1 + Landis+Gyr E650 INVESTMENT PROTECTION THROUGH FLEXIBLE MODULARITY 03-11, 1 – Investment protection through flexible modularity The Landis+Gyr E650 Family - Overview Customer Segments Grid Large industrial customers Industrial customers Commercial customers Residential customers Active Meter-AT/AR - Direct connected - Transformer connected Combi Meter-CT/CR - Direct connected - Transformer connected 03-11, 2 – Investment protection through flexible modularity Basic Configurations xxxxxxxR44.0457.c1 S3(a) Application Range High voltage Medium voltage Low voltage Connection Type Transf. connection Direct connection Measuring Accuracy Class 0.2/0.5 Class 0.5 (C)/1.0 Energy Type Active energy Reactive energy Apparent energy COMBI ACTIVE active energy (MID) / reactive energy ZMD310A ZMD410A ZFD410A ZMD310C ZMD410C ZMD405C ZMD402C ZFD410C ZFD405C ZFD402C Class 1.0 (B)/1.0 03-11, 3 – Investment protection through flexible modularity ZMD405A ZFD405A ZMD402A ZFD402A The Landis+Gyr E650 Family - Overview 03-11, 4 – Investment protection through flexible modularity The Landis+Gyr E650 Family - Overview Voltage and Current Ranges ZFD410... ZMD402... ZMD405... ZMD310... 3x220V 3x100V 3x230/400V 3x127/220V 3x58/100V ZMD410... 5 (120)A 5 (10)A 1 (10)A 1 (2)A 2 (4)A Wide voltage ZFD402... ZFD405... ZxDxxxCT44.0457 S3(a) 5 (20)A New in B31 0.3(1.2)A Modular or Simple ZMD310CR/AR ZFD4xxCR/AR ZMD4xxCR/AR ZMD310CT/AT ZFD4xxCT/AT ZMD4xxCT/AT integrated interface exchangeable modules ( type T ) ( type R ) ZxDxxxXR44.2407.c2 S3(a) 03-11, 5 – Investment protection through flexible modularity Note: xx can be 10 / 05 / 02 The Landis+Gyr E650 Family - Overview ZxDxxxXT44.2407 S3(a) Tariff Functions Tariff Type Energy only Energy and Demand Time of Use Without Time of Use With Time of Use 44 41 24 21 ZMD405CRxx.0457.c1 S3 03-11, 6 – Investment protection through flexible modularity The Landis+Gyr E650 Family - Overview

Upload: others

Post on 08-Feb-2021

4 views

Category:

Documents


0 download

TRANSCRIPT

  • 1

    + Landis+Gyr E650 INVESTMENT PROTECTION THROUGH FLEXIBLE MODULARITY

    03-11, 1 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    Customer Segments

    Grid

    Large industrial customers

    Industrial customers

    Commercial customers

    Residential customers

    Activ

    e Mete

    r-AT/A

    R

    - D

    irect co

    nnecte

    d

    - Tr

    ansfor

    mer co

    nnecte

    d Co

    mbi M

    eter-C

    T/CR

    - D

    irect co

    nnecte

    d

    - Tr

    ansfor

    mer co

    nnecte

    d

    03-11, 2 – Investment protection through flexible modularity

    Basic Configurations xxxxxxxR44.0457.c1 S3(a)

    Application Range High voltage Medium voltage Low voltage

    Connection Type Transf. connection Direct connection

    Measuring Accuracy Class 0.2/0.5 Class 0.5 (C)/1.0

    Energy Type Active energy Reactive energy Apparent energy

    COMBI ACTIVE

    active energy (MID) / reactive energy

    ZMD

    310A

    ZMD

    410A

    ZF

    D41

    0A

    ZMD

    310C

    ZM

    D41

    0C

    ZMD

    405C

    ZM

    D40

    2C

    ZFD

    410C

    ZF

    D40

    5C

    ZFD

    402C

    Class 1.0 (B)/1.0

    03-11, 3 – Investment protection through flexible modularity

    ZMD

    405A

    ZF

    D40

    5A

    ZMD

    402A

    ZF

    D40

    2A

    The Landis+Gyr E650 Family - Overview

    03-11, 4 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    Voltage and Current Ranges

    ZFD410...

    ZMD402...

    ZMD405...

    ZMD310...

    3x22

    0V

    3x10

    0V

    3x23

    0/40

    0V

    3x12

    7/22

    0V

    3x58

    /100

    V

    ZMD410...

