Page 1: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM

RECAPP Facility Evaluation Report

Bethany MeadowsB4660ACamrose

Alberta Health Services-Central

Page 2: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 2 of 45

B4660ABuilding Id:

Bethany MeadowsBuilding Name:

CamroseLocation:4209 - 55 Street Address:

6,780.00Gross Area (sq. m): $24,655,216Replacement Cost:0Construction Year:

Evaluation Date: October 7 2013

Francis Ng Architect Ltd.Evaluation Company:

Francis NgEvaluator Name:

Bethany Meadows of 6915.62 square metres was built in Camrose in 2003 and has three asphalt paved publicroadways - 55th Street on the west, 42nd Avenue on the south and 53rd Street on the east. There is one asphaltpaved Service Lane on the north. It is under the jurisdiction of Bethany Meadows. House A - 1217.7 square metres Link A - 38.2 square metres House B - 1205.5 square metres Link B - 13.0 square metres House C - 1205.5 square metres Link C - 13.0 square metres House D - 1747.6 square metres Link D - 45.6 square metres Downtown - 1092.5 square metres Basement - 289.7 square metres Utility building - 47.32 square metres Total building area - 6915.62 square metres Downtown - administration, chapel, hair, offices, family room/kitchen, materials management, maintenance,gymnasium/treatment area. Basement - mechanical Room House A - resident rooms House B - resident rooms House C - resident rooms House D - resident rooms ABC 2006 Group B2 - Hospital and Infirmary. The care centre is single storey with combustible and non-combustibleconstruction and sprinklered.

General Summary:

Structural Summary:Building (House A, B, C and D), Downtown) - have concrete slab on grade, concrete grade beams on concrete pilesalong perimeter and interior concrete pier on concrete pedestal footings; exterior walls have wood studs and interior hasmetal columns; basement has concrete columns; roof has plywood sheathing on engineered trusses. Downtown (basement mechanical room) - has concrete slab on grade, concrete foundation walls on strip concrete footingalong perimeter and interior concrete columns on concrete pad footings. Utility building - has concrete slab on grade, concrete grade beams on concrete piles along perimeter; exterior walls havewood studs; roof has OSB sheathing on wood trusses. Recommendations for future action include: Mud jack floor slab; repair concrete foundation walls. Overall structural system rating is acceptable.

Envelope Summary:Building (House A, B, C, D and Downtown) - have asphalt shingles, vinyl siding, perforated metal soffits, PVC windowsc/w awnings, metal overhead door, metal entrance door and metal frame, exterior utility metal doors and metal frames.

2.45%5 year Facility Condition Index (FCI):

Facility Details Evaluation Details

Total Maintenance Events Next 5 years: $603,500

Camrose - Bethany Meadows (B4660A)

Page 3: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 3 of 45

Utility building - has asphalt shingles, vinyl siding, perforated metal soffit, PVC window c/w awning, metal overheaddoor, exterior utility metal door and metal frame. Recommendations for future action include: repair vinyl siding; repair PVC windows. Overall envelope system rating is acceptable.

Interior Summary:Building (House A, B, C, D and Downtown) - have textured ceiling or painted drywall ceiling, painted gypsum wallboard and sheet vinyl or carpet flooring; concrete ceiling, concrete walls and painted concrete flooring in basementmechanical room; ceramic wall tiles around patient showers; wood doors and metal frames. Utility building - has painted drywall ceiling, painted gypsum wall board and painted concrete flooring. Recommendations for future action include: repair interior partitions; replace wood doors and frames; replace woodpocket; repaint interior walls. Overall interior system rating is acceptable.

Mechanical Summary:Ventilation is provided by 9 indirect gas fired air handling units located throughout facility. These units are generallylocated in the Attic spaces above each of the "Houses" and in the basement Mechanical room below the "downtown"area. The air distribution system is via low velocity single ductwork, connected to the various grilles and diffusers. Air conditioning is provided by DX coils in the air handling units, connected to 9 outdoor mounted condensing units. The heating system includes two natural gas fired hot water boilers. Heating water is distributed with a piping networkto perimeter radiant heating units, force flows and unit heaters. The hot water system is reverse return type. Two other hot water boilers and storage tanks provide domestic hot water to the facility. Galvanized steel and copper piping distribution to plumbing fixtures complete with domestic hot water recirculationsystem. The Control systems include a combination of electric and Johnson Controls digital programmable buildingmanagement control system. Fire protection system for the facility consists of automatic sprinkler system and hand held fire extinguishers. Overall mechanical systems are in Acceptable condition.

Electrical Summary:Bethany Meadows is a senior citizens lodge complex consisting of four (4) houses;each house is further divided into 2cottages. All 4 houses are linked together. The Downtown House has a basement that houses the main mechanicaland electrical rooms. From these rooms, services are routed to the other houses via the crawl spaces. Each househas been provided with sub electrical rooms for distribution within the house. The complex is fed with power from apad mounted utility owned transformer; the secondary feeders are routed underground to the main distribution centrelocated in the basement of the Downtown House. The main service is 600A, 600V, 3 phase, 4 wire. Step down transformers have been provided in each of the housesthat step the voltage down to 120/208V 3 phase, 4 wire for general use. Panel boards have been provided in the subelectrical room for power distribution within the house. Interior lighting is provided by fluorescent fixtures. In common areas, fixtures utilize T8 linear lamps, while in theresidents room the fixtures are complete with compact fluorescent lamps. An addressable fire alarm system has been provided. Each house has been provided with its own system controlpanel. All the control panels are networked. An alarm in any point within the complex is annunciated on all the panelswithin the complex. A Nortel telephone system has been provided for the administration area, Residents have their own personal line. The call system is of the wireless type; each resident has been provided with a wireless pendant that they press whenrequiring assistance. Data systems have been provided in the administration area. Cable TV service has been provided along with an antenna system.

Camrose - Bethany Meadows (B4660A)

Page 4: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 4 of 45

Overall, the electrical systems are in good condition.

Camrose - Bethany Meadows (B4660A)

Condition Rating Performance1 - Critical Unsafe, high risk of injury or critical system failure.2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs.

3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs.4 - Acceptable Meets present requirements, minor deficiencies. Average operating/maintenance costs.

Rating Guide

5 - Good Meets all present requirements. No deficiencies.6 - Excellent As new/state of the art, meets present and foreseeable requirements.

Page 5: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 5 of 45

A1010 Standard Foundations*

A1030 Slab on Grade*

4 - Acceptable

3 - Marginal

Rating

Rating

2003

2003

Installed

Installed

0

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Mud jack floor slab. (approx. 3360 square metres)

Repair 2014 $168,000 High

Slab on grade has 25 mm to 50 mm level differences inplaces along the perimeter of Building (House A, B, C and D)and Downtown.

Concern:

Mud jack floor slab. (approx. 3360 square metres)Recommendation:

Camrose - Bethany Meadows (B4660A)S1 STRUCTURAL

Event:

Type Year Cost Priority

Updated: MAR-14

Building (House A, B, C and D) - have concrete grade beams on concrete piles along perimeter and interior concrete pieron concrete pedestal footings. Downtown (basement mechanical room and main floor) - have concrete grade beams on concrete piles along perimeterand interior concrete pier on concrete pedestal footings. Utility building - has concrete grade beams on concrete piles along perimeter.

Building (House A, B, C and D) - have 125 mm concrete slab on grade. Downtown (basement mechanical room and main floor) - have 125mm concrete slab on grade. Utility building - has 125mm concrete slab on grade.

Page 6: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 6 of 45

A2020 Basement Walls (& Crawl Space)*

B1010.01 Floor Structural Frame (Building Frame)*

B1010.02 Structural Interior Walls Supporting Floors (or Roof)*

B1010.03 Floor Decks, Slabs, and Toppings*

B1010.06 Ramps: Exterior*

3 - Marginal

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

0

0

0

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Repair concrete foundation walls. (approx. 10square metres)

Repair 2014 $5,000 High

Water leaks through cracks of concrete foundation walls nearthe electrical cables.

Concern:

Repair concrete foundation walls. (approx. 10 square metres)Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (basement mechanical room) - has concrete foundation walls on strip concrete footing along perimeter andinterior concrete columns on concrete pad footings.

