psychrometrics rev

82
PSYCHROMETRICS PSYCHROMETRICS J.ILANGUMARAN J.ILANGUMARAN

Upload: api-25999517

Post on 10-Apr-2015

1.592 views

Category:

Documents


9 download

TRANSCRIPT

Page 1: Psychrometrics Rev

PSYCHROMETRICSPSYCHROMETRICS

J.ILANGUMARANJ.ILANGUMARAN

Page 2: Psychrometrics Rev

Psychrometrics

Psychrometrics

The The PsychrometricPsychrometric ChartChart

Page 3: Psychrometrics Rev

COMFORT

“We air condition buildings to provide a comfortabl e environment for the occupants”

Temperature and Humidity:24oC DB and 60% RH for summer and 21oC DB and 50% RH for winter is energy efficient.

Air Movement: The terminal velocity, at neck level, should be designed for approximately 0.2m/s.

Air Freshness: For body odour dilution of 8l/s of fresh air per person should be introduced.If smokers are present 16l/s of fresh air is required.

Air Cleanliness: Selection of an adequate filtration system is very important and some types of air conditioning system permit better air cleansing than others.

Noise Levels: Careful selection of equipment and consideration of both external and internal noise pollution is important. A certain level of noise is necessary to mask clarity of individual conversations etc.

Relative Humidity:A minimum RH of 35% is recommended to prevent dry eyes, nose and throat.A maximum RH of 70% is recommended to prevent surface condensation and mould etc.Electrostatic charges can be generated at RH less than 45%.

Page 4: Psychrometrics Rev
Page 5: Psychrometrics Rev

-5 0 5 10 15 20 25 30 35 40

Dry Bulb Temperature oC

DRY BULB TEMPERATURE

Page 6: Psychrometrics Rev

0.005

0.01

0.015

0.02

Mo

istu

re C

on

ten

t kg

/kg

(D

ry A

ir)

MOISTURE CONTENT(Specific Humidity)

The weight of water in the air

21oC DB and 50% RH = 0.007857 kg/kg

0.007857kg/kg 1.186kg/m3 (air density)

= 0.66%

Page 7: Psychrometrics Rev

100% Relative Humidty(Saturation Curve)90%80%70%60%50%40%30%20%10%

RELATIVE HUMIDITY

RH is actual vapour pressurecompared to the vapour pressure at saturation for the same dry bulbtemperature.

Page 8: Psychrometrics Rev

COOLING

HEATING

COOLING & HEATING

Page 9: Psychrometrics Rev

DEWPOINTDewpoint is the temperature where

moisture begins to condense.

• Cool to dewpoint (from A to B)no change in moisture content.

• Further cooling (to C) water vapour condenseslowering the moisture content.

MoistureContent0.01kg/kg

Dewpoint

22oCDry

Bulb

AB

14oCDry

Bulb

COOL

COOL

C

10oCDry

Bulb

MoistureContent0.075kg/kg

A

B

C

Saturation Curve

Page 10: Psychrometrics Rev

WET BULB TEMPERATUREThe sling psychrometer is used to determine

the moisture content of the air.

Wet BulbThermometer

Dry BulbThermometer

WettedCotton wick

Handle

If air is saturated none of the moisture on the wick will evaporate and the WB temperature will be the same as the DB.If the air is less than saturated moisture will evaporatefrom the wick cooling the WB thermometer.

The difference between the WB and DB is called the WB depression.

Page 11: Psychrometrics Rev

WB T

empe

ratu

re o C

WET BULB TEMPERATURE

-50

5

10

15

20

25

15oC Dry Bulb

On the saturation curve WB and DBtemperatures are the same

Saturation Curve

Page 12: Psychrometrics Rev

The inverse of density is the Specific Volumem3 /kgThe volume increases with temperature increase.The density decreases with temperature increase.

