residential/commercial generator sets - wholesale solar...on or near the generator set. never...

40
Residential/Commercial Generator Sets Model: 12RES Controller: Advanced Digital Control ADC-RES TP-6967 8/15 Installation

Upload: others

Post on 27-May-2020

16 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

Residential/Commercial Generator Sets

Model:

12RES

Controller:Advanced Digital Control ADC-RES

TP-6967 8/15

Installation

Page 2: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

Engine exhaust from this product contains chemicalsknown to the State of California to cause cancer, birthdefects, or other reproductive harm.

WARNINGCalifornia Proposition 65

Kohler strongly recommendsthat only factory-authorizeddistributors or dealers installand service the generator.

Product Identification Information

Generator Set Identification NumbersRecord the product identification numbers from thegenerator set nameplate(s).

Model Designation

Specification Number

Serial Number

Accessory Number Accessory Description

Engine IdentificationRecord the product identification information from theengine nameplate.

Manufacturer

Model Designation

Serial Number

Controller IdentificationRecord the controller description from the generator setoperation manual, spec sheet, or sales invoice.

Controller Description

Page 3: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

Table of Contents

TP-6967 8/15 Table of Contents 3

Product Identification Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety Precautions and Instructions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service Assistance 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 1 Installation 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.1 Introduction 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.2 Lifting 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.3 Generator Set Inspection 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4 Location and Mounting 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4.1 Exhaust Requirements 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.4.2 Air Requirements 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Power Supply 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.6 Fuel Requirements 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.6.1 Fuel Supply 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.6.2 Fuel Pipe Size 14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.7 Fuel Conversion 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.7.1 Fuel Conversion 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.8 Electrical Connections 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8.1 Field Connections 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8.2 Remote Start Connection 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8.3 Grounding 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.8.4 Battery Charger 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.9 Battery 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.10 Accessories 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.10.1 Common Fault and Auxiliary Run Relay Board 21. . . . . . . . . . . . . . . . . . . . .1.10.2 Carburetor Heater 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.11 Prestart Installation Check 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.12 Startup Notification 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.13 Controller Configuration 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.13.1 System Parameters 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.13.2 Application Code Version 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.14 Voltage and Frequency Adjustments 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.14.1 Voltage Adjustment 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1.14.2 Frequency Adjustment 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 2 Dimension Drawings and Wiring Diagrams 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix A Abbreviations 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/154

Notes

Page 5: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 5Safety Precautions and Instructions

Safety Precautions and Instructions

IMPORTANTSAFETY INSTRUCTIONS.Electromechanical equipment,including generator sets, transferswitches, switchgear, and accessories,can cause bodily harm and poselife-threatening danger whenimproperly installed, operated, ormaintained. To prevent accidents beaware of potential dangers and actsafely. Read and follow all safetyprecautions and instructions. SAVETHESE INSTRUCTIONS.

Thismanual has several types of safetyprecautions and instructions: Danger,Warning, Caution, and Notice.

DANGER

Danger indicates the presence of ahazard that will cause severepersonal injury, death, orsubstantialproperty damage.

WARNING

Warning indicates the presence of ahazard that can cause severepersonal injury, death, orsubstantialproperty damage.

CAUTION

Caution indicates the presence of ahazard that will or can cause minorpersonal injury or property damage.

NOTICENotice communicates installation,operation, or maintenance informationthat is safety related but not hazardrelated.

Safety decals affixed to the equipmentin prominent places alert the operatoror service technician to potentialhazards and explain how to act safely.The decals are shown throughout thispublication to improve operatorrecognition. Replace missing ordamaged decals.

Accidental Starting

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set.Accidental starting can causesevere injury or death. Beforeworking on the generator set orconnected equipment, disable thegenerator set as follows: (1) Move thegenerator set master switch to the OFFposition. (2) Disconnect the power tothe battery charger. (3) Remove thebattery cables, negative (--) lead first.Reconnect the negative (--) lead lastwhen reconnecting the battery. Followthese precautions to prevent starting ofthe generator set by an automatictransfer switch, remote start/stopswitch, or engine start command fromaremote computer.

Battery

Sulfuric acid in batteries.Can cause severe injury or death.

Wear protective goggles andclothing. Battery acid may causeblindness and burn skin.

WARNING

Explosion.Can cause severe injury or death.Relays in the battery chargercause arcs or sparks.

Locate the battery in a well-ventilatedarea. Isolate the battery charger fromexplosive fumes.

WARNING

Battery electrolyte is a dilutedsulfuric acid. Battery acid cancausesevere injury or death. Battery acidcan cause blindness and burn skin.Always wear splashproof safetygoggles, rubber gloves, and bootswhen servicing the battery. Do notopen a sealed battery or mutilate thebattery case. If battery acid splashes inthe eyes or on the skin, immediatelyflush the affected area for 15 minuteswith large quantities of clean water.Seek immediatemedical aid in the caseof eye contact. Never add acid to abattery after placing the battery inservice, as this may result in hazardousspattering of battery acid.

Battery acid cleanup. Battery acidcan cause severe injury or death.Battery acid is electrically conductiveand corrosive. Add 500 g (1 lb.) ofbicarbonate of soda (baking soda) to acontainer with 4 L (1 gal.) of water andmix the neutralizing solution. Pour theneutralizing solution on the spilledbattery acid and continue to add theneutralizing solution to the spilledbattery acid until all evidence of achemical reaction (foaming) hasceased. Flush the resulting liquid withwater and dry the area.

Page 6: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/156 Safety Precautions and Instructions

Battery gases. Explosion can causesevere injury or death. Battery gasescan cause an explosion. Do not smokeor permit flames or sparks to occur neara battery at any time, particularly whenit is charging. Do not dispose of abattery in a fire. To prevent burns andsparks that could cause an explosion,avoid touching the battery terminalswith tools or other metal objects.Remove all jewelry before servicing theequipment. Discharge static electricityfrom your body before touchingbatteries by first touching a groundedmetal surface away from thebattery. Toavoid sparks, do not disturb the batterycharger connections while the batteryis charging. Always turn the batterycharger off before disconnecting thebattery connections. Ventilate thecompartments containing batteries toprevent accumulation of explosivegases.

Battery short circuits. Explosioncan cause severe injury or death.Short circuits can cause bodily injuryand/or equipment damage.Disconnect the battery beforegenerator set installation ormaintenance. Remove all jewelrybefore servicing the equipment. Usetools with insulated handles. Removethe negative (--) lead first whendisconnecting the battery. Reconnectthe negative (--) lead last whenreconnecting the battery. Neverconnect the negative (--) battery cableto the positive (+) connection terminalof the starter solenoid. Do not test thebattery condition by shorting theterminals together.

Engine Backfire/FlashFire

Risk of fire.Can cause severe injury or death.

Do not smoke or permit flames orsparks near fuels or the fuel system.

WARNING

Servicing the air cleaner. A suddenbackfire can cause severe injury ordeath. Do not operate the generatorset with the air cleaner removed.

Servicing the fuel system. A flashfire cancausesevere injuryor death.Do not smoke or permit flames orsparks near the carburetor, fuel line,fuel filter, fuel pump, or other potentialsources of spilled fuels or fuel vapors.Catch fuels in an approved containerwhen removing the fuel line orcarburetor.

Combustible materials. A fire cancause severe injury or death.Generator set engine fuels and fuelvapors are flammable and explosive.Handle these materials carefully tominimize the risk of fire or explosion.Equip the compartment or nearby areawith a fully charged fire extinguisher.Select a fire extinguisher rated ABC orBC for electrical fires or asrecommended by the local fire code oran authorized agency. Train allpersonnel on fire extinguisheroperation and fire preventionprocedures.

Exhaust System

Carbon monoxide.Can cause severe nausea,fainting, or death.

The exhaust system must beleakproof and routinely inspected.

WARNING

Generator set operation. Carbonmonoxide can cause severe nausea,fainting, or death. Carbon monoxideis an odorless, colorless, tasteless,nonirritating gas that can cause death ifinhaled for even a short time. Avoidbreathing exhaust fumeswhenworkingon or near the generator set. Neveroperate the generator set inside abuilding. Never operate the generatorset where exhaust gas could seepinside or be drawn into a potentiallyoccupied building through windows, airintake vents, or other openings.

Carbon monoxide detectors.Carbon monoxide can cause severenausea, fainting, or death. Installcarbon monoxide detectors on eachlevel of any building adjacent to thegenerator set. Locate the detectors toadequately warn the building’soccupants of the presence of carbonmonoxide. Keep the detectorsoperational at all times. Periodicallytest and replace the carbon monoxidedetectors according to themanufacturer’s instructions.

Carbon monoxide symptoms.Carbon monoxide can cause severenausea, fainting, or death. Carbonmonoxide is a poisonous gas present inexhaust gases. Carbonmonoxide is anodorless, colorless, tasteless,nonirritating gas that can cause death ifinhaled for even a short time. Carbonmonoxide poisoning symptoms includebut are not limited to the following:D Light-headedness, dizzinessD Physical fatigue, weakness injoints and muscles

D Sleepiness, mental fatigue,inability to concentrateor speak clearly, blurred vision

D Stomachache, vomiting, nauseaIf experiencing any of these symptomsand carbon monoxide poisoning ispossible, seek fresh air immediatelyand remain active. Do not sit, lie down,or fall asleep. Alert others to thepossibility of carbon monoxidepoisoning. Seek medical attention ifthe condition of affected persons doesnot improvewithinminutes of breathingfresh air.