    5 (1

    20)A

    5 (1

    0)A

    1 (1

    0)A

    1 (2

    )A

    2 (4

    )A

    Wid

    e vo

    ltage

    ZFD402...

    ZFD405...

    ZxDxxxCT44.0457 S3(a)

    5 (2

    0)A

    New in B31

    0.3(

    1.2)

    A

    Modular or Simple

    ZMD310CR/AR ZFD4xxCR/AR ZMD4xxCR/AR

    ZMD310CT/AT ZFD4xxCT/AT ZMD4xxCT/AT

    integrated interface exchangeable modules ( type T ) ( type R )

    ZxDxxxXR44.2407.c2 S3(a)

    03-11, 5 – Investment protection through flexible modularity

    Note: xx can be 10 / 05 / 02

    The Landis+Gyr E650 Family - Overview

    ZxDxxxXT44.2407 S3(a) Tariff Functions

    Tariff Type Energy only Energy and Demand

    Time of Use Without Time of Use With Time of Use

    44

    41

    24

    21

    ZMD405CRxx.0457.c1 S3

    03-11, 6 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

  • 2

    Additional Functionality (1)

    Control Inputs 2 additional inputs 4 additional inputs

    2 additional outputs Output Contacts 4 additional outputs 6 additional outputs

    Integrated Ripple Control Receiver

    Additional Power Supply (100…240VDC/AC)

    The following In- and Outputs are standard in the Basic E650: •  3 control inputs •  2 output contacts

    ZMD310CR44.xxx7.c1 S3a

    0457

    04

    37

    0037

    42

    07

    2407

    06

    07

    0467

    Additional Power Supply (12…24VDC)

    03-11, 7 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    not applicable for Series 3

    X

    X

    DC magnet detection is supported by the following meter types: +  ZMD310xT +  ZxD410xT +  ZxD405xT +  ZxD402xT Series 2: The meter supports either the DC magnet detection or the terminal cover detection but not both at the same time. Series 3: The meter supports both the DC magnet and terminal cover detection at the same time.

    Additional Functionality (2)

    ZMD405CR44.045x.c1 S3

    Load Profile disabled enabled

    DC magnet detection

    disabled enabled

    9 7 2 0

    03-11, 8 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    Communication

    ZMD405CR44.0257.xx S3 ZMD405CT44.0257.xx S3

    RS232 Interface CS Interface

    2 Pulse Inputs S0

    A4

    c3

    c2

    c1

    M-Bus Interface

    D2

    PSTN Modem *

    GSM/GPRS Modem

    G32

    G

    31

    G30

    P3

    2

    E22

    B4

    B2

    B1 A5

    Integrated Interfaces (Meter-Type R)

    Interchangeable Interface (Meter-Type T)

    * /V22b, V34b

    RS422 Interface

    GSM Modem

    Ethernet Interface

    Interchangeable Modems (Meter-Type T)

    P30

    RS485 Interface

    c6

    E20

    M22

    M

    20

    03-11, 9 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    Symmetrical connection

    +  Is available in all transformer connected meter versions of the ZMD400. +  The type designation is extended with a small “s” to indicate the

    symmetrical connection.

    I1 I1U1 I2 U2 I2I3 U3 I3N

    1 2 3 4 5 6 7 8 9 11

    ZMD410CT44.0457 S3s

    03-11, 10 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    Type Designation

    Connection ZFD 3-phase, 3-wire Diagram ZMD 3-phase, 4-wire Connection 3 Direct, digital measuring Type 4 Transformer, digital measuring Accuracy 10 Class 1.0 to IEC

    05 Class 0.5 to IEC 02 Class 0.2 to IEC

    Energy C Active, Reactive and Apparent Type A Active Model T modular Communication

    R integrated Interface Tariff 21 Energy only, no TOU Functions 24 Energy only, with TOU

    41 Energy and Demand, no TOU 44 Energy and Demand, with TOU

    Additional additional inputs on extension board Functions* additional outputs on extension board

    5/6 integrated additional Power Supply 2/7 DC magnet detection / Load Profile Memory

    Series 3

    ZMD x 10 C T 44 . 2 4 0 7 S3(a)

    03-11, 11 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

    * Integrated ripple control receiver is available with Series 2

    +  Terminal cover detection + With the ZMD310 and ZxD400 meter a accessory kit is available to detect

    the terminal cover removal.

    +  The state changes of the switch can be registered in to the event log over a control input.

    Note: Series 2: The meter supports either the DC magnet detection or the terminal cover detection but not both at the same time. Series 3: The meter supports both the DC magnet and terminal cover detection at the same time.

