rack-mounted emergency pa system · 2.3. remote control unit numbers/zone numbers vs. fuse capacity...

44
INSTALLATION MANUAL APPLIED INSTALLATION RACK-MOUNTED EMERGENCY PA SYSTEM FS-971 SERIES MODEL NUMBERS : FS-971

Upload: others

Post on 05-Jan-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

INSTALLATION MANUALAPPLIED INSTALLATION

RACK-MOUNTED EMERGENCY PA SYSTEM

FS-971 SERIES MODEL NUMBERS : FS-971

Page 2: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

2

TABLE OF CONTENTS

1. SUPPLIED MANUALS ........................................................................................................... 4

2. CONNECTIONS OF INTEGRATED REMOTE CONTROL UNIT RM-971 2.1. Connection Method ................................................................................................................. 5

2.2. Notes on Connections

2.2.1. Maximum line resistance ............................................................................................... 5

2.2.2. Connections of multiple remote control units ................................................................ 6

2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity .......................................... 7

2.4. Connections of Multiple Remote Control Units ........................................................................ 8

3. CONNECTION OF REMOTE MICROPHONE RM-1200 3.1. Notes on Connections ............................................................................................................. 9

3.2. Connections .......................................................................................................................... 10

3.3. Connection of the RM-1200's Push-in Terminal Block .......................................................... 11

4. CONNECTION OF REMOTE MICROPHONE RM-1100 (AUX CONTROL TERMINAL)4.1. Notes on Connections ........................................................................................................... 12

4.2. Connections .......................................................................................................................... 12

4.3. Priority Setting When Multiple RM-1100s Are Connected

4.3.1. Priority setting .............................................................................................................. 13

4.3.2. When not setting the priority order .............................................................................. 13

5. GENERAL BROADCAST AND ATTENUATOR-FREE BROADCAST DURING POWER FAILURE5.1. How to Make "Power-Failure" General Broadcast and Attenuator-Free Broadcast .............. 14

5.2. Terminals for Power-Failure General Broadcast and Attenuator-Free Broadcast

5.2.1. Power-failure control input ........................................................................................... 14

5.2.2. Attenuator-free control input ........................................................................................ 14

5.3. Connections .......................................................................................................................... 15

6. CONNECTIONS WHEN MULTIPLE EQUIPMENT RACKS ARE INSTALLED SIDE BY SIDE 6.1. Expansion Control Panel Connections .................................................................................. 17

6.2. Expansion Junction Panel Connections ................................................................................ 17

6.3. Expansion Junction Panel Connection when Expanding the DC Power Supply Panel ......... 18

6.4. Specifications of Each Cable Set .......................................................................................... 19

Page 3: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

3

7. ABOUT THE MULTI-ORIGINATION MATRIX SYSTEM ............................................... 20

7.1. How to Divide the Speaker Lines of the Junction Panel ........................................................ 21

7.2. Input Matrix Panel Connections

7.2.1. Possible input and output combinations ...................................................................... 23

7.2.2. Address and audio input/output numbers .................................................................... 24

7.3. IM-011 Address Setting ......................................................................................................... 25

7.4. Front-Mounted Switch Setting and Volume Control Adjustment ........................................... 25

7.5. Connections .......................................................................................................................... 26

7.6. IM-011 Connections

7.6.1. Rear view diagrams and block diagrams .................................................................... 27

7.6.2. Single IM-011 unit: 4-input/4-output configuration ....................................................... 28

7.6.3. Input expansion: 8-input/4-output configuration .......................................................... 28

7.6.4. Output expansion: 4-input/8-output configuration ....................................................... 29

7.6.5. Input/output expansion: 16-input/8-output configuration ............................................. 30

7.6.6. Input/output expansion: 8-input/16-output configuration ............................................. 31

7.6.7. Notes on input level settings when increasing the output ........................................... 32

8. ABOUT THE EP-0510'S STATUS OUTPUTS ............................................................... 34

9. APPENDIX ............................................................................................................................... 35

Page 4: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

4

1. SUPPLIED MANUALS

The following manuals are supplied with the emergency PA system.

Read only the manuals that are suited for your purpose.

Installation manual(Basic installation)

· Installation

· The basics of installationand its inspection

The book you are reading now

The book you are reading now

Emergency PA System FS-971 Series Instruction Manual

Emergency PA System FS-971 Series Installation Manual - Basic Installation

Emergency PA System FS-971 Series Installation Manual - Applied Installation

Emergency PA System FS-971 Series Installation Manual - Writing

Installation manual(Writing)

· Initialization

· Registration setting

· Setting registration chart

· Associated equipmentconnections

· Reference items

Installation manual(Applied installation)

Instruction Manual

· Function

· Operation

· Routine inspection

· Overall inspection

· Those who operate the PA system to makeboth emergency and general broadcasts

· Those who install the emergency PA system

· Those who settle on a plan of use, such asbroadcast zone assignment, and write(register) data

· Those who check system operations

1

2

3

4

1

2

3

4

Page 5: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

Control cable (4 pairs)

Under 50 ΩUnder 50 ΩUnder 50 ΩUnder 50 ΩUnder 50 ΩUnder 50 Ω

5

2. CONNECTIONS OF INTEGRATED REMOTE CONTROL UNIT RM-971

2.1. Connection Method

• Use heat-resistant, shielded twisted-paired cables for connection.

• Connect between the front-mounted terminal block of Junction Panel JP-0410 and the terminal block of theremote control unit.

2.2. Notes on Connections

The maximum cable distance between the main rack and the remote control unit is 800 m, and there is alimitation to the cable length depending on the type and zone numbers of the connected remote control unit.

2.2.1. Maximum line resistance

EF(FA)

EMGACTI

CPUOFF

C H GND 24V GND 24V BATT 1 BATT 2 CHECK GND

MONITOR 1 EMG RM 24V 2 EMG RM 24V DS CHECK

C1 H1 C2 H2 C3 H3 C4 H4 (-)1 (+)1 (-)2 (+)2 (-)3 (+)3 (-)4 (+)4 GND

EMG REMOTE BUSEMG REMOTE AUDIO IN

REMOTE OUT

C H C H

RM BUS EMGACTI

CPUCTRL OFF

MONITOR 24 VDC POWER GND

JP-0410 front-mounted upper row terminal block

Remote control unit's terminal block

Control line Power supply line

No. of zones

10 zones

20 zones

30 zones

40 zones

50-90 zones

Over 100 zones

Power cable (1 pair)

Under 5 ΩUnder 3 ΩUnder 2.5 ΩUnder 1.5 ΩUnder 1 ΩUnder 0.5 Ω

Page 6: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

6

2.2.2. Connections of multiple remote control units

When connecting two or more remote control units, be sure to branch each cable at the main rack.

