rectifier and feeder circuit breaker (dc switchgear)€¦ · • the dcdb shall comply with...

187
Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________ Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-21 Decembert 2015 d) Rectifier and Feeder Circuit Breaker (DC Switchgear): The 1500VDC Switchgear shall be type-tested, similar or better to the existing equipment in LRT Line 2 and in accordance to the standards stated in this PPSP. The equipment to be supplied shall be comprised of the isolator complete with mounting insulator and framework enclosed in a metal-clad enclosure. Bus-bar chamber shall be comprised of main bus bars, termination for connection to the isolator and the adjoining cubicles and the necessary wiring. The DC Switchgear shall support regenerative braking. The DC Switchgear shall consist of the following main components, as a minimum, but not limited to: Circuit breaker Disconnectors (open, closed and ground) Local/Remote indicating light Disconnectors and circuit breaker position indicating lights Push-button for lock-out reset Two-position selector for local maneuver of the circuit breakers and disconectors Two-position key selector for local/remote Voltage presence Indicating light Current and voltage meters Interlocking’s The design shall incorporate safety provisions for workers conducting maintenance of the DC Switchgear. The circuit breaker shall be capable of being closed and tripped manually in the service position. Under manual operation it shall be possible to disconnect the 110VDC control power supply without interfering with the operation of the breaker. The circuit shall be trip-free, track-mounted, electrically-operated, suitable for local and remote control, and shall be provided with operation counters. Each circuit breaker shall have a DC current rating of not less than 4000A. e) Negative Return Panel (NRP) The specification applies to indoor type negative return line panel for connecting the running rail with the negative pole of the rectifier. The proposed NRP shall consist of the following, but not limited to: Manually-operated single pole disconnecting switch Local alarm indication ON/OFF status indication with LEDs for the disconnecting switch

Upload: vantram

Post on 05-Sep-2018

236 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-21 Decembert 2015

d) Rectifier and Feeder Circuit Breaker (DC Switchgear): • The 1500VDC Switchgear shall be type-tested, similar or better to the existing

equipment in LRT Line 2 and in accordance to the standards stated in this PPSP.

• The equipment to be supplied shall be comprised of the isolator complete with mounting insulator and framework enclosed in a metal-clad enclosure. Bus-bar chamber shall be comprised of main bus bars, termination for connection to the isolator and the adjoining cubicles and the necessary wiring.

• The DC Switchgear shall support regenerative braking.

• The DC Switchgear shall consist of the following main components, as a minimum,

but not limited to: Circuit breaker Disconnectors (open, closed and ground) Local/Remote indicating light Disconnectors and circuit breaker position indicating lights Push-button for lock-out reset Two-position selector for local maneuver of the circuit breakers and disconectors Two-position key selector for local/remote Voltage presence Indicating light Current and voltage meters Interlocking’s

• The design shall incorporate safety provisions for workers conducting maintenance of

the DC Switchgear.

• The circuit breaker shall be capable of being closed and tripped manually in the service position.

• Under manual operation it shall be possible to disconnect the 110VDC control power supply without interfering with the operation of the breaker.

• The circuit shall be trip-free, track-mounted, electrically-operated, suitable for local

and remote control, and shall be provided with operation counters.

• Each circuit breaker shall have a DC current rating of not less than 4000A.

e) Negative Return Panel (NRP) • The specification applies to indoor type negative return line panel for connecting the

running rail with the negative pole of the rectifier. • The proposed NRP shall consist of the following, but not limited to: Manually-operated single pole disconnecting switch Local alarm indication ON/OFF status indication with LEDs for the disconnecting switch

Page 2: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-22 Decembert 2015

Interlocking of the disconnecting switch with the circuit breaker of the incoming panel

Shunts for metering

• The design of the new NRP shall be based on the existing panels in Line 2.

f) Auxiliary and Ring (Station) Transformer: • In the Substation, the auxiliary transformers shall be: Dyn11 d0 34.5kV/ 6.6kV 1700kVA/1500kVA

• The ring (station) transformer shall be 6.6kV/480V indoor dry-type distribution

transformers to be used for feeding a supply at 480V for the facilities of the station. Dyn11 6.6kV/480V 630kVA

• The contractor shall provide transformer with 220VAC output for essential equipment

such as telecom, signaling, power and OCS lighting

• The transformers offered shall be complete in all respects with all parts and accessories, of a similar or better standard to the existing equipment on the LRT Line 2 in Substation and Electrical Rooms. All such parts and accessories shall be deemed to be within the work under the Contract whether specifically mentioned or not.

• The transformers shall be designed for minimum losses and maximum efficiency

level.

• The design shall incorporate or provide full provision for safety of all personnel conducting maintenance of the transformers.

• Transformers shall be fitted with a temperature-protection system that allows winding

temperatures to be monitored. • The primary and the secondary windings shall be capable of withstanding a

symmetrical three-phase short-circuit regardless of the tapping selected. • The transformer winding shall be made of copper. The winding shall be designed so

as to facilitate better heat dissipation and withstand mechanical forces. • The windings and connectors of the transformer shall be brazed and suitably

designed, so as to withstand shock which may occur during transport or due to switching and other transient conditions during services.

• A metallic shield shall be provided for the medium-voltage and low-voltage

windings.

Page 3: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-23 Decembert 2015

• A winding temperature indicator with alarm and trip arrangement shall be provided. The device shall have two thresholds (alarm and tripping). Sensors shall be located on the upper part of the secondary windings.

g) Ring (6.6kV) Cabinets and Switchgear:

• The 6.6kV components shall be designed, installed, tested, commissioned and

brought into operation according to the Philippine Electrical Code and applicable standards.

• The Switchgear shall be gas-insulated 6.6kV Switchgear containing triple-pole circuit

breakers similar or better to the existing in Line 2. • The 6.6kV Switchgear shall be complete in all respects with all parts and accessories,

including framework, necessary for efficient operation, maintenance and protection. All such parts and accessories shall be within the work under the Contract whether specifically stated or not.

• The 6.6kV Switchgear shall be designed, installed, tested, commissioned and brought

into operation according to the standards as stated in this PPSP. • The 6.6kV Switchgear shall be designed as indoor-type. • The cubicles shall be capable of withstanding the defined rated capacities (e.g. current

capacity, short-circuit capacity, insulation coordination) without any damage. • The design shall incorporate full provisions for safety of personal performing

maintenance of the Switchgear. • Protection relays for the Switchgear shall be normally mounted on the panel. • The 6.6kV Switchgear shall be equipped with metering instruments. The metering

system required shall be as follows: Ammeters Voltmeter and Digital Power Meter

• The incoming and outgoing 6.6 kV switchgear shall consist of the following main

components, as a minimum, but not limited to: Circuit breaker Disconnectors (open, closed and ground) Local/Remote indicating light Disconnectors and circuit breaker position indicating light Push-button for lock-out reset Two-position selector for local maneuver of the circuit breakers and disconectors Two-position key selector for local/remote Voltage presence Indicating light (220V) Current transformers

Page 4: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-24 Decembert 2015

Voltage transformers Switchgear cubicles Interlocking’s

h) AC Distribution Board (ACDB):

The low-voltage ACDB shall be used for distribution of AC power at single phase, and three phases at the Rectifier Substation. • The low-voltage ACDB shall have incoming feeders from the auxiliary transformers.

There shall be several outgoing feeders for feeding the power required for lighting, ventilation system and the other facilities in the Substation.

• The supply shall include all supporting structures, embedded parts, auxiliary

equipment, mechanical linkages, auxiliary circuit wiring, and interlocking devices necessary for efficient operation. All such parts and accessories shall be deemed to be within the scope of this PPSP whether specifically stated or not.

• The ACDB covered by this PPSP shall comply with the relevant requirements of

MERALCO and shall conform to the IEC standard or equivalent standards applied in the existing installation in Line 2.

• The ACDB shall include the following accessories of suitable rating, but not limited

to: 480V Triple-pole neutral molded case circuit breaker Bus bar chamber with copper bus of adequate size Ammeters Voltmeters Single-pole and triple-pole miniature circuit breakers for distribution Fuses Indication lamps Connection to SCADA panel, by cabling, for AC supply failure

• The distribution boards shall be of heavy sheet steel construction and shall be

completely dust proof. These shall be supplied complete with framework, fixing bolts, barriers enclosure, internal wiring cable-ending boxes, labels, etc.

• The various items constituting the ACDB shall be neatly and securely fixed. • The indication lamps shall be a low-power-consumption type, which shall be

interchangeable and replaceable on the front of the panel. • Suitable markings for identification of circuits shall be provided on the distribution

panel. Suitable nameplate also shall be provided on the ACDB. • All metallic parts of the panel shall be connected to the main earth loop. Suitable

earth terminals for this purpose shall be provided.

Page 5: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-25 Decembert 2015

i) DC (110V) Distribution Board (DCDB): • This design specification applies to the 110V DC for RSS utilization for the new

Substation. • The DCDB shall include all supporting structures, embedded parts, auxiliary

equipment, mechanical linkages, auxiliary circuits wiring and interlocking’s and shall be considered to be within the scope of work whether specifically stated or not.

• The DCDB shall comply with relevant technical specifications of the Philippine

Electrical Code and shall conform to the IEC standard or equivalent standards applied in the existing installation in Line 2.

• Distribution of the DC source shall be contained inside two specific cabinets, or two

halves of a single cabinet, one for each half substation. These cabinets shall be equipped with doors, fitted with flexible seals, closed via lock-bars and on which shall be installed a mimic diagram with indicating lights denoting the status of the main equipment.

• All units of DCDB including supporting frameworks shall be rust-proof. • The circuit breaker changeover switch shall be arranged neatly and mounted on the

panel, which shall be of standard design and provided within a hinged cover to facilitate inspection.

• The various items constituting the DCDB shall be neatly and securely fixed. • The indication lamps shall be of the low-power-consumption-type, which shall be

interchangeable and replaceable on the front of the panel.

• Suitable markings for identification of circuits shall be provided on the distribution panel. A suitable name plate also shall be provided on the DCDB.

• The DCDB shall comprise of the following accessories of suitable rating, but not

limited to: Copper bus of adequate size Ammeter Voltmeter Circuit breakers for distribution and protection Fuses Indication lamps Connection to SCADA panel, by cabling, for DC supply failure.

j) DC Power Supply System (Batteries and battery charger):

• The DC Power Supply System shall include batteries and battery charger for supply

of DC required equipment at the Rectifier Substation.

Page 6: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-26 Decembert 2015

• The DC Power Supply System shall include all supporting structures, embedded parts, auxiliary equipment, mechanical linkages, auxiliary circuits wiring, and interlocking devices necessary for their efficient operation. All such parts and accessories shall be deemed to be within the scope of work whether specifically stated or not.

• The DC power supply voltage level shall be 110V. The parameter of main

components and the required systems to be supplied shall be designed according to requirements of the new Substation and the existing system specifications.

• The DC system shall be robust, simple and clearly arranged and shall be based on the

following principles: High selectivity No common fuse for battery An installation, which is free from the risk of short-circuits between the battery

and the distribution board.

• The DC system shall be earthed across a high resistance resistor, so that a simple earth fault shall not cause tripping of the system. The Contractor shall define the dimensioning of this resistor.

• The DC system shall be designed to allow unloading tests, boost charging and

maintenance of each component to be carried out during normal operation. This implies that the provision shall be made for isolating the battery and the associated rectifier from the load.

• The Contractor shall submit battery and resistor sizing calculations to the Engineer

for approval.

• The battery protection shall be as close as possible to the batteries and shall be contained in a separate enclosure for negative and positive pole respectively. The enclosure shall be made of insulating material.

• The connection between the battery and its protection shall consist of a single

conductor and shall be run in such a manner so that it is protected from physical damage.

• The following information shall be indelibly marked on the outside of the cell or

battery: Manufacturer’s type and trade name Country of manufacture Electrolyte level (upper and lower limits) Capacity in Ah

• The rectifiers shall be suitably protected against overloading when short bursts of

heavy currents are drawn by closing circuit breakers and voltage spikes. Short-term overload capacity of the rectifier cells with the characteristics of the protective

Page 7: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-27 Decembert 2015

devices shall be made. The protection arrangement proposed shall be stated by the Contractor.

• The equipment shall be housed in a sheet-steel casing, which shall be provided with

side and bottom-perforated metal panels with louvers to provide adequate ventilation. Adequate protection against entry of insects, lizards etc. shall be made. The chargers shall be of robust construction and the noise level shall be kept to a minimum.

• The switches, meters and fuses shall be from reputable manufacturers.

k) Grounding System:

• The grounding system for the station electrical rooms, metering room and substation

rooms shall be provided by other contractors.

The E&M Contractor shall consider the following conditions in the design, but not be limited to; Except where specifically required elsewhere, all non-current carrying metal parts

shall be effectively connected in an approved manner on to the main earthing system.

A continuous copper earth bus bar shall run the length of each switchgear and the like, and shall be provided with terminals for connections to the shielding of all incoming and outgoing cables and, where specified, to Substation earthing system.

Unless otherwise approved, control, relay and instrument panels shall be provided with continuous earth bars which shall run along the bottom of the panels and which shall be connected to the Substation earthing system. The earth bars shall be of an approved design having a cross-sectional area not less than 80 square mm copper in accordance with the railway standards and the Philippine Electrical Code.

High-voltage, medium voltage and 1500VDC apparatus shall have two connections to the Substation earthing system.

Connections from apparatus shall be made to the Substation earth bar via a single branch. No sub-branches shall be allowed.

Joints in connections to the earthing system shall be so efficient as to avoid undue reduction of the current-carrying capacity of the earth bar. Special precautions shall be taken to ensure that the available contact area is fully utilized in connections to equipment.

l) SCADA Interface:

• Alarms and connections: Equipment in the Substation shall be connected to the SCADA Panel via cabling

to send notifications and alarms and to execute the OCC commands. Equipment in the Electrical Rooms in the Stations shall be connected to the

SCADA Panel via cabling to send notifications and alarms and to execute the OCC commands.

Page 8: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-28 Decembert 2015

• SCADA and communication interface: The scope of work of the Substations and Electrical Room includes all the

material and software necessary to establish the communication between the SCADA Panel and Synchronous Digital Hierarchy node via Ethernet copper cable.

m) Lightning Protection System: RSS shall be protected from lightning.

n) Inter-trip panel including the fiber-optic box: The Contractor shall include in the design of the new Substation RSS#7 the Inter-trip system including the fiber optic box to enable RSS#7 to communicate with the existing Substations in Line 2.

o) Safety and Maintenance Tools:

The Contractor shall provide the following testing facilities and maintenance accessories, but not limited to:

• Fixed and moving portions of the switchgear shall be provided with facilities to allow

applied high voltage tests to be carried out.

• When current transformers and protective relays are fitted, facilities shall be provided for primary and secondary injection tests to be carried out. These facilities shall preferably be such that wires and connections need not be disconnected for the tests.

• The complete Switchgear assembly for each Substation shall be furnished with the

following accessories: Provisions for functionally testing of a circuit breaker when completely

withdrawn from the switchgear. One set of special tools. One set of circuit breaker removal accessories, including lifting and handling of

devices. Where gas insulated compartments are provided, one set of gas filling and testing

equipment shall be furnished at the new Substation, unless otherwise approved. In addition to the amount of insulating gas furnished with the switchgear, the Contactor shall furnish 10% of that amount for maintenance purposes.

p) Cabling and Wiring:

• Apparatus shall have adequate provision for the entry and termination of associated power and control cables and, where necessary, the Contractor shall provide for this purpose a suitable terminal box mounted directly upon and immediately adjacent to each item of equipment involving such interconnection.

• Cable shall have reduced flame propagation characteristics and shall be adequately rated for their duty.

Page 9: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-29 Decembert 2015

• Cabling shall be neatly run and fitted in or upon such cable trays, trenches, ducts, or conduits as may be appropriate to the layout and equipment. The Contractor shall provide and install conduit, trays, supporting steelwork, brackets, clamps, and other fixings necessary for the support of cables supplied for power supply in the Substation, Electrical Rooms in the stations, and cable containment along the viaduct.

• The Contractor shall provide, install, and terminate internal wiring within cubicles,

panels, boxes, etc. Internal wiring shall be to IEC 227 or equivalent standard. Colour coding shall be approved by the Engineer.

• Internal wiring shall be neatly run and securely fixed in cleats in such a manner that,

wherever practicable, wiring can be checked against diagrams without removal of cleats. Cleats shall be porcelain, non-rustable metal, or approved molded insulating material and preferably of the limited compression type. Alternatively, internal wiring may be routed in metal or flame retardant plastic ducts with removable covers. Wire insulation shall be suitably protected where it emerges from the duct.

• Wire between the terminals of two items of equipment shall be given unique wire

numbers according to an approved system. A wire number shall not change solely by virtue of passing through a marshalling box terminal block.

• Identification markers shall be fitted to all wires and multicore cable tails within

enclosures in accordance with the diagram for the apparatus concerned. Cable and core markers shall be of insulating material, colored as approved by the Engineer, with a glossy finish to prevent adhesion of dirt. They shall be legibly and durably marked and shall not be affected by oil or moisture; numbers shall not be duplicated unless the corresponding wires are directly in series or parallel.

q) Electrical Room Equipment:

• The station electrical room equipment will be housed in a separate room provided by

the Civil Contractor (others) within a station structure.

• The main items to be furnished and installed are, but not limited to: Interface provisions; 600VAC insulated power and control cables and accessories; Installation materials; Local annunciator panel, etc.

• Local annunciator panel: Malfunctions of the RSS and Electrical Room equipment shall be alarmed at a

local annunciator panel, one in each for Substation and one in each Electrical Room, and designated alarms shall be transmitted to the OCC. The intended local and remote alarm requirements shall be approved by the Engineer. These requirements shall be incorporated in the detail equipment and installation designs.

The Local annunciator panel shall be of the solid-state type with illuminated alarm indications. The alarm legends shall be in English.

Page 10: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-30 Decembert 2015

The persisting alarm indications shall be retained until reset by the maintenance personnel. Visual alarm annunciations shall be supplemented with audible signals of fifteen (15) second duration.

r) Ventilation

The E&M Contractor shall design, provide and install the ventilation system (manual and automatic operation) to remove heat generated by power equipment. The supply air inlet shall be filtered. Separate exhaust ventilation shall be provided for the batteries. The E&M Contractor shall design, provide and install the ventilation system in substations and electrical rooms in the stations.

4.2 Interfaces and Coordination

To assure system-wide, integrated construction, the PSS installation shall be coordinated with various disciplines of the project, including but not limited to: • Overhead Catenary System (OCS); • Civil Contractors; • Station Contractors; • OCC; • Communication and Signaling System; • MERALCO; and • LRTA.

4.3 Substation and Electrical Rooms Protection

The Contractor shall consider in the design, the protection system against, but not limited to:

a) The mechanical damage, especially in the cable terminations and panels.

b) The electrical damage, especially the ones caused by Lightning, switching over-voltages in the OCS catenary, and catenary short circuit.

4.4 Power Supply System Testing and Commissioning

The following test and measurements shall be made and recorded in the presence of the Engineer, but not limited to:

4.4.1 During and Before the Installation and Execution

• Material approval; • Supplier’s approval; • Factory test; • Site test; • MOS approval; and • Execution and mock-up approval.

Page 11: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-31 Decembert 2015

4.4.2 Installation Completion

The following test and measurements shall be made and recorded in the presence of the Engineer, but not limited to:

a) Visual and mechanical inspection including, but not limited to:

• Inspect physical and mechanical connections. • Inspect anchorage and alignment. • Inspect all bolted connections and verify the bolt-torque values according to the

standards. • Test all electrical and mechanical interlocks for correct operation • Inspect insulating assemblies for evidence of physical damage or contaminated

surfaces. • Exercise all active components. • Verify correct operation of all indicating and control devices for correct operation. • Perform all mechanical operations test on both the circuit breaker and its operating

mechanism. • Verify operation of heaters, if applicable. • Measure critical distances. • Inspect all circuit breaker contacts. • Inspect all disconectors and switch contacts • Where applicable, check contacts for: Cleanliness, Wipe, Pressure, etc. • Verify adequacy of battery support racks, mounting, anchorage, and clearances. • Verify the ventilation of battery room or enclosure. • Verify existence of suitable eyewash equipment. • Inspect the protective relay contacts for burns, damage, misalignment, corrosion, or

other contamination. • Verify that cooling fans operate, where applicable. • Verify control and alarm settings. • Verify that the core, frame, and enclosure are grounded. • Verify appropriate equipment grounding. • Test all interlocking systems for correct operation and sequencing.

b) Cabling, termination and connection inspection including, but not limited to:

• Inspect all control wiring for integrity. • Inspect all power cables, terminations, connections, etc. • Inspect communication cables.

c) Electrical tests including, but not limited to:

• Perform resistance measurements through all bolted connections with a low-

resistance ohmmeter. • Perform insulation/resistance tests on each pole, phase-to-phase and phase-to-ground. • Perform an over-potential test on each pole with the switch closed. • Measure fuse resistance, if applicable.

Page 12: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-32 Decembert 2015

• Perform insulation/resistance tests winding-to-winding and each winding-to-ground, with the proper test voltage.

d) Operation checks including, but not limited to:

Check each DC traction circuit breaker and DC panels for proper operation. Test the following as a minimum: Open and close the breaker via local control; Open and close the breaker via remote control (SCADA if applicable); Open and close the breaker while in the test position; and Verify mechanical trip features where applicable.

• Check each AC switchgear and panel traction circuit breaker for proper operation.

Test the following as a minimum: Open and close the breaker via local control; Open and close the breaker via remote control (SCADA if applicable); Open and close the breaker while in the test position; and Verify mechanical trip features where applicable.

• For each operation check, verify the following (when applicable): Local indication: Ensure that the indication lamps and any mechanical indications

function properly; and Remote indications: Ensure that the OCC receives the proper indication.

e) Test values including, but not limited to:

• Compare bolted connection resistances to values of similar connections; • Ensure bolt-torque levels are as specified in the design and the standards; • Ensure micro ohm or millivolt drop values do not exceed the high levels of the

normal range; • Ensure the insulation withstands the over-potential test voltage applied; and • Ensure insulation resistance is in accordance with the standards.

4.5 Completion and Energization

For completion and energization of the LRT Line 2 East Extension Project Substations and Electrical Rooms in stations. It may be necessary for the Contractor to obtain traction power outages and distribution power outages in order to progress the DC and AC cabinet and cable installation. It will be necessary to ensure that all required inter-track or inter-section insulation have been installed prior to returning the system to normal operation and allowing the system to be re-energized. The Contractor shall coordinate with MERALCO and LRTA for compliance of the work in RSS #7, as well as the Electrical Rooms. The Contractor shall be required to operate and maintain the PSS until Final Acceptance by the Engineer and the Client.

Page 13: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-33 Decembert 2015

5.0 Applicable Codes and Standards

Except where otherwise specified or implied, the works shall comply with the latest applicable standards of: • Philippine Electrical Code; • International Electro technical Commission; • Institute of Electrical & Electronics Engineers; • American Institute of Steel Construction; • American Society for Testing and Materials; • American Welding Society; • American Concrete Institute; • Deutsches Institut fur Normung, Germany; • American National Standard Institute; • National Electrical Manufacturers Association; • National Fire Protection Association; • European Standards; • Technical Regulatory Standards on Japanese Railways; and • United Laboratories.

The standards shall be applied in this order of descending precedence in case of ambiguity.

6.0 Design Conditions 6.1 Environmental Conditions

The PSS shall be designed to operate satisfactorily in the following environment: • Elevation above mean sea level: 0 to 250m; • Humidity: 80 to 100%; • Precipitation (record in 24 hrs.): 472.4mm (7-20-1972); • Precipitation extremes (mm);

Table 6.1-1 Precipitation Extremes

60 minutes 15 minutes

20-year 216mm 118mm

50-year 257mm 141mm

100-year 287mm 159mm

Page 14: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-34 Decembert 2015

• Ambient outdoor temperature range: minimum recorded + 14.5˚C (1-11-1914), maximum recorded + 40.1˚C (4-06-2013); and

• Seismic: Zone 4, in accordance with NSCP.

6.2 Design Parameters

The following shall constitute the basis for the PSS design and rating: • Minimum temperature for structural analysis: + 15˚C; • Initial temperature for computer simulations: + 35˚C; • Normal temperature for PSS design: + 40˚C; • Preferred upper conductor temperature: + 65˚C maximum; • Maximum acceptable conductor temperature: + 75˚C; • Maximum authorized train operating speed: 80kph; • Catenary nominal voltage: 1500VDC; • Vehicle operating voltage range: 1050 to 1800VDC; • Vehicle auxiliary load: 67kW; • Pantograph current draw - continuous: 800 Amps, Peak 1000 Amps; and • Maximum operation speed: 110kph.

7.0 Delivery, Storage and Handling

a) The Contractor shall arrange suitable off-site storage facilities for all power supply materials (substations material, ring and electrical rooms). Sufficient stock of items shall be in continuous storage and on site to permit the Engineer to inspect on a regular basis all components prior to their inclusion in the Works. The security and protection of all stored items will be the sole responsibility of the Contractor.

b) The identification mark of the manufacturer or foundry and the pattern numbers assigned

by the supplier shall be cast into all castings. Marks and numbers shall be of readable size and in such a position that they will not affect the electrical or mechanical performance of the components or of the system.

c) The Contractor shall ensure that all materials are suitably packaged and protected against

damage during transportation and delivery. Transformers, switchgear, etc shall be prepared and shipped in a manner that will prevent damage to the galvanized or painted surfaces.

d) All wire and cable shall be shipped on reels suitable for the type and weight carried.

Damage to reels shall be cause for rejection of the wire or cable.

e) All shipping boxes, bags or crates shall be properly marked showing the contents of each. If different materials are packaged in a box, bag or crate, all items shall be appropriately packaged and properly marked or tagged prior to packing.

f) The Contractor shall store all products in accordance with the manufacturer's instructions

and shall ensure that all material is protected from damage and exposure. Fittings and

Page 15: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-35 Decembert 2015

hardware shall be packaged in a manner that will allow stacking and outdoor storage until installation with no harmful effects.

g) Any damage to the equipment and material shall be the Contractor's responsibility, and all

repairs and replacements shall be accomplished by the Contractor in accordance with the manufacturer's instructions at the Contractor's cost.

8.0 Spare Parts and Consumables

The Contractor shall submit a list of spare parts, tools and equipment that are to support the normal operation of the ring, substations and electrical rooms. The final-listed spare parts and consumables shall be supplied by the Contractor. All the spare parts shall be properly packed in a safe container with the complete list, part number, and name of manufacturer and supplier during the final acceptance. The Contractor shall be required to guarantee spare parts availability for not less than fifteen (15) years after the date of issue of taking over certificate, in case of additional spares required after the Defects Notification Period. The following main components shall be considered in the list of spare parts, but not limited to: a) For Rectifiers:

Diodes: minimum 10 Fuses: minimum 10 Micro Switches: minimum 10 Harmonic filters: minimum 3 Temperature sensors: minimum 3

b) For Switchgear (AC and DC) in substations: LV circuit breakers: minimum 20 AC Protection relays: minimum 3 DC Protection relays: minimum 3 Contactors: minimum 20 Relays: minimum 20 Voltage transformer: minimum 2 Current transformer: minimum 2 Ammeters, Voltmeters, and Wattmeter: minimum 2 of each 3

c) For Switchgear and panels in stations (electrical rooms): Auxiliary circuit breakers: minimum 20 Main circuit breaker: minimum 2 Contactors: minimum 20 Relays: minimum 20 Voltage transformer: minimum 2 Current transformer: minimum 2 Ammeters, Voltmeters, and Wattmeter: minimum 2 of each 3

d) For Battery chargers:

Diodes: minimum 6 Electronic cards: minimum 3 Fuses: minimum 4

Page 16: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –PSS-36 Decembert 2015

9.0 Special Tools

One set of special tools, test equipment, jigs, fixtures and gauges required to carry out all functions described in the Maintenance and Operation Manuals, or as required by the PPSP; shall be delivered before the Issue of the Taking Over Certificate. This shall not be less than the list of equipment provided by the Contractor, along with his Bid. The Contractor may add any additional equipment required, but, at no extra cost to the Employer. The extent of supply shall include protective or carrying cases, as may be appropriate for the storage and use of each item as agreed by the Engineer. As part of the supply, the Contractor shall also provide one (1) complete set of DC Power load simulation package, inclusive of hardware and software, programmed and configured to allow Power flow simulation fo the whole LRT Line 2 Power Supply System. The simulation program shall allow for re-configuration for power flow simulation in the future, including any conditions of further expanded/extended line 2.

The Contractor shall submit six (6) copies of complete illustrated parts lists and overall "exploded views" of assemblies and sub-assemblies for all Plant. This shall include reference to all assemblies, sub-assemblies special tools, jigs, fixtures and gauges required for the operation and maintenance of the equipment by the Employer.

10.0 Training Program

The Contractor shall provide the Training Program to the Maintenance Personnel of LRTA for Substations and Electrical Rooms. The training program for substations and electrical rooms shall include, but not limited to, maintenance of AC and DC equipment including: • 34.5kV Switchgear; • 6.6kV Switchgear; • Rectifier • 1500VDC Switchgear • Negative Return Panel • DC circuit breakers; • AC and DC panels; • SCADA Panel; • Rectifier (Traction) Transformers; • Auxiliary and ring (station) transformers; • Low voltage and facilities panels and circuit breakers; • Batteries and battery chargers; • Ventilation equipment; • Inter-trip panel; and • Power and control cables, splicing and terminations, etc.

Page 17: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

TECHNICAL SPECIFICATIONS

OVERHEAD CATENARY SYSTEM LRT Line 2 Extension Project

Page 18: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Overhead Catenary System

Table of Contents Page Abbreviations 1 1.0 Introduction 2 2.0 Description of the Existing System 2 3.0 General Requirements 3 4.0 OCS Performance Requirements 6 4.1 Scope of Work 6 4.2 Interfaces and Coordination 11 4.3 Protection against Accidental Contact with Traction Current 11 4.4 Final Adjustment of the OCS 12 4.5 Final Measurement of the OCS 12 4.6 OCS System Testing and Commissioning 14 5.0 Applicable Codes and Standards 16 6.0 Design Conditions 16 6.1 Environmental Conditions 16 6.2 Design Parameters 17 7.0 Delivery, Storage and Handling 18 8.0 Spare Parts and Consumables 18 9.0 Special Tools 19 10.0 Training Program 19

Page 19: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-1 December 2015

Abbreviations ASTM CAD

American Society for Testing and Materials Computer Aided Design

CO Close followed immediately be Open DC E&M

Direct Current Electrical and Mechanical

kA Kilo Amps km Kilometre kN kph

Kilo Newton Kilometers per hour

kV Kilovolt LRTA LRT

Light Rail Transit Authority Light Rail Transit

mm MOS NSCP

Millimetre Method of Operation Statement National Structural Code of the Philippines

OCC Operations Control Centre OCS PDF PPSP

Overhead Catenary System Portable Document Format Particular Performance Specification and Parameters

PSS Power Supply System RSS Rectifier Substation SCADA Supervisory Control and Data Acquisition UPS Uninterruptible Power Supply V Volt VAC Voltage Alternating Current VDC Voltage Direct Current

Page 20: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-2 December 2015

1.0 Introduction

This Particular Performance Specifications and Parameters (PPSP) provides the requirements of the Overhead Catenary System (OCS) for the LRT Line 2 East Extension Project. This project will extend the current Line 2 by 3.93km. This PPSP shall be read in conjunction with the Conditions of Contract, General Specification and all related Employer’s Requirements. In the event of a conflict between the General Specification and the PPSP, the requirements of the PPSP shall prevail.

2.0 Description of the Existing System

The existing OCS consists of center poles and cantilever beams; typical drawing is included in Part Two (2), Section VI-3 of the Employer’s Requirements. Simple catenary systems with automatic-tension-balancers are used for the existing OCS, 1500VDC and double insulation. The main materials for the electrical conductors are:

• Tin-coated hard-drawn grooved trolley wire, 137mm² for contact wire; • Hard-drawn copper stranded conductor, 240mm² for mainline messenger wire; • Hard-drawn copper stranded conductor, 120mm² for out-of mainline messenger wire; and • 120mm² bare copper for jumper wire.

For the integration of the LRT Line 2 Extension with the existing OCS, a drawing contained in Part Two (2), Section VI-3 of the Employers Requirements shows the last section of the existing OCS. The existing mainline catenary consists of: a) A single messenger wire and a single contact wire located over each track, using center

poles.

b) Tension length, or a conductor length, approximately 1,600m maximum between automatic termination points.

c) The existing OCS utilizes balanced weight anchors so that the conductor tensions will

remain largely constant despite temperature variations.

d) Half-tension lengths, up to 800m long, using one fixed-end-termination and one automatic termination.

e) The approximate center point is stabilized by using a midpoint anchor assembly, which

also limits the effects due to a wire breakage or defilement in the tension length.

f) The support arrangement is a single-track cantilever, mounted in a back-to-back configuration on tapered tubular steel poles. For this center pole construction, the OCS poles are mounted on the viaduct pier copings. In stations, the roof structure is used to support the OCS through the station buildings, utilizing drop-tubes.

Page 21: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-3 December 2015

g) The contact wire height is 4700mm (normal), 4300mm (minimum) and 6400mm (maximum).

h) The Substation and Parallel Feeder cables are routed in underground ductwork from

feeder circuit breakers, placed in the RSSs, to positive feeder termination boxes, placed on the viaduct structure, and extended via exposed conduit and cable trays along the viaduct. The Parallel Feeders are electrically connected in parallel with the OCS, and interconnected with the relevant feeder termination busses at adjacent RSSs. The feeders are sectionalized together with the OCS, and utilize insulated cables installed in the cable trays located between the two viaducts.

i) Frequent tap connections are made from the feeder cables to the messenger wire. At the

feeder tap points, bare copper super flexible jumpers are provided between the feeder cable and the contact wire. To balance potentials between the messenger and contact wires and to assure balanced current distribution, one bare copper super-flexible in-span jumper is installed in each span.

j) Surge protective devices are used for the lightning protection system. Surge arresters are

installed at each substation feeder, and one unit is also installed midway between two LRT stations on the OCS line. Surge arresters are metal oxide varistor. Each surge arrester is provided with a dedicated grounding.

3.0 General Requirements

a) The OCS shall be future-proof, based on proven technology and a modern, state-of-the-art system.

b) The Contractor must clearly state the proposal concerning the use of Standards and Codes.

c) The equipment shall be designed to operate satisfactorily under all variations of load,

wind, and temperature that may be met in normal usage under the prevailing climatic conditions in Manila.

d) All apparatus shall also be designed to ensure satisfactory operation in all atmospheric

conditions prevailing at the sites and during such sudden variation of load and voltage as may be met under working conditions on the system, including those due to faulty synchronizing and short circuit.

e) Scrap components shall be segregated from usable components, collected and removed

daily. Scrap components shall not be left on the viaduct or alongside the track. All scrap components are the property of the Contractor and shall be removed from the project site.

f) The factor of safety to be used in the design shall be according to the existing Line 2 and

international railway standards.

g) The Contractor shall perform studies, design calculations, and develop design documentation including, but not limited to, the following and submitted to the Engineer in Auto CAD and PDF, both in soft and hard copy, for approval:

Page 22: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-4 December 2015

• Final OCS sectioning diagram in the extension line; • Lightning Protection System; • Lighting flux along the line considering the environmental conditions; • Detailed cable layout drawings for 1500VDC positive and negative cables; • Detailed layout drawings for the OCS equipment and accessories, including the

grounding system for poles; poles flanges and anchoring. • Detailed layout drawings for the lighting system along the walkway, equipment,

accessories, and fixings to the poles; and, • Detailed layout drawings for the lightning protection system along the track,

equipment, accessories and fixings to the poles.

h) The Contractor shall determine and provide as necessary any software and software license for the operation and maintenance of the system.

i) The Contractor shall define and assume the design of all equipment which has to be connected to the protective circuits of the traction current and shall coordinate with other project Contractors.

j) The Contractor shall coordinate with the trackworks and the viaduct contractors regarding

the stray current corrosion control.

k) The OCS design shall incorporate equipment that has proven reliability and a history of at least ten (10) years in a similar metro rail application.

l) The OCS and its elements shall be designed to revert to safe modes under failure

conditions. The Contractor shall employ high quality components, proven systems, redundancy, checking devices and other techniques to achieve this goal.

m) The mechanical manoveure of the motorized disconnectors shall allow for maintenance and emergency operation purposes.

n) All non-welded assemblies shall be assembled by means of bolts and nuts with mandatory

use of lock-washers.

o) All panels, separating partitions and accessories shall be mounted similarly, in such a way as to withstand indefinitely the vibrations transmitted, in particular by the resetting mechanism of the circuit breakers and their actuation.

p) The OCS on the mainline shall consist of a single messenger wire and a single contact

wire located over each track and using the outside pole arrangement of the mainline.

q) The OCS configuration systematically respects the principle of double insulation, all along the line. The following principles are applied, but not limited to:

• Insulating distance between live parts and structure; and • Protection by clearance.

Page 23: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-5 December 2015

r) The interface with the rolling stock is the contact between pantograph and contact wire. To ensure proper operation of the equipment, this contact must be continuous.

s) A parallel line feeder shall be installed along the line to minimize voltage drops. This feeder is connected to both parallel OCS lines every 500m. The connections between OCS lines and feeder are made of two insulated cables, one per each track.

t) To protect OCS equipment against atmospheric overvoltage, the Contractor shall install

surges arresters connected to the OCS between the Rectifier Substation (RSS) and the OCS.

u) The Contractor shall design, provide and install a lightning protection system along the

line. The design shall be approved by the Engineer and the LRTA.

v) In-situ connections of main structural metal elements shall be by means of bolts. If other forms of in-situ connection are proposed, then their static and fatigue design strength shall be calculated from first principles and shall be agreed with the Engineer. Alternatively, the design strength may be based on the results of full-scale load tests, subject to the agreement of the LRTA and the Engineer.

w) Fabricated steel shall be galvanized in accordance with ASTM A123 or an equivalent

standard.

x) Wire splices will not normally be permitted in the new construction. However, it is recognized that there may be a need, under certain exceptional circumstances to be approved by the Engineer, to incorporate a limited number of wire splices into the works.

y) The As-built and drawing files for the OCS shall be in Auto CAD and PDF format.

z) The Contractor shall prepare, and keep up-to-date, a complete set of "as-built" records of

the execution of the Works, showing the exact as-built locations, sizes and details of the work as executed. These records shall be kept on Site and shall be used exclusively for the purposes of this Sub-Clause. Two copies shall be supplied to the Engineer prior to the commencement of the Tests on Completion.

aa) The Contractor shall supply to the Engineer as-built drawings of the Works, showing all

Works as executed, and submit them to the Engineer for review as specified within the time frames in the contract documents. The Contractor shall obtain the consent of the Engineer as to their size, the referencing system, and other relevant details for document control.

bb) All calculations and designs shall be submitted to the Engineer in Excel, MS Word and

Auto CAD, as applicable, or as requested by the Engineer.

cc) Prior to the issue of any Taking-Over Certificate, the Contractor shall supply to the Engineer the specified numbers and types of copies of the relevant as-built drawings, as specified within the time frames in the contract documents. The Works shall not be considered to be completed for the purposes of taking-over until the Engineer has received these documents

Page 24: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-6 December 2015

dd) The Contractor shall submit a Method of Operation Statement (MOS) related to each main task and shall be approved by the Engineer before starting the work. The approval of the MOS shall not remove responsibility from the Contractor.

ee) Insulated Wire and Cable: conductors for general use shall be soft or annealed copper

complying with ASTM B8, Class B stranded. Insulation level shall be 2,000V.

ff) Structure design shall allow for, at least, one (1) minute sustained wind speed up to 250kph under typhoon conditions.

gg) Prior to commencement of the Tests on Completion, the Contractor shall supply to the

Engineer provisional Operation and Maintenance Manuals in sufficient detail for the Employer to operate, maintain, dismantle, reassemble, adjust and repair the system. The Contractor should also submit catalogues and manuals of the spare parts to be provided, detailing the complete specifications and data.

hh) The Works shall not be considered to be completed for the purposes of taking-over until

the Engineer has received final Operation and Maintenance Manuals, and any other manuals specified for these purposes.

4.0 OCS Performance Requirements 4.1 Scope of Work

4.1.1 General

a) The OCS system proposed for the extension is comprised of a single contact wire hung by dropper from a messenger wire; for each track. In stations, drop tubes shall be used for fixing the OCS. The total length of the extension is 3.93km with double-track on viaduct.

b) The E&M Contractor shall provide and install the OCS fixing-down bolts. The E&M Contractor shall also provide and install the reinforced concrete OCS upstand/pedestal. Please note that the positions of the OCS Poles will be provided to the E&M Contractor not later than ten (10) days prior to the submission of the bid.

c) The integration of OCS- related equipment alarms in the OCC.

d) Provide, laying, installation and connection of the DC cables to feed DC power from the

RSS to the OCS, including, but not limited to, the positive and the negative cables.

e) Provide, laying, installation and connection of the AC cables for the lightning protection system.

f) Design, provide and install the lighting system along the line for the walkway illumination, including cables, accessories, etc.

g) Design, provide and install the lightning protection system along the line.

h) The Contractor shall consider in the design the curve of the track. A concept design of the

track is contained within Part Two (2), Section VI-3 of the Employer’s Requirements.

