pwm harmonic signature based islanding detection for a ... · pwm harmonic signature based...

11
This is a repository copy of PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping. White Rose Research Online URL for this paper: http://eprints.whiterose.ac.uk/110053/ Version: Accepted Version Article: Colombage, K., Wang, J. orcid.org/0000-0003-4870-3744, Gould, C. et al. (1 more author) (2017) PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping. IEEE Transactions on Industry Applications, 53 (1). pp. 411-419. ISSN 0093-9994 https://doi.org/10.1109/TIA.2016.2611671 [email protected] https://eprints.whiterose.ac.uk/ Reuse Unless indicated otherwise, fulltext items are protected by copyright with all rights reserved. The copyright exception in section 29 of the Copyright, Designs and Patents Act 1988 allows the making of a single copy solely for the purpose of non-commercial research or private study within the limits of fair dealing. The publisher or other rights-holder may allow further reproduction and re-use of this version - refer to the White Rose Research Online record for this item. Where records identify the publisher as the copyright holder, users can verify any specific terms of use on the publisher’s website. Takedown If you consider content in White Rose Research Online to be in breach of UK law, please notify us by emailing [email protected] including the URL of the record and the reason for the withdrawal request.

Upload: others

Post on 23-Mar-2020

16 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

This is a repository copy of PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping.

White Rose Research Online URL for this paper:http://eprints.whiterose.ac.uk/110053/

Version: Accepted Version

Article:

Colombage, K., Wang, J. orcid.org/0000-0003-4870-3744, Gould, C. et al. (1 more author) (2017) PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping. IEEE Transactions on Industry Applications, 53 (1). pp. 411-419. ISSN 0093-9994

https://doi.org/10.1109/TIA.2016.2611671

[email protected]://eprints.whiterose.ac.uk/

Reuse

Unless indicated otherwise, fulltext items are protected by copyright with all rights reserved. The copyright exception in section 29 of the Copyright, Designs and Patents Act 1988 allows the making of a single copy solely for the purpose of non-commercial research or private study within the limits of fair dealing. The publisher or other rights-holder may allow further reproduction and re-use of this version - refer to the White Rose Research Online record for this item. Where records identify the publisher as the copyright holder, users can verify any specific terms of use on the publisher’s website.

Takedown

If you consider content in White Rose Research Online to be in breach of UK law, please notify us by emailing [email protected] including the URL of the record and the reason for the withdrawal request.

Page 2: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

PWM Harmonic Signature Based Islanding Detection

for a Single-Phase Inverter with PWM Frequency

Hopping

Kalhana Colombage (Student Member, IEEE), Jiabin Wang (Senior Member, IEEE), Chris Gould (Member, IEEE),

Chaohui Liu (Student Member, IEEE)

Department of Electronic and Electrical Engineering

The University of Sheffield

Sheffield, S1 3JD, UK

[email protected]

Abstract -- Distributed generation (DG) has gained

popularity in recent years due to the increasing requirement

for renewable power sources. A problem that exists with DG

systems is the islanding of DG units that creates safety issues

for personnel as well as the potential for damage to utility

infrastructure. Therefore, islanding detection methods are

utilized to mitigate the risk of islanded operation of DG units.

A new passive method of islanding detection based on the

signature of the PWM voltage harmonics is proposed. The

viability of the algorithm is investigated with the use of an

analytical and time domain model of the inverter and further

validated with experimental results. Furthermore, an

extension of the detection scheme is proposed for use in multi-

inverter scenarios composed of adaptive frequency hopping to

eliminate unwanted tripping.

Keywords—passive islanding detection, PWM harmonic

signature, frequency hopping

I.! INTRODUCTION

Islanding is defined as the condition where the

distributed generator (DG) continues to operate with local

loads after the utility grid has been disconnected [1].

Unintentional islanding is undesired since it is a hazard to

utility workers and causes possible damage to equipment as

a result of asynchronous re-closure. Asynchronous re-

closure occurs when the utility recloses with an energized

DG which is out of phase with the utility and can therefore

cause large currents to flow, hence possibly damaging the

DG converter infrastructure [2]. Islanding also has the

potential to interfere with the power restoration service of

the utility [3].

According to the IEEE1547 standard for interconnecting

distributed resources with electric power systems, it is a

requirement for grid connected DG systems to be able to

detect islanding within 2 seconds and cease to energize the

area electrical power system (EPS) that is coupled through

the point of common coupling (PCC) [4].

As a consequence, a diverse range of islanding detection

methods have been developed and reported in literature each

with their merits and limitations.

The two main categories of islanding detection are

passive and active methods. Passive methods consist of the

detection of islanding through non-invasive means whereas

active methods introduce a small perturbation to the grid

current and thereby has some impact on power quality. The

advantage of the active methods is the reduction/elimination

of the non-detection zone (NDZ). In addition to the two

main groups, there are also detection methods that rely on

communication with the grid and inverter.

A variety of passive methods have been reported in

literature such as over/under voltage protection (OVP/UVP)

and over/under frequency protection (OFP/UFP) methods

[3]. These basic types of detection methods have a large

NDZ and therefore are not sufficient in most applications of

DG systems. Other types of passive detection methods

include voltage phase jump [5], harmonic voltage or current

detection methods [6] as well as the passive method

proposed in [7] which monitors the oscillations in rate of

change of frequency at the PCC.

