residential hvac system design report - pe...

23
RESIDENTIAL HVAC SYSTEM DESIGN REPORT

Upload: truongthuan

Post on 06-Feb-2018

215 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

RESIDENTIAL HVAC SYSTEM DESIGN REPORT

Page 2: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Table of Contents

1) HVAC System Design Disclaimer

2) Equipment Selection Form

3) Heat Pump Balance Point Diagram

4) Examiner Review Form

5) Building Analysis Report

6) Project Summary Report

7) Manual J Worksheets

8) Duct System Summary

9) Friction Rate Worksheet

10) Duct Distribution Drawing

11) Air Volume Balance Report Form

12) Equipment Bill of Materials

13) ASHRAE 62.2 Report

PE LOAD CALCS, LLC 901.257.5910

www.peloadcalcs.com [email protected]

Page 3: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

HVAC System Design Disclaimer

The following pages summarizes the load calculations, equipment selection, and duct design of a residence using ACCA/ASHRAE procedures (J, S, D, 62.2) and current codes (IRC, IECC). All calculations are based on information given to PE Load Calcs LLC in the form of surveys, drawings, sketches, pictures, and meetings. In certain cases, PE Load Calcs may make reasonable assumptions about design conditions and construction materials that may or may not be accurate for the building of concern. It is the responsibility of the installing HVAC contractor to verify the design conditions, construction materials, and compatibility with existing equipment before equipment purchase and installation.

All HVAC system design work provided in the following pages are based upon information provided by the particular party submitting a particular project to PE Load Calcs. PE Load Calcs has not and does not independently verify that the data provided to us is correct or complete, and any design made by PE Load Calcs are based upon the information provided by third parties. PE Load Calcs makes no claim that the information given to us is correct or complete.

PE Load Calcs utilizes the latest Wrightsoft’s Right-Suite Universal 2015 which is an ACCA Certified and ASHRAE recommended HVAC system design software. The mathematical model and design of the HVAC system, designed by PE Load Calcs, is only as accurate as the input provided. PE Load Calcs makes every attempt possible to be as detailed and accurate as possible, however, there is no reasonable means to mathematically model an HVAC system that has not been properly installed, or has had after-the-fact building modifications or HVAC system component alterations or substitutions.

If there is any construction modifications (floor plan, roofing material, window types/sizes, insulation characteristics, or any other change that will alter the load calculation results), HVAC equipment substitutions, duct sizing or layout changes, which is not noted in this report, and therefore not provided to PE Load Calcs for consideration for the HVAC system design, then PE Load Calcs may not guarantee the performance of the HVAC system design, and all design standards and procedures performed for this HVAC system design, including this report, may no longer be valid.

PE Load Calcs will not guarantee the performance of the HVAC system design if the equipment selection and/or duct design has been performed by another party. Also, PE Load Calcs will not guarantee the performance of the HVAC system design that has not been properly installed or tested to verify performance has conformed to manufacturer specifications and design criteria provided in this report. It is up to the installing HVAC contractor to properly install, test, and verify all components of the HVAC system. All installing HVAC contractors are expected to follow ACCA Standards 5 and 9 for quality HVAC equipment installation.

All information on any existing HVAC equipment (prior to design) to remain with an existing structure must be provided to PE Load Calcs prior to the design for appropriate selection of new and compatible equipment. It is up to the installing HVAC contractor to verify equipment compatibility between with the newly installed equipment (per design) and any existing equipment remaining, via manufacture specifications and airflow/static pressure measurements.

PE Load Calcs does not provide architectural or engineering plans or diagrams for the public or for use by contractors or construction companies as final “construction documents”. PE Load Calcs works with architectural and engineering firms and with contractors in connection with their designs of HVAC systems.

Copies of this report, including the completed balance report (and any other documents that need to be completed by the installing HVAC contractor verifying equipment performance meeting design requirements and manufacturer specifications), must be kept on file by the installing HVAC contractor, and also a copy given to the homeowner to remain attached to the HVAC equipment, and to any other party of specific interest (i.e., code official, county, builder/architect).

PE LOAD CALCS, LLC 901.257.5910

www.peloadcalcs.com [email protected]

Page 1 of 1

Page 4: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Equipment Selection Form From ACCA’s Manual S

PROJECT INFORMATION

Building Address: City, State and Zip: ASHRAE Location: HDD/CDD: Altitude: ACF:

COOLING EQUIPMENT

Design Conditions

Outdoor Design DB: F Total Gain: Btuh Design Airflow: CFM Outdoor Design WB: F Latent Gain: Btuh Entering Coil DB: F Indoor Design DB: F Sensible Gain: Btuh Entering Coil WB: F Indoor RH: % JSHR:

Manufacturer's Performance Data at Actual Design Conditions

HEATING EQUIPMENT

Design Conditions

Outdoor Design DB: F Heat Loss: Btuh Design Airflow: CFM Indoor Design DB: F Humidification: Btuh Entering Coil DB: F

Manufacturer’s Performance Data at Actual Design Conditions

Equipment Type: Manufacturer: Model: Output Capacity: Btuh Supplemental Heat Required: Btuh Thermal Balance Point: F

Model: Btuh % load F kW F kW

Temp Rise:1st Stage Lock-Out Temp:

2nd Stage Lock-Out Temp: F

Backup Equipment Type: Manufacturer: Output Capacity: 1st Stage Supplement: 2nd Stage Supplement: Reserve Heat: kW

The above equipment was selected in accordance with ACCA Manual S.