    03-11, 12 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Overview

  • 3

    The Landis+Gyr E650 Family - Measuring System Measured Quantities

    +Q

    +P-P

    -Q

    44 Measuring quantities based on power: +  Active energy / power +  Reactive energy / power +  Apparent energy / power +  Power factor +  for each direction or quadrant +  for each phase or total

    16 additional measuring quantities as instantaneous values: + 

    +  Voltage (per phase) +  Current (per phase and neutral) +  Active- and Reactive Power (Sum) +  Phase angles (U-U and U-I) +  Frequency

    03-11, 13 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Measuring System Block-Diagram of E650-Meter

    Ut

    U1 U2 U3 N

    I1 I2 I3

    Control Inputs

    Measurement System

    Power supply

    Voltage Supervision

    Memory Load-Profile

    Microprocessor

    Signal processing

    Signal Utilization

    Tariff

    Control

    Data for

    Billing

    Time Switch

    Display Keys

    Calendar Clock

    Reset

    A/D Calibra- tion

    Extension Board Inputs Outputs Add. PS

    A/D

    Communication Unit with

    Impulse-Inputs

    LCD-Display

    Optical Interface

    Test Diodes

    Output Contacts

    Interface Board

    03-11, 14 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Measuring System Block-Diagram of Digital Signal Processor

    Digital Values

    Ix Analogue

    Input Signals

    A/D Converter

    Ix i

    Ux

    u

    u, i: calibrated instantaneous values for voltage and current

    Px

    p: instantaneous active power q: instantaneous reactive power u*: voltage displaced by 90° tn: zero passage time

    Qx

    ϕ u-i

    fn

    tn

    Ux

    Digital Filter

    Calibra- tion i

    A/D Converter

    Digital Filter

    Calibra- tion u

    ϕ u

    2i

    2u

    iuq * ×=

    iup ×=

    03-11, 15 – Investment protection through flexible modularity

    THD

    Form

    atio

    n of

    mea

    n va

    lues

    per

    sec

    ond

    THD

    The Landis+Gyr E650 Family - Energy and Demand Registers Measured Quantities Selection

    6 x ±Ax

    6 x ±Rx

    6 x ±Rix

    6 x ±Rcx

    6 x ±VAx

    2 x ±AΣ

    2 x ±RΣ

    2 x ±RiΣ

    2 x ±RcΣ

    2 x ±VAΣ

    Sele

    ctio

    n of

    max

    imal

    8 q

    uant

    ities

    Ext. Impulses 1, 2

    Summation 1,2

    ME 1

    ME 2

    ME 7

    ME 8

    ME 19

    ME 27

    ME 9, 10

    ME 11, 12

    Total Energy

    Total Energy

    Total Energy

    Total Energy

    Total Energy

    Total Energy

    Total Energy

    Current Average

    Current Average

    Current Average

    Current Average

    Last Average

    Last Average

    Last Average

    Last Average

    03-11, 16 – Investment protection through flexible modularity

    +THD, -THD

    OLA, NLA, I2, U2 ME 13, 14 ME 15-18

    Total Energy

    Total Energy

    … … …

    New from B31

    Maximum 24 Cum. Maximum 24 Energy Rate 32

    The Landis+Gyr E650 Family - Energy and Demand Registers Energy and Demand Rate Registers

    Sele

    ctio

    n of

    Mea

    sure

    d Q

    uant

    ities

    ME 1

    ME 7

    ME 8

    ME 19

    ME 27

    Maximum 2 Cum. Maximum 2 Energy Rate 2

    Maximum 1 Cum. Maximum 1 …

    SP

    PF = PF Average over Billing Period PF Minimum 2

    PF Minimum 1

    03-11, 17 – Investment protection through flexible modularity

    Energy Rate 1

    ME 1-8, 19-27 ME 1-8 ME 1-8

    New from B31

    The Landis+Gyr E650 Family - Energy and Demand Registers Special Energy Registers

    All Energy Rate Registers can be defined in three different modes:

    Available for:

    Cumulative Value

    Billing Period Delta Value

    Integration Period Delta Value

    Billing Period

    Yes

    Yes

    No

    Load Profile 1, 2

    Yes

    No

    Yes

    03-11, 18 – Investment protection through flexible modularity

  • 4

    The Landis+Gyr E650 Family - Energy and Demand Registers Sliding (Rolling) Demand

    The Integration Period for the Demand Registers can be divided into Sub-Intervals. This Function is called Sliding Demand or Rolling Demand.

