research article transformer magnetizing inrush currents...
TRANSCRIPT
Hindawi Publishing CorporationISRN ElectronicsVolume 2013 Article ID 361643 8 pageshttpdxdoiorg1011552013361643
Research ArticleTransformer Magnetizing Inrush Currents Using a DirectlyCoupled Voltage-Source Inverter
Rickard Ekstroumlm Senad Apelfroumljd and Mats Leijon
Division of Electricity Department of Engineering Physics Swedish Centre for Renewable Electric Energy ConversionUppsala University PO Box 534 751 21 Uppsala Sweden
Correspondence should be addressed to Rickard Ekstrom rickardekstromangstromuuse
Received 20 July 2013 Accepted 19 September 2013
Academic Editors J Abu Qahouq and J Doval-Gandoy
Copyright copy 2013 Rickard Ekstrom et al This is an open access article distributed under the Creative Commons AttributionLicense which permits unrestricted use distribution and reproduction in any medium provided the original work is properlycited
The connection of a power transformer to the grid is associated with magnetizing inrush currents that may result in power qualityissues as well as faulty relay tripping In distributed generation the transformer may instead be premagnetized from the source toavoid this In this paper a VSI is directly coupled to a transformer Three different strategies of premagnetization are implementedinto the control system and the inrush currents are measured for various values of the remanent flux in the core The results showgood reduction in the peak magnetizing inrush currents without using any external circuitry
1 Introduction
When energizing a power transformer the magnetizinginrush currents that follow may be several times higher thanthe rated currents for the transformer The magnitude of theinrush currents may cause voltage dips in the local gridresulting in poor power quality [1] Also the magnetizinginrush currents are rich in harmonic content usually have ahigh direct current component and may erroneously triggertransformer overcurrent protections [2]Muchwork has beenconducted in making the protective relays recognize thedifference between overcurrents at a fault and a magnetizinginrush current [3]
Themagnitude of the inrush currents depends on the cir-cuit reactance the phase angle120572 of the voltage source and thetransformer remanent magnetic flux 120601
119903 The remanent flux
in the transformer is the flux that exists in the transformerafter it is powered down This phenomenon has long beenstudied and variousmethods andmodels can be found in theliterature To measure the remanent flux is not easy but maybe approximated with measurements of the voltage integralduring deenergization
Several ways to reduce or eliminate the inrush currentshave been presented Ways to handle the issues are throughcontrolled switching and removal of remanent flux [4 5]
sequential phase energization [6 7] insertion of dampingresistors [8] capacitive loading or thyristor switching control[9]
Work that uses PWM inverters to inject a cancelling-outcurrent via the inverter during powerup of the transformerhas also been presented [10] along with methods to detectthe remanent flux by analysing the DC component duringswitching [11]
Many renewable energy sources are nonsynchronouswith the grid which will require a power electronics conver-sion stage for grid connection A commonly used conversionis the voltage-source inverter (VSI) followed by an LCL-filterand a step-up transformer The full control of the VSI allowsthe transformer magnetization to be handled by the sourcerather than the grid which can give a great advantage inhandling the magnetizing inrush currents
In this paper the power transformer is directly magne-tized by a VSI The LCL filter is put on the secondary side ofthe transformer to reduce the ampacity of the filter inductorsas discussed in [12] No external circuitry is required forthe transformer magnetization Three different strategies ofmagnetization are experimentally evaluated with variationsin the remanent flux and the peak inrush currents aredetected
2 ISRN Electronics
Im
V1 120601
120601
120601min
120596t
120601max
Figure 1 The induced core flux 120601(119905) lags the induced voltage V1(119905) by almost 90∘ The resultant magnetizing current 119868
119898grows rapidly when
the transformer goes into saturation
Im
120601
(a) Strategy 1
Im
120601
(b) Strategy 2
Im
120601
(c) Strategy 3
Figure 2 Three different typical paths in the B-H plane 120601119903is assumed to be maximum for all cases In strategy 1 the core is directly pushed
into saturation and it can take a long time before it stabilizes In strategy 2120601119903is pulled down to zero for all phases which reduces themagnitude
of the inrush current In strategy 3 the voltage ramping will slowly converge to the stable B-H-path while avoiding large inrush currents
2 Theory
When a variable voltage source V1(119905) is applied to the trans-
former windings a resulting flux 120601(119905) will be induced in thetransformer core according to Faradayrsquos law as follows
V1(119905) = radic2
1003816100381610038161003816V1
1003816100381610038161003816cos (120596119905 + 120572) = 119873
119889120601 (119905)
119889119905
(1)