Building (House A, B, C, D and Downtown) - have wood studs at 400 mm o.c.

Building (House A, B, C, D and Downtown) - have HSS columns.

Building (House A, B, C, D and Downtown) - have concrete slab on grade. Utility building - has concrete slab on grade.

House D (northwest corridor exit to parking lot) - has concrete ramp c/w metal pipe handrails.

Page 7: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 7 of 45

B1010.07 Exterior Stairs*

B1010.09 Floor Construction Fireproofing*

B1020.01 Roof Structural Frame*

B1020.03 Roof Decks, Slabs, and Sheathing*

B1020.04 Canopies*

B1020.06 Roof Construction Fireproofing*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

Installed

0

0

0

0

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)

House D (northwest corridor exit to parking lot) - has concrete stair c/w metal pipe handrails.

Building (House A, B, C, D and Downtown) - have concrete slab on grade. Utility building - has concrete slab on grade.

Building (House A, B, C, D and Downtown) - have engineered wood trusses Utility building - has wood trusses

Building (House A, B, C, D and Downtown) - have 13mm sheathing, 38x89 mm wood strapping at 600 mm o.c., 13 mmsheathing, engineered wood trusses. Utility building - has 12 mm gypsum board sheathing, wood trusses. Entrance - asphalt shingles, 12 mm gypsum board sheathing. prefinished metal soffit.

Downtown (west main entrance) - has asphalt shingles, 12 mm gypsum board sheathing. prefinished metal soffit.

Building (House A, B, C, D and Downtown) - have 16 mm gypsum board. Utility building - has 16 mm type X gypsul board.

Page 8: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 8 of 45

B2010.01.06.05 Vinyl Siding**

B2010.01.11 Joint Sealers (caulking): Ext. Wall**

B2010.02.05 Wood Framing: Ext. Wall Const.*

3 - Marginal

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

30

20

0

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Repair vinyl siding. (approx. 500 square metres)

Replace vinyl siding. (approx. 3195 square metres)

Replace joint sealants. (approx. 925 linear metres)

Repair

Lifecycle Replacement

Lifecycle Replacement

2014

2033

2023

$50,000

$319,500

$46,300

Medium

Unassigned

Unassigned

Building has damaged vinyl siding. (approx. 500 squaremetres)

Concern:

Repair vinyl siding. (approx. 500 square metres)Recommendation:

Camrose - Bethany Meadows (B4660A)S2 ENVELOPE

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-14

MAR-14

MAR-14

Building (House A, B, C, D and Downtown) - have vinyl siding. (approx. 3160 square metres) Utility building - has vinyl siding. (approx. 35 square metres)

Building (House A, B, C, D and Downtown) - window and door openings - have joint sealants. (approx. 925 linear metres)

Building (House A, B, C, D and Downtown) - have 38x89 mm wood studs at 400 mm o.c. Utility building - has 38x140 mm woos studs at 400 mm o.c.

Page 9: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 9 of 45

B2010.03 Exterior Wall Vapour Retarders, Air Barriers, and Insulation*

B2010.06 Exterior Louvers, Grilles, and Screens*

B2010.09 Exterior Soffits*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)

Building (House A, B, C, D and Downtown) - have building paper, 50 mm rigid insulation, torched-on membrane. Utility building - has RSI 3.5 batt insulation, vapour barrier.

Building (House A, B, C, D - attics) - have metal louvres.

Building (west main entrance, Porch 101, 130, Porch 201, 230, Porch 301, 330, Porch 401, 430, overhangs) - haveperforated metal soffits.

Page 10: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 10 of 45

B2020.01.01.06 Vinyl, Fibreglass & Plastic Windows**

3 - MarginalRating

2003Installed

40Design Life

MAR-14Updated

Repair PVC windows. (203 windows)

Downtown (West Main Vestibule 501, Waiting 503, MeetingRoom 504, Education Coordinator 508, Visiting Professional509, Social Work 510, Nurse Manager 511, CC Program 512,Server 513, Hair 515, Volunteer 516, Store 520, Chapel Office530, Group Activity Room 532, Office 534, Adapt Comp 535,Equip Workroom 541, Gym/Treat 543, PT Office 544, StoreAssess Workroom 546, OT Office 547, Smoke 551, Café 552,Sun Room 553, Nursing Office 554, Housekeeping 566,Maintenance 567, Maintenance Office 568, FamilyRoom/Kitchen 569, Corridors) - windows fail to close properly.(approx. 62 windows) House A (Activity/Dining 102, 131, Resident 112, 113, 114,115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144,145, 146, 147, 148, 149, 151, Sun Room 121, 150, StaffLounge 572) - windows fail to close properly. (approx. 31windows) House B (Activity/Dining 202, 231, Resident 212, 213, 214,215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244,245, 246, 247, 248, 249, 251, 252, Sun Room 221, 250,Corridor) - windows fail to close properly. (approx. 31windows) House C (Activity/Dining 302, 331, Resident 312, 313, 314,315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344,345, 346, 347, 348, 349, 351, 352, Sun Room 321, 350,Corridor) - windows fail to close properly. (approx. 31windows) House D (Activity/Dining 403, 440, Resident 415, 416, 417,418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431,452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464,465, Sun Room 429, 466, Corridor) - windows fail to closeproperly. (approx. 48 windows)

Concern:

Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Downtown (West Main Vestibule 501, Waiting 503, Meeting Room 504, Education Coordinator 508, Visiting Professional509, Social Work 510, Nurse Manager 511, CC Program 512, Server 513, Hair 515, Volunteer 516, Store 520, ChapelOffice 530, Group Activity Room 532, Office 534, Adapt Comp 535, Equip Workroom 541, Gym/Treat 543, PT Office 544,Store Assess Workroom 546, OT Office 547, Smoke 551, Café 552, Sun Room 553, Nursing Office 554, Housekeeping566, Maintenance 567, Maintenance Office 568, Family Room/Kitchen 569, Corridors) - have PVC windows c/w awnings.(approx. 62 windows) Downtown (Chapel 523) - has high PVC windows. (5 windows) House A (Activity/Dining 102, 131, Resident 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144,145, 146, 147, 148, 149, 151, Sun Room 121, 150, Staff Lounge 572) - have PVC windows c/w awnings. (approx. 31windows) House B (Activity/Dining 202, 231, Resident 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244,245, 246, 247, 248, 249, 251, 252, Sun Room 221, 250, Corridor) - have PVC windows c/w awnings. (approx. 31windows) House C (Activity/Dining 302, 331, Resident 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344,345, 346, 347, 348, 349, 351, 352, Sun Room 321, 350, Corridor) - have PVC windows c/w awnings. (approx. 31windows) House D (Activity/Dining 403, 440, Resident 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431,452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465, Sun Room 429, 466, Corridor) - have PVC windows c/wawnings. (approx. 48 windows) Utility building - has PVC window c/w awning. (approx. 1 window)

Page 11: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 11 of 45

B2030.01.06 Automatic Entrance Doors**

B2030.01.11 Metal Entrance Door**

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

30

30

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Replace PVC windows. (approx. 209 windows)

Replace automatic entrance doors. (18 doors)

Replace metal entrance door. (1 door)

Repair

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2014

2043

2033

2033

$101,500

$209,000

$180,000

$2,000

Low

Unassigned

Unassigned

Unassigned

Repair PVC windows. (203 windows)

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Event:

Type

Type

Type

Type

Year

Year

Year

Year

Cost

Cost

Cost

Cost

Priority

Priority

Priority

Priority

Updated:

Updated:

Updated:

Updated:

MAR-14

MAR-14

MAR-14

MAR-14

Downtown (West Main Vestibule 501) - has handicapped doors with automatic operators. (2 doors) House A (Porch 101, 130) - have handicapped doors with automatic operators. (4 doors) House B (Porch 201, 230) - have handicapped doors with automatic operators. (4 doors) House C (Porch 301, 330) - have handicapped doors with automatic operators. (4 doors) House D (Porch 401, 430) - have handicapped doors with automatic operators. (4 doors)

Downtown (West Main Vestibule 501) - has painted metal door c/w half clear glass panel and metal door frame. (1 door)

