repair and maintenance history of anoud power 10 mw
DESCRIPTION
asasTRANSCRIPT
Repair and Maintenance History of
Anoud Power 10 MW
P a g e 2 | 37
Contents 1. General Product Overview ........................................................................................... 3
1.1. Gensets ............................................................................................................... 3
1.2. Model View Illustration ......................................................................................... 4
1.3. Product Description .............................................................................................. 5
1.4. Specifications ....................................................................................................... 7
1.5. Benefits & Features ............................................................................................. 8
2. Repair and Maintenance ............................................................................................... 9
2.1. Overview .............................................................................................................. 9
2.2. Fluids Maintenance .............................................................................................. 9
2.3. Repair/rebuild/replacement history ..................................................................... 10
2.3.1. Generator Set # 01 ....................................................................................... 10
2.3.2. Generator Set # 02 ....................................................................................... 11
2.3.3. Generator Set # 03 ....................................................................................... 12
2.3.4. Generator Set # 04 ....................................................................................... 14
2.3.5. Generator Set # 05 ....................................................................................... 16
2.3.6. Generator Set # 06 ....................................................................................... 17
3. Valve Data .................................................................................................................... 18
3.1. Generator Set # 01 ............................................................................................ 18
3.2. Generator Set # 02 ............................................................................................ 19
3.3. Generator Set # 03 ............................................................................................ 20
3.4. Generator Set # 04 ............................................................................................ 21
3.5. Generator Set # 05 ............................................................................................ 22
3.6. Generator Set # 06 ............................................................................................ 23
4. Operational Considerations ........................................................................................ 24
Appendix A: CAT® Maintenance Recommendations ..................................................... 26
Appendix B: CAT® Cylinder Pressure Recommendations ............................................ 32
Appendix C: CAT® Valve Stem Projection Recommendations ...................................... 34
Appendix D: Glossary of Terms ....................................................................................... 36
P a g e 3 | 37
1. General Product Overview
1.1. Gensets
Genset 1 2 3 4 5 6
Engine Serial GZN00788 GZN00789 GZN00790 GZN00794 GZN00793 GZN00792
Gen Serial PCP00553 PCP00554 PCP00555 PCP00559 PCP00558 PCP00557
Arr Number 260-3693 260-3693 260-3693 260-3693 260-3693 260-3693
Model G3520C G3520C G3520C G3520C G3520C G3520C
Rating 1,950 ekW 1,950 ekW 1,950 ekW 1,950 ekW 1,950 ekW 1,950 ekW
Full load rpm 1,500 rpm 1,500 rpm 1,500 rpm 1,500 rpm 1,500 rpm 1,500 rpm
Built Date 11-Oct-10 11-Oct-10 11-Oct-10 11-Oct-10 11-Oct-10 11-Oct-10
Tested Date 28-Oct-10 28-Oct-10 28-Oct-10 28-Oct-10 28-Oct-10 28-Oct-10
Shipped Date 11-Nov-10 11-Nov-10 11-Nov-10 11-Nov-10 11-Nov-10 11-Nov-10
Plant Lafayette Lafayette Lafayette Lafayette Lafayette Lafayette
Comissioned 4-Jun-11 4-Jun-11 4-Jun-11 4-Jun-11 4-Jun-11 4-Jun-11
Current SMU1 32,626 32,871 32,125 32,288 32,542 32,723
1 As at 14
th of June, 2015 (Sunday)
P a g e 4 | 37
1.2. Model View Illustration
The illustration above shows various typical features of G3520C Generator Set. These
illustrations do not, however, show all of the options that are available.
(1) Oil filler
(2) Engine control module
(3) Jacket water outlet
(4) Lifting eyes
(5) Aftercooler
(6) Throttle
(7) Aftercooler drains
(8) Oil filters
(9) Oil level gauge
(dipstick)
(10) Jacket water inlet
(11) Fuel inlet
(12) Fuel metering valve
(13) Air inlet
(14) Exhaust stack
(15) Oil drain
P a g e 5 | 37
1.3. Product Description
Product Description
The Generator Set consists of an engine, a generator, and a control system.
Intended Use
This Power Generator is intended to be used to generate electrical power.
Engine Description
Fuel System (Air/Fuel Ratio Control)
The fuel system includes these components:
Fuel metering valve
Engine control module (ECM)
Inlet Manifold Pressure Sensor
Load Signal
Inlet manifold temperature sensor
The fuel metering valve controls the flow of fuel to the engine. The ECM determines the
requirement for the mixture of air and fuel. The ECM sends a signal to the fuel metering valve.
The fuel metering valve controls the volume of the gas flow to the engine.
The fuel flows through the fuel metering valve into the air inlet elbow. The mixture of air and fuel
flows through the turbocharger compressor. The air/fuel mixture is cooled in the aftercooler. The
mixture enters the manifold through a throttle which is electronically controlled.
The ECM sends an electronic throttle signal to the electronic actuator. The throttle is controlled
by the actuator.
Ignition System
The engine is equipped with an electronic ignition system. The system provides dependable
firing and low maintenance. The system provides precise control of the spark and the ignition
timing for each cylinder.
The system also provides diagnostic capability that enhances troubleshooting.
The engines are equipped with protection from detonation. A detonation sensor is located
between every two cylinders. The ignition timing is retarded for a cylinder when excessive
detonation is sensed in that cylinder. If the maximum retarded position is attained and
detonation continues to occur, the ECM shuts down the engine.
P a g e 6 | 37
The engines are equipped with flame arresters. The flame arresters are located at the entrance
of each inlet port. If the engine backfires, the flame arresters prevent the fire from entering the
air/fuel mixture.
Lubrication System
The engine lubrication oil is circulated by a gear-driven pump. The oil is cooled and filtered. A
bypass valve provides unrestricted flow of lubrication oil to the engine parts if the oil filter
elements become plugged.
Cooling System
The cooling system uses a water pump. The cooling system has temperature regulators that
regulate the temperature of the coolant. The temperature depends on the application.
