public input no. 8-nfpa 86-2012 [ chapter nfpa ] statement

163
1/18/13 TerraView™ submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/163 Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Note: This Proposal originates from Tentative Interim Amendment 86-11-1 (TIA 987) issued by the Standards Council on August 5, 2010. 1. Revise text to read as follows: 7.4.10.2* The number of safety shutoff valve cycles shall be determined in one of the following ways: (A) Counting of actual safety shutoff valve open-closed cycles. (B) Estimated time to reach 90% of lifetime total cycles based upon normal burner cycling rates. Statement of Problem and Substantiation for Public Input The proposed text of 7.4.10.2 part (B) was written to allow estimating of lifetime valve cycles for safety shutoff valves. This would normally be useful for safety shutoff valves that are not used in high-cycle-rate applications such as pulse-fire systems. The word "burner" in part (B) inadvertently left safety shutoff valves associated with special atmosphere control limited to the requirement of part (A) where a counter would be required to monitor valve cycles. That was not the intent of the committee, and this TIA is being submitted to avoid an inappropriate change affecting safety shutoff valves used in applications beyond just burners. Emergency Nature: This TIA is needed to correct an unintended impact of new wording. Submitter Information Verification Submitter Full Name: Randy Bal Organization: GM/Nexteer Automotive Submittal Date: Wed Mar 28 12:51:05 EDT 2012 Committee Statement Resolution: FR-106-NFPA 86-2012 Statement: This revision is based on the TIA that was needed to correct an unintended impact of new wording. Copyright Assignment I, Randy Bal, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright assignment. By checking this box I affirm that I am Randy Bal, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and effect as a handw ritten signature

Upload: others

Post on 26-Dec-2021

8 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 1/163

Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ]

Note: This Proposal originates from Tentative Interim Amendment 86-11-1 (TIA 987) issued by the Standards Council onAugust 5, 2010.

1. Revise text to read as follows:

7.4.10.2* The number of safety shutoff valve cycles shall be determined in one of the following ways:

(A) Counting of actual safety shutoff valve open-closed cycles.

(B) Estimated time to reach 90% of lifetime total cycles based upon normal burner cycling rates.

Statement of Problem and Substantiation for Public Input

The proposed text of 7.4.10.2 part (B) was written to allow estimating of lifetime valve cycles for safety shutoff valves. This would normally be useful for safety shutoff valves that are not used in high-cycle-rate applications such as pulse-fire systems. The word "burner" in part (B) inadvertently left safety shutoff valves associated with special atmosphere control limited to the requirement of part (A) where a counter would be required to monitor valve cycles. That was not the intent of the committee, and this TIA is being submitted to avoid an inappropriate change affecting safety shutoff valves used in applications beyond just burners. Emergency Nature: This TIA is needed to correct an unintended impact of new wording.

Submitter Information Verification

Submitter Full Name:Randy Bal

Organization: GM/Nexteer Automotive

Submittal Date: Wed Mar 28 12:51:05 EDT 2012

Committee Statement

Resolution: FR-106-NFPA 86-2012

Statement: This revision is based on the TIA that was needed to correct an unintended impact of new wording.

Copyright Assignment

I, Randy Bal, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Randy Bal, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 2: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 2/163

Public Input No. 9-NFPA 86-2012 [ Chapter NFPA ]

Note: This Proposal originates from Tentative Interim Amendment 86-11-2 (TIA 988) issued by the Standards Council onAugust 5, 2010.

1. Revise text to read as follows:

14.5.1.7.4 Means shall be provided for metering and controlling the flow rates of all fluids comprising the specialatmosphere for a furnace.

(A) Devices with visible indication of flow shall be used to meter the flows of carrier gases, carrier gas component fluids,inert purge gases, enrichment gases, or air.

(B)* Devices that meter the flow of inert purge gases shall meter and visibly indicate the flow rate by mechanical means.

A.14.5.1.7.4(B) The indication of flow is intended to be provided by a device that will indicate flow any time a flow isoccurring including during power outage. A mechanical device that indicates the flow rate without using any source ofpower except the physical flow of the inert purge gas meets this requirement. Where an inert purge gas flow is meteredand displayed using electrical means, a reliable backup power supply, such as back-up batteries or an uninterruptiblepower supply, is needed to meet this requirement.

Where back-up power sources are used, such as batteries and uninterruptible power supplies, the power source should bedesigned to supply power for the duration needed to purge-out the complete furnace system. In addition, appropriatemaintenance procedures should be provided to inspect, test, and maintain the back-up power supply on a regular basis toreduce the possibility of its unavailability during a primary power interruption.

(C) The installation of flow control equipment shall meet the following criteria:

(1) It shall be installed either at the furnace, at the generator, or in a separate flow control unit.

(2) It shall be accessible and located in an illuminated area so that its operation can be monitored."

Statement of Problem and Substantiation for Public Input

The text of 14.5.1.7.4 does not clearly express that the visible indication of flow for inert purge gases are to be provided by a direct mechanical indication of flow as opposed to an indirect electrical indication of flow. This revision and the added annex clarifies that the visual indication of flow is to be provided by mechanical means and not solely by electrical means. Emergency Nature: This TIA is needed to clarify committee intent.

Submitter Information Verification

Submitter Full Name:Randy Bal

Organization: GM/Nexteer Automotive

Submittal Date: Wed Mar 28 13:38:34 EDT 2012

Committee Statement

Resolution: FR-28-NFPA 86-2012

Statement: The TIA 11-2 addresses Class C ovens and not Class D ovens as such it was relocated to the correct section in the Class CChapter. This revision and the added annex clarifies that the visual indication of flow is to be provided by mechanical means andnot solely by electrical means, see FR-119-NFPA 86-2012.

Copyright Assignment

I, Randy Bal, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Randy Bal, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 3: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 3/163

Public Input No. 141-NFPA 86-2012 [ Section No. 1.1.7 ]

1.1.7

This standard shall not apply to the following:

(1)

(2) Listed equipment with a heating system(s) that supplies a total input not exceeding 150,000 Btu/hr (44 kW)

(3) Fired heaters in petroleum refineries and petrochemical facilities that are designed and installed in accordance with APISTD 560, Fired Heaters for General Refinery Services, 2007; API RP 556, Instrumentation and Control Systems for FiredHeaters and Steam Generators, 1997; and API RP 2001, Fire Protection in Refineries, 2005.

(4)

(5) Fluid is flowing under pressure in tubes or pipes and is indirectly heated by combustion of liquid gas fuel or an electricalsource.

Fluid is heated indirectly by products of combustion of liquid or gas fuel flowing through tubes (firetube) as defined in NFPA87 Recommended Practice for Fluid Heaters .

Statement of Problem and Substantiation for Public Input

NFPA 87 did not exist when the language in 1.1.7(4) was drafted for the 2011 Edition. Language currently in 1.1.7(4) precludes "wash tanks" from governance by either NFPA 86 or NPFA 87, since the fluid is not under pressure. The revised exception would categorize a "wash tank" as an NFPA 86 oven.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 15:34:00 EDT 2012

Committee Statement

Resolution: FR-40-NFPA 86-2012

Statement: NFPA 87 did not exist when the language in 1.1.7(4) was drafted for the 2011 Edition. Language currently in 1.1.7(4) precludes"wash tanks" from governance by either NFPA 86 or NPFA 87, since the fluid is not under pressure. The revised exception wouldcategorize a "wash tank" as an NFPA 86 oven. The information on arc melt furnaces in NFPA 86 has not been updated sincewhen it was originally entered into the standard in 1973. There has and currently is no expertise within the committee to addressthis type of equipment. Currently, most of the industry does not use this standard because of the degree of specialized design andengineering for each unique arc furnace, this standard does not have the capability to cover such a design.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

* Coal or other solid fuel–firing systems

* Fluid heaters where either of the following conditions exists:

Page 4: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 4/163

Public Input No. 32-NFPA 86-2012 [ New Section after 3.3.2.4 ]

3.3.2.5 Process Control Air

Air introduced to a furnace containing a special atmosphere to establish a controlled oxygen level or carbon potential.

Statement of Problem and Substantiation for Public Input

Definition added for clarity in using the term in Class C furnaces.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 09:38:38 EDT 2012

Committee Statement

Resolution: FR-74-NFPA 86-2012

Statement: Definition added for clarity in using the term in Class C furnaces.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) in Class C Task Group.

Page 5: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 5/163

Public Input No. 33-NFPA 86-2012 [ New Section after 3.3.2.4 ]

3.3.2.6 Burnout Air

Air introduced into a furnace chamber for the purpose of burning out flammable atmospheres, residual soot or othercarbonaceous material.

Statement of Problem and Substantiation for Public Input

Definition to be added for clarity in using the term in Class C furnaces.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 09:40:54 EDT 2012

Committee Statement

Resolution: FR-75-NFPA 86-2012

Statement: Definition to be added for clarity in using the term in Class C furnaces.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) in Class C Task Group.

Page 6: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 6/163

Public Input No. 103-NFPA 86-2012 [ New Section after 3.3.5.14 ]

3.3.6

Burner Management System. The field devices, logic system, and final control elements dedicated to combustion safety andoperator assistance in the starting and stopping of fuel preparation and burning equipment and for preventing misoperation of anddamage to fuel preparation and burning equipment.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #102 at Section 8.3.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 102-NFPA 86-2012 [Section No. 8.3] Section 8.3 heading and Definition 3.3.6 refer to each other

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary, NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:27:31 EDT 2012

Committee Statement

Resolution: FR-16-NFPA 86-2012

Statement: The term Burner Management System is used to describe the Logic Systems covered in Section 8.3, see FR-80-NFPA 86-2012.The proposed definition from the 2011 edition of NFPA 85, Boiler and Combustion Systems Hazards Code.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 7: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 7/163

Public Input No. 101-NFPA 86-2012 [ New Section after 3.3.18 ]

3.3.18

Flame Response Time (FRT). The period of time that starts with the loss of flame and ends with the de-energizing of the terminals ofthe safety shut-off valves.

Statement of Problem and Substantiation for Public Input

See substantiation Public Input #99 at Section 8.5.2.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 99-NFPA 86-2012 [New Section after 8.5.2.1] Definition for Combustion Safeguard to accompany new required text

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:16:12 EDT 2012

Committee Statement

Resolution: FR-81-NFPA 86-2012

Statement: The Committee added definition to flame failure response time, a term that is used within the standard. See FR-143-NFPA 86-2012 for the definition of Flame Response Time (FRT).

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 8: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 8/163

Public Input No. 127-NFPA 86-2012 [ New Section after 3.3.20 ]

3.3.21 Fresh Air

Air uncontaminated by flammable or corrosive components other than moisture. A colorless, odorless, tasteless, gaseous mixture,mainly nitrogen (approximately 78 percent) and oxygen (approximately 21 percent) with lesser amounts of argon, carbon dioxide,hydrogen, neon, helium, and other gases.

Statement of Problem and Substantiation for Public Input

For purposes of purge and safety ventilation, the standard calls for the use of fresh air (3.3.53, 8.5.1.1, 10.6.3.1, 10.6.3.2, 11.6.1.10, 11.6.1.14,...). However, end users often debate what is an acceptable fresh air source. A definition is needed to clarify this question.

Submitter Information Verification

Submitter Full Name:Thomas George

Organization: Tokio Marine Management, Inc.

Submittal Date: Fri Jun 22 09:43:28 EDT 2012

Committee Statement

Resolution: The Committee could not come to a consensus on a definition of fresh air and as such decided to leave it out the standard.

Copyright Assignment

I, Thomas George, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Thomas George, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 9: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 9/163

Public Input No. 143-NFPA 86-2012 [ Section No. 3.3.25.4 ]

3.3.25.4 Class 4* Class B Furnace.

An oven or furnace that has heat utilization equipment wherein there are no flammable volatiles or combustible materials beingheated.

Statement of Problem and Substantiation for Public Input

Add asterisk to cite new Annex material

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 15:45:29 EDT 2012

Committee Statement

Resolution: FR-10-NFPA 86-2012

Statement: The Committee added annex material, see FR-11-NFPA 85-2012, for clarification on Class B Ovens.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 10: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 10/163

Public Input No. 135-NFPA 86-2012 [ New Section after 3.3.29 ]

3.3.30

Hardwired. The method of interconnecting signals or interlocks to a logic system or between logic systems using a dedicatedinterconnection

Statement of Problem and Substantiation for Public Input

Adds a new definition for a term that is used in the standard.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 11:01:50 EDT 2012

Committee Statement

Resolution: FR-44-NFPA 86-2012

Statement: Adds a new definition for a term that is used in the standard. See FR-144-NFPA 86-2012 for the additional informational materialfor further clarification on the definition of hardwired.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 11: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 11/163

Public Input No. 139-NFPA 86-2012 [ Section No. 3.3.30.8 ]

3.3.30.8 Radiant Tube Heating System.

A heating system with tubular elements open at one or both ends in which each tube has an inlet burner arrangement wherecombustion is initiated, a suitable length where combustion occurs, and an outlet which discharges outside the combustionchamber for the combustion products formed.

Statement of Problem and Substantiation for Public Input

In a recent application a client had developed a Radiant tube heating system in which the products of combustion were released directly into the combustion chamber rather than outside or into a exhaust stack or header. Therefore if a burner were to have a leak, the gas could be discharge into the combustion chamber which is not normal to Radiant tube burners. Additionally, if you treat the system as a direct fired, becasue of a nearly 25 foot combustion sleeve, the flame is not present in the combustion chamber to provide an ignition source for unburned gases. So it really does not fall into either style of system and needs to have special considerations.

Submitter Information Verification

Submitter Full Name:Franklin Switzer

Organization: S-afe, Inc.

Submittal Date: Fri Jun 22 14:18:23 EDT 2012

Committee Statement

Resolution: FR-99-NFPA 86-2012

Statement: The Committee had become aware of a user that had developed a radiant tube heating system in which the products ofcombustion were released directly into the combustion chamber rather than outside or into a exhaust stack or header. Therefore ifa burner were to have a leak, the gas could be discharge into the combustion chamber which is not normal to radiant tubeburners. dditionally, if you treat the system as a direct fired, because of a nearly 25 foot combustion sleeve, the flame is notpresent in the combustion chamber to provide an ignition source for unburned gases. So it really does not fall into either style ofsystem and needs to have special considerations. The Committee changed the submitter's definition; combustion to work.

Copyright Assignment

I, Franklin Sw itzer, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Franklin Sw itzer, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 12: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 12/163

Public Input No. 64-NFPA 86-2012 [ New Section after 3.3.53 ]

3.3.53.1*

Safety Ventilation. The ventilation necessary to dilute VOC’s within a Class A oven to the required percent of the Lower FlammableLimit (LFL).

Statement of Problem and Substantiation for Public Input

See substantiation provided for Public Input #24 at Section 3.3.53.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 24-NFPA 86-2012 [Section No. 3.3.53] Definition of "ventilation" separated into two parts

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:49:19 EDT 2012

Committee Statement

Resolution: FR-91-NFPA 86-2012

Statement: A definition is required for the term “Safety Ventilation”, which is used in the standard. The Committee wanted to clarify that theLFL can be below the maximum permitted. See FR-92-NFPA 86-2012 for the associated annex material.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 13: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 13/163

Public Input No. 24-NFPA 86-2012 [ Section No. 3.3.53 ]

3.3.53 Proven Ventilation 53 Ventilation .

A supply of fresh air to, and exhaust from, a furnace that provides a vigorous, distributed flow of air through all sections of thefurnace, such that flammable vapor concentrations in all parts of the furnace or furnace enclosure are maintained below thelower flammable limit at all times .

Statement of Problem and Substantiation for Public Input

The term “proven ventilation” is not used in the standard. The term ventilation is used for both safety ventilation and pre-ignition purge. A definition is required for the term “Safety Ventilation”, which is used in the standard.The existing language “flammable vapor concentrations … are maintained below the lower flammable limit…” is more appropriately used as enforceable language (see related public input addressing Section 11.6.1.1) and not in a definition.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Fri Apr 13 10:24:38 EDT 2012

Committee Statement

Resolution: FR-1-NFPA 86-2012

Statement: The term “proven ventilation” is not used in the standard. The term ventilation is used for both safety ventilation and pre-ignitionpurge. The Committee defined the term “Safety Ventilation” in FR-91-NFPA 86-2012, which is used in the standard. The existinglanguage “flammable vapor concentrations … are maintained below the lower flammable limit…” is more appropriately used asenforceable language and not in a definition and as such was removed.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 14: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 14/163

Public Input No. 140-NFPA 86-2012 [ Section No. 3.3.60 ]

3.3.60 Safe-Start Check.

A checking circuit incorporated in a safety-control circuit that prevents light-off if the flame-sensing relay of the combustion safeguardis in the unsafe (flame-present) position due to component failure within the combustion safeguard or due to the presence of actual orsimulated flame.

Statement of Problem and Substantiation for Public Input

Since PLC's may now implement the Safe-Start check, what additional features are included by the manufacturers of approved Burner Management systems which include Safe-Start Check. These items need to be listed so that any requirements can be met.

Submitter Information Verification

Submitter Full Name:Franklin Switzer

Organization: S-afe, Inc.

Submittal Date: Fri Jun 22 15:24:54 EDT 2012

Committee Statement

Resolution: The submitter did not provide any recommended change to the definition. Additionally, this is a definition and as such should notinclude requirements as the submitter is suggesting to include a list of features for Safe-Start Check so that requirements can bemet.

Copyright Assignment

I, Franklin Sw itzer, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Franklin Sw itzer, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 15: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 15/163

Public Input No. 95-NFPA 86-2012 [ New Section after 4.1.1.2 ]

4.1.1.3

The furnace classification (A, B, C, D) shall be included.

Statement of Problem and Substantiation for Public Input

By adding the requirement that the plans must include the furnace class, it helps ensure that the user has reviewed the requirements for that class of furnace.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 23:00:44 EDT 2012

Committee Statement

Resolution: FR-12-NFPA 86-2012

Statement: The Committee added that the furnace class to be a part of the plans to ensure that the user has reviewed the requirements forthat class of furnace.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 16: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 16/163

Public Input No. 96-NFPA 86-2012 [ New Section after 4.1.1.2 ]

4.1.1.4

If a furnace is modified and/or its process load is changed from the original design, the furnace Class shall be evaluated and eitherconfirmed to remain as the original Class or the reassigned to a new Class.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #95

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 95-NFPA 86-2012 [New Section after4.1.1.2]

Modification of a furnace requires assessment and possible re-assignment ofClass

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 23:17:22 EDT 2012

Committee Statement

Resolution: FR-13-NFPA 86-2012

Statement: If there are modifications to an existing furnace and/or process load, there is the possibility that the furnace class could change. Achange in class would cause different requirements to apply. Because of this possibility, the Committee believes that the furnacesneeds to be evaluated to ensure that the proper requirements are applied.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 17: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 17/163

Public Input No. 109-NFPA 86-2012 [ Section No. 5.4.3.6 ]

5.4.3.6

No portions of the building shall be used as an integral part of the duct leading to the approved a safe point of discharge.

Statement of Problem and Substantiation for Public Input

Based on discussions at a recent NFPA 85 TC meeting and contents of the NFPA 85 document (e.g., 6.6.3.1.2.2), NFPA does not disallow use of the word “safe” in the context of “safe location” as being unenforceable language and that NFPA 85 uses “safe location” in mandatory text.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:03:15 EDT 2012

Committee Statement

Resolution: The existing language is appropriate and enforceable. The term safe is unenforceable per the NFPA Manual of Style.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 18: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 18/163

Public Input No. 173-NFPA 86-2012 [ Section No. 6.2.5.3 ]

6.2.5.3*

A gas filter or strainer shall be installed in the fuel gas piping and shall be located downstream of the equipment isolation valveand sediment trap and upstream of all other fuel gas system components. The mesh size shall be the minimum size to protectdownstream controls as prescribed by the component manufacturer.

Statement of Problem and Substantiation for Public Input

Debris in the fuel gas is unpredictable, and many operated believe that the fuel gas is clean, when in fact is may not be. A more consistent approach would be to have the component manufacturers describe what type of gas filter/strainer is needed to properly protect the downstream controls.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:20:13 EDT 2012

Committee Statement

Resolution: FR-146-NFPA 86-2013

Statement: Section 8.2.2 already covers safety devices to be installed per manufacturer’s instructions. The Committee did see merit in addingin the statement to the annex to help users understand the need to protect downstream devices.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 19: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 19/163

Public Input No. 110-NFPA 86-2012 [ Section No. 6.2.6.3 ]

6.2.6.3*

Regulators, relief valves, and switches shall be vented to an approved a safe location, and the following criteria also shall bemet:

(1) Heavier-than-air flammable gases shall be vented outside the building to a location where the gas is diluted below its LFLbefore coming in contact with sources of ignition or re-entering the building.

(2) Vents shall be designed to prevent the entry of water and insects without restricting the flow capacity of the vent.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #109 at Section 5.4.3.6.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 109-NFPA 86-2012 [Section No. 5.4.3.6] Related link for "safe" versus "approved"

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:06:48 EDT 2012

Committee Statement

Resolution: The existing language is appropriate and enforceable. The term safe is unenforceable per the NFPA Manual of Style.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 20: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 20/163

Public Input No. 111-NFPA 86-2012 [ Section No. 6.2.6.4 ]

6.2.6.4*

Fuel gas regulators, ratio regulators, and zero governors shall not be required to be vented to an approved a safe location in thefollowing situations:

(1) Where backloaded from combustion air lines, air–gas mixture lines, or combustion chambers, provided that gas leakagethrough the backload connection does not create a hazard

(2) Where a listed regulator–vent limiter combination is used

(3) Where a regulator system is listed for use without vent piping

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #109 at Section 5.4.3.6.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 109-NFPA 86-2012 [Section No. 5.4.3.6] "Safe" versus "Approved"

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:09:17 EDT 2012

Committee Statement

Resolution: The existing language is appropriate and enforceable. The term safe is unenforceable per the NFPA Manual of Style.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 21: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 21/163

Public Input No. 167-NFPA 86-2012 [ Section No. 6.2.6.4 ]

6.2.6.4*

Fuel gas regulators, ratio regulators, and zero governors shall not be required to be vented to an approved location in thefollowing situations:

(1) Where backloaded from combustion air lines, air–gas mixture lines, or combustion chambers, provided that gas leakagethrough the backload connection does not create a hazard

(2) Where a listed regulator–vent limiter combination is used

(3) Where a regulator system is listed for use without vent piping

(4) A regulator incorporating a leak limiting system, which permits not more than 2.5 ft3/h (based on the maximum rated inletpressure rating and a gas having a specific gravity of 0.65) or less into the ambient if the atmospheric diaphragm ruptures.

Statement of Problem and Substantiation for Public Input

Recommending the use of listed regulator/vent limiter combinations essentially limits the use of the vent limiting devices to 5 PSI maximum, because the regulator standard for which such listings can be done has a limited scope of 5 PSI, 2PSI or 1/2 PSI. The proposal removes the listing combination barrier and directs the user's attention to specifically check the ratings of the limiter, and it codifies language for the use of other types of devices that limit the escape of gas into ambient if the atmospheric diaphragm ruptures. Examples of devices currently used today are safety diaphragms and ventilation valves. See also annex A.6.2.6.4 for the selection of the 2.5 ft3/h limit.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:05:09 EDT 2012

Committee Statement

Resolution: FR-101-NFPA 86-2012

Statement: Recommending the use of listed regulator/vent limiter combinations essentially limits the use of the vent limiting devices to 5 PSImaximum, because the regulator standard for which such listings can be done has a limited scope of 5 PSI, 2PSI or 1/2 PSI. Therevision removes the listing combination barrier and directs the user's attention to specifically check the ratings of the limiter, andit codifies language for the use of other types of devices that limit the escape of gas into ambient if the atmospheric diaphragmruptures. Examples of devices currently used today are safety diaphragms and ventilation valves. See also annex A.6.2.6.4 for theselection of the 2.5 ft3/h limit, see FR-102-NFPA 86-2012.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 22: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 22/163

Public Input No. 44-NFPA 86-2012 [ New Section after 6.2.6.8 ]

6.2.6.8.1

Vents from systems operating at different pressure levels shall not be manifolded together.

6.2.6.8.2

Vents from systems served from different pressure reducing stations shall not be manifolded together.

6.2.6.8.3

Vents from systems using different fuel sources shall not be manifolded together.

Statement of Problem and Substantiation for Public Input

NFPA 86 currently does not prohibit manifolding vent lines from different pressure sources, but it is good engineering practice to avoid doing this and NFPA 85 prohibits it. The proposed subparagraphs are extracted from NFPA 85 (2011), Section 4.9.3.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Wed Jun 06 19:34:24 EDT 2012

Committee Statement

Resolution: FR-2-NFPA 86-2012

Statement: NFPA 86 currently does not prohibit manifolding vent lines from different pressure sources, but it is good engineering practice toavoid doing this and NFPA 85, Boiler and Combustion Systems Hazards Code, prohibits it. The new language matches currenttext in NFPA 85 (2011), Section 4.9.3.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 23: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 23/163

Public Input No. 45-NFPA 86-2012 [ Section No. 6.2.6.9 ]

6.2.6.9

The

sizecross-sectional area of the

vent manifold specified in 6.2.6.8 shall be not less than themanifold line shall not be less than the greater of the following:

(1) The cross-sectional area of the largest vent

lineplus 50 percent of the sum of the cross-sectional areas of the additional vent

line arealines .

(2) The sum of the cross-sectional areas of the two largest vent lines.

Statement of Problem and Substantiation for Public Input

NFPA 86 currently does not prohibit manifolding vent lines from different pressure sources, but it is good engineering practice to avoid doing this and NFPA 85 prohibits it. The proposed subparagraphs are extracted from NFPA 85 (2011), Section 4.9.3.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Wed Jun 06 19:53:26 EDT 2012

Committee Statement

Resolution: FR-3-NFPA 86-2012

Statement: NFPA 86 currently does not prohibit manifolding vent lines from different pressure sources, but it is good engineering practice toavoid doing this and NFPA 85, Boiler and Combustion Systems Hazards Code, prohibits it. The new language matches the textfrom NFPA 85 (2011), Section 4.9.3.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 24: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 24/163

Public Input No. 153-NFPA 86-2012 [ New Section after 6.2.6.10 ]

Add a new section to read as follows: For a burner equipped with vents between blocking valves on both the main gas line and the pilot gas line, these two vents may becombined.

Statement of Problem and Substantiation for Public Input

This would allow a less expensive installation for venting of all of the blocking valves on a burner. Since having a vent line on the pilot gas line is a rather unusual circumstance, it is not surprising that NFPA 86 is silent about the possibility of combining them.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Mon Jul 02 08:29:53 EDT 2012

Committee Statement

Resolution: 1) Per A.6.2.6.10 NFPA 86 does not address vents between Safety Shutoff Valves and 2) the submitter's text did not includeguidance for correctly sizing vent lines between Safety Shutoff Valves such that the venting of fuel gas in one does not back loadthe other system.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 25: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 25/163

Public Input No. 164-NFPA 86-2012 [ New Section after 6.2.6.10 ]

Add a new section to read as follows: For a burner equipped with vents between blocking valves on both the main gas line and the pilot gas line, these two vents may becombined.

Statement of Problem and Substantiation for Public Input

This would allow a less expensive installation for venting of all of the blocking valves on a burner. Since having a vent line on the pilot gas line is a rather unusual circumstance, it is not surprising that NFPA 86 is silent about the possibility of combining them.

