Energy SavingEnergy Saving

Energy Saved is Energy Generated. Saving of Energy is the need of the day. Government is one of the major consumer of

Energy. The Govt. has to lead others by taking

effective steps to save the energy

Page 3: PWD Presentation

Energy SavingEnergy Saving

278 million units of energy per annum are consumed by Maharashtra State Government Office Buildings

This is equal to 105 MW Generation during working hours under the assumption of 10 hours /day, 22 days /month, 12 months /year.

One unit saved is TWO units generated. Annually Rs.111 crores are spent by the

Government on energy bill .

Page 4: PWD Presentation

Energy SavingEnergy Saving

Energy Efficient Lamps and Equipments can save energy bill up to 30 %.

100/60/40 watts bulbs can be replaced by CFL lamps of 22/11/9 watts having power factor more than 0.9.

40/36W Fluo. fittings can be replaced by 28W E+/T5 fluo. fittings or their chokes by electronic chokes.

Page 5: PWD Presentation

Four pillars of successful Four pillars of successful Energy ManagementEnergy Management

Page 6: PWD Presentation

Four pillars of successful Four pillars of successful Energy Management : Energy Management : Key Key ElementsElements

Successful energy management programme needs the total support of senior management.

The other important requirements are A well-charted strategy plan. An effective monitoring system. Adequate technical ability for analyzing and implementing energy

saving options.

In any organization, which does not already possess an energy efficient ethics, good communication downwards from senior officials will be vital first step.

Active participation & planning for the energy management

Page 7: PWD Presentation

Ways of Energy Ways of Energy ConservationConservation

Awareness Replacement of conventional fittings with E+ fluo. fittings Replacement of conventional pumps with submersible

pumps/energy efficient pumps Replacement of old water coolers with energy efficient

water coolers Replacement of GLS lamps with CFL lamps Incorporating timers for passage lights Incorporating digi guards for ACs Incorporating DPSD for compound & street lights

Page 8: PWD Presentation

Ways of Energy Ways of Energy ConservationConservation

Replacement of electric water heaters with solar water heaters

Replacement of water coolers with heat pumps Replacement of resistance type regulators with electronic

regulators Replacement of conventional chokes with electronic chokes Incorporating VFDs for hydro pneumatic systems, pumps &

central AC plants Incorporating 3VF drives for lifts Smart Card (SIM) based Power Controller

Page 9: PWD Presentation

Energy Saving at Vidhan Energy Saving at Vidhan BhavanBhavan

Sr. No.

Year Use of fitting / Equipment

Nos. Capital cost(Rs.

Lacs)

Date of

commis-

ioning

Savingin bill(Rs.

Lacs)

Simplepaybac

k period(yrs)

1 2001-02

VFD for water pump 6 Nos.

8.17 12/01 2.97 2.8

2 2001-02

Power factor correction capacitor panel

350 KVAR

13.8 12/01 5.49 2.5

3 2001-02

E+ 28 W tube fitting in place of 40 W fitting

1493 12.02 2/02 5.37 2.2

4 2001-02

Using reflector for 4 X 2’ X 20 W

1493 3.22 2/02 1.79 1.8

5 2001-02

New reflector with one tube in place of 2 X 40 W tube

1493 3.22 2/02 1.79 1.8An expenditure of An expenditure of Rs. 40.43 lacsRs. 40.43 lacs has accrued saving of has accrued saving of Rs. 17.41 lacsRs. 17.41 lacs per annum. per annum.

Page 10: PWD Presentation

Energy Saving at MantralayaEnergy Saving at MantralayaSr. No.

Year Equipment Used

Quantity

(Nos.)

Cost of installatio

n Rs.Lakhs

Units save

d

Saving in

energy bill

Rs(Lakhs)

Simple pay back Years-Months

1 2001-02

Capacitor panel

180 KVAR

3.66 2.6710 months

2 2002-03

120 KVAR

3.47 4.28

3 2002-03

E+fluo. Tubes

1238 10.78 72933

3.65 2 -11

4 2003-04

E+fluo. Tubes

2705 21.77 159357

7.97 2-8

5 2003-04

Capacitor panel

50 KVAR

- 1.58

6 2004-05

E+fluo. Tubes

3572 27.77 203246

10.16 2 -8

7 2004-05

CFL 28W 810 11.60 122705

6.14 1 -11

An expenditure of An expenditure of Rs. 79.05 lacs Rs. 79.05 lacs accrued saving of accrued saving of Rs. 36.45 lacsRs. 36.45 lacs in four in four years ( 5% increase in load).years ( 5% increase in load).

