Omega Mechanical Ltd.
Unit 202 – 5595 Roy Street
Burnaby, BC V5B 3A5 | 604.255.2460
Shop Drawings Submittal 11R1 – MUA (rev.1)
Project Name: Basalt Reviewed
Project No. OME 18311 Reviewed as Modified
Engineer: Williams Engineering Revise and Re-Submit
General Contractor: Performance Construction Not Reviewed
Review:
Tag # Comment Status
MAU-1 Makeup Air Unit c/w unit sound data information
Reviewed By: Bryan Juan
Date Submitted: May 9, 2019
Date Required: May 23, 2019
Prompt review of these shop drawings is imperative for the project schedule. Any shop drawing review over 4 weeks
will be assessed as to its impact to the schedule. Omega Mechanical will not accept or be subject to project delay
claims due to untimely shop drawing review.
Project Name
REVIEWED
REVISE
REJECTED
BY
SUBMITTAL#
DATE
SPEC
✔
Bryan Juan 5/9/2019
11R1 IFC
Basalt Company Logo
This review is only for general conformance of the project and generalcompliance. Corrections or comments made on these drawings during thisreview do not relieve Contractor/Subcontractor from compliance with therequirements of the plans and specifications. Contractor is responsible for alldimensions and fabrication to be confirmed and correlated at the job site
NOT REVIEWED
Reviewed
Reviewed as Modified
Revise
Revise and Re-SubmitNot Reviewed
Reviewed only as to general conformity with the design concept. The Engineer does notwarrant or represent that the information contained on this drawing is either accurate orcomplete. Sole responsibility for correct design, details and dimensions shall remain withthe contractor submitting the drawing. The review of this shop drawing shall not, in anyway, relieve the contractor from complying with all requirements of the contract documents.
Per,
WILLIAMS ENGINEERING CANADA INC.
By:
Date:
jjeon
05/29/2019
( )
( )
( )
( ) (X)
SHIFT ARCHITECTURE INC.
SHOP DRAWING REVIEW
Reviewed
Reviewed as Noted
Revise and Resubmit
Not Reviewed
Project
Date
Reviewed By
This review by Shift Architecture Inc. is for the sole
purpose of ascertaining conformance with the
general design concept. This review shall not mean
that Shift Architecture Inc. approves the detailed
design inherent in the shop drawings, responsibility
for which shall remain with the Contractor
submitting same, and such review shall not relieve
the Contractor of the responsibility for errors or
omissions in the shop drawings or of the
responsibility of meeting all requirements of the
contract documents. The Contractor is responsible
for dimensions to be confirmed and correlated at the
job site, for information that pertains solely to
fabrication processes or to techniques of
construction and installation, and for the
coordination of the work of all trades.
✔
6/3/2019
1505
HK
Shift Note - Comment from Brown Strachan Associates regarding acoustics (sent to Shift on May 31st 2019):
"Prior to boarding, we recommend listening tests in the corridor with the MUA operating above. A criticalrequirement is that drywall and framing be installed clear of ductwork serving the MUA or any other equipment,particularly in suites. The corridor ceiling should be loosely insulated in the vicinity of the duct. Ductwork in shaftsshould be supported at floors only (no contact to shaft walls).
During commissioning, and after all specified isolation work is complete, MUA noise should be rechecked in thesuites and corridor, preferably in the early morning, before occupancy."
DRAWING TRANSMITTAL SHEETJOB NO.58667(V22402)DATE May 02, 2019
VANCOUVER CANADIAN CANADIAN OTHER CANADIANSALES OFFICE HEAD OFFICE FACTORY SALES OFFICES303 - 8988 FRASERTON COURTBURNABY BCV5J 5H8(604) 736-2420
CALGARY AB CALGARY ABEDMONTON ABNEWMARKET ON
EDMONTON, CALGARY, SASKATOON,REGINA, WINNIPEG, LONDON, SUDBURY,TORONTO, HAMILTON, OTTAWA, MONTREAL,HALIFAX, MONCTON
CONTRACTOR OMEGA MECHANICAL LTDADDRESS 2433 HOLDOM AVE
BURNABY BCV5B 5A1
ENGINEER WILLIAMS ENGINEERING (ABBOTSFORD)JOB NAME BASALT
THIS ORDER IS SUBJECT TO APPROVAL. MANUFACTURING IS HELD PENDING RETURN OF ONE APPROVED COPY OFTHESE FORMS TO THE INDICATED OFFICE.