Equipment Type: Condition A or B: (Applicable to Heat Pumps Only) Manufacturer: Model: Sensible Capacity: Btuh Total Capacity (TC): Btuh % of Total Gain (TG) 115% ≥ TC/TG ≥ 90% Latent Capacity (LC): Btuh % of Latent Gain (LG) 150% ≥ LC/LG ≥ 100% Adj. Sensible (SC): Btuh % of Sensible Gain (SG) SC/SG ≥ 90%

Page 1 of 1

7007 Lystra Road

Harrison TN 37341

Chattanooga TN 0.65 689 0.97

92 29457 1050

75 5975 75

75

50

23482

0.80

63

Packaged Air Source Heat Pump

A

Goodman Manufacturing Company GPH14H36H41C

24025

31040 105 Y

7015 117

24545 98

Y

Y

22 44141 1050

70 0 69

Packaged Air Source Heat Pump

Goodman Manufacturing Company GPH14H36H41C

23660

20481 37

Electric Strip - 15 kW Electrical Heat Kit (3 stages of 5 kW)

Goodman Manufacturing Company HKR-05 (Qt. 3)

56084 127 50.8

5.0 37

5.0 25

5.0

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

Page 5: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Heat Pump Balance Point Diagram From ACCA’s Manual S

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

Page 1 of 1

Page 6: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Right-Suite® Universal 2015 15.0.07 RSU18218

FormRPER 1

15 Mar 09

Residential Plans Examiner Review Formfor HVAC System Design (Loads, Equipment, Ducts)

Hamilton CountyHeader Information

Contractor: ATTACHEDREQUIRED ATTACHMENTSNoYesManual J1 Form (and supporting worksheets):

Mechanical license: NoYesor MJ1AE Form* (and supporting worksheets):NoYesOEM performance data (heating, cooling, blower):

Building plan #: NoYesManual D Friction Rate Worksheet:NoYesDuct distribution sketch:

Home address (Street or Lot#, Block, Subdivision): 7007 Lystra Rd, Entire House

HVAC LOAD CALCULATION (IRC M1401.3)

Design Conditions Building Construction Information

Front Door faces NorthBuildingWinter Design Conditions

North, East, West, South, Northeast, Northwest, Southeast, SouthwestOrientation:°F22Outdoor temperature:

°F70Indoor temperature:

3Number of bedrooms:Btuh44141Total heat loss:ft²1679Conditioned floor area:

4Number of occupants:Summer Design Conditions°F92Outdoor temperature:

Windows°F75Indoor temperature:ft6.5Eave overhang depth:% RH50gr/lb @38Grains difference:

Blinds, drapes, etc.blinds,drapesInternal shade:Btuh24183Sensible heat gain:

Btuh6154Latent heat gain:

0Number of skylights:Btuh30337Total heat gain:

HVAC EQUIPMENT SELECTION (IRC M1401.3)

Heating Equipment Data Blower Data Cooling Equipment Data

1050Heating cfm:Air Conditioner, Heat pump, etc.

Pkg ASHPEquipment type:Furnace, Heat pump, Boiler, etc.

Pkg ASHPEquipment type:

1050Cooling cfm:

Fan's rated external static pressure for designairflow

in H2O0.56Static pressure:Goodman Mfg.Model:Goodman Mfg.Model:GPH1436H41C+ GPH1436H41C+

Btuh31040Total cooling capacity:Heat pumps - capacity at winter design outdoor conditions

Btuh23660Heating output capacity:Btuh24025Sensible cooling capacity:Btuh7015Latent cooling capacity:Btuh45769Aux. heating output capacity:

HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1)

Duct Materials Usedft219Longest supply duct:cfm1050Design airflow:Sheet metalTrunk duct:ft59Longest return duct:in H2O0.56Equipment design ESP:

ft277Total effective length (TEL):in H2O-0.3Total device pressure losses:Sheet metalBranch duct:

Friction Rate = ASP ÷ (TEL x 100)in/100ft0.094Friction rate:in H2O0.26Available static pressure (ASP):

I declare the load calculation, equipment, equipment selection and duct design were rigorously performed based on the building plan listed above. I understand the claims made on these forms will be subject to review and verification.

Contractor's printed name:

Contractor's signature: Date:

Reserved for County, Town Municipality or Authority having jurisdiction use.

*Home qualifies for MJ1AE Form based on Abridged Edition Checklist

Anthony Amadio, Deisgner of PE Load Calcs, LLC

11-24-2014

Page 7: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

2014-Dec-19 13:05:27Right-Suite® Universal 2015 15.0.07 RSU18218 Page 1

...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

Building AnalysisEntire House

Job: 0001Date: Nov 24, 2014By: PE Load Calcs, LLC

Project InformationFor: Joe Chen, Homeowner

7007 Lystra Rd, Harrison, TN 37341 Phone: (423) Email: tiu

Design ConditionsLocation: CoolingHeatingIndoor:

7570Indoor temperature (°F)Chattanooga Lovell Field AP, TN, US1748Design TD (°F)ft689Elevation:5050Relative humidity (%)°N35Latitude:

Outdoor: 38.142.5Moisture difference (gr/lb)CoolingHeatingInfiltration:9222Dry bulb (°F)

Blower doorMethod)M(19-Daily range (°F)1 (no shielding) / 1Shielding / stories75-Wet bulb (°F)50 Pa / 2700 cfmPressure / AVF7.515.0Wind speed (mph)