Remote control unit Remote control unit Remote control unitMain rack

Main rack Remote control unit

Remote control unit

Remote control unit

Main rack

Remote control unit

Remote control unit

Total distance of (a) and (b) is shorter than 800 m.

(a)

(b)

Up to eight remote control units can be connected per system. However, when the system includes theremote control unit of the type that receives power from the main rack, the additional emergency power supply(p. 24 of Installation Manual - Basic Installation) and the expansion DC power supply (p. 35 of BasicInstallation) may have to be installed in the main rack.

Junction Panel JP-0410 comes with four Emergency RM BUS terminals to control communications with theremote control unit. Note that up to two remote control units can be connected per terminal, and that the totaldistance between the main rack and two remote control units must be shorter than 800 m.

A maximum of two remote control units can be connected per RM BUS terminal.

The JP-0410 is equipped with four Emergency RM Audio Input terminals for audio output from the remotecontrol unit. Only a maximum of two remote control units can be connected per audio input terminal.

Page 7: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

Suitable zone numbers

Under 80 zones

90 – 110 zones

120 – 150 zone

160 – 220 zones

230 – 330 zones

7

110 zones

1.2 A

2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity

When a large current is consumed depending on the number of connected remote control units and zones,the JP-0410's fuses (Emergency Remote Control 1 and 2 fuses) for remote control units must be replaced.

The following table shows the relationship between current consumption and zone numbers per remotecontrol unit.

10 zones

0.3 A

20 zones

0.4 A

30 zones

0.48 A

40 zones

0.58 A

50 zones

0.66 A

60 zones

0.76 A

70 zones

0.84 A

80 zones

0.94 A

90 zones

1.02 A

100 zones

1.12 A

220 zones

2.2 A

120 zones

1.3 A

130 zones

1.38 A

140 zones

1.48 A

150 zones

1.56 A

160 zones

1.66 A

170 zones

1.74 A

180 zones

1.84 A

190 zones

1.92 A

200 zones

2.02 A

210 zones

2.1 A

330 zones

3.18 A

230 zones

2.28 A

240 zones

2.38 A

250 zones

2.46 A

260 zones

2.56 A

270 zones

2.64 A

280 zones

2.74 A

290 zones

2.82 A

300 zones

2.92 A

310 zones

3.0 A

320 zones

3.1 A

EMG RM1

1.6A

EMG RM2 EMG OFF GEN RM CONTROL

1.6A 0.5A 0.5A 3A

10987

For "1 EMG RM 24V"

For "2 EMG RM 24V"

JP-0410 fuse holder

EF(FA)

EMGACTI

CPUOFF

C H GND 24V GND 24V BATT 1 BATT 2

MONITOR 1 EMG RM 24V 2 EMG RM 24V DS CHECK

C1 H1 C2 H2 C3 H3 C4 H4 (-)1 (+)1 (-)2 (+)2 (-)3 (+)3

EMG REMOTE BUSEMG REMOTE AUDIO IN

JP-0410 upper row terminal block

Fuse capacity2 A

2.5 A

3.15 A

4 A

5 A

Part name

Fuse 250V 2A 5x20 time lag

Fuse 250V 2.5A 5x20 time lag

Fuse 250V 3.15A 5x20 time lag

Fuse 250V 4A 5x20 time lag

Fuse 250V 5A 5x20 time lag

Part code number115-40-089-00

115-40-090-80

115-40-091-90

115-40-092-20

115-40-093-70

Two circuits of fuse/power supply terminal combinations are provided for the remote control unit. Themaximum permissible current is 5 A for both circuits put together.

When replacing the fuse for the remote control unit, use the "time-lag" type fuse. Note that the fuse exceeding5 A cannot be used because the fuse holder is 5 A in maximum rating.

Page 8: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

8

2.4. Connections of Multiple Remote Control Units

• Wiring diagram of Integrated Remote Control Unit

CH

OthersRM BUS ( / )

24 VDC ( / )

REMOTE OUT (H / C)

CH

REMOTE OUT

RM BUS

EMG ACTICPU CTRL OFF

MONITOR

24 VDC

Eighth remote control unit

First remote control unit

Third remote control unit

Fourth remote control unit

Fifth remote control unit

Sixth remote control unit

Seventh remote control unit

Second remote control unit

EF(FA)

EMGACTI

CPUOFF

C H GND 24V GND 24V BATT 1 BATT 2 CHECK GND

MONITOR 1 EMG RM 24V 2 EMG RM 24V DS CHECK

C1 H1 C2 H2 C3 H3 C4 H4 (-)1 (+)1 (-)2 (+)2 (-)3 (+)3 (-)4 (+)4 GND

EMG REMOTE BUSEMG REMOTE AUDIO IN

JP-0410 front-mounted upper row terminal block

Page 9: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

9

3. CONNECTION OF REMOTE MICROPHONE RM-1200

3.1. Notes on Connections

The maximum distance between the main rack and the RM-1200 is 800 m.

Use cables with line resistance of less than 10 Ω.

Use twisted paired cables for bus lines.

Use two-core shielded cables for signal lines.

When connecting the bus line to the RM-1200, be sure to use the RM-1200's BUS1 terminal.

Be sure to observe the correct polarity when connecting the bus line.

• Connections of multiple RM-1200 units

When connecting two or more RM-1200 units, be sure to branch each cable at the main rack.

Up to 8 RM-1200 units

RM-1200

RM-1200

Distance (a + b + c) must be shorter than 800 m.

(a)

(b)

Main rack

Main rack

Main rack

(c)

A maximum of eight RM-1200 units can be connected. However, the DC power supply is additionally requiredwhen the JP-0410's power capacity is insufficient depending on the system configuration.

Make connections so that the total cable distance between the main rack and the RM-1200 is shorter than 800 m.

Page 10: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

10

H C 24V

GN

D

BU

S (

)

BU

S (

)

1

EHC

JP-0410 front-mounted middle row terminal block

GND

GND

GND GND

GNDGND

24 V CHIME

ACTIGEM RM PWR

1

1

2

2

3 4 5 6 7 8

1

9 10 11 12

IN USEREMOTE REMOTE TIMER

GEN RM BUS

PWR FAIL

CTRL

AUX CONTROL

To pre-amplifier

RM-1200 terminal block

Note Do not connect E of the phone plug to RM-1200.

