Type G Washdown Nozzle United States Navy Worldwide Contacts www.tyco-fire.com Page 1 of 2 APRIL 2015 TFP820 General Description TYCO Type G Nozzles are washdown nozzles for use on United States Navy ships. They are external deflector-type nozzles that discharge a filled cone of small water droplets at a relatively low velocity. Four frame arms support the deflector in order to help protect the nozzle from mechanical damage. Technical Data Approvals TYCO Type G Nozzles are manufactured in compliance with NAVSEA Drawing No. 803-1385828 and have been qualified to the High Impact Shock requirements of MIL-S-901C (Navy), Grade A, Hull Mounted, Class I, Light Weight Test. Discharge Coefficient 3.0 gpm/psi 1/2 (43,2 lpm/bar 1/2 ) Water Discharge Pattern The design of water spray systems using the Type G Nozzles is to be in accordance with the applicable stan- dards of the Naval Sea Systems Command. The approximate water discharge pattern at the deflector is 125 degrees. The recommended range of flowing pressure at the nozzle inlet is 20 to 60 psi (1,4 to 4,1 bar). Thread Connection 1/2 Inch NPT Nozzle Marking “G-125-.328” Weight 0.3 lbs. (0,14 kg) Physical Characteristics The Body of the Type G Nozzle is cast from aluminum bronze per ASTM B148 (UNS C95300), the Splitter is naval brass per ASTM B21 (UNS C46400), the Deflector is silicon bronze per ASTM B96 (UNS C65500), and the Pin is bronze per ASTM B159 (UNS C51000). Installation TYCO Type G Nozzles must be installed in compliance with the stan- dards of the Fire Protection Branch of the Ship Systems Directorate, Naval Sea Systems Command. Maintenance TYCO Type G Nozzles require regu- larly scheduled inspection and main- tenance. For instructions, refer to the Preventative Maintenance System of the United States Navy.

Upload: ivaldrete

Post on 07-Apr-2016

269 views

Category:

Documents


7 download

DESCRIPTION

fichas técnicas de rociadores tyco

TRANSCRIPT

Page 1: rociadores std tyco

Type G Washdown Nozzle United States Navy

Worldwide Contacts www.tyco-fire.com

Page 1 of 2 APRIL 2015 TFP820

General DescriptionTYCO Type G Nozzles are washdown nozzles for use on United States Navy ships. They are external deflector-type nozzles that discharge a filled cone of small water droplets at a relatively low velocity. Four frame arms support the deflector in order to help protect the nozzle from mechanical damage.

Technical DataApprovalsTYCO Type G Nozzles are manufactured in compliance with NAVSEA Drawing No. 803-1385828 and have been qualified to the High Impact Shock requirements of MIL-S-901C (Navy), Grade A, Hull Mounted, Class I, Light Weight Test.Discharge Coefficient3.0 gpm/psi1/2 (43,2 lpm/bar1/2)Water Discharge PatternThe design of water spray systems using the Type G Nozzles is to be in accordance with the applicable stan-dards of the Naval Sea Systems Command. The approximate water discharge pattern at the deflector is 125 degrees. The recommended range of flowing pressure at the nozzle inlet is 20 to 60 psi (1,4 to 4,1 bar).Thread Connection1/2 Inch NPTNozzle Marking“G-125-.328”Weight0.3 lbs. (0,14 kg)Physical CharacteristicsThe Body of the Type G Nozzle is cast from aluminum bronze per ASTM B148 (UNS C95300), the Splitter is naval brass per ASTM B21 (UNS C46400), the Deflector is silicon bronze per ASTM B96 (UNS C65500), and the Pin is bronze per ASTM B159 (UNS C51000).

InstallationTYCO Type G Nozzles must be installed in compliance with the stan-dards of the Fire Protection Branch of the Ship Systems Directorate, Naval Sea Systems Command.

MaintenanceTYCO Type G Nozzles require regu-larly scheduled inspection and main-tenance. For instructions, refer to the Preventative Maintenance System of the United States Navy.

Page 2: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP820Page 2 of 2

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indi-cate the full product name, including description and part number (P/N).

Type G NozzleSpecify: Bronze Type G Nozzle, P/N 49-554-1-328

7/16" (11,1 mm)NOMINAL MAKE-IN

1/2" NPT

1.69"(42,9 mm)

SPLITTER

DEFLECTORPIN

2.43"(59,4 mm)

BODY

FIGURE 1 TYPE G NOZZLE

ASSEMBLY

Page 3: rociadores std tyco

Model BFV-N Butterfly Valve Wafer Style

Page 1 of 4 MARCH 2015 TFP1515

Worldwide Contacts www.tyco-fire.com

General DescriptionThe TYCO Model BFV-N Wafer Style Butterfly Valves (Ref. Figure 1) are indi-cating type valves designed for use in fire protection systems where a visual indication is required as to whether the valve is open or closed. They are used, for example, as system, sectional, and pump water control valves. They are suitable for installation between ANSI Class 125 or 150 flanges without the need for flange gaskets.

For applications requiring supervision of the open position of the valve, the Gear Operators for the Model BFV-N Butterfly Valves are provided with two sets of factory installed internal switches each having SPDT contacts. The supervisory switches transfer their electrical contacts when there is move-ment from the valve’s normal open posi-tion during the first two revolutions of the handwheel.

NOTICEThe TYCO Model BFV-N Wafer Style Butterfly Valves described herein must be installed and maintained in compli-ance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any other authori-ties having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Con-tact the installing contractor or product manufacturer with any questions.

Technical DataModelBFV-N

Sizes: ANSI Inches (DN)2 (DN50), 2-1/2 (DN65), 3 (DN80), 4 (DN100), 5 (DN125), 6 (DN150), 8 (DN200), 10 (DN250), 12 (DN300)

ApprovalsUL and C-UL Listed FM Approved California State Fire Marshall under Listing No. 7770-1670:101

Maximum Working Pressure250 psi (17,2) bar

Materials of Construction:BodyDuctile iron conforming to ASTM A536

DiscDuctile iron conforming to ASTM A395, Nickel Plated

Seat MaterialGrade EPDM “E” rubber conforming to ASTM D2000

Upper StemType 416 Stainless Steel conforming to ASTM 582

OperatorGear operator with iron housing

Friction LossThe approximate friction loss, based on the Hazen Williams formula and expressed in equivalent length of pipe with C= 120, is as follows. Unless oth-erwise indicated, the data is based on friction loss information collected at a typical flow rate of 15 feet per second.

• 4.4 feet of 2 inch Sch. 40 pipe for the 2 inch valve.

• 6.2 feet of 2-1/2 inch Sch. 40 pipe for the 2-1/2 inch valve.

• 7.6 feet of 3 inch Sch. 40 pipe for the 3 inch valve.

• 9.2 feet of 4 inch Sch. 40 pipe for the 4 inch valve.

• 9.0 feet* of 5 inch Sch. 40 pipe for the 5 inch valve.

• 8.2 feet of 6 inch Sch. 40 pipe for the 6 inch valve.

• 12.7 feet* of 8 inch Sch. 30 pipe for the 8 inch valve.

• 20.1 feet* of 10 inch Sch. 30 pipe for the 10 inch valve.

• 22.3 feet* of 12 inch Sch. 30 pipe for the 12 inch valve.

*NFPA 13

Page 4: rociadores std tyco

TFP1515Page 2 of 4

InstallationThe TYCO Model BFV-N Wafer Style Butterfly Valves may be installed with flow in either direction and can be positioned either horizontally or verti-cally. They are designed for installation between the faces of ANSI Class 125 and 150 flanges. The Series BFV-N are self-sealing between mating flanges; therefore, they do not require the use of additional gaskets.

The Model BFV-N may be installed with any pressure class or schedule of pipe or tubing no greater than schedule 40 that is listed or approved for fire protec-tion service and installed in accordance with the manufacturer’s instructions.

The wafer bodies have locating lugs to ensure proper centering of the valve body when flange bolts are installed. Refer to Figure 1 for bolt diameter. Bolts and studs must meet the minimum strength requirements of ASTM A307 (Grade B), and the nuts must meet the minimum strength requirements of ASTM A563 (Grade A).

Prior to installation, close the valve. Spread the flanges apart to allow the valve to slip easily between the flanges. Make sure the pipe flange faces are clean of any foreign material such as scale, metal shavings, or welding slag. Insert the valve between the flanges (without flange gaskets). Do not apply lubricant to the seat faces as this may

Nominal Flange Size ANSI Inches

(DN)

Recommended Minimum Torque

Ft.-Lbs (Nm)

2 - 4 (50 - 100)

20 - 30 (27,1 - 40,7)

5 - 8 (125 - 200)

33 - 50 (44,7 - 67,8)

10 (250)

53 - 75 (71,8 - 101,7)

12 (300)

80 - 110 (108,4 - 149,1)

Nominal Valve Sizes

Inches (DN)

Nominal Installation Dimensions Inches (mm) Weight

Lbs. (kg)A B C D E F G H J K

2(50)

2.53(64,0)

1.68(43,0)

12.62(320,5)

2.88(73,0)

6.48(164,6)

6.00(152,4)

5.80(147,3)

2.12(53,8)

1.38(35,1)

5/8(15,9)

21(10,0)

2-1/2(65)

2.90(74,0)

1.81(46,0)

13.51(343,1)

3.25(83,0)

6.98(177,3)

6.00(152,4)

5.80(147,3)

2.12(53,8)

2.00(50,8)

5/8(15,9)

24(11,0)

3(80)

3.17(81,0)

1.81(46,0)

13,88(352,6)

3.38(86,0)

7.22(183,4)

6.00(152,4)

5.80(147,3)

2.12(53,8)

2.55(64,8)

5/8(15,9)

24(11,0)

4(100)

4.17(106,0)

2.06(52,0)

15.24(387,0)

4.00(160,3)

7.98(202,7)

6.00(152,4)

5.80(147,3)

2.12(53,8)

2.58(65,5)

5/8(15,9)

27(12,0)

5(125)

5.17(131,0)

2.19(56,0)

16.49(418,8)

4.75(121,0)

8.48(215,4)

6.00(152,4)

7.80(198,1)

2.12(53,8)

4.64(117,9)

3/4(19,1)

31(14,1)

6(150)

6.17(157,0)

2.19(56,0)

17.65(448,3)

5.25(133,0)

9.10(231,1)

6.00(152,4)

7.80(198,1)

2.12(53,8)

5.75(146,1)

3/4(19,1)

34(15,0)

8(200)

8.17(208,0)

2.38(60,0)

20.11(510,8)

6.50(165,0)

10.35(262,9)

10.00(254,0)

7.90(200,7)

2.12(53,8)

7.77(197,4)

3/4(19,1)

49(22,0)

10(250)

10.17(258,0)

2.68(69,0)

23.35(593,1)

8.00(203,0)

12.27(311,7)

11.80(300,0)

9.50(241,3)

3.03(77,0)

9.77(248,2)

7/8(22,2)

78(35,0)

12(300)

12.17(309,0)

3.00(76,0)

26.10(663,0)

9.25(235,0)

13.77(349,8)

11.80(300,0)

9.50(241,3)

3.03(77,0)

11.75(298,5)

7/8(22,2)

103(47,0)

G HANDWHEEL

DISC

BODY

F

E

D

C

H

B

AJ

KBOLT

DIAMETER

INDICATORFLAG

GEAROPERATOR

1/2" NPTCONDUIT

CONNECTION

FIGURE 1 MODEL BFV-N WAFER STYLE BUTTERFLY VALVE

NOMINAL DIMENSIONS

TABLE A RECOMMENDED TORQUES

Page 5: rociadores std tyco

TFP1515Page 3 of 4

damage the seat material. Be sure to center the valve and do not damage the liner. Relax the separation of the flanges, install, and hand-tighten all flange bolts. Slowly open the valve, checking for free movement of the disc. If valve opens freely, leave the valve in the open position, and using a cross-draw sequence, tighten all flange bolts until the valve is metal-to-metal with both mating flanges. Recommended tightening torques are listed in Table A.

Be certain to keep flange faces as paral-lel as possible during and after tighten-ing bolts or studs. After final tightening, again check the valve for full opening and closing.

As applicable, refer to Figure 2 for the internal switch wiring diagram.

Conduit and electrical connections are to be made in accordance with the authority having jurisdiction and/or the National Electrical Code. With reference to Figure 2, the supervisory switch is intended for connection to the supervi-sory circuit of a fire alarm control panel in accordance with NFPA 72. The auxil-iary switch is intended for the unsuper-vised connection to auxiliary equipment in accordance with NFPA 70, National Electric Code.

NOTE: For outdoor applications with internal supervisory switches, it is rec-ommended that wiring connections be made at a temperature above 15°F (-9°C), in order to insure sufficient flex-ibility of the wire lead insulation.

Stop Adjustment ProcedureThe gear operator’s OPEN and SHUT position have been factory set. The following procedure should be used if slight adjustments are needed. Refer to Figure 3.

Step 1. Turn the Handwheel until the valve is fully closed.

Step 2. Remove the two Lock Screws (A) from the gear operator body.

Step 3. Turn the Shut Stop Screw (B) clockwise until snug.

Step 4. Turn the Handwheel until the valve is fully open.

Step 5. Turn the Open Stop Screw (C) clockwise until snug.

Step 6. Close the valve by turning the Handwheel until the valve is fully in the closed position. Ensure the disc has returned to the fully closed posi-tion and the disc is centered in the seat area. Readjust the Shut Stop Screw if necessary.

Step 7. Replace the two Lock Screws (A) into the gear operator body, locking the stops into position.

Care and MaintenanceThe TYCO Model BFV-N Wafer Style Butterfly Valves must be maintained and serviced in accordance with this section.

Before closing a fire protection system control valve for maintenance or inspec-tion work on either the valve or fire protection system which it controls, per-mission to shut down the affected fire protection systems must be obtained from the proper authorities and all per-sonnel who may be affected by this decision must be notified.

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in accordance with the applicable stan-dards of the National Fire Protection

Association (e.g., NFPA 25), in addi-tion to the standards of any authority having jurisdiction. Contact the install-ing contractor or product manufacturer with any questions. Any impairment must be immediately corrected.

It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified inspec-tion service.

1/2A @ 125 VDC1/4A @ 250 VDC15.1A/12HP @ 125, 250 VAC5A @ 125 VAC "L"

END OF LINERESISTOR

PANEL

OR

AN

GE

OR

AN

GE

YE

LLO

W

YE

LLO

W

SUPERVISORYSWITCH

SWITCH SHOWNWITH VALVEFULL OPEN

GR

EE

N

VIO

LET

AUXILIARY

SWITCH SHOWNWITH VALVEFULL OPEN

BLU

E

RE

D

BELL

SWITCHGND

POWER

+

- -

+

CONTACT RATING:

AC

A

BOPEN

SHUT

FIGURE 2 MODEL BFV-N BUTTERFLY VALVE

INTERNAL SWITCH WIRING DIAGRAM WITH VALVE IN OPEN POSITION

FIGURE 3 MODEL BFV-N WAFER STYLE

BUTTERFLY VALVE OPERATOR ADJUSTMENT

Page 6: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP1515Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureWafer Style Butterfly ValvesSpecify: (specify inch size) Model BFV-N Wafer Style Butterfly Valve with internal supervisory switches, P/N (specify)Valve Size Valve Part Number2 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-020N2-1/2 . . . . . . . . . . . . . . . . . . . . . . .59-801-1-025N3 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-030N4 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-040N5 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-050N6 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-060N8 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-080N10 . . . . . . . . . . . . . . . . . . . . . . . . .59-801-1-100N12 . . . . . . . . . . . . . . . . . . . . . . . . . 59-801-1-120N

Page 7: rociadores std tyco

Series TY-B – 5.6 K-factor Horizontal and Vertical Sidewall Sprinklers Standard Response, Standard Coverage

Page 1 of 6 APRIL 2015 TFP161

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and in-stallation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

plicable approval agencies, the test-ing is not representative of all possible corrosive atmospheres. Consequently, it is recommended that the end user be consulted with respect to the suit-ability of these coatings for any given corrosive environment. The effects of ambient temperature, concentration of chemicals, and gas/chemical velocity, should be considered, as a minimum, along with the corrosive nature of the chemical to which the sprinklers will be exposed.

NOTICEThe Series TY-B Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Association, in addition to the standards of any oth-er authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for maintaining their fire protection system and devices in proper operating condition. Contact the installing contractor or product man-ufacturer with any questions.

Sprinkler Identification NumbersTY3351 – Horizontal Sidewall TY3451 – Vertical Sidewall

Technical DataApprovalsUL and C-UL Listed FM Approved LPCB Certified NYC Approved

(Refer to Table A for complete approval information, including corrosion-resis-tant status.)