Submitter Information Verification

Submitter Full Name:Grant Tiefenbruck

Organization: 3M Company

Submittal Date: Mon Jul 02 12:40:49 EDT 2012

Committee Statement

Resolution: 1) Per A.6.2.6.10 NFPA 86 does not address vents between Safety Shutoff Valves and 2) the submitter's text did not includeguidance for correctly sizing vent lines between Safety Shutoff Valves such that the venting of fuel gas in one does not back loadthe other system.

Copyright Assignment

I, Grant Tiefenbruck, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Grant Tiefenbruck, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions

contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same

legal force and effect as a handw ritten signature

Page 26: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 26/163

Public Input No. 112-NFPA 86-2012 [ Section No. 6.2.6.10 ]

6.2.6.10*

A vent between safety shutoff valves, where installed:

(1) Shall not be combined with other vents

(2)

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #109 at Section 5.4.3.6.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 109-NFPA 86-2012 [Section No. 5.4.3.6] "Approved" versus "Safe"

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:10:36 EDT 2012

Committee Statement

Resolution: The existing language is appropriate and enforceable. The term safe is unenforceable per the NFPA Manual of Style.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

* Shall terminate to an approved location a safe location

Page 27: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 27/163

Public Input No. 89-NFPA 86-2012 [ Section No. 6.3.8.3 ]

6.3.8.3

Pilot burners shall be considered burners, and all provisions of Section 6.2 3 shall apply.

Statement of Problem and Substantiation for Public Input

Reference should be to the oil fired section 6.3, not to the gas fired section 6.2. This was a copy-paste editing error, see 6.2.10.3 for the corresponding fuel gas requirement.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Thu Jun 21 11:12:09 EDT 2012

Committee Statement

Resolution: FR-103-NFPA 86-2012

Statement: Reference should be to the oil fired section 6.3, not to the gas fired section 6.2. This was a copy-paste editing error, see 6.2.10.3for the corresponding fuel gas requirement.

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 28: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 28/163

Public Input No. 113-NFPA 86-2012 [ Section No. 6.4.3.8 ]

6.4.3.8*

Oxygen from pressure relief devices and purge outlets shall be vented to an approved a safe location by vents designed toprevent the entry of water and insects.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #109 at Section 5.4.3.6.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 109-NFPA 86-2012 [Section No. 5.4.3.6] "Approved" versus "Safe"

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:12:05 EDT 2012

Committee Statement

Resolution: The existing language is appropriate and enforceable. The term safe is unenforceable per the NFPA Manual of Style.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 29: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 29/163

Public Input No. 97-NFPA 86-2012 [ Section No. 6.5.2 ]

6.5.2

The following shall apply to collecting and venting systems for radiant tube–type heating systems:

(1) The system shall be of a capacity to prevent an explosion or fire hazard due to the flow of unburned fuel through theradiant tubes.

(2)

(3) A * A radiant tube–type heating system provided with two safety shutoff valves interlocked with combustion safeguardsshall be exempt from the requirements of 6.5.2.

Statement of Problem and Substantiation for Public Input

See substantiation at Public Input #98 for Section A.6.5.2(3)

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 23:37:13 EDT 2012

Committee Statement

Resolution: FR-14-NFPA 86-2012

Statement: Added annex material, see FR-15-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 174-NFPA 86-2012 [ New Section after 7.1.6 ]

Add new text to read as follows: 7.1.7* A confirmed source of combustible gas shall be provided to the inlet of the equipment isolation valve(s) (see 6.2.4.1 and13.5.11.10.2.1) each time a combustible gas supply is placed into service or restored to service.

Statement of Problem and Substantiation for Public Input

Note: This Proposal originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to the following fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54 took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1 Appliance Shutoff Valve. A valve located in the piping system used to shut off individual equipment. Excerpt from NFPA 86-2011 3.3.76.3 Equipment Isolation Valve. A manual shutoff valve for shutoff of the fuel to each piece of equipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. The emergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management of liquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public a benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. The submitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 on evacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the Technical Committee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard Investigation Board (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditions but does not provide any

* The system shall be capable of dilution of the rated maximum input capacity of the system to a noncombustible state.

Page 30: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 30/163

requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supply contained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gas being delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitter and members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposed requirements and Annex referencing NFPA 54’s related requirements.

Submitter Information Verification

Submitter Full Name:Ted Jablkowski

Organization: Fives North American Combustio

Submittal Date: Fri Sep 14 12:08:58 EDT 2012

Committee Statement

Resolution: FR-93-NFPA 86-2012

Statement: This revision originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to thefollowing fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1Appliance Shutoff Valve.   A valve located in the piping system used to shut off individual equipment. Excerpt fromNFPA 86-2011 3.3.76.3 Equipment Isolation Valve.   A manual shutoff valve for shutoff of the fuel to each piece ofequipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. Theemergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management ofliquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public abenefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. Thesubmitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 onevacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the TechnicalCommittee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard InvestigationBoard (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditionsbut does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supplycontained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gasbeing delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitterand members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposedrequirements and Annex referencing NFPA 54’s related requirements.

Copyright Assignment

I, Ted Jablkow ski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Ted Jablkow ski, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 31: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 31/163

Public Input No. 87-NFPA 86-2012 [ New Section after 7.3.1 ]

7.3.2

Furnaces shall not be operated unless there are personnel instructed and trained per Section 7.2.1 present within the operatingfacility to respond in a timely manner to furnace alarms or other situations requiring a trained operator response.

Statement of Problem and Substantiation for Public Input

To clarify that the trained operators must be present when equipment is operated.

Submitter Information Verification

Submitter Full Name:Randall Conklen

Organization: Caterpillar Incorporated

Submittal Date: Tue Jun 19 17:27:24 EDT 2012

Committee Statement

Resolution: FR-104-NFPA 86-2012

Statement: To clarify that the trained operators must be present when equipment is operated. The Committee understands that some furnacesare designed for unattended operation and as such changed the text.

Copyright Assignment

I, Randall Conklen, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Randall Conklen, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 32: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 32/163

Public Input No. 137-NFPA 86-2012 [ Section No. 7.4.10 ]

7.4.10 Safety Shutoff Valve Replacement.

7.4.10.1

Safety shutoff valves use for pulse fire applications shall be replaced before they exceed their maximum allowable number oflifetime open–closed cycles.

7.4.10.2*

The number of safety shutoff valve cycles shall be determined in one of the following ways:

(1) By counting the number of actual safety shutoff valve open-closed cycles

(2) By estimating the time to reach 90 percent of lifetime total cycles based on normal cycling rates

Subsection 7.4.10.2 was revised by a tentative interim amendment (TIA). See page 1.

Statement of Problem and Substantiation for Public Input

The counting of cycles does not determine or define the safe or even usefull life of a safety shut-off valve under normal applications. It should be applied only during the extreme use such as is seen in Pulse Fired Applications. The mandatory seat leakage testing performed on a periodic basis of annually is much more usefull definition of safety.

A definition of Pulse fired or Rapid cycle may be required.

Submitter Information Verification

Submitter Full Name:Franklin Switzer

Organization: S-afe, Inc.

Submittal Date: Fri Jun 22 13:47:14 EDT 2012

Committee Statement

Resolution: FR-30-NFPA 86-2012

Statement: There is no definition of pulse fired. The Committee clarified both submitters intent by adding a reference to section 8.5.1.8(4)which relates to pulse fired operations and similar rapid cycling of SSOV operations.

Copyright Assignment

I, Franklin Sw itzer, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Franklin Sw itzer, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 33: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 33/163

Public Input No. 105-NFPA 86-2012 [ New Section after 7.4.10.1 ]

7.4.10.2

When the maximum allowable number of lifetime open–closed cycles for Safety shutoff valves are not available from the Safety shutoffvalves manufacturer, the user must replace the Safety shutoff valves when their leak tightness tests indicate that the leakage rate hasincreased to any one of the following levels:

(1) the rate that is 100% greater than the previously required leak tightness test

(2) 44 bubbles per minute

(3) the leakage rate that would result in a condition where the heating zone concentration of fuel gas is greater than 25% LFL underany possible circumstance.

Statement of Problem and Substantiation for Public Input

It is difficult for a user to be in compliance with the requirements of this Standard when the SSOV manufacturer doesn't provide life cycle ratings. This proposal attempts to provide an alternate determination for SSOV replacement timing when life cycle ratings are not available.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:45:18 EDT 2012

Committee Statement

Resolution: The action taken for FR-(PI-161 and -137) eliminates the need for this proposed change.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 34: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 34/163

Public Input No. 161-NFPA 86-2012 [ Section No. 7.4.10.1 ]

7.4.10.1

Safety shutoff valves used to comply with 8.5.1.8 and are not proved closed shall be replaced before they exceed theirmaximum allowable number of lifetime open–closed cycles.

Statement of Problem and Substantiation for Public Input

The language inadvertently imposes requirements on systems that don't skip purge in any case, but rather include a pre-purge before lighting any burner system. It is those valves that are used to skip a pre-purge but are not monitored by a proof of closure switch or a valve proving systems, which necessitate the need for the replacing valves when the valves' cycle life has been exceeded.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:26:18 EDT 2012

Committee Statement

Resolution: FR-30-NFPA 86-2012

Statement: There is no definition of pulse fired. The Committee clarified both submitters intent by adding a reference to section 8.5.1.8(4)which relates to pulse fired operations and similar rapid cycling of SSOV operations.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 175-NFPA 86-2012 [ New Section after 7.4.18 ]

Add new text to read as follows: 7.4.19* Whenever combustible gas piping is placed into service or removed from service, any release of combustible gas shall bevented to an approved location.

Statement of Problem and Substantiation for Public Input

Note: This Proposal originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to the following fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54 took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1 Appliance Shutoff Valve. A valve located in the piping system used to shut off individual equipment. Excerpt from NFPA 86-2011 3.3.76.3 Equipment Isolation Valve. A manual shutoff valve for shutoff of the fuel to each piece of equipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. The emergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management of liquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public a benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. The submitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 on evacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the Technical Committee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard Investigation Board (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditions but does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supply contained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gas being delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitter and members of the NFPA 86 Technical

Page 35: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 35/163

Committee wish to draw attention to this potential hazard by the addition of the proposed requirements and Annex referencing NFPA 54’s related requirements.

Submitter Information Verification

Submitter Full Name:Ted Jablkowski

Organization: Fives North American Combustio

Submittal Date: Fri Sep 14 12:10:16 EDT 2012

Committee Statement

Resolution: FR-97-NFPA 86-2012

Statement: This revision originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to thefollowing fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1Appliance Shutoff Valve.   A valve located in the piping system used to shut off individual equipment. Excerpt fromNFPA 86-2011 3.3.76.3 Equipment Isolation Valve.   A manual shutoff valve for shutoff of the fuel to each piece ofequipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. Theemergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management ofliquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public abenefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. Thesubmitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 onevacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the TechnicalCommittee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard InvestigationBoard (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditionsbut does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supplycontained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gasbeing delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitterand members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposedrequirements and Annex referencing NFPA 54’s related requirements.

Copyright Assignment

I, Ted Jablkow ski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Ted Jablkow ski, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 36: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 36/163

Public Input No. 50-NFPA 86-2012 [ Section No. 8.2.1 ]

8.2.1

All safety devices shall meet one of the following criteria:

(1) Be listed for the service the service intended

(2) Combustion safeguards, excess temperature limit interlocks, safety shutoff valves listed for combustion safety service

(3) Be approved if listed devices are not available

(4) Be programmable controllers applied in accordance with Section 8.4

Statement of Problem and Substantiation for Public Input

New text clarifies types of acceptable devices. Certain types (combustion safeguards, excess temperature limit interlocks and safety shutoff valves require separate listing for combustion safety service.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 10:11:30 EDT 2012

Committee Statement

Resolution: FR-8-NFPA 86-2012

Statement: New text clarifies types of acceptable devices. Certain types (combustion safeguards, excess temperature limit interlocks andsafety shutoff valves require separate listing for combustion safety service. The Committee added annex material to help clarifywhen approving devices when listed devices are not available, see FR-118-NFPA 86-2012. The new 8.2.2 does not replace theexisting 8.2.2. The subsequent sections are to be renumbered.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 37: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 37/163

Public Input No. 162-NFPA 86-2012 [ Section No. 8.2.3 ]

8.2.3

Electric relays and safety shutoff valves shall not be used as substitutes for electrical disconnects and manual shutoff valves

3.1

If the furnace heating system will not be used for a period more than 24 hours, then a manual device, such as the maindisconnect, the emergency shut-off valve or the equipment isolation valve must be set to isolate the equipment from its fuel orelectrical supply .

Statement of Problem and Substantiation for Public Input

Clarify intent. Equipment not in service is not regularly monitored by operators and other personnel may not be aware of the possible hazards with inoperative equipment. Other facility operations, fork lift activity, maintenance, or other incidents may lead to an exposed electrical or fuel leak hazard that may not be immediately detected.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:27:19 EDT 2012

Committee Statement

Resolution: The original text is not intended to define when manual shutoff valves and electrical disconnects are to be used.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 38: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 38/163

Public Input No. 168-NFPA 86-2012 [ Section No. 8.2.7.2 ]

8.2.7.2

The requirement in 8.2.7 shall not prohibit a time delay applied to the action of pressure-proving, flow-proving, or proof-of-closuresafety switch as used in accordance with 8.8.1.3(3)(c a ), where the following conditions exist:

(1) There is an operational need demonstrated for the time delay.

(2) The use of a time delay is approved.

(3) The time delay feature is not adjustable beyond 5 seconds.

(4) A single time delay does not serve more than one pressure-proving or flow-proving safety device.

(5) The time from an abnormal pressure or flow condition until the holding medium is removed from the safety shutoff valvesdoes not exceed 5 seconds.

Statement of Problem and Substantiation for Public Input

8.8.1.3(3)(a) deals with the application of proof.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:06:42 EDT 2012

Committee Statement

Resolution: FR-107-NFPA 86-2012

Statement: 8.8.1.3(3)(c) deals with the application of proof, the entire 8.8.1.3(3).

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 39: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 39/163

Public Input No. 117-NFPA 86-2012 [ Section No. 8.2.8 ]

8.2.8*

A At least one manual emergency switch shall be provided to initiate a safety shutdown.

Statement of Problem and Substantiation for Public Input

The 2011 Edition implies there is to be a single manual emergency switch. Depending upon the type of furnace there maybe multiple manual emergency switches to address the multiple “safety” hazards of the furnace. All of the furnace’s safety hazards should be evaluated and a manual emergency “system” should be designed/incorporated into the furnace design.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:22:09 EDT 2012

Committee Statement

Resolution: FR-22-NFPA 86-2012

Statement: The Committee revised the current text that implies there is to be a single manual emergency switch. Depending upon the type offurnace there maybe multiple manual emergency switches to address the multiple “safety” hazards of the furnace. All of thefurnace’s safety hazards should be evaluated and a manual emergency “system” should be designed/incorporated into the furnacedesign.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 40: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 40/163

Public Input No. 125-NFPA 86-2012 [ Section No. 8.2.9 ]

8.2.9

Shutdown of the heating system by any safety feature or safety device shall require manual intervention of an operator for re-establishment of normal operation of the system.8.2.9.1 Recycling without manual intervention shall be permitted provided all of the following are met:

(1) When using a listed combination combustion safeguard and burner safety sequence controller with recycle feature.

(2) The number of re-cycles shall not exceed 2.

(3) The recycling shall not cause the combustible concentration to exceed 25% of the LFL.

Statement of Problem and Substantiation for Public Input

Recycling is a feature of a majority of combination combustion safeguard and burner safety sequence controllers that are listed by UL, CSA and FM. The proposal calls specific attention to this feature so that the user understands its relationship to 8.2.9 and how to apply it safely.

Submitter Information Verification

Submitter Full Name:John Eley

Organization: GN Electronics Inc.

Submittal Date: Fri Jun 22 09:10:27 EDT 2012

Committee Statement

Resolution: FR-32-NFPA 86-2012

Statement: The Committee believes that the revised section and the added annex material meets the submitter's intent on when manualintervention is required, see the added annex in FR-120-NFPA 86-2012.

Copyright Assignment

I, John Eley, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Eley, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained therein.

I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force and

effect as a handw ritten signature

Page 41: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 41/163

Public Input No. 51-NFPA 86-2012 [ New Section after 8.2.10 ]

8.2.11

Where transmitters are used in place of switches for safety functions, the following shall apply:

(a) The transmitter shall possess a MTBF rating of 250,000 hours, or possess a safety integrity level (SIL) rating of 2.

(b) Transmitter failure shall be detected and initiate a safety shutdown.

(c) The transmitter shall be dedicated to safety service unless listed for simultaneous process and safety service.

Statement of Problem and Substantiation for Public Input

Relocates and modifies requirement from PLC subsection and makes it generally applicable to all safety control systems (including hardwired). See also related Public Input that deletes this text from Section 8.4.4

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 10:15:24 EDT 2012

Committee Statement

Resolution: FR-9-NFPA 86-2012

Statement: Relocates text from 8.4.4 and modifies requirement from PLC subsection and makes it generally applicable to all safety controlsystems (including hardwired), see FR-83- NFPA 86-2012 for the deletion of this text in 8.4.4. Use of MTBF (Mean Time BetweenFailures) is ambiguous as to the type of failure mode. MTBF does not distinguish if the safety function is compromised. AProbability of Failure on Demand (PFD) measures the failure rate that compromises the safety function. A transmitter that is SIL-2capable has met or exceeded a PFD defined by IEC61508 as well as other fault criteria. Requiring the transmitter be SIL-2capable simplifies the selection. SIL-2 capable transmitters are readily available, so this requirement would not cause an undueburden.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 42: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 42/163

Public Input No. 102-NFPA 86-2012 [ Section No. 8.3 ]

8.3* Logic Systems Burner Management System Logic .

8.3.1 General.

8.3.1.1

Purge, ignition trials, and other burner safety sequencing shall be performed using either devices listed for such service orprogrammable controllers used in accordance with Section 8.4.

8.3.1.2

The activation of any safety interlock required in Chapter 8 shall result in a safety shutdown.

8.3.2 Hardwired Logic Systems.

8.3.2.1

Safety interlocks shall meet one or more of the following criteria:

(1) Be hardwired without relays in series ahead of the controlled device

(2) Be connected to an input of a programmable controller logic system complying with Section 8.4

(3) Be connected to a relay that represents a single safety interlock configured to initiate safety shutdown in the event ofpower loss

(4) Be connected to a listed safety relay that represents one or more safety interlocks and initiates safety shutdown uponpower loss

8.3.2.2*

Electrical power for safety control circuits shall be dc or single-phase ac, 250 volt maximum, one-side grounded, with allbreaking contacts in the ungrounded, fuse-protected, or circuit breaker–protected line.

Statement of Problem and Substantiation for Public Input

The term Burner Management System is used to describe the Logic Systems covered in section 8.3. The proposed definition for Section 3.3.6 is taken directly from NFPA 85-2011. The annex material proposed for A.3.3.6 is new for NFPA 86.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:25:13 EDT 2012

Committee Statement

Resolution: FR-80-NFPA 86-2012

Statement: The term Burner Management System is used to describe the Logic Systems covered in section 8.3. The proposed definition forSection 3.3.6 is taken directly from NFPA 85-2011. The annex material proposed for A.3.3.6 is new for NFPA 86.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 43: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 43/163

Public Input No. 129-NFPA 86-2012 [ Section No. 8.3.1.1 ]

8.3.1.1

Purge , and ignition trials , and other burner safety sequencing shall be performed using either devices listed for such serviceor programmable controllers used in accordance with Section 8.4.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #99 at Section 8.5.2.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 99-NFPA 86-2012 [New Section after 8.5.2.1] Interrelated proposals for combustion safeguards

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:12:10 EDT 2012

Committee Statement

Resolution: FR-80-NFPA 86-2012

Statement: The term Burner Management System is used to describe the Logic Systems covered in section 8.3. The proposed definition forSection 3.3.6 is taken directly from NFPA 85-2011. The annex material proposed for A.3.3.6 is new for NFPA 86.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 119-NFPA 86-2012 [ Section No. 8.4.2 ]

8.4.2

PLCs , except those listed for combustion safety service, shall be used in accordance with 8.4.2.1 through 8.4.2.3 . andassociated I/O used to perform safety functions shall be certified to IEC 61508 for use in safety applications with a safetyintegrity level of 2 or greater. The safety functions shall be implemented according to the device’s safety manual requirementsto achieve a safety integrity level of 2 or greater.

8.4.2.1 General.

(A)

Before the PLC is placed in operation, documentation shall be provided that confirms that all related safety devices and safetylogic are functional.

(B)

All changes to hardware or software shall be documented and maintained in a file that is separate from the furnaceprogrammable controller.

(C)

System operation shall be tested and verified for compliance with the design criteria when the PLC is replaced, repaired, orupdated.

(D)

The control system shall have at least one manual emergency switch that initiates a safety shutdown.

Page 44: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 44/163

(E)

The PLC shall detect the following conditions:

(1) Failure to execute any program or task containing safety logic

(2) Failure to communicate with any safety input or output

(3) Changes in software set points of safety functions

(4) Failure of outputs related to safety functions

(5) Failure of timing related to safety functions

(F)

A safety shutdown shall occur within 3 seconds of detecting any condition listed in

8.4.2.

1(E).

(G)

A dedicated PLC output shall initiate a safety shutdown for faults detected by the PLC.

(H)

Unless allowed by 8.4.5 , the following devices and logic shall be hardwired external to the PLC:

(1) Manual emergency switch

(2) Combustion safeguards

(3) Safe-start checks

(4) Ignition transformers

(5) Trial-for-ignition periods

(6) Excess temperature limit interlocks

(7) The 1400°F (760°C) bypass interlocks required by Section 8.17

(8) Continuous vapor concentration high limit controller

(9) Valve-proving systems

(I)

Unless allowed by 8.4.5 , a combustion safeguard shall directly control at least one safety shutoff valve between the fuel gassupply and the monitored burner.

(J)

Unless allowed by 8.4.5 , where two oxygen safety shutoff valves are required, combustion safeguards shall control at leastone oxygen safety shutoff valve.

(K)

Where airflow-proving logic is performed in the PLC, the logic shall include the following:

(1) Verification of a change of state in each airflow-proving device during the startup of the related ventilation equipment

(2) Initiation of a safety shutdown if a change of state in an airflow-proving device is not detected

8.4.2.2 Hardware.

(A)

Memory that retains information on loss of system power shall be provided for software.

(B)

The PLC shall have a minimum mean-time-between-failures (MTBF) rating of 250,000 hours.

(C)

Only one safety device shall be connected to a PLC input or output.

(D)

Output checking shall be provided for PLC outputs controlling fuel safety shutoff valves and oxygen safety shutoff valves.

8.4.2.

3 Software.

(A)

Access to the PLC and its logic shall be restricted to authorized personnel.

(E)

Page 45: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 45/163

(B)

The following power supplies shall be monitored:

(1) Power supplies used to power PLC inputs and outputs that control furnace safety functions

(2) Power supplies used to power pressure and flow transmitters required by 8.4.4

(C)

When any power supply required by 8.4.2.3(B) (1) fails, the dedicated PLC output required in 8.4.2.1(G) shall be deactivated.

(D)

When the voltage of any power supply required by 8.4.2.3(B) (2) is detected outside the manufacturer's recommended range,the dedicated PLC output required in 8.4.2.1(G) shall be deactivated.

Software shall be documented as follows:

(1) Labeled to identify elements or group of elements containing safety software

(2) Labeled to describe the function of each element containing safety software

(F C )

A listing of the program with documentation shall be available.

Statement of Problem and Substantiation for Public Input

Section 8.4 currently requires that developers or end-users who want to use a general purpose PLC in a combustion application to ensure that the general purpose PLC meets a list of performance criterion. Once those criteria are met, the general purpose PLC is still forbidden from performing most safety functions. In this proposed change, a simplification is made to require that all safety functions must be performed in a device that has been certified to IEC 61508 for use in safety applications with a safety integrity level of 2 or greater.Section 8.4.3 was kept because it is widely accepted that general purpose PLCs perform timing functions with very high reliability.Section 8.4.5(B) (3) was dropped from the list to be consistent with the new Siemens interpretation of the combustion safeguard (Public Input # at Section 8.10.1) to be a flame sensor. For consistency, safety PLCs should not be excluded from doing flame sensing.Section 8.4.5(B) (4) was dropped from the list because the safety PLC is permitted to do ignition timing, purge timing, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic so the excess temperature safety function should also be included.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:27:10 EDT 2012

Committee Statement

Resolution: FR-83-NFPA 86-2012

Statement: General revisions to sections 8.3 and 8.4 to clarify Committee intent regarding logic systems and the application of PLC’s.Regarding paragraph 8.4.4, the use of MTBF (Mean Time Between Failures) is ambiguous as to the type of failure mode. MTBFdoes not distinguish if the safety function is compromised. A Probability of Failure on Demand (PFD) measures the failure ratethat compromises the safety function. A transmitter that is SIL2 capable has met or exceeded a PFD defined by IEC61508 as wellas other fault criteria. Requiring the transmitter be SIL?2 capable simplifies the selection. SIL2 capable transmitters are readilyavailable, so this requirement would not cause an undue burden. Combustion safeguard was removed from the safety PLCbecause it is a physical component that cannot be part of the logic system. The Committee believes that Safety PLCs should beable to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purgetiming, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic sothere is no logical reason to exclude the excess temperature safety function from Safety PLC functionality. Deletes and relocates8.4.4 and to 8.2.11 to makes it generally applicable to all safety control systems (including hardwired). See FR-9-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 46: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 46/163

Public Input No. 121-NFPA 86-2012 [ Section No. 8.4.3 ]

8.4.3

PLCs that do not comply with 8.4.1 or 8.4.2 shall comply with the following:

(1) The PLC shall not perform required safety functions.

(2) The PLC shall not interfere with or prevent the operation of the safety interlocks.

(3) Only isolated PLC contacts shall be used in the required safety circuits.

General purpose PLCs shall be permitted to perform the purge timing function.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #119 at Section 8.4.2.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 119-NFPA 86-2012 [Section No. 8.4.2] Several interrelated PLC proposals

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:51:57 EDT 2012

Committee Statement

Resolution: FR-83-NFPA 86-2012

Statement: General revisions to sections 8.3 and 8.4 to clarify Committee intent regarding logic systems and the application of PLC’s.Regarding paragraph 8.4.4, the use of MTBF (Mean Time Between Failures) is ambiguous as to the type of failure mode. MTBFdoes not distinguish if the safety function is compromised. A Probability of Failure on Demand (PFD) measures the failure ratethat compromises the safety function. A transmitter that is SIL2 capable has met or exceeded a PFD defined by IEC61508 as wellas other fault criteria. Requiring the transmitter be SIL?2 capable simplifies the selection. SIL2 capable transmitters are readilyavailable, so this requirement would not cause an undue burden. Combustion safeguard was removed from the safety PLCbecause it is a physical component that cannot be part of the logic system. The Committee believes that Safety PLCs should beable to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purgetiming, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic sothere is no logical reason to exclude the excess temperature safety function from Safety PLC functionality. Deletes and relocates8.4.4 and to 8.2.11 to makes it generally applicable to all safety control systems (including hardwired). See FR-9-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 47: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 47/163

Public Input No. 144-NFPA 86-2012 [ Section No. 8.4.4 ]

8.4.4

Where PLC-based systems use flow transmitters in place of flow switches and pressure transmitters in place of pressureswitches for safety functions, the following shall apply:

(1) The transmitter shall be listed, possess a MTBF rating of 250,000 hours, or possess a safety integrity level (SIL) rating of2.

(2) Upon transmitter failure, the PLC shall detect the failure and initiate a safety shutdown.

(3) The transmitter shall be dedicated to safety service unless listed for simultaneous process and safety service.

