rc500 rtu specification - honeywell · rc500 rtu specification 4 1. product introduction rc500...

15
RC500 RTU Specification Release 200 October 2019, Version 1.1

Upload: others

Post on 18-May-2020

80 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification

Release 200

October 2019, Version 1.1

Page 2: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 2

Revision History

Revision Date Description

1.0 November 2011 Reviewed and updated

1.1 October, 2019 Reviewed and Updated

Page 3: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 3

Table of Contents

1. Product Introduction ....................................................................................................... 4 2. RC500 Specifications ..................................................................................................... 5

2.1. RC500 RTU Models .................................................................................................. 5 2.2. RC-SCONTRL RTU Specifications ........................................................................... 6 2.3. RC-MVACONTRL and RC-MVBCONTRL RTU Specifications ................................................................................................................... 10

Page 4: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 4

1. Product Introduction

RC500 Remote Terminal Units

Honeywell’s RC500 RTU is a modular and scalable controller capable

of all remote automation and control applications. RC500 RTU

combined with Honeywell’s powerful and feature-rich SCADA products

provides an integrated solution solving complex remote automation

requirements.

RC500 Overview

RC500 offers the flexibility to choose appropriate RTU model to suit

specific application needs. RTU variants are available based on

number of communication ports needed, memory requirements,

system topology needs, protocol needs and type of Input/Output

modules needed. RC500 RTUs are capable of all remote automation

and control applications. RC500 RTUs integrates into Experion using

industry standard protocols such as Modbus and DNP3. This seamless

RTU integration with Experion answers the most critical and complex

automation needs and at the same time brings in all the latest

technology that Experion platform offers.

RC500 RTU provides flexibility in I/O expansion. RC500 provides

Ethernet I/O options to suit specific application needs. These I/O

modules are DIN Rail mountable and allow hot swapping of modules in

a live system for easy replacement, configuring, and self-calibration.

There is a full range of different I/O module types available.

The RTU Engineering station consists mainly of Honeywell RC500 I/O

Toolkit and ISAGRAF software. The Honeywell RC500 I/O Toolkit is an

easy-to-use software package for designing, configuring and

maintaining RC500 RTU & I/O modules. ISAGRAF programming for

RC500 gives all IEC 61131 standard programming languages

Sequential Function Chart, Ladder Diagram, Structured Text,

Instruction List and Function Block Diagram and Flow Charting

127

RC500 Engineering Station

Modbus/DNP3

RC500 RTU

RC500 I/O Toolkit & ISAGRAF

Experion

Station

Redundant

Experion SCADA

RC500 Ethernet I/O

Page 5: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification

2. RC500 Specifications

2.1. RC500 RTU Models

RC500 RTU Models Ports On-board I/O

Redundancy (RTU & Communication) Memory

Ethernet RS232 RS485 DI DO AI AO

Battery Backed RAM (NVRAM)

Program Flash DRAM

RC-SCONTRL 6 2 1 - - - - Yes 8M 512M 512M

RC-MVACONTRL 1 2 2 12 4 8 2 No 512K 64M 32M

RC-MVBCONTRL 1 2 1 12 8 6 - No 512K 64M 32M Note:

- RC-MVxCONTRL RTU models include in-built AGA support.

Page 6: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 6

2.2. RC-SCONTRL RTU Specifications

Feature Description

Performance

Processor

Industrial PowerPC (32 bit data bus)

Unique station addresses (unit Ids) 247 (Modbus) & 16000 (RC500 protocol)

Dynamic memory (RAM)

(for program execution, dynamic variables, dynamic file system)

512 Megabytes (32 bit, 0 wait states)

Program memory (Flash)

(for program storage, data logging and file system)

512 Megabytes

Battery Backed memory (NVRAM)

(for datalogging and retained variables)

8 Megabytes (Battery-backed – Rechargeable Lithium)

Battery backup time / life 1 year / 10+ years

Real-time clock resolution 10 mS

Real-time clock accuracy

IO Expansion

+/-15 seconds per month

I/O expansion

Number of Ethernet I/O-2 modules connected through

Ethernet per RTU.

