Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460 Shop Drawings Submittal 11R1 – MUA (rev.1) Project Name: Basalt Reviewed Project No. OME 18311 Reviewed as Modified Engineer: Williams Engineering Revise and Re-Submit General Contractor: Performance Construction Not Reviewed Review: Tag # Comment Status MAU-1 Makeup Air Unit c/w unit sound data information Reviewed By: Bryan Juan Date Submitted: May 9, 2019 Date Required: May 23, 2019 Prompt review of these shop drawings is imperative for the project schedule. Any shop drawing review over 4 weeks will be assessed as to its impact to the schedule. Omega Mechanical will not accept or be subject to project delay claims due to untimely shop drawing review. Project Name REVIEWED REVISE REJECTED BY SUBMITTAL# DATE SPEC Bryan Juan 5/9/2019 11R1 IFC Basalt Company Logo This review is only for general conformance of the project and general compliance. Corrections or comments made on these drawings during this review do not relieve Contractor/Subcontractor from compliance with the requirements of the plans and specifications. Contractor is responsible for all dimensions and fabrication to be confirmed and correlated at the job site NOT REVIEWED Reviewed Reviewed as Modified Revise Revise and Re-Submit Not Reviewed Reviewed only as to general conformity with the design concept. The Engineer does not warrant or represent that the information contained on this drawing is either accurate or complete. Sole responsibility for correct design, details and dimensions shall remain with the contractor submitting the drawing. The review of this shop drawing shall not, in any way, relieve the contractor from complying with all requirements of the contract documents. Per, WILLIAMS ENGINEERING CANADA INC. By: Date: jjeon 05/29/2019 ( ) ( ) ( ) ( ) (X) SHIFT ARCHITECTURE INC. SHOP DRAWING REVIEW Reviewed Reviewed as Noted Revise and Resubmit Not Reviewed Project Date Reviewed By This review by Shift Architecture Inc. is for the sole purpose of ascertaining conformance with the general design concept. This review shall not mean that Shift Architecture Inc. approves the detailed design inherent in the shop drawings, responsibility for which shall remain with the Contractor submitting same, and such review shall not relieve the Contractor of the responsibility for errors or omissions in the shop drawings or of the responsibility of meeting all requirements of the contract documents. The Contractor is responsible for dimensions to be confirmed and correlated at the job site, for information that pertains solely to fabrication processes or to techniques of construction and installation, and for the coordination of the work of all trades. 6/3/2019 1505 HK Shift Note - Comment from Brown Strachan Associates regarding acoustics (sent to Shift on May 31st 2019): "Prior to boarding, we recommend listening tests in the corridor with the MUA operating above. A critical requirement is that drywall and framing be installed clear of ductwork serving the MUA or any other equipment, particularly in suites. The corridor ceiling should be loosely insulated in the vicinity of the duct. Ductwork in shafts should be supported at floors only (no contact to shaft walls). During commissioning, and after all specified isolation work is complete, MUA noise should be rechecked in the suites and corridor, preferably in the early morning, before occupancy."

Upload: others

Post on 22-Sep-2020

9 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

Omega Mechanical Ltd.

Unit 202 – 5595 Roy Street

Burnaby, BC V5B 3A5 | 604.255.2460

Shop Drawings Submittal 11R1 – MUA (rev.1)

Project Name: Basalt Reviewed

Project No. OME 18311 Reviewed as Modified

Engineer: Williams Engineering Revise and Re-Submit

General Contractor: Performance Construction Not Reviewed

Review:

Tag # Comment Status

MAU-1 Makeup Air Unit c/w unit sound data information

Reviewed By: Bryan Juan

Date Submitted: May 9, 2019

Date Required: May 23, 2019

Prompt review of these shop drawings is imperative for the project schedule. Any shop drawing review over 4 weeks

will be assessed as to its impact to the schedule. Omega Mechanical will not accept or be subject to project delay

claims due to untimely shop drawing review.

Project Name

REVIEWED

REVISE

REJECTED

BY

SUBMITTAL#

DATE

SPEC

Bryan Juan 5/9/2019

11R1 IFC

Basalt Company Logo

This review is only for general conformance of the project and generalcompliance. Corrections or comments made on these drawings during thisreview do not relieve Contractor/Subcontractor from compliance with therequirements of the plans and specifications. Contractor is responsible for alldimensions and fabrication to be confirmed and correlated at the job site

NOT REVIEWED

Reviewed

Reviewed as Modified

Revise

Revise and Re-SubmitNot Reviewed

Reviewed only as to general conformity with the design concept. The Engineer does notwarrant or represent that the information contained on this drawing is either accurate orcomplete. Sole responsibility for correct design, details and dimensions shall remain withthe contractor submitting the drawing. The review of this shop drawing shall not, in anyway, relieve the contractor from complying with all requirements of the contract documents.