    Integration Period

    1 2 3 5 10 15 20 30 60

    1 1 2 3 5 10 15 20 30 60

    2 - 1 - - 5 -

    10 15 30

    3 - - 1 - - 5 -

    10 20

    4 - - - - - - 5 -

    15

    5 - - - 1 2 3 4 6 12

    6 - - - - - - - 5 10

    10 - - - - 1 - 2 3 6

    12 - - - - - - - - 5

    15 - - - - - 1 - 2 4

    Number of Sub-Intervals

    Duration of Sub-Intervals in Minutes In Minutes

    03-11, 19 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Energy and Demand Registers Stored Values (Billing Periods) Stored Values are Captured at the Event of a Billing Period Reset:

    •  Control Inputs (KA / KB) •  Integrated RCR* •  Reset Button •  Communication

    Billing Periods can be stored by the following Controls:

    •  Internal Real Time Clock (at full hours) - weekly (any day) - monthly at up to 6 days - at daylight saving begin and end

    •  *Maximum Demand Registers •  *Minimum Power Factor Registers •  *Billing Period Average Power Factor

    The following Registers can be Captured at the Billing Period Reset:

    •  Energy Total Registers •  Energy Rate Registers - Cumulating Value Registers - *Billing Period Delta Value Registers

    * : These Registers are reset at Billing Period Reset

    03-11, 20 – Investment protection through flexible modularity

    * : not applicable to Series 3

    The Landis+Gyr E650 Family 2nd Demand Period with B31

    +  One customer in NL requires the possibility to define Pmax with 15min and demand values captured in the load profile with a period of 5min.

    +  For this purpose we introduce a new parameter in the sliding demand in order to enable the new feature. In this case the Pmax is captured with the integration period and the demand values are captured in the LP with the subinterval period.

    +  Using this function with two LP‘s it is possible to define 3 different periods, the integration period for the maximum demand, the subinterval capture period for one LP and an independent capture period for the 2nd LP.

    New in B31

    03-11, 21 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Summation function with B31 +  Summation is a very common function for meter points where the billing is

    based on the total maximum of more than just one meter.

    +  ZMD300/400 Series 3 supports now up to 2 summation channels SUM1 and SUM2

    ME1

    EX1

    EX2

    MExx+ Total energy register

    Demand, max. demandstored valuespulse outputs

    displayreadout

    load profile(s)

    03-11, 22 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Losses in ZMD400 Series 3 with B31

    +  We support now the calculation of Losses: §  OLA, On load active. Line (copper) losses of active

    energy. OLA = I2h x RCu. The value of RCu can be set by parameterisation

    §  NLA, No load active. Transformer (iron) losses of active energy. NLA = U2h / RFe. The value of RFe can be set by parameterisation.

    §  I2h (Cu), Ampere square hours (with RCu = 1 W) §  U2h (Fe), Voltage square hours (with RFe 1 MW)

    Generator

    Meter AProduction

    Load

    Meter B Customer

    Metering point A Metering point B Metering point C

    RCuRFe

    Transmission

    03-11, 23 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Total Harmonic distortion with B31 +  We support now the calculation of Total

    Harmonic Distortion (THD):

    +  Following values are available:

    +THDA+A +THD = +A - (+A )A fundamental

    -THDA-A -THD = -A - (-AA fundamental)

    THD of active energy import +THDA Sum Sum

    THD of active energy export -THDA Sum Sum

    THD of active energy (percent) THDA [%] Sum Sum

    THD of phase voltages (absolute) THDU Sum / Phases Sum

    THD of voltage (percent) THDU [%] Sum Sum

    THD of phase currents (absolute) THDI Sum / Phases Sum

    THD of current (percent) THDI [%] Sum Sum

    03-11, 24 – Investment protection through flexible modularity

  • 5

    The Landis+Gyr E650 Family - Load Profile Load Profile Capturing

    Profile Values are Captured in regular Intervals:

    The Capture Period is selected between the Demand Integration Period

    and the Demand Subinterval*.