1.32 1.3 1.28 1.26 1.24 1.22 1.2 1.18 1.16 1.14 1.12

Density kg/m3

DENSITY (Specific Weight)

Page 13: Psychrometrics Rev

7570

656055

5045

05

1015

20 2530

3540

0 5 10 15 20 25 30 35 40

45

50

55

60

65

70

75

80

85

90

95

100

Total Heat Content kJ/kg

-5-10

TOTAL HEAT CONTENT (SPECIFIC ENTHALPY)

Page 14: Psychrometrics Rev

0 1000 2000 3000

1.0

0.9

0.8

0.7

Altitude Metres

Specific EnthalpyCorrection Factor

SPECIFIC ENTHALPY CORRECTION FACTORDUE TO ALTITUDE

Page 15: Psychrometrics Rev

1

2

3

4

5

5

6

7

PSYCHROMETRIC DATA

1 DB Temperature = 24oC2 WB Temperature = 17oC3 RH = 50%4 Moisture Content = 0.0093kg/kg5 Total Heat Content = 48kj/kg6 Dewpoint = 13oC7 Saturated Moisture

Content = 0.0188kg/kg

Page 16: Psychrometrics Rev

COOLING

HEATING

COOLING & HEATING

Page 17: Psychrometrics Rev

COOLING CURVES Due to Cooling Coil inefficiencythe air loses moisture before it reaches the saturation curve.The cooling process of a Cooling coil follows the Cooling Curves.

Page 18: Psychrometrics Rev

HU

MID

IFY

ING

DE

HU

MID

IFY

ING

HUMIDIFYING To add moisture

DEHUMIDIFYING To remove moisture

Page 19: Psychrometrics Rev

SENSIBLE HEAT:A change in DB temperature. No change in moisture content.

LATENT HEAT:A change In moisture content . No change in DB temperature.

TOTAL HEAT (ENTHALPY):Sensible Heat + Latent Heat

Page 20: Psychrometrics Rev

Tota

lH

eat

TOTAL HEAT

Page 21: Psychrometrics Rev

Total

Heat

TOTAL COOLING

SensibleHeat

LatentHeat

Page 22: Psychrometrics Rev

Dehumidification

Humidification

Cooling & Dehumidification

Sensible Cooling Sensible Heating

Heating & HumidificationEvaporative Cooling

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 23: Psychrometrics Rev

Brian Fossey

�Tech

Winter

Summer

THE COMFORT ZONE

Page 24: Psychrometrics Rev

CIRCULATIONZONE

Floor Conduction Sensible Gain

Light SensibleGain

To RoomCeiling

SensibleGainTo Room

Occupants GainSensible & Latent

Miscellaneous Equipment Sensible Gain

PERIMETERZONE

INTERIORZONE

Glass Solar &Conduction Sensible Gainto Room

Infiltration Gain - Sensible & Latentto Room

Wall Solar & Conduction Sensible Gainto Room

PERIMETERZONE

INTERIORZONE

Roof Solar & Conduction Sensible Gain to Ceiling Void

Floor Sensible Gain

To Room

CIRCULATIONZONE

Wall Solar & Conduction Sensible Gainto Ceiling Void

Page 25: Psychrometrics Rev

ROOM SENSIBLE HEAT FACTOR=

SENSIBLE HEATSENSIBLE HEAT + LATENT HEAT

=SENSIBLE HEAT

TOTAL HEAT

Page 26: Psychrometrics Rev

SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES

1.) Calculate SHF.

2.) Plot line through SHF ratio and plotting point.

3.) Plot line parallel to item 2.)through point of room condition.

SHF Plotting Point

Room Condition

SHF

Page 27: Psychrometrics Rev

Brian Fossey

�Tech

Heat gain from fan

RSHF - Room Sensible Heat FactorRoom Sensible and Latent Heat Gainsfrom Walls, windows, infiltration,people, lights and miscellaneousequipment

