Page 1: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Quick SelectionUK Special Edition

The art of handling air

Page 2: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

1

Quick SelectionUK Special Edition

TROX UK Ltd Tel: +44 (0) 1842 754545Caxton Way Fax: +44 (0) 1842 763051Thetford E-Mail: [email protected] IP24 3SQ www.troxuk.co.uk

Page 3: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Why Quick Selection?

This Quick Selection Guide has been designed to help you select theproducts you require quickly and easily. It provides an overview of thevarious product designs and dimensions for selected TROX products.

Full product details can be found in technical leaflets or the Easy ProductFinder software on our website - www.troxuk.co.uk

TROX Products for ventilation and air conditioning technology:

Components

• Air terminal devices

• Air terminal units

• Fire and smoke protection components

• Sound attenuators

• Dampers and external louvres

• Filter units and filter elements

Systems

• Air handling units

• Chilled beams

• Laboratory ventilation systems

• Communication systems for fire and smoke protection

2

Page 4: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

3

Introduction

In ventilation technology, two criteria are of particular importance:

• the air velocity in the occupied zone and

• the sound pressure level in the room

Air velocity

The air velocity depends on variables such as

• flow rate in combination with type and size of the diffuser

• arrangement of the diffusers within the room

• the height of the room

The flow pattern provided by the diffuser (swirl, linear or displacement)

also influences the maximum possible air change rate.

Drafts are caused by excessive air velocity in the occupied zone. The

configuration tables in this Quick Selection Guide have been chosen to

meet the most critical comfort criteria at a level exceeding that required

by European Standards.

Sound pressure level

A defined sound pressure level, depending on the type of room

involved, should not be exceeded. The following components of the

ventilation system influence the sound pressure level:

• fans

• fire dampers

• air terminal units

• diffusers

The Quick Selection Guide contains the necessary data for calculating

the sound power levels. The Guide also allows selection of the

necessary attenuators.

Generally, the sound power level per diffuser is limited to 40 dB(A)

without room attenuation.

Page 5: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

4

Application

The table below provides an overview of the TROX products to be used

depending on the air change rates per hour.

Legend

KVS Constant volume system

VVS Variable volume system

++ very suitable

+ suitable

– unsuitable

* flow discharge alternating horizontal!

Room height up to 4 m

Air changeFlow

Slot Swirl Blade Perforatedrates/h

rate Grillediffuser diffuser diffuser diffuser

control

≤ 10KVS ++ ++ ++ ++ ++

VVS + + ++ + +

10 – 20KVS – ++* ++ ++ ++

VVS – ++* ++ + +

20 – 30KVS – – ++ – –

VVS – – ++ – –

Typical applications

Velocity / m.s-1

Typical noise Main ducts Branch Runoutsrating (NR)*

Domestic buildings (bedrooms) 25 3.0 2.5 <2.0

Theatres, concert halls 20-25 4.0 2.5 <2.0

Auditoria, lecture halls, cinemas 25-30 4.0 3.5 <2.0

Bedrooms (non domestic buildings) 20-30 5.0 4.5 2.5

Private offices, libraries 30-35 6.0 5.5 3.0

General offices, restaurants, banks 35-40 7.5 6.0 3.5

Department stores, supermarkets, shops 40-45 9.0 7.0 4.5

Industrial buildings 45-55 10.0 8.0 5.0

Page 6: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

5

Table of Contents

Product Type Page

Grilles AH-WAP-AF 7 - 9Grilles AT-VAT 10

Grilles AGS 11

Grilles AR 12

Grilles AE-AP 13 - 14

Grilles LCG 15

Disc Valves LVS Z-LVS 16

Jet Nozzles DUK 17

Jet Nozzles TJN 18

Jet Nozzles DJ 19

Floor Diffusers FB 20

Floor Diffusers AFG 21

Slot Diffusers VSD35 22 - 23

Slot Diffusers VSD50 24 - 25

Slot Diffusers AKV-VSD 26

Slot Diffusers ALS20 27 - 28

Slot Diffusers ALS25 29 - 30

Slot Diffusers AKV-ALS 31

Swirl Diffusers SDW 32 - 34

Swirl Diffusers XARTO 35 - 37

Swirl Diffusers RFD 38 - 39

Swirl Diffusers DCS 40 - 41

Swirl Diffusers VDL 42

Ceiling Diffusers ADT 43 - 45

Ceiling Diffusers DLQ/ADLQ 46

Ceiling Diffusers ADLR 47

Ceiling Diffusers ADM 48

Ceiling Diffusers VDR 49

Ceiling Diffusers DLQL 50 - 51

Multileaf Dampers JZ-P, JZ-P-A2, JZ-S, JZ-S-A2, JZ-HL, JZ-LL, JZ-LL-A2 52

Multileaf Dampers JZ-AL, JZ-LL-AL 53

Weather Resistant Louvres WG, WGK 54 - 55

Fire Dampers FK-EU 56

Fire Dampers FKS-EU 57

Fire Dampers FKR-EU 58

Fire Dampers FKRS-EU 59

Fire Dampers Attachments 60

Fire Dampers Accessories 61

VARYCONTROL VAV Terminal Boxes TVZ, TVA 62

VARYCONTROL VAV Terminal Boxes TZ-Silenzio 63

VARYCONTROL VAV Terminal Boxes TA-Silenzio 64

VARYCONTROL VAV Controllers TVR 65

VARYCONTROL VAV Controllers TVR-Easy 66

VARYCONTROL VAV Controllers TVJ Easy/TVT Easy 67

VARYCONTROL VAV EasySet 68

VARYCONTROL EASYLAB-LABCONTROL 69

Clean rooms and Containment facilities HEPA and ULPA filtration 70

Volume Flow Controllers RN, RNS 71

Volume Flow Controllers EN 72

Circular Silencers CA, CF, CS 73

Circular Silencers CB 74

Rectangular Splitter Attenuators- Splitters MSA 200 75

Air Handling Unit X-CUBE 76

Active Chilled Beam DID614 77

Active Chilled Beam DID642 78

Passive Chilled Beam PKV 79

Multi Service Chilled Beam MSCB 80

Fancoil Unit PWH 81

Page 7: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

7

GrillesType AH · WAP · AF

Order Code

TypeAFAHAHR (20mm border)WAPWAPR (20mm border)

Blade deflection15°0°

Subframe0 = No subframeB30 = 75mm subframe(30mm borders) for finite grilleB20 = as above but for 20mmborder grilleL30 = 1800mm subframe (30mmborders) for linear grille**L20 = as above but for 20mm border grille

Note: ** = Also for use when S11 fix plenum box supplied

Rear AssembliesA = Grille Face onlyAG = Rear opposedblade damperD = Rear adjustablebladesDG = Rear adjustableblades and damper

Fixing0 = Without (screwfix)S11 = With (secret fix)X = Without flange drilling

L x H (mm)Powder coat finish

AH - 15 - AG 1000 x 150 B30 S11 P3 RAL 9010 20% Gloss/ / / / / /

Order Code - Plaster In

Type- Linear ConstructionF Finite ConstructionE End SectionM Middle Section

AHP-0AHP-15WAPP-0WAPP-15

L x H (mm)Powder coat finish

F - AHP15 1000 x 150 P3 RAL 9010 20% Gloss/ / / /

Type AH-0Type AH - WAP

Type AF

Type AF-0 AF...-0° AF...-15°

Type AHP-0 (Plaster-In)

H/L

H +

41(2

1)/L

+ 4

1(21

)12

.5

'H' -

4 /

'L' -

4 12

,5

H/L

12.5

H+30/L+30

...-AGOpposed blade action volume controldamper, adjustable from the front face.

...-DA set of individually adjustable vertical airpattern control blades.For type VAT these blades are horizontal.

...-DGVolume control dampers as ...-AG plus aset of individually adjustable vertical airpattern control blades.

10

775

643

2

10

775

Rear Assembly

18

5,5

18

5,5

18

5,5

18

5,5

AH...-0° AH...-15°

18

3,0

18

3,0

WAP...-0° WAP...-15°

Page 8: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

8

GrillesType AH · WAP · AF

Installation situation

Type AH, AF

≥X

Nomenclature‡ in l/s/m based on 1000mm nominal grille

length.H Nominal grille height.ls in m = Throw distance to a maximum

time averaged air velocity of 0.7m/sVolume flow rates apply to a nominal grillelength [L] of 1000mm, maximum soundpower level of the air-regenerated noise of40 dB(A) with an open damper unit(unrestricted airflow) and maximum 15Papressure drop.

Throw length [lS] provided in metres to amaximum time average velocity [VL] of 0.7m/swithout rear deflection blades.For reduced throw applications, rear deflectionblades ...-D, ...-DG should be used. Refer tocorrection factors for adjustment to the figuresbelow.Correction factors for other terminal velocitiesand nominal grilles lengths are provided below.

Flow rate and throw distanceV (l/s/m) 60 85 100 125 150 175 200 225 250 275 300 350 400 450

H (mm) ls(m)

75 3.4 4.8 5.6 7.0

100 4.0 4.7 5.8 7.0 8.1

150 5.5 6.4 7.3 8.2 9.1

200 6.2 7.0 7.7 8.5 9.3 10.8 12.4

250 6.8 7.5 8.2 9.6 10.9 12.3

300 7.4 8.7 9.9 11.1

350 8.0 9.1 10.2

400 8.5 9.5

450 9.0

Flow rate and throw distanceV (l/s/m) 500 550 600 650 700 750 800 850 900 950 1000 1100 1200

H (mm) ls(m)

250 13.6

300 12.4 13.6 14.8

350 11.4 12.5 13.7 14.8 15.9 17.1

400 10.6 11.7 12.7 13.8 14.9 15.9 17.0 18.0

450 10.0 11.0 12.0 13.0 14.0 15.0 16.0 17.0 18.0 19.0

500 9.0 10.4 11.3 12.3 13.2 14.2 15.1 16.1 17.1 17.9 18.9 20.8

550 9.9 10.8 11.7 12.6 13.5 14.4 15.3 16.2 17.1 18.0 19.8 21.6

600 10.8 11.7 12.6 13.5 14.4 15.3 16.2 17.1 18.0 19.8 21.6

Throw length correction based on grille lengthNominal grille length (m) 0.3 0.6 0.9 1.0 1.2 1.5 1.8

Correction factor (Kf) x 0.55 x 0.78 x 0.95 x 1.00 x 1.09 x 1.22 x 1.34

Throw length correction(for setting of blade divergence)

β 45° 90°

α 35° 60°

lS x 0.7 x 0.5

ΔtL / ΔtZ x 0.7 x 0.5

With ceiling effect B ≥ LS x 0.2 LS x 0.3

Without ceiling effect B ≥ LS x 0.25 LS x 0.3

Extract Air VolumeΔpt (Pa) 5 10 15

H (mm) V (l/s/m)

75 78 111 136

100 113 160 195

150 182 257 315

200 251 355 435

250 320 453 554

300 389 550 674

350 458 648 794

400 527 746 913

450 596 843 1033

500 665 941 1152

550 734 1039 1272

600 803 1136 1392

Terminal velocity correctionMaximum time average velocity 0.5 m/s 0.25 m/s

lS x 1.4 x 2.8

Page 9: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

9

GrillesType AH · WAP · AF

Installation situation

Type WAP

≥X

Nomenclature‡ in l/s/m based on 1000mm nominal grille

length.H Nominal grille height.ls in m = Throw distance to a maximum

time averaged air velocity of 0.7m/sVolume flow rates apply to a nominal grillelength [L] of 1000mm, maximum soundpower level of the air-regenerated noise of40 dB(A) with an open damper unit(unrestricted airflow) and maximum 15Papressure drop.

Throw length [lS] provided in metres to amaximum time average velocity [VL] of 0.7m/swithout rear deflection blades.For reduced throw applications, rear deflectionblades ...-D, ...-DG should be used. Refer tocorrection factors for adjustment to the figuresbelow.Correction factors for other terminal velocitiesand nominal grilles lengths are provided below.

Flow rate and throw distanceV (l/s) 85 100 125 150 175 200 225 250 275 300 350 400 450 500

H (mm) ls(m)

75 4.1 4.8 6.0 7.2

100 5.0 5.9 6.9 7.9 8.9

150 6.2 7.0 7.7 8.5 9.3 10.8

200 7.2 7.9 9.2 10.5 11.8 13.1

250 8.1 9.3 10.4 11.6

300 9.5 10.5

350 9.7

Flow rate and throw distanceV (l/s) 550 600 650 700 750 800 850 900 950 1000 1100 1200 1300 1400

H (mm) ls(m)

250 12.8 13.9 15.1

300 11.6 12.6 13.7 14.7 15.8 16.8

350 10.7 11.6 12.6 13.6 14.5 15.5 16.5 17.5 18.4

400 9.9 10.8 11.7 12.6 13.6 14.5 15.4 16.3 17.2 18.1 19.9

450 11.0 11.9 12.7 13.6 14.4 15.3 16.1 17.0 18.7 20.4

500 11.3 12.1 12.9 13.7 14.5 15.3 16.1 17.7 19.3 20.9

550 12.2 13.0 13.8 14.5 15.3 16.8 18.4 19.9 21.4

600 12.4 13.2 13.9 14.6 16.1 17.5 19.0 20.5

Throw length correction based on grille lengthNominal grille length (m) 0.3 0.6 0.9 1.0 1.2 1.5 1.8

Correction factor (Kf) x 0.55 x 0.78 x 0.95 x 1.00 x 1.09 x 1.22 x 1.34

Throw length correction(for setting of blade divergence)

β 45° 90°

α 35° 60°

lS x 0.7 x 0.5

ΔtL / ΔtZ x 0.7 x 0.5

With ceiling effect B ≥ LS x 0.2 LS x 0.3

Without ceiling effect B ≥ LS x 0.25 LS x 0.3

Extract Air VolumeΔpt (Pa) 5 10 15

H (mm) V (l/s/m)

75 108 153 188

100 156 220 270

150 251 355 435

200 346 490 600

250 442 625

300 537 759

350 632 894

400 727 1029

450 823 1164

500 918 1299

550 1013 1433

600 1109 1568

Terminal velocity correctionMaximum time average velocity 0.5 m/s 0.25 m/s

lS x 1.4 x 2.8

Page 10: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

...-AGOpposed bladeaction volumecontrol damper,adjustable fromthe front face.

...-DA set ofindividuallyadjustable verticalair pattern controlblades. For typeVAT these bladesare horizontal.

...-DGVolume controldampers as ...-AGplus a set ofindividuallyadjustable verticalair pattern controlblades.

10

GrillesType AT · VAT

64

32

Order Code

Rear Assembly

TypeAT = Horizontal front blade

VAT= Vertical front blade

Rear AssembliesA = Grille face only

AG = Rear opposed blade damper

D = Rear adjustable blades

DG = Rear adjustable blades and damper

0 = No subframe

B30 = 75mm

subframe bracketFixing Variant0 = Without (screw fix)S11 = With (secret fix)X = Without flange drilling or secret fix

L x H (mm) Powder coat finish

AT - AG 800 x 200 B30 S11 P3 RAL 9010 20% Gloss/ / / / / /

107

75

H /

L

H +

22

/L +

22

H +

45

/L +

45

16,7

107

75

Type AT · VAT

Installation situation≥X

Nomenclature‡ in l/s/m based on

1000mm nominal grille length.

H Nominal grille height.ls in m = Throw distance

to a maximum time averaged air velocity of 0.7m/s

Volume flow rates apply to a nominal grille length [L] of1000mm, maximum soundpower level of the airregenerated noise of 40 dB(A)with an open damper unit(unrestricted airflow) andmaximum 15Pa pressure drop.

Type AT

Type VAT

Flow rate and throw distance

Grille length correctionNominal grille length (m) 0.3 0.6 0.9 1.0 1.2 1.5 1.8

Correction factor (Kf) x 0.55 x 0.78 x 0.95 x 1.00 x 1.09 x 1.22 x 1.34

Throw length correction(for setting of blade divergence)

β 45° 90°

α 35° 60°

lS x 0.7 x 0.5

ΔtL / ΔtZ x 0.7 x 0.5

With ceiling effect B ≥ LS x 0.2 LS x 0.3

Without ceiling effect B ≥ LS x 0.25 LS x 0.3

Terminal velocity correctionMaximum time average velocity 0.5 m/s 0.25 m/s

lS x 1.4 x 2.8

V (l/s/m) 125 150 175 200 225 250 275 300 325 350 375 400 450 500H (mm) ls(m)

100 5.1 6.1 7.2 8.2 9.2150 5.6 6.4 7.1 7.9 8.7 9.5 10.3 11.1 11.9200 6.7 7.4 8.1 8.7 9.4 10.1 10.7 12.1 13.4250 7.7 8.3 8.9 9.5 10.7 11.8300 8.6 9.7 10.7350 9.9

Flow rate and throw distanceV (l/s/m) 550 600 650 700 750 800 850 900 950 1000 1100 1200 1300 1400H (mm) ls(m)

250 13.0 14.2 15.4300 11.8 12.8 13.9 15.0 16.1 17.2350 10.8 11.8 12.8 13.8 14.8 15.8 16.8 17.8 18.7400 10.1 11.0 11.9 12.9 13.8 14.7 15.6 16.5 17.4 19.0450 10.4 11.2 12.1 12.9 13.8 14.7 15.5 16.4 17.3 19.0500 11.4 12.2 13.1 13.9 14.7 15.5 16.3 17.9 19.6550 11.7 12.4 13.2 14.0 14.8 15.5 17.1 18.6 20.2600 11.9 12.6 13.4 14.1 14.8 16.3 17.8 19.3 20.8

Page 11: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

11

GrillesType AGS

Type AGS-T

'H' -

5 /

'L' -

10

①②

A

'H' +

48 / '

L' +4

2'H

' -5 / '

L' -1

0

'H' +

34 / '

L' +2

8

Min 25Max 44

B

3 1

A Ventilation grille AGS with screw fixingB Ventilation grille AGS-T with screw fixing and matching rear frame1 Ventilation grille2 Fixing screw (by others)3 Matching frame

Type AGS

Type AGS

Type AGS

Performance Data

Neck Pressure Drop (Pa) 3 7 12.5 19.5 28

Size (l/s) (LWA) (l/s) (LWA) (l/s) (LWA) (l/s) (LWA) (l/s) (LWA)

150 x 145 Volume (l/s) 6 15 9 24 12 30 15 34 18 38

200 x 145 Volume (l/s) 8 16 13 26 17 31 21 36 25 39

200 x 205 Volume (l/s) 13 18 20 27 27 33 34 38 41 42

300 x 205 Volume (l/s) 21 20 32 29 43 35 54 40 65 44

300 x 305 Volume (l/s) 35 23 53 32 70 37 88 42 106 46

400 x 305 Volume (l/s) 48 24 72 33 96 39 121 43 145 47

450 x 305 Volume (l/s) 54 25 82 33 109 39 137 44 164 48

450 x 445 Volume (l/s) 84 27 126 35 168 41 211 46 253 50

600 x 405 Volume (l/s) 103 28 154 36 206 42 257 47 309 50

500 x 505 Volume (l/s) 108 28 163 36 217 42 271 47 326 51

600 x 605 Volume (l/s) 160 30 240 34 320 44 400 49 480 52

800 x 605 Volume (l/s) 216 31 324 39 432 45 540 50 649 54

1000 x 605 Volume (l/s) 272 32 408 40 544 46 681 51 817 55

1200 x 605 Volume (l/s) 328 33 492 41 656 47 821 52 985 56

Order Code

TypeAGSAGS-T (Matching frame - T)

0 = without subframe

0 = ScrewfixX = Without flange drilling

L x H (mm)L = 25mm incrementsH = 20mm increments

Powder coat finish

AGS - T 300 x 305 0 0 P3 RAL 9010 20% Gloss/ / / / / /

Page 12: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

12

GrillesType AR

Order Code

Type

Rear AssembliesA = Grille face onlyAG = Rear opposed blade damper

Fixing Variant0 = Without (screw fix)X = Without flange drilling or secret fix

L x H (mm) Powder coat finish

AR - AG 800 x 200 0 P3 RAL 9010 20% Gloss/ / / / /

Rear Assembly

...-AGOpposed blade action volumecontrol damper, adjustable from thefront face.

Type AR Type AR

NoteIn all cases, the max. pressure drop ΔPt = 15 Pa.

Nomenclature‡min in l/s = Minimum flow rate‡max in l/s = Maximum flow rate

10

775

H /

L

16,7

H +

45

/L +

45

H +

22

/L +

22

Aerodynamic data

H(mm)Length (mm)

Data200 300 400 500 600 700 800 900 1000 1100 1200

‡min – ‡max 15 - 28 21 - 39 30 - 56 39 - 73 48 - 90 57 - 106 66 - 123 72 - 134 84 - 263 93 - 174 102 - 190100 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15

LWA 7 - 19 8 - 20 10 - 22 11 - 23 12 - 24 13 - 25 13 - 25 14 - 26 14 - 26 15 - 27 15 - 27‡min – ‡max 24 - 45 39 - 73 54 - 101 69 - 129 84 - 157 99 - 185 114 - 213 129 - 241 141 - 263 156 - 291 171 - 319

150 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 9 - 21 11 - 23 12 - 24 13 - 25 14 - 26 15 - 27 16 - 28 16 - 28 16 - 29 17 - 29 17 - 29‡min – ‡max 33 - 62 57 - 106 78 - 146 99 - 185 120 - 224 138 - 258 159 - 297 177 - 330 198 - 370 219 - 409 246 - 459

200 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 10 - 22 13 - 25 14 - 26 15 - 27 16 - 28 16 - 28 17 - 29 17 - 30 18 - 30 18 - 30 19 - 31‡min – ‡max 72 - 134 96 - 179 123 - 230 150 - 280 174 - 325 198 - 370 222 - 414 249 - 465 273 - 510 306 - 571

250 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 14 - 26 15 - 27 16 - 28 17 - 29 17 - 29 18 - 30 18 - 31 19 - 31 19 - 31 20 - 32‡min – ‡max 93 - 174 123 - 230 159 - 297 189 - 353 222 - 414 252 - 470 291 - 543 324 - 605 357 - 666 390 - 728

300 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 15 - 27 16 - 28 17 - 29 18 - 30 18 - 31 19 - 31 20 - 32 20 - 32 20 - 33 21 - 33‡min – ‡max 150 - 280 189 - 353 228 - 426 264 - 493 303 - 566 339 - 633 378 - 706 417 - 778 465 - 868

350 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 17 - 29 18 - 30 19 - 31 19 - 31 20 - 32 20 - 32 21 - 33 21 - 33 22 - 34‡min – ‡max 174 - 325 216 - 403 258 - 482 303 - 566 345 - 644 390 - 728 444 - 829 489 - 913 534 - 997

400 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 17 - 29 18 - 30 19 - 31 20 - 32 20 - 32 21 - 33 21 - 34 22 - 34 22 - 34‡min – ‡max 258 - 482 309 - 577 360 - 672 411 - 767 462 - 862 528 - 986 579 - 1081 633 - 1182

450 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 19 - 31 20 - 32 21 - 33 21 - 33 22 - 34 22 - 34 23 - 35 23 - 35‡min – ‡max 279 - 521 339 - 633 393 - 734 450 - 840 507 - 946 564 - 1053 618 - 1154 675 - 1260

500 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 19 - 32 20 - 32 21 - 33 21 - 34 22 - 34 22 - 35 23 - 35 23 - 35‡min – ‡max 390 - 728 465 - 868 534 - 997 600 - 1120 666 - 1243 732 - 1366 1392 - 2598

600 Pa 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15 4 - 15LWA 21 - 33 22 - 34 22 - 34 23 - 35 23 - 35 24 - 36 26 - 38

Page 13: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

13

GrillesType AE · AP

1

Type AEL-A shown(Lay-in grille)

Type AE

1

Type AP

Type AE-Ashown

H/L

H + 5 / L + 5

100

TYP

H/L

13

H +

41 /

L +

41

1

NoteIn all cases, the max. pressure drop ΔPt = 15 Pa.

