purmo technical catalogue under floor heating pipe system ufh hks 08 2011 ang
TRANSCRIPT
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
1/36
POLAND2
011
Technical catalgueflr heating
and pipe systems
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
2/36
2
floor heating General inrmatin
In last years floor heating has become verypopular solution. Many factors have causedit. In opposition to the traditional solu-tions, floor heating heats uniformly thewhole floor area and assures good thermalcomfort.
Floor heating systems work with lowparameters, which limits energy consump-tion. Heat emission through the wholefloor area causes subjective feeling of high-er temperature in the room. It allows todecrease temperature by 1-2 C, saving from6 to 12% of energy.
Low temperature of water in the systemgives wide possibilities of unconventionalheat sources use, as solar energy, heatpumps, waste heat. Moreover, floor heat-ing allows complete freedom of interiorarrangement, gives unlimited architecturalpossibilities and rooms partitioning.
Heating pipesspacing
[mm]
Heating pipesconsumption
[m/m]
Clipsconsumption
[pcs./m]
Edge tapeconsumption
[m/m]
Concrete addi-tive consump-
tion* [l/m]
System elements NOPPJET
Connecting element forNoppjet boards in expan-
sion joint location [pcs./m]
Clipping element forNoppjet boards
[pcs./m]
Skew pipe fixingelement[pcs./m]
300 3.3 7
1.1 0.1 0.1 0.06 0.
50 4.0 8
00 5.0 10
150 6.5 14
100 9.5 0
* - For floor thickness 6.5 cm
Properties of PE-X pipe:- maximum operational parameters: temperature 90 C, pressure 6 bar,- high thermal conductivity coefficient =0.35 W/(mK),- linear expansion coefficient k=0.15 mm/(mK),- low modulus of elasticity E (550 N/mm),- low pressure loss absolute roughness k=0.007 mm,- minimum bending radius r=5 x d
z,
- completely eliminated oxygen diffusion,- complete integration of oxygen barrier with PE-X pipe (identical thermal expansion
coefficient of pipe and anti-diffusion barrier)
Expansion joint
Expansion joint use conditionsJointless floor thermal expansion factor is 0.01 mm/(mK). It means that 8 m long screed due toheating from 10 C to 40 C extends by 3 mm. This extension must be taken over by edge tape.
If the room has non-typical shape or is too big, the heating screed must be additionally separatedwith use of expansion joint profile with insulation tape.
Expansion joint profile must be used when:- screed area exceeds 40 m,
- one of screed edges is longer than 8 m,- screed edges lengths ratio is higher than :1,- room has complicated shape, e.g. L, T, C.
Caution: Expansion joint profile must be installed in each door-way. No expansion joint in abovecases may lead to floor or pipes destruction.
Spiral Spiral with integratededge (wall) zone
Loopformingmethods
Meanders Double meanders
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
3/36
loor heating
3
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
PEX pipes with anti-diffusion layer EVOH
Heating pipe PE-X rm crsslinked plyethylenewith anti-difusin barrier, maximum peratinalparameters: temperature C, pressure bar
16x216x216x2
17x217x217x220x2
20x220x2
25x2.3
UFH 0054002UFH 0054003UFH 0054004
UFH 0054000UFH 0054009UFH 0054026UFH 0054001
UFH 0054023UFH 0054027IND 0050000
FBAXB5C1620120P0FBAXB5C1620240P0FBAXB5C1620600P0
FBAXB5C1720120P0FBAXB5C1720240P0FBAXB5C1720600P0FBAXB5C2020120P0
FBAXB5C2020240P0FBAXB5C2020500P0FBAXA3C252330000
cartn a 120 mcartn a 240 mcartn a 600 m
cartn a 120 mcartn a 240 mcartn a 600 mcartn a 120 m
cartn a 240 mcartn a 500 mcartn a 300 m
m
Heating pipe as abve, but in plyethylene prtectivepipe - red
Heating pipe as abve, but in plyethylene prtective
pipe - blue
16x2
16x2
UFH 0054040
UFH 0054041
FBAXA3R162007500
FBAXA3B162007500
75 m/cil
75 m/cil
m
m
Protective polyethylene pipe - red
Protective polyethylene pipe - blue
19/24
19/24
UFH 0054051
UFH 0054052
FBAPM1R192410000
FBAPM1B192410000
100 m/cil
100 m/cil
m
m
PE-RT pipes with anti-diffusion layer EVOH
Heating pipe PE-RT or floor heating rm hightemperature resistant plyethylene with anti-
difusin layer, maximum peratinal parameters:temperature C,pressure bar
17x217x2
UFH 0054054UFH 0054055
FBAPT3C1720240P0FBAPT3C1720600P0
cartn a 240 mcartn a 600 m
m
Multilayer pipes PE-RT/Al/PE-RT
Multilayer heating pipe PE-RT/Al/PE-RT profitherm Alr flr heating and lw temperature radiatrs
made rm tw layers high temperature resistantplyethylene and stabilizing aluminium layerbetween, assuring abslute anti-difusin tightness.Operating parameters:
temperature C, pressure bar.
16x216x2
CSY 0052994CSY 0052995
FBDPTAC1620240P0FBDPTAC1620600P0
240 m/cil600 m/cil
m
Insulations
Rlljetr lads up t kg/m
Foamed polystyrene board EPS 80 cvered with filmwith anchring mesh and scale- mm thick- mm thick
1000x150001000x12000
UFH 0054241UFH 0054242
FBMCA201001500P0FBMCA251001200P0
15 m12 m
mm
Rlljetr lads up t kg/m
Foamed polystyrene board EPS 100-038 cvered withfilm with anchring mesh and scale- mm thick- mm thick
1000x120001000x9000
UFH 0050242UFH 0050248
FBMC0251001200P0FBMC0351000900P0
12 m9 m
mm
System elements
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
4/36
loor heating
4
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Insulations
Rlljetr lads up t kg/m
Foamed polystyrene board EPST 5.0 - 2628 dB(acustic), cvered with film with anchring meshand scale- / mm thick
- / mm thick
1000x12000
1000x9000
UFH 0054212
UFH 0054218
FBMC4271001200P0
FBMC4381000900P0
12 m
9 mm
m
Rlljetr lads up t kg/m
Foamed polystyrene board EPS 200 - 0.36 cveredwith film with anchring mesh and scale- mm thick- mm thick
1000x120001000x10000
UFH 0050252UFH 0050254
FBMC1251001200P0FBMC1301001000P0
12 m10 m
mm
Flatjet
r lads up t kg/m
Foamed polystyrene board EPS 100 038 cveredwith film with anchring mesh and scale- mm thick
1000x2000 UFH 0050350 FBMF0501000200P0 10 m m
Faltjetr lads up t kg/m, resistant t slvents
Polyurethane oam board cvered with film with
anchring mesh and scale, st plyethylene amlayer rm belw ( mm)- mm thick
1250x1600 UFH 0050191 FBMF674125016000 2 m m
Recommended insulation layers thickness
Case RD [m2K/ W] T hickn ess [mm] No. of layers In su lation [ mm]
A 0.75 35 1 Rolljet 35 35
31 2 Noppjet 11F. polyst. EPS 100-038
1120
B 1.25 55 2 Rolljet 25F. polyst. EPS 100-038
2530
51 2 Noppjet 11F. polyst. EPS 100-038
1140
C 2.62 74 1 Faltjet 74 74
105 2 Rolljet 25F. polyst. EPS 100-038
2580
101 2 Noppjet 11F. polyst. EPS 100-038
1190
D 2.86 74 1 Faltjet 74 74
115 2 Rolljet 25F. polyst. EPS 100-038
2590
111 2 Noppjet 11F. polyst. EPS 100-038
11100
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
5/36
loor heating
5
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Insulations
Nppjet amed plystyrene bard EPS -with tabs r pipes -
r lads up t kg/m- mm thick
1200x800 UFH 0050201 FBLD421158012000 9.6 m m
Cnnecting element r Nppjet bards in expansinjint lcatin (n insulatin)
1250x200 UFH 0050199 FBLADOO1F5019900 10 pcs. pcs.
Clipping element r Nppjet bards (n insulatin)
1200x100 UFH 0050195 FBLACON1F5019500 10 pcs. pcs.
Skew pipe fixing element
100x50 UFH 0050198 FBLADIAGF5019800 10 pcs. pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
6/36
loor heating
6
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Expansion joints elements
Insulating edge tape with film
8x160 UFH 0050220 FBAOTHEFB50220P0 30 m m
Insulation tape r expansin jint prfile
8x100x2000 UFH 0050077 FBSOTHEFB50077P0 2 m m
Accessories
Clips in magazines, pcs. each
UFH 0050227 FBMACLI120P300P0 cartn a 300 pcs. pcs.
Railjet - strip r pipe installatin, clip cnnected, rpipes -
200x40 UFH 0050229 FA9IP08114170000 100 pcs. pcs.
Additive (plasticizer) or jointless floor, suitable or all floor types, ce-ment and anhidrite, reduces water consumption, improves thermalconductivity, consumption . l/m or mm thick floor(. . l/m o mix). Recipe example: floor mix is prepared in con-crete mixer, dosing components in the following sequence:
1. shovels o gravel sand with graining - mm, - m m orfloor thickness higher than cm (approx. l) 2. kg o cement3. l o water 4. . l o admixture 5. - shovels o gravelsand (approx. l) 6. complete with water to appropriate consist-ence (approx. - l o water)
UFH 0050075UFH 0050075P
FBSADDIFB5007500FBSADDIFB0075PP0
20 l5 l
liter
Adhesive tape r cnnecting jints hrizntalthermal insulatin
75 UFH 0050225 FBAOTHEFB0225PP0 66 m pcs.
Plastic expansion joint profile
2000 UFH 0050076 FBSOTHEFB5007600 2 m m
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
7/36
loor heating
7
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Accessories
Protective pipe - cm lng
400 UFH 0050078 FBSOTHEFB5007800 individually pcs.
Pipe guide at manild - elbw
14-1720
UFH 0050070UFH 0050071
FBWAMPP017014000FBWAMPP020018000
individually pcs.