Page 25: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-7 December 2015

4.1.2 Equipment/Material Requirements

The Contractor shall be responsible for the design, fabrication, furnishing, and installation and testing of a complete OCS, including but not necessarily limited to, the following major elements: a) OCS Structural Steel:

• Catenary Poles and Portal Structures – to be octagonal and H section poles with wide

flange the same as the existing poles on LRT Line 2, galvanized steel poles and portal structures for support of the OCS on the viaduct. Drop-tubes for support of the OCS in stations.

• Small Part Steelwork Fabrications - galvanized small-part steelwork assemblies required to support the OCS, and for special structural down guy assemblies.

b) Basic Electrical Materials and Methods: Conduit, inserts, connectors, insulating tape and other miscellaneous items applicable to the OCS installation.

c) Grounding and Bonding Systems: For the grounding and bonding of the OCS structures and surge arresters. The E&M Contractor shall design the grounding system, and utilize the conduits provided by the Civil Contractor and installed in the piers. All grounding installations shall be suitably protected against vandalism, theft and elements. A concept drawing is contained in Part Two (2), Section VI-3 of the Employers Requirements. The E&M Contractor shall install the necessary cables, clamps, grounding rods and protection system of the OCS grounding system. The earth resistance requirement for the grounding system shall be five (5) ohms or less. The earth resistance for surge arrester and lightning protection system shall be as recommended by the manufacturer.

d) Surge Arresters and Lightning Protection System for OCS: For the protection of the OCS from lightning and accidental power surges from other causes. The original alignment is suffering from frequent lightning strikes and disrupting operations. Isokeraunic map is to be provided by the E&M Contractor and the quality and quantity of lightning arresters will be based from this mapping.

e) Wire and Wire Rope:

Galvanized Steel and Stainless Steel Wire and Wire Rope - for special hangers, pole guys, cantilever, head span, cross-span and wire pull-off assemblies.

f) Synthetic Rope: Synthetic Rope for special hangers, cantilever, head-span, cross-span and pull-off assemblies.

g) OCS Assemblies, Fittings and Hardware:

Special hardware for OCS support and installation, including small castings, tubular items and fabrications using metal plates and shapes.

h) Bare Conductors:

Page 26: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-8 December 2015

Uninsulated electrical conductors and wires for the OCS including the messenger wire and contact wire, and super flexible jumper wire.

i) Feeder Cable

j) Cable Splices and Terminations:

k) Insulators: Non-ceramic, vandal resistant, synthetic insulators of various types for use in tension, compression and bending applications to provide for a completely insulated OCS, together with bridging and non-bridging section insulators for OCS sectionalizing applications.

l) Disconnect Switches: Pole mounted outdoor, single pole, non-load break disconnect switches, with manual and motor operators.

m) Pole Mounted Luminaries: Pole-top mounted emergency lighting units to illuminate the viaduct emergency walkway, including dual feeding arrangements.

n) SCADA: • Motorized disconnect switches are to have provisions for remote operation and status

indication via the SCADA; and

• Voltage detectors (1500VDC nominal) installed in the OCS sectionalizing shall have provision for status indication via the SCADA.

o) OCS Voltage Detector: The E&M Contractor shall consider, in the design, the catenary voltage detectors to detect the status of each section in the mainline.

p) Special Tools and Equipment:

E&M Contractor to provide all tools and equipment necessary for the installation, testing and commissioning of the OCS to include, but not limited to, the furnishing of OCS installation vehicles and trailers, height and stagger gauges, step wedges, cable splicing and cutting tools, hoists, slings, clamps, ladders, protective gloves and insulation blankets, temporary grounding devices, and other miscellaneous tools and equipment

q) Overhead Catenary System Installation: The installation of all OCS components, including poles, portal structures, down-guys, cantilevers, cross-spans and head spans, messenger wire, drop-tubes, contact wire, wire terminations and anchoring assemblies, jumpers and other components as noted, including pole numbering.

r) OCS System Testing and Commissioning: OCS system testing and commissioning including the testing, inspection, and measurement and acceptance procedures for the OCS together with their implementation.

Page 27: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-9 December 2015

4.1.3 Main OCS Equipment Description

a) OCS poles: • Poles baseplates shall be a symmetric steel plate for all pole types.

• The poles and baseplates shall be hot-dip galvanized.

• The poles shall provide the following main functions: To support the overhead contact lines and protective associated equipment; To support the feeder cables to the catenary, if it’s required according to the final

design; To support the lightning conductors, as required according to the lightning

protection system design; To support walkway lighting; To support the signaling equipment (signaling boxes, signs, etc.); and To support particular local information.

• Pole Tolerances shall be in accordance with railway standard requirements for the

designated pole sections.

• Ground lug connector, to suit the specified grounding cable size, shall be furnished with each pole and shall be stainless steel, tinned copper, or bronze.

Each pole shall have its designated Pole Number, stenciled on either the nominal east or west face of the pole, at a height of 3m above rail level.

b) Pole-Mounted Lighting System: • Lighting System shall be installed on OCS poles. Locations of lighting devices and

accessories mounted on the poles must satisfy the required electrical clearances from conductors and lightning protection system devices. The Contractor shall design, supply and install lighting system to provide illumination along the walkway surface/level in accordance with relevant standards subject to approval by the Engineers.

• The lighting installations (cables, light device, guards) must be designed according to the principle of double insulation between traction voltage and lighting equipment.

• This lighting will only be switched on when required, either from the appropriate stations or from the OCC. The station control will not be able to switch off the lighting once energized (except from the electrical room circuit breaker). The OCC will have switch off responsibility. In normal operations, the lighting will not be on, thereby avoiding glare to train drivers or adjacent property.

• 220 VAC circuits shall run along the viaduct from each station in the up and down

track directions and be connected to both lighting fixtures on every alternate pole. Should the power at or the circuit from one station fail, lighting will still be available along the walkway (on the circuit from the next station) but from every second pole.

Page 28: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-10 December 2015

• The E&M Contractor shall supply and install a back-up power source for the lighting system, which shall provide sixty (60) minutes of power during a power failure at a station.

c) Lightning Protection System:

The E&M Contractor shall propose and design a lightning protection system based on the lightning density in Manila and the lightning standards.

d) OCS Disconnectors: • The DC disconnect switches shall be outdoor type, single-pole, single-throw, no-load

break and non-fusible air switches. The switches shall be exposed type, suitable for pole mounting.

• Disconnectors shall be rated for 1500VDC operations with 3.0 kV, rms, and minimum insulation level. Continuous current rating shall be as required without exceeding 50ºC rises above a maximum ambient plus solar heating temperature of 45ºC. Switches shall have a momentary current withstand rating of not less than 100 kA, rms.

• Moving and stationary contact surfaces shall be silver-plated copper. All other

current-carrying parts shall be of high-conductivity copper or copper alloy. Contacts shall be self-aligning, wear-compensating and with initial wiping action.

• Each switch shall be furnished with an insulated operating rod with the operating

handle positioned at a suitable height above ground or guide way walkway level. Operating handles shall be furnished with heavy duty lugs to accept padlocks in the fully open and closed switch positions. Switch positions shall be indicated with “OPEN” in white lettering on a green background and “CLOSED” in white lettering on a red background. All non-current carrying metal parts shall be hot-dip galvanized steel.

• Each disconnect switch shall be provided with an outdoor type, heavy duty, security

class, keyed padlock having a hasp diameter of 9mm minimum. All padlocks shall be keyed alike. Two keys shall be provided for each padlock.

e) Contact Wire and Messenger Wire: • One typical full-tension splice for each type of conductor shall be fabricated,

independently from the OCS, and shall be tested by an independent testing laboratory, approved by the Engineer, or by another means acceptable to the Engineer. Copper and bronze full-tension line splices shall offer 95 percent tensile strength and 100 percent conductivity (minimums).

• Contact wire splices shall be designed to avoid the formation of “Hard Spots” in the OCS system. Maximum separation under tension of the ends of spliced contact wires inside the splice shall be 1mm.

Page 29: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-11 December 2015

f) Traction Power Cables: • Substation positive and negative cables, and the parallel feeder cables, shall be

insulated, non-shielded, single conductor suitable for use in wet or dry locations and rated 2000VDC, 90 degrees Celsius conductor temperature for normal operation. They shall be capable of operating at 130 degrees Celsius for emergency operation, and 250 degrees Celsius under short circuit conditions. The conductors shall be copper; ASTM B8 Class B (or equivalent) compressed stranding with EPR (ethylene propylene rubber) insulation. Cable jacket material shall be neoprene or equivalent for outdoor cables.

• Traction power positive and negative feeder cables connecting the DC feeder circuit breakers to the overhead contact system, and the running rails to the negative bus, shall be sized to accept maximum overload and short-circuit current, based on a temperature rise that does not exceed the safe insulation design limits of the cables. The contractor shall design and provide the method to connect the rail to the negative bus-bar considering the stray current in the design.

• The substation feeder and negative return cables shall be standardized on a single-

conductor size by using multiple smaller conductors to satisfy feeder capacities. Where possible, the paralleling feeder cables shall also be standardized on a single conductor size, which may not necessarily be the same size as the substation feeder cable. The multiple cables shall have sufficient conductivity to maintain adequate train voltage levels and to support the current capacities.

• For the protection of the insulated cables the Contractor shall provide and install

surge arresters not more than 400m spacing, at the points where the feeder tap connections are to be installed.

4.2 Interfaces and Coordination

To assure system wide, integrated construction, the OCS installation shall be coordinated with various disciplines and Contractors of the project, including but not limited to:

• Power Supply System; • Civil Contractors; • Station Contractors; • OCC System; • Communication and Signaling System; and • LRTA (Employer/ Employers Representative).

4.3 Protection against Accidental Contact with Traction Current

a) Structures and equipment may accidentally come in contact with a live broken overhead

contact line. In compliance with the railway standards, an OCS “ZONE” shall be defined. This “ZONE” shall respect the values defined in the railway standards.

Page 30: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-12 December 2015

b) To ensure the people are protected, and to be in compliance with the railway standards, two means of protection can be used:

• Double insulation (traction equipment and overhead contact lines); and • Transformation of the default in a short-circuit default between positive/negative

traction circuits via a discharge interval. 4.4 Final Adjustment of the OCS

a) After tensioning has been completed, support hangers and clips fastened, steady arms

erected, and pull-offs installed, a check of the construction and adjustment to final position of the OCS shall be made.

b) In making final adjustments to the OCS, the Contractor shall ensure that turnbuckles and other adjustable fasteners have at least 60 percent of their take-up adjustment remaining to provide for future maintenance.

c) The height and lateral positions of the messenger wire and contact wire shall be checked

in accordance with the standard and the existing system and adjusted where necessary. Height measurements shall be taken normal to the track along the elevated track centerline. Contact wire stagger measurements shall be taken as lateral offsets from the elevated track centerline.

d) On tangent track, the stagger of the contact wire will be alternately to the right or left of

the centerline of pantograph at consecutive structures.

e) The lateral position of the contact wire on curved track will vary with the curvature and span length.

f) The installation tolerance for contact wire stagger shall be +/- 15mm.

g) If the construction indicates that changes are required, the Contractor shall bring the

subject to the attention of the Engineer at once.

h) The messenger wire shall be installed vertically above the final contact wire stagger with an allowance of +/- 10mm for system heights of 300mm or less, increasing to +/- 60mm for system heights of 800mm, and to +/- 100mm for system heights of 1200mm or greater, where used.

i) The normal height of the contact wire is 4700mm and above a tolerance of +75mm, -0

mm. 4.5 Final Measurement of the OCS

a) The following measurements shall be made and recorded in the presence of the Engineer

for each wire run with the contact wire in its final position: • Pole number and stationing location of each support or registration point measured;

Page 31: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-13 December 2015

• System height - the distance between the centerline of the messenger wire and the underside of the contact wire shall be measured at each support or wire pull-off registration point;

• Contact wire stagger relative to both design and final super elevated track centerline

at each registration point and at mid span point;

• Differences between design and final super elevation shall be recorded at each location measured;

• Contact wire height above each track at each support point and at mid span point;

• Wire temperature and air temperature, plus time of day and date;

• Track centerline to face of pole at rail level at each structure location, final track

super elevation and pole rake, and (where appropriate) track centerline to track centerline distance at rail level; and

• The result and data shall be represented in the final drawings, and submitted to the

Engineer in Auto CAD and PDF format. Both hard and soft copies shall be provided.

b) At tensioning pole locations, a check shall be made to ensure that the balance weights move freely after which measurements shall be taken of the separation between the pulleys, and of the clear length of the fall rope below the guide pulley. A calculation shall be made and recorded of the distance available from the underside of the weight stack to the top of the pole baseplate. A record shall be made of the wire temperature, air temperature, day and date, and tensioning response time. The result and data shall be represented in the final drawings, and submitted to the engineer in Auto CAD and PDF format.

c) The Contractor shall rectify all errors and shall re-measure the OCS in the presence of the

Engineer.

d) A complete set of the final height and stagger dimensions, as accepted, shall be available at the Final Inspection, and shall be incorporated into the final As-Built documents.

e) Clearance Check: The Contractor shall make a clearance check, using the height and stagger gauge fitted with the removable clearance ears. If fouling occurs at any point, the Contractor shall rectify the condition.

• At each point measured, the contact wire shall be lifted by 50mm to allow for uplift

of the contact wire. In this position, no part of the registration assembly, with the exception of the contact wire clip and insulator, shall be within 30mm of the upper surface of the pantograph.

• The clearance ears shall allow for an additional allowance of 75mm for mechanical clearance to common live parts of assemblies and an additional allowance of 15mm for passing electrical clearance to non-energized parts. All parts of the system shall be outside this clearance envelope, with the exception of the steady arm. Any

Page 32: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-14 December 2015

registration pipe drop bracket to which the steady arm is attached shall be outside the mechanical clearance envelope.

4.6 OCS System Testing and Commissioning 4.6.1 Pantograph Tests

The Pantograph Tests on the catenary will be performed using the OCS installation vehicle with the pantograph in contact with the contact wire. These tests are to assure a smooth, shock-free passage of the pantograph with no interruption to pantograph passage, especially at turnouts, section insulators, and wire height changes. Particular attention will be focused on wire takeover at turnouts and crossovers, to minimize the possibility of arcing at all locations. The Contractor shall be responsible for all adjustments required as a result of these tests, which shall be performed at the expense of the Contractor.

4.6.2 Circuit Continuity and Loop Resistance Tests:

a) The purpose of this test is to obtain the DC loop resistance of each OCS section. This test checks both the OCS and the rail return system for electrical continuity and the absence of high resistance connections or inadvertent ground connections.

b) The test entails short circuiting a discrete section of the OCS by connecting the OCS to the rails at one end and applying a dc voltage at the other end. The length of section under test should be approximately 1.5 - 3.0km. The test shall be carried out in the following steps:

• Feeders which are electrically common to the OCS shall be connected to the OCS.

• A DC source is required which will provide a current of nominally 100 Amps with an

applied voltage of 24V.

• Measurements shall be made of the dc voltage and dc current, and the circuit resistance calculated from the measured values of voltage and current, which shall be compared with the design values.

• Any section having a discrepancy of more than 20 percent between the design value

and the measured value shall be rechecked to ensure that all electrical connections are correctly made, or that there are not inadvertent bound connections to the OCS which are reducing the total length of the loop.

• The following items shall be recorded for each section: Length of section in meters. DC Volts. DC Amps. Resistance in Ohms. Ohms/km.

c) The test required for loop resistance requires passing a relatively high dc current through

the OCS and rails. Test zones shall be clearly identified. All safety requirements,

Page 33: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-15 December 2015

established in the Safety Program, concerning the public, work personnel and equipment shall be strictly enforced. Personnel not directly associated with the test shall be kept clear of the tracks. The section of OCS and associated feeders under test must be isolated from the adjacent section of the system.

4.6.3 High Potential (Hi-Pot) Insulation Testing

DC Hi-Pot testing shall be performed on discrete sections of the OCS of 1.5 - 3.0km in length. The Hi-Pot test shall serve the following purposes: a) Insulators and feeders are checked for leakage.

b) The electrical insulation of minimum clearance areas is confirmed under static conditions.

c) The electrical insulation of section insulators and disconnect switches is verified.

d) The test results provide a reference against which periodic checking for any reduction in

the insulation level of the OCS can be made by comparing new voltage and leakage current values against the initial value.

e) A nominal dc Hi-Pot voltage of 2.5kV shall be used for the test. Hi-Pot tests shall be

carried out on the OCS sections as soon as possible after the continuity tests have been completed, in order to ensure that the section being tested is electrically continuous. Leakage current between 0 and 5 mA can be expected for section length of 1.5 - 3.0km.

f) Procedure for Main Line Tracks: Adjacent OCS sections, which are electrically isolated

from the section under test, shall be grounded by connecting the OCS to the rails. All surge arresters shall be disconnected from the section under test. A DC test voltage shall be applied to each OCS section. The test voltage shall be held for thirty (30) seconds. The leakage current shall be measured and recorded together with weather conditions and temperature.

g) The Hi-Pot measurements require application of a high voltage to the OCS.

4.6.4 Integrated Testing

Following the testing of the OCS as described above, the Contractor shall assist the Engineer in performing integrated tests with other systems for the LRT Line 2 Extension Project and the Original Line 2 System. The Contractor shall be responsible for all adjustments required as a result of these tests.

4.6.5 Completion and Energisation

For completion and energisation of the LRT Line 2 East Extension Project and commencement of train operations, it may be necessary for the Contractor to obtain traction power outages in order to complete the OCS installation. It will be necessary to ensure that all required inter-track or inter-section insulation has been installed prior to returning the system to normal operation and allowing the catenary to be re-energized. The effect of the

Page 34: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-16 December 2015

work accomplished in each shift shall be carefully checked from both electrical and mechanical aspects to assure safe and satisfactory operation of the trains. The Contractor shall be required to operate and maintain the OCS until Final Acceptance by the Engineer and the LRTA.

5.0 Applicable Codes and Standards

Except where otherwise specified or implied, the works shall comply with the latest applicable standards of: • Philippine Electrical Code; • International Electro technical Commission; • Institute of Electrical & Electronics Engineers; • American Institute of Steel Construction; • American Society for Testing and Materials; • American Welding Society; • American Concrete Institute; • Deutsches Institut fur Normung, Germany; • American National Standard Institute; • National Electrical Manufacturers Association; • National Fire Protection Association; • European Standards; • Technical Regulatory Standards on Japanese Railways; and • United Laboratories.

The standards shall be applied in this order of descending precedence in case of ambiguity.

6.0 Design Conditions 6.1 Environmental Conditions

The OCS shall be designed to operate satisfactorily in the following environment: • Elevation above mean sea level: 0 to 250m; • Humidity: 80 to 100%; • Precipitation (record in 24 hrs.): 472.4mm (7-20-1972); • Precipitation extremes (mm);

Table 6.1-1 Precipitation Extremes

60 minutes 15 minutes

20-year 216mm 118mm

50-year 257mm 141mm

Page 35: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-17 December 2015

100-year 287mm 159mm

• Ambient outdoor temperature range: minimum recorded + 14.5˚C (1-11-1914),

maximum recorded + 40.1 ˚C (4-06-2013); • Wind speeds - maximum recorded: (9-1-1970 & 7-20-1972) 56mps (202kph); and • Seismic: Zone 4, in accordance with NSCP.

6.2 Design Parameters

The following shall constitute the basis for the OCS design and rating: • Minimum temperature for structural analysis: + 15 ˚C • Minimum temperature for OCS design: + 15 ˚C • Initial temperature for computer simulations: + 35 ˚C • Normal temperature for OCS design: + 40 ˚C • Preferred upper conductor temperature: + 65 ˚C maximum • Maximum acceptable conductor temperature: + 75 ˚C • Minimum wind speed for conductor heating calculations: 1.6kph • Normal wind speed for OCS structure spacing: 160kph • Maximum sustained wind for typhoon condition: 250kph • Maximum authorized train operating speed: 80kph • Catenary nominal voltage: 1500VDC • Vehicle operating voltage range: 1050 to 1800VDC • Vehicle auxiliary load: 67kW • Pantograph current draw - continuous: 800 Amps, Peak 1000 Amps • Maximum conductor length: 1600 meters • Maximum half tension: 800 meters • Contact wire stagger (the lateral deflection of the contact wire registration points) shall be

designed to provide for good current collection and uniform wear of the pantograph carbon collector, with stagger at succeeding structures being normally to the opposite side of the track centreline with the provision that the rate of change of stagger should not normally exceed 1:100, relative to span length.

• For the design of the registration elements at the support points, without wind, shall be the maximum dynamic value. Accordingly, the following staggers shall be adopted.

Table 6.2-1 Stagger Criteria

Normal Absolute max

Mainline tangent track 200mm 250mm

Mainline curved track 200/250mm 300mm

• Maximum operation speed: 110kph.

Page 36: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-18 December 2015

7.0 Delivery, Storage and Handling

a) The Contractor shall arrange suitable off-site storage facilities for all materials. Sufficient stock of items shall be in continuous storage and on site to permit the Engineer to inspect on a regular basis all components prior to their inclusion in the Works. The security and protection of all stored items will be the sole responsibility of the Contractor.

b) The identification mark of the manufacturer or foundry and the pattern numbers assigned by the supplier shall be infused into all castings. Marks and numbers shall be of readable size and in such a position that they will not affect the electrical or mechanical performance of the components or of the system.

c) The Contractor shall ensure that all materials are suitably packaged and protected against

damage during transportation and delivery. Poles, disconnectors, voltage detectors, etc shall be prepared and shipped in a manner that will prevent damage to the galvanized or painted surfaces.

d) All wire and cable shall be shipped on reels suitable for the type and weight carried.

Damage to reels shall be cause for rejection of the wire or cable.

e) All shipping boxes, bags or crates shall be properly marked showing the contents of each. If different materials are packaged in a box, bag or crate, all items shall be appropriately packaged and properly marked or tagged prior to packing.

f) The Contractor shall store all products in accordance with the manufacturer's instructions

and shall ensure that all material is protected from damage and exposure. Fittings and hardware shall be packaged in a manner that will allow stacking and outdoor storage until installation with no harmful effects.

g) Any damage to the equipment and material shall be the Contractor's responsibility, and all

repairs and replacements shall be accomplished by the Contractor in accordance with the manufacturer's instructions at the Contractor's cost.

8.0 Spare Parts and Consumables

The Contractor shall submit a list of spare parts, tools and equipment that are to support the normal operation of the OCS. The final-listed spare parts and consumables shall be supplied by the Contractor. All the spare parts shall be properly packed in a safe container with the complete list, part number, and name of manufacturer and supplier during the final acceptance. The Contractor shall be required to guarantee spare parts availability for not less than fifteen (15) years after the date of issue of taking over certificate, in case of additional spares required after the Defects Notification Period. The following main components shall be considered in the list of spare parts, but not limited to: • Insulators: minimum 10; • Poles: minimum 1 of each type; • Voltage detectors: minimum 2; • Disconnectors: minimum 1;

Page 37: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCS-19 December 2015

• Section insulators: minimum 1; • Cantilever tubes: minimum 2 of each type; • Tensioning clamps: minimum 2 of each type; and • Pulley: minimum 1 of each type.

9.0 Special Tools

One set of special tools, test equipment, jigs, fixtures and gauges required to carry out all functions described in the Maintenance and Operation Manuals, or as required by the PSPR; shall be delivered before the Issue of the Taking Over Certificate. This shall not be less than the list of equipment provided by the Contractor, along with his Bid. The Contractor may add any additional equipment required, but, at no extra cost to the Employer. The extent of supply shall include protective or carrying cases, as may be appropriate for the storage and use of each item as agreed by the Engineer.

The Contractor shall submit six (6) copies of complete illustrated parts lists and overall "exploded views" of assemblies and sub-assemblies for all Plant. This shall include reference to all assemblies, sub-assemblies special tools, jigs, fixtures and gauges required for the operation and maintenance of the equipment by the Employer.

10.0 Training Program

The Contractor shall provide the Training Program to the Maintenance Personnel of LRTA. The Training Program shall include, but not limited to: • Maintenance and Isolation Method of Newly Installed OCS; • Stagger and Height Measurement using Electronic Measuring Devices; and • Others which are necessary for the technical benefit of the Maintenance Personnel and the

LRTA.

Page 38: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

TECHNICAL SPECIFICATIONS

SIGNALING LRT Line 2 Extension Project

Page 39: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Signaling Table of Contents Page Abbreviations 1 1.0 Introduction 3 2.0 Scope of Works 3 3.0 Definitions 4 4.0 System Description 5 4.1 System Description of LRT East Extension Line 2 5 4.2 Extension of the Existing Line 2 5 4.3 General Technical Requirements 6 5.0 Signaling System Safety Criteria 7 6.0 Electromagnetic Compatibility 9 7.0 Quality, Safety and System Assurance 9 7.1 Quality Assurance 9 7.2 Safety and Systems Assurance 10 7.3 Systems and Equipment Rams 12 8.0 Signaling Requirements 12 8.1 Automatic Train Protection (ATP) System 12 8.2 Automatic Train Operation (ATO) System 14 8.3 Automatic Train Supervision (ATS) System 14 8.4 Functional Requirements of the ATS 16 8.5 Automatic Train Regulation (ATR) 18 8.6 Scheduling 19 8.7 Timetable Editing 19 8.8 Additional Trains 20 8.9 Additional Journey 20 8.10 Cancellation of Trains 20 8.11 Dwell Times 21 8.12 Train Describer and Train I.D. 21 8.13 Service and Diagnostics 21 8.14 Recording 22 8.15 Traffic Reporting and Statistics 22 8.16 Simulator 23 8.17 Playback 23 9.0 Signaling Hardware and Software 23 9.1 Interlocking 23 9.2 Signaling Interlocking System Principles 24 9.3 Software 30 9.4 System Software 30 9.5 Application Software 30 9.6 Operational Requirements 31 9.7 Operational Control Center (OCC) 32 9.8 Wayside Equipment 33 9.9 Power Supply 34 9.10 Grounding 37 9.11 Transient and Lightning Protection 39 10.0 Interfaces Between other Systems 40

Page 40: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

10.1 Interface Management Plan 40 10.2 Point Machine Area Lighting and Communications 41 11.0 Installation Requirements 41 11.1 Cabling for Signaling 43 12.0 Testing and Commissioning Requirements for the Signaling System 45 13.0 Environmental Conditions 47 14.0 Maintenance 48 14.1 Maintenance During Defect Notification Period (DNP) 49 14.2 Wrong Side Failure 49 14.3 Defects Notification Management Plan 49 14.4 Temporary Alterations to Restore Service 49 14.5 Discrepancies Between Installation and Design Records 49 14.6 Storage of Equipment and Materials During the Maintenance Period 50 14.7 Failure Investigations 50 14.8 Software Support 50 14.9 Security Obligations 50 14.10 Error Correction 51 14.11 Fixes or Patches 51 14.12 New Versions 51 14.13 Debugging and Trace Software 51 14.14 Corrective Maintenance Procedures 52 14.15 Defect Notification Period 52 15.0 Maintenance Tools, Special Tools and Test Equipment 53 16.0 Manuals 53 17.0 Spare Parts 54 17.1 Contractor Spare Parts 54 17.2 Defect Notification Parts 55 17.3 Commissioning Spare Parts 56 18.0 Training 57

Page 41: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-1 December 2015

Abbreviations

ARS Automatic Route Setting ATC Automatic Train Control ATO Automatic Train Operation ATP Automatic Train Protection ATS Automatic Traffic Supervision ATR Automatic Train Regulation CATC Continuous Automatic Train Control CTC Centralized Traffic Control DLP Digital Light Processor DNP Defects Notification Period DTS Data Transmission System EMC Electro Magnetic Compatibility EMI Electro Magnetic Interference EN Euro Norm FAT Factory Acceptance Test FS Fail-safe GS General Specification GUI Graphical User Interface HMI Human Machine Interface IEC International Electro-technical Commission IEEE Institute of Electrical and Electronic Engineers ISO International Standards Organization JTC Joint-less Track Circuit KHz Kilo Hertz LAN Local Area Network LED Light Emitting Diode LCW Local Control Workstations LOMA Limit of Movement Authority LRT Light Rail Transit LRTA Light Rail Transit Authority LRV Light Rail Vehicle LCD Liquid Crystal Display LCP Liquid Crystal Panel MTBF Mean Time Between Failure MTTR Mean Time To Repair NFPA National Fire Protection Association OCC Operations Control Center O&M Operations and Maintenance OTDR Optical Time Domain Reflectometer PEC Philippine Electrical Code PPSP Particular Performance Specification and Parameters QAP Quality Assurance Plan QMP Quality Management Plan RAMS Reliability, Availability, Maintainability and Safety SA System Assurance SAP Systems Assurance Plan SCADA Supervisory Control & Data Acquisition System

Page 42: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-2 December 2015

SER Signaling Equipment Room SIL Safety Integrity Level TD Train detection TEL Telecommunications TER Telecommunication Equipment Room UPS Uninterruptible Power Supply V&V Verification and Validation VDU Visual Display Units WS Workstations

Page 43: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-3 December 2015

1.0 Introduction

This Particular Performance Specifications and Parameter (PPSP) provides the requirements for the signaling system due to the provision of two (2) new stations at Emerald and Masinag. This will extend the current LRT Line 2 by 3.93km. This PPSP shall be read in conjunction with the Conditions of Contract, General Specification (GS) and Employer’s Requirements as well as Tender Drawings for Electrical and Mechanical Works and all other documents attached to the Contract. In the event of a conflict between the GS and the PPSP, the requirements of the PPSP shall prevail.

2.0 Scope of Works

a) The Contractor shall design, manufacture, supply, factory test, ship, delivery to site, installation, setting-to-work, site testing, commissioning and provide attendance during the Defects Notification Period of the Signaling and Train Control system and associated sub-systems. The Contractor must ensure the seamless operability with the existing Signaling system of LRT Line 2. Additionally, for the LRT Line 2 East Extension Project the Signaling and Train Control System shall be fully compatible with the existing signaling system.

b) For the LRT Line 2 East Extension Project, the Contractor shall modify and/or upgrade the existing signaling system from Santolan and the OCC, to ensure a seamless integration and interface for the safe movement of trains in accordance with established operating procedures. Also in accordance with Signaling Standards and in conformity with the requirements of the LRTA to fulfill the required headway. The signaling for LRT Line 2 East Extension Project shall not reduce the current functionality of the operating capabilities.

c) The Scope of Signaling works for the LRT Line 2 East Extension shall include, but not be limited to the following:

• The upgrade of the Operations Control Center (OCC), Signaling Equipment Room

(SER) and in the Depot SER, and the Electrical Room. Upgrading of OCC works shall include all signaling consoles, server, simulator and shall establish a Local Area Network (LAN) for signaling;

• The Signaling system between Santolan Station and Emerald Station including wayside equipment;

• At Emerald Station all related signaling system equipment including the wayside apparatus;

• The Signaling system between Emerald Station and Masinag Station including wayside equipment;

• The Signaling equipment between Masinag Station including wayside apparatus to the end point of the extension track including wayside;

Page 44: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-4 December 2015

• At Masinag station, all related signaling system equipment (wayside and interlocking), for all approaches;

• Installation of any and all signaling functions and equipment, required to seamlessly

operate trains from the existing line 2

• (Santolan) to the LRT Line 2 East Extension;

• All inspection equipment, facilities, special tools and test equipment;

• Training of the Operation and Maintenance personnel for the signaling system;

• Six (6) hard and one (1) soft copies shall be submitted for the Design Operating and Maintenance Manuals and other pertinent documents for the signaling system and equipment; and

• Spare parts for the signaling system as described in this Specification.

3.0 Definitions

The following defined terms shall be adopted within this Specification: a) Abnormal Operation -The situation where the Signaling and/or Train Control System

operates in a manner not intended by the design.

b) Availability -The probability that an item will be in a state to perform a required function under given conditions, at a given instant in time or over a time interval, assuming that the given external resources are provided.

c) In - Cab Signaling -Signaling in the train cab which governs the movement of the train by conveying the Limit of Movement Authority (LOMA) and the authorized speed target distance/speed as deduced from the most restricting ATP condition.

d) Controller -Any staff authorized by the Employer to control the System.

e) Dwell -The period of time taken from the instant that a train stops at a station until the point in time when the train restarts.

f) Equipped Train -A train with fully operational Signaling and Train Control System equipment installed onboard.

g) Fault-Tolerant -Ensures that the system deteriorates only within the permissible design criteria. The design principles ensure that any failure will not interrupt the consistent functions of the overall system or any portion thereof.

h) Human Machine Interface (HMI) -The visual interface between the controller and the control system. The HMI consists of the computer screens, displayed objects, icons, and equipment as well as the facilities by which the Controller executes control.

Page 45: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-5 December 2015

i) LOMA -The point beyond which a train may not safely proceed.

j) Mimic -A graphical representation of the railway and its global operating status.

k) Reliability -The measure of ability to rely upon equipment and systems to perform to their intended function. The measure of reliability is Mean Time Between Failure (MTBF).

l) Safety-Critical -Failure of the system, sub-system or equipment will directly lead to a situation with the potential to cause harm, injury, or damage.

m) Signaled Headway -The minimum time interval that the Signaling and Train Control System will permit between two travelling trains.

n) Unauthorized Roll-back -An unintentional reversal of the train’s direction.

o) Wrong-Side Failure -A failure which results in the protection normally provided by the signaling equipment being reduced, which could directly lead to a situation with the potential to cause harm, injury, damage.

4.0 System Description

4.1 System Description of LRT Line 2 East Extension

The present LRT Line 2 system is approximately 14km in length and runs from Recto Av. to Santolan where the Depot is located. The trains are 92.6m in length and consist of four (4)-cars. The LRT Line 2 existing signaling system is comprised of a fixed block system adopting Continuous Automatic Train Control (CATC). The CATC comprises of Automatic Train Protection (ATP), Automatic Train Operation (ATO) and Automatic Train Supervision (ATS) in conjunction with a Microprocessor-based Interlocking System. It operates as a train control system that provides safety functions for train detection, train separation and control and protection for train movements. The system is designed as fail-safe; so that if any malfunctions occur, the system will revert to a safe condition. Train movement is controlled by operators from in the Operations Control Center (OCC), which is located within the Santolan Depot. The system may also be controlled from Local Workstations. The wayside equipment consist of point machines. Additionally, transponders/balises are provided on the wayside for the transmission of data to and from the trains.

4.2 Extension of the Existing Line 2

In order to efficiently accomplish the works, the Contractor shall comprehensively liaise and coordinate with all other Systems to define the interface details. This shall include, but not be limited to:

• Detailed requirements on the railway route alignment, track layout, etc; • Power supply and distribution system; • Data transmission system with Telecommunications (TEL) system; • Installation of wayside signaling facilities;

Page 46: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-6 December 2015

• The interface strategy to ensure a seamless integration with the existing Line 2 signaling and completion of the extension line; and

• Migration and Integration Plan.

4.3 General Technical Requirements

a) For the LRT Line 2 East Extension Project, equipment, materials and designs supplied for signaling systems shall be designed and installed in accordance with the most stringent railway Standards and Codes. Where such standards, regulations or codes are unavailable appropriate international standards shall apply. The Contractor shall indicate the relevant standard and specification for all equipment that is to be supplied for the Project. The equipment shall be one that has been previously employed on similar Railway Administrations and is proven for its intended application.

b) Equipment in this particular context shall be construed to include both hardware and software. The equipment shall be one that has been previously employed on similar Railway Administrations and is proven for its intended application.

• Train detection equipment; • Microprocessor-based interlocking system and other Microprocessor-based

equipment; • Wayside signals with direction indicators where necessary; • Wayside ATP/ATO equipment; • Safety Relays (if required); • Point Machines; • LCW; and • Cabling and wiring inclusive of cable cabinets or cable rack systems.

c) The Contractor shall comply with all relevant National Standards and the Philippine

Electrical Code (PEC) for the design and installation of electrical equipment with respect to grounding and bonding. Moreover, the Contractor shall take into consideration corrosion control associated with stray currents derived from the traction power system in conjunction with the respective codes and regulations currently in effect. The Contractor shall also refer to the Power Supply and Electrical Works, Employer’s Requirements and any or all Performance Specifications, with respect to grounding, bonding and corrosion protection.

d) The Contractor shall present a consistent policy for the complete LRT Line 2 system by

providing a functional compatibility analysis for each proposed system interface taking into consideration those already in operation and the existing equipment. Such analysis shall be documented and submitted to the Engineer for approval. The Contractor shall provide an assurance or statement that the functionality and performance of the new sub-system for the LRT Line 2 East Extension Project, does not differ from the function and performance of the sub-system for the existing LRT Line 2.

e) Details of the in-service LRT Line 2 equipment and systems shall be made available to the Contractor, for their information, at the premises of the LRTA. No information in this Specification shall be construed in any manner as a full technical definition of any system

Page 47: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-7 December 2015

or part thereof. The numbering scheme proposed by the Contractor shall be consistent with the system currently adopted by LRT Line 2 and shall be subject to approval by the Engineer. All drawings, schedules and plans shall be prepared in a format agreed with the Engineer. All symbols, definitions and abbreviations shall be fully consistent with the existing system and shall be described on the drawings. All symbols, definitions and abbreviations shall comply with relevant standards applicable to Railway signaling symbols, definitions and wiring diagrams. All drawings, plans, schedules, wiring and cabling diagrams shall be provided with an appropriate description of the operation of the proposed systems.

f) All materials shall comply with Philippine National Fire Codes, and where applicable, international fire standards. All designs, materials and equipment shall continue to operate safely and correctly with the existing traction power system. All designs, materials and equipment shall continue to operate safely and correctly in the presence of electro-magnetic fields generated by other railway related equipment or by the environment in which the equipment is operating. The Contractor shall identify sources of potential EMI/RFI and provide adequate mitigation measures to counteract the possible effect on equipment.

g) All designs, materials and equipment shall be of fully proven technology with substantiated historical proof of operation in similar conditions. All designs, materials, equipment, fixtures, fittings and other accessories supplied under the contract shall require approval from the Engineer.

h) The Contractor shall prepare, and keep up-to-date, a complete set of "As-Built" records of the execution of the Works, showing the exact as-built locations, sizes and details of the Works as executed. These records shall be kept on the Site and shall be used exclusively for the purposes of this Sub-Clause. Sufficient copies (numbers to be agreed with the Engineer) shall be supplied to the Engineer prior to the commencement of the Tests on Completion.

i) In addition, the Contractor shall supply to the Engineer as-built drawings of the Works, showing all Works as executed, and submit them to the Engineer for review as specified within the time frames in the contract documents. The Contractor shall obtain the consent of the Engineer as to their size, the referencing system, and other relevant details.

j) Prior to the issue of any Taking-Over Certificate, the Contractor shall supply to the Engineer the specified numbers and types of copies of the relevant as-built drawings, as specified within the time frames in the contract documents. The Works shall not be considered to be complete for the purposes of taking-over until the Engineer has received these documents.

5.0 Signaling System Safety Criteria

a) The prime objective of extending the signaling system on LRT Line 2 East Extension Project is to provide an efficient system for the traveling public. It is essential that safety shall be considered paramount in the signaling design, during installation and testing phases of the project. The Contractor shall warrant the safety of the installation, demonstrate to the Employer the safety of the system through a series of rigorous tests,

Page 48: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-8 December 2015

and supply all essential items to maintain the safety level throughout the life-cycle of the system.

b) The Contractor shall comply with requirements indicated in the following standards, but not be limited to the following: • IEC 60068 Environmental Testing Procedures • IEC 60721 Classification of Environmental Conditions • IEC 61508 Functional Safety of Electrical/Electronic/Programmable

Electronic Safety-Related Systems • IEC 62236 Railway applications - Electromagnetic compatibility • IEC 62267 Railway applications - Automated Urban Guided Transport

(AUGT) safety requirements • IEC 62278 Railway applications - Specification and demonstration of

reliability, availability, maintainability and safety (RAMS) • IEC 62279 Railway applications - Communications, signaling and

processing systems - Software for railway control and protection systems

• lEC 62280 Railway applications - Communication, signaling and processing systems

• lEC 62290 Railway applications - Urban guided transport management and command / control systems-

• lEC 62425 Railway applications - Communication, signaling and processing systems-Safety related electronic systems for signaling

• lEC 62427 Railway applications – Compatibility between rolling stock and train detection systems.

• lEC 62493 Railway applications – Environmental conditions for equipment

• lEC 62305 Protection against lightning • ISO 9000-3 Quality management and quality assurance standards-Part 3:

Guidelines for the application of ISO 9001 to the development, supply installation and maintenance of computer software

• CENELEC EN 50081 Electromagnetic Compatibility – generic emission • ISO 10007 Quality management – Guidelines for configuration

management • European Norm Radio Equipment and Systems (RES), Inductive Short Range I-ETS 303330 Device (SRD)

c) The Contractor may propose standards of their respective countries or other international standards agencies provided it is proved that they are at least equivalent or better than those stated above. Moreover, the Contractor shall also apply any applicable Philippine regulations. All designs, material and equipment (including software) associated directly with the control of train movements and speed profiles shall be fail-safe whereas a single malfunction, breakage or disconnection, shall result in a more restrictive condition being applied to the system, and shall not conclude in train movements being allowed under unsafe conditions

Page 49: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-9 December 2015

d) The safety level of all vital systems i.e. Automatic Train Protection (ATP) and the Microprocessor-based Microprocessor based interlocking system and the corresponding application criteria shall comply with lEC 62425 Safety Integrity Level 4 (SIL 4). Additionally the ATS and the ATO systems shall comply with Safety Integrity Level 2 (SIL 2) or more.

