revised quantity for amendment-2 04.02.11
TRANSCRIPT
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 1/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Title : REVISED PRICE SCHEDULE FOR Amendment - 2 Rev:2 21.01.2011
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
1 Transformers
1.1 Unloading, Installation, testing & commissioning of the
following oil immersed transformers, including charges for
s ecified site tests:
a) 40/50 MVA, 132/33 kV,dyn11 Power transformer with 2 No. 95200 190400
OLTC along with RTCC panel
1.2 Su l of necessar rails 90 LB and embedments shall 16 M
Supply Installation
Supplied by Client
form art of the sco e.
Total in Rupees 44544 191856
3 Clients 132kv switchyard
Incoming bay
3.1 Motorised 132KV, 1250A, 31.5 kA Horizontal Double Break
Isolator complete with insulators control gear etc. (for
APTCL suitable for olluted areaa. with earth switch 2 Sets 244200 488400 4550 9100
b. without earth switch 2 Sets 210900 421800 4550 9100
3.2 132 kV SF6 1250A, 31.5 kA circuit breakers 2 No. 665100 1330200 16380 32760
3.3 Line Metering & Protection-3 core 6 Nos.149200 895200 2730 16380
for PS class
conversionCore -1 : 300-150/1A, CL-0.2, 30VA
Core -2 : 300-150/1A, CL-5P20, 30VA
Core -3 : 300-150/1A, CL-PS, Vk=650 V
4 Transformer bay Nos
Page 1 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 2/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
4.1 Motorised 132KV, 1250A, 31.5 kA Horizontal Double Break
Isolator complete with insulators control gear etc. (for
APTCLa. with earth switch 2 Sets 244200 488400 4550 9100
b. without earth switch 3 Sets 210900 632700 4550 13650
4.2 132kV SF6 1250A, 31.5 kA circuit breakers 2 No. 665100 1330200 16380 32760
4.3 Transformer Metering & Protection-3 core 6 Nos. 172500 1035000 2730 16380
Core -1 : 300-150/1A, CL-0.2, 30VA
Core -2 : 300-150/1A, CL-5P20, 30 VA
Core -3 : 300-150/1A, CL-PS,
4.4 40/50MVA Tranmsformer Neutral CTs
1200/1A, Cl: PS 2 Nos 16650 33300 1950 39001200/1A, Cl: 5P10, 20VA 2 Nos 16650 33300 1950 3900
4.5
Single phase oil cooled potential transformers- 2 core 6 Nos. 139200 835200 2730 16380
132 KV / 110V / 110V
√3 √3 3Class - 0.2, 50 VA
Class - 3P, 50 VA
4.6 120KV, 10KA, Lightning Arrestor Complete with base and
discharge counter.
6 Nos42960 257760 1820 10920
4.7 I)Junction Boxes for the instrument transformers 7 Nos. 6380 44660 910 6370
II) Marshalling Box 2 No. 45240 90480 2275 4550
4.8 Switchyard structure comprising of GI structures, GI nuts,
and bolts and foundation bolts
1 LS2207709 2207709 220900 220900
4.9 Bus bar materials ( qnty indicated are tentative ) 1 LS 379664.5 379664.5 73500 73500
4.9.1 - ACSR Moos conductor (50Hz) for over head bus
Page 2 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 3/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
4.9.2 Rigid clams & connectors4.9.3 CT's-4.9.4 PT's -4.9.5 Isolators4.9.6 LA's -4.9.7 Transformer