The turbocharged engine has a Separate Circuit Aftercooler (SCAC). The temperature depends
on the engine rating and the application.
The circuit for the aftercooler may be combined or the circuit for the aftercooler may be separate
circuits. In the combined system, a pump circulates water through both the aftercooler and oil
cooler cores. The combined system uses a thermostatic control to regulate the oil temperature.
This prevents overcooling.
Description of the Generator
The SR4B brushless generator can be used with the following loads: mixed loads of motors and
lights, SCR-controlled equipment, computer centers and petroleum drilling applications.
The generator set packages can be utilized for prime power generation or standby power
generation.
SR4B generators are utilized in three-phase full-wave excitation and regulation. The generators
are either four pole or six pole design. The generators have six lead configuration or twelve lead
configuration. The generators are capable of producing electrical power in either 50 Hz or 60 Hz
applications.
P a g e 7 | 37
1.4. Specifications
Cylinder and valve location
(A) Inlet valve
(B) Exhaust valve
Number and arrangement of cylinders ... 60 degree V-20
Valves per cylinder ... 4
Displacement ... 86 L (5263 cu in)
Bore ... 170 mm (6.7 inch)
Stroke ... 190 mm (7.5 inch)
Combustion ... Spark ignited
When the crankshaft is viewed from the flywheel end, the crankshaft rotates in the following
direction. ... Counterclockwise
Firing order
Standard rotation CCW ... 1, 2, 11, 12, 3, 4, 15, 16, 7, 8, 19, 20, 9, 10, 17, 18, 5, 6, 13, 14
Note: The front end of the engine is opposite the flywheel end of the engine. The left and the
right side of the engine are seen from the flywheel end. The number 1 cylinder is the front
cylinder on the right side. The number 2 cylinder is the front cylinder on the left side.
P a g e 8 | 37
1.5. Benefits & Features
WORLD WIDE PRODUCT SUPPORT
Cat Dealers provide extensive post sale support including maintenance and repair agreements.
Cat dealers have over 1,800 dealer branch stores operating in 200 countries.The Cat® S•O•S
program cost effectively detects internal engine component condition, even the presence of
unwanted fluids and combustion by-products.
PROVEN SYSTEM
FIELD PROVEN IN A WIDE RANGE OF APLLICATIONS WORLDWIDE
FULLY PROTYPE TESTED
CERTIFIED TORSIONAL VIBRATION ANALYSIS AVAILABLE
CAT SR4B GENERATOR
Designed to match performance and output characteristics of Caterpillar gas engines. Industry
leading mechanical and electrical design. High efficiency
CAT ELECTRONIC CONTROL SYSTEM
Simple user friendly interface and navigation. Digital monitoring, metering and protection setting.
Fully-featured power metering and protective relaying. Remote control and monitor capability
options
EMISSIONS
Meets most worldwide emissions requirements down to 0.5 g/bhp-hr Nox level without
aftertreatment
FULL RANGE OF ATTACHMENTS
Wide range of bolt-on system expansion attachments, factory designed and tested
CAT® G3520C GAS ENGINE
Robust high speed block design provides prolonged life and lower owning operationg costs.
Designed for maximum performance on low pressure pipeline natural gas. Simple open hamber
combustion system for reliability and fuel flexibility. Leading edge technology in ignition system
and air/fuel ratio control for lower emission and engine efficiency. One electronic control module
handles all engine functions: ignition, governing, air/fuel ratio control and engine protection
P a g e 9 | 37
2. Repair and Maintenance
2.1. Overview
All Caterpillar recommended standard maintenance intervals have been fully complied2. Walk-
around inspections and 1000 hr basic preventive maintenance procedures have been carried
out ever since the plant’s inception. Detailed logs of all maintenance activities are available at
Anoud Power.
2.2. Fluids Maintenance
Only ORIGINAL Caterpillar fluids have been used in refill and maintenance of gensets3. These
have been regularly monitored as per OEM recommendations, details of which are as below:
Lubricant Usage
Brand of lube oil Cat NGEO (Natural Gas Engine Oil)
Grade of Viscocity SAE 40
Approximate Refill Capacity 423 liters
Monitoring technique CAT SOS (Scheduled Oil Sampling)
Coolant Usage
Brand of coolant Water and CAT® SCA (Supplemental Coolant Additive)
Refill Capacity 344 L in Jacket Water Circuit, 47.5 L in Aftercooler Circuit
Monitoring technique CAT® Coolant Conditioner Test Kit
Grease Usage
Brand of grease CAT® Ball Bearing Grease
Refill Area Generator Bearings
2 Check Appendix A: Maintenance Interval Recommendation for CAT® G3520C
3 As per SEBU6400: CAT Gas Engine Lubricant, Fuel, and Coolant Recommendations.
Link: https://parts.cat.com/wcs-static/pdfs/SEBU6400-05-secure.pdf
P a g e 10 | 37
2.3. Repair/rebuild history
2.3.1. Generator Set # 1 -
History: Consumable Items
Component Activity Undertaken Of last change
R/H4
CAT® Recommended R/H
5 Date SMU
Engine Oil & Filters
Replaced with new 21-05-15 32,130 496 1,000 hours
Air filters Replaced with new 07-06-15 32,486 140 3,000 hours
Spark plugs Replaced with new 11-01-15 29,420 3,206 3,000 hours
History: Miscellaneous repairs/rebuilds/overhauls
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
1st Topend 15-03-14 22,669 9,957
Between 10,000 and 20,000 hours
Turbocharger 1
st ABB Certified Rebuild 10-03-13 14,674
2,453 Inspection every
8,000 hours 2
nd ABB Certified Rebuild 15-02-15 30,173
Generator Bearing
1st CAT® Certified Rebuild 15-03-14 22,669
8,292 Inspection every
10,000 hours 2
nd CAT® Certified Rebuild 31-05-14 24,334
Throttle Replaced with spare 30-03-15 31,001 1,625 As per requirement Damper CAT® Certified Rebuild 20-10-14 27,570 5,056
