+ Landis+Gyr E650 INVESTMENT PROTECTION THROUGH FLEXIBLE MODULARITY
03-11, 1 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
Customer Segments
Grid
Large industrial customers
Industrial customers
Commercial customers
Residential customers
Activ
e Mete
r-AT/A
R
- D
irect co
nnecte
d
- Tr
ansfor
mer co
nnecte
d Co
mbi M
eter-C
T/CR
- D
irect co
nnecte
d
- Tr
ansfor
mer co
nnecte
d
03-11, 2 – Investment protection through flexible modularity
Basic Configurations xxxxxxxR44.0457.c1 S3(a)
Application Range High voltage Medium voltage Low voltage
Connection Type Transf. connection Direct connection
Measuring Accuracy Class 0.2/0.5 Class 0.5 (C)/1.0
Energy Type Active energy Reactive energy Apparent energy
COMBI ACTIVE
active energy (MID) / reactive energy
ZMD
310A
ZMD
410A
ZF
D41
0A
ZMD
310C
ZM
D41
0C
ZMD
405C
ZM
D40
2C
ZFD
410C
ZF
D40
5C
ZFD
402C
Class 1.0 (B)/1.0
03-11, 3 – Investment protection through flexible modularity
ZMD
405A
ZF
D40
5A
ZMD
402A
ZF
D40
2A
The Landis+Gyr E650 Family - Overview
03-11, 4 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
Voltage and Current Ranges
ZFD410...
ZMD402...
ZMD405...
ZMD310...
3x22
0V
3x10
0V
3x23
0/40
0V
3x12
7/22
0V
3x58
/100
V
ZMD410...
5 (1
20)A
5 (1
0)A
1 (1
0)A
1 (2
)A
2 (4
)A
Wid
e vo
ltage
ZFD402...
ZFD405...
ZxDxxxCT44.0457 S3(a)
5 (2
0)A
New in B31
0.3(
1.2)
A
Modular or Simple
ZMD310CR/AR ZFD4xxCR/AR ZMD4xxCR/AR
ZMD310CT/AT ZFD4xxCT/AT ZMD4xxCT/AT
integrated interface exchangeable modules ( type T ) ( type R )
ZxDxxxXR44.2407.c2 S3(a)
03-11, 5 – Investment protection through flexible modularity
Note: xx can be 10 / 05 / 02
The Landis+Gyr E650 Family - Overview
ZxDxxxXT44.2407 S3(a) Tariff Functions
Tariff Type Energy only Energy and Demand
Time of Use Without Time of Use With Time of Use
44
41
24
21
ZMD405CRxx.0457.c1 S3
03-11, 6 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
-
2
Additional Functionality (1)
Control Inputs 2 additional inputs 4 additional inputs
2 additional outputs Output Contacts 4 additional outputs 6 additional outputs
Integrated Ripple Control Receiver
Additional Power Supply (100…240VDC/AC)
The following In- and Outputs are standard in the Basic E650: • 3 control inputs • 2 output contacts
ZMD310CR44.xxx7.c1 S3a
0457
04
37
0037
42
07
2407
06
07
0467
Additional Power Supply (12…24VDC)
03-11, 7 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
not applicable for Series 3
X
X
DC magnet detection is supported by the following meter types: + ZMD310xT + ZxD410xT + ZxD405xT + ZxD402xT Series 2: The meter supports either the DC magnet detection or the terminal cover detection but not both at the same time. Series 3: The meter supports both the DC magnet and terminal cover detection at the same time.