Tools
Taker - tl r clips striking
U FH 0 050216 FBMATOOL20 P21 6P0 individually pcs.
Metal uncoiler r adhesive tape
U FH 0 050230 FBMAOTHE00P2 3000 individually pcs.
Metal collapsible uncoiler r pipes in cils - m
500x300x200 UFH 0050018 FBSOTHEFB50018P0 individually pcs.
Uncoiler with carriage r pipes in cils - m
UFH 0050017 FAZTT00FB50017P0 individually pcs.
Installation pressure test pump
CSY 0053918 FAZTT00FB53918P0 individually pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
8/36
loor heating
8
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Brass fittings
Uni male coupling with /" nut
16x2 by CSY 0053020 FAZ1S12M16A12FP0 10 pcs. pcs.
Nickel plated screw coupling with /" nut(pipe - manild)
14x2 by 16x2 by 17x2 by
20x2 by
CSY 0053032CSY 0053033UFH 0050114
CSY 0053035
FAZ1S34C14A000P0FAZ1S34C16A000P0
FBWAMFNE17E000P0
FAZ1S34C20A000P0
10 pcs.10 pcs.10 pcs.
10 pcs.
pcs.
Nickel plated screw coupling double with /" nuts(pipe - pipe)
Screw coupling double with /" nuts (pipe - pipe)
16x2 - 16x217x2 - 17x2
20x2 - 20x2
25x2.3 - 25x2.3
CSY 0053040UFH 0050010
CSY 0053042
IND 0050010
FAZ1C34C16A000P0FAZ1C34C17S000P0
FAZ1C34C20A000P0
FAZ0C25S34M25S00
10 pcs.10 pcs.10 pcs.
individually
pcs.
Nickel plated male screw coupling with /" nut and-ring seal (pipe - radiatr)
16x2 by 17x2 by 20x2 by
CSY 0053023UFH 0050082CSY 0053025
FAZ1S12M16A34FP0FAZ1S12M17S000P0FAZ1S12M20A000P0
10 pcs.10 pcs.10 pcs.
pcs.
Male screw coupling with 3/4" nut
25x2.3 by IND 0050011 FAZ0C34M25S00000 individually pcs.
Coupling double (pipe - pipe)
16x2 - 16x217x2 - 17x220x2 - 20x2
CSY 0053241UFH 0050049CSY 0053243
FAZ4C16A16A000P0FAZ5C17S17S00000FAZ4C20A20A000P0
10 pcs.
10 pcs.10 pcs.
pcs.
pcs.pcs.
Stainless steel sleeve with cntrl ring
1617
20
CSY 0053291UFH 0050051
CSY 0053293
FAZTA00COLLA16P0FBSOTHEFB50051P0
FAZTA00COLLA20P0
10 pcs.individually
10 pcs.
pcs.pcs.pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
9/36
loor heating
9
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Brass fittings
O-ring seal
161720
CSY 0053295UFH 0050052CSY 0053297
FAZTA00ORING16P0FAZTA00FB50052P0FAZTA00ORING20P0
10 pcs.individually
10 pcs.
pcs.pcs.pcs.
Pressing jaws
Cautin: Other jaws dimensins in pipe systemPurm HKS 16
1720
CSY 0053133UFH 0050050CSY 0053135
FAZTTPJFB16000P0FAZTTPJFB50050P0FAZTTPJFB20000P0
individually
individuallyindividually
pcs.
pcs.pcs.
Manifolds with valve insertsassembled, equipped with vibration damping pads brackets, checked for 8 bar pressure, in carton package
1 - M 1 brass (M 63)
kit cntents:- utlets M ,- valve inserts r actuatrs
assembling,- flw adjustment valves,
- vent and drain grups
2 circuits
3 circuits4 circuits5 circuits6 circuits7 circuits
8 circuits9 circuits
10 circuits11 circuits
12 circuits
165x293x77
220x293x77275x293x77330x293x77385x293x77440x293x77
495x293x77550x293x77605x293x77660x293x77
715x293x77
UFH 0050402
UFH 0050403UFH 0050404UFH 0050405UFH 0050406UFH 0050407
UFH 0050408UFH 0050409UFH 0050410UFH 0050411
UFH 0050412
FBWMRBS0240522P0
FBWMRBS0340522P0FBWMRBS0440522P0FBWMRBS0540522P0FBWMRBS0640522P0FBWMRBS0740522P0
FBWMRBS0840522P0FBWMRBS0940522P0FBWMRBS1040522P0FBWMRBS1140522P0
FBWMRBS1240522P0
individually set
1 - M 1 rom stainless steel
kit cntents:- utlets M ,- valve inserts r actuatrs
assembling,- flw adjustment valves,- vent and drain grups
2 circuits3 circuits4 circuits5 circuits
6 circuits7 circuits8 circuits9 circuits
10 circuits11 circuits12 circuits
190x330x86245x330x86300x330x86355x330x86
410x330x86465x330x86520x330x86575x330x86
630x330x86685x330x86740x330x86
UFH50402VAUFH50403VAUFH50404VAUFH50405VA
UFH50406VAUFH50407VAUFH50408VAUFH50409VA
UFH50410VAUFH50411VAUFH50412VA
FBWMRSS024052200FBWMRSS034052200FBWMRSS044052200FBWMRSS054052200
FBWMRSS064052200FBWMRSS074052200FBWMRSS084052200FBWMRSS094052200
FBWMRSS104052200FBWMRSS114052200FBWMRSS124052200
individually set
Manifolds with valve inserts and flow indicators
assembled, equipped with vibration damping pads brackets, checked for 8 bar pressure, in carton package
1 - M 1 rom stainless steel
kit cntents:
- flwmeters,- utlets M ,- valve inserts r actuatrs
assembling,
- flw adjustment valves,- vent and drain grups
2 circuits3 circuits
4 circuits5 circuits6 circuits7 circuits
8 circuits9 circuits
10 circuits11 circuits12 circuits
190x330x86245x330x86
300x330x86355x330x86410x330x86465x330x86
520x330x86575x330x86630x330x86685x330x86740x330x86
UFH50302VAUFH50303VA
UFH50304VAUFH50305VAUFH50306VAUFH50307VA
UFH50308VAUFH50309VAUFH50310VAUFH50311VAUFH50312VA
FBWMRST024052200FBWMRST034052200
FBWMRST044052200FBWMRST054052200FBWMRST064052200FBWMRST074052200
FBWMRST084052200FBWMRST094052200FBWMRST104052200FBWMRST114052200FBWMRST124052200
individually set
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
10/36
loor heating
10
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Brass manifolds 5/4" M
5/4" - M/F 1" brass (M 63)kit contents:- cnnectin pipes with clsing valves
utlets with clsing valves M - flw adjustment valves with
flwmeters- drain valves and air vent set
2 circuits3 circuits
4 circuits5 circuits6 circuits7 circuits
8 circuits9 circuits
10 circuits11 circuits12 circuits
160x365x93210x365x93
260x365x93310x365x93360x365x93410x365x93
460x365x93510x365x93560x365x93610x365x93660x365x93
UFH 0050802UFH 0050803
UFH 0050804UFH 0050805UFH 0050806UFH 0050807
UFH 0050808UFH 0050809UFH 0050810UFH 0050811UFH 0050812
FBWMRBO0250422P0FBWMRBO0350422P0
FBWMRBO0450422P0FBWMRBO0550422P0FBWMRBO0650422P0FBWMRBO0750422P0
FBWMRBO0850422P0FBWMRBO0950422P0FBWMRBO1050422P0FBWMRBO1150422P0FBWMRBO1250422P0
individually set
Ball valves for manifolds
Ball valve with hal cnnectr r manilds series: - M brass (M ) or floor heating - M rom stainless steel or floor heating
- M brass (M ) or heating and tap water
Ball valve with hal cnnectr / r manildsseries - pcs./manild
F 1 - F 1
F 5/4 - F 1
UFH 0050420VA
UFH 0050120
FBWAMVNT44F440P0
FBWAMVNT54F440P0
2 pcs.
2 pcs.
pcs.
pcs.
Automatic elements mixing systems
Mixing valve block r systems up t kW, -waymixing valve, pump U-, adjustable bypass, saetyvalve, tw thermmeters, cperates with cntrllersSM
UFH 0050085 FAW3IHOOB25X44P0 individually pcs.
Manifold
Mixing valve block
Actuator
F "
F "
Heat sourcewith requiredequipment
Contact temp. sensor
External temp. sensor
Weather controllerDIAGRAM
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
11/36
loor heating
11
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Automatic elements mixing systems
Insulating housing r abve mixing blck
UFH 0050086 FBSOTHEINSUBOXP0 individually pcs.
SM4 controller or mixing blockMaximum trque Nm, pening time s/
UFH 0054084 FAW3MAO0P54084P0 individually pcs.