Page 12: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 12 of 45

B2030.02 Exterior Utility Doors**

B2030.03 Large Exterior Special Doors (Overhead)*

B3010.01 Deck Vapour Retarder and Insulation*

B3010.02.01.01 Asphalt Shingles**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

40

0

0

25

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace exterior utility doors. (31 doors)

Replace shingles. (approx. 6960 square metres)

Lifecycle Replacement

Lifecycle Replacement

2043

2028

$31,000

$696,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Downtown (Community Hall 523, 524, Group Activity Room 532, Gym/Treat 543, Café 552, Sun Room 553, SouthCorridor Exit) - have painted metal doors c/w half clear glass panels and metal door frames. (7 doors) Downtown - Recycle 560, Family Room/Kitchen 569 - has metal door and metal frame. (2 doors) House A (Porch 101, 130, Sun Room 121, 150, Corridor to Downtown) - have painted metal doors c/w half clear glasspanels and metal door frames. (5 doors) House B (Porch 201, 230, Sun Room 221, 250, Corridor to Downtown) - have painted metal doors c/w half clear glasspanels and metal door frames. (5 doors) House C (Porch 301, 330, Sun Room 321, 350, Corridor to Downtown) - have painted metal doors c/w half clear glasspanels and metal door frames. (5 doors) House D (Porch 401, 430, Sun Room 429, 466, Northwest Corridor Exit, Corridor to Downtown) - have painted metaldoors c/w half clear glass panels and metal door frames. (6 doors) Utility Building - has metal door and metal frame. (1 door)

Downtown (Dock Break 561) - has power operated metal sectional overhead door. Utility building - has metal sectional overhead door.

Building (House A, B, C, D and Downtown) - have 100 mm rigid insulation and torched-on membrane. Utility building - has RSI 7 batt insulation and poly vapour barrier.

Building (House A, B, C, D and Downtown) - have asphalt shingles. (approx. 6870 square metres) Utility building - has asphalt shingles. (approx. 45 square metres) Downtown (west main entrance canopy)- has asphalt shingles. (approx. 45 square metres)

Page 13: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 13 of 45

B3010.08.02 Metal Gutters and Downspouts**

4 - AcceptableRating

2003Installed

30Design Life

MAR-14Updated

Replace gutters and downspouts. (approx. 3360linear metres)

Lifecycle Replacement 2033 $168,000 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Building and Utility building - have metal gutters and downspouts. (approx. 3360 linear metres)

Page 14: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 14 of 45

C1010.01 Interior Fixed Partitions*

C1010.03 Interior Operable Folding Panel Partitions**

C1010.05 Interior Windows*

C1010.07 Interior Partition Firestopping*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

0

30

0

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace operable folding partitions. (3 partitions)

Lifecycle Replacement 2033 $15,000 Unassigned

Camrose - Bethany Meadows (B4660A)S3 INTERIOR

Event:

Type Year Cost Priority

Updated: MAR-14

Building - has steel studs c/w 70 sound attenulation batt insulation and gypsum boards on both sides. Building - has concrete block fire walls.

Downtown (Chapel 523, Community Hall/Chapel Expansion 525) - have accordion wood folding partitions. (3 partitions)

Downtown (Store 520, Museum 521, Community Hall/Chapel Expansion 525, Sun Room 553) - have wood framedwindows. House A (Porch 101, 130) - have wood framed windows. House B (Porch 201, 230) - have wood framed windows. House C (Porch 301, 330) - have wood framed windows. House D (Porch 401, 430) - have wood framed windows.

Building - has steel studs c/w gypsum boards on both sides. Building - has concrete block fire walls.

Page 15: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 15 of 45

C1020.01 Interior Swinging Doors (& Hardware)*

3 - MarginalRating

2003Installed

0Design Life

MAR-14Updated

Replace wood doors and frames. (approx. 186doors)

Failure Replacement 2014 $186,000 High

House A - Resident 112, 113, 114, 115, 116, 117, 118, 119,120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149,151, Resident Bathroom 112, 113, 114, 115, 116, 117, 118,119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148,149, 151 - have damaged wood doors and frames and doorsdo not open and close properly. (42 doors) House B - Resident 212, 213, 214, 215, 216, 217, 218, 219,220, 222, 223, 241, 242, 243, 244, 245, 246, 247, 248, 249,251, 252, Resident Bathroom 212, 213, 214, 215, 216, 217,218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247,248, 249, 251, 252 - have damaged wood doors and framesand frames and doors do not open and close properly. (44doors) House C - Resident 312, 313, 314, 315, 316, 317, 318, 319,320, 322, 323, 341, 342, 343, 344, 345, 346, 347, 348, 349,351, 352, Resident Bathroom 312, 313, 314, 315, 316, 317,318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347,348, 349, 351, 352 - have damaged wood doors and framesand frames and doors do not open and close properly. (44doors) House D - Resident 415, 416, 417, 418, 419, 420, 421, 422,423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456,457, 458, 459, 460, 462, 463, 464, 465, Resident Bathroom415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427,428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460,462, 463, 464, 465 - have damaged wood doors and framesand frames and doors do not open and close properly. (56doors)

Concern:

Replace wood doors and frames. (approx. 186 doors)Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Building - has wood doors and metal frames.

Page 16: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 16 of 45

C1020.03 Interior Fire Doors*

C1020.04 Interior Sliding and Folding Doors*

C1020.06 Interior Gates*

4 - Acceptable

3 - Marginal

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace wood pocket doors. (8 doors)

Failure Replacement 2014 $8,000 Low

House A (Sun Room 121, 150) - have damaged pocket wooddoors. (2 doors) House B (Sun Room 221, 250) - have damaged pocket wooddoors. (2 doors) House C (Sun Room 321, 350) - have damaged pocket wooddoors. (2 doors) House D (Sun Room 429, 466) - have damaged pocket wooddoors. (2 doors)

Concern:

Replace wood pocket doors. (8 doors)Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (Dock Break 561 to Mechanical Room) - has 1.5 hour fire rated metal door and metal frame. Downtown (Clean Hold 557, Soil Hold 559, Maintenance 567, Maintenance Office 568) - have metal doors and metalframes. House A (Corridor to Downtown) - has 1.5 hour fire rated metal doors and metal frame. House B (Corridor to Downtown) - has 1.5 hour fire rated metal doors and metal frame. House C (Corridor to Downtown) - has 1.5 hour fire rated metal doors and metal frame. House D (Corridor to Downtown) - has 1.5 hour fire rated metal doors and metal frame.

Downtown (Reception 207) - has aluminum sliding and folding shutter c/w open grilles and track. House A (Sun Room 121, 150) - have pocket wood doors. (2 doors) House B (Sun Room 221, 250) - have pocket wood doors. (2 doors) House C (Sun Room 321, 350) - have pocket wood doors. (2 doors) House D (Sun Room 429, 466) - have pocket wood doors. (2 doors)

Downtown (Materials Management 564) - has chain link fence and gate.

Page 17: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 17 of 45

C1030.01 Visual Display Boards**

C1030.02 Fabricated Compartments (Toilets/Showers)**

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

20

30

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Replace visual display boards. (approx. 32 boards)

Replace jacuzzis and shower compartments. (8jacuzzis and 11 compartments)

Lifecycle Replacement

Lifecycle Replacement

2023

2033

$32,000

$13,500

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Downtown (Visiting Professional 509, Nurse Manager 511) - has 1 whiteboard and 1 tackboard. Downtown (Volunteer 516, Chapel Office 530, Nursing Office 554, Family Room/Kitchen 569) - have 4 tackboards. Downtown (Office 534, Store Assess Workroom 546) - has 5 whiteboards. Downtown (PT Office 544, Maintenance Office 568) - have 2 whiteboards and 2 tackboards. House A (Living 104, 133, Soil Storage 210, Staff Lounge 572) - have 3 whiteboards and 4 tackboards. House B (Activity/Dining 202, 231) - have 2 whiteboards and 2 tackboards. House C (Activity/Dining 302, 331) - have 1 whiteboard and 2 tackboards. House D (Living 404, Sun Room 429) - have 2 whiteboards and 1 tackboard.