Inspection every 1,000 hours
Flexible Coupling
Replaced with new 15-03-14 22,669 9,957 Inspection every
1,500 hours Fuel metering
valve Repaired 20-07-14 25,441 7,185 As per requirement
Compressor bypass valve
- - - - Checked every
2,000 hours
History: Replacement of Heads
Date SMU R/H Qty Head No. Reason
15-03-14 22,669 22,669 20 All Topend Overhaul
21-09-14 26,896 4,227 1 12 Leakage
19-04-15 31,420 8,751 2 4 &18 Leakage
07-06-15 32,486 9,817 4 6,7,10, & 19 CAT® Reman head # 6
4 R/H = Running Hours = Current SMU – SMU. Current SMU is as in page 3.
5 CAT recommended R/H as per Maintenance Schedule. Refer to Appendix A. A indicates that the component is
currently maintained/rebuilt as per CAT® standards. A , on the other hand, indicates that maintenance activity is pending on that particular component.
P a g e 11 | 37
2.3.2. Generator Set # 02
History: Replacement of Consumables
Component Activity Undertaken Of last change
R/H CAT®
Recommended R/H Date SMU
Engine Oil & Filters
Replaced with new 24-05-15 32,407 464 1,000 hours
Air filters Replaced with new 07-12-14 28,823 4,048 3,000 hours
Spark plugs Replaced with new 11-01-15 29,619 3,252 3,000 hours
Miscellaneous major repairs/rebuilds/replacements
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
1st Topend 19-09-13 18,943 13,928
Between 10,000 and 20,000 hours
Turbocharger 1
st ABB Certified Rebuild 03-03-13 14,571 - Inspection every
8,000 hours 2
nd ABB Certified Rebuild 15-02-15 30,359 2,512
Generator Bearing
1st CAT® Certified Rebuild 19-09-13 18,943 13,928
Inspection every 10,000 hours
Throttle 1
st repair 20-07-14 25,278
1,928 As per
requirement 2
nd repair 15-03-15 30,943
Damper CAT® Certified Rebuild 16-01-15 29,727 3,144 Inspection every
1,000 hours Flexible
Coupling Replaced with new 01-08-14 25,844 7,027
Inspection every 1,500 hours
Fuel metering valve
- - - - As per
requirement Compressor bypass valve
- - - - Checked every
2,000 hours
Head Replacement Detail
Date SMU R/H Qty Head No. Reason
17-09-12 10,773 10,773 2 14 & 16 Water Leakage
04-11-12 11,855 11,855 1 2 (New Head) Water Leakage
20-02-13 14,333 3,560 1 16 High valve recession.
19-09-13 18,943 - 20 All T.E.O
07-12-14 28,823 9,880 1 19 leakage
14-12-14 28,980 10,037 2 5 & 13 leakage
25-01-15 29,932 10,989 1 18 leakage (used gasket)
01-02-15 30,079 11,136 1 20 leakage (new spacer plate)
22-03-15 31,100 12,157 1 10 leakage
07-06-15 32,720 13,777 1 14 leakage
P a g e 12 | 37
2.3.3. Generator Set # 3
History: Replacement of Consumables
Component Activity Undertaken Of last change
R/H CAT®
Recommended R/H Date SMU
Engine Oil & Filters
Replaced with new 10-05-15 31,380 745 1,000 hours
Air filters Replaced with new 07-12-14 28,253 3,872 3,000 hours
Spark plugs Replaced with new 01-02-15 29,512 2,613 3,000 hours
Miscellaneous repairs/rebuilds/replacements
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
1st Topend 03-12-13 20,644
8,769 Between 10,000 and 20,000 hours
2nd
Topend 23-04-14 23,356
Turbocharger 1
st ABB Certified Rebuild 20-02-13 14,419
2,339 Inspection every
8,000 hours 2
nd ABB Certified Rebuild 18-02-15 29,786
Generator Bearing
1st CAT® Certified Rebuild 21-07-13 17,729
2,339 Inspection every
10,000 hours 2nd
CAT® Certified Rebuild 28-03-14 22,927
3rd
CAT® Certified Rebuild 18-02-15 29,786
Throttle Replaced by CAT® under
warranty 05-01-12 4,854 27,271
As per requirement
Damper - - - - Inspection every
1,000 hours Flexible
Coupling Replaced with new 28-03-14 22,927 9,198
Inspection every 1,500 hours
Fuel metering valve
Replaced with spare 22-03-15 30,454
1,178 As per
requirement Old valve repaired and re-installed
19-04-15 30,947
Compressor bypass valve
Repaired 10-03-14 22,927 9,198 Checked every
2,000 hours
P a g e 13 | 37
Head Replacement Detail
Date SMU R/H Qty Head No. Reason
16-05-13 16,267 16,267 1 13 High valve recession
03-12-13 20,644 20,644 20 All Topend overhaul
17-04-14 23,356 2,712 20 All Due to water leakage
30-05-14 24,203 8,47 1 4 Due to water leakage
12-06-14 24,484 1,128 1 11 Due to water leakage
17-08-14 25,945 2,589 1 16 Due to water leakage
24-08-14 26,101 2,745 1 18 Due to water leakage
31-08-14 26,265 2,909 3 6,12,15 Due to water leakage
07-09-14 26,408 3,052 2 3,5 Due to water leakage
14-09-14 26,652 3,296 1 13 Due to water leakage
05-10-14 27,038 3,682 2 10 & 20 Due to water leakage
26-10-14 27,517 3,033 1 11 Due to water leakage
26-10-14 27,517 4,161 2 1 & 14 Due to water leakage
16-11-14 27,970 4,614 1 2 Due to water leakage
28-12-14 28,730 5,374 3 8,9,17 Due to water leakage
04-01-15 28,896 - 1 3 Head gasket replaced (external leak)
11-01-15 29,037 2,772 1 6 Due to water leakage
18-01-15 29,189 2,781 1 3 With used Gasket
18-01-15 29,189 4,986 1 4 Gasket new
08-03-15 30,153 3,888 2 12 & 15 Due to water leakage
08-03-15 30,153 4,208 1 16 with new accessories
24-05-15 31,680 8,324 1 7 Due to water leakage
P a g e 14 | 37
2.3.4. Generator Set # 04
History: Replacement of Consumables
Component Activity Undertaken Of last change
R/H CAT®
Recommended R/H Date SMU
Engine Oil & Filters
Replaced with new 08-06-15 32,148 140 1,000 hours
Air filters Replaced with new 19-04-15 31,085 1,203 3,000 hours
Spark plugs Replaced with new 30-04-15 31,309 979 3,000 hours
Miscellaneous repairs/rebuilds/replacements
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
1st Topend 07-03-14 22,262
5,819 Between 10,000 and 20,000 hours
2nd
Topend 11-09-14 26,469
Turbocharger 1
st ABB Certified Rebuild 27-12-12 13,031
2,289 Inspection every
8,000 hours 2
nd ABB Certified Rebuild 22-02-15 29,999
Generator Bearing
1st CAT® Certified Rebuild 17-02-13 13,935
5,819 Inspection every
10,000 hours 2
nd CAT® Certified Rebuild 11-09-14 26,469
Throttle Repaired 23-04-15 31,600 688 As per requirement Damper - - - -
Inspection every 1,000 hours
Flexible Coupling
Replaced with new 07-05-14 23,603 8,685 Inspection every
1,500 hours Fuel metering
valve - - - - As per requirement
Compressor bypass valve
- - - - Checked every
2,000 hours
P a g e 15 | 37
Head Replacement Detail
Date SMU R/H Qty Head No. Reason
04-11-11 3,458 3,458 2 8 & 9 Exhaust side bridge damage.