Nomenclature‡min in l/s = Minimum flow rate‡max in l/s = Maximum flow rate

Aerodynamic data

H(mm)Length (mm)

Data200 300 400 500 600 700 800 900 1000 1100 1200

‡min – ‡max 27 - 59 42 - 91 57 - 124 72 - 156 87 - 189 102 - 221 117 - 254 132 - 286 147 - 540 162 - 351 177 - 384100 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15

LWA 12 - 28 14 - 30 15 - 31 16 - 32 17 - 33 18 - 34 18 - 35 19 - 35 19 - 36 20 - 36 20 - 36‡min – ‡max 45 - 98 69 - 150 96 - 208 120 - 260 147 - 319 171 - 371 198 - 429 222 - 481 249 - 540 276 - 598 300 - 650

150 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 14 - 30 16 - 32 17 - 34 18 - 35 19 - 36 20 - 36 20 - 37 21 - 37 21 - 38 22 - 38 22 - 39‡min – ‡max 63 - 137 99 - 215 135 - 293 171 - 371 207 - 449 243 - 527 279 - 605 315 - 683 351 - 761 387 - 839 423 - 917

200 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 16 - 32 17 - 34 19 - 35 20 - 36 21 - 37 21 - 38 22 - 38 23 - 39 23 - 39 23 - 40 24 - 40‡min – ‡max 126 - 273 171 - 371 219 - 475 264 - 572 312 - 676 360 - 780 405 - 878 450 - 975 498 - 1079 543 - 1177

250 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 19 - 35 20 - 36 21 - 37 22 - 38 22 - 39 23 - 39 24 - 40 24 - 40 24 - 41 25 - 41‡min – ‡max 156 - 338 213 - 462 267 - 579 324 - 702 384 - 832 426 - 923 495 - 1073 552 - 1196 609 - 1320 666 - 1443

300 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 19 - 36 21 - 37 22 - 38 23 - 39 23 - 40 24 - 40 24 - 41 25 - 41 25 - 42 26 - 42‡min – ‡max 252 - 546 318 - 689 384 - 832 453 - 982 519 - 1125 585 - 1268 651 - 1411 720 - 1560 786 - 1703

350 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 22 - 38 23 - 39 23 - 40 24 - 40 25 - 41 25 - 42 26 - 42 26 - 42 26 - 43‡min – ‡max 288 - 624 366 - 793 444 - 962 522 - 1131 600 - 1300 675 - 1463 753 - 1632 831 - 1801 909 - 1970

400 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 22 - 38 23 - 40 24 - 40 25 - 41 25 - 42 26 - 42 26 - 43 27 - 43 27 - 43‡min – ‡max 426 - 923 504 - 1092 591 - 1281 678 - 1469 768 - 1664 855 - 1853 942 - 2041 1029 - 2230

450 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 24 - 40 25 - 41 25 - 42 26 - 42 26 - 43 27 - 43 27 - 44 28 - 44‡min – ‡max 465 - 1008 564 - 1222 687 - 1489 759 - 1645 858 - 1859 957 - 2074 1053 - 2282 1155 - 2503

500 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 24 - 41 25 - 41 26 - 42 26 - 43 27 - 43 27 - 44 28 - 44 28 - 45‡min – ‡max 681 - 1476 801 - 1736 918 - 1989 1038 - 2249 1158 - 2509 1275 - 2763 1392 - 3016

600 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 26 - 42 27 - 43 27 - 44 28 - 44 28 - 45 29 - 45 29 - 45

Type AE/AEL

Page 14: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

14

GrillesType AE · AP

NoteIn all cases, the max. pressure drop ΔPt = 15 Pa.

Nomenclature‡min in l/s = Minimum flow rate‡max in l/s = Maximum flow rate

Order Code

TypeAE = Eggcrate coreAEL = Eggcrate core (595x595 only)AP = Perforated coreAPL = Perforated core (595x595 only)

Rear AssembliesA = Grille face onlyAG = Rear opposed blade damper

Fixing Variant0 = Without (screw fix)S11 = With (secret fix) AE, AP onlyX = Without flange drilling or secret fix

0 = No subframe

B30 = 75mmsubframe bracket

L x H (mm) Powder coat finish

AE - AG 800 x 200 P3 RAL 9010 20% Gloss/ / B30 / S11 / / /

Aerodynamic data

H(mm)Length (mm)

Data200 300 400 500 600 700 800 900 1000 1100 1200

‡min – ‡max 15 - 33 21 - 46 30 - 65 39 - 85 48 - 104 57 - 124 66 - 143 72 - 156 84 - 306 93 - 202 102 - 221100 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15

LWA 9 - 26 11 - 27 12 - 29 13 - 30 14 - 31 15 - 31 16 - 32 16 - 32 17 - 33 17 - 34 18 - 34‡min – ‡max 24 - 52 39 - 85 54 - 117 69 - 150 84 - 182 99 - 215 114 - 247 129 - 280 141 - 306 156 - 338 171 - 371

150 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 11 - 28 13 - 30 15 - 31 16 - 32 17 - 33 17 - 34 18 - 34 19 - 35 19 - 35 19 - 36 20 - 36‡min – ‡max 33 - 72 57 - 124 78 - 169 99 - 215 120 - 260 138 - 299 159 - 345 177 - 384 198 - 429 219 - 475 246 - 533

200 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 13 - 29 15 - 31 16 - 33 17 - 34 18 - 35 19 - 35 20 - 36 20 - 36 20 - 37 21 - 37 21 - 38‡min – ‡max 72 - 156 96 - 208 123 - 267 150 - 325 174 - 377 198 - 429 222 - 481 249 - 540 273 - 592 306 - 663

250 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 16 - 32 17 - 34 18 - 35 19 - 36 20 - 36 20 - 37 21 - 37 21 - 38 22 - 38 22 - 39‡min – ‡max 93 - 202 123 - 267 159 - 345 189 - 410 222 - 481 252 - 546 291 - 631 324 - 702 357 - 774 390 - 845

300 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 17 - 34 18 - 35 20 - 36 20 - 37 21 - 37 22 - 38 22 - 39 23 - 39 23 - 39 23 - 40‡min – ‡max 150 - 325 189 - 410 228 - 494 264 - 572 303 - 657 339 - 735 378 - 819 417 - 904 465 - 1008

350 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 19 - 36 20 - 37 21 - 37 22 - 38 22 - 39 23 - 39 23 - 40 24 - 40 24 - 41‡min – ‡max 174 - 377 216 - 468 258 - 559 303 - 657 345 - 748 390 - 845 444 - 962 489 - 1060 534 - 1157

400 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 20 - 36 21 - 37 22 - 38 22 - 39 23 - 39 23 - 40 24 - 40 24 - 41 25 - 41‡min – ‡max 258 - 559 309 - 670 360 - 780 411 - 891 462 - 1001 528 - 1144 579 - 1255 633 - 1372

450 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 22 - 38 22 - 39 23 - 39 24 - 40 24 - 41 25 - 41 25 - 42 26 - 42‡min – ‡max 279 - 605 339 - 735 393 - 852 450 - 975 507 - 1099 564 - 1222 618 - 1339 675 - 1463

500 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 22 - 38 23 - 39 23 - 40 24 - 40 25 - 41 25 - 41 25 - 42 26 - 42‡min – ‡max 390 - 845 465 - 1008 534 - 1157 600 - 1300 666 - 1443 732 - 1586 822 - 1781

600 Pa 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15 3 - 15LWA 23 - 40 24 - 41 25 - 41 25 - 42 26 - 42 26 - 43 27 - 43

Type AP/APL

Page 15: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

15

GrillesType LCG

TypeLCG

L x H (mm) Powder coat finish

Order Code

LCG 150 x 150 0 0 P3 RAL 9010 20% Gloss/ / / / / /

TypeLVV 40LVH 44Note: For use with LCG Grilles

L x H (mm)

LVV 40 150 x 150/

Intumescentmastic by others

LVV40 intumescentfireblock

LCG cover grille

LCG / LVV40 / LVH44

LVV40 + LCG (60 minute fire rating)Nominal LWA 30 dB LWA 35 dB LWA 40 dB LWA 45 dB

Size Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa)150 x 150 45 15 52 20 63 28 74 40200 x 150 55 14 66 19 78 26 93 35200 x 200 68 13 82 17 98 24 118 33300 x 200 94 11 111 16 133 21 160 30300 x 300 130 10 158 14 185 19 222 26400 x 300 165 9 198 13 235 17 285 24450 x 300 180 9 218 12 259 16 310 24450 x 450 252 8 300 11 360 15 440 21600 x 400 288 8 342 10 410 14 490 19500 x 500 290 8 350 10 420 14 500 19600 x 600 400 7 460 10 560 14 690 18

LVH40 + LCG (120 minute fire rating)Nominal LWA 30 dB LWA 35 dB LWA 40 dB LWA 45 dB

Size Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa) Volume (l/s) ΔPt (Pa)150 x 150 27 8 35 11 42 15 50 23200 x 150 36 8 44 11 54 15 65 22200 x 200 46 8 56 11 70 15 85 22300 x 200 68 8 84 11 100 15 121 21300 x 300 98 8 120 11 149 15 180 21400 x 300 129 8 158 11 191 15 235 21450 x 300 142 8 173 11 212 15 260 21450 x 450 209 8 255 11 310 15 380 21600 x 400 245 8 300 10 365 15 450 21500 x 500 255 8 310 10 380 15 460 21600 x 600 355 7 425 9 520 14 640 21

Page 16: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

16

Dimensions (mm)

LVS Z-LVS Installation LVS Installation Z-LVS

L in m: Throw distance related to ‡L = 0.2 m/s

Type

Supply air Z-LVSExtract air LVS

Order CodeStandard finish RAL 9010

/ /LVS 125

Size100125160200

G1

IEEEEOEEEEPTEEEZEEEU0 without subframeG1 subframe (Standard)1)

1) Unless otherwise specified on order, equipment is delivered with subframe (G1).

50

x Dx D

B B

x C x Cx E* x E*

50

8 8

Size B ØC ØD ØE

100 40 99 132 104

125 46 124 162 129

160 54 159 193 164

200 61 199 245 204

Disc ValvesType LVS · Z-LVS

Quick selection table

Type Size V.

V.

∆ WA Lin m3/h in l/s in Pa in dB(A) in m

100 115 32 130 40 –

125 180 50 135 40 –

160 260 72 125 40 –

200 350 97 110 40 –

100 100 28 37 40 1.7

125 155 43 77 40 2.5

160 235 65 90 40 4.0

200 290 81 90 40 4.6

LVS

s =

0 m

m

Z-L

VS

s =

12 m

m

Page 17: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

17

Dimensions (mm)Throw distance and pressure drop

DUK DUK-FL2

ØD4

ØD3

ØD5

DUK-V

Installation situation – isothermal

Size ØD1 ØD3 ØD4 ØD5 L1 L2

100 136 146 98 50 94 78

125 159 169 123 64 112 86

160 225 200 158 82 122 98

200 265 257 198 108 153 117

250 315 302 248 136 187 155

315 400 384 313 174 224 183

400 485 467 398 230 287 208

V.

(l/s) 20 28 42 70 111 167 222 278 347 416

X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m)Size

∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa)

1008 11

50 100

1256 9 11

25 50 100

1605 6 9 12

10 20 40 100

2005 7 9 18

10 15 40 100

2505 7 15 22

5 15 40 90

3155 11 17 23 28

5 15 30 60 90

4008 13 18 23 28 32

5 10 15 25 40 60

X

Occupied zoneNomenclature

X in m = Throw distance∆Pt in Pa = Total pressure dropDimension of recess = ØD4 + 15 mm

Note

The combinations of flow rate and size as shown in the tableproduce a sound power level:

LWA = 35 dB(A) for axial connectionLWA = 43 dB(A) for lateral connection

1) For attachment without counterpunched holes: Supplementary text necessary for order2) For sizes 100 and 125, construction with actuator not available3) Please indicate onsite duct diameter (ØR) as supplementary text4) GE = Gloss level

Type

Fixed F1)

Adjustable V

Duct connection element KSpigot ADuct connection element for circular ducting R3)

Externalrotary actuator E1...E3

Internallinear actuator E4...E6

Size2)Specify RAL colour

0 Standard finish “unfinished”

P0 Powder coatingto RAL 9010 (GE 50%)4)

P1 Powder coatingto RAL 9006 (GE 30%)4)Other coloursto RAL... (GE 70%)4)

Order Code

DUK - V - K - E1 400 P1 RAL 9016/ / /

IEEOEEPIEEEEEEOEEEEEEP

IEEEEEEEEOEEEEEEEEP

TEEEEEEEEEEEEEEEZEEEEEEEEEEEEEEU

Jet NozzlesType DUK

L1

ØD

1

ØD

5

9

These codes need not be completed for standard products

Page 18: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

18

Dimensions (mm)Throw distance and pressure drop

TJN TJN TJN-...-D...-...

Installation situation – isothermal

Size ØD ØD1 ØD3 ØD5 L1 L2

160 158 258 227 50 15 242

200 198 298 263 64 14 250

250 248 348 315 82 14 260

315 313 413 376 108 15 275

400 398 501 468 136 16 285

V.

(l/s) 20 28 42 70 111 167 222 278 347 416

X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m)Size

∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa) ∆pt (Pa)

1605 6 9 12

10 20 40 100

2005 7 9 18

10 15 40 100

2505 7 15 22

5 15 40 90

3155 11 17 23 28

5 15 30 60 90

4008 13 18 23 28 32

5 10 15 25 40 60X

Occupied zone

Nomenclature

X in m = Throw distance∆pt in Pa = Total pressure drop

Note

The combinations of flow rate and size as shown in the tableproduce a sound power level:

LWA = 35 dB(A) for axial connectionLWA = 43 dB(A) for lateral connection

Type

Connection PieceNone - For rectangular ducts K For circular ducts (saddleconnector), duct diameterto be specified. R

ActuatorManual Adjustment - Min/Max or 3-point, 230 V AC E7 Min/Max or 3-point, 24 V AC E8 Modulating 2-10 V DC, 24 V AC E9 Thermal actuator T1

Size160200250315400

FinishSimilar to RAL9010, pure white - Similar to RAL9006, white aluminium S1

AccessoriesNone - Swirl unit for throw distance reduction D

AttachmentsNo entry NoneOuter casing C

Circular duct diameter(specify only for variant 'R')Specify only for nominal size 160 315 only up to nominal size 315 500

630800

Order Code

TJN - R - E7 160 - 315 C D S1/ / / /

IEEEEEEEEOEEEEEEEEP

IEEEEEEEEOEEEEEEEEPIEEEEEEEEOEEEEEEEEPIEEEEEEEEOEEEEEEEEP

IEEEEEEEEOEEEEEEEEP

Jet NozzlesType TJN

Page 19: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

19

TypeDJDJD – DJ C/W Adjustable Blades

AncillariesOB – Diffuser Mounted Opposed Blade Damper

OB/DM – Duct Mounted OBD (Supplied loose)

VED – Diffuser Mounted Volume Equalising Deflector

VED/DM – Duct Mounted VC (Supplied loose)

OB/VED – Diffuser Mounted Volume Equalising Deflector withopposed blade damper (add 50mm to required stub duct length)

OB/VED/DM – Duct Mounted Volume Equalising Deflector withopposed blade damper (add 50mm to required stub duct length)(Supplied loose).

No entry - No ancillaries

Size9061206180624062010251030103510

Finish/colour

FinishPC – Powder Coated to RAL.... BS....

DJ - OB / DM 906 PC RAL 9010 20% Gloss/ / / /IEEEEEOEEEEEEP

Drum Jet Dimensions (mm)

Size A B W H C D E F J KWeight

(Kg)

906 300 217 261 170 36 87 85 146 1.5

1206 376 217 337 170 36 87 85 146 1.7

1806 529 217 490 170 36 87 85 146 2

2406 681 217 642 170 36 87 85 146 2.5

2010 579 319 540 271 63 138 150 207 5.5

2510 706 319 667 271 63 138 150 207 6.5

3010 833 319 794 271 63 138 150 207 7.0

3510 960 319 921 271 63 138 150 207 7.5

DJ DJ DJ-OB

Nomenclature

X in m = Throw distance∆pt in Pa = Total pressure drop

Note

The combinations of flow rate and size as shown in the tableproduce a sound power level:

LPNR = 40

Order Code

Jet NozzlesType DJ

Throw distance and pressure drop

V.

(l/s) 100 150 250 350 450 550 650 750 850 1000 1200 1400 1500

X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m) X (m)Size

∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆pPt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa)

9064 9 28 50

20 45 125 245

12062 5 15 32 50

12 25 70 130 225

18063.2 10 20 31 5012 35 63 100 135

24066 13 20 30 40 50

30 37 50 75 100 130

201010 15 23 29 3525 38 58 70 90

251011 17 22 28 36 5024 30 40 50 70 100

301012 16 20 27 36 5022 28 38 50 70 90

351016 21 30 40 5026 35 50 68 75

Page 20: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

20

Dimensions (mm)

FB

47

704.5

ØD2

2

ØD3

163

ØD1

2

4

3

1

1 Diffuser core, ring spacing 6 mm2 Trim ring with spring clips3 Height adjustable dirt trap4 Swirl element

Size ØD1 ØD2 ØD3

150 200 149 137

200 250 199 187

600 mm600 mm

∆tZ max = -6K∆tZ max = -10K

Mindestabstand Mindestabstand

Discharge situation

horizontal(displacement flow)

Minimum distancecomfort zone

Minimum distancecomfort zone

vertical(mixed flow)

Floor DiffusersType FB

IEEEEEEEOEEEEEEEP

IEEEEEEEEOEEEEEEEEP

1) For orders without trim ring, a spacing ring is provided for technicalperformance reasons and to ensure correct height

2) For orders without adjustable swirl element, the discharge direction is vertical3) Only available for size 200

Surface of diffuser core and trim ring:Die cast and deburred 1Die cast, deburred,tumble fettled black stove enamel,face skimmed 3Die cast, deburred,face skimmed 4

Adjustable swirl element2)for discharge controlvertical Vhorizontal Hvertical fixed (3 VF

A Plenum box

Type Type

SM Dirt trap includingadjustable flow ratecontrol at rear

SV Dirt trap includingadjustable flow ratecontrol at face

KF1) Trim ring

Size

Order Code - Aluminium Order Code - Plastic

150/

Surface of diffuser, core and trim ring:Dusty grey 1similar to RAL 7037Black 2similar to RAL 9005

Adjustable swirl element2)for discharge controlvertical Vhorizontal Hvertical fixed (3

A Plenum box

Standard 0Plastic (PA6)

flame retardant V00(PA6-V0)

SM Dirt trap includingadjustable flow ratecontrol at rear

SV Dirt trap includingadjustable flow ratecontrol at front

KF1) Trim ring

Size

FBK - 1 - V - KF - SM - A 150 V00/ /

IEEOEEP

IEEOEEP

IEEEEEEEEEEEEEEEEEOEEEEEEEEEEEEEEEEEP

TEEEEEEEEEEEEEZEEEEEEEEEEEEUTEEEEEEEEEEEEEZEEEEEEEEEEEEU

Throw distance and pressure dropHorizontal Discharge Vertical

Size Throw (m) Discharge

0.3 m 0.9 m 1.2 m

150Air Volume (l/s) min - max 10 - 16 15 - 25 18 - 30 10 - 30

Press Drop (Pa) min - max 8 - 20 18 - 50 28 - 70 5 - 35

200Air Volume (l/s) min - max 16 - 27 21 - 35 25 - 41 10 - 50

Press Drop (Pa) min - max 8 - 20 13 - 35 18 - 50 5 - 50

Max noise level LWNC 40. Data for FBA diffusers and dirt trap, damper fully open no plenum box. Horizontal discharge is throwdistance to terminal velocity of 0.15m/s (min vol) and 0.25m/s (max vol). A 600mm clear zone (from centre of diffuser) isrecommmended with vertical discharge.

FBA - 1 - V - KF - SM - A

Page 21: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

21

AFG-A AFG-AG

DetailA

6mm13mm Nominal Pitch

90mm MaximumPedestal

'A' u +0.5/-1mm

25 Min

X can be in 1mm stepsup to 50mm

Shims to suit height required(factory fitted)

X

C

B

Floor GrilleType AFG

AFG

Dimensions (mm)

Nominal Size A B C

600 x 600 599 68.5 140 approx

Detail A (variable pedestal height)

Test Result

Stability of deflection (centre of grille):

4.5 kN static load through 25mmsquare indentor

Impact load test:

40 kg Sand Bag from 1mheight

Deflection 23 hours after loadapplied - 3mmDeflection 24 hours after loadapplied - 3mm0.09mm permanent deformation0.01mm permanent indentation

Did not collapse

Test Result

Dynamic rolling load test:

4.5 kN load 50 passes of wheel3 kN load 50 passes of wheel

3 kN load 50 passes of wheel

Safety load test(centre of grille):

13.5 kN load through 25mmsquare indentor

Did not collapse0.40mm Vertical permanentdeformation (max)0.20mm Horizontal permanentdeformation (max)

Did not collapse

Sound power level and pressure drop

V.

(l/s) 100 150 200 250 300 350 400 450 500

Damper ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa) ∆Pt (Pa)Position LWA LWA LWA LWA LWA LWA LWA LWA LWA

100%1.1 2.4 4.3 6.6 9.4 12.6 16.4 20.6 25.3

<15 <15 18 24 31 36 41 44 47

50%1.4 3.0 5.3 8.2 11.7 15.8 20.6 25.9 32

<15 <15 22 28 35 40 44 48 51

Rear Assemblies

Face only A

Rear opposed blade damper AG

Size (mm)Type P2 Polyester powder coat silver grey

RAL 9006 25% Gloss (Standard)P4 Polyester powder coat black

RAL 9005 20% Gloss

Frame Depth (mm) between face ofgrille and face of pedestal 25 standardOptionally 26 - 50 in 1mm steps

Order Code AFG - A 600 x 600 0 35 P2

Not used

/ / / /

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEP

Page 22: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

22

NF

FL

TZ

PL

Order Code

TEEEEEEEEEZEEEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

Slot DiffusersType VSD35

VSD35

Face Dimensions 'P' (mm)No. of NF FL TZ PLslots

1 44 64 - -

2 71 91 - -

3 98 118 133 -

4 124.5 144.5 - 299

Diffuser layoutflow dischargehorizontal, one direction

flow dischargealternating horizontal

ƒH1 ƒL

A X

1,80

m

ƒL

X

1,80

m1.80

m

1.80

m

Type ‘P’ end cap

Type ‘A’ end cap

Type ‘P’ end cap

Type ‘PL’ end cap

Type ‘L’ end cap

/ / / / / /

Blade SettingHH1 = All blades in one directionHH2 = Alternating blades every 300mmHA2 = 45o Alternating blades every 150mmHH3 = Alternating blade 33%/66%.