where 120596 is the natural frequency of the applied voltage 120572is the start angle and 119873 the number of winding turnsThe induced flux may be derived by computing the voltageintegral over time as follows
120601 (119905) = int
1199052
1199051
V1(119905)
1198731
119889119905 =
radic21003816100381610038161003816V1
1003816100381610038161003816
1205961198731
sin (120596119905) + 120601119903 (2)
where 120601119903is the remanent flux Figure 1 shows how this is used
to derive the classical 120601-119868119898-curve or 119861-119867-curve It is clear
how even a small saturation in themagnetic fluxmay result ina large magnitude of the magnetizing current 119868
119898 As a worst
case scenario the peak amplitude of 119868119898may be approximated
by [1]
119868119898=
1
119883 + 119883119901+ 119883119888(min)
[pu] (3)
where 119883 is the source impedance 119883119901
is the windingimpedance and 119883
119888(min) is the minimum magnetization
impedance When the core is completely saturated it may betreated as an air core and it has been shown that 119883
119888may be
approximated by the short-circuit impedance119883SC [13]More accurately the magnetizing inrush current is calcu-
lated by
119868119898=
radic21003816100381610038161003816V1
1003816100381610038161003816
radic(120596119871)2
+ 1198772
sdot (
2119861119873+ 119861119877minus 119861119878
119861119873
) (4)
where 119861119873is the normal rated flux density 119861
119903is the remanent
flux density and 119861119878is the saturation flux density For more
detailed analysis a finite-element method (FEM) model hasto be set up for the transformer
3 Magnetizing Strategies
With the VSI directly connected to the power transformerthree different magnetization strategies have been evaluatedfor start-up of the transformer
(1) step response with remanent flux(2) step response without remanent flux(3) voltage ramping with remanent flux
The general plots of the B-H-curves for the differentstrategies are illustrated in Figure 2 but they should only be
ISRN Electronics 3
(a) VSI (b) Power transformer
Figure 3 The VSI and the power transformer used in the experimental set-up
C
E
G
Ove
rcur
rent
desa
t pro
tect
ion
VCE
(a)
400
300
200
100
0
A
30 1 2 V
VCE
IC
tp = 80120583s
TJ = 25∘C
VGE = 15V
VGE = 17VVGE = 15VVGE = 11V
TJ = 125∘C
(b)
Figure 4 (a) De-sat protection circuit (b) 119881CE vs 119868119862 from datasheet
considered as rough estimates To vary the remanent flux overthe entire range the transformer is magnetized at 1 pu andthen abruptly stopped at different angles 120573 of the appliedvoltage Stopping at 120573 = 0∘ results in a maximum negativeflux 120601maxminus and stopping at 120573 = 180∘ results in a maximumpositive flux 120601max+
In the first strategy the inverter is started abruptly givingfullmagnetization to the transformerThis becomes similar toan immediate grid connection and will be used as a referencecase In Figure 2(a) the remanent flux was positive at start-up and the transformer core is pushed into saturation as thestarting angle 120572 = 0
∘ If instead 120572 = 180∘ for this case a
minimal inrush current would have been obtained for thisphase
In the second strategy the inverter is started at zeroamplitude modulation 119898
119886 which will slowly force the core
flux to zero for all the transformer legs The switchingfrequency of the inverter is much faster than the transformer
time constant resulting in only a small pulse ripple in thetransformer core flux This essentially results in a removal ofthe remanent flux that is 120601
119903= 0 and becomes a special case
of strategy 1 when 120572 = 90∘ or 270∘ Once the transformer hassettled a step response is made in the induced voltage to 1 puThis is illustrated in Figure 2(b) where the flux is forced tocircle around origo before energization
The third strategy starts at 119898119886= 0 and slowly increases
the applied voltagewith a constant ramping function until fullmagnetization is reached in the transformer coreThe appliedvoltage can be described as
V1(119905) = V
119873
119905 minus 1199050
119879119877
cos (120596 (119905 minus 1199050) + 120572) 119905
0le 119905 le 119879
119877 (5)
where V119873is the nominal voltage 119879
119877is the slope of the ramp
and 119905 minus 1199050is the duration of the voltage ramping The major
benefit of this method is that it becomes rather insensitiveto the initial 120601
119903 and the core flux will smoothly settle
4 ISRN Electronics
0 10 20 30 40 50 60 70 80 90 100
Overcurrent limit
Time (ms)
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(a) 120572 = 180∘ 120573 = 0∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Cur
rent
(A)
100
50
0
minus50
minus100
(b) 120572 = 180∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Overcurrent limit
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(c) 120572 = 0∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(d) 120572 = 0∘ 120573 = 0∘
Figure 5 Strategy 1 time plots for different firing angles 120572 and stop angles 120573
according to Figure 2(c) while the largest inrush currentsmay be avoided
4 Experimental Set-Up