Number of Ethernet I/O-2 modules connected through

RS485 per RTU

Scan time of IO Modules

Maximum number of IO Points supported per RTU

Data logging Support

Yes - RC500 Ethernet I/O-2

160 (Ring mode)

160 (Pass through mode)

32

10 mS to 192000 seconds.

4000 (This includes both physical and virtual IO points)

Datalogging support Yes – Honeywell RC500 Datalog

Datalogging modes

Datalogging Media

Host Transfers and client transfers

NVRAM (8 MB)

Flash (512 MB)

Page 7: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 7

Fastest Data logging rate

Datalog Timestamp resolution

IEC 61131 Capabilities

10 mS in NVRAM

1 S in Flash.

1 mS

IEC 61131 programming Yes – ISaGRAF

Languages supported Ladder logic, function chart, function block, instruction list, structured text, and flow chart.

Number of programs allowed to be run in RTU at same time 4

Execution Cycle time

IsaGRAF License Mechanism

10 mS minimum (user settable)

USB based license.

Different types of licenses based on IO Tags are supported.

Virtual points which are exported from Honeywell RC500 I/O Toolkit are counted against the License. Internal Points in ISaGRAF does not count against license.

IsaGRAF runtime supported in RTU

Communication Protocol between RTU and IsaGRAF

Communication Port used

Communication Capabilities

Communication media supported

Communication Protocols supported

3

RC500 Proprietary protocol

1594 (UDP)

Serial, Ethernet, telemetry, telephone (dialup and leased line), radio

(dumb and smart), other wireless, fiber optic, short haul.

Modbus Master, Modbus slave, DNP3 Slave, report on exception

(DNP3), peer to peer (RC500 protocol)

Ethernet Ports

Number of ports

Independent Networks

Network port 1 Connection

Network port 1 Speed

Network port 2 Connection

Network port 2 Speed

6

2 (w/ unique MAC and IP addresses)

1 shielded RJ45 connector (auto-crossover)

10/100BaseTx (auto-detecting)

5 shielded RJ45 (auto-crossover) connector (linked via integrated Ethernet switch). All the 4 ports share a common IP address.

10/100BaseTx (auto-detecting) (Limitation – Maximum speed achieved is 10 MBps)

Isolation 1500 Volts RMS 1 minute (60 Hz.)

Message response time (typical) 5mS

Diagnostic LEDs on each port Indicates speed, link and activity

Protocols supported

Subnet selection

TCP/IP, ARP, UDP, ICMP, DHCP, Modbus TCP, DNP3 TCP, DNP3 UDP and RC500 protocol.

Network port 1 and Network port 2 must be on separate subnets.

Serial Ports

Number of Ports

Baud rate supported

RS232 port – 2 & RS485 ports – 1

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

RS232 Port A RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR/RI , GND)

RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR/RI , GND)

RS485 Port C Screws (GND, 485+, 485-, termination) (2-wire half-duplex)

Maximum number of slaves connected to RS485 network Up to 32 (full-load)

RS485 distance Up to 0.5 miles (1 km)

Protocols Modbus RTU Master, Modbus RTU Slave, Modbus ASCII Master,

Modbus ASCII Slave, DNP3 Slave and RC500 protocol

Page 8: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 8

Diagnostic LEDs on each port Transmit Data (TD) & Receive Data (RD)

Flow Control Hardware, software, RTS-party (for radios and RS485)

DNP3 Capabilities

Device Function

Protocol Compliance Level

Maximum number of events buffered

Multi-Master support

Report by Exception Capability

SBE and CBO capability

Data Logging Support

Maximum RTUs configured for DNP3 in a single Honeywell

RC500 IO Tool kit project

Modbus Capabilities

Device Function

Multi-Master support

Watchdog & Monitors

CPU Watchdog

Communications watchdog

Heartbeat watchdog

Redundancy Capabilities

RTU Redundancy

Redundant Ethernet links

Redundant power inputs

Outstation (Slave)

Level 2 (Also supports many Level 3 and Level 4 functionalities)

50000

Yes (Data monitoring by multiple DNP3 Masters)

Maximum number of DNP3 Masters supported - 4

Yes.

Unsolicited Mode – Reports IO changes without DNP3 Master request.

Solicited Mode – Reports IO changes for class poll requests from DNP3

Master.

