Residential/Commercial Generator Sets Models: 8.5/12/18RES 12/18TRES Controller: Advanced Digital Control ADC-RES TP-6515 1/11e Operation

Upload: others

Post on 27-May-2020

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Residential/Commercial Generator Sets

Models:

8.5/12/18RES

12/18TRES

Controller:

Advanced Digital Control ADC-RES

TP-6515 1/11e

Operation

Page 2: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Engine exhaust from this product contains chemicals

known to the State of California to cause cancer, birth

defects, or other reproductive harm.

WARNING

California Proposition 65

Product Identification Information

Product identification numbers determine service parts.

Record the product identification numbers in the spaces

below immediately after unpacking the products so that

the numbers are readily available for future reference.

Record field-installed kit numbers after installing the

kits.

Generator Set Identification Numbers

Record the product identification numbers from the

generator set nameplate(s).

Model Designation

Specification Number

Serial Number

Accessory Number Accessory Description

Controller Identification

Record the controller description from the generator set

operation manual, spec sheet, or sales invoice.

Controller Description

Engine Identification

Record the product identification information from the

engine nameplate.

Manufacturer

Model Designation

Serial Number

Page 3: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Table of Contents

TP-6515 1/11 Table of Contents

Product Identification Information 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Safety Precautions and Instructions 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Introduction 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service Assistance 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 1 Specifications 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.1 Introduction 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Generator 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3 Engine 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.4 Advanced Digital Control 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.5 Service Views for Maintenance 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 2 Operation 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Prestart Checklist 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Exercising Generator Set 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 ADC-RES Controls and Indicators 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 LED Display 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.2 Controller Keypad 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.3 Generator Set Master Switch 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Controller Power 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 Standby Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.2 Sleep Mode 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5 Generator Set Operation 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Starting Generator Set 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.2 Stopping Generator Set 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.3 Resetting Emergency Stop Switch (TRES Models only) 18. . . . . . . . . . . . .

2.6 Faults 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6.1 Shutdowns 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6.2 Warnings 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.6.3 Resetting Controller after a Fault Shutdown 19. . . . . . . . . . . . . . . . . . . . . . .

2.7 Battery Charger 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.7.1 RES Battery Charger 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.7.2 TRES Battery Charger 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 3 Scheduled Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Scheduled Maintenance 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.1 Service Schedule, 8.5/12 kW Models 24. . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1.2 Service Schedule, 18 kW Models 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Lubrication System 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.1 Low Oil Pressure Shutdown 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.2 Oil Check 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.3 Engine Oil Recommendation 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.4 Oil Change Procedure 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2.5 Oil Cooler, 18 kW 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Spark Plugs 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Air Cleaner Service 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Air Cleaner, 8.5/12RES 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 Air Cleaner, 18RES 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5 Cooling System 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.6 Exhaust System 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.7 Battery 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.8 Battery Charger 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9 Circuit Protection 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.1 Line Circuit Breaker 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.9.2 Fuses 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 4: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Table of Contents, continued

TP-6515 1/11Table of Contents

3.10 Storage Procedure 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.1 Lubricating System 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.2 Fuel System 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.3 Cylinder Lubrication 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.4 Exterior Preparation 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.10.5 Battery 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Section 4 Troubleshooting 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 Introduction 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.2 Controller Troubleshooting 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Generator Set Troubleshooting 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4 Battery Charger Troubleshooting 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Appendix A Abbreviations 39. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 5: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 5Safety Precautions and Instructions

Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS.

Electromechanical equipment,including generator sets, transferswitches, switchgear, andaccessories, can cause bodily harmand pose life-threatening danger whenimproperly installed, operated, ormaintained. To prevent accidents beaware of potential dangers and actsafely. Read and follow all safetyprecautions and instructions. SAVETHESE INSTRUCTIONS.

This manual has several types ofsafety precautions and instructions:Danger, Warning, Caution, and Notice.

DANGER

Danger indicates the presence of ahazard that will cause severe

personal injury, death, orsubstantial property damage.

WARNING

Warning indicates the presence of ahazard that can cause severe

personal injury, death, orsubstantial property damage.

CAUTION

Caution indicates the presence of ahazard that will or can cause minor

personal injury or property damage.

NOTICE

Notice communicates installation,operation, or maintenance informationthat is safety related but not hazardrelated.

Safety decals affixed to the equipmentin prominent places alert the operatoror service technician to potentialhazards and explain how to act safely.The decals are shown throughout thispublication to improve operatorrecognition. Replace missing ordamaged decals.

Accidental Starting

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set.Accidental starting can causesevere injury or death. Beforeworking on the generator set orconnected equipment, disable thegenerator set as follows: (1) Move thegenerator set master switch to theOFFposition. (2) Disconnect the power tothe battery charger. (3) Remove thebattery cables, negative (--) lead first.Reconnect the negative (--) lead lastwhen reconnecting the battery. Followthese precautions to prevent starting ofthe generator set by an automatictransfer switch, remote start/stopswitch, or engine start command fromaremote computer.

Battery

Sulfuric acid in batteries.Can cause severe injury or death.

Wear protective goggles andclothing. Battery acid may causeblindness and burn skin.

WARNING

Explosion.Can cause severe injury or death.Relays in the battery chargercause arcs or sparks.

Locate the battery in awell-ventilatedarea. Isolate thebattery charger fromexplosive fumes.

WARNING

Battery electrolyte is a dilutedsulfuric acid. Battery acid cancausesevere injuryordeath. Batteryacid can cause blindness and burnskin. Always wear splashproof safetygoggles, rubber gloves, and bootswhen servicing the battery. Do notopen a sealed battery or mutilate thebattery case. If battery acid splashes inthe eyes or on the skin, immediatelyflush the affected area for 15 minuteswith large quantities of clean water.Seek immediate medical aid in thecase of eye contact. Never add acid toa battery after placing the battery inservice, as this may result inhazardous spattering of battery acid.

Battery acid cleanup. Battery acidcan cause severe injury or death.Battery acid is electrically conductiveand corrosive. Add 500 g (1 lb.) ofbicarbonate of soda (baking soda) to acontainer with 4 L (1 gal.) of water andmix the neutralizing solution. Pour theneutralizing solution on the spilledbattery acid and continue to add theneutralizing solution to the spilledbattery acid until all evidence of achemical reaction (foaming) hasceased. Flush the resulting liquid withwater and dry the area.

Page 6: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/116 Safety Precautions and Instructions

Battery gases. Explosion can causesevere injury or death. Battery gasescan cause an explosion. Do not smokeor permit flames or sparks to occurnear a battery at any time, particularlywhen it is charging. Do not dispose of abattery in a fire. To prevent burns andsparks that could cause an explosion,avoid touching the battery terminalswith tools or other metal objects.Remove all jewelry before servicingthe equipment. Discharge staticelectricity from your body beforetouching batteries by first touching agrounded metal surface away from thebattery. To avoid sparks, do not disturbthe battery charger connections whilethe battery is charging. Always turn thebattery charger off beforedisconnecting the battery connections.Ventilate the compartments containingbatteries to prevent accumulation ofexplosive gases.

Battery short circuits. Explosioncan cause severe injury or death.Short circuits can cause bodily injuryand/or equipment damage.Disconnect the battery beforegenerator set installation ormaintenance. Remove all jewelrybefore servicing the equipment. Usetools with insulated handles. Removethe negative (--) lead first whendisconnecting the battery. Reconnectthe negative (--) lead last whenreconnecting the battery. Neverconnect the negative (--) battery cableto the positive (+) connection terminalof the starter solenoid. Do not test thebattery condition by shorting theterminals together.

Engine Backfire/FlashFire

Fire.Can cause severe injury or death.

Do not smoke or permit flames orsparks near fuels or the fuel system.

WARNING

Servicing the air cleaner. A suddenbackfire can cause severe injury ordeath. Do not operate the generatorset with the air cleaner removed.

Servicing the fuel system. A flashfire can cause severe injury ordeath. Do not smoke or permit flamesor sparks near the carburetor, fuel line,fuel filter, fuel pump, or other potentialsources of spilled fuels or fuel vapors.Catch fuels in an approved containerwhen removing the fuel line orcarburetor.

Combustible materials. A fire can

cause severe injury or death.Generator set engine fuels and fuelvapors are flammable and explosive.Handle these materials carefully tominimize the risk of fire or explosion.Equip the compartment or nearby areawith a fully charged fire extinguisher.Select a fire extinguisher rated ABC orBC for electrical fires or asrecommended by the local fire code oran authorized agency. Train allpersonnel on fire extinguisheroperation and fire preventionprocedures.

Exhaust System

Carbon monoxide.Can cause severe nausea,fainting, or death.

The exhaust system must beleakproof and routinely inspected.

WARNING

Generator set operation. Carbon

monoxide can cause severe

nausea, fainting, or death. Carbon

monoxide is an odorless, colorless,

tasteless, nonirritating gas that can

cause death if inhaled for even a short

time. Avoid breathing exhaust fumes

when working on or near the generator

set. Never operate the generator set

inside a building. Never operate the

generator set where exhaust gas could

seep inside or be drawn into a

potentially occupied building through

windows, air intake vents, or other

openings.

Carbon monoxide symptoms.Carbonmonoxide can cause severenausea, fainting, or death. Carbonmonoxide is a poisonous gas presentin exhaust gases. Carbon monoxide isan odorless, colorless, tasteless,nonirritating gas that can cause death ifinhaled for even a short time. Carbonmonoxide poisoning symptomsinclude but are not limited to thefollowing:

Light-headedness, dizziness Physical fatigue, weakness in

joints and muscles Sleepiness, mental fatigue,

inability to concentrateor speak clearly, blurred vision

Stomachache, vomiting, nauseaIf experiencing any of these symptomsand carbon monoxide poisoning ispossible, seek fresh air immediatelyand remain active. Do not sit, lie down,or fall asleep. Alert others to thepossibility of carbon monoxidepoisoning. Seek medical attention ifthe condition of affected persons doesnot improvewithinminutes of breathingfresh air.

Fuel System

Explosive fuel vapors.Can cause severe injury or death.

Use extreme care when handling,storing, and using fuels.