10-04-13 15,140 15,140 1 18 Water Leakage
01-05-13 15,619 15,619 1 11 Water leakage
07-03-14 22,262 - 20 All Topend Overhaul
07-09-14 26,374 4,112 1 12 Spring break
11-09-14 26,469 4,207 20 All Water Leakage
04-01-15 28,981 2,512 1 5 Water Leakage
26-04-15 31,221 4,847 3 12,14,17 Water Leakage
03-05-15 31373 4,904 2 13,06 Water Leakage
03-05-15 31,373 2,392 1 5 Water Leakage
24-05-15 31,833 5,364 1 4 Water Leakage
11-06-15 32,214 5,745 4 2,9,10,16 Water Leakage
P a g e 16 | 37
2.3.5. Generator Set # 05
History: Replacement of Consumables
Component Activity Undertaken Of last change
R/H CAT®
Recommended R/H Date SMU
Engine Oil & Filters
Replaced with new 25-03-15 30,976 1,566 1,000 hours
Air filters Replaced with new 12-07-14 28,799 3,743 3,000 hours
Spark plugs Replaced with new 10-05-15 31,934 608 3,000 hours
Miscellaneous repairs/rebuilds/replacements
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
Topend 10-01-14 21,344 11,198 Between 10,000
and 20,000 hours
Turbocharger 1
st ABB Certified Rebuild 04-02-13 13,980
2,188 Inspection every
8,000 hours 2
nd ABB Certified Rebuild
6 22-02-15 30,354
Generator Bearing
1st CAT® Certified Rebuild 24-02-13 14,430
0 Inspection every
10,000 hours 2nd
CAT® Certified Rebuild 25-12-14 29,096
3rd
CAT® Certified Rebuild 14-06-15 32,542
Throttle Replaced 16-12-13 20,969 11,573 As per
requirement Damper CAT® Certified Rebuild 25-01-15 29,784 2,758
Inspection every 1,000 hours
Flexible Coupling
Replaced with new 06-03-14 22,563 9,979 Inspection every
1,500 hours Fuel metering
valve Repaired 26-10-14 27,834 4,708
As per requirement
Compressor bypass valve
- - - - Checked every
2,000 hours
Head replacement detail
Date SMU R/H Qty Head No. Reason
06-03-13 14,623 14,623 1 8 (New Head) High valve recession.
10-01-14 21,344 21,344 20 All T.E.O
01-01-15 29,257 7,913 3 7,9,10 Leakage
11-01-15 29,471 8,127 1 11 leakage (used gasket)
08-02-15 30,095 8,751 2 4 & 20 with used Gasket
05-04-15 31,172 9,828 2 16 & 18 leakage (used gasket)
6 ABB Service Report recommended replacement of bladed shaft, which has been ordered. It will be replaced upon
arrival of consignment.
P a g e 17 | 37
2.3.6. Generator Set # 06
History: Replacement of Consumables
Component Activity Undertaken Of last change
R/H CAT®
Recommended R/H Date SMU
Engine Oil & Filters
Replaced with new 19-04-15 31,518 1,205 1,000 hours
Air filters Replaced with new 07-12-14 28,699 4,024 3,000 hours
Spark plugs Replaced with new 10-05-15 31,958 765 3,000 hours
Miscellaneous repairs/rebuilds/replacements
Component Nature of work Date & SMU R/H CAT®
Recommended R/H
Topend Overhaul
Topend 10-10-13 19,413 13,310 Between 10,000
and 20,000 hours
Turbocharger 1
st ABB Certified Rebuild 18-02-13 14,217
2,215 Inspection every
8,000 hours 2
nd ABB Certified Rebuild 01-03-15 30,508
Generator Bearing
1st CAT® Certified Rebuild 10-10-13 19,413 13,310
Inspection every 10,000 hours
Throttle 1
st repair 06-07-14 25,286
1,518 As per
requirement 2
nd repair 05-04-15 31,205
Damper CAT® Certified Rebuild 11-12-13 20,706 12,017 Inspection every
1,000 hours Flexible
Coupling
Replaced with new 06-10-13 19,462 6,138
Inspection every 1,500 hours
Replaced with new 01-09-14 26,585
Fuel metering valve
- - - - As per
requirement Compressor bypass valve
Replaced with spare 22-03-15 30,943 1,780 Checked every
2,000 hours
Head replacement detail
Date SMU R/H Qty Head No. Reason
10-10-13 19,413 19,413 20 All T.E.O
30-11-14 28,542 9,129 1 7 leakage
01-02-15 29,955 10,542 2 14 & 4 leakage
08-02-15 30,108 10,695 1 1 with used gasket
22-02-15 30,375 10,962 1 17 17 low comp pressure
22-02-15 30,375 10,962 1 13 13 water leakage.