Additional Functionality (2)
ZMD405CR44.045x.c1 S3
Load Profile disabled enabled
DC magnet detection
disabled enabled
9 7 2 0
03-11, 8 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
Communication
ZMD405CR44.0257.xx S3 ZMD405CT44.0257.xx S3
RS232 Interface CS Interface
2 Pulse Inputs S0
A4
c3
c2
c1
M-Bus Interface
D2
PSTN Modem *
GSM/GPRS Modem
G32
G
31
G30
P3
2
E22
B4
B2
B1 A5
Integrated Interfaces (Meter-Type R)
Interchangeable Interface (Meter-Type T)
* /V22b, V34b
RS422 Interface
GSM Modem
Ethernet Interface
Interchangeable Modems (Meter-Type T)
P30
RS485 Interface
c6
E20
M22
M
20
03-11, 9 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
Symmetrical connection
+ Is available in all transformer connected meter versions of the ZMD400. + The type designation is extended with a small “s” to indicate the
symmetrical connection.
I1 I1U1 I2 U2 I2I3 U3 I3N
1 2 3 4 5 6 7 8 9 11
ZMD410CT44.0457 S3s
03-11, 10 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
Type Designation
Connection ZFD 3-phase, 3-wire Diagram ZMD 3-phase, 4-wire Connection 3 Direct, digital measuring Type 4 Transformer, digital measuring Accuracy 10 Class 1.0 to IEC
05 Class 0.5 to IEC 02 Class 0.2 to IEC
Energy C Active, Reactive and Apparent Type A Active Model T modular Communication
R integrated Interface Tariff 21 Energy only, no TOU Functions 24 Energy only, with TOU
41 Energy and Demand, no TOU 44 Energy and Demand, with TOU
Additional additional inputs on extension board Functions* additional outputs on extension board
5/6 integrated additional Power Supply 2/7 DC magnet detection / Load Profile Memory
Series 3
ZMD x 10 C T 44 . 2 4 0 7 S3(a)
03-11, 11 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
* Integrated ripple control receiver is available with Series 2
+ Terminal cover detection + With the ZMD310 and ZxD400 meter a accessory kit is available to detect
the terminal cover removal.
+ The state changes of the switch can be registered in to the event log over a control input.
Note: Series 2: The meter supports either the DC magnet detection or the terminal cover detection but not both at the same time. Series 3: The meter supports both the DC magnet and terminal cover detection at the same time.
03-11, 12 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Overview
-
3
The Landis+Gyr E650 Family - Measuring System Measured Quantities
+Q
+P-P
-Q
44 Measuring quantities based on power: + Active energy / power + Reactive energy / power + Apparent energy / power + Power factor + for each direction or quadrant + for each phase or total
16 additional measuring quantities as instantaneous values: +
+ Voltage (per phase) + Current (per phase and neutral) + Active- and Reactive Power (Sum) + Phase angles (U-U and U-I) + Frequency
03-11, 13 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Measuring System Block-Diagram of E650-Meter
Ut
U1 U2 U3 N
I1 I2 I3
Control Inputs
Measurement System
Power supply
Voltage Supervision
Memory Load-Profile
Microprocessor
Signal processing
Signal Utilization
Tariff
Control
Data for
Billing
Time Switch
Display Keys
Calendar Clock
Reset
A/D Calibra- tion
Extension Board Inputs Outputs Add. PS
A/D
Communication Unit with
Impulse-Inputs
LCD-Display
Optical Interface
Test Diodes
Output Contacts
Interface Board
03-11, 14 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Measuring System Block-Diagram of Digital Signal Processor
Digital Values
Ix Analogue
Input Signals
A/D Converter
Ix i
Ux
u
u, i: calibrated instantaneous values for voltage and current
Px
p: instantaneous active power q: instantaneous reactive power u*: voltage displaced by 90° tn: zero passage time
Qx
ϕ u-i
fn
tn
Ux
Digital Filter
Calibra- tion i
A/D Converter
