psychrometrics rev
TRANSCRIPT
PSYCHROMETRICSPSYCHROMETRICS
J.ILANGUMARANJ.ILANGUMARAN
Psychrometrics
Psychrometrics
The The PsychrometricPsychrometric ChartChart
COMFORT
“We air condition buildings to provide a comfortabl e environment for the occupants”
Temperature and Humidity:24oC DB and 60% RH for summer and 21oC DB and 50% RH for winter is energy efficient.
Air Movement: The terminal velocity, at neck level, should be designed for approximately 0.2m/s.
Air Freshness: For body odour dilution of 8l/s of fresh air per person should be introduced.If smokers are present 16l/s of fresh air is required.
Air Cleanliness: Selection of an adequate filtration system is very important and some types of air conditioning system permit better air cleansing than others.
Noise Levels: Careful selection of equipment and consideration of both external and internal noise pollution is important. A certain level of noise is necessary to mask clarity of individual conversations etc.
Relative Humidity:A minimum RH of 35% is recommended to prevent dry eyes, nose and throat.A maximum RH of 70% is recommended to prevent surface condensation and mould etc.Electrostatic charges can be generated at RH less than 45%.
-5 0 5 10 15 20 25 30 35 40
Dry Bulb Temperature oC
DRY BULB TEMPERATURE
0.005
0.01
0.015
0.02
Mo
istu
re C
on
ten
t kg
/kg
(D
ry A
ir)
MOISTURE CONTENT(Specific Humidity)
The weight of water in the air
21oC DB and 50% RH = 0.007857 kg/kg
0.007857kg/kg 1.186kg/m3 (air density)
= 0.66%
100% Relative Humidty(Saturation Curve)90%80%70%60%50%40%30%20%10%
RELATIVE HUMIDITY
RH is actual vapour pressurecompared to the vapour pressure at saturation for the same dry bulbtemperature.
COOLING
HEATING
COOLING & HEATING
DEWPOINTDewpoint is the temperature where
moisture begins to condense.
• Cool to dewpoint (from A to B)no change in moisture content.
• Further cooling (to C) water vapour condenseslowering the moisture content.
MoistureContent0.01kg/kg
Dewpoint
22oCDry
Bulb
AB
14oCDry
Bulb
COOL
COOL
C
10oCDry
Bulb
MoistureContent0.075kg/kg
A
B
C
Saturation Curve
WET BULB TEMPERATUREThe sling psychrometer is used to determine
the moisture content of the air.
Wet BulbThermometer
Dry BulbThermometer
WettedCotton wick
Handle
If air is saturated none of the moisture on the wick will evaporate and the WB temperature will be the same as the DB.If the air is less than saturated moisture will evaporatefrom the wick cooling the WB thermometer.
The difference between the WB and DB is called the WB depression.
WB T
empe
ratu
re o C
WET BULB TEMPERATURE
-50
5
10
15
20
25
15oC Dry Bulb
On the saturation curve WB and DBtemperatures are the same
Saturation Curve
The inverse of density is the Specific Volumem3 /kgThe volume increases with temperature increase.The density decreases with temperature increase.
1.32 1.3 1.28 1.26 1.24 1.22 1.2 1.18 1.16 1.14 1.12
Density kg/m3
DENSITY (Specific Weight)
7570
656055
5045
05
1015
20 2530
3540
0 5 10 15 20 25 30 35 40
45
50
55
60
65
70
75
80
85
90
95
100
Total Heat Content kJ/kg
-5-10
TOTAL HEAT CONTENT (SPECIFIC ENTHALPY)
0 1000 2000 3000
1.0
0.9
0.8
0.7
Altitude Metres
Specific EnthalpyCorrection Factor
SPECIFIC ENTHALPY CORRECTION FACTORDUE TO ALTITUDE
1
2
3
4
5
5
6
7
PSYCHROMETRIC DATA
1 DB Temperature = 24oC2 WB Temperature = 17oC3 RH = 50%4 Moisture Content = 0.0093kg/kg5 Total Heat Content = 48kj/kg6 Dewpoint = 13oC7 Saturated Moisture
Content = 0.0188kg/kg
COOLING
HEATING
COOLING & HEATING
COOLING CURVES Due to Cooling Coil inefficiencythe air loses moisture before it reaches the saturation curve.The cooling process of a Cooling coil follows the Cooling Curves.
