    REG - D Operating Manual

    Operating ManualREG-D Relay for Voltage Control

    & Transformer Monitoring

    Issue 12.02.2009/03

    Issue GB

    Version 02.2009

    Software Version

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

  • 8/7/2019 reg d

    2/3032

    REG - D

    REG - D Operating Manual

    REG-D Relay for Voltage Control &

    Transformer Monitoring

    Operating Manual

    Issue 12.02.2009

    Copyright 2009 by A. Eberle GmbH & Co. KG.

    All rights reserved.

    Published by:

    A. Eberle GmbH & Co. KG

    Aalener Strae 30/32

    90441 Nuremberg, Germany

    Tel: +49 (0) 911 / 62 81 08 - 0

    Fax No.: +49 (0) 911 / 66 66 64

    e-mail: [email protected]

    Internet: www.a-eberle.de, www.regsys.de

    The company A. Eberle GmbH & Co. KG cannot be held liable for

    any damages or losses resulting from printing errors or changes

    in this operating manual.

    Furthermore, A. Eberle GmbH & Co. KG does not assume

    responsibility for any damages and losses resulting from

    defective devices or from devices altered by the user.

  • 8/7/2019 reg d

    3/3033

    REG - D

    REG - D Operating Manual

    Table of Contents

    1 Warnings and Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    2 Scope of Delivery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    3 Technical Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    3.1 Plug-in modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    3.2 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    3.4 Block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203.4.1 Block diagram of socket connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    3.4.2 Socket connector 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.4.3 Socket connector 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    3.4.4 Socket connector 3; (Measuring voltage, auxiliary voltage) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    3.4.5 Socket connector 4; (measuring current input) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    3.4.6 Socket connector 5; (tap changing via feature T1) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    3.4.7 Socket connector 6; (analogue inputs / outputs; interfaces) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    3.4.8 Interface COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    3.5 Installation in the mounting rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    3.6 Wall-mounted housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3.6.1 Wall-mounted housing, type 30 MW, feature B02 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 373.6.2 Wall-mounted housing, type 30 MW, feature B03 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3.6.3 Control panel mounting enclosure, type 30 MW, feature B05. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    3.6.4 Control panel mounting enclosure, type 49 MW, feature B06. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    3.6.5 Wall-mounted housing, type 49 MW, feature B07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    3.5.1 19 mounting rack, feature B92. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    3.7 Pin assignment for types B05, B06 and B07 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    4 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    4.1 The front panel operator interface of the REG-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    4.1.1 Display elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 444.1.2 Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    4.1.3 Plug connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    4.2 Operating principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    4.3 Selecting the display mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    4.4 Lamp check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    4.5 Resetting fault signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    4.6 Operating the Recorder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

  • 8/7/2019 reg d

    4/3034

    REG - D

    REG - D Operating Manual

    5 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

    5.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

    5.2 Transducer mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 625.3 Recorder mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

    5.4 Statistics mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

    5.5 Paragramer mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

    5.6 Choosing the language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    5.7 Setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66

    5.8 Permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

    5.9 Time behaviour. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68

    5.10 Backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

    5.11 Tap-changer running time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

    5.12 Knx transformer mounting ratios and transformer connection . . . . . . . . . . . . . . . . . . . . . . . . . 75

    5.13 Setting the nominal current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

    5.14 Inhibit low limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

    5.15 Triggering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

    5.16 Short description of the individual limit values, the setpoint values and the permissible regulative

    deviation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82

    6 Basic Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

    6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 876.1.2 Station name. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .88

    6.1.3 Setting the time/date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89

    6.1.4 LCD contrast (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89

    6.1.5 Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90

    6.1.6 Deleting recorder data (resetting the measured value memory). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

    6.1.7 Deleting tap-change sums (resetting the tap-counter to zero). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91

    6.1.8 Actual value correction of the measuring voltage UE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

    6.1.9 Actual value correction of the measuring current IE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92

    6.2 RS-232 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 936.2.1 COM 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93

    6.2.2 COM 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94

    6.3 E-LAN (Energy-Local Area Network). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

    6.4 PAN-D voltage monitoring unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

    6.5 Status (actual ID data of the REG-D Relay for Voltage Control & Transformer Monitoring). . . . . . 99

  • 8/7/2019 reg d

    5/3035

    REG - D

    REG - D Operating Manual

    7 Parameterisation of the REG-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

    7.1 Permissible regulative deviation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

    7.2 Time behaviour (regulation behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1037.2.1 Time factor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

    7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

    7.2.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

    7.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1057.3.1 1st setpoint value . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

    7.3.2 Further setpoint values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

    7.4 Programs (parameters for parallel transformer regulation). . . . . . . . . . . . . . . . . . . . . . . . . . . 1077.4.1 Selection of the parallel programs (regulation programs) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

    7.4.2 Parameters for the parallel program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

    7.2.2 Time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1047.4.3 Current influence (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    7.4.4 LDC parameter R (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    7.4.5 LDC parameter X (line-drop compensation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

    7.5 Gradient (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    7.6 Limitation (U/I characteristic). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    7.7 < U Undervoltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

    7.8 > U Overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

    7.9 > I, < Limit (upper and lower current limits). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1127.10 Trigger inhibit high (highest limit value of the voltage). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

    7.11 High-speed switching during undervoltage/overvoltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1147.11.1 High-speed switching when undervoltage occurs (RAISE) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

    7.11.2 High-speed switching when overvoltage occurs (LOWER) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

    7.12 Relay for Voltage Control & Transformer Monitoring inhibit low when undervoltage occurs . . . 115

    7.13 Time delays (limit signals) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1157.13.1 Time Delay > U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

    7.13.2 Time delay < U . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    7.13.3 Time delay > I, < I limit value. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1167.13.4 Time delay trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    7.13.5 Time delay forward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    7.13.6 Time delay backward high-speed switching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

    7.13.7 Time delay inhibit low . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118

  • 8/7/2019 reg d

    6/3036

    REG - D

    REG - D Operating Manual

    7.14 Add-Ons (Relay behaviour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1187.14.1 Overview of the Add-Ons menus numbers 1 to 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .118

    7.14.2 Maximum time TC in operation (motor drive running time) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .120

    7.14.3 Manual/Automatic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1217.14.4 Tap-changing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .122

    7.14.5 Self-Conduction of the operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

    7.14.6 Current Display (of the Transformer) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .123

    7.14.7 LCD saver (display) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

    7.14.8 Regulator mode: large display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124

    7.14.9 Language selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125

    7.14.10 Parallel Program Activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126

    7.14.11 Up/down relay on time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126

    7.14.12 AUTO(MATIC) LOCK in the event of an E-LAN error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

    7.14.13 Setpoint adjustment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .127

    7.14.14 Creeping net breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .128

    7.14.15 Limit base (reference value) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129

    7.14.16 Setting the Relay to inhibit low if I . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

    7.14.17 Maximum tap difference (monitoring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

    7.14.18 PARAGRAMER activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131

    7.15 Transformer configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1317.15.1 Transformer configuration voltage (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .132

    7.15.2 Transformer mounting ratio for the voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134

    7.15.3 Transformer mounting current (conductor connection) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134

    7.15.4 Transformer mounting current (conversion 1 A / 5 A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135

    7.15.5 Transformer mounting ratio for the current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .137

    7.16 Input assignments (binary inputs). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138

    7.17 Relay assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139

    7.18 LED assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141

    8 Measurement Value Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143

    8.1 Setting the simulated voltage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

    8.2 Setting the simulated current. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145

    8.3 Setting the simulated phase angle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1458.4 Setting the simulated tap-change . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

    9 Parallel Operation of Transformers with REG-D . . . . . . . . . . . . . . . . . . . . . . 147

    9.1 Connection diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149

    9.2 Programs for parallel operation and their prerequisites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1519.2.1 Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .151

    9.2.2 Preparing manual activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .153

    9.2.3 Preparing automatic activation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .160

    9.3 Parallel operation using the Master-Slave-Independent (MSI) procedure . . . . . . . . . . . . . . . 1709.3.1 Trouble-shooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181

  • 8/7/2019 reg d

    7/3037

    REG - D

    REG - D Operating Manual

    10 Resistance Measuring Equipment for Tap-Changers with Resistance-Coded Tap-

    Change Signalling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184

    10.1 Error detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18510.2 Level detection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185