Weather controller or mixing block cntrls ne circuit with mixer,des nt interere with biler peratin, kit cntents: external
temperature sensr, supply temperature cntact sensr, cntrllerinstallatin strip n the wall, cperates with cntrllers SM
UFH 0054200 FAW3MEC0P54200P0 individually set
TempCo fix mixing setTempCo fix eco mixing setPurm mixing sets TempC fix and TempC fix ec fits M " mani-
lds. Assure a prper parameters flr heating supply watertemperature (e.g. / oC). Purm mixing sets are assembliedbere being packed and cntain:- -gears circulatin pump Grunds UPS / ( TempC fix)- highly e cient pump Grunds Alpha L / (TempC fix ec)
- -way mixing valve, check valve and flw adjustment valve- thermstatic head with sensr - oC- thermmeter
UFH 0051060UFH 0051061
FAW3MTF3T5106000FAW3MTFVT5106100
individuallyindividually
setset
210mm
ca. 225 mm
System elements1. flr heating/cling supply (F 1")
2. flr heating/cling return (F 1")3. primary supply (M 1")4. primary return (M 1")5. circulatin pump6. thermstatic head with blcade7. 3-way mixing valve8. check valce9. supply temperature thermmeter10. supply temperature limiter11. supply temperature sensr12. flw adjustment valve13. ball valve F 1" with mving nut
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
12/36
loor heating
12
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Automatic elements mixing systems
Small mixing set with pump and thermostatic head r direct cn-nectin ne r tw* heating lps flr heating t radiatrssystem (des nt require manild)
kit cntents:- pump- flw adjustment valve- thermstatic head with remte sensr
- air vent
* - use branchings t cnnect lps
UFH 0050470 FAW3MTF1P047E0P0 individually set
Small mixing set with pump and actuator 230 V r direct cnnec-tin ne r tw* flr heating lps within radiatrs system(des nt require manild)kit cntents:- pump
- flw adjustment valve- actuatr V- air vent
* - use branchings t cnnect lps
** - cperates with thermstats V (e.g. TempC Basic, Cmrt, Digital -
thermstat is nt included in a set)
UFH 0050470E FAW3MTF1P047E000 individually set
Branching for small mixing set, allows or connecting floor heating loops (use branchings to connect loops)
cnnectin r pipes , and mm UFH 0050473 FAW3MAO0P50473P0 individually pcs.
TempCo VT setAbility t cnnect radiatr (e.g. bathrm) with flr heating upt m.- radiatr and flr heating adjustment with ne thermstatic
head
- flr heating supply temperature limiter up t C- by-pass which clses flr heating circuit when supply tempera-
ture crsses C- ne hydraulic presetting r radiatr and flr heating tgather
TempC VT cnnectin set whiteTempC VT cnnectin set chrmeTempC VT head whiteTempC VT head chrme
UFH 0051080UFH 0051081
FBSOTHEFB51080PR9016
FBSOTHEFB51081PVCHRO
FBSCONTFB5108300
FBSCONTFB510840VCHRO
individuallyindividuallyindividually
individually
pcs.pcs.pcs.pcs.
Z - supplyP - returnG - radiatrOP - flr heatingBiler - biler circuit
STW - temperature limiter
thermstatic valve BilerBiler
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
13/36
loor heating
13
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Wire automatic elements
TempCo Basic thermostat 230 VElectrnic regulatrAir temperature sensr
Flush munting versinOnly mm thickMechanical temperature limit min and maxLED dide
Sensr accuracy . C
UFH 0051000 FAW3RWRFENCH0100 individually pcs.
TempCo Comort thermostat 230 VTempCo Comort thermostat 24 VElectrnic PI regulatr (hysteresis r PWM) Air temperature sensr,Flush munting versin Only mm thick Mechanical tem-
perature limit min and max Night reductin Anti-reeze r withprgrammer Wrks in heating r cling mde LED dide indicating wrking mde (red = heating; blue = cling) Sensr accurac . C
UFH 0051001UFH 0051021
FAW3RWRFEFNC0100FAW0RWRFEFNC0100
individuallyindividually
pcs.pcs.
TempCo Digital thermostat 230 VTempCo Digital thermostat 24 VElectrnic PI regulatr (hysteresis r PWM) LCD display with am-ber backlight Flush munting versin Wrks in heating r cl-ing mde Air sensr, ptinal flr temperature sensr waysr regulatin: rm temperature regulatin, rm temperature
regulatin and flr temperature limit (min/max) Flr tempera-ture regulatin Sensr accuracy . C
UFH 0051002
UFH 0051022
FAW3RWRFDVNC0300
FAW0RWRFDVNC0300
individuallyindividually
pcs.pcs.
TempCo Central thermostat 230 V
TempCo Central thermostat 24 V
Electronic PI regulator (hysteresis or PWM) Intelligent control - I.T.C.S.
LCD display with amber backlight Flush mounting version Works in heating or cooling mode (with reversible heat pump) Built in hygrostat or cooling mode Air temperature sensor, optionalfloor temperature sensor Sensor auto checks short circuit or break Program or diferent zones Week and vacation program deault and user programs Permanent storage Main zone programmer which control slave thermostats connectedto TempCo Connect module Sensor accuracy . C
UFH 0051003UFH 0051023
FAW3RWRFGC3C0500FAW0RWRFGC3C0500
individuallyindividually
pcs.pcs.
Thermoelectric head (actuator) 230Vnrmally clsed, plastic adaptr Mx., supply crd m x mm,pwer utput W, pwer supply V, cperates with TempCCnnect V r TempC Cnnect RF V
Thermoelectric head (actuator) 24 Vas abve but pwer supply V,cperates with TempC Cnnect V
UFH 0050140
UFH 0050143
FAW3ANCACNN54P00
FAW0ANCACNN54P00
individually
individually
pcs.
pcs.
Main board TempCo Connect 6M 230 V with pump control moduleindyvidual temperature regulatin in each rm. Main mdule r
max thermstats and actuatrs (max actuatrs each zne)
Main board TempCo Connect 6M 24 V with pump control moduleand transormatoras abve
UFH 0051012
UFH 0051032
FAW3RWCDM0603P00
FAW0RWCDM0603P00
individually
individually
pcs.
pcs.
Extension board TempCo Connect 6S 230 Vr additinal max thermstats
Heating and cooling board TempCo Cool 230 Vability t cnnect and cntrl heating r cling devices
(e.g. reversible heat pump) cperates with main bard TempCCnnect M V
UFH 0051014
UFH 0051015
FAW3RWCDS0601P00
FAW3RWCDS0605C00
individually
individually
pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
14/36
loor heating
14
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Wireless (radio) automatic elements
TempCo Comort RF thermostatElectrnic PI regulatr (hysteresis r PWM) Air temperature sensr,standing r n-wall munting versin Only mm thick
Mechanical temperature limit min and max Night reductin, anti-reeze Wrks in heating r cling mde(nly with prgrammer LED dide indicating radi transmissin Pwer supply - x AAA batteries Cperates with TempC Cen-
tral RF thermstat Sensr accuracy . C
UFH 0051041 FAW3R8RSEFNC0100 individually pcs.
TempCo Digital RF thermostatElectrnic PI regulatr (hysteresis r PWM) LCD display withamber backlight standing r n-wall munting versin Wrksin heating r cling mde Air sensr, ptinal flr temperaturesensr ways regulatin: rm temperature regulatin, rmtemperature regulatin and flr temperature limit (min/max) Flr temperature regulatin Cperates with TempC CentralRF thermstat Sensr accuracy . C
UFH 0051042 FAW3R8RSDVNC0300 individually pcs.
TempCo Central RF 230 V thermostatElectronic PI regulator (hysteresis or PWM) Intelligent control -I.T.C.S. LCD display with amber backlight Flush mounting version Works in heating or cooling mode (with reversible heat pump) Built in hygrostat or cooling mode Air temperature sensor,optional floor temperature sensor Sensor auto checks shortcircuit or break Program or diferent zones Week and vacationprogram deault and user programs Permanent storage Main zone programmer which control slave thermostats Power supply VAC Sensor accuracy . C
UFH 0051043 FAW3R8RFGC9C0500 individually pcs.
Main board TempCo Connect 6M RF 230 V with pump controlmodule and antennar indyvidual temperature regulatin in each rm.
Main mdule r max thermstats and actuatrs(max actuatrs each zne)
Extension board TempCo Connect 6S 230 Vr additinal max thermstats
UFH 0051052
UFH 0051054
FAW3R8CDM0603P00
FAW3R8CDS0603P00
individually pcs.
TempCo Connect 1M RF 230 V modulethermstat r individual regulatin in ne rm
mdule r ne thermstat, cperates with TempCCmrt, Digital r Central RF utput relay A,range m utdr nad m indr, pwer supply
VAC
UFH 0051050 FAW3R8CDM0103P00 individually pcs.
TempCo Sensor - floor temperature measurementcperates with wired and wireless thermstatsSensr type NTC m k C
UFH 0051091 FAW4ROROSPTDFL00 1 pcs.
TempCo GSM moduleAbility t cntrl and regulate a flr heating installatin viambile phne- utput, relay A
- external inputs (burglar alarm, fire alarm)- indr and utdr temperature sensrs
- building indr temperature regulatin- alarm mde - SMS inrmatin and raprt
UFH 0051092 FAW3OGSMM5109200 individually pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
15/36
loor heating
15
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Manifolds cabinets
Cabinets or maniolds installation(flush mounted)made rm galvanized steel sheet, easy remving lacquered dr r installatin, plastering and paint-ing wrks, adjustable height and depth
Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)
Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)
Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)
Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)
Cabinet /-/- (fl. heat. - to circ., heat. - to circ.)
Cabinet /-/- (fl. heat. - to circ., with mixing unit)
380430560710790
9601130
CSY 0000999CSY 0010000CSY 0010001CSY 0010002CSY 0010003
CSY 0010008CSY 0010009
FBWCFS02A70038P0FBWCFS03A70043P0FBWCFS06A70055P0FBWCFS08A70071P0FBWCFS10A70079P0
FBWCFS12A70096P0FBWCFS12A70113P0
individually pcs.
Cabinets for manifolds installation
(on wall mounted)from galvanized steel sheet, lacquered, easy door removing,adjustable height)Cabinet /-/ (fl. heat. - to circ., heat. - to circ.)Cabinet /-/ (fl. heat. - to circ., heat. - to circ.)Cabinet /-/ (fl. heat. - to circ., heat. - to circ.)Cabinet /-/ (fl. heat. - to circ., heat. - to circ.)Cabinet /-/ (fl. heat. - to circ., heat. - to circ.)Cabinet /-/ (fl. heat. - to circ., with mixing unit)
420
550700780950
1120
CSY 0010150
CSY 0010151CSY 0010152CSY 0010153CSY 0010154
CSY 0010155
FBWCWS03H70042P0
FBWCWS06H70055P0FBWCWS08H70070P0FBWCWS10H70078P0FBWCWS12H70096P0
FBWCWS15H70112P0
individually pcs.