WARNING

Gas fuel leaks. Explosive fuelvapors can cause severe injury ordeath. Fuel leakage can cause anexplosion. Check the LP vapor gas ornatural gas fuel system for leakage byusing a soap and water solution withthe fuel system test pressurized to6--8 ounces per square inch(10--14 inches water column). Do notuse a soap solution containing eitherammonia or chlorine because bothprevent bubble formation. Asuccessful test depends on the abilityof the solution to bubble.

Page 7: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 7Safety Precautions and Instructions

Hazardous Noise

Hazardous noise.

Can cause hearing loss.

Never operate the generator setwithout a muffler or with a faultyexhaust system.

CAUTION

Engine noise. Hazardous noise cancause hearing loss. Generator setsnot equipped with sound enclosurescan produce noise levels greater than105 dBA. Prolonged exposure tonoise levels greater than 85 dBA cancause permanent hearing loss. Wearhearing protection when near anoperating generator set.

Hazardous Voltage/Moving Parts

Hazardous voltage.Can cause severe injury or death.

Operate the generator set only whenall guards and electrical enclosuresare in place.

Moving parts.

WARNING

Hazardous voltage.

Backfeed to the utility system can

cause property damage, severe

injury, or death.

If the generator set is used forstandby power, install an automatictransfer switch to prevent inadvertentinterconnection of standby andnormal sources of supply.

WARNING

Welding the generator set.

Can cause severe electrical

equipment damage.

Never weld components of thegenerator set without firstdisconnecting the battery, controllerwiring harness, and engineelectronic control module (ECM).

CAUTION

Grounding electrical equipment.Hazardous voltage can causesevere injury or death. Electrocutionis possible whenever electricity ispresent. Ensure you comply with allapplicable codes and standards.Electrically ground the generator set,transfer switch, and related equipmentand electrical circuits. Turn off themain circuit breakers of all powersources before servicing theequipment. Never contact electricalleads or appliances when standing inwater or on wet ground because theseconditions increase the risk ofelectrocution.

Welding on the generator set. Cancause severe electrical equipmentdamage. Before welding on thegenerator set perform the followingsteps: (1) Remove the battery cables,negative (--) lead first. (2) Disconnectall engine electronic control module(ECM) connectors. (3) Disconnect allgenerator set controller and voltageregulator circuit board connectors.(4) Disconnect the engine battery-charging alternator connections.(5) Attach the weld ground connectionclose to the weld location.

Connecting the battery and thebattery charger. Hazardous voltagecan cause severe injury or death.Reconnect the battery correctly,positive to positive and negative tonegative, to avoid electrical shock anddamage to the battery charger andbattery(ies). Have a qualifiedelectrician install the battery(ies).

Short circuits. Hazardousvoltage/current can cause severeinjury or death. Short circuits cancause bodily injury and/or equipmentdamage. Do not contact electricalconnections with tools or jewelry whilemaking adjustments or repairs.Remove all jewelry before servicingthe equipment.

Electrical backfeed to the utility.

Hazardous backfeed voltage cancause severe injury or death. Installa transfer switch in standby powerinstallations to prevent the connectionof standby and other sources of power.Electrical backfeed into a utilityelectrical system can cause severeinjury or death to utility personnelworking on power lines.

Airborne particles.

Can cause severe injury or

blindness.

Wear protective goggles and clothingwhen using power tools, hand tools,or compressed air.

WARNING

Heavy Equipment

Unbalanced weight.

Improper lifting can cause severe

injury or death and equipment

damage.

Do not use lifting eyes.Lift the generator set using lifting barsinserted through the lifting holes onthe skid.

WARNING

Page 8: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/118 Safety Precautions and Instructions

Hot Parts

Hot engine and exhaust system.Can cause severe injury or death.

Do not work on the generator set untilit cools.

WARNING

Servicing the exhaust system. Hotparts can cause severe injury ordeath. Do not touch hot engine parts.The engine and exhaust systemcomponents become extremely hotduring operation.

Servicing the engine heater. Hotparts can cause minor personalinjuryorpropertydamage. Install theheater before connecting it to power.Operating the heater beforeinstallation can cause burns andcomponent damage. Disconnectpower to the heater and allow it to coolbefore servicing the heater or nearbyparts.

Notice

NOTICE

Canadian installations only. Forstandby service connect the output ofthe generator set to a suitably ratedtransfer switch in accordance withCanadian Electrical Code, Part 1.

Page 9: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 9Introduction

Introduction

This manual provides operation and maintenance

instructions for residential/commercial generator sets

equipped with ADC-RES controls. The generator set

models covered by this manual are listed on the front

cover.

This generator set is approved for use in stationary

applications in locations served by a reliable utility

power source. Have the generator set installed by an

authorized distributor/dealer or service technician.

Refer to TP-6514, Installation Manual, for installation

instructions.

Information in this publication represents data available

at the time of print. Kohler Co. reserves the right to

change this publication and the products represented

without notice and without any obligation or liability

whatsoever.

Read this manual and carefully follow all procedures

and safety precautions to ensure proper equipment

operation and to avoid bodily injury. Read and follow the

Safety Precautions and Instructions section at the

beginning of this manual. Keep this manual with the

equipment for future reference.

The equipment service requirements are very important

to safe and efficient operation. Inspect the parts often

and perform required service at the prescribed intervals.

Obtain service from an authorized service distributor/

dealer to keep equipment in top condition.

Nameplate

The following illustration shows a typical generator set

nameplate. Copy the model, serial, and specification

numbers from the nameplate into the spaces provided in

the product information section on the inside front cover

of this manual. See Section 1.5 for the nameplate

location.

Emission Information

The Kohler Model CH640 engine used on the model

8.5RES generator set, CH740 engine used on the

12RES generator set, and CH980 engine used on the

18RES generator set are certified to operate using

natural gas or propane fuel.

The Emission Compliance Period referred to on the

EmissionControl or Air Index label indicates the number

of operating hours for which the engine has been shown

to meet CARB or EPA emission requirements. The

following table provides the engine compliance period

(in hours) associatedwith the category descriptor, which

may be found on the certification label.

Emission Compliance Period

EPACategory C250 hours

Category B500 hours

Category A1000 hours

CARBModerate125 hours

Intermediate250 hours

Extended500 hours

Figure 1 Emission Compliance Period

Refer to the certification label for engine displacement.

The exhaust emission control system for the CH640,

CH740, and CH980 engines is EM for U.S. EPA,

California, and Europe.

The engine used in the Model 18RES generator set is

certified for emergency standby use only.

Page 10: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1110 Service Assistance

Service Assistance

For professional advice on generator set power

requirements and conscientious service, please contact

your nearest Kohler distributor or dealer.

Consult the Yellow Pages under the heading

Generators—Electric.

Visit the Kohler Power Systems website at

KohlerPower.com.

Look at the labels and stickers on your Kohler product

or review the appropriate literature or documents

included with the product.

Call toll free in the US and Canada 1-800-544-2444.

Outside the US andCanada, call the nearest regional

office.

Headquarters Europe, Middle East, Africa

(EMEA)

Kohler Power Systems

3 rue de Brennus

93200 Saint Denis

France

Phone: (33) 1 49 178300

Fax: (33) 1 49 178301

Asia Pacific

Power Systems Asia Pacific Regional Office

Singapore, Republic of Singapore

Phone: (65) 6264-6422

Fax: (65) 6264-6455

China

North China Regional Office, Beijing

Phone: (86) 10 6518 7950

(86) 10 6518 7951

(86) 10 6518 7952

Fax: (86) 10 6518 7955

East China Regional Office, Shanghai

Phone: (86) 21 6288 0500

Fax: (86) 21 6288 0550

India, Bangladesh, Sri Lanka

India Regional Office

Bangalore, India

Phone: (91) 80 3366208

(91) 80 3366231

Fax: (91) 80 3315972

Japan, Korea

North Asia Regional Office

Tokyo, Japan

Phone: (813) 3440-4515

Fax: (813) 3440-2727

Latin America

Latin America Regional Office

Lakeland, Florida, USA

Phone: (863) 619-7568

Fax: (863) 701-7131

Page 11: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 11Section 1 Specifications

Section 1 Specifications

1.1 Introduction

The generator set specification sheets provide specific

generator and engine information. Refer to the spec

sheet for data not supplied in this manual. Consult the

generator set servicemanual, engine operationmanual,

and engine service manual for additional specifications.

Obtain copies of the latest spec sheets, manuals,

diagrams, and drawings from your local distributor/

dealer.

1.2 Generator

The generator uses Kohler’s unique PowerBoost

voltage regulation system, which provides instant

response to load changes.

PowerBoost ensures reliable motor starting and

consistent voltage levels. PowerBoost utilizes a

voltage excitation system that employs a winding

independent of the main output windings to provide

excitation voltage.

1.3 Engine

The generator set has a four-cycle, twin cylinder, air-

cooled Kohler engine. The engine operates on clean-

burning natural gas or propane (LP) vapor. Engine

features include:

Efficient overhead valve design and full pressure

lubrication for maximum power, torque, and reliability

under all operating conditions.

Dependable, maintenance-free electronic ignition.

Precision-formulated cast iron construction of parts

subjected to the most wear and tear.

Field-convertible multi-fuel systems that allow fuel

changeover from natural gas to LP vapor (and vice-

versa) while maintaining CARB emission

certification.

Digital spark advance optimizes ignition timing for the

selected fuel. (12 --18 kW models)

1.4 Advanced Digital Control

The generator set is equipped with the Kohler

ADC-RES Advanced Digital Control. Controller

features include the following:

Compact controller

Integrally mounted to the generator set

LED display:

Engine runtime, hours

AC voltage

Frequency (Hz)

Battery voltage

Crank cycle status

Setup information

Application software version

LED display communicates faults:

High battery voltage

High engine temperature

Low battery voltage

Low oil pressure

Overcrank safety

Overfrequency

Overspeed

Overvoltage

Underfrequency

Undervoltage

Membrane keypad for configuration and adjustment

Password-protected user access to menus

Voltage, gain, and speed adjustment

System configuration (system voltage/frequency

settings and generator set model)

Remote two-wire start/stop capability

Digital isochronous governor to maintain steady-

state speed at all loads

Digital voltage regulation: ±1.5% RMS no-load to

full-load

Automatic start for programmed cranking cycle

Master control switch mounted on the junction box:

Run/Off-Reset/Auto

Upgradeable application software

Page 12: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1112 Section 1 Specifications

1.5 Service Views for Maintenance

ADV-7466-

1. Muffler

2. Oil check3. Oil fill

4. Air cleaner

5. Fuses6. RS-232 connector (for application program updates)

7. Controller user interface (see Figure 2-1)

8. Generator set master switch (RUN-OFF/RESET-AUTO)

9. Line circuit breaker (single-phase models)*10. Field-connection terminal block location (single-phase

models)*

11. Spark plug locations (both sides)12. Oil drain hose

13. Oil drain valve

14. Oil filter15. Exhaust

16. Equipment ground

17. Relay board location (optional)18. Battery charger (single-phase models)

19. DSAI lead location (12 kW models)

20. Fuel block

21. Gas regulator assembly22. Fuel solenoid valve

23. Fuel inlet

24. Air intake25. Engine starting battery location (battery purchased separately)

1 2 3 4

14 13

25

9

816

18 21

22

23

24

15

11

10

19 2017

12

5 6 7

24

* See Figure 1-3 for additional components for 3-phase models.