    10.3 Connection options. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186

    11 mA inputs, mA outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187

    11.1 Analogue inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 188

    11.2 Analogue outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198

    12 Updating the Operating Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209

    12.1 Preparing the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21012.1.1 Windows NT/2000/XP operating system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 210

    12.2 Starting the bootstrap loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211

    13 Updating Analogue Inputs, Outputs, Tap-Change Potentiometer Input. . . . . . . . . . 215

    14 Maintenance and Current Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217

    14.1 Cleaning information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217

    14.2 Changing fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218

    14.3 Changing the battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218

    14.4 REG-D current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219

    15 Storage Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220

    16 Background Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221

    16.1 Regulator mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 221

    16.2 Command variable W . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22216.2.1 Fixed command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222

    16.2.2 Variable command variable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223

    16.2.3 Current-dependent setpoint value increment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22616.3 Summary and Examples for Current Influencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230

    16.4 Regulative deviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23316.4.1 Regulative deviation Xw . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233

    16.4.2 Permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233

    16.4.3 Displaying the permissible regulative deviation Xw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234

    16.4.4 Setting the permissible regulative deviation Xwz . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234

    16.5 Monitoring extreme operation values (faults) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23516.5.1 Limit signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235

  • 8/7/2019 reg d

    8/3038

    REG - D

    REG - D Operating Manual

    16.6 Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24016.6.1 High-speed switching Add-On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .240

    16.6.2 Relay inhibit low function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .241

    16.6.3 Measuring the Creeping Net Breakdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24216.6.4 Add-On: monitoring the maximum tap-change difference . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244

    16.6.5 Add-On: monitoring the tap-changer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244

    16.7 Time behaviour of the Relay when a control command is output . . . . . . . . . . . . . . . . . . . . . . 24516.7.1 Determining the reaction delay tv . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .247

    16.7.2 Integrated time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .250

    16.7.3 Trend memory. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .251

    16.7.4 Const time program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .252

    16.7.5 Setting the time factor Ft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .257

    16.8 E-LAN (Energy Local Area Network) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258

    16.9 Voltage regulation with parallel-switched transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26216.9.1 Regulation programs for transformers switched in parallel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .263

    16.9.2 Functional principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .264

    16.9.3 Influence of the circulating current regulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .264

    16.9.4 Activation of the regulation program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .265

    16.9.5 Description of the regulation programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .266

    16.10 Nominal transformation of the measuring transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 281

    16.11 Self-conduct. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 282

    16.12 LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28216.12.1 LCD contrast. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282

    16.12.2 LCD saver. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282

    16.12.3 Background illumination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .282

    17 Definition of the Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283

    18 Symbols and their Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289

    19 Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292

    20 Notes on the Interpreter Language. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294

    21 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 295

    22 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303

  • 8/7/2019 reg d

    9/3039

    REG - D

    REG - D Operating Manual

    1 Warnings and Information

    The REG-D Relay for Voltage Control & Transformer Monitoring

    is exclusively designed for implementation in systems and

    equipment incorporating electrical energy technology on which

    only trained experts are permitted to carry out all required work.

    Experts are persons who are familiar with the installation,

    mounting, commissioning and operation of these types of

    products. Furthermore, experts have qualifications which

    comply with their field of work.

    The REG-D Relay for Voltage Control & Transformer Monitoringhas been designed and tested in accordance with all important

    electrical safety regulations and left the factory in perfect

    condition. To maintain this condition and to ensure safe

    operation, the following instructions and warnings in this

    operating manual must be observed.

    The REG-D Relay for Voltage Control & Transformer

    Monitoring has been designed to comply with IEC 10110/

    EN61010 (DIN VDE 0411), degree of protection I and was

    tested according to this standard before delivery.

    The REG-D Relay for Voltage Control & Transformer

    Monitoring must be earthed via a protective earth

    conductor. This condition is fulfilled when the Relay for

    Voltage Control & Transformer Monitoring is connected to

    an auxiliary voltage with a protective earth conductor

    (European power supply system). If the auxiliary voltage

    power supply system does not have a protective earth

    conductor, an additional connection must be established

    from the protective earth conductor terminal to earth.

    The upper limit of the permissible auxiliary voltage UAUX may

    not be exceeded, neither permanently nor for a short period

    of time.

    Before changing the fuse, separate the REG-D Relay for

    Voltage Control & Transformer Monitoring completely from

    the auxiliary voltage UAUX.

    The use of fuses other than those of the indicated type and

    rated current is prohibited.

    A REG-D Relay for Voltage Control & TransformerMonitoring which displays visible damage or clear

    malfunctioning must not be used and has to be secured

    against unintentionally being switched on.

  • 8/7/2019 reg d

    10/30310

    REG - D

    REG - D Operating Manual

    Maintenance and repair work on an opened REG-D Relay

    for Voltage Control & Transformer Monitoring may only be

    carried out by authorised experts.

    Warning signs

    Please familiarise yourself with the nominal insulation voltage of

    the Relay for Voltage Control & Transformer Monitoring before

    connecting the device.

    Ensure that the voltages are connected via a disconnecting

    mechanism, and that the current path can be short circuited ifthere is a device fault to enable problem-free device

    replacement.

    This is only required if the device, including the device housing/

    mounting rack, has to be disassembled. If the plug-in modules

    alone are removed, the short circuit plug prevents the circuits

    from being used whilst open.

    When wiring, please ensure that the conductors are either

    bound short or kept sufficiently short, so that they can neither

    come into contact with the connecting elements (plugs,terminals etc.) nor the stripped conductor ends of circuits with

    a low nominal insulation voltage. If this is not ensured, a self-

    feeding voltage may form when an error occur, turning the

    originally safe low voltage circuits (e.g. mA outputs) into ones

    that are dangerous if touched.

    !

  • 8/7/2019 reg d

    11/30311

    REG - D

    REG - D Operating Manual

    2 Scope of Delivery

    1 REG-D Relay for Voltage Control & Transformer Monitoring

    1 short-form operating manual in English

    1 operating manual in English

    1 WinREG programming and parameterisation software

    1 cable

    1 replacement fuse

  • 8/7/2019 reg d

    12/30312

    REG - D

    REG - D Operating Manual

    3 Technical Data

    3.1 Plug-in modules

    Front panel Plastic film on aluminium support

    RAL 7035 light grey

    Height 3 U (128.5 mm)

    Width 28 T (142.2 mm)

    Weight 1.5 kg

    Degree of protection

    Plug-in modules IP00

    Socket connector IP00

    Configuration according to DIN 41494 Part 5

    Plug-in connector DIN 41612

    Dimensions

    3

    U

    28 TE1 7 3 . 51 2

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

    28 MW

  • 8/7/2019 reg d

    13/30313

    REG - D

    REG - D Operating Manual

    Location of

    blade connectors

    Location of

    socket connectors

    LP-REG-REL

    LP-REG-EA

    LP-REG-NTZ

    LP-REG-CPU

    7,62

    2

    0,32

    20,32

    40,64

    4

    5,72

    142,2

    173,5

    15,24

    LP-REG-STU

    12

    1

    2

    3

    4

    5

    6

    Analogue module

    optional

    4 MW4 MW5 MW9 MW 3 MW

    d b z2

    32

    2

    1 6

    20

    24

    28

    32

    22

    26

    30

    2

    32

    d b zd b z2

    32

    2

    32

    d b zd b z

    II II I IIVVVI

    5

    6

    1

    2

    3

    4

    123456

  • 8/7/2019 reg d

    14/30314

    REG - D

    REG - D Operating Manual

    3.2 Connection diagram

    Contact load R1, R2: AC 250 V, 5 A, cos = 1,DC 250 V, 150 W

    REG-D

    * Please observe the contact load at R1 and

    R2 (see below)!

    ** The connections for I and U can be freely

    assigned via the menu.

    110 V DC 230 V AC

    20 A Switch on 5 A @ cos = 1

    5 A Hold 3 A @ cos = 0.4

    0.4 A Switch off

  • 8/7/2019 reg d

    15/30315

    REG - D

    REG - D Operating Manual

    3.3 Overview of features

    REG-D is a highly variable product.

    The operating manual must take this factor into account andprovide different descriptions for the for the various

    specifications.