Per,

WILLIAMS ENGINEERING CANADA INC.

By:

Date:

jjeon

05/29/2019

( )

( )

( )

( ) (X)

SHIFT ARCHITECTURE INC.

SHOP DRAWING REVIEW

Reviewed

Reviewed as Noted

Revise and Resubmit

Not Reviewed

Project

Date

Reviewed By

This review by Shift Architecture Inc. is for the sole

purpose of ascertaining conformance with the

general design concept. This review shall not mean

that Shift Architecture Inc. approves the detailed

design inherent in the shop drawings, responsibility

for which shall remain with the Contractor

submitting same, and such review shall not relieve

the Contractor of the responsibility for errors or

omissions in the shop drawings or of the

responsibility of meeting all requirements of the

contract documents. The Contractor is responsible

for dimensions to be confirmed and correlated at the

job site, for information that pertains solely to

fabrication processes or to techniques of

construction and installation, and for the

coordination of the work of all trades.

6/3/2019

1505

HK

Shift Note - Comment from Brown Strachan Associates regarding acoustics (sent to Shift on May 31st 2019):

"Prior to boarding, we recommend listening tests in the corridor with the MUA operating above. A criticalrequirement is that drywall and framing be installed clear of ductwork serving the MUA or any other equipment,particularly in suites. The corridor ceiling should be loosely insulated in the vicinity of the duct. Ductwork in shaftsshould be supported at floors only (no contact to shaft walls).

During commissioning, and after all specified isolation work is complete, MUA noise should be rechecked in thesuites and corridor, preferably in the early morning, before occupancy."

Page 2: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

DRAWING TRANSMITTAL SHEETJOB NO.58667(V22402)DATE May 02, 2019

VANCOUVER CANADIAN CANADIAN OTHER CANADIANSALES OFFICE HEAD OFFICE FACTORY SALES OFFICES303 - 8988 FRASERTON COURTBURNABY BCV5J 5H8(604) 736-2420

CALGARY AB CALGARY ABEDMONTON ABNEWMARKET ON

EDMONTON, CALGARY, SASKATOON,REGINA, WINNIPEG, LONDON, SUDBURY,TORONTO, HAMILTON, OTTAWA, MONTREAL,HALIFAX, MONCTON

CONTRACTOR OMEGA MECHANICAL LTDADDRESS 2433 HOLDOM AVE

BURNABY BCV5B 5A1

ENGINEER WILLIAMS ENGINEERING (ABBOTSFORD)JOB NAME BASALT

THIS ORDER IS SUBJECT TO APPROVAL. MANUFACTURING IS HELD PENDING RETURN OF ONE APPROVED COPY OFTHESE FORMS TO THE INDICATED OFFICE.

THIS ORDER IS NOT SUBJECT TO APPROVAL AND IS BEING MANUFACTURED ACCORDING TO THE ATTACHED FORMS.

COPIES ENCLOSED DESCRIPTION

1 EngA Submittal Revision Summary

1 EngA Submittal Record MAU-11 Heatcraft Evaporator Coil Certificate Data Sheet1 EngA Supply Fan Sound Data1 EngA Mechanical Drawing 58667M-01-11 EngA Roof Curb Drawing 58667C-01-11 EngA Internal Wiring Diagram 58667E-01-11 EngA Electrical Data Sheet MAU-11 EngA Field Wiring Diagram 58667F-01-1

1 Foam Curb Gasket Specification Sheet1 EngA Installation Operation and Maintenance Manual (LM Series)

PER BOB CORNFIELD / RLK

Condenser coil(heating mode)certificate data sheetis missing.

Page 3: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

SUBMITTAL REVISIONSJOB NAME: BASALT 58667(V22402)JOB NO:

CUSTOMER:OMEGA MECHANICAL LTD

ENGINEER: WILLIAMS ENGINEERING (ABBOTSFORD) REVISION DATE:May 02, 2019

CHANGES AND/OR REVISIONS MADE TO THIS ORDER:

Revision:- Changed fan isolators to spring isolators.- Added Sound Calculation data.- Provided specification data sheet for curb gasket.

