TYPE OF OCCUPANCY

1. BUSINESS:

2. RESIDENTIAL:

b. Dormitories

c. Apartment Buildings

d. Lodging or Rooming Houses

3. MERCANTILE:

a.Hotel

e. Single-and- two Family Dwellings

ØCLASS A- 2,787 m2 or more

ØCLASS B- Less than 2,787 m2

ØCLASS C- 278 m2 below the street floor

Page 2: Requirements Per Occupancy

4. STORAGE:

5. INDUSTRIAL:

6. HEALTH CARE FACILITIES:

7. ASSEMBLY:

8. EDUCATIONAL OCCUPANCY:

Page 3: Requirements Per Occupancy

PORTABLE FIRE EXTINGUISHER

Required

Required

Required

Required

Required

Required

Required

Page 4: Requirements Per Occupancy

Required

Required

Required

Required

Required

Page 5: Requirements Per Occupancy

Building is 15 m or more in height

four (4) or more storey in height

four (4) or more storey in height

four (4) or more storey in height

Not required

AUTOMATIC FIRE SUPPRESSION SYSTEM

four (4) or more storey in height

ØThree (3) or more storey in height.

ØExceeding 1115 m2 in gross area.

ØBelow street floors exceeding 232 m2 use for sale , storage or handling of combustible goods and merchandise

Page 6: Requirements Per Occupancy

Every high hazard occupancy

Every high hazard occupancy

All hospitals

ØBars with live entertainmentØDance hallsØDiscothequesØAssembly occupancy with festival seating

ØWith occupant load of more 300 persons

ØBuilding is 15 m or more in height

ØBasement used as a classroom or laboratory

Page 7: Requirements Per Occupancy

STANDPIPE SYSTEM

WET

4 or more storeys in height

4 or more storeys in height

4 or more storeys in height

4 or more storeys in height

Not required

Ø4 or more storeys in height

ØExceeding 1860 m2

Ø4 or more storeys in height

ØExceeding 1860 m2

Page 8: Requirements Per Occupancy

4 or more storeys in height

4 or more storeys in height

4 or more storeys in height

Exceeding 1860 m2

Occupant load exceeding 1000 persons

Page 9: Requirements Per Occupancy

STANDPIPE SYSTEM

DRY

Not required

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or

smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

Page 10: Requirements Per Occupancy

All buildings with required enclosed stairway or

smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or

smokeproof enclosure

All buildings with required enclosed stairway or smokeproof enclosure

All buildings with required enclosed stairway or

smokeproof enclosure

Page 11: Requirements Per Occupancy

FIRE DETECTION AND ALARM SYSTEM

MANUAL

2 or more storey in height

Less than 15 guest

Less than 15 guest

Required

Single Station smoke detectors

CLASS C

Not more than 3 storeys in height provided that the dwelling units shall installed with single station

smoke detectors.

Page 12: Requirements Per Occupancy

Less than 25 employees

N/A

All assembly occupancies

Every educational building

Ordinary or low hazard building not exceeding 2000 m2

Page 13: Requirements Per Occupancy

FIRE DETECTION AND ALARM SYSTEM

AUTOMATIC

50 or more occupants

15 or more guests

15 or more guests

N/A

N/A

CLASS A and B

4 or more storeys in height or more than 12 apartment unit

Page 14: Requirements Per Occupancy

More than 25 employees

Every building

All storage occupancies except ordinary or low hazard building

not exceeding 2000 m2

Occupant load exceeding 300 persons

If building is protected with AFSS

Page 15: Requirements Per Occupancy

TYPE OF OCCUPANCY1 Assembly

a. concentrated use without fixed seatsb. less concentrated usec. standing room or waiting space d.areas not in excess of 930 square meterse.areas in excess of 930 square meters

2 Educational a.net classroom area

c.dry nurseries where sleeping facilities are providedd. occupant load of an area having fixed seats

3 Health Care a. sleeping departmentsb. inpatient treatment departments

4 Detention and Correctional 5 Residential 6 Mercantile

a.Street floorb.Upper floors

Covered walls7 Business

b.net area of shops, laboratories and similar vocational rooms

c.floors or sections used only for offices, storage, shipping and not open to the general public

Page 16: Requirements Per Occupancy

8 Industrial 9 Storage Maximum probable population

fixed seats-number of fixed seats installed

Page 17: Requirements Per Occupancy

sqm sqm sqm

0.65 16 25 17 26 32 491.4 35 25 36 26 69 490.28 7 25 7 26 14 490.46 12 25 12 26 23 490.65 16 25 17 26 32 49