    Because the features ... M2, S1... D2 ... are noted on the name

    plate of the device, but the relation to the function which it

    stands for is not always given, the complete structure of the

    device's features is listed here.

    Feature Code

    REG-D Relay for Voltage Control & Transformer

    Monitoring, 28TE, 3HE plug-in module

    Standard version, with double E-LAN interface, COM

    1, COM 2,

    16 binary inputs, 10 relay outputs plus status relays

    and

    WinREG parameterisation and programming soft-

    ware incl. connection cable

    REG-D

    Design19 plug-in module

    Wall-mounting housing (30TE) - without wiring

    Wall-mounting housing (30TE) - with wiring

    (Terminals compatible with REG 5A)

    Panel-mounting housing (30TE) with wiring

    Panel-mounting housing (49TE) with wiring

    Wall-mounting housing (49TE) with wiring

    Wall-mounting or panel-mounting housing (30/49TE)

    on request

    19 mounting rack according on request

    B01

    B02

    B03

    B05

    B06

    B07

    B91

    B92

    Power supply

    From monitoring network AC 80V ... 110V ... 185V

    AC 85V ... 110V ... 264V / DC 88V ... 220V ... 280V

    DC 18V ... 60V ... 72V

    H0

    H1

    H2

    Input current

    IEN 1A

    IEN 5A

    F1

    F2

  • 8/7/2019 reg d

    16/30316

    REG - D

    REG - D Operating Manual

    Measurement transducer display functions for net-

    work quantitiesThree-phase current with equal load

    Three-phase current with unequal load

    U measurement for overvoltage, U and I measure-

    ments for undervoltage

    Other uses of the transformer ( 2 x I, 2 x U, e.g. triple-

    wound transformer)

    M1

    M2

    M3

    M9

    Recorder functions for network quantities

    Incl. evaluation software

    WithoutWith S0S1

    Parallel operation

    without firmware for parallel operation

    with firmware for parallel operation

    K0

    K1

    Feature Code

  • 8/7/2019 reg d

    17/30317

    REG - D

    REG - D Operating Manual

    Analogue inputs and outputs

    withoutwith 2 inputs

    with 4 inputs

    with 6 inputs

    with 2 outputs

    with 4 outputs

    with 6 outputs

    with 2 inputs and 2 outputs

    with 2 inputs and 4 outputs

    with 4 inputs and 2 outputs

    Any combination on requesteach with 2 analogue inputs and outputs

    PT 100 direct input

    Tap-change potentiometer input

    Note:

    Please specify the scale if known!:

    Example:

    Channel 1:-100 ... 0 ... +100 MW

    -20 ... 0 ... +20 mA

    Channel 2:0 ... 80 ... 100 V

    4 ... 16 ... 20 mA

    Channel 3:1 ... 19 Stufen

    0 ... 20 mA

    Note:

    A total of 3 modules may be used. Pay attention

    to the TMM particularly with use of the

    transformer monitoring module!

    E00E91

    E92

    E93

    E94

    E95

    E96

    E97

    E98

    E99

    E900

    Binary inputs (freely programmable)

    E1...E8: AC/DC48..250V, E9...E16: AC/DC 10 ...

    50V (can also be used as a BCD input)

    E1...E16: AC/DC 48 ...250V (can also be used as a

    BCD input)

    E1...E16: AC/DC 10 ...50V (can also be used as a

    BCD input)

    D1

    D2

    D3

    RS485 interface (COM 3)

    withoutwith

    Note:

    COM 3 is only required for ANA-D and BIN-D!

    R0R1

    Feature Code

  • 8/7/2019 reg d

    18/30318

    REG - D

    REG - D Operating Manual

    Control system connection: Internal or external:

    without (more in Feature Group Y))with integrated connection (more in Feature Group

    XL)

    with ext. connection (REG-P/PE/PM) more in Feature

    Group Y)

    XW0XW1

    XW9

    Integrated protocol interface card

    for control connection of REG-D system

    for control connection of multiple systems

    Note: XL9 can only be combined with XZ15..XZ19

    and XZ91

    XL1

    XL9

    Type of connection:

    Copper RS 232

    RS 485 only for 2-wire operation

    Note:

    XV13 .. XV 19 can only be selected in combination

    with B02B92.

    In all other case, select the appropriate fibre optic

    cable module!

    Fibre optic cable with FSMA connection

    Glass fibre

    (wavelength 800...900 nm, range 2000 m)

    Plastic

    (wavelength 620...680 nm, range 50 m)

    Fibre optic cable with ST connection

    Glass fibre

    (wavelength 800...900 nm, range 2000 m)

    Plastic(wavelength 620...680 nm, range 50 m)

    XV10

    XV11

    XV13

    XV15

    XV17

    XV19

    Feature Code

  • 8/7/2019 reg d

    19/30319

    REG - D

    REG - D Operating Manual

    Log

    IEC60870-5-103 for ABB

    IEC60870-5-103 for Areva

    IEC60870-5-103 for SAT

    IEC60870-5-103 for Siemens (LSA/SAS)

    IEC60870-5-103 for Sprecher Automation

    IEC60870-5-103 for andere

    IEC60870-5-101 for ABB

    IEC60870-5-101 for IDS

    IEC60870-5-101 for SAT

    IEC60870-5-101 for Siemens (LSA/SAS)

    IEC60870-5-101 for others

    DNP 3.00

    LONMark

    SPABUS

    MODBUS RTU

    XZ10

    XZ11

    XZ12

    XZ13

    XZ14

    XZ90

    XZ15

    XZ17

    XZ18

    XZ19

    XZ91

    XZ20

    XZ21

    XZ22

    XZ23

    Local/remote switching using the keyboardwithout

    with

    Y0

    Y1

    Status output

    closes during fault

    opens during fault

    U0

    U1

    Operating manual

    German

    English

    FrenchSpanish

    Italian

    Russian

    G1

    G2

    G3G4

    G5

    G8

    Display text

    Same as operating manual

    German

    English

    French

    Spanish

    ItalianDutch

    Czech

    Russian

    A0

    A1

    A2

    A3

    A4

    A5A6

    A7

    A8

    Feature Code

  • 8/7/2019 reg d

    20/30320

    REG - D

    REG - D Operating Manual

    3.4 Block diagram

    3.4.1 Block diagram of socket connectors

    Feature ... D1 ...

    Option

    M2

    O

    ptionD1

    GND

    GND

    E9 . . . E12 GND

    E13 . . . E1 6 GND

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Freely programmable

    Free

    Free

    Powersupply

    AC

    orDC

    Status

    Analog

    uechannels(OptionE9x)

    InputorOutput

    LCD

    P

    LED

    RAM/ROM

    128x128DOTS

    D

    isplay

    E-LAN

    L

    E-LAN

    R

    +Module

    1

    L(+)

    L(-)

    Man./Auto

    Automatic (A/M)

    Manual (M)

    -20 ... 0 ... +20 mA

    -20 ... 0 ... +20 mA

    -20 ... 0 ... +20 mA

    -20 ... 0 ... +20 mA

    -20 ... 0 ... +20 mA

    -20 ... 0 ... +20 mA

    Lower

    Raise

    28

    32

    30

    3

    -

    +

    +

    +

    +

    +

    -

    -

    -

    -

    -

    Module2

    Module3

    4

    2

    4

    14

    16

    b

    z

    z

    b

    b

    14

    16

    26

    28

    26

    28

    z

    z

    b

    b

    z

    z

    2

    Binaryinpu

    t48...230VAC/DC

    +

    -

    +

    +

    +

    +

    +

    -

    -

    -

    -

    -

    +

    -

    +

    -

    b2

    2

    4

    4

    6

    6

    z

    b

    z

    b

    z

    8

    8

    10

    10

    12

    12

    b

    z

    b

    z

    b

    z

    b14

    14

    16

    16

    z

    b

    z

    26

    28

    30

    3

    2

    b

    b

    b

    b

    Assignment

    PinNo.

    ocketconnectorNo.

    Row

    b2

    24 z

    26 z

    Assignment

    PinNo.

    SocketconnectorNo.