41 Hardware Implementation A three-phase two-levelvoltage-source inverter (VSI) has been designed as shown inFigure 3(a) It is made from three dual-package 400GB126Dinsulated-gate bipolar transistor (IGBT) modules with2SC0108T2Ax-17 driver boards mounted on top Thesehave in-built desaturation (desat) protections set to trigger25 120583s after a fault detection of an overcurrent of 250A orabove The de-sat protection circuit is shown in Figure 4(a)The collector-emitter voltage 119881CE across the IGBT iscontinuously detected and if it goes above a set thresholdvalue 119881th during conduction this is recognized as a faultycurrent and the IGBT is turned off 119881CE is a function of thethe collector current 119868
119862as shown in Figure 4(b) The IGBT
will be turned on again after a delay time but after multiplefault detections it will stop to avoid overheating
The inverter is directly connected to a three-phase345V1 kV YY-connected transformer shown in Figure 3(b)The transformer ratings are given in Table 1
Table 1 Transformer rating
Power rating 80 kVAVoltage ratio 138V1 kVPrimary winding resistance 68mΩPrimary leakage reactance 04mHSecondary winding resistance 48mΩSecondary leakage reactance 88mHMagnetizing impedance (50Hz) 0368HMagnetizing resistance (50Hz) 2768Ω
42 Software Implementation A compactRIO NI-9014 mod-ule with integrated RT-controller and FPGA chip has beenused to implement grid control strategies and the proposedtransformer magnetization strategies The FPGA chip is ofmodel Xilinx-5 [14] with an internal clock frequency of40MHz The RT-controller is of the model NI-9022
The VSI is controlled by sinusoidal pulse-width modu-lation (SPWM) where a sinusoidal reference waveform iscompared with sawtooth carrier waveforms to generate theoutput logic to the IGBTs It is possible to control the startangle 120572 and stop angle 120573 as well as the voltage rampingslope
ISRN Electronics 5
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(a) 120573 = 0∘
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(b) 120573 = 90∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(c) 120573 = 180∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(d) 120573 = 270∘
Figure 6 Strategy 1 varying the firing angle 120572 for different stop angles 120573
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Curr
ent (
A)
200
150
100
50
0minus50
minus100
minus150
minus200
Phase APhase BPhase C
(a) 120572 = 0∘
Curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus2500 10 20 30 40 50 60 70 80 90 100
Time (ms)
Phase APhase BPhase C
(b) 120572 = 180∘
Figure 7 Strategy 2 time plots
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
2 ISRN Electronics
Im
V1 120601
120601
120601min
120596t
120601max
Figure 1 The induced core flux 120601(119905) lags the induced voltage V1(119905) by almost 90∘ The resultant magnetizing current 119868
119898grows rapidly when
the transformer goes into saturation
Im
120601
(a) Strategy 1
Im
120601
(b) Strategy 2
Im
120601
(c) Strategy 3
Figure 2 Three different typical paths in the B-H plane 120601119903is assumed to be maximum for all cases In strategy 1 the core is directly pushed
into saturation and it can take a long time before it stabilizes In strategy 2120601119903is pulled down to zero for all phases which reduces themagnitude
of the inrush current In strategy 3 the voltage ramping will slowly converge to the stable B-H-path while avoiding large inrush currents
2 Theory
When a variable voltage source V1(119905) is applied to the trans-
former windings a resulting flux 120601(119905) will be induced in thetransformer core according to Faradayrsquos law as follows
V1(119905) = radic2
1003816100381610038161003816V1
1003816100381610038161003816cos (120596119905 + 120572) = 119873
119889120601 (119905)
119889119905
(1)
where 120596 is the natural frequency of the applied voltage 120572is the start angle and 119873 the number of winding turnsThe induced flux may be derived by computing the voltageintegral over time as follows
120601 (119905) = int
1199052
1199051
V1(119905)
1198731
119889119905 =
radic21003816100381610038161003816V1
1003816100381610038161003816
1205961198731
sin (120596119905) + 120601119903 (2)
where 120601119903is the remanent flux Figure 1 shows how this is used
to derive the classical 120601-119868119898-curve or 119861-119867-curve It is clear
how even a small saturation in themagnetic fluxmay result ina large magnitude of the magnetizing current 119868
119898 As a worst
case scenario the peak amplitude of 119868119898may be approximated
by [1]
119868119898=
1
119883 + 119883119901+ 119883119888(min)
[pu] (3)
where 119883 is the source impedance 119883119901
is the windingimpedance and 119883
119888(min) is the minimum magnetization
impedance When the core is completely saturated it may betreated as an air core and it has been shown that 119883
119888may be
approximated by the short-circuit impedance119883SC [13]More accurately the magnetizing inrush current is calcu-
lated by
119868119898=
radic21003816100381610038161003816V1
1003816100381610038161003816
radic(120596119871)2
+ 1198772
sdot (
2119861119873+ 119861119877minus 119861119878
119861119873
) (4)
where 119861119873is the normal rated flux density 119861
119903is the remanent
flux density and 119861119878is the saturation flux density For more