Page 11: PWD Presentation

9 Watt 11 Watt 2x11W 1x18 W 2x26W 125W 250W 11W 18W

1 Mumbai 10436 269 1003 350 48 1128 1353 123 535 20 0 10 0 2

2 Pune 3127 0 1410 0 641 0 150 233 0 63 526 123 0 0

3 Aurangabad 1397 0 598 0 255 0 43 62 169 0 46 0 6 2

4 Nagpur 2310 0 331 526 16 262 52 52 30 2 264 0 0 0

Total 17270 269 3342 876 960 1390 1598 470 734 85 836 133 6 4

Electronic

choke (Nos.)

DPSD (Nos.)CFLStreet Light (Nos.)

Electronic Regulator

(Nos.)

Solar Street Light

Solar Solar water heate

r

CFL Lamp (Nos.)Sr. No . Name of

Circle

E+ Fitting (Nos.)

Energy Efficient Equipments used in New Govt. Building works

during 2001-2005

By this Demand Side, 822 KW is saved. Saving by Awareness in J.J. Hospital – Units 0.8 MU & Amount Rs. 38.53

Lakhs in three years

Saving by use of VFD in New Administrative Building -- Unit 30,000/year & Amount Rs.1.5 Lakhs/ year

Page 12: PWD Presentation

Energy Saving Proposals Energy Saving Proposals submitted to Govt. for 35 bldgs. submitted to Govt. for 35 bldgs.

attracting EC Act 2001attracting EC Act 2001Sr. No.

Category Present Replacement

(Quantity)

Capital Cost (Rs. lacs)

Energy bill

saving /year(Rs. lacs)

Payback

period(yrs)

1. Fluo. fitting Conventional 40W(76023 Nos.)

E+(28W)(53303 Nos.)

469.06 399.16 1.2

2. Passage Lights:

Conventional 40W fluo. fitting (1896 Nos.)

CFL 11 W(1896 Nos.)

2.84 7.98 0.4

3. Water Pumps

Conventional(61 Nos.)

Submersible(61 Nos.)

18.3 13.97 1.3

4. Passage Lights:

Without Timer(144 Nos.)

With Timer(144 Nos.)

0.3 0.76 0.5

5. Lamps GLS (40/100W)(3374 Nos.)

CFL 11W(3374 Nos.)

5.06 27.75 0.2

Page 13: PWD Presentation

Energy Saving Proposals Energy Saving Proposals submitted to Govt. for 35 bldgs. submitted to Govt. for 35 bldgs.

attracting EC Act 2001attracting EC Act 2001Sr.

No.

Category Present Replacement

Capital Cost (Rs. lacs)

Energy bill

saving /year(Rs. lacs)

Payback

period(yrs)

6. AC units Without Digiguard(539 Nos.)

With Digiguard(539 Nos.)

19.94 12.76 1.6

7. Compound & Flood Lights

Without DPSD(614 Nos.)

With DPSD(614 Nos.)

17.19 9.88 1.74

8. Water Heating System

Electric(1145 Nos.)

Solar(167 Nos.)

480 75.23 6.4

9. Water Cooling Water Coolers(425 Nos.)

Heat Pumps(9 Nos.)

90 32.39 2.7

10.

Hydro Pneumatic System

Without VFD(15 Nos.)

With VFD(15 Nos.)

22.5 6.48 3.5

Page 14: PWD Presentation

Energy Saving Proposals Energy Saving Proposals submitted to Govt. for 35 bldgs. submitted to Govt. for 35 bldgs.

attracting EC Act 2001attracting EC Act 2001Sr. No.

Category Present Replacement

Capital Cost (Rs. lacs)

Energy bill

saving /year(Rs. lacs)

Payback

period(yrs)

11. Water Pumps Without VFD(41 Nos.)

With VFD(41 Nos.)

202.18 41.26 5

12. Lifts Without 3VF drive(19Nos.)

With 3VF drive(19Nos.)

48.94 13.84 3.5

13. Ceiling Fan Regulators

Resistive(6716 Nos.)

Electronic(6716 Nos.)

12.08 12 1

Page 15: PWD Presentation

Sr. No. Present Replace by

Capital Cost for replacement (Rs.

Lacs)

Saving in energy Bill every year (Rs. Lacs)

Pay back Period

14 Water coolers (328 Nos.)

Heat water Pump for Chilled water/ A.C. (151

Nos.)261.76 51.6 5

15Water coolers & L.