CAUTION!!! Manifolds dimensions in brackets are approximate values. To avoid mistake make sure, that the cabinet dimension will be suitable formanifold and its additional equipment (cut-off valves, mixing set, etc.). It refers especially to floor heating manifolds.
Cabinets dimensins(n wall munted)
Cabinets dimensins(flush munted)
170max
120
70
62
50
80
195
Hmax-800
Hmin-700
110
min
Typ SWP 0
380 430 560 710 790 960 1130
SWP 1 SWP 2 SWP 3 SWP 4 SWP 5 SWP 6Typ
420 550 700 780 950 1120
SW 1 SW 2 SW 3 SW 4 SW 5 SW 6
Hmax-800
Hmin-700
110
62
45
65
110
140
215
" L "
" L " " L "
" L "
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
16/36
pipe system
16
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Multilayer pipe with aluminium layer
Pipe HKS-Sitec or heating and tap water- multilayer PE-X/Al/PE
between two layers o crosslinked polyethylene there isstabilizing butt-welded aluminium layer, assuring absoluteanti-difusion tightness; cooperates with compression,press and push fittings; maximum operational
parameters: temperature C (max. C temporary),pressure bar, supplied in coils
14x216x2
16x220x226x332x3
CSY 0053003CSY 0053000
CSY 0053005CSY 0053007CSY 0053009CSY 0053026
FBDXBAC1420200P0FBDXBAC1620100P0
FBDXBAC1620200P0FBDXBAC2020100P0FBDXBAC2630050P0FBDXBAC323005000
cartn a 200 mcartn a 100 m
cartn a 200 mcartn a 100 mcartn a 50 mcartn a 50 m
m
Pipe HKS-Sitec or heating and tap water
- multilayer PE-RT/Al/PE-RTbetween two layers o high temperature resistant poly-ethylene there is stabilizing butt-welded aluminium layer,assuring absolute anti-difusion tightness; cooperates
with compression, press and push fittings; maximumoperational parameters: temperature oC (max. oC orheating), pressure bar, supplied in coils
16x2
20x226x3
32x3
CSY 0052999
CSY 0053006CSY 0052993
CSY 0052991
FBDPTAC1620200P0
FBDPTAC2020200P0FBDPTAC2630050P0
FBDPTAC3230050P0
cartn a 200 m
cartn a 200 mcartn a 50 m
cartn a 50 m
m
Multilayer heating pipe PE-RT/Al/PE-RT profitherm Alr flr heating and lw temperature radiatrs
made rm tw layers high temperature resistantplyethylene and stabilizing butt-welded aluminiumlayer between, assuring abslute anti-difusin tight-ness. Maximum peratinal parameters: tempera-
ture oC, pressure bar.
16x216x2
CSY 0052994CSY 0052995
FBDPTAC1620240P0FBDPTAC1620600P0
240 m/cil600 m/cil
m
Pipe HKS-Sitec r heating and tap water mul-tiplayer PE-X/Al/PE cperates with press fittingsprperties as abve, delivered in m bars
Higher diameter connectors on demand
32x3
40x3.550x4
63x4.575x5
CSY 0053027
CSY 0053028CSY 0053029CSY 0053030CSY 0053010
FBDXBAL323000500
FBDXBAL403500500FBDXBAL504000500FBDXBAL634500500FBDXBAL755000500
cartn a 20 m
cartn a 25 mcartn a 25 mcartn a 15 mcartn a 5 m
m
mmmm
PE-X pipes with anti-diffusion layer EVOH
Heating pipe PE-X rm tw layers crsslinkedplyethylene with anti-difusin barrier between,
maximum peratinal parameters:temperature oC, pressure bar
16x2
16x216x220x220x220x2
UFH 0054002
UFH 0054003UFH 0054004UFH 0054001UFH 0054023UFH 0054027
FBAXB5C1620120P0
FBAXB5C1620240P0FBAXB5C1620600P0FBAXB5C2020120P0FBAXB5C2020240P0FBAXB5C2020500P0
120 m/cil
240 m/cil600 m/cil120 m/cil240 m/cil600 m/cil
m
Compression brass nickel plated fittings nut
HKS-Uni male screw coupling with 1/2" nut
16x2 by CSY 0053020 FAZ1S12M16A12FP0 10 pcs. pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
17/36
pipe system
17
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Compression brass nickel plated fittings nut
Uni emale screw wallplate elbow with /" nut
16x2 by CSY 0053021 FAZ1W12F16A000P0 individually pcs.
Uni screw Tee with /" nuts
16x16x16by
CSY 0 053022 FAZ1T16A16A16AP0 individually pcs.
Compression brass nickel plated fittings nut
Nickel plated male screw cupling with /" nut andO-ring seal
(pipe - radiatr) 16x2 by 20x2 by
CSY 0053023CSY 0053025
FAZ1S12M16A34FP0FAZ1S12M20A000P0
10 pcs.10 pcs.
pcs.
Nickel plated male screw coupling with /" nut
26x3 by 26x3 by 1
CSY 0053037CSY 0053031
FAZ1S34M26A000P0FAZ1S44M26A000P0
5 pcs.5 pcs.
pcs.
HKS screw coupling double with /" nuts(pipe-pipe)
16x2-16x2
20x2-20x2
CSY 0053040
CSY 0053042
FAZ1C34C16A000P0
FAZ1C34C20A000P010 pcs. pcs.
HKS screw coupling with /" nut (pipe - manild)
14x2 by
16x2 by 20x2 by
CSY 0053032
CSY 0053033CSY 0053035
FAZ1S34C14A000P0
FAZ1S34C16A000P0FAZ1S34C20A000P0
10 pcs. pcs.
HKS screw Tee with /" nuts
16x16x16 by 20x20x20 by CSY 0053060
CSY 0053046
FAZ1T16A16A16A00
FAZ1T20S20A20AP0
10 pcs.
10 pcs.
pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
18/36
pipe system
18
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Compression brass nickel plated fittings nut
HKS screw elbow with /" nut
16x16 by 20x20 by
CSY 0053050CSY 0053043
FAZ1E16A16A000P0FAZ1E20A20A000P0
10 pcs. pcs.
HKS male screw elbow with /" nut
16x2 by 20x2 by
CSY 0053051CSY 0053044
FAZ1E12M16A000P0FAZ1E12M20A000P0
10 pcs. pcs.
HKS emale screw elbow with /" nut
16x2 by 20x2 by
CSY 0053045CSY 0053052
FAZ1E12F16A000P0FAZ1E12F20A000P0
10 pcs. pcs.
Press fittings Purmo HKS - Sitec Press (brass)
Male coupling double, with stainless steel sleeve 16x
20x20x26x26x26x1
32x140x150x1
CSY 0053223
CSY 0053227CSY 0053226CSY 0053222CSY 0053228CSY 0053229
CSY 0053230CSY 0053231CSY 0053232
FAZ4C12M16A000P0
FAZ4C12M20A000P0FAZ4C34M20A000P0FAZ4C12M26A000P0FAZ4C34M26A000P0FAZ4C44M26A000P0
FAZ4C44M32A000P0FAZ4C54M40A000P0FAZ4C64M50A000P0
10 pcs.
10 pcs.10 pcs.10 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.
pcs.
Female coupling double, with stainless steel sleeve 16x20x20x
26x26x132x1
40x1
50x1
CSY 0053346CSY 0053349CSY 0053350CSY 0053351
CSY 0053352CSY 0053353CSY 0053354
CSY 0053452
FAZ4A12F16A000P0FAZ4A12F20A000P0FAZ4A34F20A000P0FAZ4A34F26A000P0
FAZ4A44F26A000P0FAZ4A44F32A000P0FAZ4A54F40A000P0
FAZ4C64F50A000P0
10 pcs.10 pcs.10 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Nickel plated screw connector with flat seal, withstainless steel sleeve
16x20x26x1
32x1
40x1
CSY 0053233CSY 0053235CSY 0053236CSY 0053237
CSY 0053238
FAZ4C34F16A000P0FAZ4C34F20A000P0FAZ4C44F26A000P0FAZ4C54F32A000P0
FAZ4C64F40A000P0
10 pcs.10 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Nickel plated connecting screw fitting with eurcne, with stainless steel sleeve
16x20x
CSY 0053356CSY 0053358
FAZ4A34C16A000P0FAZ4A34C20A000P0
10 pcs.10 pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
19/36
pipe system
19
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS - Sitec Press (brass)
Coupling double (pipe-pipe) with stainless steelsleeves 16x16
20x2026x2632x32
40x4050x50
CSY 0053241CSY 0053243CSY 0053194CSY 0053195
CSY 0053196CSY 0053456
FAZ4C16A16A000P0FAZ4C20A20A000P0FAZ4C26A26A000P0FAZ4C32A32A000P0
FAZ4C40A40A000P0FAZ4C50A50A000P0
10 pcs.10 pcs.10 pcs.5 pcs.
5 pcs.5 pcs.
pcs.
Reduced coulping dobule with stainless steel sleeves 20x1626x16
26x2032x1632x2032x26
40x2640x3250x3250x40
CSY 0053198CSY 0053200
CSY 0053201CSY 0053206CSY 0053202CSY 0053203
CSY 0053204CSY 0053205CSY 0053458CSY 0053459
FAZ4C20A16A000P0FAZ4C26A16A000P0
FAZ4C26A20A000P0FAZ4C32A16A000P0FAZ4C32A20A000P0FAZ4C32A26A000P0
FAZ4C40A26A000P0FAZ4C40A32A000P0FAZ4C50A32A000P0FAZ4C50A40A000P0
10 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.
pcs.