(4) Each transmitter shall be used to replace only 1 safety component required within this code

A.8.4.4(4) When applying transmitters, each transmitter may replace only one Combustion Safeguard. ie Low Gas Pressureswitch and High Gas Pressure switch would require 1 transmitter for each device or service.

Statement of Problem and Substantiation for Public Input

While it may be practical to apply 1 transmitter to sense both high and low gas pressure, location becomes an issue and currently we require 2 switches because of location. Is this an acceptable substitution from a safety standpoint?

Submitter Information Verification

Submitter Full Name:Franklin Switzer

Organization: S-afe, Inc.

Submittal Date: Fri Jun 22 15:46:28 EDT 2012

Committee Statement

Resolution: The correct gas pressure for the system is a single safety function and as such there is no need for two transmitters.

Copyright Assignment

I, Franklin Sw itzer, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Franklin Sw itzer, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 48: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 48/163

Public Input No. 52-NFPA 86-2012 [ Section No. 8.4.4 ]

8.4.4

Where PLC-based systems use flow transmitters in place of flow switches and pressure transmitters in place of pressureswitches for safety functions, the following shall apply:

(1) The transmitter shall be listed, possess a MTBF rating of 250,000 hours, or possess a safety integrity level (SIL) rating of2.

(2) Upon transmitter failure, the PLC shall detect the failure and initiate a safety shutdown.

(3) The transmitter shall be dedicated to safety service unless listed for simultaneous process and safety service.

Statement of Problem and Substantiation for Public Input

Relocates and modifies requirement from PLC subsection and makes it generally applicable to all safety control systems (including hardwired). See also related Public Input that adds this text to Section 8.2.11.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 51-NFPA 86-2012 [New Section after 8.2.10] Interrelated new section on transmitters

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 10:18:59 EDT 2012

Committee Statement

Resolution: FR-83-NFPA 86-2012

Statement: General revisions to sections 8.3 and 8.4 to clarify Committee intent regarding logic systems and the application of PLC’s.Regarding paragraph 8.4.4, the use of MTBF (Mean Time Between Failures) is ambiguous as to the type of failure mode. MTBFdoes not distinguish if the safety function is compromised. A Probability of Failure on Demand (PFD) measures the failure ratethat compromises the safety function. A transmitter that is SIL2 capable has met or exceeded a PFD defined by IEC61508 as wellas other fault criteria. Requiring the transmitter be SIL?2 capable simplifies the selection. SIL2 capable transmitters are readilyavailable, so this requirement would not cause an undue burden. Combustion safeguard was removed from the safety PLCbecause it is a physical component that cannot be part of the logic system. The Committee believes that Safety PLCs should beable to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purgetiming, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic sothere is no logical reason to exclude the excess temperature safety function from Safety PLC functionality. Deletes and relocates8.4.4 and to 8.2.11 to makes it generally applicable to all safety control systems (including hardwired). See FR-9-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 49: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 49/163

Public Input No. 122-NFPA 86-2012 [ New Section after 8.4.5(B) ]

8.4.6

PLCs shall not implement the following:

(1) Manual emergency switches

(2) Continuous vapor concentration high limit controllers

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #119 at Section 8.4.2

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 119-NFPA 86-2012 [Section No. 8.4.2] Several interrelated PLC proposals

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:55:59 EDT 2012

Committee Statement

Resolution: FR-83-NFPA 86-2012

Statement: General revisions to sections 8.3 and 8.4 to clarify Committee intent regarding logic systems and the application of PLC’s.Regarding paragraph 8.4.4, the use of MTBF (Mean Time Between Failures) is ambiguous as to the type of failure mode. MTBFdoes not distinguish if the safety function is compromised. A Probability of Failure on Demand (PFD) measures the failure ratethat compromises the safety function. A transmitter that is SIL2 capable has met or exceeded a PFD defined by IEC61508 as wellas other fault criteria. Requiring the transmitter be SIL?2 capable simplifies the selection. SIL2 capable transmitters are readilyavailable, so this requirement would not cause an undue burden. Combustion safeguard was removed from the safety PLCbecause it is a physical component that cannot be part of the logic system. The Committee believes that Safety PLCs should beable to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purgetiming, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic sothere is no logical reason to exclude the excess temperature safety function from Safety PLC functionality. Deletes and relocates8.4.4 and to 8.2.11 to makes it generally applicable to all safety control systems (including hardwired). See FR-9-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 50: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 50/163

Public Input No. 114-NFPA 86-2012 [ Section No. 8.4.5(B) ]

(B)

Safety PLCs shall not implement the following:

(1) Manual emergency switches

(2) Continuous vapor concentration high limit controllers

(3) Combustion safeguards

(4) Excess temperature limit interlocks

Statement of Problem and Substantiation for Public Input

The "Siemens Interpretation" of the term combustion safeguard (Public Input # at Section 8.10.1, and linked sections) essentially redefines the term to be a flame sensor. As such, Safety PLCs should be able to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purge timing, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic so there is no logical reason to exclude the excess temperature safety function from Safety PLC functionality.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 02:55:00 EDT 2012

Committee Statement

Resolution: FR-83-NFPA 86-2012

Statement: General revisions to sections 8.3 and 8.4 to clarify Committee intent regarding logic systems and the application of PLC’s.Regarding paragraph 8.4.4, the use of MTBF (Mean Time Between Failures) is ambiguous as to the type of failure mode. MTBFdoes not distinguish if the safety function is compromised. A Probability of Failure on Demand (PFD) measures the failure ratethat compromises the safety function. A transmitter that is SIL2 capable has met or exceeded a PFD defined by IEC61508 as wellas other fault criteria. Requiring the transmitter be SIL?2 capable simplifies the selection. SIL2 capable transmitters are readilyavailable, so this requirement would not cause an undue burden. Combustion safeguard was removed from the safety PLCbecause it is a physical component that cannot be part of the logic system. The Committee believes that Safety PLCs should beable to perform flame sensing and it should not be excluded here. Similarly, Safety PLCs are permitted to do ignition timing, purgetiming, safe start check, low temperature permissive, limits monitoring, the combustion sequence, and all associated logic sothere is no logical reason to exclude the excess temperature safety function from Safety PLC functionality. Deletes and relocates8.4.4 and to 8.2.11 to makes it generally applicable to all safety control systems (including hardwired). See FR-9-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 51: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 51/163

Public Input No. 160-NFPA 86-2012 [ Section No. 8.5.1.2(C) ]

(C)

To begin the timed pre-ignition purge interval, both of the following conditions shall be satisfied:

(1)

(2) The safety shutoff valve(s) is proved closed when proved closed is required in 8 .8.2.

Statement of Problem and Substantiation for Public Input

Clarifies that in order to begin the pre-ignition purge interval, the requirement to prove the safety shutoff valve closed only applies when proved close is required in 8.8.2, not on every burner system, especially those less than 400,000 btu/hr.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:25:02 EDT 2012

Committee Statement

Resolution: FR-37-NFPA 86-2012

Statement: The intent of the submitter has been met by the reference to 8.8.2.2, for proven closed requirement has been incorporated into8.5.1.2(C). See FR-35-NFPA 86-2012 for the added annex material for 8.5.1.2(c).

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

* The minimum required pre-ignition airflow is proved.

Page 52: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 52/163

Public Input No. 43-NFPA 86-2012 [ Section No. 8.5.1.2(C) ]

(C)

To begin the timed pre-ignition purge interval, both of the following conditions shall be satisfied:

(1)

(2) The safety shutoff valve(s) is proved required by 8.8.2 are proved closed.

Statement of Problem and Substantiation for Public Input

Clarifies that in order to begin the pre-ignition purge interval, the requirement for the safety shutoff valve to be "proved closed" only applies when a "proved closed" condition is required in 8.8.2. "Proved closed" is not required on every burner system, especially those less than 400,000 BTU/hr.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Submitted as Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Wed Jun 06 18:59:15 EDT 2012

Committee Statement

Resolution: FR-37-NFPA 86-2012

Statement: The intent of the submitter has been met by the reference to 8.8.2.2, for proven closed requirement has been incorporated into8.5.1.2(C). See FR-35-NFPA 86-2012 for the added annex material for 8.5.1.2(c).

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 147-NFPA 86-2012 [ Section No. 8.5.1.8 ]

* The minimum required pre-ignition airflow is proved.

Page 53: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 53/163

8.5.1.8*

Repeating the pre-ignition purge shall not be required where any one of the following conditions is satisfied:

(1) The heating chamber temperature is proved above 1400°F (760°C).

(2) For a multiburner fuel-fired system not proved above 1400°F (760°C), all of the following conditions are satisfied:

(a)

(b) The burner(s) remaining in operation shall provide ignition of any unintended release of fuel through other burners thatare not in operation without explosion.

(3)

(4) All of the following conditions are satisfied (does not apply to fuel oil systems):

(a) At least two safety shutoff valves are proved closed between a burner The number of safety shutoff valves required toclose in 8.8.1.3 and 8.8.2.1 will close between the burner system and the fuel gas supply when that burnerburner system is off.

(b) Safety shutoff valve seat leak testing is performed on at least a semiannual basis.

(c) The burner system uses natural gas, butane, or propane fuel gas.

(d)

(e) The minimum airflow used in the LFL calculation in 8.5.1.8(4)(d) is proved and maintained during the period theburner(s) are off.

Statement of Problem and Substantiation for Public Input

This proposal incorporates but changes TIA 11-4. It resolves a conflict and eliminates multiple-level referencing (a section that refers to another section). The conflict is that 8.5.1.8 (4) ‘does not apply to fuel oil systems’ but the original TIA 11-4 cites 8.8.1.2 which refers to 8.8.3.1 on Oil Safety Shutoff Valves. By deleting TIA 11-4's referral to 8.8.1.2 and replacing it with 8.8.2.1, the proposed language more directly points the user to the number of valves required for fuel gas.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Fri Jun 22 16:21:42 EDT 2012

Committee Statement

Resolution: FR-29-NFPA 86-2012

Statement: This revision incorporates but changes TIA 11-4. It resolves a conflict and eliminates multiple-level referencing (a section that refersto another section). The conflict is that 8.5.1.8 (4) ‘does not apply to fuel oil systems’ but the original TIA 11-4 cites 8.8.1.2 whichrefers to 8.8.3.1 on Oil Safety Shutoff Valves. By deleting TIA 11-4's referral to 8.8.1.2 and replacing it with 8.8.2.1, the proposedlanguage more directly points the user to the number of valves required for fuel gas. The Committee did not incorporate thechanges of PI-159 because existing requirements preclude the need for time limits. The submitter did not provide datasubstantiation for the time limits submitted.

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 159-NFPA 86-2012 [ Section No. 8.5.1.8 ]

* At least one burner remains operating in the common combustion chamber of the burner to be re-ignited.

* For fuel gas–fired burner systems and assuming that all safety shutoff valves fail in the full open position, it can bedemonstrated that the combustible concentration in the heating chamber and all other passages that handle therecirculation and exhaust of products of combustion cannot exceed 25 percent of the LFL.

* It can be demonstrated that the , based on the safety shutoff valve leakage rates, that the combustibleconcentration in the heating chamber and all other passages that handle the recirculation and exhaust of products ofcombustion cannot exceed 25 percent of the LFL.

Page 54: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 54/163

8.5.1.8*

Repeating the pre-ignition purge shall not be required where the oven idle (no processing and no maintenance supervision)period is not longer than 48 hours. the duration of all burners off has not exceeded 24 hours. and any one of the followingconditions is satisfied:

(1) The heating chamber temperature is proved above 1400°F (760°C).

(2) For a multiburner fuel-fired system not proved above 1400°F (760°C), all of the following conditions are satisfied:

(a)

(b) The burner(s) remaining in operation shall provide ignition of any unintended release of fuel through other burners thatare not in operation without explosion.

(3)

(4) All of the following conditions are satisfied (does not apply to fuel oil systems):

(a) At least two safety shutoff valves are proved closed between a burner and the fuel gas supply when that burner is off.

(b) Safety shutoff valve seat leak testing is performed on at least a semiannual basis.

(c) The burner system uses natural gas, butane, or propane fuel gas.

(d)

(e) The minimum airflow used in the LFL calculation in 8.5.1.8(4)(d) is proved and maintained during the period theburner(s) are off.

Statement of Problem and Substantiation for Public Input

The proposed change is to clarify that current language is not intended to permit leaving an oven in an idle state (no processing is occurring) and unattended over a weekend. Also, the proposal limits the length of the "all burners off- time" to 24 hours as the maximum permitted off-time. Permitting an infinite "all burners off-time" in 8.5.1.8(4)(d) is an unsafe practice because unforeseen conditions during the off-time can gradually change during the off-time, which can then lead to a hazardous condition. By limiting the burner off-time and forcing at least some burners to operate at least once every 24 hours increases the safety of the oven by resetting the parameters and conditions that are used to comply with 8.5.1.8(4)(d).

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:23:51 EDT 2012

Committee Statement

Resolution: FR-29-NFPA 86-2012

Statement: This revision incorporates but changes TIA 11-4. It resolves a conflict and eliminates multiple-level referencing (a section that refersto another section). The conflict is that 8.5.1.8 (4) ‘does not apply to fuel oil systems’ but the original TIA 11-4 cites 8.8.1.2 whichrefers to 8.8.3.1 on Oil Safety Shutoff Valves. By deleting TIA 11-4's referral to 8.8.1.2 and replacing it with 8.8.2.1, the proposedlanguage more directly points the user to the number of valves required for fuel gas. The Committee did not incorporate thechanges of PI-159 because existing requirements preclude the need for time limits. The submitter did not provide datasubstantiation for the time limits submitted.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 178-NFPA 86-2012 [ Section No. 8.5.1.8 ]

* At least one burner remains operating in the common combustion chamber of the burner to be re-ignited.

* For fuel gas–fired burner systems and assuming that all safety shutoff valves fail in the full open position, it can bedemonstrated that the combustible concentration in the heating chamber and all other passages that handle therecirculation and exhaust of products of combustion cannot exceed 25 percent of the LFL.

* It can be demonstrated that the combustible concentration in the heating chamber and all other passages thathandle the recirculation and exhaust of products of combustion cannot exceed 25 percent of the LFL.

Page 55: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 55/163

8.5.1.8*

Repeating the pre-ignition purge shall not be required where any one of the following conditions is satisfied:

(1) The heating chamber temperature is proved above 1400°F (760°C).

(2) For a multiburner fuel-fired system not proved above 1400°F (760°C), all of the following conditions are satisfied:

(a)

(b) The burner(s) remaining in operation shall provide ignition of any unintended release of fuel through other burners thatare not in operation without explosion.

(3)

(4) All of the following conditions are satisfied (does not apply to fuel oil systems):

(a) At least two The number of safety shutoff valves are proved closed between a burner required to close in 8.8.1.2 and8.8.1.3 will close between the burner system and the fuel gas supply when that burner system is off.

(b) Safety shutoff valve seat leak testing is performed on at least a semiannual basis.

(c) The burner system uses natural gas, butane, or propane fuel gas.

(d)

(e) The minimum airflow used in the LFL calculation in 8.5.1.8(4)(d) is proved and maintained during the period theburner(s) are off.T

Statement of Problem and Substantiation for Public Input

Note: This Proposal originates from Tentative Interim Amendment 86-11-4 (TIA 1011) issued by the Standards Council on March 1, 2011.The revised NFPA 86 (2011) paragraph 8.5.1.8 has introduced a new requirement that will require new or renovated bakery ovens to add a proof-of-closure switch to each safety shutoff valve. Bakery ovens can have up to 300 or more burners. As such, the change represents: 1) Installing a large number of proof-of-closure switches. 2) Expanded testing, inspection, and maintenance to cover all of the added switches. 3) Considerable wiring to connect all of these added switches. 4) Complex logic to monitor and process signals from all of the added switches.Emergency Nature: The revised NFPA 86 (2011) paragraph 8.5.1.8 contains an omission that was overlooked during the last revision cycle. Guidance specific to burners firing at rates less than or equal to 400,000 Btu/hr were not addressed in the revised text. In addition, the revised NFPA 86 (2011) paragraph 8.5.1.8 contains guidance that is in conflict with Section 8.8.2.2 as discussed further here. Consider the requirements of NFPA 86 as they would apply to an oven with the following characteristics: · Multiple burners · Each burner has a firing rate under 400,000 Btu/hr · Each burner has two safety shutoff valves · Each burner has a direct spark ignition with separate ignition electrode and separate flame sensing electrode. 1) NFPA 86 (2011) paragraph 8.8.2.2 would not require proof-of-closure on any of the safety shutoff valves. 2) NFPA 86 (2011) would not prohibit the shutdown of one or more burners (by closing the two burner safety shutoff valves) while maintaining other burners in service.Overall, if it is safe to operate this oven with any number of burners (fired under 400,000 Btu/hr) turned off by closing two safety shutoff valves, it should be equally safe to allow a restart of any or all burners without a repurge of the oven as long as the airflow rate needed to keep the oven atmosphere below 25% of LFL (based upon a valve seat leakage rate of 1 scfh) is maintain at all times that any burners are turned off. Overall, the basis of safety for the burners rated less than or equal to 400,000 Btu/hr is the use of two safety shutoff valves. The basis of safety does not expand to include proving valves closed until the burner rate exceeds 400,000 Btu/hr or a burner is taken out of service by closing one safety shutoff valve.

Submitter Information Verification

Submitter Full Name:PHILIP DOMENICUCCI

Organization: American Society of Bakers

Submittal Date: Fri Sep 14 12:25:01 EDT 2012

Committee Statement

Resolution: FR-29-NFPA 86-2012

Statement: This revision incorporates but changes TIA 11-4. It resolves a conflict and eliminates multiple-level referencing (a section that refersto another section). The conflict is that 8.5.1.8 (4) ‘does not apply to fuel oil systems’ but the original TIA 11-4 cites 8.8.1.2 whichrefers to 8.8.3.1 on Oil Safety Shutoff Valves. By deleting TIA 11-4's referral to 8.8.1.2 and replacing it with 8.8.2.1, the proposedlanguage more directly points the user to the number of valves required for fuel gas. The Committee did not incorporate thechanges of PI-159 because existing requirements preclude the need for time limits. The submitter did not provide datasubstantiation for the time limits submitted.

Copyright Assignment

I, PHILIP DOMENICUCCI, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input

(including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint

author, in any publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public

Input and that I have full pow er and authority to enter into this copyright assignment.

* At least one burner remains operating in the common combustion chamber of the burner to be re-ignited.

* For fuel gas–fired burner systems and assuming that all safety shutoff valves fail in the full open position, it can bedemonstrated that the combustible concentration in the heating chamber and all other passages that handle therecirculation and exhaust of products of combustion cannot exceed 25 percent of the LFL.

* It can be demonstrated that the combustible concentration in the heating chamber and all other passages thathandle the recirculation and exhaust of products of combustion cannot exceed 25 percent of the LFL.

Page 56: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 56/163

Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am PHILIP DOMENICUCCI, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions

contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same

legal force and effect as a handw ritten signature

Public Input No. 99-NFPA 86-2012 [ New Section after 8.5.2.1 ]

8.5.2.1

Prior to the trial for ignition the logic solver in conjunction with the flame safeguard shall perform a safe start check.

Statement of Problem and Substantiation for Public Input

The original definition of the combustion safeguard included a flame relay and all of the associated logic and the new definition is just a flame sensor. The flame sensor cannot perform a safe start check as that is a logic function. The intent of this requirement is to limit the maximum time between loss of flame and de-energization of SSOVs to be 4 seconds, and as such, the flame scanner cannot consume all of the allotted 4.0 seconds. Time must also remain for the interfacing logic, logic solver, and valve actuation. Or, on the other hand, If the intent is to permit the flame sensor to take up to 4 seconds by itself, then we must decide what is a reasonable time for the logic solver to actuate the valves and for the valves to close.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 23:59:23 EDT 2012

Committee Statement

Resolution: FR-125-NFPA 86-2012

Statement: The Committee clarified when combustion safeguards are required and not required. Additionally, the Committee clarified the flameresponse time requirement, safe-start check requirement, and allowable arrangements of combustion safeguards. The Committeereplaced the term "combustion safety circuitry" with "burner management system" per the removal of combustion safety circuitryfrom FR-85-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 57: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 57/163

Public Input No. 21-NFPA 86-2012 [ Section No. 8.5.2.1 ]

8.5.2.1

The trial-for-ignition period of the pilot burner shall not exceed 15 seconds unless it can be proven that an extension beyond 15seconds is beneficial and can not result in the furnace reaching 25% LFL .

Examples of beneficial extensions may include extension to allow maintenance adjustment of pilot burners, or to accomodategas travel time delays associated with location of pilot burner components to facilitate safe access. Safety of furnace operationsand maintenance personell shall not be compromised in order to reduce the pilot trial for ignition period.

Statement of Problem and Substantiation for Public Input

Particularly on large furnaces with multiple burners and a common combustion chamber, reliable operation of burner pilots is a common maintenance issue. On many of these furnaces it can be proven that constant operation of all pilot gas solenoids even with no flame detected can not allow 25% lfl to be reached regardless of elasped time due to contribution of pilot air and low fire setting burner air flows. On other furnaces the safe trial for pilot ignition interval may be minutes or hours instead of 15 seconds.Historic restrictions to 15 second trial for ignition intervals for pilots have created unneccessary complications to pilot maintenance and adjustment and have encouraged the practice of installing pilot control devices in close proximity to pilot burners. The combination of increased time required to address pilot issues, increased difficulty required to access pilot components, and installation of pilot components where most exposed to dirt and heat and mechanical damage, creates or exacerbates exposure by maintenance personell to fall and burn and heat stress hazards. In addition to increased risk to personell, the 15 second limitation creates additional downtime and loss of revenue. It is assumed, but not known, that 15 seconds came about historically due to convenience of commonality in regulation and to limitations of customization capabilities of older listed safeguard components.

Submitter Information Verification

Submitter Full Name:Jeff Jones

Organization: Flanders

Submittal Date: Wed Apr 11 15:26:58 EDT 2012

Committee Statement

Resolution: FR-33-NFPA 86-2012

Statement: The Committee believes the changes to the sections covers the submitter's intent.

Copyright Assignment

I, Jeff Jones, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Jeff Jones, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 58: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 58/163

Public Input No. 133-NFPA 86-2012 [ Section No. 8.5.2.4 ]

8.5.2.4

Electrical ignition energy for direct Where spark ignition systems cause a false flame signal in required combustionsafeguards, the electrical spark shall be terminated after the main burner trial-for-ignition period.

Exception : Continuous operation of direct spark igniters shall be permitted for explosion-resistant radiant tube–type heatingsystems, which do not require combustion safeguards.

Statement of Problem and Substantiation for Public Input

Clarifies intent and removes violation of NFPA’s “manual of style” concerning exceptions. Note that the exception still exists with the phrase “in required combustion safeguards”. Intent needed clarification because common understanding of direct spark burners versus piloted burners confuses the meaning of “direct spark ignition systems”. A user may assume that the spark can remain on throughout the pilot flame establishing period and then terminate after the main TFI period. Also, the user may assume that a piloted burner can have a spark that never terminates since this requirement applies to direct spark.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:38:52 EDT 2012

Committee Statement

Resolution: FR-43-NFPA 86-2012

Statement: Clarifies intent and conforms to NFPA’s “manual of style” concerning exceptions. Intent needed clarification because commonunderstanding of direct spark burners versus piloted burners confuses the meaning of “direct spark ignition systems”.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 59: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 59/163

Public Input No. 55-NFPA 86-2012 [ Section No. 8.6.1 ]

8.6.1 1*

Where a fan is essential to the operation of the oven or allied equipment, fan operation shall be proved and interlocked into thesafety circuitry.

8.6.1.1

Electrical interlocks and flow switches shall be arranged in the safety control circuit so that loss of ventilation or airflow shutsdown the heating system of the affected section, or, if necessary, loss of ventilation shall shut down the entire heating systemas well as the conveyor.

8.6.1.2

Air pressure switches shall not be used to prove airflow where dampers downstream of the pressure switch can be closed to thepoint of reducing airflow below the minimum required.

8.6.1.3

Air suction switches shall not be used to prove airflow where dampers upstream of the pressure switch can be closed to thepoint of reducing airflow below the minimum required.

8.6.1.4

Switches used to prove airflow on systems where the air is contaminated with any substance that might condense or otherwisecreate a deposit shall be selected and installed to prevent interference with the performance of the switch.

Statement of Problem and Substantiation for Public Input

See related substantiation for 8.6.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 54-NFPA 86-2012 [Section No. 8.6.1 [Excluding any Sub-Sections]] Indicates new Annex material affecting 8.6.1

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:04:11 EDT 2012

Committee Statement

Resolution: FR-27-NFPA 86-2012

Statement: The Committee clarified the breadth of the requirement and helps ensure consistency with other parts of this Standard.Additionally, the Committee added annex material to help clarify this requirement, see FR-51-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 60: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 60/163

Public Input No. 54-NFPA 86-2012 [ Section No. 8.6.1 [Excluding any Sub-Sections] ]

Where a fan or airflow is essential to the operation of the purge or safety ventilation of an oven or allied equipment, fanoperation and/or airflow shall be proved and interlocked into the safety circuitry.

Statement of Problem and Substantiation for Public Input

The proposed change clarifies the breadth of the requirement and helps ensure consistency with other parts of the Standard. • The existing wording only focused on proving a device (a fan), but fans are are only one means of creating the flows necessary for purge or safety ventilation. • The context of section 8.6 provides a basis for both purge and safety ventilation language in Chapters 8 and 11. However, there is a natural bias in Chapter 8 toward purge (since safety ventilation is only applicable to Class A ovens) so it is important to use more inclusive language to ensure the reader considers safety ventilation needs when determining if a fan or airflow is essential.• The existing wording “essential to the operation” was imprecise because it could be construed to pertain to concerns beyond the scope of NFPA 86, for example “essential for quality control”Annex material is also added in response to industry questions regarding acceptable methods for monitoring operation of non-ducted fans or fans not enclosed in a dedicated housing.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 13:51:52 EDT 2012

Committee Statement

Resolution: FR-27-NFPA 86-2012

Statement: The Committee clarified the breadth of the requirement and helps ensure consistency with other parts of this Standard.Additionally, the Committee added annex material to help clarify this requirement, see FR-51-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 61: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 61/163

Public Input No. 115-NFPA 86-2012 [ New Section after 8.6.2 ]

8.6.3

In any combustion system where the combustion air supply can be diverted to an alternate flow path than a burner (such as to aregenerative burner system’s exhaust path), that burner’s associated combustion air flow path valve(s) must be proven open, and itsalternate air flow path valve(s) proven closed, before that burner’s fuel Safety Shutoff Valve(s) are energized.

Statement of Problem and Substantiation for Public Input

In a regenerative combustion system, independent combustion air and exhaust cycle valves may be used to correctly establish the simultaneous flow paths of combustion air and exhaust during each regenerative cycle. With an exhaust cycle valve incorrectly positioned during a firing cycle, fuel will be introduced into the burner without combustion air available. Even though the combustion chamber may be proven above 1400F, the exhaust system would be expected to be well below 1400F. Fuel passing to the exhaust system creates a potential hazard. This proposal seeks to add requirements to ensure combustion air and exhaust cycle valves are in the correct position prior to energizing the fuel SSOV’s.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:10:18 EDT 2012

Committee Statement

Resolution: FR-20-NFPA 86-2012

Statement: In a regenerative combustion system, independent combustion air and exhaust cycle valves may be used to correctly establishthe simultaneous flow paths of combustion air and exhaust during each regenerative cycle. With an exhaust cycle valve incorrectlypositioned during a firing cycle, fuel will be introduced into the burner without combustion air available. Even though thecombustion chamber may be proven above 1400F, the exhaust system would be expected to be well below 1400F. Fuel passingto the exhaust system creates a potential hazard. This revision adds requirements to ensure combustion air and exhaust cyclevalves are in the correct position prior to energizing the fuel SSOV’s.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 62: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 62/163

Public Input No. 131-NFPA 86-2012 [ Section No. 8.7.1 ]

8.7.1

Where air from the exhaust or recirculating fans is required for combustion of the fuel, the minimum required airflow shall beproved prior to an ignition attempt. interlocked according to 8.7.5.