6.0 Electromagnetic Compatibility

a) The Signaling system and associated sub-systems shall be electro-magnetically compatible with their environment. They shall not produce electro-magnetic emissions, whether conducted, radiated or induced, which may interfere with the normal operation of the system, or any of the other subsystems, or any equipment used in and around the area. Conversely, all signaling equipment shall function correctly in the presence of electro-magnetic emissions, which may be generated by other components within the system or devices within the surrounding environment.

b) It shall be the responsibility of the Contractor to ensure that any frequencies proposed or generated from their equipment shall not create frequencies or harmonics, which may interfere with signaling or other systems and shall operate within their electromagnetic energy limits. This shall be demonstrated during the Factory Acceptance Tests (FAT) of equipment to be delivered under this project.

c) The Contractor shall provide adequate shielding for both equipment and cabling to ensure that no interference or unwanted signals can be produced. Equipment designs shall ensure that unwanted frequencies are eliminated or as a minimum are reduced below the level of susceptibility to other equipment.

d) The Contractor shall prepare for the approval of the Engineer, a plan to ensure electromagnetic compatibility for all equipment, materials and designs for use on the LRT Line 2 East Extension Project. The Contractor shall additionally, indicate in the plan their specific experience on such matters and shall demonstrate through type test the electromagnetic compatibility of the signaling system with other systems.

e) The electromagnetic compatibility of the signaling equipment shall as a minimum be in accordance with the required standards.

f) The Contractor shall incorporate in their design devices to protect electronic and other equipment from lightning, surges or transients.

7.0 Quality, Safety and System Assurance 7.1 Quality Management Plan (QMP)

a) The Contractor shall prepare a Quality Management Plan to guarantee the quality of the signaling system. The Quality Management Plan must include effective control of designs and manufacture of equipment inclusive of all inspections, calibration, tests and documentation as specified within the GS. The Contractor’s quality Management Plan shall be submitted in a timely manner as specified in the contract.

Page 50: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-10 December 2015

b) The Quality Management Plan will apply to all stages of the project and the plan shall be managed in accordance with the principles enshrined in ISO 9000 series.

c) The Engineer reserves the right to perform audits based upon the agreed Quality

Management plan at any period throughout the project duration. The Employer or their nominated representative shall conduct the audits. The Employer shall give reasonable notice to the Contractor of their intention to conduct such audits.

d) Equipment to be delivered under this Contract shall be subject to factory testing. Where possible, the FAT shall be conducted on complete systems. The Contractor shall generate the FAT procedures in accordance with guidelines set forth in the Quality Management Plan. The FAT shall not commence until the Engineer has approved the procedures.

e) The Contractor shall provide reasonable advanced notice of their intention to conduct factory testing. The Engineer/Employer reserves the right to witness all tests at contractors expense in whatever location, and shall advise the Contractor of their intent to observe tests or otherwise. The Contractor shall inform the Engineer in advance of the type of tests to be conducted.

f) The Contractor shall record all results of tested equipment; any faults or failure of quality standards shall be rectified and retested at the Contractor’s expense. Ordinarily, no equipment shall be transported to site until all faults are resolved and the quality of the works deemed acceptable. Under certain circumstances, this condition may be waived, but only with the written permission of the Employer.

g) All electronic equipment shall be tested in accordance with related standards.

7.2 Safety and Systems Assurance

a) In accordance with the standards mentioned in Clause 5.0, the Contractor shall submit for approval a Systems Assurance Plan (SAP), which describes the methodology on how safety shall be achieved with regard to the equipment proposed for inclusion on the Project. The SAP shall depict how safety is accomplished and managed throughout the life-cycle of the Project inclusive of all activities affecting safety, ranging from, but not limited to, requirements analysis, material and equipment selection to design and the systems validation and verification.

b) The objectives of the Safety and SAP should be the overall elimination or control of hazards and assurance that no single point failure or undetected latent failure in combination with any additional fault would result in a hazard. A resulting acceptable level of risk and in full compliance with safety standards shall be achieved.

c) Equipment used for the extension of the signaling system especially those employed in fail-safe systems shall be required to fully satisfy the criteria for safety and system assurance. To ensure the equipment and design requirements are completely fulfilled, the contractor shall employ scientific and engineering principles to analyze the loss or malfunction of each function and categorize its effect on the system, personnel, passengers and the general public in order to eliminate, mitigate or control potential hazards. The SAP shall ensure the following:

Page 51: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-11 December 2015

• That the system attains the correct level of safety in all phases of the Project. The SAP shall address all activities, which may affect the safe implementation of the signaling system. This includes material selection and conformance, design and installation, verification and validation testing, and maintenance.

• Minimizing the probability of a hazardous condition arising.

• Minimizing the effect of a hazardous condition. An additional aspect of the SAP is to provide a high degree of protection and reliability and minimize downtime during maintenance and malfunction. Quantitative and qualitative goals and requirements shall be specified for system elements where applicable.

• The Contractor shall develop and put into practice a SAP based upon international recognized standards in addition to any relevant local codes and ordinances.

• The Contractor shall submit an overall Technical Safety Report for approval by the Engineer. The report shall include relevant facts pertaining to the safety of the design, inclusive of all supporting documentation. The documentation shall include, but not be limited to the following: Assurance of correct operation; Operation under failure conditions; Operation with external influences Safety related conditions; Test verification and validation results; Quantitative and Qualitative safety analysis; Safety with respect to existing operating rules and regulations; and Maintenance analysis.

d) Should modifications be performed on any safety system for any reason, including interfacing with new equipment to the existing system, the Contractor shall submit detailed work method statements describing the modification and how it is intended to be conducted for approval prior to the commencement of such work. The Contractor shall additionally document any such modifications and shall submit all test certificates.

e) The Employer or their designated representatives throughout the course of the Project reserve the right to conduct audits. The Contractor shall provide all documentation and any other materials as requested by the auditors. The Employer shall give reasonable notice to the Contractor stating their intention to conduct such an audit.

f) Any software programs or modules, which have been specifically written or modified for the Project, shall be subject to quality control as specified in Safety Criteria or an acceptable equivalent standard. The Contractor shall submit their Configuration Management Plan for approval by the Engineer. The configuration plan shall be in accordance with ISO 10007. The Contractor shall also provide and maintain a change record in which all modifications to software and hardware are recorded and the reason for the change. The Engineer shall be notified of any changes to the software.

Page 52: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-12 December 2015

g) Should changes to software modules exceed 20% of the total modules, the software shall be considered as development and be subject to requirements as stipulated in IEC Standard.

h) Prior to the introduction of the signaling system for the LRT Line 2 East Extension

Project, the Contractor shall provide a comprehensive safety case of the systems for which they are responsible, including equipment, designs, verification, validation and testing procedures, and documentation. The safety of the signaling system shall be verified by an independent safety assessor, should such an agency be appointed or requested by the Employer.

7.3 Reliability, Availability, Maintainability and Safety (RAMS)

a) In order to calculate the total system and equipment RAMS, the Contractor shall undertake a study based upon procedures as indicated in IEC 62278 or an acceptable equivalent standard. It is expected that the figures are comparable to those experienced by a modern transit system. The study shall take into consideration the current signaling system.

b) The Contractor shall prepare a RAMS plan/analysis and in addition to the System Safety Plan, for the effects of failure modes and their potential consequence to the system. The Contractor shall also produce a reliability critical items list.

c) The Contractor shall also provide the following information: • MTBF of the Signaling and Train Control system; • MTBF for individual subsystems pertaining to the entire signaling system; and • MTBF for individual components and elements of the various subsystems.

d) The Contractor for maintenance purposes shall provide Mean-Time-To-Repair (MTTR)

figures for signaling equipment and their effect on the overall availability of the system.

e) The additional requirements of the LRT Line 2 Extension Project shall not diminish the availability of the signaling sub-systems. The Contractor shall stipulate the availability of their equipment and subsystems and shall achieve the minimum availability criteria, which is as follows: • Automatic Train Protection System – 99.99%; • Automatic Train Operation – 99.98%; • Automatic Train Supervision – 99.97%; and • Microprocessor- based Microprocessor based interlocking system – 99.99%.

8.0 Signaling Requirements 8.1 Automatic Train Protection (ATP) System

a) The ATP System is comprised of two major elements, namely, the wayside equipment and the on-board vehicle apparatus. For the LRT Line 2 Extension Project, no new on-

Page 53: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-13 December 2015

board equipment is required. Therefore, this section is mainly concerned with the ATP wayside equipment.

b) The ATP equipment shall be of fail-safe design with high availability and designed in accordance with SIL 4 requirements as stipulated in standards or an acceptable equivalent. The Contractor shall provide valid substantiation of implementation of the proposed system and associated equipment together with references of successful in-service operation on similar transit networks. This shall be supported by full technical details and description of equipment and system operating philosophy, including failure modes.

c) The ATP system should be modular in design for installation, and wayside equipment or other related apparatus enclosures shall be mounted for ease of replacement in the event of malfunction. The equipment (hardware and software) must be of proven design and application.

d) ATP shall be provided on all main line running sections inclusive of turn-back facilities at terminal stations and emergency turn-backs.

e) The ATP shall also be capable of establishing and ensuring observance of temporary or permanent speed restrictions in addition to the provision of safe stopping profiles for all train movements.

f) The ATP system design and equipment shall be capable of maintaining a safe braking

distance between following trains at all times. The Contractor shall explain in a separate document the method and all parameters adopted for use in the calculation of overlap distances. The braking distances shall assume worst case braking with variables including equipment reaction, poor rail/wheel adhesion and other imprecise characteristics shall also be taken into consideration. The Contractor shall identify and quantify all tolerances and assumptions, the measures adopted in the calculations and their subsequent evaluation, and submit them for approval by the Engineer.

g) The design of the signaling system shall be based upon a train service braking rate of 1.3/sec.2 and an emergency train-braking rate of 1.5m/sec.2.

h) The ATP target speed profiles are to be determined in conjunction with the Microprocessor based interlocking system. The method of transmitting information from the wayside equipment to the train-borne apparatus and receiving data from the on-board equipment will be by track circuits. Additionally, wire loops may be adopted for the transmission of data to the train.

i) The Contractor shall document the design and the method of operation of the proposed ATP wayside equipment. The explanation shall be detailed and shall provide the necessary documentation in order to substantiate that the system is fully compatible with existing equipment, which shall be retained.

j) The Contractor shall document in detail the effect of ATP wayside transmission failure as

prescribed by The Contractor’s system and its potential consequences to the safety of the ATP system inclusive of maintaining safe braking distances.

Page 54: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-14 December 2015

k) With the inception of the LRT Line 2 Extension Project at Santolan station, where the existing reversing turnouts are located, the existing balises or loop coils (inclusive of signals and Track circuit equipment) within the vicinity shall be modified. If necessary they may require to be changed to support the required headway operational requirement of this project. The Microprocessor based interlocking system shall adopt the necessary changes, alterations and additional wayside equipment. This includes, but not limited to, additional hardware/modules/boards for track circuits, balises, loop coils, cables and power supply upgrade to complement the additional loads.

l) Masinag station being the end of the line where train turn around shall be provided with Buffer Stops as presently installed in Line 2. The ATP braking curve shall ensure that under the worst case scenario, the train shall stop before reaching the buffer stop. The criteria and method of calculation related to this installation shall be submitted for the Engineer’s approval.

m) Corresponding signaling signage shall be installed at the emergency turnouts, end of line and, if necessary, the reversing turnouts as well, for operator’s visual aid. These shall be located before the end of the ATP programmed target distance.

n) However, beyond the signage, especially in the end of line, the ATP system shall ensure that the train shall come to a complete stop prior to reaching any such signage, Should the train overrun this sign the ATP system shall invoke the train’s emergency brake.

o) An overlap distance shall be ensured at all times within the target distance as indicated by the ATP system. The Contractor shall propose and justify the minimum overlap distance.

8.2 Automatic Train Operation (ATO) System

a) The ATO system compromises of two major sections namely, the wayside equipment and the on-board vehicle apparatus. For the LRT Line 2 Extension Project the Contractor shall ensure that all onboard equipment is modified, updated as required to cater for the additional route information required for the LRT Line 2 extension. Additional ATO equipment, modifications shall also be necessary at the two new stations.

b) ATO controls the normal train operating functions including propulsion, coasting,

braking, and correct station stop location in accordance with track characteristics such as gradient and curvature, and performance of rolling stock. ATO information is exchanged at stations and any auto start location.

c) Train operation shall be performed by the ATO system. However, it will be required that a train operator starts the train in ATO by pressing a button. The ATO system drives the train from station to station smoothly and efficiently. It shall stop the train at the required platform position with a minimum of 99.98% accuracy and opens the train doors and the tolerance shall be within ± 1.0 meter.

d) ATO system shall fulfill the performance requirements that are required by the train operation plan especially the turn back operation at Masinag station.

Page 55: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-15 December 2015

e) The ATO wayside system transmits data by both loop coils and possibly transponders/ balises. The Contractor shall ensure the ATO system is compatible with that currently employed on the existing line.

8.3 Automatic Train Supervision (ATS) System

a) This section depicts the design and operational requirements of the ATS, which forms part of the ATC concept provided for Line 2. The ATS system shall require modification to include the additional control and monitoring functions as needed by the LRT Line 2 Extension Project.

b) The Contractor shall perform all modifications to all appropriate modules of the ATS software inclusive of Simulator, Playback, etc. – and should it be necessary, to the ATS hardware.

c) The Contractor shall also take into consideration response time of the ATS system and the effect of additional functions may have to the system, and shall replace units with faster processors should they fail to fulfill the stipulated requirements.

d) The Contractor shall submit all proposed alterations to software modules to the Employer for approval.

e) The ATS software shall be rigorously tested using formal methods of verification and validation in accordance with the relevant standards. The Contractor shall ensure operational and functionality of the ATS system remains similar or better to those of the existing facilities.

f) The ATS System enables operators to supervise and monitor the entire rail system from an OCC. The OCC shall be capable of directing all transit operations both in normal and perturbed conditions. Should a complete failure of the OCC occur, operations may be continued from LCW located at the main Microprocessor based interlocking System areas. The LCW shall be capable of performing and displaying the same features and functionality as the OCC workstations.

g) The existing ATS subsystem Local Area Network (LAN) architecture shall be extended to incorporate the additional two (2) stations and the respective equipment. The Contractor shall ensure the additional connections to the existing LAN system do not have a detrimental effect to the overall availability objectives. The system shall be capable of expansion with minimal modification to the operating and application software. The Contractor shall provide appropriate documentation to confirm this requirement.

h) The OCC and LCW which generate geographical representation of the transit system network and shall be modified to incorporate the additional control and monitoring functions as required by the LRT Line 2 East Extension Project. The existing display shall display pages incorporating an ergonomically designed user-friendly HMI, adopting Graphical User Interface (GUI) techniques in a windows driven or similar environment. The display shall be capable of displaying an overview of the system and of individual stations and Microprocessor based interlocking system areas.

Page 56: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-16 December 2015

i) The Visual Display Units (VDU) shall be capable of rapid change between the display pages. The Contractor shall indicate the response times for the following: • Request a change of display page; • To fully display the requested page; • To request operation of route setting or equipment; • To action the request; and • Confirmation to the operator that request is accepted and operation complete.

j) The total response time under worst-case conditions for a complete operation shall not be

greater than ten (10) seconds. The changing of display pages shall require a response time of not greater than two (2) seconds under worst-case conditions inclusive of the additional loading of the system with respect to the Line 2 East Extension Project requirements.

k) Workstation visual display units shall not be degraded by EMI and processor connections and shall be appropriately isolated to avoid spurious operation. All processors inclusive of memories shall not be corrupted by the loss or momentary interruption of power, and shall be capable of restarting upon restoration of power. Battery backup shall be supplied for all essential memories. The ATS shall be configured to ensure that availability requirements are fulfilled. Where redundant servers are used both the on-line and standby shall receive data in order that both are fully updated; only the on-line machine provides the output function. Changeover from the on-line machine to the standby shall be automatically achieved. However, this may also be performed manually.

8.4 Functional Requirements of the ATS

a) The ATS shall directly interface with the microprocessor-based Microprocessor based

interlocking system located within the OCC. The Contractor shall provide fully documented listings of all inputs and outputs.

b) The ATS should typically monitor the status of the signaling and train control functions

as indicated below:

• Track section occupation; • Route set including Automatic Route Setting (ARS) and Fleet Mode; • Turnout position; • Signal Aspects • Train describer; and • Alarm Handling.

c) Any failure of the above functions generates an alarm, which shall be displayed on the

operator’s workstation indicating the criticality of the malfunction, and also logged (inclusive of date and time) in hard copy form on a dedicated printer. All alarms shall be time and date stamped; this shall be derived from the master clock, to which the ATS must interface. Alarms may be grouped and shall be differentiated by the level of criticality. Critical alarms shall take preference over non-critical alarms and shall remain displayed until the associated problem has been rectified. Additionally, alarms shall be annunciated with an audible device, which shall require to be acknowledged by the

Page 57: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-17 December 2015

operator. The Contractor shall submit their proposed alarm detection and display philosophy for approval by the Engineer.

d) The operators shall be able to set and cancel routes manually using a pointing device

and/or a keyboard. However, to ensure that trains are not unnecessarily held due to the operator not setting the route, ARS is to be included. This allows routes to be automatically set in front of trains provided the train is scheduled and the route ahead is clear. Unscheduled trains will not invoke the ARS. The operator may also inhibit the ARS.

e) The ARS function automatically sets routes for trains based upon: • The position of trains as reported by the train describer; • The train number, in accordance with timetable; and • Destination information with respect to where the train will terminate and turn around.

f) ARS requests shall be tested for route availability by the Microprocessor based interlocking system prior to the request being successful or otherwise. The ARS may try several attempts to set the route if the first effort fails. However, the ARS is not capable of route canceling. The Contractor shall stipulate either the number of re-tries for ARS, or a pre-determined timeout should the route setting fail. The ARS shall be capable of junction and terminal management in order to avoid conflicts and potential delays to traffic.

g) Signals shall also be capable of operating in “Fleet Mode”. This operating mode shall indicate a distinct color on the ATS workstation that distinguishes it from other signal modes on the traffic controller’s display. In fleet mode particular signals perform as automatic signals, with the signal returning to its most restrictive aspect automatically, when a train clears the overlap of the signal ahead.

h) In addition to the above, the following functions should also be available and in some cases, the parameters are to be adjustable both automatically and manually: • Automatic Train Regulation (ATR); • Scheduling; • Timetable Editing; • Additional Trains; • Additional Journey; • Cancelation of Trains; • Dwell Times; • Train Describer and Train Identification; • Service and Diagnostic; • Recording; • Traffic Reporting and Statistics; • Simulator; and • Playback.

Page 58: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-18 December 2015

8.5 Automatic Train Regulation (ATR)

a) The ATR enables trains to be regulated automatically and manually, to achieve a given “traffic quality of service target”. This operates in conjunction with station dwell times and train target speed profile between stations with minimum energy consumption.

b) In order to maintain timetable operation, the ATS shall continuously compare the actual service against the schedule. The system shall provide automatic train regulation in order to minimize traffic deviations from a target “traffic quality of service”. Automatic regulation services shall apply only when the system is set in normal operating mode.

c) The system shall provide services to manage two different “traffic quality of service” targets, these being: • Timetable adherence; and • Headway adherence.

d) Timetable adherence shall minimize deviations between the operating timetable and

actual train movements.

e) Headway adherence shall minimize headway deviation due to train departures at terminal and intermediate stations in order to maintain constant headway as much as possible during perturbations to the system. The system shall not automatically regulate the following types of traffic: • Any non-stop trains; and • Unscheduled trains.

f) Should a changed state occur to the system, the ATR shall also be capable of being

switched into manual mode to allow operator adjustment.

g) In the event of timetable deviation, the ATR shall be capable of immediately implementing a recovery strategy, which shall attempt to restore trains to normal timetable running. The Contractor shall describe their operational philosophies on how they intend to comply with this requirement.

h) Additionally, the system shall provide recovery from the following, which may introduce perturbations into the service: • Disruptions resulting from platform overcrowding and consequentially, extended

dwell times; • Disabled vehicles; • Signaling failures; and • Power failures.

i) Strategy management shall include, but not be limited to the following:

• Centralized automatic regulation;

Page 59: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-19 December 2015

• Centralized manual intervention; and • Schedule reformatting which may include the addition or deletion of trains.

8.6 Scheduling

a) The scheduling function shall be capable of accepting timetables for regular and specials services (e.g. holidays, weekends, etc.). These timetables may be validated by the use of simulators and are able to be loaded directly into the system. The service will then operate to that timetable. The schedule is required to be loaded in order that automatic regulation operates, otherwise nominal, or default or operator adjusted dwell times will be used. The timetable model shall support the following operating features of the complete LRT Line 2 network: • Operational requirements inclusive of number trains necessary; and • Systematic withdrawal of trains from revenue service.

b) The scheduling function shall support timetables containing as many journeys as needed

to operate a service with a theoretical ninety (90) second headways. The total number of journeys will be calculated based on the operating headway and the number of trains running on the line. An on-line display of scheduled trains shall allow timetable performance to be monitored. Each train scheduled shall display their on-time data measured against the timetable and following information: • Train running number and destination code; • Train location (track section number); and • On-time performance such as:

very early (insert parameters); early; on-time; late; and very late.

c) The time criteria for the above categories shall be the same as presently used. Deviation

from the timetable or failure to leave a platform in a pre-determined period shall generate a warning to the traffic operator.

8.7 Timetable Editing

a) The Time Table Editing shall provide convenient functions and HMI to support off-line

editing of a timetable (creation, modification, and storage.). This function shall permit definition of dwell times and running times for various time periods. The Contractor shall submit the type of timetable editor to be employed for approval and shall provide training for operational staff in the use of such an editor. The timetable editor shall be capable of input of different dwell times per timetable selectable by platform / journey number and by time of day (begin and end times), for establishment of default for each time period of the day. The timetable shall also allow definition of different time periods. Additionally, it shall be possible to manually define a dwell time for any train at any platform during any journey. The dwell times shall be determined by operational requirements.

Page 60: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-20 December 2015

b) Additionally, different run time performance levels for each journey and by time of day, dependent upon operational requirements shall also be capable of being input to the editor. Definition of any skip station stops by definition of zero (0) dwell time (exception to minimum dwell time) on a station-by-station basis during each journey. Skip stop operations shall only be used when operationally necessary and are not normally scheduled. Therefore, no allowance in any timetables is required for this feature.

c) The system shall provide processing and storage medium for the timetable editor, which is separate from the resources managing the system operation functions. The Contractor shall state the number of timetables that the system allows to be stored within the ATS system.

d) This function shall also provide convenient functions and HMI together with appropriate functional checking to support alterations to the current timetable by the operations supervisor during revenue service should it be necessary. The function shall reject any alteration that would lead to an inconsistent timetable.

e) Time table shall be printable on the existing system and can be exported using excel,

word or other readable format.

8.8 Additional Trains

The Time Table editing function shall allow the insertion of an additional train into the working timetable. The function shall add the new train to the timetable and shall recalculate automatically the departure times of the other trains, so as to achieve equal train spacing provided that the minimum specified headway is maintained. The traffic operator shall specify the running number and the journey of the previous train in the timetable, if the new train is replacing a defective unit, the number of journeys to be run by the new train, the origin of the new train and the final destination of the new train. Trains may also be inserted into the system at any time for operational requirements.

8.9 Additional Journey

The traffic operator shall be able to perform this control to add journeys at the end of service in the loaded timetable. The journeys shall be added to the timetable and the departure times of the trains shall be recalculated in order to avoid shifting of the timetable. The traffic operator shall specify the running number of the train, and the number of journeys to be added for the train, and the final destination of the train.

8.10 Cancellation of Trains

The traffic operator shall be capable of canceling a train from the loaded timetable. The remaining trains and their departure times shall be recalculated in order to avoid congestion of the system. The traffic operator shall specify the running number of the train to be cancelled, the journey number from which the train is to be cancelled (including the journey), and the final destination of the train.

Page 61: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-21 December 2015

8.11 Dwell Times

a) The dwell time is the amount of time a train stops at a station before proceeding. The dwell time may be adjusted manually, but when used in combination with ATR the value will be attuned upwards or downwards dependent upon whether the train is early or late. The default dwell time shall be set at 30 seconds.

b) When a scheduled train stops in a station, the system shall automatically compute the dwell time at that particular station and a target arrival time in the next station. Calculation of both times shall take into account:

• Current “Regulation Strategy” (Mode of operation); • Current “Target” (schedule or headway); and • Train deviation as compared to the target.

c) The system shall guarantee in any case a minimum dwell time.

8.12 Train Describer and Train Identification (I.D)

a) This function enables the allocation of a journey number to each train on the line and scheduled in the timetable. Each train within the system is given a running number; this unique number allows the train to be tracked. The train describer function enables the operators to view the train as it passes throughout the network. The ATS will identify any train delayed in accordance with the timetable when the train is departing from a station or should the operator wish to display the particular train’s on-time performance record.

b) A train I.D. may be entered manually, if a train is required to be inserted into the system. The running number should automatically change for the return journey. The system shall allow the operator to allocate a train number to a train that has an “unidentified or spurious train number”, or to override a train number.

c) This function shall be capable of identifying all trains in the same sequence pattern as in the timetable or individually by the operator if required to do so. This function shall unambiguously indicate to the operator, which train has been identified. In the event that the system does not associate a train number with the timetable, an alarm shall be produced.

d) The train describer shall indicate all train numbers as they traverse each track section throughout the network. Should the train number fail to step through into the track section upon occupation of the track section or the train number disappears an alarm shall be raised on the operator’s workstation. Train describer berths shall be installed on the mimic panel for each track section, and shall be capable of storing up to several train numbers if necessary.

8.13 Service and Diagnostics

a) The Service Computers are located at the OCC and serve as a user interface for displaying and processing the detected failure stamped with date, time and failure location. It also includes repair instructions for each fault type selected.

Page 62: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-22 December 2015

b) For the LRT Line 2 East Extension Project, additional Service Computers (with updated software version) shall be made available with similar functions as the existing system. The Service & Diagnostic computer, which is located at OCC, is always connected to the Microprocessor based interlocking system to enable failure messages to be continuously collected. The detected failures are stored in a data-base and report in return to the Service computers. Recording, Traffic Reporting and Statistics.

8.14 Recording

a) The ATS system shall provide several services defined hereunder, which allow users to retrieve information relating to traffic, operator controls and system activities during and after train operation. This data shall encompass events and alarms associated with train movement, signaling system changes as provided by the Microprocessor based interlocking system and wayside equipment. The Contractor shall provide appropriate recording facilities to complement these services. All data generated by the ATS shall be capable of being stored on a suitable medium. This shall allow playback in the event of an incident and also provides information on performance. Back up of the system may be done both automatically and manually. The system shall provide three kinds of recording media:

• Access of the data relating to signaling system wherein operational service is

recorded and available for playback;

• Permanent and removable electronic storage medium, which shall be in the form of a Compact Disk (CD) or USB mass storage devices; and

• Paper recording shall be on a dedicated operation printer suitable for an office environment. Permanent electronic storage medium shall utilize an industrial strength hard drive, compact disk or suitably sized USB mass storage devices.

b) Whichever medium is used, data shall be recorded with the date/time stamp, which shall

be derived from the Master Clock. Recording on electronic medium shall be in ASCII format. Recording on electronic medium shall be on specific data log files each covering one full day from 00.00 to 24:00, incorporating the date as the file name.

c) For the permanent electronic storage medium, the system shall automatically manage opening and closing of daily log files, without any loss of data. Retrieval of the data shall be done using the appropriate file names in accordance with the date of recorded event. The system shall provide the capability to switch data recording on and off through an appropriate HMI. However, if the data recording is switched off, a reminder device shall indicate that currently, events are not being recorded.

8.15 Traffic Reporting and Statistics

a) The ATS system shall be capable of supporting the following reports and statistics for

service analysis. The Contractor shall include an appropriate HMI to display and print: • Theoretical number of roundtrips (based on timetable) on any given day; • Actual number of roundtrips made on any given day;

Page 63: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-23 December 2015

• Maximum theoretical headway by time range; and • Effective maximum headway by time range.

b) This function shall allow real-time retrieval and display of the above information during operation with automatic refresh of the appropriate page display. Deferred time retrieval after operation shall also be available.

c) This function shall be capable of providing both state-of-the-art graphical and textual display.

d) This function shall allow identification of individual trains and their performance, and can provide printouts.

e) The timetable deviations shall be shown in time-distance diagrams. These diagrams shall portray the route on the horizontal axis and the time on the vertical axis. The time-distance curves shall be distinct by displaying them in different colors. The diagrams shall be able to be printed on a color printer.

8.16 Simulator

a) The use of a stand-alone ATS simulator facilitates the ability to verify software changes before they are loaded into the main system. The simulator shall operate on exactly the same software as the main system and therefore, shall be required to be modified in connection with the requirements of the LRT Line 2 Extension Project.

b) The simulator provides the capability to test timetables and is also beneficial in the training of operators. The ability to print the screen display shall be provided.

c) Subsequent maintenance measures and procedures will be introduced to ensure that storage devices are backed-up on a regular basis. Accessibility shall only be available to appropriate staff with log-in passwords to ensure that only trained personnel are able to gain access to the simulator system.

8.17 Playback

The data generated by the ATS equipment shall be capable of being “played-back” and shall be used in the event of incident or accident investigation. It also allows operations personnel to study information on “quality-of-service” performance. The playback feature shall be selectable by date and time.

9.0 Signaling Hardware and Software 9.1 Interlocking

a) To accommodate the introduction of additional control and monitoring functions associated with the LRT Line 2 Extension Project, the Microprocessor-based interlocking system will be installed at Masinag station. A Microprocessor-based interlocking system at Santolan shall be required to be modified, if necessary. The Contractor shall perform all necessary modifications to the computer-based Microprocessor-based interlocking

Page 64: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-24 December 2015

system. The System Application and System Software specific to the Microprocessor-based interlocking system shall be rigorously tested using formal methods of verification and validation in accordance with IEC 62279 or an acceptable equivalent standard. All modifications shall be submitted to the Engineer for review. A further Element Control Computer may be necessary for additional control and monitoring functions as required by the LRT Line 2 Extension Project.

b) The design of Signaling logic for the Microprocessor-based interlocking system shall be in accordance with fail-safe principles. All hardware employed shall be of proven design, modular in architecture, easily replaceable with diagnostic features to assist maintenance staff during faultfinding.

c) The hardware employed for the Microprocessor-based interlocking system shall ensure the highest levels of reliability, availability and safety. The software shall be modular in design and proven for use in railway safety control systems and shall comply with IEC 61508 or an equivalent acceptable standard. The additional Microprocessor-based interlocking system shall be capable of interfacing with equipment that exists and be able to communicate with the existing Microprocessor-based interlocking system.

d) The electronic Microprocessor-based interlocking system shall be configured using proven techniques to enable safe performance of all Microprocessor-based interlocking functions.

e) Power supplies shall include appropriate redundancy to ensure an adequate source of supply at all times. The Microprocessor-based interlocking system shall include appropriate modules or otherwise to ensure all track sections, signals, points at emergency and reversing turn backs, ATP equipment and routes, including any cross boundary Microprocessor-based interlocking system information are able to be controlled and monitored. Modules used for the interfacing of wayside or other equipment with the Microprocessor-based interlocking system shall be fail-safe in design.

f) Communication between the Microprocessor-based interlocking system, distributed modules and wayside equipment for control and monitoring purpose shall be fail-safe. Comprehensive error detection measures shall also be employed in order to achieve secure data transmission.

g) The communication between the main Microprocessor-based interlocking system and distributed equipment through Element Control Computer shall be achieved using a dedicated data transmission network. This network shall adopt fiber-optic cables. The Contractor shall identify and justify their selection of the data transmission system and the associated cabling architecture, which shall include redundancy for high availability. The redundancy configuration shall be similar with the existing LRT Line 2 system.

9.2 Signaling Interlocking System Principles

a) The micro-based signaling Microprocessor-based interlocking system shall ensure that a route to be established for the passage of a train may only set under the following conditions:

Page 65: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-25 December 2015

• The track section ahead to the next signal and its subsequent overlap is clear of vehicles.

• All point machines within the route are in the correct position, detected and locked. • No conflicting routes are set and the route is free from opposing locking. • Flank Protection is set. • Signal ahead is proved to be illuminated.

b) Prior to the commencement of design work related to routes and their pre-condition for setting, the Contractor shall produce and submit for approval by the Engineer, documents, which shall describe all possible routes and their management based upon operating and Microprocessor-based interlocking system principles as prescribed by the Employer and as indicated in this specification. The documents shall in principle adhere to rules currently adopted for the current Microprocessor-based interlocking system logic. The documents to be submitted by the Contractor shall contain, but not be limited to the following: • A schematic plan of the track layout indicating track sections, signals, points, balises,

cable loops and any other wayside equipment proposed for the project by the Contractor inclusive of their geographical position.

• Interlocking tables (control tables) that depict all routes and the conditions under which they may operate. This shall include entrance and exit point of the route, the track sections, which are required to be clear, overlap, flank protection, points, and opposing routes and locking. Each route shall be individually detailed and any special conditions or controls which may apply shall be listed. Routes that emanate from controlled signals shall be capable of setting automatically in conjunction with timetable and train describer functions as used within the ATS system.

• The Microprocessor-based interlocking system tables shall also include information that describes available speed profiles transmitted by the ATP equipment dependent on data received from the Microprocessor-based interlocking. Where possible, the information shall be prepared on a per route basis.

• All information transmitted between the Microprocessor-based interlocking system and the ATP system shall be included in an appropriate interface document.

• The Microprocessor-based interlocking system tables shall also indicate conditions

for the locking of points. This shall include deadlocking with track sections, route, and overlap locking. It should list which routes request the points to a required position.

• All information transmitted to and from the Microprocessor-based interlocking system and the ATS system shall be included in an appropriate interface document.

• Other documentation relating to functionality and interfaces with the Microprocessor-based interlocking, which the Contractor deems adequate to further describe and explain its operation to the Engineer’s approval.

Page 66: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-26 December 2015

c) The design of the signaling logic for the Microprocessor-based interlocking system shall be consistent with Microprocessor-based interlocking system principles established for the present Line 2 signaling system. Upon request, the Employer shall provide access to the Contractor to drawings and system currently in use. The Contractor shall also stipulate any additional principles, which may be necessary subject to the Engineer’s approval. The additional control computer to be installed for the LRT Line 2 Extension Project shall comply with the present Microprocessor-based interlocking system principles. This shall include all cross boundary data interfacing with the control computer. The Microprocessor-based interlocking system shall be capable of providing and receiving all necessary data required for the monitoring and control of the system by the ATS system.

d) The electronic Microprocessor-based interlocking system shall interface with the ATP system in order to provide information for maximum allowable speeds with respect to safe braking distances between trains traveling in the same direction on the same line and where trains cross at junctions.

e) ATP target speed profiles to be transmitted to the train shall be provided in conjunction with track conditions ahead. The Microprocessor-based interlocking system shall ensure that only the correct speed profiles are able to be transmitted by interfacing with the ATP equipment. The Contractor shall design Microprocessor-based interlocking system programs and circuitry using fail-safe principles and techniques. All designs shall be submitted to the Engineer.

f) The basis of programs or other software applications shall be consistent with nomenclatures, names, and abbreviations currently used, which shall also be made available to the Contractor upon request.

g) The re-start of Microprocessor-based interlocking system upon restoration of power after

an interruption shall be consistent with the existing system in LRT Line 2.

h) The design shall ensure that any intermittent operation of the vehicle detection system (track sections) from whatever cause shall not initiate premature release of Microprocessor-based interlocking system or any other unsafe condition. Release of the route by the passage of a train shall be achieved by sequential occupation of track sections. The release shall include an inherent time delay; this is to ensure that the Microprocessor-based interlocking system does not prematurely release the route due to a transient operation of the track section.

i) The electronic Microprocessor-based interlocking system shall provide the capability for

manual operation of point machines from both the OCC and the LOW. The request for manual operation of the point machines shall be verified by the Microprocessor-based interlocking system before being executed.

j) Points operated automatically by the Microprocessor-based interlocking system shall remain in their last position until required to be operated by a new route being set or for providing flank protection or manually moved by the operator. The exception is where automatic route setting shall be applied at terminal stations to reduce turnaround times and maintain headway. The Microprocessor-based interlocking system shall monitor all point operations by the use of a timer. If detection is not achieved within a preset time,

Page 67: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-27 December 2015

the power to the point machine shall be removed. The Microprocessor-based interlocking system shall prevent movement of point machines when the respective track section indicates occupied status. However, should occupancy of a track section containing a point switch occur after the point switch has started moving the movement shall not be stopped.

k) Operation of points shall be interlocked under the following conditions: • Route set through the respective points; • Overlap condition extending through the points; and • Flank protection for route.

l) Points shall be capable of being blocked against any operation from both the OCC and the local workstation. Unblocking of the points must be performed from the same location and shall be registered.

m) The present signaling principles allow points to be moved under track section failure conditions in which the respective track section locks the points. This movement is undertaken with the use of an override command, which also operates a counter that increments each time the override is operated. The override command shall also be logged.

n) The Microprocessor-based interlocking system shall test for the availability of a route

prior to issuing the command to set the route. The initialization command for a route request shall emanate from the ATS system. Should the route not be available for whatever reason, an alarm shall be generated after a pre-determined time or after a number of consecutive attempts to set the route failed. If the route is available to be set, the Microprocessor-based interlocking system shall test to ensure that all conditions such as, track sections within the route and its associated overlap are clear, points are locked and detected, no conflicting routes are set, and any opposing locking is free. Should any one of the conditions not be validated, the route shall not be able to display a proceed aspect at the entrance signal, and no ATP target speed transmitted to the train.

o) The Microprocessor-based interlocking system in conjunction with the ATS system shall be capable of performing ARS. The ARS shall only operate for trains that are scheduled within the time-table or have a valid destination code, and may only function if the following Microprocessor-based interlocking system conditions are fulfilled:

• No conflicting route set; • No other train attempting to use ARS using the same route conditions; • ARS is switched on; and • No opposing route set.

p) The ARS shall attempt to set the route for a number of pre-determined time or a number of consecutive times if the route is not immediately available. Upon expiry of the pre-determined time or number of attempts to set the route an alarm shall be generated by the ATS stating that the route is unable to be set.

Page 68: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-28 December 2015

q) The setting of a main route enables data to be transmitted to the ATP system. The Microprocessor-based interlocking system shall guarantee that the signal displays a “proceed” signal prior to any information being sent to the ATP system. Routes set ahead of trains enabling them to proceed shall be automatically released by the Microprocessor-based interlocking system upon successful passage of the train.

r) The routes shall be released sequentially providing correct validation of track sections being occupied and cleared in the correct order. Routes set shall remain locked once the train has entered the route. Cancellation by the train dispatcher shall remove all ATP information; the route however, shall not immediately reset and shall only clear after a pre-determined time period has expired. Automatic release of the route shall be performed in the following manner: • Approach track section(s) – occupied; • First track section of the route – occupied; • Approach track section(s) – clear; • Second track section of the route – occupied; and • First track section of the route – clear.

s) Upon completion of the above sequence sectional route release is applied. Route locking

is still applied to the remainder of the route ahead of the train and shall be released upon sequential occupation and clearance of track sections. This sequential releasing of the route behind the train shall continue until the route is completely released. Any interruption of power supply during this process shall cause the automatic route release to cease, and the route locking ahead of the train maintained.

t) The system shall provide automatic routes in all sections of the system. ARS in conjunction with the ATS system shall also be provided.

u) Enables scheduled trains to be automatically routed in accordance with the timetable. The

ARS shall also be capable of being “switched off” should dispatchers wish to reform the schedule due to perturbations.

v) Where routes occupy the same sections of track in opposite directions or where they may conflict, route locking shall prevent any opposite or conflicting route being able to be set. Route locking shall be released upon the passage of a train or by manual cancellation if the route was not used.

w) The Contractor shall provide the ability to block routes for traffic, inspection and maintenance purposes. Blocking or disabling of routes shall be performed at the ATS level. The blocking function shall be supported by a symbolic reference on the monitors on both the OCC and LCW.

x) If an operator attempts to set the particular route that is blocked, a warning prompt shall remind the operator of the route status. Should the operator attempt to re-establish the blocked route, the operator shall be prompted to confirm their action. Blocking of routes shall be implemented between any entrance signal and their respective exit signal. The blocking of a route shall also inhibit the ARS feature. The inhibiting of any route shall be

Page 69: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-29 December 2015

logged on the event printer for record purposes. Additionally, when the route is unblocked it shall also be recorded in hard copy on the event printer

y) For the LCW, the operational area shall be interfaced with the present system. The Contractor shall adopt the same the methodology as currently used for the transfer from central to local control which controls will remain in the same state prior to any switchover. All indications necessary for operational requirements shall be displayed in a geographical representation of the layout and shall include vehicle detection, point indications, routes set, and signal information. Other indications shall be displayed either by the use of graphics or alphanumerical form. As a general guideline all commands and indications shall be operationally similar to those already used in the existing system.

z) All LCW’s shall be password protected and the user must log-on to the system using an assigned password. Only trained operators with the assigned authorization shall be allowed to gain access to operate the workstation. The workstation shall be located in the room as indicated in the drawings subject to approval of the Engineer. The hardware used for the local control workstation shall be compatible with the system being used for the OCC.

aa) The ATS system and application software shall be the same as that used within the OCC,

operating at the same Safety Integrity Level (SIL-2). The associated printer for the workstation shall be of the low-noise type suitable for an office environment. It shall also be possible to switch off the workstation without affecting the operation of the system.

bb) All LCW’s and associated equipment shall be supplied from a UPS located within the

SER. An event counter shall be integrated into each workstation to count the number of overrides and abnormal operations used.

cc) Each Microprocessor-based interlocking system shall be equipped with diagnostic

features in order to provide efficient faultfinding by means of user-friendly diagnostics. Faults and failures shall be detected and analyzed by this system and these shall be grouped and categorized in different levels dependent upon their criticality to the overall system.

dd) The system shall be capable of providing definitive information to enable the malfunction

to be quickly found and rectified minimizing downtime and possible delays to operations. ee) The diagnostic system shall display the state of all controlled equipment, and shall record

and continuously display any fault conditions until the failure has been rectified. The system shall monitor, but not be limited to the following functions:

• Train Detection -Track sections occupied or free; • Point Machine - Detected in correct position, locked, free-to-move, blocked, and out-

of-correspondence; • Routes - Manual, automatic fleet mode or disabled, route set, emergency cancellation. • Interlocking Status; and • Information concerning the Microprocessor-based interlocking system computers,

error detection, data link and internal communications, buffer overflow, safety devices operation, stand-by available, etc.