Supports select-before-execute (SBE) and a check-before-operate

(CBO) communication sequence for control operation.

Yes. IO Changes (events) are buffered (logged) and maintained in the

DNP3 Event Buffers when there is communication loss between RTU

and SCADA system and the buffered events are sent to the SCADA

System once the communication is restored.

999

Master and Slave

Yes (Data monitoring by multiple Modbus Masters)

CPU automatically resets if error is detected; status LED flashes error code

Settable timeout and output action (force off or freeze)

Settable timeout & output action (force off or freeze)

Automatic switch-over is supported with in-built redundancy capability.

Yes – 2 unique MAC & IP addresses allow for 2 unique network connections

Yes – automatic switch-over on failure (diode protection, and internal voltage monitoring)

Environmental

Mounting

Packaging

Size

Weight

Input voltage

DIN rail (EN50022) or flat panel mount

Alum. Cover (iridite finish) on Lexan base

4.75”L x 3.25”W x 3.15”H

(12.1cm x 8.3cm x 8cm)

0.840 Lb

10-30 VDC (integrated switching supply)

Input power (@ 24 VDC unless otherwise noted) (+/-10%)

(NOTE: The power consumption variations mostly depend on the number of Ethernet and/or serial connections.)

4.8 W (159 mA) – typical (no communications)

5.7 W (190 mA) – typical (some serial and Ethernet comms.)

6.2 W (220 mA) – typical (all ports communicating)

(rated current at max. voltage 30 VDC is 175 mA)

Operating Temperature -40 to 70°C (-40 to 85°C storage)

Humidity 5% to 95% RH (non-condensing)

Standards & Certifications Flammability - UL 94V-0 materials

Page 9: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 9

Electrical Safety - UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE

EMI emissions - FCC part 15, ICES-003, Class A; EN55022; EN61326-1; CE

EMC immunity - EN61326-1 (EN61000-4-2,3,4,6); CE

Surge withstand - IEEE-472 (ANSI C37.90); EN61000-4-2, 4

Vibration - IEC68-2-6

Hazardous locations - UL 1604, CSA C22.2/213 (Class I, Div 2, Groups A,B,C,D), ATEX Directive 94/9/EC relating to Group II, Category 3 Locations

Page 10: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 10

2.3. RC-MVACONTRL and RC-MVBCONTRL RTU Specifications

Feature Description

Performance

Processor

Local I/O (on board)

Industrial PowerPC (32 bit data bus)

RC-MVACONTRL (26)

DI – 12, DO – 4, AI – 8, AO – 2

RC-MVBCONTRL (26)

DI – 12, DO – 8, AI – 6

Unique station addresses (unit Ids) 247 (Modbus) & 16000 (RC500 protocol)

Dynamic memory (RAM)

(for program execution, dynamic variables, dynamic file system)

32 Megabytes (32 bit, 0 wait states)

Program memory (Flash)

(for program storage, data logging and file system)

64 Megabytes

Battery Backed memory (NVRAM)

(for datalogging and retained variables)

512K bytes (Battery-backed – Rechargeable Lithium)

Battery backup time / life 1 year / 10+ years

Real-time clock resolution 10 mS

Real-time clock accuracy

IO Expansion

+/-15 seconds per month

I/O expansion

Number of Ethernet I/O-2 modules connected through

Ethernet per RTU.

Number of Ethernet I/O-2 modules connected through

Yes - RC500 Ethernet I/O-2

128 (Ring mode)

128 (Pass through mode)

32

Page 11: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 11

RS485 per RTU

Scan time of IO Modules

Maximum number of IO Points supported per RTU

Data logging Support

10 mS to 192000 seconds.

4000 (This includes both physical and virtual IO points)

Datalogging support Yes – Honeywell RC500 Datalog

Datalogging modes

Datalogging Media

Fastest Data logging rate

Datalog Timestamp resolution

IEC 61131 Capabilities

Host Transfers and client transfers

NVRAM (512 KB)

Flash (64 MB)

10 mS in NVRAM

1 S in Flash.

1 mS

IEC 61131 programming Yes – ISaGRAF

Languages supported Ladder logic, function chart, function block, instruction list, structured text, and flow chart.