    Row

    RS232

    COM

    1

    (OptionP1)

    COM

    2

    RS232

    (OptionR1)

    COM3

    RS485

    6

    8

    10

    12

    20

    22

    24

    20

    22

    24

    32

    30

    32

    30

    b

    b

    b

    b

    z

    z

    z

    z

    6

    8

    10

    12

    EA+

    EA-

    E+

    E-

    EA+

    EA-

    E+

    E-

    Tx+

    Tx-

    Rx+

    Rx-

    b

    b

    z

    z

    TxD

    RxD

    GND

    RTS

    CTS

    don't use

    b

    b

    b

    z

    z

    z

    D-Subplugconnector

    onthefrontpanel

    6

    56

    k l

    4 22

    1

    4 10 8 810

    14

    14

    16

    16

    20

    20

    22

    24

    22

    28

    30

    32

    30

    26 b

    24 z

    1Pole

    NC contact/NO contact

    32

    b b z z b b z z b z b z

    BA4

    BA3

    z

    BA2

    b

    BA1

    bz

    H A

    zbbzbz

    Assignment Pin No.

    Socket connector No.

    Row

    Binary output 250 VBinary output

    48 - 250 V(Option N2)

    6

    61

    2

    3

    4

    5

    7

    8

    9

    GND

    RI

    DTR

    CTS

    TXD

    RTS

    RXD

    DSR

    DCD

    E1

    E2

    E3

    E4

    E5

    E6

    E7

    E8

    GND

    Free

    Keyboard

    Timer

    24 b +

    E9

    +

    E10

    +E11

    +

    -

    E12

    +E13

    28 z

    +E14

    30 z

    +E15

    32 z

    +

    -

    E16

    IE1

    34

    k l

    4

    UL1

    20

    L2

    L3

    3

    Assignment Pin No.

    Socket connector No.24

    22

    R2

    R3

    R4

    R5

    R6

    R1

    IE2

    Freely programmable

    Option

    M2

    Binaryinput

    10...48VAC/DC

  • 8/7/2019 reg d

    21/30321

    REG - D

    REG - D Operating Manual

    Feature ... D2 ...

    Option

    M2

    Powersupply

    AC

    orDC

    Status

    Analoguechanne

    ls(OptionE9x)

    InputorO

    utput

    LCD

    P

    LED

    RAM/ROM

    128x128DOTS

    Display

    E-LAN

    L

    E-LAN

    R

    +Module1

    L(+)

    L(-)

    Man./Auto

    Automatic(A/M)

    Manual(M)

    -20...0...+20mA

    -20...0...+20mA

    -20...0...+20mA

    -20...0...+20mA

    -20...0...+20mA

    -20...0...+20mA

    Lower

    Raise

    28

    32

    30

    3

    -

    +

    +

    +

    +

    +

    -

    -

    -

    -

    -

    Module2

    Module3

    4

    2

    4

    14

    16

    b

    z

    z

    b

    b1

    4

    16

    26

    28

    26

    28

    z

    z

    b

    b

    z

    z

    2

    Binaryinput

    48...23

    0VAC/DC

    +

    -

    +

    +

    +

    +

    +

    -

    -

    -

    -

    -

    +

    -

    +

    -

    b 2

    2

    4

    4

    6

    6

    z

    b

    z

    b

    z

    8

    8

    10

    10

    12

    12

    b

    z

    b

    z

    b

    z

    b 14

    14

    16

    16

    18

    z

    b

    z

    z

    20

    20

    22

    22

    24

    24

    b

    z

    b

    z

    b

    z

    A

    ssignment

    PinNo.

    S

    ocketconnectorNo.

    Row

    b 2

    26b

    26z2

    8b

    Assignment

    PinNo.

    SocketconnectorNo.

    Row

    RS232

    COM

    1

    (OptionP1)

    COM

    2

    RS232

    (OptionR1)

    COM3

    RS485

    6

    8

    10

    12

    20

    22

    24

    20

    22

    24

    32

    30

    32

    30

    b

    b

    b

    b

    z

    z

    z

    z

    6

    8

    10

    12

    EA+

    EA-

    E+

    E-

    EA+

    EA-

    E+

    E-

    Tx+

    Tx-

    Rx+

    Rx-

    b

    b

    z

    z

    TxD

    RxD

    GND

    RTS

    CTS

    don'tuse

    b

    b

    b

    z

    z

    z

    D-Sub

    plugconnector

    onthefrontpanel

    6

    5 6

    42 2

    1

    410881

    014

    14

    16

    16

    20

    20

    22

    24

    22

    28

    30

    32

    30

    26b

    24z

    1Pole

    NCcontact/NOcontact

    32

    bbzzbbzzbzbz

    BA4

    BA3

    z

    BA2

    b

    BA1

    b z

    HA

    z b b z b z

    AssignmentPinNo.

    SocketconnectorNo.

    Row

    Binaryoutput250VBinaryoutput

    50V(OptionN1)

    6

    61

    2

    3

    4

    5

    7

    8

    9

    GND

    RI

    DTR

    CTS

    TXD

    RTSRXD

    DSR

    DCD

    E1

    E2

    E3

    E4

    E5

    E6

    E7

    E8

    GND

    Free

    Keyboard

    Timer

    18b

    28z

    30b

    30z

    32b

    32z

    IE1

    3 4

    4

    U L1

    20

    L2

    L3

    3

    AssignmentPinNo.

    SocketconnectorNo.24

    22

    R2

    R3

    R4

    R5

    R6

    R1

    IE2

    Freelyprogrammable

    Option

    M2

    +

    -

    E9

    +

    -

    E10

    +

    -

    E11

    +

    -

    E12

    +

    -

    E13

    +

    -

    E14

    +

    -

    E15

    +

    -

    E16

    kl kl

    OptionD2

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Free

    Free

  • 8/7/2019 reg d

    22/30322

    REG - D

    REG - D Operating Manual

    3.4.2 Socket connector 1

    Socket connector 1,

    (Binary outputs BOR1 ... R6

    BA1 ... BA4)

    3.4.2.1 Socket connector 1; (binary outputs BO

    Note)Option N2 is connected to the local-remote switch via

    the keypad (feature Y1) by default.

    R1 ... R6, BA1 ... BA4: potential free relay contacts

    Load: 250 V AC, 5 A, cos = 1,250 V DC, 150 W

    NoteThe Status binary output can be used as either an NC

    contact or an NO contact through the appropriateconfiguration of a wire jumper. The location of the wire

    jumper is shown in the diagram on page 23.

    Function Des Assignment Pin Assignment Pin

    Raise (2 contact pairs)

    1 NC contact and

    1 NO contact

    R1 Pole b2 NC contact z2

    Pole b4 NO contact z4

    Lower (2 contact

    pairs)

    1 NC contact and

    1 NO contact

    R2 Pole b8 NC contact z8

    Pole b10 NO contact z10

    Freely programmable R3 Pole b14 NO contact z14

    Freely programmable R4 Pole b16 NO contact z16

    Freely programmable R5 Pole b20 NO contact z20

    Manual/Automatic

    (switch)

    R6 Pole b22 NO contact z22

    NC contact b24

    Status Status Pole b26 NO contact z24

    Freely programmable

    Binary outputs (BO)4 relays

    BA1

    ...BA4

    Poles

    BA1...4

    z28

    NC contact

    BA1

    b30 NC contact

    BA3

    z30

    NC contact

    BA2

    b32 NC contact

    BA4

    z32

    Assignment Pin No.

    Socket connector No.

    Row

    26

    b

    24

    z

    Pole

    NC

    contact/

    NO

    contact

    Man./Auto

    Lower

    Raise

    4 22

    4 1 0 8 8 1 0 1 4 1 4 1 6 1 6 20 20 22 24 22 28 30 32 30 32

    b b z z b b z z b z b z

    BA4

    BA3

    z

    BA2

    b

    BA1

    bz

    M A

    zbb

    Free

    zbz

    Free

    Binary output 230 V

    R2 R3 R4 R5 R6R1

    Free

    StatusBinary output

    48 - 230 V(Option N2)

  • 8/7/2019 reg d

    23/30323

    REG - D

    REG - D Operating Manual

    Location of the wire jumper on terminal block 1

    Caution!Only use one function at a time!