Maximum Working PressureRefer to Table B

Discharge CoefficientK=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)

Temperature RatingsRefer to Table A

FinishesSprinkler: Refer to Table C

Recessed Escutcheon: Signal or Pure White, Jet Black, Chrome Plated, or Natural Brass

Physical CharacteristicsFrame � � � � � � � � � � � � � � � � � � � � � � � � � � � �BronzeButton � � � � � � � � � � � � � � � � � � � � � � Brass/CopperSealing Assembly � � Beryllium Nickel w/TEFLONBulb � � � � � � � � � � � � � � � � � � � � � � � � � � � � � � �GlassCompression Screw � � � � � � � � � � � � � � � � �BronzeHSW Deflector � � � � � � � � � � � � � � � � � � � � �BronzeVSW Deflector � � � � � � � � � � � � � � � � � � � � � Copper

General DescriptionThe TYCO Series TY-B, 5.6 K-factor, Horizontal and Vertical Sidewall Sprin-klers described in this technical data sheet are standard response, standard coverage decorative 5 mm glass bulb type spray sprinklers designed for use in light and ordinary hazard, commercial occupancies such as banks, hotels, and shopping malls.

They are designed for installation along a wall or the side of a beam and just beneath a smooth ceiling. Sidewall sprinklers are commonly used instead of pendent or upright sprinklers due to aesthetics or building construction con-siderations, where piping across the ceiling is not desirable.

The recessed version of the Series TY-B Horizontal Sidewall Sprinkler is intend-ed for use in areas with a finished wall. It uses a two-piece Style 10 Recessed Escutcheon. The Recessed Escutcheon provides 1/2 inch (12,7 mm) of recessed adjustment or up to 3/4 inch (19,1 mm) of total adjustment from the flush side-wall position. The adjustment provided by the Recessed Escutcheon reduces the accuracy to which the fixed pipe nipples to the sprinklers must be cut.

Corrosion-resistant coatings, where applicable, are utilized to extend the life of copper alloy sprinklers beyond that which would otherwise be obtained when exposed to corrosive atmospheres. Although corrosion re-sistant coated sprinklers have passed the standard corrosion tests of the ap-

Page 8: rociadores std tyco

TFP161Page 2 of 6

OperationThe glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to ac-tivate and water to flow.

Design CriteriaThe TYCO Series TY-B, 5.6 K-factor, Horizontal and Vertical Sidewall Sprin-klers are intended for fire protection systems designed in accordance with the standard installation rules recog-nized by the applicable Listing or Ap-proval agency (for example, UL Listing is based on the requirements of NFPA 13, and FM Approval is based on the requirements of the FM Loss Preven-tion Data Sheets). Only the Style 10 Recessed Escutcheon, as applicable, is to be used for recessed horizontal installations.

InstallationThe TYCO Series TY-B, 5.6 K-factor, Horizontal and Vertical Sidewall Sprin-klers must be installed in accordance with this section.

General InstructionsDo not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 360°F (182°C) tem-perature ratings.

A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min-imum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.

Do not attempt to make-up for insuf-ficient adjustment in the escutcheon plate by under- or over-tightening the sprinkler. Readjust the position of the sprinkler fitting to suit.

Horizontal Sidewall Sprinkler InstallationThe TYCO Series TY-B Recessed Hori-zontal Sidewall Sprinklers must be in-stalled in accordance with the following instructions.

Install recessed horizontal sidewall sprinklers in the horizontal position with the centerline of waterway perpendicu-lar to the back wall and parallel to the

ceiling. The word “TOP” on the Deflec-tor is to face towards the ceiling.

Step A. After installing the Style 10 Mounting Plate over the sprinkler threads, hand-tighten the sprinkler into the sprinkler fitting.

Step B. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Ref. Figure 5). Apply the W-Type 7 Recessed Sprin-kler Wrench to the sprinkler wrench flats (Ref. Figure 1).

Step C. After the ceiling is installed or the finish coat is applied, slide on the Style 10 Closure over the Series TY-B Sprinkler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling.

Vertical Sidewall Sprinkler InstallationThe Series TY-B Vertical Sidewall Sprin-klers must be installed in accordance with the following instructions.

Install vertical sidewall sprinklers in the pendent or upright position with the ar-row on the Deflector pointing away from the wall.

Step 1. With pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting.

Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 4). For wax-coated sprinklers, use an 8 or 10 inch adjustable Crescent wrench. Apply the W-Type 6 Sprinkler Wrench or the Crescent wrench, as applicable, to the wrench flats (Ref. Figure 2).

**

*

*

**

*

ESCUTCHEONPLATE SEATING

SURFACE

1-13/16"(46,0 mm)

CENTERLINEOF SPRINKLER

WATERWAY

2-7/8" DIA.(73,0 mm)

STYLE 10RECESSED

ESCUTCHEON

2-3/16"(55,6 mm)

1-1/2"(38,1 mm)

DEFLECTORHAT

9/16"(14,3 mm)

6

WRENCHFLATS

4

7/16"(11,1 mm)NOMINALMAKE-IN

2

5

3

1/2"NPT

1

Pipe threadconnections perISO 7-1 can beprovided onspecial request.

Temperature ratingis indicated onDe�ector.

12

SealingAssembly

ButtonFrame

--

Bulb

3 -

4 -

6 - De�ector

CompressionScrew

5 -

FIGURE 1 SERIES TY-B HORIZONTAL SIDEWALL (TY3351) SPRINKLER

5.6 K-FACTOR STANDARD RESPONSE

Page 9: rociadores std tyco

TFP161Page 3 of 6

sprinkler, loosen the wrench jaws before removing the wrench.

After installation, inspect the sprinkler wrench flats and frame arms and re-touch (repair) the wax coating when-ever the coating has been damaged and bare metal is exposed. Retouch the wax coating on the wrench flats by gently applying a heated 1/8 inch diam-eter steel rod to the damaged areas of wax to smooth it back over areas where bare metal is exposed.

NOTICEOnly retouching of the wax coating ap-plied to the wrench flats and frame arms is permitted, and the retouching is to be performed only at the time of the initial sprinkler installation.

The steel rod should be heated only to the point at which it can begin to melt the wax, and appropriate precautions need to be taken when handling the heated rod in order to prevent the in-staller from being burned.

When installing wax-coated sprinklers with the adjustable Crescent wrench, exercise care to prevent damage to the wax coating on the sprinkler wrench flats or frame arms and, consequent-ly, exposure of bare metal to the cor-

rosive environment. Open the jaws of the wrench sufficiently wide to pass over the wrench flats without damaging the wax coating. Before wrench-tight-ening the sprinkler, adjust the jaws of the wrench to contact only the sprinkler wrench flats. After wrench tightening the

**

* **

*

*

PENDENT UPRIGHT SECTIONCROSSSHOWN SHOWN

1-1/2"(38,1 mm)

ESCUTCHEONPLATE SEATING

SURFACE

2-3/16"(55,6 mm)

WRENCHFLATS

1/2"NPT

7/16"(11,1 mm)NOMINALMAKE-IN

ARROW MUSTPOINT AWAY

FROM AND BEPERPENDICULAR

TO THE BACKWALL SURFACE

7

2-3/16"(55,6 mm)

3

1

6

5

2

4

Pipe threadconnectionsper ISO 7-1 canbe provided onspecial request.

Temperaturerating isindicated onDe�ector.

12

SealingAssembly

ButtonFrame

-- Bulb

3 -

4 -

6 - De�ector

CompressionScrew

5 -

FLOW

EjectionSpring

7 -

WRENCH RECESS(END "A" USED FOR1/2" NPT MODELS)

WRENCHRECESS

PUSH WRENCHIN TO ENSUREENGAGEMENT

WITH SPRINKLERWRENCHING AREA

2-7/8" DIA.(73,0 mm)

MOUNTINGSURFACE

CLOSURE

1-1/4" (31,8 mm)

3/4" (19,1 mm)

SERIESTY-B

MOUNTINGPLATE

3/4" (19,1 mm)

1/8"(3,2 mm)

1/4" (6,4 mm)

FACE OFSPRINKLER

FITTING

5/8±1/4"(15,9±6,4 mm)

2-1/4" DIA.(57,2 mm)

FIGURE 2 SERIES TY-B VERTICAL SIDEWALL (TY3451) SPRINKLER

5.6 K-FACTOR, STANDARD RESPONSE

FIGURE 4 W-TYPE 6

SPRINKLER WRENCH

FIGURE 5 W-TYPE 7 RECESSED SPRINKLER WRENCH

FIGURE 3 SERIES TY-B RECESSED PENDENT SPRINKLER ASSEMBLY

WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT STYLE 10 RECESSED ESCUTCHEON, 5.6 K-FACTOR, 1/2 INCH NPT

Page 10: rociadores std tyco

TFP161Page 4 of 6

K SPRINKLER TYPE

TEMPERATURE RATING

BULB LIQUID COLOR

SPRINKLER FINISH (10)

NATURAL BRASS

CHROME PLATED POLYESTER*** LEAD

COATEDWAX

COATEDWAX-OVER-LEAD

COATED

5.6 1/2˝ NPT

HORIZONTAL SIDEWALL (TY3351) Figure 1

135°F (57°C) Orange

1, 2, 3, 4, 9 1, 2, 3, 91, 2, 3, 9

1, 2, 3, 9155°F (68°C) Red

175°F (79°C) Yellow

200°F (93°C) Green

286°F (141°C) Blue 1**, 2**, 3**, 9**

360°F (182°C) Mauve 1, 2, 4, 9 1, 2, 9 N/A

RECESSED HORIZONTAL

SIDEWALL (TY3351)* Figure 3

135°F (57°C) Orange

1, 2, 3, 9 N/A155°F (68°C) Red

175°F (79°C) Yellow

200°F (93°C) Green

5.6 1/2˝ NPT

VERTICAL SIDEWALL (TY3451)

PENDENT or

UPRIGHT Figure 2

135°F (57°C) Orange

4, 5, 6, 7, 8, 95, 6, 7, 9

5, 6, 7, 9155°F (68°C) Red

175°F (79°C) Yellow

200°F (93°C) Green

286°F (141°C) Blue 5**, 6**, 7**, 9**

360°F (182°C) Mauve 4, 5, 6, 8, 9 N/A

Notes:1. UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance2. C-UL Listed for use in Light and Ordinary Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance3. FM Approved for use in Light Hazard Occupancies at a 4 to 12 inch (100 to 300 mm) top of deflector-to-ceiling distance4. LPCB Approved (Ref. No. 094a & 007k) at a 4 to 6 inch (100 to 150 mm) deflector-to-ceiling distance5. UL Listed for use in Light and Ordinary Hazard Occupancies6. C-UL Listed for use in Light and Ordinary Hazard Occupancies7. FM Approved for use in Light Hazard Occupancies8. LPCB Approved (Ref. No. 094a & 007k)9. Approved by the City of New York under MEA 354-01-E10. Where Polyester Coated, Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as corro-

sion-resistant sprinklers. Where Lead Coated, Wax Coated, and Wax-over-Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as corrosion-resistant sprinklers.

* Installed with Style 10 (1/2˝ NPT) or Style 40 (3/4˝ NPT) 3/4˝ Total Adjustment Recessed Escutcheon, as applicable** 150°F (66°C) maximum ceiling temperature*** Frame and deflector onlyN/A – Not Applicable

TABLE A SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS

LABORATORY LISTINGS AND APPROVALS

Page 11: rociadores std tyco

TFP161Page 5 of 6

Care and MaintenanceThe TYCO Series TY-B, 5.6 K-factor, Horizontal and Vertical Sidewall Sprin-klers must be maintained and serviced in accordance with this section.

Before closing a fire protection sys-tem main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection sys-tem from the proper authorities and no-tify all personnel who may be affected by this action.

The owner must assure that the sprin-klers are not used for hanging any ob-jects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-opera-tion in the event of a fire or inadvertent operation may result.

Absence of an escutcheon, which is used to cover a clearance, may delay the time to sprinkler operation in a fire situation.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied sprinklers must be replaced. Sprin-klers that have been exposed to corro-sive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid dam-age to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a

cracked bulb or that has lost liquid from its bulb. (Refer to Installation Section.)

The owner is responsible for the inspec-tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (e.g., NFPA 25), in addition to the stan-dards of any other authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinklers are recommended to be inspected, tested, and maintained by a qualified Inspection Service in ac-cordance with local requirements and/or national codes.

K SPRINKLER TYPE

SPRINKLER FINISH

NATURAL BRASS

CHROME PLATED POLYESTER* LEAD

COATEDWAX

COATEDWAX-OVER-LEAD

COATED

5.6 1/2˝ NPT

HORIZONTAL SIDEWALL (TY3351) 250 psi (17,2 bar) (a)

OR

175 psi (12,1 bar)RECESSED HORIZONTAL SIDEWALL

(TY3351)

VERTICAL SIDEWALL (TY3451) 175 psi (12,1 bar)

Note:a. The maximum working pressure of 250 psi (17,2 bar) only applies to UL Listing, C-UL Listing and Approval by the City of New York* Frame and deflector only

TABLE B SERIES TY-B HORIZONTAL AND VERTICAL SPRINKLERS

MAXIMUM WORKING PRESSURE

Page 12: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP161Page 6 of 6

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of The DuPont Corporation

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N).

Sprinkler Assemblies with NPT Thread ConnectionsSpecify: Series TY-B (specify SIN), (specify K-factor), (specify Horizontal or Vertical Sidewall) Sprinklers with (spec-ify) temperature rating, (specify) finish or coating, P/N (Refer to Table C)

Recessed EscutcheonSpecify: Style 10 Recessed Escutcheon with (specify) finish, P/N (specify*)* Refer to Technical Data Sheet TFP770

Sprinkler WrenchSpecify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387

Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001

Wax Sticks (for retouching wrench-damaged wax coating)Specify: (specify color, below) Colored Coded Wax Stick for retouching (speci-fy temperature rating) temperature-rated Series TY-B Sprinklers, P/N (specify)

Note: Each wax stick is suitable for retouching up to 25 sprinklers.

Note: The wax used for 286°F (141°C) sprinklers is the same as for 200°F (93°C) sprinklers, and, therefore, the 286°F (141°C) sprinkler is limited to the same maximum ceiling temperature as the 200°F (93°C) sprinkler (i.e., 150°F [66°C]).

Notes:* Eastern Hemisphere sales only** Available only for 155°F (68°C) or 200°F (93°C) temperature

rated sprinklers*** Available only for horizontal sidewall TY3351 for use in

Deluge Systems (“OPEN” indicates sprinkler assembly without glass bulb, button, and sealing assembly)

P/N 57 – XXX – X – XXX

Color Sprinkler Temperature Rating Part Number

Black 135°F (57°C) 56-065-1-135

Red 155°F (68°C) 56-065-1-155

Yellow 175°F (79°C 56-065-1-175

Blue 200°F (93°C)286°F (141°C) 56-065-1-286

SIN

578 HORIZONTAL SIDEWALL TY3351

575 VERTICAL SIDEWALL TY3451

TEMPERATURE RATING

135 135°F (57°C)

155 155°F (68°C)

175 175°F (79°C)

200 200°F (93°C)

286 286°F (141°C)

360 360°F (182°C)

000 OPEN***

SPRINKLER FINISH

1 NATURAL BRASS

3 PURE WHITE (RAL9010)* POLYESTER

4 SIGNAL WHITE (RAL9003) POLYESTER

5 JET BLACK (RAL9005)** POLYESTER

6 WAX COATED 286°F (141°C) MAX

7 LEAD COATED

8 WAX-OVER-LEAD 286°F (141°C) MAX

9 CHROME PLATED

TABLE C SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS

PART NUMBER SELECTION

TABLE D SERIES TY-B HORIZONTAL AND VERTICAL SIDEWALL SPRINKLERS

WAX RETOUCHING STICK PART NUMBER SELECTION

Page 13: rociadores std tyco

Model EC-25 (CMDA and CMSA Applications) 25.2 (360) K-factor (360) Upright Sprinkler Extended Coverage

Page 1 of 4 APRIL 2015 TFP213

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionThe TYCO Model EC-25 Extended Coverage (EC) 25.2K Upright Sprin-kler is a UL Listed, standard response, extended coverage Control Mode Density Area (CMDA) sprinkler for storage applications. It is also FM Approved as a quick response, extended coverage Control Mode Density Area (CMDA) sprinkler and as a Control Mode Specific Appli-cation (CMSA) sprinkler, as well as FM Approved for storage and non-stor-age applications.

In addition, these sprinklers may be used in accordance with the new Chapter 21 of the 2013 edition of NFPA 13. As such, tables 21.2.2 and 21.3.2 of NFPA 13 may be utilized for design options. When used in accor-dance with NFPA Chapter 21, smoke vents and draft curtains are not required as specified in the 2015 edition of the International Building Code (IBC) and International Fire Code (IFC) for CMSA sprinklers with an RTI of 50 or less and a design of 12 or fewer sprinklers.