HU
MID
IFY
ING
DE
HU
MID
IFY
ING
HUMIDIFYING To add moisture
DEHUMIDIFYING To remove moisture
SENSIBLE HEAT:A change in DB temperature. No change in moisture content.
LATENT HEAT:A change In moisture content . No change in DB temperature.
TOTAL HEAT (ENTHALPY):Sensible Heat + Latent Heat
Tota
lH
eat
TOTAL HEAT
Total
Heat
TOTAL COOLING
SensibleHeat
LatentHeat
Dehumidification
Humidification
Cooling & Dehumidification
Sensible Cooling Sensible Heating
Heating & HumidificationEvaporative Cooling
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
Brian Fossey
�Tech
Winter
Summer
THE COMFORT ZONE
CIRCULATIONZONE
Floor Conduction Sensible Gain
Light SensibleGain
To RoomCeiling
SensibleGainTo Room
Occupants GainSensible & Latent
Miscellaneous Equipment Sensible Gain
PERIMETERZONE
INTERIORZONE
Glass Solar &Conduction Sensible Gainto Room
Infiltration Gain - Sensible & Latentto Room
Wall Solar & Conduction Sensible Gainto Room
PERIMETERZONE
INTERIORZONE
Roof Solar & Conduction Sensible Gain to Ceiling Void
Floor Sensible Gain
To Room
CIRCULATIONZONE
Wall Solar & Conduction Sensible Gainto Ceiling Void
ROOM SENSIBLE HEAT FACTOR=
SENSIBLE HEATSENSIBLE HEAT + LATENT HEAT
=SENSIBLE HEAT
TOTAL HEAT
SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES
1.) Calculate SHF.
2.) Plot line through SHF ratio and plotting point.
3.) Plot line parallel to item 2.)through point of room condition.
SHF Plotting Point
Room Condition
SHF
Brian Fossey
�Tech
Heat gain from fan
RSHF - Room Sensible Heat FactorRoom Sensible and Latent Heat Gainsfrom Walls, windows, infiltration,people, lights and miscellaneousequipment
Condition of airleaving cooling coil
FAN COIL UNITS
Condition of airentering cooling coil
Room Condition
A
BC
B
C
A
AIR HANDLING UNIT SUPPLYING 100% OUTSIDE AIR
Filt
er
Hea
tin
g C
oil
Co
olin
g C
oil
Su
pp
ly F
an
Ou
tsid
e A
ir L
ou
vre
Hu
mid
ifie
r
A
B
D
C
Supply AirCondition
Leaving CoolingCoil Condition
Fan Gain
Brian Fossey
�Tech
AIR HANDLING UNIT SUPPLYING 100%
OUTSIDE AIR
Outside Air Summerand
Entering CoolingCoil Condition
SUMMER
A
C
D
A
B
D
C
Supply AirCondition
Preheater for Steam Humidifier
Preheater for Spray Humidifier
Spray Humidifier
Ste
am
Ste
am H
um
idif
ier
WINTERAIR HANDLING UNIT
SUPPLYING 100% OUTSIDE AIR
Fan GainA
B
C
Outside Air Winterand
Entering HeatingCoil Condition
B
D
A
B
D
C
Air ConditionedRoom
SupplyAir
ReturnAir
AIR HANDLING UNIT WITH RECIRCULATED AIR
B
Filt
er
Hea
tin
g C
oil
Co
olin
g C
oil
SupplyAirFanO
uts
ide
Air
Lo
uvr
e
Outside
Air
Disharge
Air
ReturnAirFan
Ou
tsid
e A
ir D