    Either NC contact or NO contact

    To interlock a control command, the relays R1 and R2 may be

    switched as follows:

    REG-REL

    NO contact (NO) function NC contact (NC) function

    R1

    Raise

    R2

    Lower

  • 8/7/2019 reg d

    24/30324

    REG - D

    REG - D Operating Manual

    3.4.3 Socket connector 2

    Socket connector 2

    (binary inputsE1 ... E16

    3.4.3.1 Socket connector 2; (binary inputs, feature D1)

    NoteE9 ... E16 are always factory-paramaterised as a BCD

    input, when not working with feature T1. If, however, it

    will be used with feature T1, the BCD-input can beachieved by using terminal block 5 (or socket connector

    5).

    Function Des Assignment Pin Assignment PinFreely configurable

    (raise)

    E1 + b2 - z2

    Freely configurable

    (lower)

    E2 + b4 - z4

    Freely configurable

    (Inhibit Low)

    E3 + b6 - z6

    Freely configurable

    (high-speed

    switching)

    E4 + b8 - z8

    Manual / Automatic

    (M/A)

    E5 + b10 - z10

    Manual (M) E6 + b12 - z12

    Freely configurable E7 + b14 - z14

    Freely configurable E8 + b16 - z16

    Freely configurable

    (BCD1)

    E 9 + b24 - b32

    Freely configurable

    (BCD2)

    E 10 + b26 - b32

    Freely configurable

    (BCD4)

    E 11 + b28 - b32

    Freely configurable

    (BCD8)

    E 12 + b30 - b32

    Freely configurable

    (BCD10)

    E 13 + z24 - z32

    Freely configurable(BCD20)

    E 14 + z26 - z32

    Freely configurable E 15 + z28 - z32

    Negative sign for

    BCD-Code

    E 16 + z30 - z32

  • 8/7/2019 reg d

    25/30325

    REG - D

    REG - D Operating Manual

    NoteThe Relay for Voltage Control & Transformer Monitoring

    can be influenced by external signals via inputs E1 ...

    E16.

    Only inputs 5 and 6 are permanently assigned. All other

    inputs are freely configurable The factory settings are

    shown in brackets (refer to table on page 24)!

    Option D1

    GN DGN D

    E9...E12GND

    E13...E16GND

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Automatic(A/M)

    Manual(M)

    2

    Binary input 48 ... 230 V AC/DC

    + - + + + + +- - - - - + - + -

    b

    2 2 4 4 6 6

    z b z b z

    8 8 1 0 1 0 1 2 1 2

    b z b z b z b

    1 4 1 4 1 6 1 6

    z b z

    26 28 30 32

    b b b b

    24

    z

    26

    z

    E1 E2 E3 E4 E5 E6 E7 E8

    24

    b

    +E9

    +E1 0

    +E1 1

    + -E1 2

    +E1 3

    28

    z

    +E1 4

    30

    z

    +E1 5

    32

    z

    + -E1 6

    Freelyprogrammable

    Binary input 1 0 ... 48 V AC/DC

  • 8/7/2019 reg d

    26/30326

    REG - D

    REG - D Operating Manual

    Socket connector 2

    (binary inputs

    E1 ... E16

    3.4.3.2 Socket connector 2; (binary inputs, feature D2)

    NoteE9 ... E16 are always factory-paramaterised as BCD

    inputs, when not working with feature T1. However, if

    feature T1 is used, the BCD-input can be configured byusing terminal block 5 (or socket connector 5).

    Function Des Assignment Pin Assignment Pin

    Freely configurable

    (Raise)

    E1 + b2 - z2

    Freely configurable

    (Lower)

    E2 + b4 - z4

    Freely configurable

    (Inhibit Low)

    E3 + b6 - z6

    Freely configurable

    (high-speed switching)

    E4 + b8 - z8

    Manual/Automatic(M/A)

    E5 + b10 - z10

    Manual (M) E6 + b12 - z12

    Freely configurable E7 + b14 - z14

    Freely configurable E8 + b16 - z16

    Freely configurable

    (BCD1)

    E 9 + b18 - z18

    Freely configurable(BCD2) E 10 + b20 - z20

    Freely configurable

    (BCD4)

    E 11 + b22 - z22

    Freely configurable

    (BCD8)

    E 12 + b24 - z24

    Freely configurable

    (BCD10)

    E 13 + b26 - z26

    Freely configurable

    (BCD20)

    E 14 + b28 - z28

    Freely configurable E 15 + b30 - z30

    Negative sign for

    BCD-Code

    E 16 + b32 - z32

  • 8/7/2019 reg d

    27/30327

    REG - D

    REG - D Operating Manual

    NoteThe Relay for Voltage Control & Transformer Monitoring

    can be influenced by external signals via inputs E1 ...

    E16.

    Only inputs 5 and 6 are permanently assigned. All other

    inputs are freely configurable. The factory settings are

    shown in brackets (refer to table on page 26)!

    Automatic(A/M)

    Manual(M)

    2

    Binary input 48 ... 230 V AC/DC

    + - + + + + +- - - - - + - + -

    b

    2 2 4 4 6 6

    z b z b z

    8 8 1 0 1 0 1 2 1 2

    b z b z b z b

    1 4 1 4 1 6 1 6 1 8

    z b z z

    20 20 22 22 24 24

    b z b z b z

    26

    b

    26

    z

    28

    b

    E1 E2 E3 E4 E5 E6 E7 E8

    1 8

    b

    28

    z

    30

    b

    30

    z

    32

    b

    32

    z

    Freelyprogrammable

    + -

    E9+ -

    E1 0+ -

    E1 1+ -

    E1 2+ -

    E1 3+ -

    E1 4+ -

    E1 5+ -

    E1 6

    Option D2

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

    Freelyprogrammable

  • 8/7/2019 reg d

    28/30328

    REG - D

    REG - D Operating Manual

    Socket connector 3

    (measuring voltage

    UE,

    auxiliary voltage UH)

    3.4.4 Socket connector 3; (Measuring voltage, auxiliary

    voltage)

    NoteIn the standard version, the Relay for Voltage Control &

    Transformer Monitoring is supplied with only one

    voltage transformer (U1). A second voltage transformer

    (U2) can optionally be supplied that can operate either

    together with U1 in a V-circuit or when electronically

    isolated from U1. If operating only with U1, the

    measuring voltage (command variable) must always be

    connected to pins 20 and 22.

    The two voltage transformers U1 and U2 can also be

    used to regulate the triple-wound transformers.

    However, in all cases additional consultation is

    necessary.

    Function Assign-ment

    Pin

    Measuring voltage UE L1 20

    L2 22

    L3 24

    Auxiliary voltage (AC/DC) UH) L (+) 28

    N (-) 30

    Earth 32

    Power supplyAC or DC

    L(+)

    L(-)

    2 8 32 30

    !

    Assignment Pin No.

    Socket conne ctor N o.

    Row

    Option M 2

    U L1

    L2

    L3

    20 22

    !

    24

    U2U1

  • 8/7/2019 reg d

    29/30329

    REG - D

    REG - D Operating Manual

    Socket connector 4

    (input for

    measuring current IE)

    3.4.5 Socket connector 4; (measuring current input)

    NoteCurrent IE2 is only used for special applications and

    measurements in three-phase current networks (Aroncircuit) loaded according to the requirements of the user

    (feature M2).

    Command variable

    (voltage)

    L1 L2 L3

    Pin connection

    L1 L2 20 22

    L2 L3 20 22

    L1 L2 22 20

    Function Assignment Pin

    Measuring current (AC) IE1 k 6

    l 5

    Measuring current (AC) IE2 k 4

    l 3

  • 8/7/2019 reg d

    30/30330

    REG - D

    REG - D Operating Manual

    Socket connector 5

    (tap-changer)

    BCD signal display

    3.4.6 Socket connector 5; (tap changing via feature T1)

    for control voltages USt = AC/DC 48 V ... 250 V

    Input Function Assignment Pin Assignment Pin

    E17 1 (BCD) + b2 - z2

    E18 2 (BCD) + b4 - z4

    E19 4 (BCD) + b6 - z6

    E20 8 (BCD) + b8 - z8

    E21 10 (BCD) + b10 - z10

    E22 20 (BCD) + b12 - z12

    E23 Freely

    programmable

    + b14 - z14

    E24 Positive or

    negative sign of

    the display:

    Minus

    + b16 - z16

    E25 Freely

    programmable

    + b24 - b32

    E26 Freely

    programmable

    + b26 - b32

    E27 Freely

    programmable

    + b28 - b32

    E28 Freely

    programmable

    + b30 - b32

    E29 Freely

    programmable

    + z24 - z32

    E30 Freelyprogrammable

    + z26 - z32

    E31 Freely

    programmable

    + z28 - z32

    E32 Freely

    programmable

    + z30 - z32

  • 8/7/2019 reg d

    31/30331

    REG - D

    REG - D Operating Manual

    NoteFor parameterisation at a later date or for alterations,

    ensure that inputs b24 ... z32 (48 V ... 230 V) are

    designated as

    E17 ... E24 and inputs b2 ... z16 (10 V ... 48 V) asE25 ... E32. If feature T1 is included in the scope of

    delivery, the inputs are normally prepared for switching

    with BCD signals (refer to tables).