Digital Filter
Calibra- tion u
ϕ u
2i
2u
iuq * ×=
iup ×=
03-11, 15 – Investment protection through flexible modularity
THD
Form
atio
n of
mea
n va
lues
per
sec
ond
THD
The Landis+Gyr E650 Family - Energy and Demand Registers Measured Quantities Selection
6 x ±Ax
6 x ±Rx
6 x ±Rix
6 x ±Rcx
6 x ±VAx
2 x ±AΣ
2 x ±RΣ
2 x ±RiΣ
2 x ±RcΣ
2 x ±VAΣ
Sele
ctio
n of
max
imal
8 q
uant
ities
Ext. Impulses 1, 2
Summation 1,2
ME 1
ME 2
…
ME 7
ME 8
ME 19
…
ME 27
ME 9, 10
ME 11, 12
Total Energy
Total Energy
Total Energy
Total Energy
Total Energy
Total Energy
Total Energy
Current Average
Current Average
Current Average
Current Average
Last Average
Last Average
Last Average
Last Average
03-11, 16 – Investment protection through flexible modularity
+THD, -THD
OLA, NLA, I2, U2 ME 13, 14 ME 15-18
Total Energy
Total Energy
… … …
…
…
New from B31
Maximum 24 Cum. Maximum 24 Energy Rate 32
The Landis+Gyr E650 Family - Energy and Demand Registers Energy and Demand Rate Registers
Sele
ctio
n of
Mea
sure
d Q
uant
ities
ME 1
…
ME 7
ME 8
ME 19
…
ME 27
Maximum 2 Cum. Maximum 2 Energy Rate 2
Maximum 1 Cum. Maximum 1 …
SP
PF = PF Average over Billing Period PF Minimum 2
PF Minimum 1
03-11, 17 – Investment protection through flexible modularity
…
Energy Rate 1
ME 1-8, 19-27 ME 1-8 ME 1-8
New from B31
The Landis+Gyr E650 Family - Energy and Demand Registers Special Energy Registers
All Energy Rate Registers can be defined in three different modes:
Available for:
Cumulative Value
Billing Period Delta Value
Integration Period Delta Value
Billing Period
Yes
Yes
No
Load Profile 1, 2
Yes
No
Yes
03-11, 18 – Investment protection through flexible modularity
-
4
The Landis+Gyr E650 Family - Energy and Demand Registers Sliding (Rolling) Demand
The Integration Period for the Demand Registers can be divided into Sub-Intervals. This Function is called Sliding Demand or Rolling Demand.
Integration Period
1 2 3 5 10 15 20 30 60
1 1 2 3 5 10 15 20 30 60
2 - 1 - - 5 -
10 15 30
3 - - 1 - - 5 -
10 20
4 - - - - - - 5 -
15
5 - - - 1 2 3 4 6 12
6 - - - - - - - 5 10
10 - - - - 1 - 2 3 6
12 - - - - - - - - 5
15 - - - - - 1 - 2 4
Number of Sub-Intervals
Duration of Sub-Intervals in Minutes In Minutes
03-11, 19 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Energy and Demand Registers Stored Values (Billing Periods) Stored Values are Captured at the Event of a Billing Period Reset:
• Control Inputs (KA / KB) • Integrated RCR* • Reset Button • Communication
Billing Periods can be stored by the following Controls:
• Internal Real Time Clock (at full hours) - weekly (any day) - monthly at up to 6 days - at daylight saving begin and end
• *Maximum Demand Registers • *Minimum Power Factor Registers • *Billing Period Average Power Factor
The following Registers can be Captured at the Billing Period Reset:
• Energy Total Registers • Energy Rate Registers - Cumulating Value Registers - *Billing Period Delta Value Registers
* : These Registers are reset at Billing Period Reset
03-11, 20 – Investment protection through flexible modularity
* : not applicable to Series 3
The Landis+Gyr E650 Family 2nd Demand Period with B31
+ One customer in NL requires the possibility to define Pmax with 15min and demand values captured in the load profile with a period of 5min.
+ For this purpose we introduce a new parameter in the sliding demand in order to enable the new feature. In this case the Pmax is captured with the integration period and the demand values are captured in the LP with the subinterval period.
+ Using this function with two LP‘s it is possible to define 3 different periods, the integration period for the maximum demand, the subinterval capture period for one LP and an independent capture period for the 2nd LP.