Heating

Walls

Glazing

Doors

Ceilings

Floors

Infiltration

Ducts

% of loadBtuhBtuh/ft²Component

14.162374.7Walls11.3500425.7Glazing2.5108925.9Doors9.240652.4Ceilings

20.891955.35.3Floors31.61392910.8Infiltration10.54622Ducts

00Piping00Humidification00Ventilation

0Adjustments100.044141Total

Cooling

Walls

Glazing

Doors

CeilingsFloors

Infiltration

Ducts

Internal Gains

% of loadBtuhBtuh/ft²Component

10.624791.9Walls17.8417321.5Glazing

3.071617.0Doors19.044552.6Ceilings13.932761.9Floors11.025902.0Infiltration9.72272Ducts

00Ventilation15.03520Internal gains

00Blower0Adjustments

100.023481Total

Latent Cooling Load = 5975 BtuhOverall U-value = 0.169 Btuh/ft²-°F

Data entries checked.

Page 8: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Bold/italic values have been manually overridden

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.

2014-Dec-19 13:05:27Right-Suite® Universal 2015 15.0.07 RSU18218 Page 1

...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

Project SummaryEntire House

Job: 0001Date: Nov 24, 2014By: PE Load Calcs, LLC

Project Information

For: Joe Chen, Homeowner7007 Lystra Rd, Harrison, TN 37341Phone: (423) Email: tiuHomeowner is also interested in attic duct design should he later decide to abandon his existing old duct system in small unconditioned crawlspace.

Notes:

Design Information

Chattanooga Lovell Field AP, TN, USWeather:

Winter Design Conditions Summer Design Conditions

Outside db °F22 Outside db °F92Inside db °F70 Inside db °F75Design TD °F48 Design TD °F17

Daily range MRelative humidity %50Moisture difference gr/lb38

Heating Summary Sensible Cooling Equipment Load Sizing

Structure Btuh39518 Structure Btuh21209Ducts Btuh4622 Ducts Btuh2272Central vent (0 cfm) Btuh0 Central vent (0 cfm) Btuh0Humidification Btuh0 Blower Btuh0Piping Btuh0Equipment load Btuh44141 Use manufacturer's data n

Rate/swing multiplier 0.97Infiltration Equipment sensible load Btuh22800

Method Latent Cooling Equipment Load SizingBlower doorShielding / stories 1 (no shielding) / 1

50 Pa / 2700 cfmPressure / AVF Structure Btuh4372Ducts Btuh1603

CoolingHeating Central vent (0 cfm) Btuh016791679Area (ft²) Equipment latent load Btuh5975

1343213432Volume (ft³)Air changes/hour 0.631.21 Equipment total load Btuh28776Equiv. AVF (cfm) 141270 Req. total capacity at 0.70 SHR ton2.7

Heating Equipment Summary Cooling Equipment Summary

Make Goodman Mfg. Make Goodman Mfg.Trade GOODMAN, JANITROL, AMANA DISTI... Trade GOODMAN, JANITROL, AMANA DISTI...Model GPH1436H41C Cond GPH1436H41CAHRI ref 5677876 Coil

AHRI ref 5677876Efficiency 8 HSPF Efficiency 11.5 EER, 14 SEERHeating input Sensible cooling Btuh25200Heating output Btuh @ 47°F32200 Latent cooling Btuh10800Temperature rise °F29 Total cooling Btuh36000Actual air flow cfm1050 Actual air flow cfm1050Air flow factor cfm/Btuh0.024 Air flow factor cfm/Btuh0.045Static pressure in H2O0.56 Static pressure in H2O0.56Space thermostat Load sensible heat ratio 0.80

Page 9: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 1...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire House PE Load Calcs, LLCBy:

1 Room name Entire House Guest12 Exposed wall 160.5 ft 29.5 ft3 Room height 8.0 ft 8.0 heat/coolft4 Room dimensions ft14.5x15.05 Room area 1728.5 ft² 217.5 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Loadnumber (Btuh/ft²-°F)(Btuh/ft²-°F) (Btuh/ft²)(Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12B-0bw12B-0bw 0.0970.097 nene 4.664.66 1.481.48 536 432 2009 641 120 110 511 163. GG 10A-w10A-w 0.8200.820 nene 39.3639.36 27.7027.70 84 0 3306 2327 0 0 0 0. GG 4A4-2ov4A4-2ov 0.3200.320 nene 15.3615.36 18.8918.89 20 0 314 386 10 0 157 193. WW 12B-0bw12B-0bw 0.0970.097 sese 4.664.66 1.481.48 240 230 1070 341 116 106 493 157

11 GG 4A4-2ov4A4-2ov 0.3200.320 sese 15.3615.36 21.2021.20 10 0 157 216 10 0 157 216WW 12B-0bw12B-0bw 0.0970.097 swsw 4.664.66 1.481.48 472 371 1728 551 0 0 0 0

GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 21.2021.20 35 0 534 737 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 10.2910.29 11 23 175 117 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 11.5511.55 34 68 518 390 0 0 0 0DD 11G011G0 0.5400.540 swsw 25.9225.92 15.7115.71 21 21 544 330 0 0 0 0

WW 12B-0bw12B-0bw 0.0970.097 nwnw 4.664.66 1.481.48 36 36 168 53 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 192 171 796 564 0 0 0 0