See Figure 2-9 for 3-phase battery charger locations.

Figure 1-1 Generator Set Components, 8.5/12 kW

Page 13: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 13Section 1 Specifications

1 2 54 21

16

63

13 26

17

20

1415

24

ADV-7341A-B

10

2725

9

18 22

28

Control detail, top view 8

11

7

12

1. Muffler

2. Oil check3. Oil fill

4. Air cleaner

5. Spark plug locations (both sides)6. Oil filter

7. Oil cooler location

8. ADC-RES Advanced Digital Control user interface

9. Generator set master switch (RUN-OFF/RESET-AUTO)10. Line circuit breaker (single-phase models )*

11. Fuses

12. RS-232 connector (for application program updates)13. Engine starting battery location (battery purchased separately)

14. Oil drain hose

15. Nameplate location (on base)

16. Oil drain valve

17. Exhaust outlet18. Relay board location (optional)

19. Carburetor heater access opening

20. LP fuel orifice location (inside hose fitting)21. Gas regulator assembly

22. DSAI leads

23. Fuel solenoid valve

24. Fuel inlet25. Air intake

26. Battery cables

27. Battery charger (single-phase models)28. Field-connection terminal block location (single-phase models)*

29. 120 VAC receptacles for battery charger and optional

carburetor heater (single-phase models)

See controldetail 19

29

23

25

25

* See Figure 1-3 for additional components for 3-phase models.

See Figure 2-9 for 3-phase battery charger locations.

Figure 1-2 Generator Set Components, 17/18 kW

Page 14: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1114 Section 1 Specifications

1

GM66010

1. Emergency stop switch

2. Field-connection terminal block and circuit breakers3. Cable inlet area

2

3

Figure 1-3 Additional Components, TRES (3-phase)

Models

Page 15: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 15Section 2 Operation

Section 2 Operation

2.1 Prestart Checklist

To ensure continued satisfactory operation, perform the

following checks or inspections before or at each

startup, as designated, and at the intervals specified in

the service schedule. In addition, some checks require

verification after the unit starts.

Air Cleaner. Check for a clean and installed air cleaner

element to prevent unfiltered air from entering the

engine.

Air Inlets. Check for clean and unobstructed air inlets.

Battery. Check for tight battery connections. Consult

the battery manufacturer’s instructions regarding

battery care and maintenance.

Exhaust System. Check for exhaust leaks and

blockages. Check the muffler condition and check for

tight exhaust system connections.

Inspect the exhaust system components for cracks,

leaks, and corrosion.

Check for corroded or brokenmetal parts and replace

them as needed.

Check that the exhaust outlet is unobstructed.

Oil Level. Maintain the oil level at or near, not over, the

full mark on the dipstick.

Operating Area. Check for obstructions that could

block the flow of cooling air. Keep the air intake area

clean. Do not leave rags, tools, or debris on or near the

generator set.

2.2 Exercising Generator Set

Operate the generator set without load once each week

for 20 minutes. If the generator set is not connected to

an automatic transfer switch (ATS) with an exercise

option, exercise the unit in the presence of an operator.

The operator should perform all of the prestart checks

before starting the exercise procedure. Start the

generator set according to the starting procedure in the

controller section of this manual. While the generator

set is operating, listen for a smooth-running engine and

visually inspect the generator set for fluid or exhaust

leaks. Check the air inlets and outlets and remove any

items restricting the air flow.

2.3 ADC-RES Controls and

Indicators

Figure 2-1 illustrates the ADC-RES user interface and

other items on the generator set junction box.

Figure 2-2 describes the ADC-RES controls and

indicators.

1. LED display

2. Up and down arrow buttons3. Generator set master switch

4. Line circuit breaker (single-phase models)

5. Fuses6. RS-232 connector (for application program upgrade)

7. Select button (use for setup and adjustment only)

1

7

3

2

4

5

6

Figure 2-1 ADC-RES Controls

2.3.1 LED Display

The LED display is activated by a start or RUN

command as follows:

Move the master switch to RUN.

With the master switch in AUTO, send a remote start

command (close the remote start contact across

leads 3 and 4).

The LED display indicates generator set status as

shown in Figure 2-2. When the generator set is running,

engine runtime hours are shown unless the arrow

buttons are used to step through the other displays as

described in Section 2.3.2.

When the master switch is in AUTO, the display may

turn off 48 hours after generator set shutdown. See

Section 2.4, Controller Power.

Page 16: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1116 Section 2 Operation

Control or Indicator Item Description

LED display Runtime hours Displays total generator set runtime hours while the generator set is running andwhen no other codes are displayed.

Meteringdisplay

Displays AC voltage (output), frequency, and battery voltage. Press the up ordown arrow when runtime hours are displayed to step through these displays.

Crank indication Displays CC_1, CC_2, or CC_3 to indicate the first, second, or third attempt tostart the engine. The last digit flashes during the crank cycle rest periods.

Softwareversion number

The software version number (v#.##) is displayed when entering configurationmode. See the installation manual.

Fault codes Flashes a 2- or 3-letter fault code to indicate various fault conditions. SeeSection 2.6.

Keypad Select andarrow buttons

Use the arrow buttons to step through the data displays. See Figure 2-3.

The keypad is also used for controller setup and adjustment. The setup andadjustment functions are password-protected. Have setup and adjustmentsperformed only by an authorized distributor/dealer.

Generator set masterswitch

Three-positionswitch

Switch functions as the generator set operation and controller reset switch.

Figure 2-2 ADC-RES Controls and Indicators

2.3.2 Controller Keypad

The three buttons on the controller keypad are Select,

Up, and Down. See Figure 2-1.

When the generator set is running, the up and down

arrow buttons can be used to step through system data

displays as shown in Figure 2-3. After 10 seconds, the

display returns to engine runtime hours.

The buttons on the controller keypad are also used for

system configuration and adjustment. The system

configuration is factory-set and should not require

changes under normal operating conditions. Contact an

authorized distributor/dealer or service technician if

adjustments are required.

2.3.3 Generator Set Master Switch

The generator set master switch is located on the

junction box below the ADC-RES user interface. The

master switch positions are RUN, OFF/RESET, and

AUTO. See Section 2.5 for operation instructions.

Generator set master switch in AUTO

Step through using up or down arrow buttons

After 10 seconds, display returns to runtime hours

tp6515

Engine RuntimeXXX.X hours

Output VoltageVAC

Output FrequencyHz

Battery VoltageVDC

Figure 2-3 Data Displays

Page 17: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 17Section 2 Operation

2.4 Controller Power

The ADC-RES is powered by the generator set engine

starting battery.

Note: The generator sets are equipped with factory-

installed battery chargers to prevent battery

discharge. The battery charger must be

connected to utility power.

2.4.1 Standby Mode

When the generator set master switch is in the AUTO

position and the engine is not running, the controller is in

standby mode. Engine runtime hours are shown on the

display. A remote start signal (contact closure) will start

and run the generator set.

The controller can be set to go into sleepmode if there is

no start signal for 48 hours.

2.4.2 Sleep Mode

Controllers with application code version 1.13 or higher

are shipped with the sleep mode disabled and J1939

communication enabled. The controller will remain in

standby mode whenever the master switch is in AUTO

and the engine is not running.

Communication parameter Cn can be changed to

disable communication and enable the sleep mode if

remote communication is not required. See Installation

Manual TP-6514 for instructions to change parameter

Cn.

SleepMode. If the controller communication is disabled

and the generator set master switch is in the AUTO

position, the controller powers down automatically after

48 hours of inactivity. The controller display is dark and

battery draw is minimized. A remote start signal from a

transfer switch or a remote start/stop switch connected

to controller leads 3 and 4 reactivates the controller.

Moving the generator set master switch to the RUN

position also activates the controller.

2.5 Generator Set Operation

2.5.1 Starting Generator Set

Local Starting

Move the generator set master switch to the RUN

position to immediately start the generator set.

Auto (Automatic) Starting

Move the generator set master switch to the AUTO

position to allow startup by an automatic transfer switch

(ATS) or remote start/stop switch, if equipped. Close a

contact across engine start leads 3 and 4 to signal the

controller to start the generator set.

Crank Cycle

The controller attempts to start the generator set three

times (three crank cycles, 15 seconds crank and

15 seconds off). See Figure 2-2 for display information

during the crank cycle. If the generator set does not start

in three attempts, the system shuts down on an

overcrank fault. See Section 2.6.

2.5.2 Stopping Generator Set

Local Stopping

1. Run the generator set with no load for at least

2 minutes to ensure adequate engine cooldown.

2. Move the generator set master switch to the OFF/

RESET position. The engine stops.

Automatic Stopping

With the generator set master switch in the AUTO

position, open the contact across engine start leads 3

and 4 to signal the generator set to stop.

An automatic transfer switch (ATS) connected to

controller leads 3 and 4 operates as follows:

1. The ATS disconnects the load from the generator

set.

2. If the ATS is equipped with an engine cooldown

time delay, the generator set continues to run for a

preset engine cooldown time.

Note: There is no engine cooldown time delay on

the ADC-RES controller.

3. The ATS opens the connection between controller

leads 3 and 4. The generator set shuts down. The

controller enters standby mode and displays

engine runtime hours.