1.9 48 25 49 26 93 49

4.6 115 25 120 26 225 49

3.3 83 25 86 26 162 49

11.1 278 25 289 26 544 4922.3 558 25 580 26 1093 4911.1 278 25 289 26 544 4918.6 465 25 484 26 911 49

2.8 70 25 73 26 137 495.6 140 25 146 26 274 49

9.3 233 25 242 26 456 49

2.8 70 25 73 26 137 499.3 233 25 242 26 456 49

OCCUPANT LOAD FACTOR

occupant load/smal

l

occupant load/mediu

m

occupant load/mediu

m

Page 18: Requirements Per Occupancy

9.3 233 25 242 26 456 49

Page 19: Requirements Per Occupancy

sqmSQUARE METER

SMALL MEDIUM LARGE32.5 50 16 17 - 32 32.570 50 35 36 - 69 7014 50 7 7 - 14 1423 50 12 12 - 23 23

32.5 50 16 17 - 32 32.5-

95 50 48 49 - 93 95

230 50 115 120 - 225 230

165 50 83 86 - 162 165--

555 50 278 289 - 544 5551115 50 558 580 - 1093 1115555 50 278 289 - 544 555930 50 465 484 - 911 930

-140 50 70 73 - 137 140280 50 140 146 - 274 280

465 50 233 242 - 456 465

140 50 70 73 - 137 140465 50 233 242 - 456 465

occupant load/large

Page 20: Requirements Per Occupancy

465 50 233 242 - 456 465

Page 21: Requirements Per Occupancy

FIRE SAFETY REQUIREMENTS FOR INDUSTRIAL ESTABLISHMENTS

Manual Automatic Wet

Not Required 4 or more storeys

INDUSTRIAL OCCUPANCY HAZARD

CLASSIFICATION

SPRINKLER SYSTEM (Section10.2.3 (D),

IRR of RA 9514)

FIRE ALARM SYSTEM (Section 10.2.15.3 [C], IRR of RA 9514)

STANDPIPE SYSTEM (Section 10.2.15.3 [D3], IRR of RA 9514)

LOW AND MODERATE HAZARD

If it has less than 25 employees

If it has 25 or more employees

Page 22: Requirements Per Occupancy

HIGH HAZARD 4 or more storeys

I. CLASSIFICATION OF HAZARD CONTENS OF ANY BUILDING:

1. Low HazardThose of such low combustibility that no self-propagating fire therein can occur and that consequently, the only probable danger requiring the use of emergency exits will be from panic, fumes or smoke or fire from some external source.Section 10.2.4.2 of the IRR of RA 9514

Required with Automatic Fire Suppression System

If it has less than 25 employees

If it has 25 or more employees

Page 23: Requirements Per Occupancy

FIRE SAFETY REQUIREMENTS FOR INDUSTRIAL ESTABLISHMENTS

Dry

Required

STANDPIPE SYSTEM (Section 10.2.15.3 [D3], IRR of RA 9514)

PORTABLE FIRE EXTINGUISHER (Section 10.2.15.3 [D2], IRR of RA 9514)

EMERGENCY LIGHT & ILLUMINATED

EXIT AND WAYS OF TRAVEL (Section 10.2.15.2[H], IRR

of RA 9514)

EXIT REQUIRED (Section 10.2.15.2[E], IRR of RA 9514)

Class-A (Involving ordinary solid

combustible i.e. paper, wood, plastic, etc)

Class C shall also be provided for electrical

Class-B (Involving flammable and

combustible liquid and gas) Class C shall also

be provided for electrical

With required enclosed stairway for 2 or more

storeys

Low Hazard - every 15m, at maximum area of

200 sq.m. Moderate Hazard - every 12m, at max. area of 100 sq.m.

Low Hazard - every 10m, at maximum area of

100 sq.m. Moderate Hazard - every 12m, at max. area of 100 sq.m.

At least 2 exits, but may increase depending on the occupant loads (For rooms or areas with less than 25 persons and having direct exit access to the street or open area

outside the building at ground level and travel distance of not

more than 15.5 m, single exit may be permitted.

Page 24: Requirements Per Occupancy

Required

Those of such low combustibility that no self-propagating fire therein can occur and that consequently, the only probable danger requiring the use of emergency exits will be from panic, fumes or smoke or fire from some external source.

With required enclosed stairway for 2 or more

storeys

Every 10m at maximum area of 75 sq.m.