Statement of Problem and Substantiation for Public Input

The requirements in 8.7.5 permit either airflow or air pressure interlocks. The requirements in 8.7.1 only identify airflow requirements. The revised language eliminates any possible conflict between the current requirements in 8.7.1 and those in 8.7.5. The requirement in 8.7.2 is redundant to the requirement in 8.7.5 which is to interlock airflow or pressure into the combustion safety circuitry which will result in the closure of the safety shutoff valves if the interlock is not proven.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:31:41 EDT 2012

Committee Statement

Resolution: FR-42-NFPA 86-2012

Statement: The requirements in the newly renumbered 8.7.5 permits either airflow or air pressure interlocks. The requirements in 8.7.1 onlyidentify airflow requirements. The revised language eliminates any possible conflict between the current requirements in 8.7.1 andthose in 8.7.5. The requirement in 8.7.2 is redundant to the requirement in 8.7.5 which is to interlock airflow or pressure into thecombustion safety circuitry which will result in the closure of the safety shutoff valves if the interlock is not proven. Additionally, theCommittee replaced the term "combustion safety circuitry" with "burner management system" per the removal of combustionsafety circuitry from FR-85-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 63: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 63/163

Public Input No. 132-NFPA 86-2012 [ Section No. 8.7.2 ]

Found 2 configuration elements matching the xpath: /systemconfig/systemhomeroot in file C:\TerraXML\terra_view_config.xml

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #131 at Section 8.7.1

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 131-NFPA 86-2012 [Section No. 8.7.1] Interrelated proposals about minimum airflow interlocks

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:35:46 EDT 2012

Committee Statement

Resolution: FR-42-NFPA 86-2012

Statement: The requirements in the newly renumbered 8.7.5 permits either airflow or air pressure interlocks. The requirements in 8.7.1 onlyidentify airflow requirements. The revised language eliminates any possible conflict between the current requirements in 8.7.1 andthose in 8.7.5. The requirement in 8.7.2 is redundant to the requirement in 8.7.5 which is to interlock airflow or pressure into thecombustion safety circuitry which will result in the closure of the safety shutoff valves if the interlock is not proven. Additionally, theCommittee replaced the term "combustion safety circuitry" with "burner management system" per the removal of combustionsafety circuitry from FR-85-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 64: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 64/163

Public Input No. 116-NFPA 86-2012 [ New Section after 8.7.6 ]

8.7.7

In any combustion system where the combustion air supply can be diverted to an alternate flow path than a burner (such as to aregenerative burner system’s exhaust path), that burner’s associated combustion air flow path valve(s) must be proven open, and itsalternate air flow path valve(s) proven closed, before that burner’s fuel Safety Shutoff Valve(s) are energized.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #115 at Section 8.6.3

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 115-NFPA 86-2012 [New Section after 8.6.2] Regenerative burner SSOV proposals are interrelated

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:13:00 EDT 2012

Committee Statement

Resolution: FR-21-NFPA 86-2012

Statement: In a regenerative combustion system, independent combustion air and exhaust cycle valves may be used to correctly establishthe simultaneous flow paths of combustion air and exhaust during each regenerative cycle. With an exhaust cycle valve incorrectlypositioned during a firing cycle, fuel will be introduced into the burner without combustion air available. Even though thecombustion chamber may be proven above 1400F, the exhaust system would be expected to be well below 1400F. Fuel passingto the exhaust system creates a potential hazard. This revision adds requirements to ensure combustion air and exhaust cyclevalves are in the correct position prior to energizing the fuel SSOV’s.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 151-NFPA 86-2012 [ Section No. 8.8.1.3 ]

Page 65: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 65/163

8.8.1.3*

In fuel gas burner systems or oil burner systems where multiple burners or pilots operate as a burner system firing main orpilot fuel gas burners systems fire into a common or individual heating chamber, the loss of flame signal at one or moreburners burner systems either shall comply with 8.8.1.2 or shall shut off those the burner system (s) by closing a singlesafety shutoff valve as long as a second safety shutoff valve between the fuel supply, and the burners burner systems(s) shallclose when any of the following conditions occurs:

(1) Upon activation of any safety interlock common to the burner system

(2)

(3) Where individual burner system safety shutoff valves have proof of closure and any of the following conditions occurs:

(a) Where flame supervision is used, the individual burner safety shutoff valve not proved closed after loss of flame signal

(b) Where flame supervision is not used, the individual burner safety shutoff valve not proved closed when the furnace isnot proved to be above 1400°F (760°C)

(c) Upon loss of flame signal at all burners in the burner system

Statement of Problem and Substantiation for Public Input

The current language permits one burner on a multiple burner oven to shutoff only in cases when the combustion chamber has more than one burner. It does not permit the case of a multiple burner oven where one burner system may shut off and other burner systems may have their own combustion chamber. Adding language to permit 8.8.1.3 to also apply to individual heating chambers does not reduce the level of safety since there are no other burners operating in the same heating chamber. The safety issue is relighting the burner system, which is handled in 8.5.1.8. Use the term "burner system" for consistency and because burner system is defined AS "One or more burners operated as a unit by a common safety shutoff valve(s)." It can be ambiguous if burner is used in lieu of burner system and vice versa. Other changes to the language are made to make it consistent with 8.8.2.1 and 8.8.2.2.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Mon Jul 02 08:22:33 EDT 2012

Committee Statement

Resolution: The submitter's recommendation makes the section more confusing.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

* Where the individual burner system safety shutoff valves do not have proof of closure and it is demonstrated, based onavailable airflow, that the number of failed burners burner systems will result in the furnace being above 25 percent of theLFL, assuming the single burner safety shutoff valve(s) fails in the open position

Page 66: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 66/163

Public Input No. 92-NFPA 86-2012 [ Section No. 8.8.1.3 ]

8.8.1.3*

In fuel gas systems or oil systems where multiple burners or pilots operate as a burner system firing into a common heatingchamber, the loss of flame signal at shut off of fuel at one or more burners either shall comply with 8.8.1.2 or shall shut offthose burner(s) by closing a single safety shutoff valve as long as a second safety shutoff valve between the fuel supply, and theburners shall close when any of the following conditions occurs:

(1) Upon activation of any safety interlock common to the burner system

(2)

(3) Where individual burner safety shutoff valves have proof of closure and any of the following conditions occurs:

(a) Where flame supervision is used, the individual burner safety shutoff valve not proved closed after loss of flame signal

(b) Where flame supervision is not used, the individual burner safety shutoff valve not proved closed when the furnace isnot proved to be above 1400°F (760°C)

(c) Upon loss of flame signal at all burners in the burner system

Statement of Problem and Substantiation for Public Input

The phrase "loss of flame signal" restricts the subsequent allowance for closing of one valve to only a combustion safeguard function. Shut off of fuel by a single valve from a temperature control function should also be allowed (where all requirements of this section are met). The annex Figure A.8.8.1.3 supports the idea of allowing "burner shutdown", i.e. controlled shut-off.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Thu Jun 21 12:29:57 EDT 2012

Committee Statement

Resolution: FR-95-NFPA 86-2012

Statement: The phrase "loss of flame signal" restricts the subsequent allowance for closing of one valve to only a combustion safeguardfunction. Shut off of fuel by a single valve from a temperature control function should also be allowed (where all requirements of thissection are met). The annex Figure A.8.8.1.3 supports the idea of allowing "burner shutdown", i.e. controlled shut-off.

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

* Where the individual burner safety shutoff valves do not have proof of closure and it is demonstrated, based on availableairflow, that the number of failed burners will result in the furnace being above 25 percent of the LFL, assuming the singleburner safety shutoff valve(s) fails in the open position

Page 67: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 67/163

Public Input No. 138-NFPA 86-2012 [ Section No. 8.8.1.6 ]

8 7 .8 4 .1 10 .6 3

Safety shutoff valves shall applied in pulse fired applications (rapid cycle applications) shall not be open-close cycled at a ratethat exceeds that specified by its manufacturer.

Statement of Problem and Substantiation for Public Input

This issue should only apply to rapid cycling of valves like that which occur during Pulse Fired burner applications. On a temporary basis such as during testing, rapid open and closing is sometimes used to clean the seat of the valve to clear debris.

Submitter Information Verification

Submitter Full Name:Franklin Switzer

Organization: S-afe, Inc.

Submittal Date: Fri Jun 22 14:06:40 EDT 2012

Committee Statement

Resolution: Section 8.2.2 already covers manufacturer’s instructions must always be followed.

Copyright Assignment

I, Franklin Sw itzer, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Franklin Sw itzer, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 68: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 68/163

Public Input No. 157-NFPA 86-2012 [ Section No. 8.8.2.2 ]

8.8.2.2*

Where the capacity of the main or pilot fuel gas burner system oven exceeds 400,000 Btu/hr (117 kW), at least one of thesafety shutoff valves between each burner system and the fuel supply shall be proved closed and interlocked with the pre-ignition purge interval. A safety shutoff valve with poc on the main header shall be permitted to be considered the poc valve to allburners to the oven for the puree interlock.

(A)

A proved closed condition shall be accomplished by either of the following means:

(1) A proof-of-closure switch incorporated in a listed safety shutoff value assembly in accordance with the terms of the listing

(2) A valve proving system

(B)

Auxiliary and closed position indicator switches shall not satisfy the proved closed requirement of 8.8.2.2(A).

Statement of Problem and Substantiation for Public Input

The intent of the proved closed interlock in 8.8.2.2 is to verify that during the pre-purge interval at least one valve between the fuel supply and the chamber to be purged is proven in the closed position before the pre-purge starts, so as to minimize the risk of gas flowing into the chamber(s) while purge is taking place. The current language has two ambiguities. 1) It falls short of the level of safety needed for large ovens in cases when the oven would have a total capacity of 10,000,000 btu/hr, but each individual burner system flows less than 400,000 btu/hr. There would be safety valve arrangements when 8.8.2.2 would not require that any safety valve to be proven closed before the pre-purge. 2) It does not permit having one safety valve proven closed at the header and then two safety valves at each burner system having a capacity greater than 400,000 btu/hr, which should be a permitted valve arrangement that complies with the intent of 8.8.2. 2 for the pre-purge. The proposed language, including "system" after burner, clarifies these ambiguities and addresses the intent of proved closed for pre-purge.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-SAFETY Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:21:08 EDT 2012

Committee Statement

Resolution: FR-34-NFPA 86-2012

Statement: The Committee wanted this section to explain how proving closing valves is to be accomplished. Other sections explain whenproving closed is required.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 100-NFPA 86-2012 [ Section No. 8.10.1 ]

Page 69: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 69/163

8.10.1*

Each burner flame shall have a combustion safeguard that has a maximum flame failure response time of 4 seconds orless less than 3.9 seconds , that performs a safe-start check, and that is interlocked into the combustion safety circuitry inaccordance with the following:

(1) The flame supervision shall not be required in the combustion safety circuitry of a furnace zone where that zonetemperature is greater than 1400°F (760°C) and the following criteria are met:

(a) When the zone temperature drops to less than 1400°F (760°C), the burner is interlocked to allow its operation only ifflame supervision has been re-established.

(b) A 1400°F (760°C) bypass interlock is used to meet the requirement of 8.10.1(1)(a).

(2) The flame response time shall not exceed 4 seconds.

(3) Combustion safeguards on radiant tube–type heating systems are not required where a means of ignition is provided andthe systems are arranged and designed such that either of the following conditions is satisfied:

(a) The tubes are of metal construction and open at one or both ends. If heat recovery systems are used, they shall beof explosion-resistant construction.

(b) The entire radiant tube heating system, including any associated heat recovery system, is of explosion-resistantconstruction.

(4) Burners without flame supervision are interlocked to prevent their operation when the zone temperature is less than 1400°F(760°C) by use of a 1400°F (760°C) bypass interlock.

Statement of Problem and Substantiation for Public Input

See Public Input #99 at Section 8.5.2.1

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 99-NFPA 86-2012 [New Section after 8.5.2.1] Required text to accompany new definition of combustion safeguard

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:05:06 EDT 2012

Committee Statement

Resolution: FR-125-NFPA 86-2012

Statement: The Committee clarified when combustion safeguards are required and not required. Additionally, the Committee clarified the flameresponse time requirement, safe-start check requirement, and allowable arrangements of combustion safeguards. The Committeereplaced the term "combustion safety circuitry" with "burner management system" per the removal of combustion safety circuitryfrom FR-85-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 145-NFPA 86-2012 [ Section No. 8.10.1 ]

Page 70: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 70/163

8.10.1*

Each burner flame shall have a combustion safeguard that has a maximum flame failure response time of 4 seconds or less,that performs a safe-start check, and that is interlocked into the combustion safety circuitry in accordance with the following:

(1) The flame supervision shall not be required in the combustion safety circuitry of a furnace zone where that zonetemperature is greater than 1400°F (760°C) and the following criteria are met:

(2) When the zone temperature drops to less than 1400°F (760°C), the burner is interlocked to allow its operation onlyif flame supervision has been re-established.

(3) A 1400°F (760°C) bypass interlock is used to meet the requirement of 8.10.1 (1)(a).

(4) Combustion safeguards on radiant tube–type heating systems are not required where a means of ignition is provided andthe systems are arranged and designed such that either of the following conditions is satisfied:

(5) The tubes are of metal construction and open at one or both ends. If heat recovery systems are used, they shall beof explosion-resistant construction.

(6) The entire radiant tube heating system, including any associated heat recovery system, is of explosion-resistantconstruction.

(7) Burners without flame supervision are interlocked to prevent their operation when the zone temperature is less than1400°F (760°C) by use of a 1400°F (760°C) bypass interlock.

< see attached revised text >

Additional Proposed Changes

File Name Description Approved

Clean Competing Draft Proposal Section 8-10.1.pdf

Clean proposal for new 8.10.1

Statement of Problem and Substantiation for Public Input

Major revision to combustion safeguards. Competes with Public Input #100, which contains additional substantiation.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 100-NFPA 86-2012 [Section No. 8.10.1] Competing text for linked item

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 15:49:16 EDT 2012

Committee Statement

Resolution: FR-125-NFPA 86-2012

Statement: The Committee clarified when combustion safeguards are required and not required. Additionally, the Committee clarified the flameresponse time requirement, safe-start check requirement, and allowable arrangements of combustion safeguards. The Committeereplaced the term "combustion safety circuitry" with "burner management system" per the removal of combustion safety circuitryfrom FR-85-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 71: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 71/163

Public Input No. 49-NFPA 86-2012 [ New Section after 8.11.2 ]

8.11.2.1

The low pressure switch used to supervise the atomizing medium shall be permitted to be located upstream of atomizing mediabalancing orifices and balancing valves provided the balancing devices are equipped with a locking device to prevent an unintentionalchange in the setting.

Statement of Problem and Substantiation for Public Input

Previously, A.8.11.2 included a requirement which should have been in the mandatory text. This proposal moves the prior Annex text here and augments it.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 09:49:28 EDT 2012

Committee Statement

Resolution: FR-7-NFPA 86-2012

Statement: Previously, A.8.11.2 included a requirement which should have been in the mandatory text. This proposal moves the prior Annextext here and augments it. See FR-6-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 72: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 72/163

Public Input No. 146-NFPA 86-2012 [ Section No. 8.16.10 ]

8.16.10

The Except as allowed in 8.4, the operating temperature controller and its temperature-sensing element shall not be used asthe excess temperature limit interlock.

Statement of Problem and Substantiation for Public Input

Resolves potential conflict with 8.4

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 119-NFPA 86-2012 [Section No. 8.4.2] Interrelated sections?

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 15:53:41 EDT 2012

Committee Statement

Resolution: The Submitter's intent is addressed by the PLC first revision (FR-DEREK TO GET REFERENCE)

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 73: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 73/163

Public Input No. 165-NFPA 86-2012 [ New Section after 9.1.2 ]

Add a new section to read as follows: 9.1.3* Written procedures shall be established or interlocks provided for each action to be taken in response to a fire in an oven.

Statement of Problem and Substantiation for Public Input

Existing requirements in Chapter 11 do not address what action should be taken in the event of a fire in an oven or furnace. While such actions are not "one-size-fits-all", where fire protection is needed it is important it be a coordinated system and, where manual actions are required, written procedures exist and operator training (addressed in Section 7.2) is done.

Submitter Information Verification

Submitter Full Name:Michael Polagye

Organization: FM Global

Submittal Date: Mon Jul 02 12:43:21 EDT 2012

Committee Statement

Resolution: FR-109-NFPA 86-2012

Statement: Existing requirements in Chapter 9 do not address what action should be taken in the event of a fire in an oven or furnace. Whilesuch actions are not "one-size-fits-all", where fire protection is needed it is important it be a coordinated system and, wheremanual actions are required, written procedures exist and operator training (addressed in Section 7.2) is done. The Committeechanged text from "each action" to "actions" and removed interlocks. It is virtually impossible to define precise actions to be takenwhile fighting a fire. Personnel trained to fight fires need the latitude to adjust their actions to a particular event.

Copyright Assignment

I, Michael Polagye, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Michael Polagye, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 74: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 74/163

Public Input No. 124-NFPA 86-2012 [ Section No. 10.6.3.3 ]

10.6.3.3 3*

Where direct heat recovery systems are employed and portions of the incinerator exhaust gases are utilized as the heat sourcefor one or more of the zones of the fume-generating oven, special one of the following precautions shall be taken to preventrecycling unburned solvent vapors:

(1) Mechanical means such as fixed dampers shall be used to ensure that the ratio of fresh air to recycled exhaust cannotreduce the efficiency of the incinerator below specification or 90%, whichever is higher .

(2) Oxygen sensors in the air stream to the incinerator are interlocked to divert recyled exhaust gases to atmosphere if levelsdrop below specifications for the incinerator.

(3) A continuous vapor concentration high limit controller is provided in accordance with 11.6.10

Statement of Problem and Substantiation for Public Input

The term "special precautions" is imprecise and unenforceable language. The goal of this paragraph is to prevent the exhaust from the incinerator increasing the concentration of flammable vapors within the heated ovens to above 25% LFL (or 50% if a continuous vapor concentration controller is used).

When exhaust is recycled, it can reduce the oxygen content supplied to the incinerator (reducing efficiency) and allow concentrations of flammable vapors to build over time. System design should have inherent physical characteristics or control and interlocks to prevent this from occuring.

Annex material is proposed separately to provide more guidance to the reader of the standard.

Submitter Information Verification

Submitter Full Name:Thomas George

Organization: Tokio Marine Management, Inc.

Submittal Date: Fri Jun 22 08:51:10 EDT 2012

Committee Statement

Resolution: FR-87-NFPA 86-2012

Statement: The term "special precautions" is imprecise and unenforceable language. The goal of this paragraph is to prevent the exhaust fromthe incinerator increasing the concentration of flammable vapors within the heated ovens to above 25% LFL (or 50% if a continuousvapor concentration controller is used). When exhaust is recycled, it can reduce the oxygen content supplied to the incinerator(reducing efficiency) and allow concentrations of flammable vapors to build over time. System design should have inherent physicalcharacteristics or control and interlocks to prevent this from occuring. Annex material is proposed separately to provide moreguidance to the reader of the standard, see FR-88-NFPA 86-2012.

Copyright Assignment

I, Thomas George, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Thomas George, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 75: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 75/163

Public Input No. 84-NFPA 86-2012 [ Section No. 10.6.3.3 ]

10.6.3.3

Where direct heat recovery systems are employed and portions of the incinerator exhaust gases are utilized as the heat sourcefor one or more of the zones of the fume-generating oven, special precautions shall be taken to prevent recycling unburnedsolvent vapors vapors and unburned primary burner fuel .

Statement of Problem and Substantiation for Public Input

The existing requirements unnecessarily prohibit the recovery of chemical energy available in solvent vapors driven off in a drying oven to be used as a direct source of heat for the oven itself, after those vapors are incinerated in a thermal oxidizer. Oven systems that enhance energy efficiency without posing safety hazards should not be prohibited. - New text at 10.6.3.3 adds "unburned primary fuel" to the set of flammable gases/vapors that should not be recycled to the drying oven. - New text at 11.6.6.3 clarifies that products of combustion are not flammable and should be excluded from the gases that are prohibited from being recycled to the drying oven.If all of the conditions of Chapter 10 Thermal Oxidizer are met then the vast majority of the solvent vapor and primary burner fuel are oxidized to inert compounds which may be used effectively as a source of heat in the drying oven.Annex text and figure also provided to accompany the new requirements. This public input should be evaluated in the context of cross-referenced public input addressing 8.6.1 and 11.6.1.10.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 54-NFPA 86-2012 [Section No. 8.6.1 [Excluding any Sub-Sections]]

Several related public inputs all dealing with safetyventilation.

Public Input No. 82-NFPA 86-2012 [New Section after 11.6.1.10]Several related public inputs all dealing with safetyventilation.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 16:28:41 EDT 2012

Committee Statement

Resolution: FR-87-NFPA 86-2012

Statement: The term "special precautions" is imprecise and unenforceable language. The goal of this paragraph is to prevent the exhaust fromthe incinerator increasing the concentration of flammable vapors within the heated ovens to above 25% LFL (or 50% if a continuousvapor concentration controller is used). When exhaust is recycled, it can reduce the oxygen content supplied to the incinerator(reducing efficiency) and allow concentrations of flammable vapors to build over time. System design should have inherent physicalcharacteristics or control and interlocks to prevent this from occuring. Annex material is proposed separately to provide moreguidance to the reader of the standard, see FR-88-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 76: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 76/163

Public Input No. 75-NFPA 86-2012 [ Section No. 11.5 ]

11.5 Fire Protection. (Reserved)

11.5.1 Upon detection of a fire by an automated fire detection or suppression system, the system design shall incorporate thefollowing automated interlocks:

(1) A safety shutdown of the oven shall be initiated.

(2) Conveyors or sources of flammable or combustible material shall shut down.

(3) Fans shall remain in operation to maintain the required safety ventilation or it shall be demonstrated by calculationthat the combustible concentration in the work chamber cannot exceed 25 percent of the lower flammable limit (LFL)under any conditions.

(4) Dampers positions shall maintain the minimum airflow through all oven passages to provide the required safetyventilation or it shall be demonstrated by calculation that the combustible concentration in the work chamber cannotexceed 25 percent of the lower flammable limit (LFL) under any conditions.

Statement of Problem and Substantiation for Public Input

Two different types of hazards may develop when an emergency shutdown of the oven is required. (1) In cases where a fire involving combustible solids or liquids in the oven has been initiated, but hasn't grown very large, allowing more air into the oven will “fan the flames”.(2) In cases where excess temperature might cause the buildup of flammable gases and an approach to LFL, shutting off the source of air to the oven could create an explosive atmosphere.The goal of the shutdown logic should be:- Distinguish between overtemperature situation and internal fire.- Initiate action that is consistent with the type of problem discerned and the nature of fire detection and suppression systems present in the oven.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 15:35:13 EDT 2012

Committee Statement

Resolution: FR-90-NFPA 86-2012

Statement: Two different types of hazards may develop when an emergency shutdown of the oven is required. (1) In cases where a fireinvolving combustible solids or liquids in the oven has been initiated, but hasn't grown very large, allowing more air into the ovenwill “fan the flames”. (2) In cases where excess temperature might cause the buildup of flammable gases and an approach to LFL,shutting off the source of air to the oven could create an explosive atmosphere. The goal of the shutdown logic should be: -Distinguish between over temperature situation and internal fire. - Initiate action that is consistent with the type of problemdiscerned and the nature of fire detection and suppression systems present in the oven.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 77: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 77/163

Public Input No. 69-NFPA 86-2012 [ Section No. 11.6.1.1 ]

11.6.1.1

Air circulation shall be used to minimize the to achieve the following:

(1) Minimize the volume of flammable concentration regions that are present at the

point

points of evaporation within the oven.

(2) Maintain flammable vapor concentrations in all other regions of the furnace or furnace enclosure below the applicable safetylimits with respect to percent of LFL.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #24 (Section 3.3.53). The new text clarifies that there are two types of regions in many Class A ovens - (1) near surfaces where flammable liquids are being evaporated and it is impossible to dilute the concentration below 25% of the LFL and (2) all other regions where concentrations should be kept below 25% of LFL.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 24-NFPA 86-2012 [Section No. 3.3.53] Enforceable language moved from definition to a new requirement in 11.6.1.1

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 15:11:56 EDT 2012

Committee Statement

Resolution: The modified text does not add any additional guidance that is not already captured in the standard.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 78: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 78/163

Public Input No. 82-NFPA 86-2012 [ New Section after 11.6.1.10 ]

11.6.1.11*

Safety ventilation shall be arranged to meet the following design characteristics:

(a) Reduction of air flow below the minimum required by 11.6.1 shall activate the ventilation safety devices provided in accordancewith section 8.6.

(b) The physical arrangement of dampers, fans, ducts, chambers, and passages shall ensure that a short-circuited airflow cannotoccur without activating the ventilation safety devices provided in accordance with section 8.6.

Statement of Problem and Substantiation for Public Input

New requirements are added to clarify the functionality of ventilation safety devices and the dual objectives of (1) monitoring for insufficient ventilation air flow and (2) ensuring that short-circuiting around necessary ventilation flow pathways does not occur.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 78-NFPA 86-2012 [Section No.11.6.1.10]

New requirements added in proposed revision to 11.6.1.10

Public Input No. 54-NFPA 86-2012 [Section No. 8.6.1[Excluding any Sub-Sections]]

New safety ventilation requirements in Chapter 11 should be reviewed incontext of interlocks required in 8.6.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 16:01:34 EDT 2012

Committee Statement

Resolution: FR-25-NFPA 86-2012

Statement: New requirements are added to clarify the functionality of ventilation safety devices and the dual objectives of (1) monitoring forinsufficient ventilation air flow and (2) ensuring that short-circuiting around necessary ventilation flow pathways does not occur.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 79: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 79/163

Public Input No. 78-NFPA 86-2012 [ Section No. 11.6.1.10 ]

11.6.1.10*

Required safety Safety ventilation shall be proved by one of the following:

(1) A dedicated exhaust fan proved in accordance with Section 8.6

(2) The presence of at least the required fresh air flow into the system proven in accordance with Section 8 11 .6 .1.11

(3) The presence of at least the required exhaust flow out of the system proven in accordance with Section 8 11 .6 .1.11

(4) A continuous vapor concentration high limit controller in accordance with 11.6.10

Statement of Problem and Substantiation for Public Input

Complex systems with multiple airflow paths, multiple heating zones, and other variations are not adequately encompassed by the current 11.6.1.10, which simply provides a generic reference to requirements in Section 8.6. The new 11.6.1.11 language is necessary to ensure that the designer, AHJ, and end user are able to apply the requirements for safety ventilation to these complex systems.The solution presented in this Public Input is an alternative to the solution presented in a cross-referenced Public Input that alters requirements in 11.6.6.3 and 10.6.3.3.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 15:50:40 EDT 2012

Committee Statement

Resolution: FR-26-NFPA 86-2012

Statement: Complex systems with multiple airflow paths, multiple heating zones, and other variations are not adequately encompassed by thecurrent 11.6.1.10, which simply provides a generic reference to requirements in Section 8.6. The new 11.6.1.11, see FR-25-NFPA86-2012, language is necessary to ensure that the designer, AHJ, and end user are able to apply the requirements for safetyventilation to these complex systems.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 80: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 80/163

Public Input No. 57-NFPA 86-2012 [ Section No. 11.6.2.1 ]

11.6.2.1 1*

Interlocks for exhaust and recirculation fans shall be installed in accordance with Sections 8.6 and 8.7.