amp
erD
isch
arg
e L
ou
vre
Dis
char
ge
Dam
per
Recirculated Air
A
C
D EG
Hu
mid
ifie
r
F
SaturationCurve
RoomCondition
RSHF
B
B
Maximum60% RH
SaturationCurve Return Air
Fan Gain
CRecirculated AirCondition
B
BC
SaturationCurve Return Air
Fan Gain
CRecirculated AirCondition
Outside AirConditionSummer
A
B
B
A
C
SUMMER COOLING
SaturationCurve Return Air
Fan Gain
Outside AirConditionSummer
A
B
Outside Air and Recirculated AirMixture Condition
D
CRecirculated AirCondition
% Outside Air(minimum outside air)
% RecirculatedAir
B
A
C
D
SUMMER COOLING
SaturationCurve
A
B
Outside Air and Recirculated AirMixture Condition
D
C
Cooling Coil
B
A
C
D
SUMMER COOLING
SaturationCurve
A
B
Outside Air and Recirculated AirMixture Condition
D
C
Cooling Coil
Bypass Factornormally 10%of total coil
Leaving CoolingCoil Condition
E
ApparatusDewpoint
(ADP)
B
A
C
DE
SUMMER COOLING
SaturationCurve
A
B
D
C
Cooling CoilE
Supply AirFan Gain
Supply AirCondition G
B
A
C
DE
G
SUMMER COOLING
A
D
SaturationCurve
B C
E
Supply AirFan Gain
Supply AirCondition G
WINTER
B
A
C
DE
G
Minimum40% RH
Outside Air and Recirculated AirMixture Condition
% Outside Air(minimum outside air)
% RecirculatedAir
A
D
SaturationCurve
B C
F
Supply AirFan Gain
Supply AirCondition G
WINTER - SPRAY HUMIDIFIER
B
A
C
D G
F
Wet bulb Line
DMore than minimumoutside air is required
Spray Humidifier
In this situation a Preheater is not requiredfor daytime operation but would be neededfor morning warm-up.
A
D
SaturationCurve
B C
F
Supply AirFan Gain
Supply AirCondition G
WINTER - SPRAY HUMIDIFIER
B
A
C
D G
F
Wet bulb Line
Spray Humidifier
Preheat
Preheater required whenlow temperature or high %outside air
E
E
A
D
SaturationCurve
B C
F
Supply AirFan Gain
Supply AirCondition G
WINTER - STEAM HUMIDIFIER
B
A
C
D GF
DMore than minimumoutside air is required
Steam Humidifier
In this situation a Preheater is not requiredfor daytime operation but would be neededfor morning warm-up.
RoomCondition
Supply AirFan Gain
Outside AirConditionSummer
Return AirFan Gain
EnteringCooling CoilCondition
LeavingCooling CoilCondition
Supply AirCondition
% Return Air
RSHF
RSHF plotting
line
AIR HANDLING UNIT WITH RECIRCULATED AIROutside Air Condition Summer 32oC DB, 19oC WB.
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
Brian Fossey
�Tech
RoomCondition
Supply AirFan Gain
Return AirFan Gain
Outside AirConditionSummer
EnteringCooling CoilCondition
LeavingCooling CoilCondition
Supply AirCondition
RSHF RSHF plotting
line
AIR HANDLING UNIT WITH RECIRCULATED AIROutside Air Summer 28oC DB, 19oC WB.