Every 10m at maximum area of 75 sq.m.

At least 2 exits, but may increase depending on the occupant loads (For rooms or areas with less than 25 persons and having direct exit access to the street or open area

outside the building at ground level and travel distance of not

more than 15.5 m, single exit may be permitted.

Page 25: Requirements Per Occupancy

FIRE SAFETY REQUIREMENTS FOR INDUSTRIAL ESTABLISHMENTS

Fire Exit DrillCompany Fire

Brigade

If employing at least 50 persons.

2 times a year if subject to occupancy

of 50 or more persons.

Page 26: Requirements Per Occupancy

If employing at least 50 persons.

2 times a year if subject to occupancy

of 50 or more persons.

Page 27: Requirements Per Occupancy
Page 28: Requirements Per Occupancy
Page 29: Requirements Per Occupancy
Page 30: Requirements Per Occupancy
Page 31: Requirements Per Occupancy

GENERAL PROVISIONS VIOLATIONSNo Fire Safety Certificate as per Sec 9.0.4.1 of RA 9514 IRR

No directional / exit markings as per Sec 10.2.5.12 of RA 9514 IRR

No visual fire alarm system as per Sec 10.2.6.4 of RA 9514 IRRNo dry standpipe system as per Sec 10.2.6.6 of RA 9514 IRRNo wet standpipe system as per Sec 10.2.6.6 of RA 9514 IRR

No organized fire brigade as per Sec 6.0.2.1 of RA 9514 IRR

No Fire Safety Clearance For Hazardous Materials as per Rule 9 Div 5 of RA 9514 IRR

Failed to submit fire insurance coverage as per Rule 9 Div 6 of RA 9514 IRR

No/Insufficient fire fighting appliance as per Sec 10.2.6.7 of RA 9514 IRR

Door/s not swinging in the direction of exit travel as per Sec 10.2.5.12 of RA 9514 IRR

No fire alarm system as per Rule 10 Chapter 2, Div 2 (G) / Sec 10.2.6.4 of RA 9514 IRR

Blocking of fire exits as per Rule 10, Chapter 2, Divisions 2 (D) of RA 9514 IRR

Locking of fire exits during periods when people are inside the building as per Sec 11.0.0.1 (f) of RA 9514 IRR

No secondary means of egress (fire exit) as per Rule 10, Chapter 2, Divisions 2 (H) of RA 9514 IRR

Failed to conduct fire exit drills (Educ. 4 times) as per Sec 10.2.18.3 (A) (2) of RA 9514 IRR

Failed to conduct fire exit drills (Child Care Center - 6 times) as per Sec 10.2.18.3 (C) (2) of RA 9514 IRR

Failed to conduct fire exit drills (Health care - quarterly on each shift) times) as per Sec 10.2.18.4 of RA 9514 IRR

Failed to conduct fire exit drills (Res. Hotel and Dormitories - twice a year) as per Sec 10.2.18.5 (A) (2) of RA 9514 IRR

Failed to conduct fire exit drills (Mercantile - twice a year for 50 occupants) as per Sec 10.2.18.6 of RA 9514 IRR

Failed to conduct fire exit drills (Business - twice a year for 50 occupants) as per Sec 10.2.18.6 of RA 9514 IRR

Failed to conduct fire exit drills (Industrial - twice a year for 50 occupants) as per Sec 10.2.18.6 of RA 9514 IRR

Non posting of emergency evacualtion plan as per Sec 10.2.5.13 of RA 9514 IRR

Page 32: Requirements Per Occupancy

Failed to implement fire safety programs as per Rule 10, Chapter 2, Division 2 (J) of RA 9514 IRR

Failed to submit FALAR (Fire and Life Safety Assessment Report) as per Sec 9.0.3.1 of RA 9514 IRR

Obstructing or blocking the exit ways or across to buildings clearly marked for fire safety purposes, such as but not limited to aisles in interior rooms, any part of stairways, hallways, corridors, vestibules balconies, or bridges leading to a stairway or exit of any kind, or tolerating or allowing said violations as per Sec 11.0.0.1 (A) of RA 9514 IRR

Constructing gates, entrances and walkways to buildings components and yards which obstruct the orderly and easy passage of fire fighting vehicles vehicles and equipment as per Sec 11.0.0.1 (B) of RA 9514 IRR

Prevention, interference or obstruction of any operation of the Fire Service, or of duly organized and authorized fire brigades as per Sec 11.0.0.1 (C) of RA 9514 IRR