New in B31
03-11, 21 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Summation function with B31 + Summation is a very common function for meter points where the billing is
based on the total maximum of more than just one meter.
+ ZMD300/400 Series 3 supports now up to 2 summation channels SUM1 and SUM2
ME1
EX1
EX2
MExx+ Total energy register
Demand, max. demandstored valuespulse outputs
displayreadout
load profile(s)
03-11, 22 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Losses in ZMD400 Series 3 with B31
+ We support now the calculation of Losses: § OLA, On load active. Line (copper) losses of active
energy. OLA = I2h x RCu. The value of RCu can be set by parameterisation
§ NLA, No load active. Transformer (iron) losses of active energy. NLA = U2h / RFe. The value of RFe can be set by parameterisation.
§ I2h (Cu), Ampere square hours (with RCu = 1 W) § U2h (Fe), Voltage square hours (with RFe 1 MW)
Generator
Meter AProduction
Load
Meter B Customer
Metering point A Metering point B Metering point C
RCuRFe
Transmission
03-11, 23 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Total Harmonic distortion with B31 + We support now the calculation of Total
Harmonic Distortion (THD):
+ Following values are available:
+THDA+A +THD = +A - (+A )A fundamental
-THDA-A -THD = -A - (-AA fundamental)
THD of active energy import +THDA Sum Sum
THD of active energy export -THDA Sum Sum
THD of active energy (percent) THDA [%] Sum Sum
THD of phase voltages (absolute) THDU Sum / Phases Sum
THD of voltage (percent) THDU [%] Sum Sum
THD of phase currents (absolute) THDI Sum / Phases Sum
THD of current (percent) THDI [%] Sum Sum
03-11, 24 – Investment protection through flexible modularity
-
5
The Landis+Gyr E650 Family - Load Profile Load Profile Capturing
Profile Values are Captured in regular Intervals:
The Capture Period is selected between the Demand Integration Period
and the Demand Subinterval*.
The Capture Period of the Profile is always synchronous to the full hour
• Last Average Demand • Last Average Power Factor • Energy Total Registers • Energy Integration Period Registers
The following Registers can be Captured into the Load Profile:
• Average Values (over Capture Period) - Voltages (all 3 Phases) - Currents (3 Phases and Neutral) - Mains Frequency
* : With Subinterval as Capturing period, no Demand Values can be selected
03-11, 25 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Load Profile Load Profile Data Format
Identification / Header
End
Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry
Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Date / Time / Status
Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry
Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Date / Time / Status
Definition of Profile including: • Definition of Captured Values • Length of Capture Period • Number of Entries
Start of a new Day with: • Date and Time • Status (acc. VDEW)
Captured Objects: • 1 to 14 Values
The handling of the following Events must be parameterised: • Supply Interruptions • Demand Rate Switching • Billing Period Reset
03-11, 26 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Two Load profiles with B31 + The capacity of the load profile has
been increased (double) as well as the number of captured channels (from 14 to 26).
+ The ZMD300/400 Series 3 supports now up to 2 load profiles, e.g. for billing and monitoring purposes.
+ The two capture periods are independent.
+ One of the capture period is equal to the demand integration period.
+ The instantaneous values can be captured in either in the load profile 1 or in the load profile 2, depending on parameterization.
03-11, 27 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Load Profile Load Profile 1 and 2 Memory allocation
03-11, 28 – Investment protection through flexible modularity
Use Number of memory pages
Default setting memory pages
Event log 1 to max. 74 11 pages Stored values 1 to max. 78 17 pages Load profile 1 2390 to max. 7541 1) Load profile 2 50 2) to max. 5000 3500 pages
In total a maximum of 7542 memory pages can be allocated as followed:
1) The memory size available for the Load Profile 1 is the remaining memory which is not allocated for the stored values, event log or the 2nd load profile.
2) Minimum numbers of memory pages for 2nd load profile (if activated).
