Test report No RA05-0005A - Translation DLA Piper CSTB te futur en construction SAFETY, STRUCTURES AND FIRE DEPARTMENT Reaction to Fire REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING TO THE EUROPEAN STANDARDS NF EN 13823 AND NF ISO 11925-2 Valid for 5 years cofrnc This test report certifies only the characteristics of the object submitted for testing but does not prejudge the characteristics of similar products. So it does not constitute a product certification in the meaning of Article L 115-27 ofthe Consumer Code and Law of 3 June 1994. The reproduction of this test report is only authorised in its integral form. It comprises 8 pages. APPENDIX 1: Charts APPENDIX 2: Photographs At the request of : ALCOA ARCHITECTURAL PRODUCTS S.A.S. 1 rue du Ballon 68500 MERXHEIM FRANCE CENTRE SCIENTIFiatlE ET TECHNIQUE DU BATIMENT ill:! TnriA . M*VIS„- I4N .41. t"; | r'w -i -'H .R-kAiv I /.'.vi.' M4RSI-I**A. ; rn-*? TELtfD •>! £4(8 8412 1 PAX. (33) 01 64SB 64 75 1 www.citli.tr MARNE-LA-VALLtE | PAK|S | 0 K E N • B L E | NANTES | S P H | A-A N T| P • L | S GTID0000358A ARC00000535 0001 ARC00000535/1

Upload: others

Post on 15-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

CSTB te futur en construction S A F E T Y , S T R U C T U R E S AND F I R E D E P A R T M E N T Reaction to Fire

REACTION TO FIRE T E S T REPORT No. RA05-0005A

ACCORDING TO THE EUROPEAN STANDARDS NF EN 13823 AND NF ISO 11925-2

Valid for 5 y e a r s

cofrnc

This test report certifies only the characteristics of the object submitted for testing but does not prejudge the characteristics of similar products. So it does not constitute a product certification in the meaning of Article L 115-27 ofthe Consumer Code and Law of 3 June 1994.

The reproduction of this test report is only authorised in its integral form.

It comprises 8 pages.

APPENDIX 1: Charts

APPENDIX 2: Photographs

At the request of : ALCOA ARCHITECTURAL PRODUCTS S.A.S. 1 rue du Ballon 68500 MERXHEIM FRANCE

CENTRE SCIENTIFiat lE ET TECHNIQUE DU BATIMENT i l l : ! T n r i A . M * V I S „ - I 4 N . 4 1 . t " ; | r ' w - i - ' H . R - k A i v I /.'.vi.' M 4 R S I - I * * A .

; rn-*? TELtfD •>! £4(8 8412 1 PAX. (33) 01 64SB 6475 1 www.citli.tr

M A R N E - L A - V A L L t E | P A K | S | 0 K E N • B L E | N A N T E S | S • P H | A - A N T | P • L | S

GTID0000358A

ARC00000535 0001 ARC00000535/1

Page 2: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= CSTfi 2/8 Test report No. RA05-0005A

S U B J E C T

The tests reported in this document aim to determine the behaviour of the products, in accordance with the tests prescribed in the European standards relating to the reaction to fire of building products excluding floorings.

R E F E R E N C E T E X T S

The tests were carried out according to the standards: NF EN ISO 11925-2 "Reaction to fire tests for building products - Ignitability of building products subjected to direct impingement of flame (Part 2: Single-flame source test)". NF EN 13823 "Reaction to fire test for building products - Building products, excluding floorings, exposed to thermal attack by a single burning item." NF EN 13238 "Reaction to fire test for building products - Conditioning procedures and general rules for selection of substrates."

N A T U R E O F T H E T E S T ( S )

- Determination of ignitability of building products by direct small flame impingement under zero impressed irradiance.

- Determination of behaviour of building products exposed to thermal attack by a single burning item (S.B.I, in English).

GTID0000358A

ARC00000535 0002 ARC00000535/2

Page 3: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= C S T B 3/8 Test report No. RA05-0005A

S A M P L E S ORIGIN AND IDENTIFICATION

Delivery clate(s): 3 November 2004

Conditioning according to NF EN 13238: 2 weeks

Date(s) of test: 2 December 2004

Material submitted by: A L C O A A R C H I T E C T U R A L P R O D U C T S S . A . S . 1 rue du Ballon 68500 MERXHEIM F R A N C E

Identification No: ES541040535

Commercial brand(s): REYNOBOND® 55 P E Riveted s y s t e m

Manufacturer: A L C O A A R C H I T E C T U R A L P R O D U C T S S . A . S . 1 rue du Ballon 68500 MERXHEIM F R A N C E

The test results relate to the behaviour of the test specimens of a product under the particular conditions of the test; they are not intended to be the sole criterion for assessing the potential fire hazard of the product in use.