THIS ORDER IS NOT SUBJECT TO APPROVAL AND IS BEING MANUFACTURED ACCORDING TO THE ATTACHED FORMS.
COPIES ENCLOSED DESCRIPTION
1 EngA Submittal Revision Summary
1 EngA Submittal Record MAU-11 Heatcraft Evaporator Coil Certificate Data Sheet1 EngA Supply Fan Sound Data1 EngA Mechanical Drawing 58667M-01-11 EngA Roof Curb Drawing 58667C-01-11 EngA Internal Wiring Diagram 58667E-01-11 EngA Electrical Data Sheet MAU-11 EngA Field Wiring Diagram 58667F-01-1
1 Foam Curb Gasket Specification Sheet1 EngA Installation Operation and Maintenance Manual (LM Series)
PER BOB CORNFIELD / RLK
Condenser coil(heating mode)certificate data sheetis missing.
SUBMITTAL REVISIONSJOB NAME: BASALT 58667(V22402)JOB NO:
CUSTOMER:OMEGA MECHANICAL LTD
ENGINEER: WILLIAMS ENGINEERING (ABBOTSFORD) REVISION DATE:May 02, 2019
CHANGES AND/OR REVISIONS MADE TO THIS ORDER:
Revision:- Changed fan isolators to spring isolators.- Added Sound Calculation data.- Provided specification data sheet for curb gasket.
SUBMITTED BY:BOB CORNFIELD / RLK
SUBMITTAL RECORD
JOB NAME: BASALT 58667(V22402)JOB NO:CUSTOMER: ENGINEER:OMEGA MECHANICAL LTD WILLIAMS ENGINEERING (ABBOTSFORD)
EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1
SHIPPING AND APPROVAL INFORMATIONMOUNTING Outdoor Base Mounted c/w Prefab Seismic Roof Curb ACCESS As Per Drawing
OPERATING WEIGHT1200 lb (545 kg)UNIT MINIMUM AMBIENT0°F (-17.8°C) SHIPPING WEIGHT 1100 lb (500 kg)NO. OF PIECES 3 (Unit + Curb + Hood)
•IntertekcETL approval.
SUPPLY AIR DATAAIR FLOW 1,100 CFM (519 l/s) FAN SIZE (1) 9/7 FC DIDW TSP 2.69 in w.c. (670 Pa) RPM 1826MOTOR SIZE 1 1/2 HP (1.12 kW) TYPE (RPM)ODP (1750) ESP 1.5 in w.c. (374 Pa) BHP 0.84 BHP (.63 kW)
•Supply air fan/motor c/w seismic spring vibration isolation and pillow block bearings.•Drives have a service factor of 1.
AIR OPENING DATAAIR OPENING LOCATION DAMPER TYPE OPERATION
SUPPLY AIR BottomOUTSIDE AIR Back EngA Parallel Blade Two Position
CONSTRUCTION DATAUNIT CABINET 18 gauge satin coat galvanized sheet metal c/w 2" (51 mm) 1.5 lb/ft³ (24 kg/m³) insulation on entire unit casing.
UNIT LINER 22 gauge solid liner on coil and discharge plenum section.
UNIT FLOOR 18 gauge satin coat galvanized sheet metal on entire unit floor.
EXTERIOR PAINTElectrostatically applied Alkyd Enamel in Aluminum Gray color - Level 1 on all exterior surface but not including unitunderside.