These sprinklers offer a maximum cov-erage area of 196 ft.² (18,2 m²), which is almost double the area offered by standard coverage sprinklers used for similar applications.

The Model EC-25 Upright Sprinklers comply with the criteria for the protec-tion of retail stores as described in the 2013 Edition of NFPA 13, Section 20.3.

Where the FM Approval is utilized, the Model EC-25 Upright Sprinkler has successfully undergone full-scale fire testing at FM Global for ceiling-only storage and non-storage applica-tions. When used in conformance with applicable FM Global Property Loss Prevention Data Sheets, the Model EC-25 Sprinkler provides low hydrau-lic demand, the spacing advantages of extended coverage, and the obstruc-tion benefits of an upright sprinkler.

For more information on applications and benefits of the Model EC-25 Sprin-kler, refer to the available white papers at www.tyco-fire.com.

NOTICEThe Model EC-25 Upright Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the National Fire Pro-tection Association (NFPA), in addition to the standards of any other authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the perfor-mance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or sprinkler manufacturer with any questions.

Sprinkler Identification Number (SIN)TY9128

Technical DataApprovalsUL and C-UL Listed: CMDA (Standard Response) FM Approved: CMDA and CMSA (Quick Response) NYC Approved under MEA 355-01-E

(Approvals only apply to the service conditions indicated in the Design Cri-teria section.)Maximum Working Pressure175 psi (12,1 bar)Pipe Thread Connection1 Inch NPT or ISO 7-R1Discharge CoefficientK=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)

Temperature Ratings165°F (74°C) and 212°F (100°C)Maximum Coverage Area196 ft.² (18,2 m²)FinishNatural BrassPhysical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper Compression Screw . . . . . . . . . . Stainless Steel Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Sealing Assembly . Beryllium Nickel w/TEFLON Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL Deflector Nut . . . . . . . . . . . . . . . . . . . . . . . .Brass

Response Time Index (RTI)Less than or equal to 50 (m-s)0.5

Page 14: rociadores std tyco

TFP213Page 2 of 4

OperationThe fusible link assembly is com-prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, allowing the sprinkler to acti-vate and flow water.

Design CriteriaUL and C-UL Listing CriteriaNFPA 13, Chapters 12 thru 20 – Density / Area DesignThe TYCO Model EC-25 Extended Coverage Upright Sprinklers (TY9128) are UL and C-UL Listed for installation in accordance with the extended cov-erage upright spray sprinkler require-ments of NFPA 13 or other applicable NFPA standards when used in conjunc-tion with the following guidelines:

• Suitable for the protection of extra hazard and high-piled storage occupancies where area/density design criteria are provided

• Suitable for unobstructed or noncombustible obstructed construction

• The Model EC-25 Sprinklers having been specifically tested and Listed for noncombustible obstructed construction are suitable for use within trusses or bar joists having noncombustible web members greater than 1 inch (25,4 mm) when applying the 4 times obstruction criteria rule defined under “Obstruc-tions to Sprinkler Discharge Pattern Devel opment.”

• The maximum coverage area per sprinkler is 196 ft.² (18,2 m²).

• The maximum distance between sprinklers is 15 feet (4,6 m) when the coverage area does not exceed 144 ft.² (13,4 m²), and the maximum distance between sprinklers is 14 feet (4,3 m) when the coverage area does not exceed 196 ft² (18,2 m²).

• The minimum distance between sprinklers is 8 feet (2,44 m).

• The minimum flow requirement is based on the design density applied over the actual coverage area per sprinkler.

For example: when sprinkler spacing is 14 ft. x 12 ft. - 6 in. (4,3 m x 3,8 m) or 175 ft² (16,3 m²), and the design density is 0.6 gpm/ft.² (24,4 mm/min), the sprinkler design flow rate is 105 gpm (397 lpm) and the required design pressure is 17.4 psi (1,2 bar).

• The minimum clearance between the deflector and the top of storage is 36 inches (0,9 m). For clearances of 36 inches (0,9 m) up to 48 inches (1,21 m), the minimum design pressure is 22 psi (1,52 bar). For clearances of 48 inches (1,21 m) and greater, the minimum design pressure is estab-lished by the minimum flow require-ment. However, the pressure can never be less than 7 psi (0,5 bar).

• Ordinary and intermediate temper-ature rated Model EC-25 Sprin-klers have been investigated for use in high-piled storage occu-pancies at the hydraulic demand normally associated with high temperature sprinklers. As such, the Model EC-25 Sprinklers are

listed storage sprinklers having a K-factor greater than 11.2 (161,4) and having ordinary and interme-diate temperature ratings (i.e., 165°F or 74°C and 214°F or 101°C). Conse-quently, the Model EC-25 Sprin-klers, in accordance with NFPA 13, may be used in conjunction with the density curves for high temperature sprinklers.

• NFPA obstruction rules for Extended Coverage Sprinklers must be utilized.

System TypeWet pipe, dry pipe, and preaction systems are acceptable.

FM Approval CriteriaFM Loss Prevention Data Sheets 2-0, 3-26, and 8-9TYCO Model EC-25 Extended Cover-age 25.2K Upright Sprinklers (TY9128) are FM Approved to be utilized in accor-dance with the following guidelines.

ApplicationThe Model EC-25 Extended Cov-erage Upright Sprinklers are FM Approved ceiling-level Storage Sprinklers for storage occupancy hazards and other similar high heat release type fires. When compared with other FM Approved Storage Sprinklers, the Model EC-25 Sprinkler provides low hydraulic demand, the spacing advan-tages of extended coverage, and the FM Global obstruction benefits of an upright sprinkler.

Model EC-25 Sprinklers should be used in conformance with applicable FM Global Property Loss Prevention Data Sheets.

1- Frame2- Deflector3- Compression Screw4- Hook5- Strut6- Link Assembly7- Button8- Gasketed Spring Plate9- Ejection Spring

10- Deflector Nut

* ISO 7-R1 pipe thread can be provided on special request.

*

7

11" NPT

8

6

9

5

4

2

WRENCHFLATS

TEMPERATURERATING

9/16"(14,3 mm)NOMINALMAKE-IN

3-3/4"(95,3 mm)

3 102-9/16" DIA.(65,0 mm)

FIGURE 1 MODEL EC-25 UPRIGHT SPRINKLER, 25.2K

EXTENDED COVERAGE

Page 15: rociadores std tyco

TFP213Page 3 of 4

Hydraulic DesignTo determine the hydraulic design for the Model EC-25 Sprinkler refer to the applicable FM Global Property Loss Prevention Data Sheet.

System TypeWet pipe systems only

Sprinkler SpacingThe maximum coverage area per sprinkler is 196 ft.² (18,2 m²). The minimum coverage area per sprinkler is 100 ft.² (9,3 m²). The maximum distance between sprinklers is 14 feet (4,3 m). The minimum distance between sprin-klers is 10 feet (3,05 m).

Note: When a wall or obstruction makes a minimum spacing of 10 feet (3,05 m) impossible, consult FM Global Property Loss Prevention Data Sheet 2.0 for applicable guidelines.

Sprinkler LocationLocate sprinklers with respect to the ceiling/roof in accordance with FM Global Property Loss Prevention Data Sheet 2.0.

ObstructionsFollow the obstruction requirements as detailed in FM Global Property Loss Prevention Data Sheet 2.0.

Other DetailsAll other design details should be in accordance with FM Global Property Loss Prevention Data Sheet 2.0 as well as any other applicable FM Global Data Sheet.

NFPA 13, Chapter 21 – Alternative System Design (CMSA)TYCO Model EC-25 Extended Cover-age Upright Sprinklers (TY9128) have successfully undergone large-scale fire tests at FM Global to comply with Chapter 21 of NFPA 13, 2013 Edition. As such, Tables 21.2.2 and 21.3.2 of NFPA 13 may be utilized for design options with the Model EC-25 Upright Sprinklers for providing ceiling-only protection.

This allows for the protection of Pal-letized, Solid Piled, Bin Box, Shelf, or Back-to-Back Shelf Storage as well as Single, Double, and Multiple Row Open Rack protection of up to 30 feet (9,1 m) of Cartoned Unexpanded Group A Plastic Commodities in a maximum 35 feet (11 m) ceiling condition with extended spacing up to 196 ft.2 while maintaining very reasonable flow and pressure requirements. Pipe sizes as well as water supply requirements can now be kept to a minimum when compared to other design methods for high piled storage challenges. Refer to Tables A and B of this data sheet for specific flow, pressure, and number of sprinklers to be calculated.

When used in accordance with NFPA Chapter 21, smoke vents and draft cur-tains are not required as specified in the 2015 edition of the International Building Code (IBC) and International Fire Code (IFC) for CMSA sprinklers with an RTI of 50 or less and a design of 12 or fewer sprinklers.

Construction TypeIn accordance with NFPA 13 for Extended Coverage Sprinklers for High Piled Storage.

Obstruction CriteriaFollow Sections 8.8.5.1, “Extended Coverage Obstruction Guidelines for Sprinkler Discharge Pattern Develop-ment”; 8.12.5.2 and 8.12.5.3, “ESFR Obstruction Criteria,” for obstructions that prevent the pattern from reaching the hazard below.

Exception: When using the Upright EC-25 Sprinkler, any continuous obstruction 4 inches (100 mm) or less shall be permitted to be ignored in accordance with NFPA 13, section 21.5.3.2.3.

Deflector Distance below CeilingFollow NFPA 13, Section 8.8.4 for allowed deflector distances below ceiling.

Clearance to StorageMinimum 36 inches from deflector to top of storage required.

Maximum Distance between Sprinklers14 feet (4,3 m)

Minimum Distance between Sprinklers10 feet (3,0 m)

InstallationTYCO Model EC-25 Extended Cover-age 25.2K Upright Sprinklers are to be installed in accordance with this section.

Damage to the fusible Link Assembly during installation can be avoided by handling the sprinkler using only the frame arms and the appropriate sprin-kler wrench. Do not grip or apply any force to the fusible Link Assembly. Damaged sprinklers must be replaced immediately.

A leak-tight 1 inch NPT sprinkler joint should be obtained by apply-ing a minimum-to-maximum torque of 20 to 30 lbs.-ft. (26,8 to 40,2 Nm). Higher levels of torque may distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model EC-25 Upright Sprinkler in the upright position.

Step 1. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting. Do not apply any force to the Link Assembly, and handle the Model EC-25 Sprinkler only by the Frame arms.

Step 3. Wrench-tighten the Model EC-25 Sprinkler using only the W-Type 1 Sprinkler Wrench (Ref. Figure 2) and by fully engaging (seating) the wrench on the sprinkler wrench flats.

Step 4. After installation, inspect the Link Assembly of each Model EC-25 Sprinkler for damage. In particu-lar, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assembly has not been bent, creased, or forced out of its normal position in any way. Damaged sprinklers must be replaced immediately.

"FITTING SIDE"

FITTINGTOWARDS SPRINKLER

RECESSWRENCH

FIGURE 2 W-TYPE 1

SPRINKLER WRENCH

Page 16: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP213Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of DuPont Corporation.

Care and MaintenanceTYCO Model EC-25 Extended Cover-age 25.2K Upright Sprinklers must be maintained and serviced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this decision.

Inspection, testing, and maintenance must be performed as indicated below and in accordance with the local requirements and/or national codes. Any impairment must be immediately corrected.

The owner is responsible for the inspec-tion, testing, and maintenance of their fire protection system and devices in

compliance with this document, as well as with the applicable standards of any authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product description and part number (P/N).

Sprinkler AssembliesSpecify: Model EC-25 Extended Cover-age 25.2K Upright Sprinklers (TY9128), (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-450-1-165 212°F (100°C) . . . . . . . . . . . . P/N 58-450-1-214

Special Order Sprinkler Assemblies with ISO 7-R 1 Thread ConnectionSpecify: Model EC-25 Extended Cover-age 25.2K Upright Sprinklers (TY9128) with ISO 7-R 1 thread connection, (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . .P/N 58-451-1-165 212°F (100°C) . . . . . . . . . . . . .P/N 58-451-1-214

Sprinkler WrenchSpecify W-Type 1 Sprinkler Wrench, P/N 56-872-1-025

Storage Arrangement

Commodity Class

Max. Storage HeightFeet (m)

Max. Ceiling/

Roof HeightFeet (m)

Type of System

Number of Design Sprinklers

Min. Operating Pressure

psi (bar)

Max. Coverage

AreaFt. x Ft. (m x m)

Hose Stream

Allowancegpm (lpm)

Water Supply

DurationHours

Palletized, Solid-Piled,

Bin Box, Shelf, or

Back-to-Back Shelf Storage

Class I thru Class IV,

encapsulated and unencapsulated,

and cartoned non-expanded

plastics

25 (7,6)

30 (9,1) Wet 6 30

(2,1)14 x 14

(4,3 x 4,3)250

(950) 1

30 (9,1)

35 (11) Wet 8 40

(2,8)12 x 12

(3,7 x 3,7)250

(950) 1

30 (9,1)

35 (11) Wet 8 40

(2,8)14 x 14

(4,3 x 4,3)500

(1900) 1.5

Storage Arrangement

Commodity Class

Max. Storage HeightFeet (m)

Max. Ceiling/

Roof HeightFeet (m)

Type of System

Number of Design Sprinklers

Min. Operating Pressure

psi (bar)

Max. Coverage

AreaFt. x Ft. (m x m)

Hose Stream

Allowancegpm (lpm)

Water Supply

DurationHours

Sprinkler protection criteria for

open-frame rack storage

Class I thru Class IV,

encapsulated and unencapsulated, and cartoned non-expanded plastics

25 (7,6)

30 (9,1) Wet 6 30

(2,1)14 x 14

(4,3 x 4,3)250

(950) 1

30 (9,1)

35 (11) Wet 8 40

(2,8)12 x 12

(3,7 x 3,7)250

(950) 1

30 (9,1)

35 (11) Wet 8 40

(2,8)14 x 14

(4,3 x 4,3)500

(1900) 1.5

TABLE A NFPA 13, CHAPTER 21 – ALTERNATIVE SYSTEM DESIGN

PALLETIZED, SOLID-PILED, BIN BOX, SHELF, OR BACK-TO-BACK SHELF STORAGE OF CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES

TABLE B NFPA 13, CHAPTER 21 – ALTERNATIVE SYSTEM DESIGN

OPEN-FRAME RACK (SINGLE, DOUBLE, AND MULTIPLE ROW) STORAGE OF CLASSES I - IV AND CARTONED NON-EXPANDED PLASTIC COMMODITIES

Page 17: rociadores std tyco

Model ESFR-25 25.2 K-factor Pendent Sprinkler Early Suppression, Fast Response

Page 1 of 4 APRIL 2015 TFP312

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

In all cases, the appropriate NFPA or FM Global installation standard, or other applicable standard, must be referenced to ensure applicability and to obtain complete installation guide-lines. The general guidelines in this data sheet are not intended to provide complete installation criteria.

Sprinkler Identification Number (SIN)TY9226

TY9226 is a re-designation for Central SIN 9226, Gem SIN G8441, and Star SIN S8010.

sures, as compared to ESFR Sprinklers having nominal K-factors of 14.0 and 16.8. This feature offers flexibility when sizing system piping, as well as possi-bly reducing or eliminating the need for a system fire pump.

Also, Model ESFR-25 Sprinklers permit use of a maximum deflec-tor-to-ceiling distance of 18 inches (460 mm) versus 14 inches (356 mm). Additionally, a storage arrangement of 40 ft. (12,2 m) with a ceiling height of 45 ft. (13,7 m) does not require in-rack sprinklers as do other ESFR Sprin-klers having nominal K-factors of 14.0 and 16.8.

The Model ESFR-25 Sprinklers are listed by Underwriters Laborato-ries (UL) for specific applications with a maximum storage height of 43 ft. (13,1 m) with a maximum ceiling height of 48 ft. (14,6 m) without the requirement for in-rack sprinklers. Refer to the Specific Application Listing (UL) for the design criteria.

Applications for the TYCO ESFR Sprin-klers are expanding beyond currently recognized installation standards. For information on research fire tests (e.g., with flammable liquids and aerosols) that may be acceptable to an author-ity having jurisdiction, contact Tyco Fire Protection Products (TFPP) Technical Services.

NOTICEThe Model ESFR-25 Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the National Fire Pro-tection Association (NFPA), in addition to the standards of any authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the perfor-mance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

General DescriptionTYCO Model ESFR-25 Pendent Sprin-klers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 25.2 (Ref. Figure 1). They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.

The Model ESFR-25 Sprinklers are pri-marily used for ceiling-only sprinkler protection of (but not limited to) the fol-lowing storage applications:

• most encapsulated or non-encap-sulated common materials including cartoned, unexpanded plastics

• uncartoned (exposed) expanded plastics in accordance with NFPA 13 and FM Global standards

• some storage arrangements of rub-ber tires, roll paper, flammable liq-uids, aerosols, and automotive components

For more specific criteria, refer to Table A as well as the applicable design standard.

