Real World Application of the Heat Machine. A chiller capable of producing water temperatures of low 40’s on the evaporator side and above 135° on the condenser side. What is a Heat Machine. Wherever there is a simultaneous demand for hot water and chilled water. Heat Machine Application. - PowerPoint PPT PresentationTRANSCRIPT
![Page 1: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/1.jpg)
Real World Application of the Heat Machine
![Page 2: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/2.jpg)
*What is a Heat Machine
*A chiller capable of producing water temperatures of low 40’s on the evaporator side and above 135° on the condenser side.
![Page 3: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/3.jpg)
*Heat Machine Application
*Wherever there is a simultaneous demand for hot water and chilled water.
![Page 4: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/4.jpg)
UAH Central Plant
•Serves app. 1 million square feet•Dorms, classrooms and research labs•Half a million square feet in research labs•Once through air has to be de-humidified•Accomplished by chilling air to 55 and reheating to maintain comfort conditions•Year round heating demand
![Page 5: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/5.jpg)
*UAH Central Plant
*3600 tons of conventional cooling*1300 horsepower Natural gas/fuel oil boilers
![Page 6: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/6.jpg)
Boilers
•Two 500 hp natural gas fire tube boilers•“Most efficient fire tube boilers in the state”•180 degree water, 190 degree stack temperature
![Page 7: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/7.jpg)
Primary/Secondary Pumping
•Low Delta T syndrome•Characterized by:•Over pumping primary system•Higher chilled water supply temperatures•Forcing additional chillers on before chillers are fully loaded.
![Page 8: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/8.jpg)
UAH Chilled Water Plant
![Page 9: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/9.jpg)
UAH Heat Machines
![Page 10: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/10.jpg)
Reasons for Heat Machine
•Lowest first cost option•Solved Boiler condensing •Reduced run time on boiler by 3•Reduced maintenance on boiler
•Essentially solved low Delta T syndrome
![Page 11: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/11.jpg)
Why We Decided To Install Heat-Machines
•Allowed Us To Condition Our New Student Center From Our Existing Central PlantNo Square Footage Needed for Boiler in New BuildingNo Air-Cooled Chiller Near Building (Noise)•Lowest Design/Construction Option
Total Project Cost ~ $550,000•Added Cooling and Heating Redundancy•~ 400 Tons of Cooling (4,800,000 BTUH)•~ 180 Boiler Horsepower (6,000,000 BTUH)•Most Economical Way For Us to Make Hot Water
![Page 12: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/12.jpg)
What Is The Product Of A Water To Water Chiller?
![Page 13: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/13.jpg)
What Is The Product Of A Water To Water Chiller?
COLD WATER
![Page 14: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/14.jpg)
What Is The BY-Product Of A Water To Water Chiller?
![Page 15: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/15.jpg)
Warm/Hot
Water
What Is The BY-Product Of A Water To Water Chiller?
![Page 16: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/16.jpg)
October 11, 2013 Heat-Machine Snapshot
What Is My Product – What Is My By-Product?
![Page 17: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/17.jpg)
October 11, 2013 Heat-Machine Snapshot
![Page 18: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/18.jpg)
18
*Coefficient Of Performance
COP is the ratio of the heating or cooling provided over energy consumed
![Page 19: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/19.jpg)
19
* COP - COOLING
![Page 20: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/20.jpg)
20
*COOLING Example 1 (Snapshot in time)
VAC AMPS BTUH4160 1.73 76.7 3.412 1,883,405
COP3.821333
GPM CHWRT CHWST DT GPH Weight2000 50.7 43.5 7.2 60 8.33 7,197,120
WORK IN
![Page 21: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/21.jpg)
21
* COP - HEATING
![Page 22: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/22.jpg)
22
*HEATING Example 1
COP is the ratio of the heating or cooling provided over energy consumed
*Electric Boiler/Water Heater ~100% Efficient *1 KWH = 3,412 BTUs *COP = ~1
ElectricityBTU/KWH
BTUs IN 3412BTUs Out 3412
COP = Heat Out / Work InCOP = 3412/3412COP = 1
![Page 23: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/23.jpg)
23
*HEATING Example 2
COP is the ratio of the heating or cooling provided over energy consumed
*Natural Gas Boiler Combustion Efficiencies *Fire Tube Boiler – 83 to 85%
*COP = .85 Nat. GasBTU/cf
BTUs IN (W) 1027BTUs Out (Q) 873
COP = Heat Out / Work InCOP = 873/1027COP = 0.850048685
![Page 24: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/24.jpg)
24
*What Would The Formula To Calculate COP Look Like If We Had An Application For Using Both Hot Water (Product) and Chilled Water (Byproduct) Simultaneously?
![Page 25: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/25.jpg)
25
* COPTotal = COPHEATING + COPCOOLING
![Page 26: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/26.jpg)
Current Fuel Cost
For 1,000,000 BTUsElectricity $25.25
Nat. Gas $8.02 #2 Fuel Oil $24.51
![Page 27: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/27.jpg)
Current Fuel Cost
For 1,000,000 BTUsElectricity $25.25 ____with COP of 7.09
Nat. Gas $8.02 $9.22 if used in 85% eff. Boiler COP 0.85
#2 Fuel Oil $24.51 $28.84 if used in 85% eff. boiler COP 0.85
![Page 28: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/28.jpg)
Current Fuel Cost
For 1,000,000 BTUsElectricity $25.25 $3.56 with COP of 7.09
Nat. Gas $8.02 $9.22 if used in 85% eff. Boiler COP 0.85
#2 Fuel Oil $24.51 $28.84 if used in 85% eff. boiler COP 0.85
![Page 29: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/29.jpg)
COP TREND DATA
BTU s
![Page 30: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/30.jpg)
HEATING RESULTS TO DATE (01-16-14)
BTU s
Product:13,395,000,000 BTUs
![Page 31: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/31.jpg)
COOLING RESULTS TO DATE (01-16-14)
By-Product:108,322,148,000 BTUs902,679 Ton Hours
Tons
![Page 32: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/32.jpg)
WATER SAVINGS TO DATE (01-16-14)
2,040,054 GALLONS$3,162.08Chemical Savings Yet To Be Determined.
![Page 33: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/33.jpg)
$130,000.Cumulative
Savings Since Installation
$
May 13TH To
January 16TH
![Page 34: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/34.jpg)
198,000Projected Annual
Savings Rate
$
![Page 35: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/35.jpg)
2.5 to 3 Projected Payback
Years
0 years?
![Page 36: Real World Application of the Heat Machine](https://reader035.vdocuments.net/reader035/viewer/2022062305/56816584550346895dd82d8a/html5/thumbnails/36.jpg)
Questions