15-03-15 30,802 11,389 1 10 leakage/used gasket
10-05-15 31,958 12,545 2 18 & 19 Leakage
P a g e 18 | 37
3. Valve Data
3.1. Generator Set # 01
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
7
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)8
1 Pushrod Side 1.03
< 2.3 250 250 – 290 Inlet Manifold 0.83
2 Pushrod Side 0.80
< 2.3 250 250 – 290 Inlet Manifold 0.90
3 Pushrod Side 0.90
< 2.3 255 250 – 290 Inlet Manifold 0.62
4 Pushrod Side 0.66
< 2.3 250 250 – 290 Inlet Manifold 0.80
5 Pushrod Side 0.70
< 2.3 260 250 – 290 Inlet Manifold 1.09
6 Pushrod Side 0.58
< 2.3 260 250 – 290 Inlet Manifold 1.04
7 Pushrod Side 0.78
< 2.3 250 250 – 290 Inlet Manifold 0.96
8 Pushrod Side 1.18
< 2.3 240 250 – 290 Inlet Manifold 0.74
9 Pushrod Side 0.67
< 2.3 250 250 – 290 Inlet Manifold 0.87
10 Pushrod Side 0.80
< 2.3 260 250 – 290 Inlet Manifold 0.64
11 Pushrod Side 1.11
< 2.3 250 250 – 290 Inlet Manifold 0.75
12 Pushrod Side 0.98
< 2.3 250 250 – 290 Inlet Manifold 1.03
13 Pushrod Side 0.68
< 2.3 250 250 – 290 Inlet Manifold 0.73
14 Pushrod Side 0.70
< 2.3 250 250 – 290 Inlet Manifold 0.90
15 Pushrod Side 0.94
< 2.3 250 250 – 290 Inlet Manifold 0.86
16 Pushrod Side 0.65
< 2.3 250 250 – 290 Inlet Manifold 0.79
17 Pushrod Side 1.05
< 2.3 260 250 – 290 Inlet Manifold 0.84
18 Pushrod Side 0.66
< 2.3 260 250 – 290 Inlet Manifold 0.54
19 Pushrod Side 0.60
< 2.3 250 250 – 290 Inlet Manifold 0.60
20 Pushrod Side 1.06
< 2.3 255 250 – 290 Inlet Manifold 0.78
7 As per SEBU7681-18: Operation and Maintenance Manual – G3500C and G3500E Generator Sets, Maintenance
Section, Valve Stem Projection – Measure/Record 8 Same as
6. Refer to Maintenance Section, Cylinder Pressure – Measure/Record
P a g e 19 | 37
3.2. Generator Set # 02
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)
1 Pushrod Side 0.56
< 2.3 250 250 – 290 Inlet Manifold 0.90
2 Pushrod Side 0.64
< 2.3 250 250 – 290 Inlet Manifold 0.88
3 Pushrod Side 0.74
< 2.3 260 250 – 290 Inlet Manifold 0.92
4 Pushrod Side 1.11
< 2.3 260 250 – 290 Inlet Manifold 0.94
5 Pushrod Side 0.65
< 2.3 250 250 – 290 Inlet Manifold 0.83
6 Pushrod Side 0.90
< 2.3 260 250 – 290 Inlet Manifold 0.68
7 Pushrod Side 0.99
< 2.3 265 250 – 290 Inlet Manifold 0.72
8 Pushrod Side 0.79
< 2.3 272 250 – 290 Inlet Manifold 0.97
9 Pushrod Side 0.95
< 2.3 255 250 – 290 Inlet Manifold 0.68
10 Pushrod Side 0.54
< 2.3 260 250 – 290 Inlet Manifold 0.87
11 Pushrod Side 0.60
< 2.3 265 250 – 290 Inlet Manifold 0.77
12 Pushrod Side 0.54
< 2.3 270 250 – 290 Inlet Manifold 0.72
13 Pushrod Side 1.02
< 2.3 256 250 – 290 Inlet Manifold 0.88
14 Pushrod Side 0.89
< 2.3 266 250 – 290 Inlet Manifold 0.58
15 Pushrod Side 0.78
< 2.3 250 250 – 290 Inlet Manifold 0.55
16 Pushrod Side 0.99
< 2.3 276 250 – 290 Inlet Manifold 0.85
17 Pushrod Side 0.90
< 2.3 255 250 – 290 Inlet Manifold 0.58
18 Pushrod Side 0.78
< 2.3 262 250 – 290 Inlet Manifold 0.66
19 Pushrod Side 0.88
< 2.3 275 250 – 290 Inlet Manifold 0.54
20 Pushrod Side 1.12
< 2.3 255 250 – 290 Inlet Manifold 0.69
P a g e 20 | 37
3.3. Generator Set # 03
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)
1 Pushrod Side 0.91
< 2.3 250 250 – 290 Inlet Manifold 1.07
2 Pushrod Side 1.10
< 2.3 258 250 – 290 Inlet Manifold 0.98
3 Pushrod Side 1.08
< 2.3 265 250 – 290 Inlet Manifold 0.90
4 Pushrod Side 0.95
< 2.3 272 250 – 290 Inlet Manifold 1.06
5 Pushrod Side 1.16
< 2.3 250 250 – 290 Inlet Manifold 0.72
6 Pushrod Side 1.18
< 2.3 259 250 – 290 Inlet Manifold 0.91
7 Pushrod Side 0.95
< 2.3 268 250 – 290 Inlet Manifold 1.02
8 Pushrod Side 0.99
< 2.3 255 250 – 290 Inlet Manifold 0.75
9 Pushrod Side 1.05
< 2.3 257 250 – 290 Inlet Manifold 0.86
10 Pushrod Side 1.01
< 2.3 259 250 – 290 Inlet Manifold 0.99
11 Pushrod Side 0.80
< 2.3 260 250 – 290 Inlet Manifold 0.74
12 Pushrod Side 1.01
< 2.3 257 250 – 290 Inlet Manifold 0.53
13 Pushrod Side 0.88
< 2.3 258 250 – 290 Inlet Manifold 0.72
14 Pushrod Side 1.17
< 2.3 251 250 – 290 Inlet Manifold 0.79
15 Pushrod Side 1.19
< 2.3 275 250 – 290 Inlet Manifold 1.02
16 Pushrod Side 0.99
< 2.3 251 250 – 290 Inlet Manifold 0.68
17 Pushrod Side 1.05
< 2.3 265 250 – 290 Inlet Manifold 0.76
18 Pushrod Side 0.65
< 2.3 250 250 – 290 Inlet Manifold 0.88
19 Pushrod Side 1.01
< 2.3 252 250 – 290 Inlet Manifold 0.95
20 Pushrod Side 1.17
< 2.3 255 250 – 290 Inlet Manifold 0.84
P a g e 21 | 37
3.4. Generator Set # 04
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)
1 Pushrod Side 0.92
< 2.3 265 250 – 290 Inlet Manifold 0.79
2 Pushrod Side 0.90