The Model ESFR-25 Pendent Sprin-klers provide the system designer with hydraulic and sprinkler place-ment options not presently available to the traditional ESFR sprinklers having nominal K-factors of 14.0 and 16.8. In particular, the Model ESFR-25 Sprin-kler has been designed to operate at substantially lower-end head pres-

Page 18: rociadores std tyco

TFP312Page 2 of 4

Technical DataApprovalsUL and C-UL Listed FM Approved VdS Approved NYC Approved under MEA 356-01-E LPCB Certified (Cert. Nos. 094b and 007l) CE Certified (Certificate of Conformity 1725-CPD-H0010)Maximum Working Pressure175 psi (12,1 bar)Pipe Thread Connections1 Inch NPT or ISO 7-R 1Discharge CoefficientK=25.2 gpm/psi1/2 (362,9 lpm/bar1/2)Temperature Ratings165°F (74°C) and 212°F (100°C)FinishNatural BrassPhysical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Compression Screw . . . . . . . . . . Stainless Steel Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Sealing Assembly . Beryllium Nickel w/TEFLON Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL

Design CriteriaThe following general guidelines pro-vided for the TYCO Model ESFR-25

Pendent Sprinklers can be used for a quick reference.

The National Fire Protection Associa-tion (NFPA) and FM Global (FM Approv-als) provide installation standards that must be used to properly design an automatic sprinkler system utilizing Early Suppression, Fast Response (ESFR) Sprinklers. The guidelines pro-vided by NFPA and FM Global may differ. Consequently, the appropri-ate standard must be used for a given installation.

In all cases, the appropriate NFPA or FM Global installation standard must be referenced to ensure applicabil-ity and to obtain complete installation guidelines.

The following general guidelines are not intended to provide complete installa-tion criteria.

In addition to this technical data sheet, the following data sheets describe other TYCO ESFR Sprinklers:

• TFP315 Model ESFR-17 (TY7226) K=16.8 Pendent Sprinkler

• TFP316 Model ESFR-17 (TY7126) K=16.8 Upright Sprinkler

• TFP318 Model ESFR-1 (TY6226) K=14.0 Pendent Sprinkler

System TypeWet Pipe

Roof ConstructionUnobstructed or obstructed con-

struction (e.g., smooth ceiling, bar joists, beam and girder, and so forth). Where the depths of the solid struc-tural members (e.g., beams and stem) exceed 12 inches (302 mm), install ESFR Sprinklers in each channel formed by the structural members.

Ceiling SlopeMaximum 2 inch rise for 12 inch run (16.7%)

Maximum Coverage Area100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Coverage Area64 ft.2 (5,8 m2) per NFPA 13 / FM Global 2-0

Maximum Spacing

Components:

2

3

6

4

5

9

8

7

1

1" NPT

WRENCHFLATS

3-13/16"(96,8 mm)

9/16"(14,3 mm)NOMINALMAKE-IN

2" (50,8 mm)

1-13/16"(46,0 mm)

THERMALSENSINGELEMENT

TEMPERATURERATING

- Hook4

-9

-78 -

56

-- Link Assembly

Ejection Spring

SealingAssembly

Button

Strut

-23 -

1 -

CompressionScrew

De�ectorFrame

"FITTING SIDE"TOWARDS SPRINKLER

FITTING

WRENCHRECESS

FIGURE 1 MODEL ESFR-25 PENDENT SPRINKLER, 25.2K

EARLY SUPPRESSION, FAST RESPONSE

FIGURE 2 W-TYPE 1

SPRINKLER WRENCH

Page 19: rociadores std tyco

TFP312Page 3 of 4

12 feet (3,7 m) for building heights up to 30 feet (9,1 m)

10 feet (3,1 m) for building heights greater than 30 feet (9,1 m). In some cases, installation standards permit a greater spacing.

Minimum Spacing8 feet (2,4 m)

Minimum Clearance to Commodity36 inches (914 mm)

NFPA Deflector-to-Ceiling Distance6 to 18 inches (152 to 457 mm)

FM Global Centerline of Thermal Sensing Element-to-Ceiling DistanceRefer to FM Global 2-0 for Storage Sprinklers.

Specific Application Listing (UL)TYCO Model ESFR-25 Pendent Sprin-klers are listed by Underwriters Labo-ratories (UL) for Specific Applications with a ceiling height greater than 45 ft. (13,7 m) up to and includ-ing 48 ft. (14,6 m), and a storage arrangement up to and including 43 ft. (13,1 m), the following guide-line are provided for the TYCO Model ESFR-25 Pendent Sprinklers:

Sprinkler PositionPendent: Frame arms aligned with pipe Deflectors parallel with ceiling or roof

System TypeWet Pipe only

Maximum Area of Coverage100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Area of Coverage64 ft.2 (5,8 m2) according to NFPA 13

Maximum Slope Ceiling2 inch rise for 12 inch run (16.7%)

Maximum Spacing10 feet (3,1 m)

In some cases, the installation stan-dards permit a greater spacing.

Minimum Spacing8 feet (2,4 m)

Temperature Rating212°F (100°C)

Deflector Distance from WallsMinimum of 4 inches (102 mm) from walls but no more than 1/2 the allow-able distance permitted between sprinklers

Deflector to Top of StorageMinimum of 36 inches (914 mm)

Deflector-to-Ceiling Distance6 to 14 inches (152 to 356 mm)

Maximum Ceiling Height48 feet (14,6 m)

Maximum Storage Height43 feet (13,1 m)

Storage ArrangementPalletized, solid piled, open frame, single row, or double row

CommodityClass I-IV Cartoned, unexpanded plastic

Sprinkler System DesignNFPA 13 for ESFR Sprinklers based upon 45 psi (3,1 bar) design pressure, 169 gpm (640 lpm) with 12 sprinkler remote area

Minimum Aisle Width8 feet (2,4 m)

OperationThe fusible link assembly is com-prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and flowing water.

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves)Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 16 and 17

Refer to FM Global 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 14 and 15

Refer to FM Global 2-0 and 8-9

Idle Pallet Storage Refer to NFPA 13 Chapter 12

Refer to FM Global 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Chapter 18

Refer to FM Global 2-0 and 8-9

Roll Paper Storage (Refer to the Standard)

Refer to NFPA 13 Chapter 19 Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage (Refer to the Standard) Refer to NFPA 30 Refer to FM Global 7-29

Aerosol Storage (Refer to the Standard) Refer to NFPA 30B Refer to FM Global 7-31

Automotive Components in Portable Racks (Control mode only; refer to the Standard)

Refer to NFPA 13 Chapter 20 N/A

N/A – Not Applicable

TABLE A MODEL ESFR-25 PENDENT SPRINKLER

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Page 20: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP312Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.MONEL and INCONEL are trademark of Special Metals Corporation. TEFLON is trademark of DuPont Corporation.

ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Sprinkler AssembliesSpecify: Model ESFR-25 Early Sup-pression, Fast Response 25.2K Pendent Sprinklers (TY9226), (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . .P/N 58-441-1-165 212°F (100°C) . . . . . . . . . . . . . .P/N 58-441-1-214

Special Order Sprinkler Assemblies with ISO 7-1 Thread ConnectionSpecify: Model ESFR-25, Early Sup-pression, Fast Response 25.2K Pendent Sprinklers (TY9226) with ISO 7-1 thread connection, (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-442-1-165 212°F (100°C) . . . . . . . . . . . . . P/N 58-442-1-214

Sprinkler WrenchSpecify: W-Type 1 Sprinkler Wrench, P/N 56-872-1-025

main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installa-tion section).

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering

InstallationTYCO Model ESFR-25 Early Suppres-sion, Fast Response 25.2K Pendent Sprinklers must be installed in accor-dance with this section.

General InstructionsDamage to the fusible Link Assem-bly during installation can be avoided by handling the sprinkler by the frame arms only (i.e., do not apply pressure to the fusible Link Assembly), and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.

A leak-tight 1 inch NPT sprinkler joint should be obtained by apply-ing a minimum-to-maximum torque of 20 to 30 lbs.-ft. (26,8 to 40,2 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model ESFR-25 Pendent Sprinkler in the pendent posi-tion (Ref. Figure 2).

Step 1. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting. Do not apply pres-sure to the Link Assembly, and handle the Model ESFR-25 Pendent Sprinkler only by the Frame arms.

Step 2. Wrench-tighten the Model ESFR-25 Pendent Sprinkler using only the W-Type 1 Sprinkler Wrench (Ref. Figure 2) and by fully engaging (seating) the wrench on the sprinkler wrench flats (Ref. Figure 1).

Step 4. After installation, inspect the Link Assembly of each Model ESFR-25 Pendent Sprinkler for damage. In par-ticular, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assem-bly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.

Care and MaintenanceTYCO Model ESFR-25 Early Suppres-sion, Fast Response 25.2K Pendent Sprinklers must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system

Page 21: rociadores std tyco

Model ESFR-17 16.8 K-factor Upright Sprinkler Early Suppression, Fast Response

Page 1 of 4 APRIL 2015 TFP316

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionTYCO Model ESFR-17 Upright Sprin-klers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 16.8 (Ref. Figure 1). They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled storage.

Model ESFR-17 Sprinklers are primarily used for ceiling-only sprinkler protec-tion of (but not limited to) the following storage applications:

• most encapsulated or non-encap-sulated common materials including cartoned, unexpanded plastics

• cartoned, expanded plastics

• some storage arrangements of rubber tires and roll paper

For more specific criteria, refer to Table A in this technical data sheet as well as the applicable design standard.

The Model ESFR-17 Upright Sprin-klers provide the system designer with an upright option to the traditional pendent ESFR Sprinklers. With a K-fac-tor of 16.8, Model ESFR-17 Sprinklers provide system designers with hydrau-lic and sprinkler placement options not presently available to traditional ESFR Sprinklers having a K-factor of 14.0. In particular, the Model ESFR-17 Upright Sprinklers are designed to operate at substantially lower-end head pressures compared to ESFR Sprinklers with 14.0 K-factors. This feature offers flexibility

when sizing system piping and posi-tioning the system piping with respect to the ceiling.

Applications for the TYCO ESFR Sprin-klers are expanding beyond currently recognized installation standards. For information on research fire tests that may be acceptable to an authority having jurisdiction, contact Tyco Fire Protection Products (TFPP) Technical Services.

NOTICEThe Model ESFR-17 Upright Sprinklers described herein must be installed and maintained in compliance with this doc-ument, as well as with the applicable standards of the National Fire Protec-tion Association (NFPA), in addition to the standards of any authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the performance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

In all cases, the appropriate NFPA or FM Global installation standard must be referenced to ensure applicabil-ity and to obtain complete installa-tion guidelines. The general guidelines in this data sheet are not intended to provide complete installation criteria.

Sprinkler Identification Number (SIN)TY7126

Technical DataApprovalsFM Approved CE Certified (Certificate of Conformity 1725-CPD-H0012)Maximum Working Pressure175 psi (12,1 bar)Pipe Thread Connections3/4 Inch NPT or ISO 7-R 3/4Discharge CoefficientK=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)Temperature Ratings165°F (74°C) and 212°F (100°C)FinishNatural BrassPhysical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . Copper Compression Screw . . . . . . . . . . Stainless Steel Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Sealing Assembly . . Beryllium Nickel w/TEFLON Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL Deflector Nut . . . . . . . . . . . . . . . . . . . . . . . .Brass

Page 22: rociadores std tyco

TFP316Page 2 of 4

Design CriteriaThe following general guidelines pro-vided for the TYCO Model ESFR-17 Upright Sprinklers may be used for quick reference.

The National Fire Protection Associa-tion (NFPA) and FM Global (FM Approv-als) provide installation standards that must be used to properly design an automatic sprinkler system utilizing Early Suppression, Fast Response (ESFR) Sprinklers. The guidelines pro-vided by NFPA and FM Global may differ; consequently, the appropriate standard must be used for a given installation.

In all cases, the appropriate NFPA or FM Global installation standard must be referenced to ensure applicabil-ity and to obtain complete installation guidelines, since the following general guidelines are not intended to provide complete installation criteria.

In addition to this technical data sheet, the following data sheets describe other TYCO ESFR Sprinklers:

• TFP312 Model ESFR-25 (TY9226) K=25.2 Pendent Sprinkler

• TFP315 Model ESFR-17 (TY7226) K=16.8 Pendent Sprinkler

• TFP318 Model ESFR-1 (TY6226) K=14.0 Pendent Sprinkler

System TypeWet Pipe

Roof ConstructionUnobstructed or obstructed construc-tion (e.g., smooth ceiling, bar joists, beam and girder, and so forth)

Where the depths of the solid struc-tural members (e.g., beams and stem) exceed 12 inches (302 mm), install ESFR Sprinklers in each channel formed by the structural members.

Ceiling SlopeMaximum 2 inch rise for 12 inch run (16.7%)

Maximum Coverage Area100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Coverage Area64 ft.2 (5,8 m2) per NFPA 13 / FM Global 2-0

Maximum Spacing12 feet (3,7 m) for building heights up to 30 feet (9,1 m)

10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)

Minimum Spacing8 feet (2,4 m)

Minimum Clearance to Commodity36 inches (914 mm)

NFPA 13 Deflector-to-Ceiling Distance3 to 12 inches (76,2 to 304 mm)

FM Global Centerline of Thermal Sensing Element-to-Ceiling DistanceRefer to FM Global 2-0 for Storage Sprinklers.

Obstructions below Upright ESFR Sprinklers, Including BranchlinesPer the requirements of FM, obstruc-tions below upright ESFR Sprinklers can be ignored as follows

• open-web bar joists or trusses having chords no more than 4 inches (102 mm) wide

• bridging or wind bracing no more than 4 inches (102 mm) wide

• individual pipes and conduit 4 inches (102 mm) diameter or less 3 inch [DN80] pipe size or less will not require sprigs)

• individual groups of smaller pipe or conduit having a total width of 4 inches or less

OperationThe fusible link assembly is com-prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and flowing water.

Components:

9

2

6

5

4

3

1

7

8

10

2-9/16" DIA.(65,0 mm)

3-5/8"(92,1 mm)

1/2"(12,7 mm)NOMINALMAKE-IN

WRENCHFLATS

1-5/8"(41,3 mm)

THERMALSENSINGELEMENT

TEMPERATURERATING

3/4" NPT

-2 De�ector

Ejection Spring

SealingAssembly

Hook

CompressionScrew

-8

-4

7 -

3 -

Frame1 -

ButtonLink Assembly-6

5 - Strut

De�ector Nut9 -

10 -

FIGURE 1 MODEL ESFR-17 UPRIGHT SPRINKLER, 16.8K

EARLY SUPPRESSION, FAST RESPONSE

Page 23: rociadores std tyco

TFP316Page 3 of 4

InstallationTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Upright Sprinklers must be installed in accor-dance with this section.

General InstructionsAvoid damage to the fusible Link Assembly during installation by using the Frame arms only to handle the sprinkler (i.e., do not apply pressure to the fusible Link Assembly) and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.

A leak-tight 3/4 inch NPT sprinkler joint should be obtained by apply-ing a minimum-to-maximum torque of 10 to 20 lbs.-ft. (13,4 to 26,8 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model ESFR-17 Upright Sprinkler in the Upright posi-tion (Ref. Figure 2).

Step 1. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting. Do not apply pres-sure to the Link Assembly, and handle the Model ESFR-17 Sprinkler only by the Frame arms.

Step 2. Wrench-tighten the Model ESFR-17 Upright Sprinkler using only the W-Type 21 Sprinkler Wrench (Ref. Figure 2) and by fully engaging (seating) the wrench on the sprinkler wrench flats (Ref. Figure 1).

Step 3. After installation, inspect the Link Assembly of each Model ESFR-17 Sprinkler for damage. In particular, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assembly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves)Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 16 and 17 Refer to FM 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 14 and 15 Refer to FM 2-0 and 8-9

Idle Pallet Storage Refer to NFPA 13 Chapter 12 Refer to FM 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Chapter 18 Refer to FM 2-0 and 8-9

Roll Paper Storage (Refer to the standard)

Refer to Chapter 13 Chapter 19 Refer to FM 8-21

Flammable/Ignitable Liquid Storage (Refer to the standard) N/A Refer to FM 7-29

Aerosol Storage (Refer to the standard) N/A N/A

Automotive Components in Portable Racks (Control mode only; refer to the standard) N/A N/A

N/A – Not Applicable

WRENCHRECESS

"FITTING SIDE"TOWARDS SPRINKLER

FITTING

TABLE A MODEL ESFR-17 UPRIGHT SPRINKLER

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

FIGURE 2 W-TYPE 21

SPRINKLER WRENCH

Page 24: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP316Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.INCONEL and MONEL are trademark of Special Metals Corporation. TEFLON is trademark of the DuPont Corporation.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Care and MaintenanceTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Upright Sprinklers must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installa-tion Section).