Two-core shielded cable Twisted paired cable

Observe correct polarity of bus lines.

3.2. Connections

Page 11: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

11

1. Strip the cable sheath 9 mm using the strip gaugeprovided on the side of the terminal block.

2. Insert the cable into the terminal block.

• Solid cableFully Insert the cable into the hole in the terminalblock.

• Twisted cablePress the lock switch on the terminal block, andfully insert the cable. Then, release the switchwith the cable inserted.

When removing the cable, pull it out of the terminalblock while pressing the lock switch.

Note: Do not press the lock switch extremelystrong.

3. After connection completion, bundle cablestogether using the cable clip, then fix the clip with ascrew.

If cables are too thick to be bundled together,replace the cable clip with the supplied clip.

9 mm

Strip gauge

Lock switch

Cable clip

NoteDo not tighten the clip extremely strong.

3.3. Connection of the RM-1200's Push-in Terminal Block

Page 12: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

Under 1200 m

Over ø1.2 mm

Over ø0.5 mm

12

4. CONNECTION OF REMOTE MICROPHONE RM-1100 (AUX CONTROL TERMINAL)

4.1. Notes on Connections

The maximum cable distance between the main rack and the RM-1100 is 1200 m.

Use two-core shielded cables for signal lines.

Use twisted paired cables for control lines.

Referring to the table below, select the cable to use depending on the cable length.

A maximum of eight (five when the first-in-first-out priority or individual unit priority function is used) RM-1100units can be connected. However, the DC power supply panel may be additionally required when the JP-0410's power capacity is insufficient depending on the system configuration.

• Cable length vs. usable cable

Under 800 m

Over ø0.9 mm

Over ø0.35 mm

Under 400 m

Over ø0.65 mm

Over ø0.26 mm

Cable length

Power/control cable

Shielded cable

To pre-amplifier PP-025B line input

RM-1100 bottom-mounted terminal block

JP-0410 front-mounted middle row terminal block

CE

H

Twinshieldedcable

GND

GND

GND GND

GNDGND

24 V CHIME

ACTIGEM RM PWR

1

1

2

2

3 4 5 6 7 8

1

9 10 11 12 13 14

IN USEREMOTE REMOTE TIMER

GEN RM BUS

PWR FAIL

CTRL

AUX CONTROL

4.2. Connections

To connect the remote control unit to the AUX control terminal, operations for "writing" (registration) arerequired. For details, refer to the Installation Manual - Writing.

Page 13: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

13

4.3. Priority Setting When Multiple RM-1100s Are Connected

4.3.1. Priority setting

First-in-first-out priority: Connect the First-in-first-out terminal of one remote control unit to the same terminalof another. Up to five units can be connected for the FIFO priority function.

Remote Control Unit 1 Remote Control Unit 2

AN

N O

N

RM

1ST

-IN-1S

T-O

UT

R T

PR

IOR

ITY

ALL-Z

ON

E

CH

IME

COM+-24 VDCPOWER

REMOTEOUTPUT

H C E

AN

N O

N

RM

1ST

-IN-1S

T-O

UT

R T

PR

IOR

ITY

ALL-Z

ON

E

CH

IME

COM+-24 VDCPOWER

REMOTEOUTPUT

H C E

Remote Control Unit 1 Remote Control Unit 2

AN

N O

N

RM

1ST

-IN-1S

T-O

UT

R T

PR

IOR

ITY

ALL-Z

ON

E

CH

IME

COM+-24 VDCPOWER

REMOTEOUTPUT

H C E

AN

N O

N

RM

1ST

-IN-1S

T-O

UT

R T

PR

IOR

ITY

ALL-Z

ON

E

CH

IME

COM+-24 VDCPOWER

REMOTEOUTPUT

H C E

Of the two remote control units, the unit making an announcement first takesprecedence. While one unit is in use, other remote control unit cannot be used.

Individual unit priority: Connect the Individual unit priority/sending [priority/T] terminal of the remote control unitgiven higher priority to the Individual unit priority/receiving [priority/R] terminal of the unitwith lower priority. Up to five units can be connected.

4.3.2. When not setting the priority order

When using only one RM-1100 unit or when using multiple units but not assigning priority, do not connect theFirst-in-first-out terminal or Individual unit priority terminal.

NoteTo play chime from the RM-1100, the Pre-amplifier Panel PP-025B which has an internal chime unit CK-025must be installed in the main rack.

In this example, Remote Control Unit 1 takes precedence over Remote Control Unit 2.While Unit 1 is making broadcast, Unit 2 cannot be used. Conversely, while Unit 2 ismaking broadcast, Unit 1 can be used.

Page 14: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

14

5. GENERAL BROADCAST AND ATTENUATOR-FREE BROADCAST DURING POWER FAILURE

5.1. How to Make "Power-Failure" General Broadcast and Attenuator-Free Broadcast

By installing an emergency power supply panel, which is independent of that for emergency broadcast,general broadcast can be made even during a power failure using the battery. The battery to be installed inthe emergency power supply panel is optional.

Notes• To make power-failure general broadcast or attenuator-free broadcast, the emergency power supply panel

and battery solely intended for this purpose must be installed in the main rack.• The emergency power supply panel and battery, installed for emergency broadcast, cannot be used for

power-failure general broadcast or attenuator-free broadcast.

5.2. Terminals for Power-Failure General Broadcast and Attenuator-Free Broadcast

The JP-0410 is equipped with two control inputs, power-failure control input and attenuator-free control input,for activating general broadcast during a power failure.

5.2.1. Power-failure control input

Shorting the power failure control input terminal with the grounding terminal supplies power from theemergency power supply panel for power-failure general/attenuator-free broadcast to equipment, therebyenabling broadcast. When the power-failure general broadcast gets started, the speaker line is not selected. To make broadcast, select the speaker line at the main rack or remote control unit.

Ground

Power-failure general broadcast activation contact. (Procure this switch separately.)Contact capacity: 30 VDC, over 100 mA

JP-0410 front-mounted terminal block

Power-failure control input

Output

JP-0410

EP-0510

Power-failure general broadcast activation contact. (Procure this switch separately.)Contact capacity: 30 VDC, over 100 mA

Digital announcer, etc.(24VDC-operated equipment) JP-0410 rear-mounted

terminal block

Ground

Attenuator-free input

Attenuator-free control inputStart terminal

+

-

Power-failure general broadcast can be made while the switch for activation of power-failure generalbroadcast is at make. If the switch for activation of power-failure general broadcast is at break, the power-failure general broadcast is terminated, putting the system in the standby mode.