The harmonics based methods consist of either detecting

change in the total harmonic distortion [6], detecting

changes in the individual low order harmonics [8], or

monitoring the changes in the switching harmonics due to

the PWM operation of the inverter [10].

A few examples of active methods of detection are, slide-

mode frequency shift (SMS) [11], active frequency drift and

Sandia frequency shift (SFS) [11-14], Sandia voltage shift

(SVS) [11], methods based on impedance measurement by

harmonic injection [15-18], impedance measurement by

output power shift [8] and impedance measurement by

active frequency drift [9].

Other types of active methods include DQ-frame based

feedback methods [19]; methods based on the perturbation

of the reactive power [20, 21, 22] and second order

generalized integrator (SOGI) PLL based methods [23] that

introduce a small disturbance in the phase of the inverter

current. A more recent method involves a multi principle

local area measurement and communication based scheme

where the islanding method is applied to a refinery power

system [24].

Page 3: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

Although active methods significantly decrease the NDZ,

they share the disadvantage of degrading the power quality

to some degree and some of the active methods have the

disadvantage of causing instability to the grid in multi-

inverter scenarios [25]. Furthermore, with the common

prevalence of photovoltaic (PV) inverter systems, there may

be situations where the islanding detection mechanisms of

multiple inverter systems which are connected to the same

utility, fail to detect islanding due to the interaction between

these systems [2].

II.! PROPOSED METHOD

This paper presents a new detection technique that has

been developed to overcome the drawbacks of islanding

detection schemes reported in literature. The proposed

islanding detection method consists of monitoring the

frequency spectrum of the voltage at the PCC (VPCC). When

islanding occurs, the shunt impedance at the PCC for high

frequencies increases and this results in the increase of

PWM voltage harmonics. A fast Fourier transform (FFT) is

performed on the VPCC signal for each cycle of the

fundamental frequency after which the switching harmonic

sidebands are compared with the noise floor to obtain a

relative magnitude. A look up table (LUT) is utilized to

compare the obtained magnitude to the trip value for the

given modulation index. The decision logic then determines

whether islanding has taken place and if so, the inverter is

shut down. Two sideband harmonic components are used as

the signature of the inverter’s harmonics for the detection of

islanding which provides a degree of immunity from false

tripping due to external noise sources.

Whilst PWM harmonic voltage based anti-islanding has

been reported in [10], no experimental demonstration has

been performed. The proposed method differs from the

method reported in [10] through utilisation of multiple

harmonic components, thereby detecting the unique

signature of the inverter under consideration for the

purposes of noise immunity. Further extension of the

algorithm whereby the PWM frequency is varied upon

encountering multi-inverter interference is also investigated.

Furthermore, the limitations common to both the

proposed method and the method reported in [10] due to

large capacitive loads, as well as the positive effect of series

impedance of the capacitive load on the ease of detection

are investigated.

III.!MODELLING OF INVERTER LCL FILTER AND UTILITY

GRID

In order to analyze the behaviour of the grid-connected

inverter upon islanding, it is necessary to establish a model

of the system at the high frequency level. The schematic

given in Fig. 1 represents the inverter’s LCL filter, the RLC

load and the grid. The RL represents a combination of the

most common resistive and inductive loads while C

represents capacitance for any power factor correction or

harmonic filtering. The grid can be considered a short

circuit at the high frequencies of interest due to the large

capacitor banks that are common for power factor

correction. However, the series impedance (Zgrid) of the

power lines must be considered in the model. The circuit

breaker (SW1) represents the breaking point when islanding

occurs.

Fig. 1.! Equivalent model of inverter, RLC load and grid

The high frequency voltage harmonics are generated in

the inverter due to the voltage source converter’s (VSC)

PWM operation and the individual harmonic components

can be quantified as given in (1) [26]. For the H-bridge

inverter under investigation, unipolar PWM modulation

scheme is utilized and therefore the harmonics appear

centred around integer multiples of the switching frequency

(10 kHz), starting from double the switching frequency

onwards as illustrated in Fig. 2, where the harmonic orders

are normalized to the 50 Hz fundamental. As can be seen,

the two side bands at 20 kHz ±50 Hz have the highest

magnitude.

Vinv

t( ) =Vdc

Mcos ωot( )+

4Vdc

πm=1

∑n=−∞

∑1

2mJ

2n−1mπ M( )cos m+ n−1⎡⎣ ⎤⎦π( )

cos 2mωsw

t + 2n−1⎡⎣ ⎤⎦ωot( )

(1)

According to IEEE standard 519-1992, current

harmonics over the 35th

order generated by the inverter must

be lower than 0.3% of the maximum load current for short

circuit current ratios lower than 20. Therefore the inverter

LCL filter can be designed to meet these regulations. For the

purposes of analysis and experiment, the following inverter

specifications given in Table I are used.

Fig. 2.! Harmonics of unipolar PWM VSC switching at 10 kHz

L2

H-Bridge

VSCR L

L1

R1

C1C

ZgridSW1

PCC

Page 4: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

TABLE I. ! INVERTER SPECIFICATIONS

Inverter active power L1 L2 C1 R1

2.2 kW 5 mH 145 µH 6.8 µF 1.2 Ω

For the ease of analysis, the inverter consisting of the

VSC and LCL filter can be simplified by a Thévenin

equivalent circuit as shown in Fig. 3 where eth(h) and Zth(h)

are given by (2) and (3) respectively. The impedance seen

by the inverter before and after islanding for the parallel

RLC load is defined by (4) and (5). Therefore the voltage

harmonics present at the PCC before and after islanding can

be evaluated as given in (6) and (7).