SUBMITTED BY:BOB CORNFIELD / RLK

Page 4: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

SUBMITTAL RECORD

JOB NAME: BASALT 58667(V22402)JOB NO:CUSTOMER: ENGINEER:OMEGA MECHANICAL LTD WILLIAMS ENGINEERING (ABBOTSFORD)

EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1

SHIPPING AND APPROVAL INFORMATIONMOUNTING Outdoor Base Mounted c/w Prefab Seismic Roof Curb ACCESS As Per Drawing

OPERATING WEIGHT1200 lb (545 kg)UNIT MINIMUM AMBIENT0°F (-17.8°C) SHIPPING WEIGHT 1100 lb (500 kg)NO. OF PIECES 3 (Unit + Curb + Hood)

•IntertekcETL approval.

SUPPLY AIR DATAAIR FLOW 1,100 CFM (519 l/s) FAN SIZE (1) 9/7 FC DIDW TSP 2.69 in w.c. (670 Pa) RPM 1826MOTOR SIZE 1 1/2 HP (1.12 kW) TYPE (RPM)ODP (1750) ESP 1.5 in w.c. (374 Pa) BHP 0.84 BHP (.63 kW)

•Supply air fan/motor c/w seismic spring vibration isolation and pillow block bearings.•Drives have a service factor of 1.

AIR OPENING DATAAIR OPENING LOCATION DAMPER TYPE OPERATION

SUPPLY AIR BottomOUTSIDE AIR Back EngA Parallel Blade Two Position

CONSTRUCTION DATAUNIT CABINET 18 gauge satin coat galvanized sheet metal c/w 2" (51 mm) 1.5 lb/ft³ (24 kg/m³) insulation on entire unit casing.

UNIT LINER 22 gauge solid liner on coil and discharge plenum section.

UNIT FLOOR 18 gauge satin coat galvanized sheet metal on entire unit floor.

EXTERIOR PAINTElectrostatically applied Alkyd Enamel in Aluminum Gray color - Level 1 on all exterior surface but not including unitunderside.

AIRSIDE DOOR All access - hinged c/w lever type door handles

SERVICE DOOR All access - hinged c/w lever type door handle

DRAIN PAN G90 galvanized drain pan c/w floor drain connection through base frame on entire floor section.304L stainless steel drain pan c/w floor drain connection through base frame on coil (by others) section.

•Unit to be built with .- Rain gutters and down spouts on both side of unit

ELECTRICAL DATAPOWER SUPPLY MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE(D.E.) MAXIMUM BREAKER208 / 1 / 60 14.1 AMPS 25 AMPS 25 AMPS

•See Electrical Data Sheet for details.

FILTER SECTION DATA - Side LoadedFILTER TYPE Dafco Pleated Filter with MERV 13 rating c/w Metal FrameQTY/SIZE 1 - 24 x 20 x 2" (610 x 508 x 51 mm) QTY/SIZETOTAL GROSS AREA 3.33 SQ.FT. (0.31 SQ. MTRS) FACE VELOCITY 330 FPM (1.68 m/s)

•Filters may be shipped loose or mounted in the tracks•Dwyer series 2000 magnehelic gauge 0-1" wc across filter section

- 1 -DATE 02-May-2019 Continued on page 2

Page 5: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

SUBMITTAL RECORD

JOB NAME: BASALT 58667(V22402)JOB NO:EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1

DX COIL DATACOIL SIZE 18 (457) x 26 (660) x 2R x 10 FPI VELOCITY 338 FPM (1.72 m/s)

CAPACITY 29,200 Btuh (8.6 kW) AIR P.D.0.27 in.wc. (67 Pa)ENTERING AIR DB / WB 82°F (27.8°C) / 67.0°F (19.4°C) LEAVING AIR DB / WB 63.0°F (17.2°C) / 60.0°F (15.6°C)SST/SCT 42°F (5.6°C) / 100°F (37.8°C) REFRIGERANT TYPE R-410ADISTRIBUTOR TYPE (1) 5/8" SUCTION SIZE 7/8 in (22 mm) QUANTITY 1

•Heatcraft coil provided and installed by EngA c/w auxiliary drain pan(1/2"(13 mm) drain connection) and drain pan.•Coil control and all associated components are by others.

