows indicate the direction of pro-duction orentation.

QuotesRequests for quotes must alreadystate the direction of production forevery parcel of panels. This infor-mation determines the number offull panels required for the job inquestion.

InstallationInstall all panels orientated alike.No matter how small the job, thearrows on the back of all the panelsmust point in the same direction.

Where this requirement is notstrictly observed, panels that areorientated incorrectly will appear inthe facade as color deviations.

Correct Wrong

PlanningAlready at the design stage thedirection of production of the panelmust be considered in order to as-sure the consistency in the aspectof the iridescent surface; i.e. allthe panels must be installed eitherhorizontally or vertically throug-hout.

Page 31: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

31S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

Facade System SIGMA 12®

PROV

ISIO

NAL

Execution I WWWWWarrantyarrantyarrantyarrantyarranty

Warranty Letter (Example)With reference to your order n°of 200. and our consignment(s) forabove mentioned building we con-firm that we give a warranty for aperiod of 10 years, beginning ondate of delivery, provided that:

• the panels were cut/drilled at thefabricator’s shop, transported,stored and cut/drilled on the buil-dingsite according to the recommenda-tionsapplicable to Swisspearlpanels as specified in the technicalguidelines valid at the date ofordering/delivery; and

• the panels were fixed- according to our recommendationsapplicable to Swisspearl® panels- with our prescribed system ac-cessories, i.e. rivets, screws, fixpoint sleeves, etc.

This warranty covers• the water tightness and frost re-sistance as well as the mechanicaland physical characteristics of theSwisspearl panels, the averagefigures of which are defined in theEN Standarts and Eternit Standards.• the functional quality of the ac-cessories supplied by Eternit, i.e.rivets, screws, fix point sleeves,EPDM strips, etc.

The warranty does not cover• defects caused or substantiallycontributed to by• inappropriate fabricating and sto-rage (at the fabricator’s shop and/oron the building site), handling andinstallation of the panels• inappropriate application of thepanels for the local conditions• the use of inappropriate fastenersfor the building location and/or subframing

• slight modifications in colourssuch as homogeneous lighteningaccording to test values or alterati-ons due to air pollution or other en-vironmental influences (dust, soi-ling from window sills, metalprofiles, etc.)• damages due to the use of ac-cessories which do not belong toour range• damages due to aggressive clea-ning procedures• damages due to algaes

Any SWISSPEARL product whichdoes not comply with these qualitystandards will be replaced free ofcharge, ex works Niederurnen, onthe condition that Eternit (Schweiz)AG, Niederurnen, are notified withina period of 4 weeks after the appea-rance of any defect. Purchaser’s re-medies hereunder for replacementof the defective product are exclu-sive and in lieu of any other reme-dies, such as

rescission of the purchase contractor reduction of the purchase price,which purchaser might have.In particular, the warranty coversneither the transport costs nor la-bour expenses for dismantling anddumping defective panels and in-stalling new panels. Except for thewarranties set out in this document,Eternit makes no warranty, expressor implied, with respect to the pa-nels and accessories and expresslydisclaims any warranty of merchan-tability, description or fitness forany particular purpose or function.In no event shall Eternit be liableto purchaser or any other party forspecial, consequential, incidentalor punitive damages including, wit-hout limitation, loss of use, profits,revenue or goodwill. Eternit shallnot be liable for failure of perfor-mance hereunder due to force ma-jeures.

Attachment: Technical Data sheet

Page 32: PROVISIONAL - Eternit Portugal · PROVISIONAL This design installation manual ... external wall and its cladding - in-cluding all thermal, water, ... Undercut anchor

32S W I S S

05.2006Eternit (Schweiz) AG www.swisspearl.ch IIIII CH 8867 Niederurnen

PROV

ISIO

NAL

Facade System SIGMA 12®

Execution I VVVVVererererery important:y important:y important:y important:y important: „dos and don’ „dos and don’ „dos and don’ „dos and don’ „dos and don’ts“ts“ts“ts“ts“

Generalities• All local, state, federal and otherapplicable safety regulations mustalways be complied with• Purchase Swisspearl facade pa-nels/systems only from appointedauthorised distributors• Use Swisspearl facade panels/systems only for applications re-commended by manufacturer• All manufacturer’s recommendati-ons regarding design, storage, fab-rication, installation and cleaningof Swisspearl facade panels/sys-tems must be fully complied with

Design and Installation• Before start of installation, verify that:- detail drawings have been appro

ved by Swisspearl/distributor- correct fasteners and accessories

have been delivered to site• Sub frames are to be designed bystructural engineer/contractor. Ther-mal expansion/retraction is to beaccounted for by providing fixed/expansion point brackets• Expansion joints within supportprofiles must coincide with paneljoints

• Uninterrupted air circulation, frombottom to top, must be maintainedbehind Swisspearl facade panels• Do not install Swisspearl facadepanels/systems directly onto wallsurfaces of any kind• Do not use any sealant in con-nection with Swisspearl facade pa-nels

Storage and Handling• For off loading lift long palletsfrom short side, using fork extensi-ons. Otherwise lift from pallet longside, setting forks apart to preventpallet from bending.• When lifting pallet up by crane,attach pallet at sufficient supportpoints to prevent it from bending• Stacked Swisspearl panels to bestored under roof. If not possible (e.g. on building site) use tarpaulin tocover the pallets (the plastic shee-ting the pallets are wrapped in, isnot sufficient)

• Pallets/stacks always to beplaced horizontally, and to be keptoff the grade• Never slide panels across oneanother. Lift panels individually toavoid scratching• Panel stacks to be max. 500 mm (2’)high, do not stack more than 2 pallets.When re-stacking panels, insert foamfoil between each panel to protect thesurface. Protect stack adequately• All manufacturer’s labels, in-structions, DesignInstallationManuals must be made available tothe entire staff on building site.When re-stacking/re-palletising,the instructions must be attachedonto the new stacks/pallets such asto be noticed easily

Fabrication and Handling• Fabricate Swisspearl facade panelswith vacuum equipped power tools• Fabricate Swisspearl facade pa-nels with tools recommended bymanufacturer• Immediately remove fabricatingdust from panel• Never use sawing system withwater cooled blade

• After saw cutting, each paneledge must be sealed by usingLUKO impregnation liquid• Do not allow LUKO impregnationliquid to flow onto the panel face• Install Swisspearl facade panels/systems by contractors trained &instructed by Swisspearl/distributor• Make sure that dust is removedfrom face and back side of panelprior to it’s installation• If a panel is to be rested on it’sedge, use protection pads to avoiddamage

Cleaning• Do not clean Swisspearl facadepanels by dry methods• Immediately remove cement tainsby applying a solution of 10% aceticacid in water, allow to react 5-20 mi-nutes, but do not allow to dry out.Follow up with a cold, clean waterrinse. If required, use high pressurewater blaster at 40-80 bars (580-160psi), always test this methodon in-conspicuous panel area• Never clean a facade in thebright sun light