AIRSIDE DOOR All access - hinged c/w lever type door handles
SERVICE DOOR All access - hinged c/w lever type door handle
DRAIN PAN G90 galvanized drain pan c/w floor drain connection through base frame on entire floor section.304L stainless steel drain pan c/w floor drain connection through base frame on coil (by others) section.
•Unit to be built with .- Rain gutters and down spouts on both side of unit
ELECTRICAL DATAPOWER SUPPLY MINIMUM CIRCUIT AMPACITY MAXIMUM FUSE(D.E.) MAXIMUM BREAKER208 / 1 / 60 14.1 AMPS 25 AMPS 25 AMPS
•See Electrical Data Sheet for details.
FILTER SECTION DATA - Side LoadedFILTER TYPE Dafco Pleated Filter with MERV 13 rating c/w Metal FrameQTY/SIZE 1 - 24 x 20 x 2" (610 x 508 x 51 mm) QTY/SIZETOTAL GROSS AREA 3.33 SQ.FT. (0.31 SQ. MTRS) FACE VELOCITY 330 FPM (1.68 m/s)
•Filters may be shipped loose or mounted in the tracks•Dwyer series 2000 magnehelic gauge 0-1" wc across filter section
- 1 -DATE 02-May-2019 Continued on page 2
SUBMITTAL RECORD
JOB NAME: BASALT 58667(V22402)JOB NO:EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1
DX COIL DATACOIL SIZE 18 (457) x 26 (660) x 2R x 10 FPI VELOCITY 338 FPM (1.72 m/s)
CAPACITY 29,200 Btuh (8.6 kW) AIR P.D.0.27 in.wc. (67 Pa)ENTERING AIR DB / WB 82°F (27.8°C) / 67.0°F (19.4°C) LEAVING AIR DB / WB 63.0°F (17.2°C) / 60.0°F (15.6°C)SST/SCT 42°F (5.6°C) / 100°F (37.8°C) REFRIGERANT TYPE R-410ADISTRIBUTOR TYPE (1) 5/8" SUCTION SIZE 7/8 in (22 mm) QUANTITY 1
•Heatcraft coil provided and installed by EngA c/w auxiliary drain pan(1/2"(13 mm) drain connection) and drain pan.•Coil control and all associated components are by others.
SHIPPED LOOSE ITEMS (See filter section for filters)1 - Pre fabricated seismic roof curb (See drawing for details).1 - Inlet hood c/w 1"(25 mm) birdscreen.
- 2 -DATE 02-May-2019 SUBMITTED BYBOB CORNFIELD / RLK
$1 i ftpwrwt"ivrsrtr heh{trans!erN G (J Lu l(l coils
/1'n4R>ogniv
%?'
COILCALC EVAPORATOR
Customer
Contact
Telephone
Proiect
Engineered Air
Geoff Gorai
(26064) Basalt - C8-15-28
Date
BY
Company
Return Telephone
2/7/2019 5:05:48 PM
Pavlos Pavlides
Modine CIS
662-614-7374
CONSTRUCTION
Item
Coils in bank
Style
Tube OD
Fins per inch
Rows
Fin surface
Fin height / Length
Tubing material
Fin material
Circuiting
Face area
in
in/
in
in
in
sqft
Default #1
1
EN
3/8
10
2
Optimize ABC
18.00 / 26.00
0.C)16 Copper
0.0050 Aluminum
-3
3.25
AIR SIDE
Air flow (Standard)
Altitude
Entering air (db) / (wb)
Leaving air (db) / (wb)
Total / Sens. capacity
Max air PD
REFRIGERANT SIDE
Refrigerant
Super heat temp.
Saturated suc. temp.