Page 18: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1118 Section 2 Operation

Emergency Stopping (TRES Models Only)

Push the red emergency stop switch for immediate

generator set shutdown in the case of an emergency.

See Figure 2-4 for the emergency stop switch location.

The emergency stop switch shuts down the generator

set immediately. The controller display shows AF

(auxiliary fault) when the emergency stop button is

activated.

Use the generator set master switch for normal

shutdowns.

1

GM66010

1. Emergency stop switch

Figure 2-4 Emergency Stop Switch, TRES Models

2.5.3 Resetting Emergency Stop Switch

(TRES Models only)

Use the following procedure to reset the generator set

after shutdown by the emergency stop switch. See

Section 2.6.3 to reset the generator set after a fault

shutdown.

1. Place the generator set master switch in the

OFF/RESET position.

2. Investigate and correct the cause of the

emergency stop.

3. Rotate the emergency stop switch knob clockwise

and release it. Check that the knob returns to the

deactivated (out) position.

4. Move the generator set master switch to the RUN

or AUTO position to restart the generator set.

Verify that the controller display no longer shows a

fault code. The generator set engine will not start

until the reset procedure is complete.

Page 19: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 19Section 2 Operation

2.6 Faults

2.6.1 Shutdowns

Under the fault shutdown conditions listed in Figure 2-5,

the generator set shuts down automatically and the

controller displays a fault code. The generator set

cannot be restarted until the fault condition is corrected

and the controller is reset. SeeSection 2.6.3 to reset the

controller after a fault shutdown.

The shutdown switches on the generator set will

automatically reset when the problem is corrected. For

example, the high engine temperature switch resets

automatically when the generator set cools. However,

the fault does not clear until the controller is reset.

2.6.2 Warnings

The controller displays a fault code but the generator set

does not shut down on a high battery voltage warning or

a low battery voltage warning. The controller resets

automatically after a battery voltage fault condition is

corrected.

2.6.3 Resetting Controller after a Fault

Shutdown

Always identify and correct the cause of a fault

shutdown before resetting the controller. Check the

fault code displayed on the ADC-RES and refer to

Figure 2-5 to identify and correct the fault condition

before proceeding.

Use the following procedure to reset the generator set

controller after a fault shutdown.

1. Move the generator set master switch to OFF/

RESET.

2. Disconnect the generator set from the load using

the line circuit breaker or ATS. See the safety

precautions at the beginning of this manual before

proceeding.

3. Identify and correct the cause of the fault

shutdown. See the safety precautions at the

beginning of this manual before proceeding. Refer

to Section 4, Troubleshooting.

4. Start the generator set bymoving the generator set

master switch to RUN. Test operate the generator

set to verify that the cause of the shutdown has

been corrected.

5. Move the generator set master switch to OFF/

RESET.

6. Reconnect the generator set to the load using the

line circuit breaker or ATS.

7. Move the generator set master switch to the AUTO

position for startup by remote transfer switch or

remote start/stop switch.

Note: The controller’s LED display remains off

until an engine start command is received.

Page 20: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1120 Section 2 Operation

Code Fault Description Check

AF Auxiliary faultinput shutdown

Indicates a shutdown initiated by pushing the emergencystop switch. (TRES models only)

Not used on RES models.

Check the position of the emergencystop button. (TRES models only)

HE High enginetemperatureshutdown

Shutdown occurs if the engine coolant temperatureexceeds the maximum temperature for more than5 seconds. This function becomes active after the enginereaches the crank disconnect speed.

Check for blocked air inlets andexhaust outlets.

LOP Low oilpressureshutdown

Shutdown occurs if a low oil pressure condition exists formore than 5 seconds. This function becomes active30 seconds after the engine has reached crank disconnectspeed (30 second inhibit).

Note: The low oil pressure shutdown does not protectagainst low oil level. Check the oil level at the engine.

Check for leaks in the lubricationsystem.

Check the oil level and add oil if thelevel is low.

OC Overcrankshutdown

Shutdown occurs after 3 unsuccessful starting attempts.The crank cycle is set for three starting attempts of 15seconds cranking and 15 seconds rest.

Check the fuel supply, spark plug,and battery.

Check for loose connections.

Contact an authorizeddistributor/dealer for service ifproblem continues.

Locked rotor The generator set also shuts down on OC if no enginerotation is sensed during cranking. Shuts down 3 secondsafter the fault is detected.

OF Overfrequencyshutdown

Shutdown occurs when the governed frequency exceeds110% of the system’s frequency setpoint for more than 5seconds. This function becomes active 10 seconds afterengine start (10 second inhibit).

Contact an authorizeddistributor/dealer for service ifproblem continues.

OS Overspeedshutdown

Shutdown occurs if the engine speed exceeds 110% of thenormal running speed for more than 0.3 seconds.

Contact an authorizeddistributor/dealer for service ifproblem continues.

OU Overvoltageshutdown

Shutdown occurs if the voltage exceeds 120% of thesystem nominal voltage for more than 2 seconds.

Contact an authorizeddistributor/dealer for service ifproblem continues.

UF Underfrequencyshutdown

Shutdown occurs if the governed frequency falls below54 Hz for more than 5 seconds.

Shutdown also occurs if the governed frequency fallsbelow 56.5 Hz for more than 60 seconds.

This function becomes active 10 seconds after enginestart. (10 second inhibit).

Reduce the load and restart thegenerator set.

Contact an authorizeddistributor/dealer for service ifproblem continues.

UU Undervoltageshutdown

Shutdown occurs if the voltage falls below 80% of thenominal system voltage for more than 10 seconds.

Reduce the load and restart thegenerator set.

Contact an authorizeddistributor/dealer for service ifproblem continues.

HB High batteryvoltage warning

Fault code is displayed if the engine starting batteryvoltage rises above 16 VDC for more than 30 secondswhen the engine is running. Not operative during theengine crank cycle, this fault condition does not inhibitengine starting.

The fault condition clears when the battery voltage returnsto an acceptable level.

Check the battery rating andcondition.

Check the battery charger operation.

LB Low batteryvoltage warning

Fault code is displayed if the engine starting batteryvoltage falls below 11 VDC for more than 30 seconds whenthe engine is not running. Not operative during the enginecrank cycle, this fault condition does not inhibit enginestarting.

The fault condition clears when the battery voltage returnsto an acceptable level.

Check the battery rating andcondition.

Check the battery charger operation.

Charge or replace the battery.

Figure 2-5 ADC-RES Fault Codes

Page 21: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 21Section 2 Operation

2.7 Battery Charger

2.7.1 RES Battery Charger

RES model generator sets are equipped with a 6-amp

float/equalize battery charger to maintain the engine

starting battery. The charger’s power cord must be

connected to a 120 VAC power source. Figure 2-6

illustrates the battery charger.

The battery charger uses an AGS 10 inline fuse. The

fuse is located in the battery lead. See Figure 2-6.

INDICATOR

Red:

Red & Green:

Green:

VOLTS= 11.8--14.0AMPS= 5.0--6.0

VOLTS= 14.0--14.5AMPS= 1.5--5.0

VOLTS= 13.0--13.6AMPS= 0.1--1.5

CAUTION:To reduce the risk of elect rical shock,connect only to properly gr ounded outlet.

Allowable Battery Types: Lead Acid a nd Gel Cell

INPUT: 115 VAC 50/60Hz @ 1.6A

OUTPUT: 12 VDC @ 6 Amps

MAX. BAT.: 180 Amp Hr. Max.

DATE:

6 AMP AUTOMATIC

BATTERY CHARGER

RC US LISTEDBATTERY CHARGER

53AB

2608KH

1

1. LED indicators

2. AC power cord3. Fuse

4. Battery leads, 12 VDC

4 2

3

Figure 2-6 6-Amp Float/Equalize Battery Charger

Battery Charger Operation

Figure 2-7 illustrates the three-stage charging method.

Red and green LEDs indicate charger operation. The

chart in Figure 2-8 describes the LED indicator

operation during each stage of the charging process.

See Section 4.4 for battery charger troubleshooting

information, if necessary.

Figure 2-7 Charging Method

Display Operating Condition

Red ONGreenOFF

When the red LED is on, it indicates thebattery is discharged and the battery chargeris recharging at the BULK rate (stage 1).This charging rate is 6 amps. While the redLED is on, the voltage measured (with thebattery charger on) will be 11.8--14 volts.

If the red LED stays on for more than24 hours, refer to Section 4.4 in this manual.

Red ONGreen ON

When both the green and the red LEDs areon, the battery charger is charging at anABSORPTION rate of between 1.5 and 5amps (stage 2). This mode of charginggradually tops off your battery, and reducesharmful sulfating. While both LEDs are on,the voltage measured (with the batterycharger on) should be approximately14.0--14.5 VDC.

If both LEDs stay on longer than 24 hours,refer to Section 4.4 in this manual.

Red OFFGreen ON

When the green LED is on, the batterycharger is charging at a FLOAT orMAINTENANCE rate of less than 1.5 amps(stage 3). Your battery is now 90% chargedand ready for use. This float chargingcurrent will gradually decrease to as low as0.1 amps as the battery reaches 100%charge. It will now be kept at full chargewithout overcharging.

If the green LED stays on when your batteryis known to be low, refer to Section 4.4 in thismanual.

Figure 2-8 Battery Charger LED Indicator Functions

Page 22: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1122 Section 2 Operation

2.7.2 TRES Battery Charger

Three-phase model TRES generator sets are equipped

with a 2.5-amp battery charger to maintain the engine

starting battery. Utility power must be supplied to the

generator set for the battery charger.

The battery charger is located in or near the controller

junction box. See Figure 2-9 for the battery charger

location.

A green LED on the side of the battery charger indicates

battery charger operation. See Figure 2-10.

Two internal fuses protect the battery charger. See

Section 4.4 for battery charger troubleshooting

information, if necessary.

1

ADV-7713

1. Battery charger

12 kW

18 kW

1

Figure 2-9 Battery Charger Location, TRES

(3-phase) Models

2

pdf1. Carburetor heater power connection

2. LED3. Cover (open for fuse access)

1 3

Figure 2-10 Battery Charger for 3-Phase Models

Page 23: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 23Section 3 Scheduled Maintenance

Section 3 Scheduled Maintenance

Accidental starting.Can cause severe injury or death.