House A (Tub Room 108, 137) - have jacuzzis. (2 jacuzzis) House A (Staff Washroom 127, 154, Male Locker Bathroom 570, Female Locker Bathroom 571) - have prefinished glassshower compartments. (4 compartments) House B (Tub Room 208, 237) - have jacuzzis. (2 jacuzzis) House B (Staff Washroom 227, 255) - have prefinished glass shower compartments. (2 compartments) House C (Tub Room 308, 337) - have jacuzzis. (2 jacuzzis) House C (Staff Washroom 327, 356) - have prefinished glass shower compartments. (2 compartments) House D (Tub Room 409, 446) - have jacuzzis. (2 jacuzzis) House D (Staff Washroom 437) - has prefinished glass shower compartment. (1 compartment)

Page 18: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 18 of 45

C1030.05 Wall and Corner Guards*

C1030.08 Interior Identifying Devices*

C1030.10 Lockers**

C1030.12 Storage Shelving*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

0

0

30

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace lockers. (approx. 18 lockers)

Lifecycle Replacement 2033 $9,000 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (Corridors) - have wood chair rails. House A (Corridors, Resident 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147,148, 149, 151) - have wood chair rails. House B (Corridors, Resident 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247,248, 249, 251, 252) - have wood chair rails. House C (Corridors, Resident 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347,348, 349, 351, 352) - have wood chair rails. House D (Corridors, Resident 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454,455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have wood chair rails.

Building - all rooms have interior identifying devices.

House A (Male Locker 570) - has prefinished single tier metal lockers. (9 lockers) House A (Female Locker 571) - has prefinished double tier metal lockers. (9 lockers)

Downtown (Materials Management 564) - has wood shelves. Downtown (basement mechanical room) - has metal shelves. House A (Pantry 155) - has metal shelves. House B (Pantry 255) - has metal shelves.

Page 19: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 19 of 45

C1030.14 Toilet, Bath, and Laundry Accessories*

C1030.17 Other Fittings* - Hooks

C1030.17 Other Fittings* - Mirrors

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

0

0

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)

Downtown (Staff Washroom 517, Public Washroom 518, 519, 550, Gym/Treat Washroom 542) - have toilet accessories.House A (Staff Washroom 127, 154, Resident Bathroom 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141,142, 143, 144, 145, 146, 147, 148, 149, 151, Male Locker Bathroom 570, Female Locker Bathroom 571) - have toiletaccessories. House A (Tub Room 108, 137) - have bathtub accessories. House A (Staff Washroom 127, 154, Resident Bathroom 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141,142, 143, 144, 145, 146, 147, 148, 149, 151, Male Locker Bathroom 570, Female Locker Bathroom 571) - have showeraccessories. House B (Staff Washroom 227, 255, Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241,242, 243, 244, 245, 246, 247, 248, 249, 251, 252) - have toilet accessories. House B (Tub Room 208, 237) - have tub accessories. House B (Staff Washroom 227, 255, Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241,242, 243, 244, 245, 246, 247, 248, 249, 251, 252) - have shower accessories. House C (Staff Washroom 327, 356, Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341,342, 343, 344, 345, 346, 347, 348, 349, 351, 352) - have toilet accessories. House C (Tub Room 308, 337) - have tub accessories. House C (Staff Washroom 327, 356, Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341,342, 343, 344, 345, 346, 347, 348, 349, 351, 352) - have shower accessories. House D (Staff Washroom 437, Patient Washroom 408, 445, Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422,423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have toiletaccessories. House D (Tub Room 409, 446) - have tub accessories. House D (Staff Washroom 437, Tub Room 409, 446, Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422, 423,425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have showeraccessories.

Downtown (Dock Break 561) - has coat hooks. House A (Janitor Storage 209) - has coat hooks.

Downtown (Hair 515) - has mirrors. House D (Activity/Dining 403) - has mirror.

Page 20: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 20 of 45

C2010 Stair Construction*

C2020.08 Stair Railings and Balustrades*

C3010.06 Tile Wall Finishes**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

0

40

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace tile wall finishes. (approx. 565 squaremetres)

Lifecycle Replacement 2043 $56,500 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

House A (Soil Storage 210 to Attic) - has metal ship ladder c/w metal railings. House B (Soil Storage 210 to Attic) - has metal ship ladder c/w metal railings. House C (Soil Storage 310 to Attic) - has metal ship ladder c/w metal railings. House D (Storage 412 to Attic) - has metal ship ladder c/w metal railings. Downtown (Materials Management 564 to Attic) - has metal ship ladder c/w metal railings. Downtown (Dock Break 561 to Mechanical Room) - has concrete stair c/w metal pipe railings.

House A (Soil Storage 210 to Attic) - has metal ship ladder c/w metal railings. House B (Soil Storage 210 to Attic) - has metal ship ladder c/w metal railings. House C (Soil Storage 310 to Attic) - has metal ship ladder c/w metal railings. House D (Storage 412 to Attic) - has metal ship ladder c/w metal railings. Downtown (Materials Management 564 to Attic) - has metal ship ladder c/w metal railings. Downtown (Dock Break 561 to Mechanical Room) - has concrete stair c/w metal pipe railings.

House A (Tub Room 108, 137, Resident Shower 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143,144, 145, 146, 147, 148, 149, 151) - have ceramic wall tiles. (approx. 125 square metres) House A (Soil Storage 210, 139) - have ceramic wall tiles behind sinks. (approx. 5 square metres) House B (Tub Room 208, 237, Resident Shower 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243,244, 245, 246, 247, 248, 249, 251, 252) - have ceramic wall tiles. (approx. 130 square metres) House B (Soil Storage 210, 239) - have ceramic wall tiles behind sinks. (approx. 5 square metres) House C (Tub Room 308, 337, Resident Shower 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343,344, 345, 346, 347, 348, 349, 351, 352) - have ceramic wall tiles. (approx. 130 square metres) House C (Soil Storage 310, 339) - have ceramic wall tiles behind sinks. (approx. 5 square metres) House D (Tub Room 409, 446, Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430,431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have ceramic wall tiles. (approx. 160 squaremetres) House D (Soil Housekeeping 410, 447) - have ceramic wall tiles behind sinks. (approx. 5 square metres)

Page 21: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 21 of 45

C3010.11 Interior Wall Painting*

C3020.01.02 Painted Concrete Floor Finishes*

3 - Marginal

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

0

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Repair and repaint gypsum wall boards. (approx.500 square metres)

Repair 2014 $25,000 High

Due to movement of concrete slab on grade, gypsum wallboards have cracks throughout the building.

Concern:

Repair and repaint gypsum wall boards. (approx. 500 squaremetres)

Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Building - has painted gypsum board walls. Building - has painted concrete block fire walls.

Downtown (Clean Hold 557, Soil Hold 559, Recycle 560, Dock Break 561, Loading Dock 562, Materials Management564, Housekeeping 566, Maintenance 567, Maintenance Office 568) - have concrete floor. Downtown (basement mechanical room) - has concrete floor.

Page 22: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 22 of 45

C3020.07 Resilient Flooring**

4 - AcceptableRating

2003Installed

20Design Life

MAR-14Updated

Replace resilient flooring. (approx. 6110 squaremetres)