Page 7: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 7Safety Precautions and Instructions

Fuel System

Explosive fuel vapors.Can cause severe injury or death.

Use extreme care when handling,storing, and using fuels.

WARNING

The fuel system. Explosive fuelvapors can cause severe injury ordeath. Vaporized fuels are highlyexplosive. Use extreme care whenhandling and storing fuels. Store fuelsin a well-ventilated area away fromspark-producing equipment and out ofthe reach of children. Never add fuel tothe tank while the engine is runningbecause spilled fuel may ignite oncontact with hot parts or from sparks.Do not smoke or permit flames orsparks to occur near sources of spilledfuel or fuel vapors. Keep the fuel linesand connections tight and in goodcondition. Do not replace flexible fuellines with rigid lines. Use flexiblesections to avoid fuel line breakagecausedby vibration. Donot operate thegenerator set in the presence of fuelleaks, fuel accumulation, or sparks.Repair fuel systems before resuminggenerator set operation.

Gas fuel leaks. Explosive fuelvapors can cause severe injury ordeath. Fuel leakage can cause anexplosion. Check the LPG vapor ornatural gas fuel system for leakage byusing a soap and water solution withthe fuel system test pressurized to6--8 ounces per square inch(10--14 inches water column). Do notuse a soap solution containing eitherammonia or chlorine because bothprevent bubble formation. A successfultest depends on the ability of thesolution to bubble.

Hazardous Noise

Hazardous noise.Can cause hearing loss.

Never operate the generator setwithout a muffler or with a faultyexhaust system.

CAUTION

Engine noise. Hazardous noise cancause hearing loss. Generator setsnot equipped with sound enclosurescan produce noise levels greater than105 dBA. Prolonged exposure to noiselevels greater than 85 dBA can causepermanent hearing loss. Wear hearingprotection when near an operatinggenerator set.

Hazardous Voltage/Moving Parts

Hazardous voltage.Will cause severe injury or death.

This equipment must be installed andserviced by qualified electricalpersonnel.

DANGER

Hazardous voltage.Can cause severe injury or death.

Operate the generator set only whenall guards and electrical enclosuresare in place.

Moving parts.

WARNING

Hazardous voltage.Backfeed to the utility system cancause property damage, severeinjury, or death.

If the generator set is used forstandby power, install an automatictransfer switch to prevent inadvertentinterconnection of standby andnormal sources of supply.

WARNING

Welding the generator set.Can cause severe electricalequipment damage.

Never weld components of thegenerator set without firstdisconnecting the battery, controllerwiring harness, and engine electroniccontrol module (ECM).

CAUTION

Grounding electrical equipment.Hazardous voltage can causesevere injury or death. Electrocutionis possible whenever electricity ispresent. Ensure you comply with allapplicable codes and standards.Electrically ground the generator set,transfer switch, and related equipmentand electrical circuits. Turn off themaincircuit breakers of all power sourcesbefore servicing the equipment. Nevercontact electrical leads or applianceswhen standing in water or on wetground because these conditionsincrease the risk of electrocution.

Page 8: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/158 Safety Precautions and Instructions

Welding on the generator set. Cancause severe electrical equipmentdamage. Before welding on thegenerator set perform the followingsteps: (1) Remove the battery cables,negative (--) lead first. (2) Disconnectall engine electronic control module(ECM) connectors. (3) Disconnect allgenerator set controller and voltageregulator circuit board connectors.(4) Disconnect the engine battery-charging alternator connections.(5) Attach the weld ground connectionclose to the weld location.

Connecting the battery and thebattery charger. Hazardous voltagecan cause severe injury or death.Reconnect the battery correctly,positive to positive and negative tonegative, to avoid electrical shock anddamage to the battery charger andbattery(ies). Have a qualifiedelectrician install the battery(ies).

Short circuits. Hazardousvoltage/current can cause severeinjury or death. Short circuits cancause bodily injury and/or equipmentdamage. Do not contact electricalconnections with tools or jewelry whilemaking adjustments or repairs.Remove all jewelry before servicing theequipment.

Electrical backfeed to the utility.Hazardous backfeed voltage cancause severe injury or death. Installa transfer switch in standby powerinstallations to prevent the connectionof standby and other sources of power.Electrical backfeed into a utilityelectrical system can cause severeinjury or death to utility personnelworking on power lines.

Airborne particles.Can cause severe injury orblindness.

Wear protective goggles and clothingwhen using power tools, hand tools,or compressed air.

WARNING

Heavy Equipment

Unbalanced weight.Improper lifting can cause severeinjury or death and equipmentdamage.

Do not use lifting eyes.Lift the generator set using lifting barsinserted through the lifting holes onthe skid.

WARNING

Hot Parts

Hot engine and exhaust system.Can cause severe injury or death.

Do not work on the generator set untilit cools.

WARNING

Servicing the exhaust system. Hotparts can cause severe injury ordeath. Do not touch hot engine parts.The engine and exhaust systemcomponents become extremely hotduring operation.

Servicing the engine heater. Hotparts can cause minor personalinjury or property damage. Install theheater before connecting it to power.Operating the heater before installationcan cause burns and componentdamage. Disconnect power to theheater and allow it to cool beforeservicing the heater or nearby parts.

NoticeNOTICE

Canadian installations only. Forstandby service connect the output ofthe generator set to a suitably ratedtransfer switch in accordance withCanadian Electrical Code, Part 1.

Page 9: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 9

Introduction

This manual provides installation instructions for theModel 12RES generator set.

Kohler strongly recommends that only factory-authorized distributors or dealers install andservice the generator.

Have an authorized distributor/dealer install thegenerator set outdoors according to the instructions inthismanual. The generator set installationmust complywith the National Electrical Coder (NEC) and local coderequirements. Do not install this generator set indoors.

Information in this publication represents data availableat the time of print. Kohler Co. reserves the right tochange this publication and the products representedwithout notice and without any obligation or liabilitywhatsoever.

Read this manual and carefully follow all proceduresand safety precautions to ensure proper equipmentoperation and to avoid bodily injury. Readand follow theSafety Precautions and Instructions section at thebeginning of this manual.

The generator set is shown in Figure 1. See thedimension drawing in Section 2 for generator setcomponent locations.

Figure 1 Model 12RES Generator Set

National Electrical Code is a registered trademark of the National FireProtection Association, Inc.

List of Related LiteratureFigure 2 identifies related literature available for thegenerator sets covered in thismanual. Only trained andqualified personnel should install or service thegenerator set.

Literature Type Part Number

Specification Sheet, 12RES G4-248

Operation Manual, Generator Set TP-6515

Service Manual, Generator Set TP-6196

Service Manual, Engine 24 690 06

Parts Catalog TP-5868

Operation Manual, OnCuer for ADC TP-6616

Figure 2 Related Literature

Startup Notification

Complete the startup and installation checklistssupplied with the startup notification form. Completeand sign the startup notification form and register theunit using the Kohler online Warranty ProcessingSystem.

Page 10: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1510

Service Assistance

For professional advice on generator set powerrequirementsandconscientiousservice, pleasecontactyour nearest Kohler distributor or dealer.

D Consult the Yellow Pages under the headingGenerators—Electric.

D Visit the Kohler Power Systems website atKOHLERPower.com.

D Look at the labels and decals on your Kohler productor review the appropriate literature or documentsincluded with the product.

D Call toll free in the US and Canada 1-800-544-2444.

D Outside theUSandCanada, call the nearest regionaloffice.

Headquarters Europe, Middle East, Africa(EMEA)Kohler Power Systems Netherlands B.V.Kristallaan 14761 ZC ZevenbergenThe NetherlandsPhone: (31) 168 331630Fax: (31) 168 331631

Asia PacificPower Systems Asia Pacific Regional OfficeSingapore, Republic of SingaporePhone: (65) 6264-6422Fax: (65) 6264-6455

ChinaNorth China Regional Office, BeijingPhone: (86) 10 6518 7950

(86) 10 6518 7951(86) 10 6518 7952

Fax: (86) 10 6518 7955

East China Regional Office, ShanghaiPhone: (86) 21 6288 0500Fax: (86) 21 6288 0550

India, Bangladesh, Sri LankaIndia Regional OfficeBangalore, IndiaPhone: (91) 80 3366208

(91) 80 3366231Fax: (91) 80 3315972

Japan, KoreaNorth Asia Regional OfficeTokyo, JapanPhone: (813) 3440-4515Fax: (813) 3440-2727

Latin AmericaLatin America Regional OfficeLakeland, Florida, USAPhone: (863) 619-7568Fax: (863) 701-7131

Page 11: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 11Section 1 Installation

Section 1 Installation

1.1 Introduction

Hazardous voltage.Will cause severe injury or death.

This equipment must be installed andserviced by qualified electricalpersonnel.

DANGER

Carbon monoxide.Can cause severe nausea,fainting, or death.

The exhaust system must beleakproof and routinely inspected.