5.2.2. Attenuator-free control input

If the attenuator-free control input terminal is shorted with the grounding terminal, attenuator-free broadcastcan be made to the line set by writing even during a power failure. Only the signal connected to the EP-0510'sattenuator-free input is broadcast. In this event, the broadcast is always attenuator-free broadcast (which isoutput to R line).

Closing the attenuator-free control input during AC power operation causes the broadcast to take precedenceover other broadcasts.

Page 15: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

15

5.3. Connections

24 VDC

JP-0410

EP-0510

Connection diagram 1

Power amplifier panel

Digital announcer, etc.

Pre-amplifier panel

Front-mounted terminal block power failure control

Power-failure general broadcast switch

Attenuator-free broadcast switch

Diode for prevention of reverse current flow

Emergency power supply panel for emergency broadcast

Emergency power supply panel for power-failure general broadcast/attenuator-free broadcast

Attenuator-free input

Output

Ground

Notes• Connections for emergency broadcast are omitted.• Separately procure both the broadcast switches and diode for reverse current flow prevention.

Page 16: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

16

In Connection diagram 2, attenuator-free broadcast can automatically be made using the digitalannouncement machine, etc. when the attenuator-free broadcast switch is shorted. Determine broadcastinglines by writing into the Integrated Control Panel EP-0510.

Notes• In this connection example, because power (24 VDC) is always supplied from the battery built in the

emergency power supply panel for power-failure general/attenuator-free broadcasts to the digital announcer,etc. (even when the attenuator-free broadcast switch is not shorted), the battery is drained quicker than inthe example of Connection diagram 1. Use the battery having a sufficient current capacity.

• The power-failure broadcast function is operated even when the AC power is supplied. In such cases, thepower-failure broadcast takes precedence over all other broadcasts. When the AC power is supplied, 24 VDC is not output from the emergency power supply panel's controlterminal.

• To automatically inspect the battery for power-failure general/attenuator-free broadcasts, connect the batterycheck terminal and VOLT DOWN terminal in the same manner as the emergency power supply panel. This applies to both connection examples of Connection diagrams 1 and 2.

Attenuator-free broadcast switch

Attenuator-free input

24 VDC

(+)

(-) Busy outputOutput

Digital announcer, etc.

JP-0410

To EP-0510 attenuator-free broadcast input

Emergency power supply panel for power-failure general broadcast/attenuator-free broadcast

Connection diagram 2

To power amplifier 24 VDC

Page 17: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

17

6. CONNECTIONS WHEN MULTIPLE EQUIPMENT RACKS ARE INSTALLED SIDE BY SIDE

6.1. Expansion Control Panel Connections

When many expansion control panels are used and they are separately installed in different racks, connectthose panels using the optional YR-932 Cable Set.

EP-029-20EP-029-20

EP-0510

EP-029-20

YR-932 multiple-rack EP-EP power cable

Equipment rack 1 Equipment rack 2

Note : This connection method applies to the EP-029-10 Expansion Control Panel as well.

YR-932 multiple-rack EP-EP control cable

POWER

POWER

POWER

POWER

POWER

CTRL

CTRL

CTRL

CTRL

CTRL

POWER

POWER

CTRL

CTRL

Equipment rack 1

Note : This connection method applies to the JP-039-10 Expansion Junction Panel as well.

JP-039-20

POWERPOWER CTRL

CTRL

JP-039-20

POWERPOWER CTRL

CTRL

Equipment rack 2

YR-933 multiple-rack JP-JP control cable

YR-933 multiple-rack JP-JP power cable

6.2. Expansion Junction Panel Connections

When many expansion junction panels are used and they are separately installed in different racks, connectthem using the optional YR-933 Cable Set.

Page 18: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

18

6.3. Expansion Junction Panel Connection when Expanding the DC Power Supply Panel

When many expansion junction panels are used and they are separately installed in different racks, and whenthe power from a DC power supply panel is also supplied to different racks, modify the optional "YR-933Multiple-Rack JP-JP Power Cable" and use the modified cable to connect between the DC power supply andthe junction panel.

POWERPOWER

JP-039-20 POWER

POWER

JP-039-20

AD-011

AD-031B- + - +

24VDCOUT

24VDCIN

Note : This connection applies to the Expansion Junction Panel JP-039-10 as well.

Yellow

Orange

Connect to the DS-029 output terminals

YR-933 multiple-rack JP-JP power cable

Equipment rack 1 Equipment rack 2

(-) Yellow

(+) Orange24 VDC

YR-933 Multiple-Rack JP-JP Power Cable

Cut off here.

Connect to the JP-039 in Rack 1 Connect to the JP-039 in Rack 2

5 Green4 Yellow3 Orange2 Red1 Brown

To make connections, cut off the orange and the yellow wires in the YR-933 Multiple-Rack JP-JP PowerCable at the base of connectors of Rack 1, then reconnect both wires to the DC Power Supply Panel AD-011or AD-031B.

Page 19: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

19

6.4. Specifications of Each Cable Set

600

4 Yellow3 Orange2 Red1

4321

Model No.Model Name

YR-931

Cable Set

YR-932

Cable Set

Cable

YR-931EP-EP Power

Expansion Cable

Quantity

1

Length(mm)

600

AttachedConnector

VH-VH

600

5 Green4 Yellow32 Red1 Brown

54321

YR-931JP-JP Power

Expansion Cable1 600 VH-VH

5000

BlackRed

4321

YR-931EP-AD Power

Expansion Cable1 5000 VH

5000

3 White2 Black1 Red

321

Gray

5000

5 Green4 Yellow3 Orange2 Red1 Brown

54321

YR-932Multiple-Rack EP-EP Control

Cable

1 5000 SMR-SMR

5000

BlackRed

54321

YR-931JP-AD Power

Expansion Cable1 5000 VH

5000

4 Yellow3 Orange2 Red1 Brown

4321

YR-932Multiple-Rack EP-EP Power

Cable

1 5000 VH-VH

YR-933

Cable Set5000

3 White2 Black1 Red

321

Gray

YR-933Multiple-Rack JP-JP Control

Cable

1 5000 SMR-SMR

YR-933Multiple-Rack JP-JP Power

Cable

1 5000 VH-VH

Appearance

Refer to p. 36 and p. 37 of the "Installation Manual - Basic Installation" for connections of the YR-931 cable.