150mm then 300mm

Finish/colourP3 = powder coated to RAL 9010 20%1

P2 = powder coated to RAL 9006 25%P4 = powder coated to RAL 9005 20%P6 = other colours to RAL

1) standard finish

TypeVSD35

Style Black WhiteBF WFBL WLBN WNBE WEF=FiniteL=LinearN=Non activeE=Mitre*

No. of Slots1 to 4

FlangeNF= Not flangedFL = FlangedPL = Plank ceiling1

TZ = Techzone21) 4 slot only2) VSD35 3 slot only

End Cap0 = No end plate/angleP0X1 = Plate A0X1 = AngleL0X1 = Offset anglePL0X1 = Plank

1) where X = 1 or 2

Fixings0 = WithoutFK = Fixing kit

VSD35-V3-BF-4-FL-A02 0 P3 20%RAL 9010 HH2

Length L1 mm length of diffuseror angle* of mitre in degrees*Only in 90o or 135o with 200mminside leg

1200

Tolerance Length ‘L1’ +/- 1 Width ‘P’ +/- 1

TEEEEEEEEEEEEEZEEEEEEEEEEEEEEEEEEU

Page 23: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

23

Slot DiffusersType VSD35

Throw distance X (m) · VSD35-1flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

12 0.913 1.4 0.414 1.8 0.8 0.215 2.0 1.0 0.416 1.2 0.6 0.218 1.8 1.0 0.4 0.220 1.4 0.8 0.4 0.225 1.8 1.2 0.6 0.430 2.0 1.4 0.9 0.635 1.6 1.1 0.840 1.8 1.4 1.045 2.0 1.650 2.0

Throw distance X (m) · VSD35-2flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

25 3.0 2.830 5.0 4.1 1.635 2.7 1.640 3.7 2.5 1.645 3.4 2.3 1.650 3.2 2.3 1.655 3.1 2.3 1.660 3.0 2.3 1.865 2.9 2.1 1.870 3.5 2.7 2.180 4.5 3.7 3.185 4.3 3.590 4.2

Throw distance X (m) · VSD35-3flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

30 3.035 4.4 2.440 6.0 3.6 2.145 4.9 3.150 6.0 4.0 2.755 5.0 3.3 2.4

60 4.2 3.1 2.365 3.8 2.770 4.4 3.3 2.475 4.1 3.0 2.480 3.6 2.9 2.285 3.3 2.6 2.190 4.0 3.1 2.4100 5.0 4.0 3.3110 5.0 4.2120 5.2

Throw distance X (m) · VSD35-4flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

40 4.445 5.8 3.450 4.355 5.5 3.660 4.4 3.065 5.3 3.7 2.670 4.4 3.175 5.2 3.8 2.880 4.4 3.2 2.485 5.2 3.9 3.0 2.390 6.0 4.4 3.4 2.795 5.0 3.8 3.1 2.4100 6.0 4.4 3.5 2.9 2.3110 5.6 4.4 3.5 3.0120 5.5 4.4 3.7130 6.6 5.3 4.4140 6.4 5.3150 6.2

VSD35 flow discharge alternating horizontalNo. ofslots“n”

Flow rate ranges (l/s)L1 (mm) (Ø198 Spigot)

600 750 900 1050 1200 1350 1500 1650 1800 1950‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max

V.

10 16 12 19 14 23 16 26 18 30 20 32 23 36 25 40 27 45 29 471 Pa 7 15 7 15 7 15 7 15 7 15 7 15 7 15 7 15 7 15 7 15

LWA <15 25 <15 25 <15 29 15 29 17 31 18 31 20 33 18 31 19 33 20 33

V.

15 30 19 38 23 44 26 50 30 55 34 60 38 64 41 74 45 80 49 882 Pa 4 15 4 15 4 15 5 15 5 15 6 15 6 15 6 15 6 15 6 15

LWA <15 29 <15 32 15 33 17 35 19 35 20 35 22 36 19 35 20 36 21 37

V.

23 43 29 54 34 60 40 68 46 77 51 82 57 90 63 106 68 115 74 1203 Pa 5 15 5 15 6 15 6 15 6 15 6 15 6 15 7 15 7 15 7 15

LWA <15 30 16 33 18 33 20 34 22 36 23 36 24 37 22 36 23 37 24 37

V.

30 50 38 62 45 75 53 86 60 95 68 102 75 105 83 135 90 148 98 1584 Pa 5 11 5 12 5 14 6 15 6 15 7 15 8 15 6 14 6 15 6 15

LWA <15 25 15 28 17 30 19 32 21 33 22 33 23 32 22 35 23 36 24 36

Nomenclature

‡ in l/s = Flow rateX in m = Throw distanceL1 in mm = Length of plenum boxA in m = Distance between 2 diffusersƒH1 in m/s = Time average air velocity between

2 diffusersƒL in m/s = Time average upstream velocity at the wall

Note

Room height = 2.8 m Sound power level is LWA � 40 dB(A)

ƒH1 = <0.25 m/s Pressure drop ∆Pt � 15 Pa

ƒL = <0.5 m/s Alternating Blow based on 'X' = 1.0 'A' = 3.0

1) 1650, 1800 & 1950 long plenums c/w 2x Ø198 spigots

Page 24: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

24

Slot DiffusersType VSD50

NF

FL

PL

Order Code

TEEEEEEEEEZEEEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

VSD50

Face Dimensions 'P' (mm)No. of NF FL PLslots

1 59.5 79.5 -

2 101.5 121.5 -

3 143.5 163.5 299

4 185.5 205.5 299

Diffuser layoutflow dischargehorizontal, one direction

flow dischargealternating horizontal

ƒH1 ƒL

A X

1,80

m

ƒL

X

1,80

m1.80

m

1.80

m

Type ‘P’ end cap

Type ‘A’ end cap

Type ‘PL’ end cap

Type ‘L’ end cap

/ / / / / /

Blade SettingHH1 = All blades in one directionHH2 = Alternating blades every 300mmHA2 = 45o Alternating blades every 150mmHH3 = Alternating blade 33%/66%.

150mm then 300mm

Finish/colourP3 = powder coated to RAL 9010 20%1

P2 = powder coated to RAL 9006 25%P4 = powder coated to RAL 9005 20%P6 = other colours to RAL

1) standard finish

TypeVSD50

Style Black WhiteBF WFBL WLBN WNBE WEF=FiniteL=LinearN=Non activeE=Mitre*

No. of Slots1 to 4

FlangeNF= Not flangedFL = FlangedPL = Plank ceiling1

1) 3 & 4 slot only

End Cap0 = No end plate/angleP0X1 = Plate A0X1 = AngleL0X1 = Offset anglePL0X1 = Plank

1) where X = 1 or 2

Fixings0 = WithoutFK = Fixing kit

VSD50-V3-BF-4-FL-A02 0 P3 20%RAL 9010 HH2

Length L1 mm length of diffuseror angle* of mitre in degrees*Only in 90o or 135o with 200mminside leg

1200

Tolerance Length ‘L1’ +/- 1 Width ‘P’ +/- 1

TEEEEEEEEEEEEEZEEEEEEEEEEEEEEU

Page 25: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Slot DiffusersType VSD50

25

Throw distance X (m) · VSD50-1flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

15 1.4 0.7

20 3.0 1.6 1.025 4.5 2.9 1.9 1.330 4.3 2.9 2.1 1.4 1.035 4.2 2.9 2.1 1.6 1.140 3.9 2.9 2.3 1.8 1.345 3.9 2.9 2.3 1.8 1.450 3.7 2.9 1.3 1.9 1.655 3.0 2.5 1.960 3.5 3.0 2.565 3.5 3.070 3.5

Throw distance X (m) · VSD50-2flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

25 2.630 4.0 2.535 5.6 3.4 2.340 4.5 3.1 2.245 4.0 3.0 2.250 5.0 3.7 2.8 2.155 4.4 3.4 2.760 4.0 3.3 2.565 4.4 3.5 3.0 2.370 4.5 3.9 3.2 2.780 4.9 4.0 3.485 5.2 4.490 6.2

Throw distance X (m) · VSD50-3flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

35 3.540 4.645 6.2 3.550 4.655 6.0 3.760 4.6

65 5.5 3.870 6.6 4.680 6.2 4.690 6.2 4.6 3.5100 7.6 5.9 4.6 3.7110 7.4 5.9 4.6 3.8120 5.7 4.6 3.8130 6.8 5.5 4.6140 6.6 5.5150 6.4

Throw distance X (m) · VSD50-4flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

600 750 900 1050 1200 1350 1500 16501 18001 19501

50 5.055 6.660 4.665 5.670 6.5 4.375 5.080 5.985 6.9 4.790 5.595 6.1 4.5100 6.9 5.0110 6.4 4.8120 7.7 5.9 4.6130 7.1 5.5 4.5140 6.6 5.3 4.3150 6.2 5.1 4.2160 5.9 4.9170 5.7

VSD50 flow discharge alternating horizontalNo. ofslots“n”

Flow rate ranges (l/s)L1 (mm) (Ø198 Spigot)

600 750 900 1050 1200 1350 1500 1650 1800 1950‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max ‡min ‡max

V.

12 24 14 29 17 34 20 39 23 46 26 49 29 54 31 61 34 67 37 701 Pa 4 15 4 15 4 15 4 15 5 15 5 15 5 15 4 15 5 15 5 15

LWA <15 26 <15 28 <15 29 <15 30 <15 33 15 32 16 34 15 33 16 34 17 34

V.

22 39 28 49 33 59 39 68 44 79 50 86 56 92 61 107 67 117 72 1272 Pa 4 11 4 12 4 13 5 14 5 15 5 15 6 15 5 13 5 14 5 14

LWA <15 25 <15 27 <15 29 16 31 17 33 18 34 20 34 18 34 19 35 20 36

V.

36 48 45 60 54 72 63 84 72 96 81 108 90 115 99 132 108 144 117 1453 Pa 4 8 5 10 6 11 7 13 8 14 9 15 9 15 8 15 9 15 11 15

LWA 17 25 18 26 19 27 20 27 20 28 21 28 21 28 22 29 22 30 23 30

V.

48 58 60 73 72 87 84 102 96 116 108 130 120 141 132 160 144 175 156 1904 Pa 6 8 7 10 8 12 9 13 10 14 11 15 11 15 9 15 9 15 11 15

LWA 19 24 20 25 20 25 21 26 22 27 22 27 23 27 23 28 23 28 24 30

Nomenclature

‡ in l/s = Flow rateX in m = Throw distanceL1 in mm = Length of plenum boxA in m = Distance between 2 diffusersƒH1 in m/s = Time average air velocity between

2 diffusersƒL in m/s = Time average upstream velocity at the wall

Note

Room height = 2.8 m Sound power level is LWA � 40 dB(A)

ƒH1 = <0.25 m/s Pressure drop ∆Pt � 15 Pa

ƒL = <0.5 m/s Alternating Blow based on 'X' = 1.0 'A' = 3.0

1) 1650, 1800 & 1950 long plenums c/w 2x Ø198 spigots

Page 26: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

26

TypeVSD35VSD50

Plenum Type0 = Standard plenumEH = Extended heightRA = Light baffle return air

No. of Slots1 to 4

Lining- NoneD12 = 12mm

Slot DiffusersType AKV-VSD

AKV-VSD Type '0' Type 'EH'

IEEOEEP

IEEOEEP

IEEOEEP

IEEOEEP

IEEOEEP

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEP

‘W1’

'Bb' Ø 'D

'

(D+

22)

'Eb'

O/A

HE

IGH

T

'W' 'X'

'X'

Ø 'D

'

(D+

22)

(Eb+

A) O

/A

HE

IGH

T

45EXTENSION

‘A’

Type Number of slots W W1 Bb Eb D Max

1 138 87 36.8 (D+71) 198

AKV-VSD352 176 114 63.6 (D+71) 248

3 214 140 90.4 (D+71) 298

4 254 167 117.2 (D+71) 353

1 138 102 52 (D+81) 198

2 176 144 94 (D+81) 298AKV-VSD50

3 238 186 136 (D+81) 353

4 310 228 178 (D+81) 448

Spigot Lengths

Spigot Length Dimension XSpigot Order Damper Suffix Up to 178Ø 198 to 398Ø

YES - M - 75mm 100mm

NO - 40mm 40mm

Order CodeAKV - VSD50 - V3 - 0 - 4 - D12 - M

Assembled height

Extended neckA = dimension mm0 = without extended neck

Spigot diameter

No. of Spigots

Length450mm to 1800mm150mm increments

Spigot Damper0 = Standard spigotM = Spigot damperMC = Cord operated

spigot damper

/ /

Extension ‘A’ Min. = 25mm All Types Max. = 700mm All Types

Plenum Length L - 300mm to 1500mm (150mm Increments)(2 Spigots available on request)

Plenum Length L - 1650mm, 1800mm , 1950mm (2 Spigots)

AKV-VSD AKV-VSD

1200 x 1 x 198 x 0 279

Page 27: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

27

Slot DiffusersType ALS20

Order Code - Diffuser

TypeALS20

StyleS = Return (without blades)NA = Non-Active (without blades)E = Mitred corner

(non-active without blades 300mm inside legs)

T2 = (2 supply blades with spreader plate)

Number of slots1 to 4

Not Used

FixingsSB = Support BracketsCF = Clip FixingsBF = Bridge FixingsBX = Bridge Fixings for extended height plenum0 =Without

Length of diffuser in mm or Angle of mitre indegrees

End Caps / End PlatesA1 = One end cap fittedA2 = End cap both ends fittedP1 = One end plate fittedP2 = End plate both ends fitted0 = None

Powder coat finish

ALS20 - T2 - 3 - A2 1200 SB 0 P3 RAL 9010 20% Gloss/ / / / / /

Diffuser layoutflow discharge horizontal, one direction

ALS20

flow discharge horizontaltwo directions

ƒH1 ƒL

A X

1,80

m

ƒL

X

1,80

m1.80

m

1.80

m

Dimensions (mm)

No of Slots

A P

1 41 769

2 80.5 115.5

3 120 155

4 159.5 194.5

DIM 'A' mm

SLOT2028

DIM 'P' mm

28

DIM 'A'mm

2820SLOTSLOT

19.52028

DIM 'P'mm

76 75

2

28

75

2

ALS20-T2-1 ALS20-T2-2 End Angle End Plate

Tolerance Length ‘L1’ +/- 1 Width ‘P’ +/- 1

Page 28: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

28

Slot DiffusersType ALS20

Throw distance X (m) · ALS20-1flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 18006 0.48 0.610 0.9 0.512 1.2 0.6 0.414 0.8 0.516 1.0 0.6 0.4

18 1.2 0.7 0.5 0.420 0.9 0.6 0.5 0.425 0.9 0.6 0.5 0.430 1.2 0.9 0.7 0.5 0.535 1.1 0.9 0.7 0.640 1.1 0.9 0.745 1.1 0.950 1.0

Throw distance X (m) · ALS20-2flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180015 1.220 1.425 2.4 1.230 1.435 1.9 1.240 1.4 1.2

45 1.8 1.450 1.7 1.255 1.360 1.4 1.265 1.370 1.4 1.275 1.3 1.280 1.4 1.3

Throw distance X (m) · ALS20-3flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180020 1.225 1.630 2.2 1.235 3.1 1.440 1.7 1.2

45 2.2 1.450 1.6 1.255 1.8 1.3 1.260 2.2 1.5 1.365 1.7 1.4 1.270 1.9 1.7 1.4 1.280 1.6 1.490 1.6 1.2100 1.3

Diffuser Spacing A (m)flow discharge horizontal, two directions

V.(l/s/m) 1 Slot 2 Slot 3 Slot* 4 Slot*20 0.830 1.6 0.840 3.2 1.6

50 5.2 2.3 1.660 3.2 2.0 1.670 5.2 3.0 2.280 4.9 3.090 3.9100 4.9

MIN Installation Height (m)No. of Rec. No. of Min. CeilingSlots Slots to Rm. Height

1 1 2.6

2 2 2.75

3 2 2.8

4 3 3.0

Throw distance X (m) · ALS20-4flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180025 1.430 2.035 2.740 3.6 1.6

45 4.8 2.050 2.5 1.455 3.0 1.760 3.6 2.0 1.470 2.7 1.780 3.6 2.3 1.690 2.9 2.0100 2.5 1.8110 2.2 1.7 1.4120 2.0 1.6

Nomenclature

‡ in l/s = Flow rateX in m = Throw distanceL1 in mm = Length of plenum boxA in m = Distance between 2 diffusersƒH1 in m/s = Time average air velocity between 2 diffusersƒL in m/s = Time average upstream velocity at the wall

Note

Room height = 2.8 m Sound power level is LWA � 40 dB(A)

ƒH1 = <0.25 m/s Pressure drop ∆Pt � 15 Pa

ƒL = <0.5 m/s

Page 29: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

29

Slot DiffusersType ALS25

Order Code - Diffuser

TypeALS25

StyleS = Return (without blades)NA = Non-Active (without blades)E = Mitred corner

(non-active without blades 300mm inside legs)

T2 = (2 supply blades with spreader plate)

Number of slots1 to 4

Not Used

FixingsSB = Support BracketsCF = Clip FixingsBF = Bridge FixingsBX = Bridge Fixings for extended height plenum0 =Without

Length of diffuser in mm or Angle of mitre in degrees

End Caps / End PlatesA1 = One end cap fittedA2 = End cap both ends fittedP1 = One end plate fittedP2 = End plate both ends fitted0 = None

Powder coat finish

ALS25 - T2 - 3 - A2 1200 SB 0 P3 RAL 9010 20% Gloss/ / / / / /

Diffuser layoutflow dischargehorizontal, one direction

ALS25

flow discharge horizontaltwo directions

ƒH1 ƒL

A X

1,80

m

ƒL

X

1,80

m1.80

m

1.80

m

Dimensions (mm)

No of Slots

A P

1 46 81

2 90.5 125.5

3 135 170

4 179.5 214.5

DIM 'A' mm

SLOT2528

DIM 'P' mm

28

DIM 'A'mm

2825SLOTSLOT

19.52528

DIM 'P'mm

76 752

28

75

2

ALS25-T2-1 ALS25-T2-2 End Angle End Plate

Tolerance Length ‘L1’ +/- 1 Width ‘P’ +/- 1

Page 30: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

30

Slot DiffusersType ALS25

Throw distance X (m) · ALS25-1flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 18008 0.910 1.312 1.8 0.914 2.5 1.216 3.4 1.5 0.9

18 4.4 1.8 1.120 5.6 2.3 1.3 0.925 3.7 2.0 1.3 1.030 5.6 2.9 1.8 1.3 1.035 4.2 2.5 1.7 1.3 1.040 2.3 1.7 1.3 1.145 2.1 1.6 1.350 2.6 2.0 1.655 1.9

Throw distance X (m) · ALS25-2flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180020 2.525 4.330 2.535 3.640 5.0 2.5

45 3.350 4.3 2.555 5.4 3.160 3.9 2.570 3.6 2.580 3.4 2.590 3.3 2.5100 3.2105 3.6

Throw distance X (m) · ALS25-3flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180025 2.730 3.835 5.240 6.7 3.1

45 3.850 4.7 2.755 5.6 3.360 6.7 3.8 2.570 5.2 3.4 2.480 6.7 4.3 3.190 5.4 3.8 2.9100 4.7 3.5 2.7110 4.2 3.3 2.6120 3.8 3.1

Diffuser Spacing A (m)flow discharge horizontal, two directions

V.(l/s/m) 1 Slot 2 Slot 3 Slot* 4 Slot*20 1.530 3.040 5.0 2.5

50 4.060 6.0 3.070 4.080 5.0 5.090 6.0100 5.0

MIN Installation Height (m)No. of Rec. No. of Min. CeilingSlots Slots to Rm. Height

1 1 2.6

2 2 2.75

3 2 2.8

4 3 3.0

Throw distance X (m) · ALS25-4flow discharge horizontal, one direction

L1 (mm) (Ø198 Spigot)V.