WARNING

Generator set operation. Carbon monoxide can causesevere nausea, fainting, or death. Carbon monoxide is anodorless, colorless, tasteless, nonirritating gas that can causedeath if inhaled for even a short time. Avoid breathing exhaustfumes when working on or near the generator set. Neveroperate the generator set inside a building. Never operate thegenerator set where exhaust gas could seep inside or bedrawn into a potentially occupied building throughwindows, airintake vents, or other openings.

Carbon monoxide detectors. Carbon monoxide cancause severe nausea, fainting, or death. Install carbonmonoxide detectors on each level of any building adjacent tothe generator set. Locate the detectors to adequately warn thebuilding’s occupants of the presence of carbon monoxide.Keep the detectors operational at all times. Periodically testand replace the carbon monoxide detectors according to themanufacturer’s instructions.

Have thegenerator set installedbyanauthorizedKohlerdistributor/dealer. For all locations, ensure that theinstallation complies with applicable national and localcodes. In theUnitedStates, the installationmust complywith the National Electrical Code (NEC) and allapplicable state and local codes. For Canadianinstallations, refer to the Canadian Electrical Code(CEC).

The generator set must be installed outdoors. Theexhaust systems on enclosed units are designed foroutdoor installation only.

Note: DO NOT install these generator sets inside abuilding.

Note: Install carbon monoxide (CO) detector(s) oneach level of any building adjacent to a generatorset. Locate the detectors to adequately warn thebuilding’s occupants of the presence of carbonmonoxide.

Obtain a building permit and contact your local utilitycompanies to mark the locations of underground pipesand cables.

Read and follow the safety precautions in this manualand observe the decals on the equipment. Refer to thediagrams and drawings in this manual for dimensionsand electrical connections during the installationprocedure. Read the entire installation procedure andobtain the accessories and tools needed beforebeginning installation. Perform the steps in the ordershown.

To install optional accessories, follow the instructionsprovided with each kit.

1.2 Lifting

Unbalanced weight.Improper lifting can cause severeinjury or death and equipmentdamage.

Do not use lifting eyes.Lift the generator set using lifting barsinserted through the lifting holes onthe skid.

WARNING

Model Weight, kg (lb.)

12RES 186 (410)

Figure 1-1 Approximate Weight

The approximate generator set weight is shown inFigure 1-1. Use lifting bars inserted through the holes inthe skid to lift the unit. See the dimension drawings inSection 2 for lifting hole locations.

Page 12: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1512 Section 1 Installation

1.3 Generator Set Inspection

Complete a thorough inspection of the generator set.Check for the following:

1. Inspect the generator set for loose or damagedparts or wires. Repair or tighten any loose partsbefore installation.

2. Check the engine oil. Fill, if necessary, with therecommended viscosity and grade of oil. Usesynthetic oil, API (American Petroleum Institute)Service Class SG or higher. See TP-6515,Operation Manual, for additional information.

1.4 Location and Mounting

Install the generator set outdoors near the incoming gasservice. The generator set location must allow easyaccess for maintenance and service. The requireddistance from a structure is dependent on state orprovince and local codes. See the dimension drawing inSection 2 for the minimum clearance from structuresand non-combustible materials.

Locate the generator set so that the hot exhaust doesnot blow on plants or other combustible materials. Noplants, shrubs, or other combustible materials areallowed within 1.2 m (4 ft.) of the exhaust end of thegenerator set.

Donot install the generator setwhere exhaust gas couldaccumulate and seep inside or be drawn into apotentially occupied building. Furnace and other similarintakes must be at least 3 m (10 ft.) from the exhaustend of the generator set.

NoticeDO NOT locate the generator set near patios,decks, play areas, or animal shelters. Keep itemssuch as lawn furniture, toys, sports equipment,and all combustible materials away from thegenerator set exhaust outlet.

Remind family members, children, and visitors touse caution near the generator set. Generatorsets connected to automatic transfer switchesstart automatically during exercise periods andpower outages. Some generator set componentsbecome hot when the generator set is running andremain hot for a time after the generator set shutsdown.

The generator set is shipped on a plastic mounting pad.Prepare a flat, level mounting area covered with a weedbarrier and gravel or a concrete pad as shown in thegenerator set clearance drawing. Set the plasticmounting pad directly on the gravel or concrete. Do notinstall the mounting pad directly on grass.

See the dimension drawings in Section 2 for specialmounting instructions for high wind (150 MPH) areas.

1.4.1 Exhaust Requirements

Carbon monoxide.Can cause severe nausea,fainting, or death.

The exhaust system must beleakproof and routinely inspected.

WARNING

Generator set operation. Carbon monoxide can causesevere nausea, fainting, or death. Carbon monoxide is anodorless, colorless, tasteless, nonirritating gas that can causedeath if inhaled for even a short time. Avoid breathing exhaustfumes when working on or near the generator set. Neveroperate the generator set inside a building. Never operate thegenerator set where exhaust gas could seep inside or bedrawn into a potentially occupied building throughwindows, airintake vents, or other openings.

The exhaust system is designed for generator setsinstalled outdoors. Do not install this generator setindoors.

Figure 1-2 gives the exhaust flow and temperature atrated load. The engine exhaust mixes with thegenerator set cooling air at the exhaust end of theenclosure. Mount the generator set so that the hotexhaust does not blow on plants or other combustiblematerials. Maintain the clearances shown in thedimension drawings in Section 2.

Exhaust System 60 Hz 50 Hz

Exhaust flow at rated kW,m3/min. (cfm) 3.8 (135) 3.2 (113)

Exhaust gas exiting the enclosureat rated kW, _C (_F) 216 (420)

Figure 1-2 Exhaust Flow and Temperature

Page 13: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 13Section 1 Installation

1.4.2 Air Requirements

The generator set requires correct air flow for coolingand combustion. The inlet and outlet openings in thesound enclosure provide the cooling and combustionair. Figure 1-3 shows the locations of the cooling airintake and exhaust vents. Inspect the air inlet and outletopenings inside and outside the housing to ensure thatthe air flow is not blocked.

tp61952

1. Exhaust outlet2. Alternator air intake (both sides)3. Engine air intake

3

1

3

Figure 1-3 Cooling Air Intake and Exhaust, Typical

Air Requirements, m3/min. (cfm)

Model HzCoolingAir

CombustionAir

TotalInlet Air

12RES60 26.9 (950) 1.1 (39.2) 28.0 (990)

50 22.4 (790) 0.9 (32.6) 23.4 (825)

Figure 1-4 Air Requirements

1.5 Power Supply

Power must be supplied from a source that is GFCIprotected to the generator set location for the batterycharger and the optional accessories shown inFigure 1-5.

Connect power from a circuit on the essential loadspanel to the utility power connection points on theterminal block. The circuit must be backed up by thegenerator set. SeeSection 1.8 and thewiring diagramsin Section 2 for connection details. See Figure 1-5 forthe power requirements for the battery charger andaccessories.

Equipment

Power Requirement, Max.

Watts Amps Volts

Battery charger (standard) 192 1.6

120Carburetor heater (optional) 37 0.33

Battery heater (optional) 110 0.92

Figure 1-5 Power Requirements

1.6 Fuel Requirements

The generator set operates using natural gas or LPGfuel. The generator set is EPA-certified for both naturalgas and LPG fuels.

The fuel system installationmust complywith applicablenational, state, and local codes.

Explosive fuel vapors.Can cause severe injury or death.

Use extreme care when handling,storing, and using fuels.

WARNING

Gas fuel leaks. Explosive fuel vapors can cause severeinjury or death. Fuel leakage can cause anexplosion. Checkthe LPG vapor or natural gas fuel system for leakage by usinga soap andwater solutionwith the fuel system test pressurizedto 6--8 ounces per square inch (10--14 inches water column).Do not use a soap solution containing either ammonia orchlorine because both prevent bubble formation. A successfultest depends on the ability of the solution to bubble.

Page 14: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1514 Section 1 Installation

The fuel system. Explosive fuel vapors can cause severeinjury or death. Vaporized fuels are highly explosive. Useextreme care when handling and storing fuels. Store fuels in awell-ventilated area away from spark-producing equipmentand out of the reach of children. Never add fuel to the tankwhile the engine is running because spilled fuel may ignite oncontact with hot parts or from sparks. Do not smoke or permitflames or sparks to occur near sources of spilled fuel or fuelvapors. Keep the fuel lines and connections tight and in goodcondition. Donot replace flexible fuel lineswith rigid lines. Useflexible sections to avoid fuel line breakage caused byvibration. Do not operate the generator set in the presence offuel leaks, fuel accumulation, or sparks. Repair fuel systemsbefore resuming generator set operation.

1.6.1 Fuel Supply

Because of variable climates and geographicalconsiderations, contact the local fuel supplier for fuelsystem planning and installation. Figure 1-6 lists therecommended fuel ratings and other fuel supplyinformation for natural gas and LPG fuels.

Fuel Type Natural Gas LPG

Fuel supply inlet 1/2 NPT 1/2 NPT

Fuel supply pressure,kPa (in. H2O)

0.9--2.7(3.5--11)

1.7--2.7(7--11)

Fuel flow rate, Btu/hr. 193000 203000

Nominal Fuel Rating,Btu/ft.3 1000 2500

Figure 1-6 Fuel Supply

Verify that the output pressure from the primary gasutility (or LPG tank) pressure regulator meets thespecifications in Figure 1-6 and that the utility gasmeterflow rate is sufficient to supply the generator set at ratedload plus all other gas-consuming appliances. SeeFigure 1-7 for fuel consumption. Contact the fuelsupplier for flow rate information or a gas meterupgrade.