Fig. 3.! Thévenin equivalent circuit of inverter with RLC load

eth

h( ) =1+ jω

hR

1C

1

1+ jωhR

1C

1−ω

h2L

1C

1

.Vinv

h( )

(2)

Zth

h( ) =

jωh

L1

1+ jωhR

1C

1( )+

L2

1+ jωhR

1C

1−ω

h2L

1C

1( )

⎨⎪

⎩⎪

⎬⎪

⎭⎪

1+ jωhR

1C

1−ω

h2L

1C

1

(3)

Z

pre−islandingh( ) = R ! L !C ! Z

grid

(4)

Z

post−islandingh( ) = R ! L !C

(5)

VPCC− pre−islanding

h( ) =e

thh( )

Zth

h( )+ Zpre−islanding

h( )

. Zpre−islanding

h( )

(6)

VPCC− post−islanding

h( ) =e

thh( )

Zth

h( )+ Zpost−islanding

h( )

. Zpost−islanding

h( )

(7)

It is clear that during islanding, the impedance at the

PCC for switching frequencies increases due to the absence

of the low impedance shunt component of the grid. It is this

increase that also causes an increase in the voltage

harmonics that appear at the PCC, which is the basis of the

detection method. However, as the capacitance of the RLC

load increases, the post-islanding impedance for the

switching frequencies decreases. Therefore the difference

between the highest level of non-islanded state voltage

ripple and islanded state voltage ripple reduce to levels that

are not detectable for higher values of load capacitance.

IEEE standard 929 states that the islanding detection

method must be able to detect islanding for an RLC load

that is resonant at the grid frequency and having a quality

factor under 2.5. In order to quantify the detectable zone as

a function of load capacitance C, the following Fig. 4 is

presented whereby the grid impedance, Zgrid, at high PWM

frequencies is assumed to be zero for a 2.2 kW power level.

The figure shows the variation of harmonic voltage

difference ΔV(h) before and after islanding for an RLC load

resonant at 50 Hz.

Fig. 4.! Difference in voltage ripple (20.05 kHz) for an RLC resonant load with varying load capacitance

Although the ideal grid condition of 0 Ω for high

frequencies has been assumed for analysis of the detection

zone, in practice the series grid inductance at the switching

frequency will be a finite value, which sets the baseline

value of the voltage harmonics above which the trip

threshold lies. Furthermore, in reality the parallel RLC load

will have a series impedance component which represents

cable effect at the switching frequency as well as ESR of

the load capacitance and load inductance as shown in Fig.

5.

Fig. 5.! RLC load with parasitic impedance elements

TABLE II. ! CONDITIONS FOR THE RIPPLE VOLTAGE ANALYSIS

Symbol Description Value

P Inverter active power 2.2 kW

R Load resistance 26 Ω

R L C

Zgrid

SW1

PCC

eth(h)

Zth

R L C

Resr

Zrlc

RL

Zgrid

Zth

Page 5: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

Symbol Description Value

C Load capacitance 0 to 350 µF sweep

RL Inductor series resistance 10 mΩ

Resr Capacitor ESR 10 mΩ

|Zrlc (20 kHz)| RLC series impedance 0 to 5 Ω

|Zgrid (20 kHz)| Grid impedance 2.5 Ω

M Modulation index 0.62

Fig. 6.! Voltage ripple after islanding as a function of load capacitance (C)

and series impedance at 20 kHz (|Zrlc (20 kHz)|)

Fig. 6 shows the variation in post-islanded switching

voltage ripple (20.05 kHz) present at the PCC for the

conditions given in Table II for an RLC load resonant at 50

Hz (The value for L is chosen for resonance at 50 Hz).

In Fig. 6, islanding is detectable if the magnitude of the

post islanding voltage ripple lies above the detection

threshold plane. The detection threshold plane is defined as

a value that is 5% larger than the worst-case value of

voltage ripple present under normal operation (i.e. when no

RLC load is connected to the inverter and the inverter is not

islanded). It is found that islanding is detectable for all

values of series impedance, |Zrlc (20 kHz)| for load

capacitances that are under 3.65 µF. For series impedances

higher than 2.75 Ω, islanding is detectable for all values of

load capacitance. The effect of spurious noise that can be

present in the sensed voltage is minimized by comparing

both harmonic components (19.95 kHz and 20.05 kHz) to

the threshold values.