4.9.8 Breaker4.9.9 Bus post clamp4.9.10 T-connectors suitable for Moose condocdor
4.9.11 PG / Tension clamps for ACSR conductors and shield wire
5 Insulators
I)Tension string insulators suitable for 132 KV system 18 Sets 10767 193806 546 9828
uspens on str ng nsu ators u ta e or system ets
III) 132 KV Bus post solid core type insulators 22 Nos 11988 263736 910 20020
11046430.5 514412
6 Control & Relay Panels6.1 40/50MVA 132/33KV Trnasformer C&R panel 2 Nos 888000 1776000 16380 32760
6.2 132kv Incoming Contorl & Relay panel 2 Nos 815000 1630000 16380 32760Total in Rupees 3406000 65520
7 Cable Trays & Accessories
7.1 Galvanised cable trays of ladder type, for the above cables
alongwith supports. Trays for switchyard area be
consideredonl toa) - 450 mm wide cable tray (inside switchard only) 1550 M 694 1075700 41 63550b) - 300 mm wide cable tray (inside switchard only) 610 M 431 262605 40 24400c) - 150 mm wide cable tray (inside switchard only) 707 M 267 188769 25 17675d) - Supports for cable trays (inside switchard only) 3 MT 44080 132240 13830 41490
Total in Rupees 1659314 147115
8 33KV Switch yard
8.1 33KV, 31.5 kA Horizontal Double Break Isolator complete
with 2 nos of 22kv insulators stack etc.a. 1600A with earth switch 2 Sets 91640 183280 2730 5460
b. 800A with earth switch 8 Sets 68440 547520 2730 21840
for Distance
relay
Page 3 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 4/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
c. 1600A without earth switch 1 Sets 80040 80040 2730 2730
d. 800A without earth switch 20 Sets 60320 1206400 2730 54600
e. 800A with earth switch 8 Sets 68440 547520 2730 21840
8.2 1200/1-1-1A, Current Transformer 6 Nos. 41850 251100 2730 16380
Metering & Protection- 3core
Core -1 : 1200/1A, CL-0.2, 30VACore -2 : 1200/1A, CL-5P20, 30 VA
Core -3 : 1200/1A, CL-PS,
8.3 600/1-1-1A, Current Transformer 12 Nos. 34635 415620 2730 32760
-
Core -1 : 600/1A, CL-0.2, 30VA
Core -2 : 600/1A, CL-5P20, 30 VA
Core -3 : 600/1A, CL-PS,
8.4 150/1-1A, Current Transformer 12 Nos. 34635 415620 2730 32760
Metering & Protection-3 core
Core -1 : 150/1A, CL-0.2, 30VA
Core -2 : 150/1A, CL-5P20, 30 VA
8.5 75/1-1A Current Transformer 24 Nos. 34635 831240 2730 65520
Metering & Protection-3 core
Core -1 : 75/1A, CL-0.2, 30VA
Core -2 : 75/1A, CL-5P20, 30 VA
8.6 Single phase oil cooled potential transformers- 2 core 6 Nos. 34292.3 205753.8 2730 16380
33 KV / 110V / 110V √3
√3 √3Core 1 - Class 0.5, 50 VA
Core 2 - Class 3P, 50 VA
8.7 Single phase oil cooled potential transformers- 1 core 6 Nos. 37292.3 223753.8 2730 16380
Page 4 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 5/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
33 KV / 110V / 110V √3
√3 √3Core 1 - Class 0.5, 100 VA
8.8 30KV, 10KA, Station class Lightning Arrestor Complete with
base and dischar e counter.