Statement of Problem and Substantiation for Public Input

Adds reference to Annex A.8.6.1 where new content was added to clarify the need for interlocking the operation of non-ducted fans into the safety circuitry.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 56-NFPA 86-2012 [New Section after A.8.5.2] Asterisk added to indicated presence of new Annex content.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:14:01 EDT 2012

Committee Statement

Resolution: FR-52-NFPA 86-2012

Statement: Adds reference to Annex A.8.6.1 where new content was added to clarify the need for interlocking the operation of non-ducted fansinto the safety circuitry, see FR-53-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 81: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 81/163

Public Input No. 85-NFPA 86-2012 [ New Section after 11.6.6.2 ]

11.6.6.3

When the conditions of 10.6.3.3 have been met, the products of combustion exiting the thermal oxidizer shall be permitted to beexcluded from the requirements for safety ventilation in 11.6.6.

Additional Proposed Changes

File Name Description Approved

Example 8 - new figurefor 11.6.6.3.png

One of several examples considered by Class A Task Group where combustion products from a thermal oxidizer may be safely recycled to a drying oven.

Statement of Problem and Substantiation for Public Input

See substantiation provided with new public input at 10.6.3.3.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 84-NFPA 86-2012 [Section No.10.6.3.3]

Several related public inputs addressing safety ventilation and energyefficiency

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 16:45:45 EDT 2012

Committee Statement

Resolution: The Committee was concerned that there are insufficient requirement to avoid the carryover of flammable components from thethermal oxidizer back into the oven.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 82: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 82/163

Public Input No. 163-NFPA 86-2012 [ Section No. 11.6.8.3 ]

11.6.8.3* LFL Correction Factor.

(A)

The LFL value for continuous process ovens shall be corrected for the oven operating temperature in accordance with one of thefollowing formulas or by using Table 11.6.8.3(A) :

In the equation below delete 436 and replace with 401. Also delete 784 and replace with 721.

where:

t = oven temperature

Table 11.6.8.3(A) Oven Temperature Correction Factors

Oven Temperature LFL Correction

Factor°F °C

77 25 1.00

212 100 0.94 95

300 149 0.90 91

400 204 0.86 87

500 260 0.81 83

(B)

For batch process ovens, the temperature multiplier specified in 11.6.9.2 shall be used.

Statement of Problem and Substantiation for Public Input

The formulas come from the Bureau of Mines 627 [see A.11.6.8.3 and A.6.5.2(2)] but the cited reference formula uses 0.000721 instead of 0.000784. The Fahrenheit formula is corrected by multiplying 0.000721 by 5 and dividing by 9. The table correction factors must be adjusted to agree with the corrected formulas.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:29:04 EDT 2012

Committee Statement

Resolution: The Committee wants to keep the more conservative coefficient.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 83: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 83/163

Public Input No. 126-NFPA 86-2012 [ Section No. 11.6.8.7 ]

11.6.8.7

The products of combustion in direct-fired process ovens shall be accounted for by implementing one of the followingapproaches:

(1) The safety ventilation shall be increased

for direct-fired process ovens

(1) to include the products of combustion ventilation rate determined in 11.6.6 .

(2) A continuous vapor concentration high limit controller has been provided in accordance with 11.6.10

Statement of Problem and Substantiation for Public Input

The text desired could not be created by TerraView:"11.6.8.7 The products of combustion in direct-fired process ovens shall be accounted for by implementing one of the following approaches:(1) The safety ventilation shall be increased to include the products of combustion ventilation rate determined in 11.6.6.(2) A continuous vapor concentration high limit controller has been provided in accordance with 11.6.10"

In cases where a continuous vapor concentration high limit controller has been provided, the products of combustion will be addressed by the system without the need for an additional calculated safety ventilation rate. Moreover, it has been demonstrated that the inert components of the products of combustion are effective in diluting flammable vapors as required by the standard.

Combustible components such as CO and those resulting from incomplete combustion will be monitored by the continuous vapor concentration high limit controller.

Submitter Information Verification

Submitter Full Name:Thomas George

Organization: Tokio Marine Management, Inc.

Affilliation: Developed as a result of work with the NFPA 86 Class A Oven Task Force

Submittal Date: Fri Jun 22 09:28:27 EDT 2012

Committee Statement

Resolution: FR-89-NFPA 86-2012

Statement: In cases where a continuous vapor concentration high limit controller has been provided, the products of combustion will beaddressed by the system without the need for an additional calculated safety ventilation rate. Moreover, it has been demonstratedthat the inert components of the products of combustion are effective in diluting flammable vapors as required by the standard.Combustible components such as CO and those resulting from incomplete combustion will be monitored by the continuous vaporconcentration high limit controller.

Copyright Assignment

I, Thomas George, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Thomas George, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 84: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 84/163

Public Input No. 136-NFPA 86-2012 [ New Section after 12.5.1 ]

Pre-ignition Purge

Failure to maintain the minimum required pre-ignition purge airflow shall permit stopping and holding the pre-ignition purge timer withoutreset and resuming the remaining purge time when the minimum purge airflow is re-established. The timer shall be reset when thehold time exceeds 15 minutes.

Statement of Problem and Substantiation for Public Input

This proposal allows systems with long purge times to perform additional functions during the pre-ignition purge that may momentarily affect the air flow. It also reduces the temptation to defeat the purge timer. When the minimum air flow drops below the monitoring switch, the concentration of combustibles in the heating chambers will not increase. The safety shut off valves have been proven closed and there is no other source that would increase flammable vapors and gases in Class B systems. There is no risk in holding the purge timer within the limitation of 15 minutes.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Fri Jun 22 12:48:41 EDT 2012

Committee Statement

Resolution: Insufficient guidance has been provided to interrupt purge time.

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 85: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 85/163

Public Input No. 106-NFPA 86-2012 [ Section No. 12.5.2.5(A) ]

(A)

The main furnace structure tilt system shall be interlocked where the arc furnace operation includes tilting of with the mainpower to prevent tilting the furnace to remove molten metal at the end of the furnace heat, and the following criteria also shall bemet:

The furnace shall not be tilted during the melt operation, and interlocks shall be provided to prevent furnace tilting untilfurnace controls have been proved in the correct position.

Interlocks shall be fitted to prevent tilting of the furnace unless both of the following conditions are satisfied:

The roof is down.

The limit switches are at forward and backward limits of travel heat if there is power at the electrode(s) .

Statement of Problem and Substantiation for Public Input

• Electric Arc furnace operation does require tilting the furnace during the normal operation of the furnace. One of reasons an electric arc furnace is tilted is to facilitate slag removal from the furnace during the refining process. Therefore, the old (A)(1) is not correct and should be deleted. • Power to the electrodes should not be present when the furnace is tilted into the pouring (tapping) position• The old (A)(2) now becomes the new (B)• The old (B) becomes the new (C)

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Class B Furnaces

Submittal Date: Fri Jun 22 01:19:11 EDT 2012

Committee Statement

Resolution: FR-38-NFPA 86-2012

Statement: The information on arc melt furnaces in NFPA 86 has not been updated since when it was originally entered into the standard in1973. There has and currently is no expertise within the committee to address this type of equipment. Currently, most of theindustry does not use this standard because of the degree of specialized design and engineering for each unique arc furnace, thisstandard does not have the capability to cover such a design.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 86: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 86/163

Public Input No. 108-NFPA 86-2012 [ New Section after 12.5.2.5(B) ]

(C)

Interlocks shall be fitted to prevent swinging of the roof and electrodes unless the following three conditions are satisfied:

(a) The electrode arms are up and clear of shell.

(b) The furnace tilt platform is normal and locked (if fitted).

(c) The roof is raised.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #108 at Section 12.5.2.5.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 107-NFPA 86-2012 [Section No. 12.5.2.5(B)] Revisions to several sections of 12.5.2.5 are all interconnected

Public Input No. 106-NFPA 86-2012 [Section No. 12.5.2.5(A)] Revisions to several sections of 12.5.2.5 are all interconnected

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Class B Furnaces

Submittal Date: Fri Jun 22 01:35:57 EDT 2012

Committee Statement

Resolution: FR-38-NFPA 86-2012

Statement: The information on arc melt furnaces in NFPA 86 has not been updated since when it was originally entered into the standard in1973. There has and currently is no expertise within the committee to address this type of equipment. Currently, most of theindustry does not use this standard because of the degree of specialized design and engineering for each unique arc furnace, thisstandard does not have the capability to cover such a design.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 87: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 87/163

Public Input No. 107-NFPA 86-2012 [ Section No. 12.5.2.5(B) ]

(B)

Interlocks shall be fitted to prevent

swingingtilting of the

roof and electrodes unlessfurnace for normal furnace operation unless both of the following

threeconditions are satisfied:

The electrode arms are up and clear of shell.

The furnace tilt platform is normal and locked (if fitted).

The roof is raised.

(A) The roof is down.

(B) the furnace is within the forward and backward limits of tilt.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #106 at Section 12.5.2.5

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 106-NFPA 86-2012 [Section No. 12.5.2.5(A)] Several revisions to 12.5.2.5 are all interconnected

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Class B Furnaces

Submittal Date: Fri Jun 22 01:33:52 EDT 2012

Committee Statement

Resolution: FR-38-NFPA 86-2012

Statement: The information on arc melt furnaces in NFPA 86 has not been updated since when it was originally entered into the standard in1973. There has and currently is no expertise within the committee to address this type of equipment. Currently, most of theindustry does not use this standard because of the degree of specialized design and engineering for each unique arc furnace, thisstandard does not have the capability to cover such a design.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 88: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 88/163

Public Input No. 26-NFPA 86-2012 [ Section No. 13.5.1.5 ]

13.5.1.5

Nonflammable and nontoxic fluids nontoxic gases shall be vented to an approved location outside the building at a rate thatdoes not pose a hazard of asphyxiation.

Statement of Problem and Substantiation for Public Input

We believe that at this point we are specifically addressing gases. "Fluids" applies to both liquids and gases (liquids can not be "vented")

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Thu Apr 26 16:11:35 EDT 2012

Committee Statement

Resolution: FR-54-NFPA 86-2012

Statement: The Committee believes that at this point we are specifically addressing gases. "Fluids" applies to both liquids and gases (liquidscan not be "vented")

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

This information w as provided by Mark Stender (Surface Combustion) as part of the Class C Task Group.

Page 89: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 89/163

Public Input No. 41-NFPA 86-2012 [ Section No. 13.5.2.1(B) ]

(B)

Copper and copper alloy components or materials shall not be used in exothermic atmosphere gas generators, coolingsystems, heat exchangers, and distribution systems where they will be exposed to makeup, reacting, or final productexothermic atmosphere gas.

Statement of Problem and Substantiation for Public Input

Duplicate statement from 13.5.2.1 (A)

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Task Group Class C

Submittal Date: Thu May 10 13:38:52 EDT 2012

Committee Statement

Resolution: FR-55-NFPA 86-2012

Statement: Removed because it is a duplicate statement from 13.5.2.1 (A).

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Jak Kozma (Holcroft) in NFPA 86 Class C Task Group.

Public Input No. 27-NFPA 86-2012 [ Section No. 13.5.3.5 ]

Page 90: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 90/163

13.5.3.5*

Protective equipment for the reaction section of endothermic generators shall include the following:

(1) Safety shutoff valve(s) in the reaction gas supply piping requiring manual operation for opening shall close under any ofthe following conditions:

(a) Low reaction gas pressure

(b) High reaction gas pressure

(c) Loss of reaction air supply

(d) Low generator temperature

(e) Power failure

(2) A low pressure switch in the reaction gas supply piping shall close the safety shutoff valve and shut off the reaction airsupply in case of abnormally low reaction gas pressure at the mixer.

(3) Where the system is subject to abnormally high reaction gas pressure, a high pressure switch shall be installed in thereaction gas supply piping that operates as follows when the gas reaction pressure exceeds a predetermined upper value:

(a) The device closes the safety shutoff valve.

(b) The device shuts off the reaction air supply.

(4) A When an air blower or compressed air line is used to supply the reaction air a low pressure switch in the reaction airsupply piping connected to an air blower or compressed air line shall piping shall close the safety shutoff valve and shutoff the reaction air supply in case of abnormally low reaction air pressure.

(5) A device that shuts off reaction air in case of power failure or abnormally low or abnormally high reaction gas pressure atthe mixer shall be included.

(6) A means for making tightness checks of all reaction gas safety shutoff valves shall be included.

(7) A valve shall be designated the main shutoff valve and shall be located upstream of the safety shutoff valve and shall beaccessible for normal and emergency shutdown.

(8) A generator temperature control to prevent the flow of reaction air and reaction gas unless the generator is at theminimum generator temperature specified by the generator manufacturer shall be included.

(9) Automatic fire check protection shall be included.

(10) A visual and audible alarm when the reaction gas safety shutoff valve is closed shall be included.

Statement of Problem and Substantiation for Public Input

The way the intro is worded could imply that either an air blower or a compressed air line is required to provide the reaction air. One industry design does not use an air blower or compressed air line for the reaction air.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Thu Apr 26 16:16:31 EDT 2012

Committee Statement

Resolution: FR-56-NFPA 86-2012

Statement: The way the intro is worded could imply that either an air blower or a compressed air line is required to provide the reaction air.The Committee is aware of one industry design that does not use an air blower or compressed air line for the reaction air.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Changes provided by Mark Stender (Surface Combustion) as part of Class C Task Group.

Page 91: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 91/163

Public Input No. 74-NFPA 86-2012 [ New Section after 13.5.7.4(C) ]

13.5.7.5

It shall not be permissible to manifold flammable special atmospheres and process control air or admit both via a common inlet whenflow rates and piping arrangements create a risk of flame strike back and burning within the furnace piping.

Statement of Problem and Substantiation for Public Input

Flammable gas and air admitted to a furnace via a common inlet pipe may create a rick of flame strike back and burning within the furnace piping.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:34:56 EDT 2012

Committee Statement

Resolution: FR-57-NFPA 86-2012

Statement: Flammable gas and air admitted to a furnace via a common inlet pipe may create a rick of flame strike back and burning within thefurnace piping.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 92: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 92/163

Public Input No. 68-NFPA 86-2012 [ Section No. 13.5.8.3 ]

13.5.8.3*

A safety When a flammable liquid is used as a carrier gas and introduced in the liquid state, a second low termperatureinterlock shall be provided to if flow of the liquid is continued at less than 1400F(760C). This second interlock shall interruptthe flow of methanol (methyl alcohol) or other the flammable liquid atmospheres atmosphere into a the furnace when thetemperature inside drops below a minimum dissociation temperature required to maintain a positive furnace pressure furnacetemperature is less than the temperature needed to reliably dissociated the liquid special atmosphere used .

Statement of Problem and Substantiation for Public Input

The modified wording unifies the requirement in a single location.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:11:22 EDT 2012

Committee Statement

Resolution: FR-58-NFPA 86-2012

Statement: The Committee modified the wording to unify the requirement in a single location.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 93: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 93/163

Public Input No. 70-NFPA 86-2012 [ New Section after 13.5.8.11 ]

13.5.8.12

Automatic excess flow shutoff protection shall be provided for each liquid special atmosphere.

(A) The excess flow sensor shall be located immediately downstream of the filter required in 13.5.11.10.5.

(B) Upon detection of liquid special atmosphere excess flow, the liquid special atmosphere safety shutoff valve shall close.

Statement of Problem and Substantiation for Public Input

Relocated from 13.5.11.11.11

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:17:41 EDT 2012

Committee Statement

Resolution: FR-59-NFPA 86-2012

Statement: Relocated from 13.5.11.11.11, see FR-60-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 16-NFPA 86-2012 [ Section No. 13.5.10.3 ]

Page 94: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 94/163

13.5.10.3 Furnace Type (Class C) .

The type of furnace shall be determined in accordance with Table 13.5.10.3.

Table 13.5.10.3 Types of Class C Furnaces

FurnaceType Feature Operating Temperature Example

Type IThe chamber(s) <1400°F areseparated by doors from thoseoperating at > 1400°F

One or more zones always >1400°FPusher tray (cold chambers at eachend, inner and outer doors with andwithout integral quench)

Type IICan be <1400°F after introduction of acold load

Batch integral quench (1 or more coldchambers, integral quench)

Type IIIBoth inlet and outlet ends offurnace are open and no externaldoors or covers

At least one zone >1400°F and have noinner doors separating zones > and<1400°F

Belt (both ends open)

Type IVOnly one end of the furnace isopen and there are no externaldoors or covers

Belt (with integral quench, entry endopen)

Type V Outer doors or covers are provided Box (exterior door)

Type VI >1400°F before introduction and removalof special atmosphere gas

Type VII Never >1400°F

Type VIIIA heating cover furnace with aninner cover A heating cover and inner cover are

separated from a base that supports thework being processed

Bell (with or without retort)

Type IXA heating cover furnace withoutan inner cover or with a nonsealedinner cover

Car tip-up

For SI units, 1400°F =760°C.

Statement of Problem and Substantiation for Public Input

With its current title, users may inadvertently think that Table 13.5.10.3 provides guidance for distinguishing between different classes of furnaces, when in fact the table is only applicable to Class C furnaces.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Submittal Date: Fri Mar 30 23:50:25 EDT 2012

Committee Statement

Resolution: FR-61-NFPA 86-2012

Statement: The Committee clarified that Table 13.5.10.3 is only applicable to Class C furnaces to avoid any confusion or misuse of the table.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 95: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 95/163

Public Input No. 37-NFPA 86-2012 [ New Section No. after 13.5.11.1(E) ]

13.5.11.1 (F)

Process Control Air or Burnout Air shall be supplied from an air blower.

Statement of Problem and Substantiation for Public Input

Often plant airlines can become slugged with water. Regulator failures could result in high-pressure air admission to furnace.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 10:10:53 EDT 2012

Committee Statement

Resolution: FR-62-NFPA 86-2012

Statement: Often plant airlines can become slugged with water. Regulator failures could result in high-pressure air admission to furnace.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) in Class C Task Group.

Page 96: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 96/163

Public Input No. 149-NFPA 86-2012 [ Section No. 13.5.11.2(G) ]

(G)*

Burn-off pilot gas shall not shut off in the event of power failure except for the following case .

(1) Burn-off pilot gas for a Type II batch integral quench furnace vestibule outer door burn-off pilot shall be allowed to be shut-offwhere each of the following conditions is met:

(a) The burn-off pilot is equipped with flame supervision.

(b) The burn-off pilot gas is shut-off by a fuel gas safety shutoff valve.

(c) The burn-off pilot is interlocked to prevent automatic door opening in the event of a flame failure.

(d) The furnace is designed to follow purge-in for the introduction of flammable special atmosphere gas per 13.5.11.6.

(e) The furnace is designed to follow purge-out for the removal of flammable special atmosphere gas per 13.5.11.8.

(f) Written instructions are provided stating that the door shall not be opened by manual means unless the door burn-offpilot is lit or an alternate source of ignition is provided.

Statement of Problem and Substantiation for Public Input

The proposed change would reduce the potential for an explosive gas mixture to develope inside the furnace in the event of a power failure or when the furnace is being shut-down. This condition could develop should the door burn-off pilot be unexpectedly extinguished and the operator fails to close the manual burn-off pilot gas valve.

Vestibules on Type II furnaces have large internal volumes in which a considerable volume of explosive gas mixture could develop should the outer vestibule door remain open when a burn-off pilot is extinguished and the burn-off pilot gas is not manually shut off by the operator. Further, most if not all Type II furnace outer doors open vertically upward such that the required location of the door burn-off pilot is at the bottom of the door opening. Fuel gas is bouyant in air so it will tend to rise and therefore can readily flow into and accumulate in a vestibule whose outer door is open.

A secondary benefit is the reduction of outer door burn-off pilot fuel gas consumption during long furnace cycles.

Submitter Information Verification

Submitter Full Name:Joseph Kozma III

Organization: AFC-Holcroft LLC

Submittal Date: Fri Jun 22 17:27:53 EDT 2012

Committee Statement

Resolution: FR-142-NFPA 86-2012

Statement: The added definition of a flame curtain pilot divorces the flame curtain pilot from the provisions of 13.5.11.2(G) such that flamecurtain pilot gas may be shut-off in the event of flame curtain pilot flame failure. The Committee believes that the submitter's intentis captured. See FR-141-NFPA 86-2012.

Copyright Assignment

I, Joseph Kozma III, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Joseph Kozma III, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 97: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 97/163

Public Input No. 34-NFPA 86-2012 [ New Section after 13.5.11.9.4 ]

13.5.11.9.5

Burnout air shall be admitted by any of the following arrangements:

(A) Through furnace doors.

(B) Through independent piping and furnace gas inlets.

(C) Through sections of piping and furance inlets that are common to both flammable special atmosphere and burnoutair when the systems are designed to prevent the flow of air and flammable special atmosphere at the same time.

Statement of Problem and Substantiation for Public Input

Flammable gas and air admitted to a furnace via a common inlet pipe creates a risk of flame strike back and burning within the furnace piping.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA Class C Task Group

Submittal Date: Fri Apr 27 09:44:01 EDT 2012

Committee Statement

Resolution: FR-63-NFPA 86-2012

Statement: Flammable gas and air admitted to a furnace via a common inlet pipe creates a risk of flame strike back and burning within thefurnace piping.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) as part of Class C Task Group.

Page 98: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 98/163

Public Input No. 77-NFPA 86-2012 [ Section No. 13.5.11.10.2.3 ]

13.5.11.10.2.3

A bypass manual shutoff valve shall be provided to bypass each normally open emergency inert gas purge valve. The bypassmanual shutoff valve shall be arranged as follows:

Statement of Problem and Substantiation for Public Input

This unifies the requirement into a single item.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:50:39 EDT 2012

Committee Statement

Resolution: FR-110-NFPA 86-2012

Statement: This unifies the requirement into a single item.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 99: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 99/163

Public Input No. 79-NFPA 86-2012 [ Section No. 13.5.11.10.2.4 ]

13.5.11.10.2.4

The bypass manual shutoff valve shall be arranged as follows:

(1) Be accessible to the operator for use in accordance with written operating instructions

(2) Have a port area equal to or larger than the bypassed normally open emergency inert gas purge valve

Statement of Problem and Substantiation for Public Input

This unifies the requirement into a single item.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:52:43 EDT 2012

Committee Statement

Resolution: FR-110-NFPA 86-2012

Statement: This unifies the requirement into a single item.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 100: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 100/163

Public Input No. 80-NFPA 86-2012 [ Section No. 13.5.11.10.2.6 ]

Found 2 configuration elements matching the xpath: /systemconfig/systemhomeroot in file C:\TerraXML\terra_view_config.xml

Statement of Problem and Substantiation for Public Input

Corrects the references.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:54:40 EDT 2012

Committee Statement

Resolution: FR-65-NFPA 86-2012

Statement: Corrects the references due to First Revisions. This change is taking into account the removal of the current 13.5.11.10.2.4 (FR-110-NFPA 86-2012), and anticipating the section renumbering. It is intended to reference the current 13.5.11.10.2.5 which will be13.5.11.10.2.4 through FR-110-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 101: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 101/163

Public Input No. 81-NFPA 86-2012 [ Section No. 13.5.11.10.2.8 ]

13.5.11.10.2.8

Manual valves that are not used for shutoff shall not be required to comply with 13.5.11.10.2 other than 13.5.11.10.2.5 4 .

Statement of Problem and Substantiation for Public Input

Corrects the references.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:55:46 EDT 2012

Committee Statement

Resolution: FR-64-NFPA 86-2012

Statement: Corrects the references. This change is taking into account the removal of the current 13.5.11.10.2.4 (FR-110-NFPA 86-2012), andanticipating the section renumbering. It is intended to reference the current 13.5.11.10.2.5 which will be 13.5.11.10.2.4 throughFR-110-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 102: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 102/163

Public Input No. 30-NFPA 86-2012 [ New Section after 13.5.11.10.7 ]

13.5.11.10.8 Atmosphere Inlets

Atmosphere inlets shall not be located in such a way that atmosphere flow will directly impinge on temperature controlor over temperature control thermocouples.

Statement of Problem and Substantiation for Public Input

Atmosphere impingement on the temperature control thermocouple can result in overheating of the furance: impingement on the over temperature thermocouple can cause erroneous control readings.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Thu Apr 26 16:29:00 EDT 2012

Committee Statement

Resolution: FR-66-NFPA 86-2012

Statement: Atmosphere impingement on the temperature control thermocouple can result in overheating of the furance: impingement on theover temperature thermocouple can cause erroneous control readings.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) as part of Class C Task Group.

Page 103: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 103/163

Public Input No. 71-NFPA 86-2012 [ Section No. 13.5.11.11.11 ]

13.5.11.11.11 Liquid Excess Flow Control.

(A) *

Automatic, excess flow, and shutoff protection shall be provided for each liquid special atmosphere.

(B)

The excess flow sensor shall be located immediately downstream of the filter required in 13.5.11.10.5 .

(C)

Upon detection of liquid special atmosphere excess flow, the liquid special atmosphere safety shutoff valve shall close.

Statement of Problem and Substantiation for Public Input

Relocated to section 13.5.8.12

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:24:34 EDT 2012

Committee Statement

Resolution: FR-60-NFPA 86-2012

Statement: Relocated to section 13.5.8.12, see FR-59-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 104: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 104/163

Public Input No. 59-NFPA 86-2012 [ Section No. 13.5.11.11.13(A) ]

(A)

For furnaces using burn-in procedures for introducing flammable special atmosphere carrier gases, the flammable it shall bepermissible to admit flammable special atmosphere carrier gas safety shutoff valves shall open only when one of gas when thefollowing conditions exists exist :

(1) The furnace temperature exceeds 1400°F (760°C) at the point where the flammable special atmosphere carrier gas isintroduced.

(2) If the furnace is designed to operate with an automatic inert gas purge, the presence of the required inert gas pressureshall be verified manually or automatically.

(3) Operator action opens the valve.

Statement of Problem and Substantiation for Public Input

During the last cycle when reorganizing the document the intent of the language was inadvertently changed. The language has been changed to establish the original intent.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 14:24:20 EDT 2012

Committee Statement

Resolution: FR-67-NFPA 86-2012

Statement: During the last cycle when reorganizing the document the intent of the language was inadvertently changed. The language hasbeen changed to establish the original intent.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 105: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 105/163

Public Input No. 60-NFPA 86-2012 [ Section No. 13.5.11.11.13(B) ]

(B)

For furnaces using purge-in procedures for introducing flammable special atmospheres carrier gases, the flammable it shall bepermissible to admit flammable special atmosphere carrier gas safety shutoff valves shall open only when one of the followingexists conditions exist :

(1) The inert gas purge is complete.

(2) If the furnace is designed to operate with an automatic inert gas purge, the presence of the required inert gas pressureshall be verified manually or automatically.

(3) Operator action opens the valve.

Statement of Problem and Substantiation for Public Input

During the last cycle when reorganizing the document the intent of the language was inadvertently changed. The language has been changed to establish the original intent.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 14:31:58 EDT 2012

Committee Statement

Resolution: FR-68-NFPA 86-2012

Statement: During the last cycle when reorganizing the document the intent of the language was inadvertently changed. The language hasbeen changed to establish the original intent.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 106: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 106/163

Public Input No. 61-NFPA 86-2012 [ Section No. 13.5.11.11.13(C) ]

(C)

For furnaces using burn-in or purge-in procedures for introducing flammable special atmosphere gases that are not carrier gases, thesafety shutoff valves for the noncarrier gases shall open only when the carrier gas flow has been established.