IV.! ISLANDING DETECTION

A.! Detection Algorithm

The block diagram of the islanding detection algorithm

is illustrated in Fig. 7 and the detailed flow chart is given in

Fig. 8 (a). Voltage at the PCC (Vg) is first attenuated after

which it is band-pass filtered. This stage removes the

fundamental (50 Hz) signal thereby maximising the ADC’s

dynamic range as well as removing out-of-band signals that

are not of interest. The ADC digitises the filtered signal

after which the signal is processed in the FPGA. The data

processing is overseen by the control logic, which first

takes 8192 data samples (20 ms of data = 1 cycle of the

fundamental) from the ADC to the FIFO memory and

initiates the FFT transform. The higher sampling frequency

and hence the 8k size for the FFT is used to increase the

FFT process gain, thereby increasing the signal-to-noise

ratio (SNR) as the design is a proof of concept. For actual

implementation, the sampling rate and resulting FFT size

may be reduced dramatically. After the data is processed

through the FFT logic, data points except the harmonic

sideband components are averaged to obtain the noise

floor. The level of the noise floor is subsequently checked

for any interference as a form of sanity check. The final

part of the algorithm is the comparator logic, which

compares the 2 harmonic components (19.95 kHz and

20.05 kHz) to the detection threshold in the LUT

(predefined as worst-case ripple +5% for the operating

power range). If both components are above the trip limit,

the logic asserts the islanding detected signal. This process

repeats itself every ~20 ms (20 ms capture window + FFT

process time which depends on the FPGA speed and actual

FFT size used in final implementation) and therefore the

typical detection time is also ~20 ms.

Fig. 7.! Block diagram of islanding detection algorithm

Fig. 8.! (a) Islanding detection algorithm. (b) Islanding detection

algorithm for multi-inverter operation

BPFAttenuation(-34.32 dB)

ADC409.6 kSPS

Buffer

Control FFT

CompareLUT

Islanded?

Vg

Start Inverter

Capture 20 ms of samples

FFT

Average noise floor

Is noise floor below

threshold?

Compare harmonics

Are the harmonics above

threshold?

No

No

Yes

Yes

Islanded

Capture 20 ms of samples

FFT

Average noise floor

Is noise floor below

threshold?

Compare harmonics

Are the harmonics above

threshold?

No

No

Yes

Start inverter

Scan frequency spectrum

Yes

Scan spectrum & change PWM

frequency

Capture 20 ms of samples

FFT

Average noise floor

Is noise floor below

threshold?

Compare harmonics

Are the harmonics above

threshold?

Islanded

No

Yes

No

(a) (b)

Yes

Page 6: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

B.! Noise immunity from other switching converters

It is possible that other power converter systems

operating nearby to the inverter could cause a false trip if

the external systems operate at the same switching

frequency, thereby causing the magnitude of the voltage

harmonics to exceed the threshold value. If noise immunity

from other switching converters is a design criterion, the

detection logic can be configured to dynamically change the

inverter PWM frequency for the subsequent cycle of

fundamental frequency upon detection of the first trip

condition. The 2nd

PWM modulation frequency to be

‘hopped’ to is determined by scanning the adjacent

spectrum (20 kHz ±4 kHz), and selecting a frequency that

has a low level of noise present, and is an integer multiple of

the grid frequency. If the spectrum of the subsequent cycle

also matches the sideband characteristics for islanding

condition, it can be determined that actual islanding has

taken place and inverter operation ceased. The detailed flow

chart of the islanding detection algorithm for multi-inverter

operation is illustrated in Fig. 8 (b).

It must be noted that the amount of inverters that can be

supported by the islanding detection algorithm is limited to

the spectral bandwidth (20 kHz ± 4 kHz in this instance) and

therefore optimum utilization may be obtained by

interleaving the spectrum. For instance, if ±3 sideband

harmonics around 20 kHz are considered (19.75 to 20.25

kHz), it is observed that the harmonics are separated by 100

Hz and hence occupies a bandwidth of 500 Hz. Therefore, it

is possible to interleave another inverter between the

harmonic spurs that are separated by 100 Hz, yielding a total

bandwidth of 600 Hz for 2 inverters. Therefore, the 16 kHz -

24 kHz band can support 13 pairs of inverters, or 26 in total.

As an example, in a residential application, each utility

phase in a neighbourhood may contain 26 separate inverters.

Each inverter must therefore scan the available band and

self-allocate a suitable switching frequency before initiating

power switching.

V.! SIMULATION OF ISLANDING ALGORITHM

The algorithm has been simulated in MATLAB using the

SimPowerSystems toolbox to validate its performance. The

first simulation test case consists of islanding under an RLC

load that is resonant at 50 Hz where the RLC parameters are

listed in Table III. Furthermore, the PWM frequency

hopping multi-inverter (2 inverters simulated) islanding

detection algorithm has been validated in Simulink for

which the conditions are also shown in Table III.

TABLE III. ! SIMULATION TEST CONDITIONS

Parameter RLC Load (Resonant) Test Multi Inverter Test

R 26.18 Ω 13.09 Ω

L 33.77 mH Not Used

C 300 µF Not Used

RL 10 mΩ N/A

Resr 10 mΩ N/A

Parameter RLC Load (Resonant) Test Multi Inverter Test

|Zrlc (20 kHz)| 2.75 Ω N/A

|Zgrid (20 kHz)| 2.5 Ω 2.5 Ω

A.! Simulation case 1 – RLC resonant load

Since the RLC load is resonant at 50 Hz, the islanding

condition lies in the NDZ of the OVP/UVP and OFP/UFP

methods. Fig. 9 and Fig. 10 show the VPCC, inverter current

and VPCC spectral content variation over time. It can be

observed that the islanding is successfully detected after 20

ms (1 electrical cycle) after islanding occurs.

After islanding, the magnitude and the frequency of

VPCC’s fundamental component continue to be unaffected,

but the voltage ripple of the 19.95 kHz component (and

20.05 kHz) increases to 77 mV from 49 mV after islanding.