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Sprinkler AssembliesSpecify: Model ESFR-17 Early Sup-pression, Fast Response 16.8K Upright Sprinklers (TY7126), (specify tempera-ture rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . .P/N 58-447-1-165 212°F (100°C) . . . . . . . . . . . . . .P/N 58-447-1-214

Special Order Sprinkler Assemblies with ISO 7-1 Thread ConnectionSpecify: Model ESFR-17 Early Sup-pression, Fast Response 16.8K Upright Sprinklers (TY7126) with ISO 7-1 thread connection, (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-448-1-165 212°F (100°C) . . . . . . . . . . . . . P/N 58-448-1-214

Sprinkler WrenchSpecify: W-Type 21 Sprinkler Wrench, P/N 56-001-0-686

Page 25: rociadores std tyco

Model ESFR-17 16.8 K-factor Pendent Sprinkler Early Suppression, Fast Response

Page 1 of 4 APRIL 2015 TFP317

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

Technical DataApprovalsUL Listed C-UL Listed FM ApprovedMaximum Working Pressure175 psi (12,1 bar)Pipe Thread Connections3/4 Inch NPT or ISO 7-R 3/4Discharge CoefficientK=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)Temperature Ratings165°F (74°C) and 212°F (100°C)FinishNatural BrassPhysical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Compression Screw . . . . . . . . . . Stainless Steel Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel Button . . . . . . . . . . . . . . . . . . . Phosphor Bronze Sealing Assembly . . Beryllium Nickel w/TEFLON

General DescriptionTYCO Model ESFR-17 Pendent Sprin-klers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 16.8 (Ref. Figures 1 and 2). They are suppression mode sprinklers that are especially advanta-geous as a means of eliminating in-rack sprinklers when protecting high-piled storage.

Model ESFR-17 Pendent Sprinklers are primarily used for ceiling-only sprinkler protection of (but not limited to) the fol-lowing storage applications:

• most encapsulated or non-encap-sulated common materials including cartoned, unexpanded plastics

• cartoned, expanded plastics

• uncartoned, unexpanded plastics

• uncartoned, expanded plastics

• some storage arrangements of rubber tires, roll paper, and aerosols

For more specific criteria, refer to Table 1 in this technical data sheet as well as the applicable design standard.

The Model ESFR-17 Pendent Sprin-klers provide the system designer with hydraulic and sprinkler place-ment options not presently available to traditional ESFR Sprinklers having a nominal K-factor of 14.0. In particu-lar, Model ESFR-17 Pendent Sprinklers are designed to operate at substan-tially lower-end head pressures, as

compared to ESFR Sprinklers having a nominal K-factor of 14.0. This feature offers flexibility when sizing system piping, as well as possibly reducing or eliminating the need for a system fire pump.

Applications for the ESFR-17 Pendent Sprinklers are expanding beyond cur-rently recognized installation stan-dards. For information on research fire tests (with flammable liquids and aero-sols, for example) that may be accept-able to an authority having jurisdiction, contact Tyco Fire Protection Products (TFPP) Technical Services.

NOTICEThe Model ESFR-17 Pendent Sprinklers described herein must be installed and maintained in compliance with this doc-ument, as well as with the applicable standards of the National Fire Protec-tion Association (NFPA), in addition to the standards of any authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the performance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

In all cases, the appropriate NFPA or FM Global installation standard, or other applicable standard, must be ref-erenced to ensure applicability and to obtain complete installation guidelines. The general guidelines in this technical data sheet are not intended to provide complete installation criteria.

Sprinkler Identification Number (SIN)TY7223

Page 26: rociadores std tyco

TFP317Page 2 of 4

Design CriteriaThe following general guidelines pro-vided for the TYCO Model ESFR-17 Pendent Sprinklers can be used for a quick reference.

The National Fire Protection Associa-tion (NFPA) and FM Global (FM Approv-als) provide installation standards that must be used to properly design an automatic sprinkler system utilizing Early Suppression, Fast Response (ESFR) Sprinklers. The guidelines pro-vided by NFPA and FM Global may differ. Consequently, the appropri-ate standard must be used for a given installation.

In all cases, the appropriate NFPA or FM Global installation standard must be referenced to ensure applicabil-ity and to obtain complete installa-tion guidelines. The following general guidelines are not intended to provide complete installation criteria.

System TypeWet Pipe

Roof ConstructionUnobstructed or obstructed construc-tion (e.g., smooth ceiling, bar joists, beam and girder, etc.).

Where the depths of the solid struc-tural members (e.g., beams and stem) exceed 12 in. (302 mm), install ESFR Sprinklers in each channel formed by the structural members.

Ceiling SlopeMaximum 2 inch rise for 12 inch run (16.7%)

Maximum Coverage Area100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Coverage Area64 ft.2 (5,8 m2) per NFPA 13

Maximum Spacing12 feet (3,7 m) for building heights up to 30 feet (9,1 m)

10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)

Minimum Spacing8 feet (2,4 m)

Minimum Clearance to Commodity36 inches (914 mm)

NFPA 13 Deflector-to-Ceiling Distance6 to 14 inches (152 to 356 mm)

FM Global 2-0Consult FM Global and/or FM Global guidelines for allowable deflector-to-ceiling distances as well as thermal sensing element-to-ceiling criteria.

OperationThe fusible link assembly is com-prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and flowing water.

*

*

**

***

1-1/2"(38,1 mm)

THERMALSENSINGELEMENT

3/4"NPT

2-3/8"(60,3 mm)

WRENCHFLATS

1/2"(12,7 mm)NOMINALMAKE-IN

- Link Assembly6

- Compression Screw3HookStrut

-4-5

De�ector

Components:Frame-1

2 -

7 -8 - Sealing Assembly

Button

Temperature rating is indicatedon De�ector.

ISO 7-R 3/4 pipe thread can beprovided on special request. 2

3

6

7

8

1

4

5

*

*

**

***

1-1/2"(38,1 mm)

THERMALSENSINGELEMENT

3/4"NPT

2-3/8"(60,3 mm)

WRENCHFLATS

1/2"(12,7 mm)NOMINALMAKE-IN

- Link Assembly6

- Compression Screw3HookStrut

-4-5

De�ector

Components:Frame-1

2 -

7 -8 - Sealing Assembly

Button

Temperature rating is indicatedon De�ector.

ISO 7-R 3/4 pipe thread can beprovided on special request. 2

3

6

7

8

1

4

5

FIGURE 1 MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 165°F (74°C)

EARLY SUPPRESSION, FAST RESPONSE

FIGURE 2 MODEL ESFR-17 PENDENT SPRINKLER, 16.8K, 212°F (100°C)

EARLY SUPPRESSION, FAST RESPONSE

Page 27: rociadores std tyco

TFP317Page 3 of 4

InstallationTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Pendent Sprinklers must be installed in accor-dance with this section.

General InstructionsAvoid damage to the fusible Link Assembly during installation by using only the Frame arms to handle the sprinkler (i.e., do not apply pressure to the fusible Link Assembly), and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.

A leak-tight 3/4 inch NPT sprinkler joint should be obtained by apply-ing a minimum-to-maximum torque of 10 to 20 lbs.-ft. (13,4 to 26,8 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model ESFR-17 Pendent Sprinkler in the pendent posi-tion (Ref. Figures 3 and 4).

Step 1. With pipe-thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting. Do not apply pres-sure to the Link Assembly, and handle the Model ESFR-17 Sprinkler only by the Frame arms.

Step 2. Wrench-tighten the Model ESFR-17 Sprinkler using only the W-Type 2 Sprinkler Wrench or the W-Type 30 Sprinkler Wrench (Ref. Figures 3 and 4), and by fully engag-ing (seating) the wrench on the sprin-kler wrench flats (Ref. Figures 1 and 2).

Step 3. After installation, inspect the Link Assembly of each Model ESFR-17 Sprinkler for damage. In particular, verify that the Link Assembly and Hook are positioned as illustrated in Figures 1 and 2, and that the Link Assembly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.

Storage Type NFPA

Open Frame (i.e., no solid shelves)Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 16 & 17

Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 14 & 15

Idle Pallet Storage Refer to NFPA 13 Chapter 12

Rubber Tire Storage Refer to NFPA 13 Chapter 18

Rolled Paper Storage (Refer to the standard)

Refer to NFPA 13 Chapter 19

Flammable Liquid Storage (Refer to the standard) Refer to NFPA 30

Aerosol Storage (Refer to the standard) Refer to NFPA 30B

Automotive Components in Portable Racks (Control mode only; refer to the standard) N/A

N/A – Not Applicable

WRENCHRECESS

"FITTING SIDE"TOWARD SPRINKLER

FITTING

1" WRENCHACCEPTS

WRENCHRECESS

1/2" DRIVEACCEPTSSOCKET

HEX

FLATSWRENCH

FIGURE 4 W-TYPE 30

SPRINKLER WRENCH

FIGURE 3 W-TYPE 2

SPRINKLER WRENCH

TABLE 1 MODEL ESFR-17 PENDENT SPRINKLER

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Page 28: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP317Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.MONEL is trademark of Special Metals Corporation. TEFLON is trademark of the DuPont Corporation.

Care and MaintenanceTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Pendent Sprinklers must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affected by this action.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installa-tion section).

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Sprinkler Assemblies with 3/4 NPT Thread ConnectionSpecify: Model ESFR-17 Early Sup-pression, Fast Response 16.8K Pendent Sprinklers (TY7223) with 3/4 NPT thread connection, (specify tem-perature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-455-1-165 212°F (100°C) . . . . . . . . . . . . . P/N 58-455-1-214

Special Order Sprinkler Assemblies with ISO 7-R 3/4 Thread ConnectionSpecify: Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Pendent Sprinklers (TY7223) with ISO 7-R 3/4 thread connection, (specify tempera-ture rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-456-1-165 212°F (100°C) . . . . . . . . . . . . . P/N 58-456-1-214

Sprinkler WrenchSpecify: W-Type 2 Sprinkler Wrench, P/N 56-872-1-001

Specify: W-Type 30 Sprinkler Wrench, P/N 56-001-0-688

Page 29: rociadores std tyco

Model ESFR-1 14.0 K-Factor Pendent Sprinkler Early Suppression, Fast Response

Page 1 of 4 MARCH 2015 TFP318

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionTYCO Model ESFR-1 Pendent Sprin-klers are Early Suppression, Fast Response (ESFR) sprinklers having a nominal K-factor of 14.0. They are suppression-mode sprinklers that are especially advantageous as a means of eliminating the use of in-rack sprinklers when protecting high-piled storage.

Model ESFR-1 Sprinklers are primarily designed for protection of the following storage arrangements:

• most encapsulated or non-encap-sulated common materials including cartoned, unexpanded plastics

• some storage arrangements of rubber tires, roll paper, flammable liquids

For more specific criteria, refer to Table A as well as the applicable design standard.

Applications for the TYCO ESFR Sprin-klers are expanding beyond currently recognized installation standards. For information on research fire tests (with flammable liquids and aerosols, for example) that may be acceptable to an authority having jurisdiction, contact the Tyco Fire Protection Products (TFPP) Technical Services.

NOTICEThe Model ESFR-1 Sprinklers described herein must be installed and maintained in compliance with this document, as well as with the applica-ble standards of the National Fire Pro-tection Association (NFPA), in addition to the standards of any other authorities having jurisdiction (e.g., FM Global). Failure to do so may impair the perfor-mance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

In all cases, the appropriate NFPA, FM Global installation standard, or other applicable standard, must be referenced to ensure applicability and to obtain complete installation guide-lines. The general guidelines in this data sheet are not intended to provide complete installation criteria.

Sprinkler Identification Number (SIN)TY6226

TY6226 is a re-designation for Central SIN C6226, Gem SIN G8440, and Star SIN S8000.

Technical DataApprovalsUL and C-UL Listed FM Approved VdS Approved NYC Approved under MEA 356-01-E LPCB Approved (Cert. Nos. 094b and 007l)Maximum Working Pressure175 psi (12,1 bar)Pipe Thread Connections3/4 Inch NPTDischarge CoefficientK=14.0 gpm/psi1/2 (201,6 lpm/bar1/2)Temperature Ratings165°F (74°C) and 212°F (100°C) FinishNatural BrassPhysical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Compression Screw . . . . . . . . . . Stainless Steel Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Ejection Spring . . . . . . . . . . . . . . . . . . INCONEL Sealing Assembly . Beryllium Nickel w/TEFLON

Page 30: rociadores std tyco

TFP318Page 2 of 4

Design CriteriaThe following general guidelines pro-vided for the TYCO ESFR-1 Sprinklers can be used for quick reference.

NOTICEThe National Fire Protection Associa-tion (NFPA) and FM Global (FM Approv-als) provide installation standards that must be used to properly design an automatic sprinkler system utilizing Early Suppression, Fast Response (ESFR) Sprinklers. The guidelines pro-vided by NFPA and FM may differ; con-sequently, the appropriate standard must be used for a given installation.

In all cases, the appropriate NFPA or FM installation standard must be ref-erenced to assure applicability and to obtain complete installation guidelines, since the following general guidelines are not intended to provide complete installation criteria.

In addition to this technical data sheet, the following data sheets describe other TYCO ESFR Sprinklers:

• TFP312 Model ESFR-25 (TY9226) K=25.2 Pendent Sprinkler

• TFP315 Model ESFR-17 (TY7226) K=16.8 Pendent Sprinkler

• TFP316 Model ESFR-17 (TY7126) K=16.8 Upright Sprinkler

System TypeWet Pipe

Roof ConstructionUnobstructed or obstructed construc-tion (e.g., smooth ceiling, bar joists, beam and girder, and so forth)

Where the depths of solid struc-tural members (beams and stem, for example) exceed 12 inches (302 mm), install ESFR Sprinklers in each channel formed by the structural members.

Ceiling SlopeMaximum 2-inch rise for 12-inch run (16.7%)

Maximum Coverage Area 100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Coverage Area 64 ft.2 (5,8 m2) per NFPA 13 / FM Global 2-0

Maximum Spacing12 feet (3,7 m) for building heights up to 30 feet (9,1 m)

10 feet (3,1 m) for building heights greater than 30 feet (9,1 m)

Minimum Spacing8 feet (2,4 m)

Minimum Clearance to Commodity36 inches (914 mm)

NFPA Deflector-to-Ceiling Distance6 to 14 inches (152 to 356 mm)

FM Global Centerline of Thermal Sensing Element-to-Ceiling DistanceRefer to FM Global 2-0 for Storage Sprinklers.

Operation The fusible link assembly is com-prised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and flowing water.

Components:

(12,7 mm)NOMINALMAKE-IN

1/2"

FLATSWRENCH

3-9/16"(90,5 mm)

1-7/8"(47,6 mm)

SENSINGELEMENT

THERMAL

1-1/2"(38,1 mm)

TEMPERATURERATING

Screw

FrameDe�ectorCompression

Assembly

ButtonSealing

Ejection Spring

Link Assembly-

9 -

6

87 -

-

-3

54 -

-

12 -

-

StrutHook

3/4" NPT

2

3

4

5

8

9

6

7

1

FIGURE 1 MODEL ESFR-1 PENDENT SPRINKLER, 14.0K

EARLY SUPPRESSION, FAST RESPONSE

Page 31: rociadores std tyco

TFP318Page 3 of 4

InstallationTYCO Model ESFR-1 Early Suppres-sion, Fast Response 14.0K Pendent Sprinklers must be installed in accor-dance with this section.

NOTICEDamage to the fusible Link Assem-bly during installation can be avoided by handling the sprinkler by the frame arms only (i.e., do not apply pressure to the fusible Link Assembly), and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.

A leak-tight 3/4 inch NPT sprinkler joint should be obtained by apply-ing a minimum-to-maximum torque of 10 to 20 lbs.-ft. (13,4 to 26,8 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model ESFR-1 Pendent Sprinkler in the pendent posi-tion (Ref. Figure 2).

Step 1. With pipe thread sealant applied, hand-tighten the sprinkler into the sprinkler fitting. Do not apply pres-sure to the Link Assembly, and handle the Model ESFR-1 Sprinkler only by the Frame arms.

Step 2. Wrench-tighten the Model ESFR-1 Sprinkler using only the W-Type 2 Sprinkler Wrench (Ref. Figure 2) and by fully engaging (seating) the wrench on the sprinkler wrench flats (Ref. Figure 1).