Lifecycle Replacement 2023 $611,000 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (west Main Vestibule 501, Waiting 503, Meeting Room 504, Hair 515, Store 520, Museum 521, CommunityHall 523, 524, Community Hall/Chapel Expansion 525, Storage 527, Storage 531, Group Activity Room 532, Adapt Comp535, Equip Workroom 541, Gym/Treat 543, PT Treat Plinth 545, Store Assess Workroom 546, OT Office 547, Sack 548,Smoke 551, Café 552, Sun Room 553, Nursing Office 554, Storage 555, Family Room/Kitchen 569, Corridors, StaffWashroom 517, Public Washroom 518, 519, 550, Gym/Treat Washroom 542) - have sheet vinyl flooring. (approx. 890square metres) House A (Porch 101, 130, Activity/Dining 102, 131, Kitchen 103, 132, Living 104, 133, Resident 112, 113, 114, 115, 116,117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149, 151, Soil 125, Laundry 126, 153, Pantry 128,155, Storage 129, Male Locker 570, Female Locker 571, Janitor Storage 209, 138, Soil Storage 210, 139, Storage 311,140, Corridors, Staff Washroom 127, 154, Tub Room 108, 137, Resident Bathroom 112, 113, 114, 115, 116, 117, 118,119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149, 151, Male Locker Bathroom 570, Female LockerBathroom 571) - have sheet vinyl flooring. (approx. 1150 square metres) House B (Porch 201, 230, Activity/Dining 202, 231, Kitchen 203, 232, Living 204, 233, Resident 212, 213, 214, 215, 216,217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247, 248, 249, 251, 252, Soil 225, Laundry 226, 254, Pantry228, 255, Storage 229, Janitor Storage 209, 238, Soil Storage 210, 239, Storage 311, 240, Electrical 540, Corridors, StaffWashroom 227, 255, Tub Room 208, 237, Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223,241, 242, 243, 244, 245, 246, 247, 248, 249, 251, 252) - have sheet vinyl flooring. (approx. 1175 square metres) House C (Porch 301, 330, Activity/Dining 302, 331, Kitchen 303, 332, Living 304, 333, Resident 312, 313, 314, 315, 316,317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347, 348, 349, 351, 352, Soil 325, Laundry 326, 354, Pantry328, 355, Storage 329, Janitor Storage 309, 338, Soil Storage 310, 339, Storage 311, 340, Electrical 538, Corridors, StaffWashroom 327, 356, Tub Room 308, 337, Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323,341, 342, 343, 344, 345, 346, 347, 348, 349, 351, 352) - have sheet vinyl flooring. (approx. 1175 square metres) House D (Porch 401, 430, Activity/Dining 403, 440, Kitchen 402, 439, Living 404, 438, Resident 415, 416, 417, 418, 419,420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465, Soil433, Laundry 434, 470, Pantry 435, 477, Storage 436, Janitor Storage 411, 448, Soil Housekeeping 410, 447, Storage412, 450, Electrical 506.1, Corridors, Staff Washroom 437, Patient Washroom 408, 445, Tub Room 409, 446, ResidentBathroom 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458,459, 460, 462, 463, 464, 465) - have sheet vinyl flooring. (approx. 1720 square metres)

Page 23: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 23 of 45

C3020.08 Carpet Flooring**

C3030.01 Concrete Ceiling Finishes (Unpainted)*

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

15

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Replace carpet flooring. (approx. 310 squaremetres)

Lifecycle Replacement 2018 $31,000 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (Reception 207, Education Coordinator 508, Visiting Professional 509, Social Work 510, Nurse Manager 511,CC Program 512, Server 513, Work/Mail 514, Volunteer 516, Chapel 523, Chapel Office 530, Office 534, PT Office 544) -have carpet flooring. (approx. 150 square metres) House A (Sun Room 121, 150, Staff Lounge 572) - have carpet flooring. (approx. 70 square metres) House B (Sun Room 221, 250) - have carpet flooring. (approx. 30 square metres) House C (Sun Room 321, 350) - have carpet flooring. (approx. 30 square metres) House D (Sun Room 429, 466) - have carpet flooring. (approx. 30 square metres)

Downtown (basement mechanical room) - has concrete ceiling.

Page 24: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 24 of 45

C3030.07 Interior Ceiling Painting*

D1090 Other Conveying Systems* - Hoist

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

0

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Camrose - Bethany Meadows (B4660A)

Downtown (Waiting 503, Reception 207, Education Coordinator 508, Visiting Professional 509, Social Work 510, NurseManager 511, CC Program 512, Server 513, Work/Mail 514, Hair 515, Volunteer 516, Store 520, Museum 521, Chapel523, Community Hall 523, 524, Community Hall/Chapel Expansion 525, Chapel Office 530, Storage 531, Group ActivityRoom 532, Office 534, Adapt Comp 535, Equip Workroom 541, Gym/Treat 543, PT Treat Plinth 545, PT Office 544,Store Assess Workroom 546, OT Office 547, Sack 548, Smoke 551, Café 552, Sun Room 553, Nursing Office 554,Storage 555, Family Room/Kitchen 569, Corridors - have textured ceiling finish. Downtown - Main Vestibule 501, Meeting Room 504, Storage 527, Staff Washroom 517, Public Washroom 518, 519,550, Gym/Treat Washroom 542, Clean Hold 557, Soil Hold 559, Recycle 560, Dock Break 561, Loading Dock 562,Materials Management 564, Housekeeping 566, Maintenance 567, Maintenance Office 568) - have painted gypsumboard ceiling finish. House A (Activity/Dining 102, 131, Kitchen 103, 132, Living 104, 133, Resident 112, 113, 114, 115, 116, 117, 118, 119,120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149, 151, Staff Lounge 572, Corridors) - have textured ceilingfinish. House A (Porch 101, 130, Sun Room 121, 150, Soil 125, Laundry 126, 153, Pantry 128, 155, Storage 129, Male Locker570, Female Locker 571, Janitor Storage 209, 138, Soil Storage 210, 139, Storage 311, 140, Staff Washroom 127, 154, Tub Room 108, 137, Resident Bathroom 112, 113,114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149, 151, Male Locker Bathroom570, Female Locker Bathroom 571) - have painted gypsum board ceiling finish. House B (Activity/Dining 202, 231, Kitchen 203, 232, Living 204, 233, Resident 212, 213, 214, 215, 216, 217, 218, 219,220, 222, 223, 241, 242, 243, 244, 245, 246, 247, 248, 249, 251, 252, Corridors) - have textured ceiling finish. House B (Porch 201, 230, Sun Room 221, 250, Soil 225, Laundry 226, 254, Pantry 228, 255, Storage 229, JanitorStorage 209, 238, Soil Storage 210, 239, Storage 311, 240, Electrical 540, Staff Washroom 227, 255, Tub Room 208,237, Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247, 248,249, 251, 252) - have painted gypsum board ceiling finish. House C (Activity/Dining 302, 331, Kitchen 303, 332, Living 304, 333, Resident 312, 313, 314, 315, 316, 317, 318, 319,320, 322, 323, 341, 342, 343, 344, 345, 346, 347, 348, 349, 351, 352, Corridors) - have textured ceiling finish. House C (Porch 301, 330, Sun Room 321, 350, Soil 325, Laundry 326, 354, Pantry 328, 355, Storage 329, JanitorStorage 309, 338, Soil Storage 310, 339, Storage 311, 340, Electrical 538, Staff Washroom 327, 356, Tub Room 308,337, Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347, 348,349, 351, 352) - have painted gypsum board ceiling finish. House D (Activity/Dining 403, 440, Kitchen 402, 439, Living 404, 438, Resident 415, 416, 417, 418, 419, 420, 421, 422,423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465, Corridors) - havetextured ceiling finish. House D (Porch 401, 430, Sun Room 429, 466, Soil 433, Laundry 434, 470, Pantry 435, 477, Storage 436, JanitorStorage 411, 448, Soil Housekeeping 410, 447, Storage 412, 450, Electrical 506.1, Staff Washroom 437, PatientWashroom 408, 445, Tub Room 409, 446, Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426,427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have painted gypsum board ceilingfinish.

Downtown (Dock Break 561 to Mechanical Room) - has 1/2 HP hoist.

Page 25: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 25 of 45

D2010.04 Sinks**

D2010.05 Showers**

D2010.06 Bathtubs**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

30

30

30

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace 83 stainless steel, 9 janitor & 1 hairdresser sinks.

Replace 101 Shower stations.

Replace 8 Assisted Bathtubs

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2033

2033

2033

$150,000

$350,000

$250,000

Unassigned

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)S4 MECHANICAL

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-14

MAR-14

MAR-14

Various single and two compartment stainless steel sinks, hairdressing sinks, janitor mop sinks throughout the facility.

Various assisted shower stalls with pressure balanced valves and telephone heads on slide rails- located in assistedbathrooms. Conventional shower stalls with acrylic enclosures, pressure balanced valves and conventional heads -located in resident rooms and staff rooms throughout building.

Assisted bathtubs c/w integral chair lifts in assisted bath rooms.

Page 26: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 26 of 45

D2010.10 Washroom Fixtures (WC, Lav, Urnl)**

D2020.01.01 Pipes and Tubes: Domestic Water*

D2020.01.02 Valves: Domestic Water**

4 - Acceptable

4 - Acceptable

3 - Marginal

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

35

0

40

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace 101 Lavatories & 101 water closets.