The Landis+Gyr E650 Family - Event Monitoring Monitors for Voltage and Current
The following parameters are available: • Threshold for Over-Voltage • Threshold for Under-Voltage • Activation Delay for Voltage Monitors • Threshold for Phase Over-Current • Threshold for Neutral Over-Current • Activation Delay for Current Monitors (to filter out short Events)
For each Phase individual Event-Counters store the number of Exceedings.
The Events of every Phase can be used for Control
purposes and stored in the Event Log-Book
Vm Vt
td
td Vm: Monitored Value Vt: Threshold Value td: Activation Delay Alert: Alert Signal Alert
03-11, 29 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Event Monitoring Monitors for Power and Power-Factor
8 Demand Monitors with: - Selection of Measured Quantity - Current- or Last Average-Demand - Definition of Threshold and Tariff
2 Power-Factor (PF) Monitors with: - Definition of Threshold and Tariff - Apparent Power Threshold for PF
For each Monitor individual Event-Counters store the number of Exceedings.
The Events of every Monitor can be used for Control
purposes and stored in the Event Log-Book
Vm Vt
Vm: Monitored Value Vt: Threshold Value CA-Alert: Current-Average-Alert LA-Alert: Last-Average-Alert &
Power-Factor-Alert
CA-Alert
LA-Alert
03-11, 30 – Investment protection through flexible modularity
-
6
The Landis+Gyr E650 Family - Event Monitoring Monitors for other special Events
Many other Internal Signals of State Information or Actions are available for the Event Log-Book. We list here some of the most used ones, please refer to the user manual for detailed information: • Phase Fail per Phase, Total Power Down, • Battery (voltage low, replaced, voltage ok), • Time/Date invalid, Time/Date adjusted, • Error in the data processing detected • and many others
For the Control of Outputs (like LCD-Display-Arrows or Output-Contacts) you can select the Alarm Signal for the invalid Time/Date and all Monitors for Demand, Power-Factor, Voltage and Current.
03-11, 31 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Event Monitoring The Event Log-Book
The Event Log-Book stores the Events in an a-periodic Memory according to the parameterisation. With full Memory new entries delete the oldest ones.
Time / Day Stamp of the Event
Status-Byte („VDEW“-standard)
Event-Number (Landis+Gyr specific)
Actual Information of Error-Bytes
Optional the following fields can be captured: • Event-State (Landis+Gyr specific) • Energy Total Registers
03-11, 32 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Event Monitoring Alert-Function
Supervision of selected functions: • Phase voltage • Checksum errors • Low battery voltage • etc.
These events will (if selected) set a special control signal The following actions can now be controlled: - indication with an arrow on the LCD - state of output contact - Rate-Registers for Energy, Power, Power-Factor and Time
These events will (if selected) initiate the emission of an SMS through a connected GSM modem
03-11, 33 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Network Quality Events with B31 + We have introduced 3 new network quality
dedicated events:
§ Under- and Overvoltage per phase - total number of the events - cumulated duration of the events - duration of the longest, with time stamp - duration of the shortest, with time stamp - 30 last events (with time stamp, duration, magnitude, phase)
§ Phase fail - number of cuts - cumulated duration of cuts - duration of the longest, with time stamp - duration of the shortest, with time stamp - 30 last cuts (with time stamp, duration, magnitude, phase)
+ The three events can be defined as previously in the event log or as the new dedicated event log.
+ With the new dedicated event log it is possible to define a snapshot buffer.
03-11, 34 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Additional features with B31
+ Billing period reset § With B31 it is possible to define one fixed day per
month, e.g. 3 days before end of each month.
+ Vectorial calculation of reactive energy § With B31 it is possible to calculate reactive power Q
using the values of active power and apparent power.
§ This calculation method is limited to Class 2. § Power factor calculation is not supported when this
method is in use.
§ This method includes the harmonics.