Page 70: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-30 December 2015

ff) A selection of these alarms shall also be generated on the operator’s workstations to alert staff of failures.

gg) The diagnostic system shall be located within the signaling equipment room located at the OCC. In addition to monitoring equipment and displaying fault messages, the system shall be capable of activating any utilities such as intentionally disconnecting the Microprocessor-based interlocking system computers or wayside modules during testing or maintenance.

hh) The diagnostic system shall be connected to a PC and monitor, and a logging printer of

the low-noise type using continuous form paper for the recording of failures and operational information.

9.3 Software

a) This section will describe software requirements for train operation, vital signaling principles, processing software requirements.

b) In conjunction with the modification of hardware as stipulated in the Microprocessor-based interlocking system, software shall also be modified to incorporate the additional control and monitoring requirements of the LRT Line 2 East Extension Project. The Contractor shall modify the software in accordance with the quality standards as prescribed in this specification. The Contractor shall also submit all modifications to software modules to the Engineer for evaluation.

c) The software shall be divided into two distinct sections, system or fixed program software and the application software.

9.4 System Software

a) The system software shall be the latest release as updated by the system supplier. The system software shall enable start-up including all self-tests and checks on hardware, memories and safety components, and that the programs and processes are executed in the correct sequence. This shall also ensure that communications with other Microprocessor-based interlocking system and wayside modules is established and that an alternative communication channel is verified as available.

b) The system software shall be proven for its application in railway safety control systems and shall comply with requirements as stipulated in IEC 62279 or an acceptable equivalent standard.

9.5 Application Software

a) The application software shall be designed to meet the requirements of the enhanced signaling system. It shall be capable of fulfilling all Microprocessor-based interlocking system and operating principles.

b) The Contractor shall submit details of the signaling logic to be employed, the method of configuration of the logic inclusive of software tools. The software shall be written in a

Page 71: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-31 December 2015

well-structured format and shall be subject to rigorous testing using formal methods of both validation and verification in accordance with recognized standards.

c) The application software shall also provide status management of the signaling system.

Any change of status of signaling elements such as track circuit occupation or vacancy, point machine detection, signal aspect, route setting and locking shall update the respective element-specific memory. Intermediate status of functions, pre-set or automatic commands and any calculated or virtual elements shall also be included. This data shall then update the components of the operations control system. The Contractor shall submit detailed descriptions of how they shall meet these requirements.

d) The application software shall be approved by the Engineer and shall comply with the following: • It shall be well structured, documented in detail and be capable of being analyzed by

charts, state diagrams, which shall also be subject to approval of Engineer;

• The graphical environment of the electronic Microprocessor-based interlocking system shall provide ATS real time status of all elements of the signaling system, which offers the end-user the opportunity to define the exact structure of the system and the source of any malfunction; and

• All necessary manuals in order that relevant Employer’s personnel are able to

understand the application software.

e) The application software in conjunction with the in-built diagnostics shall monitor the responses from the system. In the event of a malfunction, the application software and/or hardware shall detect the failure within one (1) second. An error message shall be generated to both the ATS system and OCC and to a maintenance technician terminal or workstation with an associated hard copy provided on a printer. All alarms shall be time and date stamped; the Microprocessor-based interlocking system shall interface with the existing master clock system to ensure correct timing and calendar information.

9.6 Operational Requirements

In order for the LRT Line 2 East Extension Project operations to be congruent with the existing LRT Line 2 operations, and to support the same headway during peak hour traffic, the Contractor shall consider all aspects in the signaling design and installation to meet the required headway, especially the configuration of the turn backs.

9.6.1 Graceful Degradation

The Signaling and Train Control systems shall provide for graceful degradation of overall system performance as a result of component failures inclusive of interfaces to other systems. The design shall ensure the highest level of safety during any malfunction whilst maintaining the operational integrity of the system. The Contractor shall refer to the track alignment plan for determining all permanent speed restriction sections; these speed restrictions shall be enforced by the train control system.

Page 72: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-32 December 2015

9.6.2 Reverse Running

During normal operating conditions, the trains shall reverse at terminal stations and at the turn back track of Masinag station. In addition, a reversing capability shall be provided at emergency crossovers and pocket tracks. The ATP facility will supervise all phases of the reversing operation and initiate emergency braking in the event of irregularities or running faults.

9.6.3 Braking and Overlap

The Contractor shall be responsible for determining safe braking distances and other basic parameters of the ATP system. The Signaling and Train Control Contractor shall ensure they coordinate with the Client to determine the characteristics of the Rolling Stock and the alignment data. The braking distances shall assume worst case braking with 25% of braking capacity ineffective, and shall include a factor of safety to cover variations in adhesion and other imprecise characteristics. The Contractor shall state and justify the figure proposed to be used.

9.7 Operational Control Center (OCC)

a) The existing ATS system located at the OCC incorporates the use of an overview mimic

panel. This provides a global display of the status of the entire rail network and includes train identification numbers. This extension contract shall adopt the use of LCD type Digital Light Processing by Techniques.

b) As the existing overview mimic panel will require upgrading, the Contractor shall propose the methodology of how the alteration will be implemented while taking into consideration the ergonomics of the overview panel. Specific attention shall be given the inclusion of the additional display requirement in relation to the present font size. The overall picture quality shall not be diminished due to the inclusion of the LRT Line 2 East Extension Project into the mimic panel. Additionally, as a whole the ergonomics of the OCC shall not be compromised and the Contractor shall ensure that human factors of operations personnel are included in all modifications to be performed.

c) The Contractor shall design the height and the width of the mimic panel considering the operational needs and the size of the OCC. There shall be provision for future expansion.

d) The mimic display shall be positioned and sized such that it presents an unobstructed view to all control room staff when seated at their consoles. The contractor shall perform an ergonomic study for the OCC theatre and submit their proposed layout to the Employer for review.

e) Redundant processors and/or redundant I/O (Input output) modules with auto testing facility shall be used in the design of Mimic Display in order that no single failure of any of the processors and /or I/O shall result in the failure/ blanking of a zone on the display board.

f) The mimic display shall be clearly readable in lighting of 550 lux.

Page 73: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-33 December 2015

g) The mimic display shall as a minimum display the following: • Real time train movement using track circuits’ status; • Display train ID of moving train; • Position of points (locking and detection) and status of routes; • Track circuit failure or track circuit “put out of service” shall allow the progression of

train movement to be followed on the mimic panel without the loss of train description using train tracking algorithm;

• Line side signal status; and • Blocking and unblocking of points, signals and routes.

9.8 Wayside Equipment

a) All trackside equipment shall be installed within and verified against the structure gauge and submitted for the Engineer’s review.

b) All wayside equipment shall be capable of operation in the prevailing environment and climate encountered and shall be suitably protected from the ingress of water and dust particles. All outdoor equipment, termination enclosures, etc. shall be protected to IP 65. The LRT Line 2 East Extension Project signaling system shall incorporate the following wayside signaling equipment inclusive of their fittings, fixtures, accessories, etc.

9.8.1 Point Machines

a) The Contractor shall supply and install new Point machines at the reversing turn back located in Masinag in accordance with the track layout for the LRT Line 2 East Extension Project. The Contractor shall also perform tests and adjustments as necessary to ensure correct operation of the Point Machines.

b) The Point Machine shall be operated using 220V Alternating Current (AC). The Point Machine shall be immune from the potential effects of the traction power system.

c) The Point Machine to be installed shall be of the non-trailable type, and any malfunction

of the machine shall be indicated to the ATS/OCC and on the Maintenance Workstation. 9.8.2 Signals

The Point indicator shall be broadly based upon the existing type currently in use. They shall be of the two-aspect adopting red and green aspects and utilizing route indicators where necessary.

9.8.3 Train Detection System

a) The methodology for train detection adopts the use of Fixed Length Joint-less Audio Frequency Track Circuits (AFTC). Each fixed block section comprise of a transmitter and receiver. The track circuits shall be arranged so that train always runs on to the receiver end first. Moreover, the track circuits are used also to transmit ATP data to the train.

Page 74: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-34 December 2015

b) The Contractor shall adopt the same or similar type of track circuits currently in use on the existing system. Where a line section is capable of being bi-directional, changeover circuitry shall be provided in order that the transmitter and receiver can be reversed.

c) All trains and maintenance vehicles shall be positively detected, whether moving or stationary, under all conditions.

d) If insulated joints are used, the Contractor shall ensure the continuity of traction return current is coordinated with the traction power system design. The number of impedance bonds used (if any) in ensuring continuity shall be limited and shall be subject to the approval of the Engineer.

e) An optimal amount of train detection equipment shall be located on the trackside, and shall be subject to the approval of the Engineer.

f) No equipment failure shall result in a loss of train detection and position.

g) The Contractor shall supply and install inclusive of all fixtures and accessories all equipment pertaining to the train detection system. The Contractor shall perform all adjustments to ensure correct operation of the train detection equipment.

h) At Santolan, the train detection equipment will be required for modification or relocation

to effect the changes in the overlap and speed restrictions in support of required headway requirement. The Microprocessor-based interlocking system shall also subsequently be modified to incorporate the modification or relocation to be made with train detection equipment.

i) The detection system shall be EMC/EMI compatible and shall operate correctly within the prevailing conditions that exist on Line 2.

9.8.4 Balises and Cable Loops

a) The ATO data is transmitted via cable loops. For the LRT Line 2 East Extension Project it is envisaged that the same technology may be adopted. However, the Contractor may wish to introduce Balises, which are also capable of providing such information. The Contractor shall therefore, propose for approval by the Engineer the type of transmission system they wish to introduce. The system selected shall be proven in use on other Metro’s or Rail systems elsewhere, should the Contractor propose to utilize differing technology.

b) Cable loops may also use to transmit ATP/ATO data in crossover areas due to the inability to adopt both rails for train detection purposes. A loop feed unit shall be used to provide the ability to transmit the ATP/ATO data. The Contractor shall propose the type of technology to be used for transmission of ATP/ATO data at crossing areas.

9.9 Power Supply

a) The power supply for the signaling should be derived from a highly reliable source. For this purpose, a main supply for signaling of three-phase 480 VAC, 60 Hz shall be made

Page 75: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-35 December 2015

available at all stations. The Contractor shall supply all required transformers and auxiliary equipment, which are to be contained in a cabinet, to provide the correct power supplies for Signaling equipment at Emerald and Masinag stations. The Contractor shall additionally provide an Uninterruptible Power Supply (UPS) at Masinag station and Emerald to complement the main power source.

b) The Contractor shall upgrade, if required, the power supply system including the UPS at Santolan station to complement the additional load from wayside equipment within its vicinity.

c) The UPS shall be suitably rated to ensure the signaling system’s continuous operation for a period of not less than four (4) hours in the event of failure of the main supply.

d) The UPS shall be installed in the SER for main signaling power supply.

e) The input of the UPS shall be protected from over-voltages and surges of current.

f) Additionally, it shall be protected from the effects of lightning. The UPS shall also

function as a filter in order to remove transients and other noise, which may affect the operation of electronic equipment.

g) A static bypass switch shall be provided to circumvent the UPS unit should a malfunction occur. Also a manual bypass switch shall be supplied to enable maintenance to be undertaken to the UPS.

h) The UPS output power for use by all signaling facilities; shall be stable and reliable.

i) The batteries shall be installed in a dedicated room. Cabling between the batteries and UPS shall be sufficient to carry the full load.

j) The design and performance of the UPS shall be in accordance with the latest edition of

IEC 62040 or an acceptable equivalent standard and with the following criterion:

• Main Supply Voltage three phase 480 VAC ±10%; and Frequency 60 Hz ±3%.

• Output The voltage output is dependent upon Contractor’s equipment requirements; Voltage variation ±2%; Frequency 60 Hz ±3% (dependent on equipment requirement); Harmonic distortion ±3%; and Ambient temperature 15– 40℃.

k) The UPS shall be equipped with fans and filters for air-cooling. The noise produced by

the UPS and any cooling fans shall be limited to 50 dB for frequencies 500 Hz, 1000 Hz and 2000 Hz. Noise produced by internal transformers shall be limited to 40 dB for frequencies 60 Hz, 100 Hz and 300 Hz.

Page 76: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-36 December 2015

l) The UPS shall be provided with output current limiters, which afford short–circuit protection. The overload capacity of the inverter shall be 150% for one (1) minute and 125% for the next ten (10) minutes.

m) The Contractor shall submit test reports proving that these test criteria and the overload capacity test are within limit as provided in a well-known Standards.

n) In addition to the above, the UPS shall be capable of monitoring and detecting potential malfunctions; these include:

• Overload; • Over voltage and current; • Under voltage; and • Temperature.

o) Should the battery temperature exceed the specified maximum during charging, the

inverter shall terminate the charging to prevent thermal runaway of the batteries. An alarm shall be generated for each of the above-mentioned features should they occur.

p) The operational status of the UPS shall be capable of being exhibited using a LCD or similar device. The differing features of the UPS shall be selectable using a keypad; these would include but not be limited to the following:

• Input voltage; • Input current; • Power factor; • Frequency; • Battery voltage; • Battery and rectifier current; • Output voltage and current; • Inverter kW; and • Temperature.

q) The UPS shall be capable of providing information to the remote control SCADA system.

The points to be monitored shall be consistent with the existing system as a minimum requirement. An alarm shall be generated for failure or malfunction of these items.

r) The UPS mechanical construction shall allow for maintenance from the front.

s) The UPS proposed by the Contractor shall be subject to approval by the Engineer.

t) The output from the UPS shall be fed into a distribution cabinet where power will be disseminated accordingly to supply equipment with power. The distribution cabinet shall be supplied with circuit breakers, which shall be suitably rated for the equipment they supply and will be in accordance with the Philippine Electrical Code. The Contractor shall supply all equipment and accessories in accordance with equipment requirements.

Page 77: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-37 December 2015

u) The UPS and other power supply equipment shall be designed with a spare capacity of 25% of the nominal load.

v) Transformers used within the power supply system shall be suitably rated and shall be of

the low loss type.

w) The Signaling power supply/UPS system shall interface with the Electrical System for the provision of equipment grounding, lightning protection and bonding arrangement (refer to the PPSP for Power Supply and Electrical Works).

x) All signaling power supplies, which are not connected to an established earth, shall be equipped with earth fault detection capability. Indications of the earth status shall be sent to the OCC and LCW as an equipment alarm.

y) All power supply transformers shall have sufficient tappings available to enable power supply voltage adjustments to be made in accordance with load requirements.

z) All equipment and cables shall be capable of withstanding over voltages and other power

supply surges, which may be caused by lightning, switching effects, etc. The Contractor shall submit for approval the design of the lightning protection scheme proposed.

aa) Front panels of power supply cubicles shall include as a minimum, indications and instruments to display the status of the power system.

bb) The Contractor shall provide a safety analysis, which demonstrates that the proposed power supply design and any equipment fault cannot result in a safety critical condition arising.

cc) The Contractor’s scope of work for the power supply shall also include, but not be limited

to the following: • Cabling from Electric Power distribution bay to SER; • All cabling from the SER to the Power Cubicle; • All grounding connections related with signaling facilities; • All lightning protection related with signaling facilities such as SPD, Isolation

Transformer etc; and • Grounding shall be separated and independent from other facilities (e.g.

Telecommunication system).

dd) The Contractor shall design a suitable power supply system which shall protect the signaling equipment from lightning, noise and etc. and shall ensure power stabilization.

9.10 Grounding 9.10.1 Grounding points shall be provided for all indoor and outdoor Signaling and Train Control

System installations to achieve the following objectives:

Page 78: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-38 December 2015

a) To provide the safety to the operating and maintenance personnel against possible electric shock in the event of any potential (voltage) appearing on exposed parts with respect to earth or due to electromagnetic or to electrostatic induction.

b) To ensure safe and reliable operation of the equipment by limiting or eliminating any possible induced voltages and transients in the Signaling and Train Control equipment.

c) To protect the equipment against buildup of unduly high voltages as this may cause dielectric (Insulation) breakdown, or damage to equipment, or their components.

d) Provision of a comprehensive grounding methodology for all equipment enclosures, cabinets, drawers, assemblies and sub-assemblies.

e) Provision of a clean zero-volt reference point where required.

f) The grounding system shall be so designed by the Contractor so as to give earth resistance within the stipulated limits at all locations and under all climatic conditions.

g) Any electrical joints in the grounding system shall be protected from moisture ingress by using proper sealing as approved by the Engineer.

h) Reduction in potential to traction return and fault currents; and

i) Reduction or elimination of the effects of electrostatic interference and electromagnetic interference arising from within the auxiliary electrical systems and other extraneous sources in the vicinity of Signaling and Train Control installations.

• Main Earth

Apart from the separate clean grounding points, an additional earth point shall also be provided from the “Main-Earth” bus in each of the Signaling and Train Control equipment room, Station Control Room (SCR) and UPS/Battery room at stations. This shall be used as the chassis earth. The value of this earth should not be more than 10.0 Ohm (or in accordance with the PEC, whichever is the lowest) at any location and under any climatic condition.

• The Civil/E&M Contractor shall provide the grounding pits for clean earths and main earth and shall connect them up to the grounding terminals inside the rooms as above.

• The Signaling and Train Control Contractor shall set up a grounding ring bus inside the operational rooms.

• Contractors shall together set up an appropriate mechanism in order to achieve the desired earth resistance values.

• Out Door Installations: The following outdoor installations are required to be earthed:

Metallic sheath and armoring of all main cables at regular intervals; Equipment enclosures;

Page 79: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-39 December 2015

Signal posts; Train Detection equipment; and Any other installation as may be necessary to cover the complete scope of works

under the Signaling and Train Control Contract.

9.10.2 The Grounding and other protective measures in preceding paragraphs are given only as indicative guidelines. The Signaling and Train Control Contractor shall design, manufacture, install and be responsible for safe and correct working of all equipment/subsystems under the scope of their contract. To achieve this objective, the Signaling and Train Control Contractor shall submit their proposals requiring any changes or modifications. The Signaling and Train Control Contractor shall also submit their proposal for protection devices at power lines, data communication lines and equipment parts and elsewhere for review.

9.11 Transient and Lightning Protection 9.11.1 Despite the provision of grounding as specified above, failures of Solid State Electronic

equipment do occasionally occur on account of finite earth resistance, particularly high voltage transients and also due to lightning. Typically, transient and lightning are usually short in duration with surge voltages of limited energy. Electronic equipment with high input impedance is inherently more susceptible to transients.

9.11.2 Requirements for effective transient and surge protection:

a) Physical distance from the transient source does not necessarily guarantee immunity from transients. An effective protection system must protect the Signaling and Train Control equipment from transients of the following specifications as follows:

• Peak transients of up to 700 Volts on the DC Power Supply line for several

microseconds.

• Average transient duration of 2 microseconds with a repetition frequency of 15 kHz to 100 kHz.

• For short duration transients (< 5ms) the variation approaches a sine wave.

• For longer duration transients (> 5ms) the variation approaches rectangular pulses with an initial rate of rise up to 5 x 104 Volts per second.

9.11.3 Suitable electronic devices such as silicon avalanche suppressor devices having high surge

handling capability, fast response time, low clamping voltage, etc., shall be incorporated in the Signaling and Train Control equipment and sub-systems offered. This is to ensure that the latter withstands the conditions mentioned above without any damage or permanent degradation in performance throughout the system lifetime. The selection criteria for such devices shall include, but not be limited to, the following:

a) Reverse Standoff Voltage: At least twice the maximum operating voltage and allowing

operation over the temperature range –65oC to +175oC

Page 80: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-40 December 2015

b) Pulse Power Rating: This shall have a value to handle the peak pulse power of the transients and to ensure their decay in less than 10% of the rise time for the worst pulse likely to be encountered from all possible sources. Including lightning and transients from traction power system.

c) Device Lifetime: This shall not be less than that of the system for which it affords protection.

9.11.4 Lightning Protection While the viaduct and civil works shall be provided with lightning protection arrangements by

the Contractor, the protection against lightning surges travelling through conductors into the equipment shall be done by the Signaling and Train Control Contractor using appropriate devices in accordance with the Contract documents and prevailing international practices.

10.0 Interfaces Between Other Systems

a) The Contractor shall design and coordinate in detail with all disciplines where defined

interfaces are required. The Contractor in their Project Management Plan, and Interface Management Plan, shall identify and produce a matrix of all interfaces.

b) The purpose of the Interface Matrix is to provide all Project Contractors involved in the interface with a clear overview of the purpose and functionality of each interface. It provides a framework such that Project Contractors can work in a co-operative way to produce the interfacing standard.

c) Interfaces required between the individual sub-systems of Signaling and Train Control system shall be coordinated by the various Contractors so as to fulfill the functional requirements of the Signaling and Train Control Systems.

d) Where necessary, the Contractor shall coordinate with the Employer ensuring that daily operations are maintained and the safety and integrity of the system is not compromised. This will be especially pertinent for the works concerned with Santolan and the OCC.

10.1 Interface Management Plan (IMP)

a) The Contractor shall interface and liaise with other designated Contractors in accordance with the requirements given in this PPSP and relevant clauses of the GS.

b) The Contractor shall develop and submit to the Engineer an IMP, within the time scales as defined in the contract, which is mutually acceptable to both the Contractor and the other designated Contractors.

c) Other requirements of the Interface management plan shall be indicated in the GS.

d) The Signaling and Train Control system shall also interface with other major elements of

the overall system; these may include but are not limited to the following:

Page 81: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-41 December 2015

• The Interface Matrix shall describe the interface requirements between the Signaling and Train Control system, E&M and Civil Construction Contractors for the civil design and construction of the viaducts and stations.

• The Interface Matrix shall also describe the interface requirements between the Signaling and Train Control system and the Track Works.

• The Interface Matrix shall also describe the interface requirements between the

Signaling and Train Control system and the Power Distribution and OCS works.

• The Interface Matrix shall also describe the interface requirements between the Signaling and Train Control system and the Telecommunication works.

e) The Contractor shall detail how they intend to integrate with the existing signaling equipment, which is currently operating, namely:

• The Interlocking at Santolan; • ATS system (OCC and LCW at Santolan); and • Wayside equipment at Santolan including turn-outs, signals, train detection

equipment, and Balises/Cable loops.

f) The Contractor shall provide detailed descriptions on how the equipment shall interface with the existing LRT Line 2. These descriptions shall be submitted to the Engineer for evaluation.

10.2 Point Machine area Lighting

In the vicinity of the Point Machines at Masinag, a source of power supply (230VAC, 60Hz, 250VA) - independent of the Point Machine power supply – shall be provided to enable illumination of the area for maintenance and calibration purposes. The failure of the lighting power supply shall not effect in any way the operation of the Point Machine. The Contractor shall submit their proposal for the inclusion of this function to the Engineer for evaluation.

11.0 Installation Requirements

a) As part of the Construction plan, the Contractor shall submit their detailed approach and

methodology on how they shall install equipment and cabling. These method statements of work shall include the intended practice to ensure safe operation of the existing system.

b) Details of how it is proposed to integrate the extended signaling system with the existing signaling network, while operating the existing system during the testing/commissioning period should also be incorporated into the methodology inclusive of any temporary works requirements.

c) For the LRT Line 2 East Extension Project equipment rooms with a suitable raised floor

shall be made available at the two additional stations. These rooms shall house all signaling equipment except those required to be mounted at the wayside. All cabinets inclusive of Microprocessor-based interlocking, power supply and UPS shall be

Page 82: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-42 December 2015

appropriately mounted and connected to a clean earth. All installations shall be subject to suitability of purpose as stipulated in the GS.

d) All cables both main and local shall terminate upon designated termination racks located within the equipment room. Local cables shall be installed from the termination rack to their respective wayside termination boxes. No wayside junction or termination boxes for the use of through cables or associated with any local cabling shall be allowed. All cable reticulation or network plans shall be submitted by the Contractor to the Engineer for approval prior to any ordering of cables.

e) All signaling cable and wire shall be fastened for the avoidance of serious damage. Moreover, the contractor shall consider any wayside special conditions and shall design the cable reticulation in an efficient and cost-effective manner. Therefore connecting cables and wires shall not adopt cable joints without prior consent of the Engineer.

f) All signaling equipment and cables shall be installed by suitably trained and competent staff, supplied with the necessary plant, equipment and tools. The installation of cables shall be in an orderly and neat formation free from unnecessary bends, entanglement and kinks. The cables shall be laid in a manner, which allows ease of removal without undue disturbance to adjacent cables. Precautions shall be taken to ensure that cables are not unduly damaged or insulation chafed during installation, which may be detrimental to performance and potential premature replacement of the cable before its intended life-cycle.

g) Penetrations through walls, ceilings and floors required for the entrance of cables shall be sealed after installation with an approved fire resilient material.

h) Cables shall be installed in the main cable duct which shall be free from debris and other

materials. If ducts are left open during the installation of cables, the ducts shall be cleared of debris and other materials prior to ducts being closed. Where groups of cables are required to cross the track, cable ducts/troughs shall be provided. The tail connecting cable of track equipment that crosses or which are laid along the track shall be protected with approved-type conduits. The Contractor shall submit the methodology and plans in the positioning of conduits prior to installation subject to Engineer’s approval.

i) The cable route shall be diverse to complement the redundant configuration of the signaling and telecommunications transmission systems.

j) The Contractor shall evaluate the armoring and shielding of cables with respect to isolation from high voltage, EMI and lightning. The Contractor shall submit such an evaluation for approval.

k) The Fiber Optical Cable (FOC) installation along the cable ducts and technical rooms shall be based on well-known standards (IEC 60793-1 or equivalent) taking into account the unnecessary cable loss through excessive loops, kinks, bends, intertwines, joints/splices etc. that may affect the operation of the FOC. All outdoor and indoor FOC shall also be appropriately labeled.

Page 83: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-43 December 2015

l) The Contractor should take into consideration the wayside installations will not be affected or damaged by the operation of the track maintenance vehicles.

m) The Contractor shall be responsible for providing temporary electricity supply, all instruments, gauges, test equipment, tools, accessories, personnel, services and any other facilities required for the execution of all tests and inspection. The Contractor shall provide sufficient sets of testing equipment, tools, etc. to expedite testing. All test equipment shall be accompanied with the appropriate calibration certificate from a testing authority where details have been submitted to the Engineer and reviewed without objection before submission to the Engineer. Tests shall not proceed until a statement of “No Objection” is received from the Engineer or his representative.

11.1 Cabling for Signaling

a) All cables, including FOC, installed on any part of the viaducts, buildings and stations shall be in accordance with the PEC. Where such codes do not comprehensively encompass all requirements, appropriate international standards shall be used. The construction of cables shall be of fire resistant materials as specified in IEC 60331 or an acceptable equivalent. Where cables are used in confined spaces the insulation and sheath shall be constructed with Low Smoke Zero Halogen (LSOH) materials. Testing for halogen free properties shall be in accordance with IEC 60754 -1 and 60754 – 2 or an acceptable equivalent.

b) All cables and their construction inclusive of any testing certification shall be subject to approval by the Engineer.

c) All outdoor cables shall be armored and should the cables require screening, the braid shall not be less than 80%.

d) All cable accessories, termination racks and other materials shall comply with the PEC

and shall be subject to approval by the Engineer. The Contractor shall supply detailed information and appropriate specifications for all cables they propose to use.

e) No manufacturer’s joints shall be permitted in cables or wires carrying safety information.

f) All cables shall be UV-protected and resistant to corrosion, vermin and insect attack. The

cables shall be suitable in all respects for continuous operation in the prevailing environmental conditions encountered in Manila. The Contractor shall adopt suitably protected cables as defined in international standards.

g) If multi-core cables are to be used they shall have a clearly identifiable system of distinguishing individual cores, which shall be indelible and impervious to chemicals and greases used by maintenance personnel. The Contractor shall make an allowance of four (4) cores, for spares purposes. The Contractor shall provide detailed information on the core identification system to be used. Multi-core cables between stations may be of the solid core type. However, cables from the station termination rack to wayside equipment shall be preferably of the stranded type.

Page 84: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-44 December 2015

h) The Fiber Optic Cable that connects to the network switch of each station shall be configured as redundant. The FAT for FOC shall be based on applicable TIA/EIA Standards which includes measurement of attenuation, insertion loss, power budget, etc.

i) Data transmission cables for connecting the signaling Microprocessor-based interlocking system to the Microprocessor-based interlocking system at Masinag station shall be fiber-optic. The signaling data transmission system shall be independent from the communications or other transmission systems.

j) An approved method of identifying manufacture and cable type shall be provided throughout the length of all cables and wires. The signaling FOC shall be easily distinguishable from other data transmission cables laid on the wayside.

k) All cables entering termination boxes or equipment rooms shall be suitably clamped using appropriate cable glands and the entrances sealed against vermin and the environment.

l) All cables shall be terminated in the order of their core numbers on combined terminal links equipped with screw terminals. The cable cores shall be terminated consecutively with no gaps between terminations. The cable termination links shall be easily accessible for testing purposes using standard equipment. Each link or terminal shall be consecutively numbered.

m) Wayside terminations boxes shall only be allowed for local connection to signaling equipment, e.g. signals, etc. No termination boxes shall be allowed for through cables or for terminating main cables. All unused cores shall be terminated unless extenuating circumstances dictate otherwise and approved by the Engineer. Wayside termination boxes shall comply with IP 65.

n) After installation, all cables shall undergo as a minimum, insulation and continuity testing. The Contractor shall undertake these tests and submit all test results for approval. The Engineer reserves the right to witness these tests. The Engineer shall require the replacement of any cable, which does not fulfill the minimum requirements at the Contractors cost.

o) All cable shall be rated such that adequate voltage, current and power is available and is compliant with stipulated national standards. Additionally, all cables shall be correctly sized and that cable sizes shall be selected to ensure that a voltage drop in excess of 10% of the applied voltage does not occur between the relevant bus bar and the final equipment terminals. Furthermore, the doubling - or other multiples - of cores to alleviate excess voltage drop shall not be allowed.

p) Data transmission and frequency systems shall employ amplifiers where necessary, to ensure that sufficient signal levels are maintained.

q) All signaling cables must be segregated from power supply cabling as far as possible. The minimum distance between these cables shall be in accordance with the PEC.

r) All cables where necessary shall include screens to protect circuitry from the potential of any induced electro-magnetic radiation. Any shielding or armoring shall be correctly

Page 85: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-45 December 2015

insulated. In areas where metallic screens may be incorporated into the cable design, adequate insulation shall be provided to ensure that the sheath cannot form a path for traction current return. The Contractor shall propose their method of connection to screens and armoring to achieve this requirement. The Contractor shall additionally provide details of the construction and effectiveness of any cable screens.

s) Where cable routes are made common for more than one system, e.g. telecommunications, the design shall include mutually satisfactory arrangements for running of cables and shall determine any possibility of interference from cables running in parallel.

t) All indoor data and power cabling shall be neatly and separately installed in either cable trays, ducting or conduits as appropriate to the layout of equipment. All materials necessary for the routing of cables and wiring, equipment rooms, apparatus boxes, fittings, brackets, clamps, etc. shall be provided under this Contract.

u) All indoor and outdoor cables shall be installed, tied and labeled appropriately in accordance with established standards, without kinks, excessive bends, unnecessary long loops and splices. The methodology of cable installation shall be submitted to the Employer for approval prior to any cable works commencing.

v) Wiring within equipment rooms shall conform to regulations and codes stipulated in the PEC. The Contractor shall supply details of the wiring schemes they propose.

w) Any concrete ducting or similar devices used for carrying cables shall not allow the accumulation of water nor shall they be surrogate drains for water.

12.0 Testing and Commissioning Requirements for the Signaling System

a) For the LRT Line 2 East Extension Project, the Contractor shall submit a commissioning plan, procedure/instruction and testing records/result. The Contractor shall prepare, develop and implement a comprehensive inspection, testing and commissioning plan, which shall ensure the capability of the signaling system to fulfill all safety, technical and operational performance requirements. In support of this specification, the Contractor shall also refer to the GS. Additionally, the Contractor shall demonstrate full integration between the signaling and other systems.

b) The Contractor’s Inspection, Test and Commissioning Plan shall include all tests to be performed during any FAT, which shall demonstrate various tests to be performed on Signaling and Train Control equipment. The FAT shall where possible, be conducted on complete systems. However, when this is not possible, simulation of the unavailable parts of the system shall be used. The Contractor shall conduct tests at a later date to prove the integration of all the parts of the system missing in this instance. The FAT shall verify, but not be limited to, the following: • Type tests; • Tests by sample and routine; • Equipment cabinets shall be tested for correctness of wiring;

Page 86: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-46 December 2015

• Tests to ensure that commands to the system are acknowledged and the correct response received;

• Tests to ensure that the Microprocessor-based interlocking system responds in accordance with signaling principles; and

• Tests to ensure system response time is within specified tolerances.

c) The results of the FAT shall be such that the equipment may be transported to site for installation. Any unresolved or outstanding items shall be written into the test report, and these shall be rectified prior to shipment. Only under special circumstances, shall equipment with unresolved or outstanding items be allowed to be transported to site, and then only with the written consent of the Engineer. Post installation testing and inspection shall validate that all signaling equipment, inclusive of hardware and software function works correctly within the site environment. The (SAT) shall verify, but not be limited to the following:

• Train detection system tests; • Interlocking system relationship between signals, points, train detection system, etc.; • Control from remote and local workstations and correct indications received; • ATP and ATO static and dynamic tests; and • Latest and correct versions of software are used.

d) The SAT shall include a comprehensive inspection to establish the correct installation of

equipment, conformance to drawings, specification, and an acceptable standard of installation. All cables shall be tested for specified insulation properties and continuity. The FOC shall be tested in accordance with industry standards. The Contractor shall stipulate the standards to be adopted.

e) The Contractor shall include in their inspection the test and commissioning plan. Their proposed approach and methodology on how all subsystems and systems shall be tested whilst ensuring that daily operations are uninterrupted, and the existing system’s safety and operational performance is not compromised during the testing period.

f) Commissioning tests shall be performed to validate that the system has been correctly installed and to demonstrate that the Signaling and Train Control system fulfills all safety, technical and operational performance requirements. All commissioning tests shall be documented and submitted to the Engineer for review. Subsequent to the completion of commissioning tests, a series of test running using operational scenarios shall commence. These tests ensure that headway and other operational requirements can be examined thoroughly. Further to the conclusion of test running, a trial running period may commence with the extended fully integrated system under centralized operational control. The correct operation and monitoring of performance of system functions shall be evaluated during this phase.

g) The Contractor shall provide all commissioning test results for power supply and UPS systems. This includes, but not limited to: FAT results, certified manufacturers test reports, site inspection upon installation and full functional tests inclusive of interfaces with other systems. The power supply specifications as stipulated in Clause 9.9 of this PPSP shall be established in the commissioning tests.

Page 87: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-47 December 2015

h) The Contractor shall conduct an Optical Time Domain Reflectometer (OTDR) test to all Signaling FOC to check the integrity of any splices, connectors and amount of fiber attenuation. The test shall demonstrate that the optical signal be received by the equipment based on their receiver sensitivity is within limit as prescribed in international or local Standards. The test results shall be submitted for Engineer’s evaluation.

i) The Contractor shall verify and confirm by an independent third party that the new

Interlocking, and any changes to the existing Interlocking will meet all applicable standards.

13.0 Environmental Conditions

a) All equipment shall be capable of efficient operation within the specified temperature and humidity ranges as stated in the GS without any accelerated deterioration. All equipment shall be tropicalized for use in the climate experienced in the Philippines, particularly in Manila.

b) Wayside signaling equipment shall be suitably sealed to prevent the ingress of water and dust and shall be in accordance with IP 65. This equipment shall be installed to withstand the effects of typhoons, which are prevalent within the Philippines and which, may generate wind gusts in excess of 250 km/h, and also the effects of solar and ultraviolet radiation. All equipment housed in apparatus rooms shall be capable of continuous operation in ambient temperatures up to 40° Celsius with a relative humidity of 95% (non-condensing). Temperatures inside equipment cabinets may reach up to 70° Celsius.

c) Equipment rooms will be provided within stations. The Signaling and Train Control Contractor shall coordinate with the relevant Civil Contractors regarding air-conditioning requirements and humidity control.

d) Upon completion of installation all cable entries will be sealed with an approved material.

Where penetrations between rooms are required for cabling or other equipment, the penetrations will be sealed with an approved fire-resilient material.

e) The Contractor shall additionally coordinate with the Contractor regarding lighting and

grounding requirements. All equipment and cabling located within equipment rooms shall be protected from the potential effects of lightning. Therefore, the Contractor shall take into consideration in their design, an appropriate protection system to alleviate this potential problem. Furthermore, the Contractor shall identify grounding requirements for their equipment, which include a clean earth for electronic equipment in addition to a safety earth. Grounding and bonding shall be in accordance with the PEC.

f) Signaling equipment connected to the wayside shall be capable of enduring vibration and

shock in accordance with the GS and IEC 60721 or an acceptable equivalent standard. The equipment shall be appropriately tested to ensure suitability to the application it is intended.

g) It is a basic requirement that trackside equipment should as far as possible be minimized. Where possible, equipment shall be housed in the signaling equipment rooms located at each station. The Engineer prior to preparation of advanced designs shall approve all

Page 88: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-48 December 2015

equipment that requires to be installed trackside. The equipment shall be mounted so that it is clear of the structure gauge with any doors, lids or other items in the open position.

h) All equipment shall be able to withstand power supply distortion, and interference caused

by transient voltages from lightning and train propulsion systems. In addition to surges which may emanate from the traction power system and switching of power supplies.

i) Equipment cabinets shall be capable of removing heat generated from modules or power supplies by either suitable convection or forced air methods. If fans are used to remove heat, filters shall be provided to prevent the ingress of dust and other material.

j) Equipment installed at the trackside shall not obstruct passengers whom in the event of an

emergency may detrain and have to walk to the nearest station.

k) The Contractor shall ensure that all materials and work practices conform to the GS and Environmental Policy Statement (EPS), which forms part of the project requirement.

14.0 Maintenance

a) The Contractor shall indicate all necessary maintenance that is necessary to be carried out

on their equipment in order to keep the system operating efficiently for the full service life of the equipment. The Contractor shall detail in their system maintenance plan the procedures including the frequency of routine maintenance, which shall also be tangibly demonstrated to the Engineer and client. The maintainability of the system shall be demonstrated in accordance with the RAMS study as indicated in IEC 62278 or equivalent standard.

b) The maintenance plan shall be developed using recognized maintenance techniques such as reliability centered maintenance methodology. The maintenance plan shall be used to determine the new maintenance policy based upon the incorporation of new equipment.

c) The Contractor shall ensure that the supplier provide a written guarantee that all spare parts will be available for a period of not less than fifteen (15) years with the exception of computers, servers, VDU’s, etc.

d) The Contractor shall stipulate minimum periods for the back-up of systems such as the ATS system where mass storage devices may be used for playback in the event of an incident occurring.

e) An on-line remote access to the ATS software shall be provided. This shall enable the

supplier to gain access to the system, retrieve information and assist in resolving problems in the event of a malfunction occurring. No changes to the software of ATS equipment shall be allowable by remote access. Additionally, it shall not use such mediums as the internet and shall use safety mediums such as VPN.

Page 89: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-49 December 2015

14.1 Maintenance during Defect Notification Period (DNP) 14.1.2 Competency of Personnel

a) During the DNP the Contractor shall support the Employer with sufficiently trained and

competent personnel. Such persons shall have their generic competence established and must demonstrate their specific competence and knowledge in the particular systems, environment and procedures.

b) The Contractor shall provide evidence of specific competence and knowledge, which shall include but not limited to:

• Assessment and certified training in particular software applications and operations; • Recording of competence and work in the license holders logbook; and • Receiving or in receipt of sufficient and current exposure to the area of work that the

holder is licensed for.

c) Routine spot checks on licensing may be carried out from time to time by the Engineer, or his representatives on the proficiency of the Contractor Staff.