detailed analysis a finite-element method (FEM) model hasto be set up for the transformer
3 Magnetizing Strategies
With the VSI directly connected to the power transformerthree different magnetization strategies have been evaluatedfor start-up of the transformer
(1) step response with remanent flux(2) step response without remanent flux(3) voltage ramping with remanent flux
The general plots of the B-H-curves for the differentstrategies are illustrated in Figure 2 but they should only be
ISRN Electronics 3
(a) VSI (b) Power transformer
Figure 3 The VSI and the power transformer used in the experimental set-up
C
E
G
Ove
rcur
rent
desa
t pro
tect
ion
VCE
(a)
400
300
200
100
0
A
30 1 2 V
VCE
IC
tp = 80120583s
TJ = 25∘C
VGE = 15V
VGE = 17VVGE = 15VVGE = 11V
TJ = 125∘C
(b)
Figure 4 (a) De-sat protection circuit (b) 119881CE vs 119868119862 from datasheet
considered as rough estimates To vary the remanent flux overthe entire range the transformer is magnetized at 1 pu andthen abruptly stopped at different angles 120573 of the appliedvoltage Stopping at 120573 = 0∘ results in a maximum negativeflux 120601maxminus and stopping at 120573 = 180∘ results in a maximumpositive flux 120601max+
In the first strategy the inverter is started abruptly givingfullmagnetization to the transformerThis becomes similar toan immediate grid connection and will be used as a referencecase In Figure 2(a) the remanent flux was positive at start-up and the transformer core is pushed into saturation as thestarting angle 120572 = 0
∘ If instead 120572 = 180∘ for this case a
minimal inrush current would have been obtained for thisphase
In the second strategy the inverter is started at zeroamplitude modulation 119898
119886 which will slowly force the core
flux to zero for all the transformer legs The switchingfrequency of the inverter is much faster than the transformer
time constant resulting in only a small pulse ripple in thetransformer core flux This essentially results in a removal ofthe remanent flux that is 120601
119903= 0 and becomes a special case
of strategy 1 when 120572 = 90∘ or 270∘ Once the transformer hassettled a step response is made in the induced voltage to 1 puThis is illustrated in Figure 2(b) where the flux is forced tocircle around origo before energization
The third strategy starts at 119898119886= 0 and slowly increases
the applied voltagewith a constant ramping function until fullmagnetization is reached in the transformer coreThe appliedvoltage can be described as
V1(119905) = V
119873
119905 minus 1199050
119879119877
cos (120596 (119905 minus 1199050) + 120572) 119905
0le 119905 le 119879
119877 (5)
where V119873is the nominal voltage 119879
119877is the slope of the ramp
and 119905 minus 1199050is the duration of the voltage ramping The major
benefit of this method is that it becomes rather insensitiveto the initial 120601
119903 and the core flux will smoothly settle
4 ISRN Electronics
0 10 20 30 40 50 60 70 80 90 100
Overcurrent limit
Time (ms)
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(a) 120572 = 180∘ 120573 = 0∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Cur
rent
(A)
100
50
0
minus50
minus100
(b) 120572 = 180∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Overcurrent limit
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(c) 120572 = 0∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(d) 120572 = 0∘ 120573 = 0∘
Figure 5 Strategy 1 time plots for different firing angles 120572 and stop angles 120573
according to Figure 2(c) while the largest inrush currentsmay be avoided
4 Experimental Set-Up
41 Hardware Implementation A three-phase two-levelvoltage-source inverter (VSI) has been designed as shown inFigure 3(a) It is made from three dual-package 400GB126Dinsulated-gate bipolar transistor (IGBT) modules with2SC0108T2Ax-17 driver boards mounted on top Thesehave in-built desaturation (desat) protections set to trigger25 120583s after a fault detection of an overcurrent of 250A orabove The de-sat protection circuit is shown in Figure 4(a)The collector-emitter voltage 119881CE across the IGBT iscontinuously detected and if it goes above a set thresholdvalue 119881th during conduction this is recognized as a faultycurrent and the IGBT is turned off 119881CE is a function of thethe collector current 119868
119862as shown in Figure 4(b) The IGBT
will be turned on again after a delay time but after multiplefault detections it will stop to avoid overheating
The inverter is directly connected to a three-phase345V1 kV YY-connected transformer shown in Figure 3(b)The transformer ratings are given in Table 1
Table 1 Transformer rating
Power rating 80 kVAVoltage ratio 138V1 kVPrimary winding resistance 68mΩPrimary leakage reactance 04mHSecondary winding resistance 48mΩSecondary leakage reactance 88mHMagnetizing impedance (50Hz) 0368HMagnetizing resistance (50Hz) 2768Ω
42 Software Implementation A compactRIO NI-9014 mod-ule with integrated RT-controller and FPGA chip has beenused to implement grid control strategies and the proposedtransformer magnetization strategies The FPGA chip is ofmodel Xilinx-5 [14] with an internal clock frequency of40MHz The RT-controller is of the model NI-9022