The dimension drawings in Section 2 show the locationof the fuel inlet connection. Use flexible sections toprevent fuel line breakage causedby vibration. Hold thefuel solenoid valve with a wrench when tightening thefuel connections. Protect all fuel lines frommachineryorequipment contact, adverse weather conditions, andenvironmental damage.

Fuel Consumption,at % load, m3/hr. (cfh) 60 Hz 50 Hz

Natural Gas, m3/hr. (cfh)

100% 5.4 (193) 4.8 (173)

75% 4.7 (163) 4.2 (148)

50% 3.5 (124) 3.1 (108)

25% 2.6 (93) 2.4 (84)

LPG, m3/hr. (cfh)

100% 2.3 (81) 2.1 (74)

75% 2.1 (75) 1.9 (68)

50% 1.8 (60) 1.5 (53)

25% 1.2 (45) 1.1 (40)

LPG conversion factors:8.58 ft.3 = 1 lb.0.535 m3 = 1 kg36.39 ft.3 = 1 gal.

Nominal fuel rating:Natural gas: 37 MJ/m3 (1000 Btu/ft.3)LPG: 93 MJ/m3 (2500 Btu/ft.3)

Figure 1-7 Fuel Consumption

1.6.2 Fuel Pipe Size

Ensure that the natural gas pipe size and length meetthe specifications in Figure 1-8. Measure the pipelength from the primary gas pressure regulator to thepipe connection on the generator set fuel inlet. Add2.4 m (8 ft.) to the measured length for each 90 degreeelbow. Compare the total pipe length with the chart inFigure 1-8 to find the required pipe size.

Contact the local LPG provider for LPG installationinformation.

Minimum Gas Pipe Size Recommendation, in. NPT

Pipe Length,m (ft.)

Natural Gas(193,000 Btu/hr.)

LPG(203,000 Btu/hr.)

8 m (25 ft.) 3/4 3/4

15 m (50 ft.) 1 3/4

30 m (100 ft.) 1 1

46 m (150 ft.) 1 1/4 1

61 m (200 ft.) 1 1/4 1

Figure 1-8 Fuel Pipe Size

Page 15: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 15Section 1 Installation

1.7 Fuel Conversion

The multi-fuel system allows conversion from naturalgas to LPG (or vice-versa) in the field while maintainingemissions-standard compliance. A Kohler authorizeddistributor/dealer can convert the fuel system.

Rating Change

Converting the fuel will change the generator set rating.See thegenerator set specification sheet for ratingswithnatural gas and LP. Order a new nameplate with theupdated rating and fuel information from a Kohlerauthorized distributor/dealer, if necessary. Provide thefollowing information from the original nameplate:

D Model Number D kVAD Spec Number D AmpsD Serial Number D VoltsD Fuel (original and new) D HzD kW

Attach the new nameplate over the old one. Do NOTcover the UL listing information on the old nameplate.

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set. Accidental starting cancause severe injury or death. Before working on thegenerator set or connected equipment, disable the generatorset as follows: (1) Move the generator setmaster switch to theOFFposition. (2) Disconnect the power to the battery charger.(3) Remove the battery cables, negative (--) lead first.Reconnect the negative (--) lead last when reconnecting thebattery. Follow these precautions to prevent starting of thegenerator set by an automatic transfer switch, remotestart/stop switch, or engine start command from a remotecomputer.

Explosive fuel vapors.Can cause severe injury or death.

Use extreme care when handling,storing, and using fuels.

WARNING

1.7.1 Fuel Conversion

For natural gas and LPG fuel, orifice fittings are used inthe fuel line. See Figure 1-9. The natural gas orificefitting is silver in color and stamped NG. The LPG fittingis gold in color and stamped LPG. The fittings arethreaded. A straight-blade screwdriver is required toremove and replace the fittings.

NG LPG

Figure 1-9 NG and LPG Fuel Orifice Fittings

The unit is typically shipped set up for natural gas, withthe LPG fitting tied to the fuel regulator. To convert toLPG, remove the NG fitting and install the LPG fitting asdescribed below. See Figure 1-10 for the fuel systemcomponent locations.

Procedure to Convert from NG to LPG

1. Place the generator set master switch in theOFF/RESET position.

2. Disconnect the utility power to the generator.

3. Disconnect the generator set engine startingbattery, negative (--) lead first.

4. Turn off and disconnect the fuel supply.

Page 16: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1516 Section 1 Installation

5. Remove the hose clamp and fuel hose from thehose fitting. See Figure 1-10.

6. Use a straight-blade screwdriver to remove theNGorifice from the hose fitting. See Figure 1-11.

7. Insert the LPG orifice into the hose fitting. Use astraight-blade screwdriver to tighten the fitting untilit is snug.

8. Slide the hose onto the hose fitting and secure itwith the clamp.

9. Disconnect ignition timing leads 65 and N5 forLPG. The ignition timing leads are located near thefuel solenoid valve. See Figure 1-10.

Note: Do not disconnect the leads to the fuelsolenoid valve.

3

1. LPG fitting tied to regulator for shipping2. Fuel hose and clamp3. Ignition timing lead location (leads not shown)

2

Ignition Timing Lead Connection

1

Figure 1-10 Fuel System, As Shipped

10. Connect and turn on the new fuel supply.

11. Reconnect the generator set engine startingbattery leads, negative (--) lead last.

12. Reconnect the utility power to the generator.

13. Start thegenerator setbymoving themaster switchto the RUN position.

14. Check for leaks using a gas leak detector.

15. Run the generator set and check the operation.

16. Move the generator set master switch to theOFF/RESET position to shut down the generatorset.

Conversion from LPG to Natural Gas

To convert from LPG to natural gas, repeat the stepsabove, removing the LPG fuel orifice and installing theNG fitting. Connect ignition timing leads 65 and N5together for natural gas.

1. Fuel orifice fitting2. Hose fitting3. Orifice tied to regulator for shipping

1

GM29253

2

3

Figure 1-11 Fuel Orifice Fitting Installation

Page 17: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 17Section 1 Installation

1.8 Electrical Connections

Hazardous voltage.Backfeed to the utility system cancause property damage, severeinjury, or death.

If the generator set is used forstandby power, install an automatictransfer switch to prevent inadvertentinterconnection of standby andnormal sources of supply.

WARNING

Grounding electrical equipment. Hazardous voltage cancause severe injury or death. Electrocution is possiblewhenever electricity is present. Ensure you comply with allapplicable codes and standards. Electrically ground thegenerator set, transfer switch, and related equipment andelectrical circuits. Turn off the main circuit breakers of allpower sources before servicing the equipment. Never contactelectrical leads or appliances when standing inwater or onwetground because these conditions increase the risk ofelectrocution.

Electrical backfeed to the utility. Hazardous backfeedvoltage can cause severe injury or death. Install a transferswitch in standby power installations to prevent the connectionof standby and other sources of power. Electrical backfeedinto a utility electrical system can cause severe injury or deathto utility personnel working on power lines.

NOTICECanadian installations only. For standby service connectthe output of the generator set to a suitably rated transferswitch in accordance with Canadian Electrical Code, Part 1.

Have a Kohler authorized distributor/dealer or alicensed electrician make the following electricalconnections. The electrical installation must complywith the National Electrical Code (NEC) and allapplicable local codes. Canadian installations mustcomply with the Canadian Electrical Code (CEC) andapplicable local codes.

Ground the generator set according to applicablecodes. See Section 1.8.3.

For customer-supplied wiring, select the wiretemperature rating in Figure 1-12 based upon thefollowing criteria:

D Select row 1, 2, 3, or 4 if the circuit rating is110 amperes or less or requires #1 AWG (42.4 mm2)or smaller conductors.

D Select row 3 or 4 if the circuit rating is greater than110 amperes or requires #1 AWG (42.4 mm2) orlarger conductors.

Row Temp. Rating Copper (Cu) Only Cu/Aluminum (Al) Combinations Al Only

1 60_C (140_F)or

75_C (167_F)

Use No. * AWG, 60_C wire oruse No. * AWG, 75_C wire

Use 60_C wire, either No. * AWG Cu, or No. *AWG Al or use 75_C wire, either No. * AWGCu or No. * AWG Al

Use 60_C wire, No. * AWG oruse 75_C wire, No. * AWG

2 60_C (140_F) Use No. * AWG, 60_C wire Use 60_C wire, either No. * AWG Cu or No. *AWG Al

Use 60_C wire, No. * AWG

3 75_C (167_F) Use No. *[ AWG, 75_C wire Use 75_C wire, either No. *[ AWG Cu or No.*[ AWG Al

Use 75_C wire, No.*[ AWG

4 90_C (194_F) Use No. *[ AWG, 90_C wire Use 90_C wire, either No. *[ AWG Cu or No.*[ AWG Al

Use 90_C wire, No.*[ AWG

* The wire size for 60_C (140_F) wire is not required to be included in the marking. If included, the wire size is based on ampacities for thewire given in Table 310-16 of the National Electrical Coder, in ANSI/NFPA 70, and on 115% of the maximum current that the circuit carriesunder rated conditions. The National Electrical Coder is a registered trademark of the National Fire Protection Association, Inc.

