  • 112.6.0H

    Study: Steady-State Temperature

    Revision: Base

    Date: 03-09-2015

    Contract:

    ETAPProject:

    Filename: Test 5

    SN:

    Page:

    Study Case: CDEngineer:

    Location:

    Analysis Results (RW1)

    DielectricLossesWatt/ft Yc Ys

    Temp.C

    ConductorLossesWatt/ftCable ID Conduit/Location ID Cable

    Conductorper

    per Cable

    EnergizedConductor

    Rdc @ 0.00

    AmpNo.Final Temp. Current

    Ohm/ft

    Cable10 Cond2 3 0 21.80 0.000 0.068 0.124 68.36 0.000 0.00 1

    Cable11 Cond3 3 0 22.16 0.000 0.066 0.122 73.31 0.000 2.00 0.00 2

    Cable12 Cond5 3 0 22.71 0.000 0.063 0.120 80.98 0.000 3.00 0.00 3

    Cable13 Cond7 3 0 21.70 0.000 0.068 0.125 66.95 0.000 4.00 0.00 4

    Cable6 Cond8 3 0 21.94 0.000 0.067 0.124 70.24 0.000 5.00 0.00 5

    Cable8 Cond4 3 0 22.32 0.000 0.065 0.122 75.55 0.000 6.00 0.00 6

    Cable9 Cond1 3 0 21.58 0.000 0.069 0.125 65.32 0.000 7.00 0.00 7

    Yc = Increment of AC/DC resistance ratio due to AC current skin and proximity effectYs = Increment of AC/DC resistance ratio due to losses of circulation and eddy current effect in shield , sheath and armor