    The inputs can be used for a variety of other functions

    using setup 5 of the Relay for Voltage Control &

    Transformer Monitoring.

    If the BCD signal is only in the range 10 V ... 48 V, inputs E25 ...E30 must also be configured as BCD inputs using setup 5 or

    WinREG.

    e.g.: E25 BCD1

    E26 BCD2

    E27 BCD4

    E28 BCD8

    E29 BCD10

    E30 BCD20

    1

    2 2 4

    5

    4 6 6 8 8 1 0 1 0 1 2 1 2 1 4 1 4 1 6 1 6

    zbzb zb zb zb zb zb zb

    + - + - + - + - + - + - + - + -2 4 8 1 0 20 VZ+ VZ-

    48 ... 230 V or 10 ... 50 V

    UE: 48V . . . 230V

    2 4 3 2 2 6 3 2 2 8 3 2 3 0 3 2 2 4 3 2 2 6 3 2 2 8 3 2 3 0 3 2

    bbbb bb bb zz zz zz zz

    UE: 10V . . . 50V

    Assignment Pin No.

    Socket connector No.

    Row

    Assignment Pin No.

    Row

    BCD Tap-changer Position

    (OptionT1 )

  • 8/7/2019 reg d

    32/30332

    REG - D

    REG - D Operating Manual

    Socket connector 5

    (tap-changer)

    BCD signal display

    BCD coding

    Socket connector 5

    (tap-changer)

    BCD signal display

    For control voltages USt = AC/DC 10 V ... 48 V

    BCD input signal Relay display

    + 20 10 8 4 2 1

    0 0 0 0 0 0 0 0 0

    0 0 0 0 0 0 0 1 1

    0 0 0 0 0 0 1 0 2

    0 0 0 0 0 0 1 1 3

    0 0 0 0 0 1 0 0 4

    0 0 0 0 0 1 0 1 5

    0 0 0 0 0 1 1 0 6

    0 0 0 0 0 1 1 1 7

    0 0 0 0 1 0 0 0 8

    0 0 0 0 1 0 0 1 9

    0 0 0 1 0 0 0 0 10

    0 0 0 1 0 0 0 1 11

    0 0 0 1 0 0 1 0 12

    0 0 0 1 0 0 1 1 13

    0 0 0 1 0 1 0 0 14

    0 0 1 0 0 0 0 0 20

    0 0 1 0 0 0 0 1 21

    1 0 1 0 0 0 0 1 21

    Input BCD Pin Input BCD Pin

    E25 1 b24 E29 10 z24

    E26 2 b26 E30 20 z26

    E27 4 b28 E31 Vz+ z28

    E28 8 b30 E32 Vz - z30

    GND 1 ... 8 b32 GND 10 ... VZ - z32

  • 8/7/2019 reg d

    33/30333

    REG - D

    REG - D Operating Manual

    Socket connector 6

    (Analogue inputs AI...

    and/or

    analogue outputs

    AO ... .

    Programmable

    assignment,

    interfaces)

    3.4.7 Socket connector 6; (analogue inputs / outputs;

    interfaces)

    Function Assignment Pin Assignment PinAnalogue modules 1.1

    and 1.2

    1.1 + b2 1.2 + z2

    1.1 - b4 1.2 - z4

    E-LAN left EA + b6 right EA + z6

    left EA - b8 right EA - z8

    left E + b10 right E + z10

    left E - b12 right E - z12

    Analogue modules 2.1

    and 2.2

    2.1 + b14 2.2 + z14

    2.1 - b16 2.2 - z16

    COM 2 TxD b20 RTS z20

    RxD b22 CTS z22

    GND b24 dont use z24

    Analogue modules 3.1

    and 3.2

    3.1 + b26 3.2 + z26

    3.1 - b28 3.2 - z28

    COM 3 Tx + b30 Rx + z30

    Tx - b32 Rx - z32

    +

    -20...0

    ..

    .+20mA

    -20...0

    ..

    .+20mA

    -20...0

    ..

    .+20mA

    -20...0

    ..

    .+20mA

    -20...0

    ..

    .+20mA

    -20...0

    ..

    .+20mA

    - + + + + +- - - - -

    4 2 4 1 4 1 6

    b z z b b

    1 4 1 6 26 28 26 28

    z z b b z zb

    2

    $Socket connector No.

    Row

    Analogue channels (Option E9x)Input or output

    m od ul e 1 m od ul e 2 m od ul e 3

    Assignment Pin No.

    E-LAN

    L

    E-LAN

    R

    (Option P1 )

    COM 2

    RS232 (Optionl R1 )

    COM3

    RS485

    681 01 2202224202224 32 303230

    bbbbzzzz

    681 01 2

    EA+

    EA-

    E+

    E-

    EA+

    EA-

    E+

    E-

    Tx+

    Tx-

    Rx+

    Rx-

    bbzz

    TxD

    RxD

    GND

    RTS

    CTS

    +12V

    bbbzzz

    $Socket connector No.

    Row

    Assignment Pin No.

  • 8/7/2019 reg d

    34/30334

    REG - D

    REG - D Operating Manual

    NoteThe analogue inputs and outputs can be adjusted to the

    appropriate measuring tasks via SETUP 6, F1, F5 on the

    keypad, or far more elegantly by using WinREG.In principle, all the analogue measurement quantities (U,

    I, P, Q, S, ...) that the Relay for Voltage Control &

    Transformer Monitoring can measure can be output as

    mA values. This means the Relay for Voltage Control &

    Transformer Monitoring can be used as a cost-effective

    transducer without requiring additional space.

    In some cases an adjustment using additional

    background programs may be required. In this case we

    recommend contacting our headquarters.

    Quasi-analogue signals, e.g. tap-changing, can also be

    output as analogue values if required.

    To upgrade the Relay for Voltage Control & Transformer

    Monitoring at a later point, the input and output modules

    must be connected to the REG-CPU terminal block with

    two channels each (see Updating Analogue Inputs,

    Outputs, Tap-Change Potentiometer Input on page

    215).

  • 8/7/2019 reg d

    35/30335

    REG - D

    REG - D Operating Manual

    Interface COM 13.4.8 Interface COM 1

    Function Pin

    DCD 1

    RXD 2

    TXD 3

    DTR 4

    Signal-Ground 5

    DSR 6

    RTS 7

    CTS 8

    RI 9

    RS232

    COM 1

    6

    1 2 3 4 5

    7 8 9

    GND

    RI

    DTR

    CTS

    TXD

    RTS

    RXD

    DSR

    DCD

    D-Sub plug connectoron the front panel

  • 8/7/2019 reg d

    36/30336

    REG - D

    REG - D Operating Manual

    3.5 Installation in the mounting rack

    3.5.1 19 mounting rack, feature B92The diagrams show the main components of a REGSys

    regulation system in a 19 mounting rack.

    The number and location of the individual connection blocks

    depends on the respective system version.

    The specified dimensions must never be exceeded. Each

    mounting rack is prepared for connecting up to 2 LWL

    connections (FSMA or ST), that will be mounted if ordered.

    Caution!The mounting rack must be earthed!

    Earth it using an earthing clamp (green/yellow) and/or an

    earth strap.

    The mounting rack has 84 sections and therefore 84 n place

    numbers. A specific place number is the reference point for the

    installation of the guide and the connection element on the rear

    side of the mounting rack.