P. G. at New Council Hall

Hot & chilled water heat pump system (

6 Nos.) 20.4 7.32 2.8

16Centralised Air condition units

(6 Nos.)

Split AC Units ( 73 Nos) 36.54 37.49 1

17 60/ 80W ceiling fans ( 1728 Nos.)

Energy Efficient ceiling Fans ( 1728 Nos.) 16.03 13.32 1.2

1723.12 763.19 2.26Total ::

Energy Saving Proposals Energy Saving Proposals submitted to Govt. for 35 bldgs. submitted to Govt. for 35 bldgs.

attracting EC Act 2001attracting EC Act 2001

An expenditure of Rs.1723.12 lacs can save 17.09 Millions Energy units per annum & accrues saving of Rs. 763.19 lacs per annum in bill.

Page 16: PWD Presentation

1 Home (Police) 35057 3.09 7386 0.11 0 0.00 3.20 3.012 Home (Jail) 7415 0.65 1653 0.02 0 0.00 0.67 0.643 Law & Judiciary 32288 2.84 5521 0.08 0 0.00 2.92 2.74 Education 46199 4.07 8907 0.13 0 0.00 4.20 3.925 Social Welfare 9342 0.82 2807 0.04 0 0.00 0.86 0.856 Revenue 34907 3.07 7496 0.11 0 0.00 3.18 3

7 Public Works (Non-Resi) 34938 3.07 12772 0.19 287750 5.80 3.26 6.52

8 Pblic Works (Resi) 6084 0.54 1288 0.02 0 0.00 0.56 0.529 Other Administrative. 16759 1.47 2146 0.03 0 0.00 1.50 1.3610 Labour Dept. 92 0.01 16 0.00 0 0.00 0.01 0.0111 Vidhan Bhavan 855 0.08 134 0.00 0 0.00 0.08 0.0712 Public Health 63638 5.60 11385 0.17 0 0.00 5.77 5.3513 Finance 3974 0.35 826 0.01 0 0.00 0.36 0.3414 Animal Husbandry 3245 0.29 638 0.01 0 0.00 0.30 0.2815 Fisheries 861 0.08 334 0.01 0 0.00 0.09 0.0816 Tech. Education 337 0.03 53 0.00 0 0.00 0.03 0.0317 Dairy Deptt. 425 0.04 209 0.00 0 0.00 0.04 0.04

296416 26.10 63571 0.93 287750 5.80 27.03 28.72

Qty (Ltrs)

Capital Cost

Capital Cost

Capital Cost

Capital Cost

Qty (Nos)

Sr. no.

ENERGY SAVING PROPOSAL OF OTHER GOVT. BUILDINGS (Rs. in Crores)

Energy Saving per year

(million units)

Grand Total E+ fittings CFL Fittings

DepartmentQty

(Nos)

Solar Water Heaters

An expenditure of An expenditure of Rs. 27.03 croresRs. 27.03 crores accrues saving of accrues saving of Rs. 12.92 croresRs. 12.92 crores per annum & 28 per annum & 28.72 million units.72 million units . .

Page 17: PWD Presentation

1 Home (Police) 35057 3.09 7386 0.11 4424 10.35 0 0.00 13.55 4.152 Home (Jail) 7415 0.65 1653 0.02 776 1.82 0 0.00 2.49 0.843 Law & Judiciary 32288 2.84 5521 0.08 1952 4.57 0 0.00 7.49 3.24 Education 46199 4.07 8907 0.13 2992 7.00 0 0.00 11.20 4.695 Social Welfare 9342 0.82 2807 0.04 1590 3.72 0 0.00 4.58 1.266 Revenue 34907 3.07 7496 0.11 2937 6.87 0 0.00 10.05 3.76

7 Public Works (Non-Resi) 34938 3.07 12772 0.19 3942 9.22 287750 5.80 18.28 7.54

8 Public Works (Non-Resi) 6084 0.54 1288 0.02 1118 2.62 0 0.00 3.18 0.819 Other Administrative. 16759 1.47 2146 0.03 477 1.12 0 0.00 2.62 1.4810 Labour Dept. 92 0.01 16 0.00 0 0.00 0 0.00 0.01 0.0111 Vidhan Bhavan 855 0.08 134 0.00 72 0.17 0 0.00 0.25 0.0912 Public Health 63638 5.60 11385 0.17 3822 8.94 0 0.00 14.71 6.3313 Finance 3974 0.35 826 0.01 470 1.10 0 0.00 1.46 0.4614 Animal Husbundary 3245 0.29 638 0.01 513 1.20 0 0.00 1.50 0.4115 Fisheries 861 0.08 334 0.01 195 0.46 0 0.00 0.55 0.1316 Tech. Education 337 0.03 53 0.00 35 0.08 0 0.00 0.11 0.0417 Dairy Deptt. 425 0.04 209 0.00 203 0.48 0 0.00 0.52 0.1

296416 26.10 63571 0.93 25518 59.72 287750 5.80 92.55 35.3

Sr. no.