DD 11G011G0 0.5400.540 nn 25.9225.92 18.3618.36 21 21 544 386 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 100 100 466 330 0 0 0 0CC 16B-19ad16B-19ad 0.0490.049 -- 2.352.35 2.582.58 1729 1729 4065 4455 218 218 512 561FF 19A-0cvcp19A-0cvcp 0.2950.295 -- 5.325.32 1.901.90 1729 1729 9195 3276 218 218 1157 412

6 c) AED excursion 0 -84

Envelope loss/gain 25589 15099 2986 1618

12 a) Infiltration 13929 2590 2560 476b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 4 920 0 0Appliances/other 2600 0

Subtotal (lines 6 to 13) 39518 21209 5546 2094

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 39518 21209 5546 209415 Duct loads 12% 11% 4622 2272 12% 11% 649 224

Total room load 44141 23481 6195 2318Air required (cfm)Air required (cfm) 1050 1050 147 104

Page 10: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 2...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire House PE Load Calcs, LLCBy:

1 Room name Master Guest22 Exposed wall 33.5 ft 17.0 ft3 Room height 8.0 heat/coolft 8.0 heat/coolft4 Room dimensions ft273.0x1.0 ft216.5x1.05 Room area 273.0 ft² 216.5 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Loadnumber (Btuh/ft²-°F)(Btuh/ft²-°F) (Btuh/ft²)(Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12B-0bw12B-0bw 0.0970.097 nene 4.664.66 1.481.48 0 0 0 0 136 126 586 187. GG 10A-w10A-w 0.8200.820 nene 39.3639.36 27.7027.70 0 0 0 0 0 0 0 0. GG 4A4-2ov4A4-2ov 0.3200.320 nene 15.3615.36 18.8918.89 0 0 0 0 10 0 157 193. WW 12B-0bw12B-0bw 0.0970.097 sese 4.664.66 1.481.48 124 124 577 184 0 0 0 0

11 GG 4A4-2ov4A4-2ov 0.3200.320 sese 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0WW 12B-0bw12B-0bw 0.0970.097 swsw 4.664.66 1.481.48 144 120 556 177 0 0 0 0

GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 21.2021.20 25 0 376 520 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 10.2910.29 0 0 0 0 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 11.5511.55 0 0 0 0 0 0 0 0DD 11G011G0 0.5400.540 swsw 25.9225.92 15.7115.71 0 0 0 0 0 0 0 0

WW 12B-0bw12B-0bw 0.0970.097 nwnw 4.664.66 1.481.48 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0

DD 11G011G0 0.5400.540 nn 25.9225.92 18.3618.36 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0CC 16B-19ad16B-19ad 0.0490.049 -- 2.352.35 2.582.58 273 273 642 704 217 217 509 558FF 19A-0cvcp19A-0cvcp 0.2950.295 -- 5.325.32 1.901.90 273 273 1452 517 217 217 1152 410

6 c) AED excursion 43 -59

Envelope loss/gain 3604 2145 2403 1289

12 a) Infiltration 2907 541 1475 274b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 6512 2686 3879 1563

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 6512 2686 3879 156315 Duct loads 12% 11% 762 288 12% 11% 454 167

Total room load 7273 2973 4332 1730Air required (cfm)Air required (cfm) 173 133 103 77

Page 11: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 3...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire House PE Load Calcs, LLCBy:

1 Room name Mbath Hall2 Exposed wall 6.0 ft 6.0 ft3 Room height 8.0 heat/coolft 8.0 heat/coolft4 Room dimensions ft13.5x6.0 ft139.0x1.05 Room area 81.0 ft² 139.0 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Loadnumber (Btuh/ft²-°F)(Btuh/ft²-°F) (Btuh/ft²)(Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12B-0bw12B-0bw 0.0970.097 nene 4.664.66 1.481.48 0 0 0 0 0 0 0 0. GG 10A-w10A-w 0.8200.820 nene 39.3639.36 27.7027.70 0 0 0 0 0 0 0 0. GG 4A4-2ov4A4-2ov 0.3200.320 nene 15.3615.36 18.8918.89 0 0 0 0 0 0 0 0. WW 12B-0bw12B-0bw 0.0970.097 sese 4.664.66 1.481.48 0 0 0 0 0 0 0 0

11 GG 4A4-2ov4A4-2ov 0.3200.320 sese 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0WW 12B-0bw12B-0bw 0.0970.097 swsw 4.664.66 1.481.48 48 43 200 64 48 27 126 40

GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 21.2021.20 5 0 79 109 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 10.2910.29 0 0 0 0 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 11.5511.55 0 0 0 0 0 0 0 0DD 11G011G0 0.5400.540 swsw 25.9225.92 15.7115.71 0 0 0 0 21 21 544 330

WW 12B-0bw12B-0bw 0.0970.097 nwnw 4.664.66 1.481.48 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0

DD 11G011G0 0.5400.540 nn 25.9225.92 18.3618.36 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0CC 16B-19ad16B-19ad 0.0490.049 -- 2.352.35 2.582.58 81 81 191 209 139 139 327 358FF 19A-0cvcp19A-0cvcp 0.2950.295 -- 5.325.32 1.901.90 81 81 431 153 139 139 739 263

6 c) AED excursion 5 -61

Envelope loss/gain 900 539 1736 931

12 a) Infiltration 521 97 521 97b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 0 0Appliances/other 0 0

Subtotal (lines 6 to 13) 1421 636 2257 1028

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 1421 636 2257 102815 Duct loads 12% 11% 166 68 12% 11% 264 110