400 600 800 1000 1200 1400 1600 180030 3.840 6.750 10.2 4.7

60 6.770 8.9 5.280 6.7 4.390 8.3 5.4100 6.7 4.7110 5.6 4.2120 6.7 5.0130 5.8 4.5140 5.2150 4.7160 5.3

Nomenclature

‡ in l/s = Flow rateX in m = Throw distanceL1 in mm = Length of plenum boxA in m = Distance between 2 diffusersƒH1 in m/s = Time average air velocity between 2 diffusersƒL in m/s = Time average upstream velocity at the wall

Note

Room height = 2.8 m Sound power level is LWA � 40 dB(A)

ƒH1 = <0.25 m/s Pressure drop ∆Pt � 15 Pa

ƒL = <0.5 m/s

Page 31: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

31

AKV-ALS Type 'BF' Type 'CF'

Type BX or CF

IEEOEEP

IEEEEEEOEEEEEEP

IEEOEEP

Slot DiffusersType AKV-ALS

Extended Neck Plenum(Type ‘BX’ shown)

‘Bb’

Ø ‘D

’Ø

‘D

(D+

22

)

‘Eb

’ O/A

HE

IGH

T

‘W’ ‘X’

TYPICAL SLOT(VSD TYPE SHOWN)

‘Bc’

Ø ‘D

’Ø

‘D

(D+

22

)

‘Ec’ O

/A H

EIG

HT

‘W’ ‘X’

‘Bb’

Ø ‘D’

Ø ‘D’

‘W’ ‘X’

1 MIN ‘Y’ = 25mm A

EXTENSION‘Y’

(*)

(D+22)

‘Ec+Y) OR (Eb+Y) O/A HEIGHT

Type Number of slots W Bc Bb Eb D Max Ec

1 138 43 61 (D+122) 198 (D+98)

AKV-ALS202 176 82.5 100.5 (D+122) 248 (D+98)

3 214 122 140 (D+122) 298 (D+98)

4 254 161.5 179.5 (D+122) 353 (D+98)

1 138 48 66 (D+122) 198 (D+98)

2 176 92.5 110.5 (D+122) 298 (D+98)AKV-ALS25

3 238 137 155 (D+122) 353 (D+98)

4 310 181.5 199.5 (D+122) 448 (D+98)

Spigot Lengths

Spigot Length Dimension XSpigot Order Damper Suffix Up to 178Ø 198 to 398Ø

YES - M - 75mm 100mm

NO - 40mm 40mm

Order Code

VariablePlenum

Diffuser TypeALS20ALS25

Number of slots

FixingCF = Clip fixBF = Bridge fixBX = Bridge fix for extended height plenum

Overall Height (mm)Length(mm)

AKV - ALS20 - 3 - BF - D - M 1200 x 248 x 2 x 430 0 0

Spigot (mm)

Number of spigots

M = Spigot Damper or no entry

D = Lining or no entry

/ //

Extension ‘Y’ Min. = 25mm All Types Max. = 700mm All Types

Plenum length L - 300mm to 1800mm (150mm increments) Multiple spigots on request

AKV-ALS

Page 32: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

32

SDW-Q

Swirl DiffusersType SDW

Type QFace-mounted

Type QS15To ‘Lay-on’ Tegular tee-bar15mm wide x 8mm deep

Type QM15To ‘Lay-on’ Tegular tee-bar15mm wide x 16mm deep

5988 1525

595 face size

tee bar width 15584 face size8

15

16

584 face size 26 573

16

599

35

26 584

8

Type QM26To ‘Lay-on’ Tegular tee-bar26mm wide x 16mm deep

Type QBTo ‘Push-In’ spring tee-barSuitable for ‘tee’ or ‘omega’ type

Type QS26To ‘Lay-on’ Tegular tee-bar26mm wide x 8mm deep

Tile levelled viacentre screw i.e.no location pip

Nominal ΔPt LWA

Size l/s m³/h Pa dB(A)7 26 1 <15

300 x 8 35 126 15 2360 216 45 3985 306 91 5013 46 1 <15

400 x 16 60 216 13 22100 360 36 38140 504 71 50

19 70 1 <15

500 x 24 70 252 11 19125 450 35 38175 630 68 50

28 102 1 <15600 x 24 105 378 11 20625 x 24 165 594 26 34

260 936 65 5040 145 1 <15

600 x 48 130 468 12 21210 756 32 37305 1098 67 50

52 186 2 <15

625 x 54 140 504 13 22225 810 34 38310 1116 64 50

Nominal ΔPt LWA

Size l/s m³/h Pa dB(A)7 26 1 <15

300 x 8 30 108 12 2055 198 41 3880 288 87 5013 46 1 <15

400 x 16 55 198 11 21100 360 38 39140 504 74 50

19 70 1 <15

500 x 24 70 252 10 18125 450 31 36180 648 65 50

28 102 1 <15600 x 24 100 360 10 22625 x 24 170 612 28 38

240 864 56 5040 145 1 <15

600 x 48 120 432 10 22200 720 27 38280 1008 53 50

52 186 2 <15

625 x 54 130 468 10 23210 756 27 38290 1044 51 50

Diffuser Face Variants

Order Code - Diffuser

Type

Q Square flush faceQL Square lay in T barQM15 Square lay in threadline 15x16QM26 Square lay in threadline 26x16QS15 Square lay in threadline 15x8QS26 Square lay in threadline 26x8QB Spring tee ceilings

Z SupplyA ExtractF Face only (1

Panel Size600750No Entry

Number of blades

Diffuseractive size

Not used

0 Supply Air (SDW-*-Z) black blades0 Extract Air (SDW-*-A/F) no bladesQ11 Extract Air black bladesQ21 Supply Air white bladesQ21 Extract Air white blades

Powder coat finish

SDW - QS - Z 500 - 24 - 600 0 P3Q21 RAL 9010 20%/ / / / //

1) Face section without central fixing hole, for use on lay in ceilings QL, QS15, QS26, QM15 & QM26 without rear plenum

Type QLTo ‘Lay-on’ FLAT tee-bar15mm wide or 25mm wide

Quick sizing – SDW-...-ZVQuick sizing – SDW-...-ZH

Page 33: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

33

Swirl DiffusersType SDW

Paint Option0 Not RequiredP3 RAL9010:20% WhiteP4 RAL9005:20% BlackP6 RAL... BS...

Finish0 UnpaintedI Painted Internally (4

E Painted Externally

//

Order Code - Plenum

Plenum

Q Square flush faceQL Square lay in T barQM15 Square lay in threadline 15x16QM26 Square lay in threadline 26x16QS15 Square lay in threadline15x8QS26 Square lay in threadline 26x8QB Spring tee ceilings

ConstructionZH Horizontal SupplyAH Horizontal ExtractZV Vertical SupplyAV Vertical Extract

Rear Assembly0 Not applicableM Spigot damperMC Cord operated spigot damperMN Spigot damper plus test point (3

MNC Cord operated spigot damper plus test point (3

Lining- Not LinedD12 12mm Lining

Height of Plenum Box

Number of blades(see SDW order code)

2) For spigot sizes, refer to table on previous page3) Available on type ZH only (horizontal supply)4) Not available on type ...-ZV (vertical supply)

Active Sizeof Diffuser

Spigot2)

Size (mm)

500 x 198 x 24 x 276/ P3E RAL 9010 20%//AKV - SDW - Q - ZH - D12 - MN

SDW-Q

① Diffuser face

② Central fixing screw

③ Adjustable air control blades

④ Plenum box

⑤ Cross bar

⑥ Suspension hole

⑦ Spigot

⑧ Lip seal

⑨ Damper blade for volume flow rate balancing

⑩ Pressure tap

⑪ Cord for closing the damper blade

⑫ Cord for opening the damper blade

⑬ Measuring tube

SDW-Q-...-H

SDW-Q-...-V

'X'

H1 Ø

D

See Type below

W1

W1

H2

See Type below

Dimensions SDW-Q / QL* (mm)

Size ØD W1 H1 H2 X X1

300 x 8 158 290 236 154 40 75

400 x 16 198 373 276 174 40 100

500 x 24 198 477 276 174 40 100

600 x 24 248 567 326 199 40 100

600 x 48 248 584 326 199 40 100

625 x 54 248 612 326 199 40 100

Note: ‘1’ dimension when selected with spigot damper

Page 34: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

34

Swirl DiffusersType SDW

SDW-Q

Minimumflow rate

Flow rate (l/s) – Arrangement single-row

Diffuser layout

Flow rate (l/s) –Arrangement square/rectangular

SizeB A (m)

(m) 1.2 1.8 2.4 3.0 3.6 4.2300 x 8 56 52 54 60 60 60400 x 16 74 72 78 84 102 104500 x 24 88 80 84 110 108 120600 x 24 3.0 106 104 112 124 154 180600 x 48 124 120 122 130 160 190625 x 24 106 104 112 124 154 180625 x 54 145 180 214300 x 8 60 60 60 60 60 60400 x 16 88 86 94 102 104 104500 x 24 110 100 104 108 130 130600 x 24 3.6 128 126 138 154 180 186600 x 48 150 140 152 160 180 226625 x 24 128 126 138 154 180 186625 x 54 164 150 166 178 200 232300 x 8 60 60 60 60 60 60400 x 16 102 100 104 104 104 104500 x 24 130 122 124 122 130 130600 x 24 4.2 150 146 160 180 186 186600 x 48 180 170 180 190 226 226625 x 24 150 146 160 180 186 186625 x 54 194 180 190 210 232 232

B≥1

/2B

≥1/2AA A

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA, B in m = Distance between two diffusers

Note

In all cases, the sound power level is LWA � 40 dB(A) per diffuser and the pressure drop ∆Pt � 40 Pa.

Selection valid for ceiling height = 2.7...3 m.

SizeA (m)

0 1.2 1.8 2.4 3.0 3.6 4.2300 x 8 60 60 60 60 60 60 60400 x 16 104 102 100 104 104 104 104500 x 24 133 133 122 124 133 133 133600 x 24 188 150 146 160 188 188 188600 x 48 226 180 170 180 226 226 226625 x 24 188 150 146 160 188 188 188625 x 54 232 196 180 190 232 232 232

Size V.min

300 x 8 15

400 x 16 30

500 x 24 45

600 x 24 60

600 x 48 120

625 x 54 145

Page 35: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

35

Swirl DiffusersType XARTO

① Diffuser face

② Central fixing screw

③ Swirl unit (for supply air only)

④ Damper blade for volume flow rate balancing

⑤ Spigot

⑥ Double lip seal

⑦ Suspension lug

⑧ Equalising element (for supply air only)

⑨ Cross bar

Nominal Size �Q1 H1 ØD3 H3 ØD A C

600 598 8 462 371 248 220 60

625 623 8 462 371 248 220 60

XARTO-Q1

XARTO-Q XARTO-Q1 XARTO-Q2 XARTO-Q3 XARTO-Q4

XARTO-Q5 XARTO-Q6XARTO-Q Dimensions (mm)

Nominal Size �Q1 H1 ØD3 H3 ØD A C

600 598 8 462 356 248 205 60

625 623 8 462 356 248 205 60

XARTO-R XARTO-R1 XARTO-R2 XARTO-R3 XARTO-R4

XARTO-R Dimensions (mm)

Page 36: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

36

Swirl DiffusersType XARTO

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA, B in m = Distance between two diffusers

Note

In all cases, the sound power level is LWA � 40 dB(A) per diffuser and the pressure drop ∆Pt � 45 Pa.

Selection valid for ceiling height 2.7 m to 3 m. with VH1 = <0.25 m/s

Diffuser layout

B≥1

/2B

≥1/2AA A

Flow rate (l/s) – Arrangement single-row

SizeA (m)

0 1.2 1.8 2.4 3.0 3.6 4.2

600200 150 145 130 140 190 200

625

Minimumflow rate

Size V.min

600625

75

Flow rate (l/s) –Arrangement square/rectangular

SizeB A (m)

(m) 1.2 1.8 2.4 3.0 3.6 4.2600 2.4 100 100 103 107 134 200625

6003.0 120 120 125 128 162 200

625

6003.6 137 137 130 135 180 200

625

6004.2 148 148 130 140 190 200

625

Nominal Size �Q1 H1 ØD3 H3 ØD A C

600 600 8 462 356 248 205 60

XARTO-C XARTO-C1 XARTO-C2 XARTO-C3 XARTO-C4

XARTO-C5 XARTO-C6XARTO-C Dimensions (mm)

Page 37: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Swirl DiffusersType XARTO

Circular (R1...R4) R*Square (Q1...Q6) Q*Circular (C1...C6) C*

Supply ZExtract A

Size600 □Q, ∅D625 □Q only

Type No entry: powder-coated RAL 9010,pure white

P1 Powder-coated,specify RAL CLASSIC colour

Gloss levelRAL 9010 50 %RAL 9006 30 %All other RAL colours 70 %

Order Code

Quick sizing – sound power level and total differential pressure

XARTO - Q4 - Z 600 P1 - RAL .../ /

TEEEEEEEEEEEEZEEEEEEEEEEEEU

IEEEEEEOEEEEEEP

IEEEEOEEEEP

Q*-Z

Diffuser Δpt LWA

Face l/s m³/h Pa dB(A)39 142 2 <15

Q1 100 360 11 19160 576 29 32260 936 77 5038 137 2 <15

Q2 105 378 13 21175 630 36 35255 918 76 5042 151 2 <15

Q3 115 414 14 22185 666 37 37258 930 72 5034 124 1 <15

Q4 105 378 13 22175 630 37 37

245 882 73 5042 150 2 <15

Q5 115 414 14 22190 684 38 37265 954 75 5043 155 2 <15

Q6 120 432 16 23190 684 39 37260 936 73 50

XARTO-C* / R*-Z

Diffuser ΔPt LWA

Face l/s m³/h Pa dB(A)38 138 2 <15

C1 105 378 13 24R1 170 612 33 38

240 864 66 5038 138 2 <15

C2 105 378 12 23R2 170 612 32 36

240 864 65 5038 136 2 <15

C3 105 378 13 23R3 170 612 33 37

240 864 65 5031 110 1 <15

C4 95 342 12 23R4 155 558 31 37

220 792 63 5038 138 2 <15

C5 110 396 14 26180 648 37 39250 900 72 5138 138 2 <15

C6 110 396 14 26180 648 36 39250 900 70 50

Quick sizing tables provide a good overview of the volume flow rates and corresponding sound power levels and differentialpressures.

The minimum volume flow rates apply to a supply air to room air temperature difference of –6 K.

The maximum volume flow rates apply to a sound power level of approx. 50 dB (A) with damper blade position 0°.

37

Page 38: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

38

Minimumflow rate

Dimensions (mm)

Flow rate (l/s) –Arrangement square/rectangular

Square QCircular R

Nozzle D

Collar K

Top entry plenum US

Plenum box A

SizeType Specify RAL colour

0 Standard finishpowder coatedto RAL 9010 (GE 50%)1)

P1 Powder coatingto RAL 9006 (GE 30%)1)Other coloursto RAL... (GE 70%)1)

RFD-Q/R-D-A RFD-Q/R-D-K RFD-Q/R-D-US

Order Code RFD - Q - D - A 400 0 0 P1 RAL 9016/ / / / /

1) GE = Gloss level

Flow rate (l/s) – Arrangement single-row

SizeA (m)

0 1.2 1.8 2.4 3.0 3.6 4.2125 29 29 29 29 29 29 29160 50 50 48 48 50 50 50200 75 68 59 59 63 70 75250 116 82 70 70 75 82 116315 163 120 105 104 110 122 163400 215 125 118 125 140 160 215

Diffuser layout

Size ØA ØD H2 U2 U4 �Q2 ØR2 �K

125 123 98 284 75 153 198 200 216160 158 123 309 78 158 248 250 266200 198 158 339 78 161 248 300 290250 248 198 384 75 166 298 350 476315 313 248 444 88 183 398 450 567400 398 313 509 88 193 498 580 615

B≥1

/2B

≥1/2AA A

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA, B in m = Distance between two diffusers

Note

In all cases, the sound power level is LWA � 40 dB(A) per diffuser and the pressure drop ∆Pt � 45 Pa.

Selection valid for ceiling height 2.7 m to 3 m. with VH1 = <0.25 m/s

IEEOEEPTEEEEEEEEEEEEZEEEEEEEEEEEEU

H2

w K

ØD

ØR2w Q2

ØR2�Q2

ØR2�Q2

ØA

ØD

U2

U4

40

These codes need not be completed for standard products

IEEEEEEOEEEEEEP

Swirl DiffusersType RFD

SizeB A (m)

(m) 1.2 1.8 2.4 3.0 3.6 4.2125 18 18 22 27 28 29160 25 25 30 35 42 48200

2.433 33 39 45 53 58

250 33 33 43 56 64 70315 64 80 93 103400 75 98 112 125125 25 26 27 29 29 29160 33 34 35 38 45 50200

3.042 43 45 48 56 62

250 52 53 55 55 67 74315 75 75 78 78 98 110400 85 88 98 88 125 140125 28 28 28 28 28 28160 43 41 41 42 50 50200

3.655 51 52 55 62 70

250 66 63 63 68 70 83315 95 91 93 96 100 120400 105 105 112 118 100 160125 28 28 28 28 28 28160 50 47 47 50 50 50200

4.268 58 58 62 70 75

250 82 70 70 75 82 90315 120 105 103 110 120 130400 125 115 125 140 160 120

Size V.min

125 7160 12200 20250 30315 55400 75

RFD-Q

Page 39: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

39

Swirl DiffusersType RFD

① Diffuser face

② Central fixing screw

③ Plenum box

④ Cross bar

⑤ Suspension hole

⑥ Spigot

RFD-*-ANominal ΔPt LWA

Size l/s m³/h Pa dB(A)4 14 2 <15

125 10 36 17 2815 54 38 3822 79 82 505 18 1 <15

160 15 54 9 1630 108 35 3447 169 86 507 25 1 <15

200 25 90 12 2144 158 36 3570 252 91 5010 36 1 <15

250 45 162 14 2575 270 40 38

110 396 86 5019 68 1 <15

315 70 252 12 24120 432 35 39175 630 75 5027 97 1 <15

400 90 324 10 24160 576 33 40220 792 63 50

RFD-*-D-K ΔPt LWA

l/s m³/h Pa dB(A)4.4 16 1 <1515 54 8 1830 108 33 3646 166 79 506.4 23 1 <1525 90 8 1645 162 26 3376 274 74 509 32 0 <15

45 162 11 2375 270 31 37

110 396 66 5014 50 0 <1565 234 10 21

115 414 33 38164 590 66 5025 90 1 <1595 342 11 23

165 594 32 38240 864 67 5036 130 1 <15

135 486 12 24235 846 36 40330 1188 71 50

RFD-*-D-US ΔPt LWA

l/s m³/h Pa dB(A)4.4 16 1 <1515 54 10 1725 90 28 3438 137 64 506 22 1 <15

25 90 9 1645 162 29 3566 238 62 509 32 1 <15

40 144 22 2070 252 66 37

102 367 140 5014 50 1 <1560 216 21 22

105 378 63 39145 522 120 5025 90 2 <1590 324 21 22

155 558 62 38220 792 125 5036 130 1 <15

120 432 17 22205 738 49 38285 1026 95 50

Schematic illustration of the RFD-R-D, with plenum box for horizontal duct connection

②①

⑥⑤

RFD-R-D

Page 40: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

40

Dimensions (mm)

DCS-P DCS-P-...-A resp. -AK DCS-P-...-K DCS-P-...-US

Flow rate (l/s) – Arrangement single-row

SizeA (m)

0 1.2 1.8 2.4 3.0 3.6 4.2125 27 27 27 27 27 27 27160 47 47 47 47 47 47 47200 68 48 60 60 65 68 68250 96 66 75 74 84 96 96315 138 115 102 102 115 130 138400 190 115 110 115 128 140 190

Diffuser layoutFlow rate (l/s) –Arrangement square/rectangular

B≥1

/2B

≥1/2AA A

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA, B in m = Distance between two diffusers

Note

The sound power level is LWA � 40 dB(A) per diffuser in allcases and the pressure drop ∆Pt � 45 Pa.

Selection valid for ceiling height = 2.7...3 m. with VH1 = <0.25 m/s

w 593 (w 598, w 623)

H2

H1

xD

8

w K11 11

w 593 (w 598, w 623)

H2

8

xA

xD

8

H3

w 593 (w 598, w 623)

Swirl Diffusers with perforated sheet facingType DCS

SizeB A (m)

(m) 1.2 1.8 2.4 3.0 3.6 4.2125 16 16 21 27 27 27160 35 35 36 37 42 47200

2.456 56 50 46 54 60

250 54 54 54 56 66 75315 80 80 80 80 92 104400 75 75 85 92 106 116125 26 26 27 27 27 27160 35 35 37 44 46 47200

3.043 44 46 60 58 66

250 53 53 56 66 72 85315 76 80 80 96 102 116400 82 86 92 96 116 128125 27 27 27 27 27 27160 44 42 42 44 44 47200

3.656 52 54 54 58 68

250 68 65 66 65 64 96315 96 90 92 94 94 130400 100 98 106 114 96 140125 27 27 27 27 27 27160 47 47 47 47 47 47200

4.268 60 60 66 68 68

250 86 74 75 85 96 88315 118 102 102 116 130 130400 116 110 116 128 140 122

Size ØA ØD H1 H2 H3 �K

125 123 98 156 76 154 180160 158 123 180 79 159 215200 198 158 215 79 162 255250 248 198 255 76 167 305315 313 248 305 89 184 370400 398 313 361 89 194 454

Minimumflow rate

Size V.min

125 7160 12200 20250 30315 55400 75

Face plate:Perforated PNon-perforated Nwith discharge nozzle ring C

T-bar:Visible VHidden H

Connection KTop entry plenum USPlenum box APlenum box AKwith acoustic insulation

Size125160200250315400

Type Specify RAL colour

0 Standard finishpowder coatedto RAL 9010 (GE 50%)1)

P1 Powder coatingto RAL 9006 (GE 30%)1)Other coloursto RAL... (GE 70%)1)

Order Code DCS - P - V - AK 5932) x 315 P1 RAL 9016/ / /

1) GE = Gloss level2) 593 x ... with face plates ...-V

598 x ... and 623 x ... with face plates ...-H

IEEOEEP

TEEEEEEEEEEEEZEEEEEEEEEEEEUIEEEEEEEEEOEEEEEEEEEP

IEEEEOEEEEP

These codes need not be completed for standard products

Page 41: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

41

Swirl Diffusers with perforated sheet facingType DCS

① Diffuser face

② Discharge nozzle

③ Blade

④ Plenum box

⑤ Suspension lug

⑥ Spigot

DCS-P-A, DCS-P-AK,DCS-N-A, DCS-N- AK

Nominal ΔPt LWA

Size l/s m³/h Pa dB(A)4 16 1 <15

125 15 54 13 2125 90 36 3539 140 88 516 23 1 <15

160 25 90 12 2045 162 40 3665 234 84 509 32 1 <15

200 35 126 11 2265 234 39 3990 324 76 5014 50 1 <15

250 50 180 10 2390 324 34 38

128 462 68 5025 90 1 <15

315 80 288 12 25130 468 31 38185 666 62 5036 128 1 <15

400 110 396 11 25180 648 29 39250 900 57 50

DCS-P-K, DCS-N-K

ΔPt LWA

l/s m³/h Pa dB(A)4 16 1 <15

20 72 17 2830 108 38 4040 146 69 506 23 1 <15

30 108 16 2650 180 43 3970 252 85 509 32 1 <15

35 126 8 2165 234 28 3798 354 65 5014 50 1 <1555 198 10 2695 342 29 39

135 486 59 5025 90 1 <1585 306 9 27

145 522 27 40200 720 52 5036 128 1 <15

110 396 9 26185 666 27 39260 936 53 50

DCS-P-US, DCS-N-US

ΔPt LWA

l/s m³/h Pa dB(A)4 16 1 <15

20 72 19 3030 108 43 4337 132 64 506 23 1 <15

30 108 15 2950 180 42 4363 225 66 509 32 1 <15

35 126 17 2265 234 57 38

93 334 116 5014 50 1 <1550 180 16 2285 306 47 36

128 460 106 5025 90 2 <1585 306 21 28

145 522 60 42180 648 92 5036 128 2 <15

110 396 16 26180 648 42 39250 900 81 50

Schematic illustration of the DCS, with perforated diffuser faceand plenum box for horizontal duct connection

DCS-P

Quick sizing – sound power level and total differential pressure

Page 42: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

42

Swirl DiffusersType VDL

Discharge ring without flange ADischarge ring with flange B

Side entry spigot HTop entry spigot VDiffuser face only F

With lip seal L1)

Diffuser face not removable N1)

Diffuser face removable D1)

With square collar K2)

With protection grid S2)

M manually adjustableE1 electric actuator, 230 V, 50 HzE2 electric actuator, 24 V, 50 HzE3 electric actuator, 24 V, 50 Hz, 2...10 VX fixed blades (for horizontal flow discharge only)

Order code These codes need not be completed for standard products

/ / / / /VDL - B - H - L - D - S - E3 RAL 9016400 0 0 P1

Specify colour

0 Standard finishpowder coatedto RAL 9010 (GE 50%)3)

P1 Powder coatingto RAL 9006 (GE 30%)3)Other coloursto RAL.. . (GE 70%)3)

Size

IEEOEEP

IEEEEEEEEEEEEEEOEEEEEEEEEEEEEEEP

Not used

1) only in combination with constructions H and V2) only in combination with discharge ring B3) GE = Gloss level

IEEEEOEEEEP

IEEOEEPIEEOEEP

IEEEEEEEEEOEEEEEEEEEP

VDL VDL-...-F VDL-...-V VDL-...-H

H1

ØD2ØD3

ØD1

H2(

X)H

3(M

)

A

H4

ØD2

ØD3

ØD1

A

ØD2ØD3

H8

ØD

5

H6

H7

H5

mK

ØD465

A

Dimensions (mm)Size A ØD1 ØD2 ØD3 ØD4 ØD5 H1 H2 H3 H4 H5 H6 H7 H8 �K315 42 313 464 381 317 248 145 92 80 215 474 150 282 290 435400 45 398 567 468 402 313 157 101 89 236 581 168 368 351 500630 51 628 871 700 628 398 204 117 105 367 812 293 468 526 750800 55 798 1077 871 798 498 229 123 111 538 1081 458 568 741 1000

Technical Data Diffuser layout

Nomenclature‡ in l/s = Flow rate‡min in l/s = Minimum flow rateH in m = Room heightH1 in m = Distance between discharge level and occupied zoneH1 in m = jet penetration distance, vertical discharge,

in heating operationAmin, B in m = Distance between 2 diffusersXmin in m = Distance from wallƒH1 in m/s = time average air velocity between 2 diffusersƒL in m/s = time average air velocity at the wallLWA in dB(A) = Sound power level∆pt in Pa = Pressure drop

NoteB = > 5 mƒH1 = < 0.2 m/sƒL = 0.4 m/sXmin = 2 m

Selection valid for ceiling height 3.8 m to 6.8 m

VDL-...-H Heating mode Cooling modeH = 3.8 H > 6.8

Size LWA V.