Number of programs allowed to be run in RTU at same time 2

Execution Cycle time

IsaGRAF License Mechanism

10 mS minimum (user settable)

USB based license.

Different types of licenses based on IO Tags are supported.

Virtual points which are exported from Honeywell RC500 I/O Toolkit are counted against the License. Internal Points in ISaGRAF does not count against license.

IsaGRAF runtime supported in RTU

Communication Protocol between RTU and IsaGRAF

Communication Port used

Communication Capabilities

Communication media supported

Communication Protocols supported

3

RC500 Proprietary protocol

1594 (UDP)

Serial, Ethernet, telemetry, telephone (dialup and leased line), radio

(dumb and smart), other wireless, fiber optic, short haul.

Modbus Master, Modbus slave, DNP3 Slave, report on exception

(DNP3), peer to peer (RC500 protocol)

Ethernet Ports

Number of ports

Network port Connection

Network port Speed

RC-MVACONTRL -1

RC-MVBCONTRL -1

1 shielded RJ45 connector (auto-crossover)

10/100BaseTx (auto-detecting)

Isolation 1500 Volts RMS 1 minute (60 Hz.)

Message response time (typical) 5mS

Diagnostic LEDs on network port Indicates speed, link and activity

Protocols supported

TCP/IP, ARP, UDP, ICMP, DHCP, Modbus TCP, DNP3 TCP, DNP3

UDP and RC500 protocol.

Serial Ports

Number of Ports

Baud rate supported

RC-MVACONTRL:

RS232 port – 2 & RS485 ports – 2

RC-MVBCONTRL:

RS232 port – 2 & RS485 ports – 2

300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200

RS232 Port B RJ45 (TD, RD, CTS, RTS, CD, DTR, DSR/RI , GND)

RS232 Port D RJ45 (TD, RD, RTS, GND)

Page 12: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 12

RS485 Port A, C Screws (GND, 485+, 485-, termination) (2-wire half-duplex) (Port C GND

common with port D)

Maximum number of slaves connected to RS485 network Up to 32 (full-load)

RS485 distance Up to 0.5 miles (1 km)

Protocols Modbus RTU Master, Modbus RTU Slave, Modbus ASCII Master, Modbus ASCII Slave, DNP3 Slave and RC500 protocol

Diagnostic LEDs on each port Transmit Data (TD) & Receive Data (RD)

Flow Control Hardware, software, RTS-party (for radios and RS485)

DNP3 Capabilities

Device Function

Protocol Compliance Level

Maximum number of events buffered

Multi-Master support

Report by Exception Capability

SBE and CBO capability

Data Logging Support

Maximum RTUs configured for DNP3 in a single Honeywell

RC500 IO Tool kit project

Modbus Capabilities

Device Function

Multi-Master support

Watchdog & Monitors

CPU Watchdog

Communications watchdog

Heartbeat watchdog

Outstation (Slave)

Level 2 (Also supports many Level 3 and Level 4 functionalities)

50000

Yes (Data monitoring by multiple DNP3 Masters)

Maximum number of DNP3 Masters supported - 4

Yes.

Unsolicited Mode – Reports IO changes without DNP3 Master request.

Solicited Mode – Reports IO changes for class poll requests from DNP3

Master.

Supports select-before-execute (SBE) and a check-before-operate

(CBO) communication sequence for control operation.

Yes. IO Changes (events) are buffered (logged) and maintained in the

DNP3 Event Buffers when there is communication loss between RTU

and SCADA system and the buffered events are sent to the SCADA

System once the communication is restored.

999

Master and Slave

Yes (Data monitoring by multiple Modbus Masters)

CPU automatically resets if error is detected; status LED flashes error

code

Settable timeout and output action (force off or freeze)

Settable timeout & output action (force off or freeze)

Discrete Inputs

Number of Channels

Guaranteed ON Voltage

Maximum Voltage

Guaranteed OFF

Input Resistance

Input Current @ 24V

Filtered ON/OFF delay

Fast ON/OFF delay

Count Rate

Indicator (LEDs)

RC-MVACONTRL – 12

RC-MVBCONTRL – 12

9 VDC

30 VDC

5.0 VDC & 1.5mA DC

10K Ohms

3 mA

25ms (20Hz max. counting)

4 ms (100Hz max counting)

10KHz on channel 1 and refer above for other rates

Each channel has an LED to indicate the status of the input.