Total room load 1587 704 2521 1138Air required (cfm)Air required (cfm) 38 31 60 51

Page 12: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 4...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire House PE Load Calcs, LLCBy:

1 Room name Dining Kitchen2 Exposed wall 11.0 ft 10.0 ft3 Room height 8.0 heat/coolft 8.0 heat/coolft4 Room dimensions ft12.5x11.0 ft12.5x10.05 Room area 137.5 ft² 125.0 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Loadnumber (Btuh/ft²-°F)(Btuh/ft²-°F) (Btuh/ft²)(Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12B-0bw12B-0bw 0.0970.097 nene 4.664.66 1.481.48 0 0 0 0 0 0 0 0. GG 10A-w10A-w 0.8200.820 nene 39.3639.36 27.7027.70 0 0 0 0 0 0 0 0. GG 4A4-2ov4A4-2ov 0.3200.320 nene 15.3615.36 18.8918.89 0 0 0 0 0 0 0 0. WW 12B-0bw12B-0bw 0.0970.097 sese 4.664.66 1.481.48 0 0 0 0 0 0 0 0

11 GG 4A4-2ov4A4-2ov 0.3200.320 sese 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0WW 12B-0bw12B-0bw 0.0970.097 swsw 4.664.66 1.481.48 88 54 253 81 80 69 320 102

GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 10.2910.29 0 0 0 0 11 11 175 117GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 11.5511.55 34 34 518 390 0 0 0 0DD 11G011G0 0.5400.540 swsw 25.9225.92 15.7115.71 0 0 0 0 0 0 0 0

WW 12B-0bw12B-0bw 0.0970.097 nwnw 4.664.66 1.481.48 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0

DD 11G011G0 0.5400.540 nn 25.9225.92 18.3618.36 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 100 100 466 330CC 16B-19ad16B-19ad 0.0490.049 -- 2.352.35 2.582.58 138 138 323 354 125 125 294 322FF 19A-0cvcp19A-0cvcp 0.2950.295 -- 5.325.32 1.901.90 138 138 731 261 125 125 665 237

6 c) AED excursion 436 -2

Envelope loss/gain 1826 1521 1919 1106

12 a) Infiltration 955 178 868 161b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 1 230 1 230Appliances/other 0 1200

Subtotal (lines 6 to 13) 2780 1928 2787 2697

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 2780 1928 2787 269715 Duct loads 12% 11% 325 207 12% 11% 326 289

Total room load 3106 2135 3113 2986Air required (cfm)Air required (cfm) 74 95 74 134

Page 13: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 5...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire House PE Load Calcs, LLCBy:

1 Room name Laundry Living2 Exposed wall 6.0 ft 29.0 ft3 Room height 8.0 heat/coolft 8.0 heat/coolft4 Room dimensions ft9.0x6.0 ft13.0x29.05 Room area 54.0 ft² 377.0 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area (ft²) Loadnumber (Btuh/ft²-°F)(Btuh/ft²-°F) (Btuh/ft²)(Btuh/ft²) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh)

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 WW 12B-0bw12B-0bw 0.0970.097 nene 4.664.66 1.481.48 48 48 223 71 232 148 689 220. GG 10A-w10A-w 0.8200.820 nene 39.3639.36 27.7027.70 0 0 0 0 84 0 3306 2327. GG 4A4-2ov4A4-2ov 0.3200.320 nene 15.3615.36 18.8918.89 0 0 0 0 0 0 0 0. WW 12B-0bw12B-0bw 0.0970.097 sese 4.664.66 1.481.48 0 0 0 0 0 0 0 0

11 GG 4A4-2ov4A4-2ov 0.3200.320 sese 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0WW 12B-0bw12B-0bw 0.0970.097 swsw 4.664.66 1.481.48 0 0 0 0 0 0 0 0

GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 21.2021.20 0 0 0 0 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 10.2910.29 0 0 0 0 0 0 0 0GG 4A4-2ov4A4-2ov 0.3200.320 swsw 15.3615.36 11.5511.55 0 0 0 0 0 0 0 0DD 11G011G0 0.5400.540 swsw 25.9225.92 15.7115.71 0 0 0 0 0 0 0 0

WW 12B-0bw12B-0bw 0.0970.097 nwnw 4.664.66 1.481.48 0 0 0 0 0 0 0 0PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 72 72 335 237 120 99 461 327

DD 11G011G0 0.5400.540 nn 25.9225.92 18.3618.36 0 0 0 0 21 21 544 386PP 12B-0sw12B-0sw 0.0970.097 -- 4.664.66 3.303.30 0 0 0 0 0 0 0 0CC 16B-19ad16B-19ad 0.0490.049 -- 2.352.35 2.582.58 54 54 127 139 377 377 887 972FF 19A-0cvcp19A-0cvcp 0.2950.295 -- 5.325.32 1.901.90 54 54 287 102 377 377 2005 714

6 c) AED excursion -64 -201

Envelope loss/gain 973 486 7893 4744

12 a) Infiltration 521 97 2517 468b) Room ventilation 0 0 0 0

13 Internal gains: Occupants @ 230230 0 0 2 460Appliances/other 500 900

Subtotal (lines 6 to 13) 1494 1083 10409 6572

Less external loadLess external load 0 0 0 0Less transferLess transfer 0 0 0 0RedistributionRedistribution 0 0 0 0