Condition of airleaving cooling coil

FAN COIL UNITS

Condition of airentering cooling coil

Room Condition

A

BC

B

C

A

Page 28: Psychrometrics Rev

AIR HANDLING UNIT SUPPLYING 100% OUTSIDE AIR

Filt

er

Hea

tin

g C

oil

Co

olin

g C

oil

Su

pp

ly F

an

Ou

tsid

e A

ir L

ou

vre

Hu

mid

ifie

r

A

B

D

C

Page 29: Psychrometrics Rev

Supply AirCondition

Leaving CoolingCoil Condition

Fan Gain

Brian Fossey

�Tech

AIR HANDLING UNIT SUPPLYING 100%

OUTSIDE AIR

Outside Air Summerand

Entering CoolingCoil Condition

SUMMER

A

C

D

A

B

D

C

Page 30: Psychrometrics Rev

Supply AirCondition

Preheater for Steam Humidifier

Preheater for Spray Humidifier

Spray Humidifier

Ste

am

Ste

am H

um

idif

ier

WINTERAIR HANDLING UNIT

SUPPLYING 100% OUTSIDE AIR

Fan GainA

B

C

Outside Air Winterand

Entering HeatingCoil Condition

B

D

A

B

D

C

Page 31: Psychrometrics Rev

Air ConditionedRoom

SupplyAir

ReturnAir

AIR HANDLING UNIT WITH RECIRCULATED AIR

B

Filt

er

Hea

tin

g C

oil

Co

olin

g C

oil

SupplyAirFanO

uts

ide

Air

Lo

uvr

e

Outside

Air

Disharge

Air

ReturnAirFan

Ou

tsid

e A

ir D

amp

erD

isch

arg

e L

ou

vre

Dis

char

ge

Dam

per

Recirculated Air

A

C

D EG

Hu

mid

ifie

r

F

Page 32: Psychrometrics Rev

SaturationCurve

RoomCondition

RSHF

B

B

Maximum60% RH

Page 33: Psychrometrics Rev

SaturationCurve Return Air

Fan Gain

CRecirculated AirCondition

B

BC

Page 34: Psychrometrics Rev

SaturationCurve Return Air

Fan Gain

CRecirculated AirCondition

Outside AirConditionSummer

A

B

B

A

C

SUMMER COOLING

Page 35: Psychrometrics Rev

SaturationCurve Return Air

Fan Gain

Outside AirConditionSummer

A

B

Outside Air and Recirculated AirMixture Condition

D

CRecirculated AirCondition

% Outside Air(minimum outside air)

% RecirculatedAir

B

A

C

D

SUMMER COOLING

Page 36: Psychrometrics Rev

SaturationCurve

A

B

Outside Air and Recirculated AirMixture Condition

D

C

Cooling Coil

B

A

C

D

SUMMER COOLING

Page 37: Psychrometrics Rev

SaturationCurve

A

B

Outside Air and Recirculated AirMixture Condition

D

C

Cooling Coil

Bypass Factornormally 10%of total coil

Leaving CoolingCoil Condition

E

ApparatusDewpoint

(ADP)

B

A

C

DE

SUMMER COOLING

Page 38: Psychrometrics Rev

SaturationCurve

A

B

D

C

Cooling CoilE

Supply AirFan Gain

Supply AirCondition G

B

A

C

DE

G

SUMMER COOLING

Page 39: Psychrometrics Rev

A

D

SaturationCurve

B C

E

Supply AirFan Gain

Supply AirCondition G

WINTER

B

A

C

DE

G

Minimum40% RH

Outside Air and Recirculated AirMixture Condition

% Outside Air(minimum outside air)

% RecirculatedAir

Page 40: Psychrometrics Rev

A

D

SaturationCurve

B C

F

Supply AirFan Gain

Supply AirCondition G

WINTER - SPRAY HUMIDIFIER

B

A

C

D G

F

Wet bulb Line

DMore than minimumoutside air is required

Spray Humidifier

In this situation a Preheater is not requiredfor daytime operation but would be neededfor morning warm-up.

Page 41: Psychrometrics Rev

A

D

SaturationCurve

B C

F

Supply AirFan Gain

Supply AirCondition G

WINTER - SPRAY HUMIDIFIER

B

A

C

D G

F

Wet bulb Line

Spray Humidifier

Preheat

Preheater required whenlow temperature or high %outside air

E

E

Page 42: Psychrometrics Rev

A

D

SaturationCurve

B C

F

Supply AirFan Gain

Supply AirCondition G

WINTER - STEAM HUMIDIFIER

B

A

C

D GF

DMore than minimumoutside air is required

Steam Humidifier

In this situation a Preheater is not requiredfor daytime operation but would be neededfor morning warm-up.

Page 43: Psychrometrics Rev

RoomCondition

Supply AirFan Gain

Outside AirConditionSummer

Return AirFan Gain

EnteringCooling CoilCondition

LeavingCooling CoilCondition

Supply AirCondition

% Return Air

RSHF

RSHF plotting

line

AIR HANDLING UNIT WITH RECIRCULATED AIROutside Air Condition Summer 32oC DB, 19oC WB.

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 44: Psychrometrics Rev

Brian Fossey

�Tech

RoomCondition

Supply AirFan Gain

Return AirFan Gain

Outside AirConditionSummer

EnteringCooling CoilCondition

LeavingCooling CoilCondition

Supply AirCondition

RSHF RSHF plotting

line

AIR HANDLING UNIT WITH RECIRCULATED AIROutside Air Summer 28oC DB, 19oC WB.