Disconnect the battery cables beforeworking on the generator set.Remove the negative (--) lead firstwhen disconnecting the battery.Reconnect the negative (--) lead lastwhen reconnecting the battery.

WARNING

Disabling the generator set. Accidental starting cancause severe injury or death. Before working on thegenerator set or connected equipment, disable the generatorset as follows: (1) Move thegenerator setmaster switch to theOFF position. (2) Disconnect the power to the batterycharger. (3) Remove the battery cables, negative (--) leadfirst. Reconnect the negative (--) lead last when reconnectingthebattery. Follow these precautions to prevent starting of thegenerator set by an automatic transfer switch, remotestart/stop switch, or engine start command from a remotecomputer.

Hot engine and exhaust system.Can cause severe injury or death.

Do not work on the generator set untilit cools.

WARNING

Servicing the exhaust system. Hot parts can cause

severe injury or death. Do not touch hot engine parts. Theengine and exhaust system components become extremelyhot during operation.

Hazardous voltage.Can cause severe injury or death.

Operate the generator set only whenall guards and electrical enclosuresare in place.

Moving parts.

WARNING

Servicing thegenerator setwhen it is operating. Exposedmoving parts can cause severe injury or death. Keephands, feet, hair, clothing, and test leads away from the beltsand pulleys when the generator set is running. Replaceguards, screens, and covers before operating the generatorset.

3.1 Scheduled Maintenance

Refer to the following service schedules and the runtime

hours displayed on the ADC-RES display to schedule

routine maintenance. Intervals are shown in hours of

operation and/or time intervals (i.e. weekly, monthly,

quarterly, etc.) Have an authorized distributor/dealer

service the generator set at the designated intervals in

the service schedule for the life of the generator set.

Service units subject to extremeweather, long operating

hours, or dusty or dirty conditions more frequently.

Contact an authorized distributor/dealer for parts.

Page 24: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1124 Section 3 Scheduled Maintenance

3.1.1 Service Schedule, 8.5/12 kW Models

System Component or ProcedureSee

Section

Procedure

Frequency

VisuallyInspect Check Change Clean Test

Fuel

Flexible lines and connections X R Quarterly

Main tank supply level X Weekly

Fuel piping X Yearly

Lubrication 3.2

Oil levelX X

8 hours orbefore use

Crankcase breather hose X Yearly or 500 hours

Change oil X Yearly or 100 hours

Replace filter X Yearly or 200 hours

Cooling 3.5

Air ducts, louvers X X Yearly

Exhaust Line 3.6

Leakage X X Weekly

Insulation, fire hazards X Yearly

Obstructions or combustible materials near exhaustoutlet

X Weekly

DC Electrical System 3.7

Battery charger operation, charge rate (if equipped) X Monthly

Remove corrosion, clean and dry battery and rack X X Yearly

Clean and tighten battery terminals and inspectboots

X X Yearly

Battery electrolyte level and specific gravity * X Yearly

AC Electrical System

Tighten control and power wiring connections X Yearly

Remote control system, if equipped X Monthly

Visible wear or damage X Quarterly

Wire abrasions where subject to motion X X Six Months

Wire-cable insulation condition X 3 Years or 500 hours

Engine and Mounting

Visible wear or damage X Weekly

Air cleaner and precleaner service 3.4 R Yearly or 100 hours

Spark plugs 3.3 X Yearly or 300 hours

Replace stepper motor coupling and bushing D 500 hours

Generator

Visible wear or damage X Quarterly

Exercise generator set X Weekly

Brushes and collector ring D D Yearly

Measure and record resistance readings ofwindings with insulation tester (Megger, withSCR assembly or rectifier and load leadsdisconnected) *

D 3 Years

General Condition of Equipment

Evidence of vibration, leakage, excessive noise,temperature, or deterioration

X X X Weekly

Interior of sound enclosure X X Quarterly

* *Not necessary for maintenance-free batteries.

Service more frequently under extremely dusty/dirty conditions.

Megger is a registered trademark of Biddle Instruments.

X Action

D Authorized distributor/dealer onlyR Replace as necessary

Page 25: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 25Section 3 Scheduled Maintenance

3.1.2 Service Schedule, 18 kW Models

System Component or ProcedureSee

Section

Procedure

Frequency

VisuallyInspect Check Change Clean Test

Fuel

Flexible lines and connections X R Quarterly

Main tank supply level X Weekly

Fuel piping X Yearly

Lubrication 3.2

Oil level X 8 hours orbefore each use

Change oil X Yearly or 150 hours

Replace filter X Yearly or 150 hours

Crankcase breather hose X Yearly or 500 hours

Oil cooler X X Yearly or 100 hours

Cooling 3.5

Air ducts, louvers X X Yearly

Exhaust System 3.6

Leakage X X Weekly

Insulation, fire hazards X Yearly

Obstructions or combustible materials nearexhaust outlet

XWeekly

DC Electrical System 3.7

Battery charger operation, charge rate X Monthly

Remove corrosion, clean and dry battery andrack

X XYearly

Clean and tighten battery terminals and inspectboots

X XYearly

Battery electrolyte level and specific gravity * X Yearly

AC Electrical System

Tighten control and power wiring connections X Yearly

Remote control system, if equipped X Monthly

Visible wear or damage X Quarterly

Wire abrasions where subject to motion X X Six Months

Wire-cable insulation condition X 3 Years or 500 hours

Engine and Mounting

Visible wear or damage X Weekly

Air cleaner service 3.4 150 300 Yearly or hours shown

Spark plugs 3.3 150 300 Yearly or hours shown

Replace stepper motor coupling and bushing D 500 hours

Generator

Visible wear or damage X Quarterly

Exercise generator set W Weekly

Brushes and collector ring D D Yearly

Measure and record resistance readings ofwindings with insulation tester (Megger, withSCR assembly or rectifier and load leadsdisconnected)

D 3 Years

General Condition of Equipment

Evidence of vibration, leakage, deterioration,unusual or excessive noise or temperature

X X X Weekly

Interior of sound enclosure X X Quarterly

* Not necessary for maintenance-free batteries.

Service more frequently under extremely dusty/dirty conditions.

Megger is a registered trademark of Biddle Instruments.

X = Action

D Authorized distributor/dealer onlyR Replace as necessary

Page 26: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1126 Section 3 Scheduled Maintenance

3.2 Lubrication System

See the service schedules in Section 3.1 for oil change

and oil filter replacement intervals. See the service

views in Section 1.5 for the oil drain, oil check, oil fill, and

oil filter locations.

3.2.1 Low Oil Pressure Shutdown

The low oil pressure (LOP) shutdown feature protects

the engine against internal damage if the oil pressure

drops below a minimum pressure because of oil pump

failure or other malfunction.

Note: The LOP shutdown feature does not protect

against damage caused by operating when the

oil level is low; it is not a low oil level shutdown.

Check the oil level regularly, and add oil as

needed.

3.2.2 Oil Check

The generator set is shipped with oil. Before operating

the generator set, check the engine oil in the crankcase.

See Figure 3-1.

Maintain the oil level at or near, not over, the full mark on

the dipstick. Add 5W-30 synthetic oil when the oil level is

low.

Check the oil level before each use. For extended

operation, check the oil level every 8 hours. Do not

check the oil level when the generator set is running.

Shut down the generator set and wait several minutes

before checking the oil.

6515

Figure 3-1 Oil Check (18 kW shown)

3.2.3 Engine Oil Recommendation

Use 5W-30 API (American Petroleum Institute) Service

Class SG, SH, or SJ synthetic oil. Synthetic oil oxidizes

and thickens less than other oils and leaves the engine

intake valves and pistons cleaner.

3.2.4 Oil Change Procedure

Note: Dispose of all waste materials (engine oil, fuel,

filter, etc.) in an environmentally safe manner.

Drain the oil while it is still warm.

1. Drain the oil.

a. Place the generator set master switch in the

OFF position.

b. Disconnect the power to the battery charger.

c. Disconnect the generator set engine starting

battery, negative (--) lead first.

d. Remove the housing side panel.

e. Clean the area around the dipstick and oil fill

cap.

f. Remove the oil drain hose from its retaining

clip. Remove the cap from the oil drain hose

and lower the hose into an oil collection

container.

g. Open the oil drain valve on the engine.

h. Remove the dipstick and oil fill cap. Allow time

for the engine oil to drain completely.

i. Close the oil drain valve. Replace the cap on

the oil drain hose. Replace the oil drain hose in

its retaining clip.

j. Replace the dipstick.

2. Replace the oil filter.

a. Clean the area around the oil filter. Remove the

oil filter by rotating it counterclockwise with an

oil filter wrench.

b. Clean the gasket sealing surface of the oil filter

adapter.

c. Apply a light coat of clean oil to the rubber seal

of the new oil filter.

d. Install the new oil filter following the instructions

provided with the filter.

Page 27: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 27Section 3 Scheduled Maintenance

3. Fill with oil.

a. Fill the engine to theFmarkon thedipstick. The

engine oil capacity is shown in Figure 3-2. See

Section 3.2.3, Engine Oil Recommendation,

for oil selection.

Generator Set Oil Capacity, L (qt.)

8.5/12RES8.5/12RES 1.9 (2.0)

18RES18RES 2.8 (3.0)

Figure 3-2 Engine Oil Capacity

b. Reinstall the dipstick and the oil fill cap.

c. Check that the generator set master switch is in

the OFF position.

d. Reconnect the generator set engine starting

battery, negative (--) lead last.

e. Reconnect the power to the battery charger.

f. Start and run the generator set for a minute to

allow the oil pressure to reach operating range.

g. Stop the generator set, wait 1 minute, and then

recheck the oil level. Add oil to bring the level

up to the F mark on the dipstick.

4. Check for leaks.

a. Check for oil leaks.

b. Fix leaks and recheck the oil level.

c. Reinstall the housing side panel.

3.2.5 Oil Cooler, 18 kW

Inspect and clean the oil cooler at the intervals indicated

in the service schedule. The oil cooler must be kept free

of debris.

See Figure 3-3 for the oil cooler location. The oil cooler

is located under the No. 2 cylinder shroud. Remove the

top mounting screw and loosen the two side screws,

then lift off the cylinder shroud.

Clean the outside of the oil cooler fins with a brush or

with compressed air.