03-11, 35 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Additional features with B31 + Instantaneous power with sign § If the meter is parameterized to calculate
the instantaneous power as signed values: Active P: + in QI and QIV, - in QII and QIII Reactive P: + in QI and QII, - in QIII and QIV
+ Auxiliary power loss detection § The extension board type 045x and 046x feature an
auxiliary power supply. When the auxiliary power is missing an event is triggered according to its parameterisation.
§ According to its parameterization, the auxiliary power loss detection can trigger the Missing Additional Power supply event (58) and can be used to trigger an alert. The appearance of an alert can be indicated by an arrow on display or by the Alert LED.
- Landis+Gyr - E650 Series 3
Bit # Description State definition
Bit 0 Missing additional power supply
0 = Us present 1 = Us absent
Bit 1-7 not used
Status C.4.3
03-11, 36 – Investment protection through flexible modularity
-
7
The Landis+Gyr E650 Family Additional features with B31 + Current without voltage § In some applications the voltage transformer is protected against short circuit by a fuse
in the measurement circuit. In case the fuse blows up, this is detected and indicated.
§ 3 new events are defined to indicate current without voltage per phase (event nr 55, 56 and 57)
§ The occurrence of the event is indicated in a status, C.4.2 Current without Voltage Status
§ The event occurrence can be included in bit 24 of the status code of the load profile if it is enabled by parameterisation.
Bit # Description State definition
Bit 0 Current without voltage L1 0 = I below threshold 1 = I above threshold
Bit 1 Current without voltage L2 0 = I below threshold 1 = I above threshold
Bit 2 Current without voltage L3 0 = I below threshold 1 = I above threshold
Bit 3-7 not used
03-11, 37 – Investment protection through flexible modularity
The Landis+Gyr E650 Family General Meter Functions Real Time Clock
+ Accuracy < 5ppm ( < 0,5sec/Tag) + Synchronization / Setting by - By control input or integrated RCR*
(to the Minute, Integration-Period or Day) - With Set Commands via Communication - Manually in Set-Mode with the Push-Buttons * Not applicable for Series 3
+ Summer-/winter time to: - European Standard - Free parameterised Start and End
+ Backup time: - Standard with Super cap approx. 21 days
(after continuous supply during 300 hours)
- With optional Battery approx. 10 years (ENERGIZER Lithium EL 223AP • 6 V)
03-11, 38 – Investment protection through flexible modularity
The Landis+Gyr E650 Family General Meter Functions Time Of Use, Activity Calendar
2 Time Of Use Tables (TOU) available: - Each table with up to 12 seasons - Table 1 is active - Table 2 can be pre-programmed to be activated at a defined Date
1 Exception day table with 100 entries 1 Emergency Table (if Time/Date is invalid)
2 Sets of 12 Day Tables (for each TOU) Each Day Table with 12 Switching Times Each Switching-Time with 16 Control-Signals
03-11, 39 – Investment protection through flexible modularity
The Landis+Gyr E650 Family General Meter Functions Meter Identification Numbers
+ IEC Identification Number + Physical IEC Device Address + Dlms Device Identification + Physical HDLC Device Address + General Identification Numbers - Identification Number 1 (4 x 8 ASCII) - Identification Number 2 (2 x 8 ASCII)
+ Special Identification Numbers: - Parameterisation ID - Connection ID - Display List ID - TOU 1 & 2 ID - RCR ID*
03-11, 40 – Investment protection through flexible modularity
* is available only with Series 2
The Landis+Gyr E650 Family - Visual Meter Interface Overview of Interface Objects
1) Test LED Reactive 2) Test LED Active 3) Optical Port 4) Push-Button „Up“ 5) Push-Button „Down“ 6) Reset-Button 7) Lower Face-Plate 8) Upper Face-Plate 9) Alert LED (optional)
1 2 3
4 5
6
7
8
03-11, 41 – Investment protection through flexible modularity
9
The Landis+Gyr E650 Family - Visual Meter Interface Liquid Crystal Display Elements
1) Energy-Direction, +P: Active Import; -P: Active Export; Q Reactive 2) Phase Voltage Presence, blinking for incorrect Phase-Sequence 3) Battery, blinking if Battery Voltage is to low 4) Field to indicate the Units of the Value 5) Field of 8 Digits for the Values 6) Field of 8 Digits for the OBIS Identification Code 7) 12 Arrows for status indication (e.g. active Rate)
3 1 2 4
5 6
7
03-11, 42 – Investment protection through flexible modularity
-
8
The Landis+Gyr E650 Family - Visual Meter Interface OBIS: Identification System (IEC62056-61)
A BB CC DD EE FF - : . . .