Obstructing designated fire lanes or access to fire hydrants as per Sec 11.0.0.1 (D) of RA 9514 IRR

Overcrowding or admission of persons beyond the authorized capacity in movie houses, theaters, coliseums, auditoriums or other public assembly areas on the ground floor with open sides or open doors sufficient to provide safe exits as per Sec 11.0.0.1 (E) of RA 9514 IRR

Locking fire exits during period when people are inside the building as per Sec 11.0.0.1 (F) of RA 9514 IRR

Prevention or obstruction of the automatic closure of fire doors or smoke partitions or damages as per Sec 11.0.0.1 (G) of RA 9514 IRR

Use of fire protective of fire fighting equipment of the fire service other than for fire fighting except in other emergencies where their use are justified as per Sec 11.0.0.1 (H) of RA 9514 IRR

Giving false or malicious fire alarms as per Sec 11.0.0.1 (I) of RA 9514 IRR

Smoking in prohibited areas as may be determined by fire service, or throwing of cigars, cigarettes, burning objects in places which may start or cause fire as per Sec 11.0.0.1 (J) of RA 9514 IRR

Abandoning or leaving a building or structure by the occupant or owner without appropriate safety measures as per Sec 11.0.0.1 (K) of RA 9514 IRR

Page 33: Requirements Per Occupancy

Automatic sprinklers as per Sec 10.2.6.5 of RA 9514 IRR

Defective fire alarm system as per Sec 10.2.18.1 (D) of RA 9514 IRR

Removing, destroying, tampering or obliterating any authorized mark, seal, sign or tag posted or required by the fire service for fire safety in any building, structure or processing equipment as per Sec 11.0.0.1 (L) of RA 9514 IRR

Use of jumpers or tampering with electrical wiring or overloading the electrical system beyond its designated capacity or such other practices that would tend to undermine the fire safety features of the electrical system as per Sec 11.0.0.1 (M) of RA 9514 IRR

Width of means of egress not approved type (915 mm) as per Sec 10.2.5.2 (F) of RA 9514 IRR

Insufficient exits (3 exits for 500-1,000 / 4 exits for more than 1,000) as per Sec 10.2.5.2 (G) of RA 9514 IRR

Stairs (2,000 persons - 1120 mm / 2,000 persons - 1420 mm) as per Sec 10.2.5.4 of RA 9514 IRR

Fire Safety Clearance for storage, handling, installation of hazardous materials as per Rule 9 Division 5 of RA 9514 IRR

No automatic fire department notification (high rise, hospital, (educational, & 4 storey hotel & apartment) malls, highly hazardous occupancies as per Sec 10.2.6.4.(E) (3) of RA 9514 IRR

Installation Clearance (utilities, heating, ventilating, airconditioning, incinerators, elevators, escalator) as per Sec 1.2.7.6 of RA 9514 IRR

Defective automatic fire suppression system as per Sec 10.2.18.1 (C) of RA 9514 IRR

Failed to submit fire preventive maintenance record as per Sec 10.2.18.1 (G) of RA 9514 IRR

No Fire Clearance for hazardous materials & chemicals as per Sec 10.3.1.2 of RA 9514 IRR

Flammable and combustible liquids (dispensing) as per Sec 10.3.4.2 (2) (r) of RA 9514 IRR

Flammable and combustible liquids (Storage) as per Sec 10.3.4.2 (2) (s) of RA 9514 IRR

Flammable and combustible liquids (fire fighting appliances) as per Sec 10.3.4.2 (2) (s) of RA 9514 IRR

Flammable and combustible liquids (sprinkler system) as per Sec 10.3.4.2 (2) (s) of RA 9514 IRR

Flammable and combustible liquids (pre connected fire hose) as per Sec 10.3.4.2 (2) (s) of RA 9514 IRR

Page 34: Requirements Per Occupancy

Exit door should not be less than 71cm

Flammable and combustible liquids (No Smoking Sign) as per Sec 10.3.4.2 (2) (s) of RA 9514 IRR

Flammable and combustible liquids (No Smoking Sign) Bulk as per Sec 10.3.4.2 (3) of RA 9514 IRR

Flammable and combustible liquids (foam fire protection) as per Sec 10.3.4.2 (3) of RA 9514 IRR

Fire fighting appliances need servicing and maintenance as per Sec 10.5.3.3 of RA 9514 IRR