Step 3. After installation, inspect the Link Assembly of each Model ESFR-1 Sprinkler for damage. In particu-lar, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assembly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves)Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 16 and 17

Refer to FM Global 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 14 and 15

Refer to FM Global 2-0 and 8-9

Idle Pallet Storage Refer to NFPA 13 Chapter 12

Refer to FM Global 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Chapter 18

Refer to FM Global 2-0 and 8-9

Roll Paper Storage (Refer to the standard)

Refer to NFPA 13 Chapter 19

Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage (Refer to the standard) Refer to NFPA 30 Refer to FM Global

7-29

Aerosol Storage (Refer to the standard) Refer to NFPA 30B Refer to FM Global

7-31

Automotive Components in Portable Racks (Control mode only; refer to the standard) N/A N/A

N/A – Not Applicable

"FITTING SIDE"

FITTINGTOWARDS SPRINKLER

RECESSWRENCH

FIGURE 2 W-TYPE 2

SPRINKLER WRENCH

TABLE A MODEL ESFR-1 PENDENT SPRINKLER

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Page 32: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP318Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.MONEL and INCONEL are trademark of Special Metals Corporation. TEFLON is trademark of DuPont Corporation.

Care and MaintenanceTYCO Model ESFR-1 Early Suppres-sion, Fast Response 14.0K Pendent Sprinklers must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action.

Exercise care to avoid damage before, during, and after installation. Never paint, plate, coat, or otherwise alter automatic sprinklers after they leave the factory.

Replace sprinklers that:

• were modified or over-heated

• were damaged by dropping, striking, wrench twisting, wrench slippage, or the like

• are leaking or exhibiting visible signs of corrosion

Responsibility lies with the owner for the inspection, testing, and mainte-nance of their fire protection system and devices in compliance with this document, as well as with the applica-ble standards of the National Fire Pro-tection Association (for example, NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.

Automatic sprinkler systems are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).Sprinkler AssembliesSpecify: Model ESFR-14 Early Sup-pression, Fast Response 14.0K Pendent Sprinklers (TY6226), (specify temperature rating), with Natural Brass finish, P/N (specify):165°F (74°C) . . . . . . . . . . . . . . P/N 58-440-1-165 212°F (100°C) . . . . . . . . . . . . . P/N 58-440-1-214

Sprinkler WrenchSpecify: W-Type 2 Sprinkler Wrench, P/N 56-872-1-001

Page 33: rociadores std tyco

Model ESFR-17 16.8 K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response

Worldwide Contacts www.tyco-fire.com

Page 1 of 8 MARCH 2015 TFP320

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

General DescriptionTYCO Model ESFR-17 Dry Type Pendent Sprinklers are Early Suppres-sion, Fast Response (ESFR) sprinklers having a nominal K-factor of 16.8. They are suppression mode sprinklers that are especially advantageous as a means of eliminating in-rack sprinklers when protecting high-piled box-in-box refrigerated storage areas.

The Model ESFR-17 Dry Type Pendent Sprinkler is FM Approved and has successfully undergone full-scale fire testing at FM Global, when used in con-formance with applicable FM Global Property Loss Prevention Data Sheets.

The Model ESFR-17 Dry Type Sprin-kler consists of an ESFR sprinkler per-manently secured to a sprinkler drop featuring an inlet with both grooved and threaded connections. The drop between the inlet and sprinkler remains dry until the sprinkler operates, allow-ing for a pendent sprinkler installa-tion on a wet pipe sprinkler system where the dry drop and sprinkler are located in an area subjected to freezing temperatures.

The Model ESFR-17 Dry Type Sprin-klers are primarily used for ceiling only sprinkler protection (i.e., no need for in-rack sprinklers) and used to protect solid piled, palletized, and rack storage that is subject to freezing temperatures. The water supply is provided from a wet pipe system located outside of the refrigerated storage area. The Model ESFR-17 Dry Type Sprinklers feature

all of the same design criteria as 16.8 K-factor ESFR Pendent Sprinklers, and substantially lowers the end head pres-sure requirement as compared to the 14.0 K-factor ESFR Dry Type Pendent Sprinklers.

Combining a 16.8 K-factor with a dry-type sprinkler design, the Model ESFR-17 Dry Type Sprinkler provides the system designer with features that offer flexibility when sizing system piping, as well as possibly reducing or eliminating the need for a system fire pump when protecting high-piled box-in-box refrigerated storage areas.

The ESFR-17 Dry Type Sprinkler also includes two Insulating Seal Assem-blies that help seal the clearance space around the sprinkler casing. The seal assemblies are intended to slow the exchange of air between the heated area and the protected area to help prevent humidity and temperature dif-ferential in the area around the sprin-kler. Condensation on the sprinkler and subsequent ice buildup on or around the sprinkler can occur that might damage the sprinkler or prevent proper operation in a fire situation.

To install the Insulating Seal Assem-blies, follow the installation instruc-tions in this data sheet. The Insulating Seal Assemblies are recommended to be installed on smooth, flat, and clean surfaces. If it is expected that environ-mental conditions may result in exces-sive condensation, additional sealing of the assembly is recommended.

There are specific situations, such as corrugated surfaces where alternate methods to seal the clearance hole are recommended. For additional guid-ance, contact Tyco Fire Protection Products (TFPP) Technical Services.

NOTICEThe Model ESFR-17 Dry Type Pendent Sprinklers (TY7229) described herein must be installed and maintained in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa-tion (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor-mance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Sprinkler Identification Number (SIN)TY7229

Page 34: rociadores std tyco

TFP320Page 2 of 8

Technical DataApprovalsUL Listed FM Approved

(Refer to Table B for specific details on Laboratory listings and approvals.)Maximum Working Pressure175 psi (12,1 bar)Pipe Thread Connections1-1/4 Inch NPT or ISO 7-R 1-1/4Grooved Connection2 Inch Standard Cut Grooved per Technical Data Sheet TFP1898Discharge CoefficientK=16.8 gpm/psi1/2 (241,9 lpm/bar1/2)Temperature Ratings165°F (74°C) and 212°F (100°C)FinishRefer to Physical Characteristics.Physical CharacteristicsThreaded and Grooved Inlet . . . . . . . . . . .BronzeCasing . . . . . . . . . . . . . . . .Galvanized Steel Pipe Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . MONEL Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel

Design CriteriaThe following general guidelines and Table C, provide the key design criteria for the TYCO Model ESFR-17 Dry Type Pendent Sprinklers (TY7229).

In all cases, the appropriate NFPA installation standard, or other appli-cable standard, must be referenced to ensure applicability and to obtain complete installation guidelines. The general guidelines in this technical data sheet are not intended to provide com-plete installation criteria.

System TypeWet Pipe system only

Ceiling ConstructionUnobstructed or non-combustible obstructed construction (e.g., smooth ceiling, bar joists, beam and girder, etc.)

Ceiling SlopeMaximum 2 inch rise for 12 inch run (16.7%)

Maximum Coverage Area100 ft.2 (9,3 m2)

In some cases, the installation stan-dards permit a greater coverage area.

Minimum Coverage Area64 ft.2 (5,8 m2)

36 Inch (914 mm) Sprinkler

30 Inch (762 mm) Sprinkler

23 Inch (584 mm) Sprinkler

Dimension “A” 37.5 in. (952,5 mm)

31.3 in. (795 mm)

24.3 in. (617 mm)

Dimension “B” 36.2 (919,5 mm)

30.0 (762 mm)

23.0 (584 mm)

Dimension “C” 33.9 (861 mm)

27.7 (704 mm)

20.7 (526 mm)

Sprinkler Type

Temperature Rating

Laboratory Listings and Approvals

Pendent K=16.8 (TY7229)

165°F (74°C) 1, 2

212°F (100°C) 1

Notes:1. UL Listed2. FM Approved

2" (DN50)GROOVED

CONNECTION

1-1/4" NPTOR ISO 7-R 1-1/4PIPE THREADED

CONNECTION

INLETWRENCH

HEX

FRAMEWRENCH

FLATS

THREADEDAND GROOVED

INLET

LINKASSEMBLY

GROOVEDCOUPLING

GASKETSEALINGSURFACE

BUTTONWITH VENT

HOLES

TABLE ADIM. A

TABLE ADIM. B

TABLE ADIM. C

DEFLECTOR

HOOK

STRUT

FRAME

CASING

CENTERLINEOF THERMAL

SENSINGELEMENT

TABLE A SPRINKLER LENGTHS

TABLE B LABORATORY LISTINGS AND APPROVALS

FIGURE 1 MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER (TY7229)

Page 35: rociadores std tyco

TFP320Page 3 of 8

Maximum Spacing12 feet (3,7 m) for ceiling heights up to 30 feet (9,1 m)

10 feet (3,1 m) for ceiling heights greater than 30 feet (9,1 m)

Minimum Spacing8 feet (2,4 m)

Minimum Clearance to Commodity36 inches (914 mm)

NFPA Deflector-to-Ceiling Distance6 to 14 inches (152 to 356 mm)FM Global Centerline of Thermal Sensing Element-to-Ceiling DistanceRefer to FM Global 2-0 for Storage Sprinklers.Sprinkler Threaded Fittings1-1/4 inch NPT Model ESFR-17 Dry Type Sprinklers are to be installed in the 1-1/4 inch NPT outlet or run of the following fittings:

• malleable or ductile iron threaded tee fittings that meet the dimen-sional requirements of ANSI B16.3 (Class 150)

• cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125)

Do not install Model ESFR-17 Dry Type Sprinkler into elbow fittings. The inlet of the sprinkler can contact the interior of the elbow and result in damage to the assembly, resulting in leakage.

The Model ESFR-17 Dry Type Sprinkler can also be installed in the 1-1/4 inch NPT outlet of a GRINNELL Figure 730 Mechanical Tee.Sprinkler Grooved ConnectionThe Model ESFR-17 Dry Type Sprin-klers can be installed in typical grooved connection scenarios illustrated in Figure 7.

For flexible couplings, use of the 2 inch Figure 705 GRINNELL Flexible Cou-plings with “C” Shape Pre-Lubricated Grade “A” EPDM Gasket (Ref. TFP1820) is recommended.

For rigid couplings, use of the 2 inch, Figure 577 GRINNELL G-FIRE Grooved Rigid Coupling with “C” Shape Pre-Lubricated Grade “A” EPDM Gasket (Ref. TFP1854) is recommended.

When using tees, use of the Figure 219 GRINNELL Grooved Ductile Iron Cast Fittings (Ref. TFP1810) is recommended.

NOTICEDo not install Model ESFR-17 Dry Type Sprinkler into any other type fitting con-nection without first consulting TFPP Technical Services. Failure to use the appropriate fitting may result in insuf-ficient engagement of the inlet pipe threads with consequent leakage.Exposure LengthWhen using Model ESFR-17 Dry Type Sprinklers to protect areas subject to freezing temperatures, use Figures 2 and 3, and Table D to determine a sprinkler’s appropriate exposed barrel length to prevent water from freezing in the connection pipes due to conduc-tion. The exposed barrel length mea-surement must be taken from the face of the sprinkler fitting to the exterior surface of the structure or insulation that is exposed to the heated area.

Do not attempt to add additional insu-lation around the barrel in the heated area as a method to minimize conden-sation. This will reduce the calculated exposure length.

Storage Type NFPA FM Global

Open Frame (i.e., no solid shelves)Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 16 and 17

Refer to FM Global 2-0 and 8-9

Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics

Refer to NFPA 13 Chapters 14 and 15

Refer to FM Global 2-0 and 8-9

Idle Pallet Storage Refer to NFPA 13 Chapter 12

Refer to FM Global 2-0, 8-9, and 8-24

Rubber Tire Storage Refer to NFPA 13 Chapter 18

Refer to FM Global 2-0 and 8-3

Roll Paper Storage (Refer to the standard)

Refer to NFPA 13 Chapter 19 Refer to FM Global 8-21

Flammable/Ignitable Liquid Storage (Refer to the standard) Refer to NFPA 30 Refer to FM Global 7-29

Aerosol Storage (Refer to the standard) Refer to 30B Refer to FM Global 7-31

Automotive Components in Portable Racks (Control mode only; refer to the standard) N/A N/A

N/A = Not Applicable

TABLE C MODEL ESFR-17 DRY TYPE PENDENT SPRINKLER

COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW

Page 36: rociadores std tyco

TFP320Page 4 of 8

Ambient Temp. of

Protected Area(a)

Exposed Barrel Ambient

Temperature(b)(c)

40°F (4°C)

50°F (10°C)

60°F (16°C)

Minimum Exposed Barrel Length

Inches (mm)

40°F (4°C) 0 0 0

30°F (-1°C) 0 0 0

20°F (-7°C)

4 (101,6) 0 0

10°F (-12°C)

8 (203)

1 (25,4) 0

0°F (-18°C)

12 (305)

3 (76) 0

-10°F (-23°C)

14 (356)

4 (101,6)

1 (25,4)

-20°F (-29°C)

14 (356)

6 (152)

3 (76)

-30°F (-34°C)

16 (406)

8 (203)

4 (101,6)

-40°F (-40°C)

18 (457)

8 (203)

4 (101,6)

-50°F (-46°C)

20 (508)

10 (254)

6 (152)

-60°F (-51°C)

20 (508)

10 (254)

6 (152)

Notes:a. The area below the ceiling is referred to as the

protected area. Ambient temperature is the tem-perature at the discharge end of the sprinkler. For protected area temperatures that range between the listed temperatures, use the next cooler temperature.

b. Lengths are inclusive of wind velocities up to 30 mph (48,3 km/h) and assume a minimum 40°F (4°C) in heated area.

c. Minimum exposed barrel length when Insulating Seal Assembly is installed on exterior surface of ceiling:• Threaded Fitting Installation – 5 in. (125 mm)

(Ref. Figure 2)• Grooved Fitting Installation – 4-1/2 in. (114

mm) (Ref. Figure 3)

PROTECTEDAREA

HEATEDAREA

EXPOSEDBARRELLENGTH

(REFER TOTABLE D

AND DESIGNCRITERIA)

FACE OFSPRINKLER

FITTING

CEILINGDEPTH

6" (152 mm)MINIMUM

14" (356 mm)MAXIMUM

CLEARANCEHOLE

2-1/2" to 3"(65 to 75 mm)

DIA.

END OFSPRINKLER

INLET

THREADEDFITTING

(REFER TODESIGN

CRITERIA)

INSULATINGSEAL

ASSEMBLIESEXTERIOR

SURFACE OFCEILING

INTERIORSURFACE OF

CEILING

DIM. ATABLE A DIM. B

TABLE A

1" (25,4 mm) NOMINAL SYSTEMPIPE

HEATEDAREA

PROTECTEDAREA

EXPOSEDBARRELLENGTH

(REFER TOTABLE D

AND DESIGNCRITERIA)

FACE OFSPRINKLER

FITTING

EXTERIORSURFACE OF

CEILING

INTERIORSURFACE OF

CEILING

CEILINGDEPTH

6" (152 mm)MINIMUM

14" (356 mm)MAXIMUM

CLEARANCEHOLE

2-1/2" to 3"(65 to 75 mm)

DIA.

SYSTEMPIPE

END OFSPRINKLER

INLETGROOVED

FITTING ANDRIGID ORFLEXIBLE

COUPLING(REFER TO

DESIGNCRITERIA)

INSULATINGSEAL

ASSEMBLIES

1-3/8"(35 mm)

DIM. BTABLE A

DIM. ATABLE A

TABLE D MINIMUM EXPOSED

BARREL LENGTH REQUIRED PER AMBIENT TEMPERATURE

FIGURE 2 THREADED FITTING INSTALLATION

FIGURE 3 GROOVED CONNECTION INSTALLATION

Page 37: rociadores std tyco

TFP320Page 5 of 8

GROOVEDTEE

WELDEDGROOVED OUTLET

GROOVEDDROP NIPPLE

GROOVED RIGID ORFLEXIBLE COUPLING(REFER TO DESIGN

CRITERIA)

MODEL ESFR-17SPRINKLER

"SPRINKLERSIDE"

APPLY WRENCHJAW TO INLETWRENCH HEX

APPLYWRENCHJAW TOFRAME

WRENCHFLATS

WRENCHJAW

"INLETSIDE"

FRAMEARM

W-TYPE 26WRENCH

W-TYPE 26WRENCH

"FITTINGSIDE"

W-TYPE 26WRENCH

WRENCHJAW

WRENCHFRAME ARMCLEARANCE

RECESS

THREADEDSPRINKLER

FITTING

SPRINKLERDEFLECTOR

"SPRINKLERSIDE" TOWARD

SPRINKLERDEFLECTOR

"FITTING SIDE"TOWARD

SPRINKLERFITTING

SPRINKLERFRAMEARMS

SYSTEMPIPE

SPRINKLERFITTING

CLEARANCEHOLE

CEILING

"FRAMEARMS"

REFERENCEMARKS

INDICATERELATIVE

SPRINKLERFRAME ARMORIENTATION

BELOWCEILING

ORIENTHOUSINGSLOT 180°OPPOSEDTO INSERT

SLOT

INSERT

HOUSING

INSULATIONRING

CLEARANCEHOLE

SELFTAPPINGSCREWS

ORIENTINSULATIONRING SPLITBETWEENHOUSINGSLOT AND

SCREW

FIGURE 4 TYPICAL GROOVED CONNECTION

OPTIONS

FIGURE 6 SPRINKLER FRAME ARMS

ORIENTATION MARK

FIGURE 7 INSULATING SEAL ASSEMBLY

INSTALLATION

FIGURE 5 W-TYPE 26

SPRINKLER WRENCH

Page 38: rociadores std tyco

TFP320Page 6 of 8

Clearance SpaceIn accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, when protecting insulated freezer structures with dry type sprinklers, the clearance hole around the sprinkler barrel of the Dry Type Sprinkler and the clear-ance hole must be sealed. Sealing is accomplished by use of the Insulating Seal Assemblies (Ref. Figure 7). Failure to use the Insulating Seal Assemblies will increase the potential for the for-mation of condensation on the sprin-kler and subsequent ice build-up on or around the sprinkler can occur that might damage the dry type sprinkler and/or prevent proper operation in a fire situation.FM Global 2-0Consult FM Global and/or FM Global guidelines for allowable vertical dis-tance from ceiling to centerline of thermal sensing element.