Male elbow, with stainless steel sleeve
16x
20x26x32x1
40x1
CSY 0053181
CSY 0053183CSY 0053184CSY 0053185CSY 0053186
FAZ4E12M16A000P0
FAZ4E12M20A000P0FAZ4E34M26A000P0FAZ4E44M32A000P0FAZ4E54M40A000P0
10 pcs.
10 pcs.5 pcs.5 pcs.5 pcs.
pcs.
Female elbow with stainless steel sleeve16x
20x20x26x
32x140x150x1
CSY 0053188
CSY 0053190CSY 0053189CSY 0053191
CSY 0053192CSY 0053193CSY 0053244
FAZ4E12F16A000P0
FAZ4E12F20A000P0FAZ4E34F20A000P0FAZ4E34F26A000P0
FAZ4E44F32A000P0FAZ4E54F40A000P0FAZ4E64F50A000P0
10 pcs.
10 pcs.10 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.
pcs.
Elbow with stainless steel sleeves
16x16
20x2026x2632x3240x40
50x50
CSY 0053250
CSY 0053253CSY 0053255CSY 0053256CSY 0053257
CSY 0053466
FAZ4E16A16A000P0
FAZ4E20A20A000P0FAZ4E26A26A000P0FAZ4E32A32A000P0FAZ4E40A40A000P0
FAZ4E50A50A000P0
10 pcs.
10 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Elbow 45 with stainless steel sleeves
26x26
32x3240x40
CSY 0053248
CSY 0053258CSY 0053259
FAZ4E26A26A45DP0
FAZ4E32A32A45DP0FAZ4E40A40A45DP0
5 pcs.
5 pcs.5 pcs.
pcs.
Wallplate elbow - short,with stainless steel sleeve - mm
Elbow as above, medium - mm
Elbow as above, long - mm
16x
20x
16x
CSY 0053280
CSY 0053282
CSY 0053288
FAZ4W12F16A000P0
FAZ4W12F20A000P0
FAZ4W12F16ALONP0
individually
individually
individually
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
20/36
pipe system
20
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS - Sitec Press (brass)
Wallplate elbow double, for circulation, short - mm
16x20x
CSY 0053276CSY 0053278
FAZ4B16A12F16AP0FAZ4B20A12F20AP0
individuallyindividually
pcs.
Passing through partition wall 60 mm
16x F
r MCSY 0053057 FAZ4W16A24F34MP0 10 pcs. pcs.
Tap installation setkit cntents: tw wall shrt elbws, installatin rail,
fixing screws
16x2 CSY 0053298 FAZ4B16A12F000P0 set pcs.
Elbow or reservoir with stainless steel sleeve
16x F CSY 0053284 FAZ4E16A24F000P0 10 pcs. pcs.
Tee, with stainless steel sleeves
16x220x226x332x3
40x3.550x4
CSY 0053260CSY 0053262CSY 0053301CSY 0053302
CSY 0053303CSY 0053304
FAZ4T16A16A16AP0FAZ4T20A20A20AP0FAZ4T26A26A26AP0FAZ4T32A32A32AP0
FAZ4T40A40A40AP0FAZ4T50A50A50AP0
10 pcs.10 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.
pcs.
Tee reduced passing and middle, with stainless
steel sleeves
20x16x16
26x16x2026x20x20
32x20x2632x26x2640x26x3240x32x32
50x32x4050x40x40
CSY 0053269
CSY 0053323CSY 0053324
CSY 0053325CSY 0053326CSY 0053327CSY 0053328
CSY 0053481CSY 0053320
FAZ4T20A16A16AP0
FAZ4T26A16A20AP0FAZ4T26A20A20AP0
FAZ4T32A20A26AP0FAZ4T32A26A26AP0FAZ4T40A26A32AP0FAZ4T40A32A32AP0FAZ4T50A32A40AP0
FAZ4T50A40A40AP0
10 pcs.
5 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Tee - reduced middle, with stainless steel sleeves 20x16x2026x16x2626x20x2632x20x3232x26x32
40x26x4040x32x40
50x26x5050x32x5050x40x50
CSY 0053268
CSY 0053306CSY 0053308CSY 0053309CSY 0053310
CSY 0053311CSY 0053312
CSY 0053313CSY 0053476CSY 0053477
FAZ4T20A16A20AP0
FAZ4T26A16A26AP0FAZ4T26A20A26AP0FAZ4T32A20A32AP0FAZ4T32A26A32AP0
FAZ4T40A26A40AP0FAZ4T40A32A40AP0
FAZ4T50A26A50AP0FAZ4T50A32A50AP0FAZ4T50A40A50AP0
10 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.
5 pcs.5 pcs.5 pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
21/36
pipe system
21
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS - Sitec Press (brass)
Tee - reduced passing, with stainless steel sleeves 20x20x1626x26x16
26x26x2032x32x2032x32x2640x40x2640x40x32
50x50x3250x50x40
CSY 0053270CSY 0053314
CSY 0053315CSY 0053316CSY 0053317CSY 0053318CSY 0053319
CSY 0053321CSY 0053322
FAZ4T20A20A16AP0FAZ4T26A26A16AP0
FAZ4T26A26A20AP0FAZ4T32A32A20AP0FAZ4T32A32A26AP0FAZ4T40A40A26AP0FAZ4T40A40A32AP0
FAZ4T50A50A32AP0FAZ4T50A50A40AP0
10 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.
pcs.
Tee - enlarged middle, with stainless steel sleeves
16x20x1620x26x20
26x32x26
32x40x32
CSY 0053330CSY 0053331
CSY 0053332
CSY 0053333
FAZ4T16A20A16AP0FAZ4T20A26A20AP0
FAZ4T26A32A26AP0
FAZ4T32A40A32AP0
10 pcs.5 pcs.
5 pcs.
5 pcs.
pcs.
Female tee end with internal threadwith stainless steel sleeves
16xx16
20xx2026xx2632x1x32
40x1x40
CSY 0053334
CSY 0053336CSY 0053337CSY 0053338CSY 0053339
FAZ4T16A12F16AP0
FAZ4T20A12F20AP0FAZ4T26A34F26AP0FAZ4T32A44F32AP0FAZ4T40A54F40AP0
10 pcs.
10 pcs.5 pcs.5 pcs.5 pcs.
pcs.
Male tee, with stainless steel sleeves
16xx1620xx2026xx2632x1x32
50x1x50
CSY 0053340CSY 0053342CSY 0053343CSY 0053344CSY 0053480
FAZ4T16A12M16AP0FAZ4T20A12M20AP0FAZ4T26A34M26AP0FAZ4T32A44M32AP0FAZ4T50A64M50AP0
10 pcs.10 pcs.5 pcs.5 pcs.5 pcs.
pcs.
T-pipes crossing, with stainless steel sleeves
16x16x1620x16x20
CSY 0053173CSY 0053175
FAZ4D16A16A16AP0FAZ4D20A16A20AP0
individuallyindividually
pcs.
Connection nickel plated elbow with stainless steelsleeve
shrt mm 16/15x1 CSY 0053065L FAZ5E16A03C000P0 individually pcs.
Connection nickel plated elbow with stainless steelsleeve and cntrl ring
lng mm 16x2/15x1 CSY 0053054 FAZ5E16A11C000P0 individually pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
22/36
pipe system
22
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS - Sitec Press (brass)
Connection nickel plated Tee with stainless steelsleevesshrt mm
lng mm
16x2/15x1
20x2/15x1
16x2/15x120x2/15x1
CSY 0053066
CSY 0053096
CSY 0053055CSY 0053097
FAZ5T16A03C000P0
FAZ5T20A03C000P0
FAZ5T16A11C000P0FAZ5T20A11C000P0
individually
individually
individuallyindividually
pcs.
Stainless steel sleeve with cntrl ring
16202632
40
CSY 0053291CSY 0053293CSY 0053359CSY 0053360
CSY 0053361
FAZTA00COLLA16P0FAZTA00COLLA20P0FAZTA00COLLA26P0FAZTA00COLLA32P0FAZTA00COLLA40P0
10 pcs.10 pcs.5 pcs.5 pcs.5 pcs.
pcs.
O-ring seal
1620
263240
CSY 0053295CSY 0053297
CSY 0053362CSY 0053363CSY 0053364
FAZTA00ORING16P0FAZTA00ORING20P0
FAZTA00ORING26P0FAZTA00ORING32P0FAZTA00ORING40P0
10 pcs.10 pcs.
5 pcs.5 pcs.5 pcs.
pcs.
Stop end t clse unused ends, with stainless steelsleeve
16x220x2
CSY 0053122CSY 0053123
FAZ4S16A000000P0FAZ4S20A000000P0
10 pcs.10 pcs.
pcs.
Push fittings Purmo HKS Plus made from plastic PPSU with stainless steel sleeve
Purmo HKS Plus. Fast assembly technlgy.- multiple assembling and disassembling available- additional system - allows mountage in hard-to-reach
places without any tools- suitable with the same HKS pipe system - special pipes
are not necessary
Cupling duble (pipe-pipe) PPSU HKS plus
Cupling duble (pipe-pipe) PPSU HKS plusReduced cupling duble (pipe-pipe) PPSU HKS plusElbw PPSU HKS plus
Elbw PPSU HKS plusTee PPSU HKS plusTee PPSU HKS plusTee PPSU HKS plus
HKS Plus male couplingHKS Plus with male threadHKS Plus with emale thread
Male elbow HKS PlusFemale wallplate elbo mm HKS Plus
16x16
20x2020x1616x16
20x2016x16x1620x16x2020x16x1616x1/2"
20x1/2"16x1/2"16x1/2"16x1/2"
CSY 88316100
CSY 88320100CSY 88320130CSY 88316200CSY 88320200CSY 88316300CSY 88320330CSY 88320333CSY 87316762CSY 87320762CSY 87316762CSY 87316792CSY 87316720
on request
on requeston requeston requeston requeston requeston requeston requeston requeston requeston requeston requeston request
10 pcs.