Liquid temp.
cfm
fl
oF
oF
MBH
in wg
A"F
"F
oF
i,ioo.oo
o.oo
82.00 / 67.00
63.00 l 60.00
0.00
R-410A
8.0
42.0
100.0
OUTPUT DATA
Model number
FPI i Rows i Surf
Circuit
Air velocity (Standard)
Total capacity
Sensible capacity
Lvg. air DB
Lvg. air WB
Standard APD
Code 18/19 #1
Code 18/19 #2
Suction conn.
Distributor conn. 1
Distributor conn. 2
Refrigerant PD
Refrigerant velocity
Internal volume
Weight
Notes
ft/min
MBH
MBH
oF
oF
in wg
in
in
in
psi
ft/min
ills
lbs
COIL1
3ENi202A
12102iA
Normal
338
25.3
17.7
67.12
60.04
0.068
6003/1-1/2
N/A
(1)0.875
(1 ) 0.500
(0) 0.000
3.70
1,262.78
110.7
36.9
CM
MOST ECONOMICAL
COIL2
3ENO802B
08 i02 i B
Normal
338
26.1
18.8
66.20
59.80
0.091
6003/1-1/2
N/A
(1 ) 0.875
(1 ) 0.500
(0) 0.000
3.91
1 ,303.26
110.7
34.6
CM
COIL3
3ENO802C
081 021 C
Normal
338
28.2
20.7
64.60
59.18
0.123
7003/1-1 /2
N/A
(1 ) 0.875
(1 ) 0.500
(o) o.ooo
4.45
1 ,405.70
110.7
34.6
CM
COIL4
3EN1002A
l0i02iA
Normal
338
22.9
15.8
68.71
60.75
0.055
6003/1-1/2
N/A
(1 ) 0.875
(1)0.500
(o) o.ooo
3.12
1,143.26
110.7
35.8
CM
SPEC?FIED COIL
COILs J3EN1002B
lOl021B
Normal
338
29.2
21.2
64.14
58.87
0.112
7003/1-1/2
N/A
(1)0.875
(1 ) 0.500
(0) 0.000
4.73
1,456.82
110.7
35.8
CM
COIL6
3EN1002C
lOl021C
Normal
338
:31.3
23.2
62.51
58.22
0.152
7003/02
N/A
(1)0.875
(t)o.soo
(o) o.ooo
5.34
1,560.79
*10.7
35.8
CM
NOTES FROM CALCULATIONS
C) Coil is NOT cer(i{ied by AHRI.M) Coil racing valid for Hea{crafl coils only.
USER NOTES
Copyright 2003 Modine Grenada LLC Confidentral and Proprietary. Thrs design is for the exclusive and confidential use of Modrne Grenada LLCand-its-clrent. Any duplicalron made for lhe purpose of disclosrng this desrgn or any part of the design to a competrlor of Modine Grenada LLC isin direct vrolation of khis confidentiality. Any duplrcalion must be approved rn writing by Modine Grenada.
Page 1 of 1
April 29, 2019Unit Sound Data
JOB NAME: JOB NUMBER:
UNIT TAG:INSTALLATION:
SOUND SOURCE DATA:
UNIT CONSTRUCTION:
UNIT S/A OUTLET:
UNIT O/A INLET:
UNIT CASING *:
* Unit casing sound includes casing breakout and sound sources outside the air streams only. Sound from openings are not included in unit casing sound.
Note:Unit sound data are calculated for the specified unit construction and operating condition as shown above.
generated byDATE: DRWN BY: CHKD BY: DRWG NO.:
REVISIONS:
TAG:58667(V22402)
MAU-1LM1/C/O/V
AIR HANDLING UNIT
JAN 22 2019 RLK MXC 58667M-01-1
DOOR SIZES AND INTERNAL COMPONENTS ARE APPROX. VALUES. DIMENSIONS SHOWN IN INCHES ONLY UNLESS OTHERWISE NOTED.