14 Subtotal 1494 1083 10409 657215 Duct loads 12% 11% 175 116 12% 11% 1218 704

Total room load 1668 1199 11627 7276Air required (cfm)Air required (cfm) 40 54 277 325

Page 14: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.2014-Dec-19 13:05:27

Right-Suite® Universal 2015 15.0.07 RSU18218 Page 6...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

0001Job:Right-J® WorksheetNov 24, 2014Date:Entire HousePE Load Calcs, LLCBy:

1 Room name Bath2 Exposed wall 12.5 ft3 Room height 8.0 heat/coolft4 Room dimensions ft13.5x8.05 Room area 108.0 ft²

Ty Construction U-value Or HTM Area (ft²) Load Area Loadnumber (Btuh/ft²-°F) (Btuh/ft²) or perimeter (ft) (Btuh) or perimeter

Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool

6 W 12B-0bw 0.097 ne 4.66 1.48 0 0 0 0. G 10A-w 0.820 ne 39.36 27.70 0 0 0 0. G 4A4-2ov 0.320 ne 15.36 18.89 0 0 0 0. W 12B-0bw 0.097 se 4.66 1.48 0 0 0 0

11 G 4A4-2ov 0.320 se 15.36 21.20 0 0 0 0W 12B-0bw 0.097 sw 4.66 1.48 64 59 274 87

G 4A4-2ov 0.320 sw 15.36 21.20 5 0 79 109G 4A4-2ov 0.320 sw 15.36 10.29 0 0 0 0G 4A4-2ov 0.320 sw 15.36 11.55 0 0 0 0D 11G0 0.540 sw 25.92 15.71 0 0 0 0

W 12B-0bw 0.097 nw 4.66 1.48 36 36 168 53P 12B-0sw 0.097 - 4.66 3.30 0 0 0 0

D 11G0 0.540 n 25.92 18.36 0 0 0 0P 12B-0sw 0.097 - 4.66 3.30 0 0 0 0C 16B-19ad 0.049 - 2.35 2.58 108 108 254 278F 19A-0cvcp 0.295 - 5.32 1.90 108 108 574 205

6 c) AED excursion -12

Envelope loss/gain 1349 720

12 a) Infiltration 1085 202b) Room ventilation 0 0

13 Internal gains: Occupants @ 230 0 0Appliances/other 0

Subtotal (lines 6 to 13) 2434 922

Less external load 0 0Less transfer 0 0Redistribution 0 0

14 Subtotal 2434 92215 Duct loads 12% 11% 285 99

Total room load 2719 1021Air required (cfm) 65 46

Page 15: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Bold/italic values have been manually overridden

2014-Dec-19 13:05:28Right-Suite® Universal 2015 15.0.07 RSU18218 Page 1

...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

Duct System SummaryEntire House

Job: 0001Date: Nov 24, 2014By: PE Load Calcs, LLC

Project InformationFor: Joe Chen, Homeowner

7007 Lystra Rd, Harrison, TN 37341 Phone: (423) Email: tiu

CoolingHeatingExternal static pressure in H2O0.56in H2O0.56Pressure losses in H2O0.30in H2O0.30Available static pressure in H2O0.26in H2O0.26Supply / return available pressure 0.205 / 0.055 in H2O in H2O0.205 / 0.055Lowest friction rate in/100ft0.094in/100ft0.094Actual air flow cfm1050cfm1050Total effective length (TEL) ft277

Supply Branch Detail Table

Design Htg Clg Design Diam H x W Duct Actual Ftg.EqvName (Btuh) (cfm) (cfm) FR (in) (in) Matl Ln (ft) Ln (ft) Trunk

st2110.038.5ShMt0x05.00.13846652719hBath

st2110.047.0ShMt0x05.00.13148371067cDining-A

st2A125.053.0ShMt0x05.00.11548371067cDining-B

st3100.047.0ShMt0x05.00.14052743097hGuest1-A

st3A100.046.5ShMt0x05.00.14052743097hGuest1-B

st2115.039.0ShMt0x06.00.133771034332hGuest2-A

st2105.037.5ShMt0x05.00.14451602521hHall-A

st2B140.060.0ShMt0x07.00.103134742986cKitchen-A

st2B150.068.5ShMt0x05.00.09454401199cLaundry-A

st290.051.5ShMt0x07.00.1451631383638cLiving-A

st2A115.066.5ShMt0x07.00.1131631383638cLiving-B

st3155.036.5ShMt0x06.00.10766873637hMaster-A

st3105.040.5ShMt0x06.00.14166873637hMaster-B

st2120.031.5ShMt0x04.00.13531381587hMbath-A

Supply Trunk Detail Table

Trunk Htg Clg Design Veloc Diam H x W DuctName Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk

st2 Peak AVF 730 813 0.094 813 12.9 18x8 ShtMetl st1st3 Peak AVF 320 237 0.107 577 8.9 10x8 ShtMetl st1st1 Peak AVF 1050 1050 0.094 788 14.2 24x8 ShtMetlst2A Peak AVF 289 398 0.094 596 9.9 12x8 ShtMetl st2st2B Peak AVF 114 187 0.094 421 7.5 8x8 ShtMetl st2Ast3A Peak AVF 74 52 0.140 166 4.9 8x8 ShtMetl st3

Page 16: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

2014-Dec-19 13:05:28Right-Suite® Universal 2015 15.0.07 RSU18218 Page 2

...anian\Documents\Wrightsoft HVAC\7007 Lystra.rup Calc = MJ8 Front Door faces: N