Page 20: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

20

7. ABOUT THE MULTI-ORIGINATION MATRIX SYSTEM

By employing the Input Matrix Panel IM-011, you can provide simultaneous outputs of paging calls orbackground music (BGM) separately to different zones.

• One Input Matrix Panel IM-011 provides 4 inputs/4 outputs matrix configuration.

• Programs of up to four sound sources can be simultaneously broadcast per IM-011. However, the IM-011's Input 1 is designated as an input for emergency broadcast.

• Up to eight IM-011s can be connected, permitting matrix configuration of a maximum of 16 inputs and 8outputs or 8 inputs and 16 outputs.

• Write the setting into the Integrated Control Panel EP-0510. (Refer to the Installation Manual - Writing.)

• Address numbers must be set for the IM-011. (Refer to p. 25.)

[System Example]

Security center, etc.

Integrated Control Panel

JP-0410

JP-039-20

JP-039-20

JP-039-10

EP-0510MInput 1

Input 2

Input 3

Input 4

Output 1

Output 2

Output 3

Output 4

Power AmplifierPanel Junction Panel

InputMatrixPanel

IM-011

Zone A

Zone B

Zone C

Zone A

Zone B

Zone C

General-purpose remote control unit

General-purpose remote control unit

BGM, etc.

Page 21: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

21

7.1. How to Divide the Speaker Lines of the Junction Panel

Junction panel's power amplifier terminals can be divided for a group of consecutive five lines.

For multi-origination broadcast, remove jumper wires on the power amplifier terminals so that the outputs ofthe power amplifier panel are divided for each broadcasting zone.

• The 10-zone Expansion Junction Panel JP-039-10 is not equipped with terminals C3, C4, H3, and H4.

• Remove jumper wires from both C and H terminals depending on the combinations.

GND C1 C2

H1 H2AMP

FAULTFAULT

BATTERYGEN DSEMG DS

CHECKCTRL +CTRL + ACTI +ACTI +CHIME

OUTOUTIN

TIMER

2

EMG

24 V

24 V

ATT

FREE

Jumper wires

POWER AMPLIFIER

C1 C2 C3 C4 H1 H2 H3 H4

JP-039-20 rear-mounted terminal block

JP-0410 rear-mounted terminal block

20-zone Expansion Junction Panel

Junction Panel

Page 22: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

22

• Be sure to divide the speaker lines when connecting two or more power amplifier panels to the junctionpanel or expansion junction panel. Failure to do this shorts the power amplifier panel outputs, causingdamage to the power amplifier panels.

The figure is based on the JP-039-20. Neither the JP-039-10 nor the JP-0410 has lines 11-20.

H3, C3

H4, C4

H2, C2

H1, C1

Remove jumper wires.

Line 1

Line 5

Line 11

Line 15

Line 6

Line 10

Line 16

Line 20

Page 23: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

23

7.2. Input Matrix Panel Connections

• Up to eight Input Matrix Panels IM-011 can be connected.• Inputs and outputs must be of full matrix configuration (i.e. I/O configuration must be as shown below). Also,

the address of each panel must be set correctly depending on the input and output configuration. If notcorrectly set, the matrix panel does not operate normally.

7.2.1. Possible input and output combinations

NoteCombinations other than those above are impossible. Connections are impossible for five and seven units.

0

4

1

5

2

6

0

4

8

1

5

96 units

8 inputs/12 outputs

12 inputs/8 outputs

0

4

1

5

2

6

3

7

0

4

8

A

1

5

9

B8 units

8 inputs/16 outputs

16 inputs/8 outputs

0

0 1

0

4

Connected input Nos. Audio I/O Nos.

1 unit 4 inputs/4 outputs

2 units

4 inputs/8 outputs

8 inputs/4 outputs

0 1 2

0

4

83 units

4 inputs/12 outputs

12 inputs/4 outputs

0 1 2 3

0

4

1

5

4 units

4 inputs/16 outputs

8 inputs/8 outputs

0

4

8

A

16 inputs/4 outputs

Address of the IM-011 to use

Page 24: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

24

[Important] Audio Input 1 is solely intended for emergency broadcast. Be sure to connect Input 1 to the EP-0510'sEmergency/General output.

4

3

2

1

16

15

14

13 1 2 3 4

4

3

2

1 1 2 3 4

4

3

2

1

12

11

10

9 1 2 3 4

4

3

2

1 1 2 3 4

4

3

2

1

8

7

6

5 1 2 3 4

4

3

2

1

4

3

2

1 1 2 3 4

1 2 3 4

4

3

2

1 1 2 3 4

5 6 7 8

4

3

2

1 1 2 3 4

9 10 11 12

4

3

2

1 1 2 3 4

13 14 15 16

4

3

2

1 1 2 3 4

4

3

2

1 1 2 3 4

4

3

2

1 1 2 3 4

Audio input

AddressA

AddressB

Address8

Address9

Address4

Address5

Address0

Address1

Address6

Address7

Address2

Address3

Audio output

Dedicated input foremergency broadcast

7.2.2. Address and audio input/output numbers

Page 25: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

25

7.3. IM-011 Address Setting

1. Remove the IM-011's two front panel screws to remove the front panel.

2. Rotate the address switch with a screwdriver to set the address.

0FEDC

BA9876543

21

ADDRESS

Rotate the address switch with screwdriver to set the address.

The switch is set to 0 at the factory, as shown in the figure.

Remove screws to remove the front panel.

Input level setting switchSelects either –20 dBV or 0 dBV depending onthe input source signal level. The switch is set tothe [0 dBV] position at the factory.

Input volume controlAdjusts the sound volume. (The control is set to the MAXIMUMposition at the factory.)

Set the control mode switchto the [AUTO] position. Theswitch is set to the [AUTO]position at the factory.

When the control mode switch is in the [AUTO]position, the switching time setting switch and theinput/output setting switch are both disregarded.Both switches can be used when the controlmode switch is in the [MANUAL] position.

AUTOMANUAL

CONTROL SW

7.4. Front-Mounted Switch Setting and Volume Control Adjustment

Ensure that the front panel is replaced after setting and adjustment completion.

NoteEmergency broadcast is output at the maximumvolume level regardless of the input volumecontrol setting.

Page 26: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

26

7.5. Connections

Note : Connections of both the emergency broadcasting and power supply sections are omitted.

