refrigeration lecture 4
TRANSCRIPT
-
8/12/2019 Refrigeration Lecture 4
1/16
Refrigeration and CryogenicsMaciej Chorowski
Faculty of Mechanical and Power Engineering
-
8/12/2019 Refrigeration Lecture 4
2/16
COEFFICIENT OF PERFORMANCE
OF REFRIGERATION CYCLE The coefficient of performance is an index of
performance of a thermodynamic cycle or athermal system. Because the COP can be
greater than 1, COP is used instead of thermalefficiency. The coefficient of performance canbe used for the analysis of the following:
A refrigerator that is used to produce a refrigerationeffect only, that is, COP
ref
A heat pump in which the heating effect is produced byrejected heat COPhp
A heat recovery system in which both the refrigerationeffect and the heating effect are used at thesame time,COPhr
-
8/12/2019 Refrigeration Lecture 4
3/16
Refrigeration processes of a vapor
compression refrigerating system Evaporation. In this process, the refrigerant evaporates
at a lower temperature than that of its surroundings,absorbing its latent heat of vaporization.
Superheating. Saturated refrigerant vapor is usuallysuperheated to ensure that liquid refrigerant does notflow into the compressor.
Compression. Refrigerant is compressed to a higherpressure and temperature for condensation.
Condensation. Gaseous refrigerant is condensed toliquid form by being desuperheated, then condensed,and finally subcooled, transferring its latent heat ofcondensation to a coolant.
Throttling and expansion. The higher-pressure liquidrefrigerant is throttled to the lower evaporating pressure
and is ready for evaporation.
-
8/12/2019 Refrigeration Lecture 4
4/16
Single stage vapour compression cycle
-
8/12/2019 Refrigeration Lecture 4
5/16
Lennard-Jones potential
-
8/12/2019 Refrigeration Lecture 4
6/16
COEFFICIENT OF PERFORMANCE of
Single stage vapour compression cycle
-
8/12/2019 Refrigeration Lecture 4
7/16
Single stage vapour compression cycle
-
8/12/2019 Refrigeration Lecture 4
8/16
MULTISTAGE VAPOR COMPRESSION
SYSTEMS
Two-stage compound system with a flash cooler:
(a) schematic diagram; (b) refrigeration cycle.
-
8/12/2019 Refrigeration Lecture 4
9/16
MULTISTAGE VAPOR COMPRESSION
SYSTEMS - interstage pressureInterstage pressure is usually set so that the compression ratio at
each stage is nearly the same for higher COPs.
For a two-stage compound system, interstage pressure p i, psia
(kPa abs.), can be calculated as:
For a multistage vapor compression system with z stages, the
compression ratio Rcomfor each stage can be calculated as
where pcon condensing pressure, psia (kPa abs.)
pev
evaporating pressure, psia (kPa abs.)
-
8/12/2019 Refrigeration Lecture 4
10/16
MULTISTAGE VAPOR COMPRESSION
SYSTEMS
Heat balance of entering and leaving refrigerants in a flash cooler
and at the mixing point: (a) in the flash cooler; (b) at the mixing
point 3 before entering the second-stage impeller.
-
8/12/2019 Refrigeration Lecture 4
11/16
MULTISTAGE VAPOR COMPRESSION
SYSTEMS
Coefficient of Performance
-
8/12/2019 Refrigeration Lecture 4
12/16
THREE-STAGE COMPOUND SYSTEM WITHA TWO-STAGE FLASH COOLER
-
8/12/2019 Refrigeration Lecture 4
13/16
THREE-STAGE COMPOUND SYSTEM WITHA TWO-STAGE FLASH COOLER - COP
-
8/12/2019 Refrigeration Lecture 4
14/16
TWO-STAGE COMPOUND SYSTEM WITH
A VERTICAL INTERCOOLER (ammonia)
-
8/12/2019 Refrigeration Lecture 4
15/16
Cascade system (different refrigerants,
equipment, oil)
-
8/12/2019 Refrigeration Lecture 4
16/16
Cascade system