162 590 011. Oil cooler

Figure 3-3 Oil Cooler Location

Page 28: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1128 Section 3 Scheduled Maintenance

3.3 Spark Plugs

Reset the spark plug gap or replace the plugs with new

plugs as necessary.

1. Clean the area around the base of the spark plug to

keep dirt and debris out of the engine.

2. Remove the spark plug and check its condition.

Replace the spark plug if it is worn or if its reuse is

questionable.

3. Check the spark plug gap using a wire feeler

gauge. See Figure 3-4 for the recommended

spark plug gap. Adjust the gap by carefully bending

the ground electrode. See Figure 3-5 and

Figure 3-6.

4. Reinstall the spark plug into the cylinder head.

Torque the spark plug to 24.4--29.8 Nm

(18--22 ft. lb.)

Generator Set Spark Plug Gap

8.5 kW 0.51 mm (0.020 in.)

12/18RES 0.76 mm (0.030 in.)

Figure 3-4 Spark Plug Gap

1--514

Figure 3-5 Checking the Spark Plug Gap

1--511

Figure 3-6 Adjusting the Spark Plug Gap

3.4 Air Cleaner Service

3.4.1 Air Cleaner, 8.5/12RES

The engine has a replaceable high-density paper air

cleaner element with an oiled foam precleaner. See

Figure 3-7.

1

2

3

4

5

6

7

586536

1. Cover knob

2. Air cleaner cover3. Element cover nut

4. Element cover

5. Foam precleaner6. Air cleaner element

7. Air cleaner base

Figure 3-7 Air Cleaner Components

Check for a buildup of dirt and debris around the air

cleaner system. Keep this area clean. Also check for

loose or damaged components. Replace all bent or

damaged air cleaner components.

Note: Operating the engine with loose or damaged air

cleaner components could allow unfiltered air

into the engine causing premature wear and

failure.

Precleaner Service

Use the following procedure to wash and reoil the

precleaner as indicated in the service schedule. Wash

and reoil the precleaner more often under extremely

dusty or dirty conditions.

1. Place the generator set master switch in the OFF/

RESET position.

Page 29: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 29Section 3 Scheduled Maintenance

2. Disconnect the power to the battery charger.

3. Disconnect the battery, negative (--) lead first.

4. Loosen the cover retaining knob and remove the

cover. Remove the precleaner from the paper

element. Wash the precleaner in warm water with

detergent. Rinse the precleaner thoroughly until all

traces of detergent are eliminated. Squeeze out

excess water (do not wring). Allow the precleaner

to air dry.

5. Saturate the precleaner with new engine oil.

Squeeze out all of the excess oil.

6. Reinstall the precleaner over the paper element.

7. Reinstall the air cleaner cover. Secure the cover

with the cover retaining knob.

8. Reconnect the power to the battery charger.

9. Reconnect the generator set engine starting

battery, negative (--) lead last.

Paper Element Service

Use the following procedure to replace the paper

element at the intervals specified in the service

schedule. Replace the paper element more often under

extremely dusty or dirty conditions.

1. Place the generator set master switch in the OFF/

RESET position.

2. Disconnect the power to the battery charger.

3. Disconnect the generator set engine starting

battery, negative (--) lead first.

4. Loosen the cover retaining knob and remove the

cover.

5. Remove the element cover nut, element cover, and

the paper element with precleaner.

6. Remove the precleaner from the paper element.

Note: Do not wash the paper element or clean it

with pressurized air, as this will damage the

element.

7. Replace the element if it is dirty, bent, or damaged.

8. Check the air cleaner base. Make sure it is secure

and not bent or damaged. Also check the element

cover for damage and fit. Replace all damaged air

cleaner components. Remove any loose dirt or

debris from the air cleaner base. Wipe the base

carefully so that no dirt drops into the intake throat.

Check the condition of the rubber seal on the air

cleaner stud and replace the seal if necessary.

9. Reinstall the paper element, precleaner, element

cover, element cover nut, and the air cleaner cover.

Secure the cover with the cover retaining knob.

10. Reconnect the power to the battery charger.

11. Reconnect the generator set engine starting

battery, negative (--) lead last.

3.4.2 Air Cleaner, 18RES

The engine is equipped with a replaceable, high density

paper air cleaner element. See Figure 3-8.

1

tp6515

1. Knobs (qty.2)

2. Cover

3. Paper element

4. Air filter latch

3

4

2

Figure 3-8 Air Cleaner Components

Check the air cleaner daily or before starting the engine.

Check for a buildup of dirt and debris around the air

cleaner system. Keep this area clean. Also check for

loose or damaged components. Replace all bent or

damaged air cleaner components.

Note: Operating the engine with loose or damaged air

cleaner components could allow unfiltered air

into the engine causing premature wear and

failure.

Page 30: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1130 Section 3 Scheduled Maintenance

Paper Element Service

Replace the paper element at the intervals indicated in

the service schedule. See Section 3.1.2 for the service

schedule. See Figure 3-8 for the air cleaner

components.

1. Loosen the two cover retaining knobs and remove

the cover.

2. Rotate the air filter latch counterclockwise to

unlock, then remove the paper element.

3. Do not wash the paper element or use pressurized

air, as this will damage the element. Replace a

dirty, bent, or damaged element. Handle new

elements carefully; do not use if the sealing

surfaces are bent or damaged.

4. When servicing the air cleaner, check the air

cleaner base and latch.Make sure it is secured and

not bent or damaged. Also, check the element

cover for damage or improper fit. Replace all

damaged air cleaner components.

Note: If any loose dirt or debris fell on the air cleaner

base when the element was removed, carefully

remove it andwipe the base clean. Be careful that

none of it drops into the intake throat.

5. Reinstall the paper element onto the air cleaner

base. Make sure the element is flat and properly

seated. Rotate the latch clockwise, over the

molded lip on the element.

6. Install the air cleaner cover and securewith the two

retaining knobs.

7. When element replacement is necessary, order

genuine Kohler parts.

3.5 Cooling System

The engine fan draws cooling air through the openings

in the sides and end near the battery. The alternator fan

draws cooling air through openings on the side walls of

the enclosure. The cooling air mixes with the engine

exhaust and is discharged at the exhaust outlet. See

Figure 3-9. To prevent generator set damage caused by

overheating, keep the housing cooling inlets and outlets

clean and unobstructed at all times.

Note: Do not block the generator set cooling air inlets or

mount other equipment above them. Overheating

and severe generator damage may occur.

tp61952

1. Exhaust outlet

2. Alternator air intake (both sides)3. Engine air intake

3

1

3

Figure 3-9 Cooling Air Intake and Exhaust

3.6 Exhaust System

Remove all combustible materials from the exhaust

location. Combustible materials include building

materials aswell as natural surroundings. Keep dry field

grass, foliage, and combustible landscaping material a

minimum of 1.5 m (5 ft.) from the exhaust outlet.

Periodically inspect the exhaust system components for

cracks, leaks, and corrosion.

Check for corroded or brokenmetal parts and replace

them as needed.

Check that the exhaust outlet is clear.

Page 31: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 31Section 3 Scheduled Maintenance

3.7 Battery

Sulfuric acid in batteries.Can cause severe injury or death.

Wear protective goggles andclothing. Battery acid may causeblindness and burn skin.

WARNING

Battery electrolyte is a diluted sulfuric acid. Battery acid

can cause severe injury or death. Battery acid can causeblindness and burn skin. Always wear splashproof safetygoggles, rubber gloves, and boots when servicing the battery.Do not open a sealed battery or mutilate the battery case. Ifbattery acid splashes in the eyes or on the skin, immediatelyflush the affected area for 15 minutes with large quantities ofclean water. Seek immediate medical aid in the case of eyecontact. Never addacid to a battery after placing the battery inservice, as this may result in hazardous spattering of batteryacid.

Battery acid cleanup. Battery acid can cause severeinjury or death. Battery acid is electrically conductive andcorrosive. Add 500 g (1 lb.) of bicarbonate of soda (bakingsoda) to a container with 4 L (1 gal.) of water and mix theneutralizing solution. Pour the neutralizing solution on thespilled battery acid and continue to add the neutralizingsolution to the spilled battery acid until all evidence of achemical reaction (foaming) has ceased. Flush the resultingliquid with water and dry the area.

Battery gases. Explosion can cause severe injury ordeath. Battery gases can cause an explosion. Do not smokeor permit flames or sparks to occur near a battery at any time,particularly when it is charging. Do not dispose of a battery ina fire. To prevent burns and sparks that could cause anexplosion, avoid touching the battery terminals with tools orother metal objects. Remove all jewelry before servicing theequipment. Discharge static electricity from your body beforetouching batteries by first touching a grounded metal surfaceaway from the battery. To avoid sparks, do not disturb thebattery charger connections while the battery is charging.Always turn the battery charger off before disconnecting thebattery connections. Ventilate the compartments containingbatteries to prevent accumulation of explosive gases.

Battery short circuits. Explosion can cause severe injuryor death. Short circuits can cause bodily injury and/orequipment damage. Disconnect the battery before generatorset installation or maintenance. Remove all jewelry beforeservicing the equipment. Use tools with insulated handles.Remove the negative (--) lead first when disconnecting thebattery. Reconnect the negative (--) lead last whenreconnecting the battery. Never connect the negative (--)battery cable to the positive (+) connection terminal of thestarter solenoid. Do not test the battery condition by shortingthe terminals together.

Refer to this section for general battery information and

maintenance. Also consult the battery manufacturer’s

instructions for battery maintenance.

All generator set models use a negative ground with a

12-volt engine electrical system. Consult the generator

set nameplate for the engine electrical system voltage.

Consult the generator spec sheet for battery capacity

recommendations for replacement purposes. Wiring

diagrams provide battery connection information. See

Figure 3-10 for typical battery connections.

EZ-273000-J

1 2

1. To positive (+) terminal on starter solenoid.

2. To ground (--) terminal on or near starter motor.

Figure 3-10 12-Volt Engine Electrical System Single

Starter Motor, Typical Battery Connection

Clean the battery and cables and tighten battery

terminals using the service schedule recommendations.

To prevent corrosion, maintain tight, dry electrical

connections at the battery terminals. To remove

corrosion from battery terminals, disconnect the cables

from the battery and scrub the terminals with a wire

brush. Clean the battery and cables with a solution of

baking soda and water. After cleaning, flush the battery

and cables with clean water and wipe them with a dry,

lint-free cloth.