10 pcs.10 pcs.10 pcs.
10 pcs.10 pcs.10 pcs.10 pcs.10 pcs.
10 pcs.10 pcs.10 pcs.10 pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
23/36
pipe system
23
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS Sitec Press (from PPSU plastic)
Coupling double (pipe-pipe) with stainless steelsleeves
16x1620x2026x2632x32
CSY 88616100CSY 88620100CSY 88626100CSY 88632100
FAZ8C16A16A000P0FAZ8C20A20A000P0FAZ8C26A26A000P0FAZ8C32A32A000P0
10 pcs.10 pcs.5 pcs.5 pcs.
pcs.
Reduced coupling double with stainless steel sleeves
20x16
26x1626x2032x20
32x26
CSY 88620130CSY 88626130CSY 88626150CSY 88632150
CSY 88632160
FAZ8A16A20A000P0FAZ8C26A16A000P0FAZ8C26A20A000P0FAZ8A32A20A000P0
FAZ8A32A26A000P0
10 pcs.
10 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Elbow with stainless steel sleeves
16x16
20x2026x2632x32
CSY 88616200CSY 88620200CSY 88626200CSY 88632200
FAZ8E16A16A000P0FAZ8E20A20A000P0FAZ8E26A26A000P0FAZ8E32A32A000P0
10 pcs.
10 pcs.5 pcs.5 pcs.
pcs.
Tee, with stainless steel sleeves
16x16x16
20x20x2026x26x26
32x32x32
CSY 88616300
CSY 88620300CSY 88626300CSY 88632300
FAZ8T16A16A16AP0
FAZ8T20A20A20AP0FAZ8T26A26A26AP0FAZ8T32A32A32AP0
10 pcs.
10 pcs.5 pcs.
5 pcs.
pcs.
Tee - reduced passing and middle, with stainless steelsleeves
20x16x1626x16x2026x20x16
26x20x2032x16x2632x20x2632x26x2032x20x20
32x26x26
CSY 88620333CSY 88626335CSY 88626353CSY 88626355CSY 88632336CSY 88632356CSY 88632365CSY 88632355CSY 88632366
FAZ8T20A16A16AP0FAZ8T26A16A20AP0FAZ8T26A20A16AP0FAZ8T26A20A20AP0FAZ8T32A16A26AP0FAZ8T32A20A26AP0FAZ8T32A26A20AP0FAZ8T32A20A20AP0FAZ8T32A26A26AP0
10 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.
pcs.
Tee - reduced middle, with stainless steel sleeves 20x16x2026x16x2626x20x2632x16x32
32x20x3232x26x32
CSY 88620330CSY 88626330CSY 88626350CSY 88632330CSY 88632350CSY 88632360
FAZ8T20A16A20AP0FAZ8T26A16A26AP0FAZ8T26A20A26AP0FAZ8T32A16A32AP0FAZ8T32A20A32AP0FAZ8T32A26A32AP0
10 pcs.5 pcs.5 pcs.5 pcs.
5 pcs.5 pcs.
pcs.
Tee - reduced passing, with stainless steel sleeves
20x20x16
26x26x1626x26x2032x32x2032x32x26
CSY 88620303CSY 88626303CSY 88626305CSY 88632305CSY 88632306
FAZ8T20A20A16AP0FAZ8T26A26A16AP0FAZ8T26A26A20AP0FAZ8T32A32A20AP0FAZ8T32A32A26AP0
10 pcs.
5 pcs.5 pcs.5 pcs.5 pcs.
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
24/36
pipe system
24
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Press fittings Purmo HKS Sitec Press (from PPSU plastic)
Tee enlarged middle, with stainless steel sleeves
16x20x1620x26x2020x32x2026x32x2626x32x20
CSY 88616350CSY 88620360CSY 88620370CSY 88626370CSY 88626375
FAZ8T16A20A16AP0FAZ8T20A26A20AP0FAZ8T20A32A20AP0FAZ8T26A32A26AP0FAZ8T26A32A20AP0
10 pcs.5 pcs.5 pcs.5 pcs.5 pcs.
pcs.
Stop end t clse unused ends, with stainless steelsleeve
16x2
20x2CSY 88616820CSY 88620820
FAZ8T16A000000P0FAZ8T20A000000P0
10 pcs.
10 pcs.pcs.
Manifoldsassembled, equipped with vibration damping pads brackets, checked for 8 bar pressure, in carton package
1 - M 1 brass (M 63)
kit cntents:- cnnectin pipes M ,- vents
2 circuits3 circuits
4 circuits5 circuits6 circuits7 circuits8 circuits
9 circuits10 circuits11 circuits12 circuits
160x293x77210x293x77
260x293x77310x293x77360x293x77410x293x77460x293x77
510x293x77560x293x77610x293x77660x293x77
CSY 0053433CSY 0053434CSY 0053435CSY 0053436CSY 0053437CSY 0053438CSY 0053439CSY 0053440CSY 0053441CSY 0053442CSY 0053443
FAZMRBR0240520P0FAZMRBR0340520P0FAZMRBR0440520P0FAZMRBR0540520P0FAZMRBR0640520P0FAZMRBR0740520P0FAZMRBR0840520P0FAZMRBR0940520P0FAZMRBR1040520P0FAZMRBR1140520P0FAZMRBR1240520P0
1 pcs. pcs.
Ball valves for manifolds
Ball valve with hal cnnectr r manilds series: - M brass (M ) r flr heating - M rm stainless steel r flr heating - M brass (M ) r heating and tap water
F 1 - F 1 UFH 0050420VA FBWAMVNT44F440P0 2 pcs. pcs.
Tools
Calibrators setr calibrating HKS Sitec pipes bere making
pressed cnnectin 14, 16, 17, 2016, 20, 26, 32
4050
63
CSY 0053130CSY 0053147CSY 0053149CSY 0053151
FAZTTCAFB5023100FAZTTCAFB53130P0FAZTTCAFB40000P0FAZTTCAFB50000P0
individually pcs.
Calibrator HKS r pipe
16 CSY 0053131 FAZTTCAFB53131P0 1 pcs. pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
25/36
pipe system
25
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Tools
Pipe cutter HKS - mm
14-20 UFH 0050040 FAZTTCUFB5004000 individually pcs.
Pipe cutter - mm
Pipe cutter - mm
14-40
14-63
CSY 0053087
CSY 0053088
FAZTTCUFB16400P0
FAZTTCUFB14630P0
individually
individually
pcs.
pcs.
Internal spring r pipe bending
length mm, mmlength mm, mmlength mm, mm
162026
CSY 0053141CSY 0053143CSY 0053500
FAZTTBSFB53141P0FAZTTBSFB53143P0FAZTTBAFB26000P0
individually pcs.
Pressing jawsr Sitec-Press fittings 16
17
2026324050
CSY 0053133UFH 0050050CSY 0053135CSY 0053144CSY 0053145CSY 0053146CSY 0053148
FAZTTPJFB16000P0FAZTTPJFB50050P0FAZTTPJFB20000P0FAZTTPJFB26000P0FAZTTPJFB32000P0FAZTTPJFB40000P0FAZTTPJFB50000P0
1 pcs.1 pcs.
1 pcs.1 pcs.1 pcs.1 pcs.1 pcs.
pcs.
Powered pressing toolapprx. pressing cycles r ne charging;r jaws mm;kit cntents: suitcase, charger and battery;
spare battery Ni-Cd
spare battery Li-Inbattery charger
Power supply pressing tool Sitec Press, supply 230V,
r jaws - mm, with metal suitcase
CSY 0053136
CSY 0053137CSY 0053137LICSY 0053138
CSY 0053139 E
FAZTTBPFB53136P0
FAZTT00FB53137P0FAZTT00FB137LIP0FAZTT00FB53138P0
FAZTTPPFB3139EP0
1 pcs.
1 pcs.
1 pcs.1 pcs.
1 pcs.
pcs.
Hand pressing tool - mm
CSY 0053900 FAZTTMPFB53900P0 1 pcs. pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
26/36
pipe system
26
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Accessories
Single HKS rosette
16 CSY 0053090 FAZTA00FB53090P0 50 pcs. pcs.
Duble HKS rosette
16 CSY 0053093 FAZTA00FB53093P0 10 pcs. pcs.
Pipe guide arc with t
1625
CSY 0053279CSY 0053379
FAZTA00ARCH160P0FAZTA00ARCH250P0
individually pcs.
Single plastic pipes holderDuble plastic pipes holder
8x909x90
CSY 0053085CSY 0053086
FAZTA00FB53085P0FAZTA00FB53086P0
50 pcs.
50 pcs.
pcs.
pcs.
Wallplate elbow mounting kit, helps in crrect andprecise installatin wallplate elbws r tap waterkit cntents fixing screws
CSY 0053069 FAZTA00RAILWE0P0 individually pcs.
Perorated plate r wallplate elbws
Plates or fixing wallplate elbws n perrated plate2000x50x3
CSY 0053283
CSY 0053286
FAZTA00RAIL200P0
FAZTA00FB53286P0
2 m
50 pcs.
m
pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
27/36
pipe system
27
System elements
image description dimension(mm); "
old cataloguenumber order code in package unit
Connection elements for radiators
Angle radiator connection valve kit
Straight radiator connection valve kit by
SAR0040126
SAR0040121
FAZ1R34M24MELBP0
FAZ1R34M24MSTRP0individually pcs.
Straight radiator connection double valve kit, nickelplated
Angle radiator connection double valve kit, nickelplated
by
SAR0040127
SAR0040128
FAZ1P34M24MSTRP0
FAZ1P34M24MELBP0
individually pcs.
Screw coupling or copper pipe with 3/4" nut
15x1 by SAR0040213 FAZ1S34F151000P0 10 pcs. pcs.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
28/36
loor heating
28
Floor heatingNecessary condition to obtain PURMO warranty
This orm is the basis or application or 10-years warranty or floor heating. Fill it with capital letters andsend to us. In 14 days You will receive our warranty, provided or investors and realization companies good.