Therefore islanding is successfully detected, as the detection

threshold is 76 mV.

Fig. 9.! VPCC, inverter current and VPCC frequency (RLC Load)

Fig. 10.!Time domain plot of the VPCC spectral content (RLC Load)

B.! Simulation case 2 – detection of islanding under

multiple inverter operation

In the situation where immunity from false tripping due

to other converters operating with the same PWM frequency

is required, the adaptive PWM hopping method can be used

at the cost of increasing the detection time from ~20 ms to

~40 ms (2 electrical cycles).

The simulation can be summarized as follows, where the

device under test in which the islanding detection algorithm

Page 7: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

is applied is referred to as ‘Inverter 1’ and the external

system that causes interference is referred to as ‘Inverter 2’.

Initially ‘Inverter 2’ is non-operational and ‘Inverter 1’

feeds power to the utility grid. At t = 0.6 s, ‘Inverter 2’ starts

operating at the same 10 kHz device switching frequency

(20 kHz harmonics generated), which causes the harmonics

seen at the PCC to increase as shown in Fig. 11.

Fig. 11.!Time domain variation of the VPCC spectral content (2 inverter case)

At t = 0.62 s, upon detection that the harmonic voltage

limits have been exceeded, the islanding prevention

algorithm of ‘Inverter 1’ scans the adjacent spectrum for a

suitable frequency with low interference, and changes its

PWM frequency to 10.5 kHz (harmonics at 21 kHz). After

the subsequent electrical cycle (at t = 0.64 s), the FFT of

VPCC reveals that the harmonic spectrum for ‘Inverter 1’ is

below the limits that would be identified as being islanded.

Therefore ‘Inverter 1’ continues to operate at 21 kHz. At t =

0.68 s, actual islanding occurs where the breaker opens and

therefore the 2 inverters (both operating at 2.2 kW) continue

to power the local resistive load. At t = 0.7, the islanding

detection algorithm detects the increased voltage harmonics

and therefore changes the PWM frequency to 9.5 kHz

(causing voltage harmonics to appear at 19 kHz). In the

following electrical cycle (t = 0.72), it can be seen in Fig. 11

that despite the frequency jump, the harmonics are still at

the increased level (234 mV). Therefore, at t = 0.72 s,

islanding is detected since the algorithm detected increased

harmonics in 2 consecutive cycles of the grid voltage.

The proposed algorithm for islanding detection has

therefore been shown to provide immunity from false

tripping due to external power converters operating at the

same PWM frequency.

VI.!DESIGN OF ISLANDING DETECTION HARDWARE

A.! Voltage detection hardware design

The detection of the small signal high frequency

components present at the PCC can be achieved by

sampling the grid voltage through an ADC converter.

However, since most commercially available voltage

transducers are not able to detect signals with bandwidth

exceeding 20 kHz, a resistor divider based circuit is

designed where the isolation between the high voltage side

and the low voltage controller is introduced after the ADC

stage with the use of ADUM1400 digital isolators.

The resistor divider attenuates the grid voltage by a

factor of 52 (34.32 dB) in order to reduce the peak value of

the signal to under ±7 V so as to be compatible with the

analogue signal conditioning circuit.

In order to maximize the dynamic range of the ADC, the

fundamental grid frequency component is removed by

filtering and the remaining high frequency signal is

amplified prior to digitisation. An active band-pass filter

was designed for this purpose, which also serves as the

anti-aliasing filter for the ADC. Fig. 12 shows the

frequency response of the 4th

order multiple feedback

Chebyshev band pass filter that was designed for the

filtering. Since the dominant switching harmonics appear at

20 kHz, the pass-band of the filter was chosen to be

between 16 kHz-24 kHz with a gain of 34 dB and

attenuation at the fundamental frequency (50 Hz) of -87

dB.

Fig. 12.!Voltage sensing circuit band pass filter frequency response

Fig. 13.!Band pass filter schematic

This configuration allows the full dynamic range of the

ADC to be utilized whilst preventing saturation of the ADC

at the highest value of ripple voltage (i.e. when islanding

takes place with a purely resistive load). The schematic of

the op-amp based filter circuit is shown in Fig. 13. A 16-bit

SAR ADC converter (ADS8422) thereafter digitises the

signal with a sampling frequency of 409.6 kSPS. The ADC

output is carried in an 8-bit data bus and therefore the data

bus is clocked at twice the sampling frequency. The ADC is

interfaced through three ADUM1400 digital isolator chips,

which provide the galvanic isolation required for safety. An

NI cRIO-9082 controller is used for processing the data for

the experimental demonstration.

Frequency (Hz)10

110

210

310

410

510

6

Gain

(d

B)

-140

-120

-100

-80

-60

-40

-20

0

20

40

-

+

R1

R3

C1

C2

R2

-

+

R4

R6

C3

C4

R5

Vout

Vin

Page 8: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

B.! Inverter current detection circuit hardware design

A current sensing circuit has been designed with similar

band pass characteristics as the voltage sensing circuit with

an independent ADC. Although the current sensing circuit is

not used in the detection of islanding, it serves the purpose

of measuring the grid impedance at 20 kHz frequency for

analysis purposes.