    The Capture Period of the Profile is always synchronous to the full hour

    •  Last Average Demand •  Last Average Power Factor •  Energy Total Registers •  Energy Integration Period Registers

    The following Registers can be Captured into the Load Profile:

    •  Average Values (over Capture Period) - Voltages (all 3 Phases) - Currents (3 Phases and Neutral) - Mains Frequency

    * : With Subinterval as Capturing period, no Demand Values can be selected

    03-11, 25 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Load Profile Load Profile Data Format

    Identification / Header

    End

    Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry

    Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Date / Time / Status

    Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry

    Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Maximum 14 Values each Entry Date / Time / Status

    Definition of Profile including: •  Definition of Captured Values •  Length of Capture Period • Number of Entries

    Start of a new Day with: •  Date and Time •  Status (acc. VDEW)

    Captured Objects: •  1 to 14 Values

    The handling of the following Events must be parameterised: •  Supply Interruptions •  Demand Rate Switching •  Billing Period Reset

    03-11, 26 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Two Load profiles with B31 +  The capacity of the load profile has

    been increased (double) as well as the number of captured channels (from 14 to 26).

    +  The ZMD300/400 Series 3 supports now up to 2 load profiles, e.g. for billing and monitoring purposes.

    +  The two capture periods are independent.

    + One of the capture period is equal to the demand integration period.

    +  The instantaneous values can be captured in either in the load profile 1 or in the load profile 2, depending on parameterization.

    03-11, 27 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Load Profile Load Profile 1 and 2 Memory allocation

    03-11, 28 – Investment protection through flexible modularity

    Use Number of memory pages

    Default setting memory pages

    Event log 1 to max. 74 11 pages Stored values 1 to max. 78 17 pages Load profile 1 2390 to max. 7541 1) Load profile 2 50 2) to max. 5000 3500 pages

    In total a maximum of 7542 memory pages can be allocated as followed:

    1) The memory size available for the Load Profile 1 is the remaining memory which is not allocated for the stored values, event log or the 2nd load profile.

    2) Minimum numbers of memory pages for 2nd load profile (if activated).

    The Landis+Gyr E650 Family - Event Monitoring Monitors for Voltage and Current

    The following parameters are available: •  Threshold for Over-Voltage •  Threshold for Under-Voltage •  Activation Delay for Voltage Monitors •  Threshold for Phase Over-Current •  Threshold for Neutral Over-Current •  Activation Delay for Current Monitors (to filter out short Events)

    For each Phase individual Event-Counters store the number of Exceedings.

    The Events of every Phase can be used for Control

    purposes and stored in the Event Log-Book

    Vm Vt

    td

    td Vm: Monitored Value Vt: Threshold Value td: Activation Delay Alert: Alert Signal Alert

    03-11, 29 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Event Monitoring Monitors for Power and Power-Factor

    8 Demand Monitors with: - Selection of Measured Quantity - Current- or Last Average-Demand - Definition of Threshold and Tariff

    2 Power-Factor (PF) Monitors with: - Definition of Threshold and Tariff - Apparent Power Threshold for PF

    For each Monitor individual Event-Counters store the number of Exceedings.

    The Events of every Monitor can be used for Control

    purposes and stored in the Event Log-Book

    Vm Vt

    Vm: Monitored Value Vt: Threshold Value CA-Alert: Current-Average-Alert LA-Alert: Last-Average-Alert &

    Power-Factor-Alert

    CA-Alert

    LA-Alert

    03-11, 30 – Investment protection through flexible modularity

  • 6

    The Landis+Gyr E650 Family - Event Monitoring Monitors for other special Events

    Many other Internal Signals of State Information or Actions are available for the Event Log-Book. We list here some of the most used ones, please refer to the user manual for detailed information: •  Phase Fail per Phase, Total Power Down, •  Battery (voltage low, replaced, voltage ok), •  Time/Date invalid, Time/Date adjusted, •  Error in the data processing detected •  and many others

    For the Control of Outputs (like LCD-Display-Arrows or Output-Contacts) you can select the Alarm Signal for the invalid Time/Date and all Monitors for Demand, Power-Factor, Voltage and Current.

    03-11, 31 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Event Monitoring The Event Log-Book

    The Event Log-Book stores the Events in an a-periodic Memory according to the parameterisation. With full Memory new entries delete the oldest ones.

    Time / Day Stamp of the Event

    Status-Byte („VDEW“-standard)

    Event-Number (Landis+Gyr specific)

    Actual Information of Error-Bytes

    Optional the following fields can be captured: •  Event-State (Landis+Gyr specific) •  Energy Total Registers

    03-11, 32 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Event Monitoring Alert-Function

    Supervision of selected functions: •  Phase voltage •  Checksum errors •  Low battery voltage •  etc.