18 Set36060 649080 2786 50148
8.9 I)Junction Boxes for the instrument transformers 22 Nos. 6380 140360 910 20020
9 Switchyard structure comprising of GI structures, GI nuts,
and bolts and foundation bolts
1 LS1478292 1478291.85 87750 87750
10 Bus bar materials ( Double bus bar system ) 1 LS 1529433 1529432.5 253097 2530970 Bus bar materials ( Double bus bar system )
- ACSR Twin moose conductor (50Hz) for over head bus
Rigid clams & connectors
Breakers-
CT's -
PT's -
Isolators -
LA's -
Capacitor -
Bus post clamp -
T-connectors suitable for Panther condocdor -
Spacers
11 InsulatorsI)Double Tension string insulators suitable for 33 KV system 12 Sets 9213 110556 390 4680
II) single Tension string insulators suitable for 33 KV system 12 Sets 3497.5 41970 273 3276
III)Suspension string insulators Suitable for 33KV system 6 Sets 2886 17316 273 1638
IV) 22 KV Bus post insulators (2 nos per set) 78 Sets 1887 147186 292.5 22815
9022039.95 730074
12 Cables and Terminations
12.1 33 KV Cables & Terminations
Page 5 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 6/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
Laying of 33 kV (E) C x 630 sq. mm grade stranded,
aluminium conductor, XLPE insulated, armoured PVC
overall sheathed, to bury in underground trenches or
overhead trays having following sizes to run on cable trays
Engraved aluminium tags shall be provided at both the ends
of cables for identification ur ose.a) 33 kV cables:
1Cx630 Sq.mm XLPE Cable (Approx) 1450 M 927.4138 1344750 48.9310345 70950
Termination shall include termination kits (for 33 kV
cables), including all terminating materials and ferrules
com lete of all termination.with su lb Termination kits for the above:
a. Outdoor Termination for 1Cx630 Sq.mm XLPE Cable 24 Nos 6771 162504 910 21840
12.2 1.1 KV Cables (Laying & Terminations) 1 LS 3609993 3609993 285655 2856551.1 kV Grade PVC insulated, PVC sheathed armoured power
and control cables and termination arrangements, for
Switchyard including control cables of generator
transformer, RTCC panel, Distribution transformers and
I) Power Cables- Layinga) 3.5 C x 150 sq. mm Al. Cable 275 M
b) 3.5C x 35 sq. mm Al. Cable 665 M
c) 2C x 10 sq. mm Al Cable 600 M
II) Control Cables (Cu)-Laying
a) 19 C x 2.5 Sq.mm Cable 500 M
b) 14 C x 2.5 Sq.mm Cable 1500 M
c) 7 C x 2.5 Sq.mm Cable 1200 M
d) 5 C x 2.5 Sq.mm Cable 5000 M
e) 4 C x 4 Sq.mm Cable 8500 M
f) 3 C x 2.5 Sq.mm Cable 4000 M
g) 2 C x 4 Sq.mm Cable 600 M
Page 6 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 7/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
III) Power Cables- termination
a) 3.5 C x 150 sq. mm Al. Cableb) 3.5C x 35 sq. mm Al. Cablec) 2C x 10 sq. mm Al. Cable
IV] Control Cables (Cu)-Termination
a) 19 C x 2.5 Sq.mm Cableb) 14 C x 2.5 Sq.mm Cablec) 7 C x 2.5 Sq.mm Cabled) 5 C x 2.5 Sq.mm Cablee) 4 C x 4 Sq.mm Cablef) 3 C x 2.5 Sq.mm Cable) 2 C x 4 S .mm Cable
5117247 378445
13 Earthing & Lightning Protection
Earthing & Lightning protection for switchard including
neutral / body earthing of 16/20MVA trafo. Furnace trafo.
and Distribution trafo.
1 LS 2023844 2023844 383998.7 383998.7
a) - 7/9 SWG Shield wireb) - 75 x 10 GI Flat (main earth mat)c) - 50 x 6 GI Flat (Eqpt./cable tray)d) - 8 SWG GI Wire (Fencing)
e)
- Treated earth pits 100 mm dia, 2.7M long CI pipe
electrode (PT/FT/DT/Switchyard area)h)
Total in Rupees 2023844 383998.7
14 33 KV outdoor Breakers
33 KV VCB 26.3 KA Panel ( As per SLD and specifications)
14.1 I/C - 1600A 2 Nos 287500 575000 13650 27300
Page 7 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 8/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
14.2 O/G -1600A 8 Nos 287500 2300000 13650 10920014.3 800A for capacitor bank 8 Nos 287500 2300000 13650 109200
Total in Rupees 5175000 24570015 33Kv C&R Panels
15.1 Capcitor bank control & Relay Panel 8 Nos 303051 2424408 7735 6188015.2 33KV Breaker Control and Relay panel 2 Nos 303051 606102 7735 15470
15.3 2.5MVA Transformer Control & Relay Panel 4 Nos 303051 1212204 7735 3094015.4 Furnace transformer breaker Control & Relay Panel 4 Nos 303051 1212204 7735 3094015.4 7.9MVAR & 3.8MVAR Capacitor bank with NCT 8 Nos 0 91000 728000
5454918 867230
16 Miscellaneous items:
16.1 Batter char er cum DC DB with 110 V DC 200 AH ratin 1 No.
with VRLA batteries sets stand , char er.