The VSI is controlled by sinusoidal pulse-width modu-lation (SPWM) where a sinusoidal reference waveform iscompared with sawtooth carrier waveforms to generate theoutput logic to the IGBTs It is possible to control the startangle 120572 and stop angle 120573 as well as the voltage rampingslope
ISRN Electronics 5
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(a) 120573 = 0∘
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(b) 120573 = 90∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(c) 120573 = 180∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(d) 120573 = 270∘
Figure 6 Strategy 1 varying the firing angle 120572 for different stop angles 120573
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Curr
ent (
A)
200
150
100
50
0minus50
minus100
minus150
minus200
Phase APhase BPhase C
(a) 120572 = 0∘
Curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus2500 10 20 30 40 50 60 70 80 90 100
Time (ms)
Phase APhase BPhase C
(b) 120572 = 180∘
Figure 7 Strategy 2 time plots
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
ISRN Electronics 3
(a) VSI (b) Power transformer
Figure 3 The VSI and the power transformer used in the experimental set-up
C
E
G
Ove
rcur
rent
desa
t pro
tect
ion
VCE
(a)
400
300
200
100
0
A
30 1 2 V
VCE
IC
tp = 80120583s
TJ = 25∘C
VGE = 15V
VGE = 17VVGE = 15VVGE = 11V
TJ = 125∘C
(b)
Figure 4 (a) De-sat protection circuit (b) 119881CE vs 119868119862 from datasheet
considered as rough estimates To vary the remanent flux overthe entire range the transformer is magnetized at 1 pu andthen abruptly stopped at different angles 120573 of the appliedvoltage Stopping at 120573 = 0∘ results in a maximum negativeflux 120601maxminus and stopping at 120573 = 180∘ results in a maximumpositive flux 120601max+
In the first strategy the inverter is started abruptly givingfullmagnetization to the transformerThis becomes similar toan immediate grid connection and will be used as a referencecase In Figure 2(a) the remanent flux was positive at start-up and the transformer core is pushed into saturation as thestarting angle 120572 = 0
∘ If instead 120572 = 180∘ for this case a
minimal inrush current would have been obtained for thisphase
In the second strategy the inverter is started at zeroamplitude modulation 119898
119886 which will slowly force the core
flux to zero for all the transformer legs The switchingfrequency of the inverter is much faster than the transformer
time constant resulting in only a small pulse ripple in thetransformer core flux This essentially results in a removal ofthe remanent flux that is 120601
119903= 0 and becomes a special case
of strategy 1 when 120572 = 90∘ or 270∘ Once the transformer hassettled a step response is made in the induced voltage to 1 puThis is illustrated in Figure 2(b) where the flux is forced tocircle around origo before energization
The third strategy starts at 119898119886= 0 and slowly increases
the applied voltagewith a constant ramping function until fullmagnetization is reached in the transformer coreThe appliedvoltage can be described as
V1(119905) = V
119873
119905 minus 1199050
119879119877
cos (120596 (119905 minus 1199050) + 120572) 119905
0le 119905 le 119879
119877 (5)
where V119873is the nominal voltage 119879
119877is the slope of the ramp
and 119905 minus 1199050is the duration of the voltage ramping The major
benefit of this method is that it becomes rather insensitiveto the initial 120601
119903 and the core flux will smoothly settle
4 ISRN Electronics
0 10 20 30 40 50 60 70 80 90 100
Overcurrent limit
Time (ms)
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(a) 120572 = 180∘ 120573 = 0∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Cur
rent
(A)
100
50
0
minus50
minus100
(b) 120572 = 180∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Overcurrent limit
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(c) 120572 = 0∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(d) 120572 = 0∘ 120573 = 0∘
Figure 5 Strategy 1 time plots for different firing angles 120572 and stop angles 120573
according to Figure 2(c) while the largest inrush currentsmay be avoided
4 Experimental Set-Up
41 Hardware Implementation A three-phase two-levelvoltage-source inverter (VSI) has been designed as shown inFigure 3(a) It is made from three dual-package 400GB126Dinsulated-gate bipolar transistor (IGBT) modules with2SC0108T2Ax-17 driver boards mounted on top Thesehave in-built desaturation (desat) protections set to trigger25 120583s after a fault detection of an overcurrent of 250A orabove The de-sat protection circuit is shown in Figure 4(a)The collector-emitter voltage 119881CE across the IGBT iscontinuously detected and if it goes above a set thresholdvalue 119881th during conduction this is recognized as a faultycurrent and the IGBT is turned off 119881CE is a function of thethe collector current 119868
119862as shown in Figure 4(b) The IGBT
will be turned on again after a delay time but after multiplefault detections it will stop to avoid overheating
The inverter is directly connected to a three-phase345V1 kV YY-connected transformer shown in Figure 3(b)The transformer ratings are given in Table 1
Table 1 Transformer rating