    These events will (if selected) set a special control signal The following actions can now be controlled: -  indication with an arrow on the LCD -  state of output contact -  Rate-Registers for Energy, Power, Power-Factor and Time

    These events will (if selected) initiate the emission of an SMS through a connected GSM modem

    03-11, 33 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Network Quality Events with B31 +  We have introduced 3 new network quality

    dedicated events:

    §  Under- and Overvoltage per phase - total number of the events - cumulated duration of the events - duration of the longest, with time stamp - duration of the shortest, with time stamp - 30 last events (with time stamp, duration, magnitude, phase)

    §  Phase fail - number of cuts - cumulated duration of cuts - duration of the longest, with time stamp - duration of the shortest, with time stamp - 30 last cuts (with time stamp, duration, magnitude, phase)

    +  The three events can be defined as previously in the event log or as the new dedicated event log.

    +  With the new dedicated event log it is possible to define a snapshot buffer.

    03-11, 34 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Additional features with B31

    +  Billing period reset §  With B31 it is possible to define one fixed day per

    month, e.g. 3 days before end of each month.

    +  Vectorial calculation of reactive energy §  With B31 it is possible to calculate reactive power Q

    using the values of active power and apparent power.

    §  This calculation method is limited to Class 2. §  Power factor calculation is not supported when this

    method is in use.

    §  This method includes the harmonics.

    03-11, 35 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Additional features with B31 +  Instantaneous power with sign §  If the meter is parameterized to calculate

    the instantaneous power as signed values: Active P: + in QI and QIV, - in QII and QIII Reactive P: + in QI and QII, - in QIII and QIV

    +  Auxiliary power loss detection §  The extension board type 045x and 046x feature an

    auxiliary power supply. When the auxiliary power is missing an event is triggered according to its parameterisation.

    §  According to its parameterization, the auxiliary power loss detection can trigger the Missing Additional Power supply event (58) and can be used to trigger an alert. The appearance of an alert can be indicated by an arrow on display or by the Alert LED.

    - Landis+Gyr - E650 Series 3

    Bit # Description State definition

    Bit 0 Missing additional power supply

    0 = Us present 1 = Us absent

    Bit 1-7 not used

    Status C.4.3

    03-11, 36 – Investment protection through flexible modularity

  • 7

    The Landis+Gyr E650 Family Additional features with B31 +  Current without voltage §  In some applications the voltage transformer is protected against short circuit by a fuse

    in the measurement circuit. In case the fuse blows up, this is detected and indicated.

    §  3 new events are defined to indicate current without voltage per phase (event nr 55, 56 and 57)

    §  The occurrence of the event is indicated in a status, C.4.2 Current without Voltage Status

    §  The event occurrence can be included in bit 24 of the status code of the load profile if it is enabled by parameterisation.

    Bit # Description State definition

    Bit 0 Current without voltage L1 0 = I below threshold 1 = I above threshold

    Bit 1 Current without voltage L2 0 = I below threshold 1 = I above threshold

    Bit 2 Current without voltage L3 0 = I below threshold 1 = I above threshold

    Bit 3-7 not used

    03-11, 37 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family General Meter Functions Real Time Clock

    +  Accuracy < 5ppm ( < 0,5sec/Tag) +  Synchronization / Setting by -  By control input or integrated RCR*

    (to the Minute, Integration-Period or Day) -  With Set Commands via Communication -  Manually in Set-Mode with the Push-Buttons * Not applicable for Series 3

    +  Summer-/winter time to: -  European Standard -  Free parameterised Start and End

    +  Backup time: -  Standard with Super cap approx. 21 days

    (after continuous supply during 300 hours)

    -  With optional Battery approx. 10 years (ENERGIZER Lithium EL 223AP • 6 V)

    03-11, 38 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family General Meter Functions Time Of Use, Activity Calendar

    2 Time Of Use Tables (TOU) available: - Each table with up to 12 seasons - Table 1 is active - Table 2 can be pre-programmed to be activated at a defined Date

    1 Exception day table with 100 entries 1 Emergency Table (if Time/Date is invalid)

    2 Sets of 12 Day Tables (for each TOU) Each Day Table with 12 Switching Times Each Switching-Time with 16 Control-Signals

    03-11, 39 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family General Meter Functions Meter Identification Numbers

    +  IEC Identification Number +  Physical IEC Device Address +  Dlms Device Identification +  Physical HDLC Device Address +  General Identification Numbers -  Identification Number 1 (4 x 8 ASCII) -  Identification Number 2 (2 x 8 ASCII)

    +  Special Identification Numbers: -  Parameterisation ID -  Connection ID -  Display List ID -  TOU 1 & 2 ID -  RCR ID*

    03-11, 40 – Investment protection through flexible modularity

    * is available only with Series 2

    The Landis+Gyr E650 Family - Visual Meter Interface Overview of Interface Objects