The current sensing element consists of a 10 mΩ shunt

resistor through which the inverter current passes. The

voltage signal that appears across the resistor due to the

PWM ripple current is small in magnitude and therefore the

succeeding filter stage is designed with a high gain at the

pass band frequency. For instance, if the ripple current

magnitude is assumed to be 0.3% of the fundamental

current, the rms value of voltage present across the shunt

resistor due to the ripple current is only 275 µV.

The filter circuit consists of a 6th

order multiple feedback

Chebyshev band pass filter with a pass band of 16 kHz-24

kHz, pass band gain of 60 dB and attenuation of -115.7 dB

at 50 Hz. Since the filter contains 6 poles, it is implemented

with 3 op-amps.

VII.!EXPERIMENTAL RESULTS

The experimental setup used for the islanding tests is

shown in Fig. 14. The inverter is connected to the grid and

the load via a low frequency (50 Hz) isolation transformer.

A dedicated isolation and data acquisition board is designed

and constructed. The inverter control and island detetion

algorithms are implemented on NI CRIO-9082.

Fig. 14.!Experimental setup that was used for islanding test. (a) Low

frequency transformer based inverter. (b) Inductor (318 mH) used for RLC

test. (c) Islanding detection data acquisition circuit (d) NI cRIO-9082 used for data processing and detection algorithm

A.! Estimation of grid impedance

The magnitude of the grid impedance at 20 kHz

(|Zgrid(20 kHz)|) can be estimated by measuring the

magnitude of the high frequency components of VPCC and

Ig during operation of the inverter when the RLC load is not

connected. The results that were obtained for the utility grid

of the laboratory when the inverter was operating at 2.2 kW

are given in Table IV.

TABLE IV. ! ESTIMATED GRID IMPEDANCE FROM MEASURED VALUES

OF VOLTAGE AND CURRENT RIPPLE

Parameter Value Parameter Value

|VPCC(19.95 kHz)| 73.4 mV |VPCC(20.05 kHz)| 72.2 mV

|Ig(19.95 kHz)| 30.0 mA |Ig(20.05 kHz)| 30.1 mA

|Zgrid(19.95 kHz)| 2.44 Ω |Zgrid(20.05 kHz)| 2.39 Ω

The experimentally derived high frequency grid

impedance value has been utilized as a starting point for

determining the worst-case ripple magnitude. It must be

noted that in practical realization of the system, the

maximum acceptable grid impedance for high frequencies

must be determined on a case-by-case basis dependant on

the grid configuration (for which the detailed analysis is

beyond the scope of this paper).

B.! Resistive load islanding test

Experimental validation has been carried out for an

islanding condition with a purely resistive load (26.2 Ω) at

2.2 kW, and the results are depicted in Fig. 15 and Fig. 16.

In Fig. 15, the band pass filtered ADC captured data is

shown together with the magnitude of the 19.95 kHz voltage

harmonic component (from the FFT of the band pass

filtered signal). The islanding takes place at t = 0.011s, and

the system detects the islanding at 0.02 s (9 ms detection

time). Since the FFT is performed for each cycle (20 ms),

the first FFT magnitude value is lower than the steady-state

islanded magnitude since the FFT time window contains

both islanded and non-islanded data in the first cycle. It

must be noted that the system is allowed to operate after the

islanding is detected to observe the behaviour under

islanding condition. Since the resistive load is not resonant

at 50 Hz and due to the difficulty in having an exactly

matched active load in the experiment, the dynamic

behaviour of the system is such that the inverter output

frequency increases after the islanding and the inverter is

subsequently shut down after a few cycles for protection. Of

course, it is possible to implement droop control after the

islanding for stable islanded operation, but this is beyond

the current scope. Nevertheless, it is evident that the

resistive load islanding is detectable.

Transformer

Inverter

Lg

C

(a) (b)

(c)

(d)

Page 9: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

Fig. 15.!Islanding test waveforms for resistive load test (top: voltage and

inverter current at PCC, middle: the band pass filtered signal from the ADC, bottom: the FFT magnitude of the 19.95 kHz component)

Fig. 16 shows the pre and post islanding (steady state)

voltage ripple. The pre-islanding voltage ripple of the 19.95

kHz component is 71.57 mV and under post islanding, it

reaches 612.8 mV. The values obtained experimentally

compare to the analytical prediction of 70.5 mV and 444.3

mV, and to the numerical simulation results of 72.19 mV

and 442.2 mV for pre- and post-islanding cases,

respectively. It can be seen that the predicted and measured

pre-islanding ripple matches. The higher value of post

islanding voltage ripple can be attributed to the series

inductance of the load resistor bank, which is neglected in

analytical prediction and in numerical simulation.

Fig. 16.!Islanding test frequency spectrum for resistive load test

C.! RLC load islanding test

The RLC load-based islanding detection test has been

carried out with the conditions depicted in Table V for an

inverter power output of 2.2 kW. The resulting waveforms

are presented in Fig. 17 and the spectrum of the switching

frequency harmonics in Fig. 18. Islanding takes place at t =

0.051 s and is detected at t = 0.06 s (9 ms detection time).

Similar to the resistive case, the first FFT output after the

islanding contains both pre and post islanding data, and

therefore the magnitude is initially lower than the steady-

state islanded harmonic magnitude. Furthermore, at t =

0.075 s, contact bounce due to arcing occurs on the relay

that emulates the islanding andextinguishes at t = 0.082 s.