OperationThe casing between the inlet and the sprinkler remains dry until the sprinkler operates. The fusible link assembly is comprised of two link halves that are joined together by a thin layer of solder. When the rated temperature is reached, the solder melts and the two link halves separate, activating the sprinkler and allowing water to flow through the casing and to the activated sprinkler.

InstallationTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Pendent Sprinklers must be installed in accor-dance with this section.

General InstructionsAvoid damage to the fusible Link Assembly during installation by using only the Casing to handle the sprin-kler (i.e., do not apply pressure to the fusible Link Assembly), and by using the appropriate sprinkler wrench. Failure to do so can lead to an unstable link assembly and premature activation of the sprinkler. Damaged sprinklers must be replaced.

Model ESFR-17 Dry Type Sprinklers must only be installed in fittings/con-nections that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important requirements regarding piping design, exposure length, and the sealing of the clearance space around the sprinkler casing.

If a sprinkler using a threaded connec-tion (vs. grooved connection) requires replacement, remove the sprinkler using only the W-Type 26 Sprinkler Wrench. Fully engage the wrench on the inlet wrench hex (Ref. Figure 5).

Replace with the new sprinkler follow-ing the installation instructions in this section.

Threaded Connection InstructionsA leak-tight 1-1/4 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 45 to 65 lbs.-ft. (61 to 88 Nm). Higher levels of torque can distort the sprinkler inlet with consequent leakage or impairment of the sprinkler.

Note: Install the Model ESFR-17 Dry Type Pendent Sprinkler in the pendent position (Ref. Figure 5) by carefully raising the pendent sprinkler through the clearance hole. The deflector of the pendent sprinkler is to be parallel to the ceiling.

Step 1. Apply a non-hardening pipe thread sealant such as TEFLON to the male 1-1/4 inch NPT inlet threads.

Step 2. Wrench-tighten the Model ESFR-17 Dry Type Sprinkler using only the W-Type 26 Sprinkler Wrench and by fully engaging the wrench on the inlet wrench hex (Ref. Figure 5). For refer-ence, the “FRAME ARMS” marking can be used to align the frame arms with the System Pipe as shown in Figure 5.

Step 3. After installation, inspect the Link Assembly of each Model ESFR-17 Dry Type Sprinkler for damage. In par-ticular, verify that the Link Assembly and Hook are positioned as illustrated in Figure 1, and that the Link Assem-bly is not bent, creased, or forced out of normal position in any way. Replace damaged sprinklers.

Step 4. Install the insulation rings of the Insulating Seal Assemblies by slipping the insulation rings around the sprin-kler casing as shown in Figure 7. Place the inserts over the insulation rings by sliding the inserts around the casing. Place the housings over the Inserts and insulation rings ensuring that the slot on the housings are 180 degrees to the inserts slot. Ensure that the Insulat-ing Seal Assemblies are snug against the refrigerated storage ceiling. Secure the Insulating Seal Assemblies to the ceiling using two self-tapping screws per assembly.

Grooved Connection InstructionsThe following instructions are based on using the 2 inch Figure 705 Grooved Flexible Coupling or the 2 inch Figure 577 Grooved Rigid Coupling.

Step 1. Inspect the exterior groove and the end connection of the mating grooved connection and sprinkler to verify all burrs, loose debris, dirt, chips, paint and other foreign materials such as grease are removed. Sealing sur-faces must be free from sharp edges, projections, indentations, and/or other defects.

Step 2. Verify that the coupling and gasket grade are correct for the appli-cation intended. Refer to Technical Data Sheet TFP1895 for additional gasket information. The sealing edges and the outer surfaces of the gasket should be covered with a fine layer of lubricant. To prevent deterioration of the gasket material, a silicone lubricant should be used to prevent freezing of the lubricant.

Step 3. Install the Model ESFR-17 Dry Type Pendent Sprinkler in the pendent position (Ref. Figures 4 and 7) by care-fully raising the pendent sprinkler through the clearance hole. The deflec-tor of the pendent sprinkler is to be par-allel to the ceiling. Also, ensure that the “FRAME ARMS” markings on the sprin-kler casing are aligned with the System Pipe (Ref. Figure 6).

Step 4. Install the gasket by placing it over the sealing portion of the grooved inlet connection so that the gasket lip does not extend beyond the end of the groove sealing surface. Bring end of the grooved inlet together with end of grooved fitting ensuring vertical and horizontal alignment. Slide the gasket over both sealing surfaces.

Step 5. With one bolt and nut removed, separate the coupling housings and place over the gasket. Verify that the coupling housings are over the gasket and that the coupling housing keys are fully engaged into the grooves.

Step 6. Insert the bolt and nut into the coupling and finger tighten both nuts. Verify that the bolt heads are fully recessed in the housing.

The 2 inch Figure 705 Grooved Flexible Coupling Housing bolt pads must be in metal-to-metal contact. For Flexible Coupling deflection data, refer to Tech-nical Data Sheet TFP1820.

The 2 inch Figure 577 Grooved Rigid Coupling has an intended gap of up to 1/16 of an inch at each pad to allow for positive rigid gripping onto the pipe. The patented tongue and groove design provides protection to the back of the gasket during installation.

Step 7. Alternate between both sides of the coupling when tightening the bolts. Torque bolts to 30 lbs-ft. (41 Nm).

Step 8. Install the insulation rings of the Insulating Seal Assemblies by slipping the insulation rings around the sprin-kler casing as shown in Figure 7. Place the inserts over the insulation rings by sliding the inserts around the casing. Place the housings over the Inserts and insulation rings ensuring that the slot on the housings is 180 degrees to the inserts slot. Ensure that the Insulat-ing Seal Assemblies are snug against the refrigerated storage ceiling. Secure the Insulating Seal Assemblies to the ceiling using two self-tapping screws per assembly.

Page 39: rociadores std tyco

TFP320Page 7 of 8

Care and MaintenanceTYCO Model ESFR-17 Early Suppres-sion, Fast Response 16.8K Pendent Sprinklers must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection from the proper authorities and notify all personnel who may be affected by this action.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied or overheated sprinklers must be replaced.

A Vent Hole is provided in the Link Assembly Button (Ref. Figure 1) to indi-cate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent Hole indicates potential leakage past the Inlet seal and the need to remove the sprinkler to determine the cause of leakage; e.g., an improper installation or an ice plug. Close the fire protec-tion system control valve and drain the system before removing the sprinkler.

When replacing a sprinkler, remove and discard the old Insulating Seal Assem-blies and replace as shown in Figure 7.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced.

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Sprinkler AssembliesSpecify: Model ESFR-17 Dry Type Early Suppression, Fast Response 16.8K Pendent Sprinklers (TY7229) with two (2) Insulating Sealing Assemblies, P/N (specify):36 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . . 614411360 212°F (100°C) . . . . . . . . . . . . . . . . . . . 614421360

30 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . . 614411300 212°F (100°C) . . . . . . . . . . . . . . . . . . . 614421300

23 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . . 614411230 212°F (100°C) . . . . . . . . . . . . . . . . . . . 614421230

Special Order Sprinkler Assemblies with ISO 7-1 Thread ConnectionsSpecify: Model ESFR-17 Dry Type Early Suppression, Fast Response 16.8K Pendent Sprinkler (TY7229) with ISO 7-1 thread connection and two (2) Insulating Sealing Assemblies, (specify temperature rating), P/N (specify):36 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . .I614411360 212°F (100°C) . . . . . . . . . . . . . . . . . . .I614421360

30 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . .I614411300 212°F (100°C) . . . . . . . . . . . . . . . . . . .I614421300

23 Inch Sprinkler165°F (74°C) . . . . . . . . . . . . . . . . . . . .I614411230 212°F (100°C) . . . . . . . . . . . . . . . . . . .I614421230

Sprinkler WrenchSpecify: W-Type 26 Sprinkler Wrench, P/N 563411001

Insulating Seal Assembly KitEach Insulating Seal Assembly kit con-sists of one (1) Insulation Ring, one (1) Insert, one (1) Housing, and two (2) Screws.

Specify: Insulating Sealing Assembly, P/N 911061500

Page 40: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP320Page 8 of 8

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.MONEL is trademark of Special Metals Corporation.

Page 41: rociadores std tyco

RAPID RESPONSE Series LFII Residential 4.9 K-factor Pendent Sprinkler Wet Pipe and Dry Pipe Systems

Page 1 of 6 MARCH 2015 TFP400

Worldwide Contacts www.tyco-fire.com

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its components and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

General DescriptionTYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers (TY2234) are decorative, fast response, frangi-ble bulb sprinklers designed for use in residential occupancies such as homes, apartments, dormitories, and hotels. When aesthetics and optimized flow characteristics are the major con-sideration, the Series LFII Residential Sprinklers (TY2234) should be the first choice.

The Series LFII Residential Sprinklers are intended for use in the following scenarios:

• wet and dry pipe residential sprin-kler systems for one- and two-fam-ily dwellings and mobile homes per NFPA 13D

• wet and dry pipe residential sprinkler systems for residential occupancies up to and including four stories in height per NFPA 13R

• wet and dry pipe sprinkler systems for the residential portions of any occupancy per NFPA 13

The recessed version of the Series LFII Residential Sprinklers is intended for use in areas with finished ceilings. It employs a two-piece Style 20 Recessed Escutcheon. The Recessed Escutcheon provides 1/4 inch (6,4 mm) of recessed adjustment or up to 1/2 inch (12,7 mm) of total adjustment from the flush ceiling position. The

adjustment provided by the Recessed Escutcheon reduces the accuracy to which the pipe drops to the sprinklers must be cut.

The Series LFII Residential Sprinklers have been designed with heat sensi-tivity and water distribution charac-teristics proven to help in the control of residential fires and to improve the chance for occupants to escape or be evacuated.

Dry Pipe System ApplicationThe Series LFII Residential Pendent and Recessed Pendent Sprinklers offers a laboratory approved option for designing dry pipe residential sprin-kler systems, whereas, most residential sprinklers are laboratory approved for wet systems only.

Through extensive testing, it has been determined that the number of design sprinklers (hydraulic design area) for the Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) need not be increased over the number of design sprinklers (hydraulic design area) as specified for wet pipe sprinkler systems, as is accustomed for density/area sprinkler systems designed per NFPA 13.

Consequently, the Series LFII Resi-dential Sprinklers offer the features of non-water filled pipe in addition to not having to increase the number of design sprinklers (hydraulic design area) for systems designed to NFPA 13, 13D, or 13R.

NOTICEThe Series LFII Residential Pendent and Recessed Pendent Sprinklers (TY2234) described herein must be installed and maintained in compliance with this document and the applicable standards of the National Fire Protec-tion Association (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Sprinkler Identification Number (SIN)TY2234

Technical DataApprovalsUL Listed (for use with wet pipe and dry pipe sys-tems)C-UL Listed (for use only with wet pipe systems)Certified to all requirements of NSF/ANSI 61

(Refer to the Design Criteria section for de-tails on these approvals.)

Maximum Working Pressure175 psi (12,1 bar)

Discharge CoefficientK=4.9 gpm/psi1/2 (70,6 lpm/bar1/2)

Temperature Rating155°F (68°C) or 175°F (79°C)

FinishesNatural Brass, Pure White, Signal White, or Chrome Plated

Physical CharacteristicsFrame . . . . . . . . . . . . . . . . . . . . . . . . Brass Button . . . . . . . . . . . . . . . . . . . . . . Copper Sealing Assembly . . . . . . Beryllium Nickel

w/TEFLON Bulb (3 mm) . . . . . . . . . . . . . . . . . . . Glass Compression Screw . . . . . . . . . . . .Bronze Deflector . . . . . . . . . . . . . . . . . . . . .Bronze

Page 42: rociadores std tyco

TFP400Page 2 of 6

OperationThe glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and flow water.

Design CriteriaThe TYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers are UL and C-UL Listed for installation in accordance with this section.

Residential Sprinkler Design GuideWhen conditions exist that are outside the scope of the provided criteria, refer to the Residential Sprinkler Design Guide TFP490 for the manufactur-er’s recommendations that may be acceptable to the local authority having jurisdiction.

System TypesPer the UL Listing, wet pipe and dry pipe systems may be utilized. Per the C-UL Listing, only wet pipe systems may be utilized.

Refer to Technical Data Sheet TFP485 for the use of residential sprinklers in residential dry pipe systems.

Ceiling TypesSmooth flat horizontal, or beamed, or sloped, in accordance with the 2013 Edition of NFPA 13D, 13R, or 13, as applicable.

SURFACE

ESCUTCHEONPLATE SEATING

1-5/8"(41,3 mm)

-2 Button

Temperaturerating isindicated onDe�ector.

De�ector

CompressionScrew

BulbSealing Assembly

-6

*

-45 -

3 -

*

*

6

4

5

1

3

2

Components:

Frame1 -

1/2"NPT

7/16" (11,1 mm)

MAKE-INNOMINAL

ESCUTCHEON

STYLE 20RECESSEDWRENCH

(57,2 mm)2-1/4"

FLATS

(73,0 mm)2-7/8" DIA.

CROSS SECTION PENDENT RECESSED PENDENT

TY2234

2-7/8" DIA.(73,0 mm)

(57,2 mm)2-1/4" DIA.

MOUNTING

SPRINKLER

CLOSURE

SURFACE

FITTING

FACE OF

(11,1±3,2 mm)7/16±1/8"

MOUNTINGPLATE

1-3/8" (34,9 mm)

1-1/8" (28,6 mm)

(3,2 mm)1/8"

1/2" (12,7 mm)

1/4" (6,4 mm) WRENCH RECESS(END "A" USEDFOR TY2234)

RECESSWRENCH

WITH SPRINKLERENGAGEMENTIN TO ENSURE

WRENCHING AREA

PUSH WRENCH

FIGURE 1 RAPID RESPONSE SERIES LFII RESIDENTIAL

4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234)

FIGURE 3 W-TYPE 6

SPRINKLER WRENCH

FIGURE 4 W-TYPE 7 RECESSED SPRINKLER WRENCH

FIGURE 2 STYLE 20 RECESSED ESCUTCHEON FOR USE WITH THE

RAPID RESPONSE SERIES LFII RESIDENTIAL PENDENT SPRINKLER

Page 43: rociadores std tyco

TFP400Page 3 of 6

Hydraulic Design (NFPA 13D and 13R)For systems designed to NFPA 13D or NFPA 13R, the minimum re quired sprinkler flow rates are given in Tables A and B as a function of tem-perature rating and the maximum allowable coverage areas. The sprinkler flow rate is the minimum required discharge from each of the total number of “design sprinklers” as specified in NFPA 13D or NFPA 13R. The number of “design sprinklers” specified in NFPA 13D and 13R for wet pipe systems is to be applied when designing dry pipe systems.

Hydraulic Design (NFPA 13)For systems designed to NFPA 13, the number of design sprinklers is to be the four most hydraulically demanding sprinklers. The minimum required dis-charge from each of the four sprinklers is to be the greater of the following:

• The flow rates given in Table A or B as a function of temperature rating and the maximum allowable coverage area .

• A minimum discharge of 0 .1 gpm/ft2 over the “design area” comprised of the four most hydraulically demanding sprinklers for actual coverage areas protected by the four sprinklers .

The number of design sprinklers speci-fied in NFPA 13 for wet pipe systems is to be applied when designing dry pipe systems.

Dry Pipe System Water DeliveryWhen using the Series LFII Residential Sprinklers (TY2234) in dry pipe sprin-kler systems, the time for water deliv-ery must not exceed 15 seconds for the most remote operating sprinkler.

Obstruction to Water DistributionSprinklers are to be located in accor-dance with the obstruction rules of NFPA 13D, 13R, and 13 as applicable for residential sprinklers as well as with the obstruction criteria described within the Technical Data Sheet TFP490.