14.2 Wrong Side Failure

a) In the event of a Wrong Side Failure, the Contractor shall undertake the management and investigation necessary to identify and rectify the cause.

b) Should the Employer, during the DNP require further investigations at other sites throughout the railway, the Employer will formally request the Contractor to undertake such investigations, and the Contractor shall undertake the same.

14.3 Defects Notification Management Plan

a) As part of the Defects Notification Management Plan, the Contractor shall detail the management and organization to be provided during the DNP.

b) Testing and Re-commissioning of Signaling and Train Control Equipment. In the event of a failure requiring modifications to the System. The Contractor shall undertake any testing and re-commissioning required. Any such modification shall be submitted for review by the Engineer.

14.4 Temporary Alterations to Restore Service

The Contractor shall undertake any temporary modifications necessary to maintain service. Any such modification shall be submitted for review by the Engineer.

14.5 Discrepancies between Installation and Design Records

Should the Contractor discover inconsistencies between the maintenance drawings and documentation and the installed equipment, the Contractor shall correct all such errors within two (2) weeks.

Page 90: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-50 December 2015

14.6 Storage of Equipment and Materials during the Maintenance Period

a) The Contractor shall ensure that no equipment is to be stored along the trackside.

b) The employer will provide defined storage locations for the support of First, Second and Third Line Maintenance (dependent upon their maintenance strategy).

c) The Contractor shall satisfy itself and the Engineer that the storage locations for

equipment and materials will meet the performance requirements of this Specification. 14.7 Failure Investigations

a) Failure investigations shall be conducted by the Contractor. The Employer will determine

priorities in the event of a conflict between the Contractor and other Project Contractors during failure investigation.

b) Disputes between the Contractor and other Project contractors will be resolved in accordance with the Conditions of Contract. The Contractor shall make available to the employer all test and failure data as required.

14.8 Software Support 14.8.1 General

a) The Contractor shall submit to the Engineer for review, the software support plan at least ninety (90) days before commencement of software installation.

b) All changes, bug fixes, updates, modifications, amendments, new versions shall not result in any non-conformance with the Specification.

c) The Contractors shall submit all new versions to the Employer’s Engineer for review at least two (2) weeks prior to their installation. Any new versions of software shall not degrade the operation of the System.

14.9 Security Obligations

a) Within fourteen (14) days of the installation of any software into the Permanent Works by the Contractor, the Contractor shall submit to the Engineer for retention by the Employer two backup copies of the software, which shall include, without limitation:

• All design documentation relating to the software; and • Any specified development tools required for maintenance of the software, including,

but not limited to, editors, compilers and linkers.

b) Any software item delivered by the Contractor to the Engineer shall not be translated or modified by the Employer without the prior consent of the Contractor unless:

• The owner of the software becomes insolvent or has a receiving order made against it

or makes an arrangement or assignment or composition with or in favor on its

Page 91: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-51 December 2015

creditors (including the appointment of a committee of inspection) or goes into liquidation or commences to be wound up or has a receiver, liquidator, trustee or similar officer appointed over all or any part of its undertaking or assets or if distress, execution or attachment is levied on, or if another agency takes possession of, any of its assets or any proceeding or step is taken which has an effect comparable to the foregoing in any relevant jurisdiction; or

• The owner of the software ceases to trade; or

• The owner of the software assigns copyright in the software and the Contractor fails within sixty (60) days of such assignment to procure in favor of the Employer, license from the new owner in the terms as that required by the Contract; or

• The contractor is in breach of any of his obligations under the Contract.

14.10 Error Correction

The Contractor shall inform the Engineer immediately when a fault is discovered within the delivered software or documentation. On receipt of a request from the Engineer for identification or further diagnosis of a failure or fault, the Contractor shall provide appropriate resources. The contractor shall provide written details as to the nature of the proposed correction to the Engineer and undertake the correction. After the correction of the detected errors, the software shall be validated and tested.

14.11 Fixes or Patches

The Contractor shall notify the Engineer promptly of any fixes or patches that are available to correct or patch faults. The Contractor shall detail any effect such fixes or patches are expected to have, upon the Signaling and Train Control System.

14.12 New Versions

a) The Contractor shall ensure that all new versions are fully tested and validated on the simulation and development system prior to installation. The Contractor shall ensure that all new versions are fully tested and commissioned once installed on the Site. The Contractor shall deliver to the Engineer any new versions, together with the updated Operation and Maintenance Manuals.

b) The Engineer shall not be obliged to use any new version and that shall not relieve the Contractor of any of its obligations.

c) Any effect on the performance or operation of the Signaling and Train Control System that may be caused by a new version shall be brought to the Engineer`s attention.

14.13 Debugging and Trace Software

The Contractor shall provide debugging or trace logging software along with a Laptop for Trackside or wayside ATP/ATO equipment, On board ATP/ATO equipment, CBI, AFTC equipment etc.

Page 92: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-52 December 2015

The Contractor shall not install debugging or trace logging software that affects the performance or functionality of the Signaling and Train Control System.

14.14 Corrective Maintenance Procedures

a) Routine and corrective maintenance procedures shall be supplied for all equipment. The format shall be as follows:

• Uniform format and layout irrespective of equipment supplier; • Color coding for each activity (if applicable); • Cross referenced to the Operation and Maintenance Manuals; and • Document control information.

b) The procedures shall be submitted for review by the Engineer. The following shall be

included as a minimum:

• Frequency of maintenance; • Type of maintenance; • The equipment identification; • Safety precautions to be observed; • Step by step guide to the maintenance required; and • Explanatory diagrams.

c) The Contractor shall supply the Configuration and Customization data, Parameters and

Settings in both Hard copy and electronic format.

14.15 Defect Notification Period

a) The Contractor shall supply technical-orientated staff, spare parts, and test facilities to enable them to repair all systems equipment, cables and wiring for a period of not less than 24 calendar months commencing from the issuance of the handover certificate of the system for revenue service. In some instances where equipment may have been handed over earlier and was in use by the Employer, that equipment’s DNP shall commence from the date of official handover of the particular equipment.

b) The Contractor shall provide a detailed analysis of all faults, defective parts and the remedial actions taken to rectify these malfunctions. Additionally, the Contractor shall supply sufficient technical staff, spare parts and test equipment to enable them to modify any part of the system, or complete subsystems, or any equipment, which in the opinion of the Engineer requires modification to comply with the requirements of this specification.

c) The meaning of systems or subsystems in the previous paragraphs shall be construed to include both hardware and software.

d) The Contractor shall be obliged to replace any spare parts used during the DNP free of charge to the Employer.

Page 93: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-53 December 2015

15.0 Maintenance Tools, Special Tools and Test Equipment

a) The Contractor shall supply an inventory of special tools, maintenance tools, test or measuring equipment and other materials necessary to ensure efficient operation and maintenance of the equipment they propose.

b) The Contractor shall state the type and quantity of special tools and special equipment to ensure proficient operation of the system. The Contractor shall supply all special tools, maintenance tools and test equipment upon endorsement of the proposed list by the Engineer. Where equipment is considered not economically viable to maintain by the Employer, e.g. computer processors, the Contractor shall specify maintenance facilities available for such equipment. Should no facilities be available, the Contractor shall propose how this equipment shall be maintained. Special consideration shall be given to the provision of portable test and diagnostic equipment.

c) This equipment shall be capable of being used whilst equipment is in service without

producing any detrimental effect to the operation of the apparatus under measurement or test. This is especially pertinent for equipment, which is inherently fail-safe.

d) The Contractor shall provide for each special tool and test equipment, training and comprehensive documentation in the form of manuals, which shall contain all technical data, drawings, calibration requirements, etc.

e) The Contractor in addition to providing quantities of special tools and test equipment shall include the cost of supplementary equipment, which may be purchased by the Employer at a later date. The required tools/equipment for the maintenance and calibration of the Point Machines to be installed shall also be provided. This includes, but not limited to, test gauge for track blade operating force, various mounting tools/gauges/jigs, torque wrench, etc. to ensure its safe operation.

16.0 Manuals

a) The Contractor shall submit for approval by the Engineer all Training, Operation and

Maintenance manuals for equipment supplied under this Contract in order that the signaling system can be efficiently operated and maintained. The manuals shall contain as a minimum block diagrams, illustrations, three dimensional exploded views, and schematic drawings etc, to enable detailed explanation of assemblies, components and their interrelationship with the system and subsystems. All manuals shall be written in the English language. Manuals shall follow the format as prescribed by the Engineer and shall be thorough, and written in clear unambiguous terms using syntax that is easily understandable.

b) Prior to commencement of the Tests on Completion, the Contractor shall supply to the Engineer provisional Operation and Maintenance manuals in sufficient detail for the Employer to operate, maintain, dismantle, reassemble, adjust and repair the equipment.

c) The works shall not be considered to be completed for the purpose of taking until the Engineer has received final operation and maintenance manuals in such detail, and any other manuals specified for these purposes.

Page 94: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-54 December 2015

d) The Contractor shall indicate the reason for any changes or revisions to the manuals. Manuals to be submitted shall include, but not be limited to the following:

• System Manuals - Containing comprehensive description of system principles.

• Operations Manuals, which as a minimum shall contain the following:

Descriptions, specifications and operational philosophy; Comprehensive operating information; Operator adjustment instructions; Operator test procedures; Operational safety functions; Malfunction detection indications; Operational limits and restrictions; Functional association with other equipment; Illustrations and drawings depicting pertinent features, which will enhance the

description of operational procedures; and Any other information deemed necessary for correct and efficient operation of the

system.

• Software Manuals - Containing all equipment, which consists of programming devices. These manuals shall contain software principles, source listings inclusive of comments, flow charts, communication protocols and operating instructions. Source codes and their development tools shall also be provided in electronic format.

• Maintenance Manuals – Shall convey sufficient information with respect to equipment diagnostics and maintenance practices to enable efficient maintenance of the system. This manual shall comprise of components such as:

Preventative and routine maintenance; Fault and diagnostics; and Overhaul and repair.

• Drawings Manuals – Including all as-built information in both reproducible and

electronic format. The number of copies and electronic format requirements shall be in accordance with the conditions of Contract.

17.0 Spare Parts

General Requirements for spare parts are described in the GS. This chapter defines particular requirements for Signaling System. Spare parts are divided into three parts. The first is Contractor spare parts, the second is DNP parts, and the third is commissioning spare parts. The Contractor shall submit these parts lists required in this section respectively.

17.1 Contractor Spare Parts

a) The Contractor shall provide spares in sufficient quantity to ensure a replacement item is available when required for use based on predicted MTBF. The Contractor shall submit a

Page 95: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-55 December 2015

detailed list with supporting calculations including the source of MTBF data for the Engineer’s review not later than twelve (12) months after award of the Contract.

b) The Contractor shall undertake the obligation to continue the supply of spare parts or acceptable replacements for a period of not less than fifteen (15) years with the exception of computers, servers, VDU’s, etc.

c) The list of spare parts shall be divided into groups, namely Capital Spares, Replacement (Unit Exchange) Spares and Consumables.

d) The Contractor where necessary, shall provide at least two sources for spare parts or components. The Contractor shall be obliged to replace any spare parts used within the DNP or any other guaranty period, whichever is later.

e) The Contractor shall submit a list of recommended spare parts for operation during the DNP within six (6) months after the Commencement Date of the works and shall supply these spare parts upon endorsement and approval of the list by the Engineer.

f) The spare parts list shall contain sufficient information to enable location of all components within the system. This list shall provide adequate information to facilitate the Employer to purchase replacement parts from the original manufacturer. The payment for the same shall be made from the provisional sum item provided for the same.

g) The Contractor shall format the spare parts lists for ATS, ATO/ATP equipment,

Microprocessor-based interlocking, TD, Point Machine, Power Supply and UPS including batteries in an organized and structured manner, fully comprehensible.

17.2 Defect Notification Parts

a) The Contractor shall provide his own spares during installation and commissioning period as well as for support during the DNP.

b) The Contractor shall submit the list of DNP spares, with the types and quantities of spares the contractor intends to hold, at least three (3) months before the commencement of the DNP to the Engineer for review.

c) The Contractor shall include details of the stock of the Contractor’s own spares in the Monthly progress Report. The status of the spares, either in store or under workshop repair, shall also be included.

d) The Contractor shall be responsible for defects caused due to the absence of coordination with relevant contractors.

Page 96: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-56 December 2015

Table 17.2-1 Parts List to be prepared during Defect Notification Period

Item No. Item Qty. Comment

1 OCC Devices ---- ----------------------------------------- 2 Monitor 1 For train operation 3 Server 1 For train operation 4 Key board/mouse 1 For train operation 5 Hub (if needed) 1 For train operation 6 Signaling Room ---- ----------------------------------------- 7 CTC control board 1 1 For CTC control type one 8 CTC control board 2 1 For CTC control type two 9 CTC control board 3 1 For CTC control type three

10 CTC control board 4 1 For CTC control type four 11 CTC control board others 1 For CTC control others respectively 12 ATO/ATP control board 3 One set per each station 13 Desktop computer 1 For diagnose computer 14 Workstation for Local control 1 For Set 15 Track Relays 4 Including solid state type 16 INTERLOCKING system processing unit 4 Including for existing modifying

17 INTERLOCKING system I/O processing unit 4 Including for existing modifying

18 Relays 10 Mechanical/ electronics type 19 Server / board 2 For sake of signaling purpose 20 Battery 4 Including backup purpose 21 UPS 1 22 Fuse/arrester 20 For each system protection use 23 Electrical wire 100m Various type 24 Wayside ---- ----------------------------------------- 25 Balise 2 Transponders/ loop coils included 26 Point machine 1 Electrical point machine 27 Wayside signal(if needed) 1 28 Transmitter 4 For track circuits 29 Impedance bond 1 For return current 30 Cable 300m For outside various type 31 Test Equipment ---- ----------------------------------------- 32 ATO/ATP board tester 1 Depending Manufacture 33 INTERLOCKING system board tester 1 Depending Manufacture 34 ATO/ATP on-board tester 1 Depending Manufacture 35 Tester 1 36 Synchronized scope 1 Depending Manufacture

17.3 Commissioning Spare Parts

The Contractor shall submit the list of Commissioning Spares, with the types and quantities of spares the Contractor intends to hold, at least three (3) months before the commencement of the installation activity to the Engineer for review.

Page 97: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project _________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page – SIG-57 December 2015

The Contractor shall provide his own spares during installation and commissioning period as well as for support during the DNP.

18.0 Training

a) The Contractor shall provide a comprehensive training program for the Employer’s

training and supervisory staff as indicated in the GS. The training program using the “Train the Trainer” concept shall be of sufficient detail to enable the Employer’s staff to gain full knowledge of the system and equipment operating principles, and the associated maintenance of the system.

b) The Contractor shall employ state-of-the-art techniques such as computer-aided teaching methods to deliver subject matter. The tools used for the course shall become the property of the Employer upon completion of the training in order that further training may be given to other employees. The curriculum shall be subject to approval by the Engineer prior to any commencement of training.

c) The Contractor shall continuously monitor the progress of the training and trainees by verification through proficiency tests, results of which shall be submitted to the Engineer for evaluation as embodied in the GS. The Contractor in developing the objective of the training courses shall assist the trained trainer when required. It is the full responsibility of the Contractor to transfer the technology imposed on this project to the Employer. The duration of the courses and the final number of personnel to attend such courses shall be agreed between the Contractor and Employer. The Contractor shall provide on-site management and co-ordination of the training program to ensure continuity and timely distribution of training materials.

d) The Contractor shall also interface with the Employer’s training department and staff. The

Contractor shall identify any exclusive training needs such as the secondment of staff to the Contractor’s premises for specialized instruction. All of which will be at the Contractors expense. All training courses and manuals to be provided by the Contractor shall be in the English language.

Page 98: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

TECHNICAL SPECIFICATIONS

TELECOMMUNICATIONS SYSTEM LRT Line 2 Extension Project

Page 99: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Telecommunications System

Table of Contents Page Abbreviations 1 1.0 Introduction 4 2.0 Scope of Specification for the Telecommunications System 4 3.0 System Overview 5 3.1 Existing Systems And Equipment 5 4.0 General Technical Requirements 5 5.0 Master Clock System 7 5.1 Existing Master Clock System 7 5.2 Scope of Work 8 5.3 System Requirements 9 5.4 Installation Requirements 9 5.5 Technical Requirements 9 5.6 Display Clocks 10 6.0 Audio Paging System (APS) 10 6.1 Overview of Existing APS 10 6.2 Scope of Works 11 6.3 System Requirements 11 6.4 APS Operational Requirements 12 6.5 Design and Submittals 14 6.6 APS Performance Specification Requirements 14 6.7 Power Amplifier Specifications 15 6.8 Loudspeakers 15 6.9 Installation Requirements 16 6.10 Software 17 7.0 Closed Circuit Television (CCTV) 17 7.1 Overview of Existing CCTV System 17 7.2 General 17 7.3 System Requirements 18 7.4 Camera Specifications 20 7.5 System Design 21 7.6 Submission Requirements 21 7.7 Scope of Work and Installation Requirements 21 7.8 Technical Specifications/Standards 23 7.9 Station’s Network Video Server Specification 24 7.10 Software/ GUI 25 7.11 Network Video Management Software 26 7.12 Testing and Commissioning 26 8.0 Supervisory, Control And Data Acquisition (SCADA) 26 8.1 Introduction 26 8.2 Scope of Work 27 8.3 Specification Requirements for SCADA RTUs 28 8.4 Interface with Equipment Provided by Other Sections 29 8.5 RTU at the New Stations 30 8.6 Environmental Specifications/ and Standards 30

Page 100: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

8.7 SCADA I/O Points 30 9.0 MSTP/ Fiber Optic Transmission System 38 9.1 Overview 38 9.2 Scope of Work/Responsibilities 39 9.3 System Requirements 40 9.4 Fiber Optic Cable Specification 42 9.5 Installation Requirements 43 9.6 Pre - Delivery Requirements 46 9.7 MSTP Equipment Integration 46 10.0 Automated Fare Collection (AFC) – Local Area Network (LAN) 46 10.1 Existing System Description 46 10.2 AFC LAN Requirements for LRT Line 2 East Extension 47 10.3 AFC LAN Equipment Installation and Interface Requirements 47 11.0 Telephone System 48 11.1 Overview of the Existing System 48 11.2 Scope of Works 48 11.3 Submittals 50 11.4 Telephone Equipment Specifications 50 11.5 Overview of Telephone Sets per Stations 51 12.0 Radio System 52 12.1 Current UHF Trunked Radio Network 52 12.2 Scope of Work 52 12.3 Base Station 53 12.4 Base Radio 55 12.5 Alarm Module 55 12.6 Base Station Reliability 56 12.7 Independent Site Trunking 56 12.8 Wide Area Restoration 56 12.9 Power Supply 56 12.10 Spares Radio Units 56 12.11 NTC Requirements 57 13.0 Uninterruptible Power Supply (UPS) 57 13.1 UPS in Every Station 57 13.2 Scope of Works 57 13.3 UPS Performance Specifications 57 13.5 UPS Installation Environment 60 13.6 Standards 60 14.0 Passenger Information System (PIS) 60 14.1 Overview 60 14.2 System Requirements 61 14.3 Technical Requirements 62 14.4 Scope of Work 62 15.0 Special Tools and Test Equipment 63 16.0 Spare Parts 64 16.1 General 64 16.2 Operational Spares Required After the Defects Notification Period 64 17.0 Defects Liability/ Warranty 65 17.1 General 65 17.2 Guarantee Period 66

Page 101: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

17.3 Technical Support 66 18.0 Operating and Maintenance Manuals 66 18.1 Maintenance Manuals 67 18.2 Operating Manuals 67 19.0 Training Requirements 67 19.1 General 67 19.3 Proficiency Verification 68

Page 102: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-1 December 2015

Abbreviations AC Alternating Current AFC Automated Fare Collection ANSI American National Standards Institute APS Audio Paging System ASTM American Society for Testing and Materials BMC Building Management System °C Degree Centigrade CAAB Controlled Atmosphere Aluminum Bracing CB Circuit Breaker CCTV Closed Circuit Tele Vision CD Compact Disc CENELEC Committee European de Normalization Electrotecnique CIF Common Intermediate Format dB Decibel dBA Decibel A-Weighted DC Direct Current DHCP Dynamic Host Control Protocol DNP Defect Notification Period DOTC Department of Transportation and Communications DVAS Digital Voice Announcement System DVD Digital Video Disc DVR Digital Video Recorder E1 European Standard @ 2.048 MBPS EIA Electronic Industry Alliance EMI Electro Magnetic Interference EMS Electro Mechanical System EVACS Emergency Voice Alarm Communication Systems FAT Factory Acceptance Test FOC Fiber Optic Cable FOTS Fiber Optic Transmission System FPP Fiber Patch Panel GB Gigabit GPS Global Positioning System GUI Graphical User Interface HVAC Heating Ventilation Air Conditioning Hz Hertz IEC International Electro technical Commission IEEE Institute of Electrical and Electronic Engineers I/O Input/Output IP Ingress Protection IP Internet Protocol ISO International Standards Organization ITU-T International Telecommunication Union – Telecommunication KHz Kilohertz Km Kilometer KVA Kilo Volt Amphere LAN Local Area Network

Page 103: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-2 December 2015

LED Light Emitting Diode LRTA Light Rail Transit Authority LRV Light Rail Vehicle m Meters MAC Media Access Control MC Master Clock mm millimeters MPEG Motion Picture Experts Group MLS Multiprotocol Label Switching MSTP Multi Service Transport Platform MTBF Mean Time Between Failures NEMA National Electrical Manufacturer Association NFPA National Fire Protection Association NTC National Telecommunication Commission NTP Network Time Protocol NVR Network Video Recorder O&M Operations and Maintenance OCC Operation Control Center OFTSP Optical Fiber System Test Procedure OSC Overhead Catenary System OTDR Optical Time Domain Reflectometer PAO Passenger Assistance Office PEC Philippine Electrical Code PDH Plesiochronous Digital Hierarchy PIS Passenger Information System PLC Programmable Logic Control PMD Polarization Mode Dispersion PMIS Project Management Information System PNFC Philippine National Fire Codes PoE Power Over Ethernet PPE Personal Protective Equipment PPSP Performance Specifications and Particulars PTZ Pan-Tilt-Zoom QAP Quality Assurance Plan RAID Redundant Array Independent Disk RASTI Rapid Speech Transmission Index RF Radio Frequency RFID Radio frequency identification ROHS Restriction of Hazardous Substances RSS Rectifier Sub Station RT Reverberation Time RTU Remote Terminal Unit SAT Site Acceptance Test SCADA Supervisory Control & Data Acquisition System SDH Synchronous Digital Hierarchy SER Signaling Equipment Room SIP Session Initiation Protocol SPL Sound Pressure Level STP Shielded Twisted Pair

Page 104: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-3 December 2015

SWC Surge Withstand Capability TB Terabyte TCP/IP Transmission Control Protocol/Internet Protocol TER Telecommunication Equipment Room THD Total Harmonic Distortion TIA Telecommunication Industries Association TPS Traction Power Supply UL Underwriters Laboratory UPS Uninterruptible Power Supply UTP Unshielded Twisted Pair V Volt VU Volume Unit SMOF Single Mode Optical Fiber SPS Station Processor System

Page 105: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-4 December 2015

1.0 Introduction

This Particular Performance, Specifications and Parameters (PPSP) defines the Employer’s Requirements for the Telecommunication Systems for the LRT Line 2 East Extension Project, and shall be read in conjunction with other bidding documents. All works under this section of Employer’s Requirements shall be carried out in accordance with the governing codes and regulations which are made part of these specifications.

2.0 Scope of Specification for the Telecommunications System

This PPSP covers the principles and fundamental requirements for the design, manufacture, supply, Factory Acceptance Testing (FAT), shipment, delivery to site, installation, Site Acceptance Testing (SAT), commissioning and defects liability for the maintenance period of the Telecommunication Systems, which collectively will fully conform to the existing Telecommunication Systems and those systems recently upgraded under The Stimulus Fund Project. All new equipment to be provided for the LRT Line 2 East Extension Project and for the improvement works to the existing Telecommunication System shall be provided with all necessary communication channels to ensure efficient exchange of voice, data and video information among the personnel, departments and offices pertaining to LRT Line 2 operations and activities. This Specification covers the provision of the following communications sub-systems and works for the LRT Line 2 East Extension but not limited to: • Master Clock; • Supervisory Control & Data Acquisition System (SCADA); • Closed Circuit Television (CCTV); • Audio Paging (AP) System; • Multiprotocol Label Switching (MSTP)/Fiber Optic Transmission System (FOTS); • Telephone System; • Digital Radio Repeater (DRR) System; • Operation Control Centre (OCC) Centralized Equipment; • Uninterruptible Power Supply (UPS); • Interface with Other Systems; • Installation Requirements; • Factory Acceptance Testing (FAT); • Site Acceptance Testing (SAT); • Tools and Test Equipment; • Spare Parts; • Defects Liability; and • Training.

The Contractor shall provide all new telecommunication systems and associated equipment described within this specification.

Page 106: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-5 December 2015

The integration and interfacing of new telecommunication equipment shall take into consideration certain existing equipment which shall be retained. The Contractor shall ensure that adequate safety arrangements are implemented to works performed during installation, test and commissioning, in the fact that these works do not compromise the safety and operational integrity of the present functioning systems. Provisions shall be made in the designs and installations of equipment to minimize any alterations necessary for the introduction of further Line 2 extensions. However, no specific equipment shall be provided for further Line 2 extensions under this Contract. The Manufacturers of the equipment/systems through the Contractor shall offer technical support to either the dealer/installer or the end user with a web site or toll-free number at no extra charge. The Contractor shall ensure that all equipment and materials used shall be able to meet the specified availability throughout its service life as required to minimize disruption to the railway operation and to minimize maintenance costs.

3.0 System Overview 3.1 Existing Systems and Equipment

The existing telecommunications facilities of the existing Line 2 and those being upgraded under the recent Stimulus Fund Project are as follows; • Master Clock (MC); • Closed Circuit Television (CCTV); • Audio Paging (AP) System; • Telephone System; • OCC Centralized Equipment; • Uninterruptible Power Supply (UPS); • Lightning Protection System; • MSTP/Synchronous Digital Hierarchy (SDH) Fiber Optics Transmission System; • Tetra Digital Radio System; and • Supervisory Control and Data Acquisition (SCADA).

4.0 General Technical Requirements

No information in this Specification shall be construed in any manner as a full technical specifications of any system or part thereof. a) All equipment, materials, engineering drawings and proposals to be supplied for various

telecommunication systems shall be designed and installed in accordance with the latest National and International Standards and Codes of Practice, whichever is more stringent and applicable. The Contractor shall indicate all relevant Standard and Specification for all equipment that is to be supplied for the project. Equipment in this particular context shall be construed to include both hardware and software.

Page 107: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-6 December 2015

b) All equipment or system shall preferably have been previously employed on similar Railway Administrations and is proven for its intended application. Proof of new technology applied to modern systems shall be actually demonstrated if required by the Engineer.

c) The Contractor shall comply with all relevant National and International Standards, Codes of Practice and the Philippine Electrical Code (PEC) for the design and installation of electrical equipment with respect to earthing and bonding.

d) The Contractor shall take into consideration, corrosion control associated with stray

currents derived from the traction power system in conjunction with the respective National and International Standards, Codes of Practice currently in effect.

e) The Contractor shall present a consistent policy for the complete Line 2 East Extension system by providing a functional compatibility analysis for each proposed system interface taking into consideration the subsystems to be retained, upgraded and replaced. Information on the in-service LRTA equipment and systems shall be available to the Contractor, for reference, at the premises of LRTA. The Contractor shall provide an assurance or statement that the functionality and performance of the new sub-system for the LRT Line 2 East Extension Project, does not differ from the function and performance of the sub-system for the existing LRT Line 2.

f) The Contractor shall provide a detailed description of their proposed system, which shall

clearly identify all equipment to ensure that controls and associated functions are readily discernable. The proposed system shall be subject to acceptance by the Engineer.

g) All design drawings, documentation, schedules, plans or alike shall be prepared in a format agreed with the Engineer. All symbols, nomenclature and abbreviations shall be fully consistent with the existing relevant standards and shall be clearly described on the drawings.

h) All design drawings, documentation, schedules, plans or alike shall be corroborated by appropriate description of the operation of the proposed systems.

i) All materials and equipment shall comply with Philippine National Fire Codes (PNFC), PEC, National Telecommunication Commission (NTC) Regulations and where applicable, National Fire Protection Association (NFPA).

j) The Contractor shall provide adequate protection for all installed telecommunication equipment in stations and wayside telephones against lightning and power supply surges.

k) All designs, materials and equipment shall continue to operate safely and correctly in the presence of the existing Traction Power Supply (TPS) system.

l) All equipment shall continue to operate safely and correctly and be resistant to Electromagnetic Interference (EMI) in the presence of electromagnetic fields generated by other railway related equipment or by the environment in which the equipment is

Page 108: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-7 December 2015

operating. The Contractor shall identify sources of potential EMI and provide adequate mitigation measures to counteract its possible effect on equipment.

m) All systems designs, materials and equipment shall be fully proven with substantiated historical evidence of operation in similar conditions. Prototypes shall not be allowed.

n) All systems designs, materials, equipment, fixtures, fittings and other accessories to be supplied under the Contract shall require acceptance from the Engineer before installation take place.

o) Drawings showing the Works as-built, shall be prepared by the Contractor and submitted for approval. The Contractor shall issue to the Employer six (6) prints of each drawing and a copy of the electronic files. The electronic format shall be as approved by the Employer, but must allow the Employer to clearly document future changes.

The Contractor shall prepare, and keep up-to-date, a complete set of “as-built” records of the execution of the Works, showing the exact as-built locations, sizes and details of the work as executed. These records shall be kept on the Site and shall be used exclusively for the purposes of this Sub-Clause. Two copies shall be supplied to the Engineer prior to the commencement of the Tests on Completion.

p) The Contractor shall supply to the Engineer all as-built records for review within the time frames as specified in the Contract documents. The Contractor shall supply all As-built details clearly visible and understanding to any operation and maintenance personnel. The Contractor shall obtain the agreement of the Engineer as to drawing sizes, i.e. size A0, A1, A3, A4 etc.

q) Prior to the issue of any Taking-Over Certificates, the Contractor shall supply to the Engineer the specified numbers and types of copies of the relevant as-built documents and drawings, as approved and specified within the time frames in the Contract Documents. The Works shall be considered not completed for the purposes of taking-over until the Engineer has received all as-built documents.

5.0 Master Clock System 5.1 Existing Master Clock System

The Master Clock System implemented in Line 2 provides accurate time to passengers and synchronizes all Telecommunication and IT Equipment installed in the stations that require synchronization to ensure their accurate performance. The standard time and frequencies are derived from GPS satellites via a combination of GPS receiving system and Stratum 1 server installed at the OCC. The GPS synchronized Master Clock is installed in the TER of the Depot, and sub-master clocks are installed in all train stations and depot where all digital clocks in the Depot are connected. These sub-master clocks then synchronize slave (platform) clocks and other IT systems in their environment, in the OCC and stations, whereas the main Master Clock is connected to all sub-master clocks by means of the MSTP and NTP.

Page 109: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-8 December 2015

5.2 Scope of Work

a) The proposed GPS derived reference time under the LRT Line 2 Extension shall be designed, supplied, delivered, installed, tested and commissioned, by the Contractor. Its primary purpose is to provide precision timing to the new display clocks and to synchronize all telecommunication devices and other electronic systems in the new stations, requiring an accurate time reference source. These devices and systems shall include the following but not limited to: • SCADA; • MSTP/Fiber Optic Transmission System (FOTS); • PABX; • CCTV; • LAN station equipment (such as routers, network switches etc.); • Tetra Trunked Radio; • Audio Paging System; • Passenger Information System; • IT Equipment; and • Signaling Equipment.

b) The Contractor shall provide the required hardware and software to interconnect the new

station’s NTP server to the existing Master Clock at the OCC via the station’s MSTP Transmission equipment.

c) The Contractor shall supply all cabling, accessories, fittings and fixtures for the installation of the new display clocks.

d) All Equipment to be supplied and installed for the new stations shall be fully compatible,

and interoperable with the existing Line 2 Master Clock System.

e) Display Clocks shall be installed on platforms, concourses, ticket booths and in other locations as required for the operation of the system.

f) The Contractor shall submit all clock face profiles for approval by the Engineer.

g) The Contractor shall submit the system design to the Engineer for approval prior to the

commencement of purchase.

h) All interfaces to electronic equipment, transmission equipment and the cable distribution system shall be provided by the contractor and incorporated into the design of the existing Master Clock System.

i) The Contractor shall make provisions for the integration of the new Master Clock

equipment with the signaling system in the new stations.

Page 110: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-9 December 2015

5.3 System Requirements

a) An NTP server or sub master clock in the new station shall receive the time information from the Master Clock at the OCC through the MSTP and shall convert it into synchronization pulses for the station slave clocks and Telecommunication equipment requiring synchronization.

b) Time synchronization for equipment requiring this functionality shall be performed using appropriate protocols such as Network Time Protocol (NTP).

c) The system shall support connectivity of Ethernet 10/100/1000T ports for the TCP/IP network.

d) Network time synchronization over the data network shall have an accuracy of ± 80 milliseconds per 24 hours to the reference clock,

e) In the absence of master clock signals, the clock system in the new stations shall have a minimum accuracy of 1 second a day.

5.4 Installation Requirements

a) The Contractor shall supply and install all cables, conduits, cable trays, and supply all accessories, fittings, and fixtures required for the implementation of new equipment for the time servers in the new stations.

b) There shall be one clock per platform. It shall be double face and shall be installed half way of each platform. Display clocks shall also be provided in the Concourse area and offices within the stations as maybe required.

c) The Contractor shall submit all proposed locations of clocks to the Engineer for approval.

d) The Network Switch for Master Clock distribution shall be designed to be housed within

a 72” high cabinet inside the TER using standard 19” (wide) racks. The equipment shall be modular and made up of interconnecting modules that are easily configured and replaceable during malfunction.

e) The Switch / Server shall have 24 ports and DHCP features or manual configuration. It

shall have sufficient PoE capable ports and redundant power supply module for powering the clocks in the station.

f) High-grade Category 6 UTP cables shall be used between the Station Time server and all

display clocks in the station.

5.5 Technical Requirements

a) The display clocks and telecommunications equipment in the new stations shall derive its timing signals and synchronization from the existing Master Clock System at the OCC

Page 111: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-10 December 2015

through the new network switches and MSTP equipment installed in the new TERs of the new stations.

b) Suitable AC powering from the UPS shall be implemented to assure continuous operation of network devices and clocks.

c) All electronic equipment to be supplied for the Master Clock System shall be capable of

co-existing within the electromagnetic environment within the new stations and are not influenced by each other or external systems.

d) Where applicable, the Contractor shall provide adequate shielding for both equipment and

cabling to ensure that no interference or unwanted signals can be produced. Equipment designs shall ensure that unwanted frequencies are eliminated or as a minimum are reduced below the level of susceptibility of other equipment.

e) All equipment shall be grounded in accordance with ANSI TIA/EIA 607.

5.6 Display Clocks

a) The clocks shall have a digital display and PoE capabilities. The size of the display for

platform clocks shall be such that it can be read and highly visible from a distance of 50 meters under any lighting condition.

b) Once connected to the Network, the digital clock’s DHCP features shall automatically synchronize with the NTP Network Switch over the Ethernet Network.

c) Clocks shall have multiple time and date formats.

d) The clocks shall be weatherproofed and comply with relevant Ingress Protection

standards.

e) The clocks shall provide their own light source for illumination during evening or low ambient light and shall be energy efficient and dependable. Brightness shall be adjustable.

f) All clocks and equipment requiring time synchronization shall contain their own

precision oscillators or similar devices in order that they may continue to operate accurately in the event of a loss of GPS signal.

g) Upon recovery of the GPS signals, display clocks shall immediately synchronize with the Master Clock timing signals.

h) Clocks shall maintain their configuration in memory even if supply of power is removed.

6.0 Audio Paging System (APS) 6.1 Overview of Existing APS

a) The APS installed in the existing eleven (11) Line 2 stations enables the OCC perform

public announcement of live, prerecorded, and emergency messages for passengers,

Page 112: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-11 December 2015

employees, and emergency response personnel. In the stations, only live announcement is possible. The system employs analog technology comprising of amplifiers in conjunction with audio recorders and associated equipment.

b) The control of the APS in the station is done locally at each station Passenger Assistance Office and remotely from the OCC via RS485. At the OCC, the APS is able to broadcast through a designated EPABX phone.

6.2 Scope of Works

a) The Contractor shall design, supply, install, test, commission, and support in the maintenance of a new set of APS equipment up to the end of DNP with IP-based technology to facilitate the transmission of public address announcements to the new stations of the LRT Line 2 East Extension.

b) All interfaces required for the new system shall be provided by the Contractor in conjunction with the termination works involving the audio cables and the fiber cores used for the new APS in the stations via the MSTP Transmission system.

c) The Contractor shall interconnect all the APS elements to be installed in the new stations

to the MSTP Transmission System for centralized control of the APS from the OCC.

d) All equipment, installation materials and related works required to fulfill the above, shall be furnished by the Contractor whether or not specifically detailed herein or in the drawings.

e) The Contractor shall supply new software versions or upgrades for programming and

configuration of the supplied equipment.

f) The Contractor shall be responsible for powering the APS Equipment from the UPS to the ticket booth.

g) The Contractor shall coordinate with the Civil and Architectural group with respect to the locations of Telecommunication Equipment Rooms (TER) and ticket booth and for the routing of required conduits for cabling and interfacing.

h) The Contractor shall be responsible for all works and materials for the integration of the

new APS for the LRT Line 2 East Extension to the existing APS system of Line 2. 6.3 System Requirements

a) Equipment to be supplied shall be IP based and of the latest version or model, proven

design, tested and successfully employed in Railways.

b) The APS equipment for the new stations shall be fully compatible and interoperable with the new APS hardware equipment and software to be installed at the OCC.

c) The system shall be digital and of modular design to facilitate both expansion and service.

Page 113: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-12 December 2015

d) The APS equipment shall include phone input processing circuits, power amplifiers, mixers, speakers, local paging, ambient noise sensing microphones, cabling, conduit, and all other station oriented equipment defined in this Section and as shown on the Contract Drawings.

e) The APS at the OCC shall have facilities for Background Music.

f) The APS at the station shall satisfy the Sound System for Emergency Purposes

specification IEC60849 and any applicable local standards.

g) The APS in the new stations shall be configurable locally or remotely using the configuration software supplied.

h) All Network equipment shall have individual IP addresses which are automatically

checked by a network management.

i) The system shall have a DVAS for pre-recorded announcements.

j) The DVAS shall have sufficient storage capacity for at least 90 minutes of accumulated messages.

k) The new APS system and equipment in the new stations shall be synchronized from the

existing Master Clock at the OCC through the new Gigabit Network switch in the new station.

l) The contractor shall provide at least 25% spare capacity after commissioning and system

acceptance to allow for future APS expansion. 6.4 APS Operational Requirements

a) The new APS of the new stations shall allow the OCC Dispatcher to make public address announcements using either a system of pre-recorded announcements or real time announcements from a microphone incorporated within the remote control workstation facilities. The platform supervisor shall make public address real time announcements on the station only.

b) Area-selection of Audio Paging zones in the new stations and Depot shall be available from these remote control units.

c) The new Centralized APS equipment at the OCC shall be able to link and broadcast to all

existing eleven (11) stations and the 2 new stations.

d) The OCC operator shall have complete control over the APS of the new stations being able to select one station, a group of stations or all stations.

e) The audio from the APS shall cover the platform areas, gates, concourses, offices and

stairways of the stations.

Page 114: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-13 December 2015

f) The system shall provide an automatic announcement facility for making routine, situational and emergency announcements.

g) The new APS in the new stations shall function independently in the event that the APS

network via the MSTP fails.

h) The system shall provide adequate dynamic gain at an acoustic distortion level sufficiently low to ensure minimum listening fatigue to intended listeners.

i) No positive feedback or audio feedback from microphone to loudspeaker system shall be

experienced by the users of the system. j) The APS shall be capable of providing sufficient Sound Pressure Level at any location

within the targeted area at an acoustic distortion level of less than 5%.

k) The reverberations during the playback of messages and real time announcements shall be within 15%, which is the acceptable level or industry standards.

l) The intelligibility of all Audio Paging announcements shall achieve a minimum Rapid

Speech Transmission Index (RASTI) of 0.45 for 95% of areas. The remaining 5% of areas with RASTI below 0.45 shall only be scattered uniformly among the station areas and shall not form clusters of appreciable size.

m) The Frequency response shall not vary more than ±3 dB at any location within the

platform.

n) The Sound Pressure Level (SPL) of audio announcements shall be maintained between 10 and 15 dB. Above total ambient noise level and or train noise in the station referenced from 5 feet (1.5m) above floor level.

o) Automatic ambient-noise-dependent volume adjustment shall be implemented for the two

(2) stations to maintain SPL level and compensate for varying acoustic conditions especially when trains are in the stations.

p) The APS in the new stations shall allow the OCC operator using the Telecommunication

workstation to access the station’s amplifier for remote volume control adjustments.

q) The APS components should be protected from unauthorized use, vandalism, or other damage.

r) Emergency announcements over the APS in the new stations shall be able to be made by

the OCC operator or station platform supervisor during times of crisis or emergency.

s) These announcements shall override all other announcements as required.

t) The APS announcement shall be heard by passengers within the LRV once it has stopped at the platform and the LRV doors have opened.