Although this contact bounce causes a transient in the

measured voltage for 7 ms, the experiment outcome is not

affected. It can be seen that islanding is successfully

detected for the RLC load under consideration. The pre-

islanding voltage ripple of the 19.95 kHz component is

55.1 mV and after islanding, it reaches 132.7 mV. The

values obtained experimentally compare to the analytical

prediction of 57.6 mV and 131.2 mV for pre- and post-

islanding cases, respectively. It is observed that the

predicted and measured post-islanding ripples match better

than the purely resistive test case. This is because the load

resistor bank’s series inductance is the reason for the large

difference between the prediction and measurement that

appears during the resistive load test. However, it can be

seen that in the RLC load test, the capacitance is the

dominant shunt component for high frequencies and

therefore the series inductance of the load resistor has a

negligible affect on the post-islanding ripple.

In simulations, the system when islanded with a RLC

load that is resonant at 50 Hz is capable of continuous

operation. However, during the experimental tests with an

RLC load, it was observed that the system becomes

unstable after ~0.5 s of the islanded operation. This is

attributed to the noise and other disturbances that occur in

the experiment because the PLL and the current control

loop is highly sensitive to these disturbances and therefore

causes the voltage/frequency to drift beyond the safe limits.

TABLE V. ! RLC TEST CONDITIONS

R

(Ω)

L

(mH)

C

(µF)

RL

(Ω)

Resr

(mΩ)

|Zrlc (20 kHz)|

(Ω)

26.4 318 32.3 6.28 20 5

Fig. 17.!Islanding test waveforms for RLC load test (top: voltage and

inverter current at PCC, middle: the band pass filtered signal from the ADC, bottom: the FFT magnitude of the 19.95 kHz component)

Frequency (kHz)18 18.5 19 19.5 20 20.5 21 21.5 22

VP

CC

(m

V)

0

100

200

300

400

500

600

700Before IslandingAfter Islanding

X: 19.95Y: 71.57

X: 19.95Y: 612.8

Page 10: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

Fig. 18.!Islanding test frequency spectrum for RLC load test

VIII.!CONCLUSION

A new islanding detection algorithm has been presented

which has the advantage of multi-inverter compatibility

compared to similar voltage harmonic monitoring methods.

Furthermore, the difficulty in detection for PWM

harmonic based methods when capacitive loads are present

has been analyzed and the detectable conditions as a

function of the load’s characteristics established. The

algorithm has been simulated and two test cases

demonstrated experimentally in hardware.

The detection hardware designed and demonstrated

herein has been over-engineered since the exercise was

purely as a proof-of-concept. It follows from analysis of

the measured signal-to-noise ratio (SNR: 124 dB relative to

340 V peak grid voltage) and spurious free dynamic range

(SFDR: 71 dBFS) of the prototype detector, that the

hardware may be optimized in terms of ADC resolution

and sample rate to achieve a trade-off between performance

and cost. In particular, it is feasible to use the integrated 12-

bit ADCs that are common in many low cost

DSP/microcontrollers that are used in the control of grid

converters.

The requirement for computing power can be minimized

by either optimising the FFT length or by utilising an

optimized version of an FFT algorithm that caters only for

the frequency range of interest.

The proposed frequency hopping method may also be

suitable for other active islanding detection schemes where

low order harmonics are injected. Further investigations are

required for its applicability in these schemes.

REFERENCES

[1]! "IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems," IEEE Std 929-2000, p. i, 2000.

[2]! M. E. Ropp, M. Begovic, and A. Rohatgi, "Prevention of islanding in grid-connected photovoltaic systems," Progress in Photovoltaics:

Research and Applications, vol. 7, pp. 39-59, 1999.

[3]! W. Bower and M. E. Ropp, "Evaluation Of Islanding Detection

Methods For Photovoltaic Utility-Interactive Power Systems," Rep. IEA-PVPS T5-09:2002, Mar. 2002.

[4]! "IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems," IEEE Std 1547-2003, pp. 1-28, 2003.

[5]! F. De Mango, M. Liserre, A. D. Aquila, and A. Pigazo, "Overview of Anti-Islanding Algorithms for PV Systems. Part I: Passive

Methods," in Power Electronics and Motion Control Conference, 2006. EPE-PEMC 2006. 12th International, 2006, pp. 1878-1883.

[6]! J. Sung-Il and K. Kwang-Ho, "An islanding detection method for

distributed generations using voltage unbalance and total harmonic distortion of current," Power Delivery, IEEE Transactions on, vol.

19, pp. 745-752, 2004.

[7]! B. Guha, R. J. Haddad, and Y. Kalaani, "A passive islanding detection approach for inverter-based distributed generation using

rate of change of frequency analysis," in SoutheastCon 2015, 2015, pp. 1-6.

[8]! H. Kobayashi, K. Takigawa, E. Hashimoto, A. Kitamura, and H.

Matsuda, "Method for preventing islanding phenomenon on utility grid with a number of small scale PV systems," in Photovoltaic

Specialists Conference, 1991., Conference Record of the Twenty Second IEEE, 1991, pp. 695-700 vol.1.

[9]! B. Wen, D. Boroyevich, R. Burgos, Z. Shen, and P. Mattavelli, "Impedance-Based Analysis of Active Frequency Drift Islanding

Detection for Grid-Tied Inverter System," IEEE Transactions on Industry Applications, vol. 52, pp. 332-341, 2016.