SHIPPED LOOSE ITEMS (See filter section for filters)1 - Pre fabricated seismic roof curb (See drawing for details).1 - Inlet hood c/w 1"(25 mm) birdscreen.

- 2 -DATE 02-May-2019 SUBMITTED BYBOB CORNFIELD / RLK

Page 6: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

$1 i ftpwrwt"ivrsrtr heh{trans!erN G (J Lu l(l coils

/1'n4R>ogniv

%?'

COILCALC EVAPORATOR

Customer

Contact

Telephone

Proiect

Email

Engineered Air

Geoff Gorai

(26064) Basalt - C8-15-28

Date

BY

Company

Return Telephone

Email

2/7/2019 5:05:48 PM

Pavlos Pavlides

Modine CIS

662-614-7374

[email protected]

CONSTRUCTION

Item

Coils in bank

Style

Tube OD

Fins per inch

Rows

Fin surface

Fin height / Length

Tubing material

Fin material

Circuiting

Face area

in

in/

in

in

in

sqft

Default #1

1

EN

3/8

10

2

Optimize ABC

18.00 / 26.00

0.C)16 Copper

0.0050 Aluminum

-3

3.25

AIR SIDE

Air flow (Standard)

Altitude

Entering air (db) / (wb)

Leaving air (db) / (wb)

Total / Sens. capacity

Max air PD

REFRIGERANT SIDE

Refrigerant

Super heat temp.

Saturated suc. temp.

Liquid temp.

cfm

fl

oF

oF

MBH

in wg

A"F

"F

oF

i,ioo.oo

o.oo

82.00 / 67.00

63.00 l 60.00

0.00

R-410A

8.0

42.0

100.0

OUTPUT DATA

Model number

FPI i Rows i Surf

Circuit

Air velocity (Standard)

Total capacity

Sensible capacity

Lvg. air DB

Lvg. air WB

Standard APD

Code 18/19 #1

Code 18/19 #2

Suction conn.

Distributor conn. 1

Distributor conn. 2

Refrigerant PD

Refrigerant velocity

Internal volume

Weight

Notes

ft/min

MBH

MBH

oF

oF

in wg

in

in

in

psi

ft/min

ills

lbs

COIL1

3ENi202A

12102iA

Normal

338

25.3

17.7

67.12

60.04

0.068

6003/1-1/2

N/A

(1)0.875

(1 ) 0.500

(0) 0.000

3.70

1,262.78

110.7

36.9

CM

MOST ECONOMICAL

COIL2

3ENO802B

08 i02 i B

Normal

338

26.1

18.8

66.20

59.80

0.091

6003/1-1/2

N/A

(1 ) 0.875

(1 ) 0.500

(0) 0.000

3.91

1 ,303.26

110.7

34.6

CM

COIL3

3ENO802C

081 021 C

Normal

338

28.2

20.7

64.60

59.18

0.123

7003/1-1 /2

N/A

(1 ) 0.875

(1 ) 0.500

(o) o.ooo

4.45

1 ,405.70

110.7

34.6

CM

COIL4

3EN1002A

l0i02iA

Normal

338

22.9

15.8

68.71

60.75

0.055

6003/1-1/2

N/A

(1 ) 0.875

(1)0.500

(o) o.ooo

3.12

1,143.26

110.7

35.8

CM

SPEC?FIED COIL

COILs J3EN1002B

lOl021B

Normal

338

29.2

21.2

64.14

58.87

0.112

7003/1-1/2

N/A

(1)0.875

(1 ) 0.500

(0) 0.000

4.73

1,456.82

110.7

35.8

CM

COIL6

3EN1002C

lOl021C

Normal

338

:31.3

23.2

62.51

58.22

0.152

7003/02

N/A

(1)0.875

(t)o.soo

(o) o.ooo

5.34

1,560.79

*10.7

35.8

CM

NOTES FROM CALCULATIONS

C) Coil is NOT cer(i{ied by AHRI.M) Coil racing valid for Hea{crafl coils only.

USER NOTES

Copyright 2003 Modine Grenada LLC Confidentral and Proprietary. Thrs design is for the exclusive and confidential use of Modrne Grenada LLCand-its-clrent. Any duplicalron made for lhe purpose of disclosrng this desrgn or any part of the design to a competrlor of Modine Grenada LLC isin direct vrolation of khis confidentiality. Any duplrcalion must be approved rn writing by Modine Grenada.