PSYCHROMETRIC TERMS AND FORMULEA
ROOM CONDITIONSRSH = Room Sensible Heat (watts)
RLH = Room Latent Heat (watts)
RTH = Room Total Heat (watts) = RSH + RLH
RSHF = Room Sensible Heat Factor = RSH/RTH
OASH = Outside Air Sensible Heat - kW = OA volume m3/s X specific heat 1.02kj/kg oC X (OADB oC - Room DB oC) X density kg/m3
OUTSIDE AIR CONDITIONSOutside Air Volume m3/s = Number of occupants X 0.008 to 0.01m3/s
OATH = Outside Air Total Heat - kW = OA volume m3/s X (OA enthalpy kj/kg - Room enthalpy kj/kg) X OA density kg/m3
OALH = Outside Air Latent Heat - kW = OATH - OASH
TSH = Total Sensible Heat = RSH + OASH + *Air conditioning system gains* Includes supply air and return air fan gains, duct leakage sensible losses,return air gains from lights.
TOTAL CONDITIONS
TLH = Total Latent Heat = RLH + OALH + supply air duct leakage latent losses.
GTH = Grand Total Heat = TSH + TLH
GSHF = TSH/GTH
EFFECTIVE CONDITIONS
ERSH = Effective Room Sensible Heat= RSH + (BF* X OASH) + **Air conditioning system gains* BF = Cooling coil bypass factor (approximately 0.1)
** Includes supply air and return air fan gains, duct leakage sensible losses,return air gains from lights.
ERLH = Effective Room Latent Heat= RLH + (BF* X OALH) + **Air conditioning system gains* BF = Cooling coil bypass factor (approximately 0.1)** Includes supply air and return air fan gains, duct leakage latent losses,return air gains from lights.
ERTH = Effective Room Total Heat= ERSH + ERLH
ESHF = Effective Sensible Heat Factor = ERSH / ERTH
AIR VOLUME CALCULATIONS
Dehumidified Supply Air Volume m3/s= ERSH / Specific Heat 1.02 kj/kgoC X (RoomoC DB - ADPoC DB) X Density kg/m3
PsychrometricPsychrometricCalculationCalculation
ExampleExample
CIRCULATIONZONE
Floor Transmission Sensible Gain
Light SensibleGain
To RoomCeiling
SensibleGainTo Room
Occupants GainSensible & Latent
Miscellaneous Equipment Sensible Gain
PERIMETERZONE
INTERIORZONE
Glass Solar & Transmission Sensible Gainto Room
Infiltration Gain - Sensible & Latentto Room
Wall Solar & Transmission Sensible Gainto Room
PERIMETERZONE
INTERIORZONE
Roof Solar & Transmission Sensible Gain to Ceiling Void
Floor Sensible Gain
To Room
CIRCULATIONZONE
Wall Solar & Transmission Sensible Gainto Ceiling Void
BUILDING COOLING LOADS ASSOCIATED WITH AIR HANDLING UNIT No 1
ROOM COOLING LOADSSENSIBLE HEAT GAINS RSH1. Conduction Heat Gains:
walls, roof, ceiling, floor.2. Solar Heat Gains-
windows, Walls,Roof.3. Heat gains from lighting
load to space.4. Miscellaneous equipment:
computers, printers etc.5. OccupantsTotal= 329.45kWInfiltration Gain= -5.079kWTotal Space Gains= 325kW
LATENT HEAT GAINS RLH3. Occupants= 31.9kW4. Infiltration= 11.64kWTotal = 44kW
AIR CONDITIONING SYSTEM SYSTEM SENSIBLE HEAT GAINS SSH5. Supply air fan and motor. = 28.59kW6. Supply air duct gain. = 23.53kW7. Supply air duct leakage to areas
other than the air conditioned space. = 0
8. Heat gain from lights to the return air plenum via the ceiling void. = 27kW
9. Minimum Outside Air Volume =4.84m3/sHeat gain from minimum outside air OASH.To be calculated using Psychrometric data.