Page 45: Psychrometrics Rev

PSYCHROMETRIC TERMS AND FORMULEA

ROOM CONDITIONSRSH = Room Sensible Heat (watts)

RLH = Room Latent Heat (watts)

RTH = Room Total Heat (watts) = RSH + RLH

RSHF = Room Sensible Heat Factor = RSH/RTH

OASH = Outside Air Sensible Heat - kW = OA volume m3/s X specific heat 1.02kj/kg oC X (OADB oC - Room DB oC) X density kg/m3

OUTSIDE AIR CONDITIONSOutside Air Volume m3/s = Number of occupants X 0.008 to 0.01m3/s

OATH = Outside Air Total Heat - kW = OA volume m3/s X (OA enthalpy kj/kg - Room enthalpy kj/kg) X OA density kg/m3

OALH = Outside Air Latent Heat - kW = OATH - OASH

Page 46: Psychrometrics Rev

TSH = Total Sensible Heat = RSH + OASH + *Air conditioning system gains* Includes supply air and return air fan gains, duct leakage sensible losses,return air gains from lights.

TOTAL CONDITIONS

TLH = Total Latent Heat = RLH + OALH + supply air duct leakage latent losses.

GTH = Grand Total Heat = TSH + TLH

GSHF = TSH/GTH

Page 47: Psychrometrics Rev

EFFECTIVE CONDITIONS

ERSH = Effective Room Sensible Heat= RSH + (BF* X OASH) + **Air conditioning system gains* BF = Cooling coil bypass factor (approximately 0.1)

** Includes supply air and return air fan gains, duct leakage sensible losses,return air gains from lights.

ERLH = Effective Room Latent Heat= RLH + (BF* X OALH) + **Air conditioning system gains* BF = Cooling coil bypass factor (approximately 0.1)** Includes supply air and return air fan gains, duct leakage latent losses,return air gains from lights.

ERTH = Effective Room Total Heat= ERSH + ERLH

ESHF = Effective Sensible Heat Factor = ERSH / ERTH

Page 48: Psychrometrics Rev

AIR VOLUME CALCULATIONS

Dehumidified Supply Air Volume m3/s= ERSH / Specific Heat 1.02 kj/kgoC X (RoomoC DB - ADPoC DB) X Density kg/m3

Page 49: Psychrometrics Rev

PsychrometricPsychrometricCalculationCalculation

ExampleExample

Page 50: Psychrometrics Rev

CIRCULATIONZONE

Floor Transmission Sensible Gain

Light SensibleGain

To RoomCeiling

SensibleGainTo Room

Occupants GainSensible & Latent

Miscellaneous Equipment Sensible Gain

PERIMETERZONE

INTERIORZONE

Glass Solar & Transmission Sensible Gainto Room

Infiltration Gain - Sensible & Latentto Room

Wall Solar & Transmission Sensible Gainto Room

PERIMETERZONE

INTERIORZONE

Roof Solar & Transmission Sensible Gain to Ceiling Void

Floor Sensible Gain

To Room

CIRCULATIONZONE

Wall Solar & Transmission Sensible Gainto Ceiling Void

Page 51: Psychrometrics Rev

BUILDING COOLING LOADS ASSOCIATED WITH AIR HANDLING UNIT No 1

ROOM COOLING LOADSSENSIBLE HEAT GAINS RSH1. Conduction Heat Gains:

walls, roof, ceiling, floor.2. Solar Heat Gains-

windows, Walls,Roof.3. Heat gains from lighting

load to space.4. Miscellaneous equipment:

computers, printers etc.5. OccupantsTotal= 329.45kWInfiltration Gain= -5.079kWTotal Space Gains= 325kW

LATENT HEAT GAINS RLH3. Occupants= 31.9kW4. Infiltration= 11.64kWTotal = 44kW

AIR CONDITIONING SYSTEM SYSTEM SENSIBLE HEAT GAINS SSH5. Supply air fan and motor. = 28.59kW6. Supply air duct gain. = 23.53kW7. Supply air duct leakage to areas

other than the air conditioned space. = 0

8. Heat gain from lights to the return air plenum via the ceiling void. = 27kW

9. Minimum Outside Air Volume =4.84m3/sHeat gain from minimum outside air OASH.To be calculated using Psychrometric data.