[ Use the larger of the following conductors: the same size conductor as that used for the temperature test or one selected using theguidelines in the preceding footnote.

Figure 1-12 Terminal Markings for Various Temperature Ratings and Conductors

Page 18: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1518 Section 1 Installation

1.8.1 Field Connections

The generator set is equipped with a field-connectionterminal block located below the fuel inlet. Leads havebeen factory-installed from the junction box to theterminal block for easy field wiring. Refer to the decalnear the terminal block for connections. Also seeSection 2, Wiring Diagrams.

Refer to the decal below the terminal block and thetransfer switch specifications for the cable size range foreach connection. Route leads through flexible conduit.Use separate conduit for AC wiring and low-voltageengine start leads. Ensure that the leads and conduit donot interfere with the operation of the generator set orobstruct the service areas.

Field Connections to the Terminal Block

1. Remove the cover from the electrical connectionaccess area. See Figure 1-13.

2. Drill holes for conduit fittings:

a. See Figure 1-13 for the electrical inlet location.Remove the cover from the electrical inlet area.

b. Drill holes in the cover for the conduit fittingsand replace the cover. Use separate conduitfor AC wiring and low-voltage engine startleads.

c. Feed the cables through the openings.

ADV-8024

Figure 1-13 Electrical Connection Area

3. See Figure 1-14. Connect the leads from thetransfer switch emergency source lugs to the L1and L2 connections on the generator set terminalblock.

4. Connect the neutral (L0) and ground (GRD) leadsfrom the ATS and the main panel to thecorresponding connection points on the terminalblock. See Section 1.8.3, Grounding.

5. Connect 120 VAC utility power to the terminalsmarked Utility Power. Power to this circuit must bebacked-up by the generator set. See Section 1.5for more information about the utility powerrequirement.

6. Connect the engine start leads from the automatictransfer switch or remote start switch to terminals 3and 4 on the terminal block. See Section 1.8.2.

7. Replace the cover over the electrical connectionaccess area. See Figure 1-13.

GM58022GM54820

Note: Sample decal shown. See the decal on the generatorset for wire gauge.

Figure 1-14 Field-Connection Terminal Block, typical

Page 19: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 19Section 1 Installation

1.8.2 Remote Start Connection

Connect terminals 3 and 4 to the automatic transferswitch’s engine start terminals or to an optional remotestart/stop switch. Route the engine start leads throughseparate conduit from the AC power and load leads.

1.8.3 Grounding

Ground the generator set. The grounding methodmustcomply with NEC and local codes. Connect thegrounding cable to the generator set ground lug,terminal GND inside the controller compartment.

Generator sets are shipped with the generator neutralbonded (connected) to the generator ground in thejunction box. The requirement for having a bonded(grounded) or ungrounded neutral is determined by thetype of installation. At installation, the neutral can begrounded at the generator set or lifted from the groundstud and isolated if the installation requires anungrounded neutral connection at the generator. Thegenerator setwill operateproperlywith theneutral eitherbonded to ground or isolated from ground at thegenerator.

Various regulationsandsite configurations including theNational Electrical Code (NEC), local codes, and thetype of transfer switch used in the application determinethe grounding of the neutral at the generator. NECSection 250 is one example that has a very goodexplanation of the neutral grounding requirements forgenerators.

1.8.4 Battery Charger

A battery charger is factory-installed in the batterycompartment to keep the starting battery fully charged.The battery charger’s DC leads are factory-connectedto the battery. Supply power to the generator set for thebattery charger and carburetor heater as described inSections 1.5 and 1.8.1.

Plug the battery charger’s power cord into thereceptacle on the bottom of the controller junction box.

Refer to the generator set operation manual for batterycharger operation information.

1.9 Battery

Sulfuric acid in batteries.Can cause severe injury or death.

Wear protective goggles andclothing. Battery acid may causeblindness and burn skin.

WARNING

Explosion.Can cause severe injury or death.Relays in the battery chargercause arcs or sparks.

Locate the battery in a well-ventilatedarea. Isolate the battery charger fromexplosive fumes.

WARNING

Battery electrolyte is a diluted sulfuric acid. Battery acidcan cause severe injury or death. Battery acid can causeblindness and burn skin. Always wear splashproof safetygoggles, rubber gloves, and boots when servicing the battery.Do not open a sealed battery or mutilate the battery case. Ifbattery acid splashes in the eyes or on the skin, immediatelyflush the affected area for 15 minutes with large quantities ofclean water. Seek immediate medical aid in the case of eyecontact. Never add acid to a battery after placing the battery inservice, as this may result in hazardous spattering of batteryacid.

Battery acid cleanup. Battery acid can cause severeinjury or death. Battery acid is electrically conductive andcorrosive. Add 500 g (1 lb.) of bicarbonate of soda (bakingsoda) to a container with 4 L (1 gal.) of water and mix theneutralizing solution. Pour the neutralizing solution on thespilled battery acid and continue to add the neutralizingsolution to the spilled battery acid until all evidence of achemical reaction (foaming) has ceased. Flush the resultingliquid with water and dry the area.

Page 20: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1520 Section 1 Installation

Battery gases. Explosion can cause severe injury ordeath. Battery gases can cause an explosion. Do not smokeor permit flames or sparks to occur near a battery at any time,particularly when it is charging. Do not dispose of a battery in afire. To prevent burns and sparks that could cause anexplosion, avoid touching the battery terminals with tools orother metal objects. Remove all jewelry before servicing theequipment. Discharge static electricity from your body beforetouching batteries by first touching a grounded metal surfaceaway from the battery. To avoid sparks, do not disturb thebattery charger connections while the battery is charging.Always turn the battery charger off before disconnecting thebattery connections. Ventilate the compartments containingbatteries to prevent accumulation of explosive gases.

Battery short circuits. Explosion can cause severe injuryor death. Short circuits can cause bodily injury and/orequipment damage. Disconnect the battery before generatorset installation or maintenance. Remove all jewelry beforeservicing the equipment. Use tools with insulated handles.Remove the negative (--) lead first when disconnecting thebattery. Reconnect the negative (--) lead last whenreconnecting the battery. Never connect the negative (--)battery cable to the positive (+) connection terminal of thestarter solenoid. Do not test the battery condition by shortingthe terminals together.

Hazardous voltage.Will cause severe injury or death.

This equipment must be installed andserviced by qualified electricalpersonnel.

DANGER

Connecting the battery and the battery charger.Hazardous voltage can cause severe injury or death.Reconnect the battery correctly, positive to positive andnegative to negative, to avoid electrical shock and damage tothe battery charger and battery(ies). Have a qualifiedelectrician install the battery(ies).

Use a 12-volt group 26 battery with a minimum rating of500 cold cranking amps at 0_F. The generator set usesa negative ground with a 12-volt engine electricalsystem. SeeFigure 1-15 for battery connections. Makesure that the battery is correctly connected and theterminals are tight.

Note: The generator set will not start and circuit boarddamage may occur if the battery is connected inreverse.

Figure 1-16 shows the location of the engine startingbattery. Standard battery cables provide easy

connection to the battery. Use the following procedureto install and connect the battery.

Battery Installation Procedure

1. Ensure that the starting battery is fully chargedbefore placing the battery in service.

2. Clean the battery posts and/or adapters ifnecessary.

3. Install the battery post adapters, if needed.

4. Place the battery in the housing.

5. Verify that the controllermaster switch is in theOFFposition.

6. Connect the positive (+) lead to the engine startingbattery.

7. Connect thenegative (--) lead to the engine startingbattery.

Refer to the generator set operation manual and thebattery manufacturer’s instructions for batterymaintenance instructions.

EZ-273000-J

1 2

1. To positive (+) terminal on starter solenoid.2. To ground (--) terminal on or near starter motor.

Figure 1-15 12-Volt Engine Electrical System SingleStarter Motor Typical Battery Connection

ADV-8025

1. Engine starting battery location

1

Figure 1-16 Battery Location, Air Intake End (typical)

Page 21: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 21Section 1 Installation

1.10 Accessories

Have accessories installed by a Kohler authorizeddistributor/ dealer or a licensed electrician. Follow theinstallation instructions provided with each kit. Useseparate conduit for AC and DC leads to reduce thepossibility of electrical interference. Verify that the leadsand conduit do not interfere with the operation of thegenerator set or obstruct the service areas. Verify thatthe electrical installation complies with the NationalElectrical Code (NEC) and all applicable local codes.See Section 2, Wiring Diagrams, for more informationregarding generator set electrical connections.

If there are no accessories, proceed to Section 1.11,Prestart Installation Check.

1.10.1 Common Fault and Auxiliary RunRelay Board

The optional relay board provides two additional relaysto control customer-provided equipment:

D Common fault relay, energized on a fault.

D Auxiliary run relay, energized when the generator setis running.

See Figure 1-17 for the relay board location.