Page 115: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-14 December 2015

6.5 Design and Submittals

a) An audio test measurement or acoustical modeling shall be performed by the contractor on the station to verify conformance of the Audio Paging system design as indicated in ANSI S3.2 for intelligibility of speech and voice announcement requirements for a minimum Articulation Index of 0.80.

b) The modeling shall include recommended locations and number of additional speakers necessary for the Audio Paging system to achieve an average of 80 dBA ± 3 dB at 5 feet above the floor levels in accordance with ANSI S1.8 and S1.13. The background ambient noise level of 60 dBA shall be used to calculate the nominal sound pressure level in accordance with ANSI.

c) The Contractor shall submit their design, which must contain full circuit description and

block diagram and schematics to the Engineer for approval. This shall include conduiting and cabling works within the station.

d) The block diagram must include the method of integration with the Network Switch or

multiplexing equipment and transmission system details with the public address system equipment.

e) The design is intended to permit half the loudspeakers on the platform to still function

should a fault develop within the wiring of other circuit by isolating or removing the defective circuit.

f) The design of the loudspeaker enclosures for the concourse area, stairways and over

bridge areas where provided shall be sealed against dust and moisture ingress. 6.6 APS Performance Specification Requirements

The APS equipment to be supplied shall have EN 54 certification which is a European standard for alarm products and shall comply with EN50121-4 standards. The Audio Paging amplifiers shall be designed in accordance with EIA SE-104, engineering specifications for amplifiers for sound equipment and the following requirements: a) Frequency Response: ± 3 dB over the frequency range of 30 Hz to 20 kHz, and plus or

minus 1 dB or better over the frequency range of 250 Hz to 5000 Hz as measured from any installed speaker within the station.

b) Total Harmonic Distortion (THD): less than 1% over the frequency range of 30 Hz to 20

kHz measured at the output of any speaker. c) Operating Temperature: -Ambient temperature between 0°C and 60°C, and relative

humidity from 5% to 95%. d) Headroom: + 15 dB above nominal SPL without increase in hum, noise, total harmonic

distortion, or frequency response.

Page 116: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-15 December 2015

e) Hum and Noise: 0 dB below Nominal SPL. f) Reserve Audio Power Capacity: 50% greater than required power output for the station at

nominal SPL.

g) Power for the APS shall be derived from a UPS as detailed in the UPS specification.

h) It shall permit up to four (4) hours operation on loss of power. 6.7 Power Amplifier Specifications

a) The amplifier shall be designed for digital audio public address system. The equipment

shall be provided with digital audio processing facilities for all audio inputs and outputs.

b) The audio output voltage can be selected between 100V and 70V by moving jumpers.

c) There shall be at least four (4) audio channels for the stations; 2 active and 2 as spare.

d) The power amplifier shall have at least two (2) auxiliary audio inputs with microphone/line level selection. The audio input of the power amplifier can be selected as automatic volume control input.

e) The amplifier shall have sufficient number of freely programmable control inputs for

functionalities to be initiated in the system and can be assigned with priorities.

f) There shall be at least four (4) control outputs freely programmable for diagnostics and fault monitoring.

g) The frontal display shall show the Volume Unit (VU) meter reading when the audio

monitoring mode is selected. The audio output can be monitored by connecting a headphone to the headphone socket.

h) Any change in status of the unit shall be monitored continuously and reported to the

network controller for fault/status reporting.

i) The amplifier monitoring and changeover facility shall be incorporated in the power amplifier. The changeover relays shall be included in the unit. The changeover shall be automatically activated to transfer all loads of a defective amplifier to the spare amplifier.

6.8 Loudspeakers

Loudspeakers shall conform to EIA SE-103, EIA-299, and EIA-426 standards, and shall meet the following requirements: a) Power is minimum of 10 watts continuous. b) Weatherproof, corrosion and fire resistant. c) Loudspeakers in offices shall be provided with volume control.

Page 117: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-16 December 2015

d) Frequency response shall be plus or minus 3 dB at the following frequencies:

• Loudspeakers for rooms and concourses: 50 Hz to 19 kHz. • Loudspeakers for platforms: 300 Hz to 12 kHz.

6.9 Installation Requirements

The Contractor shall take such precautions as are necessary to guard against electromagnetic and electrostatic hum, to supply adequate ventilation, and to install the equipment so as to provide maximum safety to the person who operates it.

a) Conduits running the whole length of the platform shall be provided and shall support the

suspended loudspeaker mounting bracket.

b) The loudspeaker system shall be on each platform, on stairways, on over-bridge areas and concourse areas (both paid and unpaid areas) equipment rooms such as TER, SER and lifts.

c) The Audio Paging equipment shall be mounted on 482.6mm (19-inch) racks located

inside the Telecommunication Equipment Room of the new stations in accordance with EIA-310-D.

d) Ventilated rear panels, solid side panels, and solid top panels shall be provided.

Equipment racks shall be provided with accessible lockable front and back panels that limit access to equipment. The lockable front shall not cover items that require O&M personnel access.

e) Rack cooling shall be through perforations or louvers in front panels to ensure adequate

ventilation of equipment and top rack mounted fans. The racks and panels shall be factory finished with a uniform baked enamel over rust inhibiting primer.

f) All equipment shall be modular for easy insertion and removal into the rack for

equipment servicing.

g) All audio equipment shall be held firmly in place. This shall include loudspeakers, amplifiers, racks, cables, conduits, etc.

h) Fastening and support shall be adequate to support their loads with a safety factor of at least three (3).

i) All switches, connectors, outlets, etc. shall be clearly, logically and permanently marked

during installation.

j) Grounding and shielding of rack-mounted equipment shall be implemented in accordance with the local PEC and international codes.

Page 118: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-17 December 2015

6.10 Software

a) Six (6) sets of error free CD/DVD software complete with covering documentation shall be supplied to the Employer.

b) The software shall be displayed with a version number and the date of issue. c) Updates to the software must be available to the Employer either through a website or via

issue on CD/DVD. d) The Contractor must advise the Employer promptly by email or letter of their availability. e) Windows based software is preferred. f) All software licenses shall be paid for by the Contractor up to the expiration of the

warranty period.

7.0 Closed Circuit Television (CCTV) 7.1 Overview of Existing CCTV System

All eleven (11) stations along LRT Line 2 are currently provided with CCTV systems to monitor passenger movements and safety in the stations. The CCTV system can be operated independently from the station’s ticket booth CCTV monitoring facilities and can be controlled simultaneously from Workstations in the OCC via the existing Fiber Optic backbone. Recording from all the cameras in the passenger stations and Substations is accomplished at the OCC using VHS Recorders. Security cameras are also installed in selected buildings, stabling areas and locations such as the OCC within the Santolan Depot.

7.2 General

The specification of the CCTV system covers technical specification and requirement of an IP based CCTV system for Line 2 East Extension and the 3 existing stations and OCC consisting of the following but not limited to: • Indoor & outdoor fixed type IP cameras; • Fixed dome type IP cameras; • Indoor P/T/Z IP dome cameras; • Outdoor P/T/Z cameras in the reversing tracks; • Video encoders for existing analog cameras (at OCC); • Video management hardware & software; • NVR/RAID recording servers; • Ethernet Gigabit switches; and • Workstations at OCC and Ticket booths at the new stations.

Page 119: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-18 December 2015

7.3 System Requirements

a) The CCTV system for the LRT Line 2 East Extension shall be designed, supplied, installed, tested and commissioned by the Contractor. The system shall be color, digital IP based and employ state-of-the-art equipment.

b) The video surveillance system shall be end to end IP base with IP cameras installed in stations as per site requirements. This shall include the Gigabit switches, CCTV workstations for the stations and OCC, redundant servers and digital video recorders comprising an IP based Video Management System at the OCC.

c) The CCTV system shall enable the ticket booth staff of the new stations and OCC

operational staff viewing of high quality CCTV images which are very vital in providing train and passenger control, safety, security surveillance and controlled evacuation of the new railway stations.

d) Fixed box type IP color cameras with varifocal lens shall be provided in platforms, gates,

entrance/exit points, or any other locations as required by the Employer.

e) Fixed dome type IP color cameras shall be installed in indoor locations such as concourses, ticket counters, ticket booths, offices, train controller’s booth or any other locations as required by the Employer.

f) High speed PTZ IP dome cameras shall cover circulating areas, concourses, Rectifier

Substations, foot bridges, station walkways, interconnecting walkways to other locations and for general area surveillance. Strategically installed overhead PTZ cameras inside the RSS shall be able to cover the RSS.

g) Security provisions are required at each part of the passenger’s movement through the

station. As such, CCTV cameras with adequate resolution to permit the use of facial recognition technology shall be provided.

h) The Contractor shall install two optical fiber cables running on separate tracks, thus

providing cable path diversity.

i) The CCTV system shall permit the OCC and Station Ticket Booth to view the same scene simultaneously should it be so required.

j) Industrial IP Gigabit switches over dedicated fiber optic rings shall be the medium of

transporting CCTV images from the station’s camera outputs to the OCC.

k) IP based Centralized Monitoring system and video recording system at the OCC will replace the existing analog CCTV centralized equipment at the OCC.

l) The Station’s Digital Video Codec (compressor/decompressor) and Ethernet Switch shall

be IP based Video Management system converting the analogue camera signal into a compressed digital format (e.g. H.264 or MPEG4 -10) thus allowing the recovery of full-motion NTSC TV signals.

Page 120: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-19 December 2015

m) The CCTV monitor shall be installed in the new station’s Ticket Booth/s and shall have the ability to switch to any view of the station areas and all areas covered by the cameras. Display shall be via a 40 inch high-resolution LED monitors giving single or up to 16 multi split views of all cameras installed in the stations.

n) Camera Sequencing or scanning shall be possible and can be varied depending on

operator’s preference.

o) The OCC operator shall have the ability to view and record any camera output from the new stations and existing 11 stations on the new Network Video recorder at the OCC.

p) A video wall at the OCC shall be provided to project selected video information, from

Signaling, SCADA & CCTV systems

q) Compression systems shall be configured to allow H.264 video compression algorithms to be used with minimum latency between reference frames such that an acceptable playback system resolution of 4CIF is achieved when viewing a recorded image of a resolution test target of 30 frames per second.

r) The Contractor shall employ low latency design to prevent pixelization during playback

of images on the workstation monitors. Packet loss shall also be avoided to prevent image impairment.

s) No distortion shall occur to the video images in any CCTV monitor, in either quad or full

frame display format, immediately after video switching or any other circumstances due to the signal traveling time differences among video signals and power phase differences of video cameras within the station(s).

t) The digital video storage array shall be fully compatible with the proposed IP CCTV

Video Management System.

u) The recording capacity of the Rapid Array Independent Disk (RAID) shall be sufficient for thirty one (31) days motion detected mode recording/archiving from all cameras of existing and new stations of Line 2. Computation for the Terabytes storage capacity based on the above conditions and H.264 compression shall be submitted for approval by the Engineer.

v) To save on Network Video Recorder (NVR) storage capacity at the OCC, the stations

shall be equipped with an IP digital storage medium for temporary storage of recorded images before final recording and storage at the NVR storage disks at the OCC.

w) The NVR while providing for recording, local and remote surveillance shall be equipped

with intelligent video analytics and enhanced file security by digital watermark as may be required.

x) The CCTV systems for the new stations must include the capability to associate text

information, such as time, date, and camera identification, with the images recorded by the system as well as any digital signature used for security. The time displayed on the system shall be derived from the Master Clock System.

Page 121: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-20 December 2015

y) The system shall provide diagnostics facility for serial, video & network interfaces. System logging shall be possible either to a remote IP address or console port or on the system.

For the new stations of Line 2, as much as possible, IP Camera and Software (Video Management, Video Recording and Video analytic software) shall be from the same manufacturer. The System shall provide secured recording for evidence purposes and user authentication to protect data integrity.

7.4 Camera Specifications

a) The cameras shall be a high-resolution day and night network camera integrated into an all-weather NEMA 4/IP66 rated enclosure designed for both indoor and outdoor applications.

b) The cameras shall be an industrial grade, color, and full-featured for day/night operation

with at least 2 megapixel resolution to capture HD images at 30 frames per seconds. c) The cameras shall be powered via the Ethernet (Power-Over-Ethernet) using an IEEE

802.3af power source to save on electrical wiring and conduits. d) The product shall be designed to meet industrial and surveillance applications requiring a

low power, rugged video camera with IP network capability. e) Auto dome cameras shall have 1080 and 720 P video resolution. f) The operating temperature range shall be 0 to 60°C. Relative humidity up to 95%.

g) Each camera shall have a video at various Common Intermediate Format (CIF) and a dual

stream capability such that the viewing and recording are achieved at different resolutions.

h) Digital image authentication shall be optionally available and licensed to verify that

images have not been altered, manipulated, or tampered with, in anyway. i) The camera shall provide on-screen time/date and text displays. The text display can

be programmed to dynamically change when motion alarms are detected. j) The camera shall provide built-in motion detection allowing up to multiple separate,

rectangular motion windows (zones) to be independently configured to have pixels included in the motion calculations.

k) The camera shall support 10/100BASE-TX communications and incorporate a built-in

web server, built-in FTP server, and a built-in FTP client.

Page 122: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-21 December 2015

7.5 System Design

a) Prior to system design, a thorough survey of the station facility in which the system will be installed must be carried out and analyzed as an integral part of the existing total system-design process and risk assessment.

b) A layout plan documenting the location and field-of-view of each camera in the system

should be included as a part of this survey. c) The control of the new CCTV and APS system in the stations shall be integrated into a

single workstation.

d) These systems will act as “stand alone” systems initially, i.e. as two (2) independent “stand alone” CCTV systems. At a later stage these stations shall be linked back to the OCC.

e) This is contingent upon completion of the OCC upgrade, MSTP expansion and

installation of a new fiber optic backbone. f) The Contractor shall propose a seamless integration of the new CCTV equipment for the

LRT Line 2 East Extension to the existing CCTV system of Line 2.

7.6 Submission Requirements

a) The Contractor shall submit with his tender, block diagrams of proposed CCTV system at each station and process of integration with the existing CCTV network. This shall include cameras, network switches, workstations, servers, RAID storage device and monitors, video wall at OCC drawings of each platform or area being viewed by the CCTV system, indicating the choice of lens, the angle of view and the rationale for positioning the camera at the locations indicated in the drawings.

b) The drawing shall indicate the position of the camera in plan view and the angle of

intended view at each platform, concourse, stairway, elevator and escalator areas and other areas as required.

7.7 Scope of Work and Installation Requirements

a) The scope of work includes but not limited to installing field CCTV assemblies consisting of camera, zoom lens, pan/tilt drive, power supply and standard or dome enclosure. Work scope also includes furnishing and installation of associated CCTV workstation equipment, GB Ethernet Switches, Fiber Optic/UTP cabling and network electronics.

b) At the OCC, a complete Video Management System with centralized monitoring and recording facilities shall be installed:

c) The work also includes installation of communication interfaces for fiber optic and data

cable.

Page 123: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-22 December 2015

d) The Contractor shall take such precautions that are necessary to guard against electromagnetic interference, to supply adequate ventilation, and to install the equipment so as to provide maximum safety to the person who operates it.

e) The contractor shall provide all the necessary hardware and software, interfaces and

accessories for the CCTV cameras to be installed in the new stations and RSS.

f) The equipment for the CCTV shall be mounted within the TER of the new station.

g) The Contractor shall be responsible for powering the CCTV Equipment from the UPS at the TER to the Ticket booth, RSS and designated locations.

h) The platform cameras shall be strategically located in order to have a clear and

unobstructed view of all train doors to be displayed on split view workstation screen.

i) To protect against damage or theft, cameras must be mounted in such a position to be out of reach of members of the public or vandals. Where this is not possible, the camera shall be installed such as to make it very difficult for the member of the public or vandals to remove or damage such items easily.

j) All switches, connectors, outlets, conduits and cables shall be clearly, logically and

permanently marked during installation.

k) The camera/lens assembly shall be setup at the factory and installed in an outdoor environmental housing.

l) Cabling shall be based on ANSI/TIA/EIA sets of standards for CCTV cabling installation.

m) CCTV cameras requiring Power over Ethernet (PoE) shall utilize Cat 6 cable. The Gigabit

Ethernet Switches shall incorporate sufficient PoE capable Ethernet ports with redundant power supplies.

n) The external power injectors shall be used only for locations where the Ethernet switches

are existing and do not incorporate PoE capable ports functionality.

o) The contractor shall provide and install high grade UTP Category 6, 4-pair cable with RJ45 connectors between the Gigabit Switch and the camera location.

p) For cabling distances exceeding 300 ft., the contractor shall provide, install and terminate

a 4-strand single-mode fiber cable. Such installation shall be accompanied by the corresponding installation and termination of the 220VAC UPS-backed power wiring and shall be routed in separate raceways from the TER.

q) The corresponding standard Media Converter with IEEE802.3af standard for PoE supply

shall be implemented on the receiving end as per project design.

r) The video monitors at the ticket booth when wall mounted shall use standard steel brackets and the included base.

Page 124: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-23 December 2015

s) The equipment for the CCTV such as Video Encoders, decoders and Gigabit Switches shall be mounted within the TER at each station.

t) The workstation PC in the station and OCC shall have a digital keyboard for P/T/Z

functionality. 7.8 Technical Specifications/Standards

a) All equipment shall conform to NTSC video standard, EMC compatibility standards for

railway applications. b) All displayed images, bandwidth and CIF shall conform to relevant video surveillance

standards. c) Cameras should be equipped with automatic mechanisms to ensure proper exposure under

varying lighting conditions. Such mechanisms include, but are not limited to, automatic gain circuitry, day/night sensor switching, and lenses with automatic iris functions.

d) The selection of lenses shall be dictated by the field-of-view to be covered by each

camera, as well as by the size of the camera's detector.

e) All cameras shall be provided with waterproof, dust proof and vandal resistant housings. f) High Speed Pan Tilt Zoom (PTZ) shall be dome type with imager designed for day and

night surveillance. The mounting shall provide an adjustable head that shall allow the housing to be rotated in a 360° horizontal pan, and a 180° vertical tilt. The ingress protection shall conform to IP 54.

g) Minimum light requirement to produce a color image shall be

approximately 0.30 lux. When in the IR sensitive Night mode, less than 0.05 lux (.005fc) will produce a black and white image. Cameras shall also have these features: • UTP video transmission option (PTZ models); • 25X optical zoom lens (PTZ models); • Auto/manual focus; • 12X digital zoom (PTZ); • Lens: varifocal; • Focus : Automatic with manual override; • Iris adjustment: Automatic with Manual Override; • Contour Sharpness enhancement level: selectable; • Signal-to-Noise Ratio > 50 dB; • Gain : up to 28 dB selectable; • Aperture Correction : Horizontal and vertical; • Programmable electronic shutter control; • Backlight compensation; • 360° continuous pan (PTZ); and

Page 125: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-24 December 2015

• Line lock.

h) All monitors to be supplied shall have the following specifications:

• Monitor 22 inches; • Type TFTLCD; • Native Resolution 1280 x 1024 pixels or higher; • Colour 24-bit true colour or higher; • Viewing angle 160 degrees; • Brightness 300cdlm2 or better; • Contrast 700: 1 or better; and • Response time l2ms or faster.

7.9 Station’s Network Video Server Specification 7.9.1 Basic Technical Requirements

The station’s network video server shall have the basic functions to: • Encode NTSC images from surveillance cameras installed in the stations or other video

source into MPEG-4, DVD-like quality video for transmission to the station’s workstation PC and to OCC via a Gigabit Ethernet LAN Switch/FOTS.

• Provide storage of the MPEG-4 (H.264) video in its local hard drive. • The unit shall be designed for use in CCTV applications. • The server shall be rack mounted with front panel LED indicators that display the status

of power, any transfer of data to and from the hard drive, and the occurrence of a hardware failure.

• The server shall be fully compatible with the Video Management software. 7.9.2 Network Video Recorder (NVR) Technical Requirements

a) The recorder shall be capable of simultaneously encoding 30 frames per second of non-multiplexed, video for each of the eight channels at a data rate of 9.6kBit/s to 6Mbit/s per channel or better.

b) The NVR shall have an external Storage Device with RAID 5 array consisting of similar internal storage drive capacity from 1TB to 50 TB thus allowing the server to function efficiently as a DVR to provide long term video recording of the H.264 video streams.

c) The server shall be capable of sending images to the network video recorder (NVR) at the

OCC via FOTS for long term archiving.

d) The front panel of the server shall allow the user to view configuration settings and status of the unit such as IP address, gateway or MAC address and other information but shall not allow reconfiguration of those parameters from the front panel.

Page 126: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-25 December 2015

e) The server shall function as a web video server via the network when used with a standard web browser as the decoder. The server’s encoder shall provide dual stream MPEG-4 video or H.264 images to the browser.

f) The server shall support a recording mode that allows live or recorded sections of a video sequence currently being viewed at the browser to be recorded on the hard drive of the OCC workstation.

g) The server shall allow the recorded video to be played back and viewed from a

workstation(s) and simultaneously be capable of recording the H.264 video to the server’s internal hard drive.

h) The internal clock of the Video server shall be synchronized from the existing master

clock system of LRT Line 2.

i) The server shall have multi Password-protected authorization levels to prevent unauthorized access to the Video server.

j) The server shall be provided with all the necessary software for programming,

configuration and viewing from the web browser.

k) The system shall allow the recording, live monitoring, playback of archived video and data simultaneously.

7.10 Software/GUI

a) The CCTV system for the new stations shall be compatible and interoperable with the

accompanying CCTV Management software. All CCTV equipment with embedded computers for the new stations can be programmed by accompanying software or upgrades.

b) All software components shall be part of the manufacturer’s standard software product

offering. All software components shall be thoroughly tested and proven in reference installations.

c) The GUI shall interface directly with the Video Management or video switcher/control

system and provide complete control and programming of all system features. d) The RAID shall be implemented either using a special controller (hardware RAID), or by

an operating system driver (software RAID). e) The contractor shall supply the software to program and configure the new equipment for

the new stations. The software shall work in conjunction with the latest Windows (8) Operating System, which shall be backward compatible with the earlier versions.

f) Software shall consist of the following but not limited to;

• Network Video Management Software; • Network Video Recording Software;

Page 127: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-26 December 2015

• Video Analytics Software; and • Graphical User Interface Client Software features.

7.11 Network Video Management Software

a) The software shall be a highly scalable enterprise level software with complete video

surveillance solution that will be scalable to a required numbers of cameras that can be added on a unit-by-unit basis.

b) The network video management software shall allow for video to be streamed on a

video mosaic wall. c) Video management software shall offer both video stream management and video stream

storage management. Recording frame rate and resolution in respect of individual channel shall be programmable.

d) All Software and upgrades shall be licensed. Six copies of each type shall be supplied

with the system. e) The disks shall indicate the date, version no. and the operating system employed.

7.12 Testing and Commissioning

a) The Contractor shall conduct Factory Acceptance Test at the place of manufacture to

demonstrate compliance to technical specification and system performance with functional description of the proposed system. The test shall be witnessed by the Engineer and qualified technical staff of the Employer. The cost of all tests shall be borne by the Contractor.

b) The testing and commissioning of the Telecommunication system at the new stations such

as CCTV and APS systems shall proceed also in a staged manner to reflect the installation of both the stand-alone station and integrated systems.

8.0 Supervisory, Control And Data Acquisition (SCADA)

8.1 Introduction

The newly upgraded SCADA System under the Stimulus Fund Project for LRT Line 2 installed in the six (6) Rectifier Substations enables remote monitoring, telemetering and control of Substation facilities. SCADA systems were likewise provided in eleven (11) stations for monitoring of electrical devices, fire alarm systems, UPS and for monitoring the condition of Escalators and Lifts in the stations. It is envisaged that key locations and installations such as electrical substations and train stations for Line 2 East Extension shall be equipped with SCADA and the same shall cover the various sub-station electrical facilities and their respective distribution feeders. Likewise, the SCADA system for the new stations shall monitor important electrical loads and systems in the stations.

Page 128: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-27 December 2015

The SCADA for LRT Line 2 East Extension shall achieve the following functionality:

a) Real time Monitoring and control of Electrical Distribution and Traction Power Systems within the RSS.

b) Acquisition and storage of parameters of Traction Power Supply and Building Management Systems (BMS).

c) Monitor conditions of Fire Detection and Suppression System located within certain nominated station rooms in the stations.

d) Monitor the conditions of the UPS equipment and Battery banks installed in the two (2) new LRT stations and one (1) RSS.

e) Monitor the conditions of Escalators and Elevators in the new stations. f) Monitor the status of various Telecommunications System in the starting OCC such as

Master Clock, CCTV, APS, MSTP, PIS and TETRA Trunked Radio.

g) Monitor status of station’s Jockey Pumps, Fire Engine and water level in cistern tank.

h) Centralized programming and monitoring of systems and processes with regards to change of status of monitored devices for triggering of predefined actions, reporting and analysis of events.

8.2 Scope of Work

The Scope of Work specifically includes but not limited to the following:

a) The Contractor shall design, supply, install, test and commission Remote Terminal Units

(RTUs) for the LRT Line 2 Extension. The contractor shall be responsible for all links (hardware and software) to make the system functional. This shall include AC provision for the SCADA RTU from the electrical room to the RTU.

b) The RTUs shall be designed to handle all specified functionalities of equipment and

devices installed in the new RSS and passenger stations. c) The SCADA workstation and server at the OCC shall be upgraded to accommodate the

three (3) SCADA RTUs of Line 2 East Extension. d) RTUs shall be designed to integrate with the existing system runs on SDH. The

integration of the new equipment to the existing SCADA shall be the responsibility of the Contractor.

e) The Contractor shall supply and install all the necessary interfaces, hardware and software

for the required integration to the existing SCADA system. f) The Contractor shall ensure that current SCADA operation shall not be disrupted during

the installation and commissioning of the new SCADA RTUs in the new stations.

Page 129: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-28 December 2015

g) The Contractor shall submit plans and methodology for the seamless integration to the existing SCADA network.

h) The Contractor shall supply, install, test and commission but not limited to the following:

• The RTUs (complete) as factory supplied shall include Programmable Logic Controllers (PLCs), a CPU which is of the latest series design, sufficient Digital Inputs, Digital Output and Analog modules, Power Supply/Charger, and a four (4) hours back up battery supply, Surge Protector for 230 Volts AC power source and housed in an approved equivalent NEMA Steel lockable enclosure, communication ports to simultaneously communicate over RS-232, RS-485 and IP. The RTU unit shall be complete as manufactured.

• The Contractor shall supply and install electrical materials and accessories required for the AC input power of the RTU.

• The Contractor shall upgrade or expand the existing SCADA Programming software

and Graphical User Interface at the OCC to accommodate the new SCADA RTUs for the East Extension and to comply with the requirement of latest series CPU/s of the RTUs to be supplied.

• Adequate firewalls shall be provided for the new SCADA RTUs.

• Testing of the complete system shall consist of the following: RTU type test;

software functionality tests; routine tests SCADA/ BMS system; and tests after complete installation and commissioning.

8.3 Specification Requirements for SCADA RTUs

a) The RTU to be supplied shall provide the intelligence that will allow the central SCADA workstation at the OCC to communicate with the electrical equipment and similar devices at the new RSS and stations.

b) RTU shall have a non - volatile memory for storing programs and data, timer to ensure the RTU restarts if something fails and real time clock. The RTUs main functions are to control the operation of equipment at the remote site, acquire data from the equipment, and transfer the data back to the central SCADA system.

c) The RTU shall be modular having a separate CPU module, sufficient I/O module/s and

dual power supply. The RTU shall provide 25% I/O spare capability and capacity. The RTU shall have provisions for expansion for additional modules which can be added by plugging into a common backplane.

d) The RTU shall be capable of handling analog inputs/outputs (4-20ma); and discrete

inputs/outputs such contact closures, pulses; momentary or latch operation, in addition to power monitoring.

Page 130: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-29 December 2015

e) Any device which potentially has an embedded computer shall be checked and tested by the contractor or the supplier to verify compliance. The Contractor shall ensure compatibility checks of software configuration versus actual hardware installed.

f) The RTU shall be compatible with the existing SCADA communication protocols. RTU

shall conform to IEC 60870-5 standards for SCADA systems. Programmability and configurability shall conform to IEC1131-3 standards.

g) The RTU shall provide clear indication of local and remote diagnostics. The RTUs shall

have the ability to initiate reporting to the SCADA master. Functionalities such as time stamping, memory capacity to store data in the event of loss of communications, ability to do calculations shall be supported.

h) The RTU shall incorporate pre-programmed self-diagnostic software routines for

maintenance. It shall contain error reporting plus LEDs status indicators.

i) The RTU shall be auto-configuring at startup whereupon the contents and slot location is automatically identified to the programming software when it is initialized. The RTU shall auto-execute a self-diagnostic upon initialization. Diagnostic results shall be available to the programming software via local industrial type notebook computer and/or remotely via MSTP Transmission system.

j) The RTU shall provide peer to peer communications or RTU to RTU communication

including store and forward capability. RTU shall support data rates from 1200 baud FSK, 9600 baud data up to 64 kbps and shall have serial ports to interface with PLCs. RTU shall time stamp acquired data to the required accuracy using the existing Master Clock signals provided at the station’s TER.

k) The SCADA System shall be powered by an electrical supply of 230 V AC, 60 Hz. It

shall be tolerant to voltage variations of ±10% of the nominal; -15% (for 500ms duration) of the nominal voltage and frequency variations of ±2%, without any reduction in the efficiency of the system. An Uninterruptible Power Supply (UPS) system with special provision for smoothing and reduction of the impulse voltages, necessary for the protection of the equipment from the failures of the main power supply of the Network and main disturbances, shall supply power to the SCADA equipment.

8.4 Interface with Equipment Provided by Other Sections

a) The Contractor shall be responsible for the interfaces between the installed equipment and additional ones and equipment provided by other sections of the Works.

b) Due to the mission-critical nature of the SCADA systems, no access to the existing SCADA operating system shall be allowed unless requested in writing and approved by the Engineer and authorized LRTA staff.

c) Only authorized PC or craft terminal with licensed software shall be used during

programming or similar activities thereof in the presence of the LRTA staff.

Page 131: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-30 December 2015

8.5 RTU at the New Stations a) The RTU at the stations shall be located at the traction substation and in the TER of the

station. The incoming and outgoing circuits shall be connected with the appropriate terminals within the cubicles.

b) The Contractor shall declare, for the Employer’s approval, the degree of protection of

these cubicles. The contractor shall be responsible for all incoming and outgoing circuits. c) The incoming and outgoing circuits shall not have any direct electrical connection with

the remote-control equipment logic. The Contractor shall, for the Employer’s approval, declare the degree of isolation to be proposed.

8.6 Environmental Specifications/ and Standards

a) The SCADA RTU shall be able to perform all applicable operations reliably under a

temperature range of -5o C to 50o C and relative humidity for 60% to 95%. It must meet ISO14001 & ISO9001 standards. It shall conform to Ingress Protection IP64 standards against dust, vibration, insects and rodents.

b) The RTU shall meet or exceed the Surge Withstand Capability (SWC) standards as defined in IEEE C37.90A for all inputs and outputs. The enclosure shall conform to UL611 standards.

c) The RTU shall conform to the provisions of EN 61000 standards. d) The RTU shall be designed for open standard telemetry protocols such as DNP3 level 4

with authentication and/or data encryption. 8.7 SCADA I/O Points

The SCADA RTU shall be able to meet the required number of I/O points for the new RSS and Stations given in the Tables below. The points are only indicative and subject to final design changes and future requirements. The reserved capacity of the RTU to be supplied (I/O points) shall be 25% of the total number of actual I/O points used

Table 8.7-1 Indicative Points for SCADA

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

1 Electrical 34.5 kv main circuit breaker Close CB x

(incoming line) Open CB x CB closed x RSS #7 CB open x

Page 132: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-31 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

2 cubicles Local control selected x CB lockout x Trip circuit failure x Broken spring x Low gas density x Incoming line voltage x Incoming line kW/kWh x

2 Electrical 34.5 kV feeder circuit breaker Close CB x

(for rectifier transformer) Open CB x

CB closed x RSS #7 CB open x 2 cubicles Local control selected x CB lockout x Trip circuit failure x

Broken spring x

Low gas density x

3 Electrical 34.5 kV feeder circuit breaker Close CB x

(for auxiliary power transformer) Open CB x

CB closed x RSS #7 CB open x 1 cubicle Local control selected x CB lockout x Trip circuit failure x Broken spring x

Low gas density x

4 Electrical 34.5 kV main circuit breaker Close CB x

(for workshop transformer) Open CB x

CB closed x RSS #7 CB open x 1 cubicle Local control selected x CB lockout x Trip circuit failure x Broken spring x

Low gas density x

5 Electrical 6.6 kV main circuit Close CB x

Page 133: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-32 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

breaker

plus bus transformer cubicle Open CB x

CB closed x RSS #7 CB open x 1 cubicle Local control selected x CB lockout x Trip circuit failure x

Broken spring x

Low gas density x Incoming line kW/kWh x Bus voltage x

6 Electrical 6.6 kV feeder circuit breaker Close CB x

cubicle Open CB x CB closed x RSS #7 CB open x 2 cubicles Local control selected x CB lockout x Trip circuit failure x Broken spring x

Low gas density x

7 Electrical Rectifier Transformer Overtemperature x

RSS #7

2 cubicles

8 Electrical Rectifier Encloser fault x Encl. flt detect. Failed x RSS #7 Deficient insl. Integrity x 2 cubicles Common alarm x

(overtemperature, diode failure, ac and dc surge protection failure)

9 Electrical 1500 V dc switchgear Encloser fault x

Encl. flt detect. Failed x RSS #7 Deficient insl. Integrity x 2 cubicles Bus voltage x

10 Electrical 1500 V dc main (rectifier) Close CB x

CB Open CB x

Page 134: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-33 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

CB closed x RSS #7 CB open x 2 cubicles Local control selected x

11 Electrical 1500 V dc bus-tic CB

RSS #7 2 cubicles

1500 V dc workshop

feeder CB RSS #7

2 cubicles

12 Electrical 1500 V dc mainline Close CB x

feeder CB Open CB x CB closed x RSS #7 CB open x 5 cubicles Local control selected x Load measure/reclosing x Transfer tip operation x Tr. trip circuit failure x

Feeder current x

13 Electrical Mainline negative panel Neg-to-earth voltage x

EB trk return current x RSS #7 WB trk return current x 1 cubicle RSS return current x

14 Electrical Auxiliary power transformer Overtemperature x

RSS service voltage x RSS #7 1 cubicle

15 Electrical Battery and charger Battery charger failure x Battery earth fault x RSS #7 1 cubicle

16 Electrical Local annunciator panel LAP failure x

RSS #7 1 cubicle

17 Electrical Fire detction and intrusion Fire alarm x

control Intrusion alarm x

Page 135: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-34 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

RSS #7 1 cubicle

18 Electrical Ring-main LBS Close LBS x Open LBS x RSS #7 LBS closed x 2 cubicles LBS open x Local control selected x

Fault detected x

19 Electrical Tee-off LBS Close LBS x Open LBS x RSS #7 LBS closed x 2 cubicles LBS open x Local control selected x

Brown fuse x 20 Electrical 6.6 kV/480 V ac Over temperature x Transformer RSS #7 2 cubicles

21 Electrical Station UPS malfunction x

pre-shutdown x

offline x

on battery x

static bypass x

22 Electrical

station 480 volts supply a open

x x

station 480 volts supply b

open

station 480 volts bust tie bus open x

station main 480v power a voltage on voltage on x

station main 480v power b voltage on

voltage on

x

23 Electrical SER power status ats a ser normal supply a x

SER power status ser normal supply b x

Page 136: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-35 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

ats b

SER power status ats a & b ats both power failure x

24 Electrical TER power status ats a ter normal supply a x

TER power status ats b ter normal supply b x

TER power status ats a & b ats both power failure x

25 Electrical lighting viaduct west lighting viaduct west on x

lighting viaduct east east on x

lighting viaduct lp a lpa on x

lighting viaduct lp b lpb on x

lighting viaduct lpb elp on elp on x

26 Mechanical escalator 1 concourse platform safety indicator x

Mechanical escalator 1 up x

Mechanical escalator 1 on x

27 Mechanical

escalator 2 concourse/platform

escalator 2 safety indicator

x Mechanical escalator 2 up x

Mechanical escalator 2 on x

28 Mechanical

escalator 3 concourse/platform

escalator 3 safety indicator x

Mechanical escalator 3 up x

Mechanical escalator 3 on X

29 Mechanical escalator 4 concourse/platform escalator 4 safety indicator x

Mechanical escalator 4 up x Mechanical escalator 4 on x

30 Mechanical escalator 5 ground /concourse escalator 5 safety indicator x

Mechanical escalator 5 up x Mechanical escalator 5 on x

Page 137: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-36 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

31 Mechanical escalator 6 ground/concourse escalator 6 safety indicator x

Mechanical escalator 6 up x Mechanical escalator 6 on x

32 Mechanical elevator 1 concourse/platform elevator 1 in-car estop x

Mechanical elevator 1 low oil x Mechanical elevator 1 car stall x Mechanical elevator 1 in-pit estop x Mechanical elevator 1 power failure x Mechanical elevator 1 door adjustance x Mechanical elevator 1 in-car call button x

33 Mechanical elevator 2 concourse/platform elevator 2 in-car estop x

Mechanical elevator 2 low oil x Mechanical elevator 2 car stall x Mechanical elevator 2 c in-pit estop x Mechanical elevator 2 power failure x Mechanical elevator 2 door adjustance x Mechanical elevator 2 in-car call button x

34 Mechanical

elevator3 concourse/platform

elevator 3 in-car estop x

Mechanical elevator 3 low oil x Mechanical elevator 3 car stall x Mechanical elevator 3 in-pit estop x Mechanical elevator 3 power failure x Mechanical elevator 3 door adjustance x Mechanical elevator 3 in-car call button x

35 Mechanical

elevator 4 concourse/platform

elevator 4 in-car estop x

Mechanical elevator 4 low oil x Mechanical elevator 4 car stall x Mechanical elevator 4 in-pit estop x Mechanical elevator 4 power failure x Mechanical elevator 4 door adjustance x Mechanical elevator 4 in-car call button x

36 Fire Alarm fire alarm fire alarm x intrusion alarm x normal x trouble alarm x

fire pump fire pump fp 1 on x

jockey pump jockey pump on x

Page 138: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-37 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

submersible sump pump high water level x

fire storage tank low water level x

37 Intrusion alarm telecom room intrusion alarm x

38 FOTS alarm fiber optic fots summary alarm x

39 CCTV alarm cctv transmission cctv summary alarm x

40 APS alarm aps system aps summary alarm x

41 Signaling ATP signaling atp track atp summary alarm x

42 Signaling ATO signaling ato track ato summary alarm x

43 Theft pao hold up robbery alarm x 44 AFC afc summary afc summary alarm x

45 OCS overhead catenary disconnect 1 ocs disconnect switch 1 closed x x

ocs disconnect switch 1 open x x ocs switch 1 local x

46 OCS overhead catenary disconnect 2 ocs disconnect switch 2 closed x x

ocs disconnect switch 2 open x x ocs disconnect switch 2 local x

47 UPS ups inverter ups inverter operation x ups mains ups mains operation x ups rectifier ups rectifier fault x

ups collective ups collective fault x

48 Electrical lighting viaduct lighting viaduct west on x Electrical lighting viaduct lighting viaduct east on x

49 OCS overhead catenary switch ocs disconnect switch 1 close x x

overhead catenary switch ocs disconnect switch 1 open x x

overhead catenary switch ocs disconnect switch 2 close x x

overhead catenary switch ocs disconnect switch 2 open x x

50 pumps pressure booster system line pressure x

fire pump fp fire pump fp 1 line pressure x 51 TER temp telecom room ter temperature x 52 SER temp signaling room ser temperature x

Page 139: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-38 December 2015

SCADA POINT BREAKDOWN FOR RECTIFIER SUBSTATION / STATION EQUIPMENT

Item No.

Type

Equipment SCADA Point Digital

Input Digital Output

Analog Input

53 batt voltage telecom 48v supply battery voltage

x 9.0 MSTP/ Fiber Optic Transmission System

9.1 Overview

The originally installed SDH / FOTS served as the Telecommunication medium (backbone) for the transmission and reception of Voice, Data and Video information between all eleven (11) existing stations, 6 RSS and OCC of the Line 2 System.

This backbone was based on Synchronous Digital Hierarchy, STM-1 and Plesiochronous Digital Hierarchy (PDH) systems. The fibers installed conform to ITU-T recommendations G.652 wherein the fiber is optimized for networks where transmission occurs across a broad range of wavelengths from 1285 nm to 1625 nm.

After more than 11 years in operation, the current SDH System has become faulty, causing

outages of the various systems passing through it.