∆pt H1 Amin Amin

40 111 29 1.2 2.0 2.0315 50 152 52 2.0 2.0 2.0

60 208 95 3.0 2.0 2.040 222 37 2.5 2.0 2.0

400 50 305 75 3.5 2.3 2.060 430 140 5.0 3.5 2.040 416 30 2.8 2.5 2.0

630 50 583 60 5.0 4.0 2.060 902 125 7.5 5.3 2.740 555 23 3.0 2.7 2.0

800 50 763 47 5.0 4.5 2.160 1041 90 6.5 5.0 2.7

1.80m

Minimumflow rate

Size V.min

315 70

400 125

630 230

800 320

Page 43: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

43

Ceiling DiffusersType ADT

ADT

Order Code - Diffuser

Type ADTFADTBADTAADTTADTMADTS

Size150 x 150225 x 225300 x 300375 x 375450 x 450525 x 525600 x 600*

ADTF - 4 - AG 225 x 225 P3 RAL 9010 20%/ / / /

Blanking PlateBP-ADT / 450Diffuser sizeDischarge 4

directions 322C1

Rear AncillariesA Diffuser face onlyAG Opposed blade damper fitted to rear of diffuser

P3 Powder coated white RAL9010 20% gloss (standard)P4 Powder coated black RAL9005 20% glossP6 Powder coated colour RAL...

Gloss levelState colour

Note: Where TROX plenums are to be supplied. AG damper should be specified within plenum assembly.

Nominal Duct Size L x H

Size 150 225 300 375 450 525 600

ADTF l l l l l l l

ADTA l l l l l l

ADTB l l l l l l

ADTT l l l l l l l

ADTM l l

ADTS l l

L x H

(L + 145) (H + 145) O/A

53

15

(L + 145) (H + 145) O/A

53 7

L x H

(L + 150) (H + 150) O/A

53

715

L x H

(L + 133) (H + 133) O/A

53

‘Z’

L x H

Location clipson border (2 eachon opposite sides)

Location clipson border (2 eachon opposite sides)

25

To fit ceiling opening size (L / H +100) To ‘lay-on’ ceiling ‘T’ supports.

Detail X ADTA ‘PIP’ heights

Detail Y ADTB ‘PIP’ heights

NB: Non-standard heights available on request

Detail X & Y

To suit threadline support bar ceiling.

ADTM : 'Z' = 16mm / ADTS : 'Z' = 8mm

27.5

ADTF

ADTA / ADTB

ADTT ADTM / ADTS

Page 44: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

44

Ceiling DiffusersType ADT

ADT

Dimensions (mm)Size ØD K E X

150 148/1231 148 322 40 / 752

225 198 223 372 40 / 1002

300 248 298 422 40 / 1002

375 348 373 522 40 / 1002

450 398 448 572 40 / 1002

525 398 523 572 40 / 1002

600 398 598 572 40 / 1002

‘X’

25

Optiontype ‘AGP’

‘ØD

'E' O

/A h

eigh

t

Option type ‘M’1)

K

‘ØD’4

0

242

Optiontype ‘AGP’

K

AKV-ADT-ZH ...-AH AKV-ADT-ZV ...-AV

Order Code - Plenum Box

VariablePlenum

Diffuser TypeADT

ZH Horizontal spigot (supply)AH Horizontal spigot (extract)ZV Vertical spigot (supply)AV Vertical spigot (extract)

0 No damperM Spigot damper 2)MC Spigot damper cord operated 2)AG Opposed blade damper fitted to

body of plenum

0 No liningD Lining

Spigot Dia (mm)

Plenum size (mm)

Overall Height (mm)(including diffuser)1)

1) For ZH, AH minimum O/A height = Spigot diameter + 174 mmFor ZV, AV height fixed at 242mm

2) Not available for vertical spigots

DiffuserSize (mm)

450 x 248 x 300 x 380/

1) Reduced spigot size type...-ZV / ...-AV2) Increased length spigot, type ...-M / ...-MC

AKV - ADT - ZH - D - M

Page 45: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Ceiling DiffusersType ADT

Type ADT performance data (without damper, if fitted, 100% open) based on diffuser & side entryplenum box

ADT

45

Supply

Nominal V.min Δpt LWA VL0.5

Size l/s m³/h Pa dB(A) m

25 90 16 22 0.8

30 108 23 27 0.9150

35 126 31 32 1.0

40 144 40 36 1.2

35 126 6 <15 1.0

55 198 14 22 1.2225

75 270 25 31 1.4

95 342 41 38 1.8

60 216 6 <15 0.8

95 342 14 23 1.5300

130 468 26 33 2.1

160 576 40 39 2.6

90 324 4 <15 1.0

160 576 14 28 2.0375

220 792 27 37 2.7

270 972 40 42 3.5

135 486 5 15 1.0

235 846 15 30 2.5450

310 1116 26 37 3.4

380 1368 39 43 4.1

180 648 6 15 1.6

275 990 14 26 2.6525

370 1332 26 35 3.4

455 1638 40 40 4.1

230 828 7 15 2.1

340 1224 15 26 2.9600

445 1602 26 34 3.7

550 1980 40 41 4.3

Extract

Nominal V.min Δpt LWA

Size l/s m³/h Pa dB(A)

25 90 10 20

30 108 14 25 150

35 126 19 30

40 144 25 33

35 126 4 <15

55 198 10 21 225

75 270 18 30

95 342 28 38

60 216 4 16

95 342 10 28 300

130 468 20 37

160 576 30 42

90 324 6 19

160 576 17 34 375

220 792 32 43

270 972 49 49

135 486 4 17

235 846 12 34 450

310 1116 21 42

380 1368 31 48

180 648 4 19

275 990 10 31 525

370 1332 18 39

455 1638 28 45

230 828 5 19

340 1224 10 31 600

445 1602 18 39

550 1980 27 45

Nomenclature

‡ in l/s = Volume flow per diffuserL in m = Distance from the outlet where the

maximum time average air velocity is 0.5 m/s

ΔPt in Pa = Total pressure drop

LWA = Sound power level in dB(A)

NoteThe throw distance L should be between 75% and 100% ofthe distance to the nearest wall or 50% of the diffuserspacing dimension, based on a ceiling height of 2.7 - 2.9m.

If selecting using blanking plates the selected diffuser nominal size should be based on the following:3-way selection - 133% of design volume.2-way corner selection - 200% of design volume.Use the volume based on the 4-way dischargeperformance data shown in the table below

Page 46: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

46

Minimumflow rate

Dimensions (mm)

DLQ/ADLQ DLQ-AK DLQ-AG

Diffuser layout

A≥

A/2

A≥A/2

Nomenclature

L in m: Throw distance related to ‡L = 0.5m/s‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA in m = Minimum distance between two diffusers (2x 'L' < 0.25m/s)

Note

In all cases, the sound power level is LWA � 40 dB(A) per diffuser Selection valid for ceiling height = 2.7...3 m.

H

K 50

ØD

8

Q

Q

TypeDLQADLQ

Diffuser face AWith ancillary AR

AG1)

CWith plenum box AK

Damper in plenum box spigot M3)

Spigot damper with cordand measurement test point MN3)

Spigots with lip seal L3)

0 Without installation subframeE1 Duct cross bar 2)G1 Standard subframe 2)H1 Special subframe 2)

Size250300400500600625

Not usedState colour

0 Standard finishDLQ powder-coatedto RAL 9010 (GE 50%)4)ADLQ E6-C-0

P1 Powder-coatedto RAL 9006 (GE 30%)4)other coloursto RAL . . . (GE 70%)4)

Order Code

DLQ - AK - M - L 500 0 0 P1 RAL 9016/ / / / /

1) Not available for size 2502) Only for types ...-A, ...-AG and ...-C3) Only for construction ...-AK4) GE = Gloss level

TEEEEEEEEEEEEEEZEEEEEEEEEEEEEEU

These codes need not be completed for standard products

Ceiling DiffusersType DLQ/ADLQ

Technical Data

Size � ØD H �K

250 248 158 262 216

300 298 158 262 266

400 398 198 307 372

500 498 248 357 476

600 598 313 420 567

625 623 313 420 567

Size V.min

250 20

300 35

400 75

500 135

600 220

625 250

Size 10 Pa 15 Pa 20 Pa 30 Pa 45 Pa

250V (l/s) 30 38 44 54 60

L (m) 1.0 1.5 1.6

300V (l/s) 45 54 63 77 88

L (m) 1.0 1.5 1.7

400V (l/s) 80 97 113 148 168

L (m) 1.0 1.2 1.9 2.2

500V (l/s) 135 160 180 225 255

L (m) 1.2 1.6 2.2 2.4

600V (l/s) 235 270 305 335

L (m) 2.0 2.3 2.6

625V (l/s) 270 335 410

L (m) 2.4 2.9

IEEEEEEEEEEEOEEEEEEEEEEEP

IEEEEEEEEEEEOEEEEEEEEEEEP

IEEEEEEEEEEOEEEEEEEEEEP

IEEEEEEEEEEOEEEEEEEEEEP

Page 47: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

47

Minimumflow rate

Dimensions (mm)

ADLR-Q ADLR ADLR-...-H ADLR-...-V-M

Diffuser layoutA

≥A

/2

A ≥ A/2

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA in m = minimum distance between two diffusers

Note

In all cases, the sound power level is LWA � 40 dB(A) per diffuser and the pressure drop ∆Pt � 45 Pa.

Selection valid for ceiling height = 2.7...3 m.

Available dimensions Diffuser face ADLR-Q = � 593, 598, 618 and 623 mm

K

H2

6 35 / Ø

ØD

ØBØD

/ Ø

H1

TypeADLR(circular diffuser face)

Square diffuser face Q

Diffuser face A

Top entry supply air ZVplenum extract air AV

Side entry supply air ZHplenum extract air AH

SizeSpecify RAL colour

0 Standard finishpowder coatedto RAL 9010 (GE 50%)1)

P1 Powder coatingto RAL 9006 (GE 30%)1)Other coloursto RAL... (GE 70%)1)

Order Code

ADLR - Q - ZH - M - L 400 0 0 P1 RAL 9016/ / / / /

1) GE = Gloss level

IEEOEEPIEEOEEP

TEEEEEEEEEEEEEEZEEEEEEEEEEEEEEU

These codes need not be completed for standard products

IEEEEEEEEEEOEEEEEEEEEEP

L Spigot with lip seal

M Adjustable flow rate controlwith single blade

Ceiling DiffusersType ADLR

Size Ø ØB ØD H2 �K

1 244 202 123 220 266

2 300 258 158 250 290

3 356 314 198 295 372

4 412 370 248 345 476

5 468 426 248 345 476

6 542 482 313 410 567

7 598 538 313 410 590

8 654 594 313 410 615

Size V.min

1 20

2 35

3 55

4 80

5 110

6 150

7 200

8 230

Minimum distance between two diffusers (A)

SizeFlow rate V

.(l/s)

20 30 40 50 60 70 80 90 100 120 140 160 180 200 250 300 350 400

1 1.2 1.3 1.5 1.7 2.0

2 1.2 1.3 1.5 1.7 1.9 2.1

3 1.3 1.5 1.6 1.8 1.9 2.2 2.5

4 1.5 1.6 1.7 2.0 2.3 2.5 2.8 3.0

5 2.5 2.5 2.5 2.5 2.5 2.7 3.3

6 2.5 2.5 2.9 3.4

7 2.5 2.7 3.1 3.5

8 2.5 2.9 3.3 3.7

Page 48: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

48

Supply Aerodynamic Data ADM-1

Opening size 'H' x 'L' (Type-'X' fix)

70A

sec

tion

AG

sec

tion

50

Overall size 'H' + 38 / 'L' + 38

Blade Pitch

'H'-22 / 'L'-22

12.5

3030

7

Overall sizeADMR 'H' - 2 / 'L' - 2ADML 'H' - 5 / 'L' - 5

45

12.5Blade Pitch

Opening size 'H' x 'L' (Type-'X' fix)

Border drilled for fixing to duct / ceiling (by others)

35

Type X - Standard Supply

Opening size ('H' / 'L')

Type S11

Opening size ('H'+6 / 'L'+6)

Opening size 'H' x 'L'Support bar supplied loose for screw fixing into duct (by others)

Duct

Typ

e ...

-A70

Typ

e ...

- AG

140

Type N1 - Support bar for duct mounting

Plenum I/S size 'H'-9 x 'L'-9 Support bar supplied loose for screw fixing into duct (by others)

Plenum

Type N2 - Support bar for plenum mounting

Ceiling DiffuserType ADM

Order Code

Type ADMADMRADML

Directions 1of discharge 2

Basic construction AAncillaries AG(1

Note(1 AG damper not used in conjunction with N1 fixing.(1 ADM units supplied with TROX AK plenums - AG damper must be included within plenum(2 Q, QN2 fixing options only available for type ADMR.

Sizes available

Without installation subframe 0With installation subframe L30(Only for S11 fixing option)(Not suitable for plenum mounting)

X WithoutS11 Secret fastenerN1 Support bar for duct mountingN2 Support bar for plenum mountingQ Alignment & support angle(2

QN2 Alignment & support angle c/wsupport bar for plenum mounting(2

Powder coat finish

L x H L30 P3 RAL 9010 20% Gloss/ / / / / /

The above selections meet noise levels up to and including NC35 assuming 8dB room attenuation. ADM linear diffuser with ceiling effect (horizontal throw).Throw is the distance from diffuser to a velocity of 0.5 m/s. For ADMR/ADML effective height for performance = 'H' - 50mm.

H Pressure Drop (Pa)in mm <10 <10 12 20 28 38

150Volume (l/s/m) 80 120 160 200 240 280Throw (m) 3.3 5.0 6.7 8.4 10.0 11.7

200Volume (l/s/m) 120 180 240 300 360Throw (m) 4.1 6.1 8.2 10.2 12.3

250Volume (l/s/m) 160 240 320 400Throw (m) 4.7 7.1 9.5 11.8

300Volume (l/s/m) 200 300 400Throw (m) 5.3 7.9 10.6

350Volume (l/s/m) 240 360 480Throw (m) 5.8 8.7 11.6

400Volume (l/s/m) 280 420Throw (m) 6.2 9.4

450Volume (l/s/m) 320 480Throw (m) 6.7 10.0

Type ADM Type ADM

Fixing Arrangements

Type ADMR / ADML

Supply Aerodynamic Data ADM-2

H Pressure Drop (Pa)in mm <10 <10 12 20 28 38

150Volume (l/s/m) 60 90 120 150 180 210Throw (m) 2.0 3.0 4.1 5.1 6.1 7.2

200Volume (l/s/m) 100 150 200 250 300 350Throw (m) 2.6 3.9 5.3 6.6 7.9 9.2

250Volume (l/s/m) 140 210 280 350 420 490Throw (m) 3.1 4.7 6.2 7.8 9.4 11.0

300Volume (l/s/m) 180 270 360 450 540Throw (m) 3.5 5.3 7.1 8.9 10.6

350Volume (l/s/m) 220 330 440 550 660Throw (m) 3.9 5.9 7.8 9.8 11.8

400Volume (l/s/m) 260 390 520 650Throw (m) 4.2 6.4 8.5 10.7

450Volume (l/s/m) 300 450 600 750Throw (m) 4.6 6.9 9.2 11.5

ADM- 2 - A G

IEEOEEP

IEEOEEP

IEEOEEP

IEEEEEEEEOEEEEEEEEP

S11

Page 49: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

49

Ceiling DiffusersType VDR

VDR-...-V VDR-...-H

mKØB2

H6

H5 H

1

H2

H8

H3

ØD

ØD

ØR ØR

45VDR

These codes need not be completed for standard products

/ / / / /

Top entry spigot V Side entry spigot H

230 V, 50 Hz, E1Open-Closed control

24 V, 50 Hz, E2Open-Closed control24 V�, 2...10 V-,Constant modulating E3control

IEEOEEP

IEEEEEEEEEEEEEEOEEEEEEEEEEEEEEP

VDR-V-E1 630 0 0 P1 RAL 9016

Specify colour

0 Standard finishpowder coatedto RAL 9010 (GE 50%)1)

P1 Powder coatingto RAL 9006 (GE 30%)1)Other coloursto RAL... (GE 70%)1)

Not usedSize

1) GE = Gloss level

IEEEEEEEEEEEOEEEEEEEEEEEP

Technical DataVDR-...-H Heating mode Cooling mode

H=3.8 H>6.8Size LWA V

.∆Pt H1 (+10 K)

Amin Amin

31540 218 40 4.5 3.0 2.050 300 70 7.0 4.5 2.3

40040 320 35 5.5 4.0 2.050 440 65 6.0 6.0 3.0

63040 620 40 6.0 5.5 2.550 820 70 10.0 7.0 3.2

80040 850 30 10.0 6.0 3.050 1250 65 12.0 8.3 4.0

Dimensions (mm)Size ØB2 ØD H1 H2 H3 H5 H6 H8 �K ØR

315 314 248 570 457 301 427 270 350 415 450400 399 313 667 537 348 550 375 425 500 570630 629 398 807 632 401 670 450 490 750 870800 799 498 965 754 473 790 535 590 920 1070

Order Code

Nomenclature‡ in l/s = Flow rateH in m = Room heightH1 in m = Distance between discharge level and occupied zoneH1 in m = Vertical penetration depth of air current in heating

operationAmin, B in m = Distance between 2 diffusersXmin in m = Distance from wallƒH1 in m/s = Time average upstream velocity between 2 diffusersƒL in m/s = Time average upstream velocity at the wallLWA in dB(A) = Sound power level∆Pt in Pa = Pressure drop

NoteB = > 5 mƒH1 = < 0.2 m/sƒL = 0.4 m/sXmin = 3 m

Selection valid for ceiling height 3.8 m to 6.8 m

Diffuser layout

1.80m

Minimumflow rate

Size V.min

315 178

400 253

630 492

800 698

Page 50: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

50

Diffuser layout

A≥

A/2

A ≥ A/2

Minimum distance between two diffusers (A)

SizeFlow rate V

.(l/s)

40 50 60 70 80 90 100 110 120 140 160 180 200

250 1.6 1.8

300 1.7 2.0

400 1.7 1.8 2.1 2.3

500 1.9 2.1 2.3 2.7

600 2.4 2.7 3.0

DLQL DLQL ...-H DLQL ...-V

Nomenclature

‡ in l/s = Flow rate‡min in l/s = Minimum flow rateA in m = Minimum distance between two diffusers

Note

In all cases, the sound power level is LWA � 40 dB(A) perdiffuser.

Selection valid for ceiling height = 2.7...3 m.

Ceiling Diffusers with perforated sheet facingType DLQL

1

C

A

C

4

ØD2

Nominal SizeDLQL-P DLQL-T

�Q1

ØD1 ØD2 H1 �Q3 H2 H4 A C

250 248 593 158 123 8 216 250 20 139 50

300 298 593 158 158 8 290 250 26 139 50

400 398 593 198 198 8 372 295 36 164 50

500 498 593 248 248 8 476 345 47 189 48

600 598 593 313 313 8 590 410 56 222 50

DLQL-T: □Q1 = 618 is available for T-bar ceilings with grid size 625DLQL-P : □Q1 to 623 mm available

Dimensions (mm)

Page 51: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

51

Extract air, top connection Extract air, side connection

Supply air, top connection Supply air, side connection

Ceiling Diffusers with perforated sheet facingType DLQL

Discharge four way

Nominal V.min V

.at 35 dB(A) V

.at 45 dB(A)

Size l/s m³/h l/s m³/h ΔPt l/s m³/h ΔPt250 25 90 41 149 24 56 200 43

300 36 131 56 202 22 73 261 37

400 65 232 91 328 18 116 427 31

500 101 363 120 430 16 151 545 25

600 145 522 198 713 16 252 908 25

Note the noise levels quoted are the dBA rating of sound power level LWA.To obtain typical room levels LPA ≈ LWA − 5 dB.