    Place numbers

    Socket connector 1 2 3 4 5 6

    Screws n n+4 n+8 n+11 n+16 n+25

    Guide n - - - - n+26

    277

    255.5

    279.5

    465

    482.6

    57.2

    (3TE

    )

    7.2

    1 0 . 3

    84 x 5,08 = 426.72

    132.5

  • 8/7/2019 reg d

    37/30337

    REG - D

    REG - D Operating Manual

    3.6 Wall-mounted housing

    3.6.1 Wall-mounted housing, type 30 MW, feature B02

    3.6.2 Wall-mounted housing, type 30 MW, feature B03

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

    A:REG-D 12:34:00

    Regler-Modus MANUELL

    1. Sollwert 100.0 % 100.0 VIstwert 1 0 1 . 0 Vzul. Regelabw. 2.0 %

    Stufenstellung 1 2

    -10 % 0 +10 %

    224

    138

    280

    21 4

    1 2 3 4 5 6 7 8 9 1 0

    3 4 3 5 3 6 3 7 3 8 3 9 40 41 4233323130292827

    L+ L- L1 L2 L3

    U Hi l fssp g. U M e sp g. S ta tu s

    1A/5A

    h he rREL1

    tieferREL2

    freiREL3

    BA1REL1/R

    BA2REL2/R

    BA3REL3/R

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

    A:REG-D 12:34:00

    Regler-Modus MANUELL

    1. Sollwert 100.0 % 100.0 VIstwert 101.0 Vzul. Regelabw. 2.0 %

    Stufenstellung 12

    -10 % 0 +10 %

    1 2 3 4 5 6 7 8 9 10

    27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42

    21 4

    224

    138

    280

  • 8/7/2019 reg d

    38/30338

    REG - D

    REG - D Operating Manual

    3.6.3 Control panel mounting enclosure, type 30 MW,

    feature B05

    3.6.4 Control panel mounting enclosure, type 49 MW,

    feature B06

    NoteThe enclosure can accommodate further REGSys

    components (REG-P, BIN-D, etc.)

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    re mote

    REG - D

    A:REG-D 12:34:00

    Regler-Modus MANUELL

    1. Sollwert 100. 0 % 100.0 VIstwert 101 .0 Vzul. Regelabw. 2.0 %

    Stufenstellung 1 2

    -10 % 0 + 10 %

    28752

    1 92

    144

    34

    35

    36

    37

    38

    39

    40

    41

    42

    33

    32

    31

    30

    29

    28

    27

    50

    51

    52

    53

    54

    55

    56

    57

    58

    49

    48

    47

    46

    45

    44

    43

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1A/5Ak

    l

    UH AC/DC

    15

    14

    13

    12

    11

    18

    19

    20

    17

    16

    21

    22

    23

    24

    25

    26

    Hand

    Auto(A/H)

    Schnell-

    Still-

    E1 ...E1 2

    progr.

    (-)

    Status

    progr.

    progr.

    EA+

    EA-

    E+

    E-E-LAN

    (L)

    BCD 1

    (-)

    Status

    NO

    NC

    U E

    schaltung

    setzung

    progr.

    progr.

    BCD 2

    BCD 4

    BCD 8

    BCD 10

    BCD 20

    VZ

    I E 1

    hher

    tiefer

    Hand/Auto

    H

    A

    1 11 111 18 Terminal designation I ... IV

    a. eberle g m bh a. eberle gmb h

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

    A:REG-D 12:34:00

    Regler-Modus MANUELL

    1. Sollwert 1 00.0 % 1 00.0 VIstwert 101.0 Vzul. Regelabw. 2 .0 %

    Stufenstellung 1 2

    -10 % 0 +10 %

    52 287

    144

    288

    34

    35

    36

    37

    38

    39

    40

    41

    42

    33

    32

    31

    30

    29

    28

    27

    50

    51

    52

    53

    54

    55

    56

    57

    58

    49

    48

    47

    46

    45

    44

    43

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    1A/5A

    k

    l

    UH AC/DC

    15

    14

    13

    12

    11

    18

    19

    20

    17

    16

    21

    22

    23

    24

    25

    26

    Hand

    Auto(A/H)

    Schnell-

    S t il l-

    E 1...E 12

    progr.

    (-)

    Status

    progr.

    progr.

    EA+

    EA-

    E+

    E-E-LAN(L)

    BCD 1

    (-)

    Status

    NO

    NC

    U E

    schaltung

    setzung

    progr.

    progr.

    BCD 2

    BCD 4

    BCD 8

    BCD 10

    BCD 20

    VZ

    I E 1

    hher

    tiefer

    Hand/Auto

    H

    A

    1 11 111 18

    Terminal designation I ... IV

  • 8/7/2019 reg d

    39/30339

    REG - D

    REG - D Operating Manual

    3.6.5 Wall-mounted housing, type 49 MW, feature B07

    NoteThe housing can accommodate further REGSys

    components (REG-P, BIN-D, etc.).

    The housing feature B07 will then, however, become

    feature B91.

    hher

    E1 R E L 6 R E L 5 R E L 4

    Still-

    setzung

    -tiefer

    Schnell-

    schaltg.

    Autom.

    (A/H)

    Hand

    frei

    frei

    E 2 E 3 E 4 E 5 E 6 E 7 E 8- - - - - - - -

    Hand/Auto

    H A frei

    frei

    BE1

    BE2

    - - - - - - - -

    GND

    BE3

    BE4

    BE5

    BE6

    BE7

    BE8

    EA+

    EA-

    E+

    E-

    E-LANREL4/R

    BA4

    1 2 3 4 5 6 7 8 9 1 0

    34 35 36 37 38 39 40 41 4233323130292827

    L+ L- L1 L2 L3

    U Hilfsspg. U M e s p g. S t at us

    1A/5A

    hherREL1

    tieferREL2

    freiREL3

    BA1REL1/R

    BA2REL2/R

    BA3REL3/R

    151413121 1 1 8 1 9 20171 6 2 1 2 2 2 3 2 4 2 5 2 6

    454443 50 51 52 5 3 5449484746 55 56 57 58

    a. eberle gmbh a. eberle gmb h

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    lo cal

    remote

    REG - D

    A:REG-D 12:34:00

    Regler-Modus MANUELL

    1. Sollwert 100.0 % 100.0 VIstwert 101.0 Vzul. Regelabw. 2 .0 %

    Stufenstellung 12

    -10 % 0 +10 %

    280

    138

    224

    1 2 3 4 5 6 7 8 9 10

    27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58

    11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

    31 0

    1 11

    111 18

  • 8/7/2019 reg d

    40/30340

    REG - D

    REG - D Operating Manual

    3.7 Pin assignment for types B05, B06 and B07

    (Standard assignment, if no other agreements have been

    reached!)

    ScrewconnectorterminalI

    No.

    1 Auxiliary voltageUH AC/DC

    2 Auxiliary voltage

    3

    4 Input voltageUE

    5 Input voltage

    6

    7 kCurrent input

    8 I

    9Status

    open during fault

    10 closed during fault

    Screwconnec

    torterminalII

    No.

    11 Input 1 Raise

    12 Input 2 Lower

    13 Input 3 Inhibit low

    14 Input 4 High-speed switching

    15 Input 5 AUTO (M/A)

    16 Input 6 MANUAL

    17 Input 7 Freely programmable

    18 Input 8 Freely programmable

    19 Ground for input terminals 11 ... 18

    20

    21

    22

    23 EA+

    E-LAN (L)

    24 EA -

    25 E+

    26 E-

  • 8/7/2019 reg d

    41/30341

    REG - D

    REG - D Operating Manual

    Screwconnecto

    rterminalIII

    No.

    27

    Raise 28

    29

    30

    31

    Lower 32

    33

    34

    35Freely programmable

    36

    37Freely programmable

    38

    39Freely programmable

    4041

    42

  • 8/7/2019 reg d

    42/30342

    REG - D

    REG - D Operating Manual

    Screwconnecto

    rterminalIV

    No.

    43

    Input tap-changer

    50 ... 230 V AC/DC

    44

    45

    46

    47

    48

    49

    50

    51

    52

    53

    54

    55

    56

    57 MANUAL

    58 AUTO

    BCD 1

    BCD 2

    BCD 4

    BCD 8

    BCD 10

    BCD 20

    VZ

    (-)

  • 8/7/2019 reg d

    43/30343

    REG - D

    REG - D Operating Manual

    4 Operation

    4.1 The front panel operator interface of the

    REG-D

    The MPK operation level (people-process-communication;

    German: Mensch-Proze-Kommunikation) of the REG-D Relay

    for Voltage Control & Transformer Monitoring is implemented as

    a membrane keypad with integrated light-emitting diodes

    (LEDs).