Statement of Problem and Substantiation for Public Input

During the last cycle when reorganizing the document the intent of the language was inadvertently changed. The language has been changed to establish the original intent.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 14:36:14 EDT 2012

Committee Statement

Resolution: There was no recommended text, therefor the Committee could not consider the submitter's recommendations.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 107: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 107/163

Public Input No. 28-NFPA 86-2012 [ Section No. 13.5.11.11.13(D) ]

(D)*

Safety shutoff valves shall be de-energized automatically close upon occurrence of the following conditions:

(1) Normal furnace atmosphere burn-out initiated

(2) Normal furnace atmosphere purge-out initiated

(3) Low flow of carrier gas(es) that will not maintain a positive pressure in chambers below 1400°F (760°C) and positivepressure not restored by the automatic transfer to another source of gas

(4) A furnace temperature below which any liquid carrier gas used will not reliably dissociate

(5) Automatic emergency inert gas purge initiated

(6) Manual operator emergency inert gas purge initiated

(7) Power failure

(8) Liquid carrier gas excess flow

Statement of Problem and Substantiation for Public Input

Ultimately it is the closure of the safety shutoff valve what we desire, so lets just say it. Adding item 8 completes the list of conditions that require closing of the safety shutoff valve.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Thu Apr 26 16:21:28 EDT 2012

Committee Statement

Resolution: FR-69-NFPA 86-2012

Statement: Ultimately it is the closure of the safety shutoff valve what we desire, so lets just say it. Adding item 8 completes the list ofconditions that require closing of the safety shutoff valve.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Information provided by Mark Stender (Surface Combustion) as part of the Class C Task Group.

Page 108: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 108/163

Public Input No. 63-NFPA 86-2012 [ Sections 13.5.11.11.15(A), 13.5.11.11.15(B), 13.5.11.11.15(... ]

Sections 13.5.11.11.15(A), 13.5.11.11.15(B), 13.5.11.11.15(C), 13.5.11.11.15(D)

(A)

A flow interlock shall be provided on the equipment piping Minimum carrier gas flow(s) required by standard shall be proved byeither:

(1) A flow switch for each special atmosphere that is considered a carrier gas

.

( 2) Furnace Pressure switch(s)

(D

( B)

Carrier gas flow shall be interlocked to initiate the actions If minimum carrier gas flow is not proven:

(1) Actions listed in 13.5.11.11.10(

B) if the total carrier gas flow from gas or liquid sources falls below the minimum required to keep a furnace chamber underpositive pressure.

(C)

Furnace pressure interlock(s) shall be permitted as an alternative to the flow interlock(s) in 13.5.11.11.15(A) .

b) shall be initiated.

(2) Visual and audible alarms shall alert the operator of loss of minimum carrier gas flow.

(C )

Inert purge gas equipment piping shall be equipped with :

(1) A pressure switch that will audibly and visually alert the operator of a low

gas pressure switch interlocked to initiate audible and visual alarms to

purge pressure condition.

(2) A flow switch that will audibly and visually alert the operator of

the

a low

pressure

purge flow condition.

Statement of Problem and Substantiation for Public Input

This defines the actions of the carrier gas flow interlocks. The inert purge flow switch requirement was required in previous sections but was inadvertently omitted from the 2011 edition.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 14:43:19 EDT 2012

Committee Statement

Resolution: FR-70-NFPA 86-2012

Statement: This defines the actions of the carrier gas flow interlocks. The inert purge flow switch requirement was required in previoussections but was inadvertently omitted from the 2011 edition.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 109: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 109/163

Public Input No. 66-NFPA 86-2012 [ Section No. 13.5.11.11.17 ]

13.5.11.11.17*

The flow of noncarrier special atmosphere gases that are nonflammable shall not be permitted until minimum carrier gas flowhas been established proven .

Statement of Problem and Substantiation for Public Input

New wording clarifies that a carrier gas flow interlock is required.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:06:03 EDT 2012

Committee Statement

Resolution: FR-71-NFPA 86-2012

Statement: The revised text clarifies that a carrier gas flow interlock is required.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 110: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 110/163

Public Input No. 67-NFPA 86-2012 [ Section No. 13.5.11.11.19 ]

13.5.11.11.19 Liquids Atmosphere Low Furnace Dissociation Temperature Interlock.

(A)

Where a flammable liquid is used as a carrier gas and introduced in the liquid state, a second low temperature safety interlockshall be provided if flow of the liquid is continued at less than 1400°F (760°C).

(B)

The liquids atmosphere low furnace dissociation temperature interlock set point temperature shall not be less than thetemperature needed to reliably dissociate the liquid special atmosphere used.

Statement of Problem and Substantiation for Public Input

Content has been moved to 13.5.8.3.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:08:45 EDT 2012

Committee Statement

Resolution: FR-72-NFPA 86-2012

Statement: Content has been moved to 13.5.8.3, see FR-58-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 111: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 111/163

Public Input No. 142-NFPA 86-2012 [ Section No. A.1.1.7(4) ]

A.1.1.7(4)

For information on fluid heaters, refer to NFPA 87, Recommended Practice for Fluid Heaters .

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #142 at Section 1.1.7(4)

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 141-NFPA 86-2012 [Section No. 1.1.7] Removed annex and moved to required text

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 15:37:27 EDT 2012

Committee Statement

Resolution: FR-45-NFPA 86-2012

Statement: See FR-40-NFPA 86-2012. The Committee moved this reference to the body of the standard to ensure that it is not misapplied.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 112: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 112/163

Public Input No. 104-NFPA 86-2012 [ New Section after A.3.2.4 ]

A.3.3.6

The burner management system logic can include the following functions safety interlocks, pre-purge, trial for ignition, and safe-startcheck.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #102 at Section 8.3.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 102-NFPA 86-2012 [Section No. 8.3] Definition, Annex, and Mandatory Text are interrelated

Public Input No. 103-NFPA 86-2012 [New Section after 3.3.5.14] Definition and Annex are interrelated

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 00:30:36 EDT 2012

Committee Statement

Resolution: FR-17-NFPA 86-2012

Statement: Added annex material to FR-16-NFPA 86-2012 for clarification on burner management systems. The annex material is similar tothe annex material for burner management systems found in 2011 edition of NFPA 85, Boiler and Combustion Systems HazardsCode, but it is modified to reflect the system logic that is specific to ovens and furnaces.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 113: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 113/163

Public Input No. 94-NFPA 86-2012 [ New Section after A.3.3.25.3 ]

A.3.3.25.4

It is important to note that the loads processed in a Class B furnaces typically do not contain any flammable volatiles or combustiblematerials. However, when small amounts of flammable volatiles or combustible materials are present, it may be appropriate not to addsafety ventilation, as would be required for a Class A furnace, when doing so would be detrimental to the process and would notincrease the level of safety. See A.3.3.25.3 for additional information..

Statement of Problem and Substantiation for Public Input

See substantiation at Public Input #93

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 143-NFPA 86-2012 [Section No. 3.3.25.4] Annex linked to new asterisk at definition

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 22:56:42 EDT 2012

Committee Statement

Resolution: FR-11-NFPA 86-2012

Statement: The Committee added annex material to clarify the definition of Class B ovens.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 114: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 114/163

Public Input No. 53-NFPA 86-2012 [ Section No. A.3.3.25.3 ]

A.3.3.25.3 Class A Furnace.

Flammable volatiles or combustible materials can include, but are not limited to, any of the following:

(1) Paints, powders, inks, and adhesives from finishing processes, such as dipped, coated, sprayed, and impregnatedmaterials

(2) Substrate material

(3) Wood, paper, and plastic pallets, spacers, or packaging materials

(4) Polymerization or other molecular rearrangements

In addition, potentially flammable materials, such as quench oil, waterborne finishes, cooling oil, or cooking oils, that present ahazard are should be ventilated according to Class A standards.

Statement of Problem and Substantiation for Public Input

"Potentially flammable" materials such as quench oil, waterborne finishes, cutting oil, and cooking oils may present a hazard if they are heated to a temperature approaching their flash points. When these materials are cool enough or present in negligibly small amounts so they don't present a hazard in a heated enclosure, Class B requirements are sufficient. The proposed change adds a "should" recommendation so users are cognizant of a potential hazard that might necessitate Class A treatment (e.g., ensuring adequate safety ventilation).

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 13:12:26 EDT 2012

Committee Statement

Resolution: FR-50-NFPA 86-2012

Statement: "Potentially flammable" materials such as quench oil, waterborne finishes, cutting oil, and cooking oils may present a hazard ifthey are heated to a temperature approaching their flash points. When these materials are cool enough or present in negligiblysmall amounts so they don't present a hazard in a heated enclosure, Class B requirements are sufficient. This revision adds a"should" recommendation so users are cognizant of a potential hazard that might necessitate Class A treatment (e.g., ensuringadequate safety ventilation).

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 115: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 115/163

Public Input No. 65-NFPA 86-2012 [ New Section after A.3.3.45.1 ]

A.3.3.53.1

The required percent of the Lower Flammable Limit will be 25% when the safety ventilation rate is based upon the calculation methodsprovided in this standard for Class A ovens. As permitted by this standard, the required percent of the Lower Flammable Limit mayrange from 25% to 50% where Continuous Vapor Concentration High Limit Controllers are used.

Statement of Problem and Substantiation for Public Input

New Annex text added to assist users interpret the new definition of "Safety Ventilation" at 3.3.53.1 that refers to "the required percent of the Lower Flammable Limit (LFL)".

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 64-NFPA 86-2012 [New Section after 3.3.53] Annex material for new definition

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:53:43 EDT 2012

Committee Statement

Resolution: FR-92-NFPA 86-2012

Statement: New Annex text added to help clarify the new definition of "Safety Ventilation" from FR-91-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 169-NFPA 86-2012 [ Section No. A.6.2.6.4 ]

Page 116: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 116/163

A.6.2.6.4

See NFPA 54, National Fuel Gas Code, for exception to vent requirements.

Vent limiters are used to limit the escape of gas into the ambient atmosphere if a vented device (e.g., regulator, zero governor,pressure switch) requiring access to the atmosphere for operation has an internal component failure. When a vent limiter isused, there might not be a need to vent the device to an approved location. Following are some general guidelines andprinciples on the use of vented devices incorporating vent limiters:

(1) The listing requirements for vent limiters are covered in ANSI Z21.18/CSA 6.3, Standard for Gas Appliance PressureRegulators, for regulators and in ANSI/UL 353, Standard for Limit Controls, for pressure switches and limit controls. ANSIZ21.18/CSA 6.3 requires a maximum allowable leakage rate of 2.5 ft3/hr (0.071 m3/hr) for natural gas and 1.0 ft3/hr (0.028

m3/hr) for LP-Gas at the device's maximum rated pressure. ANSI/UL 353 allows 1.0 ft3/hr (0.028 m3/hr) for natural gas

and 1.53 ft3/hr (0.043 m3/hr) for LP-Gas at the device's maximum rated pressure. Since a field-installable vent limiter may

be rated less than the device itself and may be a field-installable device, a , or it may de-rate the device to a lowerpressure rating a combination listed device–vent limiter should be used.

(2) Where a vent limiter is used, there should be adequate airflow through the room or enclosure in which the equipment isinstalled. In reality, conditions can be less ideal, and care should be exercised for the following reasons:

(a) The relative density of the gas influences its ability to disperse in air. The higher the relative density, the more difficultit is for the gas to disperse (e.g., propane disperses more slowly than natural gas).

(b) Airflow patterns through a room or enclosure, especially in the vicinity of the gas leak, affect the ability of the air todilute that gas. The greater the local air movement, the greater the ease with which the gas is able to disperse.

(c) The vent limiter may not prevent the formation of a localized flammable air–gas concentration for the precedingreasons.

(3) Below is a table of various gases and equivalent leakage rates through a vent limiter. Leakage rates are based on themaximum pressure rating for the device.

Gas Type s.g. (based on air = 1.0 Leakage rate (ft 3 /hr)

Natural gas 0.65 2.5

Propane 1.50 1.0

Butane 1.95 0.80

(4) The standard ANSI Z21.18/CSA 6.3, Standard for Gas Appliance Pressure Regulators, to which vent limiting/regulatorcombinations are listed, has a limited scope of ½ PSI, 2 PSI, and 5 PSI. A limiting system is typically a type of leak limitingdevice that is rated for a pressure higher than 5 PSI without exceeding the allowable leakage rates of ANSI Z21.18/CSA 6.3,Standard for Gas Appliance Pressure Regulators. An example of such a device is a safety diaphragm using a fixed orifice typevent limiter, both of which are factory installed and housed within the regulator dome.

Additional Proposed Changes

File Name Description Approved

86_L32_R.docxChanges made in Terra

Statement of Problem and Substantiation for Public Input

New annex material added to provide information for the use of vent limiters with other gases, it adds some information on a leak limiting systems, and draws special attention to field installable vent limiters.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:09:03 EDT 2012

Committee Statement

Resolution: FR-102-NFPA 86-2012

Statement: New annex material added to provide information for the use of vent limiters with other gases, it adds some information on a leaklimiting systems, and draws special attention to field installable vent limiters, see FR-101-NFPA 86-2012.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

Page 117: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 117/163

and effect as a handw ritten signature

Public Input No. 98-NFPA 86-2012 [ New Section after A.6.5.2(2) ]

A.6.5.2(3)

The designer and user are cautioned that hazard conditions can result in common exhaust systems even when the radiant tubeburners connected to the common exhaust system are equipped with flame supervision.

Statement of Problem and Substantiation for Public Input

Off ratio conditions in radiant tube systems sharing a common exhaust system can create hazardous conditions even when the burners are equipped with flame supervision.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 97-NFPA 86-2012 [Section No. 6.5.2] Asterisk added to item (3) in mandatory text

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 21 23:38:55 EDT 2012

Committee Statement

Resolution: FR-15-NFPA 86-2012

Statement: Off ratio conditions in radiant tube systems sharing a common exhaust system can create hazardous conditions even when theburners are equipped with flame supervision.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 156-NFPA 86-2012 [ Section No. A.6.5.2(2) ]

A.6.5.2(2)

The following sample calculation is provided to demonstrate a method of determining the required exhaust flow moving throughthe collecting and venting system for unsupervised radiant tube burners such that the atmosphere in the collecting and ventingsystem is less than 100 percent LFL equals noncombustible state requirement. The sample calculation is based on thefollowing assumptions:

(1) The fuel is methane gas.

(2) All burners are not firing.

(3) All burner fuel valves are open.

(4) The main safety shutoff valve is open.

Overall, the sample calculation is based on the following conservative conditions:

(1) Use of the maximum fuel input rate for each burner

(2) Assumption that all burner fuel valves are open

(3) The design limit of <100% of LFL = noncombustible state

Page 118: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 118/163

(4) Inclusion of the effects of elevated furnace temperature on the LFL

(5) The use of ambient air to dilute the products of combustions exiting the radiant tubes and being conveyed in the collectingand venting system

The effects of temperature on fuel gas LFL were obtained from Bureau of Mines Bulletin 680, “Investigation of Fire and ExplosionAccidents in the Chemical, Mining, and Fuel-Related Industries – A Manual.” Figure 34 in that bulletin, “Temperature effect onlower limits of flammability of 10 normal paraffins in air at atmospheric pressure,” shows temperature (°C) versus combustibles(volume percent) and includes curves for methane, butane, and propane. It also includes a formula for computing LFL atelevated temperature. The formula, from Bureau of Mines Bulletin 627, “Flammability Characteristics of Combustible Gases andVapors,” is as follows:

where:

LT = LFL at the desired elevated temperature T (°C)

L 25= LFL at 25°C

T = Desired elevated temperature (°C)

Sample Problem — U.S. Customary Units

Objective. Calculate the exhaust flow moving through the collecting and venting system for unsupervised radiant tube burnersso as to maintain the collecting and venting system atmosphere below 100% LFL (i.e., noncombustible state).

Given the following information:

(1) Furnace type: Continuous

(2) Fuel: Methane

(3) Number of burners: 10

(4) Maximum fuel input per burner: 600 scfh

(5) Furnace temperature: 1200°F

(6) Radiant tube exhaust temperature: 2000°F

(7) Collecting and venting system temperature: 500°F, or 260°C

Step 1. Determine LFL at 500°F (which will be the same as the LFL at 260°C) using the formula from above.

Step 2. Determine exhaust flow at 70°F to control fuel input to <100% LFL. This formula follows an approach similar to thatgiven in 11.6.8.3(A) .

Step 3. Determine the temperature correction factor for volume. This formula is similar to the temperature correction factorformula used in 11.6.5.1.

Step 4. Determine exhaust flow at collection and venting system operating temperature to limit fuel input rate to 100% LFL at T

FCE TEMP. This formula follows an approach similar to that given in Chapter 9.

In the equation below delete 2.7.2 and replace with 2272. Delete 2.3.8 and replace with 1.81. Delete 4.115 and replace with4112.

Conclusion. The calculated exhaust rate of > 4.115 cfm @ 500°F is required to keep the collecting and venting system <100%LFL at its operating temperature with all burners off and fuel gas flowing at the maximum input rate.

Sample Problem — SI Units

Page 119: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 119/163

Objective. Calculate the exhaust flow moving through the collecting and venting system for unsupervised radiant tube burnersso as to maintain the collecting and venting system atmosphere below 100% LFL (i.e., noncombustible state).

Given the following information:

(1) Oven type: Continuous

(2) Fuel: Methane

(3) Number of burners: 10

(4) Maximum fuel input per burner: 16.99 m3/hr @ 21°C

(5) Furnace temperature: 649°C

(6) Radiant tube exhaust temperature: 1093°C

(7) Collecting and venting system temperature: 500°F (260°C)

Step 1. Determine LFL at 260°C using the formula from above:

Step 2. Determine exhaust airflow at 21°C to control fuel input to <100% LFL. This formula follows an approach similar to thatgiven in Chapter 11.

Step 3. Determine the temperature correction factor for volume. This formula is similar to temperature correction factor formulaused in Chapter 11.

Step 4. Determine exhaust flow at oven operating temperature to limit fuel input rate to 100% LFL at T FCE TEMP. This formula

follows an approach similar to that given in Chapter 11:

Conclusion. The calculated exhaust rate of >116.63 cfm m3/min @ 260°C is required to keep the collecting and ventingsystem <100% LFL at its operating temperature with all burners off and fuel gas flowing at the maximum input rate.

Statement of Problem and Substantiation for Public Input

The referenced section shows formulas for temperature correction of the LFL and does not relate to the formula of Step 2. The decimal in the resulting value 2.272 is not correct and the actual calculation equals 2272. The referenced section is Fire Protection and has no formulas or methods relating to the formula of Step 4. The correct value for QEXH 70°F & 100% LFL is 2272 instead of 2.72. The correct value of TCF VOL in Step 3 was 1.81 instead of 2.38. The correct final result is 4112 instead of 4.115. The cfm units are incorrect for this section and should be m3 / min as shown in the preceding text line.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 10:25:39 EDT 2012

Committee Statement

Resolution: FR-47-NFPA 86-2012

Statement: The referenced section shows formulas for temperature correction of the LFL and does not relate to the formula of Step 2. In theSample Problem — U.S. Customary Units, Step 2 and 4 the following is revised: The decimal in the resulting value 2.272 is not

correct and the actual calculation equals 2272. The referenced section is Fire Protection and has no formulas or methods relating

Page 120: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 120/163

correct and the actual calculation equals 2272. The referenced section is Fire Protection and has no formulas or methods relatingto the formula of Step 4. The correct value for QEXH 70°F & 100% LFL is 2272 instead of 2.72. The correct value of TCF VOL inStep 3 was 1.81 instead of 2.38. The correct final result is 4112 instead of 4.115. In the conclusion for the Sample Problem - SIunits, the cfm units are incorrect and should be m3 / min as shown in the preceding text line.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 176-NFPA 86-2012 [ New Section after A.7.1.6 ]

Add new text to read as follows: A.7.1.7 The evacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the piping upstream of theequipment isolation valve is governed by other codes, standards, and recommended practices. One example is NFPA 54, NationalFuel Gas Code, 2009 edition, Section 8.3 (ref: TIA 09-3 effective 08/25/10), which requires charging to be stopped upon detection ofcombustible gas at the point of discharge. Careful consideration should be given to the potential hazards that may be created in thesurrounding area for any fuel or combustible gas discharge. In NFPA 54, the term Appliance Shutoff Valve is analogous to the term Equipment Isolation Valve in NFPA 86.

Statement of Problem and Substantiation for Public Input

Note: This Proposal originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to the following fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54 took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1 Appliance Shutoff Valve. A valve located in the piping system used to shut off individual equipment. Excerpt from NFPA 86-2011 3.3.76.3 Equipment Isolation Valve. A manual shutoff valve for shutoff of the fuel to each piece of equipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. The emergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management of liquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public a benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. The submitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 on evacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the Technical Committee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard Investigation Board (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditions but does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supply contained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gas being delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitter and members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposed requirements and Annex referencing NFPA 54’s related requirements.

Submitter Information Verification

Submitter Full Name:Ted Jablkowski

Organization: Fives North American Combustio

Submittal Date: Fri Sep 14 12:11:48 EDT 2012

Committee Statement

Resolution: FR-94-NFPA 86-2012

Statement: This revision originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to thefollowing fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1Appliance Shutoff Valve.&#160;&#160; A valve located in the piping system used to shut off individual equipment. Excerpt fromNFPA 86-2011 3.3.76.3 Equipment Isolation Valve.&#160;&#160; A manual shutoff valve for shutoff of the fuel to each piece ofequipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. Theemergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management ofliquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public a

benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. The

Page 121: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 121/163

benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. Thesubmitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 onevacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the TechnicalCommittee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard InvestigationBoard (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditionsbut does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supplycontained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gasbeing delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitterand members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposedrequirements and Annex referencing NFPA 54’s related requirements.

Copyright Assignment

I, Ted Jablkow ski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Ted Jablkow ski, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 122: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 122/163

Public Input No. 152-NFPA 86-2012 [ New Section after A.7.4.9 ]

Add new text to read as follows: Another methods to perform a leak test of the valve. Leakage of valve seat can be determined by knowing the following: 1. Initial test pressure (ps(v2)) 2. Final test pressure (ps(v2)) 3. Test Time 4. Test volume

******Insert Equation Here******

Below is a sample calculation of the measured leakage on a valve seat based on measured values and known quantities (note: actualvalues are measured in metric units). 1. Test Time is 10 seconds 2. Test volume is 0.226 liters 3. Measured Initial test pressure is 27.7"WC (1 PSI) 4. Measured Final test pressure is 25.7"WC

******Insert Table Here******

This test method below is solving for Lv2 (leakage on V2) since the leakage rate on V2 is measuring using the pressure decay leaktest method.

Additional Proposed Changes

File Name Description Approved

86_L23_Tb_R.docx Table Log 23 PI #152

86_L23_Eq_R.docxEquation Log 23 PI #152

Statement of Problem and Substantiation for Public Input

The proposal describes an alternative means to leak test a safety shutoff valve.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Mon Jul 02 08:27:01 EDT 2012

Committee Statement

Resolution: FR-105-NFPA 86-2012

Statement: The revision describes an alternative means to leak test a safety shutoff valve. This is not a new section after A.7.4.9, but it is tobe added to the end of the existing A.7.4.9.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 123: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 123/163

Public Input No. 177-NFPA 86-2012 [ New Section after A.7.4.15 ]

Add new text to read as follows: A.7.4.19 See A.6.2.6.3.

Statement of Problem and Substantiation for Public Input

Note: This Proposal originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011.The U.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to the following fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54 took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1 Appliance Shutoff Valve. A valve located in the piping system used to shut off individual equipment. Excerpt from NFPA 86-2011 3.3.76.3 Equipment Isolation Valve. A manual shutoff valve for shutoff of the fuel to each piece of equipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. The emergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management of liquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public a benefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. The submitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 on evacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the Technical Committee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard Investigation Board (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditions but does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supply contained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gas being delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitter and members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposed requirements and Annex referencing NFPA 54’s related requirements.

Submitter Information Verification

Submitter Full Name:Ted Jablkowski

Organization: Fives North American Combustio

Submittal Date: Fri Sep 14 12:13:05 EDT 2012

Committee Statement

Resolution: FR-98-NFPA 86-2012

Statement: Revision originates from Tentative Interim Amendment 86-11-3 (TIA 1010) issued by the Standards Council on March 1, 2011. TheU.S. Chemical Safety and Hazard Investigation Board (CSB) requested an appropriate action by NFPA 86 in response to thefollowing fuel gas related explosion at ConAgra Foods, Garner, NC in 2009 The NFPA 86 task group elected to wait until NFPA 54took action on this matter. NFPA 54 issued TIA 09-3 with an effective date of 08/25/10. Excerpt from NFPA 54-2009 3.3.105.1Appliance Shutoff Valve.&#160;&#160; A valve located in the piping system used to shut off individual equipment. Excerpt fromNFPA 86-2011 3.3.76.3 Equipment Isolation Valve.&#160;&#160; A manual shutoff valve for shutoff of the fuel to each piece ofequipment. Note: This TIA does not address liquid fuel evacuation/purge, charging, and confirmation of liquid fuel supply. Theemergency condition identified by the CSB for fuel gas discharges did not extend to liquid fuels, however, the management ofliquid fuels should be considered in the next revision cycle. Emergency Nature: The proposed TIA intends to offer to the public abenefit that would lessen a recognized (known) hazard or ameliorate a continuing or dangerous condition or situation. Thesubmitter has proposed this Tentative Interim Amendment to add sections 7.1.7*, A.7.1.7, 7.4.19* and A.7.4.19 onevacuation/purging, charging, and confirmation of the fuel or combustible gas supply in the supply piping because of the TechnicalCommittee’s awareness of incidents including the investigation findings of the U.S. Chemical Safety and Hazard InvestigationBoard (CSB). The current requirements of the NFPA 86 Standard provide a performance approach to establishing safe conditionsbut does not provide any requirements for the evacuation/purging, charging, and confirmation of the fuel or combustible gas supplycontained within the fuel or combustible gas supply piping nor any requirements defining the quality of the fuel or combustible gasbeing delivered by piping systems governed by NFPA 54 National Fuel Gas Code and other Codes and Standards. The submitterand members of the NFPA 86 Technical Committee wish to draw attention to this potential hazard by the addition of the proposedrequirements and Annex referencing NFPA 54’s related requirements.

Copyright Assignment

I, Ted Jablkow ski, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Ted Jablkow ski, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 124: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 124/163

Public Input No. 118-NFPA 86-2012 [ Section No. A.8.2.8 ]

A.8.2.8

The actions resulting from a manual emergency switch action take into account the individual system design and the hazards(e.g., mechanical, combustion system, special atmosphere, etc.) associated with changing the existing state to another stateand initiates actions to cause the system to revert to a safe condition.

For some applications, additional manual action may be required to bring the process to a safe condition.

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #117 at Section 8.2.8

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 117-NFPA 86-2012 [Section No.8.2.8]

Annex material for revised requirement of at least one manual emergencyswitch

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 04:24:15 EDT 2012

Committee Statement

Resolution: FR-23-NFPA 86-2012

Statement: Annex material added for further clarification, see FR-22-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 125: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 125/163

Public Input No. 123-NFPA 86-2012 [ Section No. A.8.3 ]

A.8.3

Furnace controls that meet the performance-based requirements of standards such as ANSI/ISA 84.00.01, Application ofSafety Instrumented Systems for the Process Industries Industries and IEC 61511 Functional Safety: Safety InstrumentsSystems for the Process Industry Sector , can be considered equivalent. The determination of equivalency will involve completeconformance to the safety life cycle including risk analysis, safety integrity level selection, and safety integrity level verification,which should be submitted to the authority having jurisdiction.

