rexc series - solarking.co.nz · email: [email protected] website: discharge curve at different rate...

2
End voltage per cell 1hr 3hr 5hr 8hr 10hr 24hr 48hr 72hr 120hr 1.75V 226.2 104.0 72.2 50.6 42.1 18.8 9.70 6.60 4.20 1.80V 211.9 100.8 70.5 49.6 41.2 18.5 9.50 6.50 4.10 1.88V 183.2 93.6 67.5 47.6 39.8 17.7 9.20 6.10 4.00 1.85V 191.3 95.6 68.2 48.2 40.1 17.9 9.20 6.30 4.00 1.83V 198.4 97.5 68.9 48.7 40.3 18.1 9.30 6.40 4.00 227 170 108 291 REXC series REXC series REXC-400 REXC-400 Dimension (mm) Feature Parameter Application Nominal Voltage 2V Capacity 400Ah (10hr to 1.80V/cell @25) 480Ah (120hr to 1.85V/cell @25) Typical Weight 32kg Internal Resistance Approx 0.30mΩ Short-Circuit Current Self Discharge Temperature Ranges Operation(recommended):15℃~25Operation(maximum):-40℃~50Max. charging current 120A Max. constant charging current 80A Charge Voltage Floating:2.25V (25) Equalizing/ Cycle: 2. 30V(25) Terminal M8 embedded copper Terminal Hardware Torque >10N·m Constant Current Discharge Characteristics Units : Amperes(25) End voltage per cell 15min 30min 1hr 2hr 3hr 4hr 5hr 6hr 8hr 10hr The residual capacity is above 90% after 90 days storage (25) 6107A Renewable energy storage l Smart power grids and microgrids system l Distributed energy storage system l Hybrid energy storage system such l as solar and wind Home energy storage system l Solar power generation grid/off-grid l energy storage system Emergency lighting system l Generator and battery hybrid energy system l Other standby, cycling system l Design life 20 years l Combine the advantage of lead acid battery l and supercapacitor Ideal for PSOC cycle application l High power, repid charge/discharge l Reduce sulfation of negative plate, excellent l recharge acceptance performance Waterproof, anti-salt treatment, shockproof l module installation design Comply with IEC60896,IEC61427 etc. standard l Discharge Data with Constant Power Units : Watts per cell(25) 1.75V 986.5 717.2 456.8 299.5 231.8 175.5 149.0 128.3 98.1 82.4 1.80V 922.9 693.4 446.2 293.9 206.3 169.8 144.9 124.5 95.6 81.1 1.83V 886.5 656.3 430.3 282.2 201.2 167.3 141.9 120.7 93.7 79.6 1.85V 843.9 621.2 405.8 270.1 195.3 163.3 138.1 117.9 92.4 78.0 1.88V 636.9 580.6 381.3 251.0 188.7 157.7 133.6 113.7 89.9 76.1 303

Upload: others

Post on 05-Jun-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REXC series - solarking.co.nz · Email: intl@narada.biz Website: Discharge curve at different rate (25℃) Dischar ge voltage (V) Capacity vs OCV curve O C V (V) Capacity (%) Residue

End voltage per cell 1hr 3hr 5hr 8hr 10hr 24hr 48hr 72hr 120hr

1.75V 226.2 104.0 72.2 50.6 42.1 18.8 9.70 6.60 4.20

1.80V 211.9 100.8 70.5 49.6 41.2 18.5 9.50 6.50 4.10

1.88V 183.2 93.6 67.5 47.6 39.8 17.7 9.20 6.10 4.00

1.85V 191.3 95.6 68.2 48.2 40.1 17.9 9.20 6.30 4.00

1.83V 198.4 97.5 68.9 48.7 40.3 18.1 9.30 6.40 4.00

227 170

108

29

1

REXC seriesREXC seriesREXC-400REXC-400

Dimension (mm)