Power amplifier panel

Power amplifier panel

Monitor Panel MP-011

Pre-amplifier Panel PP-025B

Integrated Control Panel EP-0510

Expansion Control Panel EP-029-20

Input Matrix Panel IM-011

Input sources, such as the general-purpose remote control unit and BGM player

To DC Power Supply Panel

Junction Panel JP-0410

Expansion Junction Panel JP-039-20

Page 27: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

27

7.6. IM-011 Connections

7.6.1. Rear view diagrams and block diagrams

Notes • Be sure to connect the EP-0510's Emergency/General output to Audio Input 1 of the "Address 0" IM-011

Panel connected to the power amplifier panel. Wrong connections disable the emergency broadcastfunction.

• Only the Audio Input 1 signal of the "Address 0" IM-011 Panel is output when in emergency broadcast mode.

1 2 3 4

1 2 3 4

1 2 3 4

1 2 3 41234

1

1 2 3 4

1 2 3 4

234

EP-0510's rear panel

Control cable attached to IM-011

Connect Audio Input 1 of the "Address 0" Input Matrix Panel IM-011 to theEmergency/General output of the Integrated Control Panel EP-0510.

Block diagram

Audioinput

Expansionaudio input

Audiooutput

Expansionaudio output

IM-011's rear panel

24 VDC input(Connect this input to the DC Power Supply Panel's 24 VDC OUT terminal.)

External control input(Used for manual control. Not used in combinations with the FS-970 series.)

Expansionaudio input

Expansionaudio output

Audioinput

Audiooutput

Page 28: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

28

234

1234

1234

1

1 2 3 4

1 2 3 4

1 2 3 4

2341

1 2 3 4

IM-011 controlEmergency/General output

To Integrated Control Panel EP-0510

Address 0

To input source (general-purpose remote control unit, BGM player, etc.)

To power amplifier panel input

Audio outputnumber

Audio inputnumber

EP-0510 Emergency/General output

[ ] stands for the address number.

234

1234

1234

1

1 2 3 4

1 2 3 4

1 2 3 4

234

1234

5678

1

1 2 3 4

1 2 3 4

234

65

78

Address 4

IM-011control

Emergency/General output

To Integrated Control Panel EP-0510

1

1 2 3 4

Address 0

To power amplifier panel input

Audio outputnumber

Expansionaudio input

Audio inputnumber

Audiooutput

EP-0510 Emergency/General output

[ ] stands for the address number.

To input source

To input source

7.6.2. Single IM-011 unit: 4-input/4-output configuration

7.6.3. Input expansion: 8-input/4-output configuration

Page 29: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

29

7.6.4. Output expansion: 4-input/8-output configuration

234

5 6 7 8

Address 1

1

1 2 3 4

Address 0 To input source

To power amplifier panel input

To power amplifier panel input

IM-011 controlEmergency/General output

To Integrated Control Panel EP-0510

1234

1234

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

1 2 3 4 5 6 7 8

234

[ ] stands for the address number.

Audio inputnumber

Expansionaudio output

Audio outputnumber

Audioinput

Page 30: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

30

1 2 3 4

1 2 3 4

5 6 7 8

5 6 7 8

9 10 11 12

13 14 15 16

1234

1234

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

1 2 3 4 5 6 7 8

234

1234

5678

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

234

1234

9101112

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

234

1234

13141516

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

234

Input

Input

Input

Input

To power amplifier panel input

To power amplifier panel input

To [Emergency/General] output of Integrated Control Panel EP-0510

Audio output number

Audio inputnumber

7.6.5. Input/output expansion: 16-input/8-output configuration

[ ] stands for the address number.

Page 31: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

31

1 2 3 4

1 2 3 4

5 6 7 8

5 6 7 8

1

9 10 11 12 13 14 15 16

Input

Input

To power amplifier panel input

To power amplifier panel input

To power amplifier panel input

To power amplifier panel input

To [Emergency/General] output of Integrated Control Panel EP-0510

1234

1234

1

1 2 3 4

1 2 3 4

234

1 2 3 4

1234

1

1 2 3 4

1 2 3 4

5 6 7 8

234

1234

5678

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

9 101112

234

1234

1

1 2 3 4

1 2 3 4

234

1234

1

1 2 3 4

1 2 3 4

13141516

234

1234

1

1 2 3 4

1 2 3 4

234

Audio output number

Audio inputnumber

7.6.6. Input/output expansion: 8-input/16-output configuration

[ ] stands for the address number.

Page 32: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

32

7.6.7. Notes on input level settings when increasing the output

When increasing output numbers to 8, 12 or 16 outputs by connecting two or more IM-011s, the inputscommon to each IM-011 unit must be set for the same level. Refer to the following examples.

• Eight outputs

Important: All of the above input levels must have the same setting regardless of increased input numbers.

The figure below shows the inputs of both "Address 0" and "Address 1" panels are set for the same levelwhen their outputs are increased.

1 2 3 4

Audio input/output expansion (16 inputs/8 outputs configuration)Note: "Exp" in the figure is short for "expansion".

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

AddressA

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

AddressB

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address8

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address4

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address9

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address5

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address0

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address1

0 dB

-20 dB

0 dB

-20 dB

Audio input 2

Audio input 2

To internal circuit

To internal circuit

Expansion audio output 2

Expansion audio output 2

Input level setting switch

Input level setting switch

Address 0

Address 1

Set all inputs 1–4 of both the "address A" and "address B" panelsfor the same level.

Set all inputs 1–4 of both the "address 0" and "address 1" panelsfor the same level.

Set all inputs 1–4 of both the "address 8" and "address 9" panelsfor the same level.

Set all inputs 1–4 of both the "address 4" and "address 5" panelsfor the same level.

Page 33: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

33

The following figure shows the inputs of both "Address 0" and "Address 1" panels are set for different levelswhen their outputs are increased.

0 dB

-20 dB

0 dB

-20 dB

Audio input 2

Audio input 2

To internal circuit

To internal circuit

Expansion audio output 2

Expansion audio output 2

Input level setting switch

Input level setting switch

Address 0

Address 1

1 2 3 4

Audio input/output expansion (8 inputs/12 outputs configuration) Note: "Exp" in the figure is short for "expansion".

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address4

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address5

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address0

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address1

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address6

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address2

Set Inputs 1–4 of the "address 4–6" panels forthe same level.

Set Inputs 1–4 of the "address 0–2" panels forthe same level.

1 2 3 4

Audio input/output expansion (8 inputs/16 outputs configuration) Note: "Exp" in the figure is short for "expansion".

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address4

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address5

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address0

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address1

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address6

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address2

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address7

1 2 3 44

3

2

1

4

3

2

1

Exp audio input

Audi

o in

put

Audio output

Exp

audi

o ou

tput

Address3

Set Inputs 1–4 of the"address 4–7" panels forthe same level.