Discharge four way

Nominal V.min V

.at 35 dB(A) V

.at 45 dB(A)

Size l/s m³/h l/s m³/h ΔPt l/s m³/h ΔPt250 25 90 42 150 27 58 208 52

300 36 131 51 182 29 67 239 50

400 65 232 90 324 29 117 422 48

500 101 363 121 435 26 157 565 44

600 145 522 190 683 26 244 878 43

Intake four way

Nominal V.at 35 dB(A) V

.at 45 dB(A)

Size l/s m³/h ΔPt l/s m³/h ΔPt250 72 260 24 99 355 45

300 116 416 28 164 591 56

400 209 753 27 288 1036 50

500 245 882 21 324 1167 37

600 431 1550 23 593 2136 43

Intake four way

Nominal V.at 35 dB(A) V

.at 45 dB(A)

Size l/s m³/h ΔPt l/s m³/h ΔPt250 91 327 28 122 438 49

300 104 375 18 145 523 35

400 168 605 15 228 820 28

500 229 824 14 304 1095 25

600 385 1387 12 519 1867 22

① Diffuser face

② Central fixing screw

③ Baffle element (only for supply air)

④ Casing

⑤ Plenum box

⑥ Cross bar

⑦ Suspension hole

⑧ Spigot

Options

⑨ Lip seal

⑩ Damper blade for volume flow rate balancing

⑪ Blanking plate

Type

T-bar ceiling TGrid or plasterboardceiling P

Supply Air ZExtract Air A

Horizontal duct connection HVertical duct connection V

No entry: None -Adjustable flow rate control M(only for connection type H)

No entry: None -Spigot c/w lip seal L

NominalDiffuserSize(mm)

No entry: powder-coated RAL 9010,pure white

P1 Powder-coated,specify RAL CLASSIC colour

Gloss levelRAL 9010 50 %RAL 9006 30 %All other RAL colours 70 %Size of diffuser

face plate (mm)DLQL-PNo entry: size of diffuserface plate = nominal size – 2 mm

598 For grid size 600623 For grid size 625... Other dimensions, 623 mm max.

DLQL-T593 For T-bar ceilings, grid size 600618 For T-bar ceilings, grid size 625

Order Code

DLQL - T - Z - H - M - L 500 593 P1 - RAL.../ / /

IEEOEEPIEEOEEPIEEOEEP

IEEOEEP

TEEEEEEEEEEEEZEEEEEEEEEEEEU

IEEEEEEOEEEEEEP

Page 52: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

52

Standard sizes

Multileaf Dampers Type JZ-P · JZ-P-A2 JZ-S · JZ-S-A2 · JZ-HL · JZ-LL · JZ-LL-A2

JZ-P · JZ-P-A2 JZ-S · JZ-S-A2 · JZ-HL · JZ-LL · JZ-LL-A2

x 8

.5

2016

5

1803890

x

150

x 8

.520

1803816

590

x

150

JZ-P– Casing and blades made from galvanised rolled steel sheet, casing flanges with holes in the corners on both sides

– Blade spindles and external linkage made from galvanised steel– Plain bearings made from special plastic– Parallel blade operation– Drive arm may be located on any blade – Temperature resistant to 100°C

JZ-P-A2– Casing, blades and external linkage made from stainless steel, type No. 1.4301, casing flanges with holes in the corners on both sides

– Blade spindles made from stainless steel, type No. 1.4305– Plain bearings made from special plastic– Parallel blade operation– Drive arm may be located on any blade– Temperature resistant to 100°C

JZ-SSame as Type JZ-P, except:– Opposed blade operation

JZ-S-A2Same as Type JZ-P-A2, except: – Opposed blade operation

JZ-HLSame as Type JZ-S, except:– Additional seals on long blade sides– Temperature resistant to 90°C

JZ-LL (airtight to DIN 1946)*Same as Type JZ-S, except:– Seals on long blade sides made from special plastic, side sealsmade from foam plastic

– Drive arm may be located on every 2nd blade– Temperature resistant to 90°C* Leakage < 10 m3/h / m2 blades closed at pressure differential of 100 Pa

JZ-LL-A2 (airtight to DIN 1946)*Same as Type JZ-LL, except:– Casing, blades and external linkage made from stainless steel, type No. 1.4301, casing flanges with holes in the corners on both sides

– Blade spindles made from stainless steel, type No. 1.4305

Description

B H(mm) (mm)

400 345

600 510

800 675

1000 840

1200 1005

1400 1170

1600 1335

1800 1500

2000 1665

1830

1995

B

H

All combinations of B and H dimensions can be supplied.Within the standard dimension range, all intermediate dimensions (B dimension and/or H dimension) available.Multileaf damper variants outside the standard dimension range aresupplied subdivided on B or H dimension.

/

TypeJZ Multileaf damper

FunctionS Opposed (standard)P Parallel

MaterialNo entry: galvanised steel

A2 Stainless steel

ConstructionNo entry: corner holes on both sides; plastic bearings

G Flange holes on both sides (no corner holes)

M Brass bearingsE Stainless steel bearingsM-V Brass bearings and reinforced blades

(not for JZ-A2)E-V Stainless steel bearings and

reinforced blades (not for JZ-A2) M, E, M-V, E-V can be combined with G

Order Code JZ – P – A2 – G – M – L / /1000×1005 ER Z64 / /NC P1 – RAL ...

Nominal size [mm]B × HB > 2000 = width subdividedH > 1998 = height subdivided

Operating sideNo entry: on the right

L Left

Installation subframeNo entry: none

ER With (only for construction G)

AttachmentsNo entry: none

Z04 – Z07 Quadrant stay Z12 – Z51 ActuatorsZF01 – ZF15 Spring return actuatorsZ60 – Z77 Pneumatic actuators

Explosion-proof actuators

Z1EX, Z3EX ElectricZ60EX – Z77EX Pneumatic

Damper blade safety functionOnly for spring return actuators or pneumatic actuators

NO Pressure off/power off to OPENNC Pressure off/power off to CLOSE

SurfaceNo entry: standard construction

P1 Powder-coated, RAL CLASSIC colourPS Powder-coated, DB colour

Gloss level:RAL 9010 50 %RAL 9006 30 %All other RAL colours 70 %

Page 53: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

53

Multileaf DampersJZ-AL · JZ-LL-AL

JZ-AL . JZ-LL-AL

38

50

x 8

.5

20

100

H/B

120

150x

JZ-AL– Casing and blades of extruded aluminium sections, casing flangeswith holes in the corners on both sides

– Blade spindles made from galvanised steel– Gears made from special anti-static plastic– Galvanised steel drive arm– Blades interconnected by gears located at each end of the blade– Temperature resistant to 90°C

JZ-LL-AL (airtight to DIN 1946)*– Casing and blades of extruded aluminium sections, casing flangeswith holes in the corners on both sides

– Blade spindles (from H = 800 mm, 2 sections with coupling rods)made from galvanised steel

– Gears made from special anti-static plastic– Drive arm, locking quadrant and position indicator made from galvanised steel

– Seals on the long blade sides and bearings made from special plastic

– Blades interconnected by internal gears– Temperature resistant to 50°C

* Leakage <10 m3/h / m2 blades closed against pressure differential of 100 Pa

Description Standard sizes

All combinations of B and H dimensions can be supplied.All intermediate B dimensions within the standard dimension rangecan be supplied.

B H(mm) (mm)

200 100

250 150

300 200

350 250

400 300

450 350

500 400

550 450

600 500

650 550

700 600

Standard sizes

B H(mm) (mm)

750 650

800 700

850 750

900 800

950 850

1000 900

1050 950

1100 1000

1150

1200

/

TypeJZ Multileaf damper

MaterialAL Aluminium

Installation subframeNo entry: none

ER With

Order CodeJZ – AL / /1100×950 ER Z64 / /NC P1 – RAL ...

Nominal size [mm]B × H

SurfaceNo entry: standard constructionP1 Powder-coated,

RAL CLASSIC colourPS Powder-coated, DB colourS3 Anodised to EURAS standard, E6-C-0

Gloss level:RAL 9010 50 %RAL 9006 30 %All other RAL colours 70 %

Damper blade safety functionOnly for spring return actuatorsor pneumatic actuators

NO Pressure off/power off to OPENNC Pressure off/power off to CLOSE

AttachmentsNo entry: none

Z04 – Z07 Quadrant stay Z12 – Z51 ActuatorsZF01 – ZF15 Spring return actuatorsZ60 – Z77 Pneumatic actuators

Page 54: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

54

WG– Frames and blades of formed, galvanised

steel sheet– Bird screen using 20 x 20 mm galvanised

wire mesh (Opt. insect screen - 1.25 x 1.25)

– Flange drilled as standard– Free cross section approx. 60 % rel.

to B x (H – 0.085 m)

WG-AL

– Frames and blades of extruded aluminium sections

– Bird screen using 20 x 20 mm galvanised wire mesh (Opt. insect screen - 1.25 x 1.25)

– Flange drilled as standard

– Free cross section approx. 60 % rel. to B x (H – 0.085 m)

WG-A2

– Frames, blades and bird screen (mesh size 20 x 20 mm) in stainless steel, type No. 1.4301(Opt. insect screen - 1.25 x 1.25)

– Flange drilled as standard

– Free cross section approx. 60 % rel. to B x (H – 0.085 m)

Description

Weather Resistant LouvresType WG · WGK

WG · WG-A2WG WG-AL

Duct installation(Types A and B)

B + 100

H +

100

B

H

8

~ 15

5082

.5

83

5082

.5

95 ~ 15

10

H B

A

B

H B

C

D

Quick sizing – volume flow rate at 2.5 m/s

HeightWidth (mm)

200 400 600 800 1400 1600 1800 2000 2200 2400

mm l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s

165 40 80 120 160 280 320 360 400 438 478

330 125 245 370 490 860 980 1105 1225 1315 1434

495 205 410 615 820 1435 1640 1845 2050 2191 2390

660 290 575 865 1150 2015 2300 2590 2875 3068 3347

825 370 740 1110 1480 2590 2960 3330 3700 3506 3825

990 455 905 1360 1810 3170 3620 4075 4525 4821 5259

1155 535 1070 1605 2140 3745 4280 4815 5350 5697 6215

1320 620 1235 1855 2470 4325 4940 5560 6180 6574 7171

1485 700 1400 2100 2800 4900 5600 6300 7000 7450 8127

1650 785 1565 2350 3130 5480 6260 7040 7830 7888 8605

1815 865 1730 2595 3460 6060 6920 7790 8650 9203 9621

1980 950 1895 2845 3790 6630 7580 8530 9480 9621 10538

2145 1030 2060 3090 4120 7210 8240 9270 10300 10458 11454

2310 1115 2225 3340 4450 7790 8900 10010 11130 10956 12370

Quick sizing – differential pressure and sound power levelInstallation type

V A and C B and D

ΔPt LWA ΔPt LWA

m/s Pa dB(A) Pa dB(A)

1.5 10 32 14 34

2 20 41 25 43

2.5 30 48 35 50

3 45 54 55 56

4 75 63 95 66

5 115 70 145 73

6 170 76 210 79

Plenum installation(Types C and D)

The sound power levels LWA apply to external weather louvres with a flow cross section of 1m2

Page 55: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

TypeWGWGK (... -AL only)

MaterialNo entry: Galvanised steelA2 Stainless SteelAL Aluminium

ConstructionNo entry: wire mesh galvanised steel1 Insect screen, galvanised steel

(only WG, WG-AL, WGK-AL)2 Wire mesh, stainless steel (only WG-AL)3 Wire mesh and insect screen, stainless steel

(only WG-AL, WG-A2, WGK-AL)U Border without fixing holes (1, 2, 3 can be

combined with U)

55

Order Code

WG - AL - 2 - U 600 x 1155 ER P1 - RAL .../ / /

Nominal size (mm)B x H

SurfaceNo entry: standard construction(WGK-AL standard constructionE6-C-0, S3, natural colour)

P1 Powder-coated, RAL CLASSIC colourPS Powder-coated, DB colourOnly for WG-ALS2 Anodised to EURAS standard,

E6-C-31...35S3 Anodised to EURAS standard, E6-C-0

Gloss level:RAL9010 50%RAL9006 30%All other RAL colours 70%

Installation subframeNo entry: noneER With (not for construction U)

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEPTEEEEEEEEEEEEEEEZEEEEEEEEEEEEEEEEU

Weather Resistant LouvresType WG · WGK

WGK– Frames and blades of extruded aluminium sections, natural

anodised (E6-C-0)– Bird screen using 6 x 6 mm galvanised wire mesh

(Opt. insect screen - 1.25 x 1.25)

– Flange drilled as standard– Free cross section approx. 60 % rel. to B x (H – 0.028 m)

Description

WGKWGK

Duct installation(Types A and B)

BB + 56

HH

+ 5

6

H B

A

B

H B

C

D

2528

34 ~ 8

7Plenum installation(Types C and D)

Quick sizing – volume flow rate at 2.5 m/s

HeightWidth (mm)

97 147 197 297 397 497 597 797 997 1197 1397 1597 1797 1997

mm l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s l/s

97 15 25 35 50 70 85 105 135 170 205 240 275 310 345

147 30 45 60 90 120 150 180 235 295 355 415 475 535 595

197 40 60 85 125 170 210 250 335 420 505 590 675 760 845

247 55 80 110 165 215 270 325 435 545 655 765 875 985 1095

297 65 100 130 200 265 335 400 535 670 805 940 1075 1210 1345

347 75 115 155 235 315 395 475 635 795 955 1115 1275 1435 1595

397 90 135 180 275 365 460 550 735 920 1105 1290 1475 1660 1840

447 100 155 205 310 415 520 625 835 1045 1255 1465 1675 1880 2090

497 115 170 230 350 465 585 700 935 1170 1405 1640 1870 2105 2340

597 140 210 280 420 565 705 850 1135 1420 1705 1985 2270 2555 2840

797 185 285 380 570 765 955 1150 1530 1915 2300 2685 3070 3455 3840

997 235 355 475 720 960 1205 1445 1930 2415 2900 3385 3870 4355 4840

1197 285 430 575 870 1160 1450 1745 2330 2915 3500 4085 4665

1397 330 505 675 1015 1360 1700 2045 2730 3410 4095 4780

1597 380 575 775 1165 1555 1950 2340 3125 3910 4695

1797 430 650 870 1315 1755 2200 2640 3525 4410 5290

1997 475 725 970 1460 1955 2445 2940 3925 4910 5890

Page 56: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

/ / / /

56

Rectangular Fire DampersType FK-EU

FK-EU with spring return actuator

Nomenclature‡ in l/s = Flow rate∆Pt in Pa = Total pressure dropLWA in dB(A) = Sound power level

Class of performance to EN 13501-3,up to EI 120 (‡8 h0 i - 0) S

DoP/FK-EU/DE/2013/001

Flow rate (l/s) at ∆Pt < 35 PaH LWA B (mm)

(mm) (dB(A)) 200 250 300 350 400 450 500 550 600 650 700 750 800 900 1000 1000 1200 1300 1400 1500

200 35 181 236 292 347 389 444 486 542 583 639 681 722 778 542 597 667 736 792 861 917

45 264 333 403 486 556 625 694 750 819 889 958 1014 1083 764 861 944 1042 1125 1222 1306

250 35 250 319 389 458 528 597 653 722 778 847 903 958 1028 778 875 958 1056 1153 1236 1333

45 361 458 556 639 736 833 917 1000 1097 1181 1264 1347 1431 1111 1236 1375 1500 1625 1764 1889

300 35 319 403 486 569 653 736 819 889 972 1042 1125 1194 1264 1014 1139 1250 1375 1486 1611 1722

45 444 569 694 806 917 1028 1139 1250 1347 1458 1569 1667 1778 1444 1611 1778 1958 2125 2292 2458

350 35 389 486 583 681 778 875 972 1056 1153 1236 1333 1417 1500 1250 1403 1542 1681 1833 1972 2125

45 542 681 819 958 1097 1222 1347 1486 1611 1736 1861 1986 2097 1778 1986 2194 2403 2611 2806 3014

400 35 444 569 681 792 903 1014 1125 1222 1333 1431 1528 1639 1736 1486 1653 1819 2000 2167 2347 2514

45 625 792 958 1111 1264 1417 1569 1708 1861 2000 2139 2292 2431 2111 2347 2597 2833 3083 3333 3569

450 35 347 458 514 611 708 819 917 1014 1111 1208 1306 1417 1514 1708 1903 2111 2306 2500 2694 2903

45 500 667 722 875 1014 1153 1292 1444 1583 1722 1861 2000 2153 2431 2708 3000 3278 3556 3833 4125

500 35 431 583 583 694 806 917 1028 1153 1264 1375 1486 1597 1708 1931 2167 2389 2611 2833 3056 3278

45 611 819 819 986 1153 1306 1472 1625 1792 1958 2111 2278 2431 2750 3069 3389 3708 4028 4347 4667

550 35 653 778 903 1028 1153 1278 1403 1528 1653 1792 1917 2167 2417 2667 2917 3167 3417 3653

45 917 1097 1278 1458 1639 1819 2000 2181 2361 2542 2722 3069 3431 3778 4139 4500 4847 5208

600 35 722 861 1000 1139 1278 1417 1556 1694 1833 1972 2111 2389 2667 2931 3208 3486 3764 4042

45 1014 1222 1417 1611 1819 2014 2208 2403 2611 2806 3000 3389 3778 4181 4569 4958 5347 5736

650 35 792 944 1097 1250 1403 1556 1708 1847 2000 2153 2306 2611 2917 3208 3514 3819 4111 4417

45 1111 1333 1556 1764 1986 2208 2417 2639 2847 3069 3278 3708 4139 4569 4986 5417 5847 6278

700 35 847 1014 1181 1347 1514 1681 1847 2014 2181 2347 2500 2833 3153 3486 3806 4139 4458 4792

45 1208 1444 1681 1917 2153 2389 2625 2861 3097 3333 3556 4028 4486 4958 5417 5875 6347 6806

750 35 917 1097 1278 1458 1639 1819 2000 2167 2347 2528 2694 3056 3403 3764 4111 4458 4806 5167

45 1306 1569 1819 2069 2333 2583 2833 3083 3333 3583 3833 4347 4847 5347 5847 6333 6833 7333

800 35 986 1181 1375 1569 1764 1944 2139 2333 2514 2708 2903 3278 3653 4028 4403 4778 5153 5528

45 1403 1681 1958 2222 2500 2764 3042 3306 3583 3847 4125 4653 5194 5722 6264 6792 7333 7861

Order Code

AccessoriesZ00 to ZEX2Z00 = Basic constructionSee leaflet

Accessories 2No entry = noneRO - OASee leaflet

ES SS Z01600 x 400 x 500

Accessories 1No entry = noneVP-GL 100See leaflet

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

FK - EU -1

TypeFK-EU

Construction variantsSee leaflet

Standard sizesB x H x L mm

FK-EU with fusible link

B

H35L = 375 resp. 500

260 35 35311

35

Page 57: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

/ / / /

57

Rectangular Fire DampersType FKS-EU

185

L = 300

H30

30 30

ca. 70

B

30

FKS-EU with fusible link

FKS-EU with spring return actuator

Nomenclature‡ in l/s = Flow rate∆Pt in Pa = Total pressure dropLWA in dB(A) = Sound power level

Class of performance to EN 13501-3,up to EI 120 (‡8 h0 i - 0) S

approx.

70

Flow rate (l/s) at ∆Pt < 35 PaH LWA B (mm)

(mm) (dB(A)) 200 300 400 500 600 700 800

30 69 111 153 194 250 292 333

100 35 83 139 194 236 292 347 403

45 97 153 222 278 347 403 472

30 97 153 208 264 333 389 458

125 35 125 181 250 319 389 472 542

45 139 208 306 375 472 556 639

30 125 194 278 347 431 514 583

150 35 153 236 319 417 500 597 694

45 181 278 389 486 597 708 819

30 139 208 306 375 472 556 639

160 35 167 250 361 444 556 653 764

45 194 292 417 528 653 778 903

30 194 292 417 514 639 750 889

200 35 222 347 486 611 764 889 1042

45 278 403 583 722 903 1056 1236

Order Code

AttachmentsNone, no entry requiredZ01 to ZL08See leaflet

AttachmentsNone, no entry requiredS0 to SASee leaflet

E A0 Z43800 x 200 x 300

Installation block or orificeNone, no entry requiredE · BSee leaflet

IEEEEEEEEEEEEEEOEEEEEEEEEEEEEEP

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

FKS - EU

TypeFKS-EU

Construction variantsStandard, no entry requiredPowder-coated casing -1Stainless steel casing -2With fusible link 95°C ...-W(only for use in hot-air systems)

Available sizesW x H x L in mm

TEEZEEU

DoP/FK-EU/DE/2013/001

Page 58: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Circular Fire DampersType FKR-EU

FKR-EU with fusible link

550420

37050 50

Ø D

70150

Flow rate (l/s) at ∆Pt <35 PaH LWA V

.∆Pt

(mm) (dB(A)) (l/s) (Pa)

25 323 <5

315 35 464 10

45 668 20

25 396 <5

355 35 570 7

45 820 14

25 485 <5

400 35 697 <5

45 1003 10

25 569 <5

450 35 819 <5

45 1178 7

25 683 <5

500 35 981 <5

45 1412 <5

25 828 <5

560 35 1191 <5

45 1713 <5

25 1010 <5

630 35 1454 <5

45 2092 <5

25 1236 <5

710 35 1778 <5

45 2559 <5

25 1510 <5

800 35 2172 <5

45 3126 <5

Nomenclature‡ in l/s = Flow rate∆Pt in Pa = Total pressure dropLWA in dB(A) = Sound power level

Order Code

AttachmentsNone, no entry requiredZ01 to ZEX4See leaflet

Accessories 1None, no entry requiredTQ Dry motarless installation kitSee leaflet

Z43315UK

Accessories 1None, no entry requiredSO - ASSee leaflet

IEEEEEEEEEEEEEEEEEEEOEEEEEEEEEEEEEEEEEEEP

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

FKR - EU - FL - 1 // / / /

TypeFire Damper

FlangeNo entry: none (with spigot)FL Flange on both endsSee leaflet

Construction variantsStandard, no entry requiredPowder-coated casing -1Stainless steel casing -2Coated damper blade -7Powder-coated casing andCoated damper blade -1-7Stainless steel casing andCoated damper blade -2-7

100125150160200224250280315

Nominal size

58

Class of performance to EN 13501-3,up to EI 120 (‡8 h0 i - 0) S DoP/FK-EU/DE/2013/001

FKR-EU-FL with spring return actuator

FKR-EU-FL with explosion proof spring return actuator

TQ A0

Page 59: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

/ / / /

59

Circular Fire DampersType FKRS-EU

FKRS-EU with fusible link

FKRS-EU with spring return actuator

approx.80

L = 400270

22050 50

NW

Flow rate (l/s) at ∆Pt <35 PaH LWA V

.∆pt

(mm) (dB(A)) (l/s) (Pa)

25 22 9

100 35 36 24

45 44 36

25 44 9

125 35 67 20

45 86 34

25 69 7

150 35 106 17

45 150 35

25 81 7

160 35 125 16

45 181 34

25 139 5

200 35 208 12

45 297 25

25 169 6

224 35 247 14

45 347 27

25 217 6

250 35 317 12

45 444 23

25 281 5

280 35 406 10

45 569 19

25 361 4

315 35 525 8

45 736 15

Nomenclature‡ in m3/h = Flow rate∆Pt in Pa = Total pressure dropLWA in dB(A) = Sound power level

Order Code

AttachmentsNone, no entry requiredZ01 to ZL08See leaflet

AttachmentsNone, no entry requiredS0 to SASee leaflet

ER A0 Z43160

Installation blockNone, no entry requiredER · EQSee leaflet

IEEEEEEEEEEEEEEEEEEEOEEEEEEEEEEEEEEEEEEEP

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

TEEEEEEEZEEEEEEU

FKRS - EU

TypeFKRS-EU

Construction variantsStandard, no entry requiredPowder-coated casing -1Stainless steel casing -2Coated damper blade -7Powder-coated casing andCoated damper blade -1-7Stainless steel casing andCoated damper blade -2-7

Nominal size100125150160200224250280315

Class of performance to EN 13501-3,up to EI 120 (‡8 h0 i - 0) S

DoP/FK-EU/DE/2013/002

Page 60: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

60

Fire DampersAttachments

1) Code for attachments only for galvanised fire dampers (e. g. …-EU).The attachments (exception: flexible connectors) are supplied in galvanised constructionFlexible connectors are identical for all construction variants.

2) Code for attachments only for fire dampers with powder coating RAL 7001 (e. g. ...-EU-1).The attachments are supplied with powder coating RAL 7001. Flexible connectors are identical for all construction variants.

3) Code for attachments only for stainless steel fire dampers (e. g. ...-EU-2).The attachments are supplied with powder coating RAL 7001, exception: extension pieces for Type FKS-EU are supplied in stainless steel construction.Flexible connectors are identical for all construction variants.