Replace or provide 120 valves.

Lifecycle Replacement

Failure Replacement

2038

2014

$225,000

$60,000

Unassigned

Medium

All isolation valves should be replaced. Valves are leaking orsticking

Concern:

Replace existing isolation valves as required for each group offixtures.

Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Vitreous china, countertop Lavatories c/w two handle & sensor faucets. Floor mounted, vitreous china water closets, open front seat with flush valves and flush tanks.

Mainly insulated copper piping throughout the building. Solder joints.

Various gate and 1/4 turn ball valves. Mainly isolation service throughout the building.

Page 27: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 27 of 45

D2020.01.03 Piping Specialties (Backflow Preventers)**

D2020.02.06 Domestic Water Heaters**

D2020.03 Water Supply Insulation: Domestic*

D2030.01 Waste and Vent Piping*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

20

20

0

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace 3 Backflow Preventors

Replace 2 domestic water heating boilers, storagetanks and recirculation pumps.

Lifecycle Replacement

Lifecycle Replacement

2023

2023

$15,000

$70,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Backflow prevention installed on main service, fire line and boiler make-up water. Vacuum breakers on N.F.H.B. and mop sinks.

Two RBI model 33HW14702E2SSSS hot water boilers complete with safety and operating controls. System is located inthe main mechanical room. Input heating capacity: 1314.2 MBH each. Boilers serve domestic water systems. There are two vertical domestic hot water storage tanks for the facility, providing (40 deg.C) domestic hot water forgeneral use. Includes domestic hot water recirculation pumps serving the 40 C system.

Majority of water lines insulated with preformed fibreglass insulation. Canvas jacketting in exposed locations.

Mainly Cast iron and PVC sewer lines throughout.

Page 28: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 28 of 45

D2030.02.04 Floor Drains*

D2030.03 Waste Piping Equipment*

D2040.01 Rain Water Drainage Piping Systems*

D3020.02.01 Heating Boilers and Accessories: H.W.**

D3020.02.02 Chimneys (& Comb. Air): H.W. Boiler**

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

0

0

0

35

35

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Replace 2 Hot Water heating boilers.

Replace 2 Chimneys (B.O.E.: 6 M high)

Lifecycle Replacement

Lifecycle Replacement

2038

2038

$150,000

$15,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Mainly conventional floor drains throughout building - located in Mechanical rooms, washrooms and service areas.

Hair trap below hair dressing sink.

Rain water collection via eaves troughs and storm water piping is discharged to grade around the building perimeter.

Heating system consists of two natural gas fired boilers, RBI 8800 Series, model 33HB36002E2ASSSS. Input heatingcapacity each: 3,240 MBH, complete with operational and safety controls.

Combustion air provided by an insulated sheet metal duct, terminated in an `arctic trap`. Galvanized steel vents serving Boilers up through the roof complete with raincaps.

Page 29: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 29 of 45

D3020.02.03 Water Treatment: H. W. Boiler*

D3030.06.02 Refrigerant Condensing Units**

D3040.01.01 Air Handling Units: Air Distribution**

D3040.01.04 Ducts: Air Distribution*

D3040.01.07 Air Outlets & Inlets: Air Distribution*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

0

25

30

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Replace 9 Condensing units

Replace 9 Air Handling Units.

Lifecycle Replacement

Lifecycle Replacement

2028

2033

$100,000

$300,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Chemical pot feeders in the hydronic loop. Regular treatment program.

Trane Air cooled condensing units located on the ground at various locations around the perimeter of the building.Various model numbers. Condensing units are connected to DX coils in the make up air units serving each of the four"Houses" as well as the "Downtown" building

Engineered Air indirect fired air handling units located throughout the building in the various attic spaces. 2 Units per"house". One unit in the basement Mechanical room below the "Downtown" area. Units are complete with fans, filters,heat exchanger section, DX cooling coil.

Overhead ductwork distribution in attic spaces, to SMACNA standards. Constant volume air distribution to grilles anddiffusers.

Combination of wall mounted grilles and ceiling square diffusers for supply air application. Egg crate type grilles for return, transfer and exhaust air.

Page 30: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 30 of 45

D3040.03.01 Hot Water Distribution Systems**

D3040.04.01 Fans: Exhaust**

D3040.04.03 Ducts: Exhaust*

D3040.04.05 Air Outlets and Inlets: Exhaust*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

40

30

0

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace entire building Hot Water Distributionsystem (B.O.E.: 6780 Sq.M. GFA)

Replace 8 axial exhaust fans & 4 ceiling exhaustfans.

Lifecycle Replacement

Lifecycle Replacement

2043

2033

$500,000

$30,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Reverse return copper type L and steel distribution to ceiling mounted radiant heating panels, unit heaters and Forceflows. Primary hot water heating pumps: Armstrong 3x3x8 4380, 12.3 L/sec @ 12.24 M head, vertical in-line mountedcentrifugal.

Penn axial exhaust fans located in the attics of each "house" and connected to the various washroom exhaust grilles.Models and capacities are unknown. Ceiling exhaust fans serving the "downtown" area washrooms.

Low velocity galvanized steel ductwork connecting fans to grilles and air outlets throughout. Ducts are partially thermallyinsulated.

Various eggcrate exhaust grilles throughout building. Ceiling & sidewall.

Page 31: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 31 of 45

D3050.05.02 Fan Coil Units**

D3050.05.06 Unit Heaters**

D3060.02.01 Electric and Electronic Controls**

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

30

30

30

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace 15 Force flow units

Replace 8 Unit Heaters.

Replace Force Flow and uNit Heater controls (23points)

Lifecycle Replacement

Lifecycle Replacement

Lifecycle Replacement

2033

2033

2033

$37,500

$12,000

$15,000

Unassigned

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Event:

Type

Type

Type

Year

Year

Year

Cost

Cost

Cost

Priority

Priority

Priority

Updated:

Updated:

Updated:

MAR-14

MAR-14

MAR-14

Hot water force flow units, located mainly in entrance vestibules, fully recessed.

Horizontal discharge hot water unit heaters. Located mainly in Mechanical rooms, Loading docks and Service areas.

Electrical control of force flow heaters and unit heaters. Line voltage thermostats.

Page 32: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 32 of 45

D3060.02.05 Building Systems Controls (BMCS, EMCS)**

D4010 Sprinklers: Fire Protection*

D4030.01 Fire Extinguisher, Cabinets and Accessories*

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

20

0

0

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace Building Management System (B.O.E.:6780 Sq.M. GFA)

Upgrade BMCS controller, including the necessarycircuit boards

Lifecycle Replacement

Operating Efficiency Upgrade

2023

2014

$125,000

$15,000

Unassigned

Low

The controller does not have the capacity to add a program orupgrade software, which is currently required. The currentcontroller would have to be totally reprogrammed to do this,and will cost as much as an upgrade. The upgrade will alsoallow for future expansion to the system, and will allow forremote access to the system

Concern:

Upgrade 1 controller including circuit boards to allow forincreased capacity.

Recommendation:

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Johnson Controls Invensys digital programmable BMCS - controls Boilers, pumps, air handling units, radiant heatingpanels.

Generally Wet type sprinkler system throughout facility with Dry pipe type in the Attic spaces and Glycol legs in theEntrances.

Fire extinguishers located throughout facility: multi purpose dry chemical. On wall mounting brackets and in cabinets. Inspected as per maintenance schedule.

Page 33: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 33 of 45

D5010.01.02 Main Electrical Transformers (Utility Owned)*

D5010.02 Secondary Electrical Transformers (Interior)**

D5010.03 Main Electrical Switchboards (Main Distribution)**

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

40

40

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace Interior transformers. (5 transformers)

Replace main electrical switchoard. (1-600A, 600Vswitchboard)

Lifecycle Replacement

Lifecycle Replacement

2043

2043

$75,000

$100,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)S5 ELECTRICAL

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

The facility is serviced from a pad mounted utility owned transformer located in the north-east corner of the property.

Dry type step down transformers have been provided to step down the voltage from the incoming 600V to 120/208V, 3phase, 4 wire for general use. The transformers are located in each of the sub electrical rooms of each building. Onetransformer has been provided in the parking lot for the parking lot car plug-in receptacles.