    COM1AUTO MENUESC

    F1

    F2

    F3

    F4

    F5

    local

    remote

    REG - D

    Function keys

    LEDs

    LCD display

    Automatic operation

    Manual (M)

    Abort

    Menu

    ReturnArrow keys

    COM 1 interface

    Label

    Information:With an appropriatetool, the insertedlabel can be removedfor labelling.

    LocalRemote

    5

    671234

    Status

  • 8/7/2019 reg d

    44/30344

    REG - D

    REG - D Operating Manual

    4.1.1 Display elements

    LCD display regulator mode

    LCD Display Recorder Mode

    Address at bus (station identification) Relay name Time

    Setpoint value

    Setpoint value

    Regulative deviation

    Backwards high-speed switching is indicated by

  • 8/7/2019 reg d

    45/30345

    REG - D

    REG - D Operating Manual

    LEDs

    All LEDs (excluding status LED) are freely programmable. The

    LEDs 5 ... 7 are assigned the functions >U, I as

    standard.

    4.1.2 Function keys

    Function keys (F1 ... F5)

    Choose the various display modes and parameterise the REG-

    D Relay for Voltage Control & Transformer Monitoring.

    AUTOMATIC operation mode

    Automatic regulation with specified parameters

    MANUAL operation mode

    Parameterise the REG-D and manually control the transformer.

    NoteChanges to the parameters are only accepted when in

    MANUAL OPERATION MODE .

    Local / Remote

    Switch between local and remote.

    Use the local/remote key to change between local and remote

    modes. The selected condition is indicated by an LED (red =

    local, green = remote).

    Local function

    Switching between MANUAL / AUTOMATIC modes and

    between raise / lower control modes is only possible via the

    keypad

    ( ).

    Remote function

    Switching between MANUAL / AUTOMATIC modes and

    between raise / lower control commands is only possible via thebinary inputs or via COM1/2.

    The local / remote function is possible from Firmware version

    1.97.

    Status green

    > U Voltage limit U exceeded red

    < U Voltage limit U not reached red

    > I Current limit I exceeded red

    F1

    AUTO

    local

    remote

  • 8/7/2019 reg d

    46/30346

    REG - D

    REG - D Operating Manual

    ESC (Abort)

    Return back to the display mode from the SETUP menus.

    NoteChanges to parameters only become effective after

    confirming with RETURN .

    Measurement value simulation

    Raise or lower the simulated measurement value with the arrow

    keys during the internal measuring value simulation (see page

    143).

    NoteThe measured values are supplied by the Relay for

    Voltage Control & Transformer Monitoring. It is not

    necessary to supply the measured values from an

    external source.

    Controlling the tap-changer

    The raise (higher voltage) and lower (reduce

    voltage) arrow keys are used to control the tap-changer, i.e. to

    make changes to the transformer mounting ratio (see page

    146).

    NoteThe arrow keys are only active when the Relay for

    Voltage Control & Transformer Monitoring is in

    MANUAL OPERATION MODE .

    MENU

    Switch between the various display modes and the SETUP

    menus of the REG-D Relay for Voltage Control & Transformer

    Monitoring.

    NoteChanges to the parameters are only accepted when in

    MANUAL OPERATION MODE .

    Return

    Confirm/accept an altered parameter from the SETUP menu

    items (see page 102).

    ESC

    MENU

  • 8/7/2019 reg d

    47/30347

    REG - D

    REG - D Operating Manual

    4.1.3 Plug connection

    COM1 serial interface

    For connecting the Relay for Voltage Control & TransformerMonitoring to external devices.

    4.2 Operating principle

    The operation of the REG-D Relay for Voltage Control &

    Transformer Monitoring is completely menu-guided and is

    principally the same for each menu item in the SETUP menu.

    The following operating principles apply for setting or changing

    the regulation parameters:

    MANUAL OPERATION MODEchanges the operation mode to manual operation

    MENU Access list of operating modes

    MENU selects the menu item SETUP

    MENU can be used to scroll through the pages of the

    SETUP menu selection until the required parameter

    appears on the display.

    Select a parameter via the corresponding function key

    (F1 to F5).

    Set the value of the parameter via the function keys.

    F1 increases the value in large steps

    F2 increases the value in small steps

    F4 increases the value in small steps

    F5 decreases the value in large steps

    In some of the SETUP menus F3 has a special

    function.

    After entering a value, the changed value must be

    confirmed by pressing the RETURN key.

    Enter password (see Password request on page 91).

    Return or leave the SETUP menus using ESC (ABORT)

    COM1

    MENU

    MENU

    MENU

    F1

    F2

    F4

    F5

    F3

    ESC

  • 8/7/2019 reg d

    48/30348

    REG - D

    REG - D Operating Manual

    The SETUP menus will be automatically exited if no key is

    pressed for approx. 15 seconds.

    Once the desired parameters have been entered, checked,and confirmed with RETURN , the REG-D Relay for

    Voltage Control & Transformer Monitoring can be switched

    back into automatic operation mode using AUTOMATIC

    OPERATION MODE .

    4.3 Selecting the display mode

    After pressing the MENU key, the display modes of the

    REG-D Relay for Voltage Control & Transformer Monitoring can

    be selected.

    The following modes are available:

    Regulator mode

    Transducer mode

    Recorder mode

    Statistics mode

    ParaGramer mode

    Regulator mode The F1 key is used to select the Regulator Mode.

    The display indicates the set setpoint

    value in V (kV) and as a percentage of

    the nominal voltage, the momentary

    actual value, the value of the

    permissible regulative deviation and the

    current tap-changer position of the tap-changing transformer.

    In addition the current deviation of the

    setpoint is indicated (by a pointer) on a

    scale with a bandwidth of 10%.

    The colour of the scales pointer will change from

    transparent to solid black if the set permissible regulative

    deviation (tolerance band) is overshot or undershot.

    If required, the present value of the current may also bedisplayed.

    AUTO

    MENU

    F1

  • 8/7/2019 reg d

    49/30349

    REG - D

    REG - D Operating Manual

    NoteIf the term Actual Value is displayed in capital

    letters as ACTUAL VALUE, then the MEASUREMENT

    VALUE SIMULATION is active!(see page 143).

    Transducer

    mode

    The F2 key is used to select the Transducer

    Mode.

    When the Relay for Voltage Control & Transformer Monitoring

    carries out measurements in the Aron circuit (feature M2), a

    second transducer screen can be selected to display the

    measured values of the three-phase current networks loadedaccording to the requirements of the user.

    The second transducer screen can be selected by pressing

    either the or key.

    F2

  • 8/7/2019 reg d

    50/30350

    REG - D

    REG - D Operating Manual

    The third transducer screen may be selected by pressing either

    the or key.

    In the transducer mode, only the reactive current I sin of eachtransformer will be displayed. However, it is not possible to

    determine on the basis of this display which share of the current

    pertains to the load and which pertains to the reactive current.

    Therefore, for parallel switching it is useful to display the

    reactive current.

    The circulating active current Icirc indicates the share of the

    current that is circulating in the parallel-switched

    transformers, not the share taken up by the load.

    The quasi-analogue scale illustrates the relationship betweenthe circulating reactive current Icirc and the permissible

    circulating reactive current perm. Icirc.

    If the circulating current becomes zero, the quotient will also

    become zero and the pointer will be positioned in the middle of

    the scale.

    However, generally speaking, this ideal situation can in practice

    only then be reached when the parallel-switched transformers

    exhibit the same electrical features.

  • 8/7/2019 reg d

    51/30351

    REG - D

    REG - D Operating Manual

    Recorder mode The F3 key is used to select the Recorder Mode.

    As standard, every Relay

    for Voltage Control &Transformer Monitoring is

    equipped with a DEMO

    recorder (feature: DEMO in

    the lower left corner of the

    grid).

    Above the grid, the set

    permissible regulative

    deviation is displayed by means of two black arrows. In this

    manner, the recorder display is capable of supplying all of theinformation needed for operating the Relay for Voltage Control

    & Transformer Monitoring (see LCD Display Recorder Mode

    on page 44).

    In addition to the value of the actual voltage and the tap-

    changer position (in the lower left-hand corner), the display also

    indica