Page 35: Requirements Per Occupancy

GENERAL PROVISIONS VIOLATIONS

Three (3) Days

Three (3) Days

Fifteen (15) Days

Fifteen (15) Days

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) DaysFifteen (15) DaysFifteen (15) Days

Twenty-four (24) hours

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Page 36: Requirements Per Occupancy

Fifteen (15) Days

Three (3) Days

Twenty-four (24) hours

Three (3) Days

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Twenty-four (24) hours

Three (3) Days

Page 37: Requirements Per Occupancy

Twenty-four (24) hours

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Three (3) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Three (3) Days

Three (3) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Page 38: Requirements Per Occupancy

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Page 39: Requirements Per Occupancy
Page 40: Requirements Per Occupancy
Page 41: Requirements Per Occupancy
Page 42: Requirements Per Occupancy

PLACES OF PUBLIC ASSEMBLYTravel distance less than 46 meters (61 meters - AFSS)

Non-posting of Occupant Load as per Sec 10.2.8.1 (A) (5) of RA 9514 IRR

No Fire Alarm System as per Sec 10.2.8.8 (D) of RA 9514 IRROvercrowding as per Sec 10.2.8.11 of RA 9514 IRRNo Standby Fireman

MERCANTILE - Sec 10.2.13.1

Class C - less than 278 sqm as per Sec 10.2.13.1.(A) (2) of RA 9514 IRR

Travel Distance - 46 mNo Exit Signs as per Sec 10.2.13.2 (I) of RA 9514 IRRNo Emergency Lighting Facilities as per Sec 10.2.13.2 (I) of RA 9514 IRR

HEALTH CARENo Emergency Lighting Facilities as per Sec 10.2.10.2 (H) of RA 9514 IRRNo Fire Alarm System as per Sec 10.2.10.2 (H) of RA 9514 IRRNo Directional / Exit Signs as per Sec 10.2.10.2 (H) of RA 9514 IRR

Non-posting of plan of exit ways and aisles as per Sec 10.2.8.10 of RA 9514 IRR

Occupant Load - 0.65, 1.4, 0.28-standing, 0.46-less than 930 sqm., 0.65-more than 930 sqm

No Supervised atomatic Sprinkler System as per Sec 10.2.8.8 (E) of RA 9514 IRR

Class A - more than 2,787 sqm or 3 storeys as per Sec 10.2.13.1.(A) (2) of RA 9514 IRR

Class B - 2,787 to 287 sqm or 2 storeys as per Sec 10.2.13.1.(A) (2) of RA 9514 IRR

Occupant Load - 2.8 sqm - level of exit discharge, 3.7 sqm - above or elow exit discharge, 5.6 sqm - upper floor, 9.3 sqm - office & storage as per Sec 10.2.13.1.(C) of RA 9514 IRR

No Automatic and Manual Fire Alarm System (Class A & B) as per Sec 10.2.13.3 (C) of RA 9514 IRR

** No Automatic Fire Suppression System ( for travel distance more then 46 m) as per Sec 10.2.13.2 (F) of RA 9514 IRR

No Automatic Sprinkler Protection (for 3 Storeys / 1,115 sqm) as per Sec 10.2.13.3 (D) of RA 9514 IRR

Travel Distance - 30 m from any door, 46 m from any room, plus 15 m - AFSS as per Sec 10.2.10.2 (C) of RA 9514 IRR

Page 43: Requirements Per Occupancy

EDUCATIONAL

No Fire Alarm System as per Sec 10.2.9.5 (D) of RA 9514 IRRNo Directional / Exit Signs as per Sec 10.2.9.3 (B) of RA 9514 IRR

No Emergency Lighting Facilities as per Sec 10.2.9.3 (A) of RA 9514 IRR

RESIDENTIAL (HOTEL / DORMITORIES) - SSS REQUIRED SEC 10.2.12.3 (C) (5)Occupant Load - 18.6 sqm

No Directional sign as per Sec 10.2.12.3 (B) (8) of RA 9514 IRR

No Fire Fighting Appliances as per Sec 10.2.12.3 (C) (5) of RA 9514 IRRRESIDENTIAL (APARTMENT) - SSS REQUIRED SEC 10.2.12.4 (C) (5)

Occupant Load - 11.1 sqm, 22.3 sqm as per Sec 10.2.10.1 (E) of RA 9514 IRR

No AFSS - Underground and Windowless as per Sec 10.2.9.9 of RA 9514 IRR

No AFSS - at the floor below exit discharges as per Sec 10.2.9.5 (E) of RA 9514 IRR