Statement of Problem and Substantiation for Public Input

The requirements are identical in the two cited standards.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group Introductory Chapters

Submittal Date: Fri Jun 22 05:51:19 EDT 2012

Committee Statement

Resolution: FR-114-NFPA 86-2012

Statement: The requirements are identical in the two cited standards.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 126: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 126/163

Public Input No. 134-NFPA 86-2012 [ New Section after A.8.4 ]

A.8.4.4

A single pressure transmitter with associated logic may be used to provide both of the required low and high pressure interlockfunctions. A single flow transmitter with associated logic may be used to provide both of the required low and high flow interlockfunctions.

Statement of Problem and Substantiation for Public Input

Add clarification that 8.4.4 does not specifically require a one for one replacement of one transmitter for the low gas pressure switch and a separate transmitter for the high gas pressure switch. With advances in diagnostics of transmitters for the detection of internal failures as well as diagnostic capabilities afforded by monitoring an analog variable, the replacement of two discrete switches by a single transmitter does not reduce the level of safety. The function being monitored by a transmitter is viewed as a single function, “in safe range”.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 52-NFPA 86-2012 [Section No. 8.4.4] Annex material for modification to pressure transmitter requirement

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NPFA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:47:23 EDT 2012

Committee Statement

Resolution: FR-79-NFPA 86-2012

Statement: Add clarification that 8.2.11 (FR-9-NFPA 86-2012) does not specifically require a one for one replacement of one transmitter for thelow gas pressure switch and a separate transmitter for the high gas pressure switch. With advances in diagnostics of transmittersfor the detection of internal failures as well as diagnostic capabilities afforded by monitoring an analog variable, the replacement oftwo discrete switches by a single transmitter does not reduce the level of safety. The function being monitored by a transmitter isviewed as a single function, “in safe range”.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 148-NFPA 86-2012 [ Section No. A.8.5.1.8(4)(d) ]

A.8.5.1.8(4)(d)

In accordance with 8.5.1.8(4)(c), fuels other than natural gas, butane, or propane may require additional consideration. Theseadditional considerations would be addressed using Section 1.5. The concern with other fuel gases is the variability of fuel gascontent being delivered over time. Specific examples include landfill gas and bio gas.

The following sample calculation illustrating the use of 8.5.1.8(4)(d) is provided to demonstrate a method of determining the25% LFL requirement.

The sample calculation is based upon the following assumptions:

(1) The fuel is methane gas.

(2) All burners are turned off for the control purposes. All safety shutoff valves are de-energized.

(3) Two safety shutoff valves are closed at each burner.

(4) All safety shutoff valves are

Page 127: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 127/163

proven closed.All safety shutoff valves are

(1) tested for seat leakage at least semiannually.

(1) Safety shutoff valve seat leakage is assumed to be 1 scfh (0.0283 m 3 /hr @ 21°C).

The following thoughts are offered regarding the selection of the 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakagerate.

Limited data reviewed by the committee indicates that valve seat leakage rates over 1 scfh (0.0283 m3/hr @ 21°C) are notanticipated unless the safety shutoff valve seats are exposed to extremely unusual conditions such as corrosives in the fuel gasor furnace heat allowed to back up the fuel line and burn the safety shutoff valve seat. The former condition is the basis forlimiting the use of 8.5.1.8(4) to furnaces using natural gas, butane, or propane fuel gases. The latter condition occurred in acase where a fuel line was inappropriately opened by maintenance staff while the furnace was in operation. The furnace waspromptly shut down, and the safety shutoff valves were replaced.

Under operating conditions expected by this standard, it is anticipated that debris from internal fuel gas line oxidation (rust),pipe thread shavings not removed before fuel line assembly, or similar exposures can subject one safety shutoff valve to seatdamage that can lead to seat leakage of one safety shutoff valve; however, it is not expected that both safety shutoff valves

would experience similar seat leakage. The selected safety shutoff valve seat leakage rate of 1 scfh (0.0283 m3/hr @ 21°C)isconsidered conservative.

Overall, this sample calculation is based upon the following conservative conditions:

(1) The use of a 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakage rate.

(2) Providing two safety shutoff valves for each fuel path.

(3) Using valve proving to prove each safety shutoff valve closed.

(4) Assuming safety shutoff valve leakage at each burner fuel path.

(5) Using a design limit of 25 percent of LFL.

(6) Including the effects of elevated furnace temperature on the LFL.

(7) Assuming no fuel exits the furnace.

The effects of temperature on fuel gas LFL were obtained from a United States Department of the Interior, Bureau of MinesBulletin 680, “Investigation of Fire and Explosion Accidents in the Chemical, Mining, and Fuel-Related Industries — A Manual.”Figure 34 in that bulletin, “Temperature effect on lower limits of flammability of 10 normal paraffins in air at atmosphericpressure,” shows temperature (°C) versus combustibles (volume percent) and includes curves for methane, butane, andpropane. It also includes a formula for computing LFL at elevated temperature. That formula, based on Bureau of Mines Bulletin627, “Flammability Characteristics of Combustible Gases and Vapors,” is as follows:

where:

LT = LFL at the desired elevated temperature, T (°C)

L 25= LFL at 25°C

T = Desired elevated temperature (°C)

Sample Problem — U. S. Customary Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 8 ft wide × 6 ft deep × 8 ft tall

Number of burners: 5

Burner design rate: 0.8 MM Btu/hr

Burner design excess air: 10.0%

Burner design air capacity: 8800 scfh

Burner air minimum design flow: 100 scfh

Maximum leak rate each flow path*: 1 scfh

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnaceenclosure.

Page 128: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 128/163

Step 1. Determine LFL at 900°F using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 900°F:

Step 7. Determine the time in minutes to reach 25% LFL with all burners off:

Conclusions. Where the value of % LFL 900°F exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 900°F equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Sample Problem — SI Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 2.438 m wide × 1.828 m deep × 2.428 m tall

Number of burners: 5

Burner design rate: 234.2 kW

Burner design excess air: 10.0%

Burner design air capacity: 249.2 m3/hr @ 21°C

Burner air minimum design flow: 2.83 m3/hr @ 21°C

Maximum leak rate each flow path*: 0.0283 m3/hr @ 21°C

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

Page 129: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 129/163

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnaceenclosure.

Step 1. Determine LFL at 482°C using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 482°C:

Step 7. Determine the time in minutes to reach 25 percent LFL with all burners off:

Conclusions. Where the value of % LFL 482°C exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 482°C equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Statement of Problem and Substantiation for Public Input

This proposal fixes a discrepancy from adopting TIA86-11-4. The TIA changed the original A.8.5.1.8(4)(a) condition and replaced the “At least two safety shutoff valves are proved closed…” requirement with “The number of safety shutoff valves required to close in 8.8.1.2 and 8.8.1.3 will close…”. The Annex assumption condition of A.8.5.1.8(4)(d)(4) which refers to the original condition for “proved close” does not apply when TIA11-4 is incorporated. All use of “proven” for this annex example do not apply and should be deleted. NOTE TO EDITOR: the online software did not properly handle and show the deletion of the numbered list item (4) and renumber (5) to (4) and renumber (6) to (5).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 147-NFPA 86-2012 [Section No. 8.5.1.8] If TIA 11-4 accepted, this should be incorporated into the annex.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Fri Jun 22 16:33:40 EDT 2012

Page 130: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 130/163

Committee Statement

Resolution: FR-31-NFPA 86-2012

Statement: This revision fixes a discrepancy from adopting TIA86-11-4. The TIA changed the original A.8.5.1.8(4)(a) condition and replaced the“At least two safety shutoff valves are proved closed…” requirement with “The number of safety shutoff valves required to close in8.8.1.2 and 8.8.1.3 will close…”. The Annex assumption condition of A.8.5.1.8(4)(d)(4) which refers to the original condition for“proved close” does not apply when TIA11-4 is incorporated. All use of “proven” for this annex example do not apply and should bedeleted. The Committee also corrected a typo in the Sample Problem - U.S. Customary Units of A.8.5.1.8(4)(d) Step 1 whichshould read: L900F=L482C. Additionally, the Committee corrected the application of the formula presented in the Sample Problem- U.S. Customary Units of A.8.5.1.8(4)(d) Step 5. Which should read: (5 scfh/500 scfh)(100%).

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 170-NFPA 86-2012 [ Section No. A.8.5.1.8(4)(d) ]

A.8.5.1.8(4)(d)

In accordance with 8.5.1.8(4)(c), fuels other than natural gas, butane, or propane may require additional consideration. Theseadditional considerations would be addressed using Section 1.5. The concern with other fuel gases is the variability of fuel gascontent being delivered over time. Specific examples include landfill gas and bio gas.

The following sample calculation illustrating the use of 8.5.1.8(4)(d) is provided to demonstrate a method of determining the25% LFL requirement.

The sample calculation is based upon the following assumptions:

(1) The fuel is methane gas.

(2) All burners are turned off for the control purposes. All safety shutoff valves are de-energized.

(3) Two safety shutoff valves are closed at each burner.

(4) All safety shutoff valves are proven closed.

(5) All safety shutoff valves are tested for seat leakage at least semiannually.

(6) Safety shutoff valve seat leakage is assumed to be 1 scfh (0.0283 m3/hr @ 21°C).

The following thoughts are offered regarding the selection of the 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakagerate.

Limited data reviewed by the committee indicates that valve seat leakage rates over 1 scfh (0.0283 m3/hr @ 21°C) are notanticipated unless the safety shutoff valve seats are exposed to extremely unusual conditions such as corrosives in the fuel gasor furnace heat allowed to back up the fuel line and burn the safety shutoff valve seat. The former condition is the basis forlimiting the use of 8.5.1.8(4) to furnaces using natural gas, butane, or propane fuel gases. The latter condition occurred in acase where a fuel line was inappropriately opened by maintenance staff while the furnace was in operation. The furnace waspromptly shut down, and the safety shutoff valves were replaced.

Under operating conditions expected by this standard, it is anticipated that debris from internal fuel gas line oxidation (rust),pipe thread shavings not removed before fuel line assembly, or similar exposures can subject one safety shutoff valve to seatdamage that can lead to seat leakage of one safety shutoff valve; however, it is not expected that both safety shutoff valves

would experience similar seat leakage. The selected safety shutoff valve seat leakage rate of 1 scfh (0.0283 m3/hr @ 21°C)isconsidered conservative.

Overall, this sample calculation is based upon the following conservative conditions:

(1) The use of a 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakage rate.

(2) Providing two safety shutoff valves for each fuel path.

(3) Using valve proving to prove each safety shutoff valve closed.

(4) Assuming safety shutoff valve leakage at each burner fuel path.

(5) Using a design limit of 25 percent of LFL.

(6) Including the effects of elevated furnace temperature on the LFL.

(7) Assuming no fuel exits the furnace.

Page 131: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 131/163

The effects of temperature on fuel gas LFL were obtained from a United States Department of the Interior, Bureau of MinesBulletin 680, “Investigation of Fire and Explosion Accidents in the Chemical, Mining, and Fuel-Related Industries — A Manual.”Figure 34 in that bulletin, “Temperature effect on lower limits of flammability of 10 normal paraffins in air at atmosphericpressure,” shows temperature (°C) versus combustibles (volume percent) and includes curves for methane, butane, andpropane. It also includes a formula for computing LFL at elevated temperature. That formula, based on Bureau of Mines Bulletin627, “Flammability Characteristics of Combustible Gases and Vapors,” is as follows:

where:

LT = LFL at the desired elevated temperature, T (°C)

L 25= LFL at 25°C

T = Desired elevated temperature (°C)

Sample Problem — U. S. Customary Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 8 ft wide × 6 ft deep × 8 ft tall

Number of burners: 5

Burner design rate: 0.8 MM Btu/hr

Burner design excess air: 10.0%

Burner design air capacity: 8800 scfh

Burner air minimum design flow: 100 scfh

Maximum leak rate each flow path*: 1 scfh

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 900°F using the formula from above:

Revise this part of the equation:

L 900F = L 482FC =

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 900°F:

Page 132: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 132/163

Step 7. Determine the time in minutes to reach 25% LFL with all burners off:

Conclusions. Where the value of % LFL 900°F exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 900°F equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Sample Problem — SI Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 2.438 m wide × 1.828 m deep × 2.428 m tall

Number of burners: 5

Burner design rate: 234.2 kW

Burner design excess air: 10.0%

Burner design air capacity: 249.2 m3/hr @ 21°C

Burner air minimum design flow: 2.83 m3/hr @ 21°C

Maximum leak rate each flow path*: 0.0283 m3/hr @ 21°C

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 482°C using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Page 133: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 133/163

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 482°C:

Step 7. Determine the time in minutes to reach 25 percent LFL with all burners off:

Conclusions. Where the value of % LFL 482°C exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 482°C equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Statement of Problem and Substantiation for Public Input

The formula is below rather than above, and 482F should be 482C.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:12:46 EDT 2012

Committee Statement

Resolution: FR-31-NFPA 86-2012

Statement: This revision fixes a discrepancy from adopting TIA86-11-4. The TIA changed the original A.8.5.1.8(4)(a) condition and replaced the“At least two safety shutoff valves are proved closed…” requirement with “The number of safety shutoff valves required to close in8.8.1.2 and 8.8.1.3 will close…”. The Annex assumption condition of A.8.5.1.8(4)(d)(4) which refers to the original condition for“proved close” does not apply when TIA11-4 is incorporated. All use of “proven” for this annex example do not apply and should bedeleted. The Committee also corrected a typo in the Sample Problem - U.S. Customary Units of A.8.5.1.8(4)(d) Step 1 whichshould read: L900F=L482C. Additionally, the Committee corrected the application of the formula presented in the Sample Problem- U.S. Customary Units of A.8.5.1.8(4)(d) Step 5. Which should read: (5 scfh/500 scfh)(100%).

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 179-NFPA 86-2012 [ Section No. A.8.5.1.8(4)(d) ]

A.8.5.1.8(4)(d)

In accordance with 8.5.1.8 (4)(c), fuels other than natural gas, butane, or propane may require additional consideration. Theseadditional considerations would be addressed using Section 1.5. The concern with other fuel gases is the variability of fuel gascontent being delivered over time. Specific examples include landfill gas and bio gas.

The following sample calculation illustrating the use of 8.5.1.8 (4)(d) is provided to demonstrate a method of determining the25% LFL requirement.

Page 134: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 134/163

The sample calculation is based upon the following assumptions:

(1) The fuel is methane gas.

(2) All burners are turned off for the control purposes. All safety shutoff valves are de-energized.

(3) Two safety shutoff valves are closed at each burner.

(4) All safety shutoff valves are proven proved closed, when required .

(5) All safety shutoff valves are tested for seat leakage at least semiannually.

(6) Safety shutoff valve seat leakage is assumed to be 1 scfh (0.0283 m3/hr @ 21°C).

The following thoughts are offered regarding the selection of the 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakagerate.

Limited data reviewed by the committee indicates that valve seat leakage rates over 1 scfh (0.0283 m3/hr @ 21°C) are notanticipated unless the safety shutoff valve seats are exposed to extremely unusual conditions such as corrosives in the fuel gasor furnace heat allowed to back up the fuel line and burn the safety shutoff valve seat. The former condition is the basis forlimiting the use of 8.5.1.8 (4) to furnaces using natural gas, butane, or propane fuel gases. The latter condition occurred in acase where a fuel line was inappropriately opened by maintenance staff while the furnace was in operation. The furnace waspromptly shut down, and the safety shutoff valves were replaced.

Under operating conditions expected by this standard, it is anticipated that debris from internal fuel gas line oxidation (rust),pipe thread shavings not removed before fuel line assembly, or similar exposures can subject one safety shutoff valve to seatdamage that can lead to seat leakage of one safety shutoff valve; however, it is not expected that both safety shutoff valves

would experience similar seat leakage. The selected safety shutoff valve seat leakage rate of 1 scfh (0.0283 m3/hr @ 21°C)isconsidered conservative.

Overall, this sample calculation is based upon the following conservative conditions:

(1) The use of a 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakage rate.

(2) Providing two safety shutoff valves for each fuel path.

(3) Using valve proving to prove each safety shutoff valve closed.

(4) Assuming safety shutoff valve leakage at each burner fuel path.

(5) Using a design limit of 25 percent of LFL.

(6) Including the effects of elevated furnace temperature on the LFL.

(7) Assuming no fuel exits the furnace.

The effects of temperature on fuel gas LFL were obtained from a United States Department of the Interior, Bureau of MinesBulletin 680, “Investigation of Fire and Explosion Accidents in the Chemical, Mining, and Fuel-Related Industries — A Manual.”Figure 34 in that bulletin, “Temperature effect on lower limits of flammability of 10 normal paraffins in air at atmosphericpressure,” shows temperature (°C) versus combustibles (volume percent) and includes curves for methane, butane, andpropane. It also includes a formula for computing LFL at elevated temperature. That formula, based on Bureau of Mines Bulletin627, “Flammability Characteristics of Combustible Gases and Vapors,” is as follows:

where:

LT = LFL at the desired elevated temperature, T (°C)

L 25= LFL at 25°C

T = Desired elevated temperature (°C)

Sample Problem — U. S. Customary Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 8 ft wide × 6 ft deep × 8 ft tall

Number of burners: 5

Burner design rate: 0.8 MM Btu/hr

Burner design excess air: 10.0%

Burner design air capacity: 8800 scfh

Burner air minimum design flow: 100 scfh

Maximum leak rate each flow path*: 1 scfh

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Page 135: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 135/163

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 900°F using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 900°F:

Step 7. Determine the time in minutes to reach 25% LFL with all burners off:

Conclusions. Where the value of % LFL 900°F exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 900°F equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Sample Problem — SI Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 2.438 m wide × 1.828 m deep × 2.428 m tall

Number of burners: 5

Burner design rate: 234.2 kW

Burner design excess air: 10.0%

Burner design air capacity: 249.2 m3/hr @ 21°C

Burner air minimum design flow: 2.83 m3/hr @ 21°C

Maximum leak rate each flow path*: 0.0283 m3/hr @ 21°C

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Page 136: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 136/163

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 482°C using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 482°C:

Step 7. Determine the time in minutes to reach 25 percent LFL with all burners off:

Conclusions. Where the value of % LFL 482°C exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 482°C equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Statement of Problem and Substantiation for Public Input

Note: This ProposaThe revised NFPA 86 (2011) paragraph 8.5.1.8 has introduced a new requirement that will require new or renovated bakery ovens to add a proof-of-closure switch to each safety shutoff valve. Bakery ovens can have up to 300 or more burners. As such, the change represents: 1) Installing a large number of proof-of-closure switches. 2) Expanded testing, inspection, and maintenance to cover all of the added switches. 3) Considerable wiring to connect all of these added switches. 4) Complex logic to monitor and process signals from all of the added switches.Emergency Nature: The revised NFPA 86 (2011) paragraph 8.5.1.8 contains an omission that was overlooked during the last revision cycle. Guidance specific to burners firing at rates less than or equal to 400,000 Btu/hr were not addressed in the revised text. In addition, the revised NFPA 86 (2011) paragraph 8.5.1.8 contains guidance that is in conflict with Section 8.8.2.2 as discussed further here. Consider the requirements of NFPA 86 as they would apply to an oven with the following characteristics: · Multiple burners · Each burner has a firing rate under 400,000 Btu/hr · Each burner has two safety shutoff valves · Each burner has a direct spark ignition with separate ignition electrode and separate flame sensing electrode. 1) NFPA 86 (2011) paragraph 8.8.2.2 would not require proof-of-closure on any of the safety shutoff valves. 2) NFPA 86 (2011) would not prohibit the shutdown of one or more burners (by closing the two burner safety shutoff valves) while maintaining

Page 137: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 137/163

other burners in service.Overall, if it is safe to operate this oven with any number of burners (fired under 400,000 Btu/hr) turned off by closing two safety shutoff valves, it should be equally safe to allow a restart of any or all burners without a repurge of the oven as long as the airflow rate needed to keep the oven atmosphere below 25% of LFL (based upon a valve seat leakage rate of 1 scfh) is maintain at all times that any burners are turned off. Overall, the basis of safety for the burners rated less than or equal to 400,000 Btu/hr is the use of two safety shutoff valves. The basis of safety does not expand to include proving valves closed until the burner rate exceeds 400,000 Btu/hr or a burner is taken out of service by closing one safety shutoff valve.l originates from Tentative Interim Amendment 86-11-4 (TIA 1011) issued by the Standards Council on March 1, 2011.

Submitter Information Verification

Submitter Full Name:PHILIP DOMENICUCCI

Organization: American Society of Bakers

Submittal Date: Fri Sep 14 12:28:07 EDT 2012

Committee Statement

Resolution: FR-31-NFPA 86-2012

Statement: This revision fixes a discrepancy from adopting TIA86-11-4. The TIA changed the original A.8.5.1.8(4)(a) condition and replaced the“At least two safety shutoff valves are proved closed…” requirement with “The number of safety shutoff valves required to close in8.8.1.2 and 8.8.1.3 will close…”. The Annex assumption condition of A.8.5.1.8(4)(d)(4) which refers to the original condition for“proved close” does not apply when TIA11-4 is incorporated. All use of “proven” for this annex example do not apply and should bedeleted. The Committee also corrected a typo in the Sample Problem - U.S. Customary Units of A.8.5.1.8(4)(d) Step 1 whichshould read: L900F=L482C. Additionally, the Committee corrected the application of the formula presented in the Sample Problem- U.S. Customary Units of A.8.5.1.8(4)(d) Step 5. Which should read: (5 scfh/500 scfh)(100%).

Copyright Assignment

I, PHILIP DOMENICUCCI, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input

(including both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint

author, in any publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public

Input and that I have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am PHILIP DOMENICUCCI, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions

contained therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same

legal force and effect as a handw ritten signature

Public Input No. 40-NFPA 86-2012 [ Section No. A.8.5.1.8(4)(d) ]

A.8.5.1.8(4)(d)

In accordance with 8.5.1.8(4)(c), fuels other than natural gas, butane, or propane may require additional consideration. Theseadditional considerations would be addressed using Section 1.5. The concern with other fuel gases is the variability of fuel gascontent being delivered over time. Specific examples include landfill gas and bio gas.

The following sample calculation illustrating the use of 8.5.1.8(4)(d) is provided to demonstrate a method of determining the25% LFL requirement.

The sample calculation is based upon the following assumptions:

(1) The fuel is methane gas.

(2) All burners are turned off for the control purposes. All safety shutoff valves are de-energized.

(3) Two safety shutoff valves are closed at each burner.

(4) All safety shutoff valves are proven closed.

(5) All safety shutoff valves are tested for seat leakage at least semiannually.

(6) Safety shutoff valve seat leakage is assumed to be 1 scfh (0.0283 m3/hr @ 21°C).

The following thoughts are offered regarding the selection of the 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakagerate.

Limited data reviewed by the committee indicates that valve seat leakage rates over 1 scfh (0.0283 m3/hr @ 21°C) are notanticipated unless the safety shutoff valve seats are exposed to extremely unusual conditions such as corrosives in the fuel gasor furnace heat allowed to back up the fuel line and burn the safety shutoff valve seat. The former condition is the basis forlimiting the use of 8.5.1.8(4) to furnaces using natural gas, butane, or propane fuel gases. The latter condition occurred in acase where a fuel line was inappropriately opened by maintenance staff while the furnace was in operation. The furnace waspromptly shut down, and the safety shutoff valves were replaced.

Under operating conditions expected by this standard, it is anticipated that debris from internal fuel gas line oxidation (rust),pipe thread shavings not removed before fuel line assembly, or similar exposures can subject one safety shutoff valve to seatdamage that can lead to seat leakage of one safety shutoff valve; however, it is not expected that both safety shutoff valves

Page 138: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 138/163

would experience similar seat leakage. The selected safety shutoff valve seat leakage rate of 1 scfh (0.0283 m3/hr @ 21°C)isconsidered conservative.

Overall, this sample calculation is based upon the following conservative conditions:

(1) The use of a 1 scfh (0.0283 m3/hr @ 21°C) safety shutoff valve seat leakage rate.

(2) Providing two safety shutoff valves for each fuel path.

(3) Using valve proving to prove each safety shutoff valve closed.

(4) Assuming safety shutoff valve leakage at each burner fuel path.

(5) Using a design limit of 25 percent of LFL.

(6) Including the effects of elevated furnace temperature on the LFL.

(7) Assuming no fuel exits the furnace.

The effects of temperature on fuel gas LFL were obtained from a United States Department of the Interior, Bureau of MinesBulletin 680, “Investigation of Fire and Explosion Accidents in the Chemical, Mining, and Fuel-Related Industries — A Manual.”Figure 34 in that bulletin, “Temperature effect on lower limits of flammability of 10 normal paraffins in air at atmosphericpressure,” shows temperature (°C) versus combustibles (volume percent) and includes curves for methane, butane, andpropane. It also includes a formula for computing LFL at elevated temperature. That formula, based on Bureau of Mines Bulletin627, “Flammability Characteristics of Combustible Gases and Vapors,” is as follows:

where:

LT = LFL at the desired elevated temperature, T (°C)

L 25= LFL at 25°C

T = Desired elevated temperature (°C)

Sample Problem — U. S. Customary Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 8 ft wide × 6 ft deep × 8 ft tall

Number of burners: 5

Burner design rate: 0.8 MM Btu/hr

Burner design excess air: 10.0%

Burner design air capacity: 8800 scfh

Burner air minimum design flow: 100 scfh

Maximum leak rate each flow path*: 1 scfh

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 900°F using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Step 4. Determine the airflow into the furnace with all burners off:

Page 139: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 139/163

Step 5. Determine the percent volume methane to air through all burners: formula with example flows is incorrect - should be: =(5 scfh / 500 scfh)(100%)

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 900°F:

Step 7. Determine the time in minutes to reach 25% LFL with all burners off:

Conclusions. Where the value of % LFL 900°F exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 900°F equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Sample Problem — SI Units

Objective. Calculate the amount of time that all burners can be turned off before the furnace atmosphere will reach 25% of LFL.

Assumptions. Furnace contains no combustibles when the burners are turned off. Furnace is under positive pressure with no airinfiltration.

Given the following information:

Furnace type: Batch

Furnace size: 2.438 m wide × 1.828 m deep × 2.428 m tall

Number of burners: 5

Burner design rate: 234.2 kW

Burner design excess air: 10.0%

Burner design air capacity: 249.2 m3/hr @ 21°C

Burner air minimum design flow: 2.83 m3/hr @ 21°C

Maximum leak rate each flow path*: 0.0283 m3/hr @ 21°C

Number of burner flow paths**: 5

Furnace temperature: 900°F or 482°C

Oxygen in furnace atmosphere: 18%

Fuel: Methane

*The flow path is across one set of safety shutoff valves proven closed.

**The number of flow paths is the number of sets of safety shutoff valves proven closed that may leak into the furnace enclosure.

Step 1. Determine LFL at 482°C using the formula from above:

Step 2. Determine the furnace volume:

Step 3. Determine the methane leak rate into the furnace with all burners off:

Page 140: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 140/163

Step 4. Determine the airflow into the furnace with all burners off:

Step 5. Determine the percent volume methane to air through all burners:

Step 6. Determine the percent LFL resulting from the methane flow through all burner fuel paths at 482°C:

Step 7. Determine the time in minutes to reach 25 percent LFL with all burners off:

Conclusions. Where the value of % LFL 482°C exceeds 25 percent, the burner safety shutoff valves can remain closed and

burners be reignited without a repurge within a period of time not exceeding t FCE 25% LFL. After t FCE 25% LFL is exceeded,

a repurge of the furnace is required.