Page 1 of 1

Page 7: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

April 29, 2019Unit Sound Data

JOB NAME: JOB NUMBER:

UNIT TAG:INSTALLATION:

SOUND SOURCE DATA:

UNIT CONSTRUCTION:

UNIT S/A OUTLET:

UNIT O/A INLET:

UNIT CASING *:

* Unit casing sound includes casing breakout and sound sources outside the air streams only. Sound from openings are not included in unit casing sound.

Note:Unit sound data are calculated for the specified unit construction and operating condition as shown above.

Page 8: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

generated byDATE: DRWN BY: CHKD BY: DRWG NO.:

REVISIONS:

TAG:58667(V22402)

MAU-1LM1/C/O/V

AIR HANDLING UNIT

JAN 22 2019 RLK MXC 58667M-01-1

DOOR SIZES AND INTERNAL COMPONENTS ARE APPROX. VALUES. DIMENSIONS SHOWN IN INCHES ONLY UNLESS OTHERWISE NOTED.

ACCESS

PLENUM SECTION

SUPPLYAIR

COIL SECTION

ACCESS

BLOWER/MOTOR SECTION

OUTSIDEAIR

ACCESS

INLE

T H

OO

DC

/W B

IRD

SCR

EEN

8 [203] 6 [152] 24 [610]

113 [2870]

16 [406] 30 [762]

FILTERGAUGE

LINED SECTION

36 [914]

PROVIDED AND INSTALLED BY ENGA

ACCESS

36 [914]

8 [203]CONTROL

PANEL

4 [102]

RAIN GUTTERBOTH SIDES

CONTROL PANEL

60°

24

5 [127]

1. UNIT SUPPORT FOR WIND LOAD BY OTHERS.

8 [203]

2. UNIT SUPPORT FOR SEISMIC EVENT BY OTHERS.

1-1/2''ØBLK IRONDRAIN CONNECTION

3. UNIT IS NOT DESIGNED TO SURVIVE SEISMIC EVENT.

4. DRAIN PAN IN DUCT WORK BY OTHERS.

SOLIDLINER

HEATCRAFT COIL

Page 9: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

DesignCube°generated by

DATE: DRWN BY: CHKD BY: DRWG NO.:

REVISIONS:

TAG:DRAWING NOT TO SCALEJOB# 58667(V22402)

MAU-1LM1/C/O/V

12'' HIGH SEISMIC CURB FOR DOWN DISCHARGE UNIT

FEB 13 2019 RLK MXC 58667C-01-1

Gen

erat

ed b

y A

utoC

urb

- ver

sion

2.2

.671

.155

- C

urb

Sty

le #

2Jo

b fil

enam

e =

G:\C

alga

ry\C

urre

nt D

esig

ners

\Roh

it Ku

mar

\586

67\M

AU-1

\Cal

c an

d C

oil A

utom

ate\

5866

7-SE

ISM

IC.c

rb1. 3/8'' X 3/4'' (10 X 19) NEOPRENE GASKET FOR 2'' (51) TO 4'' (102) CHANNELS, OR 3/8'' X 1-1/2'' (10 X 38) NEOPRENE GASKET FOR CHANNELS 6'' (153) AND OVER.2. CURB MAY BE BROKEN DOWN FOR SHIPPING. IN THESE CASES, FIELD ASSEMBLY WILL BE REQUIRED BY INSTALLING CONTRACTOR.3. CONTINUOUS BASE SUPPORT TO CURB PANELS, INCLUDING THE CENTER SUPPORT PANEL IF SUPPLIED, IS REQUIRED BY OTHERS.4. DIMENSIONS GIVEN IN INCHES AND MILLIMETRES

12''(305)

4'' (102)

17''(432)

15 1/4''(387)

AA

SUPPLYAIR FLOW

INS

IDE

TO IN

SID

E C

UR

B W

ALLS

1"(25)

INSIDE TO INSIDE CURB WALLS

1"(25)

SUPPLYAIR

INSULATIONFACTORY

(BY OTHERS)

FLASHING (BY OTHERS)

(51)2"

(10)3/8"

MOUNTED (SEE NOTE 1)NEOPRENE GASKET FIELD

TAR AND GRAVELCANT STRIP (BY OTHERS)

ROOFING PAPER (BY OTHERS)

FACTORY MOUNTED2" X 4"(51 X 102)