1. Relay board location (inside customer connection box)

1

ADV-7948

Figure 1-17 Optional Relay Board Location

Connect customer equipment to terminal strip TB1 onthe relay board, following the markings on the board.Connect to each relay’s normally open or normallyclosed contacts depending on the application. Use size14 AWG maximum wire for connections to TB1. SeeFigure 1-18 and Figure 1-19.

GM51403

1

1. Connect customer equipment to TB1, 14 AWG max.

Figure 1-18 Relay Board Connections

Terminal Label Description

COMMON FAULT NC Common fault relay normallyclosed contact.Opens on a fault.

COMMON FAULT COM Common fault relay common

COMMON FAULT NO Common fault relay normallyopen contact.Closes on a fault.

AUX RUN NC Auxiliary run relay normallyclosed contact.Open when generator set isrunning.

AUX RUN COM Auxiliary run relay common

AUX RUN NO Auxiliary run relay normallyopen contact.Closed when generator set isrunning.

Note: Use maximum 14 AWG wire for TB1 connections.

Figure 1-19 Common Fault and Run Relay BoardHarness Connections

Page 22: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1522 Section 1 Installation

1.10.2 Carburetor Heater

An optional carburetor heater is recommended forimproved cold starting in locations where the ambienttemperature drops below 0_C (32_F). The carburetorheater preventscondensationandcarburetor icing. Theheater turns on when the temperature at the thermostatfalls belowapproximately 4_C(40_F) and turnsoffwhenthe temperature rises above approximately 16_C(60_F). See Figure 1-20.

The carburetor heater thermostat is installed in the cord.Figure 1-21 shows the location of the thermostat on thepower cord. The heater power cord and thermostat arelocated in the generator set housing air intake area/battery compartment. See Figure 1-16.

Note: Do not place the carburetor heater thermostatinside the generator set engine compartment.The thermostat must be exposed to the ambientair.

The heater requires a continuous source of power. Plugthe carburetor heater into an outlet that suppliescontinuous 120 VAC power .

tp6195

1. Carburetor heater (air cleaner removed to show heater)2. Carburetor heater power cord

1 2

Figure 1-20 Carburetor Heater Location

GM19463

2

1. Power plug 2. Thermostat 3. Heater

31

Figure 1-21 Carburetor Heaters

Page 23: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 23Section 1 Installation

1.11 Prestart Installation Check

Review the entire installation section. Inspect all wiringand connections to verify that the generator set is readyfor operation. Check all items in the following PrestartChecklist.

Prestart Checklist

Air Cleaner. Check that a clean air cleaner element isinstalled to prevent unfiltered air from entering theengine. See the generator set operation manual forinstructions.

Air Inlets. Check for clean and unobstructed air inlets.

Battery. Check for tight battery connections. Consultthe battery manufacturer’s instructions regardingbattery care and maintenance.

Exhaust System. Check for exhaust leaks andblockages. Check the muffler condition.

D Inspect the exhaust system components for cracks,leaks, and corrosion. Check for tight exhaust systemconnections.

D Check for corrodedor brokenmetal parts and replacethem as needed.

D Check that the exhaust outlet is unobstructed.

Oil Level. Maintain the oil level at or near, not over, thefull mark on the dipstick.

Operating Area. Check for obstructions that couldblock the flow of cooling air. Keep the air intake areaclean. Do not leave rags, tools, or debris on or near thegenerator set.

Page 24: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1524 Section 1 Installation

1.12 Controller Configuration

1.12.1 System Parameters

The controller configuration for each generator model isset at the factory and should not normally requirechanges. The controller’s configuration mode allowsadjustment of the system parameters listed in thissection. Use the instructions in this section to check theconfiguration after installation and change them tomatch the settings shown in Figure 1-22, if necessary.

Parameter Setting Definition

Unit’s systemvoltage andfrequency

Uu01 120/240 VAC, 60 Hz(single phase)

Uu06 115/230 VAC, 50 Hz(single phase)

Controller type Uc01 ADC-RES (distributor)(Use for 12RES)

Uc05 ] DC-RET (retail) ]

Engine type Ec00 12RES

Communicationsetting *

Cn00 No J1939 communication.Sleep mode enabled(48-hour power down inAUTO).

Cn01 [ J1939 communicationenabled. Sleep modedisabled (no power down inAUTO).

* Controller application code version 1.13 or higher.[ Default setting for application code version 1.13 or higher.] Default setting for service replacement controllers.Change to Uc01 for the 12RES.

Figure 1-22 Controller Configuration Parameters

Follow the instructions in Figure 1-23 to enter theconfiguration mode while the engine is not running andthen step through the following parameters. Use the up() anddown () arrowbuttons to select theappropriatesetting for the application.

The controller will automatically exit the configurationmode without saving any changes after about 1 minuteif no buttons are pressed. Start the configurationprocedure over again from the beginning if the controllerexits the configuration mode before the settings havebeen saved.

Note: Be sure to save your settings before exiting theconfiguration mode. The controller reverts to thelast saved settings when the master switch ismoved to the OFF/RESET position.

Voltage/frequency setting (Uu). Select the systemvoltage and frequency from the table in Figure 1-22.

Note: The Uu parameter sets the system’s ratedvoltage and frequency. To adjust the output(measured) voltage and frequency, see Section1.13, Voltage and Frequency Adjustments.

Engine configuration (Ec). The engine configurationmust match the generator set engine type.

Controller type (Uc). The Uc setting is used duringinitial controller installation in the factory or controllerreplacement in the field. TheUc setting can be changedonly once. The default setting for service replacementcontrollers isUc05, controller typeDC-RET. Changing itto UC01 sets the controller type to ADC-RES. Uc01 isthe correct setting for the Model 12RES.

Communication/SleepModeSetting (Cn). (Availableon controllers with application code version 1.13 orhigher.) The communication setting enables or disablesJ1939 communication, and also disables or enables thesleep mode. When J1939 communication is enabled,the sleep mode is turned off to allow uninterruptedcommunication with a personal computer runningremote monitoring software. If remote monitoring is notused, the communication canbe turnedoff, enabling thesleep mode which causes the controller to power downafter 48 hours of inactivity. The generator set masterswitch must be in AUTO for the sleep mode to function.

The default setting for controllers with application codeversion 1.13 or higher isCn01, communication on/sleepmode off. Controllers with earlier application codeversions have communication disabled and the sleepmode enabled. The Cn setting is not adjustable onthese earlier versions.

1.12.2 Application Code Version

To check the application code version number, HOLDthe select button while moving the generator set masterswitch toRUN. (Theenginewill not startwhen theselectbutton is held.) Wait about 5 seconds for the applicationcode version number to appear on the display. SeeFigure 1-23.

Page 25: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 25Section 1 Installation

Wait about 5 seconds until the display shows the program versionnumber. (The number may be different than the one shown here.)

Hold the Select button:

or To change the voltage/frequency setting,if necessary. See Figure 1-22.

To enter setting and step to the next parameter, engine type Ec.

To enter setting and step to SAVE.

Move the generator set master switch to the RUN position. (Thegenerator set engine will not start.)

Display:

orTo change the engine type,if necessary.

U u 0 x

U u 0 1

v 1 1 3

. 0

Press:

Now release the Select button.

S A V E

Note: Shaded boxes show which number in the controller display changes when the up or down arrowkey is pressed. X in the runtime hours display above denotes any number from 0 to 9.

Press the down arrow key and then the up arrow key 3 times toenter the configuration mode. (This is the controller“password.”)

Controller Configuration Mode:

To SAVE CHANGES.

To DISCARD CHANGES without saving.

Y E S

Now move the master switch to OFF/RESET.

n o

x x xx

Press:

“Yes” or “no” flashes when the up or down arrow is pressed and thenthe controller exits the configuration mode. The display returns to theruntime hours.

OR

E c 0 0

To enter setting and step to the next parameter, communicationsetting Cn.

or To change the communication setting, ifnecessary. See Figure 1-22.

C n 0 x

To enter setting and step to the next parameter, controller type Uc.

orTo change the controller type, only if necessary. Thissetting is used during controller replacement and can bechanged only once.

U c 0 1

Figure 1-23 Configuration Mode (system voltage/frequency, engine type, and communication parameters)

Page 26: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1526 Section 1 Installation

1.13 Voltage and FrequencyAdjustments

Hazardous voltage.Can cause severe injury or death.

Operate the generator set only whenall guards and electrical enclosuresare in place.

Moving parts.

WARNING

Short circuits. Hazardous voltage/current can causesevere injury or death. Short circuits can cause bodily injuryand/or equipment damage. Do not contact electricalconnections with tools or jewelry while making adjustments orrepairs. Remove all jewelry before servicing the equipment.

The controller’s adjustment mode allows adjustment ofthe output voltage and frequency, if necessary. Haveadjustments performed by a Kohler authorizeddistributor/ dealer.

Note: A digital multimeter that measures voltage andfrequency is required for these adjustments.

Use a digital multimeter to check the output voltage andfrequency. If output voltage or frequency is not withinspecifications, use the ADC controller to adjust theoutput voltage and engine speed (frequency) while thegenerator set is running. See Figure 1-24. Theflowcharts in Figure 1-27 through Figure 1-29 outlinethe adjustment procedures.

Note: Be sure to save your changes as instructed inFigure 1-29 before exiting configuration mode.