10. Return air fan and motor. = 10kW
Total = 89kW
SYSTEM LATENT HEAT GAINS SLH10. Cooling required to offset supply air
duct leakage to areas other than the air conditioned space. = 0
11. Heat gain from minimum outside air OALH.To be calculated using Psychrometric data.
Load peaks at 9am July when outside air condition is 21oC DB, 19oC WB
SYSTEM DESIGN CONDITIONS
Outside Air Summer = 21oC DB, 19oC WB
Outside Air Winter = - 4oC DB, 50% RH
Room Summer = 23oC DB, 60% RH
Room Winter = 21oC DB, 50% RH
Night set back room temperature winter = 10oC DB
B
A
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
Room 23oC DB, 60% RHB
Outside Air21oC DB, 19oC WB
A
SYSTEM DESIGN CONDITIONS
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
Minimum Outside Air = 4.84m3/s
Outside Air Total Heat (OATH)= OA air volume X (OA enthalpy - Room enthalpy ) X OA densityThe data in blue italics can be derived from the Psychrometric chart or from tables
= OA m3/s X (OA kj/kg - Room kj/kg) X OA kg/m3
= 4.84 X (54 - 50) X 1.19 = 23kW
Outside Air Sensible Heat (OASH)= OA air volume X specific heat X density X (OADB oC - Room DB oC)= OA m3/s X kj/kg oC X kg/m3 X (OADB oC - Room DB oC)= 4.84 X 1.02 X 1.16 X (21 - 23) = -11kW
Outside Air Latent Heat (OALH)= OATH - OASH = 23 - -11 = 34kW
MINIMUM OUTSIDE AIR
EFFECTIVE ROOM SENSIBLE HEAT FACTOR
Effective Room Sensible Heat (ERSH)= RSH + (Bypass factor BF X OASH) + SSHBF assume cooling coil is 10% efficient = 0.1
= 325 + (0.1 X -11) + 89 = 413kW
Effective Room Latent Heat (ERLH)= RLH + (Bypass factor BF X OALH) + SLH= 44 + (0.1 X 34) + 0 = 47kW
Effective Room Total Heat (ERTH)= ERSH + ERLH = 413 + 47 = 460kW
Effective Room Sensible Heat Factor= ERSH/ERTH = 413/460 = 0.9
SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES
1.) Calculate SHF.
2.) Plot line through SHF ratio and plotting point.
3.) Plot line parallel to item 2.)through point of room condition.
SHF Plotting Point
Room Condition
SHF
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
B
ESHF = 0.9
EFFECTIVE ROOM SENSIBLE HEAT FACTOR
ERSHF
Room 23oC DB, 60% RH
A
Outside Air21oC DB, 19oC WB
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
APPARATUS DEWPOINT ADP
The ADP is at the point where the ESHF intersects the Saturation Curve.
ADP = 14.2oC DB and WB
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
B
ESHF = 0.9ADP = 14.2oC DB and WB
APPARATUS DEWPOINT ADP
Room 23oC DB, 60% RH
A
Outside Air21oC DB, 19oC WB
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
Total Sensible Heat (TSH)= RSH + OASH + SSH = 325 + (-11) + 89 = 403kW
Total Latent Heat (TLH)= RLH + OALH + SLH = 44 + 33 + 0 = 77kW
Grand Total Heat (GTH)= TSH + TLH = 403 + 77 = 480kW
Grand Sensible Heat Factor
= TSH/GTH = 403/480 = 0.84
GRAND SENSIBLE HEAT FACTOR
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
BESHF = 0.9ADP = 14.2oC DB and WB
GRAND SENSIBLE HEAT FACTORGSHF
Room 23oC DB, 60% RH
GSHF = 0.84
A
Outside Air21oC DB, 19oC WB
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
SUPPLY AIR VOLUME
Supply Air Volume m3/s
= ERSH/Specific Heat X (Room oC DB - ADP oC DB) X Supply Air Density*
= 413kW/ 1.02kj/kgoC X (23 - 14.2) x 1.215kg/m3
Supply Air Volume = 38 m3/s
RETURN AIR SYSTEM GAINS
Return Air System Heat Gain = (Return Air Fan + Lighting gain to return air)= 10+27 = 37kW
Temperature rise due to return air system gain= (Return air System gain) - divided bySpecific heat X Supply Air Volume X (1 - % pressurisation air remaining in the building)* X Density of room air= 37kW/ 1.02kj/kgoC X 38m3/s X (1- 0.1) X 1.19kg/m3 = 0.9oC
Recirculated Air = 23 + 0.9 = 24oC
* Assume that 10% of the total air remains in the space to pressurise the building to offset some of the effects of infiltration and for makeup air to toilet exhaust.