Z-BAR WELDED TO CURB

BASECHANNEL

4'' X 2'' X 3/16'' (102 X 51 X 5) ANGLE. PRE-DRILL FOR 1/2''(13) BOLT

2" X 2" X 0.25" (51 X 51 X 6) ANGLE. DRILL AT INSTALLATION

TO SATISFACTION OFSECURE TO STRUCTURE -

(38 X 38 X 3)1 1/2" X 1 1/2" X 1/8"

CURB AT INSTALLATION (BY OTHERS)WELD BRACKET TO ROOF

REINFORCEMENT BRACKET

SEISMIC ENGINEER

(SHIPPED LOOSE)

1/2" (13) HOLES AT 24" (610) C-CIN CENTER OF BOTTOM FLANGE

3''

TYP.

2"

2"(51)

(51)(76)

B

B

3"(76) TYP

DOWN DISCHARGESA COLLAR

RIGID INSULATION (BY OTHERS)

30 1/2''(775)

26 1/2''(673)

36 1/4''(921)

32 1

/4''

(819

)

12'' (305)

(2) HOLDING ANGLES AT 10 1/2''(267) CENTERS

(2) H

OLD

ING

AN

GLE

S AT

16

1/4

''(41

3) C

EN

TER

S

10''(254)

10''(254)

10''(254)

10''(254)

8''(203)

4 1/8''(105)

24''(610)

(2) BRACKETS TOTAL:(1) IN LENGTH

3 1/4''(83)

Page 10: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460
Page 11: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

ELECTRICAL DATAJOB NAME: BASALT 58667(V22402)JOB NO:

EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1

PowerSupply

Minimum CircuitAmpacity

Terminal Block toAccept

Maximum Fuse(Dual Element)

Maximum Breaker

208 / 1 / 60 14.1 AMPS 14 Awg 25 AMPS 25 AMPS

Components Model MinimumConductor Size

AmpacityFLA / LRA

Supply Fan Motor ODP (1750) 1 1/2 HP 14 Awg 11.0Main Control Xfmr 14 Awg .4

UNIT CONTROL PANEL(S) SHORT CIRCUIT CURRENT RATING (SCCR)Short circuit current 5 kA rms symmetrical, 208 V maximum

WIRING DRAWING LEGENDAPS Air Proving SwitchASF Auto Fan SwitchAUX Auxiliary ContactBM Burner MotorC ContactorCCH Compressor Crankcase HeaterCFC Condenser Fan ControlCLC Compressor Loading ControlCPM Compressor Protection ModuleCR Cooling RelayCS Current SensorDHSS Draft Hood Spill Switch

DM Damper MotorFR Fan RelayGND GroundGV Gas ValveHL High LimitHPC High Pressure ControlHR Heating RelayIGN Ignition ControlITP Internal Thermo ProtectionLPC Low Pressure ControlM MotorMV Main Gas Valve

NFD Non Fused DisconnectOL Thermal OverloadPS Pressure SensorPV Pilot Gas ValveR RelayRevHLReverse Airflow High LimitTB Terminal BlockTDF Time Delay FuseTDR Time Delay RelayTS Temperature SensorVFD Variable Frequency DriveXFMR Transformer

UNIT FUNCTION

Disconnect switch (by others) 'on', service switch 'on', fire alarm contact (by others) 'closed' (jumper if not required).

Unit on/off contact (by others) 'closed'. Blower starts and runs continuously.

Unit on/off contact (by others) 'open'. Unit is off.

Coil control and all associated components are by others.

Note 1 - Refer to manuals shipped with unit for a more detailed explanation of maintenance, component(s) and/or controller(s).

DATE:02-MAY-2019 SUBMITTED BY:BOB CORNFIELD / RLK

Page 12: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460
Page 13: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

P8600 Series Vinyl Nitrile Foam Tape

2600 E. 107th Street | Bolingbrook, Illinois 60440 | TOLL FREE: 800.323.7467 | FAX: 630.628.8025 | [email protected] | PresOn.com

Product Description

Pres-On P8600 Series Vinyl Nitrile Foam Tape’s uniform, closed-cell structure resists the absorption of water and other fluids.

Its high-performance, permanent acrylic adhesive bond is ideal for sealing, gasketing, weatherproofing, thermal insulating,

absorbing shock and dampening vibration.

Applications

P8600 is widely utilized for roof curb sealing, pipe wrapping, filter gasketing and a variety of other demanding HVAC applications.