1

tp6514

1. Select button 2. Arrow buttons

2

Figure 1-24 Advanced Digital Control

Changes in voltage and speed adjustments are lost ifnot saved before the generator set shuts down. Thegenerator set continues to runwith the newsettings untilit shuts down but then reverts to the previous settings atthe next startup if the changes have not been saved.

1.13.1 Voltage Adjustment

Note: Refer to the flowcharts in Figure 1-27 throughFigure 1-29 during the following procedure.

Voltage Adjustment Procedure

1. With the generator set off, connect a digitalmultimeter to the output leads or an electrical outleton the load side of the generator set. Set themeterto measure AC voltage.

2. Start the generator set bymoving the generator setmaster switch to the RUN position.

3. Use the ADC controller to adjust the voltage(parameter 1P) until the output voltage reaches thedesired value. Refer to the flowcharts inFigure 1-27 through Figure 1-29 for instructions toadjust the output voltage. See Figure 1-25 for theapproximate change in voltage per step.

MeasuredVoltage, VAC

ADCDisplay

Voltage Change perStep, VAC

Coarse Fine

85--132 1P00--99 5 0.5

180--251 1P00--99 7 0.7

Figure 1-25 Voltage Adjustment (approximate)

4. Adjust the voltage stability (gain, parameter 2P) tominimize light flicker.

5. Readjust the voltage, if necessary.

6. Set the multimeter to measure frequency.

7. Adjust the engine speed to the cut-in frequencyshown in Figure 1-26 by adjusting the enginegovernor speed (parameter 4P).

Frequency Cut-In Frequency

60 Hz 57.5 Hz

50 Hz 47.5 Hz

Figure 1-26 Cut-In Frequencies

Page 27: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 27Section 1 Installation

8. Adjust the volts/Hz (parameter 3P) until the voltagelevel measured by the multimeter begins to drop.When the volts/Hz is set correctly, the generator(as load is applied) attempts to maintain normaloutput until the engine speed drops below thecut-in frequency set in step 7.

9. Reset the engine speed to the operating frequency(50 or 60 Hz) by adjusting the engine governorspeed (parameter 4P).

10. Readjust the voltage stability (gain, parameter 2P),if necessary.

11. Readjust the voltage (parameter 1P), if necessary.

12. Save settings. See Figure 1-29.

13. Stop the generator set.

1.13.2 Frequency Adjustment

The engine speed determines the generator outputfrequency; 60 Hz units operate at 3600 rpm and 50 Hzunits run at 3000 rpm. Adjust the engine governorspeed and gain to set the output frequency and stabilityusing the following procedure.

Note: Refer to the flowcharts in Figure 1-27 throughFigure 1-29 during the following procedure.

Frequency Adjustment Procedure

Note: Refer to the flowcharts in Figure 1-27 throughFigure 1-29 during the following procedure.

1. Attach a frequencymeter to the AC output leads oran electrical outlet on the load side of the generatorset.

2. Start and run the generator set until it reachesnormal operating temperature (at least 10 minutes).

3. Adjust the electronic governor speed(parameter 4P) to obtain a frequency reading of60 Hz (or 50 Hz if appropriate). Each stepchangesthe engine speed about 3.6 rpm, which changesthe output frequency about 0.06 Hz.

4. Check stability with the generator set running andwith no load applied. If the generator set speed isunstable, hunts, or surges, adjust the governorstability (gain, parameter 5P) until the generatorset becomes stable with no hunting or surging.(Increasing the gain slows the governor response.)

5. Check the frequency reading. Repeat steps 3 and4 if necessary to obtain the rated frequency andstable operation.

6. Save settings. See Figure 1-29.

Page 28: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1528 Section 1 Installation

TP6196

Move the generator set master switch to the RUN position. The generator setengine starts and the controller display shows the engine runtime hours.

Display :*

or

or

To raise or lower the voltage in large increments(approximately 5--7 volts per step). (Parameter 1P)

To enter fine voltage adjustment mode.

To raise or lower the voltage in smaller increments(approximately 0.5--0.7 volts per step). (Parameter 1P)

To enter coarse voltage stability (gain) adjustment mode.

or

To raise or lower the voltage stability (gain) in largeincrements. (Parameter 2P)

To enter fine voltage stability (gain) adjustment mode.

or

To raise or lower the voltage stability (gain) in smallerincrements. (Parameter 2P)

To enter volts/Hz adjustment mode.(Parameter 3P)

To raise or lower the volts/Hz: 00=low; 09= high

or

Hold:Wait about 5 seconds until the display changes from runtime hoursto the program version number.

Press the down arrow key and then the up arrow key 3 times to enter theadjustment mode. (This is the controller “password.”)

x x

x x x x

1 P

2 P

* Shaded boxes show which character in the controller display changes for each adjustment. X in theexamples above denotes any number from 0 to 9. The actual values may vary from model-to-model.

x.

2 P

3 P x

The controller is now in the voltage coarse adjustment mode.

Press:

1 P

Continued on Figure 1-28.

x x

x x

x x

xx

x

Output Voltage and Frequency Adjustment Mode:

1 P x x

Figure 1-27 Output Voltage and Frequency Adjustments

Page 29: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 29Section 1 Installation

Display : *

or

To enter engine governor speed coarse adjustmentmode. (Parameter 4P)

To raise or lower the engine speed in largeincrements.

To enter engine governor stability (gain) coarseadjustment mode. (Parameter 5P)

To raise or lower the engine governor stability (gain)in large increments.

To enter engine governor speed fineadjustment mode. (Parameter 4P)

To raise or lower the engine speed in smallerincrements.

To enter engine governor stability (gain) fineadjustment mode. (Parameter 5P)

To raise or lower the engine governor stability (gain)in smaller increments.

4 P

4 P

or

or

or

Continued from Figure 1-27:Press:

5 P

5 P

* Shaded boxes show which character in the controller display changes for each adjustment. X in theexamples above denotes any number from 0 to 9. The actual values may vary from model-to-model.

S A V ETo enter SAVE mode. Go to Figure 1-29.

x x

xx

x x

xx

Note: Be sure to save your settings before exiting the configuration mode. The controller reverts tothe last saved settings when the master switch is moved to the OFF/RESET position.

Figure 1-28 Output Voltage and Frequency Adjustments, Continued

Page 30: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1530 Section 1 Installation

To save changes.

To discard changes without saving.or

S A V E

Y E S

Now move the master switch to OFF/RESET.

n o

There are 3 options when the display says SAVE:Press:

or

To return to the first parameter, coarse voltage adjustment, to checkor change settings before saving. See Figure 1-27.

“Yes”or “no” flashes when the up or down arrow is pressed and then thecontroller exits the configuration mode. The display returns to theruntime hours.

1 P

x x x x

x x

Figure 1-29 Save Mode

Page 31: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 31Section 2 Dimension Drawings and Wiring Diagrams

Section 2 Dimension Drawings and Wiring Diagrams

Refer to the dimension drawings andwiring diagrams for yourmodel during generator set installation. Figure 2-1 liststhe drawing numbers and locations.

Drawing Description Drawing Number Page

Dimension Drawing ADV-8024

Mounting and Dimensions Sheet 1 32

Clearance Sheet 2 33

High Wind Mounting Sheet 3 34

Schematic Diagram ADV-7325 35

Point-to-Point Wiring Diagram GM51414 36

Figure 2-1 Drawing Numbers and Locations

Page 32: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1532 Section 2 Dimension Drawings and Wiring Diagrams

Figure 2-2 Dimension Drawing ADV-8024, Sheet 1

Page 33: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 33Section 2 Dimension Drawings and Wiring Diagrams

Figure 2-3 Dimension Drawing ADV-8024, Sheet 2

Page 34: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1534 Section 2 Dimension Drawings and Wiring Diagrams

Figure 2-4 Dimension Drawing, ADV-8024, Sheet 3

Page 35: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 35Section 2 Dimension Drawings and Wiring Diagrams

-

Figure 2-5 Schematic Diagram, ADV-7325-E

Page 36: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1536 Section 2 Dimension Drawings and Wiring Diagrams

-

Figure 2-6 Wiring Diagram, GM51414-E

Page 37: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/15 Appendix 37

Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.