ACCESS
PLENUM SECTION
SUPPLYAIR
COIL SECTION
ACCESS
BLOWER/MOTOR SECTION
OUTSIDEAIR
ACCESS
INLE
T H
OO
DC
/W B
IRD
SCR
EEN
8 [203] 6 [152] 24 [610]
113 [2870]
16 [406] 30 [762]
FILTERGAUGE
LINED SECTION
36 [914]
PROVIDED AND INSTALLED BY ENGA
ACCESS
36 [914]
8 [203]CONTROL
PANEL
4 [102]
RAIN GUTTERBOTH SIDES
CONTROL PANEL
60°
24
5 [127]
1. UNIT SUPPORT FOR WIND LOAD BY OTHERS.
8 [203]
2. UNIT SUPPORT FOR SEISMIC EVENT BY OTHERS.
1-1/2''ØBLK IRONDRAIN CONNECTION
3. UNIT IS NOT DESIGNED TO SURVIVE SEISMIC EVENT.
4. DRAIN PAN IN DUCT WORK BY OTHERS.
SOLIDLINER
HEATCRAFT COIL
DesignCube°generated by
DATE: DRWN BY: CHKD BY: DRWG NO.:
REVISIONS:
TAG:DRAWING NOT TO SCALEJOB# 58667(V22402)
MAU-1LM1/C/O/V
12'' HIGH SEISMIC CURB FOR DOWN DISCHARGE UNIT
FEB 13 2019 RLK MXC 58667C-01-1
Gen
erat
ed b
y A
utoC
urb
- ver
sion
2.2
.671
.155
- C
urb
Sty
le #
2Jo
b fil
enam
e =
G:\C
alga
ry\C
urre
nt D
esig
ners
\Roh
it Ku
mar
\586
67\M
AU-1
\Cal
c an
d C
oil A
utom
ate\
5866
7-SE
ISM
IC.c
rb1. 3/8'' X 3/4'' (10 X 19) NEOPRENE GASKET FOR 2'' (51) TO 4'' (102) CHANNELS, OR 3/8'' X 1-1/2'' (10 X 38) NEOPRENE GASKET FOR CHANNELS 6'' (153) AND OVER.2. CURB MAY BE BROKEN DOWN FOR SHIPPING. IN THESE CASES, FIELD ASSEMBLY WILL BE REQUIRED BY INSTALLING CONTRACTOR.3. CONTINUOUS BASE SUPPORT TO CURB PANELS, INCLUDING THE CENTER SUPPORT PANEL IF SUPPLIED, IS REQUIRED BY OTHERS.4. DIMENSIONS GIVEN IN INCHES AND MILLIMETRES
12''(305)
4'' (102)
17''(432)
15 1/4''(387)
AA
SUPPLYAIR FLOW
INS
IDE
TO IN
SID
E C
UR
B W
ALLS
1"(25)
INSIDE TO INSIDE CURB WALLS
1"(25)
SUPPLYAIR
INSULATIONFACTORY
(BY OTHERS)
FLASHING (BY OTHERS)
(51)2"
(10)3/8"
MOUNTED (SEE NOTE 1)NEOPRENE GASKET FIELD
TAR AND GRAVELCANT STRIP (BY OTHERS)
ROOFING PAPER (BY OTHERS)
FACTORY MOUNTED2" X 4"(51 X 102)
Z-BAR WELDED TO CURB
BASECHANNEL
4'' X 2'' X 3/16'' (102 X 51 X 5) ANGLE. PRE-DRILL FOR 1/2''(13) BOLT
2" X 2" X 0.25" (51 X 51 X 6) ANGLE. DRILL AT INSTALLATION
TO SATISFACTION OFSECURE TO STRUCTURE -
(38 X 38 X 3)1 1/2" X 1 1/2" X 1/8"
CURB AT INSTALLATION (BY OTHERS)WELD BRACKET TO ROOF
REINFORCEMENT BRACKET
SEISMIC ENGINEER
(SHIPPED LOOSE)
1/2" (13) HOLES AT 24" (610) C-CIN CENTER OF BOTTOM FLANGE
3''
TYP.