    1)  Test LED Reactive 2)  Test LED Active 3)  Optical Port 4)  Push-Button „Up“ 5)  Push-Button „Down“ 6)  Reset-Button 7)  Lower Face-Plate 8)  Upper Face-Plate 9)  Alert LED (optional)

    1 2 3

    4 5

    6

    7

    8

    03-11, 41 – Investment protection through flexible modularity

    9

    The Landis+Gyr E650 Family - Visual Meter Interface Liquid Crystal Display Elements

    1)  Energy-Direction, +P: Active Import; -P: Active Export; Q Reactive 2)  Phase Voltage Presence, blinking for incorrect Phase-Sequence 3)  Battery, blinking if Battery Voltage is to low 4)  Field to indicate the Units of the Value 5)  Field of 8 Digits for the Values 6)  Field of 8 Digits for the OBIS Identification Code 7)  12 Arrows for status indication (e.g. active Rate)

    3 1 2 4

    5 6

    7

    03-11, 42 – Investment protection through flexible modularity

  • 8

    The Landis+Gyr E650 Family - Visual Meter Interface OBIS: Identification System (IEC62056-61)

    A BB CC DD EE FF - : . . .

    l  A Medium ð  1 Electricity ð  .... ð  7 Gas ð  8 Cold Water

    l  B Channel ð  1 Ch 1 ð  2 Ch 2 ð  .... ð  64 Ch 64

    l  C Physical Quantity ð  1 Active Power + ð  2 Active Power - ð  .... ð  21 L1 Active Power +

    l  D Processing Type ð  2 P max Cumulated ð  4 Current Average P max ð  6 Last Average P max ð  8 Energy Integral 1

    l  E Rate / Tariff ð  1 Rate 1 ð  2 Rate 2 ð  .... ð  63 Rate 63

    l  F Stored Value ð  1 St-V 1 ð  2 St-V 2 ð  .... ð  99 St-V 99

    03-11, 43 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Visual Meter Interface Display of Data

    1)  OBIS Identification Code 2)  Value 3)  Units of the Value

    1 2

    3

    +  Menu Controlled +  Free definable Lists (up to 200 items) -  Operating display (Scroll-mode) -  Data List (for Meter Reading) -  Service List (for Installation-Check) -  Setting List (for Service)

    +  Display of Load Profile Data

    03-11, 44 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Visual Meter Interface Installation Check Function

    Voltage Phase Display L1 L2 L3 Phase Sequence (L1, L2, L3 blinking of wrong) Active Quadrant of Energy Flow

    +  If single Phase is reverse -> blinking Arrow Instantaneous Values for

    +  Phase Voltage and Current +  Total Active- and Reactive-Power +  Phase Angle +  Power Factor (per Phase and Total)

    Battery Voltage Low

    03-11, 45 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family - Visual Meter Interface Special Display Features and alert indication

    Advanced Operation with Up and Down Keys +  Up- and Down scrolling +  Long Key-Stroke -> Jump over Stored Values +  Press both keys simultaneously -> one level up

    Reading of LCD without voltage connected +  With the battery (optional) it is possible to

    activated the LCD without voltage connected +  The optional backlight of the LCD works only

    when voltage is connected.

    Scroll Operations also possible with Torch-Light +  The scroll function of the LCD can also be

    operated by blinking with a Torch-Light (incandescent light) on the optical interface.

    03-11, 46 – Investment protection through flexible modularity

    Alert LED +  With the optional alert LED it is possible to make

    visible any alert occurrence.

    The Landis+Gyr E650 Family - Visual Meter Interface Test Mode

    Register

    Display test mode

    Display normal mode

    ,

    +  Fast Register Testing with higher Resolution in Test Mode (up to 5 decimals in test mode)

    +  Test with one Scanning Head by switching var impulses to middle LED

    +  Fast No-Load detection and indication in 10 Seconds

    03-11, 47 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Communication Interfaces Optical Interface

    +  Physical Characteristic according to IEC62056-21 (former IEC61107) +  Initial Baud-Rate always 300 bps +  Initial Protocol always „IEC1107“ +  Change to „dlms“ at initialisation possible +  Maximum Baud-Rate 9600 bps

    03-11, 48 – Investment protection through flexible modularity

  • 9

    The Landis+Gyr E650 Family Communication Interfaces Integrated Communication Interfaces

    These Interfaces are available for:

    ZMD310AR, ZMD310CR ZxD400AR, ZxD400CR

    l  Initial Baud-Rate 300 to 9600 bps l  Initial Protocol auto-detected l  Data Baud-Rate 2400 to 9600 bps

    RS232: c1 •  simple 3-wire Interface •  1 x RJ12 Plug

    RS485: c2 •  simple 3-wire Interface •  2 x RJ12 Plug

    CS: c3 •  simple 2-wire Interface •  2 x “WAGO”

    or

    or

    RS422: c6 •  simple 4-wire interface •  2 x RJ12Plug

    or

    03-11, 49 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Communication Interfaces Modular Communication with CU-xx

    Meter modularity: „Plug + Play“ This meets your needs for today while leaving you a free hand for tomorrow. You decide when to equip your meters with what technology to give them the communication capabilities you and your customer need.

    These Communication Units are available for: ZMD300AT, ZMD300CT, ZxD400AT, ZxD400CT

    03-11, 50 – Investment protection through flexible modularity

    Communication Units The right technology at the right time. The right investment at the right time.

    The Landis+Gyr E650 Family Communication Interfaces CU-xx Modules: different Channels +  Modules with two independent Communication Channels are available -  Multidrop-Master: RS485-Master/Slave and PSTN/GSM/GPRS/RS232/

    Ethernet -  To serve two different user-groups with an own physical access

    +  Different Interfaces available: -  CS (20mA) -  RS232 -  RS485 -  M-Bus -  PSTN -  GSM -  GPRS -  Ethernet -  Others in development

    +  Initial Protocol auto-detected +  Baud-Rate depending to Interface

    03-11, 51 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Communication Interfaces CU-B1: S0 pulse inputs for other meters

    passive

    passive

    +  The S0-Interfaces of the Module are active -  If meter is not powered, no pulses are registered

    +  CU-B1 Module Functions -  Location of 2 active S0-Inputs -  RS232 and RS485

    +  E650-Meter Functions -  2 Total Registers -  Value Scaling of Impulses -  Total Registers in Load-Profile

    +  Selection of possible Media -  Electricity -  Water -  Gas -  Heat

    03-11, 52 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Communication Interfaces dlms™, the three most important features

    dlms™-Meter

    Standardised Objects

    Register

    Profile

    Time Table

    Content

    Clock

    Communication Medium x Communication Medium x Communication Medium x Communication Medium x

    Modem x Modem x Modem x Modem x

    Interface

    Interoperability trough

    +  Manufacturer Independency

    +  Channel Independency

    +  Safety and Sufficiency

    IEC-Standards for +  Interface Objects

    IEC62056-62 +  Identification System

    IEC62056-61 +  Application Layer

    IEC62056-53 +  Data Link Layer

    IEC62056-46 +  Physical Layers

    IEC62056-42 +  3rd edition IEC1107

    IEC62056-21 www.dlms.com

    03-11, 53 – Investment protection through flexible modularity

    The Landis+Gyr E650 Family Communication Interfaces Security System overview

    Dat

    a G

    rou

    p 1

    D

    ata

    Gro

    up

    2

    Dat

    a G

    rou

    p 3

    to

    D

    ata

    Gro

    up

    N

    Par

    amet

    er G

    rou

    p 1

    P

    aram

    eter

    Gro

    up

    2

    Par

    amet

    er G

    rou

    p 3

    to

    P

    aram

    eter

    Gro

    up

    N

    Co

    nfi

    gu

    rati

    on

    Level 0 Level 1 Level 2 Level 3 Level 4 Level 5

    to Level 14

    Level 6

    Security Level

    Factory Level

    Access according to

    former IEC61107

    Access under special

    conditions

    Access control is achieved by the following means +  un-coded

    Password 1 +  coded +  Password 2 +  Reset-Key (utility-

    seal) +  Para-Switch

    (Certification-seal)

    +  selected interface

    03-11, 54 – Investment protection through flexible modularity

  • 10

    The Landis+Gyr E650 Family Tools for Meter Maintenance

    MAP120, Parameter Editor +  Device configuration and parameterisation

    03-11, 55 – Investment protection through flexible modularity

    MAP110, Service Tool +  Installation, readout and maintenance

    MAP100, Download Tool +  Mass parameterisation

    MAP105, dlms Monitor +  Generic dlms monitor for debugging purposes

    Field para-meteri sation

    Configuration Test + verification Installation Readout

    Maintenance

    Manufacturer Utility Central Services Utility Local Services

    MAP110 MAP100 MAP120

    MAP105

    03-11, 56 – Investment protection through flexible modularity