A, amp ampereABDC after bottom dead centerAC alternating currentA/D analog to digitalADC advanced digital control;

analog to digital converteradj. adjust, adjustmentADV advertising dimensional

drawingAh amp-hourAHWT anticipatory high water

temperatureAISI American Iron and Steel

InstituteALOP anticipatory low oil pressurealt. alternatorAl aluminumANSI American National Standards

Institute (formerly AmericanStandards Association, ASA)

AO anticipatory onlyAPDC Air Pollution Control DistrictAPI American Petroleum Instituteapprox. approximate, approximatelyAPU Auxiliary Power UnitAQMD Air Quality Management DistrictAR as required, as requestedAS as supplied, as stated, as

suggestedASE American Society of EngineersASME American Society of

Mechanical Engineersassy. assemblyASTM American Society for Testing

MaterialsATDC after top dead centerATS automatic transfer switchauto. automaticaux. auxiliaryavg. averageAVR automatic voltage regulatorAWG American Wire GaugeAWM appliance wiring materialbat. batteryBBDC before bottom dead centerBC battery charger, battery

chargingBCA battery charging alternatorBCI Battery Council InternationalBDC before dead centerBHP brake horsepowerblk. black (paint color), block

(engine)blk. htr. block heaterBMEP brake mean effective pressurebps bits per secondbr. brassBTDC before top dead centerBtu British thermal unitBtu/min. British thermal units per minuteC Celsius, centigradecal. calorieCAN controller area networkCARB California Air Resources BoardCAT5 Category 5 (network cable)CB circuit breakerCC crank cyclecc cubic centimeterCCA cold cranking ampsccw. counterclockwiseCEC Canadian Electrical Codecert. certificate, certification, certifiedcfh cubic feet per hour

cfm cubic feet per minuteCG center of gravityCID cubic inch displacementCL centerlinecm centimeterCMOS complementary metal oxide

substrate (semiconductor)com communications (port)coml commercialComl/Rec Commercial/Recreationalconn. connectioncont. continuedCPVC chlorinated polyvinyl chloridecrit. criticalCSA Canadian Standards

AssociationCT current transformerCu coppercUL Canadian Underwriter’s

LaboratoriesCUL Canadian Underwriter’s

Laboratoriescu. in. cubic inchcw. clockwiseCWC city water-cooledcyl. cylinderD/A digital to analogDAC digital to analog converterdB decibeldB(A) decibel (A weighted)DC direct currentDCR direct current resistancedeg., degreedept. departmentdia. diameterDI/EO dual inlet/end outletDIN Deutsches Institut fur Normung

e. V. (also Deutsche IndustrieNormenausschuss)

DIP dual inline packageDPDT double-pole, double-throwDPST double-pole, single-throwDS disconnect switchDVR digital voltage regulatorE2PROM, EEPROM

electrically-erasableprogrammable read-onlymemory

E, emer. emergency (power source)ECM electronic control module,

engine control moduleEDI electronic data interchangeEFR emergency frequency relaye.g. for example (exempli gratia)EG electronic governorEGSA Electrical Generating Systems

AssociationEIA Electronic Industries

AssociationEI/EO end inlet/end outletEMI electromagnetic interferenceemiss. emissioneng. engineEPA Environmental Protection

AgencyEPS emergency power systemER emergency relayES engineering special,

engineered specialESD electrostatic dischargeest. estimatedE-Stop emergency stopetc. et cetera (and so forth)

exh. exhaustext. externalF Fahrenheit, femaleFHM flat head machine (screw)fl. oz. fluid ounceflex. flexiblefreq. frequencyFS full scaleft. foot, feetft. lb. foot pounds (torque)ft./min. feet per minuteftp file transfer protocolg gramga. gauge (meters, wire size)gal. gallongen. generatorgenset generator setGFI ground fault interrupter

GND, groundgov. governorgph gallons per hourgpm gallons per minutegr. grade, grossGRD equipment groundgr. wt. gross weightH x W x D height by width by depthHC hex capHCHT high cylinder head temperatureHD heavy dutyHET high exhaust temp., high

engine temp.hex hexagonHg mercury (element)HH hex headHHC hex head capHP horsepowerhr. hourHS heat shrinkhsg. housingHVAC heating, ventilation, and air

conditioningHWT high water temperatureHz hertz (cycles per second)IBC International Building CodeIC integrated circuitID inside diameter, identificationIEC International Electrotechnical

CommissionIEEE Institute of Electrical and

Electronics EngineersIMS improved motor startingin. inchin. H2O inches of waterin. Hg inches of mercuryin. lb. inch poundsInc. incorporatedind. industrialint. internalint./ext. internal/externalI/O input/outputIP internet protocolISO International Organization for

StandardizationJ jouleJIS Japanese Industry Standardk kilo (1000)K kelvinkA kiloampereKB kilobyte (210 bytes)KBus Kohler communication protocolkg kilogram

Page 38: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

TP-6967 8/1538 Appendix

kg/cm2 kilograms per squarecentimeter

kgm kilogram-meterkg/m3 kilograms per cubic meterkHz kilohertzkJ kilojoulekm kilometerkOhm, k kilo-ohmkPa kilopascalkph kilometers per hourkV kilovoltkVA kilovolt amperekVAR kilovolt ampere reactivekW kilowattkWh kilowatt-hourkWm kilowatt mechanicalkWth kilowatt-thermalL literLAN local area networkL x W x H length by width by heightlb. pound, poundslbm/ft3 pounds mass per cubic feetLCB line circuit breakerLCD liquid crystal displayLED light emitting diodeLph liters per hourLpm liters per minuteLOP low oil pressureLP liquefied petroleumLPG liquefied petroleum gasLS left sideLwa sound power level, A weightedLWL low water levelLWT low water temperaturem meter, milli (1/1000)M mega (106 when used with SI

units), malem3 cubic meterm3/hr. cubic meters per hourm3/min. cubic meters per minutemA milliampereman. manualmax. maximumMB megabyte (220 bytes)MCCB molded-case circuit breakerMCM one thousand circular milsmeggar megohmmeterMHz megahertzmi. milemil one one-thousandth of an inchmin. minimum, minutemisc. miscellaneousMJ megajoulemJ millijoulemm millimetermOhm, mmilliohmMOhm, MmegohmMOV metal oxide varistorMPa megapascalmpg miles per gallonmph miles per hourMS military standardms millisecondm/sec. meters per secondmtg. mountingMTU Motoren-und Turbinen-UnionMW megawattmW milliwattF microfaradN, norm. normal (power source)NA not available, not applicablenat. gas natural gas

NBS National Bureau of StandardsNC normally closedNEC National Electrical CodeNEMA National Electrical

Manufacturers AssociationNFPA National Fire Protection

AssociationNm newton meterNO normally openno., nos. number, numbersNPS National Pipe, StraightNPSC National Pipe, Straight-couplingNPT National Standard taper pipe

thread per general useNPTF National Pipe, Taper-FineNR not required, normal relayns nanosecondOC overcrankOD outside diameterOEM original equipment

manufacturerOF overfrequencyopt. option, optionalOS oversize, overspeedOSHA Occupational Safety and Health

AdministrationOV overvoltageoz. ouncep., pp. page, pagesPC personal computerPCB printed circuit boardpF picofaradPF power factorph., phasePHC Phillipsr head Crimptiter

(screw)PHH Phillipsr hex head (screw)PHM pan head machine (screw)PLC programmable logic controlPMG permanent magnet generatorpot potentiometer, potentialppm parts per millionPROM programmable read-only

memorypsi pounds per square inchpsig pounds per square inch gaugept. pintPTC positive temperature coefficientPTO power takeoffPVC polyvinyl chlorideqt. quart, quartsqty. quantityR replacement (emergency)

power sourcerad. radiator, radiusRAM random access memoryRDO relay driver outputref. referencerem. remoteRes/Coml Residential/CommercialRFI radio frequency interferenceRH round headRHM round head machine (screw)rly. relayrms root mean squarernd. roundRO read onlyROM read only memoryrot. rotate, rotatingrpm revolutions per minuteRS right sideRTDs Resistance Temperature

Detectors

RTU remote terminal unitRTV room temperature vulcanizationRW read/writeSAE Society of Automotive

Engineersscfm standard cubic feet per minuteSCR silicon controlled rectifiers, sec. secondSI Systeme international d’unites,

International System of UnitsSI/EO side in/end outsil. silencerSMTP simple mail transfer protocolSN serial numberSNMP simple network management

protocolSPDT single-pole, double-throwSPST single-pole, single-throwspec specificationspecs specification(s)sq. squaresq. cm square centimetersq. in. square inchSMS short message serviceSS stainless steelstd. standardstl. steeltach. tachometerTB terminal blockTCP transmission control protocolTD time delayTDC top dead centerTDEC time delay engine cooldownTDEN time delay emergency to

normalTDES time delay engine startTDNE time delay normal to

emergencyTDOE time delay off to emergencyTDON time delay off to normaltemp. temperatureterm. terminalTHD total harmonic distortionTIF telephone influence factortol. toleranceturbo. turbochargertyp. typical (same in multiple

locations)UF underfrequencyUHF ultrahigh frequencyUIF user interfaceUL Underwriter’s Laboratories, Inc.UNC unified coarse thread (was NC)UNF unified fine thread (was NF)univ. universalURL uniform resource locator

(web address)US undersize, underspeedUV ultraviolet, undervoltageV voltVAC volts alternating currentVAR voltampere reactiveVDC volts direct currentVFD vacuum fluorescent displayVGA video graphics adapterVHF very high frequencyW wattWCR withstand and closing ratingw/ withWO write onlyw/o withoutwt. weightxfmr transformer

Page 39: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust
Page 40: Residential/Commercial Generator Sets - Wholesale Solar...on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust

E 2015 by Kohler Co. All rights reserved.

TP-6967 8/15

KOHLER CO. Kohler, Wisconsin 53044Phone 920-457-4441, Fax 920-459-1646

Kohler Power SystemsAsia Pacific Headquarters7 Jurong Pier RoadSingapore 619159Phone (65) 6264-6422, Fax (65) 6264-6455

For the nearest KOHLER authorizedinstallation, service, and sales dealer inthe US and Canada:Call 1-800-544-2444 or visitKOHLERPower.com