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
BESHF = 0.9ADP = 14.2oC DB and WB
RETURN AIR SYSTEM GAIN
Room 23oC DB, 60% RH
GSHF = 0.84 Recirculated Air ConditionC
A
Outside Air21oC DB, 19oC WB
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
BESHF = 0.9ADP = 14.2oC DB and WB
MIXED AIR CONDITION
Room 23oC DB, 60% RH
GSHF = 0.84Recirculated Air Condition
Mixed Air Condition D
C
A
Outside Air21oC DB, 19oC WB
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
PERCENTAGE OUTSIDE AIR
The percentage of Minimum Outside Air to Supply Air Volume = Minimum Outside Air Volume / Supply air Volume= 4.84m3/s divided by 38m3/s
4.84/38 = 12.74%
Check the location of the mixed air condition
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
ESHF = 0.9ADP = 14.2oC DB and WB
MIXED AIR CONDITIONCHECK
GSHF = 0.84
A
Outside Air21oC DB, 19oC WB
12.74%100%
87.26%Mixed Air Condition
Recirculated Air Condition
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
BYPASS FACTOR BF
Due to the cooling coil inefficiency assume thatthe air bypassing the coil is 10% of the total air
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
BESHF = 0.9
ADP = 14.2oC DB and WB
BYPASS FACTOR BF
Room 23oC DB, 60% RH
GSHF = 0.84Recirculated Air Condition
BF Bypass Factor10% of length of GSHF
C
D
F
A
Outside Air21oC DB, 19oC WB
Mixed Air Condition
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
COOLING COIL
Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB
Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB
D
F
ROOM SENSIBLE HEAT FACTOR RSHF
Room Sensible Heat RSH = 325kW
Room Latent Heat RLH = 44kW
Room Total Heat RTH = 325 + 44 = 369kW
Room Sensible Heat Factor = 325/369 = 0.88
RSHF = 0.88
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
B
ESHF = 0.9
ADP = 14.2oC DB and WB
ROOM SENSIBLE HEAT FACTORRSHF
Room 23oC DB, 60% RH
GSHF = 0.88Recirculated Air Condition
BF Bypass Factor10% of length of GSHF
RSHF = 0.88 C
D
F
AOutside Air21oC DB, 19oC WB
Mixed Air Condition
�TechYORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
SUPPLY AIR SYSTEM GAINS
Temperature rise due to SUPPLY air system gain
= Supply air System gaindivided by
Density of supply air XSpecific heat X Supply Air Volume
= 52kW 1.215kg/m3 X 1.02kj/kgoC X 38m3/s= 1.1oCFinal Supply Air condition = 15.5 + 1.1 = 16.6oC DB
SYSTEM SENSIBLE HEAT GAINS SSHSupply air fan and motor.Supply air duct heat gain.Cooling required to offset supply airduct leakage to areas other than the air conditioned space.