2"
2"(51)
(51)(76)
B
B
3"(76) TYP
DOWN DISCHARGESA COLLAR
RIGID INSULATION (BY OTHERS)
30 1/2''(775)
26 1/2''(673)
36 1/4''(921)
32 1
/4''
(819
)
12'' (305)
(2) HOLDING ANGLES AT 10 1/2''(267) CENTERS
(2) H
OLD
ING
AN
GLE
S AT
16
1/4
''(41
3) C
EN
TER
S
10''(254)
10''(254)
10''(254)
10''(254)
8''(203)
4 1/8''(105)
24''(610)
(2) BRACKETS TOTAL:(1) IN LENGTH
3 1/4''(83)
ELECTRICAL DATAJOB NAME: BASALT 58667(V22402)JOB NO:
EngA MODEL: QTY: TAG:LM1/C/O/V 1 MAU-1
PowerSupply
Minimum CircuitAmpacity
Terminal Block toAccept
Maximum Fuse(Dual Element)
Maximum Breaker
208 / 1 / 60 14.1 AMPS 14 Awg 25 AMPS 25 AMPS
Components Model MinimumConductor Size
AmpacityFLA / LRA
Supply Fan Motor ODP (1750) 1 1/2 HP 14 Awg 11.0Main Control Xfmr 14 Awg .4
UNIT CONTROL PANEL(S) SHORT CIRCUIT CURRENT RATING (SCCR)Short circuit current 5 kA rms symmetrical, 208 V maximum
WIRING DRAWING LEGENDAPS Air Proving SwitchASF Auto Fan SwitchAUX Auxiliary ContactBM Burner MotorC ContactorCCH Compressor Crankcase HeaterCFC Condenser Fan ControlCLC Compressor Loading ControlCPM Compressor Protection ModuleCR Cooling RelayCS Current SensorDHSS Draft Hood Spill Switch
DM Damper MotorFR Fan RelayGND GroundGV Gas ValveHL High LimitHPC High Pressure ControlHR Heating RelayIGN Ignition ControlITP Internal Thermo ProtectionLPC Low Pressure ControlM MotorMV Main Gas Valve
NFD Non Fused DisconnectOL Thermal OverloadPS Pressure SensorPV Pilot Gas ValveR RelayRevHLReverse Airflow High LimitTB Terminal BlockTDF Time Delay FuseTDR Time Delay RelayTS Temperature SensorVFD Variable Frequency DriveXFMR Transformer
UNIT FUNCTION
Disconnect switch (by others) 'on', service switch 'on', fire alarm contact (by others) 'closed' (jumper if not required).
Unit on/off contact (by others) 'closed'. Blower starts and runs continuously.
Unit on/off contact (by others) 'open'. Unit is off.
Coil control and all associated components are by others.
Note 1 - Refer to manuals shipped with unit for a more detailed explanation of maintenance, component(s) and/or controller(s).
DATE:02-MAY-2019 SUBMITTED BY:BOB CORNFIELD / RLK
P8600 Series Vinyl Nitrile Foam Tape
2600 E. 107th Street | Bolingbrook, Illinois 60440 | TOLL FREE: 800.323.7467 | FAX: 630.628.8025 | [email protected] | PresOn.com
Product Description
Pres-On P8600 Series Vinyl Nitrile Foam Tape’s uniform, closed-cell structure resists the absorption of water and other fluids.
Its high-performance, permanent acrylic adhesive bond is ideal for sealing, gasketing, weatherproofing, thermal insulating,
absorbing shock and dampening vibration.
Applications
P8600 is widely utilized for roof curb sealing, pipe wrapping, filter gasketing and a variety of other demanding HVAC applications.