10. Return air fan and motor. = 10kW

Total = 89kW

SYSTEM LATENT HEAT GAINS SLH10. Cooling required to offset supply air

duct leakage to areas other than the air conditioned space. = 0

11. Heat gain from minimum outside air OALH.To be calculated using Psychrometric data.

Load peaks at 9am July when outside air condition is 21oC DB, 19oC WB

Page 52: Psychrometrics Rev

SYSTEM DESIGN CONDITIONS

Outside Air Summer = 21oC DB, 19oC WB

Outside Air Winter = - 4oC DB, 50% RH

Room Summer = 23oC DB, 60% RH

Room Winter = 21oC DB, 50% RH

Night set back room temperature winter = 10oC DB

Page 53: Psychrometrics Rev

B

A

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

Room 23oC DB, 60% RHB

Outside Air21oC DB, 19oC WB

A

SYSTEM DESIGN CONDITIONS

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 54: Psychrometrics Rev

Minimum Outside Air = 4.84m3/s

Outside Air Total Heat (OATH)= OA air volume X (OA enthalpy - Room enthalpy ) X OA densityThe data in blue italics can be derived from the Psychrometric chart or from tables

= OA m3/s X (OA kj/kg - Room kj/kg) X OA kg/m3

= 4.84 X (54 - 50) X 1.19 = 23kW

Outside Air Sensible Heat (OASH)= OA air volume X specific heat X density X (OADB oC - Room DB oC)= OA m3/s X kj/kg oC X kg/m3 X (OADB oC - Room DB oC)= 4.84 X 1.02 X 1.16 X (21 - 23) = -11kW

Outside Air Latent Heat (OALH)= OATH - OASH = 23 - -11 = 34kW

MINIMUM OUTSIDE AIR

Page 55: Psychrometrics Rev

EFFECTIVE ROOM SENSIBLE HEAT FACTOR

Effective Room Sensible Heat (ERSH)= RSH + (Bypass factor BF X OASH) + SSHBF assume cooling coil is 10% efficient = 0.1

= 325 + (0.1 X -11) + 89 = 413kW

Effective Room Latent Heat (ERLH)= RLH + (Bypass factor BF X OALH) + SLH= 44 + (0.1 X 34) + 0 = 47kW

Effective Room Total Heat (ERTH)= ERSH + ERLH = 413 + 47 = 460kW

Effective Room Sensible Heat Factor= ERSH/ERTH = 413/460 = 0.9

Page 56: Psychrometrics Rev

SENSIBLE HEAT FACTOR (ESHF, GSHF, RSHF) LINES

1.) Calculate SHF.

2.) Plot line through SHF ratio and plotting point.

3.) Plot line parallel to item 2.)through point of room condition.

SHF Plotting Point

Room Condition

SHF

Page 57: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

B

ESHF = 0.9

EFFECTIVE ROOM SENSIBLE HEAT FACTOR

ERSHF

Room 23oC DB, 60% RH

A

Outside Air21oC DB, 19oC WB

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 58: Psychrometrics Rev

APPARATUS DEWPOINT ADP

The ADP is at the point where the ESHF intersects the Saturation Curve.

ADP = 14.2oC DB and WB

Page 59: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

B

ESHF = 0.9ADP = 14.2oC DB and WB

APPARATUS DEWPOINT ADP

Room 23oC DB, 60% RH

A

Outside Air21oC DB, 19oC WB

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 60: Psychrometrics Rev

Total Sensible Heat (TSH)= RSH + OASH + SSH = 325 + (-11) + 89 = 403kW

Total Latent Heat (TLH)= RLH + OALH + SLH = 44 + 33 + 0 = 77kW

Grand Total Heat (GTH)= TSH + TLH = 403 + 77 = 480kW

Grand Sensible Heat Factor

= TSH/GTH = 403/480 = 0.84

GRAND SENSIBLE HEAT FACTOR

Page 61: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

BESHF = 0.9ADP = 14.2oC DB and WB

GRAND SENSIBLE HEAT FACTORGSHF

Room 23oC DB, 60% RH

GSHF = 0.84

A

Outside Air21oC DB, 19oC WB

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 62: Psychrometrics Rev

SUPPLY AIR VOLUME

Supply Air Volume m3/s

= ERSH/Specific Heat X (Room oC DB - ADP oC DB) X Supply Air Density*

= 413kW/ 1.02kj/kgoC X (23 - 14.2) x 1.215kg/m3

Supply Air Volume = 38 m3/s

Page 63: Psychrometrics Rev

RETURN AIR SYSTEM GAINS

Return Air System Heat Gain = (Return Air Fan + Lighting gain to return air)= 10+27 = 37kW