No Secondary Exits (Rooms more than 50 persons or 93 sqm) as per Sec 10.2.9.2 (B) of RA 9514 IRR

Pre-schoolers, first grade & second grade pupils located above or below exit discharge as per Sec 10.2.9.8 of RA 9514 IRR

Insufficient width of corridor (1.83 m) as per Sec 10.2.9.2 (D) of RA 9514 IRR

Travel Distance - 46 m / 61 m with AFSS as per Sec 10.2.9.2 (C) of RA 9514 IRR

Occupant Load - 1.9 sqm-room, 4.6 sqm-lab, 3.3 sqm-nursery w/ sleeping as per Sec 10.2.9.1 (B) of RA 9514 IRR

Travel Distance - 15.25m for street level / 30m from door to exit as per Sec 10.2.12.3 (B) (5) of RA 9514 IRR

Corridor should be atleast 112 cm as per Sec 10.2.12.3 (B) (3) of RA 9514 IRR

No Secondary Exit for each floor as per Sec 10.2.12.3 (B) (4) of RA 9514 IRR

No Emergency Lighting Facilities as per Sec 10.2.12.3 (B) (8) of RA 9514 IRR

No Fire Alarm System (15 occupants) as per Sec 10.2.12.3 (C) (4) of RA 9514 IRR

No Partition wall having fire resistance of four (4) hours as per Sec 10.2.12.4 (B) (6) of RA 9514 IRR

Page 44: Requirements Per Occupancy

Outside window not of approved type as per Sec 10.2.12.4 of RA 9514 IRR

No Exit Sign as per Sec 10.2.12.4 (B) (6) of RA 9514 IRR

No Fire Fighting Appliances as per Sec 10.2.12.3 (C) (5) (c) of RA 9514 IRR

RESIDENTIAL (LODGING & ROOMING HOUSES) LESS THAN 15 PAX SEC 10.2.12.5

No Fire Alarm System as per Sec 10.2.12.5 (C) of RA 9514 IRRRESIDENTIAL (SINGLE & TWO FAMILY DWELLING) SEC 10.2.12.6

BUSINESS - SEC 10.2.14.1Occupant Load - 9.3 sqm as per Sec 10.2..14.1 (C) of RA 9514 IRR

Travel Distance - 46 m, 61 m AFSS as per Sec 10.2..14.2 of RA 9514 IRRNo Secondary Exits as per Sec 10.2..14.2 (D) of RA 9514 IRR

No Fire wall constructed solidly and continuously from the ground level to level one (1) meter above the ridge line of the roof as per Sec 10.2.12.4 (C) (1) of RA 9514 IRR

Sleeping Room not provided with outside window as per Sec 10.2.12.4 of RA 9514 IRR

No Emergency Lighting Facilities as per Sec 10.2.12.4 (B) (6) of RA 9514 IRR

No Automatic Fire Alarm System (4 Storeys / 12 units )as per Sec 10.2.12.4 (C) (4) (a) of RA 9514 IRR

No Manual Fire Alarm System (less than 4 Storeys / 12 units as per Sec 10.2.12.4 (C) (4) (b) of RA 9514 IRR

No Secondary Exit atleast 2 / room) as per Sec 10.2.12.5 (B) of RA 9514 IRR

No Fire Alarm System (2 storey / 100 for street level / 50 above & below) as per Sec 10.2..14.3 (C) of RA 9514 IRR

No Supervised Sprinkler System (High Rise Bldg) as per Sec 10.2..14.2 (F) of RA 9514 IRR

Page 45: Requirements Per Occupancy

PLACES OF PUBLIC ASSEMBLYFifteen (15) Days

Fifteen (15) Days

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) DaysImmediately

Twenty-four (24) hours

MERCANTILE - Sec 10.2.13.1

Twenty-four (24) hours

Fifteen (15) DaysFifteen (15) DaysFifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

HEALTH CAREFifteen (15) DaysFifteen (15) DaysFifteen (15) Days

Fifteen (15) Days

Page 46: Requirements Per Occupancy

Twenty-four (24) hours

EDUCATIONAL

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) DaysFifteen (15) Days

Fifteen (15) Days

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Twenty-four (24) hours

Fifteen (15) Days

RESIDENTIAL (HOTEL / DORMITORIES) - SSS REQUIRED SEC 10.2.12.3 (C) (5)Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days More Than 15 occupants - FDAS; Less Than 15 occupants - Manual

Fifteen (15) DaysRESIDENTIAL (APARTMENT) - SSS REQUIRED SEC 10.2.12.4 (C) (5)

