QUICKNOTE Getting started with Rockwell Studio 5000 Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division www.molex.com 1 Rev Date File Name 1.0 24/10/2016 Getting started with Rockwell Studio 5000 Product concerned: - TCIEI-888P-DYU / SAP # 1120955122 - TCIEI-888P-D1U / SAP # 1120955121 Product version: All Environment: All Related documents: HarshIO EtherNetIP IO-Link Master user’s manual Restriction : None Although every effort was made to ensure the accuracy of this document, all information is subject to change without notice. Molex takes no liability for any errors in this document or for direct, indirect, or consequential damage resulting from the use of this manual.

Upload: others

Post on 03-Dec-2021

17 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 1

Rev Date File Name

1.0 24/10/2016 Getting started with Rockwell Studio 5000

Product concerned: - TCIEI-888P-DYU / SAP # 1120955122 - TCIEI-888P-D1U / SAP # 1120955121

Product version: All Environment: All Related documents: HarshIO EtherNetIP IO-Link Master user’s manual Restriction : None

Although every effort was made to ensure the accuracy of this document, all information is subject to change without notice. Molex takes no liability for any errors in this document or for direct, indirect, or consequential damage resulting from the use of this manual.

Page 2: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 2

1. Getting started with Rockwell Studio 5000

1.1. Configuring HarshIO module with EDS file.

1.1.1. EDS File Before proceeding to the product commissioning, the HarshIO module requires a description file (also called EDS file) that shall be imported in the Rockwell Automation Studio™ 5000 software. The EDS file as well as the product documentation can be downloaded from the Molex web site.

http://www.molex.com/molex/mysst/DownloadCenter.action

option 1 – “Search by part number” to look for TCIEI-888P-DxU (4-pin or 5-pin power connector) parts.

Page 3: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 3

1.1.2. Import HarshIO EDS file into Rockwell hardware library

To start the commissioning, the first step is to import the HarshIO EDS file into Rockwell hardware library by using Rockwell Automation RSLinx™ software. Start RA RSLinx software.

Select Menu Communications/Configure Drivers…

Select EtherNet/IP Driver

Page 4: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 4

Set a name for the Driver.

If you have multiple network interfaces in your computer, select the correct one to communicate with the HarshIO eIP module.

Page 5: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 5

Check that the Driver is running.

RSLinx is now browsing the network to detect the EtherNet/IP devices. At this stage, the HarshIO eIP module is detected but appears with an icon representing a question mark because the EDS file is not yet imported.

Page 6: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 6

Select the HarshIO module, right-click on mouse and select Upload EDS file from device

A new tool is launch. Select Next button.

Page 7: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 7

The EDS Wizard is checking the EDS file revision in the device.

Page 8: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 8

The EDS Wizard is checking integrity of the EDS file.

The EDS Wizard is checking integrity of the icon file

The EDS Wizard is importing the EDS file and icon in the Rockwell hardware library.

Page 9: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 9

The EDS Wizard has successfully import the files.

RSlinx has registered correctly the EDS file and display the correct icon of the HarshIO eIP module.

Page 10: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 10

HarshIO module into Rockwell RSLogix 5000 software

1.1.3. Add HarshIO module into Rockwell Studio 5000 software Start RSLogix 5000 software. Select the Ethernet node of the EtherNet/IP connectivity channel. Right-click on mouse and select New Module…

Page 11: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 11

Search for Vendor Molex and select in the Catalog the HarshIO module. Select the module TCIEI-888-DxU, right-click on mouse and select Create

Give a Name and set the module IP address.

Page 12: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 12

Then select the type and size of the I/O connections. By default an Exclusive Owner connection with 4 bytes IO-Link process data is configured. Select Change button to modify the connection configuration.

Note! Remember the HarshIO module supports different process IO-Link data size to optimize the frame size on the network and limit the memory space used in the CPU. Available size are:

Digital I/O data + 04 bytes I/O data per IO-Link device

Digital I/O data + 08 bytes I/O data per IO-Link device

Digital I/O data + 32 bytes I/O data per IO-Link device Refer to chapter I/O data mapping for more information.

Note! Only one single Exclusive Owner connection can be configured for the module.

Page 13: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 13

Click on the connection and select one from the drop down list. For each connection, the size in bytes is displayed for information.

EO: Exclusive Owner connection

IO: Input Only connection

LO: Listen Only Connection

See chapter I/O messaging in the user’s manual for the explanation of the different type and use of the connections. Select OK and Yes to apply the modifications. Select the Connection tab to configure the RPI, the I/O connection type (Unicast or Multicast) and the exchange mode (Cyclic or Change-of-State).

Note! The HarshIO eIP module supports RPI up to 2ms packet interval.

Note! Remember a RPI set at

ms generate 1000 packets per second (500x packets from Scanner to HarshIO + 500x packets from HarshIO to Scanner)

4ms generate 500 packets per second (250x packets from Scanner to HarshIO + 250x packets from HarshIO to Scanner)

8ms generate 250 packets per second (125x packets from Scanner to HarshIO + 125x packets from HarshIO to Scanner)

Etc

Page 14: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 14

Select OK button. The HarshIO module is now configured and in the EtherNet/IP scan list. Download the new project in the controller CPU. Go online and check the HarshIO module communication status.

Page 15: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 15

1.1.4. Modifying HarshIO module parameters in RSLogix 5000 software

Go online and double click on HarshIO module. Select Module Info tab to display HarshIO module information.

Select Internet Protocol tab to configure IP address settings of HarshIO module.

Page 16: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 16

Select Port Configuration tab to setup HarshIO Ethernet ports of the integrated 2-port switch.

1.1.5. Configuration of the IO channel

The HarshIO is running (an active connection is established between the EtherNet/IP scanner and the module). The next step is to set parameters in the Configuration Assembly of the module to configure the behavior of each I/O channel (input, output or IO-Link). See the chapter Configuration data mapping for compete description of the memory mapping. In the example, I will set:

Channel C0 in IO-Link mode HARSHIO.C.Data[7] = 3 Channel C1 in Digital Input HARSHIO.C.Data[4] = 0 Channel C8 in IO-Link mode HARSHIO.C.Data[135] = 3 Channel C9 in Digital Output HARSHIO.C.Data[132] = 1 Channel C10 in IO-Link mode HARSHIO.C.Data[167] = 3 Channel C11 in Digital Input inverted HARSHIO.C.Data[164] = 0

HARSHIO.C.Data[166] = 1

Page 17: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 17

Note! When the Configuration assembly is set, the module connection needs to be reset to send the parameters to the HarshIO.

As a result, the HarshIO has channels C0, C8 and C10 blinking in blue (pre-operate state) waiting the connection of IO-Link devices.

1.2. Configuring HarshIO module with generic profile.

The first step is to add a HarshIO in the configuration of a Rockwell Scanner supporting EtherNet/IP by selecting "ETHERNET-MODULE" (Generic Ethernet Module) device as shown below.

Page 18: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 18

And select Create. In the configuration of the "ETHERNET-MODULE", set the parameters of the HarshIO with the following properties (corresponding to Digital I/O data + 04 bytes data per IO-Link device):

See IO data mapping chapter in the user’s manual for more instance numbers and sizes.

Instance numbers

Size of each parameter

IP address of HarshIO

Page 19: Quickstart Getting Started with Rockwell Studio 5000 - Molex

QUICKNOTE

Getting started with Rockwell Studio 5000

Getting started with Rockwell Studio 5000Upgrading V1.0 ©2016 Molex.Integrated Products Division

www.molex.com 19

See the chapter Configuration of the I/O channels to configure each I/O channel in digital input, digital output or IO-Link.