Temperature rise due to return air system gain= (Return air System gain) - divided bySpecific heat X Supply Air Volume X (1 - % pressurisation air remaining in the building)* X Density of room air= 37kW/ 1.02kj/kgoC X 38m3/s X (1- 0.1) X 1.19kg/m3 = 0.9oC

Recirculated Air = 23 + 0.9 = 24oC

* Assume that 10% of the total air remains in the space to pressurise the building to offset some of the effects of infiltration and for makeup air to toilet exhaust.

Page 64: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

BESHF = 0.9ADP = 14.2oC DB and WB

RETURN AIR SYSTEM GAIN

Room 23oC DB, 60% RH

GSHF = 0.84 Recirculated Air ConditionC

A

Outside Air21oC DB, 19oC WB

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 65: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

BESHF = 0.9ADP = 14.2oC DB and WB

MIXED AIR CONDITION

Room 23oC DB, 60% RH

GSHF = 0.84Recirculated Air Condition

Mixed Air Condition D

C

A

Outside Air21oC DB, 19oC WB

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 66: Psychrometrics Rev

PERCENTAGE OUTSIDE AIR

The percentage of Minimum Outside Air to Supply Air Volume = Minimum Outside Air Volume / Supply air Volume= 4.84m3/s divided by 38m3/s

4.84/38 = 12.74%

Check the location of the mixed air condition

Page 67: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

ESHF = 0.9ADP = 14.2oC DB and WB

MIXED AIR CONDITIONCHECK

GSHF = 0.84

A

Outside Air21oC DB, 19oC WB

12.74%100%

87.26%Mixed Air Condition

Recirculated Air Condition

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 68: Psychrometrics Rev

BYPASS FACTOR BF

Due to the cooling coil inefficiency assume thatthe air bypassing the coil is 10% of the total air

Page 69: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

BESHF = 0.9

ADP = 14.2oC DB and WB

BYPASS FACTOR BF

Room 23oC DB, 60% RH

GSHF = 0.84Recirculated Air Condition

BF Bypass Factor10% of length of GSHF

C

D

F

A

Outside Air21oC DB, 19oC WB

Mixed Air Condition

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 70: Psychrometrics Rev

COOLING COIL

Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB

Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB

D

F

Page 71: Psychrometrics Rev

ROOM SENSIBLE HEAT FACTOR RSHF

Room Sensible Heat RSH = 325kW

Room Latent Heat RLH = 44kW

Room Total Heat RTH = 325 + 44 = 369kW

Room Sensible Heat Factor = 325/369 = 0.88

RSHF = 0.88

Page 72: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

B

ESHF = 0.9

ADP = 14.2oC DB and WB

ROOM SENSIBLE HEAT FACTORRSHF

Room 23oC DB, 60% RH

GSHF = 0.88Recirculated Air Condition

BF Bypass Factor10% of length of GSHF

RSHF = 0.88 C

D

F

AOutside Air21oC DB, 19oC WB

Mixed Air Condition

�TechYORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 73: Psychrometrics Rev

SUPPLY AIR SYSTEM GAINS

Temperature rise due to SUPPLY air system gain

= Supply air System gaindivided by

Density of supply air XSpecific heat X Supply Air Volume

= 52kW 1.215kg/m3 X 1.02kj/kgoC X 38m3/s= 1.1oCFinal Supply Air condition = 15.5 + 1.1 = 16.6oC DB

SYSTEM SENSIBLE HEAT GAINS SSHSupply air fan and motor.Supply air duct heat gain.Cooling required to offset supply airduct leakage to areas other than the air conditioned space.