SSH = 28.59 + 23.53 = 52kW
WB T
empe
ratu
re o C
10
15
20
10 15 20 25 30Dry Bulb Temperature oC
B
A
C
D GF
B
ESHF = 0.9
ADP = 14.2oC DB and WB
SUPPLY AIR HEAT GAIN
Room 23oC DB, 60% RH
GSHF = 0.88
Recirculated Air Condition
Mixed Air Condition(Coil Entering Condition)
BF Bypass Factor10% of length of GSHF
RSHF = 0.89
Supply Air Condition
F
G
Coil LeavingCondition
D
AOutside Air21oC DB, 19oC WB
Mixed Air Condition
�YORK Production System
All rights Reserved
Copyright 1999 by York International Inc.Brian Fossey 03/99
SUMMARY - AIR HANDLING UNIT SUMMER CONDITIONS
FANS
Supply Fan Air Volume = 38m3/s
Return Air Fan Air Volume = 38 X 0.9* = 34.2m3/s* 10% air remains in the air conditioned space to o ffsettoilet exhaust and for pressurisation against infil tration.
COOLING COIL
Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB
Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB
Supply Air condition = 16.6oC DB, 15.2oC WB
WINTER MIXED AIR CONDITION
Outside Air DB oC = - 4
Recirculated Air DB oC = 21 + 1(Return Air Gain) = 22
Minimum Outside Air = 12.74%
0.1274 X - 4 = -0.510.8726 X 22 = 19.2Mixed Air DB oC = 18.69
20
15
10
5
0
-5
-5 0 5 10 15 20 25
WB Temperature o C
Dry Bulb Temperature oC
Room Winter21oC DB, 50% RH
RSHF = 0.89
B
A
C
D GF
Mixed Air Conditionwith minimum Outside Air
RecirculatedAir Condition
B
C
DIncreased Outside Air Volume
SteamHumidifier
D
FG
STEAM HUMIDIFIER
Increase Moisture Content by0.0025kg/kg
Outside Air Winter
20
15
10
5
0
-5
-5 0 5 10 15 20 25
WB Temperature o C
Dry Bulb Temperature oC
Room Winter21oC DB, 50% RH
RSHF = 0.89
B
A
C
D GF
Mixed Air Conditionwith minimum Outside Air
RecirculatedAir Condition
B
C
D
Increased Outside Air Volume
SprayHumidifier
D
FG
SPRAY HUMIDIFIER
Increase Moisture Content by0.0015kg/kg
Outside Air Winter
HUMIDIFIER SIZING
Increase moisture content by 0.0025kg/kg
Density = 1.24 kg/m3
Steam Volume = 38m3/s X 3600 (m3/hour) X 0.0025kg/kg X 1.24kg/m3
= 424kg/Hour
STEAM HUMIDIFIER
SPRAY HUMIDIFIER
Increase moisture content by 0.0015kg/kg
Density = 1.24 kg/m3
20
15
10
5
0
-5
-5 0 5 10 15 20 25
WB Temperature o C
Dry Bulb Temperature oC
Room Winter21oC DB, 50% RH
RSHF = 0.89
B
A
C
D GF
RecirculatedAir Condition
B
C
D
SteamHumidifier
D
FG
STEAM HUMIDIFIERWITH PREHEAT
Increase Moisture Content by0.0025kg/kg
Outside Air Winter
Mixed Air Conditionwith high percentageof minimum Outside Air
Preheater
20
15
10
5
0
-5
-5 0 5 10 15 20 25
WB Temperature o C
Dry Bulb Temperature oC
Room Winter21oC DB, 50% RH
RSHF = 0.89
B
A
C
D GF
Mixed Air Conditionwith high percentage ofminimum Outside Air
RecirculatedAir Condition
B
C
SprayHumidifier
D
FG
SPRAY HUMIDIFIERWITH PREHEAT
Increase Moisture Content by0.0015kg/kg
Outside Air Winter
Preheater
20
15
10
5
0
-5
-5 0 5 10 15 20 25
WB Temperature o C
Dry Bulb Temperature oC
Room Winter21oC DB, 50% RH
RSHF = 0.89
A
C
DGF
Mixed Air Conditionwith minimum Outside Air
RecirculatedAir Condition
B
C
SprayHumidifier
D
FG
REHEAT
Increase Moisture Content by0.0015kg/kg
Outside Air Winter
Preheater
Reheater
B
H
H