Power rating 80 kVAVoltage ratio 138V1 kVPrimary winding resistance 68mΩPrimary leakage reactance 04mHSecondary winding resistance 48mΩSecondary leakage reactance 88mHMagnetizing impedance (50Hz) 0368HMagnetizing resistance (50Hz) 2768Ω
42 Software Implementation A compactRIO NI-9014 mod-ule with integrated RT-controller and FPGA chip has beenused to implement grid control strategies and the proposedtransformer magnetization strategies The FPGA chip is ofmodel Xilinx-5 [14] with an internal clock frequency of40MHz The RT-controller is of the model NI-9022
The VSI is controlled by sinusoidal pulse-width modu-lation (SPWM) where a sinusoidal reference waveform iscompared with sawtooth carrier waveforms to generate theoutput logic to the IGBTs It is possible to control the startangle 120572 and stop angle 120573 as well as the voltage rampingslope
ISRN Electronics 5
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(a) 120573 = 0∘
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(b) 120573 = 90∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(c) 120573 = 180∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(d) 120573 = 270∘
Figure 6 Strategy 1 varying the firing angle 120572 for different stop angles 120573
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Curr
ent (
A)
200
150
100
50
0minus50
minus100
minus150
minus200
Phase APhase BPhase C
(a) 120572 = 0∘
Curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus2500 10 20 30 40 50 60 70 80 90 100
Time (ms)
Phase APhase BPhase C
(b) 120572 = 180∘
Figure 7 Strategy 2 time plots
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
4 ISRN Electronics
0 10 20 30 40 50 60 70 80 90 100
Overcurrent limit
Time (ms)
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(a) 120572 = 180∘ 120573 = 0∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Cur
rent
(A)
100
50
0
minus50
minus100
(b) 120572 = 180∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Overcurrent limit
Cur
rent
(A)
300
200
100
0
minus100
minus200
minus300
(c) 120572 = 0∘ 120573 = 180∘
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Phase APhase BPhase C
0 10 20 30 40 50 60 70 80 90 10Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(d) 120572 = 0∘ 120573 = 0∘
Figure 5 Strategy 1 time plots for different firing angles 120572 and stop angles 120573
according to Figure 2(c) while the largest inrush currentsmay be avoided
4 Experimental Set-Up
41 Hardware Implementation A three-phase two-levelvoltage-source inverter (VSI) has been designed as shown inFigure 3(a) It is made from three dual-package 400GB126Dinsulated-gate bipolar transistor (IGBT) modules with2SC0108T2Ax-17 driver boards mounted on top Thesehave in-built desaturation (desat) protections set to trigger25 120583s after a fault detection of an overcurrent of 250A orabove The de-sat protection circuit is shown in Figure 4(a)The collector-emitter voltage 119881CE across the IGBT iscontinuously detected and if it goes above a set thresholdvalue 119881th during conduction this is recognized as a faultycurrent and the IGBT is turned off 119881CE is a function of thethe collector current 119868
119862as shown in Figure 4(b) The IGBT
will be turned on again after a delay time but after multiplefault detections it will stop to avoid overheating
The inverter is directly connected to a three-phase345V1 kV YY-connected transformer shown in Figure 3(b)The transformer ratings are given in Table 1
Table 1 Transformer rating
Power rating 80 kVAVoltage ratio 138V1 kVPrimary winding resistance 68mΩPrimary leakage reactance 04mHSecondary winding resistance 48mΩSecondary leakage reactance 88mHMagnetizing impedance (50Hz) 0368HMagnetizing resistance (50Hz) 2768Ω
42 Software Implementation A compactRIO NI-9014 mod-ule with integrated RT-controller and FPGA chip has beenused to implement grid control strategies and the proposedtransformer magnetization strategies The FPGA chip is ofmodel Xilinx-5 [14] with an internal clock frequency of40MHz The RT-controller is of the model NI-9022
The VSI is controlled by sinusoidal pulse-width modu-lation (SPWM) where a sinusoidal reference waveform iscompared with sawtooth carrier waveforms to generate theoutput logic to the IGBTs It is possible to control the startangle 120572 and stop angle 120573 as well as the voltage rampingslope
ISRN Electronics 5
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(a) 120573 = 0∘
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(b) 120573 = 90∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(c) 120573 = 180∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(d) 120573 = 270∘
Figure 6 Strategy 1 varying the firing angle 120572 for different stop angles 120573
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Curr
ent (
A)
200
150
100
50
0minus50
minus100
minus150
minus200
Phase APhase BPhase C
(a) 120572 = 0∘
Curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus2500 10 20 30 40 50 60 70 80 90 100
Time (ms)
Phase APhase BPhase C
(b) 120572 = 180∘
Figure 7 Strategy 2 time plots
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
ISRN Electronics 5
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(a) 120573 = 0∘
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(b) 120573 = 90∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(c) 120573 = 180∘