After reconnecting the battery cables, coat the battery

terminals with petroleum jelly, silicone grease, or other

nonconductive grease.

3.8 Battery Charger

The generator set is equipped with a battery charger to

maintain the engine starting battery. The charger’s DC

leads are factory-wired. Periodically check and tighten

all connections.

See Section 2.7, Battery Charger.

Page 32: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1132 Section 3 Scheduled Maintenance

3.9 Circuit Protection

If the generator set circuit breaker trips or the fuses blow

repeatedly, see Section 4, Troubleshooting, for possible

causes.

3.9.1 Line Circuit Breaker

A line circuit breaker interrupts the generator output in

the event of a fault in the wiring between the generator

and the load. The line circuit breaker location is shown

in Figure 1-2. The circuit breaker rating is shown in

Figure 3-11. If the circuit breaker trips, reduce the load

and switch the breaker back to theONposition. With the

breaker in the OFF position the generator set runs but

the generator output is disconnected from the load.

Model Circuit Breaker Rating, Amp

8.5RES 40

12RES 50

12TRES 20

18RES 80

18TRES 25

Figure 3-11 Line Circuit Breaker Rating

3.9.2 Fuses

Three panel-mounted fuses protect the alternator and

electrical controls. See Section 1.5 for fuse locations.

Another 10-amp fuse protects the battery charger.

See Figure 3-12 for fuse part numbers. Always identify

and correct the cause of a blown fuse before restarting

the generator set. Refer to Section 4, Troubleshooting,

for conditions that may indicate a blown fuse. Replace

blown fuses with identical replacement parts.

Fuse Rating, Amp Label Part Number

Auxiliary winding 20 F1 292937

Relay interfaceboard

10 F2 223316

Controller 10 F3 223316

Battery charger(RES)

10 — 223316

Figure 3-12 Fuses

Page 33: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 33Section 3 Scheduled Maintenance

3.10 Storage Procedure

Perform the following storage procedure before

removing the generator set from service for three

months or longer. Follow the engine manufacturer’s

recommendations for storage, if available.

Note: Run the generator set monthly whenever

possible.

3.10.1 Lubricating System

1. Operate the generator set until it reaches operating

temperature, or about 15 minutes.

2. Stop the generator set.

3. While the engine is still warm, drain the engine

lubrication oil from the engine crankcase.

4. Refill engine crankcase with oil. See Section 3.2.3

for oil recommendations.

5. Run the generator set for a few minutes to

distribute the clean oil.

6. Stop the generator set.

3.10.2 Fuel System

1. Start the generator set.

2. With the generator set running, shut off the gas

supply.

3. Run the generator set until the engine stops.

4. Place the generator set master switch in the OFF/

RESET position.

3.10.3 Cylinder Lubrication

1. Remove the spark plugs.

2. Pour one tablespoon of engine oil into each spark

plug hole. Install the spark plugs and ground the

spark plug leads. Do not connect the leads to the

plugs.

3. Toggle the generator setmaster switch to crank the

engine two or three revolutions to lubricate the

cylinders.

3.10.4 Exterior Preparation

1. Clean the exterior surface of the generator set.

2. Seal all openings in the engine with nonabsorbent

adhesive tape.

3. Mask all areas to be used for electrical contact.

4. Spread a light film of oil over unpainted metallic

surfaces to prevent rust and corrosion.

3.10.5 Battery

Perform battery storage last.

1. Place the generator set master switch in the OFF/

RESET position.

2. Disconnect the battery, negative (--) lead first.

3. Clean the battery.

4. Place the battery in a warm, dry location.

5. Connect the battery to a float/equalize battery

charger, or charge the battery monthly using a

trickle charger. Follow the battery charger

manufacturer’s recommendations.

Page 34: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1134 Section 3 Scheduled Maintenance

Notes

Page 35: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 35Section 4 Troubleshooting

Section 4 Troubleshooting

4.1 Introduction

Use the following charts to diagnose and correct

common problems. First check for simple causes such

as a dead engine starting battery, loose connections, or

an open circuit breaker. The charts include a list of

common problems, possible causes of the problem, and

recommended corrective actions.

If the procedures in this manual do not explain how to

correct the problem, contact an authorized distributor/

dealer. Maintain a record of repairs and adjustments

performed on the equipment. Use the record to help

describe the problem and repairs or adjustments made

to the equipment.

4.2 Controller Troubleshooting

Figure 4-1 contains troubleshooting, diagnostic, and

repair information for the ADC-RES controller.

4.3 Generator Set Troubleshooting

Figure 4-2 contains generator set troubleshooting,

diagnostic, and repair information. Check for loose

connections before replacing parts.

Fault Codes

The Advanced Digital Control displays fault codes to aid

in troubleshooting. Fault codes, descriptions, and

recommended actions are listed in Section 2.6.

If a fault code is displayed, identify and correct the cause

of the fault condition. Then reset the controller. See

Section 2.6.3.

Problem Possible Cause Corrective Action

Controller LEDdisplay is off

No power to the controller:

Controller fuse (F3) is blown. Replace the fuse. If the fuse blows again, contact anauthorized distributor/dealer.

Low or no battery voltage. Check connections.Check the engine starting battery and battery charger.See Figure 4-3.

Generator set master switch is in theOFF/RESET position.

Move generator set master switch to the AUTO or RUNposition. In AUTO, the display will not turn on until thefirst start command is received.

The controller is in sleep mode. See Section2.4.2.

Controller display will activate when a remote startcommand is received or the generator set master switchis moved to the RUN position. Use the remote switch tostart generator set and activate the controller display, ifdesired. See Section 2.4.

Controllers with application code version 1.13 or highercan be configured to enable or disable the sleep mode.See the generator set Installation Manual forinstructions.

Figure 4-1 ADC-RES Troubleshooting Chart

Page 36: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1136 Section 4 Troubleshooting

Problem Possible Cause Corrective Action

The generator setdoes not crank.

Fault shutdown Check for a fault code on the controller display.See Section 2.6.

Battery weak or dead Check power to the battery charger.Recharge or replace the battery.

Battery charger fuse blown Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.

Battery connections reversed or poor Check the connections.

Fuse F2 blown Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.

Fuse F3 blown Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.

Generator set master switch in the OFFposition

Move the master switch to AUTO for remote start orto RUN for local start.

The generator setcranks but does notstart, starts hard,lacks power, oroperates erratically.

Air cleaner clogged Clean and/or replace the air cleaner.

Battery weak or dead Check power to the battery charger.Recharge or replace the battery.

Battery connection poor Clean and tighten the battery connections.

Spark plug wire connection loose Check the spark plug wires.

Low oil pressure shutdown Check the oil level.

Fuel pressure insufficient Check the fuel supply and valves.

Engine malfunction Contact an authorized distributor/dealer.

No AC output. AC circuit breaker in the OFF position Place the circuit breaker in the ON position.

AC circuit breaker tripping because of overload Reduce the load on the generator set.

AC circuit breaker tripping because of shortcircuit

Contact an authorized distributor/dealer for service.

Auxiliary winding fuse (F1) blown Replace the fuse. Contact an authorized distributor/dealer for service if fuse blows repeatedly.

Low output orexcessive drop involtage.

Generator set overloaded Reduce the load.

Generator set stopssuddenly.

Low oil pressure shutdown Check the oil level. Check for signs of oil leaks.

Out of fuel Check fuel supply.

Overcrank shutdown Reset the controller. If the overcrank fault occursagain, contact an authorized distributor/dealer.

Controller fuse (F3) blown Replace the fuse. If the fuse blows again, contactan authorized distributor/dealer.

Overspeed shutdown Reset the controller. If the overspeed fault occursagain, contact an authorized distributor/dealer.

Generator set master switch in the OFF/RESETposition

Move the switch to the correct position (RUN orAUTO).

Remote stop command received from a remoteswitch or ATS

Check the remote switch position.

Engine malfunction Contact an authorized distributor/dealer.

Auxiliary winding fuse (F1) blown Replace the fuse. Contact an authorizeddistributor/dealer for service if fuse blowsrepeatedly.

Figure 4-2 General Troubleshooting Chart

Page 37: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 37Section 4 Troubleshooting

4.4 Battery Charger

Troubleshooting

Use the battery charger’s LED indicators and the table in Figure 4-3 or Figure 4-4 to troubleshoot battery charger

operation problems.

Problem Cause Solution

Red LED stays onfor more than24 hours

One or more inoperative or damaged cells. Load test the battery and replace, if necessary

Battery charger has reduced its outputvoltage below the normal level due to a DCoverload or a DC short.

Remove the source of the overload or short.Disconnect the battery charger’s black (NEGATIVE)ring terminal from the battery. Reapply AC power andthe green LED only should now light.

Onboard DC systems are drawing morecurrent than the battery charger can replace.

Turn off all DC equipment while charging.

Red and greenLEDs stay on formore than 24 hours

Onboard DC systems are drawing between1.5 and 5 amps.

Turn off all DC equipment while charging.

One or more inoperative or damaged cells. Load test the battery and replace, if necessary

Extremely low AC voltage at the batterycharger.

Apply a higher AC voltage source or reduce the lengthof the extension cord.

Green LED stays onwhen the battery isknown to be low

Open DC output fuse. Replace AGS-10 fuse.

Faulty or contaminated terminal connections. Clean and tighten or repair all terminal connections.

One or more inoperative or damaged cells. Load test the battery and replace, if necessary.

Neither of the LEDsturn on when theAC power is applied

No AC power available at the battery char-ger.

Connect AC power or reset the AC breaker on themain panel.

Component failure. Replace battery charger.

Figure 4-3 6-Amp Battery Charger Troubleshooting (for single-phase models)

Problem Cause Solution

Green LED is offand there is nooutput voltage.

No power to the battery charger. Check the power supply to the charger.

Check the upstream circuit breakers and fuses.

Check fuse FS (1A-T) inside the battery charger.

Abnormal lowvoltage, charger isoperating.

The battery completely discharged and thecharger is operating at the current limit.

Disconnect the battery and verify that the chargeroutput is 13.2 VDC.

Reconnect the charger and allow time for the batteryto recharge. The battery voltage should rise gradually.

Test the battery.

The battery isdischarged, but thecharger has powerand is operating.