Set Inputs 1–4 of the"address 0–3" panels forthe same level.

If, as shown in the figure above, the input level of the "Address 0" panel has a different setting from that of the"Address 1" panel when their audio outputs are increased,

(1) Setting the "address 1" panel for an adequate volume level will result in a significantly larger input to the"address 0" panel.

(2) Setting the "address 0" panel for an adequate volume level will result in a significantly smaller input to the"address 1" panel.

• Twelve outputs

• Sixteen outputs

Page 34: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

Status to Turn Output On

Warning Announcement or other audio alarm other than the secondsignal is being output.

Warning Announcement indicator is on or flashing during or beforeand after Warning Announcement.

Evacuation Announcement indicator is on or flashing during or beforeand after Evacuation Announcement.

False Alarm Announcement indicator is on or flashing during orbefore and after False Alarm Announcement.

Emergency announcement is being made from the PA microphone.

Communication error with the emergency remote control unit or otherirregularity has occurred and the failure indication is being displayed.

General broadcast is being made from any connected equipment.

Equipment do not correctly operate because of writing or overallcheck.

34

8. ABOUT THE EP-0510'S STATUS OUTPUTS

These outputs show the status of the Integrated Control Panel EP-0510, and each output turns on when in thefollowing states.

Signals from these outputs are provided from the status output connector (10-pole SM connector) located onthe EP-0510's rear panel. Pins of the connector are arranged as follows.

Output Name

Audio Alarm Output On

Warning Announcement On

Evacuation Announcement On

False Alarm Announcement On

Microphone Announcement On

Abnormality In Progress

General Broadcast On

System Check In Progress

1 2 3 4 5 6 7 8 9 10

EP-0510

Pin No.

Status output connector(10-pole SM connector)

Pin No. Signal Name Rating

1 Ground –

2 Audio Alarm Output On Withstand voltage: 24 VDC, Current capacity: 0.1 A

3 Warning Announcement On Withstand voltage: 24 VDC, Current capacity: 0.1 A

4 Evacuation Announcement On Withstand voltage: 24 VDC, Current capacity: 0.1 A

5 False Alarm Announcement On Withstand voltage: 24 VDC, Current capacity: 0.1 A

6 Microphone Announcement On Withstand voltage: 24 VDC, Current capacity: 0.1 A

7 Abnormality In Progress Withstand voltage: 24 VDC, Current capacity: 0.1 A

8 General Broadcast On Withstand voltage: 24 VDC, Current capacity: 0.1 A

9 System Check In Progress Withstand voltage: 24 VDC, Current capacity: 0.1 A

10 +5 V Current capacity: 1 mA

Page 35: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

35

9. APPENDIX

This appendix focuses on hints on installation and connections of associated equipment to the FS-971 Series.

TABLE OF CONTENTS

9.1. Notes on Parallel Rack Installation

9.1.1. Securing racks installed side by side ................................................................ 36

9.1.2. Adjusting the rack height ................................................................................... 36

9.2. Specifications and Connections of Monitor Panel MP-011

9.2.1. Specifications .................................................................................................... 37

9.2.2. Connections ...................................................................................................... 38

9.3. Connections to the PBX and Intercom Systems .................................................... 39

9.4. Source Equipment Connections .............................................................................. 40

9.5. Tables for Each Panel's Switch Settings

9.5.1. Integrated Control Panel EP-0510 .................................................................... 41

9.5.2. Expansion Control Panels EP-029-10 and EP-029-20 ..................................... 42

9.5.3. Junction Panel JP-0410 .................................................................................... 42

9.5.4. Expansion Junction Panels JP-039-10 and JP-039-20 ..................................... 42

9.5.5. Input Matrix Panel IM-011 ................................................................................. 42

9.5.6. Integrated Remote Control Panel EP-059R ...................................................... 43

Page 36: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

36

9.1. Notes on Parallel Rack Installation

9.1.1. Securing racks installed side by side

Two knock-out holes (ø12 mm) are provided on each side of the rack. Break these holes using a screwdriver,and secure racks to each other with M8 bolts and nuts.

9.1.2. Adjusting the rack height

(A standard screwdriver is required to adjust the height.) When multiple racks installed on the floor areunstable, adjust their height and secure levelness by turning clockwise the height adjustment screw located atthe rack base front.

Page 37: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

24 VDC

400 mA (rated output)

10 inputs - Amplifier output level: 50 V, 70 V, 100 V (changeable)Line output level: 0 dBV (1 V)

33 x 140 mm dynamic speaker, 3 W / 8 Ω7-segment LED meter

Emergency control signal (bypassing attenuators)Talk switch signal (prevention of feedback)

Black, 30% gloss

482 (w) x 44 (h) x 219.1 (d) mm

2.5 kg

4-pole connector cable ................. 1Rack mounting screw ................... 4Name label ................................... 1

37

9.2. Specifications and Connections of Monitor Panel MP-011

9.2.1. Specifications

A maximum of ten amplifier inputs and outputs can be switched and each of their levels monitored by meansof the monitor speaker and level meter.

Power Source

Current Consumption

Input

Monitor Speaker

Meter

Control Signal Input

Finish

Dimensions

Weight

Accessories

420

465

482

31.8

44

4 - 6 x 10

• Appearance

[Rear view]

[Front view]

Page 38: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

38

9.2.2. Connections

• Connecting the Monitor Panel to the Integrated Control Panel EP-0510 permits emergency broadcast to bemonitored at the specific volume level regardless of the volume control setting. When the PA microphoneattached to the EP-0510 is used, the monitoring level automatically lowers to prevent feedback.

• For ten input circuits, by changing the jumper connector position, individual power amplifier or line outputlevels can be selected. (All inputs are set for the power amplifier output level at the factory.)

• All of the ten input circuits can be simultaneously switched to the power amplifier output levels of 50 V, 70 Vor 100 V.

1 2 3 4 5 6 7 8 9 10

Yellow

Orange

Red

Brown

MP-011 top view (case removed)

MP-011 rear view

MP-0510 rear panel

Jumper connector

(Factory-preset position)

Printed circuit board

100 V, 70 V, 50 V position

1 V (line level) position

To each power amplifier output or line output

MP-011 power supplyThese cables are supplied with MP-011.

Page 39: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

39

9.3. Connections to the PBX and Intercom Systems

By connecting the PA system to the PBX and intercom system, paging calls can be made from the telephoneor intercom station. Short the power control starting cable between the AUX control and grounding terminals.The power amplifier's power is switched on and the speaker lines set in the writing are selected.