Phase APhase BPhase C
0 50 100 150 200 250 300 350
Peak
curr
ent (
A)
Firing angle 120572 (∘)
250200150100
500
minus50
minus100
minus150
minus200
minus250
(d) 120573 = 270∘
Figure 6 Strategy 1 varying the firing angle 120572 for different stop angles 120573
0 10 20 30 40 50 60 70 80 90 100Time (ms)
Curr
ent (
A)
200
150
100
50
0minus50
minus100
minus150
minus200
Phase APhase BPhase C
(a) 120572 = 0∘
Curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus2500 10 20 30 40 50 60 70 80 90 100
Time (ms)
Phase APhase BPhase C
(b) 120572 = 180∘
Figure 7 Strategy 2 time plots
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
6 ISRN Electronics
Peak
curr
ent (
A)
250200150100
500
minus50
minus100
minus150
minus200
minus250
Phase APhase BPhase C
0 50 100 150 200 250 300 350Firing angle 120572 (∘)
Figure 8 Strategy 2 varying the firing angle 120572 with zero initial core flux
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
100
50
0
minus50
minus100
(a) 1 cycle
0
20
40
60
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus20
minus40
minus60
(b) 3 cycles
0
10
20
30
40
0 20 40 60 80 100 120 140 160 180 200Time (ms)
Phase APhase BPhase C
0 20 40 60 80 100 120 140 160 180 20Time (ms)
Phase APhase BPhase C
Cur
rent
(A)
minus10
minus20
minus30
minus40
(c) 5 cycles
Figure 9 Strategy 3 varying the number of cycles from zero to full magnetization
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
ISRN Electronics 7
0 1 2 3 4 5 6 7 8 9 10Number of cycles
Peak
curr
ent (
A)
80
60
40
20
0minus20
minus40
minus60
minus80
Phase APhase BPhase C
(a) 120573 = 0∘
Number of cycles0 1 2 3 4 5 6 7 8 9 10
Peak
curr
ent (
A)
80
60
40
200
minus20
minus40
minus60
minus80
Phase APhase BPhase C
(b) 120573 = 180∘
Figure 10 Strategy 3 varying the number of cycles to full magnetization The start angle 120572 is always set to 0∘ but it will have little impact onthe current peaks for the voltage ramping strategy
5 Results and Discussion
The transformer was magnetized to its rated voltage of 1 kVusing the three different strategies proposed above whilemeasuring the peak magnetizing inrush currents In strategy1 the transformerwas stopped at different angles120573 to evaluatethe variations in the remanent flux In strategy 2 this becomesredundant as 120601
119903always converges to zero before start-up In
strategy 3 120573 = 0∘ and 120573 = 180∘ are used to evaluate 120601maxminusand 120601max+
51 Strategy 1 Results In Figure 5 the magnetizing inrushcurrents are plotted for two different 120572 and 120573 in phase AThese samples are shown to illustrate the worst scenarios withmaximum remanent flux in the core As expected the highestinrush currents are obtained when 120572 is shifted half a periodfrom 120573 and here the peak currents easily reach above 250ATo minimize the peak currents for this strategy 120572 shouldbe in phase with 120573 which here results in peak currents ofabout 100A It is clear from Figures 5(a) and 5(c) how de-satprotection is activated which otherwise could have resultedin much higher currents
In Figure 6 the peak current values are sampled anddisplayed for fixed values of 120573 The variation between phasesis due to not only 120572 and 120573 but also unbalances in thetransformer core where the center leg will have a lowerreluctance path than the outer legsThiswas not compensatedfor in the transformer design
52 Strategy 2 Results In strategy 2 the remanent flux isessentially removed resulting in the special case of strategy 1when 120573 = 0∘ for phase A Also the remanent fluxes for phasesB and C are removed which was not the case in strategy 1In Figure 7 currents are displayed for the two worst casescenarios in phase A 120572 = 0∘ and 120572 = 180∘ The worst inrushcurrents are less than half compared to those in strategy 1
and never sufficiently high to trigger the de-sat protectionIn Figure 8 the peak phase currents are shown while varying120572
53 Strategy 3 Results In Figure 9 the applied voltage startsfrom zero and is linearly ramped to 1 pu In Figure 9(a) theramping time duration is one fundamental cycle (20ms)in Figure 9(b) this is increased to 3 cycles (60ms) and inFigure 9(c) 5 cycles 120573 was set to 0∘ for all cases but it hasnegligible impact for this strategy Already at 1 cycle rampingtime the peak current has reduced by half compared to that instrategy 1 and it continues to drop for longer time durations
Inrush current peak vs number of cycles is displayed inFigure 10 As the ramping time increases the inrush currentsare effectively removed
6 Conclusions
The magnitude of the magnetizing inrush currents for apower transformer with direct VSI connection has beenevaluated where no external circuitry for the grid connec-tion is required Three magnetization strategies have beensuggested and experimentally investigated step responsewith remanent flux step response without remanent fluxand voltage ramping A de-sat protection is used to limitthe highest currents By removing the remanent flux thepeak inrush current is reduced to at least half in the worstcases However with voltage ramping the peak currentsmay be more or less completely removed depending on thetime duration of voltage ramping All strategies are easy toimplement in the FPGA-based control system
