rev. b ed-rud · cable connection terminal block, push-in. max. 1.5 mm2 (awg 16) mounting room...

3
Rev. B ED-RUD Flush-mounted room unit intended for use as a display for more advanced controllers Slimflush-mountedroomunitwithbacklittouchdisplay. IntendedeitherforPlug'nPlaywithRegin'sroom controllersRegio Eedo ,Regio Ardo ortogetherwithany Modbusmastercontroller. Flush-mounted room unit Touch display Plug'n Play to dedicated Regin controllers Flexible to use with any Modbus master controller Compatible with Regio Two room function Application This user-friendly room unit with touch display and temperature sensor is suitable for all types of indoor environments. It has an appealing design and can be used with any Modbus master controller. Together with Regin's controllers Regio Eedo , Regio Ardo no configuration is required - just Plug'n Play. Function The display can be used to control fan-speed, temperature and manual change over. The large LCD touch screen displays the room status and it is also used to access all parameters, such as setpoint, fan speed etc. When used with the Regio Two room function, it is required to use two units of the same kind. Installation The room unit is installed indoors on a wall, on an EU standard wall mounting box. It is easily connected to the supply voltage as well as the Modbus master controller via the push-in terminal block. HEAD OFFICE SWEDEN Phone: +46 31 720 02 00 Web: www.regincontrols.com E-mail: [email protected] ED-RUD —1—

Upload: others

Post on 27-May-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Rev. B

ED-RUDFlush-mounted room unit intended for useas a display for more advanced controllers

Slim flush-mounted room unit with backlit touch display.Intended either for Plug'n Play with Regin's roomcontrollers RegioEedo, RegioArdo or together with anyModbus master controller.

✓ Flush-mounted room unit

✓ Touch display

✓ Plug'n Play to dedicated Regin controllers

✓ Flexible to use with any Modbus mastercontroller

✓ Compatible with Regio Two room function

ApplicationThis user-friendly room unit with touch display andtemperature sensor is suitable for all types of indoorenvironments. It has an appealing design and can be usedwith any Modbus master controller. Together withRegin's controllers RegioEedo, RegioArdo no configuration isrequired - just Plug'n Play.

FunctionThe display can be used to control fan-speed, temperatureand manual change over. The large LCD touch screendisplays the room status and it is also used to access allparameters, such as setpoint, fan speed etc. When usedwith the Regio Two room function, it is required to usetwo units of the same kind.

InstallationThe room unit is installed indoors on a wall, on an EUstandard wall mounting box. It is easily connected to thesupply voltage as well as the Modbus master controller viathe push-in terminal block.

HEAD OFFICE SWEDEN

Phone: +46 31 720 02 00Web: www.regincontrols.com

E-mail: [email protected]

ED-RUD

— 1—

Technical dataGeneral dataSupply voltage 24 V AC/DC (22…26 V AC/DC)

Power consumption 60 mA

Protection class IP30

Ambient humidity 10…90 % RH (non-condensing)

Ambient temperature 0…50 °C

Storage temperature -20…+70 °C

Cable connection Terminal block, push-in. Max. 1.5 mm2 (AWG 16)

Mounting Room (flush-mounted with screw distance cc 60 mm)

Display Built-in

Display type LED-backlit LCD

Dimensions, external (WxHxD) 95 x 95 x 23 mm

Weight 0.18 kg

Serial port data

Serial port 1

Port type RS485

Supported protocol Modbus (RTU)

Communication speed 38400 bps (4800…38400 bps)

Parity Even (Even, Odd, None)

Stop bit 1 (1 or 2)

This product carries the CE-mark. More information is available at www.regincontrols.com.

MaterialMaterial, housing and base Polycarbonate, PC

Material, fire resistance UL 94 V-0

Colour, housing and base Signal white RAL 9003

AccessoriesArticle Description

E-Cable2-USB PC-cable for communication, with USB connection

ConverterTCP Serial adapter for Modbus, RS485 to TCP

EDSP-K3/...-K10 Cable for connecting the display to the controller

HEAD OFFICE SWEDEN

Phone: +46 31 720 02 00Web: www.regincontrols.com

E-mail: [email protected]

ED-RUD

— 2—

Dimensions

[mm]

DocumentationAll documentation can be downloaded from www.regincontrols.com.

15

95

1823

cc 60

HEAD OFFICE SWEDEN

Phone: +46 31 720 02 00Web: www.regincontrols.com

E-mail: [email protected]

ED-RUD