HEAD CALCULATION FOR CHILLED WATER PUMP
PROJECT AIRPORT SERVICE BUILDING
CHILLED WATER PIPES
RMT FT
125 53.5 175.48 2.5 4.387
9 8.2 73.8 2.5 1.845
2 12 24 2.5 0.6
RMT FT
100 38 124.64 2.2 2.74208
3 6.7 20.1 2.2 0.4422
2 9 18 2.2 0.396
RMT FT
80 9 29.52 2.1 0.61992
0 6.7 0 2.1 0
RMT FT
40 9 29.52 1.4 0.41328
0 5.9 0 1.4 0
RMT FT
LOSS IN PUMP REDUCER 0.29 FT
Pipe dia(mm)
Pressure Drop
(ft/100Ft)
total drop(ft)
No of bend (ELF-8.2FT)No of Tees(ELF-12FT)
Pipe dia(mm)
Pressure Drop
(ft/100Ft)
total drop(ft)
No of bend(ELF-6.7FT)No of Tees(ELF-9FT)
Pipe dia(mm)
Pressure Drop
(ft/100Ft)
total drop(ft)
No of bend(ELF-5.9FT)
Pipe dia(mm)
Pressure Drop
(ft/100Ft)
total drop(ft)
No of bend(ELF-5.9FT)
Pipe dia(mm)
Pressure Drop
(ft/100Ft)
total drop(ft)
IN-LINE REDUCER LOSS(EXPANSION) 0.29 FT
IN-LINE REDUCER LOSS(CONTRACTION) 0.2 FT
LOSS IN FLOW METER FT
Total Pressure drop in pipes (feet) 12.23
CHILLED WATER VALVESPUMPS
QTY
NRV 100 40 1 2.2 0.88
balancing valve 100 58 0 2.2 0
Y strainer 100 60 1 2.2 1.32
butterfly valve 100 4.5 2 2.2 0.198
CHILLER
QTY
MBY 100 4.5 1 2.2 0.099
balancing valve 100 58 1 2.2 1.276
Y strainer 100 60 1 2.2 1.32
butterfly valve 100 4.5 1 2.2 0.099
AHU
QTY
50 1 13.12 13.12
balancing valve 50 30 0 2.2 0
Y strainer 50 27 1 3.6 0.972
butterfly valve 50 2.3 2 3.6 0.1656
Total Pressure drop in Valves 19.4 feetTotal Pressure drop in Pipe length+Fittings+Valves+Flow meter 31.68 feet
Total
11.59 2.794 0.34 14.26 28.98 MTR
Dia(mm)
Equ.leng-th
in Feet
Pressure Drop
(ft/100Ft)
Total Drop(ft)
Dia(mm)
Equ.leng-th
in Feet
Pressure Drop
(ft/100Ft)
Total Drop(ft)
Dia(mm)
Equ.leng-th
in Feet
Pressure Drop
(ft/100Ft)
Total Drop(ft)
P BALANCING + 2WAY
Pipes, Bend,valve Loss(mt)
CHILLER(mt)
AIR SEPARATOR(
mt)AHU(mt)