Under the Stimulus Fund Project, a new transmission backbone designed to handle simultaneous large amounts of data and video information has taken the function of the SDH system. The new technology called Multi-Protocol Labelling System or MSTP combined with SDH over FOTS comprised a Multi-Service Platform which was recently implemented for the various telecommunication systems of Line 2. Thirty Six (36) core Single Mode Optical Fiber in dual ring configuration interconnected all MSTP equipment in all 11 stations. For fast and efficient delivery of various telecommunication services, it is envisioned that Line 2 East Extension shall also employ MSTP technology over fiber cores as the transmission backbone for all audio, video and data transmissions in the said extension.

The subsystems at the new stations that shall use the MSTP/Fiber Optic Backbone System are as follows:

• Supervisory Control and Data Acquisition (SCADA); • Trunked Radio System (TRS); • Telephone System; • Closed Circuit Television (CCTV); • Audio Paging System (APS); • Passenger Information System (PIS); • Master Clock Distribution System; and • AFC System

Page 140: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-39 December 2015

9.2 Scope of Work/Responsibilities

The Contractor’s scope of work for the MSTP system over Fiber Optics cable for Line 2 East Extension defined in this document shall include, but not be limited to: • Project Management, Survey, Design, Engineering, Manufacture/Procurement, Supply of

all related goods and providing all related services including installation, testing, training, integration, trial run, commissioning, and related electrical and civil works, cabling, preparation of the related drawings, documents, etc., of the MSTP/Fiber Optics Transmission System for Line 2 East Extension.

• The system shall comprise of an MSTP System, complete with Multiplexers, Routing Switches, Access Switches, interfaces and peripheral devices capable of delivering the quality of service (QOS) requirement in supporting real time voice, data and video services.

• The Contractor shall supply, install, commission all hardware, software upgrade, interface equipment, etc. required for the reprogramming, reconfiguration of the new MSTP equipment and accessories for the new station to the existing MSTP at the OCC.

• The contractor shall be responsible for all expenditures to be incurred in the integration of the new MSTP to the existing MSTP of Line 2.

• The Contractor shall install not less than two (2) x 36 cores Single Mode Optical Fiber (SMOF) on both sides of the new viaduct for the Line 2 Extension from Santolan Station to Masinag Station for ring and node protection.

• The Contractor shall supply termination and splicing equipment such as ODF or Fiber Patch Panels to connect all two (2) x 36 cores of the new FOC to the existing two (2) x 36 cores FOC of Line 2. Unused cores shall be properly terminated and protected from ingress of water, dust or similar objects.

• Prior to cable installation the contractor shall undertake a survey of the designated fiber

route throughout the entire system.

• The existing Fiber Optic ring configuration shall be retained for interconnection between the new MSTP of the new stations and the existing MSTP network.

• Two diverse routes shall be provided for the cable installation from Santolan Depot to Masinag Station in order to feed the Line station areas from each side of the viaduct.

• The Contractor shall connect the new TETRA Trunked Radio Base Station to the new MSTP/FOTS in Masinag station and to the existing Tetra Base Stations of Line 2.

• The Contractor shall determine the projected total capacity and transmission rate of the MSTP system based on the total data rates of the two (2) new stations and existing network of eleven (11) stations to ensure that the MSTP system shall fully support the requirements of the combined thirteen (13) stations.

Page 141: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-40 December 2015

• The Contractor shall calculate the power budget for each section of the fiber optic cable and shall include the loss margin for each respective section. These calculations shall be submitted to the Engineer for approval.

• The existing NMS software if required, shall be upgraded to be able to manage and configure the new MSTP equipment for the new stations.

• New craft Terminals and Portable PCs with licensed software for all network elements of the MSTP shall be provided by the Contractor for maintenance of MSTP equipment at OCC and remote stations.

• The Contractor shall be responsible for the supply of materials and labor for the AC powering requirement of the MSTP equipment in the TER of the new station and all other Telecommunications equipment in the new stations.

• The Contractor shall be available to assist as required up to the end of the DNP the MSTP equipment for Line 2 East Extension and the Fiber Optic Cable Backbone consisting of dual concentric rings.

9.3 System Requirements

• The MSTP shall be the Communication backbone in the new stations.

• The MSTP equipment shall operate with no degradation in performance when subjected

to various forms of electromagnetic interference as follows:

Fluorescent lighting fixtures and associated low voltage control systems; Two way radios; Electric motor-driven tools and appliances such as drills, vacuum cleaners, cooling

fans, test equipment, etc. used in close proximity of the equipment cabinets; and Relays, power supplies, rectifiers, etc., in associated equipment which may or may

not be supplied by others.

• The MSTP shall be a highly reliable system since it will be the primary means to support vital systems used for daily train operation such as SCADA, two way radio communication, Public Address, Telephone system, Master Clock and Automated Fare Collection.

• The MSTP System shall have an availability of not less than 99.995% of all time and other subsystems availability shall be not less than 99.99% of all time.

• The MSTP shall provide a high degree of reliability and redundancy by operating on two independent fiber optic rings, connecting the locations in hopping mode configuration.

• All MSTP Equipment (hardware and software) to be supplied for the new stations shall be brand new, the current model or version and fully compatible and interoperable with the existing MSTP Equipment of Line 2.

Page 142: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-41 December 2015

• For ring protection or node failure, in case a fiber is cut, the Contractor shall install two optical fiber cables running on separate tracks, thus providing cable path diversity.

• The MSTP shall use the existing Network Management System at the OCC consisting of NMS workstation, servers and logging printers.

• The workstation shall have a Graphical User Interface using pull-down menus and icons for user-friendly manipulation of the NMS.

• On-site local maintenance functions shall be possible by using a laptop PC.

• The MSTP equipment shall have sufficient bandwidth and 25% capacity reserve to be able to support digital audio, simultaneous high quality video and high speed data for all Telecommunication System installed in the new stations.

• The MSTP shall provide voice and data communication circuits or bandwidth for the following systems but not limited to:

2 Mbps El (ITU-T G.703 and G.823) Gigabit Ethernet 10/100/1000 Mbps circuits for SCADA, Clock System, PIS and the

Telephone System Data circuits for the Radio System such as Primary Rate El interface or 64 Kbps

interfaces Fast Ethernet connections dual speed 10/100 Mbps, full- or half-duplex complying

with IEEE 802.3, 802.3u and 802.3x

• Ethernet connections for each above named application need to be fire-walled between each other to provide a maximum security level.

• The MSTP shall provide a bandwidth management to ensure sufficient transmission capacity for each application to function under all traffic circumstances on the DTS system.

• The MSTP Transmission System shall be a scalable protocol-independent transport equipment.

• MSTP Multiservice equipment shall support relevant ITU-T recommendation G.8132,

shared protection ring.

• Access Multiplexers at the station shall accept TDM /PCM loads (G.703) such as Tetra Trunked Radio Systems, Telephony and SCADA RTUs.

• Ethernet interfaces shall have layer 1, layer 2 and layer 3 features VLAN capable of up to 1Gbps data rate transfer and shall conform to all relevant networking standards published by the IEEE.

• For the Ethernet based MSTP Equipment, the common modules of power supply, in the

MSTP Equipment shall be provided in (1+ 1) hot-standby power supply protection to prevent failure which shall affect the traffic and performance of the MSTP equipment.

Page 143: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-42 December 2015

• Synchronization Input and Output Interfaces (120 ohms @2048 kHz) and Traffic interfaces for all MSTP equipment are to be provided to conform with the clocking requirements.

• All clock noise specifications shall conform to ITU-T Recommendations G.812 and G.813.

• System synchronization shall be achieved from the Master Clock’s 2.048 MHz timing output.

• All equipment shall have sufficient number of alarms and supervisory indications and shall be provided with self-diagnostic facilities. All alarms, monitoring and diagnostic facilities shall be built-in and shall be displayed on the front panel of the equipment for ease of maintenance. It shall be possible to transmit these indications, parameters to the control stations/NMS.

• All important switches shall be provided with controls on the front panel with suitable safeguard to avoid accidental operation.

• All equipment shall be immune to EMI and RFI interference generated by any nearby

source and shall meet the latest international standards in this regard.

9.4 Fiber Optic Cable Specification

a) The single mode fiber shall have a core diameter 9.2µm average at 1310 nm and a cladding diameter of 125µm.

b) The mechanical and environmental specifications on the optical fiber cable shall be in accordance with ANSI/ICEA-S-83-640 for outdoor cable. The Contractor shall also submit all technical data inclusive of mechanical, environmental and optical characteristics of the fiber optic cable for approval by the Engineer.

c) The Fiber shall conform to the following standards:

• ITU-T G.652.A, B, C, D; • IEC Specifications 60793-2-50 Type B1.3; • TIA/EIA 492-Controlled Atmosphere Aluminum Bracing (CAAB); and • Telcordia’s GR-20.

The fiber shall be optimized for 16+ channel coarse wavelength division

multiplexing (CWDM) networks. The fiber shall be a full spectrum fiber for optical transmission in and around the

water-peak region (1360nm – 1460nm). Attenuation shall not be greater than 0.35dB/Km at 1310nm and 0.26 at 1550nm. Maximum PMDQ shall be ≤ 0.2dB /Km The fiber shall conform or exceed macro bend loss standard at 1310 nm and

comprehensive environmental specifications. SC/LC polished connectors shall be used for the termination of all fiber cores

Page 144: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-43 December 2015

d) The Contractor shall employ lasers for the transmission of digital signals over the fiber optic bearer.

e) Laser safety shall be in accordance with IEC 825-1 or ANSI Z 136.1 standards.

f) A comprehensive set of Optical Time Domain Reflectometer (OTDR) tests for each

of the cores of the Single Mode Optical Fiber (SMOF) cable shall be carried out by the Contractor and supplied to the Engineer in both hard and soft copy formats prior to installation showing the traces during the OTDR testing at 1310nm.

g) The OTDR tests shall be repeated upon completion of the installation of the SMOF

cable and be submitted to the Engineer for approval. Should the OTDR traces not match the cable shall be re-tested and if necessary reinstalled using a new complete length of cable.

h) The Contractor shall replace at his own expense such damaged or defective cable. i) The transmission diagram shall be provided by the Contractor showing the services

installed within the cable configuration and clearly identify each core versus its use (dark fiber, operational core and service).

j) Patch Cords and interconnecting cables between MSTP equipment at the TER shall

be factory assembled (when applicable) and not on site. 9.5 Installation Requirements

9.5.1 Fiber Optic Cabling Installation

a) All cabling installation shall conform to relevant ANSI/TIA/EIA/CENELEC/ISO/IEC Fiber Optic cabling and installation standards.

b) The cables shall be supplied on cable drums using pre-cut lengths by careful measurement of each cable run between station TERs.

c) During the installation of the cable, care shall be exercised to ensure no damage to the cable is imminent.

d) The cable shall be installed within the cable trays on either side of the viaduct.

e) After installation, the cables shall be permanently labeled every 5 meters with the letters

“Property of LRTA”. Labeling shall be provided by the Contractor.

f) All cables are to be fully supported throughout its entire run.

g) At no time shall more than 400 pounds of tension be placed on any fiber cable while it is being pulled through tray or conduit. It is preferred that all fiber cable be pulled with hand power only. If power winches or mechanical advantage devices are used to pull cable, a tension meter must be used to insure that maximum tension is not exceeded.

Page 145: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-44 December 2015

h) Alternatively, a "mechanical fuse" rated at 350 pounds may be included in the linkage. Torsion shall be avoided by the use of a swivel at the cable end. While under tension, a minimum bend radius of twenty (20) times the outside cable diameter shall be maintained through the use of pulleys and sheaves where required. After pulling, no bend may have a radius, at rest, of less than 10 times the outside cable diameter.

i) Each cable shall be permanently labeled at each end with a unique cable number. In

addition, labels shall be affixed to the cable trough at every transition of a hand hole, riser closet or major pull box. Labels shall indicate other end of the cable or from station to station.

j) Each fiber optic strand shall be labeled with a unique identifier at the coupler in the Fiber

Patch Panel. Connectors shall be labeled on the identifying sheets on the front of the panel.

k) Each fiber shall be labeled where it enters the back of the patch panels. The identifier

shall be in the format Cable # - tube - strand. For tight buffered cables the "tube identifier" shall be labeled "xx".

l) The terminal ends of all fibers cable strands shall be field connectorized. The connectors

shall be mounted on bulkheads and installed in Fiber splicing enclosures or Fiber Patch Panel (FPP). Both ends of all fibers within a fiber cable shall be terminated with SC, PC polish style connectors. Prescribed tools shall be used for the termination of cables.

m) Fiber cables are to be terminated in rack-mountable stand-alone Fiber Patch Panel units

for installation. The Fiber patch panel shall be installed inside this cabinet provided for the MSTP equipment. Each panel shall be labeled with a machine made label with permanent black ink on a white background. In addition, each FPP shall be labeled on the face plate with the identifiers of the cables it contains.

n) If it is necessary to splice pigtails onto an existing, partially terminated fiber cable, the

splice type utilized must conform to whatever is already in use at a particular station. Clearance from Engineer must be obtained before installing any type of splice.

o) At each end of the cable, sufficient slack (5 to 10 meters) shall be left to facilitate

reasonable future relocation of the FPP.

p) It is suggested that each individual fiber in a cable be tested with an OTDR for length and transmission anomalies while on the reel before installation. The Contractor shall conduct fusion splicing using electronic fusion splicing equipment complete with splicing kit designed for the fiber type.

q) The accurate alignment of fiber cores prior to splicing shall be verified by using a

technique that monitors the optical power transmitted across the splice interface. Splice loss at patch panels shall not be greater than 0.5dB at 1310nm.

r) After installation, all single mode fiber strands shall be tested end-to-end for bi-

directional attenuation, 1310nm/1550nm for single mode fibers. Tests should be

Page 146: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-45 December 2015

conducted in compliance with EIA/TIA-526-14 or OFSTP 14, Method B, according to the manufacturer’s instructions for the test set being utilized.

s) Tests must ensure that the measured link loss for each strand does not exceed the “worst

case” allowable loss defined as the sum of the connector loss (based on the number of mated connector pairs at the EIA/TIA-568 B maximum allowable loss of 0.75dB per mated pair) and the specified optical loss in db/Km.

After the cable is in place, it shall be tested in the following manner: • After termination, each fiber shall be tested with an ODTR for length, transmission

anomalies, and end-to-end attenuation. Results are to be recorded and supplied to the Engineer in the form of hard-copy printouts or photographs of screen traces.

• After termination and bulkhead mounting, each terminated fiber is to be tested for end-to-end loss with a power meter/light source. As above, results are to be recorded and supplied to the Engineer for approval.

• The maximum allowable attenuation for any splice or termination is 0.5db @ 1310nm.

• The Contractor shall review all end faces of field terminated connectors with a fiber inspection scope following the final polish. Connector end faces with hackles, scratches, and cracks chips and or surface pitting shall be rejected and repolished or replaced if repolishing will not remove the end face surface defects. The recommended minimum viewing magnifications for connector ends are 100 X for multimode fiber and 200 X for single mode fiber.

• The Contractor shall replace defective FOC cables with a brand new cable without splices from one station to another.

9.5.2 MSTP Equipment Installation

a) The MSTP Multiplexer Equipment shall be mounted on 482.6mm (19-inch) racks in accordance with CEA-310-E and located inside the Telecommunications Equipment Room of the new stations.

b) Ventilated rear panels, solid side panels and solid top panels shall be provided. Equipment racks shall be provided with lockable front and back panels that limit access to equipment. The lockable front shall not cover items that require O & M personnel access.

c) Rack cooling shall be through perforations or louvers in front panels to ensure adequate

ventilation of equipment and top rack mounted fans. The racks and panels shall be factory finished with a uniform baked enamel over rust inhibiting primer.

d) The Contractor shall be responsible for providing UPS derived AC power to the MSTP

equipment inside the TER by supplying and installing AC lines, circuit breakers, conduits and accessories between the MSTP equipment and the electrical room of the new stations.

e) The Contractor must arrange with the Engineer to carry out this work and submit a works

schedule. The Engineer shall approve such works program.

Page 147: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-46 December 2015

f) Equipment and Installation shall comply with all relevant Codes, Standards and Regulations Specified in the Tender document.

g) The MSTP Equipment shall be designed in a modular and rack-type structure using plug-in units, so that field repairs can be accomplished by direct plug-in replacements. Polarization Mode Dispersion (PMDQ).

h) The equipment construction should be such that it does not allow ingress or entry of

rodents, insects and dust. For this, equipment should be suitably sealed from all sides, top and bottom.

i) All MSTP equipment and associated circuitry shall be accommodated in fully enclosed

cabinets completely protected from dust, rodents and insects. 9.6 Pre - Delivery Requirements

a) The Contractor shall conduct a Factory Acceptance Test (FAT) of the MSTP system in

the country of manufacture to verify published technical specifications, equipment performance with simulated TDM, high speed data and IP loads such as IP Video (CCTV) Voice (telephone)

b) The FAT shall be witnessed and certified by the Engineer and qualified technical staff of

the Employer. 9.7 MSTP Equipment Integration

a) The existing MSTP equipment at the OCC shall be capable of seamlessly integrating the

two (2) MSTP remote equipment in the new stations to the existing MSTP network. The Contractor shall specify and supply all interfaces, software or upgrades required for the desired integration.

b) The integration shall not in any way affect operation of the existing MSTP system for the eleven (11) revenue stations.

c) All interfaces, both electrical and optical, multiplexing structure, clocking system, etc.,

shall be in accordance with the relevant clauses of the current ITU-TG Series recommendations.

10.0 Automated Fare Collection (AFC) – Local Area Network (LAN) 10.1 Existing System Description

All eleven (11) Line 2 stations are equipped with multiport Network switches used for interconnecting AFC equipment of the stations with the Central Processing System at the Depot via the MSTP transport system.

Page 148: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-47 December 2015

10.2 AFC LAN Requirements for LRT Line 2 East Extension

a) The Contractor shall provide a LAN to interconnect the proposed AFC SPS equipment at each station with the existing Central Processor System/Data Server located at the LRTA Santolan Depot.

b) The Contractor in designing the AFC Local Area Network (LAN) System for the new stations shall include all additional telecommunications equipment to interface where necessary with the new AFC equipment. The Contractor shall be required to design and supply the new LAN and the interfacing systems. The Contractor shall submit all designs to the Engineer for approval.

c) The planned LAN system in the new stations shall be interfaced with the proposed Multi-

Protocol Labeling System (MSTP) in the new station. The LAN switch shall have HDLC features and should be interoperable with the proposed MSTP at the new station. The LAN shall provide the required bandwidth requirement of the AFC system for the new stations.

d) The Contractor shall supply and install the AFC transmission equipment including the interfaces for operation over the new network.

e) The system shall consist of UTP/ STP cabling, conduiting works, suitable interfaces

with the Telecommunications Equipment Room (TER) rack-mounted LAN equipment, and the Fiber Optic Transmission System backbone and MSTP transmission equipment.

f) The system shall be synchronized with the Master Clock System. 10.3 AFC LAN Equipment Installation and Interface Requirements

a) The Contractor shall perform all pre-design and installation surveys to ensure they are

fully aware of all interface and on-site requirements.

b) The LAN Switch shall be installed on a 19-inch rack at the station’s TER and powered from a 220 VAC 60 Hz source. It shall be grounded to a grounding bus bar at the TER in accordance with local and international codes and standards.

c) The Contractor shall perform the necessary co-ordination with other contractors where

relevant interfaces are required.

d) The Contractor shall ensure that no interruption occurs to revenue operation throughout the installation, testing and commissioning phases of the AFC LAN for the new stations.

e) The Contractor shall provide a detailed methodology of how they intend to implement the

works. This shall include any proposed disruptions to existing equipment operation, which may only take place during non-revenue operations.

f) The Contractor shall be entirely responsible for the clearing of all work sites both during

and upon completion of the works.

Page 149: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-48 December 2015

g) All activities related to the AFC LAN installation testing and commissioning shall be subject to approval of the Engineer.

11.0 Telephone System

11.1 Overview of the Existing System

a) The telephone system of Line 2 was recently upgraded from analog to IP based telephone system to provide railway staff with telephone voice communications between locations equipped with telephone sets. Telephone sets are provided in all passenger stations, RSS and offices in the Depot in Santolan. Signal Post Telephones function as direct Line Telephones for emergency purposes between Operation Control Center and wayside.

b) To conform to the newly commissioned IP based telephone system, the LRT Line 2 East Extension shall employ IP based Telephone equipment. Likewise, additional modules or cards and or license shall be provided to accommodate the number of telephones to be provided in the new stations and RSS.

11.2 Scope of Works

a) The Contractor shall design, supply, and install, program, test and commission line cards, and accessories capable of accommodating, additional telephone requirements for the LRT Line 2 East Extension.

b) UTP cables, hardware, and termination panels inclusive of software as required shall be supplied and installed.

c) All electronic equipment to be supplied shall be fully compatible and interoperable to the

existing head end IP Telephone equipment at the OCC or related equipment of the existing IP Telephone system.

d) Where applicable, the Contractor shall install new termination panels and accessories at

the Depot Telecommunication Equipment Room or TER of new stations.

e) Likewise, the Contractor shall link the new telephones in the new stations to the existing PABX at the Depot via the MSTP equipment of the new stations. The entire commissioning procedure shall be carried out by the Contractor.

f) Network Switches with sufficient ports shall be installed in the new stations to integrate

all telephones.

g) The Contractor shall supply and install UTP cables, conduits, boxes, IDF and all necessary materials in the stations for local telephones and wayside telephones to be connected to the new network switch in the station.

h) For the Line 2 East Extension project, the Contractor shall provide the required telephone

facilities. The total number in the succeeding pages is indicative only and may change depending on the operational needs of the Line 2 East Extension Project.

Page 150: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-49 December 2015

i) The Contractor shall install Telephone facilities, but not limited to the following locations:

• Platforms, concourses; • In designated offices/rooms of the new stations; • Inside the SER of Emerald and Masinag Stations; • Inside the new RSS; • Inside the TER in the new stations; and • Train Controller office.

j) All equipment supplied shall be fully compatible with the existing IP Telephone System

of Line 2. All new modules or cards if required shall be of the latest model and can be easily configured and programmed by the licensed software to be provided by the contractor.

k) All new Telephone equipment that requires GPS reference time shall be synchronized

with the existing Master Clock at the OCC.

l) The Contractor shall ensure that the supplier is able to guarantee hardware and software upgrades and spare or compatible parts for a period of not less than 10 years.

m) The Contractor shall perform all works necessary for the installation of the new cards, modules and accessories at the OCC TER and related works. This shall include, but not be limited to the following:

• Interfacing with the existing Network Switches in each station and inside the Depot; • The supply and installation of an additional Distribution Frame (DF) or termination

assembly and associated cables; • UTP cabling from the network switch to different telephone locations; • UTP cabling in the new Line and RSS stations of the Employer due to additional

telephone sets requirement; • Installation of network switch for each stations; • Programming or Software Configuration; and • Programming of new cards.

n) The Contractor shall ensure that all works do not interrupt the existing telephone system.

Any shutdown of equipment shall only be allowed at mutually agreed periods, which shall be scheduled in advance and in accordance with the Contractor’s construction schedule and approved by the Engineer.

o) The Contractor shall not disrupt or disturb existing SPT circuitry during installation and test of the equipment.

p) The Contractor shall provide all equipment for the completion of all works as required.

Page 151: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-50 December 2015

11.3 Submittals

The Contractor shall submit, but not limited to, the following: • Shop drawings for telephone installations in new stations, Network Switches installations

in the new stations; • Product data and structured cabling in new stations; • Functional description of each telephone system and purpose of all proposed test and

diagnostic equipment; and • Telephone Directory.

11.4 Telephone Equipment Specifications

All telephone instruments shall meet the following specifications;

a) IP based of the latest model and fully interoperable with the upgraded Line 2 IP telephone

system. b) Equipped with LCD display, Power over Ethernet with 2 line capabilities. c) Conform to communication protocol Session Initiation Protocol (SIP) SIPv2 and audio

format standards G.711 G.729 and G.722. d) Ability to transfer and forward calls, call waiting, call holding, call muting, redial,

speakerphone, volume control auto answer and three way conference. e) Phone book to store 200 phone contacts and allowing manual entering of contact

information. f) Power adapter with voltage input from 100-240 VAC @ 50-60 Hz. g) The Telephone instrument shall have the capability to function as a hot line telephone.

Page 152: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-51 December 2015

11.5 Overview of Telephone Sets per Stations

Table 11.5-1 Indicative Telephone Unit

Station

Location

Recommended Sets

Emerald Platform 4

Concourse/Rooms/Other Offices 8 Technical Room (TER, SER, Mechanical Room) 4

Substation/Electrical Room 2

Masinag Platform 4

Concourse/Rooms/Other Offices 8 Technical Room (TER, SER, Mechanical Room) 4

Substation/Electrical Room 2 TOTAL

36

11.6 Signal Post Telephones

The Contractor shall supply Signal Post Telephone (SPT) sets with one (1) spare set. These telephones shall provide direct connection from their trackside location to the OCC Control Room. The SPT shall conform to the following specifications: • Stainless steel construction; • Full Keypad or Auto Dial with Remote programming; • Vandal and weather resistant to IP 66 standard; • Handset operation with armored cord; • Non-volatile memory store; • Selectable DTMF/ Pulse Dialing; • Compatible with the new upgraded IP PABX; • CE/EMC compliant; and • Inductive coupling for hard of hearing.

11.7 Signal Post Telephone Requirements

Table 11.7-1 Indicative SPT Unit

Location Required Number

of SPT

Wayside Turn out between Emerald& Masinag 1 Turn Back Masinag, RSS 2 OCS Wayside Isolator 2 Emergency Phones along viaduct To be determined later

Page 153: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-52 December 2015

11.8 Other Related Works

a) The Contractor shall coordinate with the Civil group for the floor plans of the stations, and perform a survey of all stations prior to the commencement of any design work. The Contractor shall include the survey report, plans, and drawings necessary for the proper implementation of the project and for approval by the Engineer.

b) The Contractor shall provide warranty and maintenance for all new equipment in accordance with the Conditions of Contract.

c) The Contractor shall provide all engineering plans and technical documentation of new

equipment and installations. These shall be provided in both hard and soft copy forms. Furthermore, any revision(s) of existing configuration shall be documented and indicated in drawings with detailed explanation.

d) The Contractor shall provide training for maintenance personnel of the Employer and

designated representative for the correct operation and maintenance of all Telephone Switching Equipment and telephone apparatus, installed in Line 2 East Extension.

e) The Contractor shall supply the prescribed test equipment, and tools including self-

powered telephone sets for operation and the maintenance of the telephone equipment installed in the new stations.

f) The Contractor shall prescribe and supply spare parts as approved by the Engineer.

g) The Contractor shall coordinate with the Engineer and LRTA staff for the assignment of

telephone numbers for every telephone instruments, data and voice terminal. 12.0 Radio System

12.1 Current UHF Trunked Radio Network

LRTA is currently upgrading the Line 2 Trunked Radio System from analog to TETRA Digital Radio System, The new TETRA Trunked Radio System will be capable of providing voice and data radio communication between OCC operators, train drivers and portable radio units; between holders of portable units within Line 2 Alignment and the Depot. However, an additional base station (repeater) if required shall be installed in Masinag Terminal Station to effectively cover the entire LRT Line 2 East Extension including turn back areas.

12.2 Scope of Work

a) The scope of work of the Contractor shall cover, design, engineering, `testing and pre-delivery inspection, shipment, installation, acceptance testing and commissioning of a TETRA Digital Base Station. Additional handheld units maybe required

b) The Contractor shall connect the new TETRA Base Station to the proposed MSTP/Fiber Optic Transmission System in the station and seamlessly integrated to the existing TETRA Trunked Radio System.

Page 154: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-53 December 2015

c) All interface equipment or similar devices which may be required for this interconnection shall be supplied and installed by the Contractor.

d) The Contractor shall be responsible for providing adequate power requirements for the

Base radio equipment. This shall include supply and installation of 230 volts power lines, conduits and accessories between the radio room where base station equipment will be installed and the Telecommunication UPS. The Contractor shall provide redundant air conditioning units for the optimum performance of the base radio equipment.

e) Prior to shipment, the proposed TETRA equipment manufacturer shall perform

Acceptance Tests of the Base Radio hardware and software to be used in the LRT Line 2 East Extension to be witnessed by the Engineer and qualified technical staff of the Employer. This shall include giving handouts and lectures on basic equipment/system operation.

f) The Contractor shall be responsible for providing technical training for LRTA currently

assigned in the Maintenance of the Radio System.

12.3 Base Station

a) The Base Station shall provide the necessary outdoor coverage for the operational area of Line 2 East Extension. Coverage shall include the entire LRT Line 2 East Extension alignment including turn back areas, all station areas of the new stations, inside and outside areas of the new substation to be constructed within the Emerald Station.

b) The Base Station shall be fully compatible and seamless integrating with the existing TETRA Trunked Radio System and shall permit two way operation between existing radio units, e.g. Mobile radios on board trains and handheld radios within its prescribed coverage area.

c) The Base Station shall have proven interoperability with other vendor terminals.

d) The Base Station shall be equipped with sufficient number of channels to allow for

simultaneous conversation between users of all programmed talk groups.

e) The Base Station shall be capable of being monitored and controlled by the existing trunked radio management system at the OCC.

f) The Base Station shall provide the necessary handover requirements for continuous operation of radio units between the new Base Station and adjacent Base Stations.

g) If a Base Station loses connection with the system infrastructure it shall operate on an

independent site trunking mode whereby the Base Station continues to independently support all calls within its coverage area.

h) The Base Station shall have link redundancies for IP connectivity and ring configurations

between Base Stations.

Page 155: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-54 December 2015

i) The Base Station shall operate on the same frequency band used by the existing Line 2 TETRA Radio system.

j) The Base Station shall be comprised of the following equipment, but not limited to:

• Trunking Site Controller; • Base Radio/s; • Antenna System; and • Alarm Module.

k) The Base Station shall be equipped with the appropriate battery backup providing up to four (4) hours of power backup in the event of commercial AC power failure. The Base Station shall be capable of supporting the following key features:

• Remote configuration of Base Station; • Remote diagnostics of Base Station; • Remote desktop/terminal services; • Remote and local Software download; • Remote network management; • Fast call setup time; • Instant one-to-many communication; • Support telephony, voice; and • Local Site Trunking with voice trunking capabilities for added resilience.

Technical Specifications:

Frequency: 350- 400 MHz Transmit Power: 2 watts to 40 watts (adjustable) Input Power: 24VDC operation Sensitivity: -120 dbm typical (static) 112 dbm typical (dynamic) Operating Ambient Temperature: -25 to 60° Celsius Humidity: 95%, non - condensing ITU emission class: 18K0G7W Receiver Diversity: Dual or triple-diversity, duplexed or non-

duplexed Carrier Spacing: Operating Bandwidth: 25 KHz External IP transmission Network interfaces: Number of interfaces 2 Air interface standard Compliance: TETRA V & D (EN 300 392)

External synchronous Transmission network interface: Physical interface V.11, balanced Connector: 15-pin male Sub-D Line speed: 64 or 128 kbps Bandwidth per Base Radio: 32 kbps Clock source: External, Master Clock

Page 156: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-55 December 2015

12.4 Base Radio

a) Each Base Station shall be equipped with at least two (2) R.F Channels.

b) The Base Radios shall be designed for continuous unattended twenty-four (24) hours of operation.

c) When interferences happen on the active Control Channel of the Base Station, alarms

shall be displayed on the network manager terminal. The system manager can then decide if the channel is to be taken out of service.

d) The output power of the proposed Base Station shall be 25 Watts after the transmitter

combining equipment.

e) The proposed base radio shall be capable of multi receiver diversity operation when required.

f) The proposed Base Radio shall be equipped with RF combining equipment, allowing the

use of up to maximum three (3) antennas and yet providing both transmitting and three (3) receiver diversity capability.

g) The Base Radio shall be equipped with a Front End Distribution System which accepts

inputs from the transmitters in the Base Station, to combine them into the transmit antenna.

h) The Base Radio shall have receiver preamplifiers and a splitter for each receive antenna to support multi receiver diversity operation.

i) The proposed Base Station shall be installed inside the Telecom equipment room for ease

of operation and maintainability. All modules inside the Base Station shall be easily accessible and can be replaced with ease in the event of any module failure.

j) The proposed system shall include the necessary hardware and software to support telephone interconnect services. The proposed system shall be interfaced to the LRTA Line 2 PABX (via QSIG signaling protocol over E1) to support telephone interconnect calls.

12.5 Alarm Module

a) The Base Station shall be capable of monitoring the integrity of its equipment. The Base

Station shall incorporate an alarm card to provide fault reporting and allow remote control functions at the Base Station site.

b) Software upgrades can be downloaded to the remote Base Stations over the network infrastructure. If a software upgrade is unsuccessful, the Base Stations shall be able to automatically revert to the previous version.

Page 157: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-56 December 2015

12.6 Base Station Reliability

a) The Base Station is a critical path in the communication between subscriber and infrastructure. It, therefore, shall be fitted with redundant features to ensure reliable system operation in event of a failure. If a Base Station loses connection with the system infrastructure, it shall enter a fallback mode whereby the Base Station continues to support independent site call trunking. It shall also be fitted with various alarms that can indicate a failing condition to the System Manager.

b) Two or three-branch diversity reception shall provide for protection against failure in the

receive antennas or receiver multicouplers. The proposed Base Station shall have high reliability with a Mean Time between Failure (MTBF) of at least 50,000 hours. A suitable battery backup system shall be provided to guard against failure of the AC supply mains.

12.7 Independent Site Trunking

The proposed Base Station at the remote sites shall be equipped with the Independent Site Trunking feature. This feature shall enable the Base Station to automatically act as a standalone compliant trunking system should communication with the Master Site equipment be lost. The base station shall operate in local site trunking mode independently with at least the following features when the central switching equipment or the link to the central switching equipment fails: • Subscriber radio registration and deregistration; • Talkgroups call; • Busy queuing and automatic call back; and • Emergency call.

12.8 Wide Area Restoration

While in Independent Site Trunking operation, the Base Station shall constantly monitor if the link to the master site equipment is restored. When the Base Station determines that the link is restored, it shall return to wide-area trunking. When this takes place, the site controller shall automatically up load the site registration information to the system controller.

12.9 Power Supply

The Base Station to be installed in the new station shall be powered by a dedicated UPS for increased reliability.

12.10 Spares Radio Units

The Contractor shall supply 30 units’ spare handheld radio units and 3 mobile units fully interoperable to the existing TETRA Radio system of Line 2.

Page 158: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-57 December 2015

12.11 NTC Requirements

The TETRA Radio equipment to be supplied shall be type approved by the NTC. A certified Xerox Copy of approval certificate shall be presented together with the equipment technical specifications. The Contractor shall be fully responsible for securing the required licenses and permits for the installation and operation of the Base Station, mobile and portable radios with the National Telecommunications Commission (NTC). The Contractor shall prepare all engineering drawings required by the Commission for the installation and operation of the base stations, mobile and portable radios for LRT Line 2 East Extension.

13.0 Uninterruptible Power Supply (UPS)

13.1 UPS in Every Station

Currently, Uninterruptible Power Supplies are provided exclusively for all existing Telecommunication Systems in all 11 stations and in the OCC and Depot in Santolan.

13.2 Scope of Works

a) The Contractor shall design, supply, install, test and commission complete sets of UPS for the new stations of LRT Line 2 East Extension Project. This shall include battery banks, racks, cables, all accessories, fixtures and fittings and grounding provisions necessary for reliable operation.

b) The Contractor shall supply Polyphaser or Transient Voltage Suppression System (TVSS) for AC protection.

c) UPS shall be installed at the following locations:

• Inside the station TER • Inside Substation for SCADA

d) The Contractor shall conduct a survey of individual equipment rooms and the required

load of all equipment to be provided with UPS.

e) Preliminary rating of telecommunications loads is given below. However, these may vary for different equipment and the Contractor shall confirm all load requirements: • 5 KVA each for the 1 repeater sites/base stations; • 5 KVA each for 2 stations; and • 3 KVA each for 1 SCADA RTU for Traction Power substation.

13.3 UPS Performance Specifications

a) The system shall use microprocessor circuitry in the main inverter or battery charger

circuitry.

b) The UPS shall be rack mounted and installed inside a NEMA rated cabinet together with the Service Bypass Switch and sealed battery banks.

Page 159: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-58 December 2015

c) The UPS unit shall be capable of single phase, 60 Hertz operation.

d) The UPS shall accept the standard voltage of 220VAC.

e) The UPS shall include an integral, secure, make-before-break maintenance bypass switch. The maintenance bypass switch shall incorporate a push-to-turn function. Pushing the maintenance switch shall invoke the static bypass and indicate that it is safe to turn the switch to the maintenance bypass mode.

f) The UPS System’s battery charger shall be completely automatic with a programmed

reference, and capable of restoring the battery to capacity within 3 hours after restoration of utility power.

g) The rectifier charger shall incorporate harmonic and power factor correction circuits

inherent to the UPS. External filter units will not be accepted.

h) The charger shall be all solid state and shall automatically maintain the battery in the fully charged condition whenever the utility power is available.

i) The UPS back up batteries shall be of the maintenance free type and shall be fully sealed

types with no gas leaks. The battery shall operate entirely unattended and shall have a minimum life span of not less than 3 years. Periodic inspection of batteries shall be required but kept to a minimum.

j) A low-voltage disconnect circuit designed to reduce battery discharge during extended

power outages, shall monitor the battery voltage and disconnect the inverter when battery voltage drops to approximately 85% of nominal voltage.

k) The UPS shall operate continuously at full output without de-rating while subjected to

ambient temperatures of 0ºC to 50ºC.

l) The output shall be sinusoidal with typical 3% THD under a linear load. The system shall be capable of non-linear loads with a crest factors of 3:1.

m) System metering and controls shall consist of an alpha-numeric front panel display,

normal, caution and alarm indicating LED’s or similar indicating characteristics, fused battery disconnect switch, input and output disconnect switch, audible failure alarms with silence switch, dry contact for remote failure alarm.

n) It shall use a compatible computer interface connector for the above metering and battery monitor with alarm.

o) The provision of a USB, RJ45 or RS 232 port for remote monitoring of the various

functions of the UPS shall be included.

p) All equipment shall be in compliance with the applicable national and international standards for safety, RF emission and immunity.

Page 160: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-59 December 2015

q) The UPS shall have a complete instruction and servicing manual in hard and software form.

13.4 UPS Functional Requirements.

a) All connected loads shall be continuously supplied by the UPS equipment, which shall be

fed from the normal utility power source.

b) Upon failure of the utility power input, the load shall automatically continue to be powered via the system’s battery and inverter for a minimum of 4 hours. The switching time shall be transparent with no transients when switching from normal to emergency power and vice versa.

c) The UPS shall also protect all connected equipment from transients and voltage

fluctuations. The unit shall be sufficient for the particular application.

d) When the power is restored at the normal supply terminals of the system, the rectifier charger will supply power to the load through the inverter and simultaneously recharge the battery to a float charge mode.

e) If any element of the UPS fails and the power is available at the normal supply terminals

of the UPS, the static bypass transfer switch shall transition the load to the normal source with less than 1/4 cycle interruption of the supply.

f) If a fault occurs in the load and current exceeds of the overload rating of the UPS system,

the static bypass transfer switch shall operate to bypass the fault current to the normal supply circuit of the UPS system for fault clearing.

g) When the UPS fault has cleared, the static bypass switch shall return the load to the UPS

system.

h) While in the battery operation mode, the UPS secondary output shall be capable of supplying continuous 230volts at 60 Hertz AC power to all loads up to the specified KVA rating of the system with a minimum 0.9 power factor.

i) The UPS shall boost the line voltage to the desired level of 230 VAC level should it fall

more than 10% of the nominal level.

j) The system shall automatically protect itself against damage from overloads and short circuits while powered from either the utility AC or during emergency mode operation.

k) It shall automatically recover from such overloads and clear short circuits by means of

over current protection devices. l) The UPS System shall automatically revert to emergency mode operation should the

average utility AC voltage fall below 75% of nominal line voltage.

m) Under emergency operations, the microprocessor shall regulate the output voltage within ±1% of nominal at full load for the specified discharge period and the frequency shall be within ±0.05% of nominal.

Page 161: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-60 December 2015

n) During emergency or maintenance works a maintenance bypass switch shall provide complete isolation of the UPS load terminals from external circuits. During a UPS fault, an automatic transfer switch shall disconnect the UPS should such an event occur.

o) When the load is supplied from the utility through the maintenance bypass switch, the AC

supply terminals shall remain energized to permit UPS operational checking, but the UPS load terminals shall remain isolated from the load.

p) The UPS shall operate with humidity up to 95% (non-condensing).

13.5 UPS Installation Environment

The Contractor shall ensure that: • All of the UPS ventilation grills are left clear and free from obstructions and any

recommended minimum distance required between the UPS and the nearest obstruction is not breeched;

• If the UPS is to be located within a small environment (e.g. a rack), ensure that sufficient ventilation is provided as the UPS system will generate heat;

• Always ensure that the UPS is easily accessible (front and rear); • Always provide adequate space around the cable connections points of the UPS; • Always provide adequate space around any switches or buttons that may need to be

accessed in the event of an emergency; and • Always ensure that the visual display panel of the UPS is easily accessible.