< 2.3 270 250 – 290 Inlet Manifold 0.50
3 Pushrod Side 0.73
< 2.3 255 250 – 290 Inlet Manifold 0.51
4 Pushrod Side 0.91
< 2.3 250 250 – 290 Inlet Manifold 0.79
5 Pushrod Side 0.65
< 2.3 280 250 – 290 Inlet Manifold 0.89
6 Pushrod Side 0.89
< 2.3 250 250 – 290 Inlet Manifold 0.70
7 Pushrod Side 0.50
< 2.3 265 250 – 290 Inlet Manifold 0.60
8 Pushrod Side 0.52
< 2.3 260 250 – 290 Inlet Manifold 0.68
9 Pushrod Side 0.66
< 2.3 250 250 – 290 Inlet Manifold 0.82
10 Pushrod Side 0.98
< 2.3 260 250 – 290 Inlet Manifold 0.91
11 Pushrod Side 0.90
< 2.3 250 250 – 290 Inlet Manifold 0.95
12 Pushrod Side 0.59
< 2.3 265 250 – 290 Inlet Manifold 0.81
13 Pushrod Side 0.68
< 2.3 270 250 – 290 Inlet Manifold 0.86
14 Pushrod Side 0.85
< 2.3 265 250 – 290 Inlet Manifold 1.03
15 Pushrod Side 1.05
< 2.3 250 250 – 290 Inlet Manifold 0.70
16 Pushrod Side 0.86
< 2.3 260 250 – 290 Inlet Manifold 1.02
17 Pushrod Side 0.56
< 2.3 270 250 – 290 Inlet Manifold 0.73
18 Pushrod Side 0.85
< 2.3 240 250 – 290 Inlet Manifold 0.90
19 Pushrod Side 0.80
< 2.3 265 250 – 290 Inlet Manifold 1.03
20 Pushrod Side 0.68
< 2.3 250 250 – 290 Inlet Manifold 1.02
P a g e 22 | 37
3.5. Generator Set # 05
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)
1 Pushrod Side 0.67
< 2.3 252 250 – 290 Inlet Manifold 0.71
2 Pushrod Side 0.71
< 2.3 250 250 – 290 Inlet Manifold 0.81
3 Pushrod Side 0.69
< 2.3 260 250 – 290 Inlet Manifold 0.59
4 Pushrod Side 0.59
< 2.3 250 250 – 290 Inlet Manifold 0.88
5 Pushrod Side 0.67
< 2.3 252 250 – 290 Inlet Manifold 0.90
6 Pushrod Side 0.70
< 2.3 266 250 – 290 Inlet Manifold 0.62
7 Pushrod Side 0.82
< 2.3 265 250 – 290 Inlet Manifold 0.60
8 Pushrod Side 0.88
< 2.3 272 250 – 290 Inlet Manifold 0.59
9 Pushrod Side 0.77
< 2.3 255 250 – 290 Inlet Manifold 0.63
10 Pushrod Side 0.62
< 2.3 260 250 – 290 Inlet Manifold 0.80
11 Pushrod Side 0.58
< 2.3 250 250 – 290 Inlet Manifold 0.95
12 Pushrod Side 0.72
< 2.3 265 250 – 290 Inlet Manifold 0.83
13 Pushrod Side 0.80
< 2.3 257 250 – 290 Inlet Manifold 0.72
14 Pushrod Side 0.91
< 2.3 268 250 – 290 Inlet Manifold 0.69
15 Pushrod Side 0.99
< 2.3 263 250 – 290 Inlet Manifold 0.84
16 Pushrod Side 0.81
< 2.3 273 250 – 290 Inlet Manifold 0.99
17 Pushrod Side 0.70
< 2.3 273 250 – 290 Inlet Manifold 1.02
18 Pushrod Side 0.60
< 2.3 267 250 – 290 Inlet Manifold 0.81
19 Pushrod Side 0.58
< 2.3 250 250 – 290 Inlet Manifold 0.67
20 Pushrod Side 0.70
< 2.3 250 250 – 290 Inlet Manifold 0.75
P a g e 23 | 37
3.6. Generator Set # 06
Cylinder Valve
Location
Valve Recession
(mm)
CAT® Recommended
Valve Recession (mm)
Cylinder Pressure
(psi)
CAT® Recommended cylinder pressure
(psi)
1 Pushrod Side 0.63
< 2.3 251 250 – 290 Inlet Manifold 0.52
2 Pushrod Side 0.85
< 2.3 259 250 – 290 Inlet Manifold 0.71
3 Pushrod Side 0.98
< 2.3 265 250 – 290 Inlet Manifold 0.60
4 Pushrod Side 0.70
< 2.3 268 250 – 290 Inlet Manifold 0.54
5 Pushrod Side 0.59
< 2.3 269 250 – 290 Inlet Manifold 0.52
6 Pushrod Side 0.54
< 2.3 266 250 – 290 Inlet Manifold 0.74
7 Pushrod Side 1.04
< 2.3 250 250 – 290 Inlet Manifold 0.60
8 Pushrod Side 0.85
< 2.3 255 250 – 290 Inlet Manifold 0.58
9 Pushrod Side 0.72
< 2.3 260 250 – 290 Inlet Manifold 0.55
10 Pushrod Side 0.98
< 2.3 271 250 – 290 Inlet Manifold 0.60
11 Pushrod Side 0.80
< 2.3 265 250 – 290 Inlet Manifold 0.66
12 Pushrod Side 0.80
< 2.3 252 250 – 290 Inlet Manifold 0.78
13 Pushrod Side 1.03
< 2.3 260 250 – 290 Inlet Manifold 0.66
14 Pushrod Side 0.78
< 2.3 271 250 – 290 Inlet Manifold 0.90
15 Pushrod Side 0.91
< 2.3 269 250 – 290 Inlet Manifold 0.68
16 Pushrod Side 0.55
< 2.3 269 250 – 290 Inlet Manifold 0.63
17 Pushrod Side 0.78
< 2.3 253 250 – 290 Inlet Manifold 0.60
18 Pushrod Side 0.59
< 2.3 265 250 – 290 Inlet Manifold 0.82
19 Pushrod Side 0.66
< 2.3 265 250 – 290 Inlet Manifold 0.71
20 Pushrod Side 0.82
< 2.3 275 250 – 290 Inlet Manifold 0.64
P a g e 24 | 37
4. Operational Considerations
During the course of operations at Anoud Power, a number of challenges were encountered by
ARM Operations Team which are summarily described as follows:
Cooling (Radiator) System
Cooling system of plant was designed using radiators. Radiator cooling provides a closed, self –
contained system that is both simple and practical for most installations. The system in Anoud
has saved a tremendous amount of water in its last four years of operation. In addition to
delivering savings in terms of cost of water, possibility of unscheduled downtime due to
unavailability of water was also eliminated, due to nature of this system. At the time of plant