• Composed of a vinyl/nitrile closed-cell foam blend
• Resists moisture, fire and chemicals
• Pressure sensitive acrylic adhesive exhibits high initial grab
• Provides a long lasting, permanent bond
• Uniform cell structure lends dimensional stability
TECHNICAL DATA
STANDARD ROLL SIZE SERIAL NUMBER THICKNESS LENGTH
All rolls available in widths from 1/4” to 54” P8612 1/8” 30’ or 50’
P8618 3/16” 50’
P8625 1/4” 50’
P8637 3/8” 25’
P8650 1/2” 25’
P8675 3/4” 25’
P861 1” 25’
ADHESION PROPERTIES TEST TYPICAL PERFORMANCE TEST METHOD
Adhesion to Steel @ 72°F Steel immediate Steel after 24 hours
2.5 lbs/in width or foam tear 4.0 lbs/in width or foam tear
PSTC-1PSTC-1
Adhesion to Steel, 15 min dwell 4.3 - 6.4 lbs/in PSTC-1
Adhesion to Steel, 24 hour dwell 6.0 lbs/in PSTC-1
Shear 1” x 1”, 500 gms 1000 hours PSTC-7
Shear 1” x 1”, 1000 gms 200 hours PSTC-7
Optimal Application Temperature 50°F to 80°F Pres-On PTM-1
Functional Temperature 0°F to 225°F Pres-On PTM-2
Water and Humidity Resistance Excellent Pres-On
Shelf Life 1 year stored at room temp
P8600 Series Vinyl Nitrile Foam Tape
2600 E. 107th Street | Bolingbrook, Illinois 60440 | TOLL FREE: 800.323.7467 | FAX: 630.628.8025 | [email protected] | PresOn.com
PHYSICAL PROPERTIES TEST METHOD UNIT OF MEASURE RESULT
Density ASTM D-1667 lbs/ft2 3.0 - 6.0
Tensile Strength ASTM D-412 psi 25 minimum
Shore OO Durometer -- -- 30
Compression Force 25% Deflection
ASTM D-1056 psi1.5 - 3.0
Compression Set 50% ASTM D-1056 35 maximum
Temperature Range -- °F -40° to 220°
Water Absorption ASTM D-1056 -- 10% maximum
Thermal Stability(% change in length, 7 days @ 220°F)
ASTM C-548 %10 maximum
Thermal Conductivity(BTU-IN/HR/SQ FT)
ASTM C-177 BTU-IN0.290 maximum
Ozone Resistance ASTM D-1171 Pass/Fail Pass
Fluid Immersion ASTM D-1056 100 maximum
Mold Growth UL 181 Pass/Fail Pass
Fungi Resistance ASTM G 21/C 1338 Pass/Fail Pass
Bacterial Resistance ASTM G 22 Pass/Fail Pass
Flammability RatingMVSS302UL 94HF1
Pass/FailPass/Fail
PassPass
Application NotesEnsure bonding surfaces are well unified, clean, dry and free of dirt and oils. Apply firm and even pressure to improve adhesive-to-
surface contact. Allow proper temperature and time to enhance bond strength as adhesive flows onto the surface.
IN NO EVENT WILL PRES-ON OR ANY OF ITS AFFILIATES BE LIABLE FOR ANY DIRECT OR INDIRECT DAMAGES, CLAIMS, OR LOSSES WHATSOEVER (INCLUDING, BUT NOT LIMITED TO, INCIDENTAL DAMAGES, CONSEQUENTIAL DAMAGES, LOST PROFITS AND/OR LOST OPPORTUNITIES) RESULTING FROM OR RELATED TO THIS PRODUCT OR THE USE, MISUSE, PURCHASE, OR SALE OF THIS PRODUCT, WHETHER BASED ON WARRANTY, CONTRACT, TORT, OR ANY OTHER LEGAL THEORY, WHETHER OR NOT FORESEEABLE, AND WHETHER OR NOT ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. Any specifications, instructions, or other information provided by Pres-On in connection with this product are provided for informational purposes only and shall not be deemed to impose any representations, warranties, covenants or other obligations upon Pres-On or any of its affiliates.