13.6 Standards

The systems shall be designed in accordance with: • IEC 62040-2: EMI Requirements for Uninterruptible Power Systems; • IEC 61000 series: Electromagnetic Compatibility; • MIL-STD-461F: Electromagnetic Compatibility; • American National Standards Institute (ANSI C57.110); • Institute of Electrical and Electronic Engineers (IEEE 519-1992 and IEEE C62.41-1991); • National Electric Code (NEC); • National Fire Protection Association (NFPA Article 70); • Underwriters Laboratories (U/L) 1449, 1778, 991, 924, 544; and • FCC Article 15, Section J, Class A.

14.0 Passenger Information System (PIS) 14.1 Overview

a) The existing Line 2 PIS allows the OCC personnel to send visual messages to the passengers while they are in the stations. The Running LED alphanumeric display system was used in Line 2 since 2004 to convey messages and information to passengers in the stations.

Page 162: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-61 December 2015

b) For LRT Line 2 East Extension, it is envisaged to install a modern PIS to facilitate transmission of important messages to passengers in the stations as follows: • Routine messages related to train arrival and departure; • reminder messages for passengers safety in the station; • information about train service delay and cancellation; • Emergency messages such as station evacuation should hazardous conditions exist in

the station; • Commercial messages, such as advertisements, shall also be displayed on the display

boards of the PIS; and • Weather Bulletins.

14.2 System Requirements

a) All equipment shall be the IP based, latest version or model, tested and successfully proven in numerous railway applications.

b) Display boards shall be of Light Emitting Diodes (LED) type or better which shall be clearly viewable under any lighting conditions in the stations.

c) Two (2) set of back to back display boards shall be located on each station platform.

d) The Display boards shall be equipped with complete installation hardware for ceiling or

wall mounting.

e) All public information messages sent to the stations display boards shall originate only from the OCC.

f) At the OCC, the PIS Workstation and server shall be interfaced with the Signaling

System provided for management and control of messages input and transmission procedure.

g) The information messages from the OCC shall be sent to the stations via the MSTP

Transmission System.

h) The PIS shall allow pre-defined and ad hoc messages to be selected by the signaling operators and sent to a selected station, group of stations or to all station display boards.

i) The system software shall also provide video editing, encoding and recording functions.

j) PIS equipment shall have ISO certification ISO 9001 and SO 14000 and compliant to

ROHS, CE, UL and IEC standards.

k) A receiving or encoding facility at the OCC shall be provided to handle the processing and dispatch of commercial information such as news headlines and advertisement.

Page 163: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-62 December 2015

14.3 Technical Requirements

a) The PIS shall have a user friendly graphical Man Machine Interface (MMI) for the OCC operators to perform the required PIS operations.

b) The OCC operator shall be able to create, edit and delete user defined pre stored messages.

c) The PIS software shall allow the OCC operator to cancel messages being displayed.

d) All PIS messages, commands and options shall be programmable via PC and networkable

via serial or Ethernet connection.

e) The boards and corresponding software shall support Filipino as well as English language.

f) Time information shall also be shown on the display boards using digital format.

g) The PIS shall be capable of interfacing with the Centralized Audio Paging system at the

OCC such that simultaneous display and audio announcement of train information can be initiated at the OCC.

h) Communication port for remote monitoring shall be provided.

i) Display Boards Technical Specifications:

Screen Size Diagonal : 22 inches Display Type : LED Aspect Ratio : 16 X 9 Native Display Resolution : 1920 x 1080 Color : 24 bit true color or higher Contrast Ratio (DCR) : better than 4,000:1 Brightness : better than 700cd/m² Viewing Angle : 178 degrees WIFI ready : yes No. of HDMI Ports : 2 USB 2.0 ports : 2 With Audio capability : yes

14.4 Scope of Work

a) The Contractor shall select, design, supply, install, commission and be available if required up to the end of the Defects Notification Period a PIS for the LRT Line2 East Extension Project which meets the system performance standards and parameters discussed in this section.

b) The Contractor shall be responsible for all works, equipment and interfaces in integrating the existing PIS systems of the eleven (11) stations to the proposed Centralized PIS system at the OCC using the new PIS Workstation and servers.

Page 164: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-63 December 2015

c) The Contractor shall provide plans and drawings for the proposed PIS in the new stations.

d) The Contractor shall conduct an actual survey of the station for the exact positioning of the display boards and installation requirements.

e) The Contractor shall provide conduits, power cables, attachment hardware and UTP

cabling for powering the display boards from the Telecom UPS at the TER and connecting same to the LAN in the station.

f) The PIS to be supplied shall be designed for a minimum operational life of 10 years based

on the equipment being in continuous use with a minimum system availability of 99.99%. 15.0 Special Tools and Test Equipment

a) The Contractor shall provide sufficient number of all special tools required, enabling the employer to properly maintain and repair the supplied Telecommunications Equipment and related systems.

b) This shall include diagnostic test equipment to ascertain the functionality of all discrete pieces of specialized equipment, including embedded fault monitoring and diagnostic system, portable test equipment and shop test equipment.

c) The portable test equipment shall consist of a suitable number of pre-programmed laptop computers and standard cable connectors connectable to the equipment to be tested, allowing faults to be quickly and easily diagnosed and allow data download and analysis. Suitable test equipment, hardware and software interface shall be provided for each sub- system. Test capability should include but not limited to measurement of major system parameters.

d) The shop/laboratory test equipment shall consist of at least one set of test benches for each sub-system, whereby the equipment to be tested when removed from site can be loaded and tested onto the test bench. The tester shall allow functional simulation and fault diagnosis.

e) The Contractor shall propose the type and quantity of test equipment based upon operational analysis. This submission shall be approved by the Engineer.

f) The Contractor will be required to maintain the equipment software throughout the guarantee period and hand over the same at the end of the guarantee period. As part of the diagnostic test equipment, the Contractor shall provide the following:

• Complete operational manual, schematics, maintenance and calibration instructions

for the equipment, including printed circuit boards and microprocessors; • Spare parts and consumables; • Sets of replacement cable and connector assemblies and suitable number of interface

hardware for each piece of test equipment; and • Interface Software, including source code.

Page 165: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-64 December 2015

16.0 Spare Parts

16.1 General

a) The Contractor shall guarantee spare parts availability for not less than ten (10) years from the date of issue of Taking Over Certificate.

b) Sufficient spare parts and consumables necessary to service the Telecommunication System and all sub-systems appended to it shall be provided by the Contractor during the duration of the DNP. The Contractor shall be required to submit a complete listing of the parts to be supplied, with the following information as a minimum: • Part description; • Contractor part number; • Original Equipment Manufacturer parts number; • Quantity of each; • Unit price, CIF Employer Depot; and • Minimum guaranteed delivery time from placement of order.

16.2 Operational Spares Required After the Defects Notification Period

a) The Contractor shall provide the rates and additional items required, if any, of recommended spares for major sub-assemblies, spare parts and consumables required in the normal system operation after the Defects Notification Period.

b) The approved list of major sub-assemblies, spare parts and consumables shall be

delivered by the Contractor, as part of the supply contract. c) All sub-assemblies and spare parts shall be configured to the latest revision, including

those done during the warranty period.

d) Provision of 10% of the equipment to be installed shall be provided as spares.

Table 16.2-1 Recommended List of Spare Parts

RECOMMENDED LIST OF SPARES TO BE SUPPLIED SYSTEM ITEM

NO. QTY DESCRIPTION

1. MASTER CLOCK 1 1 Double Face 4" Ceiling Mount Clock 2 1 Single Face 4" Wall Mount Clock 3 3 Network Ethernet Switch W/ 8 Poe Ports 4 2 Power Supply Module Poe Ethernet Switch 2. APS 5 2 Platform Horn Speakers 6 2 Concourse Speakers 7 1 Power Amplifier 8 1 Workstation Pc With Software

Page 166: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-65 December 2015

RECOMMENDED LIST OF SPARES TO BE SUPPLIED SYSTEM ITEM

NO. QTY DESCRIPTION

3. CCTV 9 10 5 Mp Fixed Camera Assembly 10 2 5 Mp Ptz Dome Camera Assembly 11 2 Gb Switches (10GB) 12 1 set Media Converter 13 1 Router 14 3 8 Ch. Station Video Encoders/ Servers 4. SCADA 15 1 Di Module 16 1 Do Module 5. UPS 17 1 5 Kva Ups 220 Volts Ac With Batteries 18 1 Circuit Breakers Ups Distribution Panel 6. MSTP 19 1 MSTP Access Module 20 1 MSTP Multiplexer Module 21 10 Fiber Optic Patch Cords W/ Connectors 7. TELEPHONE SYSTEM 22 3 Ip Telephone Sets 23 1 Signal Post Telephone 8. PROTECTION DEVICES 24 1 Tvss 25 1 Telephone Line Protectors 9. STRUCTURED CABLING 26

300 METERS Utp Cat 6 Cable

27 30 Rj 45 Connectors 10. RADIO SYSTEM 28 20 350-400 Mhz Tetra Handheld Radios 29 3 350-400 Mhz Train Radios 11. PIS 30 1 42” Led Display Board 31 1 Pis Display Controller 12. TOOLS / TEST EQUIPMENT 32 1 Tetra Communication Service Monitor 33 1 Bird Wattmeter ; 0-150 Watts 34 4 Fluke Multitester 35 1 Ethernet Network Tester 36 2 Electronic Tool Kits 37 1 CCTV Diagnostic Tool

17.0 Defects Liability/ Warranty

17.1 General

a) The Contractor shall warrant that the design, materials and workmanship incorporated

and used in the supply and installation of the Telecommunication System and its

Page 167: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-66 December 2015

sub-system shall be free from defects and that the systems and its related components and apparatuses comply with their corresponding specification and/or requirements.

b) Under this warranty, the Contractor shall be responsible, at his own cost and expense (including cost of removal and installation), for the repair and/or replacement of each sub-system or parts, which, under normal use and maintenance becomes defective or inadequate in the performance of its function during the guarantee period, or during such period fails to comply with the Particular Performance Specifications and Parameters.

c) Should the removal or replacement of a failed sub-system or component cause removal or

replacement of any other sub-system or parts, such work and related cost shall be borne by the Contractor.

d) The guarantee covering any component or sub-system repaired or replaced by the

Contractor shall be renewed for a period equal to the period of the original guarantee effective as of the day when such repaired/replaced part is installed. If the failure is found to affect any other component, the renewal of the guarantee shall also be extended to cover the components or sub-system so affected, and shall start as of the date the interrelated components and sub-system function is restored.

17.2 Guarantee Period

Unless otherwise specified, the guarantee period shall be for two (2) years to commence from the date of issue of Taking Over Certificate or equal to the Defects Notification Period as defined in the Contract.

17.3 Technical Support

The Contractor shall make available experienced Maintenance Engineers and maintenance staff to provide assistance throughout the Defects Notification Period.

18.0 Operating and Maintenance Manuals

a) All manuals shall be written in the English language and all drawing drawn to SI/metric

units. Documents shall be made in well-structured manner relevant to the Telecommunications System and its Sub-systems.

b) All manuals shall be provided in electronic format, and copies of properly bound oil and

dirt resistant hard copies. The material for the hard copies shall be approved by the Engineer,

Prior to commencement of the Tests on Completion, the Contractor shall supply to the Engineer provisional operation and maintenance manuals in sufficient detail for the Employer to operate, maintain, dismantle, reassemble, adjust and repair the Plant. The Works shall not be considered to be completed for the purposes of taking over until the Engineer has received final operation and maintenance manuals in such detail, and any other manuals specified for these purposes.

Page 168: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-67 December 2015

18.1 Maintenance Manuals

a) The Maintenance Manuals shall provide all necessary detail to perform the work required, and shall include the judicious use of diagrams, drawings, photographs, illustrations, etc., as appropriate for the task at hand, including necessary safety precautions. Detailed maintenance and troubleshooting procedures and test and repair procedures shall be provided for all electronic assemblies and circuit boards. Manuals shall identify all tools (special and standard) needed to perform the work. This listing of tools shall be provided in the section describing the discrete task being performed.

b) Scheduled Maintenance Manual shall describe all work and inspections to be performed according to pre-set time periods or operating hours. An appropriate troubleshooting guide and/or parts repair /replacement shall be provided.

18.2 Operating Manuals

The Operating Manuals shall contain all information required for the proper operation of the Telecommunication system, including all related sub-system. The operating manuals shall include general Telecommunication system familiarization material and the location, function and operation of all controls, switches, indicators, and user interfaces.

19.0 Training Requirements

19.1 General

a) The Contractor shall provide comprehensive training to the Employer’s staff in accordance with the requirements contained in this Particular Performance Specifications and Parameters and in the General Specifications.

b) Specific objectives of courses developed by the Contractor shall be discussed in conjunction with the Employer, through a process to be mutually agreed between the Engineer and the Contractor.

c) The training program shall be made in different modules covering each sub-system

comprising the Telecommunications System, structured to allow independent implementation.

d) The Contractor shall provide qualified instructors, all training materials and training

venue required to fulfill all training requirements. 19.2 Training Topic

a) Operations Training - this shall include operation and usage of the system, including basic intervention.

b) Maintenance Training - this shall provide designated staff of the Employer with the skills

to adequately operate and support the level of maintenance and repair foreseen for the Telecommunication System and supporting equipment.

Page 169: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project

Section VI-2-2 Technical Requirements Technical Specifications Page –TEL-68 December 2015

c) Engineering Staff Training - training on specific systems for a limited number of engineering staff of the Employer, in order to provide them with the basis for engineering management tasks.

19.3 Proficiency Verification

The Contractor shall devise a system and standards in assessing the proficiency of the trainees. The system and standards shall be subject to review by the Engineer. a) Operations Training - this shall include operation and usage of the system, including

basic intervention.

b) Maintenance Training - this shall provide designated staff of the Employer with the skills to adequately operate and support the level of maintenance and repair foreseen for the Telecommunication System and supporting equipment.

c) Engineering Staff Training - training on specific systems for a limited number of

engineering staff of the Employer, in order to provide them with the basis for engineering management tasks.

Page 170: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

TECHNICAL SPECIFICATIONS

OPERATIONS CONTROL CENTER LRT Line 2 Extension Project

Page 171: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Operations Control Center

Table of Contents Page

Abbreviations 1 1.0 Introduction 3 2.0 Scope of Specification for the Operation Control Center (OCC) 3 3.0 System Description and Operating Requirements 3 3.1 Existing OCC 3 3.2 OCC Requirement under Lrt Line 2 East Extension Project 5 4.0 General Technical Requirements 5 4.1 Duty Manager’s Console 6 4.2 System Console 6 4.3 Fleet Console 6 4.4 Station Console 7 4.5 Centralized Traffic Control (CTC) 7 4.6 Mimic Display Panel [Video Wall/Wide Screen Display] 8 4.7 Supervisory Control and Data Acquisition (SCADA) 9 4.8 Closed Circuit Television (CCTV) 9 4.9 Audio Paging (AP) System 9 4.10 Passenger Information Display System (PIDS) 9 4.11 Management Information Systems (MIS) 10 5.0 Equipment Requirements 10 6.0 Software Requirements 10 6.1 System Software 11 6.2 Application Software 11 7.0 Standards and Code 12 8.0 Interface Requirements 12 9.0 Installation 13 10.0 Testing and Commissioning 13 11.0 Operations and Maintenance (O&M) Manuals 14 12.0 As-Built Documentation 14 13.0 Spare Parts 14 14.0 Training 16

Page 172: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-1 December 2015

Abbreviations

AC Alternating Current ANSI American National Standards Institute AP Audio Paging BGM Back Ground Music BICSI Building Industry Consulting Standards Institute BMS Building Management System CCTV Closed Circuit Television CENELEC Comité Européen de Normalisation Électrotechnique cm Centimeter CMP Construction Management Plan CPU Central Processing Unit CTC Centralized Traffic Control DLP Digital Light Processor EIA Electronic Industries Association FACP Fire Alarm Control Panel FAT Factory Acceptance Test FCC Federal Communication Commission FDS Fire Detection System FOC Fiber Optic Cable GB Gigabits GCC General Conditions of Contract GPS Global Positioning System HD High Definition Hz Hertz IEEE Institute of Electrical and Electronics Engineers IETF Internet Engineering Task Force IMP Interface Management Plan ISO International Organization for Standardization LAN Local Area Network LCD Liquid Crystal Display LRT Light Rail Transit LRTA Light Rail Transit Authority MC Master Clock MIS Management Information System NEC National Electrical Code NEMA National Electrical Manufacturers Association NFPA National Fire Protection Association OCC Operation Control Center PABX Private Automatic Branch Exchange PCC Particular Conditions of Contract PEC Philippine Electrical Code PIDS Passenger Information Display System PPSP Particular Performance Specifications and Parameters PS Philippine Standards SAT Site Acceptance Test SCADA Supervisory Control and Data Acquisition SOP Standard Operating Procedure

Page 173: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-2 December 2015

TCP Testing and Commissioning Plan TOC Taking Over Certificate UPS Uninterrupted Power Supply V Volts VDU Visual Display Units

Page 174: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-3 December 2015

1.0 Introduction

This Particular Performance, Specifications and Parameters (PPSP) defines the Employer’s Requirements for the restoration and upgrade for the LRT Line 2 Operation Control Center (OCC), and shall be read in conjunction with other Bidding Documents. The requirements under this Specification shall be read in conjunction with the Employer’s General Specifications and Requirements, General Conditions of Contract (GCC) and Particular Conditions of Contract (PCC). All works under this section of “Employer’s Requirements” shall be carried out in full accordance with the governing codes and regulations which are part of these specifications.

2.0 Scope of Specification for the Operation Control Center (OCC)

This PPSP covers the principles and fundamental requirements for the design, manufacture, supply, Factory Acceptance Testing (FAT), shipment, delivery to site, installation, Site Acceptance Testing (SAT), commissioning and defects liability for the maintenance period of the restoration and upgrade of the LRT Line 2 OCC. This Specification covers the provision for the upgrading of Signaling and Telecommunications systems installed at the OCC and the OCC technical room. The replacement and / or additional equipment for the improvement and upgrading shall ensure the safe and efficient operation of LRT Line 2 in accordance with established Railways Standards and in conformance with the requirement of LRT similar to the existing system already installed at the OCC. The restoration and upgrade works which is to take place shall not cause any interruption or limitation to existing LRT Line 2 operations.

3.0 System Description and Operating Requirements 3.1 Existing OCC

a) The existing OCC is located at the LRT Line 2 Depot in Santolan, Pasig City, Metro

Manila, Philippines and it centralizes the following: • Control and monitoring of the Signaling System; • Radio and telecommunication; • Control and Monitoring of Traction rectifier substation equipment via the

Supervisory Control and Data Acquisition (SCADA) System; • Monitoring of Fire Detection System (FDS), Uninterrupted Power Supply

(UPS) and other station facilities; • Monitoring of Station Facilities status via Closed Circuit Television

(CCTV); and • Telecommunications systems such as Audio Paging (AP) System and Public

Information Display (PIDS) Systems.

b) The OCC Operations Room is equipped with four (4) consoles with specific functionalities as follows:

Page 175: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-4 December 2015

• Duty Manager Console The Duty Manager monitors and oversees all traffic management duties pertaining to safe and efficient railway system operations. The Duty Manager monitoring functions is undertaken through the three (3) consoles in the OCC namely: System Console, Fleet Console and Station Console.

• System Console The System Console monitors and log all event of the power supply substation and distribution system in each rectifier substations via the SCADA system. Also, incorporated in the SCADA system are selected facilities in the passenger stations, not limited to but deem necessary such as elevator, escalator, etc.

• Fleet Console The Fleet Console controls and monitor train operation along the mainline and within the depot area. The Fleet Console consists of work stations for Signaling system for monitoring and control, CCTV, and Communications such as PA systems, Radio and telephones Private Automatic Branch Exchange (PABX).

• Station Console The Station Console monitors stations subsystem, where necessary, pertaining to passenger safety, passenger movement and passenger information required.

c) Centralized Traffic Control (CTC)

The CTC enables operators to supervise, control and monitor the entire rail system from the OCC. The workstation generate a geographical representation of the transit system network with two (2) monitoring displays, one (1) for the revenue line and the other for depot area.

d) Closed Circuit Television (CCTV)

CCTV systems provided in essential areas at Line 2 Depot, Passenger Stations and Rectifier Substations for operation and security purposes. This is to enable monitoring of train and passengers, crowd control, security/surveillance and control evacuation during emergencies at the respective locations by the operation personnel.

e) Audio Paging (AP) System

The LRT Line 2 Depot and the Stations are equipped with AP systems. The OCC shall have the capability to transmit pre-recorded announcement, back ground music (BGM) and announcement via microphone to the stations and selected depot area. The AP systems shall be stand-alone operated in each station, or from the OCC by an operator via a fiber optic cable (FOC) back bone system. In the Depot and the stations, the AP systems shall include direct links from station Fire Alarm Control Panel (FACP).

f) Passenger Information Display Systems (PIDS)

Page 176: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-5 December 2015

The PIDS facilitate posting messages and information onto the PIDS messaging displays are installed in strategic positions within each station, easily visible to the passengers in all location. The PIDS primarily display information of train arrivals in the respective stations and important ‘flash report’ messages.

g) Supervisory Control and Data Acquisition (SCADA)

The SCADA system is a computer based system with a primary workstation at the OCC to provide centralized supervisory/control and monitoring of the power supply facilities, traction power supply facilities, stations electrical/mechanical systems including fire alarms, elevators, escalators, and communication alarms.

h) Mimic Display Panel

The existing Mimic system in the OCC is a visual synoptic system diagram which provide a continuous status overview of the track layouts and indicate real time location of all trains along the revenue line. At present, the Mimic system is not operational.

i) Common Equipment Requirements • Radio System

Each operating console in the OCC is equipped with a radio control console with selection of radio channels assigned to the LRT Line 2 system. All audio communication at each Console shall be recorded on to the voice recording system.

• Telephone (PABX)

Telephone sets are provided for each of the operating consoles with multi-line selection facility.

All telephone sets are connected to a centralized PABX

3.2 OCC Requirement under LRT LINE 2 East Extension Project

The scope of work under the LRT Line 2 East Extension project for the OCC shall cover the systems upgrades, rehabilitation and/or replacement of existing OCC equipment. The requirement is to achieve a fully functional OCC that seamlessly covers the operations and functions of the existing LRT Line 2 signaling, telecommunications and power supplies and the operations and equipment of the Line 2 East Extension.

4.0 General Technical Requirements

The new equipment to be provided under this Contract shall enable the update and upgrade of the existing OCC and shall be so designed to allow the control and monitoring of all necessary system and LRT Line 2 operation. The equipment upgrade/replacement shall provide seamless interfacing and integration of the existing facilities and systems, software and hardware, including the LRT Line 2 East extension systems, to completely satisfy the operational requirements. All works for the OCC shall have minimal disruption in existing LRT Line 2 operations.

Page 177: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-6 December 2015

The Contractor shall be responsible for the detailed design, supply, installation, testing and commissioning, which includes FAT, SAT and other tests deemed necessary for all systems and items to satisfy the operational conditions and requirements, including all coordination of specified tasks/works with LRT Line 2 OCC, as per their Standard Operating Procedures (SOP). On completion of the upgrade of the existing OCC, the OCC shall be capable of further expansion with minimal disruption to revenue service. The Specifications described in this document provides only an overview of the systems to be installed within the OCC, and shall not limit the design process and content. For added detailed requirements for each system in the OCC, the Contractor shall refer to the individual system’s detailed design and specifications.

4.1 Duty Manager’s Console

A new Duty Manager Console shall be provided and shall consists of at least six (6) workstations capable of displaying all facilities. The workstations shall is compose of CCTV workstation, CTC workstation, PA system workstation, PIDS workstation, SCADA workstation and control for the video wall / wide screen display. The workstation hardware shall consist of LCD monitor (22”/56 cm.), CPU – latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use.

4.2 System Console

The new System Console shall consist of at least two (2) workstation, one (1) for CTC and the other for SCADA. The workstation hardware shall consist of LCD monitor (22”/56 cm.), CPU -latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use.

4.3 Fleet Console

New Fleet Console shall consist of at least four (4) workstations for CTC, SCADA, PA, PIDS, and control for the video wall/wide screen display. The workstation hardware shall consist of LCD monitor (22”/56 cm.), CPU – latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use.

Page 178: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-7 December 2015

4.4 Station Console

New Station Console shall consist of at least four (4) workstations for SCADA, CCTV, AP and PIDS workstation.

The workstation hardware shall consist of LCD monitor (22”/56 cm.), CPU -latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use.

4.5 Centralized Traffic Control (CTC)

The existing CTC Operator Post requires upgrading and modernizing to include additional control and monitoring functions necessary for the Line 2 East Extension line, the new end of line reversing track and including the two new stations. The Contractor shall perform all works required for the CTC expansion and upgrade to all affected modules of the CTC software, consequent of the Line 2 East extension. The Contractor shall ensure that operational and functionality of the CTC system for the existing facilities are intact, with the extended line fully and seamlessly integrated. The CTC shall be configured to allow future upgrade and expansion. The Contractor shall submit, as part of detailed design, the schedule of all proposed software alterations / provisions to the Engineer for his review and acceptance. The CTC Operator facilities shall consist of a server with two (2) LCD monitors, one (1) monitor displaying the whole revenue line of LRT 2 and the other showing the depot area. In the event of complete failure of the OCC, operations shall be able to continue from local control panels located at Santolan, Cubao, Recto and the additional local control panel for Line 2 East Extension at Masinag, respectively. The CTC Local Area Network (LAN) structure shall be extended to incorporate the additional two (2) stations and their respective equipment. The CTC Operator facilities which generate geographical representation of the system network shall be modified to incorporate additional control and monitoring functions, consequential and consistent with the operational requirements of the Line 2 East Extension. The CTC geographical representation shall contain, but not limited to the following functionalities. • Capable of displaying an overview of the whole system; • Capable of displaying train identification number; and • Overview of [video wall / wide screen] of whole rail network.

The CTC shall monitor and control the status of the following signaling and train condition.

Page 179: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-8 December 2015

• Track section clear/occupied; • Route set; • Turnout positions; • Signal conditions; • Speed restriction; • Train descriptions; • Alarm conditions; and • Automatic Route Setting.

All CTC processors inclusive of memories shall not be corrupted by the loss or momentary interruption of power supply, and shall be capable of automatically restarting upon power restoration. The CTC workstation shall be connected in the UPS installed at the OCC to avoid interruption or instantaneous power loss. The CTC server shall consist of a redundant facility to avoid unnecessary downtime or shutdown. The duty and standby servers shall have priority access on the system functionality. Changeover from “duty” to “Stand-by” mode shall be automatic and can also be changed manually if required. The CTC workstation hardware shall consist of LCD monitor 22” (56cm.), CPU latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use. Two (2) monitors shall be provided for the CTC workstation, one (1) monitor shall display the revenue line and the second monitor shall display the depot area.

4.6 Mimic Display Panel [Video Wall/Wide Screen Display]

A new mimic display shall be provided and installed in the OCC which shall provide a visual signalization system diagram. The Mimic system shall provide a continuous static overview of the track layouts and shall indicate real time location of all trains along the revenue line and other area deem necessary The signaling system and catenary power shall be the default viewing, but shall be able to be changed from the Manager’s or Fleet Console for alternative displays. The Contractor shall submit a detailed methodology of how adaptation will be implemented taking into consideration the ergonomic viewing of the mimic overview panel. The new mimic display shall be composed of series of monitors with High Definition (HD) resolution video images, preferably 52” (132cm) LCD screens, seamless type indoor display, and shall have clear viewing within 15 meter distance, including 120 degrees viewing. The new mimic display/video wall shall be ergonomically designed.

Page 180: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-9 December 2015

The mimic diagram shall include a fully labelled and annotated tracks diagram of the complete LRT Line 2 and shall include equipment locations and designation together with the geographical information. This information shall include but not limited to the following: • Turnout designation; • Station Name; • Direction of travel for each segment; • Route areas and designation; and • Signal positions and numbers as aspect status.

The mimic display/video wall units shall not be less than 4 units of 52” LCD screen – HD borderless and anti-glare. The mimic display/video wall controller shall be capable to support bezel correction. The mimic display/video wall units shall be mounted at the front of the Operating Console. The mimic display/video wall units shall be managed by a software based PC with a video card capable of multiple input, multiple controller and multiple output for any grid layout configuration. The mimic display/video wall units configuration shall be capable of being expanded in the future as may be required. The mimic display/video wall display units shall be mounted for front access service.

4.7 Supervisory Control and Data Acquisition (SCADA)

SCADA workstations with LCD visual display units (VDU) shall display monitoring of the electrical distribution and traction power systems, fire alarms, elevators, escalators, and electrical/mechanical systems at passenger stations and communication alarms, etc.

4.8 Closed Circuit Television (CCTV)

Full facilities shall be provided in the OCC to meet the requirements of the CCTV systems as described in Section VI – 2 Technical Requirements.

4.9 Audio Paging (AP) System

Full facilities shall be provided in the OCC to meet the requirements of the AP systems as described in Section VI – 2 Technical Requirements.

4.10 Passenger Information Display System (PIDS)

Full facilities shall be provided in the OCC to meet the requirements of the PIDS systems as described in Section VI – 2 Technical Requirements.

Page 181: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-10 December 2015

4.11 Management Information Systems (MIS)

The Contractor shall provide a Management Information System (MIS) plan for the management reporting system for LRT Line 2. The MIS shall facilitate but will not limited to the following: • Maintenance Program; • Operations Program; • Procurement of materials; and • Inventories.

The Contractor shall be responsible for the design, supply, installation, testing and commissioning of whole MIS system.

5.0 Equipment Requirements

All system equipment to be supplied and installed for the new OCC shall be fully compatible, programmable, configurable, and interoperable with the existing system hardware equipment and software. All equipment shall be of the latest version or model, tested and service proven and backward compatible with the existing system/equipment. The Contractor shall supply commercially off-the-shelf application software, as much as possible, using the latest available version at the time of bid submission. The software and associate hardware shall be fully proven for their intended application. The workstation hardware shall consist of LCD monitor 22” (56cm.), CPU -latest generation (Quad core), i7, with minimum 4GB graphic card and 8GB RAM including optic drive (Blue ray), wired keyboard and mouse with ergonomic pad as a basic component, and other essential peripherals, as deemed necessary for more efficient workstation operation and use. Monitors to be supplied for each console shall be not less than 22” (56cm), LCD – HD anti-glare type. All workstations and equipment to be installed at the OCC shall be powered by 220V-240V AC, 60Hz. All workstation and equipment to be installed shall be time synchronized from the existing Master Clock (MC) / Global Positioning System (GPS). All workstations shall have multi password protected authorization level to prevent unauthorized access.

6.0 Software Requirements

The software shall be divided into two sections, system or fixed program software and the application software.

Page 182: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-11 December 2015

In conjunction with the upgrade of hardware at the OCC, the software shall also be upgraded to incorporate the additional control and monitoring requirements of the Line 2 East Extension line. The Contractor shall upgrade the software in accordance with the standards and functions as prescribed in this specification. The Contractor shall also submit all upgrades of software modules to the Engineer for evaluation. Back-up of all software shall be provided including maintenance computer /software and necessary equipment.

6.1 System Software

The system software shall be the latest release as updated by the system supplier. The system software shall enable automatic start-up including all self-tests, checks on hardware, memories and safety components, and shall ensure the programs and processes are executed in the correct sequence. The software shall ensure that communications with other modules/systems is established and that an alternative communication channel is verified as available.

6.2 Application Software

The application software shall be designed to meet the requirements of the enhanced OCC system. The software shall be capable of fulfilling all operating functions and parameters. The Contractor shall submit to the Employer details of the system logic to be employed, the method of configuration of the logic inclusive of software tools. The software shall be written in a well-structured format and shall be subject to rigorous testing using formal methods of both validation and verification in accordance with recognized standards. The application software shall also provide status management of the OCC system. The application software shall be reviewed by the Engineer and shall comply with the following: • The software shall be well structured, documented in detail and be capable of being

analyzed by flowcharts, state diagrams, which shall also be subject to review by the Engineer.

• The software shall be provided with all necessary manuals in order that relevant Employer’s personnel are able to understand the application software.

• The software shall be provided with the facility that all alarms shall be time and date

stamped.

Page 183: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-12 December 2015

• All software systems shall interface with the existing master clock system to ensure correct timing and calendar information.

7.0 Standards and Code

The OCC shall be designed and implemented to the latest applicable Standards and Codes of the following organizations: • American National Standards Institute (ANSI); • Electronic Industries Association (EIA); • Federal Communication Commission (FCC); • Institute of Electrical and Electronics Engineers (IEEE); • International Organization for Standardization (ISO); • National Electrical Manufacturers Association (NEMA); • National Fire Protection Association (NFPA); • Building Industry Consulting Standards Institute (BICSI); • Internet Engineering Task Force (IETF); • National Electrical Code (NEC); • Philippine Electrical Code (PEC); • Philippine Standards (PS); and • Comité Européen de Normalisation Électrotechnique (CENELEC).

8.0 Interface Requirements

The OCC shall be designed in such a way that all interfaces with all systems are considered and incorporated. The Contractor is to produce an Interface Management Plan (IMP) in association with the Engineer to fully identify all interfaces to achieve a complete operating OCC. The IMP shall include full details of the Contractor’s interface methodology and detail how they intended to interface with the existing systems equipment which is currently operating, such as Signaling, CCTV, PA/PIDS, SCADA, etc. The Contractor shall design and coordinate in detail with all disciplines where defined interface are required. The Contractor shall identify and prepare a matrix as part of the IMP of all interfaces. All system and human interface equipment, at the OCC, including workstations shall be connected to essential power supplies and UPS at the OCC. The Contractor shall closely coordinate with the Employer or its delegated representative to ensure that project implementation does not affect daily operations and that the safety and integrity of the system is not compromised. The Contractor shall provide full detailed design on how system equipment will be interfaced with existing system. The design and methodology shall be submitted to the Engineer for review and acceptance.

Page 184: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-13 December 2015

9.0 Installation

The Contractor shall prepare and submit to the Engineer a Construction Management Plan (CMP) complete with a detailed methodology on how they will install equipment and cabling, including a method statement detailing how they will ensure the continued safe operation of the existing system. The Contractor shall provide details of how to integrate the extended system with the existing network, without interruption to revenue operation of the existing system. Testing and commissioning period shall be defined in the CMP. In addition to the CMP individual detailed method statements shall be produced for the individual works to be carried out. These method statements shall include but will not be limited to the following: • What works are to be performed; • How the works are to be undertaken; • Any special requirements to enable the works to be performed; • Details of any special tools required; • How interference to the existing systems will be avoided; and • Details of all safety precautions that will be put into place before, during and after the

works are complete.

All equipment and cables shall be installed by suitable, qualified, trained and competent staff, supplied with all necessary equipment and tools. The Contractor shall interface and coordinate with the other contractors for the installation requirements of cable containment systems. The Contractor shall correctly install all cables on correctly designed and installed cable containment in an orderly and neat manner. Precautions shall be taken to ensure that cables are not damaged or insulation chafed during cable laying.

10.0 Testing and Commissioning

The Contractor shall prepare and submit to the Engineer a Testing and Commissioning Plan (TCP) complete with a detailed methodology on how they will test and commission all equipment including a method statement detailing how they will ensure the continued safe operation of the existing system. The Contractor TCP shall detail how the Contractor will develop and implement a comprehensive inspection, testing and commissioning plan which shall ensure the verification and confirmation of all equipment function and installation works in accordance to the contract requirements. The TCP shall include all Factory Acceptance Tests (FAT), installation inspections, Site Acceptance Test (SAT), integrated tests, and full integrated and functional tests. The Contractor shall demonstrate full integration of the respective systems at the OCC which shall include the integration of the existing systems to the extended systems of the extension line.

Page 185: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-14 December 2015

11.0 Operations and Maintenance (O&M) Manuals

Prior to commencement of the Tests on Completion, the Contractor shall supply to the Engineer provisional O&M manuals in sufficient detail for the Employer to operate, maintain, dismantle, reassemble, adjust and repair the equipment supplied. The Works shall not be considered to be completed for the purposes of taking over until the Engineer has received final O&M manuals in such detail, and any other manuals specified for these purposes. The O&M Manuals shall provide all necessary detail to perform the work required, and shall include diagrams, drawings, photographs, illustrations, etc., as appropriate for the task at hand, including necessary safety precautions. Detailed maintenance and troubleshooting procedures and test and repair procedures shall be provided for all electronic assemblies and circuit boards. O&M manuals shall identify all tools (special and standard) needed to perform the work. This listing of tools shall be provided in the section describing the discrete task being performed. Maintenance schedules shall be included within the O&M manuals and shall describe all works and inspections to be performed according to pre-set time periods or operating hours. An appropriate troubleshooting guide and / or parts repair / replacement shall be provided. All manuals shall be written in the English language.

12.0 As-Built Documentation

The Contractor shall prepare, and keep up-to-date, a complete set of "As-Built" records of the Line 2 East Extension Works, showing all Works as executed, the exact as-built locations, sizes and details of the work as executed. These records shall be kept on the Site for exclusive use on site. The Contractor shall issue to the Employer six(6) prints of each drawing and a copy of the electronic files. The electronic format shall be as approved by the Employer, but must allow the Employer to clearly document future changes. The Contractor shall supply to the Engineer all as-built records for review within the time frames as specified in the Contract documents. The Contractor shall supply all as-built details clearly visible and understanding to any operation and maintenance personnel. The Contractor shall obtain the agreement of the Engineer as to drawing sizes, i.e. size A0, A1, A3, A4 etc. Prior to the issue of any Taking-Over Certificates, the Contractor shall supply to the Engineer the specified numbers and types of copies of the relevant as-built documents and drawings, as approved and specified within the time frames in the Contract Documents. The Works shall be considered not completed for the purposes of taking-over until the Engineer has received all the as-built documents.

13.0 Spare Parts

The Contractor shall submit to the Engineer a list of recommended spare parts for a period of not less than five (5) years from the date of issue of Taking Over Certificate (TOC).

Page 186: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-15 December 2015

The Contractor shall guarantee the recommended spare parts availability for not less than five (5) years from the date of issue of Taking Over Certificate (TOC). Sufficient spare parts and consumables necessary to service the OCC systems and all sub-system appended to them shall be provided by the Contractor during the duration of the Defects Notification Period. The Contractor shall submit complete listings of the recommended spare parts to be supplied, with the following information formation as a minimum: • Parts descriptions; • Parts numbers; • Original Equipment Manufacturer’s details, including:

Manufacturer’s Name Manufacturer’s Address Manufacturer’s Telephone Number Manufacturer’s Fax Number Manufacturer’s Email Address Purchasing Contract Number if applicable

• Original Equipment Manufacturer’s parts number; • Recommended quantity of each part; • Unit price, CIF Employer Depot; and • Minimum guaranteed delivery time from placement of order.

Table 13.0-1 List of Spares to be Supplied During the Defects Notification Period

LIST OF SPARES TO BE SUPPLIED DURING THE DEFECTS NOTIFICATION PERIOD

SYSTEM ITEM NO.

QTY DESCRIPTION

1. Mimic Display Panel/ Video Wall Display

1 1 unit Video Wall Monitor, 52” LCD Screen, seamless type

2. MIS 2 1 set Workstation including Monitor, CPU with software application, keyboard and Mouse

One set of special tools, test equipment, jigs, fixtures and gauges required to carry out all functions described in the Maintenance and Operation Manuals, or as required by the PSPR; shall be delivered before the Issue of the Taking Over Certificate. This shall not be less than the list of equipment provided by the Contractor, along with his Bid. The Contractor may add any additional equipment required, but, at no extra cost to the Employer. The extent of supply shall include protective or carrying cases, as may be appropriate for the storage and use of each item as agreed by the Engineer.

The Contractor shall submit six copies of complete illustrated parts lists and overall "exploded views" of assemblies and sub-assemblies for all Plant. This shall include reference to all

Page 187: Rectifier and Feeder Circuit Breaker (DC Switchgear)€¦ · • The DCDB shall comply with relevant technical specifications of the Philippine Electrical Code and shall conform to

Capacity Enhancement of Mass Trackwork, E&M Systems and Transit Systems in Metro Manila, Integration with Existing Systems LRT Line 2 - East (Masinag) Extension Project ________________________________________________________________________________________________________________

Section VI-2-2 Technical Requirements Technical Specifications Page –OCC-16 December 2015

assemblies, sub-assemblies special tools, jigs, fixtures and gauges required for the operation and maintenance of the equipment by the Employer.

14.0 Training

a) The Contractor shall provide a comprehensive training program for the Employer’s training and supervisory staff as indicated in the GS. The training program using the “Train the Trainer” concept shall be of sufficient detail to enable the Employer’s staff to gain full knowledge of the system and equipment operating principles, and the associated maintenance of the system.

b) The Contractor shall employ state-of-the-art techniques such as computer-aided teaching methods to deliver subject matter. The tools used for the course shall become the property of the Employer upon completion of the training in order that further training may be given to other employees. The curriculum shall be subject to approval by the Engineer prior to any commencement of training.

c) The Contractor shall also interface with the Employer’s training department and staff. The

Contractor shall identify any exclusive training needs such as the secondment of staff to Contractor’s premises for specialized instruction.

d) All training courses and manuals to be provided by the Contractor shall be in the English

language.