ENERGY SAVING PROPOSAL OF OTHER GOVT. BUILDINGS (Rs. in Crores)

Energy Saving per year

(million units)

Grand Total

Qty (Nos)

E+ fittings CFL Fittings Solar Street Light Fittings

Capital Cost

Qty (Ltrs)

Capital Cost

Capital Cost

Capital Cost

Capital Cost

Qty (Nos)

DepartmentQty

(Nos)

Solar Water Heaters

An expenditure of An expenditure of Rs. 92.55 croresRs. 92.55 crores accrues saving of accrues saving of Rs. 15.89 croresRs. 15.89 crores per annum & per annum & 35.3 million units35.3 million units . .

Page 18: PWD Presentation

Energy Saving in Important Energy Saving in Important Govt.Bldgs : 2004-2005 Govt.Bldgs : 2004-2005 (Rs. In (Rs. In Lacs)Lacs)

2003-04 2004-05 (units) % 2003-04 2004-05 Rs. %

Mantralaya 4037085 3959960 77125 1.91% 260.58 229.94 30.64 11.76%

Navin Vidhan Bhavan 1325600 1225000 100600 7.59% 90.27 74.04 16.23 17.98%

Mumbai High Court 681996 675855 6141 0.90% 46.87 41.27 5.6 11.95%

Manora 2346520 2294500 52020 2.22% 159.59 157.17 2.42 1.52%

J J Hospital 1570770 1561000 9770 0.62% 60.62 52.47 8.15 13.44%

9961971 9716315 245656 2.47% 617.93 554.89 63.04 10.20%

Energy Bill Energy SavingSaving

Total

Consumption in unitsName of the

Building

Page 19: PWD Presentation

Energy Saving of Electrical Energy Saving of Electrical Wing Offices of PWDWing Offices of PWD

Units Percentage1 2 3 5 6 8 9

1 Mar-04 22125 Mar-05 17063 5062 22.88

2 Apr-04 19691 Apr-05 16726 2965 15.06

3 May-04 24379 May-05 20770 3609 14.80

4 Jun-04 21280 Jun-05 16221 5059 23.77

Annual Energy Saving of Electrical Wing

DiffernceSr. No. Month & Year Units Month &

Yearunits

Consumed

Page 20: PWD Presentation

BOT Pilot Projects of PWD BOT Pilot Projects of PWD BldgsBldgs

MLA Hostel, Nagpur Ravi Bhavan, Nagpur Golf Club, Nashik (Circuit House) Inspection Bunglow, Pune Subhedari Rest House, Aurangabad

Page 21: PWD Presentation

BOT Pilot Projects of PWD BOT Pilot Projects of PWD Bldgs : Abstract Bldgs : Abstract (Rs. In Lacs)(Rs. In Lacs)

Sr. No. Name of the Building No. of

Suits

LPD Capacity

(Ltrs)

E+ Fittings (Nos.)

CFL Fittings (Nos.)

Capital Cost

Expected Net

Saving

Payback Period IRR

1 M.L.A. Hostel, Nagpur 386 39000 1158 1644 70.71 17.23 7 YRS 15.46%

2 Ravi Bhavan, Nagpur 128 6600 340 130 14.4 3.47 7 YRS 15.08%

3 Golf Club, Nashik 51 4700 58 139 9.66 2.37 7 YRS 15.69%

4 Subhedari Rest House, Aurangabad 45 4500 177 256 12.43 2.62 8 YRS 14.01%

5 Inspection Bunglow, Pune 56 8400 200 0 15.31 4.56 5 YRS 14.93%

666 58700 1933 2169 122.51 30.25Total

Page 22: PWD Presentation

Similar Proposals for BOT can be implemented for other departments after their assurance to share the saving with the BOT operator.

Page 23: PWD Presentation

One Unit of Energy saved is One Unit of Energy saved is equivalent to Two Units of Energy equivalent to Two Units of Energy

Generated.Generated.