Return Branch Detail Table

Grill Htg Clg TEL Design Veloc Diam H x W Stud/Joist DuctName Size (in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening (in) Matl Trunk

rb2 22x 105034 1050 58.5 0.094 594 18.0 x0 0 ShMt

Page 17: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Friction Rate Worksheet From ACCA’s Manual D

Step 1) Manufacturer’s Blower Data

External static pressure (ESP) = ______ IWC Cfm = __________

Step 2) Component Pressure Losses (CPL)

Direct expansion refrigerant coil ______ Electric resistance heating coil ______ Hot water coil ______ Heat exchanger ______ Low efficiency filter ______ High or mid-efficiency filter ______ Electronic filter ______ Humidifier, UV lights, other ______ Supply outlet ______ Return grille ______ Balancing damper ______ Zone damper (full open) ______

Total component losses (CPL) ______ IWC

Step 3) Available Static Pressure (ASP)

ASP = (ESP - CPL) = ( ______ - _______ ) = _______ IWC

Step 4) Total Effective Length (TEL)

Supply-side TEL + Return-side TEL = ( _______ + _______ ) = _______ Feet

Step 5) Friction Rate Design Value (FR)

FR value from friction rate chart = ______ IWC/100

FR = 100 x ASP / TEL

0.560 1,050

0.210

0.030

0.030

0.030

0.300

0.560 0.300 0.260

219 59 278

0.094

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

Page 18: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Job #: 0001Performed by Anthony Amadio for:

Joe Chen7007 Lystra Rd

Harrison, TN 37341 Phone: (423)

PE Load Calcs, LLC Scale: 1 : 100

Page 1Right-Suite® Universal 2015

15.0.07 RSU182182014-Dec-19 16:39:14

...\Wrightsoft HVAC\7007 Lystra.rup

N

Sheet 1

Guest1

Master

Guest2

MbathBath

Hall

Dining

Living

Kitchen

Laundry

Garage

74 cfm

87 cfm

134 cfm

54 cfm

87 cfm

74 cfm 103 cfm

48 cfm

163 cfm163 cfm

48 cfm

60 cfm

38 cfm 65 cfm

5 "

5 "

7 "

5 "

5 "

5 "

5 "

7 "

6 "

6 " 4 "

7 "6 "

24 x 8

T

VD VD VD VD VD VD

VD VD

VD

VD VD VD VD VD

18 x 8

4 x 8 10 x 85 "

12 x 8

18 "

6 x 8

www.peloadcalcs.com1462 Bridge Drive

Collierville, TN 38017Phone: (901) 257-5910

Email: [email protected]

77 cfm, 4"x10"

77 cfm, 4"x10"

63 cfm, 4"x8"

63 cfm4"x8"

90 cfm, 4"x12"

56 cfm, 2"x14"35 cfm, 2"x12"

1050 cfm, 24"x30"

56 cfm2"x14"

42 cfm, 2"x12"

104 cfm, 6"x10"

42 cfm, 2"x12"

150 cfm, 6"x14"150 cfm6"x14"

47 cfm2"x12"

All Isolated Rooms shall have 8"x14" Transfer Grills above Doors in order to allow mixed room air flow to the Central Return.

Place edge of Floor Registers at about 9" - 10" from finished wall.

Recommended Central Thermostat location in the Dining Room, far from windows, on interior wall and 5' above floor.

Plenum should extend 12"-15" beyond last run-out.

All Metal Duct Dimensions are Inner Dimensions.

Page 19: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

*Air Volume Balance Report FormFor Quality Installation Verification

PROJECT INFORMATION

New or Existing Residential or Commercial

Building Address:

City, State and Zip:

Construction Type:

Technician Name:

Date and Time:

Testing Methods:

Make and Models:

Serial Numbers:

Calibration Dates:

Additional Notes: Temp: Altitude:

HEAT EXCHANGER - 1st Floor

HVAC Equipment:

Total Design Airflow per Manual J Design Report:

Design Blower Speed per Manual J Design Report: Design ESP ("wc):

*Measured Total CFM through the Heat Exchanger: **Measured ESP:

* The Technician should follow all Manufacturer’s installation instructions, local codes, as well as follow the guidelines from ACCAStandards 5 & 9. Before measuring any airflow, a thorough inspection of the duct system must be completed which includes:

1. Visual inspection to see that all ducts have been connected, sealed and are sized and laid out correctly per design report, allbranch dampers and supply terminals are installed and in the fully open position, and a new clean air filter has been installed.

2. A duct leakage test (via duct blower) that meets the more stringent of the of either the (a) 2012 IECC leakage requirements,(b) ACCA Standard 5 requirements, or (c) local code.

**If the measured total CFM through the heat exchanger is less than 85% of the design, or the ESP greater than 25% of design, at the selected design speed. Stop and go back and repeat the duct system inspection. Remember, all dampers & supply grilles should be fully open, and air filter and coils and fan should all be clean. If the problem still cannot be determined, then increase to the next blower speed setting and repeat the heat exchanger airflow measurement. Please note that it is desirable to have a 10-15% excess CFM measurement through the heat exchanger for this allows a margin for balancing the supplies since damper adjustments from the fully-open position will increase the resistance (ESP) thereby reducing the total heat exchanger airflow.