Feature

Parameter

Application

Nominal Voltage 2V

Capacity 400Ah (10hr to 1.80V/cell @25℃)

480Ah (120hr to 1.85V/cell @25℃)

Typical Weight 32kg

Internal Resistance Approx 0.30mΩ

Short-Circuit Current

Self Discharge

Temperature Ranges Operation(recommended):15℃~25℃

Operation(maximum):-40℃~50℃

Max. charging current 120A

Max. constant charging current 80A

Charge Voltage Floating:2.25V (25℃)

Equalizing/Cycle:2.30V(25℃)

Terminal M8 embedded copper

Terminal Hardware Torque >10N·m

Constant Current Discharge Characteristics Units: Amperes(25℃)

End voltage per cell 15min 30min 1hr 2hr 3hr 4hr 5hr 6hr 8hr 10hr

The residual capacity is above 90% after 90 days storage (25℃)

6107A

Renewable energy storagel

Smart power grids and microgrids systeml

Distributed energy storage systeml

Hybrid energy storage system suchl

as solar and wind Home energy storage systeml

Solar power generation grid/off-grid l

energy storage system Emergency lighting system l

Generator and battery hybrid energy systeml

Other standby, cycling systeml

Design life 20 yearsl

Combine the advantage of lead acid battery l

and supercapacitor Ideal for PSOC cycle application l

High power, repid charge/dischargel Reduce sulfation of negative plate, excellent l

recharge acceptance performanceWaterproof, anti-salt treatment, shockproof l

module installation design Comply with IEC60896,IEC61427 etc. standardl

Discharge Data with Constant Power Units: Watts per cell(25℃)

1.75V 986.5 717.2 456.8 299.5 231.8 175.5 149.0 128.3 98.1 82.4

1.80V 922.9 693.4 446.2 293.9 206.3 169.8 144.9 124.5 95.6 81.1

1.83V 886.5 656.3 430.3 282.2 201.2 167.3 141.9 120.7 93.7 79.6

1.85V 843.9 621.2 405.8 270.1 195.3 163.3 138.1 117.9 92.4 78.0

1.88V 636.9 580.6 381.3 251.0 188.7 157.7 133.6 113.7 89.9 76.1

30

3

Page 2: REXC series - solarking.co.nz · Email: intl@narada.biz Website: Discharge curve at different rate (25℃) Dischar ge voltage (V) Capacity vs OCV curve O C V (V) Capacity (%) Residue

2hr

10hr

4hr

20 10 0 10 20 30 40 50

20

40

60

80

100

2.20

2.00

1

1.80

1.60

1.40

1.20

C120C10

C3C1

2.12

2.05

1.98

1.91

1.84

2.19

HourMinute

1C2C3C

Subject to revision without prior notice

Zhejiang Narada power source Co., Ltd.

Tel: (86 571)56975980 Fax:(86 571)56975955 Email: Website: [email protected]

Discharge curve at different rate (25℃)

Dis

char

ge v

olta

ge (

V)

Capacity vs OCV curve

OC

V(V

)

Capacity (%)

Residue capacity vs storage time

Cap

acit

y (%

)

Storage �me (months)

Capacity vs temperature curve

C10

Cap

acit

y (%

)

Temperature (℃)

2.30

2.25

2.15

2.05

0 122 8 6 104

Charge curve (25℃)

Cha

rge

capa

city

(%)

Cha

rge

curr

ent(

CA

)

Cha

rge

volt

age(

V)

Charge voltage

Charge capacity

100% discharge

50% discharge

Charge current

Time ( h )

Design life vs temperature

Des

ign

life

(ye

ars)

0

8

25 30 35 40 45

16

20

4

12

24

50

Temperature ( ℃)

RE

XC

-400 -

01-N

-EN

(ver

1.2

-Oct.2015)

Subje

ct to

revis

ion w

ithout prior

notice.E

.&.O

.E.

Add:Building A, No.822 Wen'er West Road, Hangzhou, China