4) … and the corresponding extension piece (if required, depending on height and size).5) … and the corresponding extension pieces (if required, depending on height and size).6) Only for casing length L = 375 mm.7) Only for casing length L = 500 mm.8) The flexible connectors are supplied loose.9) The fire dampers are supplied with pre-mounted extension piece and/or with pre-mounted cover grille.10) Only for casing lengths L = 500 mm (FKR-01-K90) and. L = 600 mm (FKR-02-K90).

For further information on attachments, contact TROX UK.

Construction or variant Combination with Code Fire DampersType

-EU -EU-1 -EU-2 FKS-EU FKRS-EU

1) 2) 3)

With one circular entry spigot – 11 61 – –on the connecting frame sideWith two circular entry spigots 4) 7) – 12 62 – –

With one cover grille 4) – 17 67 – –on the connecting frame sideWith one cover grille 4) 7) – 43 93 – –on the wall frame sideWith one flexible connector 4) – 19 69 – –on the connecting frame sideWith two flexible connectors 5) 7) – 20 70 – –

With one surface subframe Parts kit for board cladding 6) 22 72 – –

Parts kit for board cladding 7) 41 91 – –

With one installation kit and the 7) – 24 – –appropriate fastening elements

With one flexible connector 8) – S0 X Xon the operating side One cover grille on the 9) SA X X

installation side and the correspondingextension piece

With one flexible connector 8) 9) – 0S X Xon the installation side and the One cover grille on the AS X Xappropriate extension piece operating side

With flexible connectors on both sides 8) 9) – SS X X

With one cover grille 9) – A0 X Xon the operating sideWith a cover grille on the 9) – 0A X Xinstallation side and the appropriateextension piece

With a lip seal on both sides – 10 – –

With one cover grille 4) – 11 61 – –on the drive sideWith one cover grille 4) 10) – 12 62 – –on the installation sideWith one flexible connectors 4) – 14 64 – –on the drive sideWith one flexible connectors 4) 10) – 15 65 – –on the installation sideWith two flexible connectors 5) 10) – 16 66 – –

With one installation kit 10) – 17 – –

One flexible connector 4) 18 68 – –on the drive side

One flexible connector 4) 19 69 – –on the installation side

Two flexible connectors 5) 20 70 – –

With circular installation block – ER – X

With square installation block – EQ – X

Page 61: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

61

Fire DampersAccessories

1) Fusible link 95 °C only licensed for Types FKS-EU.2) The ambient temperature for storage and operation must remain within the permissible ranges –20 °C to +50 °C

(–30 °C to +50 °C for spring return actuator Type BLF).3) Contacts in silver, gold-plated; Cable halogen-free.4) Spring return actuator Type BLF for dimension combinations up to B x H = 800 x 400 mm5) TROXNETCOM elements mounted on the fire damper. Information on the TROXNETCOM communications solutions for the control of

fire dampers on the basis of LON and AS Interface can be found on our website under Products/Automation and Systems Technology.

For further information on accessories, contact TROX UK.

Construction Combination with Code Fire Dampers Type

FKS-EU FKRS-EU

with fusible link 72 °C or 95 °C 1) – Z00 X X(Basic construction)

Limit switch indicates blade “CLOSED” Z01 X X

Limit switch indicates blade “OPEN” Z02 X X

Limit switch indicates blade “CLOSED” and “OPEN” Z03 X X

with spring return actuator Types BLF 2) 3)

or BF and thermo-electricrelease mechanism BAE72A-S,manufactured by Belimo (power off to close)

Type BLF230-T TR 4) – Z43 X X(with integrated limit switches)U = AC 230 V, 50…60 Hz, Protection Class IP 54

Type BF230-T TR – Z43 – –(with integrated limit switches)U = AC 230 V, 50…60 Hz, Protection Class IP 54

Type BLF24-T-ST TR 4) – Z45 X –(with integrated limit switches)U = AC 24 V, 50…60 Hz resp. DC 24 V, AS-EM/B module, 5) ZA03 X XProtection Level IP 54 TROXNETCOM AS-Interface

LON-WA1/B2, 5) ZL06 X XTROXNETCOM LON

LON-WA1/B2-AD, 5) ZL07 X XTROXNETCOM LON

LON-WA1/B2-AD230, 5) ZL08 X XTROXNETCOM LON

Type BF24-T-ST TR – Z45 – –(with integrated limit switches)U = AC 24 V, 50…60 Hz resp. DC 24 V, AS-EM/B module, 5) ZA03 – –Protection Level IP 54 TROXNETCOM AS-Interface

LON-WA1/B2, 5) ZL06 – –TROXNETCOM LON

LON-WA1/B2-AD, 5) ZL07 – –TROXNETCOM LON

LON-WA1/B2-AD230, 5) ZL08 – –TROXNETCOM LON

With spring return actuator (explosion-proof), – ZEX1 – –thermal-Electrical release mechanism (explosion-

AS-Interface module ZEX2 – –proof) and terminal box (explosion-proof)

Page 62: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

62

VARYCONTROL VAV Terminal BoxesType TVZ · TVA

TypeSupply air box TVZwith acoustic cladding TVZDExtract air device TVAwith acoustic cladding TVAD

Reheat CoilWith 1 row 1With 2 rows 2Electric Eor no entry -

AccessoriesBasic construction 00Lip seal D1

Atttachments1)

Explanations and additional chargesfor control components

Flow rate control1)State flow rate rangeand units

Controlcomponentssee leaflet

Operating mode1)

M. MasterS. SlaveE. SingleF. Constant value

1) If not otherwise specified in order, TVZ-Easy · TVA-Easy is delivered.

Size125160200250315400

Order Code TVZ-V2 - - 160 00 BC0 E0 25-250 l/s/ / / / /

Dimensions (mm)

SizeTVZ · TVA TVZD · TVAD*

B H L B H L

125 300 236 1035 380 316 1075

160 410 236 1035 490 316 1075

200 560 281 1320 640 361 1360

250 700 311 1440 780 391 1480

315 900 361 1440 980 441 1480

400 1000 446 1820 1080 526 1860

Sound pressure level (dB[A])

∆Pst = 100 Pa ∆Pst = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size ØDa Flow V.

without with without with without with without withrate v=5m/s silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range cladding cladding cladding claddingType TS Type TS

(mm) (l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

125 124 15 – 150 60 22 19 21 15 25 15 25 16

160 159 25 – 250 100 28 23 22 16 29 17 25 18

200 199 40 – 405 155 20 17 24 18 22 13 28 20

250 249 60 – 615 245 17 14 23 18 20 12 28 20

315 314 105 – 1030 390 19 15 23 17 23 14 29 21

400 399 170 – 1680 625 18 13 25 19 22 15 31 23

max

.120max. 600

ØD

a

70 70Ø 10,5

50

L

20

H

B

IEEEEOEEEEP

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEP

TEEEEEEEEEEZEEEEEEEEEU

TEEEEEZEEEEU

TEEEEEZEEEEU

TVZ

Maximum space required foractuator/control components

Nomenclature∆Pst in Pa = Static pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with TX silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

System attenuation: See leaflet K5-1.5-1

* with acoustic cladding

Ø 10.5

Page 63: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

63

1) If not otherwise specified in order, TVZ-Easy · TVA-Easy is delivered.

VARYCONTROL VAV Terminal BoxesType TZ-Silenzio

TypeSupply air VAV terminal unitTZ-Silenzio

Acoustic claddingNo entry: noneWith acoustic cladding D

Atttachments1)

Explanations and additional chargesfor control components

Flow rate control1)State flow rate rangeand units

Controlcomponentssee leaflet

Operating mode1)

M. MasterS. SlaveE. SingleF. Constant value

Size125160200250315

Order Code TZ-Silenzio - D 160 BC0 E0 45 - 275 l/s/ / / /

Dimensions (mm)

SizeTZ-Silenzio TZ-Silenzio-D

B3 H3 L B3 H3 L

125 300 236 1035 380 316 1075

160 410 236 1035 490 316 1075

200 560 281 1250 640 361 1250

250 700 311 1250 780 391 1250

315 900 361 1250 980 441 1250

Sound pressure level (dB[A])

∆Pst = 100 Pa ∆Pst = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range cladding cladding cladding claddingType TS Type TS

(l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

125 30 – 180 90 28 17 19 19 31 20 24 23

160 45 – 275 140 29 19 23 22 32 21 27 26

200 65 – 380 190 25 15 22 20 28 17 26 23

250 85 – 495 250 26 15 23 20 30 18 27 23

315 145 – 840 420 28 16 28 25 31 19 32 28

M238

FG1

BL

H₃

B₃ 2020

H

~ 80

B₁

H₁

M 8

IEEEEOEEEEP

IEEEOEEEEP

TEEEEEEEEEEZEEEEEEEEEU

TEEEEEZEEEEU

TEEEEEZEEEEU

TZ-Silenzio

Nomenclature∆Pst in Pa = Static pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with TX silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

System attenuation: See leaflet K5-1.5-1

* with acoustic cladding

Page 64: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

64

VARYCONTROL VAV Terminal BoxesType TA-Silenzio

TypeSupply air VAV terminal unitTA-Silenzio

Acoustic claddingNo entry: noneWith acoustic cladding D

Atttachments1)

Explanations and additional chargesfor control components

Flow rate control1)State flow rate rangeand units

Controlcomponentssee leaflet

Operating mode1)

M. MasterS. SlaveE. SingleF. Constant value

Size125160200250315

Order Code TA-Silenzio - D 160 BC0 E0 45 - 275 l/s/ / / /

Dimensions (mm)

SizeTA-Silenzio TA-Silenzio-D

B3 H3 L B3 H3 L

125 300 236 1035 380 316 1075

160 410 236 1035 490 316 1075

200 560 281 1250 640 361 1250

250 700 311 1250 780 391 1250

315 900 361 1250 980 441 1250

Sound pressure level (dB[A])

∆Pst = 100 Pa ∆Pst = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range cladding cladding cladding claddingType TS Type TS

(l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

125 30 – 180 90 28 17 19 19 31 20 24 23

160 45 – 275 140 29 19 23 22 32 21 27 26

200 65 – 380 190 25 15 22 20 28 17 26 23

250 85 – 495 250 26 15 23 20 30 18 27 23

315 145 – 840 420 28 16 28 25 31 19 32 28

B₃

B

H₃

L

20 20

H

~ 80B₁

H₁

M 8

IEEEEOEEEEP

IEEEOEEEEP

TEEEEEEEEEEZEEEEEEEEEU

TEEEEEZEEEEU

TEEEEEZEEEEU

TA-Silenzio

Nomenclature∆Pst in Pa = Static pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with TX silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

System attenuation: See leaflet K5-1.5-1

* with acoustic cladding

1) If not otherwise specified in order, TVZ-Easy · TVA-Easy is delivered.

Page 65: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

65

VARYCONTROL VAV ControllerType TVR

TypeVAV Controller TVRwith acoustic cladding TVRD

MaterialBasic construction steel, galv. 00Surface powder coated P1Colour RAL 7001

FlangeWITHOUT 00with flange both ends FL1)

AccessoriesNONE 00Matching flange both ends G2Lip seal both ends D2

Control components1)

Explanations and additional chargesfor control components

Flow rate control1)State flow rate rangeand units

Operating modeM. MasterS. SlaveE. SingleF. Constant value

1) not on TVRD with powder coating.

Size100125160200250315400

Order Code TVR - 00 - 00 160 00 BC0 E0 25-250 l/s/ / / / /IEEEEOEEEEP

IEEEEOEEEEP

TEEEEEEEEEZEEEEEEEEU

TEEEEEZEEEEU

TEEEEEZEEEEU

IEEEEEEOEEEEEEP

IEEEEEEOEEEEEEP

TVR

Controlcomponentssee leaflet

Sound pressure level (dB[A])

∆Pg = 100 Pa ∆Pg = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size ØDa Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range Type CS cladding cladding Type CS cladding cladding(L = 1000 mm) (L = 1000 mm)

(mm) (l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

100 99 10 – 95 40 42 27 21 15 48 29 28 21

125 124 15 – 150 60 42 28 22 15 47 32 28 20

160 159 25 – 250 100 44 32 24 16 51 37 31 23

200 199 40 – 405 155 45 31 26 15 49 36 31 17

250 249 60 – 615 245 45 32 34 16 48 36 36 20

315 314 105 – 1030 390 44 32 35 17 49 37 40 22

400 399 170 – 1680 625 40 28 32 18 47 35 40 23

Nomenclature∆Pg in Pa = Total pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with CS silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

System attenuation: See leaflet K5-1.5-1

Page 66: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

66

VARYCONTROL VAV ControllerType TVR-Easy

IEEEEOEEEEP

TEEEEEZEEEEU

TVR-Easy / / 00160

Size100125160200250315400

TypeVAV Controller TVR-Easywith acoustic cladding TVRD-Easy

Accessories00 withoutD2 lip seal

Order Code

Dimensions (mm)Size ØDa L

100 99 310

125 124 310

160 159 400

200 199 400

250 249 400

315 314 500

400 399 500

Nomenclature∆Pg in Pa = Total pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with CS silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

System attenuation: See leaflet K5-1.5-1

Sound pressure level (dB[A])

∆Pg = 100 Pa ∆Pg = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size ØDa Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range Type CS cladding cladding Type CS cladding cladding(L = 1000 mm) (L = 1000 mm)

(mm) (l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

100 99 10 – 95 40 42 27 21 15 48 29 28 21

125 124 15 – 150 60 42 28 22 15 47 32 28 20

160 159 25 – 250 100 44 32 24 16 51 37 31 23

200 199 40 – 405 155 45 31 26 15 49 36 31 17

250 249 60 – 615 245 45 32 34 16 48 36 36 20

315 314 105 – 1030 390 44 32 35 17 49 37 40 22

400 399 170 – 1680 625 40 28 32 18 47 35 40 23

TVR-Easy

Page 67: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

67

VARYCONTROL VAV ControllerType TVJ-Easy · TVT-Easy

400 B38

38

H

TVJ-Easy / 600 x 400

B x HTypeVAV Controller TVJ-Easywith acoustic cladding TVJD-EasyVAV Controller, airtight TVT-Easywith acoustic cladding TVTD-Easy

Order Code

Sound pressure level (dB[A])∆Pg = 100 Pa ∆Pg = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

B x H Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range cladding cladding cladding claddingTX TX

(l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

200 100 35 – 180 100 40 24 32 24 46 27 36 28300 55 – 270 150 41 25 33 25 47 28 37 29400 70 – 360 200 42 26 34 26 48 29 38 30500 90 – 450 250 43 27 35 27 49 30 39 31600 110 – 540 300 44 28 36 28 50 31 40 32200 200 70 – 360 200 39 23 35 27 46 27 39 31300 110 – 540 300 40 24 36 28 47 28 40 32400 145 – 720 400 41 25 37 29 48 29 41 33500 180 – 895 500 42 26 38 30 49 30 42 34600 215 – 1075 600 43 27 39 31 50 31 43 35700 250 – 1250 700 44 28 40 32 51 32 44 36800 285 – 1435 800 44 28 40 32 51 32 44 36300 300 175 – 880 450 40 24 37 30 46 28 42 34400 235 – 1175 600 41 25 38 31 47 29 43 35500 295 – 1470 750 42 26 39 32 48 30 44 36600 354 – 1765 900 43 27 40 33 49 31 45 37700 410 – 2055 1050 44 28 41 34 50 32 46 38800 470 – 2350 1200 44 28 41 34 50 32 46 38900 530 – 2645 1350 45 29 42 35 51 33 47 39

1000 590 – 2940 1500 45 29 42 35 51 33 47 39400 400 325 – 1635 800 41 25 39 32 47 29 44 36500 410 – 2040 1000 42 26 40 33 48 30 45 37600 490 – 2450 1200 43 27 41 34 49 31 46 38700 570 – 2860 1400 44 28 42 35 50 32 47 39800 655 – 3265 1600 44 28 42 35 50 32 47 39900 735 – 3675 1800 45 29 43 36 51 33 48 40

1000 815 – 4085 2000 45 29 43 36 51 33 48 40500 500 475 – 2365 1250 41 26 41 34 48 30 46 38600 570 – 2840 1500 42 27 42 35 49 31 47 39700 665 – 3315 1750 43 28 43 36 50 32 48 40800 754 – 3785 2000 43 28 43 36 50 32 48 40900 850 – 4260 2250 44 29 44 37 51 33 49 41

1000 945 – 4735 2500 44 29 44 37 51 33 49 41600 600 705 – 3525 1800 42 27 43 36 49 31 48 40800 940 – 4700 2400 43 28 44 37 50 32 49 41

1000 1175 – 5880 3000 44 29 45 38 51 33 50 42800 800 1305 – 6535 3200 41 25 46 39 47 30 51 43

1000 1635 – 8160 4000 42 26 47 40 48 31 52 441000 1000 2090 – 10455 5000 42 26 48 41 48 31 53 45

IEEEEEEEEEOEEEEEEEEEP

TVJ · TVT-Easy

Nomenclature∆Pg in Pa = Total pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated noise, system attenuation

taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated noise with TX silencer,

system attenuation taken into accountLpA2 in dB(A) = A-weighted sound pressure level of case-radiated noise, system attenuation

taken into accountLpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional

acoustic cladding, system attenuation taken into accountSystem attenuation: See leaflet K5-1.5-1

approx. 70

approx. 70

Slot 20 x 13

Page 68: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

68

VARYCONTROLType VAV-EasySet

VAV-EasySet

Nominal flow ratesV..NomD

(l/s)

100 95

125 155

140 195

160 250

200 405

224 525

250 615

315 1030

400 1675

TROX VAV-EasySet is an assembly consisting of control components to refurbish VAV terminal units. VAV-EasySet issuitable for systems with a circular duct system.

� Differential pressure sensor to measure the flow rate.

� TROX Compact Controller as casing unit for flow rate controller and actuator.

� Adjustment of ‡min and ‡max flow rates by potentiometerswith graduated scales. No adjustment tool required.

� Functional check by indicator light.

VAV-EasySet

Type

Order Code

> 2 D> 0,5 D

+–

36

60 45° 45°

> 1,5 D > 2 D

Differential pressure device Differential pressure sensor

Duct sytemD = 100 ... 250

Flow rate direction

Air lineD = 280 ... 400

Measuring location

Maximum tube length of 3 mper measuring line

> 1.5 D> 0.5 D

Page 69: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

69

Control System - EASYLABLABCONTROL

EASYLAB controllers for the most demanding controlengineering tasks

An electronic controller that offers plug and playcommunication for demanding control tasks, yet simple wiringand commissioning:

� Maximum control comfort for laboratories, clean rooms, hospital wards, and offices.

� Perfect system for complete room solutions from a single source.

� Demand-based and quick-response control for fume cupboards, and of supply air, extract air and pressure.

� Interactive configuration software with commissioning wizard.

� Plug-in communication cable for easy wiring.

� Adaptable control panels and many special functions allow for individual operating modes and control strategies.

� Fume cupboard control and monitoring according to EN 14175 Expansion options.

� Connection to the mains (230 V)

� Expansion modules with LonWorks, BACnet or Modbus standard interfaces to the central BMS.

� Automatic zero point correction for long-term stability and reduced maintenance.

� Control panels for fume cupboards and for room control.

TVR

TVRK

TVLK

TVJ - TVT

Page 70: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

70

Clean Rooms and ContainmentFacilities HEPA and ULPA Filtration

Ducted particulate filters for critical requirements

� Robust, welded construction with double-edged perimeter flanges

� For the fitting of Mini Pleat Filters as particulate filters or activated carbon filters

� One-stage or two-stage casing

� With sealing integrity test facility

� Optional equipment for contamination-free filter change (Safe Change)

Ceiling mounted particulate filters with MiniPleat filter panels used as final filter stageAcoustically and aerodynamically optimised; andavailable in various design and constructionoptions

To provide a solution for all architecturalrequirements

Wall mounted particulate filters come with asealing integrity test facility, a pressuremeasurement point,and a clamping mechanismfor fixing Mini Pleat filter panels

Particulate Filters H14 with EN 1822 Mini Pleatfilter panels.Used as final filters for the separation ofsuspended particles in industrial, research,medical, and pharmaceutical applications

KSFS

Ceiling Mountedl TFCl TFMl TFP

Wall Mountedl TFW

TFM

TFP

TFW

TFCTFC

TFC

TFC

KSF

Ceiling and wall mounted particulate filters for critical air purity and critical hygiene requirements

HY

GIENE TESTED

VDI 6022

Page 71: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

71

1) Nominal size 80 on RNS and RN-P1 with adapter

Volume Flow ControllersType RN · RNS

IEEEEOEEEEP

IEEEEEEEOEEEEEEEP

Dimensions (mm)

D ØDa L

80 79 310

100 99 310

125 124 310

160 159 310

200 199 310

250 249 400

315 314 400

400 399 400

øDa

50

1742)

approx.70

Lip seal optional 1) RNS: L = 2502) RNS: 110

L1)

< stands for values <15

TypeVolume flow controller RNwith acoustic cladding RND

MaterialBasic construction, steel, galv. 00Surface powder-coated P1Colour RAL 7001

Order Code RN

IEEEEEEEOEEEEEEEP

RNS - 00 / /125 00

Size80100125

TypeVolume flow controller RNS

MaterialBasic construction, steel, galv. 00Surface powder-coated P1Colour RAL 7001

Order Code RNS

Sound pressure level (dB[A])

∆Pg = 100 Pa ∆Pg = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

Size ØDa Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range Type CS cladding cladding Type CS cladding cladding(L = 1000 mm) (L = 1000 mm)

(mm) (l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

80 79 11 – 45 25 39 16 22 < 43 20 26 <

100 99 22 – 90 40 39 19 19 < 43 23 23 <

125 124 35 – 140 60 41 25 17 < 45 29 21 <

160 159 60 – 240 100 44 30 31 < 48 34 35 <

200 199 90 – 360 155 42 26 30 < 46 30 34 <

250 249 145 – 580 245 41 27 31 < 45 31 35 <

315 314 230 – 920 390 40 27 32 < 44 31 36 15

400 399 350 – 1400 625 46 34 46 16 50 38 50 20

RN

TEEEEEZEEEEU

Accessories00 withoutD2 lip seal on both ends1)

Nomenclature∆Pg in Pa = Total pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with CS silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

All sound pressure levels are based on 20 µPa.System attenuation: See leaflet K5-2.3...