[10]! L. Soo-Hyoung and P. Jung-Wook, "New Islanding Detection Method for Inverter-Based Distributed Generation Considering Its

Switching Frequency," Industry Applications, IEEE Transactions on, vol. 46, pp. 2089-2098, 2010.

[11]! S. Yuyama, T. Ichinose, K. Kimoto, T. Itami, T. Ambo, C. Okado, et al., "A high speed frequency shift method as a protection for

islanding phenomena of utility interactive PV systems," Solar Energy Materials and Solar Cells, vol. 35, pp. 477-486, 9/11/ 1994.

[12]! J. Stevens, R. Bonn, J. Ginn, S. Gonzalez, and G. Kern, Development and testing of an approach to anti-islanding in utility-

interconnected photovoltaic systems Sandia National Laboratories, Albuquerque, NM, Lab Rep. SAND2000-1939, Aug. 2000.

[13]! M. E. Ropp, M. Begovic, and A. Rohatgi, "Analysis and performance assessment of the active frequency drift method of

islanding prevention," Energy Conversion, IEEE Transactions on, vol. 14, pp. 810-816, 1999.

[14]! P. Sanchis, L. Marroyo, and J. Coloma, "Design methodology for the frequency shift method of islanding prevention and analysis of its

detection capability," Progress in Photovoltaics: Research and Applications, vol. 13, pp. 409-428, 2005.

[15]! F. De Mango, M. Liserre, and A. D. Aquila, "Overview of Anti-Islanding Algorithms for PV Systems. Part II: ActiveMethods," in

Power Electronics and Motion Control Conference, 2006. EPE-PEMC 2006. 12th International, 2006, pp. 1884-1889.

[16]! K. Jae-Hyung, K. Jun-Gu, J. Young-Hyok, J. Yong-Chae, and W. Chung-Yuen, "An Islanding Detection Method for a Grid-Connected

System Based on the Goertzel Algorithm," Power Electronics, IEEE Transactions on, vol. 26, pp. 1049-1055, 2011.

[17]! L. Faa-Jeng, T. Kuang-Hsiung, and C. Jian-Hsing, "Active islanding

detection method using wavelet fuzzy neural network," in Fuzzy Systems (FUZZ-IEEE), 2012 IEEE International Conference on,

2012, pp. 1-8.

[18]! D. D. Reigosa, F. Briz, C. B. Charro, P. Garcia, and J. M. Guerrero,

"Active Islanding Detection Using High-Frequency Signal Injection," Industry Applications, IEEE Transactions on, vol. 48, pp.

1588-1597, 2012.

[19]! Y. Zhihong, L. Li, L. Garces, C. Wang, R. Zhang, M. Dame, et al.,

"A new family of active antiislanding schemes based on DQ implementation for grid-connected inverters," in Power Electronics

Specialists Conference, 2004. PESC 04. 2004 IEEE 35th Annual, 2004, pp. 235-241 Vol.1.

[20]! C. Jeraputra and P. N. Enjeti, "Development of a robust anti-islanding algorithm for utility interconnection of distributed fuel cell

powered generation," Power Electronics, IEEE Transactions on, vol. 19, pp. 1163-1170, 2004.

[21]! Z. Jun, X. Dehong, S. Guoqiao, Z. Ye, H. Ning, and M. Jie, "An Improved Islanding Detection Method for a Grid-Connected Inverter

With Intermittent Bilateral Reactive Power Variation," Power Electronics, IEEE Transactions on, vol. 28, pp. 268-278, 2013.

[22]! X. Chen and Y. Li, "An Islanding Detection Method for Inverter-Based Distributed Generators Based on the Reactive Power

Disturbance," IEEE Transactions on Power Electronics, vol. 31, pp. 3559-3574, 2016.

[23]! M. Ciobotaru, V. Agelidis, and R. Teodorescu, "Accurate and less-disturbing active anti-islanding method based on PLL for grid-

connected PV Inverters," in Power Electronics Specialists Conference, 2008. PESC 2008. IEEE, 2008, pp. 4569-4576.

[24]! R. Anne, F. K. Basha, R. Palaniappan, K. L. Oliver, and M. J. Thompson, "Reliable Generator Islanding Detection for Industrial

Frequency (kHz)18 18.5 19 19.5 20 20.5 21 21.5 22

VP

CC

(m

V)

0

20

40

60

80

100

120

140Before IslandingAfter IslandingX: 19.95

Y: 132.7

X: 19.95

Y: 55.1

Page 11: PWM Harmonic Signature Based Islanding Detection for a ... · PWM Harmonic Signature Based Islanding Detection for a Single-Phase Inverter with PWM Frequency Hopping Kalhana Colombage

Power Consumers With On-Site Generation," IEEE Transactions on

Industry Applications, vol. 52, pp. 668-676, 2016.

[25]! Este, x, E. J. banez, V. M. Moreno, A. Pigazo, M. Liserre, et al., "Performance Evaluation of Active Islanding-Detection Algorithms

in Distributed-Generation Photovoltaic Systems: Two Inverters

Case," Industrial Electronics, IEEE Transactions on, vol. 58, pp.

1185-1193, 2011.

[26]! D. Holmes and T. Lipo, "Pulse Width Modulation for Power Converters: Principles and Practice," ed: Wiley-IEEE Press, 2003.