16.2 DCDB (Control Room )- with 160A, 2 pole MCCB incomer
outgoings. MCBs shall be suitable for DC duty.,3 nos 63 A
DP , 9nos 32A DP MCB
1 No60611 60611 4550 4550
16.3 ACDB ( Control Room )- with 1 No.200A, TPN MCCB
incomer and 2 nos 125 A TPN MCCB , 2 Nos of 63A and 2
Nos out oin feedersof 32A TPN MCB
1 No.57304 57304 4550 4550
16.4 Outdoor IP 65 DCDB ( Switchyard)- with 63A, 2 pole MCB
incomer outgoings. MCBs shall be suitable for DC duty.and
15nos 16A, 2 ole MCB
1 No.24244 24244 4550 4550
16.5 Outdoor IP65 ACDB ( Switchyard)- with 1 No.125A, TPN
MCCB incomer and 1 No 100A MCCB and 6 Nos out
oin feedersof 16A TPN MCB
1 No.41876 41876 4550 4550
Total in Rupees 761483 40950
17 Lighting
17.1 Switchyard Lighting : 1 LS 205170.1 205170.05 32500 32500
Page 8 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 9/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
17.2 Control room building elecrification 1 LS 178739.3 178739.25 49238 49237.5
17.3 Power Transformer Fire protection system 1 LS 940734 940734 97500 97500.13
Total in Rupees 1324643.3 179237.63
18 Switchyard Engineering & Site services18.1 Engineering for switchyard including preparation and
submission of engineering drawings, documents as specified
in the tender
1 LS250000 250000
18.2 Statutory approval
Pre aration & submission of com lete drawin s for the 1 LS
statutory authority / Electrical safety authority approval,
certificates for the complete installation under the arranging
for ins ection and ettin safet sco e.
300000 300000
18.3 Carrying out of pre-commissioning checks for the complete
equipment in the scope of erection & commissioning.The
verification of relay configuration and settings shall also
include numeric relays by the relay manufacturer.
1 LS
400000 400000 for Relay setting
18.4 Charges for submission and obtaining approval from APTCL
for the equipment, structures, related drawings / documents
and erection work under APTCL's supervision scope. Thisscope also includes the charges for arranging inspection and
obtaining necessary clearances from APTCL for the
equipment under APTCL supervision scope.
1 LS
100000 100000
Total in Rupees 1050000
SUMMARY Revised
1 Transformers 44544 191856
2 Clients 132KV switchyard 11046430.5 514412
3 132 kv Control Panels 3406000 65520
Page 9 of 10
8/3/2019 Revised Quantity for Amendment-2 04.02.11
http://slidepdf.com/reader/full/revised-quantity-for-amendment-2-040211 10/10
M/s. Anjaney Alloys Ltd. ANNEXURE ‐ 1 Powertech Constructions Pvt. Ltd
Sr. No. Particulars QTY Unit REMARKS
Unit Unit RateRevised Total
AmountUnit Rate Total
Supply Installation
4 Cable Trays & Accessories 1659314 147115
5 33KV Switchyard 9022040 730074
6 Cables and Terminations 5117247 378445
7 Earthing & Lightning Protection 2023844 383998.7
8 33 KV outdoor Breakers 5175000 245700
9 33kv Control & Relay Panels 5454918 867230
10 Miscellaneous items: 761483 4095011 Lighting 1324643.3 179237.63
12 Switchyard Engineering & Site services 1050000
13 Spare 1447092
46482555.9 4794538.33
TOTAL 51277094.2
Page 10 of 10