RN - 00 - 00 / 125

Size

/ B50 / 35-140 l/s

ActuatorsSee leaflet

Setpoint re-adjustment option

Page 72: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

72

Volume Flow ControllersType EN

approx. 35

38

38

B 400

H

Longitudinalhole 20 x 13

EN / /400 x 200 B50 / 210-840 l/s

B x HTypeVolume flow controller ENwith acoustic cladding END

ActuatorsSee leaflet

Order Code

Sound pressure level (dB[A])

∆Pg = 100 Pa ∆Pg = 200 Pa

Air-regenerated noise Case-radiated noise Air-regenerated noise Case-radiated noise

B x H Flow V.

without with without with without with without withrate silencer silencer acoustic acoustic silencer silencer acoustic acoustic

range cladding cladding cladding claddingType TX Type TX

(l/s) (l/s) LpA LpA1 LpA2 LpA3 LpA LpA1 LpA2 LpA3

200 100 40– 160 100 40 30 32 27 48 35 38 32

300 65– 260 150 42 31 34 29 49 36 41 34

300 150 105– 420 225 42 29 34 27 49 35 40 32

300 200 130– 520 300 43 27 34 25 52 35 42 33

400 210– 840 400 40 24 33 25 49 33 41 32

500 230– 920 500 38 23 31 23 47 31 39 31

600 255– 1020 600 36 23 31 24 44 31 39 32

400 250 220– 880 500 41 26 34 25 51 34 42 33

500 300– 1200 625 39 23 32 23 48 32 40 31

600 320– 1280 750 38 24 32 24 47 32 40 33

400 300 315– 1260 600 44 27 37 27 52 35 44 35

500 375– 1500 750 41 25 35 26 49 33 42 33

600 420– 1680 900 39 24 32 24 47 31 40 31

400 400 420- 1680 800 46 29 39 30 54 37 47 37

500 460– 1840 1000 43 26 37 27 52 34 45 35

600 510– 2040 1200 41 26 36 27 49 34 44 34

500 500 600– 2400 1250 46 28 40 30 54 36 48 38

600 640– 2560 1500 43 28 39 29 51 36 47 37

600 600 840– 3360 1800 45 28 41 31 53 36 48 38

IEEEEOEEEEP

EN

Nomenclature∆Pg in Pa = Total pressure differential‡ in l/s = Volume flow rateLpA in dB(A) = A-weighted sound pressure level of air-regenerated

noise, system attenuation taken into accountLpA1 in dB(A) = A-weighted sound pressure level of air-regenerated

noise with TX silencer, system attenuation takeninto account

LpA2 in dB(A) = A-weighted sound pressure level of case-radiatednoise, system attenuation taken into account

LpA3 in dB(A) = A-weighted sound pressure level of case-radiated noise with additional acoustic cladding, system attenuation taken into account

All sound pressure levels are based on 20 µPa.System attenuation: See leaflet K5-2.3...

Setpoint re-adjustment option

Page 73: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

73

Circular SilencersType CA · CF · CS

Construction with plug type spigots (Standard)

CA100; Insulation thickness = 100 mm

Insertion loss (dB) for L = 500 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

100 4 9 12 18 35 33 26 14

125 4 7 10 17 31 26 19 11

160 3 6 9 15 28 20 13 8

200 3 5 8 15 25 16 9 7

250 2 4 7 14 21 13 6 5

315 2 3 6 13 18 10 4 4

400 1 3 6 12 17 8 3 3

CF050.../CS050; Insulation thickness = 50 mm

Insertion loss (dB) for L = 500 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

80 4 5 11 20 30 27 16 12

100 3 4 9 17 24 21 12 10

125 2 3 7 14 20 16 11 9

160 2 2 6 12 17 14 8 6

200 1 2 5 12 16 11 6 5

250 1 2 4 12 15 8 5 4

315 1 1 3 9 12 6 4 3

400 1 1 3 7 9 6 4 3

Insertion loss (dB) for L = 1500 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

80 11 14 33 48 50 50 47 37

100 10 11 27 44 50 50 37 30

125 7 9 21 41 50 46 33 27

160 5 7 17 37 48 42 24 19

200 4 6 14 37 48 34 18 15

250 3 5 11 35 45 25 14 11

315 2 4 10 26 35 19 12 10

400 2 4 9 20 26 17 11 8

Insertion loss (dB) for L = 1500 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

250 4 11 21 37 41 27 15 12

315 3 9 18 34 35 21 10 9

400 3 7 16 32 31 16 7 7

450 2 6 15 31 29 14 6 6

500 2 6 14 30 27 13 5 6

560 2 5 13 29 25 11 4 5

630 2 5 12 28 23 10 4 4

710 2 5 11 27 22 9 3 4

800 2 4 11 26 20 8 2 3

75

xd

ax

D

L75

Dimensions (mm)Flow rate Insulation thickness

D upstream 25 mm 50 mmcross section Øda Øda ØD ØD

(m2) (mm) (mm) (mm) (mm)

80 0.005 79 80 135 191100 0.008 99 100 160 211125 0.012 124 125 191 235160 0.020 159 160 221 271200 0.031 199 200 261 311250 0.050 249 250 311 366315 0.079 314 315 376 476400 0.126 399 400 461 511

Type

Insulation thickness in mm1)

Size

Length in mm

Not required

Connection variations000 = Plug type spigotsVD2 = Lip seal on both ends

Order Code CA100 160 x 1000 00 VD2/ / /

1) Insulation thickness 25 and 50 mm available. (If the insulation thickness is not specified on the order, thickness 50 mm is delivered as standard.)

CA CF

Nomenclaturefm, oct. in Hz = Octave band centre frequencyNW = SizeL = Length

Page 74: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

74

Circular SilencersType CB

Insulation thickness 50 mm: � D = � d + 100 mmInsulation thickness 100 mm: � D = � d + 200 mm1) Low-leakage performance to DIN V 24194 Part 2, Class II without

additional on-site seals. Available up to and including size 400

Insulation thickness in mm 2)

Type 1)

Example:

Size

Length in mmMatching flange(s)00 = noneGZ = both ends

Connection variations000 = Plug-type spigotsVF2 = Flange on both ends3)

VD2 = Lip seal both ends4)

Order Code

CB 100 315 x 1000 GZ VF2/ / /

1) On Type CB: Coned end = air inlet end2) Insulation thickness 50 mm possible up to size 400 (if no insulation thickness is specified on order, thickness 100 mm is delivered as standard)3) Flange on both ends: L-20 mm4) Lip seal on both ends available for size 100...400

TEEEEEEEZEEEEEEEUTEEEEEZEEEEEU

Construction with plug type spigots (Standard)

xd

xD

L

Dimensions (mm)Upstream Plain flange in acc

D cross with DIN 24154 Part 1section Ød Øk b x s no. of

(m2) (mm) (mm) (mm) holes

100 0.008 99 132 25 x 3 4125 0.012 124 157 25 x 3 4160 0.020 159 192 25 x 4 6200 0.031 199 233 25 x 4 6250 0.050 249 283 25 x 4 6315 0.079 314 352 30 x 4 8400 0.126 399 438 30 x 4 8450 0.158 448 488 30 x 4 8500 0.198 498 538 30 x 4 8560 0.251 558 600 35 x 4 12630 0.316 628 670 35 x 4 12710 0.397 708 750 35 x 4 12800 0.499 798 840 35 x 4 16900 0.628 898 940 35 x 4 16

1000 0.785 998 1041 35 x 4 16

CB100; Insulation thickness = 100 mm

Insertion loss (dB) for L = 1000 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

250 5 10 17 30 47 50 50 36

315 4 9 15 27 44 45 39 27

400 3 7 13 25 40 38 29 21

450 3 7 12 24 39 35 26 18

500 2 6 12 23 38 33 24 17

560 2 6 11 22 36 31 21 15

630 2 5 11 21 34 29 19 13

710 2 5 10 20 33 27 17 12

800 2 5 9 19 31 25 14 10

900 2 4 9 18 30 23 13 9

1000 2 4 8 17 29 22 12 8

Insertion loss (dB) for L = 1500 mm

Dfm, oct. (Hz)

63 125 250 500 1k 2k 4k 8k

250 7 14 22 41 50 50 50 44

315 7 12 20 37 50 50 50 34

400 6 10 17 33 50 50 40 26

450 5 9 16 31 50 50 36 23

500 5 9 16 30 50 50 33 21

560 4 8 15 30 50 48 29 19

630 4 8 14 29 50 44 26 16

710 4 7 13 28 50 41 23 14

800 3 6 13 26 49 37 20 12

900 3 6 12 24 47 34 17 11

1000 3 6 11 23 45 33 16 10

Selection table

D Flow rate V. Upstream Airway- ∆pt LWAvelocity velocity

l/s m3/h m/s m/s Pa dB(A)

250 287 1035 6 9.9 41 44

315 459 1651 6 9.9 37 45

400 743 2674 6 9.9 33 45

450 942 3390 6 9.9 32 46

500 1164 4190 6 9.9 31 46

560 1462 5263 6 9.9 30 46

630 1853 6669 6 9.9 29 47

710 2355 8480 6 9.9 28 47

800 2993 10776 6 9.9 27 47

900 3792 13650 6 9.9 27 48

1000 4684 16863 6 9.9 26 48

CB CB

Nomenclaturefm, oct. in Hz = Octave band centre frequencyNW = SizeL = Length

∆Pt in Pa = Total pressure loss for L = 1000 mm

Page 75: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

75

Splitter AttenuatorType MSA 200

Insertion loss (dB) for airway width s = 100 mm

L (mm)fm (Hz)

63 125 250 500 1000 2000 4000 8000

500 2 4 12 12 15 11 9 8

1000 4 10 22 23 26 19 13 11

1500 5 14 31 33 36 25 16 13

2000 6 19 41 43 46 30 18 16

2500 8 24 49 50 50 37 22 18

3000 10 30 50 50 50 43 26 19

Combination (Width/Height) at ∆Pt approx. 50 Pa; Air-regenerated noise max. 46 dB(A) per m2 at L = 1500 mm

n = number of splitters

B

H

L

‡ (l /s)

10,000

12,000

14,000

16,000

8,000

6,000

4,000

2,000

0

300 400 500 600 700 800 900 1000H (mm)

B = 2400, n 8

B = 2100, n 7

B = 1800, n 6

B = 1500, n 5

B = 1200, n 4

B = 900, n 3

B = 600, n 2

B = 300, n 1

1100 1200 1300 1400 1500 1600 1700 1800

Type

Splitter thickness in mm

Airway width s in mm

No. of adjacent splitters n; adjacent inattenuator on direction of dimension B

F = Glass fibre fabric1)

L = Glass fibre fabric under perforated plate

Length L in mm

Height H in mm

Width B in mm

P = Air duct section 30 mm1)

W = Rectangular frame 35 x 3 mm2)

Splitter surface

Max. four digits each

Connecting frame

Order Code Splitter Attenuator

MSA200 - 100 - 3 - PF 900 x 600 x 1500/

1) Standard hygienic design2) Partitioned attenuators obligatory for division of the B and/or H dimension

IEEOEEP IEEOEEP

IEEOEEP

IEEOEEPIEEOEEP

IEEEEEOEEEEEP

MSA 200 MSA 200

Nomenclaturefm in Hz = Octave band centre frequency∆Pt in Pa = Total pressure drop‡ in m3/h = Flow rate

Page 76: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

76

Air Handling UnitX-CUBE

X-CUBE

With the TROX X-CUBE, an air handling unit with unlimited configuration options, TROX sets a new standard in the AHU marketand defines considerably higher levels of quality, performance, flexibility, reliability, energy efficiency, and hygiene. Compelling alldown the line. TROX now offers everything from a single source: air handling units and components – ideally complementary toeach other.

For even more energy efficiency and better quality with less coordination effort.

Key Features:

� Eurovent certified; ErP ready

� For the ventilation of rooms and entire buildings, for filtering, heating, and cooling the air, for heat recovery as well as for humidification and dehumidification, and for volume flow rates of up to 86,000 m³/h

� Flexible frame construction, completely covered externally by thermally insulated panels or doors

� Easy installation, maintenance and cleaning

� Integrated digital controls (Modbus or Bacnet) providing factory configure ‘plug and play’ easy to install solutions with reduced cabling.

� Special hygiene construction variant for use in hospitals and laboratories

� Weatherproof construction variant for outdoor installation

Page 77: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

77

Active Chilled BeamsType DID614

TypeDID614

Design VariantNo entry: Perforated face with

circular holes, encasedD2 Perforated face with circular

holes, no encased

Heat Exchanger2 2 Pipe4 4 Pipe

Nozzle VariantHE High efficiencyS1 Standard, smallS2 Standard, largeHP High performanceDA Twin nozzles(factory setting: all nozzles open)

Air control bladesNo entry: WithoutLE With air control blades

Exposed surfaceNo entry: Powder-coated

RAL 9010, pure whiteP1 Powder-coated,

specify RAL CLASSIC colour

Gloss levelRAL9010 50%RAL9006 30%All other RAL colours 70%

Overall dimensions [mm]L x B, nominal size 600 x 600593 x 593598 x 598L x B, nominal size 625 x 625618 x 618623 x 623L x B, nominal size 1200 x 6001193 x 5931198 x 598L x B, nominal size 1250 x 6251243 x 6181248 x 623

Order Code

DID614 DID614

Active chilled beam with four-way air discharge and horizontal heat exchanger, suitable for grid ceilings with grid size 600 or 625.

Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for integration with various ceiling systems.■ Preferably for room heights up to 4.20 m■ High heating and cooling capacity with a low conditioned primary air volume flow rate and low sound power level■ High comfort levels due to low airflow velocity in the occupied zone■ Five nozzle variants, including a variant with adjustable twin nozzles to optimise induction based on demand■ Removable induced air grille, fixed with magnets, with decreasing apertures towards the edges

Optional equipment and accessories■ Control package■ Adjustable air control blades to control the airflow■ Powder coating in many different colours, e.g. RAL CLASSIC or NCS

L142,5 42,5 G

H

557 47

∅D

A8

∅12

A

B

Dimensions (mm)Nominal Size L B L1 G

593 593 522 47.5

600 x 600598 598 522 47.5

618 618 522 47.5

623 623 522 47.5

1193 593 1122 47.5

1200 x 6001198 598 1122 47.5

1243 618 1147 35

1248 623 1147 35

Dimensions (mm)D H A

123 230 125

158 245 143

Primary air spigot123 123mm158 158mm

DID614 D2 2 HE R LEA1 593 x 593 123 P1 RAL 9016/ / / / / / / / /

Water connections (without control package)No entry: Plain pipe tails, Ø12mmA1 With G1/2" external thread & flat sealA2 With G1/2" union nut & flat seal

Position of water connectionR Right sideL Left side

Page 78: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

78

Active Chilled BeamsType DID642

DID642 DID642

Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings with grid size 600 or 625.

Active chilled beam for heating and cooling, with 2-pipe or 4-pipe heat exchanger, for integration with various ceiling systems.� Preferably for room heights up to 4.0 m� High heating and cooling capacity with a low conditioned primary air volume flow rate and low sound power level� High comfort levels due to low airflow velocity in the occupied zone� Five nozzle variants, including a variant with adjustable twin nozzles to optimise induction based on demand� Hinge down or removable induced air grille, with decreasing apertures towards the edges

Optional equipment and accessories� Control package� Adjustable air control blades to control the airflow� Powder coating in many different colours, e.g. RAL CLASSIC

LLN – 62

Y

HSØD H

8

584

B

Dimensions (mm)LN L

900 893 - 1500

1200 1193 - 1800

1500 1493 - 2100

1800 1793 - 2400

2100 2093 - 2700

2400 2393 - 3000

2700 2693 - 3000

3000 2993 - 3000

Dimensions (mm)ØD H HS

123 170 99

158 205 116.5

TypeDID642

Design VariantNo entry: Perforated face

with circular holes, encasedD2 Perforated face with circular

holes, no encased

Heat Exchanger2 2 Pipe4 4 Pipe

Nozzle VariantHE High efficiencyS1 Standard, smallS2 Standard, largeHP High performanceDA Twin nozzles(factory setting: all nozzles open)

Position of plenum & water connectionLL Left plenum, water connections on the leftLR Left plenum, water connections on the rightRL Right plenum, water connections on the leftRR Right plenum, water connections on the right

Water connections (without control package)No entry: Plain pipe tails, Ø12mmA1 With G1/2" external thread & flat sealA2 With G1/2" union nut & flat seal

Air control bladesNo entry: WithoutLE With air control blades

Exposed surfaceNo entry: Powder-coated

RAL 9010, pure whiteP1 Powder-coated,

specify RAL CLASSIC colour

Gloss levelRAL9010 50%RAL9006 30%All other RAL colours 70%

Overall dimensions [mm]L x LN x BOverall length (face) x nominal length x O/A width (face)L max = LN - 7mm

Order Code

Primary air spigot123 123mm158 158mm2x123 2x 123mm2x158 2x 158mm

Primary air spigot,additional housing123 123mm158 158mm

DID642 D2 2 HE RR LEA1 1200 x 900 - 593 123 P1 RAL 9016/ / / / / / / / /// AV 158

Function & arrangement, additional housingNo entry: None

Only for LL, RR, L = LN + 250mmAV Extract, air connection frontAH Extract, air connection rearZV Supply, air connection frontZH Supply, air connection rear

Page 79: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

79

Passive Chilled BeamsType PKV

PVK-0 PVK-L PVK-R-L

Passive chilled beam in nominal lengths of up to 3000 mm and with a horizontal heat exchanger.

Passive chilled beam with 2-pipe heat exchanger for ceiling installation, either freely suspended or above an open cell ceiling.� Preferably for room heights from 2.6m� Comfortable room cooling� Water connection from the side or top� 3 standard widths and heights for optimum dissipation of heat loads

Optional equipment and accessories� Control package� Aluminium frame with perforated metal facing� Heat exchanger powder-coated black� Powder coating in many different colours, e.g. RAL CLASSIC or NCS

LH

L B

H60

A A Dimensions (mm)

L 1000, 1500, 2000, 2500, 3000

B 295, 455, 575

W 240, 400, 520

H 110, 200, 300

TypePKV

Aluminium frameNo entry: NoneR With

Perforated metal faceNo entry: NoneL With

Water connectionG Pipe Conn. Ø12mm, straightB Pipe Conn. Ø12mm, 90° vertical

SuspensionW Hanging brackets

Surface of heat exchangerNo entry: UntreatedG3 RAL 9005, black

Exposed surfaceNo entry: No frame

RAL 9005, blackNo entry: With frame and/or perforated metal

facing, RAL 9010, pure whiteP1 Powder-coated, specify RAL CLASSIC colour

Gloss level:RAL 9010 50%RAL 9006 30%All other RAL colours 70%

Length [mm]L10001500200025003000

Width [mm]B295455575

Height [mm]H110200300

Order Code

PKV R L G W G32500 455 200 P1 - RAL 9010/ / / / / x x / /

Page 80: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

80

Multi Service Chilled BeamMSCB

The latest advance in chilled beam technology combines aesthetic flexibility with economical functionality to produce the nextgeneration in building services systems. Designed around one of TROX’s active or passive chilled beam units, beam casingsincorporate high grade architectural extrusion and the opportunity for the inclusion of integrated mechanical services to meet aclient’s bespoke needs.

TROX UK has comprehensive testing facilities which allows for the manufacture and testing of a full size sample in a mock-upsetting. Key criteria are confirmed by the in-house laboratory including: thermal, photometric, aerodynamic and acousticrequirements.

Mechanical services that can be incorporated into thebeam include:

� Lighting

� Loudspeakers

� Sprinklers

� Smoke detectors

� Motion detectors

� Hidden integral cable trays

Key advantages:

� Shorter construction period

� Earlier amortisation of the investment for the owner

� Easy installation (plug and play)

� Significant reduction of interfaces on site

� Good quality of the system due to factory assembly of the components

Page 81: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

81

Fancoil

Manufactured in the UK, to meet with the latest Part L, thelatest TROX range of horizontal concealed water sidecontrolled chassis fancoils have been redesigned into amonocoque configuration with an integral multi-spigotdischarge plenum, enabling lower SFP, reduced noise levelsand higher overall efficiency.

The PWH range comprises of six sizes to cover a range ofairflows from 75 l/s to 560l/s, with external pressures from 5Pato 75Pa, and total cooling duties from 1kW to 7.5kW. Also theycan be matched to the TROX plenum/grille sets to have theperfect system.

With the PWH fancoils having a standard height of 270mmthey are ideal where higher duties are required, and aresupplied as standard complete with either G2 or G3 washablefilters, control and valve packages, round or elliptical dischargespigots and standard sloping drain trays that are extendedunder the valve sets. For critical noise applications TROX areable to supply fully tested attenuators for the inlet anddischarges of the fancoil.

TROX ControlsThe fancoils can be supplied with standard factory fitted, and fully tested controls package that is suitable for BacNetcompatibility.

TROX Valve SetsThe fancoils can be supplied with standard factory fitted, and fully tested valve andactuator packages. These are selected to ensure correct control with the fancoilexchangers.

These valve sets consist of 2-way pressure independent control valves, with the option ofincluded electronic flow meters. The PICV’s are fully configured with diverting valves, anddrains to ensure the valve is protected during flushing. Binder points are also included forcommissioning of the unit.

TestingTROX have an in house, BSRIA approved test laboratory where all the PWH units are rigorously tested to the latest standards.The fancoils for a particular project can be witness tested to prove the given duties.

There are many variables, please enquire with TROX UK office for full computer selections.

Page 82: Quick Selection - TROX UK · This Quick Selection Guide has been designed to help you select the products you require quickly and easily. It provides an overview of the various product

Des

ign ch

ange

s rese

rved

: All rig

hts rese

rved

© TROX U

K (2

016 r2)

Headquarters Germany

TROX GmbH Phone +49(0)28 45 / 2 02-0Heinrich-TROX-Platz Fax +49(0)28 45 / 2 02-2 65

E-Mail [email protected] Neukirchen-Vluyn www.troxtechnik.com

UK Subsidiary

TROX UK Ltd Phone +44 (0)1842 754545Caxton Way Fax +44 (0) 1842 763051Thetford E-Mail [email protected] 3SQ www.troxuk.co.uk

SubsidiariesArgentinaTROX Argentina S.A.AustraliaTROX Australia Pty LtdAustriaTROX Austria GmbHBelgiumS.A. TROX Belgium N.V.BrazilTROX do Brasil Ltda.BulgariaTROX Austria GmbHChinaTROX Air Conditioning Components(Suzhou) Co., Ltd.CroatiaTROX Austria GmbHCzech RepublicTROX Austria GmbHDenmarkTROX Danmark A/S

FranceTROX France SarlGreat BritainTROX UK Ltd.Hong KongTROX Hong Kong Ltd.HungaryTROX Austria GmbHIndiaTROX INDIA PRIVATE LIMITEDItalyTROX Italia S.p.A.MalaysiaTROX Malaysia Sdn. Bhd.NorwayTROX Auranor Norge ASPolandTROX Austria GmbHRomaniaTROX Austria GmbH

RussiaOOO TROX RUSSerbiaTROX Austria GmbHSouth AfricaTROX South Africa (Pty) LtdSpainTROX España, S.A.SwedenTROX Sverige ABSwitzerlandTROX HESCO Schweiz AGTurkeyTROX TURKEY TEKNIKKLIMA SAN. Ve TIC. LTD. STIUnited Arab EmiratesTROX Middle East (LLC)USATROX USA, Inc.

International RepresentativesAbu DhabiBosnia-HerzegovinaChileCyprusEgyptFinlandGreeceIceland

IndonesiaIranIrelandIsraelJordanKoreaLatviaLebanon

LithuaniaMexicoMoroccoNetherlandsNew ZealandOmanPakistanPhilippines

PortugalSaudi ArabiaSlovak RepublicSloveniaSwedenTaiwanThailandUkraine

UruguayVenezuelaVietnamZimbabwe