Blown fuse. Check the 5-amp fuse F2 (5A-T) inside the batterycharger and replace if necessary.

Check inline fuse F4 and replace if necessary.

Figure 4-4 2.5-Amp Battery Charger Troubleshooting (for three-phase models)

Page 38: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1138 Section 4 Troubleshooting

Notes

Page 39: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/11 Appendix 39

Appendix A Abbreviations

The following list contains abbreviations that may appear in this publication.

A, amp ampereABDC after bottom dead centerAC alternating currentA/D analog to digitalADC advanced digital control;

analog to digital converteradj. adjust, adjustmentADV advertising dimensional

drawingAh amp-hourAHWT anticipatory high water

temperatureAISI American Iron and Steel

InstituteALOP anticipatory low oil pressurealt. alternatorAl aluminumANSI American National Standards

Institute (formerly AmericanStandards Association, ASA)

AO anticipatory onlyAPDC Air Pollution Control DistrictAPI American Petroleum Instituteapprox. approximate, approximatelyAPU Auxiliary Power UnitAQMD Air Quality Management DistrictAR as required, as requestedAS as supplied, as stated, as

suggestedASE American Society of EngineersASME American Society of

Mechanical Engineersassy. assemblyASTM American Society for Testing

MaterialsATDC after top dead centerATS automatic transfer switchauto. automaticaux. auxiliaryavg. averageAVR automatic voltage regulatorAWG American Wire GaugeAWM appliance wiring materialbat. batteryBBDC before bottom dead centerBC battery charger, battery

chargingBCA battery charging alternatorBCI Battery Council InternationalBDC before dead centerBHP brake horsepowerblk. black (paint color), block

(engine)blk. htr. block heaterBMEP brake mean effective pressurebps bits per secondbr. brassBTDC before top dead centerBtu British thermal unitBtu/min. British thermal units per minuteC Celsius, centigradecal. calorieCAN controller area networkCARB California Air Resources BoardCAT5 Category 5 (network cable)CB circuit breakerCC crank cyclecc cubic centimeterCCA cold cranking ampsccw. counterclockwiseCEC Canadian Electrical Codecert. certificate, certification, certifiedcfh cubic feet per hour

cfm cubic feet per minuteCG center of gravityCID cubic inch displacementCL centerlinecm centimeterCMOS complementary metal oxide

substrate (semiconductor)com communications (port)coml commercialComl/Rec Commercial/Recreationalconn. connectioncont. continuedCPVC chlorinated polyvinyl chloridecrit. criticalCSA Canadian Standards

AssociationCT current transformerCu coppercUL Canadian Underwriter’s

LaboratoriesCUL Canadian Underwriter’s

Laboratoriescu. in. cubic inchcw. clockwiseCWC city water-cooledcyl. cylinderD/A digital to analogDAC digital to analog converterdB decibeldB(A) decibel (A weighted)DC direct currentDCR direct current resistancedeg., ° degreedept. departmentdia. diameterDI/EO dual inlet/end outletDIN Deutsches Institut fur Normung

e. V. (also Deutsche IndustrieNormenausschuss)

DIP dual inline packageDPDT double-pole, double-throwDPST double-pole, single-throwDS disconnect switchDVR digital voltage regulatorE2PROM, EEPROM

electrically-erasableprogrammable read-onlymemory

E, emer. emergency (power source)ECM electronic control module,

engine control moduleEDI electronic data interchangeEFR emergency frequency relaye.g. for example (exempli gratia)EG electronic governorEGSA Electrical Generating Systems

AssociationEIA Electronic Industries

AssociationEI/EO end inlet/end outletEMI electromagnetic interferenceemiss. emissioneng. engineEPA Environmental Protection

AgencyEPS emergency power systemER emergency relayES engineering special,

engineered specialESD electrostatic dischargeest. estimatedE-Stop emergency stopetc. et cetera (and so forth)

exh. exhaustext. externalF Fahrenheit, femaleFHM flat head machine (screw)fl. oz. fluid ounceflex. flexiblefreq. frequencyFS full scaleft. foot, feetft. lb. foot pounds (torque)ft./min. feet per minuteftp file transfer protocolg gramga. gauge (meters, wire size)gal. gallongen. generatorgenset generator setGFI ground fault interrupter

GND, groundgov. governorgph gallons per hourgpm gallons per minutegr. grade, grossGRD equipment groundgr. wt. gross weightH x W x D height by width by depthHC hex capHCHT high cylinder head temperatureHD heavy dutyHET high exhaust temp., high

engine temp.hex hexagonHg mercury (element)HH hex headHHC hex head capHP horsepowerhr. hourHS heat shrinkhsg. housingHVAC heating, ventilation, and air

conditioningHWT high water temperatureHz hertz (cycles per second)IBC International Building CodeIC integrated circuitID inside diameter, identificationIEC International Electrotechnical

CommissionIEEE Institute of Electrical and

Electronics EngineersIMS improved motor startingin. inchin. H2O inches of waterin. Hg inches of mercuryin. lb. inch poundsInc. incorporatedind. industrialint. internalint./ext. internal/externalI/O input/outputIP internet protocolISO International Organization for

StandardizationJ jouleJIS Japanese Industry Standardk kilo (1000)K kelvinkA kiloampereKB kilobyte (210 bytes)KBus Kohler communication protocolkg kilogram

Page 40: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

TP-6515 1/1140 Appendix

kg/cm2 kilograms per squarecentimeter

kgm kilogram-meterkg/m3 kilograms per cubic meterkHz kilohertzkJ kilojoulekm kilometerkOhm, kΩ kilo-ohmkPa kilopascalkph kilometers per hourkV kilovoltkVA kilovolt amperekVAR kilovolt ampere reactivekW kilowattkWh kilowatt-hourkWm kilowatt mechanicalkWth kilowatt-thermalL literLAN local area networkL x W x H length by width by heightlb. pound, poundslbm/ft3 pounds mass per cubic feetLCB line circuit breakerLCD liquid crystal displayLED light emitting diodeLph liters per hourLpm liters per minuteLOP low oil pressureLP liquefied petroleumLPG liquefied petroleum gasLS left sideLwa sound power level, A weightedLWL low water levelLWT low water temperaturem meter, milli (1/1000)M mega (106 when used with SI

units), malem3 cubic meterm3/hr. cubic meters per hourm3/min. cubic meters per minutemA milliampereman. manualmax. maximumMB megabyte (220 bytes)MCCB molded-case circuit breakerMCM one thousand circular milsmeggar megohmmeterMHz megahertzmi. milemil one one-thousandth of an inchmin. minimum, minutemisc. miscellaneousMJ megajoulemJ millijoulemm millimetermOhm,mΩmilliohmMOhm, MΩmegohmMOV metal oxide varistorMPa megapascalmpg miles per gallonmph miles per hourMS military standardms millisecondm/sec. meters per secondmtg. mountingMTU Motoren-und Turbinen-UnionMW megawattmW milliwattμF microfaradN, norm. normal (power source)NA not available, not applicablenat. gas natural gas

NBS National Bureau of StandardsNC normally closedNEC National Electrical CodeNEMA National Electrical

Manufacturers AssociationNFPA National Fire Protection

AssociationNm newton meterNO normally openno., nos. number, numbersNPS National Pipe, StraightNPSC National Pipe, Straight-couplingNPT National Standard taper pipe

thread per general useNPTF National Pipe, Taper-FineNR not required, normal relayns nanosecondOC overcrankOD outside diameterOEM original equipment

manufacturerOF overfrequencyopt. option, optionalOS oversize, overspeedOSHA Occupational Safety and Health

AdministrationOV overvoltageoz. ouncep., pp. page, pagesPC personal computerPCB printed circuit boardpF picofaradPF power factorph., ∅ phasePHC Phillips head Crimptite

(screw)PHH Phillips hex head (screw)PHM pan head machine (screw)PLC programmable logic controlPMG permanent magnet generatorpot potentiometer, potentialppm parts per millionPROM programmable read-only

memorypsi pounds per square inchpsig pounds per square inch gaugept. pintPTC positive temperature coefficientPTO power takeoffPVC polyvinyl chlorideqt. quart, quartsqty. quantityR replacement (emergency)

power sourcerad. radiator, radiusRAM random access memoryRDO relay driver outputref. referencerem. remoteRes/Coml Residential/CommercialRFI radio frequency interferenceRH round headRHM round head machine (screw)rly. relayrms root mean squarernd. roundRO read onlyROM read only memoryrot. rotate, rotatingrpm revolutions per minuteRS right sideRTDs Resistance Temperature

Detectors

RTU remote terminal unitRTV room temperature vulcanizationRW read/writeSAE Society of Automotive

Engineersscfm standard cubic feet per minuteSCR silicon controlled rectifiers, sec. secondSI Systeme international d’unites,

International System of UnitsSI/EO side in/end outsil. silencerSMTP simple mail transfer protocolSN serial numberSNMP simple network management

protocolSPDT single-pole, double-throwSPST single-pole, single-throwspec specificationspecs specification(s)sq. squaresq. cm square centimetersq. in. square inchSMS short message serviceSS stainless steelstd. standardstl. steeltach. tachometerTB terminal blockTCP transmission control protocolTD time delayTDC top dead centerTDEC time delay engine cooldownTDEN time delay emergency to

normalTDES time delay engine startTDNE time delay normal to

emergencyTDOE time delay off to emergencyTDON time delay off to normaltemp. temperatureterm. terminalTHD total harmonic distortionTIF telephone influence factortol. toleranceturbo. turbochargertyp. typical (same in multiple

locations)UF underfrequencyUHF ultrahigh frequencyUIF user interfaceUL Underwriter’s Laboratories, Inc.UNC unified coarse thread (was NC)UNF unified fine thread (was NF)univ. universalURL uniform resource locator

(web address)US undersize, underspeedUV ultraviolet, undervoltageV voltVAC volts alternating currentVAR voltampere reactiveVDC volts direct currentVFD vacuum fluorescent displayVGA video graphics adapterVHF very high frequencyW wattWCR withstand and closing ratingw/ withWO write onlyw/o withoutwt. weightxfmr transformer

Page 41: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Notes

Page 42: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative

Notes

Page 43: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative
Page 44: Residential/Commercial Generator Sets - Wholesale Solar · working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative