retrofitting towards nzeb the case of residential … · 2020. 5. 4. · to design a retrofit...

99
RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL BUILDINGS IN THE MEDITERRANEAN CLIMATE POLITECNICO DI TORINO Master Degree in Building Engineering Master’s Degree Thesis Relator: prof. Marco Perino Correlator: prof. Daniel Aelenaei Candidate: Alessandro Rizzo March 2020

Upload: others

Post on 15-Sep-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL

BUILDINGS IN THE MEDITERRANEAN CLIMATE

POLITECNICO DI TORINO

Master Degree in Building Engineering

Master’s Degree Thesis

Relator: prof. Marco Perino

Correlator: prof. Daniel Aelenaei

Candidate:

Alessandro Rizzo March 2020

Page 2: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 3: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

“It has been said that something as small as the flutter of a butterfly’s wing can ultimately cause a typhoon halfway around the world”

“Si dice che il minimo battito d’ali di una farfalla sia in grado di provocare un uragano

dall’altra parte del mondo”

(The Butterfly Effect)

Page 4: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 5: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

To my family.

Page 6: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 7: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

I

ABSTRACT

The idea of designing Zero Energy Buildings (ZEBs) has been gaining international interest in recent

times because it seems the perfect solution to make buildings more independent of the electric grid

considering the growing energy demand and the climate change. Either way, before being completely

introduced in the national building regulations and international standards, the ZEB concept claims a

solid and clear definition and a shared energy calculation methodology by all the Member States of the

EU. 1 In a period of significant climate change and awareness, the improving of technologies and

materials for constructions and the Energy Performance of Building Directive (EPBD), that sets the

standards for new and renovated buildings across Europe, might play a key role for the improvement of

the building stock and to reduce the greenhouse gas emissions in the atmosphere.

This work aims at presenting a retrofit of an existing building towards nZEB standards (Portugal and

Italy), creating a dynamic model of the building via Energy Plus that is able to simulate its behaviour

in relation to the changes applied, lowering the energy demand of the building and improving the

flexibility of the electrical system by taking advantage of renewable energy generation capacities.

L'idea di progettare Edifici a Energia Zero (ZEB) sta guadagnando interesse internazionale negli ultimi

tempi perché sembra la soluzione perfetta per rendere gli edifici più indipendenti dalla rete elettrica in

vista della crescente domanda di energia e dei cambiamenti climatici. Ad ogni modo, prima di essere

completamente introdotto nei regolamenti edilizi nazionali e negli standard internazionali, il concetto

ZEB necessita di una solida e chiara definizione e una metodologia di calcolo dell'energia condivisa da

tutti gli Stati Membri dell’Unione Europea. In un periodo di significativo cambiamento climatico e presa

di coscienza, il miglioramento delle tecnologie e dei materiali per le costruzioni e la direttiva sul

rendimento energetico nell'edilizia (EPBD), che stabilisce gli standard per gli edifici nuovi e rinnovati

in Europa, potrebbe rivestire un ruolo chiave per il miglioramento del patrimonio edilizio e per ridurre

le emissioni di gas serra e anidride carbonica nell'atmosfera.

Questo documento mira a presentare un esempio di riqualificazione di un edificio esistente secondo gli

standard nZEB (Portogallo e Italia), creando un modello dinamico dell'edificio tramite ENERGY PLUS

in grado di simularne il comportamento in relazione ai cambiamenti applicati, diminuendo il fabbisogno

energetico dell’edifici e migliorando la flessibilità del sistema elettrico sfruttando le capacità di

generazione di energia rinnovabile.

1 A.J. Marszal, P. Heiselberg, J.S. Bourrelle, E. Musall, K. Voss, I. Sartori, A. Napolitano. (2010). “Zero Energy

Building – A review of definitions and calculation methodologies”

Page 8: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 9: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

TABLE OF CONTENTS

ABSTRACT .................................................................................................................................................. 1

INTRODUCTION ......................................................................................................................................... 1

1. Climate change and building sector ...................................................................................................... 5

1.1 NZEB ................................................................................................................................................. 9

1.1.1 Definitions .................................................................................................................................... 11

1.1.2 Design and construction ............................................................................................................... 12

1.1.3 Energy Harvest ............................................................................................................................. 13

1.2 EPBD (Energy Performance Building Directive) and ZEBRA2020 ................................................. 13

1.3 EPBD implementation in Italy ......................................................................................................... 17

1.3.1 Energy performance standards: NEW BUILDINGS ................................................................... 17

1.3.2 Format of national transposition and implementation of existing regulations ............................. 18

1.3.3 Standards for systems and building components for NEW buildingsErrore. Il segnalibro non è definito.

1.3.4 Energy performance requirements: EXISTING BUILDINGS .................................................... 20

2. Data acquisition and Original model .................................................................................................. 23

2.1 Methodology and tools ..................................................................................................................... 24

2.2 The Original Building ...................................................................................................................... 25

2.2.1 Geometric model .......................................................................................................................... 26

2.2.2 Envelope and Components ........................................................................................................... 27

2.2.3 Assumptions ................................................................................................................................. 29

2.2.4 Configuration 1. LISBON (Original Model – Multiple thermal zones) / Indoor temperature and Energy Demand ...................................................................................................................................... 30

2.2.5 Considerations .............................................................................................................................. 35

3. Data elaboration ................................................................................................................................... 37

3.1 Configuration 2. LISBON (Original Model – Single thermal zone) / Indoor temperature and Energy Demand ................................................................................................................................................... 38

3.1.1 Considerations .............................................................................................................................. 43

3.2 Configuration 3. LISBON (Renovated Model – Single thermal zone) ........................................... 43

Page 10: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

3.2.1 Envelope and Components ........................................................................................................... 44

3.2.2 Indoor temperature and Energy Demand (Comparison between Original building and Renovated Building) ................................................................................................................................................ 46

3.2.3 Considerations .............................................................................................................................. 50

3.2.4 Photovoltaic system...................................................................................................................... 51

3.3 Configuration 4. TURIN (Original Model – Single thermal zone) / Indoor temperature and Energy Demand ................................................................................................................................................... 53

3.3.1 Considerations .............................................................................................................................. 58

3.4 Configuration 5. TURIN (Renovated Model – Single thermal zone) ............................................. 58

3.4.1 Indoor temperature and Energy Demand (Comparison between Original building and Renovated Building) ................................................................................................................................................ 59

3.4.2 Considerations .............................................................................................................................. 63

3.4.3 Photovoltaic system...................................................................................................................... 64

3.5 ENERGY FLEXIBILITY ................................................................................................................ 66

3.5.1 Configuration 6. TURIN (Renovated Model – Energy Flexibility) / Energy Production and Energy Demand .................................................................................................................................................. 68

CONCLUSIONS ......................................................................................................................................... 75

Bibliography ................................................................................................................................................ 77

Websites ...................................................................................................................................................... 79

Index of Figures .......................................................................................................................................... 81

Index of Tables ............................................................................................................................................ 84

Page 11: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 12: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments
Page 13: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

1

INTRODUCTION In Europe, the 40% of the total energy demand comes from building sector. Thus, measures for this

sector, especially concerning energy savings, has been introduced by European Directives 2002/91/EC

and 2010/31/EU for the design of the buildings or their technical equipment. 2 The EU has set targets

for 2020 and goals for 2030-2050 to cut 20% of greenhouse gas emissions (comparing to the level of

1990), to increase the energy use from renewable sources by 20% and to raise energy proficiency by

20%. The primary tool to reach the targets in Architecture and building sector is the Energy Performance

of Building Directive (EPBD) that sets the standards for new and refurbished buildings across Europe.

The Directive at Art. 9 specifies that Member States (MS) which are part of EU must make sure that by

2021 all the buildings of new construction, and by 2019 all new public buildings, will be nearly Zero

Energy Buildings (nZEB) and Member States should outline initiatives and “encourage best practices

as regards the cost-effective transformation of existing buildings into nearly zero-energy buildings”. 3

Therefore, most Member States reviewed their existing regulations, norms and guidelines in addiction

to start to draw up the resources to increase the spreading of this kind of high-energy performance

buildings by making clear the nZEB definitions on the national-wide. Nonetheless, there are critical

points in the progress and establishment of nZEBs across the 28 Member States. On the one hand,

Northern Member States succeeded to elaborate or adjust principles, definitions and construction

technologies of nZEBs that are efficient and fit to their heating dominated climatic conditions; on the

other hand, Southern Member States are still trying to find the most suitable solutions considering the

climate and local architecture, as well aesthetic, technical and economic context. 4

In this thesis, the case study examined is a residential building, located in Lisbon (Portugal), object of a

project for which the Department of Civil Engineering of the University NOVA of Lisbon (PT)

collaborated with the Massachusetts Institute of Technology (MIT) (FIRST 5). The aim of the project is

2 D. D’Agostino, C. Marino, F. Minichiello, F. Russo. (2017). “Obtaining a NZEB in Mediterranean climate by

using only on-site renewable energy: is it a realistic goal?”

3 B. Atanasiu, T. Boermans, K.E. Thomsen, J. Rose, S. Aggerholm, A. Hermelink,M. Offermann. (2011). “Principles for Nearly Zero Energy Buildings”

4 S. Attia, P. Eleftheriou, F. Xeni, M. Rodolphe, C. Mènèzo, V. Kostopoulos, L. Pagliano, M. Cellura, M.G. Almeida, M.A. Ferreira, T. Baracu, V. Badescu, R.G. Crutescu, J.M. Hidalgo Betanzos. (2017). ”Overview and

future challenges of nearly Zero Energy Buildings (nZEB) design in Southern Europe”

5 C.A. Santos Silva, C. Sousa Monteiro, D. Aelenei, F. Costa, H. Gonçalves, J. Martins, L. Aelenei, N. Madjalani, R.A. Lopes, T. Simoes. (2018). “FIRST - Mapping flexibility of urban energy systems”

Page 14: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

2

to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures

and equipments in order to lower the Energy demand. Each component after retrofit has to reach the U-

values of the Italian existing regulation about Nearly Zero Energy Buildings.

Despite being the building in question located in Portugal, which enjoys a “Hot-Summer Mediterranean

Climate”, we started modelling the building via Energy Plus 6 with all the information (location,

envelope, fixtures, HVAC system, thermal zones, thermostat temperatures) and then, using an iterative

methodology, we calculated the energy demand of the building in different configurations. The next step

was to simulate a retrofit of the building envelope and the fixtures, and the energy demand were

calculated so that the consumptions of the building were lower than the original model. The simulations

done were made at first considering the building located in Lisbon, and then in Turin, and the results

were compared.

The data provided about the building showed graphic results of indoor temperature and energy demand

in different periods of the year, comparing the results of the original model having multiple thermal

zones to the new configurations with only a single thermal zone and with different weather files and

configurations, launched through Energy Plus.

Another relevant handled topic is the Energy Flexibility which allows the building to use the energy

produced on-site from renewable sources like Photovoltaic systems in the hours of the day when there

is a peak of energy demand; in fact as regards heating flexibility, this means to heat the building when

there is solar energy available that can cover or reduce the energy demand in the mid part of the day.

Being the case study building residential, in this work Energy Flexibility has led to lower the energy

demand of the building shifting the consumption of the heating system into the period of the day in

which the generation of energy onsite reaches a peak. That way, in the middle hours the consumptions

are totally covered by generation of energy and the house stores the heat or the cold in the walls

decreasing the peaks of demand in latter times of the day.

The project aims to achieve greater environmental sustainability due to lower energy consumption,

better indoor air quality and lower carbon dioxide emissions through the exploitation of the building's

thermal inertia and the use of renewable sources.

The EPBD requires all new buildings from 2021 (public buildings from 2019) to be nearly zero-energy

buildings (NZEB) and a proper design and retrofit of the building stock could be the start point for a big

6 U.S. Department of Energy. “EnergyPlus Version 8.9.0 Documentation- Getting Started”

Page 15: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

3

change towards a future in which the buildings have to be increasingly independent from the electric

grid.

Figure 1 - Graphic definition of a nZEB (Source: AIMS Press, “Energy efficient measure to upgrade a

multistory residential in a nZEB”)

Page 16: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

4

Page 17: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

5

1. Climate change and building sector The human activity seems to be the most likely cause of the actual warming trend since the mid-20th

century and it’s moving forward at a rate that has never reached in the past millennia. Indeed, carbon

dioxide and other gases are capable to trap the heat creating a greenhouse effect. Their ability to

compromise the transfer of infrared energy through the atmosphere is the scientific base of many

instruments conducted by NASA. 9

Figure 2 - Graph comparing carbon dioxide level in the past millennia (Source: NASA, “Climate Change: How

do we know?”, Credit: Luthi, D., et al. 2008; Etheridge, D.M., et al. 2010; Vostok ice core data/J.R. Petit et al.;

NOAA Mauna Loa CO2 record.)

The increasing of carbon dioxide and human emissions into the atmosphere as well as the increasing of

the energy demand, has driven the planet’s average surface temperature to a surge of about 1.62 degrees

Fahrenheit (0.9 °C) since the late 19th century. The last ten years was the warmest on record since 2010,

but most of the warming occurred in the past 35 years.

This rise in temperatures has led to a shift in the seasons, with anomalous periods of heat during the

winter, an equatorial-style rain and unusual disturbances. 7

7 H. Shaftel, R. Jackson, S. Callery, D. Bailey. (2019). “Climate Change: How do we know?”

Page 18: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

6

Figure 3 - Sea level (Source: NASA, “Sea level”, Last access 07/02/2020)

The Greenland and Antarctic ice caps have been decreasing in mass in the last two decades, in fact

NASA's Gravity Recovery and Climate Experiment prove that Greenland lost an average of 286 billion

tons of ice every year between 1993 and 2016, while Antarctica lost about 127 billion tons of ice per

year during the same time period. In the last decade the Antarctica has tripled its ice loss. 10

The sea level has been rising primarily for two reasons related to global warming: the dilatation of sea

water caused by its warming and the added water from melting ice caps. Figure 3 shows the rise of the

sea level since 1993 as observed by satellites. 8

The continuous growth of the population and the rising temperatures will lead to ever greater energy

demand and in most countries of the world, buildings will need more energy for cooling. 9

8 H. Shaftel, R. Jackson, S. Callery, D. Bailey. (2019). “Climate Change: How do we know?”

9 The IPBES Media Team. (2018). “Media release: Worsening worldwide land degradation now critical,

undermining well-being of 3.2 billion people”

Page 19: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

7

Changing the current attitude of building to reduce our emissions and introduce energy savings on many

different levels of our daily life could be a small step to contribute to slow down the anthropic climate

change taking place on our planet . It is estimated that about 4 billion people will live in barren areas

within the next 50 years, the issues of continuous land degradation will push up to 700 million humans

to migrate, 18% of mammals will be in danger of extinction, the combination of land degradation and

climate change could decrease agricultural production by 10% to 50%.

It is therefore necessary to implement a change in our daily lives, starting from the way we design our

houses. With the current economic system, in the immediate future, 4.3 Italy will be needed to cover the

Italian’s energy demand. 10

In the following a brief description of the main consequences is given.

Rising temperatures:

The Intergovernmental Panel on Climate Change (IPCC) Fifth Assessment Report (AR5) states that the

climate change is clear and unmistakable, and that human activities, the use of fossil fuels, old equipment

as like the emissions of CO2 are probably the principal causes. Changes are visible: the atmosphere and

oceans are warming up, weather conditions are changing, the sea level is rising, the ice caps are melting,

the wildfires are becoming increasingly extensive and intensive. 11

Projections for the future:

Computer models show that changes will continue at a faster rate and that the emissions of greenhouse

gases grew faster in the last decade than in the previous ones.

If emissions keep on rising at the running rate, effects by the end of this century are estimated to

include a global average temperature 2.6 to 4.8 degrees Celsius (°C) higher than present, and sea levels

0.45 to 0.82 metres higher than the current level.

The Paris Agreement, which was an international reunion taking place in Paris on the 12nd December

2015, where Parties to the UNFCCC (United Nations Framework Convention on Climate Change)

reached an agreement to fight and prevent the climate change and to accelerate the actions needed for

10 The IPBES Media Team. (2018). “Media release: Worsening worldwide land degradation now critical,

undermining well-being of 3.2 billion people”

11 R. Van Staden, University of Cambridge. (2014). “The Physical Science of Climate Change”

Page 20: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

8

a future with lower carbon emissions and to set a target for keeping the global temperature rise below

2°C, and to consider lowering the target to 1.5°C soon. 12

DATA

When we talk about carbon pollution, we usually have the tendency to think that the main cause the

transportation sector. We can imagine streets and cities plenty of vehicles stuck in traffic, releasing in

the atmosphere a big quantity of gases and CO2. Even if is less evident, the building sector has a higher

environmental footprint than transportation.

As shown in Figure 4, buildings produce pollution both directly and indirectly; building operations, the

processing of products, the stock and the construction are representing the 39% of the national carbon

dioxide emissions. Industry activity is in second place with 32% of emissions, and transportation is in

third place with 23%.

Direct Building Emissions

12 The IPCC’s Fifth Assessment Report, C. Symon. (2013). “Climate change: Actions, trends and implications for

business”

Figure 4 - Carbon Footprint (Source: Global Alliance for Buildings and Constructions, “Global status report”, 2018)

Page 21: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

9

Buildings usually produce carbon dioxide directly when they use equipment based on combustion.

Carbon emission for space heating are produced by:

• Boilers and furnaces that burn fuels like natural gas and heating oil;

• Water heaters also use fossil fuel combustion as a heat source;

• Power generated on-site also contributes to building emissions if the energy used is a fossil fuel.

All the equipment mentioned could be realized not using fossil fuel combustion. For instance, heat

pumps could replace boilers, furnaces and conventional water heaters could use only electricity in order

to avoid local emissions. Moreover, wind turbines and solar photovoltaic systems are useful for on-site

generation of electricity, and they can be associated to batteries for storing the electricity in the period

of excess and using it when the building needs.

Indirect Building Emissions

In addition to the direct emissions released by buildings, there are indirect emissions associated to

transportation of fuels and materials, extracting raw materials, processing products and delivering to the

construction site.

Each material bring with it incorporated CO2 emissions, but they are never considered. 13

1.1 NZEB ACROSS EUROPE According to the agreed definition of the term, “A zero-energy building (ZEB), also known as a net-

zero energy building (NZEB), is a building with zero net energy consumption, meaning the total

amount of energy used by the building on an annual basis is equal to the amount of renewable energy

created on the site”, or in other definitions by renewable energy sources off-site. These buildings

release to the atmosphere less greenhouse gas comparing to non-ZE buildings. 14 15

13 C. Bipat. (2019). “How Buildings Produce Carbon Emissions... And How to Stop Them”

14 Paul Torcellini, Shanti Pless, Michael Deru National Renewable Energy Laboratory; Drury Crawley, U.S. Department of Energy. National Renewable Energy Laboratory report. (2006). "Zero Energy Buildings: A Critical Look at the Definition"

15 US Department of Energy. (2015). "A Common Definition for Zero Energy Buildings"

Page 22: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

10

Recent data show that buildings complying with the building code, consume 40% of the national fossil

fuel energy in the US and European Union and are considerable contributors of greenhouse gases. 16

The zero-energy consumption criterion is viewed as a way to decrease carbon emissions and decrease

dependence on electric grid and fossil fuels.

Many zero-energy buildings utilizes the electric grid to store the energy, some are independent to the

grid instead and others harvest and store the energy onsite. Energy can be harvested onsite exploiting

solar energy or wind, through photovoltaic system or wind turbines but the energy demand has to be

reduced using highly efficient HVAC technologies (Heating, Ventilation and Air Conditioning) and

highly efficient lightning or a proper insulation of the envelope and airtightness. The zero energy

standards are becoming increasingly easier to realize and to design as long as the costs of these

technologies decrease and the costs of traditional fossil fuel increase.

New construction technologies and techniques as well as the evolution and advances in new energy

made the development of zero energy building ever more possible. nZEB construction technologies

usually include high efficiency solar panels, double or triple low emission glazed windows, proper

exterior insulation and heat pumps.17

16 Baden, S., et al. (2006). "Hurdling Financial Barriers to Lower Energy Buildings: Experiences from the USA and Europe on Financial Incentives and Monetizing Building Energy Savings in Private Investment Decisions."

17 Yatish T, Shah. (2020). “Modular Systems for Energy Usage Management”

Page 23: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

11

1.1.1 Definitions

Electrical grid

An electrical grid is an interconnected network for delivering electricity from producers to consumers.18

Zero net site energy use (ZNE)

In this kind of Zero Net Energy building, the amount of energy harvested onsite through renewable

sources is even to the energy demand of the building.

Zero net source energy use

In this kind of Zero Net Energy building, the energy generated is even to the energy used, including the

energy used to bring the energy to the building. The amount of energy that these ZNE buildings has to

produce is higher than zero net site energy buildings.

Net zero energy emissions

In some countries, a ZEB is generally associated to the definition of zero net emission building or zero-

carbon building (ZCB).

Carbon emissions and energy saving are two different topics but sometimes the emissions released by

the building through equipment or fossil fuel use can be balanced by the quantity of energy produced

onsite through renewable sources. Other definitions take into account also the emissions generated

during the construction and the incorporated energy of the structure (the emissions connected to the

extraction of the raw materials, the process and the transportation).

Net off-site zero energy use

A building can be defined a Zero Energy Building if the total amount of the energy it uses comes from

renewable energy sources produced onsite, or also produced offsite.

Net Zero Energy Building or Nearly Zero Energy Building

The NZEB can be described as a grid-connected building that produce the same amount of energy by

renewable sources onsite than its own energy demand; the building becomes an active part of the energy

infrastructure exchanging energy to the grid.

18 Kaplan, S. M. (2009). “Smart Grid. Electrical Power Transmission: Background and Policy Issues. The Capital.Net”

Page 24: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

12

Figure 5 - Net ZEB balance concept: balance of weighted energy import respectively energy demand (x-axis) and energy export (feed-in credits) respectively (on-site) generation (y-axis) (Source: EMusall, University of

Wuppertal, 2013)

1.1.2 Design and construction

Zero Energy Buildings are typically designed to use passive solar heat gains and shadings, combined

with thermal inertia and super insulation to decrease diurnal temperature variations during the day. 19

ZEBs are designed for having significant energy-saving features.

High-efficiency equipment are used to reduce heating and cooling loads; for instance, heat pumps which

are four times more efficient than furnaces, thick insulation, double or triple low-E glazing, LED

lighting, high efficiency appliances, natural ventilation, passive solar gains in winter and shading in the

summer.

These features can be different according to the climate zone in which the construction is based. Water

store fixtures can be used to decrease the water heating loads, or heat recovery units on wastewater or

also using solar water heating. Moreover, daytime illumination could be ensured into the house during

all day using skylights or solar tubes.

Night-time illumination is normally provided by LED lighting that consume 1/3 or less power than

incandescent lights, not adding unwanted heat.

19 Frej, Anne, editor, Urban Land Institute. (2005). “Green Office Buildings: A Practical Guide to Development”

Page 25: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

13

Once the energy demand of the building has been reduced to the minimum is possible to generate all

that energy on site through photovoltaic panels on the roof or wind turbines.

1.1.3 Energy Harvest

Zero Energy Buildings harvest energy to cover their electricity need and heating or cooling energy

demand. Most of the time, energy is harvested through solar photovoltaic panels installed on the roof

that transform the sun's light into electricity. Energy can also be harvested through solar thermal

collectors that use the heat of the sun to heat the water for the building. Heat pumps or geothermal can

also harvest heat and cool from the air or ground next to the building.

The difference between heat pumps and geothermal is that the heat pumps move the heat rather than

harvest it, but the impact of decreasing the energy demand and carbon footprint is very similar.

Talking about individual houses, to provide heat or electricity to the building, can be used

microgeneration technologies like solar cells or wind turbines for generating electricity, and biofuels or

solar thermal collectors connected to a thermal energy storage useful for space heating. This thermal

energy storage can also be used in winter storing the cold from the underground. Zero Energy Buildings

are usually connected to the electric grid in order to export electricity when there is a surplus and draw

electricity when the one produced is not enough to cover the energy demand. 20

1.2 EPBD (Energy Performance Building Directive) and ZEBRA2020 The Energy performance of buildings directive (EPBD) and the Energy Efficiency Directive are the

main legislative tools to spread the energy performance of buildings and to raise the renovation within

the European Union.

The EPBD (2010/31/EU) has been in operation since 2010 and helps users to design buildings in the

right way in order to save energy and money. Through it, has been a good change of trends in the energy

performance of buildings and its development; in fact, in the EPBD introduction about energy efficiency

requirements, the new buildings compliant to the building code are two time more efficient than the

typical buildings from the 1980s, and consume half of the energy.

20 Yatish T, Shah. (2020). “Modular Systems for Energy Usage Management”

Page 26: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

14

The European building sector is responsible for about a third of CO2 emissions, and the European Union

has established a target of 20 % reduction by 2020 and 60 % by 2030, from a 1990 level. Reaching these

targets means to reduce the energy demand of the building through retrofits of the existing building

stock and to use high efficiency equipments to decrease the carbon footprint. 21

In Europe, the 40% of the total energy demand comes from building sector. Thus, measures for this

sector, especially concerning energy savings, has been introduced by European Directives 2002/91/EC

and 2010/31/EU for the design of the buildings or their technical equipment.

The Directives foster the improvement of the energy performance of the building sector through

different points, i.e.:

• use of renewable energy sources;

• high energy efficiency technologies for Heating, Ventilation and Air Conditioning systems;

• passive approaches, like solar shading devices or super insulation;

• heat recovery on the ventilation system;

• lighting with high energy efficiency such as LED of fluorescent;

• high efficiency vehicles or transport systems.

Also, there are so many other things upon which to pay attention for an ideal building performance like

indoor air quality, thermal and acoustic comfort, enough natural light and airtightness.

In cold climates, to design and a high energy performance building is easier and simpler compared to

hot climates. This is because it’s easier to store the heat inside the building instead of dissipating it; in

fact, in cold climates, thermal insulation and low specific weight have a key role. On the other hand, in

hot climates, high thermal insulation can produce negative effects restraining the dissipation of heat. 22

The Energy Performance Building Directive (EPBD) sets standard for all new buildings from 2021 (and

already from 2019 for public buildings) to be nearly zero-energy buildings (NZEB).

The Directive requires that the nearly zero or very low amount of energy demand of the building should

be covered from the energy produced or harvested onsite through renewable sources.

21 European Commission. (2017). "Buildings"

22 D. D’Agostino, C. Marino, F. Minichiello, F. Russo. (2017). “Obtaining a NZEB in Mediterranean climate by

using only on-site renewable energy: is it a realistic goal?”

Page 27: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

15

According to a recent EU project (ZEBRA2020), which is aimed at tracking the market transition to

nearly Zero-Energy Buildings (nZEBs) and provide recommendations and guidelines for the building

sector to accelerate the market spread of nZEBs across Europe, building are analysed and catalogued in

4 different energy efficiency categories, defined by experts:

1. Better than nZEB standard;

2. nZEB buildings compliant to the national official nZEB definition;

3. Buildings with an energy performance better than the building code (2012);

4. Buildings constructed/renovated according to building code (2012).

The following figure shows the uptake of nZEB in the building sector. The diffusion of nZEBs varies a

lot between countries. In fact, in France, the nZEB definition correspond to the current thermal

regulation and the primary energy performance of residential buildings has to be below 50 kWh/m2/year.

Therefore, all new buildings are already nZEB (since 2013). In other countries, the diffusion is slower

because the nZEB standards are more severe compared to the building code requirements. 23

23 Agne Toleikyte, Lukas Kranzl, Raphael Bointner, Frances Bean, Jordi Cipriano, Maarten De Groote, Andreas Hermelink, Michael Klinski, David Kretschmer, Bruno Lapilonne, Ramón Pascual, Andrzej Rajkiewicz, Jose Santos, Sven Schimschar, Carine Sebi, Jonathan Volt (2016). “Zebra 2020 – Nearly Zero Energy Building Strategy 2020”

Figure 6 - Key years for nearly Zero-Energy Building (Directive 2010/31/EC) (Source: EPISCOPE)

Page 28: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

16

Figure 7 - Distribution of new buildings according to different building standards (Source: ZEBRA2020, “Nearly Zero Energy Building Strategy 2020”)

For residential buildings, most jurisdictions move towards having a primary energy use lower than 50

kWh/m²/year. For non-residential buildings instead, the standards are less strict in the same country,

depending on the type of building. Generally, because of different calculation methodology, climate

conditions and building typology in the different countries, the maximal primary energy level for non-

residential buildings in Europe stands from 0 to 270 kWh/m²/year.

The Directive describes only the big picture giving the right of expression to Member States to refine it.

Thus, the Nearly Zero Energy Building concept is very flexible with no single definition across the EU.

Member States are responsible to define their own definition of nZEBs in their national plans and

national contexts, improving their standards for constructions. 24

24 Building Performance Institute Europe (BPIE). (2015). “Nearly Zero Energy Buildings definitions across

Europe”

Page 29: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

17

1.3 EPBD implementation in Italy Decree 192/2005 , modified by Legislative Decree 311/2006, establishes the basis for the Energy

Performance Building Directive implementation in Italy. After the decree was set, many acts updated

the decree about the minimum standards for buildings, building systems and components, guidelines for

energy certification and calculation for cooling and lighting systems.

Law 90/2013 implemented Directive 2010/31/EU instead, adding important changes to the first 2005

implementation. Later, on the 26th of June 2015, the EPBD was implemented with 3 inter-ministerial

decrees which set stricter minimum requirements for new buildings and significant renovations, made a

definition for nZEBs and they set rules for Renewable Energy Sources for buildings.

Italian regions (21 in total) have then a clear definition on nZEB and standards in energy topics. The

recent legislation provided, with a unanimous consensus of all the regions, an agreeded implementation

of the EPBD all over the national country and took implementation a step forward:

• The six regions that had independently implemented the EPBD before October 2015 (Liguria,

Emilia Romagna, Tuscany, Val d’Aosta, Piedmont, Lombardy and the provinces of Trento and

Bolzano) have a period of two year to align their EPC (Energy Performance Certification) system

to that required by national law;

• Five more regions/autonomous provinces have already proven their EPC database since 2014

(15/21).

1.3.1 Energy performance standards: NEW BUILDINGS

The new decree 26/06/2015 “Minimum Requirements” enhanced the previous acts and provided an

updated energy performance calculation methodology, minimum standards for high efficiency

buildings, building systems and components, guidelines for energy certification and calculation for

cooling and lighting systems, as well as conversion factors. The new legislation also defined NZEB.

Current calculation methodologies are proceeding from the national standard UNI/TS 11300 (series

from 1 to 6), and the calculation of artificial lighting from the standard UNI EN 15193:20086 .

The main changes from 2015 are the following:

1. Updated methodology for the calculation of energy performance, in accordance with EPBD Annex I:

• The total annual energy demand is calculated for each energy service monthly and indicated in

primary energy;

Page 30: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

18

• The energy produced onsite through renewable sources is calculated in the same way;

2. For the energy services taking into consideration like heating, cooling, ventilation and domestic hot

water for residential buildings, and lighting and internal transports (lifts, escalators) for non-residential

buildings, the new energy performance standards for new buildings (and significant renovations) are

based on the application of the cost-optimal methodology results (EPBD, Article 5), with the use of a

“Reference Building”.

3. Factors for the conversion of delivered energy to primary energy.

1.3.2 Format of national transposition and implementation of existing regulations

Minimum standards are defined in accordance with the "reference building".

Energy parameters of the reference building will require more strict standards from 2021 and from 2019

for public buildings. (Table 1,2)

The new legislation in operation requests the calculation of the next energy performance benchmarks:

• Specific Energy demands for heating (EP H,nd), cooling (EP C,nd) and domestic hot water (EP W,nd);

• Energy performance indicators for heating (EPH), cooling (EPC), domestic hot water (EPW),

ventilation (EPV), lighting (EPL) and transport (EPT) for non-residential buildings, for non-

renewable and total primary energy [kWh/m2];

• Global energy performance indicator EPgl = EPH + EPC + EPW + EPV + EPL* + EPT* for non-

renewable and total primary energy [kWh/m2].

A new building (or significant renovated building) complies with the minimum standards if the Specific

Energy demands for heating and cooling (EP H,nd, EP C,nd) and the Global energy performance EPgl are

lower than the values of the “reference building”. Also, new buildings are required to have a minimum

percentage of Energy produced through Renewable Energy Sources for the supply.

In the evet that the required RES addiction should not be achievable, the building has to comply with a

proportionally lower Global Energy performance indicator (EPgl) limit value.

Page 31: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

19

Table 1. Reference building – Performance of single building elements (Source: Ministry of Economic Development)

Table 2. U-value limits for Second level Major renovation and Minor renovation (Source: Ministry of Economic Development)

Page 32: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

20

1.3.4 Energy performance requirements: EXISTING BUILDINGS

The building sector in Italy has the biggest impact of total energy demand with a percentage of 37.1%.

The non-residential sector revealed a decrease in consumption (- 6.7%) in 2015 for the first time in the

past 20 years. The annual rate of energy refurbishment of existing residential buildings is esteemed to

be about 0.5%.

Energy performance standards for existing buildings are equal regardless of they are residential or non-

residential buildings. Minimum standards are differentiated in accordance with the size of the renovation

intervention:

• Major renovations – 1st level (“renovation of at least 50% of the envelope and renovation of the

heating and/or cooling plant of the whole building”). Standards for new buildings consider the whole

building, limited to the concerned energy services. For building enhancements (new volume >15%

of the existing volume or >500 m3 ) these standards apply to the new volume.

• Major renovations – 2nd level (“refurbishment of at least 25% of the exterior surfaces of the

building with or without renovation of the heating and/or cooling plant”). The U-value of each

surface is lower than the limit values.

• Minor renovations (“refurbishment of less than 25% of the external surfaces of the building and/or

variation of the heating and/or cooling plants”). The performance of single components or of the

technical building systems must enforce necessarily the limit values.

Page 33: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

21

Page 34: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

22

Page 35: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

23

2. Data acquisition and Original model

The building examined in this thesis is an existing residential building, located in Lisbon (Portugal),

object of a project for which the Department of Civil Engineering of the University NOVA of Lisbon

(FCT) collaborated with the Massachusetts Institute of Technology (MIT). The building is situated in

the Encarnação Neighbourhood (Lisbon) that was built around 1940 thanks to the “Social Quarters

Programme” promoted by the City Administration. The social quarters were an archetype of Estado

Novo urbanism policy and were intended to build neighbourhoods of social housing to receive families

of lower classes. Associated was also a formal model of property by which the families could own the

property of the house after a 25 years period of monthly rates.25 Normally, these kinds of

neighbourhoods were built in the border of the city, in suburban areas, and were characterised by

symmetry and wide distribution. These neighbourhoods featured also green areas, covering about 20-

25% of the total area, the apartments were small, and the street network was organized in a hierarchical

way. 26

As regards to the architectural context, the period between 1940 and 1950 was known as “Português

Suave”. This architecture period enclosed a mix of different genres and ideas like the modernists

engineering features, disguised by a blend of exterior aesthetic elements based on Portuguese

Architecture of the XVII and XVIII centuries and on traditional houses across Portugal. 27 Today,

Encarnação Neighbourhood is a low-density residential area composed by semi-detached houses on two

elevations. Most part of the neighbourhood has already been renovated (Figure 8).

Figure 8 - Encarnação Aerial View (2005) and Encarnação Initial Plan (1940)

25 M. C. Teixeira. (1992). "As estratégias de Habitação em Portugal, 1880-1940"

26 M. Salgado. (2006). “Atlas Urbanístico de Lisboa”

27 J. M. Fernandes. (2003). “Portugês Suave - Arquitectura do Estado Novo”

Page 36: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

24

2.1 Methodology and tools EnergyPlus, an open source software for dynamic energy simulation, developed in the United States in

2001 by the Department of Energy (DOE), was used in this thesis to evaluate the energy performance

of the building and the internal temperature of the thermal zone/zones in operating conditions in the

various configurations; EnergyPlus performs integrated simulations between the environment and the

system, that is, the information relating to the load which the system must be able to balance, is used to

determine the temperature conditions of the air in the environment through an iterative process.

The software is divided into 3 main interconnected blocks: the Surface Heat Balance Manager which

solves the thermal balance at the surfaces, the Air Heat Balance Manager which solves the balance of

the environment by simulating the radiative and convective heat exchanges, and the Building System

Simulation Manager that deals with the simulation of plant components, be they hydronic or air systems.

These main modules, part of the Integrated Solution Manager, interact with other secondary modules in

such a way that all the elements of the model are solved simultaneously, and not sequentially, to obtain

a simulation as realistic as possible. 28

Figure 9 - Energy Plus internal elements (Source: U.S. Department of Energy, EnergyPlus Version 8.9.0 Documentation- Getting Started)

28 U.S. Department of Energy. “EnergyPlus Version 8.9.0 Documentation- Getting Started”

Page 37: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

25

The case study building is divided into different areas and the project in which I took part already

provided the energy performance and internal temperatures of each area at different times of the year.

In order to use the data, the geometric model of the building was created on Energy Plus considering as

in the original project each zone as a thermal zone and then the results were compared.

Having noticed that the results were almost similar, the geometric model was redesigned in such a way

as to have a single heated or cooled thermal zone that grouped all the areas of the building and another

not air-conditioned (that of the attic). The energy simulation of the single thermal zone building was

carried out with both the annual Lisbon and Turin weather conditions. Once this was done, a

redevelopment of the original building was envisaged, aimed at enforcing the thermal transmittance

values required by law from each element of the building envelope. Energy demand and indoor

temperature were then calculated and compared for each city with the values of the original model.

2.2 The Original Building The case study building has two floors above ground plus attic, but only the first floor and the attic were

taken into consideration for the simulations in the thesis.

The steps preceding the simulation are:

1. create the three-dimensional geometric model to identify the thermal zones;

2. assign materials and stratigraphy to the various components;

3. choose a meteorological file of the place.

Location: Lisbon

Latitude: 38.73 deg

Longitude : -9.15 deg

Elevation: 2 m

Page 38: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

26

2.2.1 Geometric model

The geometric model of the building was created directly on EnergyPlus by assigning to each element

the number of vertices and their respective coordinates in space; the coordinate system is Relative, the

direction chosen for the coordinates is counter clockwise and the first vertex to be inserted is the upper

left corner.

Figure 10 - Graphic example for each element (Wall, Floor, Roof)

Figure 11 - Geometric model

Page 39: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

27

The building consists of 4 rooms: 2 bedrooms, a kitchen-living room and an area called "Merged" which

includes 3 spaces. Zones 1, 2, 3 have a pitched roof that houses an attic underneath; the kitchen-living

room area instead has a flat roof on which a photovoltaic system is installed.

In the South side of the building there are 2 windows while on the North side there is a curtain wall that

covers all the facade.

2.2.2 Envelope and Components

At this point, the stratigraphy and the thermophysical values of the materials have been inserted for each

surface. The U-Factor of each surface has been calculated automatically by the software Energy Plus.

Table 3. Exterior walls stratigraphy (Original building)

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Plaster 2 1900 1046 1,3

Insulation (EPS) 4 25 1210 0,04

Brick 22 633 790 0,42

Plaster 2 1900 1046 1,3

0,587U-Factor [W/m² K]

Exterior wall

Figure 12 - Plan of the building (Floor 1)

Page 40: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

28

Table 4. Interior walls stratigraphy (Original building)

Table 5. Floor stratigraphy (Original building)

Table 6. Ceiling stratigraphy (Original building)

Table 7. Roof stratigraphy (Original building)

Table 8. Window stratigraphy (Original building)

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Plaster 2 1900 1046 1,3

Brick 7 818 790 0,37

Plaster 2 1900 1046 1,3

Internal wall

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Wood panel 12 900 820 0,34

Wood panel 3 900 820 0,34

Concrete 15 2300 1000 2

Concrete 5 700 1000 1,3

Floor

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Wood panel 3 900 820 0,34

Wood panel 12 900 820 0,34

Insulation (Mineral wool) 8 50 1100 0,04

Plasterboard 1 900 820 0,25

0,538U-Factor [W/m² K]

Ceiling

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Roof tiles 5 907 1000 0,41

Plate 4 900 820 0,025

0,538U-Factor [W/m² K]

Roof

Layer Depth [cm] Conductivity [W/m K]

Glass 0,6 0,9

Air 1,2 0,026

Glass 0,4 0,9

U-Factor [W/m² K] 1,32

Window

Page 41: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

29

2.2.3 Assumptions

Since the building is used for residential use, the following hypotheses have been established to launch

the energy simulations:

1. In order to simplify the calculation, the lights, equipment and people’s metabolic activity were

grouped as “Electric Equipment” producing 4 W/m² during all day;

2. The air-conditioned zones are Quarto 1, Quarto2, Merged and Kitchen-Sala, and not the attic

under the roof;

3. Each room has the same Thermostat Setpoint temperature;

4. The Design Flow Rate per hour is 0.4 air changes;

5. The house is occupied only in the morning and at night (nobody in the house from 09-18 pm)

(Figure 13);

6. The heating-cooling system has been programmed to work only in the periods when the house

is occupied.

Figure 13 - % of people in the house during the day

0

20

40

60

80

100

120

0 3 6 9 12 15 18 21 24

Per

cen

tage

[%

]

Time [h]

% of people in the house

Page 42: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

30

2.2.4 Configuration 1. LISBON (Original Model – Multiple thermal zones) / Indoor temperature and Energy Demand

Having as input data all the assumptions made previously, through Energy Plus has been possible to

obtain the results of indoor temperature and energy demand of the building. In this thesis project two

scenarios have been chosen to show the results and to compare them in the different configurations:

• 1 day and 1 week in January

• 1 day and 1 week in August.

In this first configuration, the simulation has been done considering the building with multiple thermal

zones and it has been the starting point and comparison for the next configurations.

Figure 20 shows the Energy demand of the original building during the whole year. Energy is expressed

in [kWh] and the two colours blue and orange represent respectively the energy demand for heating and

for cooling the thermal zones.

Figure 14 - Total Energy Demand – Multiple thermal zones (Lisbon/Original Model)

0

0,5

1

1,5

2

2,5

3

3,5

0 1000 2000 3000 4000 5000 6000 7000 8000

Ener

gy [

kWh

]

Time [h]

TOTAL ENERGY DEMAND - ALL THE YEAR

HEATING ENERGY COOLING ENERGY

Page 43: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

31

Figure 15 - Outdoor-Indoor Temperature 27th of January – Multiple thermal zones (Lisbon/Original Model)

Figure 16 - Total Energy Demand 27th of January – Multiple thermal zones (Lisbon/Original Model)

0

5

10

15

20

25

01

/27

01

:00

:00

01

/27

02

:00

:00

01

/27

03

:00

:00

01

/27

04

:00

:00

01

/27

05

:00

:00

01

/27

06

:00

:00

01

/27

07

:00

:00

01

/27

08

:00

:00

01

/27

09

:00

:00

01

/27

10

:00

:00

01

/27

11

:00

:00

01

/27

12

:00

:00

01

/27

13

:00

:00

01

/27

14

:00

:00

01

/27

15

:00

:00

01

/27

16

:00

:00

01

/27

17

:00

:00

01

/27

18

:00

:00

01

/27

19

:00

:00

01

/27

20

:00

:00

01

/27

21

:00

:00

01

/27

22

:00

:00

01

/27

23

:00

:00

01

/27

24

:00

:00

Tem

per

atu

re

Time [h]

Temperatures on the 27 of January

OUTDOOR TEMP KITCHNETTE_SALA QUARTO 1 QUARTO 2 MERGED

0

0,5

1

1,5

2

2,5

3

3,5

626 631 636 641 646

Ener

gy[k

Wh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY

Page 44: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

32

Figure 17 - Outdoor-Indoor Temperature 21-27th of January – Multiple thermal zones (Lisbon/Original Model)

Figure 18 - Total Energy Demand 21-27th of January – Multiple thermal zones (Lisbon/Original Model)

0

5

10

15

20

25

01

/21

01

:00

:00

01

/21

07

:00

:00

01

/21

13

:00

:00

01

/21

19

:00

:00

01

/22

01

:00

:00

01

/22

07

:00

:00

01

/22

13

:00

:00

01

/22

19

:00

:00

01

/23

01

:00

:00

01

/23

07

:00

:00

01

/23

13

:00

:00

01

/23

19

:00

:00

01

/24

01

:00

:00

01

/24

07

:00

:00

01

/24

13

:00

:00

01

/24

19

:00

:00

01

/25

01

:00

:00

01

/25

07

:00

:00

01

/25

13

:00

:00

01

/25

19

:00

:00

01

/26

01

:00

:00

01

/26

07

:00

:00

01

/26

13

:00

:00

01

/26

19

:00

:00

01

/27

01

:00

:00

01

/27

07

:00

:00

01

/27

13

:00

:00

01

/27

19

:00

:00

01

/28

01

:00

:00

01

/28

07

:00

:00

01

/28

13

:00

:00

01

/28

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperatures on the 21-27 of January

OUTDOOR TEMP KITCHNETTE_SALA QUARTO 1 QUARTO 2 MERGED

0

0,5

1

1,5

2

2,5

3

3,5

482 502 522 542 562 582 602 622 642 662

Ener

gy[k

Wh

]

Time [h]

ENERGY DEMAND - 21-28 of January

TOTAL ENERGY

Page 45: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

33

Figure 19 - Outdoor-Indoor Temperature 29th of August – Multiple thermal zones (Lisbon/Original Model)

Figure 20 - Total Energy Demand 29th of August – Multiple thermal zones (Lisbon/Original Model)

0

5

10

15

20

25

30

35

40

Tem

per

atu

re[°

C]

Time [h]

Temperatures on the 29 of August

OUTDOOR TEMP KITCHNETTE_SALA QUARTO 1 QUARTO 2 MERGED

0

0,5

1

1,5

2

2,5

3

3,5

5762 5767 5772 5777 5782

Ener

gy[k

Wh

]

Time [h]

ENERGY DEMAND - 29 of August

TOTAL ENERGY

Page 46: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

34

Figure 21 - Outdoor-Indoor Temperature 23-30th of August – Multiple thermal zones (Lisbon/Original Model)

Figure 22 - Total Energy Demand 23-30th of August – Multiple thermal zones (Lisbon/Original Model)

0

5

10

15

20

25

30

35

40 0

8/2

3 0

1:0

0:0

0

08

/23

07

:00

:00

08

/23

13

:00

:00

08

/23

19

:00

:00

08

/24

01

:00

:00

08

/24

07

:00

:00

08

/24

13

:00

:00

08

/24

19

:00

:00

08

/25

01

:00

:00

08

/25

07

:00

:00

08

/25

13

:00

:00

08

/25

19

:00

:00

08

/26

01

:00

:00

08

/26

07

:00

:00

08

/26

13

:00

:00

08

/26

19

:00

:00

08

/27

01

:00

:00

08

/27

07

:00

:00

08

/27

13

:00

:00

08

/27

19

:00

:00

08

/28

01

:00

:00

08

/28

07

:00

:00

08

/28

13

:00

:00

08

/28

19

:00

:00

08

/29

01

:00

:00

08

/29

07

:00

:00

08

/29

13

:00

:00

08

/29

19

:00

:00

08

/30

01

:00

:00

08

/30

07

:00

:00

08

/30

13

:00

:00

08

/30

19

:00

:00

Tem

per

atu

re[°

C]

Time [h]

Temperatures on the 23-30 of August

OUTDOOR TEMP KITCHNETTE_SALA QUARTO 1 QUARTO 2 MERGED

0

0,5

1

1,5

2

2,5

3

3,5

5618 5638 5658 5678 5698 5718 5738 5758 5778 5798

Ener

gy[k

Wh

]

Time [h]

ENERGY DEMAND - 23-30 of August

TOTAL ENERGY

Page 47: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

35

2.2.5 Considerations

As can be seen from the graphs, the indoor temperatures of the various rooms are controlled by the

thermostat set point temperatures which are generally more restrictive in the periods of the day when

people occupy the apartment.

In January the peak of energy demand reaches a value of 1,9 kWh on the day 27th, while in August, the

peak reaches a value of 3,1 kWh on the day 29th.

As for the energy demand necessary to keep the building at the set point temperature, the graphs almost

always show energy peaks at 19:00, which is the moment when people return home and the temperature

must be brought back within the values required by the thermostat and the heating or cooling system

starts to work.

The results of Energy demand are expressed in the form of Total energy, that means heating and cooling

energy in the period considered.

Page 48: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

36

Page 49: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

37

3. Data elaboration After calculating the energy demand and indoor temperature of each room of the building in the different

periods of the year with the original configuration, the first experiment was to switch from the "Multiple

thermal zones" configuration to the "Single thermal zone" configuration to simplify simulations and

control of the results.

The goal of this simplification is to be able to control and compare with the new configurations a single

temperature profile, that is that of the single thermal zone, instead of the relative temperatures of each

room. Also, for this new configuration the assumptions are the same as the previous one unlike that the

building will be composed of the only thermal zone that groups all the rooms, heated or cooled at the

same temperature, and the attic, which however is not equipped with air conditioning system.

In this chapter the results obtained from the simulations on different configurations will be shown, made

both with the weather file of Lisbon and Turin; in particular, the temperature and energy results of the

building before and after the retrofit of the envelope, before and after the change to a “Single thermal

zone”, and energy consumption after the installation of a photovoltaic system on the roof will be

compared.

Here all the configurations:

1. Lisbon / Original model – Multiple thermal zones;

2. Lisbon / Original model – Single thermal zone;

3. Lisbon / New model (Renovated) – Single thermal zone;

+ Photovoltaic system

4. Turin / Original model – Single thermal zone;

5. Turin / New model (Renovated) – Single thermal zone;

+ Photovoltaic system

6. Turin / New model (Renovated) – Energy Flexibility.

Page 50: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

38

3.1 Configuration 2. LISBON (Original Model – Single thermal zone) / Indoor temperature and Energy Demand

Input data: same assumptions of Configuration 1; only a Single thermal zone

Figure 23 - Outdoor-Indoor Temperature All year – Single thermal zone (Lisbon/Original Model)

Figure 24 - Total Energy Demand – Single thermal zone (Lisbon/Original Model)

05

10152025303540

01

/01

01

:00

:00

01

/11

05

:00

:00

01

/21

09

:00

:00

01

/31

13

:00

:00

02

/10

17

:00

:00

02

/20

21

:00

:00

03

/03

01

:00

:00

03

/13

05

:00

:00

03

/23

09

:00

:00

04

/02

13

:00

:00

04

/12

17

:00

:00

04

/22

21

:00

:00

05

/03

01

:00

:00

05

/13

05

:00

:00

05

/23

09

:00

:00

06

/02

13

:00

:00

06

/12

17

:00

:00

06

/22

21

:00

:00

07

/03

01

:00

:00

07

/13

05

:00

:00

07

/23

09

:00

:00

08

/02

13

:00

:00

08

/12

17

:00

:00

08

/22

21

:00

:00

09

/02

01

:00

:00

09

/12

05

:00

:00

09

/22

09

:00

:00

10

/02

13

:00

:00

10

/12

17

:00

:00

10

/22

21

:00

:00

11

/02

01

:00

:00

11

/12

05

:00

:00

11

/22

09

:00

:00

12

/02

13

:00

:00

12

/12

17

:00

:00

12

/22

21

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature 1 year INDOOR-OUTDOOR

OUTDOOR TEMP INDOOR TEMP

0

0,5

1

1,5

2

2,5

3

3,5

0 1000 2000 3000 4000 5000 6000 7000 8000

Ener

gy [

kWh

]

Time [h]

TOTAL ENERGY DEMAND - ALL THE YEAR

HEATING ENERGY COOLING ENERGY

Page 51: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

39

Figure 25 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Lisbon/Original Model)

Figure 26 - Total Energy Demand 27th of January – Single thermal zone (Lisbon/Original Model)

0

5

10

15

20

25

30

01

/27

01

:00

:00

01

/27

02

:00

:00

01

/27

03

:00

:00

01

/27

04

:00

:00

01

/27

05

:00

:00

01

/27

06

:00

:00

01

/27

07

:00

:00

01

/27

08

:00

:00

01

/27

09

:00

:00

01

/27

10

:00

:00

01

/27

11

:00

:00

01

/27

12

:00

:00

01

/27

13

:00

:00

01

/27

14

:00

:00

01

/27

15

:00

:00

01

/27

16

:00

:00

01

/27

17

:00

:00

01

/27

18

:00

:00

01

/27

19

:00

:00

01

/27

20

:00

:00

01

/27

21

:00

:00

01

/27

22

:00

:00

01

/27

23

:00

:00

01

/27

24

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR27 January

Outdoor temp Indoor temp SINGLE ZONE Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY SINGLE ZONE TOTAL ENERGY MULTIPLE ZONES

Page 52: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

40

Figure 27 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Lisbon/Original Model)

Figure 28 - Total Energy Demand 21-28th of January – Single thermal zone (Lisbon/Original Model)

0

5

10

15

20

25

30

01

/21

01

:00

:00

01

/21

07

:00

:00

01

/21

13

:00

:00

01

/21

19

:00

:00

01

/22

01

:00

:00

01

/22

07

:00

:00

01

/22

13

:00

:00

01

/22

19

:00

:00

01

/23

01

:00

:00

01

/23

07

:00

:00

01

/23

13

:00

:00

01

/23

19

:00

:00

01

/24

01

:00

:00

01

/24

07

:00

:00

01

/24

13

:00

:00

01

/24

19

:00

:00

01

/25

01

:00

:00

01

/25

07

:00

:00

01

/25

13

:00

:00

01

/25

19

:00

:00

01

/26

01

:00

:00

01

/26

07

:00

:00

01

/26

13

:00

:00

01

/26

19

:00

:00

01

/27

01

:00

:00

01

/27

07

:00

:00

01

/27

13

:00

:00

01

/27

19

:00

:00

01

/28

01

:00

:00

01

/28

07

:00

:00

01

/28

13

:00

:00

01

/28

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR21-28 of January

Outdoor temp Indoor temp SINGLE ZONE Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

5

12

1

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 21-28 of January

TOTAL ENERGY SINGLE ZONE TOTAL ENERGY MULTIPLE ZONES

Page 53: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

41

Figure 29 - Outdoor-Indoor Temperature 29th of August – Single thermal zone (Lisbon/Original Model)

Figure 30 - Total Energy Demand 29th of January – Single thermal zone (Lisbon/Original Model)

0

5

10

15

20

25

30

35

40

08

/29

01

:00

:00

08

/29

02

:00

:00

08

/29

03

:00

:00

08

/29

04

:00

:00

08

/29

05

:00

:00

08

/29

06

:00

:00

08

/29

07

:00

:00

08

/29

08

:00

:00

08

/29

09

:00

:00

08

/29

10

:00

:00

08

/29

11

:00

:00

08

/29

12

:00

:00

08

/29

13

:00

:00

08

/29

14

:00

:00

08

/29

15

:00

:00

08

/29

16

:00

:00

08

/29

17

:00

:00

08

/29

18

:00

:00

08

/29

19

:00

:00

08

/29

20

:00

:00

08

/29

21

:00

:00

08

/29

22

:00

:00

08

/29

23

:00

:00

08

/29

24

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR29 August

Outdoor temp Indoor temp SINGLE ZONE Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 29 of August

TOTAL ENERGY SINGLE ZONE TOTAL ENERGY MULTIPLE ZONES

Page 54: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

42

Figure 31 - Outdoor-Indoor Temperature 23-30th of August – Single thermal zone (Lisbon/Original Model)

Figure 32 - Total Energy Demand 23-30th of August – Single thermal zone (Lisbon/Original Model)

0

5

10

15

20

25

30

35

40

08

/23

01

:00

:00

08

/23

07

:00

:00

08

/23

13

:00

:00

08

/23

19

:00

:00

08

/24

01

:00

:00

08

/24

07

:00

:00

08

/24

13

:00

:00

08

/24

19

:00

:00

08

/25

01

:00

:00

08

/25

07

:00

:00

08

/25

13

:00

:00

08

/25

19

:00

:00

08

/26

01

:00

:00

08

/26

07

:00

:00

08

/26

13

:00

:00

08

/26

19

:00

:00

08

/27

01

:00

:00

08

/27

07

:00

:00

08

/27

13

:00

:00

08

/27

19

:00

:00

08

/28

01

:00

:00

08

/28

07

:00

:00

08

/28

13

:00

:00

08

/28

19

:00

:00

08

/29

01

:00

:00

08

/29

07

:00

:00

08

/29

13

:00

:00

08

/29

19

:00

:00

08

/30

01

:00

:00

08

/30

07

:00

:00

08

/30

13

:00

:00

08

/30

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR23-30 of August

Outdoor temp Indoor temp SINGLE ZONE Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

5

12

1

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 23-30 of August

TOTAL ENERGY SINGLE ZONE TOTAL ENERGY MULTIPLE ZONES

Page 55: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

43

3.1.1 Considerations

These results are related to the Configuration 2 (Lisbon / Original model – Single thermal zone) and

they have been compared with the results of Configuration 1 (Lisbon / Original model – Multiple thermal

zones).

The graphs show the indoor and outdoor temperature in the different scenarios over the year but has

been possible to compare only the results about Energy demand of the two configurations because, in

one period, the Configuration 1 with multiple thermal zones provides temperatures of each single room

which should have been compared to only one temperature of the single thermal zone of Configuration

2, that it would not make sense.

Concerning temperatures, it is clearly visible that they are free to float within the range imposed by the

thermostat that, in the period of the day between 09:00 and 19:00, is less strict; the thermostat require

the temperature to be in a smaller range in the period when people occupy the house. (Figure 25)

Therefore, the energy demand relies on the path of the indoor temperature respect the thermostat setpoint

during the day. Comparing the two configurations, the energy consumption are very similar but, even if

the demand of energy of Configuration 1 is lover in some points (Figure 32), it has been decided to

carry on the simulations with the Single thermal zone configuration in order to simplify the calculations

and to be able to compare also the temperatures.

3.2 Configuration 3. LISBON (Renovated Model – Single thermal zone) The original building has been improved designing a retrofit of the envelope changing the stratigraphy

of each component in order to reach the U-value required by the regulation. In this case, I took in

consideration the standards in force for the Italian buildings, especially about renovation of existing

buildings (see section 1.3.4, Table 2).

The main intervention was to add an external coat of XPS of 10 cm in the exterior walls and both to the

pitched roof and plan roof to ensure the building a proper insulation and to lower the loss of heat; the

floor that separates the apartment at the ground floor and the one at the first floor was improved and for

the roofs has been created an efficient envelope that was missing in the original model.

Page 56: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

44

The assumptions were the same of the other configurations like location (weather file), lights, people

occupation, equipment and people’s metabolic activity grouped as “Electric Equipment” producing 4

W/m² during all day.

3.2.1 Envelope and Components

Table 9. Exterior walls stratigraphy (Renovated Building)

Table 10. Interior walls stratigraphy (Renovated Building)

Table 11. Floor stratigraphy (Renovated Building)

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Plaster 2 1900 1046 1,3

Insulation (XPS) 10 29 1300 0,03

Brick 12 760 1000 0,15

Air 6 1,2 0,026

Brick 22 633 790 0,42

Vapor brake

Plaster 2 1900 1046 1,3

0,19

Exterior wall

U-Factor [W/m² K]

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Plaster 2 1900 1046 1,3

Brick 7 818 790 0,37

Plaster 2 1900 1046 1,3

Interior wall

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Concrete 20 2300 1000 2

Insulation (XPS) 10 29 1300 0,03

Acustic panel (rock wool) 3 70 0,037

Vapor brake

Concrete 8 700 1000 1,3

Ceramic floor 1,5 2300 1000 1,3

Floor

Page 57: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

45

Table 12. Ceilings stratigraphy (Renovated Building)

Table 13. Roof stratigraphy (Renovated Building)

Table 14. Plan Roof stratigraphy (Renovated Building)

Table 15. Windows stratigraphy (Renovated Building)

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Wood panel 3 900 820 0,34

Wood panel 12 900 820 0,34

Insulation (Mineral wool) 8 50 1100 0,04

Plasterboard 1 900 820 0,25

0,538

Ceiling

U-Factor [W/m² K]

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Roof tiles 5 907 1000 0,41

Plate 4 900 820 0,025

Waterproof plastic

Insulation (XPS) 10 29 1300 0,03

Vapor brake

Wood panel 3 900 820 0,34

Wood beam 30 608 1630 0,15

0,16U-Factor [W/m² K]

Roof

Layer Depth [cm] Density [kg/m³] Specific heat [J/kg K] Conductivity [W/m K]

Plaster 2 1900 1046 1,3

Lightweight Concrete 15 1280 840 0,53

Waterproof plastic

Insulation (XPS) 10 29 1300 0,03

Vapor brake

Wood panel 3 900 820 0,34

Wood beam 30 608 1630 0,15

0,18

Plan Roof

U-Factor [W/m² K]

Layer Depth [cm] Conductivity [W/m K]

Glass 0,6 0,9

Air 1,2 0,026

Glass 0,4 0,9

U-Factor [W/m² K] 1,32

Window

Page 58: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

46

3.2.2 Indoor temperature and Energy Demand (Comparison between Original building and Renovated Building)

Figure 33 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Lisbon/Renovated Model)

Figure 34 - Total Energy Demand 27th of January – Single thermal zone (Lisbon/Renovated Model)

0

5

10

15

20

25

30

01

/27

01

:00

:00

01

/27

02

:00

:00

01

/27

03

:00

:00

01

/27

04

:00

:00

01

/27

05

:00

:00

01

/27

06

:00

:00

01

/27

07

:00

:00

01

/27

08

:00

:00

01

/27

09

:00

:00

01

/27

10

:00

:00

01

/27

11

:00

:00

01

/27

12

:00

:00

01

/27

13

:00

:00

01

/27

14

:00

:00

01

/27

15

:00

:00

01

/27

16

:00

:00

01

/27

17

:00

:00

01

/27

18

:00

:00

01

/27

19

:00

:00

01

/27

20

:00

:00

01

/27

21

:00

:00

01

/27

22

:00

:00

01

/27

23

:00

:00

01

/27

24

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR27 January

Outdoor temp Indoor temp ONE ZONE Low thermostat

High thermostat Indoor Temp NEW MODEL

0

0,5

1

1,5

2

2,5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY ORIGINAL MODEL TOTAL ENERGY NEW MODEL

Page 59: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

47

Figure 35 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Lisbon/Renovated Model)

Figure 36 - Total Energy Demand 21-28th of January – Single thermal zone (Lisbon/Renovated Model)

0

5

10

15

20

25

30 0

1/2

1 0

1:0

0:0

0 0

1/2

1 0

7:0

0:0

0 0

1/2

1 1

3:0

0:0

0 0

1/2

1 1

9:0

0:0

0 0

1/2

2 0

1:0

0:0

0 0

1/2

2 0

7:0

0:0

0 0

1/2

2 1

3:0

0:0

0 0

1/2

2 1

9:0

0:0

0 0

1/2

3 0

1:0

0:0

0 0

1/2

3 0

7:0

0:0

0 0

1/2

3 1

3:0

0:0

0 0

1/2

3 1

9:0

0:0

0 0

1/2

4 0

1:0

0:0

0 0

1/2

4 0

7:0

0:0

0 0

1/2

4 1

3:0

0:0

0 0

1/2

4 1

9:0

0:0

0 0

1/2

5 0

1:0

0:0

0 0

1/2

5 0

7:0

0:0

0 0

1/2

5 1

3:0

0:0

0 0

1/2

5 1

9:0

0:0

0 0

1/2

6 0

1:0

0:0

0 0

1/2

6 0

7:0

0:0

0 0

1/2

6 1

3:0

0:0

0 0

1/2

6 1

9:0

0:0

0 0

1/2

7 0

1:0

0:0

0 0

1/2

7 0

7:0

0:0

0 0

1/2

7 1

3:0

0:0

0 0

1/2

7 1

9:0

0:0

0 0

1/2

8 0

1:0

0:0

0 0

1/2

8 0

7:0

0:0

0 0

1/2

8 1

3:0

0:0

0 0

1/2

8 1

9:0

0:0

0

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR21-28 of January

Outdoor temp Indoor temp ONE ZONE Low thermostat

High thermostat Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

51

21

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 21-28 of January

TOTAL ENERGY ORIGINAL MODEL TOTAL ENERGY NEW MODEL

Page 60: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

48

Figure 37 - Outdoor-Indoor Temperature 29th of August – Single thermal zone (Lisbon/Renovated Model)

Figure 38 - Total Energy Demand 29th of August – Single thermal zone (Lisbon/Renovated Model)

0

5

10

15

20

25

30

35

40

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR29 August

Outdoor temp Indoor temp ONE ZONE Low thermostat

High thermostat Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

3

3,5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 29 of August

TOTAL ENERGY ORIGINAL MODEL TOTAL ENERGY NEW MODEL

Page 61: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

49

Figure 39- Outdoor-Indoor Temperature 23-30th of August – Single thermal zone (Lisbon/Renovated Model)

Figure 40 - Total Energy Demand 23-30th of August – Single thermal zone (Lisbon/Renovated Model)

0

5

10

15

20

25

30

35

40 0

8/2

3 0

1:0

0:0

0

08

/23

07

:00

:00

08

/23

13

:00

:00

08

/23

19

:00

:00

08

/24

01

:00

:00

08

/24

07

:00

:00

08

/24

13

:00

:00

08

/24

19

:00

:00

08

/25

01

:00

:00

08

/25

07

:00

:00

08

/25

13

:00

:00

08

/25

19

:00

:00

08

/26

01

:00

:00

08

/26

07

:00

:00

08

/26

13

:00

:00

08

/26

19

:00

:00

08

/27

01

:00

:00

08

/27

07

:00

:00

08

/27

13

:00

:00

08

/27

19

:00

:00

08

/28

01

:00

:00

08

/28

07

:00

:00

08

/28

13

:00

:00

08

/28

19

:00

:00

08

/29

01

:00

:00

08

/29

07

:00

:00

08

/29

13

:00

:00

08

/29

19

:00

:00

08

/30

01

:00

:00

08

/30

07

:00

:00

08

/30

13

:00

:00

08

/30

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR23-30 of August

Outdoor temp Indoor temp ONE ZONE Low thermostat

High thermostat Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

3

3,5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

5

12

1

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 23-30 of August

TOTAL ENERGY ORIGINAL MODEL TOTAL ENERGY NEW MODEL

Page 62: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

50

3.2.3 Considerations

These results are related to the Configuration 3 (Lisbon / Renovated model – Single thermal zone) and

they have been compared with the results of Configuration 2 (Lisbon / Original model – Single thermal

zone); the graphs compare both indoor and outdoor temperatures and energy demand over the year in

the different periods analysed.

In January, configuration 3 (Renovated model) provides indoor temperature levels much greater than

the indoor temperatures of Configuration 2 (Original model) and consequently the energy demand for

heating is lower; in fact, in Configuration 2 the values stand between 1-2.4 kWh while after retrofit they

stand between 0.2-0.6 kWh. (Figure 36)

In August instead, the indoor temperatures of the two configurations are very similar but, due to the

increased thermal mass of the renovated building, the heat loss are lower, and the heat stored tends to

stay inside; that’s why in some points the energy demand for cooling is higher in the new model instead

of the old model. (Figure 40)

Table 16. Energy accounts of the building in a year (Lisbon)

Looking at the energy accounts in both periods of the year it is clear that in the warm period, which is

the period when energy is used for cooling, the renovation did not lead to an higher efficiency but, on

the other hand, in the cold period the percentage of savings is around 67% making the building energy-

efficient with an energy demand of about 19 kWh/m2.

TOT OLD [kWh] TOT NEW [kWh]

2573,96 833,32

DIFFERENCE 1740,65

% SAVINGS 67,6%

COLD PERIOD

TOT OLD [kWh] TOT NEW [kWh]

288,71 352,33

DIFFERENCE -63,62

% SAVINGS -22,0%

WARM PERIOD

TOTAL ENERGY [kWh] 1185,64

AREA [m²] 63,17

ENERGY [kWh/m²] 18,77

Page 63: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

51

3.2.4 Photovoltaic system

Part of the retrofit was also the installation of a photovoltaic system on two surfaces: the plan roof above

the kitchen and the clove of pitched roof heading the south direction.

Once given the surfaces where to install the PV system, EnergyPlus calculated automatically the area

and the generated power according to the weather file and location.

Figure 41 - PV energy production 27th of January (Lisbon/Renovated Model)

Table 17. PV energy production 27th of January (Lisbon/Renovated Model)

0

0,1

0,2

0,3

0,4

0,5

0,6

0,7

0,8

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

Energy Demand [kWh] Energy Produced [kW]

6,91 3,57

27th of January

Page 64: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

52

Figure 42 - PV energy production 29th of August (Lisbon/Renovated Model)

Table 18. PV energy production 29th of August (Lisbon/Renovated Model)

Table 19. PV energy production All year (Lisbon/Renovated Model)

The energy produced over the year from the PV system is very much higher than the energy demand of

the building but, as shown by the graphs (Figure 41,42), the energy produced can cover only a little part

of the energy demand during the day. Indeed, being a building of residential use, people is not at home

when the production of energy reaches the peak and when people occupy the house, the production is,

low in the morning and zero from 18-19 pm.

0

1

2

3

4

5

6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 29 of August

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

Energy Demand [kWh] Energy Produced [kW]

6,92 35,99

29th of August

Energy Demand [kWh] Energy Produced [kW]

1185,64 13298,98

All the year

Page 65: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

53

3.3 Configuration 4. TURIN (Original Model – Single thermal zone) / Indoor temperature and Energy Demand Input data: same assumptions of Configuration 2; only a Single thermal zone; weather file: Turin

Location: Turin

Latitude: 45.07 deg

Longitude : 7.68 deg

Elevation: 239 m

Figure 43 - Outdoor-Indoor Temperature All year – Single thermal zone (Turin/Original Model)

Figure 44 - Total Energy Demand – Single thermal zone (Turin/Original Model)

-10-505

101520253035

01

/01

01

:00

:00

01

/13

05

:00

:00

01

/25

09

:00

:00

02

/06

13

:00

:00

02

/18

17

:00

:00

03

/02

21

:00

:00

03

/15

01

:00

:00

03

/27

05

:00

:00

04

/08

09

:00

:00

04

/20

13

:00

:00

05

/02

17

:00

:00

05

/14

21

:00

:00

05

/27

01

:00

:00

06

/08

05

:00

:00

06

/20

09

:00

:00

07

/02

13

:00

:00

07

/14

17

:00

:00

07

/26

21

:00

:00

08

/08

01

:00

:00

08

/20

05

:00

:00

09

/01

09

:00

:00

09

/13

13

:00

:00

09

/25

17

:00

:00

10

/07

21

:00

:00

10

/20

01

:00

:00

11

/01

05

:00

:00

11

/13

09

:00

:00

11

/25

13

:00

:00

12

/07

17

:00

:00

12

/19

21

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature 1 year INDOOR-OUTDOOR

OUTDOOR TEMP INDOOR TEMP

0

1

2

3

4

5

0 1000 2000 3000 4000 5000 6000 7000 8000

Ener

gy [

kWh

]

Time [h]

TOTAL ENERGY DEMAND - ALL THE YEAR

HEATING ENERGY COOLING ENERGY

Page 66: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

54

Figure 45 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Turin/Original Model)

Figure 46 - Total Energy Demand 27th of January – Single thermal zone (Turin/Original Model)

-10-505

1015202530

01

/27

01

:00

:00

01

/27

02

:00

:00

01

/27

03

:00

:00

01

/27

04

:00

:00

01

/27

05

:00

:00

01

/27

06

:00

:00

01

/27

07

:00

:00

01

/27

08

:00

:00

01

/27

09

:00

:00

01

/27

10

:00

:00

01

/27

11

:00

:00

01

/27

12

:00

:00

01

/27

13

:00

:00

01

/27

14

:00

:00

01

/27

15

:00

:00

01

/27

16

:00

:00

01

/27

17

:00

:00

01

/27

18

:00

:00

01

/27

19

:00

:00

01

/27

20

:00

:00

01

/27

21

:00

:00

01

/27

22

:00

:00

01

/27

23

:00

:00

01

/27

24

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR27 January

Outdoor temp Indoor temp ORIGINAL MODEL

Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY

Page 67: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

55

Figure 47 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Turin/Original Model)

Figure 48 -Total Energy Demand 21-28th of January – Single thermal zone (Turin/Original Model)

-10

-5

0

5

10

15

20

25

30

01

/21

01

:00

:00

01

/21

07

:00

:00

01

/21

13

:00

:00

01

/21

19

:00

:00

01

/22

01

:00

:00

01

/22

07

:00

:00

01

/22

13

:00

:00

01

/22

19

:00

:00

01

/23

01

:00

:00

01

/23

07

:00

:00

01

/23

13

:00

:00

01

/23

19

:00

:00

01

/24

01

:00

:00

01

/24

07

:00

:00

01

/24

13

:00

:00

01

/24

19

:00

:00

01

/25

01

:00

:00

01

/25

07

:00

:00

01

/25

13

:00

:00

01

/25

19

:00

:00

01

/26

01

:00

:00

01

/26

07

:00

:00

01

/26

13

:00

:00

01

/26

19

:00

:00

01

/27

01

:00

:00

01

/27

07

:00

:00

01

/27

13

:00

:00

01

/27

19

:00

:00

01

/28

01

:00

:00

01

/28

07

:00

:00

01

/28

13

:00

:00

01

/28

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR21-28 of January

Outdoor temp Indoor temp ORIGINAL MODEL Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 71

31

92

53

13

74

34

95

56

16

77

37

98

59

19

71

03

10

91

15

12

11

27

13

31

39

14

51

51

15

71

63

16

91

75

18

11

87

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 21-28 of January

TOTAL ENERGY

Page 68: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

56

Figure 49 - Outdoor-Indoor Temperature 3rd of August – Single thermal zone (Turin/Original Model)

Figure 50 - Total Energy Demand 3rd of August – Single thermal zone (Turin/Original Model)

0

5

10

15

20

25

30

35

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR3 August

Outdoor temp Indoor temp ORIGINAL MODEL Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3 of August

TOTAL ENERGY

Page 69: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

57

Figure 51 - Outdoor-Indoor Temperature 3-10th of August – Single thermal zone (Turin/Original Model)

Figure 52 - Total Energy Demand 3-10th of August – Single thermal zone (Turin/Original Model)

0

5

10

15

20

25

30

35

08

/03

01

:00

:00

08

/03

07

:00

:00

08

/03

13

:00

:00

08

/03

19

:00

:00

08

/04

01

:00

:00

08

/04

07

:00

:00

08

/04

13

:00

:00

08

/04

19

:00

:00

08

/05

01

:00

:00

08

/05

07

:00

:00

08

/05

13

:00

:00

08

/05

19

:00

:00

08

/06

01

:00

:00

08

/06

07

:00

:00

08

/06

13

:00

:00

08

/06

19

:00

:00

08

/07

01

:00

:00

08

/07

07

:00

:00

08

/07

13

:00

:00

08

/07

19

:00

:00

08

/08

01

:00

:00

08

/08

07

:00

:00

08

/08

13

:00

:00

08

/08

19

:00

:00

08

/09

01

:00

:00

08

/09

07

:00

:00

08

/09

13

:00

:00

08

/09

19

:00

:00

08

/10

01

:00

:00

08

/10

07

:00

:00

08

/10

13

:00

:00

08

/10

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR3-10 of August

Outdoor temp Indoor temp ORIGINAL MODEL Low thermostat High thermostat

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

5

12

1

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3-10 of August

TOTAL ENERGY

Page 70: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

58

3.3.1 Considerations

These results are related to the Configuration 4 (Turin / Original model – Single thermal zone) and they

have been obtained running a simulation through EnergyPlus using the same assumptions and

components’ stratigraphy of Configuration 2 (Lisbon / Original model – Single thermal zone) but with

a different weather file (Turin).

As we can see in (Figure 43), during cold periods of the year, in Turin the temperature goes down to

values minus zero comparing to Lisbon where the temperature never goes under zero level; exterior

temperature combined with a not adequate envelope of the building make the energy demand higher in

order to maintain the indoor temperature within the setpoint range imposed by the thermostat.

Therefore, in January, configuration 4 (Turin/Original model) provides indoor temperature levels worse

than the indoor temperatures of configuration 2 (Lisbon / Original model) and consequently the energy

demand for heating is lower; in fact, in configuration 2 the values stand between 1-2.4 kWh while in

configuration 4 the values stand between 2.3-3.9 kWh. (Figure 48)

In August instead, the indoor temperatures of the two configurations are similar but, due to the higher

temperature of Italy, the energy demand reaches peaks up to 3.9 kWh while in Lisbon up to 3.1 kWh.

(Figure 52)

The results of Energy demand are expressed in the form of Total energy, that means heating and cooling

energy in the period considered.

3.4 Configuration 5. TURIN (Renovated Model – Single thermal zone) Input data: same assumptions of Configuration 3 (lights, people occupation, equipment and people’s

metabolic activity grouped as “Electric Equipment” producing 4 W/m² during all day); only a Single

thermal zone; weather file: Turin

The original building has been improved designing a retrofit of the envelope changing the stratigraphy

of each component (see section 3.2.1) in order to reach the U-value required by the regulation. The

standards taken in consideration are those in force for the Italian buildings, especially about renovation

of existing buildings (see section 1.3.4, Table 5).

Page 71: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

59

3.4.1 Indoor temperature and Energy Demand (Comparison between Original building and Renovated Building)

Figure 53 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Turin/Renovated Model)

Figure 54 - Total Energy Demand 27th of January – Single thermal zone (Turin/Renovated Model)

-10-505

1015202530

01

/27

01

:00

:00

01

/27

02

:00

:00

01

/27

03

:00

:00

01

/27

04

:00

:00

01

/27

05

:00

:00

01

/27

06

:00

:00

01

/27

07

:00

:00

01

/27

08

:00

:00

01

/27

09

:00

:00

01

/27

10

:00

:00

01

/27

11

:00

:00

01

/27

12

:00

:00

01

/27

13

:00

:00

01

/27

14

:00

:00

01

/27

15

:00

:00

01

/27

16

:00

:00

01

/27

17

:00

:00

01

/27

18

:00

:00

01

/27

19

:00

:00

01

/27

20

:00

:00

01

/27

21

:00

:00

01

/27

22

:00

:00

01

/27

23

:00

:00

01

/27

24

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR27 January

Outdoor temp Indoor temp NEW MODEL

Low thermostat High thermostat

Indoor temp ORIGINAL MODEL

0

0,5

1

1,5

2

2,5

3

3,5

4

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

ORIGINAL MODEL NEW MODEL

Page 72: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

60

Figure 55 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Turin/Renovated Model)

Figure 56 - Total Energy Demand 21-28th of January – Single thermal zone (Turin/Renovated Model)

-10

-5

0

5

10

15

20

25

30

01

/21

01

:00

:00

01

/21

07

:00

:00

01

/21

13

:00

:00

01

/21

19

:00

:00

01

/22

01

:00

:00

01

/22

07

:00

:00

01

/22

13

:00

:00

01

/22

19

:00

:00

01

/23

01

:00

:00

01

/23

07

:00

:00

01

/23

13

:00

:00

01

/23

19

:00

:00

01

/24

01

:00

:00

01

/24

07

:00

:00

01

/24

13

:00

:00

01

/24

19

:00

:00

01

/25

01

:00

:00

01

/25

07

:00

:00

01

/25

13

:00

:00

01

/25

19

:00

:00

01

/26

01

:00

:00

01

/26

07

:00

:00

01

/26

13

:00

:00

01

/26

19

:00

:00

01

/27

01

:00

:00

01

/27

07

:00

:00

01

/27

13

:00

:00

01

/27

19

:00

:00

01

/28

01

:00

:00

01

/28

07

:00

:00

01

/28

13

:00

:00

01

/28

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR21-28 of January

Outdoor temp Indoor temp ORIGINAL MODEL

Low thermostat High thermostat

Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

1 71

31

92

53

13

74

34

95

56

16

77

37

98

59

19

71

03

10

91

15

12

11

27

13

31

39

14

51

51

15

71

63

16

91

75

18

11

87

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 21-28 of January

ORIGINAL MODEL NEW MODEL

Page 73: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

61

Figure 57 - Outdoor-Indoor Temperature 3rd of August – Single thermal zone (Turin/Renovated Model)

Figure 58 - Total Energy Demand 3rd of August – Single thermal zone (Turin/Renovated Model)

0

5

10

15

20

25

30

35

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR3 August

Outdoor temp Indoor temp ORIGINAL MODEL

Low thermostat High thermostat

Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3 of August

ORIGINAL MODEL NEW MODEL

Page 74: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

62

Figure 59 - Outdoor-Indoor Temperature 3-10th of August – Single thermal zone (Turin/Renovated Model)

Figure 60 - Total Energy Demand 3-10th of August – Single thermal zone (Turin/Renovated Model)

0

5

10

15

20

25

30

35 0

8/0

3 0

1:0

0:0

0

08

/03

07

:00

:00

08

/03

13

:00

:00

08

/03

19

:00

:00

08

/04

01

:00

:00

08

/04

07

:00

:00

08

/04

13

:00

:00

08

/04

19

:00

:00

08

/05

01

:00

:00

08

/05

07

:00

:00

08

/05

13

:00

:00

08

/05

19

:00

:00

08

/06

01

:00

:00

08

/06

07

:00

:00

08

/06

13

:00

:00

08

/06

19

:00

:00

08

/07

01

:00

:00

08

/07

07

:00

:00

08

/07

13

:00

:00

08

/07

19

:00

:00

08

/08

01

:00

:00

08

/08

07

:00

:00

08

/08

13

:00

:00

08

/08

19

:00

:00

08

/09

01

:00

:00

08

/09

07

:00

:00

08

/09

13

:00

:00

08

/09

19

:00

:00

08

/10

01

:00

:00

08

/10

07

:00

:00

08

/10

13

:00

:00

08

/10

19

:00

:00

Tem

per

atu

re [

°C]

Time [h]

Temperature INDOOR-OUTDOOR3-10 of August

Outdoor temp Indoor temp ORIGINAL MODEL Low thermostat

High thermostat Indoor temp NEW MODEL

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

1 7

13

19

25

31

37

43

49

55

61

67

73

79

85

91

97

10

3

10

9

11

5

12

1

12

7

13

3

13

9

14

5

15

1

15

7

16

3

16

9

17

5

18

1

18

7

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3-10 of August

ORIGINAL MODEL NEW MODEL

Page 75: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

63

3.4.2 Considerations

These results are related to the Configuration 5 (Turin / Renovated model – Single thermal zone) and

they have been compared with the results of Configuration 4 (Turin / Original model – Single thermal

zone); the graphs compare both indoor and outdoor temperatures and energy demand over the year in

the different periods analysed.

In January, configuration 5 (Renovated model) provides indoor temperature levels much greater than

the indoor temperatures of Configuration 4 (Original model) because of the improved stratigraphy and

consequently the energy demand for heating is lower; in fact, in Configuration 4 the values stand

between 2.3-3.9 kWh while after retrofit they stand between 0.9-1.3 kWh. (Figure 56)

In August instead, the indoor temperatures of the two configurations are still very similar but, due to the

increased thermal mass of the renovated building, the heat loss are lower, and the heat stored tends to

stay inside; that’s why in some points the indoor temperature of the new Configuration is higher and the

energy demand for cooling is higher as well. Generally, the peaks of energy demand have been lowered

from the maximum of 3.9 kWh to 2.9 kWh. (Figure 60)

Table 20. Energy accounts of the building in a year (Turin)

Looking at the energy accounts in both periods of the year it is clear that in the warm period, which is

the period when energy is used for cooling, even if less than in the cold period, the renovation led to an

higher efficiency respectively of 23.5% and 59.5%, making the building energy-efficient with an energy

demand of about 48 kWh/m2.

TOT OLD [kWh] TOT NEW [kWh]

6319,47 2562,25

DIFFERENCE 3757,21

% SAVINGS 59,5%

COLD PERIOD

TOT OLD [kWh] TOT NEW [kWh]

611,83 468,18

DIFFERENCE 143,66

% SAVINGS 23,5%

WARM PERIOD

TOTAL ENERGY [kWh] 3030,43

AREA [m²] 63,17

ENERGY [kWh/m²] 47,97

Page 76: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

64

3.4.3 Photovoltaic system

As for Configuration 3, on the building has been installed a photovoltaic system on two surfaces: the

plan roof above the kitchen and the clove of pitched roof heading the south direction.

Once given the surfaces where to install the PV system, EnergyPlus calculated automatically the area

and the generated power according to the weather file and location.

Figure 61 - PV energy production and Energy demand on 27th of January (Turin/Renovated Model)

Table 21. PV energy production and Energy demand on 27th of January (Turin/Renovated Model)

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

NEW MODEL

Energy Demand [kWh] 17,76

PV Energy Produced [kW] 20,03

PV Energy Used [kW] 0,34

Real Energy Demand [kWh] 17,42

27th of January

Page 77: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

65

Figure 62 - PV energy production and Energy demand on 3rd of August (Turin/Renovated Model)

Table 22. PV energy production and Energy demand on 3rd of August (Turin/Renovated Model)

Table 23. PV energy production and Energy demand on All year (Turin/Renovated Model)

The energy produced over the year from the PV system is more than two times the energy demand of

the building but, as shown by the graphs (Figure 61,62), the energy produced can cover only a little part

of the energy demand during the day. Indeed, being a building of residential use, people is not at home

when the production of energy reaches the peak and when people occupy the house, the production is,

low in the morning and zero from 18-19 pm. Energy flexibility can be used to improve the energy

management during the day.

0

1

2

3

4

5

6

7

8

9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3 of August

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

NEW MODEL

Energy Demand [kWh] 13,57

Energy Produced [kW] 54,28

PV Energy Used [kW] 4,00

Real Energy Demand [kWh] 9,57

3rd of August

Energy Demand [kWh] Energy Produced [kW]

3030,43 7091,56

All the year

Page 78: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

66

3.5 ENERGY FLEXIBILITY

Flexibility in the building sector means to manage and control the energy loads according to the

requirements of the surrounding electric grids. Concerning heating flexibility, this implies to heat-up the

building in the period of the day when there is surplus of solar or wind energy available or energy

produced by renewable sources decreasing heating power at other times.

Mostly during cold periods, in residential buildings can be used a control system to lower the peaks of

energy demand reducing the reliance on heating grids. 29 “The energy flexibility of heating systems

depends on the ability of a building to retain or store the heat inside the building envelope concerning

comfort requirements. The amount of insulation, the thermal capacity and the passive solar gains of

buildings are crucial for keeping indoor thermal comfort” 30 31 32

Generally talking about flexibility, two approaches are typically used to stray the electricity

consumptions of a building from the normal schedule: thermal energy storage and appliance operation

shifting.

The first approach is generally used to anticipate the energy consumption of a determined electrical

equipment (i.e. air-conditioner, electrical water tank or heat pumps), in accordance with the thermal

properties of the device and the properties of the building (i.e. thermal mass, insulation and sun

exposition), to reduce the consumption of electricity on later times.

The second approach shifts the electricity demand of some electrical devices (e.g. washing machines,

clothes dryers, and dishwashers) through a control system, to the periods of the day when the price of

electricity is lower or in the periods in which the energy demand can be covered by energy generated by

renewable energy sources. 33 Another approach for Energy flexibility is to store the energy produced

into batteries that allow to use the energy produced in the periods of the day when the building needs;

29 I. Cardinaels W, Borremans. (2014). “Demand response for families – linear final report,” EnergyVille 30 V. B. J. Six D., Desmedt J., Vanhoudt D. (2011). “Exploring the flexibility potential of residential heat pumps combined with thermal energy storage for smart grids,” Explor. Flex. potential Resid. heat pumps Comb. with

Therm. energy storage smart grids. Distrib. 31 J. Le Dréau and P. Heiselberg. (2016). “Energy flexibility of residential buildings using short term heat storage in the thermal mass” 32 T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of building design on energy flexibility” 33 Rui Amaral Lopes, Adriana Chambel, João Neves, Daniel Aelenei, João Martins. (2016). “A literature review

of methodologies used to assess the energy flexibility of buildings”

Page 79: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

67

the weakness of these batteries is that their capacity is not enough big to contain all the energy produced

and often the cost-effectiveness is not recommended. If only the batteries could store the whole amount

of energy produced every day, they would be a great tool for covering the energy demand.

Heating energy flexibility can be defined as “thermal load shifting” that indicated the number of hours

the energy system can be delayed or forced to operate in an established period, taking into account the

indoor comfort temperature range. For instance, when space heating is switched off at the upper comfort

limit of temperature, the indoor temperature stay within the comfort zone for a period of time according

to the building insulation, ventilation and thermal mass. As the thermal energy inside the building

envelope is fading, the indoor temperature goes down. ΔT indicates the time it takes for the thermal

zone to float from the upper comfort limit to the temperature of 19 °C (lower comfort limit) after the

heating system is turned off. 34

Figure 63 – Demand-side control of set temperatures, representation of the cooling-down curve and heating-up time (Source: T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of

building design on energy flexibility”)

34 T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of building design on energy flexibility”

Page 80: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

68

3.5.1 Configuration 6. TURIN (Renovated Model – Energy Flexibility) / Energy Production and Energy Demand

The thermostat sets the set-point temperatures in the different periods of the day and they are stricter

when people occupy the house and less when people don’t (09:00 – 18:00); also, the set-point

temperatures are different in accordance to the seasons of the year.

Based on the occupation of the house, how shown previously in (Figure 13), the thermostat requires the

heating or cooling system to work and to set the indoor temperature in order to have an indoor comfort

in the hours when people are at home; when people don’t occupy the house the temperature is free to

float within the range imposed by the thermostat that is wider.

(Table 30) shows the temperature relative to the hours of the day of the original configuration on the

27th of January and (Figure 64) the corresponding energy demand for heating the thermal zone during

the day, having into consideration these set-point temperatures before people come back home at 19:00.

On 27th of January, the thermostat allows the temperature to drop to 15 °C when the house is empty until

18:00 and requires to reach 20 °C at 19:00 when people come back home; the peak of energy demand

between 18-19:00 is related to the fact that in 1 hour the heating system must cover a ΔT of 5 °C to have

an indoor temperature comfort.

The problem is that the peak of energy demand stands in the hours when the production of energy from

the Photovoltaic system is zero, and, in the event that there is not a battery for energy storage, the energy

produced would be wasted or sold to the electric grid. (Figure 64)

Table 24. Thermostat Lower set-point temperature on 27th of January (Original configuration)

Time [h]Thermostat

Lower level [°C]

09:00 15 °C

10:00 15 °C

11:00 15 °C

12:00 15 °C

13:00 15 °C

14:00 15 °C

15:00 15 °C

16:00 15 °C

17:00 15 °C

18:00 15 °C

19:00 20 °C

27th of January

ORIGINAL

Page 81: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

69

Figure 64 - PV energy production and Energy demand on 27th of January (Turin/Renovated Model)

In Configuration 6 the aim is to heat-up the house from 09:00 (Table 31) even if the house is not occupied

but taking advantage of the excess of solar energy generated by the photovoltaic system and the thermal

mass of the building; in this way from 09:00 -18:00 the house is warm and the energy demand is totally

covered by the generation of energy on-site and at 18:00 the house has already reached the temperature

of 20 °C and the peak will be lower. (Figure 65)

Table 25. Thermostat Lower set-point temperature on 27th of January (Energy Flexibility configuration)

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 27 of January

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

Time [h]Thermostat

Lower level [°C]

09:00 18 °C

10:00 21 °C

11:00 22 °C

12:00 23 °C

13:00 23 °C

14:00 23 °C

15:00 23 °C

16:00 23 °C

17:00 21 °C

18:00 20 °C

19:00 20 °C

27th of January

FLEXIBILITY

Page 82: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

70

Figure 65 - PV energy production and New Energy demand on 27th of January (Turin/Renovated Model)

Table 26. Energy demand on 27th of January (Before and after shifting loads)

Even if the energy demand of the building is actually quite far from the Zero, the Flexibility has led to

a significant decrease of the demand, using the energy generated onsite by the photovoltaic system.

Indeed, with the new Configuration, shifting the loads from 18:00 to 09:00 it has been possible to save

4.4 kWh on day 27th of January. (Table 32)

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND (FLEXIBILITY) - 27 of January

FLEXIBILITY NEW MODEL PV ENERGY PRODUCTION

NEW MODEL SHIFTING LOADS

Energy Demand [kWh] 17,76 25,17

PV Energy Produced [kW] 20,03 20,03

PV Energy Used [kW] 0,34 12,18

Real Energy Demand [kWh] 17,42 12,99

27th of January

Page 83: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

71

Concerning the Summer period, (Table 33) shows the temperature relative to the hours of the day of the

original configuration on the 3rd of August and (Figure 66) the corresponding energy demand for

cooling the thermal zone during the day, having into consideration these set-point temperatures before

people come back home at 19:00.

On the 3rd of August, the thermostat allows the temperature to raise to 30 °C when the house is empty

until 18:00 and requires to reach 26 °C at 19:00 when people come back home; the peak of energy

demand between 18-19:00 is related to the fact that in 1 hour the heating system must cover a ΔT of 4

°C to have an indoor temperature comfort.

Table 27. Thermostat Upper set-point temperature on 3rd of August (Original configuration)

Figure 66 - PV energy production and Energy demand on 3rd of August (Turin/Renovated Model)

Time [h]Thermostat

Upper level [°C]

09:00 30 °C

10:00 30 °C

11:00 30 °C

12:00 30 °C

13:00 30 °C

14:00 30 °C

15:00 30 °C

16:00 30 °C

17:00 30 °C

18:00 30 °C

19:00 26 °C

3rd of August

ORIGINAL

0

1

2

3

4

5

6

7

8

9

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND - 3 of August

TOTAL ENERGY NEW MODEL PV ENERGY PRODUCTION

Page 84: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

72

As for the Winter period, the aim is to cool-down the house from 09:00 am (Table 34) even if the house

is not occupied but taking advantage of the excess of solar energy generated by the photovoltaic system

and the thermal mass of the building; in this way from 09:00-18:00 the house is cool and the energy

demand is totally covered by the generation of energy on-site and at 18:00 the house has already reached

the temperature of 25 °C and the peak of energy to reach 26 °C will be lower. (Figure 67)

Table 28. Thermostat Upper set-point temperature on 3rd of August (Energy Flexibility configuration)

Figure 67 - PV energy production and New Energy demand on 3rd of August (Turin/Renovated Model)

Time [h]Thermostat

Upper level [°C]

09:00 25 °C

10:00 24 °C

11:00 24 °C

12:00 24 °C

13:00 24 °C

14:00 24 °C

15:00 24 °C

16:00 23 °C

17:00 24 °C

18:00 25 °C

19:00 26 °C

3rd of August

FLEXIBILITY

0

1

2

3

4

5

6

7

8

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Ener

gy [

kWh

]

Time [h]

ENERGY DEMAND (FLEXIBILITY) - 3 of August

FLEXIBILITY NEW MODEL PV ENERGY PRODUCTION

Page 85: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

73

Table 29. Energy demand on 3rd of August (Before and after shifting loads)

Compared these results to the Winter period of the same Configuration, the energy savings after

Flexibility are greater, in fact, anticipating the loads for cooling from 18:00 to 09:00, the part of the

energy demand has been covered by the production of energy obtained by PV system and the peak has

been lowered; the savings in this case amount to 8.2 kWh on day 3rd of August, and the energy demand

is nearly zero.

NEW MODEL SHIFTING LOADS

Energy Demand [kWh] 13,57 25,08

Energy Produced [kW] 54,28 54,28

PV Energy Used [kW] 4,00 23,74

Real Energy Demand [kWh] 9,57 1,34

3rd of August

Page 86: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

74

Page 87: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

75

CONCLUSIONS

The existing building stock across Europe is aged, not efficient and not appropriate to face this wave of

big climate changes. The world and especially EU are moving towards a green Architecture focusing on

NZEBs, setting standards and regulations for new building and renovation of existing building.

The increased awareness and the visible effects of the climate change are pushing the Member States to

develop and embrace the standards set by EU in order to decrease the energy consumptions, the carbon

footprint and to increase renewable energy production and its manage.

The progress of materials and the lowering prices for renewable technologies make the uptake of

NZEBs in the building sector easier and often, incentives are given by governments for installing

photovoltaic panels, highly efficient heat pumps, a greater insulation or windows in order to reduce the

cost of the construction of a NZEB.

This study provides an example of retrofit of an existing building towards NZEB requirements, starting

from the evaluation of the energy demand relative to the original configuration of the building,

presenting then a renovation of the envelope and the related energy consumptions, and finally the

calculation of the amount of energy generated by Photovoltaic panels installed on the roof and how that

energy could be managed during the days.

The case study building energy performance was so poor that the roof didn’t even have a real package

but after the designed renovation the energy performance improved until having an high-efficiency

building; the results show that the energy demand of the new configuration is very low but still far from

the NZEB definition.

Therefore, despite being the energy produced through renewable sources higher than the energy demand,

given that the building is for residential use, most of the energy generated everyday cannot be used

entirely because in the hours of excess solar energy, people don’t occupy the house, and the energy risks

to be wasted; that’s why through Energy Flexibility has been tried to shift the loads in the hours of

energy generation trying to lower the energy demand in other times.

Final results show that the energy savings after flexibility are less than expected and an explanation for

this is that, in order to simplify the calculations, the assumptions given don’t take into account the real

usage of the house and occupation; for instance, one of the assumption was that “people, lights and

equipments” were grouped into a single voice consuming 4 W/m2 during all day and the energy demand

Page 88: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

76

could be lowered considering the real consumption of the equipments during the occupation of the

house.

This study integrates the existing literature about the topic and focuses on the retrofit of the envelope

and each component in order to have a NZEB without considering the cost-effectiveness of the

renovation though; each building needs different types of renovation and the selection of materials is

wide but knowledge and commitment are essential for a proper design.

Page 89: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

77

Bibliography

1. A.J. Marszal, P. Heiselberg, J.S. Bourrelle, E. Musall, K. Voss, I. Sartori, A. Napolitano, “Zero

Energy Building – A review of definitions and calculation methodologies”, 2010

2. D. D’Agostino, C. Marino, F. Minichiello, F. Russo, “Obtaining a NZEB in Mediterranean

climate by using only on-site renewable energy: is it a realistic goal?”, 2017

3. B. Atanasiu, T. Boermans, K.E. Thomsen, J. Rose, S. Aggerholm, A. Hermelink,M. Offermann,

“Principles for Nearly Zero Energy Buildings”, 2011

4. S. Attia, P. Eleftheriou, F. Xeni, M. Rodolphe, C. Mènèzo, V. Kostopoulos, L. Pagliano, M.

Cellura, M.G. Almeida, M.A. Ferreira, T. Baracu, V. Badescu, R.G. Crutescu, J.M. Hidalgo

Betanzos, ”Overview and future challenges of nearly Zero Energy Buildings (nZEB) design in

Southern Europe”, 2017

5. C.A. Santos Silva, C. Sousa Monteiro, D. Aelenei, F. Costa, H. Gonçalves, J. Martins, L.

Aelenei, N. Madjalani, R.A. Lopes, T. Simoes. (2018). “FIRST - Mapping flexibility of urban

energy systems”

6. U.S. Department of Energy. “EnergyPlus Version 8.9.0 Documentation- Getting Started”

7. V. B. J. Six D., Desmedt J., Vanhoudt D., “Exploring the flexibility potential of residential heat

pumps combined with thermal energy storage for smart grids,” Explor. Flex. potential Resid.

heat pumps Comb. with Therm. energy storage smart grids. Distrib., no. 21st International

conference on electricity distribution, p. 0442–0442., 2011.

8. J. Le Dréau and P. Heiselberg, “Energy flexibility of residential buildings using short term heat

storage in the thermal mass,” Energy, vol. 111, pp. 991–1002, 2016.

9. H. Shaftel, R. Jackson, S. Callery, D. Bailey, “Climate Change: How do we know?”, 2019

10. H. Shaftel, R. Jackson, S. Callery, D. Bailey, “Climate Change: How do we know?”, 2019

11. The IPBES Media Team, “Media release: Worsening worldwide land degradation now critical,

undermining well-being of 3.2 billion people”, 2018

12. The IPBES Media Team, “Media release: Worsening worldwide land degradation now critical,

undermining well-being of 3.2 billion people”, 2018

13. R. Van Staden, University of Cambridge, “The Physical Science of Climate Change”, 2014

14. The IPCC’s Fifth Assessment Report, C. Symon, “Climate change: Actions, trends and

implications for business”, 2013

15. C. Bipat, “How Buildings Produce Carbon Emissions... And How to Stop Them”, 2019

16. Paul Torcellini, Shanti Pless, Michael Deru National Renewable Energy Laboratory; Drury

Crawley, U.S. Department of Energy. National Renewable Energy Laboratory report, "Zero

Page 90: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

78

Energy Buildings: A Critical Look at the Definition”, 2006"

17. US Department of Energy, "A Common Definition for Zero Energy Buildings", 2015.

18. Baden, S., et al., "Hurdling Financial Barriers to Lower Energy Buildings: Experiences from

the USA and Europe on Financial Incentives and Monetizing Building Energy Savings in

Private Investment Decisions." Proceedings of 2006 ACEEE Summer Study on Energy

Efficiency in Buildings, American Council for an Energy Efficient Economy, Washington DC,

August 2006.

19. Yatish T, Shah. (2020). “Modular Systems for Energy Usage Management”

20. Kaplan, S. M., “Smart Grid. Electrical Power Transmission: Background and Policy Issues. The

Capital.Net”, Government Series. Pp. 1-42, 2009

21. Frej, Anne, editor, “Green Office Buildings: A Practical Guide to Development”. Urban Land

Institute. pp. 138–142, 2005

22. Yatish T, Shah, “Modular Systems for Energy Usage Management”, 2020

23. European Commission: "Buildings", 2017

24. D. D’Agostino, C. Marino, F. Minichiello, F. Russo, “Obtaining a NZEB in Mediterranean

climate by using only on-site renewable energy: is it a realistic goal?”, 2017

25. Agne Toleikyte, Lukas Kranzl, Raphael Bointner, Frances Bean, Jordi Cipriano, Maarten De

Groote, Andreas Hermelink, Michael Klinski, David Kretschmer, Bruno Lapilonne, Ramón

Pascual, Andrzej Rajkiewicz, Jose Santos, Sven Schimschar, Carine Sebi, Jonathan Volt, “Zebra

2020 – Nearly Zero Energy Building Strategy 2020”, 2016

26. Building Performance Institute Europe (BPIE), “Nearly Zero Energy Buildings definitions

across Europe”, 2015

27. Ezilda Costanzo, Anna Martino, Gian Mario Varalda, Marcello Antinucci, Alessandro Federici,

“EPBD implementation in Italy”, 2016

28. M. C. Teixeira, "As estratégias de Habitação em Portugal, 1880-1940," Análise Social, vol.

XXVII (115), pp. 65-89, 1992.

29. M. Salgado, “Atlas Urbanístico de Lisboa”, 2006.

30. J. M. Fernandes, “Portugês Suave - Arquitectura do Estado Novo”, IPPAR, 2003.

31. U.S. Department of Energy, “EnergyPlus Version 8.9.0 Documentation- Getting Started”

32. Cardinaels W, Borremans, “Demand response for families – linear final report,” EnergyVille,

2014.

33. V. B. J. Six D., Desmedt J., Vanhoudt D., “Exploring the flexibility potential of residential heat

pumps combined with thermal energy storage for smart grids,” Explor. Flex. potential Resid.

heat pumps Comb. with Therm. energy storage smart grids. Distrib., no. 21st International

conference on electricity distribution, p. 0442–0442., 2011.

34. J. Le Dréau and P. Heiselberg, “Energy flexibility of residential buildings using short term heat

Page 91: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

79

storage in the thermal mass,” Energy, vol. 111, pp. 991–1002, 2016.

35. T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of

building design on energy flexibility”

36. Rui Amaral Lopes, Adriana Chambel, João Neves, Daniel Aelenei, João Martins. (2016). “A

literature review of methodologies used to assess the energy flexibility of buildings”

37. T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of

building design on energy flexibility”

Websites

Abstract and Introduction:

1. https://www.sciencedirect.com/science/article/abs/pii/S0378778810004639

2. https://www.sciencedirect.com/science/article/pii/S1876610217355315

3. http://bpie.eu/publication/principles-for-nearly-zero-energy-buildings/

4. https://www.sciencedirect.com/science/article/abs/pii/S0378778817331195

5. https://www.sciencedirect.com/science/article/abs/pii/S0360544216306934

Climate change and building sector

6. https://climate.nasa.gov/evidence/

7. https://ipbes.net/news/media-release-worsening-worldwide-land-degradation-now-

%E2%80%98critical%E2%80%99-undermining-well-being-32

8. https://www.cisl.cam.ac.uk/business-action/low-carbon-transformation/ipcc-climate-

science-business-

briefings/pdfs/briefings/IPCC_AR5__Implications_for_Cities__Briefing__WEB_EN.pdf

9. https://www.pacificclimatechange.net/document/climate-change-action-trends-and-

implications-business-ipccs-fifth-assessment-report

10. https://www.ny-engineers.com/blog/how-buildings-produce-carbon-emissions...-and-how-

to-stop-them

11. https://www.researchgate.net/publication/237429041_Zero_Energy_Buildings_A_Critical_Lo

ok_at_the_Definition

12. http://www.buildup.eu/en/practices/publications/common-definition-zero-energy-buildings

Page 92: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

80

13. http://www.fsec.ucf.edu/en/publications/pdf/FSEC-PF-396-06.pdf

14. https://www.scirp.org/(S(351jmbntvnsjt1aadkposzje))/reference/ReferencesPapers.aspx?Ref

erenceID=1689887

15. http://bpie.eu/wp-content/uploads/2016/12/ZEBRA2020_Strategies-for-nZEB_07_LQ-

double-pages.pdf

16. http://bpie.eu/uploads/lib/document/attachment/128/BPIE_factsheet_nZEB_definitions_acr

oss_Europe.pdf

17. https://epbd-ca.eu/wp-content/uploads/2018/08/CA-EPBD-IV-Italy-2018.pdf

Acquisition data and Original model

18. http://analisesocial.ics.ul.pt/documentos/1223049300Z1dLD4ro1Jn31VT6.pdf

19. https://energyplus.net/sites/all/modules/custom/nrel_custom/pdfs/pdfs_v8.9.0/GettingStarted.p

df

Data elaboration

20. http://www.linear-smartgrid.be/sites/default/files/Linear%20Final%20Report%20-

%20lr2.pdf

21. https://iopscience.iop.org/article/10.1088/1755-1315/323/1/012009

22. https://www.sciencedirect.com/science/article/pii/S1876610216303745

Page 93: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

81

Index of Figures

Figure 1 - Graphic definition of a nZEB (Source: AIMS Press, “Energy efficient measure to upgrade a

multistory residential in a nZEB”) .......................................................................................................... 3

Figure 2 - Graph comparing carbon dioxide level in the past millennia (Source: NASA, “Climate

Change: How do we know?”, Credit: Luthi, D., et al. 2008; Etheridge, D.M., et al. 2010; Vostok ice core data/J.R. Petit et al.; NOAA Mauna Loa CO2 record.) ................................................................... 5

Figure 3 - Sea level (Source: NASA, “Sea level”, Last access 07/02/2020) ........................................... 6

Figure 4 - Carbon Footprint (Source: Global Alliance for Buildings and Constructions, “Global status

report”, 2018) .......................................................................................................................................... 8

Figure 5 - Schematic definition of an nZEB (Source: H. Vardhan, “Zero-energy building”, 2017) .... 12

Figure 6 - Key years for nearly Zero-Energy Building (Directive 2010/31/EC) (Source: EPISCOPE) 15

Figure 7 - Distribution of new buildings according to different building standards (Source: ZEBRA2020, “Nearly Zero Energy Building Strategy 2020”) .................................................................................... 16

Figure 8 - Encarnação Aerial View (2005) and Encarnação Initial Plan (1940) ................................... 23

Figure 9 - Energy Plus internal elements (Source: U.S. Department of Energy, EnergyPlus Version 8.9.0 Documentation- Getting Started) .......................................................................................................... 24

Figure 10 - Graphic example for each element (Wall, Floor, Roof) .................................................... 26

Figure 11 - Geometric model ................................................................................................................ 26

Figure 12 - Plan of the building (Floor 1) ............................................................................................. 27

Figure 13 - % of people in the house during the day ............................................................................ 29

Figure 14 - Total Energy Demand – Multiple thermal zones (Lisbon/Original Model) ....................... 30

Figure 15 - Outdoor-Indoor Temperature 27th of January – Multiple thermal zones (Lisbon/Original Model) ................................................................................................................................................... 31

Figure 16 - Total Energy Demand 27th of January – Multiple thermal zones (Lisbon/Original Model) ............................................................................................................................................................... 31

Figure 17 - Outdoor-Indoor Temperature 21-27th of January – Multiple thermal zones (Lisbon/Original Model) ................................................................................................................................................... 32

Figure 18 - Total Energy Demand 21-27th of January – Multiple thermal zones (Lisbon/Original Model) ............................................................................................................................................................... 32

Figure 19 - Outdoor-Indoor Temperature 29th of August – Multiple thermal zones (Lisbon/Original Model) ................................................................................................................................................... 33

Page 94: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

82

Figure 20 - Total Energy Demand 29th of August – Multiple thermal zones (Lisbon/Original Model) ............................................................................................................................................................... 33

Figure 21 - Outdoor-Indoor Temperature 23-30th of August – Multiple thermal zones (Lisbon/Original Model) ................................................................................................................................................... 34

Figure 22 - Total Energy Demand 23-30th of August – Multiple thermal zones (Lisbon/Original Model) ............................................................................................................................................................... 34

Figure 23 - Outdoor-Indoor Temperature All year – Single thermal zone (Lisbon/Original Model) ... 38

Figure 24 - Total Energy Demand – Single thermal zone (Lisbon/Original Model) ............................ 38

Figure 25 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Lisbon/Original Model) ............................................................................................................................................................... 39

Figure 26 - Total Energy Demand 27th of January – Single thermal zone (Lisbon/Original Model) .. 39

Figure 27 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Lisbon/Original Model) ................................................................................................................................................... 40

Figure 28 - Total Energy Demand 21-28th of January – Single thermal zone (Lisbon/Original Model) ............................................................................................................................................................... 40

Figure 29 - Outdoor-Indoor Temperature 29th of August – Single thermal zone (Lisbon/Original Model) ............................................................................................................................................................... 41

Figure 30 - Total Energy Demand 29th of January – Single thermal zone (Lisbon/Original Model) .. 41

Figure 31 - Outdoor-Indoor Temperature 23-30th of August – Single thermal zone (Lisbon/Original Model) ................................................................................................................................................... 42

Figure 32 - Total Energy Demand 23-30th of August – Single thermal zone (Lisbon/Original Model) ............................................................................................................................................................... 42

Figure 33 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Lisbon/Renovated Model) ................................................................................................................................................... 46

Figure 34 - Total Energy Demand 27th of January – Single thermal zone (Lisbon/Renovated Model) 46

Figure 35 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Lisbon/Renovated Model) ................................................................................................................................................... 47

Figure 36 - Total Energy Demand 21-28th of January – Single thermal zone (Lisbon/Renovated Model) ............................................................................................................................................................... 47

Figure 37 - Outdoor-Indoor Temperature 29th of August – Single thermal zone (Lisbon/Renovated Model) ................................................................................................................................................... 48

Figure 38 - Total Energy Demand 29th of August – Single thermal zone (Lisbon/Renovated Model) 48

Page 95: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

83

Figure 39- Outdoor-Indoor Temperature 23-30th of August – Single thermal zone (Lisbon/Renovated Model) ................................................................................................................................................... 49

Figure 40 - Total Energy Demand 23-30th of August – Single thermal zone (Lisbon/Renovated Model) ............................................................................................................................................................... 49

Figure 41 - PV energy production 27th of January (Lisbon/Renovated Model) .................................... 51

Figure 42 - PV energy production 29th of August (Lisbon/Renovated Model) .................................... 52

Figure 43 - Outdoor-Indoor Temperature All year – Single thermal zone (Turin/Original Model) ..... 53

Figure 44 - Total Energy Demand – Single thermal zone (Turin/Original Model) .............................. 53

Figure 45 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Turin/Original Model) ............................................................................................................................................................... 54

Figure 46 - Total Energy Demand 27th of January – Single thermal zone (Turin/Original Model) ..... 54

Figure 47 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Turin/Original Model) ................................................................................................................................................... 55

Figure 48 -Total Energy Demand 21-28th of January – Single thermal zone (Turin/Original Model) 55

Figure 49 - Outdoor-Indoor Temperature 3rd of August – Single thermal zone (Turin/Original Model) ............................................................................................................................................................... 56

Figure 50 - Total Energy Demand 3rd of August – Single thermal zone (Turin/Original Model) ....... 56

Figure 51 - Outdoor-Indoor Temperature 3-10th of August – Single thermal zone (Turin/Original Model) ................................................................................................................................................... 57

Figure 52 - Total Energy Demand 3-10th of August – Single thermal zone (Turin/Original Model) . 57

Figure 53 - Outdoor-Indoor Temperature 27th of January – Single thermal zone (Turin/Renovated Model) ................................................................................................................................................... 59

Figure 54 - Total Energy Demand 27th of January – Single thermal zone (Turin/Renovated Model) . 59

Figure 55 - Outdoor-Indoor Temperature 21-28th of January – Single thermal zone (Turin/Renovated Model) ................................................................................................................................................... 60

Figure 56 - Total Energy Demand 21-28th of January – Single thermal zone (Turin/Renovated Model) ............................................................................................................................................................... 60

Figure 57 - Outdoor-Indoor Temperature 3rd of August – Single thermal zone (Turin/Renovated Model) ............................................................................................................................................................... 61

Figure 58 - Total Energy Demand 3rd of August – Single thermal zone (Turin/Renovated Model) ... 61

Page 96: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

84

Figure 59 - Outdoor-Indoor Temperature 3-10th of August – Single thermal zone (Turin/Renovated Model) ................................................................................................................................................... 62

Figure 60 - Total Energy Demand 3-10th of August – Single thermal zone (Turin/Renovated Model)62

Figure 61 - PV energy production and Energy demand on 27th of January (Turin/Renovated Model) 64

Figure 62 - PV energy production and Energy demand on 3rd of August (Turin/Renovated Model) .. 65

Figure 63 – Demand-side control of set temperatures, representation of the cooling-down curve and heating-up time (Source: T Weiß. (2019). IOP Conf. Ser.: Earth Environ. “Energy Flexible Buildings - The impact of building design on energy flexibility”) .......................................................................... 67

Figure 64 - PV energy production and Energy demand on 27th of January (Turin/Renovated Model) 69

Figure 65 - PV energy production and New Energy demand on 27th of January (Turin/Renovated Model) ................................................................................................................................................... 70

Figure 66 - PV energy production and Energy demand on 3rd of August (Turin/Renovated Model) .. 71

Figure 67 - PV energy production and New Energy demand on 3rd of August (Turin/Renovated Model) ............................................................................................................................................................... 72

Index of Tables

Table 1. Reference building – Performance of single building elements (Source: Ministry of Economic Development) ........................................................................................................................................ 19

Table 2. U-value limits for Second level Major renovation and Minor renovation (Source: Ministry of Economic Development) ....................................................................................................................... 19

Table 3. Exterior walls stratigraphy (Original building) ....................................................................... 27

Table 4. Interior walls stratigraphy (Original building) ........................................................................ 28

Table 5. Floor stratigraphy (Original building) ..................................................................................... 28

Table 6. Ceiling stratigraphy (Original building) .................................................................................. 28

Table 7. Roof stratigraphy (Original building) ..................................................................................... 28

Table 8. Window stratigraphy (Original building) ................................................................................ 28

Table 9. Exterior walls stratigraphy (Renovated Building)................................................................... 44

Table 10. Interior walls stratigraphy (Renovated Building) .................................................................. 44

Page 97: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

85

Table 11. Floor stratigraphy (Renovated Building) .............................................................................. 44

Table 12. Ceilings stratigraphy (Renovated Building) .......................................................................... 45

Table 13. Roof stratigraphy (Renovated Building) ............................................................................... 45

Table 14. Plan Roof stratigraphy (Renovated Building) ....................................................................... 45

Table 15. Windows stratigraphy (Renovated Building) ........................................................................ 45

Table 16. Energy accounts of the building in a year (Lisbon) .............................................................. 50

Table 17. PV energy production 27th of January (Lisbon/Renovated Model)....................................... 51

Table 18. PV energy production 29th of August (Lisbon/Renovated Model) ...................................... 52

Table 19. PV energy production All year (Lisbon/Renovated Model) ................................................. 52

Table 20. Energy accounts of the building in a year (Turin)................................................................. 63

Table 21. PV energy production and Energy demand on 27th of January (Turin/Renovated Model) .. 64

Table 22. PV energy production and Energy demand on 3rd of August (Turin/Renovated Model) .... 65

Table 23. PV energy production and Energy demand on All year (Turin/Renovated Model) .............. 65

Table 24. Thermostat Lower set-point temperature on 27th of January (Original configuration) ........ 68

Table 25. Thermostat Lower set-point temperature on 27th of January (Energy Flexibility configuration) ............................................................................................................................................................... 69

Table 26. Energy demand on 27th of January (Before and after shifting loads) ................................... 70

Table 27. Thermostat Upper set-point temperature on 3rd of August (Original configuration) ........... 71

Table 28. Thermostat Upper set-point temperature on 3rd of August (Energy Flexibility configuration) ............................................................................................................................................................... 72

Table 29. Energy demand on 3rd of August (Before and after shifting loads) ..................................... 73

Page 98: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

86

Page 99: RETROFITTING TOWARDS NZEB THE CASE OF RESIDENTIAL … · 2020. 5. 4. · to design a retrofit towards nZEB, changing the stratigraphy of the components of envelope, fixtures and equipments

87

Acknowledgements (ITA)

Questo lavoro è stato sviluppato nell'ambito del progetto "Mapping Flexibility of Urban Energy

Systems”: FIRST, con la sovvenzione MITEXPL/SUS/0015/2017 della National Foundation of Science

and Technology attraverso il MIT Portugal Programme.

Innanzitutto, devo ringraziare il mio professore universitario nonché mio relatore del Politecnico di

Torino Marco Perino che, mettendosi in contatto con l’Universidade NOVA di Lisbona e mettendosi a

mia disposizione, mi ha permesso di fare questa esperienza di Tesi di 5 mesi all’estero in Portogallo.

Inoltre, un grazie speciale va al mio correlatore/supervisore Daniel Aelenei, professore presso il

dipartimento di Ingegneria Civile dell’Universidade NOVA di Lisbona che, seguendo il mio lavoro e

rendendosi sempre disponibile durante il mio soggiorno a Lisbona, mi ha reso partecipe di un progetto

reale che l’Universidade NOVA aveva portato avanti insieme al MIT (Massachusetts Institute of

Technology) fornendomi dati di input e seguendomi durante l’elaborazione dei dati e l’ottenimento dei

risultati. Un ringraziamento va anche a Naim Majdalani, un dottorando del professor Daniel Aelenei,

che mi ha seguito durante il lavoro di tesi dandomi consigli sul da farsi e guidandomi nell’utilizzo del

software EnergyPlus.

Questo lavoro di tesi conclude un percorso di studio lungo due anni nei quali ho dovuto affrontare

difficoltà di ogni genere ma, grazie all’aiuto e il sostegno sia dei miei familiari che dei miei amici e

compagni di studio di Torino, è risultato meno faticoso del previsto, ma anzi pieno di risate e tante belle

emozioni.