Champs-sur-Marne, 7 January 2005

The Technician Responsible for the test

The Head of Reaction to fire unit

Gi ldas C R E A C H Martial BONHOMME

GTID0000358A

ARC00000535 0003 ARC00000535/3

Page 4: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSJB 4/8

Test report No. RA05-0005A

SUMMARY D E S C R I P T I O N

Composite panel consisting of a low density polyethylene core surfaced on both sides with a thermally bonded precoated aluminium sheet. Provided system: riveted on metal substructure. Finish: Duragloss® 5000 35 |jm.

Overall nominal thickness: 4 mm. Nominal thickness of the aluminum sheets: 0.5 mm. Overall nominal weight per unit area: 5.5 kg/m 2. Finish: Duragloss ® 5000. Colour: grey/green.

ADDITIONAL C H A R A C T E R I S T I C S

The detailed composition is on file.

Overall nominal thickness: about 4 mm. Nominal thickness of the aluminum sheets: about 0.5 mm. Measured overall weight per unit area: about 5.5 kg/m 2.

GTID0000358A

ARC00000535 0004 ARC00000535/4

Page 5: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= CSTB s/s Test report No. RA05-0005A

T E S T F O R BUILDING P R O D U C T S C A U S E D B Y T H E S M A L L F L A M E O F A B U R N E R (NF EN ISO 11925-2) A test apparatus is used, consisting in a test chamber and a propane burner tilted at an angle of 45°. The specimen (250x90mm) is subjected to the flame of the burner with different exposures depending on the use of the product: * Exposure ofthe surface * Exposure ofthe edges on one or several layers ofthe product The classification criteria is the flame height.

C O M M E N T S - R E S U L T S

Exposure on: precoated sheet DURAGLOSS ® 5000. Type of exposure: surface Flame application time: 30s

Specimen Description Ignition

time Flame spread

> 150mm Ignition of filter paper

Maximum height of

flame (mm)

No 1 Precoated sheet 0 No No Nil

No 2 Precoated sheet 0 No No Nil

No 3 Precoated sheet 0 No No Nil

No 4 Precoated sheet 0 No No Nil

No 5 Precoated sheet 0 No No Nil

No 6 Precoated sheet 0 No No Nil

Exposure on: low density polyethylene core. Type of exposure: edges Flame application time: 30s

Specimen Description Ignition

time Flame spread

> 150mm Ignition of filter paper

Maximum height of

flame (mm)

No 1 PE core 0 No No Nil

No 2 PE core 0 No No Nil

No 3 PE core 0 No No Nil

No 4 PE core 0 No No Nil

No 5 PE core 0 No No Nil

No 6 PE core 0 No No Nil

GTID0000358A

ARC00000535 0005 ARC00000535/5

Page 6: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

CSTB 6/8 Test report No. RA05-0005A

T E S T F O R BUILDING P R O D U C T S E X P O S E D TO T H E R M A L A T T A C K B Y A S I N G L E BURNING ITEM (OIF O R SBI ) (NF EN 13823)

A test apparatus is used, consisting ofa trolley, frame, burners, hood... A specimen, consisting of two vertical wings forming a right-angled comer, is exposed to the flame from a burner placed at the bottom of the corner formed by the two wings ("main burner"). The flame is obtained by combustion of propane gas injected through a sandbox so as to produce an output of (30.7 +/- 2.0) kW. The performance of the specimen is evaluated for a period of 20 minutes. The performance criteria are the following: heat release, smoke production, horizontal front flame spread and burning particles and droplets. A short period prior to ignition of the main burner is necessary to measure the heat output of the burner alone; this is calculated using a similar bumer placed at a distance from the specimen ("auxiliary burner"). Some measurements are obtained automatically, others result from visual observation. The exhaust duct is equipped with sensors to measure the heat, attenuation of the light beam, mole fractions 02 and C02, as well as a differential pressure caused by the gaseous effluent in the exhaust duct. These values are registered automatically and used to calculate the volume flow, the Rate of Heat Release Rate (RHR in English) and the Rate of Smoke Production (RSP in English). The horizontal front flame spread and the burning droplets or particles are subject to visual observation and are recorded on the record sheet. Complementary definitions: THR 600s: Total heat release from the specimen during the first 600s of exposure to the main burner flames. LFS edge: lateral flame spread over the long specimen wing to the external edge of the latter at a height between 500 and 1500mm during the first 1500 seconds TSP 600s: Total smoke production from the specimen during the first 600s of exposure to the main burner flames. FDP: level of release of Flaming Droplets/ Particles falling outside ofthe area ofthe burner FIGRA: Fire Growth Rate SMOGRA: Smoke Growth Rate

P R E P A R A T I O N O F T H E T E S T P I E C E S

The assembly of the specimens is done in accordance with standard NF EN 13823, paragraph 5.2.2a) and 5.2.2e).