______________ m2 oPURMO floor heating. Realization finished ________________
Investor Name _____________________________________Street: _____________________________________Postcode/city _____________________________________
Investment Street: _____________________________________address Postcode/city _____________________________________
Investment Name/company _____________________________________contractor Street: _____________________________________
Postcode/city _____________________________________
Architect Name _____________________________________Designer Street: _____________________________________Design of ce Postcode/city _____________________________________
We hereby declare, that the above PURMO floor heating system has been proessionally designed,realized and started according to use and installation principles, established RETTIG-HEATING Sp. z o.o.
The ollowing original elements o PURMO floor heating have been used:
1. pipe ________________ or floor heating, diameter _____________ mm
2. PURMO system insulation rolljet altjet noppjet
3. PURMO maniolds with flowmeters with valve inserts industrial maniold
RETTIG HEATINGSales of ceRotmistrza Pileckiego 9102-781 Warsaw, Poland
Contractor signature and stamp
1. Apartment building2. Of ce/administrative building3. industrial hall
4. Sport hall5. Hospital/rest home6. School/kindergarten
7. Car dealer salon8. Open space9.
Investment type:
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
29/36
loor heating
29
Floor heatingSYSTEM START-UP
AND SCREED WARM-UP REPORTor PURMO floor heating according to standard PN-EN 1264
Investment : ______________________________________________________________Floor : ______________________________________________________________Investor : ______________________________________________________________
PURMO floor heating in above building has been designed according to standardDIN 13813 / PN-EN 1264, part 4, and subjected to pressure test (pressure test protocol).Screed type: ______________________________________________________________Screed thickness: ______________________________________________________________Screed additives: ______________________________________________________________
Procedure according to standard PN-EN 1264, part 4:Anhidrite and cement screeds must be heated beore the cover layer realization. In case o cementfloors the system start-up must be perormed not earlier than ater 21 days, in case o anhidrite floorsaccording to producers recommendations, but not earlier than ater 7 days.
The first start-up is perormed at supply temperature 25 C, which should be maintained or three days.Then the supply temperature should be increased to the maximum value and maintain or five days.Screed finished: date: _________________________Screed warm-up with water at 25 C date: _________________________Screed warm-up with water at maximum temperature __________C date: ___________Screed warm-up end (not earlier than ater 8 days) in:Was the screed warm-up process interrupted? yes/noI yes rom: ________ to: ____________Has the heated floor been covered with stored building materialsor other things? yes/noHave there been draughts in the rooms? yes/noSystem has been commissioned at external temperature __________C date: ___________Was the system operating during commissioning? yes/no
Has the floor been previously heated with water at temperature __________C yes/no
Caution:realization o screed warm-up process according to above conditions does not assure that the floorobtains humidity level, required or finishing layer realization. Humidity test beore finishing worksshould be perormed in the ollowing way: Spread approximately 1 m2 o PE oil on the floor. Fix its edgestightly with adhesive tape. Ater 24 hours check the moisture drops under the oil. I there are visibledrops o condensation, test result is negative. Restart the system and heat the floor or a ew days, thenperorm the test once again.
Confirmation:
.Investor
Stamp/signature
..Site manager/supervisor
Stamp/signature
..Contractor
Stamp/signature
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
30/36
loor heating
30
Floor heatingPRESSURE TEST
or PURMO floor heating according to standard PN-EN 1264
Investment : ______________________________________________________________
Floor : ______________________________________________________________Investor : ______________________________________________________________
PURMO floor heating in above building has been designed according to standard DIN 13813/ PN-EN 1264,part 4.PURMO floor heating type: Wet systemUsed pipes Diustop heating pipe ________ mm, HKS pipe ________ mm
Procedure according to standard PN-EN 1264, part 4:Ater the installation completion check tightness o heating circuits, which will be covered with anhidriteor cement screed. Tightness must be confirmed directly beore and during screed realization. Pressurevalue should be at least 6 bar. In case o reezing hazard use various preventive methods, or e.g. useadditives decreasing water reezing temperature (ethylene i propylene glycol) or turn on the heating.
When anti-reezing additive becomes unnecessary, it should be flushed away rom the installtion byreplacing water at least 3 times.
Pipe installation Beginning: _______ at external temperature ___C
End: _______ at external temperature ___C
Pressure test Beginning: _______ Pressure value: ___ bar
End: _______ Pressure value: ___ bar
Floor realization Beginning: _______ System pressure value: ___ bar
End: _______ System pressure value: ___ bar
Has the anti-reezing additives been used? yes/no
System commissioning in: ___ ___
Confirmation:
.Investor
Stamp/signature
..Site manager/supervisor
Stamp/signature
..Contractor
Stamp/signature
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
31/36
pipe system
31
HKS and PurmoPE-X pipe system
Necessary condition to obtain PURMO warranty
This orm is the basis or application or 10-years warranty or HKS / Purmo PE-X pipe system. Fill it withcapital letters and send to us. In 14 days You will receive our warranty, provided or investors and realiza-tion companies good.
______________ m o HKS / PE-X system pie Realization finished ________________
Investor Name _____________________________________Street: _____________________________________Postcode/city _____________________________________
Investment Street: _____________________________________address Postcode/city _____________________________________
Investment Name/company _____________________________________contractor Street: _____________________________________
Postcode/city _____________________________________
Architect Name _____________________________________Designer Street: _____________________________________Design of ce Postcode/city _____________________________________
We hereby declare, that the above HKS / Purmo PE-X pipe system has been proessionally designed,realized and started according to use and installation principles, established RETTIG-HEATING Sp. z o.o.
The ollowing original elements o PURMO pipe system have been used:
1. System pipe HKS / PE-X diameter _____________ mm
2. PURMO fittings
3. PURMO maniold
RETTIG HEATINGSales of ceRotmistrza Pileckiego 9102-781 Warsaw, Poland
Contractor signature and stamp
1. Apartment building2. Of ce/administrative building3. industrial hall
4. Sport hall5. Hospital/rest home6. School/kindergarten
7. Car dealer salon8. 9.
Investment type:
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
32/36
loor heating
32
PURMO Floor heatingWARRANTY No. ____ 00/2007 ____ ORIGINAL/COPY ______________________________________or investors and realization companies good
Investor Name ___ JAN KOWALSKI __________________________________Street: ___ KOWALSKA 00 __________________________________Postcode/city ___ 00-000 KOWALEWO _____________________________
Investment Street: ___ KOWALSKA 00 __________________________________
address Postcode/city ___ 00-000 KOWALEWO _____________________________System Name/company ___ NOWAK / INSTALATORSTWO SANITARNE _____________contractor Street: ___ NOWAKA 00 ____________________________________
Postcode/city ___ 00-001 NOWAKOWO _____________________________
____ 185 ____ m2 oPURMO floor heating. Realization finished ____ 24.12.2006____
We hereby grant the ollowing warranty or plastic pipes and other elements o floor heating system and HKS Sitecsystem rom Rettig Heating Sp. z o.o. company, delivered or the above investment:1.1. In warranty period:
10 yearscounting rom the installation date we assure ree o charge replacement o heating pipes and other elements oPURMO system, in which the ailures occur, resulting rom production deects.
1.2. Warranty does not include electric and electronic elements o PURMO system (1 year o warranty).
1.3. In warranty period:
10 yearscounting rom the installation date we also assure reund o costs connected with:
damages occurring in property o third persons and resulting rom them urther damages, or costs o third persons, connected with removal, disassembly and verification o deective elements and replacing
them with operational elements.1.4. Warranty considerations value is limited to:
1 000 000 EUROand the condition o payment is proper contractor statement, presented according to warranty conditions.*
1.5. In order to protect the above risk the contract has been signed with renown insurance company, reerring toextended, obligatory damages insurance or damages resulting rom product deects, or amount to 1 000 000EURO.
1.6. Lump sum or covering personal and material damages, resulting rom above contract is: 1 000 000 EURO1.7. In other cases our general trade terms and conditions are used.
RETTIG HEATING Sp.zo.o.44-203 Rybnik, PrzemysowaSales Of ce in Warsaw, Pileckiego 91
* This warranty is valid only in case o presenting itby the contractor on original orm in 3 months romrealization date.In this orm the contractor declares, that the installa-tion instructions have been ollowed and only originalelements o PURMO system have been used.
Warsaw _01.01.2007 _
Signature: _____________ _____________
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
33/36
14-63 mm
PURMO HKS pipe structureSpecial gluing layers
External polyethylenelayer
Internal polyethylenelayer
Butt-weldedaluminium layer
pipe system
33
General inrmatin
Purmo is a complete system, designed or heating and tap water. Its use allowsrealization o all systems in the building radiator and loor central heating, andhot and cold water.System certiication or use in potable water systems is conirmed by proper Polish
and oreign certiicates.
Installation technologyCorrect installation o sanitary and heating systems in Purmo HKS system requiresuse o proessional tools, which eliminate the leaks possibility. They also assuremany years o ailure-ree system operation. Ater planning the pipes route or theindividual receivers the installation begins.
Pipes cuttingThe irst step is cutting pipes to the appropriate length. Cutting is perormed withuse o cutters or disc cutters. They assure cutting plane perpendicularity to the pipelongitudinal axis. It is not allowed to use saws or other cutting tools, creating mate-rial chips, which are diicult or even impossible to remove rom the system.
Pipes bendingPipes route direction is changed by bending, with use o material elasticity. Bendingis perormed with bare hands, maintaining bending radius equal to pipe diam-eters ( x d). With use o internal spring it is possible to bend without risk o acci-dental pipe breaking.