A Siemens main distribution centre has been provided in the main electrical room, located in the basement of thedowntown building. The main distribution is rated at 600A, 600V, 3 phase, 4 wire and is complete with a 600A, 3P mainbreaker and a distribution centre, that is complete with feeder breakers. There is ample spare capacity in the distributioncentre and all breakers are adequately identified.

Page 34: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 34 of 45

D5010.05 Electrical Branch Circuit Panelboards (Secondary Distribution)**

D5010.07.02 Motor Starters and Accessories**

D5020.01 Electrical Branch Wiring*

D5020.02.01 Lighting Accessories: Interior (Lighting Controls)*

5 - Good

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

30

30

0

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Replace electrical branch circuit panleboards (43panels)

Replace motor starters. (18 starters)

Lifecycle Replacement

Lifecycle Replacement

2033

2033

$50,000

$20,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Panel boards have been provided in each of the four buildings. Panels are located in the sub electrical rooms of thebuildings and are fed from the transformer in the room. The panel boards feed power to the suites and the common areasof the buildings. On average, the panels are approximately 80% full.

Individual wall mounted starters have been provided for motor control. The starters are located adjacent to the equipmentbeing controlled and are complete with hand-off-auto selector switches and pilot lights.

Branch wiring is copper. In the mechanical room it is installed in conduit and elsewhere, (wood frame construction), it isnon-metallic sheathed, NMD-7.

All lighting is controlled by line voltage switches. Each area is locally controlled. Corridor lights are time clock controlled.

Page 35: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 35 of 45

D5020.02.02.02 Interior Fluorescent Fixtures**

D5020.02.03.02 Emergency Lighting Battery Packs**

D5020.02.03.03 Exit Signs*

D5020.03.01.03 Exterior Metal Halide Fixtures*

D5020.03.02 Lighting Accessories: Exterior (Lighting Controls)*

5 - Good

5 - Good

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

30

20

0

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Replace interior fluorescent fixtures. (650 fixtures)

Replace emergency lighting battery packs. (35packs)

Lifecycle Replacement

Lifecycle Replacement

2033

2023

$150,000

$35,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Lighting is provided by fluorescent fixtures. Common areas have been provided with surface mounted fixtures which arecomplete with T8 lamps. In the residents rooms, the fixtures are complete with compact fluorescent lamps.

Emergency lighting is provided by emergency battery packs located in each house. All paths and points of egress are welladequately illuminated.

Exit signs of the LED type have been provided at each point of egress.

Wall mounted fixtures have been provided around the outside of each house.

Exterior lighting is controlled by photo-cell.

Page 36: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 36 of 45

D5030.01 Detection and Fire Alarm**

D5030.04.01 Telephone Systems*

D5030.04.03 Call Systems**

D5030.04.04 Data Systems*

5 - Good

5 - Good

5 - Good

5 - Good

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

25

0

25

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Lifecycle Replacement (6780 sq. m. GFA)

Replace call system (6780 Sq,m GFA)

Lifecycle Replacement

Lifecycle Replacement

2028

2028

$380,000

$250,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

A Siemens MXL-10 addressable fire alarm system has been provided. It is complete with detection devices, manual pullstations, and audible/visual signal devices. Each building has its own control panel and annunciator and each of thesepanels and annunciators is networked. Systems are networked such that an alarm in one location is annunciated at all theother panels and annunciators. The systems are tested annually and externally monitored.

Telephone service is underground and it terminates on the backboard in the main electrical room. Each resident isresponsible for their own lines and telephone service. A Nortel telephone system has been provided in the administrationarea.

The call system is of the wireless type, and is the product of Spider-Alert. Each resident has been provided with apendant that the resident presses when requiring assistance. Receivers are located throughout the facility and are locatedin the corridors that transmit the signal to the system computer. The system computer is located in the work-storageroom.

Cat 5 data cabling has been provided in the administration area. All offices and reception have been provided with dataoutlets.

Page 37: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 37 of 45

D5030.04.05 Local Area Network Systems*

D5030.06 Television Systems*

5 - Good

5 - Good

Rating

Rating

2003

2003

Installed

Installed

0

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Camrose - Bethany Meadows (B4660A)

Local network is located in the work-storage room within the administration area, and is complete with a wall mountedrack containing patch panels, and switches.

Cable TV service is underground and terminates on the backboard in the main electrical room. A secondary backboardhas been provided in each of the sub electrical room within each building. An antenna system has also been provided thatis available to residents who do not wish to subscribe for cable TV. Antenna cables terminate on the same backboard asthe cable system.

Page 38: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 38 of 45

E1010.05.01 Barber and Beauty Shop Equipment*

E1020.02 Library Equipment*

E1020.05 Audiovisual Equipment*

E1020.07 Laboratory Equipment*

E1020.08 Medical Equipment*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

0

0

0

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION

Downtown (Hair 515) - has barber and beauty shop equipment.

House A (Staff Lounge 572) - has wood book shelves.

Downtown (Community Hall/Chapel Expansion 525) - has projection screen.

House A (Kitchen 103, 132) - have eye wash stations. House B (Kitchen 203, 232) - have eye wash stations. House C (Kitchen 303, 332) - have eye wash stations. House D (Kitchen 402, 439) - have eye wash stations.

Downtown (PT Treat Plinth 545) - has blanket warmer. House A (Resident 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147, 148, 149,151) - have lift rails. House A (Storage 129) - has medical fridge. House B (Storage 229) - has medical fridge. House B (Tub Room 237) - has blanket warmer. House B (Resident 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247, 248, 249,251, 252) - have lift rails. House C (Resident 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347, 348, 349,351, 352) - have lift rails. House D (Resident 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456,457, 458, 459, 460, 462, 463, 464, 465) - have lift rails.

Page 39: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 39 of 45

E1030.03 Loading Dock Equipment*

E1090.04 Residential Equipment*

E2010.02 Fixed Casework** - Millwork

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

2003

2003

2003

Installed

Installed

Installed

0

0

35

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Replace millwork. (approx. 114 linear metres)

Lifecycle Replacement 2038 $114,000 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (Loading Dock 562) - has dock leveler.

Downtown (Social Work 510) - has fridge. Downtown (Equip Workroom 541) - has fridge and microwave. Downtown (Housekeeping 566) - has fridge and cooler. Downtown (Family Room/Kitchen 569) - has fridges, microwave, range and dishwasher. House A (Kitchen 103, 132) - have dishwasher, fridges, microwaves and ranges. House A (Laundry 126) - has washer and dryer. House A (Sun Room 121, Pantry 155) - have fridges. House A (Staff Lounge 572) - has fridge and microwave. House B (Laundry 226) - has washer and dryer. House B (Kitchen 203, 232) - have dishwasher, fridges, microwaves and ranges. House B (Sun Room 221, 250, Pantry 255) - have fridges. House C (Laundry 326) - has washer and dryer. House C (Kitchen 303, 332) - have dishwasher, fridges, microwaves and ranges. House C (Sun Room 350) - has fridge. House D (Laundry 434) - has washer and dryer. House D (Kitchen 402, 439) - have dishwasher, fridges, microwaves and ranges. House D (Sun Room 466) - has fridge.