Specimens 1 to 3: REYNOBOND® 55 PE riveted system

Mounting: panels fixed with rivets on a framework in aluminium profiles then applicate on gypsum plasterboard. The riveted system means that the panel edges are free and that the low density polyethylene is apparent. Assembly with horizontal join at 200mm and vertical joint at 500mm.

GTID0000358A

ARC00000535 0006 ARC00000535/6

Page 7: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 7/8 Test report No. RA05-0005A

C O M M E N T S - R E S U L T S

Specimen 1:

Test date: 02/12/2004

Name of computer file: C:\SBICALC\DATA\04120001.CSV

PRODUCT FIGRA 0,2

W/s FIGRA 0,4

W/s THR 600s

MJ L F S edge

SMOGRA m 2 /s 2

TSP 600s m 2

REYNOBOND 55 PE® Riveted system 62,6 62,6 3,8

Not reached

9,9 83,4

Comments: 360s: darkening of the sheet at 500 mm of height; distortion of the sheet in the angle and along the joint at 200 mm at a height from 0 to 1000 mm. 505s: ignition ofthe polyethylene at the joint level at 200 mm from the 0 to 200 mm of height. 560s: ignition of polyethylene at the joint level at 200 mm from the 0 to 700 mm of height. Presence of falling ignited droplets in the burner area.

Destruction ofthe product in place: Length destroyed at the basis ofthe test piece: L0 = 200mm Length destroyed at 500mm of height: L500 = 250mm The test piece is damaged at the angle level to Hmax = 1000mm of height.

Specimen 2:

Test date: 02/12/2004

Name of computer file: C:\SBICALC\DATA\04120002.CSV

PRODUCT FIGRA 0,2

W/s FIGRA 0,4

W/s THR 600s

MJ L F S edge

SMOGRA m 2 /s 2

TSP 600s m 2

REYNOBOND 55 PE® Riveted system 105,5 105,5 7,8

Not reached

5,7 48,1

Comments: 355s: darkening of the sheet to 500mm of height; distortion of the sheet in the angle and on the joint at 200 mm on a height from 0 to 1000 mm. 510s: ignition in the joint at 200 mm on a height from 0 to 500 mm. 650s: ignition ofthe polyethylene on the long wing from 0 to 1000 mm of height (inside the sheets). 830s: ignition of the polyethylene on a height from 0 to 1500 mm in the angle (long wing and small wing); the polyethylene flow and burn along the joint at 200 mm. 1170s: falling ignited drops in the burner zone.

Destruction ofthe product in place: Length destroyed at the basis ofthe test piece: L0 = 200mm Length destroyed at 500mm of height: L500 = 200mm The test piece is damaged at the angle level to Hmax = 1000mm of height.

GTID0000358A

ARC00000535/7

Page 8: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 8/8 Test report No. RA05-0005A

Specimen 3:

Test date: 02/12/2004

Name of computer file: C:\SBICALC\DATA\04120003.CSV

PRODUCT FIGRA 0,2

W/s FIGRA 0,4

W/s THR 600s

MJ L F S edge

SMOGRA m^s 2

TSP 600s m 2

REYNOBOND 55 PE® Riveted system 72,4 72,4 4,2

Not reached

7,7 43,3

Comments: 360s: darkening of the sheet to 500 mm of height; distortion of the sheet in the angle and on the joint at 200 mm on a height from 0 to 1000 mm. 510s: ignition in the joint at 200 mm at a height from 0 to 500 mm. 740s: ignition in the joint at 200 mm at a height from 0 to 800 mm. 1000s: ignition of the polyethylene at a height from 0 to 1500 mm in the angle (long wing and small wing). 1100s: falling ignited drops in the channel (burner zone).

1400s: falling ignited drops outside ofthe burner zone with (ignition on the ground > 10 secondes).

Destruction ofthe product in place:

Length destroyed at the basis ofthe test piece: L0 = 350mm Length destroyed at 500mm of height: L500 = 500mm Length destroyed at 1000mm of height: L1000 = 300mm Length destroyed at 1500mm of height: L1500 = 250mm The test piece is damaged at the angle level to Hmax = 1500mm of height.

A V E R A G E O F T H E D I F F E R E N T P A R A M E T E R S ON 3 S P E C I M E N S

PRODUCT FIGRA 0,2 W/s

FIGRA 0,4 W/s

THR 600s MJ

L F S edge SMOGRA m 2 /s 2

TSP 600s m 2

REYNOBOND 55 PE® Riveted system 80,1 80,1 5,3

Not reached

7,8 58,3

END OF THE TEST REPORT

GTID0000358A

ARC00000535 0008 ARC00000535/8

Page 9: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB DEPARTEMENTSECURITE. STRUCTURES ETFEU Reaction au feu

APPENDIX 1 TO THE T E S T REPORT No RA05-0005A

CHARTS

The reproduction of this test report is only authorised in its integral form. It comprises 7 pages.

At the request of : A L C O A A R C H I T E C T U R A L P R O D U C T S S . A . S .

1 rue du Ballon

68500 MERXHEIM

F R A N C E

PARIS - MARNE-LA-VALLEE • GRENOBLE - NANTES - SOPHiA ANTIPOLIS C E N T R E S C I E N T I F I Q U E E T T E C H N I Q U E DU B A T I M E N T

Ei. .ivi-i'iuii JMn-Jaurfei - CriSfWfjj.Sur.UjrnB - SP 2 • F-7T44T Marne-a-VaJl^e Cedex E Tfil. : Dt 54 6aB4 12- Fax: Dl 84 68 8173 - Sim ; dsil.CSlll fr

GTID0000358A

ARC00000535 0009 ARC00000535/9

Page 10: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= C S T B 2 / 7

Test report No. RA05-0005A

Specimen No 1: REYNOBOND ® 55 riveted system:

HRR HRR(30)

Time(s)

THR FIGRA

0 200 400 600 800 1000 1200 1400 1600 1800

Time(s)

GTID0000358A

ARC00000535 0010 ARC00000535/10

Page 11: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 3/7

Test report No. RA05-0005A

SPR SPR(60)

Time(s)

TSP SMOGRA

0 200 400 600 800 1000 1200 1400 1600 13Q0

Time(s)

GTID0000358A

ARC00000535 0011 ARC00000535/11

Page 12: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 4/7 Test report No. RA05-0005A

Specimen No 2: REYNOBOND ® 55 PE riveted system

40

35 -

30 -

25 -

0= 20 -T 1- 15 -

10 -

5 -

0

HRR •HRR(30)

• T H K •FIGRA

200 400 600 800 1000 1 200 1 400 1 600 1 800

Time(s)

GTID0000358A

ARC00000535 0012 ARC00000535/12

Page 13: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

5/7 - CSTB T e s t r e p o r t N o RA05-0005A

GTID0000358A

ARC00000535 0013 ARC00000535/13

Page 14: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 6/7 Test report No. RA05-0005A

Specimen No 3: REYNOBOND ® 55 PE riveted system

HRR HRR(3C)

70

60 -

50 -

40 -M

3 0 -

X 20

10

0 -t

•10 J 200 600 800 1000 1200 1400 1600 ISOO

Time(s)

-THR FIGRA

25

20

15 J

D

j 80

70

60

Q

I 40 >

30 «

- 20

•• 10

200 400 600 800 1000 1200 1400 1600

Time(s)

1800

GTID0000358A

ARC00000535 0014 ARC00000535/14

Page 15: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=CSTB 7/7 Test report No. RA05-0005A

SPR(60}

G

-02 200 400 600 800 1000 1200 1400 1600 1800

Time(s)

•TSP SMOGRA

GTID0000358A

ARC00000535 0015 ARC00000535/15

Page 16: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

=CSTB I

D£PARJEM£NT SECURtTE, STRUCTURES ETFEU HcacHcn (an

Test report No RA05-0005A - Translation DLA Piper

APPENDIX 2 TO THE T E S T REPORT No RA05-0005A

PHOTOGRAPHS

The reproduction of this test report is only authorised in its integral form. It comprises 4 pages.

At the request of : A L C O A A R C H I T E C T U R A L P R O D U C T S S . A . S .

1 rue du Ballon

68500 MERXHEIM

F R A N C E

PARIS - MARNE-LA-VALLEE - GRENOBLE • NANTES - SOPHIA ANTIPOLIS E E N T F I E S C I E N T I F I Q U E E T T E C H M I Q U E DU B A T I M E N T

B4, awenueuean-J&jrSs- Champa-sjr-Wane - Z - F-77^47 Wame-la-Vallte Cede*: 2 J6I.: 01 64 69 84 12 - Fan: 01 64 65 64 T9 - Site vieb: dsaf.cslb.lr

GTID0000358A

ARC00000535 0016 ARC00000535/16

Page 17: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= C S T B 2 / 4

Test report No. RA05-0005A

Specimen No 1: REYNOBOND ® 55 PE riveted system

Before testing

GTID0000358A

ARC00000535 0017 ARC00000535/17

Page 18: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

=C5TB 3/4 Test report No. RA05-0005A

GTID0000358A

ARC00000535 0018 ARC00000535/18

Page 19: REACTION TO FIRE TEST REPORT No. RA05-0005A ACCORDING …

Test report No RA05-0005A - Translation DLA Piper

= C 5 7 B 4/4 Test report No. RA05-0005A

Specimen No 3: REYNOBOND ® 55 PE riveted system

Before testing

After testing

GTID0000358A

ARC00000535 0019 ARC00000535/19