SSH = 28.59 + 23.53 = 52kW

Page 74: Psychrometrics Rev

WB T

empe

ratu

re o C

10

15

20

10 15 20 25 30Dry Bulb Temperature oC

B

A

C

D GF

B

ESHF = 0.9

ADP = 14.2oC DB and WB

SUPPLY AIR HEAT GAIN

Room 23oC DB, 60% RH

GSHF = 0.88

Recirculated Air Condition

Mixed Air Condition(Coil Entering Condition)

BF Bypass Factor10% of length of GSHF

RSHF = 0.89

Supply Air Condition

F

G

Coil LeavingCondition

D

AOutside Air21oC DB, 19oC WB

Mixed Air Condition

�YORK Production System

All rights Reserved

Copyright 1999 by York International Inc.Brian Fossey 03/99

Page 75: Psychrometrics Rev

SUMMARY - AIR HANDLING UNIT SUMMER CONDITIONS

FANS

Supply Fan Air Volume = 38m3/s

Return Air Fan Air Volume = 38 X 0.9* = 34.2m3/s* 10% air remains in the air conditioned space to o ffsettoilet exhaust and for pressurisation against infil tration.

COOLING COIL

Entering Cooling Coil condition = 23.8oC DB, 18.2oC WB

Leaving Cooling Coil condition = 15.5oC DB, 14.8oC WB

Supply Air condition = 16.6oC DB, 15.2oC WB

Page 76: Psychrometrics Rev

WINTER MIXED AIR CONDITION

Outside Air DB oC = - 4

Recirculated Air DB oC = 21 + 1(Return Air Gain) = 22

Minimum Outside Air = 12.74%

0.1274 X - 4 = -0.510.8726 X 22 = 19.2Mixed Air DB oC = 18.69

Page 77: Psychrometrics Rev

20

15

10

5

0

-5

-5 0 5 10 15 20 25

WB Temperature o C

Dry Bulb Temperature oC

Room Winter21oC DB, 50% RH

RSHF = 0.89

B

A

C

D GF

Mixed Air Conditionwith minimum Outside Air

RecirculatedAir Condition

B

C

DIncreased Outside Air Volume

SteamHumidifier

D

FG

STEAM HUMIDIFIER

Increase Moisture Content by0.0025kg/kg

Outside Air Winter

Page 78: Psychrometrics Rev

20

15

10

5

0

-5

-5 0 5 10 15 20 25

WB Temperature o C

Dry Bulb Temperature oC

Room Winter21oC DB, 50% RH

RSHF = 0.89

B

A

C

D GF

Mixed Air Conditionwith minimum Outside Air

RecirculatedAir Condition

B

C

D

Increased Outside Air Volume

SprayHumidifier

D

FG

SPRAY HUMIDIFIER

Increase Moisture Content by0.0015kg/kg

Outside Air Winter

Page 79: Psychrometrics Rev

HUMIDIFIER SIZING

Increase moisture content by 0.0025kg/kg

Density = 1.24 kg/m3

Steam Volume = 38m3/s X 3600 (m3/hour) X 0.0025kg/kg X 1.24kg/m3

= 424kg/Hour

STEAM HUMIDIFIER

SPRAY HUMIDIFIER

Increase moisture content by 0.0015kg/kg

Density = 1.24 kg/m3

Page 80: Psychrometrics Rev

20

15

10

5

0

-5

-5 0 5 10 15 20 25

WB Temperature o C

Dry Bulb Temperature oC

Room Winter21oC DB, 50% RH

RSHF = 0.89

B

A

C

D GF

RecirculatedAir Condition

B

C

D

SteamHumidifier

D

FG

STEAM HUMIDIFIERWITH PREHEAT

Increase Moisture Content by0.0025kg/kg

Outside Air Winter

Mixed Air Conditionwith high percentageof minimum Outside Air

Preheater

Page 81: Psychrometrics Rev

20

15

10

5

0

-5

-5 0 5 10 15 20 25

WB Temperature o C

Dry Bulb Temperature oC

Room Winter21oC DB, 50% RH

RSHF = 0.89

B

A

C

D GF

Mixed Air Conditionwith high percentage ofminimum Outside Air

RecirculatedAir Condition

B

C

SprayHumidifier

D

FG

SPRAY HUMIDIFIERWITH PREHEAT

Increase Moisture Content by0.0015kg/kg

Outside Air Winter

Preheater

Page 82: Psychrometrics Rev

20

15

10

5

0

-5

-5 0 5 10 15 20 25

WB Temperature o C

Dry Bulb Temperature oC

Room Winter21oC DB, 50% RH

RSHF = 0.89

A

C

DGF

Mixed Air Conditionwith minimum Outside Air

RecirculatedAir Condition

B

C

SprayHumidifier

D

FG

REHEAT

Increase Moisture Content by0.0015kg/kg

Outside Air Winter

Preheater

Reheater

B

H

H