Page 13: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 13

Discrete Outputs

Number of Channels

Maximum Output per channel

Maximum Output per module

Max. OFF state leakage

Minimum Load

Inrush current

Typical ON resistance

Typical ON voltage (@1A)

Indicators

Analog Inputs

Number of Channels

A/D resolution

Full scale accuracy

Span and offset temp. coef.

Input impedance

Current protection

DMRR (differential mode rejection)

Common mode rejection

Analog Outputs

Number of Channels

Output range

D/A resolution

Full Scale accuracy

Span and offset temp. coef.

Max. output settling time

Load resistance range (@ +24 VDC supply)

Short circuit protection

Environmental

RC-MVACONTRL – 4

RC-MVBCONTRL – 8

1 A

8 A

0.05 mA

1 mA

5 Amps (100 ms surge)

0.3 ohms

0.3 VDC

Each channel has an LED to indicate the status of the output.

RC-MVACONTRL – 8

RC-MVBCONTRL – 6

16 bits (0.003%)

+/- 0.1% (@20 degree C)

+/- 50 ppm per degree C

100 Ohm

Self-resetting fuses

66 dB at 50/60 Hz

Not applicable since analog inputs are single ended

RC-MVACONTRL – 2

RC-MVBCONTRL – 0

4 – 20 mA

16 bits (less than 1uA)

+/- 0.02% (@ 20 degree celicus)

+/- 50 ppm per degree C typical

5 ms (to .05%)

0-750 Ohms

Current limiting

Mounting

Packaging

Size

Weight

Input voltage

DIN rail (EN50022) or flat panel mount

Alum. Cover (iridite finish) on Lexan base

4.75”L x 3.83”W x 4.13”H

(12.07cm x 9.73cm x 10.48cm)

0.95 Lb

10-30 VDC (integrated switching supply)

Input power (@ 24 VDC unless otherwise noted) (+/-10%)

(NOTE: The power consumption variations mostly depend on

the number of Ethernet and/or serial connections.)

2.4 W (100mA) – typical (no communications)

Operating Temperature -20 to 65°C (-40 to 85°C storage)

Humidity 5% to 95% RH (non-condensing)

Standards & Certifications

Flammability - UL 94V-0 materials

Electrical Safety - UL 508, CSA C22.2/14; EN61010-1 (IEC1010); CE

EMI emissions - FCC part 15, ICES-003, Class A; EN55022; EN61326-1; CE

EMC immunity - EN61326-1 (EN61000-4-2,3,4,6); CE

Surge withstand - IEEE-472 (ANSI C37.90); EN61000-4-2, 4

Vibration - IEC68-2-6

Page 14: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 14

Hazardous locations - UL 1604, CSA C22.2/213 (Class I, Div 2, Groups A,B,C,D), ATEX Directive 94/9/EC relating to Group II, Category 3 Locations

Page 15: RC500 RTU Specification - Honeywell · RC500 RTU Specification 4 1. Product Introduction RC500 Remote Terminal Units Honeywell’s RC500 RTU is a modular and scalable controller capable

RC500 RTU Specification 15

For More Information

To learn more about Honeywell’s products or solutions

visit our website www.honeywell.com/ps or contact

your Honeywell account manager.

Automation & Control Solutions

Process Solutions

Honeywell

2500 W. Union Hills Dr.

Phoenix, AZ 85027

Tel: 877.466.3993 or 602.313.6665

www.honeywell.com/ps

RC500-010-200

October 2019

© 2019 Honeywell International Inc.

This document contains Honeywell proprietary information. It is published for the sole usage of Honeywell Process

Solutions’ customers and prospective customers worldwide. Information contained herein is to be used solely for

the purpose submitted, and no part of this document or its contents shall be reproduced, published, or disclosed to

a third party without the express permission of Honeywell International Inc.

While this information is presented in good faith and believed to be accurate, Honeywell disclaims the implied

warranties of merchantability and fitness for a particular purpose and makes no express warranties except as may

be stated in its written agreement with and for its customer.

In no event is Honeywell liable to anyone for any indirect, special or consequential damages. The information and

specifications in this document are subject to change without notice.