Fittings installationPipe end, deormed during cutting, should be deburred and calibrated. It is per-ormed with use o calibrator tool with proper diameter. It allows or correct ittingconus positioning in the pipe without O-ring damage risk. Ater those necessarypreparation activities the connector is installed. Put the nut and cut ring on the pipeend, and resolutely insert conus with O-ring into the pipe. Ater assembling all con-nector parts tighten the nut with hand, then with installation wrench.
In case o pressed connectors the preparation activities are perormed in the same
way. Press ittings are mounted, with previously deburred and calibrated pipe in away, that itting body is pushed inside the pipe, but compression sleeve stays out-side. Well positioned pipe can be seen in small check windows in the sleeve. Laststep is to press this connection, with pressing tool and using jaws with TH proile.Plastic ring assures right position o the jaw.
Pipes positioningIn the internal central heating and water systems pipes should be installed in ther-mal insulation or protective pipe. Peschel is not an insulation according to polishlaw requirements (Dz. U. th o april r.). Peschel protects pipes against injuriesand must be used when pipe trace crosses extansion joints or walls. During pipesroutes designing remember about their thermal expansion, paying attention tocorrect positioning o ixing holders, constant points and compensations. Detailedcompensation solutions should use the sel-compensation phenomenon, andshould be taken into consideration during system designing. In passages through
the loors use plastic sleeves.
Pressure testAccording to COBRTI Instal, part "Technical conditions or tap water installationsexecution and acceptance" technical requirements, pressure test must be doneater when installation is assemblied. All operations regarding installation execu-tion with HKS pipe system, must be done properly according to COBRTI Instal, part "Technical conditions or tap water installations execution and acceptance".
Pipe technical data Maximum operational temperature t
max= C
Maximum short-time temperature tmax
= C Maximum operating pressure p
max= bar
Minimum bending radius r = x dz
(with spring . x dz)
Linear expansion coeicient k = . mm/(mK)
Thermal conductivity coeicient = . W/(mK) Absolute roughness k = . mm Diameters: x mm, x mm, x mm, x mm,
x mm, x . mm, x mm, x . mm.
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
34/36
ApplicationWall heating is used, for example, in historical buildings, where it is not possibleto install floor heating due to precious floors, in rooms where heating of othersurfaces would be harmful, but also when floor heating is insufficient. In mod-
ern building it is often used as the only heat source in the room.Purmo wall heating may be installed on internal and external walls. Wall heat-ing on external walls requires thermal insulation on external side.
Energy savingOperation parameters for surface heating are much lower than those for radia-tor systems. It allows significant energy savings, resulting from heat losses limi-tation in supply pipes. Often, besides gas and oil, other energy sources are avail-able, like e.g. waste heat or heat pumps, which may not be used in traditionalheating systems due to too low temperature of heating medium. However,temperature obtained by those unconventional heat sources is just perfect forsurface heating.
Heating pipeFor over 30 years there are surface heating systems with plastic pipes. Eithercrosslinked polyethylene pipes or polyethylene pipes with aluminium layer areperfect for such systems. Safety and reliability of heating systems from plasticpipes are the reasons of their growing application range in tap water systems.Life of those pipes considerably exceeds 50 years, also for high operationalparameters.All elements of Purmo surface heating systems are subjected to regular testsin independent institutions, and have all required certificates. Our technicalconsultants will help You to solve problems connected with elements selectionand realization.
QualityUsers and contractors require durable pipes, equipped with layer preventingoxygen penetration into the system. If prices of pipes offered on the market arenot similar to each other, there are for sure differences in their quality.As in surface heating systems pipes are permanently connected with buildingelements, and system defects repair always causes very high costs, pipe selec-
tion is the most important thing, and their high quality should be assuredalready during design stage.All pipes offered by Purmo have quality certificates, issued by independent testinstitutions. They fulfil requirements of appropriate standards and regulationsand assure the highest safety and durability, which is the most important thingfor the surface heating.It is the high quality of Purmo PE-X and Purmo HKS pipes, which makes the basisfor 10 years warranty for all our systems and products.
Wall heating systemThe most often used wall heating system is wet system. Wet system is usuallyused in new buildings and during modernization, and dry system usually duringrenovation and in buildings built in dry technology.Maximum surface temperature must not exceed 35 C. Moreover, already dur-ing designing it is required to take into consideration places, where wall will
be covered by e.g. shelves or hanging cabinets. Exclude those surfaces fromwall heating or precisely define drilling points for fixing expansion bolts. Notemoreover that also standing furniture, e.g. wardrobes, make heat transfer tothe room difficult.Wall linings made from insulation materials, like cork, foam, cloth, woodenwainscot by definition do not cooperate effectively with wall heating system.Decision of lining material selection must be preceded by tests, checking if thegiven material is suitable for wall lining.
Realization in wet systemWall heating system Purmo Railjet may cooperate withcommonly used plasters. Pipes are fixed directly onraw wall with use of plastic strips. Distance betweenpipes is usually 150 mm.As the plaster should be connected with wall in the
best possible way, it is not allowed to fix pipes onthe insulation layer. When wall heating is realizedon external wall, it must be insulated from outside.Maximum temperature in case of gypsum plasters is50 C.Gypsum plaster is spread in one layer so the heatingpipes are covered with 10 mm of mortar layer. Cementand clay plasters are realized in two steps. Pipes mustbe covered with 10 mm layer.Total plaster thickness is 26-28 mm. In order to preventcracking, use special reinforcing mesh.
Pipes fixing stripPipes fixing strip in Purmo Railjet FA9IP08114170000system is made from high quality plastic. It is used for
fixing pipes 14 17 mm in intervals 50, 100, 150, etc.Circuits may be connected individually to PURMOmanifold or e.g. with use of T-pipes to HKS pipe, posi-tioned around the room.
Pipes installationRails are fixed to the wall (usually vertical) in intervals400 500 mm with use of expansion bolts. Purmo railsare equipped with clips, allowing for perfect fixing of14, 16 and 17 mm Purmo pipes usually 100-150 mm.Pipe is positioned in meander form (usually horizon-tally). Additional pipe fixing on arcs may be required.For pipe 14 mm maximum circuit length is 80 m, pres-sure loss should not exceed 20 kPa.
loor heating
34
Water wall heating
Purmo RAILJET system products specificationOrder code Name Dimmension[mm]
FBDXBAC142 0200P0 Pipe HKS PEX/Al/PE - 200 m/coil 14x2FAZ1S34C14A000P0 HKS screw fitting (pipe-manifold) - 10 pcs. 14x2 by 3/4"FA9IP08114170000 Strip for pipe installation,
clip connected 14-17 mm -100 pcs.200x40
FBWMRST024052200 Stainless steel manifolds 1" - M 1" fullyequipped with flow meters - 2 circuits
190 x 330 x 86
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
35/36
loor heating
35
Special applicatins
35
Floor heating special applicationsWater loor heating, due to its unmatched advantages: no visible heating ele-ments, heat transer by radiation on the whole loor surace, assuring propertemperature and thermal comort in places, where it is required, is used in the
ollowing objects: motion activities rooms, e.g. kindergartens, schools or sporthalls, and industrial production and storage halls. Floor heating systems maybe successully used in historical buildings, museums and churches. In coopera-tion o loor system with heat pump with cooling unction or cold water sourceit is possible to decrease rooms temperature in summer.Such heating method is used not only inside. In winter it may be used or keep-ing yards, ramps, access roads and stadiums ree rom snow and ice.
Floor heating sport floor
DesignHeating pipes are positioned in air space o wooden loor structure.They are ixed with clips to special top layer o system insulation.
Elements:DiuPex pipes 20x2 mm or 25x2.3 mm.
Industrial multisection maniolds 5/4 with valves or initial settings.System insulation Rolljet with oamed polystyrene board or Faltjet with poly-urethane oam.
Floor heating in industrial objects
DesignPurmo pipe 20x2 or 25x2.3 mm is ixed with plastic clamps to the lower rein-orcement o concrete slab. Reinorcement and insulation type, as well as slabthickness must be designed by qualiied engineer due to high dynamic loads.Insulation is usually installed as circuit insulation under the concrete slab.However the building supervision may release investor rom that obligationupon his application.Industrial multisection maniolds 5/4 with valves or initial settings.
Floor heating in open spaces
DesignHeating pipes are usually installed directly in the concrete or in sand ballastlayer. Concrete and pavement blocks layer thickness over the pipes should be15 20 cm, depending on designed loads. As the ground oten does not reezedeeper than 80 cm, insulation may be omitted.Due to temperature uniormity the heating pipes spacing should not exceed20 cm. DiuPex heating pipes 20x2 mm or 25x2.3 mm. Industrial multisectionmaniolds 5/4 with valves or initial settings. Taking pressure losses into con-sideration note that adding anti-reezing additives may double them.
Floor heating and cooling
ElementsCombined PURMO loor heating and cooling system is made rom system pipePE-X 16x2 mm, 17x2 mm, 20x2 mm, and multiplayer pipe PE-X/Al/PE or PE-RT/
Al/PE-RT 16x2 mm, 17x2 mm, 20x2 mm, and system insulation Rolljet/Faltjet.The whole thing is covered with standard loor, approximately 65 mm thick.Maniolds or loor heating are equipped with adjustment valves and thermo-static inserts, adapted or thermoelectric heads/actuators assemble.Adjustment is perormed with use o one combined adjustment device or loorheating and cooling with proper sensors.The most disadvantageous thermal load o the system takes place duringcooling, as the supply temperature must be determined and not cause thecondensation. Approximately 15 C is assumed (not less), moreover the supplyand return temperatures dierence is only 2 3 K. For such conditions the pipespacing calculations are perormed. Usually it is positioned quite densely, withmaximum spacing 100 150 mm.
Floor heating sport floor
Floor heating in industrial objects
Floor heating in open spaces
Floor heating and cooling
-
8/3/2019 Purmo Technical Catalogue Under Floor Heating Pipe System UFH HKS 08 2011 ANG
36/36
B
WWW.PURMO.PL