l A Medium ð 1 Electricity ð .... ð 7 Gas ð 8 Cold Water
l B Channel ð 1 Ch 1 ð 2 Ch 2 ð .... ð 64 Ch 64
l C Physical Quantity ð 1 Active Power + ð 2 Active Power - ð .... ð 21 L1 Active Power +
l D Processing Type ð 2 P max Cumulated ð 4 Current Average P max ð 6 Last Average P max ð 8 Energy Integral 1
l E Rate / Tariff ð 1 Rate 1 ð 2 Rate 2 ð .... ð 63 Rate 63
l F Stored Value ð 1 St-V 1 ð 2 St-V 2 ð .... ð 99 St-V 99
03-11, 43 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Visual Meter Interface Display of Data
1) OBIS Identification Code 2) Value 3) Units of the Value
1 2
3
+ Menu Controlled + Free definable Lists (up to 200 items) - Operating display (Scroll-mode) - Data List (for Meter Reading) - Service List (for Installation-Check) - Setting List (for Service)
+ Display of Load Profile Data
03-11, 44 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Visual Meter Interface Installation Check Function
Voltage Phase Display L1 L2 L3 Phase Sequence (L1, L2, L3 blinking of wrong) Active Quadrant of Energy Flow
+ If single Phase is reverse -> blinking Arrow Instantaneous Values for
+ Phase Voltage and Current + Total Active- and Reactive-Power + Phase Angle + Power Factor (per Phase and Total)
Battery Voltage Low
03-11, 45 – Investment protection through flexible modularity
The Landis+Gyr E650 Family - Visual Meter Interface Special Display Features and alert indication
Advanced Operation with Up and Down Keys + Up- and Down scrolling + Long Key-Stroke -> Jump over Stored Values + Press both keys simultaneously -> one level up
Reading of LCD without voltage connected + With the battery (optional) it is possible to
activated the LCD without voltage connected + The optional backlight of the LCD works only
when voltage is connected.
Scroll Operations also possible with Torch-Light + The scroll function of the LCD can also be
operated by blinking with a Torch-Light (incandescent light) on the optical interface.
03-11, 46 – Investment protection through flexible modularity
Alert LED + With the optional alert LED it is possible to make
visible any alert occurrence.
The Landis+Gyr E650 Family - Visual Meter Interface Test Mode
Register
Display test mode
Display normal mode
,
+ Fast Register Testing with higher Resolution in Test Mode (up to 5 decimals in test mode)
+ Test with one Scanning Head by switching var impulses to middle LED
+ Fast No-Load detection and indication in 10 Seconds
03-11, 47 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Communication Interfaces Optical Interface
+ Physical Characteristic according to IEC62056-21 (former IEC61107) + Initial Baud-Rate always 300 bps + Initial Protocol always „IEC1107“ + Change to „dlms“ at initialisation possible + Maximum Baud-Rate 9600 bps
03-11, 48 – Investment protection through flexible modularity
-
9
The Landis+Gyr E650 Family Communication Interfaces Integrated Communication Interfaces
These Interfaces are available for:
ZMD310AR, ZMD310CR ZxD400AR, ZxD400CR
l Initial Baud-Rate 300 to 9600 bps l Initial Protocol auto-detected l Data Baud-Rate 2400 to 9600 bps
RS232: c1 • simple 3-wire Interface • 1 x RJ12 Plug
RS485: c2 • simple 3-wire Interface • 2 x RJ12 Plug
CS: c3 • simple 2-wire Interface • 2 x “WAGO”
or
or
RS422: c6 • simple 4-wire interface • 2 x RJ12Plug
or
03-11, 49 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Communication Interfaces Modular Communication with CU-xx
Meter modularity: „Plug + Play“ This meets your needs for today while leaving you a free hand for tomorrow. You decide when to equip your meters with what technology to give them the communication capabilities you and your customer need.