Ten (10) Days

Page 47: Requirements Per Occupancy

Ten (10) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

RESIDENTIAL (LODGING & ROOMING HOUSES) LESS THAN 15 PAX SEC 10.2.12.5

Fifteen (15) Days

Fifteen (15) Days

BUSINESS - SEC 10.2.14.1Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) DaysFifteen (15) Days

Fifteen (15) Days

Page 48: Requirements Per Occupancy
Page 49: Requirements Per Occupancy

More Than 15 occupants - FDAS; Less Than 15 occupants - Manual

Page 50: Requirements Per Occupancy
Page 51: Requirements Per Occupancy

INDUSTRIAL - SEC 10.2.15.1

No Secondary Exit as per Sec 10.2.15.6 of RA 9514 IRR

STORAGE - SEC 10.2.16.1

No Exit Sign as per Sec 10.2.16.1 (B) (5) of RA 9514 IRR

Occupant Load - 9.3 sqm as per Sec 10.2.15.1 (2) of RA 9514 IRR

Travel Distance - 31 m, 46 m AFSS as per Sec 10.2.15.2 (F) of RA 9514 IRR

No Directional / Exit Sign as per Sec 10.2.15.2 (H) of RA 9514 IRR

No Emergency Lighting Facilities as per Sec 10.2.15.2 (H) of RA 9514 IRR

Corridor width less than 112 cm as per Sec 10.2.15.2 (C) of RA 9514 IRR

No Automatic Fire Alarm System (>25 employeses) as per Sec 10.2.15.3 (C) of RA 9514 IRR

No Manual Fire Alarm System (<25 employees) as per Sec 10.2.15.3 (C) of RA 9514 IRR

No Automatic Fire Suppression System as per Sec 10.2.15.3 (D) (1) of RA 9514 IRR

No Fire Fighting Appliances as per Sec 10.2.15.3 (D) (2) of RA 9514 IRR

No Standpipe System as per Sec 10.2.15.3 (D) (3) of RA 9514 IRR

No Secondary Exits as per Sec 10.2.16.1 (B) (3) of RA 9514 IRR

Travel Distance - 23 m, 30 m AFSS as per Sec 10.2.16.1 (B) (4) of RA 9514 IRR

No Emergency Lighting Facilities at Means of Egress as per Sec 10.2.16.1 (B) (5) of RA 9514 IRR

No Automatic Fire Alarm System ( 2,000 sqm - ordinary & low hazard) as per Sec 10.2.16.2 (B) of RA 9514 IRR

No Manual Fire Alarm System (less than 2,000 sqm) as per Sec 10.2.16.2 (B) of RA 9514 IRR

No Automatic Fire Suppression System as per Sec 10.2.16.2 (C) (1) of RA 9514 IRR

No Fire Fighting Appliances as per Sec 10.2.16.2 (C) (2)of RA 9514 IRR

Page 52: Requirements Per Occupancy

PARKING STRUCTURE - SEC 10.2.16.3

No Exit Sign as per Sec 10.2.16.3 (D) of RA 9514 IRR

TOWERS - SEC 10.2.17.1

No Fire Alarm System as per Sec 10.2.17.1 (E) of RA 9514 IRR

NFPA 10 - (145 PAGES/FIRE CODE - 4 PAGES)

BUILDING CODENo Building PermitNo Certificate of Occupancy

No Standpipe System as per Sec 10.2.16.2 (C) (3)of RA 9514 IRR

Travel Distance - 45 m, 60 m AFSS as per Sec 10.2.16.3 (B) (2) of RA 9514 IRR

No Emergency Lighting Facilities as per Sec 10.2.16.3 (C) of RA 9514 IRR

No Automatic Fire Suppresion System as per Sec 10.2.17.1 (E) of RA 9514 IRR

No Fire Fighting Appliances as per Sec 10.2.17.1 (E) of RA 9514 IRR

Fire extinguishers shall be subjected to maintenance at intervals of not more than One (1) year, at the time of hydrostatic test, or when specifically indicated by an isnpection

Stored-pressure types containing stream agent shall be disassembled on an annual basis and subjected to complete maintenance.

All rechargeable-type fore extinguishers shall be recharged after any use or as indicated by an inspection or when performing maintenance.