Conflict of Interests
The authors declare that there is no conflict of interestsregarding the publication of this paper
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
8 ISRN Electronics
Acknowledgments
This project is supported by Statkraft AS KIC InnoEnergy-CIPOWER Fortum oy the Swedish Energy Agency DrakaCable AB the Gothenburg Energy Research FoundationFalkenberg EnergyAB theWallenius FoundationHelukabelProEnviro Seabased AB the Olle Engkvist Foundationthe J Gust Richert Foundation A ngpanneforeningenrsquosFoundation for Research and Development CF Environ-mental Fund the Goran Gustavsson Research Foundationand Vargons Research Foundation This support is gratefullyacknowledged
References
[1] M Nagpal T G Martinich A Moshref K Morison and PKundur ldquoAssessing and limiting impact of transformer inrushcurrent on power qualityrdquo IEEE Transactions on Power Deliveryvol 21 no 2 pp 890ndash896 2006
[2] L-C Wu C-W Liu S-E Chien and C-S Chen ldquoThe effect ofinrush current on transformer protectionrdquo in Proceedings of the38th Annual North American Power Symposium (NAPS rsquo06) pp449ndash456 Carbondale Ill USA September 2006
[3] F Mekic R Girgis Z Gajic and E Nyenhuis ldquoPower trans-former characteristics and their effect on protective relaysrdquo inProceedings of the 33rd Western Protective Relay ConferenceOctober 2006
[4] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching I theoretical consid-erationsrdquo IEEE Transactions on Power Delivery vol 16 no 2pp 276ndash280 2001
[5] J H Brunke and K J Frohlich ldquoElimination of transformerinrush currents by controlled switching II application and per-formance considerationsrdquo IEEETransactions on PowerDeliveryvol 16 no 2 pp 281ndash285 2001
[6] Y Cui S G Abdulsalam S Chen and W Xu ldquoA sequentialphase energization technique for transformer inrush currentreduction I simulation and experimental resultsrdquo IEEE Trans-actions on Power Delivery vol 20 no 2 pp 943ndash949 2005
[7] W Xu S G Abdulsalam Y Cui and X Liu ldquoA sequentialphase energization technique for transformer inrush currentreduction II theoretical analysis and design guiderdquo IEEETransactions on PowerDelivery vol 20 no 2 pp 950ndash957 2005
[8] L Cipcigan W Xu and V Dinavahi ldquoA new technique tomitigate inrush current caused by transformer energizationrdquoin Proceedings of the IEEE Power Engineering Society SummerMeeting vol 1 pp 570ndash574 Chicago ILL USA July 2002
[9] M S J Asghar ldquoElimination of inrush current of transformersand distribution linesrdquo in Proceedings of the 1996 InternationalConference on Power Electronics Drives amp Energy Systems forIndustrial Growth (PEDES rsquo96) vol 2 pp 976ndash980 New DelhiIndia January 1996
[10] K Shinohara K Yamamoto K Iimori YMinari O Sakata andM Miyake ldquoCompensation for magnetizing inrush currents intransformers using a PWM inverterrdquo Electrical Engineering inJapan vol 140 no 2 pp 53ndash64 2002
[11] A Rasic G Herold and U Krebs ldquoFast connection recon-nection of the VSC to the power networkrdquo in Proceedings ofthe European Conference on Power Electronics and Applications(EPE rsquo07) Aalborg Denmark September 2007
[12] R Ekstrom S Apelfrojd and M Leijon ldquoTransformer mag-netization losses using a non-filtered voltage-source inverterrdquoAdvances in Power Electronics vol 2013 Article ID 261959 7pages 2013
[13] D Povh and W Schultz ldquoAnalysis of overvoltages caused bytransformer magnetizing inrush currentrdquo IEEE Transactions onPower Apparatus and Systems vol 97 no 4 pp 1355ndash1365 1978
[14] Xilinx Data Book 2006 httpwwwxilinxcom
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of
International Journal of
AerospaceEngineeringHindawi Publishing Corporationhttpwwwhindawicom Volume 2014
RoboticsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Active and Passive Electronic Components
Control Scienceand Engineering
Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
International Journal of
RotatingMachinery
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporation httpwwwhindawicom
Journal ofEngineeringVolume 2014
Submit your manuscripts athttpwwwhindawicom
VLSI Design
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Shock and Vibration
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Civil EngineeringAdvances in
Acoustics and VibrationAdvances in
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Electrical and Computer Engineering
Journal of
Advances inOptoElectronics
Hindawi Publishing Corporation httpwwwhindawicom
Volume 2014
The Scientific World JournalHindawi Publishing Corporation httpwwwhindawicom Volume 2014
SensorsJournal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Modelling amp Simulation in EngineeringHindawi Publishing Corporation httpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Chemical EngineeringInternational Journal of Antennas and
Propagation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
Navigation and Observation
International Journal of
Hindawi Publishing Corporationhttpwwwhindawicom Volume 2014
DistributedSensor Networks
International Journal of