These Communication Units are available for: ZMD300AT, ZMD300CT, ZxD400AT, ZxD400CT
03-11, 50 – Investment protection through flexible modularity
Communication Units The right technology at the right time. The right investment at the right time.
The Landis+Gyr E650 Family Communication Interfaces CU-xx Modules: different Channels + Modules with two independent Communication Channels are available - Multidrop-Master: RS485-Master/Slave and PSTN/GSM/GPRS/RS232/
Ethernet - To serve two different user-groups with an own physical access
+ Different Interfaces available: - CS (20mA) - RS232 - RS485 - M-Bus - PSTN - GSM - GPRS - Ethernet - Others in development
+ Initial Protocol auto-detected + Baud-Rate depending to Interface
03-11, 51 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Communication Interfaces CU-B1: S0 pulse inputs for other meters
passive
passive
+ The S0-Interfaces of the Module are active - If meter is not powered, no pulses are registered
+ CU-B1 Module Functions - Location of 2 active S0-Inputs - RS232 and RS485
+ E650-Meter Functions - 2 Total Registers - Value Scaling of Impulses - Total Registers in Load-Profile
+ Selection of possible Media - Electricity - Water - Gas - Heat
03-11, 52 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Communication Interfaces dlms™, the three most important features
dlms™-Meter
Standardised Objects
Register
Profile
Time Table
Content
Clock
Communication Medium x Communication Medium x Communication Medium x Communication Medium x
Modem x Modem x Modem x Modem x
Interface
Interoperability trough
+ Manufacturer Independency
+ Channel Independency
+ Safety and Sufficiency
IEC-Standards for + Interface Objects
IEC62056-62 + Identification System
IEC62056-61 + Application Layer
IEC62056-53 + Data Link Layer
IEC62056-46 + Physical Layers
IEC62056-42 + 3rd edition IEC1107
IEC62056-21 www.dlms.com
03-11, 53 – Investment protection through flexible modularity
The Landis+Gyr E650 Family Communication Interfaces Security System overview
Dat
a G
rou
p 1
D
ata
Gro
up
2
Dat
a G
rou
p 3
to
D
ata
Gro
up
N
Par
amet
er G
rou
p 1
P
aram
eter
Gro
up
2
Par
amet
er G
rou
p 3
to
P
aram
eter
Gro
up
N
Co
nfi
gu
rati
on
Level 0 Level 1 Level 2 Level 3 Level 4 Level 5
to Level 14
Level 6
Security Level
Factory Level
Access according to
former IEC61107
Access under special
conditions
Access control is achieved by the following means + un-coded
Password 1 + coded + Password 2 + Reset-Key (utility-
seal) + Para-Switch
(Certification-seal)
+ selected interface
03-11, 54 – Investment protection through flexible modularity
-
10
The Landis+Gyr E650 Family Tools for Meter Maintenance
MAP120, Parameter Editor + Device configuration and parameterisation
03-11, 55 – Investment protection through flexible modularity
MAP110, Service Tool + Installation, readout and maintenance
MAP100, Download Tool + Mass parameterisation
MAP105, dlms Monitor + Generic dlms monitor for debugging purposes
Field para-meteri sation
Configuration Test + verification Installation Readout
Maintenance
Manufacturer Utility Central Services Utility Local Services
MAP110 MAP100 MAP120
MAP105
03-11, 56 – Investment protection through flexible modularity