• Composed of a vinyl/nitrile closed-cell foam blend

• Resists moisture, fire and chemicals

• Pressure sensitive acrylic adhesive exhibits high initial grab

• Provides a long lasting, permanent bond

• Uniform cell structure lends dimensional stability

TECHNICAL DATA

STANDARD ROLL SIZE SERIAL NUMBER THICKNESS LENGTH

All rolls available in widths from 1/4” to 54” P8612 1/8” 30’ or 50’

P8618 3/16” 50’

P8625 1/4” 50’

P8637 3/8” 25’

P8650 1/2” 25’

P8675 3/4” 25’

P861 1” 25’

ADHESION PROPERTIES TEST TYPICAL PERFORMANCE TEST METHOD

Adhesion to Steel @ 72°F Steel immediate Steel after 24 hours

2.5 lbs/in width or foam tear 4.0 lbs/in width or foam tear

PSTC-1PSTC-1

Adhesion to Steel, 15 min dwell 4.3 - 6.4 lbs/in PSTC-1

Adhesion to Steel, 24 hour dwell 6.0 lbs/in PSTC-1

Shear 1” x 1”, 500 gms 1000 hours PSTC-7

Shear 1” x 1”, 1000 gms 200 hours PSTC-7

Optimal Application Temperature 50°F to 80°F Pres-On PTM-1

Functional Temperature 0°F to 225°F Pres-On PTM-2

Water and Humidity Resistance Excellent Pres-On

Shelf Life 1 year stored at room temp

Page 14: REVIEWED REJECTED SUBMITTAL# SPEC Shop Drawings …perfcon.net/drawings/1296basalt/Shop Drawings...Omega Mechanical Ltd. Unit 202 – 5595 Roy Street Burnaby, BC V5B 3A5 | 604.255.2460

P8600 Series Vinyl Nitrile Foam Tape

2600 E. 107th Street | Bolingbrook, Illinois 60440 | TOLL FREE: 800.323.7467 | FAX: 630.628.8025 | [email protected] | PresOn.com

PHYSICAL PROPERTIES TEST METHOD UNIT OF MEASURE RESULT

Density ASTM D-1667 lbs/ft2 3.0 - 6.0

Tensile Strength ASTM D-412 psi 25 minimum

Shore OO Durometer -- -- 30

Compression Force 25% Deflection

ASTM D-1056 psi1.5 - 3.0

Compression Set 50% ASTM D-1056 35 maximum

Temperature Range -- °F -40° to 220°

Water Absorption ASTM D-1056 -- 10% maximum

Thermal Stability(% change in length, 7 days @ 220°F)

ASTM C-548 %10 maximum

Thermal Conductivity(BTU-IN/HR/SQ FT)

ASTM C-177 BTU-IN0.290 maximum

Ozone Resistance ASTM D-1171 Pass/Fail Pass

Fluid Immersion ASTM D-1056 100 maximum

Mold Growth UL 181 Pass/Fail Pass

Fungi Resistance ASTM G 21/C 1338 Pass/Fail Pass

Bacterial Resistance ASTM G 22 Pass/Fail Pass

Flammability RatingMVSS302UL 94HF1

Pass/FailPass/Fail

PassPass

Application NotesEnsure bonding surfaces are well unified, clean, dry and free of dirt and oils. Apply firm and even pressure to improve adhesive-to-

surface contact. Allow proper temperature and time to enhance bond strength as adhesive flows onto the surface.

IN NO EVENT WILL PRES-ON OR ANY OF ITS AFFILIATES BE LIABLE FOR ANY DIRECT OR INDIRECT DAMAGES, CLAIMS, OR LOSSES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, INCIDENTAL DAMAGES, CONSEQUENTIAL DAMAGES, LOST PROFITS AND/OR LOST OPPORTUNITIES) RESULTING FROM OR RELATED TO THIS PRODUCT OR THE USE, MISUSE, PURCHASE, OR SALE OF THIS PRODUCT, WHETHER BASED ON WARRANTY, CONTRACT, TORT, OR ANY OTHER LEGAL THEORY, WHETHER OR NOT FORESEEABLE, AND WHETHER OR NOT ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Any specifications, instructions, or other information provided by Pres-On in connection with this product are provided for informational purposes only and shall not be deemed to impose any representations, warranties, covenants or other obligations upon Pres-On or any of its affiliates.