Page 1 of 2

7007 Lystra Road

Harrison TN 37341

E R

Goodman Packaged Heat Pump GPH1436H41C

1050 cfm

T2 0.56

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

Page 20: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

SUPPLY BRANCHES

Per ACCA Standard 5, individual room CFM are to be within ± 10%, or 25 CFM, whichever is greater, of its target CFM for the supply and return ducts. For existing construction, and existing ductwork without contractor modification, terminal CFM balancing is not required, unless otherwise specified by local code.

Room / Duct Terminal Location Target Airflow Test 1/ Final Test 2 / Final Test 3 / Final % Target

Total Airflow: Final Total: % Target Total:

Where % Target = 1 – 100 X ( Final CFM / Target CFM )

*** The Target Airflow may not necessarily be the design airflow from the design report, which was used solely for the purpose of sizing the duct design. The Target Airflow may be the averaged, or normalized average, of the design heating and cooling airflow values.

IO

Page 2 of 2

Living Room 1 150

Living Room 2 150

Dining Room 1 42

Dining Room 2 42

Hall 56

Kitchen 104

Laundry 47

Master 1 77

Master 2 77

MBath 35

Bath 56

Guest1 1 63

Guest1 2 63

Guest2 90

1,052

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

Page 21: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Equipment Bill of Materials Page 1 of 2

Equipment Qty GPH1436H41C 1 5 kW Heat Kit w/ Circuit Breaker 3 Nest Thermostat 1

Duct System Equipment Qty 14" x 8" Return Grilles above Room Doors 12 End cap for rectangular metal duct, 8"x8" 2 Floor horiz boot from round duct, size 4" 1 Floor horiz boot from round duct, size 5" 7 Floor horiz boot from round duct, size 6" 3 Floor horiz boot from round duct, size 7" 3 Manual Round Balance Damper, 4" 1 Manual Round Balance Damper, 5" 7 Manual Round Balance Damper, 6" 3 Manual Round Balance Damper, 7" 3 Plenum rect tapered take off, size 24"x8" 1 Plenum side round take off, size 18" 1 Rect tee, size 1208-0807 1 Rect tee, size 1808-0807 1 Rect to rect transition, size 10" x 8"-8" x 8" 1 Rect to rect transition, size 12" x 8"-8" x 8" 1 Rect to rect transition, size 18" x 8"-12" x 8" 1 Rect wye, size 2408-1808 1 Rectangular metal duct, 10" x 8" 16 Rectangular metal duct, 12" x 8" 11 Rectangular metal duct, 14" x 8" 4 Rectangular metal duct, 18" x 8" 21 Rectangular metal duct, 24" x 8" 20 Rectangular metal duct, 8" x 8" 12

Page 1 of 2

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

All Duct Dimensions are Inner Duct Dimensions.

Page 22: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

Equipment Bill of Materials Page 2 of 2

Duct System Equipment cont… Qty Rectangular metal floor two way grill, 10" x 6" 1 Rectangular metal floor two way grill, 10"x4" 2 Rectangular metal floor two way grill, 12" x 2" 4 Rectangular metal floor two way grill, 12"x4" 1 Rectangular metal floor two way grill, 14" x 2" 2 Rectangular metal floor two way grill, 14"x6" 2 Rectangular metal floor two way grill, 8"x4" 2 Return boot from round duct, size 18" 1 Return duct plenum, size = 25"x19", len = 18" 1 Round 5-piece elbow, size 18" 1 Round 5-piece elbow, size 4" 1 Round 5-piece elbow, size 5" 7 Round 5-piece elbow, size 6" 3 Round 5-piece elbow, size 7" 3 Round metal duct, D = 18" 14 Round metal duct, D = 4" 11 Round metal duct, D = 5" 65 Round metal duct, D = 6" 27 Round metal duct, D = 7" 34 Round tee, size 1008-0806 1 Side round transition take off, size 4" 1 Side round transition take off, size 5" 7 Side round transition take off, size 6" 2 Side round transition take off, size 7" 1

Page 2 of 2

PE LOAD CALCS, LLC901.257.5910

www.peloadcalcs.com [email protected]

All Duct Dimensions are Inner Duct Dimensions.

Page 23: RESIDENTIAL HVAC SYSTEM DESIGN REPORT - PE …peloadcalcs.com/wp-content/uploads/2015/01/PE-Load-Calcs-LLC-De… · Equipment Selection Form . From ACCA’s Manual S . PROJECT INFORMATION

ASHRAE 62.2 Report

PROJECT INFORMATION

Name: Company: Phone: Email: Building Address: City, State and Zip: New or Existing:

ASHRAE 62.2 DATA

Floor Area (Square Feet): # of Bedrooms: *Combustion CFM Threshold:

*If the sum of the highest flow rate of the two largest fans exceeds the Combustion CFM Threshold, then make-up air must be supplied to any atmospherically vented appliance.

Whole Building Ventilation Type: Continuous or Intermittent Control: ASHRAE Weather Location: Target CFM-50 (0.35 ACH):

Blower Door (CFM-50): ACH-50: ACH-N:

New Building CFM Required: Existing Building CFM Required:

Measured Mechanical Ventilation Flow:

Designer Notes: .

These calculations were made to determine the correct mechanical ventilation flow rate based on the ASHRAE 62.2-2013 Standard.

PE LOAD CALCS, LLC 901.257.5910

www.peloadcalcs.com [email protected]

Joe Chen

Homeowner

423 tiu

7007 Lystra Rd

Harrison TN 37341

Existing

1730

3

260

None

NA

Chattanooga TN

1585

2700

11.7

0.60

24

NA

Homeowner declines to have a new mechanical ventilation system installed at this time