Downtown (Work/Mail 514, Hair 515, Store 520, Group Activity Room 532, Equip Workroom 541, PT Treat Plinth 545,Store Assess Workroom 546, Sun Room 553, Nursing Office 554, Maintenance 567, Family Room/Kitchen 569) - havemillwork c/w countertops and cupboards. (approx. 70 linear metres) House A (Kitchen 103, 132, Storage 129, Staff Lounge 572) - have millwork c/w countertops and cupboards. (approx. 12linear metres) House B (Kitchen 203, 232, Storage 229) - have millwork c/w countertops and cupboards. (approx. 10 linear metres) House C (Kitchen 303, 332, Storage 329) - have millwork c/w countertops and cupboards. (approx. 10 linear metres) House D (Kitchen 402, 439, Storage 436) - have millwork c/w countertops and cupboards. (approx. 12 linear metres)

Page 40: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 40 of 45

E2010.02 Fixed Casework** - Reception Counters

E2010.02 Fixed Casework** - Vanities

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

35

35

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Replace reception counters. (approx. 3 linearmetres)

Replace vanities. (approx. 112 linear metres)

Lifecycle Replacement

Lifecycle Replacement

2038

2038

$3,000

$112,000

Unassigned

Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Event:

Type

Type

Year

Year

Cost

Cost

Priority

Priority

Updated:

Updated:

MAR-14

MAR-14

Downtown (Reception 207) - has reception counter. (approx. 3 linear metres)

Downtown (Staff Washroom 517, Public Washroom 518, 519, 550, Gym/Treat Washroom 542) - have plastic laminatedvanities. (approx. 8 linear metres) House A (Staff Washroom 127, 154, Resident Bathroom 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141,142, 143, 144, 145, 146, 147, 148, 149, 151, Male Locker Bathroom 570, Female Locker Bathroom 571) - have plasticlaminated vanities. (approx. 25 linear metres) House B (Staff Washroom 227, 255, Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241,242, 243, 244, 245, 246, 247, 248, 249, 251, 252) - have plastic laminated vanities. (approx. 24 linear metres) House C (Staff Washroom 327, 356, Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341,342, 343, 344, 345, 346, 347, 348, 349, 351, 352) - have plastic laminated vanities. (approx. 24 linear metres) House D (Staff Washroom 437, Patient Washroom 408, 445, Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422,423, 425, 426, 427, 428, 430, 431, 452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - have plasticlaminated vanities. (approx. 31 linear metres),

Page 41: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 41 of 45

E2010.03.01 Blinds**

E2010.03.02 Interior Shutters*

4 - Acceptable

4 - Acceptable

Rating

Rating

2003

2003

Installed

Installed

30

0

Design Life

Design Life

MAR-14

MAR-14

Updated

Updated

Replace blinds. (approx. 203 blinds)

Lifecycle Replacement 2033 $81,200 Unassigned

Camrose - Bethany Meadows (B4660A)

Event:

Type Year Cost Priority

Updated: MAR-14

Downtown (West Main Vestibule 501, Waiting 503, Meeting Room 504, Education Coordinator 508, Visiting Professional509, Social Work 510, Nurse Manager 511, CC Program 512, Server 513, Hair 515, Volunteer 516, Store 520, ChapelOffice 530, Group Activity Room 532, Office 534, Adapt Comp 535, Equip Workroom 541, Gym/Treat 543, PT Office 544,Store Assess Workroom 546, OT Office 547, Smoke 551, Café 552, Sun Room 553, Nursing Office 554, Housekeeping566, Maintenance 567, Maintenance Office 568, Family Room/Kitchen 569, Corridors) - have venetian blinds. (approx. 62blinds) House A (Activity/Dining 102, 131, Resident 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144,145, 146, 147, 148, 149, 151, Sun Room 121, 150, Staff Lounge 572) - have venetian blinds. (approx. 31 blinds) House B (Activity/Dining 202, 231, Resident 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244,245, 246, 247, 248, 249, 251, 252, Sun Room 221, 250, Corridor) - have venetian blinds. (approx. 31 blinds) House C (Activity/Dining 302, 331, Resident 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344,345, 346, 347, 348, 349, 351, 352, Sun Room 321, 350, Corridor) - have venetian blinds. (approx. 31 blinds) House D (Activity/Dining 403, 440, Resident 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431,452, 453, 454, 455, 456, 457, 458, 459, 460, 462, 463, 464, 465, Sun Room 429, 466, Corridor) - have venetian blinds.(approx. 48 blinds)

Downtown (Family Room/Kitchen 569) - has aluminum roll-up shutter.

Page 42: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 42 of 45

K4010.01 Barrier Free Route: Parking to Entrance*

K4010.02 Barrier Free Entrances*

K4010.03 Barrier Free Interior Circulation*

K4010.04 Barrier Free Washrooms*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

2003

2003

2003

2003

Installed

Installed

Installed

Installed

0

0

0

0

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)S8 SPECIAL ASSESSMENT

Downtown (Main Vestibule 501 to Parking Lot) - has barrier free route. House D (northwest corridor exit to parking lot) - has concrete ramp c/w metal pipe handrails.

Downtown (West Main Vestibule 501) - has handicapped doors with automatic operators. (2 doors) House A (Porch 101, 130) - have handicapped doors with automatic operators. (4 doors) House B (Porch 201, 230) - have handicapped doors with automatic operators. (4 doors) House C (Porch 301, 330) - have handicapped doors with automatic operators. (4 doors) House D (Porch 401, 430) - have handicapped doors with automatic operators. (4 doors)

Corridors are wide enough for wheelchairs.

Downtown (Public Washroom 518, 550, Gym/Treat Washroom 542) - are handicapped washrooms. House A (Tub Room 108, 137) - have handicapped tubs. House A (Resident Shower 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147,148, 149, 151) - are handicapped showers. House A (Resident Bathroom 112, 113, 114, 115, 116, 117, 118, 119, 120, 122, 123, 141, 142, 143, 144, 145, 146, 147,148, 149, 151) - are handicapped bathrooms. House B (Tub Room 208, 237) - have handicapped tubs. House B (Resident Shower 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247,248, 249, 251, 252) - are handicapped showers. House B (Resident Bathroom 212, 213, 214, 215, 216, 217, 218, 219, 220, 222, 223, 241, 242, 243, 244, 245, 246, 247,248, 249, 251, 252) - are handicapped bathrooms. House C (Tub Room 308, 337) - have handicapped tubs. House C (Resident Shower 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347,348, 349, 351, 352) - are handicapped showers. House C (Resident Bathroom 312, 313, 314, 315, 316, 317, 318, 319, 320, 322, 323, 341, 342, 343, 344, 345, 346, 347,348, 349, 351, 352) - are handicapped bathrooms. House D (Tub Room 409, 446) - have handicapped tubs. House D (Resident Shower 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454,455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - are handicapped showers. House D (Resident Bathroom 415, 416, 417, 418, 419, 420, 421, 422, 423, 425, 426, 427, 428, 430, 431, 452, 453, 454,455, 456, 457, 458, 459, 460, 462, 463, 464, 465) - are handicapped bathrooms.

Page 43: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 43 of 45

K4030.01 Asbestos*

K4030.02 PCBs*

K4030.04 Mould*

K4030.06 Radioactive Compounds*

K4030.07 Ozone Depleting Substances (CFC's, HCFC's, Halon)*

K4030.08 Biohazardous Materials*

K4030.09 Other Hazardous Materials*

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

4 - Acceptable

Rating

Rating

Rating

Rating

Rating

Rating

Rating

2003

2003

2003

2003

2003

2003

2003

Installed

Installed

Installed

Installed

Installed

Installed

Installed

0

0

0

0

0

0

0

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

Design Life

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

MAR-14

Updated

Updated

Updated

Updated

Updated

Updated

Updated

Camrose - Bethany Meadows (B4660A)

No asbestos were observed or reported.

No PCBs were observed or reported.

No mould was observed or reported.

No radioactive compounds were observed or reported.

No Ozone Depleting Substances (CFC's, HCFC's, Halon) were observed or reported.

No biohazardous materials were observed or reported.

No other hazardous materials were observed or reported.

Page 44: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 44 of 45

K5010.01 Site Documentation*

4 - AcceptableRating

2013Installed

0Design Life

MAR-14Updated

Camrose - Bethany Meadows (B4660A)

Prime Consultant Name - Francis Ng Architect Ltd. Date of Site Visit: October 7, 2013 Total building area - 6915.62 square metres Drawing attached - Site Plan.

Site plan.

Page 45: RECAPP Facility Evaluation Report...In common areas, fixtures utilize T8 linear lamps, while in the residents room the fixtures are complete with compact fluorescent lamps. An addressable

Report run on: March 7, 2014 10:48 AM Page 45 of 45

K5010.02 Building Documentation*

4 - AcceptableRating

2013Installed

0Design Life

MAR-14Updated

Camrose - Bethany Meadows (B4660A)

Prime Consultant Name - Francis Ng Architect Ltd. Date of Site Visit: October 7, 2013 Total building area - 6915.62 square metres Drawing attached - Floor Plans.

House A.