GND

GND

GND GND

GNDGND

24 V CHIME

ACTIGEM RM PWR

1

1

2

2

3 4 5 6 7 8

1

9 10

IN USEREMOTE REMOTE TIMER

GEN RM BUS

PWR FAIL

CTRL

AUX CONTROL

To pre-amplifier

JP-0410 front-mounted middle row terminal block

Audio signal

Power control starting cable

( Exchange )

Page 40: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

40

9.4. Source Equipment Connections

When using a timer to activate source equipment to play a time signal chime or broadcast commercialmessages, connect the equipment's "Play on" output to the Timer or AUX control terminal of the JP-0410'sfront-mounted terminal block.

Timer

GND

GND

GND GND

GNDGND

24 V CHIME

ACTIGEM RM PWR

1

1

2

2

3 4 5 6 7 8

1

9 10

IN USEREMOTE REMOTE TIMER

GEN RM BUS

PWR FAIL

CTRL

AUX CONTROL

JP-0410 front-mounted middle row terminal block

Control output Input*Source equipment

Play on output*To pre-amplifier

Timer

GND

GND

GND GND

GNDGND

24 V CHIME

ACTIGEM RM PWR

1

1

2

2

3 4 5 6 7 8

1

9 10

IN USEREMOTE REMOTE TIMER

GEN RM BUS

PWR FAIL

CTRL

AUX CONTROL

JP-0410 front-mounted middle row terminal block

Control output Input*Source equipment

Play on output*To pre-amplifier

Equipment name Model No. Input terminal Play on output terminal name

Digital Announcer EV-350P/-350R Start 1, 2 Busy

[Connection to the Timer terminal]

[Connection to the AUX terminal]

* The "Play on" terminal refers to the terminal that is at make while the equipment is playing. The followingtable shows the relationship of the input to "Play on" terminals of the source equipment to be connected.

Page 41: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

41

9.5. Tables for Each Panel's Switch Settings

Note: Each figure of switch shows the factory-preset position.

9.5.1. Integrated Control Panel EP-0510

ONOFF

1 2 3 4

0

5

0

6

0

7

0

8

0

ONOFF

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

ON

SW1ON

OFF

1 2 3 4 5 6 7 8

ONON

OFF

1 2

1 2

1 2

1 2

SW1 setting function

Combination of 1 and 2Line

Normal

Zone lampindication

Equipment that can play main rack BGM

For inspection (Be sure to set these switches to OFF.)

Main rack system and all integrated remote control units (Factory-preset position)

Main rack only

Be sure to set the switch to the OFF (Normal) position after checking line operation status.

All integrated remote control units

"Address 0" integrated remote control unit only

SW2, SW3 (Same construction)

1 2 3 4 5 6 7 8

ONON

OFF

SW4

SW2 setting function

Possible Check On +8 minutes +4 minutes +2 minutes +1 minute +30 seconds

+15 seconds

All-zone broadcast interval

Impossible Normal Off

Emergency reset bypressing key twice

Normal/check

ONOFF

1 2 3 4

0

5

Not Repeated

6

0

7

0

8

0

SW3 setting function

Resumed 2 more repeats 1 more repeat Repeated +30 seconds+1 minuteTerminated 0

Warning Announce-ment repeat mode

ONOFF

1 2 3 4

0

5

0

6

0

7

0

8

0

SW4 setting function

On (Non-interlock) Evacuation Interlock +8 minutes +4 minutes +2 minutes +1 minute

Evacuation Announcement interval

Off (interlock) Warning Selected floor

Warning Announce-ment interlock

Warning/Evacuation selection

Be sure to set the switch to the OFF (Normal) position.

Warning Announcement repetition Nos.

Warning Announce-ment repetition

Warning Announcement repeat interval

+30 seconds

Manual Emergency Broadcast interlock

Page 42: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

42

012

34

5 6 789A

BC

DEF

Address switch

4

Always OFF

3

24 V not output

24 V output

Emergency 24 V

2

Normal

Emergency

Emergency contact

1

Always OFF

Test mode

ON

OFF

SW1 setting function

JP-0410 top panel

012

34

5 6 789A

BC

DEF

Address switch

012

34

5 6 789A

BC

DEF 012

34

5 6 789A

BC

DEF

Control mode switch: Set this switch to the AUTO position.

CONTROL SW

MANUAL AUTO

ADDRESS SWITCHING TIME

Address switch Cannot be used when the control mode switch is in the AUTO position.

9.5.2. Expansion Control Panels EP-029-10 and EP-029-20

9.5.3. Junction Panel JP-0410

9.5.4. Expansion Junction Panels JP-039-10 and JP-039-20

9.5.5. Input Matrix Panel IM-011

Page 43: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

43

9.5.6. Integrated Remote Control Panel EP-059R

ONOFF

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

ON

SW201

1 2 3 40

ON

OFF

1 2 3 41

1 2 3 42

1 2 3 43

1 2 3 44

1 2 3 45

1 2 3 46

1 2 3 47

1 2 3 48

1 2 3 49

1 2 3 410

1 2 3 411

1 2 3 412

1 2 3 413

1 2 3 414

1 2 3 415

6 7 80

6 7 81

6 7 82

6 7 83

6 7 84

6 7 85

6 7 86

6 7 87

ON

OFF

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

ON

SW202

4 5 6 80

ON

OFF

4 5 6 81

4 5 6 82

4 5 6 83

7

7

7

7

4 5 6 84

4 5 6 85

4 5 6 86

4 5 6 87

7

7

7

7

4 5 6 88

4 5 6 89

4 5 6 810

4 5 6 811

7

7

7

7

4 5 6 812

4 5 6 813

4 5 6 814

4 5 6 815

7

7

7

7

4 5 6 816

7

Emergency

SW201 setting function

SW202 setting function

Combinations of 1 to 4 Combinations of 6 to 8

EP-029 shift switch Always OFF EP-059R address

(for inspection)

Shift No. Address

Centralizedemergency Disabled Usable

Combinations of switches 4-8

Remote control mode

Voice guide EP-029shift switch

No. of connected EP-029 units

Enabled Unusable

Page 44: RACK-MOUNTED EMERGENCY PA SYSTEM · 2.3. Remote Control Unit Numbers/Zone Numbers vs. Fuse Capacity When a large current is consumed depending on the number of connected remote control

Printed in Japan133-12-581-4C