commissioning, it was mutually agreed that the area (where the radiators are installed) will be
kept open and no construction would be made. Furthermore, planting of grass/vegetation would
also be undertaken to ensure circulation of clean, fresh air around the radiator system.
However, to comply with SSGC directives, complete waste heat recovery system was installed
around the radiators. Currently, three boilers, steam turbine and pump room have surrounded
the radiator.
Construction of WHR system has affected the radiator in following ways:
1. Supply of fresh air to radiators is now restricted.
2. Induction of cement, sand and gravel during construction has affected the internal core
of radiators, thereby affecting cooling performance.
3. Boilers are directly adjacent to the radiators. Consequently, heated air from the boilers is
directed towards the radiator intake which affects the cooling capability of radiators.
The above – mentioned factors, coupled with high ambient temperature have led to increased
coolant temperatures (above 95 C). This high temperature is the main reason of leakages of
cylinder heads, and problems encountered in throttle and compressor bypass valve.
Back Pressure and Reverse Exhaust Flow
ARM Team has observed problem of back pressure and reversing of exhaust flow (from WHR
boilers to the gensets). At the time of installation of WHR system, no proper operational or
design scheme was followed. CAT® Application and Installation Guidelines were also not
complied with. Upon ARM complaint and repeated follow-ups for a year, an operational
philosophy consisting of damper and shut – off valve was developed and implemented at site.
This problem has also contributed to failure of cylinder heads.
SSGC Weekly Curtailment
After the announcement of SSGC weekly full/partial curtailment of gas, plant was operated on
full load to meet production targets. Being connected to HESCO, this plant has always been
P a g e 25 | 37
subjected to frequent ‘hot’ shutdowns. Black shutdowns from 95% load have affected genset
mounted components such as ball-bearings, flexible coupling and damper.
Power Source of Auxiliaries
For most of the time, this plant remained the sole source of power on site. During black
shutdown due to HESCO, radiators and ventilation systems also stopped immediately. This in
turn led to sudden spikes in engine room and coolant temperatures. This high temperature has
also affected electronic components and cylinder heads.
P a g e 26 | 37
APPENDIX A:
CAT® Maintenance Recommendations9
9 Excerpted from Operation and Maintenance Manual: G3500E and G3500C Generator Sets,
Media Number: SEBU7681-18 || Publication Date: 01/06/2013 Link: https://safety.cat.com/cda/files/2450417/7/SEBU7681-15%20M.pdf
P a g e 27 | 37
Maintenance Interval Schedule - Prime
SMCS - 1000; 4450; 7500
Ensure that all safety information, warnings, and instructions are read and understood before
any operation or any maintenance procedures are performed.
An authorized operator may perform the maintenance items with daily intervals. An authorized
operator may perform the maintenance items with intervals of every week. The maintenance
that is recommended for all other maintenance intervals must be performed by an authorized
service technician or by your Cat dealer.
The user is responsible for the performance of all maintenance which includes the following
items: performing all adjustments, using proper lubricants, fluids, and filters and replacing old
components with new components due to normal wear and aging.
Failure to adhere to proper maintenance intervals and procedures may result in diminished
performance of the product and/or accelerated wear of components.
Before each consecutive interval is performed, all maintenance from the previous intervals must
be performed.
Choose the interval that occurs first in order to determine the correct maintenance interval: fuel
consumption, service hours and calendar time. Products that operate in severe operating
conditions may require more frequent maintenance.
All of the following will affect the oil change interval: operating conditions, fuel type, oil type and
size of the oil sump. Scheduled oil sampling analyzes used oil in order to determine if the oil
change interval is suitable for your specific engine.
Refer to this Operation and Maintenance Manual, "Engine Oil and Filter - Change" in order to
determine the oil change interval that is suitable for your specific engine.