Where the value of % LFL 482°C equals or is less than 25 percent, burners can be reignited at any time as long as the airflow

rate Q AIR is proven and interlocked in the combustion safety system such that loss of this proven airflow rate will require a

repurge of the furnace before burner reignition is permitted.

Statement of Problem and Substantiation for Public Input

The submitted change will correct the application of the formula presented in the Sample Problem - U.S. Customary Units of A.8.5.1.8(4)(d) Step 5.

Submitter Information Verification

Submitter Full Name:Joseph Kozma III

Organization: AFC-Holcroft LLC

Submittal Date: Thu May 10 10:55:11 EDT 2012

Committee Statement

Resolution: FR-31-NFPA 86-2012

Statement: This revision fixes a discrepancy from adopting TIA86-11-4. The TIA changed the original A.8.5.1.8(4)(a) condition and replaced the“At least two safety shutoff valves are proved closed…” requirement with “The number of safety shutoff valves required to close in8.8.1.2 and 8.8.1.3 will close…”. The Annex assumption condition of A.8.5.1.8(4)(d)(4) which refers to the original condition for“proved close” does not apply when TIA11-4 is incorporated. All use of “proven” for this annex example do not apply and should bedeleted. The Committee also corrected a typo in the Sample Problem - U.S. Customary Units of A.8.5.1.8(4)(d) Step 1 whichshould read: L900F=L482C. Additionally, the Committee corrected the application of the formula presented in the Sample Problem- U.S. Customary Units of A.8.5.1.8(4)(d) Step 5. Which should read: (5 scfh/500 scfh)(100%).

Copyright Assignment

I, Joseph Kozma III, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Joseph Kozma III, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 141: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 141/163

Public Input No. 56-NFPA 86-2012 [ New Section after A.8.5.2 ]

A.8.6.1

Use of a rotational switch is an acceptable means of proving operation of a fan where the impeller is not located in a dedicated housing(non-ducted). A Hall Effect sensor is one example of a device that can be used to prove fan shaft rotation.

Regular inspection of the impeller may be required to ensure original performance is maintained (i.e. blades still attached, angles onblades correct, etc.).

Statement of Problem and Substantiation for Public Input

See substantiation for Public Input #54 at Section 8.6.1.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 55-NFPA 86-2012 [Section No. 8.6.1] Asterisk added to indicated presence of new Annex content.

Public Input No. 54-NFPA 86-2012 [Section No. 8.6.1 [Excluding anySub-Sections]]

Revision to required text that motivated the need for newAnnex content.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:06:53 EDT 2012

Committee Statement

Resolution: FR-51-NFPA 86-2012

Statement: Annex material is added to help clarify acceptable methods for monitoring operation of non-ducted fans or fans not enclosed in adedicated housing.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 142: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 142/163

Public Input No. 46-NFPA 86-2012 [ Section No. A.8.7.5 ]

A.8.7.5

In industrial combustion applications with modulating flow control valves downstream of the combustion air blower, it is mostcommon to interlock the constant combustion air source pressure on single and multiburner systems to meet the requirementsof 8.7.3 and 8.7.5.

Because the combustion airflow is proved during each purge cycle along with the combustion air source pressure, the mostcommon convention is to prove the combustion air source pressure during burner operation following purge. In a multiburnersystem, the proof of combustion airflow during purge proves that any manual valves in the combustion air system are in anadequately open position. These manual air valves are provided for maintenance and combustion airflow balancing amongburners in a temperature control zone. In combustion air supply systems that use either an inlet damper or a speed control, thecombustion air pressure can fall below reliably repeatable levels with listed pressure switch interlocks at low fire. For thesesystems, the proof of minimum airflow can be a more reliable interlock.

A pressure switch on the inlet (suction) side of an Induced Draft (I.D.) fan can be used to prove that the minimum requiredsuction pressure is available.

For combustion systems that use high pressure gas/air to induce (inspirate) air locally at each burner, it is impractical tomonitor and prove the availability of combustion air.

For combustion systems that use Natural (stack) Draft to induce air into the burners or combustion chamber, it is impractical tomonitor and prove the availability of combustion air.

Statement of Problem and Substantiation for Public Input

Adds clarifying content to the Annex to help users differentiate between sources of combustion air for which minimum flow or pressure can be proven and sources for which it cannot, practically speaking.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 01:24:05 EDT 2012

Committee Statement

Resolution: FR-4-NFPA 86-2012

Statement: Adds clarifying content to the Annex to help users differentiate between sources of combustion air for which minimum flow orpressure can be proven and sources for which it cannot, practically speaking.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 91-NFPA 86-2012 [ Section No. A.8.8.1.3 ]

Page 143: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 143/163

A.8.8.1.3

Paragraph 8.8.1.3 addresses conditions under which only one safety shutoff valve is to close to isolate a burner from its fuelgas supply. Figure A.8.8.1.3 provides a summary of 8.8.1.3 in the form of a decision tree. See 8.5.1. 7 and 8.5.1.8 forguidance regarding conditions that are needed to allow that burner to be placed back in service. The requirements of 8.5.1.8might not allow a burner shut off by closing a single safety shutoff valve to be placed back in service without repeating a pre-ignition purge.

The requirements of 8.8.1.3 do not preclude opening of the safety shutoff valve located upstream of the individual burners usingsingle safety shutoff valves during the trial for ignition for the first burner being lighted.

Figure A.8.8.1.3 Safety Shutoff Decision Tree.

Statement of Problem and Substantiation for Public Input

8.5.1.7 is also a condition (repeating pre-purge) needed to allow a burner placed back into service. Both 8.5.1.7 and 8.5.1.8 work together and should be referenced together.

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Thu Jun 21 11:33:18 EDT 2012

Committee Statement

Resolution: FR-46-NFPA 86-2012

Statement: 8.5.1.7 is also a condition (repeating pre-purge) needed to allow a burner placed back into service. Both 8.5.1.7 and 8.5.1.8 worktogether and as such are referenced together.

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

Page 144: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 144/163

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 171-NFPA 86-2012 [ Section No. A.8.8.1.3(2) ]

A.8.8.1.3(2)

See A.8.8 5 .1.3 8 (3) for a sample calculation to demonstrate a method of determining the 25 percent LFL requirement.

Statement of Problem and Substantiation for Public Input

Incorrect section is referenced.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:17:31 EDT 2012

Committee Statement

Resolution: FR-96-NFPA 86-2012

Statement: The reference to A.8.8.1.3(3) does not exist. Section A.8.5.1.8(3) covers the case where the valve is wide open which is thesubject of 8.8.1.3(2).

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 145: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 145/163

Public Input No. 90-NFPA 86-2012 [ Section No. A.8.8.1.3(2) ]

A.8.8.1.3(2)

See A.8.8 5 .1.3 8 (3) for a sample calculation to demonstrate a method of determining the 25 percent LFL requirement.

Statement of Problem and Substantiation for Public Input

The reference to A.8.8.1.3(3) does not exist. Section A.8.5.1.8(3) covers the case where the valve is wide open which is the subject of 8.8.1.3(2).

Submitter Information Verification

Submitter Full Name:Dan Curry

Organization: Eclipse, Inc.

Submittal Date: Thu Jun 21 11:22:56 EDT 2012

Committee Statement

Resolution: FR-96-NFPA 86-2012

Statement: The reference to A.8.8.1.3(3) does not exist. Section A.8.5.1.8(3) covers the case where the valve is wide open which is thesubject of 8.8.1.3(2).

Copyright Assignment

I, Dan Curry, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both the

Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any publication

of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I have full

pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Dan Curry, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 146: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 146/163

Public Input No. 130-NFPA 86-2012 [ Section No. A.8.8.2.2 ]

A.8.8.2.2

An additional safety shutoff valve located to be common to the furnace system and proved closed and interlocked with the pre-ignitionpurge circuit can be used to meet the requirements of 8.8.2.2.

Additional Proposed Changes

File Name Description Approved

item 5.a. old 3.d NFPA 86 proposal for A.8.8.2.2 final draft 3tj120608.pdf

Word version of figure A.8.8.2.2

item 5.a. old 3.d NFPA 86 proposal for A.8.8.2.2 final draft 3tj120608.pdf

PDF version of A.8.8.2.2

Statement of Problem and Substantiation for Public Input

Modifies the drawing to be consistent with NFPA 86 (2011) symbols. Clarifies that 8.8.2.2 does not require more than one proved closed interlock for pre-purge in a multi-burner system.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary NFPA 86 Task Group on Introductory Chapters

Submittal Date: Fri Jun 22 10:19:18 EDT 2012

Committee Statement

Resolution: FR-35-NFPA 86-2012

Statement: Modifies the drawing to be consistent with NFPA 86 (2011) symbols. Clarifies that 8.8.2.2 does not require more than one provedclosed interlock for pre-purge in a multi-burner system. The Committee moved the proposed figure to annex to 8.5.1.2.(C)(2).Figure is in the attachment.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 147: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 147/163

Public Input No. 172-NFPA 86-2012 [ Section No. A.8.8.3.2 ]

A.8.8.3.2

An additional safety shutoff valve located to be common to the furnace system and proved closed and interlocked with the pre-ignition purge circuit can be used to meet the requirements of 8.8.2 3 .2.

Statement of Problem and Substantiation for Public Input

8.8.2.2 deals with gas valves.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: Karl Dungs, Inc.

Submittal Date: Tue Aug 07 12:18:37 EDT 2012

Committee Statement

Resolution: FR-49-NFPA 86-2012

Statement: 8.8.2.2 deals with gas valves, this annex is in reference to oil valves.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 148: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 148/163

Public Input No. 158-NFPA 86-2012 [ Section No. A.8.9 ]

A.8.9

A system designer may choose to use pressure switches in a pilot. However. gas pressure switches on a pilot may bedesirable. Below are list of design factors. or any combination thereof. that may need to be considered in whether or notswitches should be used.

1. If it's a continuous pilot. If a reliable pilot after light off is still a desirable part of the safety during operation of the burner, theswitches help prove the reliability of the pilot so that the gas pressure to the pilot is proven to be within designed parameters.

2. If the pilot burner capacity is above 400,000 btu/hr. Direct sparking a burner in excess of 400,000 btu/hr could introduceadded risks jf a delayed ignition occurs due to too much or too little gas pressure.

3. If the inlet pressure to the pilot regulator exceeds 1/2 PSI. The higher the pressure to the pilot burner, the greater the risk ofa problem due incorrect gas pressure. The failure or overloading of a pilot regulator may be a significantly higher risk when inletpressures to the pilot regulator exceed 1/2 PSI.

Statement of Problem and Substantiation for Public Input

The intent of this proposal is to provide some guidance on when high and low gas pressure switches for pilots are desirable.

Submitter Information Verification

Submitter Full Name:Kevin Carlisle

Organization: IHEA-Safety Codes and Standards Committee

Affilliation: Industrial Heating Equipment Association

Submittal Date: Mon Jul 02 11:22:47 EDT 2012

Committee Statement

Resolution: FR-108-NFPA 86-2012

Statement: The revision is to provide some guidance on when high and low gas pressure switches for pilots are desirable.

Copyright Assignment

I, Kevin Carlisle, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Kevin Carlisle, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 149: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 149/163

Public Input No. 48-NFPA 86-2012 [ Section No. A.8.11.2 ]

A.8.11.2

Atomizing media balancing orifices and balancing valves that can be securely locked in position by means of pinning or othertamper-resistant means are allowed.

Statement of Problem and Substantiation for Public Input

A.8.11.2 included a requirement which should be in the mandatory text. See related public comment that adds new requirement at 8.11.2.1.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 09:47:40 EDT 2012

Committee Statement

Resolution: FR-6-NFPA 86-2012

Statement: A.8.11.2 included a requirement which should be in the mandatory text. See related FR-7-NFPA 86-2012.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 150: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 150/163

Public Input No. 47-NFPA 86-2012 [ New Section after A.8.17.4 ]

A.8.17.8

An auxiliary contact in the Excess Temperature Limit Interlock device can be used as a 1400F Bypass Interlock providing therequirements of 8.17.2 are satisfied.

Statement of Problem and Substantiation for Public Input

Clarifies that the standard permits the 1400F Bypass Interlock function and the Excess Temperature Limit Interlock function may be incorporated into the same physical device.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering

Affilliation: Secretary of NFPA 86 Task Group on Introductory Chapters

Submittal Date: Thu Jun 07 01:39:05 EDT 2012

Committee Statement

Resolution: FR-5-NFPA 86-2012

Statement: Clarifies that the standard permits the 1400F (760C) Bypass Interlock function and the Excess Temperature Limit Interlockfunction can be incorporated into the same physical device.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 151: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 151/163

Public Input No. 166-NFPA 86-2012 [ New Section after A.9.1 ]

Add new text to read as follows: A.9.1.3 Where fire protection is determined to be necessary, a documented study should be conducted to determine the correctresponse to a fire to achieve a safe shutdown of the oven and an effective response of the fire protection system. Automatic interlocksshould be provided where actions do not require operator evaluation. Specific actions will depend on the oven design, type of fireprotection system, the characteristics of the combustible material(s), the source(s) of combustibles, the ability to isolate combustiblesources, and the effects of fresh air. Items to be considered should include but not be limited to: • The means for detecting a fire • Type(s) of fire protection system(s) effective at controlling the fire • Manual vs. automatic operation of the fire protection system • Shutting down the fuel supply (heating system) where such action does not increase the fire hazard • Stopping the conveyor system vs. diverting or stopping entering product and running conveyor at high speed to empty oven • Shutting down fans and closing dampers to block fresh air entry and contain the fire suppression medium vs. maintaining fans inoperations and dampers open to ensure an explosive atmosphere does not develop

Statement of Problem and Substantiation for Public Input

Existing requirements in Chapter 11 do not address what action should be taken in the event of a fire in an oven or furnace. While such actions are not "one-size-fits-all", where fire protection is needed it is important it be a coordinated system and, where manual actions are required, written procedures exist and operator training (addressed in Section 7.2) is done.

Submitter Information Verification

Submitter Full Name:Michael Polagye

Organization: FM Global

Submittal Date: Mon Jul 02 12:45:00 EDT 2012

Committee Statement

Resolution: FR-48-NFPA 86-2012

Statement: Existing requirements in Chapter 11 do not address what action should be taken in the event of a fire in an oven or furnace. Whilesuch actions are not "one-size-fits-all", where fire protection is needed it is important it be a coordinated system and, wheremanual actions are required, written procedures exist and operator training (addressed in Section 7.2) is done.

Copyright Assignment

I, Michael Polagye, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Michael Polagye, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 152: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 152/163

Public Input No. 128-NFPA 86-2012 [ New Section after A.10.6.2.2 ]

A.10.6.3.3

When exhaust is recycled, it can reduce the oxygen content supplied to the incinerator (reducing efficiency). This in turn will result inincreased levels of flammable vapors being exhausted into the oven(s) for heat recovery purposes.

The system design should have inherent physical characteristics to ensure that the ratio of heat recovery gases is limited to preventunsafe conditions or use a combination of telemetry controls and interlocks to prevent this from occuring.

Statement of Problem and Substantiation for Public Input

The new text for 10.6.3.3 requires explanatory text to assist the reader in understanding the purpose in providing "special precautions".

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 124-NFPA 86-2012 [Section No. 10.6.3.3] Annex material

Submitter Information Verification

Submitter Full Name:Thomas George

Organization: Tokio Marine Management, Inc.

Submittal Date: Fri Jun 22 09:55:04 EDT 2012

Committee Statement

Resolution: FR-88-NFPA 86-2012

Statement: The new text for 10.6.3.3 requires explanatory text to assist the reader in understanding the purpose in providing "specialprecautions". Annex material to FR-87-NFPA 86-2012.

Copyright Assignment

I, Thomas George, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including

both the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Thomas George, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 83-NFPA 86-2012 [ Section No. A.11.6.1.10 ]

Page 153: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 153/163

A.11.6.1.10

Ovens using a single fan for both recirculation and exhaust are currently in use and manufactured. These dual-purpose faninstallations have a long history of fire and explosion incidents. Figure A.11.6.1.10 shows examples of unacceptable safetyventilation systems.

Figure A.11.6.1.10 Unacceptable 10 Examples of Safety Ventilation Systems Using a Single Fan that can Result inShort-Circuited Airflows (Recirculation Combined with Spill Exhaust).

Statement of Problem and Substantiation for Public Input

Clarifies title of figure to identify the figure's content as "examples" and to inform readers that "short-circuited airflow" is the problem being addressed in the examples.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 78-NFPA 86-2012 [Section No. 11.6.1.10] Annex modification that is related to proposed change in mandatory text

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 16:14:02 EDT 2012

Committee Statement

Resolution: FR-86-NFPA 86-2012

Statement: Clarifies title of figure to identify the figure's content as "examples" and to inform readers that "short-circuited airflow" is theproblem being addressed in the examples.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 154: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 154/163

Public Input No. 58-NFPA 86-2012 [ New Section after A.11.6.1.15 ]

A.11.6.2.1

See A.8.6.1.

Statement of Problem and Substantiation for Public Input

Provides cross-reference to new annex material added at A.8.6.1 which may be instructive to users of Class A ovens.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 57-NFPA 86-2012 [Section No. 11.6.2.1]New Annex content added to be linked with new asterisk added at11.6.2.1

Public Input No. 56-NFPA 86-2012 [New Section afterA.8.5.2]

Cross referenced section cited in Public Input #58 (A.11.6.2.1)

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 14:22:16 EDT 2012

Committee Statement

Resolution: FR-53-NFPA 86-2012

Statement: Provides cross-reference to new annex material added at A.8.6.1 which will help the users of Class A ovens to clarify acceptablemethods for monitoring operation of non-ducted fans or fans not enclosed in a dedicated housing.

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 155: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 155/163

Public Input No. 86-NFPA 86-2012 [ Section No. A.11.6.1.15 ]

A.11.6.1.15

The vapors of most volatile solvents and thinners commonly used in finishing materials are heavier than air; consequently,bottom ventilation is of prime importance (see the tables in A.11.6.8.4). Liquefied petroleum gases are heavier than air, andother fuel gases are lighter than air. See NFPA 325, Guide to Fire Hazard Properties of Flammable Liquids, Gases, andVolatile Solids. (Note: Although NFPA 325 has been officially withdrawn from the National Fire Codes, the information is stillavailable in NFPA's Fire Protection Guide to Hazardous Materials.)

In areas outside the oven where volatiles are given off by material prior to entering the oven, adequate provisions should be madeto exhaust vapors to the atmosphere in accordance with applicable local, state, and federal regulations.

See Figure A.11.6.1.15.

Additional Proposed Changes

File Name Description Approved

Example 9 - new figure forA.11.6.1.15.png

New Figure A.11.6.1.15 - 86TC to consider if this is the right place for this figure or if other figures are preferred

Statement of Problem and Substantiation for Public Input

New figure helps add clarity to flow arrangements that may introduce safety concerns related to poor ventilation.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 83-NFPA 86-2012 [Section No. A.11.6.1.10] One of several related public inputs addressing safety ventilation.

Submitter Information Verification

Submitter Full Name:Richard Martin

Organization: Martin Thermal Engineering, Inc.

Affilliation: Secretary of NFPA 86 Task Group on Class A Ovens

Submittal Date: Tue Jun 19 16:59:34 EDT 2012

Committee Statement

Resolution: The submitter's recommendation is redundant and the Committee added similar material in FR-(DEREK FIND THE REFERENCE).

Copyright Assignment

I, Richard Martin, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Richard Martin, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 156: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 156/163

Public Input No. 39-NFPA 86-2012 [ New Section after A.13.5.7.4(B) ]

A13.5.7.4 (B)

The indication of flow is intended to be provided by a device that will indicate flow any time a flow is occurringincluding during power outage. A mechanical device that indicates the flow rate without using any source of powerexcept the physical flow of the inert purge gas meets this requirement. The uncertainty of a reliable backup powersupply, such as back-up batteries or an uninterruptible power supply, during a primary power interruption precludes theuse of "electronic" monitoring of flow.

Statement of Problem and Substantiation for Public Input

The rewording in the annex material emphasizes the requirement of monitoring emergency inert purge flow is to be by "mechanical" means, not "electronic" means.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Wed May 02 15:00:57 EDT 2012

Committee Statement

Resolution: FR-119-NFPA 86-2012

Statement: This annex material was from the TIA 11-2, see FR-28-NFPA 86-2012 for the requirements of the TIA. The Committee furtherclarified to emphasize the requirement of monitoring emergency inert purge flow is to be by "mechanical" means and not"electronic".

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Mark Stender (Surface Combustion) as part of the Class C Task Group.

Page 157: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 157/163

Public Input No. 73-NFPA 86-2012 [ New Section after A.13.5.8.11 ]

A.13.5.8.12(A)

This paragraph addresses excess flow in the equipment piping for an individual furnace. This would involve a device atthe special atmosphere control panel, such as an electronic sensor, along with logic to close an automatic shutoff valveupon detection of excess flow. This paragraph does not preclude operational high flow set points at thresholds belowthe shutoff excess flow set point. The operational high flow set points can be provided to initiate alarms that promptoperator intervention to restore appropriate flow levels before the shutoff excess flow level is reached.

Statement of Problem and Substantiation for Public Input

Relocated annex material with text.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:30:11 EDT 2012

Committee Statement

Resolution: FR-77-NFPA 86-2012

Statement: Relocated annex material with text.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 158: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 158/163

Public Input No. 36-NFPA 86-2012 [ New Section after A.13.5.11.1(E) ]

A 13.5.11.1 (F)

The use of plant air with reducing regulators is prohibited. Plant airlines may become slugged with water passing intothe heated furnace resulting in abnormally high furnace pressures. Plant airlines may experience regulator failuresresulting in high-pressure air admission into furnace that contains a flammable atmosphere.

Statement of Problem and Substantiation for Public Input

Plant airline failures result in unsafe operating conditions.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 10:05:11 EDT 2012

Committee Statement

Resolution: FR-111-NFPA 86-2012

Statement: Plant air line failures result in unsafe operating conditions.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil (Caterpillar) Class C Task Group.

Page 159: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 159/163

Public Input No. 76-NFPA 86-2012 [ New Section after A.13.5.11.1(E) ]

A.13.5.11.1(F)

The use of plant air with reducing regulators is prohibited. Often plant airlines become slugged with water with the water passing intothe heated furnace resulting in abnormally high furnace pressures. Often plant airlines experience regulator failures resulting in highpressure air admission into furnaces that contain a flammable atmosphere.

Statement of Problem and Substantiation for Public Input

Plant airline failures result in unsafe operating conditions.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:43:30 EDT 2012

Committee Statement

Resolution: FR-111-NFPA 86-2012

Statement: Plant air line failures result in unsafe operating conditions.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Public Input No. 38-NFPA 86-2012 [ Section No. A.13.5.11.10 ]

Page 160: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 160/163

A.13.5.11.10

See Figure A.13.5.11.10.

Figure A.13.5.11.10 Examples of Special Atmosphere Equipment Piping.

(Insert New Figure)

Additional Proposed Changes

File Name Description Approved

86FCfA-13-5-11-10 REV.B.pdf

Updated figure for A 13.5.11.10

Statement of Problem and Substantiation for Public Input

Revising annex material to match the text that it supports.

Flow meters changed to flow switches.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 10:54:36 EDT 2012

Committee Statement

Resolution: FR-112-NFPA 86-2012

Statement: Revising annex material to match the text that it supports. Flow meters changed to flow switches.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Figure provided by Surface Combustion in Class C Task Group. (Mark Stender and Keith Hancock)

Page 161: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 161/163

Public Input No. 35-NFPA 86-2012 [ New Section after A.13.5.11.10.4(C) ]

A13.5.11.10.8

Atmosphere imingement on the temperature control thermocouple can result in overheating of the furnace or erroneouscontrol readings on the over temperature thermocouple.

Statement of Problem and Substantiation for Public Input

Atmosphere impingement on the temperature control thermocouple can result in overheating of the furnace: impingement on the over temperature thermocouple can cause erroneous control readings.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Affilliation: NFPA 86 Class C Task Group

Submittal Date: Fri Apr 27 09:55:01 EDT 2012

Committee Statement

Resolution: FR-73-NFPA 86-2012

Statement: Atmosphere impingement on the temperature control thermocouple can result in overheating of the furnace: impingement on theover temperature thermocouple can cause erroneous control readings.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. Except to the extent that I may lack authority to make an

assignment of content identif ied above, I hereby w arrant that I am the author of this Public Input and that I have full pow er and authority to enter into this copyright

assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Origin (from sources other than the submitter)

Content provided by Gary Keil ( Caterpillar) Class C Task Group.

Page 162: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 162/163

Public Input No. 72-NFPA 86-2012 [ Section No. A.13.5.11.11.11(A) ]

A.13.5.11.11.11(A)

This paragraph addresses excess flow in the equipment piping for an individual furnace. This would involve a device at thespecial atmosphere control panel, such as an electronic sensor, along with logic to close an automatic shutoff valve upondetection of excess flow. This paragraph does not preclude operational high flow set points at thresholds below the shutoffexcess flow set point. The operational high flow set points can be provided to initiate alarms that prompt operator intervention torestore appropriate flow levels before the shutoff excess flow level is reached.

Statement of Problem and Substantiation for Public Input

Relocated to A13.5.8.12.

Submitter Information Verification

Submitter Full Name:Fausta Lyons

Organization: Caterpillar Inc

Submittal Date: Tue Jun 19 15:28:09 EDT 2012

Committee Statement

Resolution: FR-113-NFPA 86-2012

Statement: Relocated to A13.5.8.12, see FR-60-NFPA 86-2012.

Copyright Assignment

I, Fausta Lyons, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am Fausta Lyons, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature

Page 163: Public Input No. 8-NFPA 86-2012 [ Chapter NFPA ] Statement

1/18/13 TerraView™

submittals.nfpa.org/TerraViewWeb/ViewerPage.jsp 163/163

Public Input No. 25-NFPA 86-2012 [ Section No. M.1.2.12 ]

M.1.2.12 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

Bulletin of Research No. 43, “The Lower Limit of Flammability and the Autogenous Ignition Temperature of Certain CommonSolvent Vapors Encountered in Ovens,” January 1950.

ANSI/UL 353, Standard for Limit Controls, 1994, revised 2001 2011 .

UL 429, Standard for Electrically Operated Valves for Gas Appliances, 2006.

Statement of Problem and Substantiation for Public Input

Update referenced standard to most recent edition as indicated.

Submitter Information Verification

Submitter Full Name:John Bender

Organization: Underwriters Laboratories Inc.

Submittal Date: Wed Apr 18 13:31:54 EDT 2012

Committee Statement

Resolution: FR-41-NFPA 86-2012

Statement: Update referenced standard to most recent edition as indicated.

Copyright Assignment

I, John Bender, hereby irrevocably grant and assign to the National Fire Protection Association (NFPA) all and full rights in copyright in this Public Input (including both

the Proposed Change and the Statement of Problem and Substantiation). I understand and intend that I acquire no rights, including rights as a joint author, in any

publication of the NFPA in w hich this Public Input in this or another similar or derivative form is used. I hereby w arrant that I am the author of this Public Input and that I

have full pow er and authority to enter into this copyright assignment.

By checking this box I aff irm that I am John Bender, and I agree to be legally bound by the above Copyright Assignment and the terms and conditions contained

therein. I understand and intend that, by checking this box, I am creating an electronic signature that w ill, upon my submission of this form, have the same legal force

and effect as a handw ritten signature