Page 53: Requirements Per Occupancy

INDUSTRIAL - SEC 10.2.15.1

Twenty-four (24) hours

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

STORAGE - SEC 10.2.16.1

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

Page 54: Requirements Per Occupancy

Fifteen (15) Days

PARKING STRUCTURE - SEC 10.2.16.3

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

TOWERS - SEC 10.2.17.1

Fifteen (15) Days

Fifteen (15) Days

Fifteen (15) Days

NFPA 10 - (145 PAGES/FIRE CODE - 4 PAGES)

chapter 4

Page 55: Requirements Per Occupancy

Table 1: FIRE EXTINGUISHERS FOR DIFFERENT TYPES OF CLASS A HAZARDS

TYPE OF HAZARD

Low 2-AModerate 3-A*

High 4-A*

Table 2: FIRE EXTINGUISHER FOR DIFFERENT TYPES OF CLASS B HAZARDS

TYPE OF HAZARD

Low 5-BModerate 10-B

High 40-B

Table 3: FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS B HAZARDS

TYPE OF HAZARD

Light (low)

Ordinary (moderate)

Extra (high)

Places of Assembly 32.5Mercantile 140Health Care 555Educational 95Residential 930Business 465Industrial 465Storage 465

MIN. EXTINGUISHER RATING

MIN. EXTINGUISHER RATING

OCCUPANCY CLASSIFICATION

FLOOR AREA (sq.m.) FALAR

Page 56: Requirements Per Occupancy

Table 1: FIRE EXTINGUISHERS FOR DIFFERENT TYPES OF CLASS A HAZARDS

15 20012 10010 75

Table 2: FIRE EXTINGUISHER FOR DIFFERENT TYPES OF CLASS B HAZARDS

10 20010 10010 75

Table 3: FIRE EXTINGUISHER SIZE AND PLACEMENT FOR CLASS B HAZARDS

5-B 9.1510-B 15.2510-B 9.1520-B 15.2540-B 9.1580-B 15.25

TRAVEL DISTANCE (m)DRILLS

w/o AFSS w/ AFSS46 6146 61 246 61 1246 61 4

15.25 246 61 231 46 223 30

MAX. TRAVEL DISTANCE TO

EXTINGUISHER (m)

MAX AREA (OPEN AREA) PER

EXTINGUISHER (m2)

MAX. TRAVEL DISTANCE TO

EXTINGUISHER (m)

MAX AREA (OPEN AREA) PER

EXTINGUISHER (m2)

Basic Minimum Extinguisher Rating

Maximum Travel Distance to

Extinguishers (m)

Page 57: Requirements Per Occupancy

TRAVEL DISTANCE (m)w/o AFSS w/ AFSS

Places of Assembly 32.5 46 61Mercantile 140 46 61Health Care 555 46 61Educational 95 46 61Residential 930 15.25Business 465 46 61Industrial 465 31 46Storage 465 23 30

REQUIREMENTS FOR AN EARTHQUAKE DRILL:

CONTINGENCY PLANORGANIZED DISASTER CONTROL GROUP/ROLES AND FUNCTIONSSCENARIOIDENTIFICATION OF EVACUATION AREAEVACUATION PROCESS/ROUTESALARM/WARNING SYSTEMSIGNAGESEVALUATIONRECOMMENDATION

OCCUPANCY CLASSIFICATION

FLOOR AREA

(sq.m.) FALAR

Page 58: Requirements Per Occupancy

DRILLS

2124222

ORGANIZED DISASTER CONTROL GROUP/ROLES AND FUNCTIONS

Page 59: Requirements Per Occupancy

FIRE SAFETY INSPECTION PROCEDURE

1

2

3

4

5

Is there a violation?

Conduct of Inspection

Conduct Re-Inspection

Complied?

Conduct Re-Inspection

Yes

No

Page 60: Requirements Per Occupancy

5

6

7

8

Conduct Re-Inspection

Complied?

Conduct Re-Inspection

Complied?Issue FSIC

Yes

Yes

Page 61: Requirements Per Occupancy

FIRE SAFETY INSPECTION PROCEDURE

Is there a violation?

Conduct of Inspection

Issue Notice To Comply

Conduct Re-Inspection

Complied?

Issue Notice To Correct Violation

Impose Admin FinePost Signage

Conduct Re-Inspection

Yes

No

After Grace Period

After Grace Period

Page 62: Requirements Per Occupancy

Conduct Re-Inspection

Complied?

Issue abatementImpose Admin Fine

Effect Continuous Postingof Signage

Conduct Re-Inspection

Complied?

Effect Continuous Postingof Signage

Recommend to RDStoppage of OperationClosure of the Building

No

No

After Grace Period