To determine the maintenance intervals for the overhauls, refer to this Operation and
Maintenance Manual, "Maintenance Recommendations".
Unless other instructions are provided, perform maintenance and perform repairs under the
following conditions:
The starting system is disabled.
The engine is stopped.
The generator does not pose an electrical shock hazard.
The generator is disconnected from the load.
When Required
Battery - Recycle(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Battery - Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
P a g e 28 | 37
Battery or Battery Cable - Disconnect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Coolant Sample (Level 2) - Obtain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Fuel Metering Valve - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator - Dry(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Lead - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Set - Test(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Set Alignment - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Winding - Test(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Overhaul Considerations(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Space Heater - Test(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Stator Winding Temperature - Test(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Throttle Control Valve - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Daily
Air Tank Moisture and Sediment - Drain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Coolant Level - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Air Cleaner Service Indicator - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-
Up)
Engine Oil Level - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Fuel Filter Differential Pressure - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Fumes Disposal Filter Differential Pressure - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-
UpDKR1-
Up)
Generator Bearing Temperature - Test/Record(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-
Up)
Generator Load - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Jacket Water Heater - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Power Factor - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Voltage and Frequency - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Walk-Around Inspection(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
P a g e 29 | 37
Initial 250 Service Hours
Cylinder Pressure - Test/Record(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 250 Service Hours
Battery Electrolyte Level - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Coolant Sample (Level 1) - Obtain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Cooling System Supplemental Coolant Additive (SCA) - Test/Add(RWA1-UpGDB1-UpGHC1-
UpGHE1-UpDKR1-Up)
Engine Oil Sample - Obtain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Fumes Disposal Filter - Drain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 1000 Service Hours
Aftercooler Condensation - Drain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Alternator - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Belts - Inspect/Adjust/Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Crankcase Pressure - Measure(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Crankshaft Vibration Damper - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Crankshaft Vibration Damper - Inspect
Engine Crankcase Breather - Clean(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Oil - Change(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Oil Filter - Change(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Speed/Timing Sensor - Clean/Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Valve Lash and Bridge - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Flexible Coupling - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Gas Pressure Regulator Condensation - Drain(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-
Up)
Generator Winding Insulation - Test(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Hoses and Clamps - Inspect/Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Inlet Air System - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Radiator - Clean(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
P a g e 30 | 37
Valve Stem Projection - Measure/Record(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Water Pump - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 2000 Service Hours
Carburetor Air/Fuel Ratio - Check/Adjust(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Compressor Bypass - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Bearing - Lubricate(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Generator Set Vibration - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Stator Lead - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 3000 Service Hours
Spark Plugs - Inspect/Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 4000 Service Hours
Crankcase Blowby - Test/Record(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Cylinder Pressure - Test/Record(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Mounts - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Engine Protective Devices - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Ignition System Timing - Check/Adjust(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Starting Motor - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 8000 Service Hours
Fumes Disposal Filter Element - Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Rotating Rectifier - Check(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Turbocharger - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Between 10 000 and 20 000 Service Hours
Engine Oil Temperature Regulator - Replace(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Overhaul (Top End)(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
P a g e 31 | 37
Every 10 000 Service Hours
Generator Bearing - Inspect(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Between 22 000 and 40 000 Service Hours
Overhaul (In-Frame)(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Every 24 000 Service Hours or 3 Years
Coolant (NGEC) - Change(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
Between 45 000 and 80 000 Service Hours
Overhaul (Major)(RWA1-UpGDB1-UpGHC1-UpGHE1-UpDKR1-Up)
P a g e 32 | 37
Appendix B:
CAT® Cylinder Pressure
Recommendations10
10
Excerpted from Operation and Maintenance Manual: G3500E and G3500C Generator Sets, Media Number: SEBU7681-18 || Publication Date: 01/06/2013 Maintenance Section, Cylinder Pressure: Test/Record
P a g e 33 | 37
Cylinder Pressure
P a g e 34 | 37
Appendix C:
CAT® Valve Stem Projection
Recommendations11
11
Excerpted from Operation and Maintenance Manual: G3500E and G3500C Generator Sets, Media Number: SEBU7681-18 || Publication Date: 01/06/2013 Maintenance Section, Valve Stem Projection, Test/Record
P a g e 35 | 37
Valve Stem Projection
P a g e 36 | 37
Appendix D:
Glossary of Terms
P a g e 37 | 37
ABB Certified Rebuild
Rebuild undertaken at ABB Workshop located in Korangi Industrial Area. Parts and labor are
procured from ABB (OEM for turbochargers) hence the rebuild are covered under ABB’s
warranty policy.
CAT® Certified Rebuild
Rebuild undertaken at AESL Workshop (sole authorized dealer of CAT® in Pakistan and
Afghanistan). Parts are procured from CAT® directly (OEM for G3520C) whereas labor is CAT®
certified. Rebuilds are therefore, covered under warranty policy of CAT®.
Inspect
Inspect the components according to the instructions that are in Caterpillar reusability
publications. Refer to Guidelines for Reusable Parts and Salvage Operations, SEBF8029,
“Index of Publications on Reusability or Salvage of Used Parts”. The guidelines were developed
in order to help Caterpillar dealers and customers to avoid unnecessary expenditures. New
parts are not required if the existing parts can still be used, reconditioned, or repaired. If the
components are not in the reusability guidelines, refer to the Service Manual, “Specifications”
module.
PIP
Product Improvement Program
PSP
Product Support Program
Service Letter
Caterpillar issues service letters to its dealers to address potential issues in product. Dealer
assesses equipment condition and implements service letters, which subject to CAT® specified
conditions.
Rebuild
The component can be reconditioned in order to comply with reusability guidelines.
Replace The service life of the part is exhausted. The part may fail before the next maintenance interval. The part must be replaced with a part that meets functional specifications. The replacement part may be a new part, a CAT remanufactured part, a rebuilt part, or a used part. Some worn components may be exchanged with your Caterpillar dealer. Consult your Caterpillar dealer about repair options for your engine.
R/H
Running Hours
SMU
Service Meter Units (Miles/Hours)