Operational SensitivitySprinklers are to be installed with a deflector-to-ceiling distance of 1-1/4 to 4 inches.

Sprinkler SpacingThe minimum spacing between sprin-klers is 8 feet (2,4 m). The maximum spacing between sprinklers cannot exceed the length of the coverage area (Table A or B) being hydraulically cal-culated (e.g., maximum 12 feet for a 12 ft. x 12 ft. coverage area, or 20 feet for a 20 ft. x 20 ft. coverage area).

InstallationTYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers must be installed in accordance with this section.

General InstructionsDo not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm).

A leak-tight 1/2 inch NPT sprinkler joint should be obtained by applying a min-imum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque can distort the sprinkler Inlet with consequent leakage or impairment of the sprinkler.

Do not attempt to compensate for insufficient adjustment in an Escutch-eon Plate by under- or over- tightening the sprinkler. Re-adjust the position of the sprinkler fitting to suit.

Series LFII Residential Pendent SprinklersThe Series LFII Residential Pendent Sprinklers must be installed in accor-dance with the following instructions:

Step 1. Install pendent sprinklers in the pendent position with the deflector par-allel to the ceiling .

Step 2. With pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting .

Step 3. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Figure 3) . With ref-erence to Figure 1, apply the W-Type 6 Sprinkler Wrench to the wrench flats .

Series LFII Residential Recessed Pendent SprinklersThe Series LFII Residential Recessed Pendent Sprinklers must be installed in accordance with the following instructions:

Step A. Install recessed pendent sprin-klers in the pendent position with the deflector parallel to the ceiling .

Step B. After installing the Style 20 Mounting Plate over the sprinkler threads and with pipe thread sealant applied to the pipe threads, hand-tighten the sprinkler into the sprinkler fitting .

Step C. Tighten the sprinkler into the sprinkler fitting using only the W-Type 7 Recessed Sprinkler Wrench (Figure 4) . With reference to Figure 1, apply the W-Type 7 Recessed Sprinkler Wrench to the sprinkler wrench flats .

Step D. After the ceiling has been installed or the finish coat has been applied, slide on the Style 20 Closure over the Series LFII Residential Sprin-kler and push the Closure over the Mounting Plate until its flange comes in contact with the ceiling .

Page 44: rociadores std tyco

TFP400Page 4 of 6

Maximum Coverage

Area (1)

Ft. x Ft. (m x m)

DRY PIPE SYSTEM Minimum Flow and Residual Pressure (2)(3)

Ordinary Temperature Rating 155°F (68°C)

Intermediate Temperature Rating 175°F (79°C)

Deflector to Ceiling

Installation Type

Minimum Spacing

Ft. (m)

Flowgpm

(l/min)

Pressurepsi

(bar)

Flowgpm

(l/min)

Pressurepsi

(bar)

12 x 12 (3,7 x 3,7)

13 (49,2)

7 .0 (0,48)

13 (49,2)

7 .0 (0,48)

Smooth Ceilings

1-1/4 to 4 inches

Beamed Ceilings

per NFPA 13D or 13R

1-1/4 to 1-3/4 inches below

bottom of beam .

Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D,

13R, or 13

8 (2,4)

14 x 14 (4,3 x 4,3)

14 (53,0)

8 .2 (0,57)

14 (53,0)

8 .2 (0,57)

16 x 16 (4,9 x 4,9)

15 (56,8)

9 .4 (0,65)

15 (56,8)

9 .4 (0,65)

18 x 18 (5,5 x 5,5)

18 (68,1)

13 .5 (0,93)

18 (68,1)

13 .5 (0,93)

20 x 20 (6,1 x 6,1)

21 (79,5)

18 .4 (1,27)

21 (79,5)

18 .4 (1,27)

Notes:1 . For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design

criteria are stated .2 . Requirement is based on minimum flow in gpm (lpm) from each sprinkler . The associated residual pressures are calculated using the nominal

K-factor . Refer to Hydraulic Design under the Design Criteria section .3 . For NFPA 13 residential applications, the greater of 0 .1 gpm/ft .2 over the design area or the flow in accordance with the criteria in this table must be used .

Maximum Coverage

Area (1)

Ft. x Ft. (m x m)

WET PIPE SYSTEM Minimum Flow and Residual Pressure (2)(3)

Ordinary Temperature Rating 155°F (68°C)

Intermediate Temperature Rating 175°F (79°C)

Deflector to Ceiling

Installation Type

Minimum Spacing

Ft. (m)

Flowgpm

(l/min)

Pressurepsi

(bar)

Flowgpm

(l/min)

Pressurepsi

(bar)

12 x 12 (3,7 x 3,7)

13 (49,2)

7 .0 (0,48)

13 (49,2)

7 .0 (0,48)

Smooth Ceilings 1-1/4 to 4 inches

Beamed Ceilings per NFPA 13D

or 13R 1-1/4 to 1-3/4 inches below

bottom of beam .

Recessed using Style 20 Escutcheon or non-recessed per NFPA 13D,

13R, or 13

8(2,4)

14 x 14 (4,3 x 4,3)

13 (49,2)

7 .0 (0,48)

13 (49,2)

7 .0 (0,48)

16 x 16 (4,9 x 4,9)

13 (49,2)

7 .0 (0,48)

13 (49,2)

7 .0 (0,48)

18 x 18 (5,5 x 5,5)

17 (64,3)

12 .0 (0,83)

17 (64,3)

12 .0 (0,83)

20 x 20 (6,1 x 6,1)

20 (75,7)

16 .7 (1,15)

20 (75,7)

16 .7 (1,15)

Notes:1 . For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage area for which hydraulic design

criteria are stated .2 . Requirement is based on minimum flow in gpm (lpm) from each sprinkler . The associated residual pressures are calculated using the nominal

K-factor . Refer to Hydraulic Design under the Design Criteria section .3 . For NFPA 13 residential applications, the greater of 0 .1 gpm/ft .2 over the design area or the flow in accordance with the criteria in this table must be used .

TABLE A WET PIPE SYSTEM

SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

TABLE B DRY PIPE SYSTEM

SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2234) NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

Page 45: rociadores std tyco

TFP400Page 5 of 6

Care and MaintenanceTYCO RAPID RESPONSE Series LFII Residential 4.9K Pendent and Recessed Pendent Sprinklers must be maintained and serviced in accordance with this section:

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, permission to shut down the affected fire protection system must be obtained from the proper authorities and notify all personnel who may be affected by this action.

Absence of the outer piece of an escutcheon, which is used to cover a clearance hole, can delay sprinkler operation in a fire situation.

The owner must assure that the sprin-klers are not used for hanging any objects and that the sprinklers are only cleaned by means of gently dusting with a feather duster; otherwise, non-operation in the event of a fire or inad-vertent operation may result.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprin-kler that has a cracked bulb or that has lost liquid from its bulb (Ref. Installa-tion section).

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Associa-tion (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. Contact the installing con-tractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Sprinkler AssembliesSpecify: Series LFII 4.9K Residential Pendent Sprinkler (TY2234), (specify temperature rating), with (specify) finish, P/N (specify):155°F (68°C)Natural Brass . . . . . . . . . . . . . .P/N 51-201-1-155 Pure White (RAL 9010)* . . . . . .P/N 51-201-3-155 Signal White (RAL 9003) . . . . .P/N 51-201-4-155 Chrome Plated . . . . . . . . . . . . .P/N 51-201-9-155

175°F (79°C)Natural Brass . . . . . . . . . . . . . .P/N 51-201-1-175 Pure White (RAL 9010)* . . . . . .P/N 51-201-3-175 Signal White (RAL 9003) . . . . .P/N 51-201-4-175 Chrome Plated . . . . . . . . . . . . .P/N 51-201-9-175

* Eastern Hemisphere sales only

Recessed EscutcheonSpecify: Style 20 Recessed Escutch-eon with (specify*) finish, P/N (specify*)* Refer to Technical Data Sheet TFP770 .

Sprinkler WrenchesSpecify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387

Specify: W-Type 7 Sprinkler Wrench, P/N 56-850-4-001

Page 46: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP400Page 6 of 6

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of the DuPont Corporation.

Page 47: rociadores std tyco

RAVEN Studio Sprinklers 5.6K Pendent and Horizontal Sidewall Quick Response, Standard and Extended Coverage

Page 1 of 16 MARCH 2015 TFP658

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionTYCO RAVEN Studio Sprinklers 5.6K Pendent and Horizontal Sidewall (HSW) Quick Response, Standard Coverage for Light and Ordinary Hazard applica-tions and Extended Coverage for Light Hazard applications only, are intended for use in areas as designed per NFPA 13.

The flush design is made aesthetical-ly appealing by concealing the deflec-tor and other operating parts behind the link assembly. The RAVEN Studio Sprinklers, with a heat sensitive solder type release element, are Listed as quick response sprinklers.

NOTICERAVEN Studio Sprinklers described herein must be installed and main-tained in compliance with this docu-ment and with the applicable standards of the National Fire Protection Associa-tion (NFPA), in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the perfor-mance of these devices.

Tyco Fire Protection Products (TFPP)specifically disclaims any liability for damages or injury (including death) arising out of or caused by manipula-tion, dismantling, or misuse of RAVEN Studio Sprinklers or the use or attempt-ed use of the RAVEN Studio Sprinklers or any component thereof as an instru-ment unrelated to its intended function as a fire protection device.

The owner is responsible for main-taining their fire protection system

and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Sprinkler Identification Numbers (SINs)Standard CoverageTY1281 – Pendent TY1381 – Horizontal Sidewall

Extended CoverageTY1282 – Pendent TY1382 – Horizontal Sidewall

Technical DataApprovalsUL and C-UL Listed

Maximum Working Pressure175 psi (12,1 bar)

Thread ConnectionAdapter: 1/2” NPT x ISO 228 G3/8” Sprinkler: ISO 228 G3/8”

Note: Threads per ISO 228 are parallel pipe threads.

Discharge CoefficientK=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)

Temperature Rating165°F (74°C)

FinishesSprinkler: White, Grey, or Custom Color

Escutcheon: White, Grey, Chrome, Primed*, Custom Color, or Electropolish**

(Refer to Ordering Procedure for details.)* Ready to paint-in-place** Chrome-coated appearance, available for Stainless

Steel only

Physical CharacteristicsBody. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Brass Deflector Assembly . . . . . . . . . . . . . . . . . Bronze Sealing Assembly . Beryllium Nickel w/TEFLON Link Assembly . . . . . . . . . . . . . . . . . . . . .Copper Thread Adapter . . . . . . . . . . . . . . . . . . . . . Brass Escutcheon . . . . . . . . Carbon or Stainless Steel

Page 48: rociadores std tyco

TFP658Page 2 of 16

NOTES:

USE LIP OF PAINTED SPRINKLER BODY, NOT BRASSSHOULDER, AS INSTALLATION SURFACE,REF. FIGURES 11 OR 12 AND INSTALLATIONPROCEDURE STEPS 8 OR G

1.

1

1

1

LINK VIEWSIDE VIEW

1-3/8" DIA.(35 mm)

ISO 228 G3/8"PARALLEL

INLETTHREADS

SPRINKLERWRENCHING

NOTCHES

DUSTCAP

ENCLOSEDDEFLECTOR

(HORIZONTALSIDEWALLSHOWN)

LINKASSEMBLY

FACTORYPAINTED

AREA

EXPOSEDBRASS

SHOULDER

BODY

A

INSTALLATIONLIP

BASEFLANGE

CLEARANCEHOLE

C

B A

PRONGS

Application Coverage SIN Dust Cap Color

A Inches (mm)

PendentStandard TY1281

Red 1-7/8 (48)Extended TY1282

Horizontal Sidewall

Standard TY1381Green 2-13/16

(56)Extended TY1382

Dimensions Inches (mm)

Dim.Escutcheon

Style

J K

A Dia.

3 (76)

4 (101)

B 7/16 (11)

C Dia.

Min. 2 (51)

Max. 2-1/2 (63)

3-1/2 (88)

FIGURE 1 RAVEN STUDIO SPRINKLERS

ASSEMBLY

FIGURE 2 RAVEN STUDIO SPRINKLERS

ESCUTCHEONS

Page 49: rociadores std tyco

TFP658Page 3 of 16

COMMON THREADADAPTER FEATURES

STANDARD

MEDIUM

LONG

SHORT

WRENCH HEX,1" (25 mm)

ACROSS FLATS

7/16"(11 mm)

NOMINALMAKE-IN

1"(25 mm)

ISO228 G3/8"PARALLELTHREADS

1/2" NPTTAPEREDTHREADS

1-1/2"(38 mm)

2"(50 mm)

3/4"(19 mm)

NOTES:

3.

1.

4.

2.

APPLY ONLY PERMABOND LH056 SEALANT ONINLET THREADS OF RAVEN STUDIO SPRINKLERWHEN INSTALLING IN CPVC SPRINKLER ADAPTERFITTINGS, REF. FIGURE 10

INSTALL INLET THREADS OF RAVEN STUDIOSPRINKLER DIRECTLY INTO ISO 228 G3/8" OUTLETTHREADS OF CPVC SPRINKLER ADAPTER FITTING;THREAD ADAPTER NOT REQUIRED

REFER TO CPVC INSTALLATION HANDBOOK IH-1900FOR GUIDANCE ON INSTALLING FITTINGS IN CPVCPIPE SYSTEMS

CPVC SPRINKLER ADAPTER FITTINGS WITH ISO 228G3/8" OUTLET THREADS DESIGNED FOR USE INLOW-PROFILE, LIMITED-SPACE INSTALLATIONS

90° ELBOW

TEE

D Y

C

CX

YD

A

A

B

E

C

X

X

B

A

Fitting Type

A Nominal Pipe Size

Inches DN

B Outlet Thread ISO 228 Inches

Dimensions Inches (mm)

C D E X Y

90° Elbow1

DN25 G3/8

1-5/8 (41)

13/16 (21)

13/16 (21)

3/4 (19)

1-3/4 (44)

Tee 1-5/8 (41)

13/16 (21) N/A 11/16

(17)1-13/16

(46)

FIGURE 3 RAVEN STUDIO SPRINKLERS

THREAD ADAPTERS

FIGURE 4 RAVEN STUDIO SPRINKLERS

CPVC SPRINKLER ADAPTER FITTINGS

Page 50: rociadores std tyco

TFP658Page 4 of 16

2

1

3

3

NOTES:

2.

1.

3. THREAD ADAPTER NOT APPLICABLE WHENINSTALLING SPRINKLER DIRECTLY IN ISO 228 G3/8"OUTLET THREADS OF CPVC SPRINKLER ADAPTERFITTING (REF. FIGURES 4 AND 6)

MINIMUM THREAD ENGAGEMENT APPROX.3/16" (5 mm) = 3 FULL REVOLUTIONS AFTER INITIALENGAGEMENT OF SPRINKLER INLET THREADS WITHTHREAD ADAPTER OUTLET THREADS

SPRINKLER FITTING AND WATERWAY CENTERLINEMUST BE PERPENDICULAR TO ESCUTCHEONMOUNTING SURFACE

3/16" (5 mm)MINIMUM THREAD

ENGAGEMENT

7/16"(11 mm)

NOMINALMAKE-IN

FACE OFSPRINKLER

FITTING

FACE OFTHREAD

ADAPTER

SPRINKLERFITTING ANDWATERWAY

CENETRLINE

STYLE J OR KESCUTCHEON

CEILINGOR WALL

ESCUTCHEONMOUNTINGSURFACE

CLEARANCEHOLE

CEILINGOR WALL

COVERINGMATERIAL

FACE OFFRAMINGMEMBER

SPRINKLERBODY ENGAGEDBY ESCUTCHEON

PRONGS

A

B

SPRINKLERFITTING

THREADADAPTER

Thread Adapter

Size

Thread Adapter Length Inches (mm)

A Inches (mm) B

Nominal Inches (mm)Pendent Horizontal

Sidewall

Min. Max. Min. Max.

Short 3/4 (19)

1-1/4 (32)

1-3/4 (44)

1-1/2 (38)

2 (51)

5/16 (8)

Standard 1 (25)

1-1/2 (38)

2 (51)

1-3/4 (44

2-1/4 (57)

9/16 (14)

Medium 1-1/2 (38)

2 (51)

2-1/2 (64)

2-1/4 (57)

2-3/4 (70)

1-1/16 (27)

Long 2 (50)

2-1/2 (64)

3 (64)

2-3/4 (70)

3-1/4 (83)

1-9/16 (40)

FIGURE 5 RAVEN STUDIO SPRINKLERS

PENDENT AND HORIZONTAL SIDEWALL INSTALLATION CRITERIA

Page 51: rociadores std tyco

TFP658Page 5 of 16

2

1

MINIMUM THREAD ENGAGEMENT APPROX.7/32" (6 mm) = 4 FULL REVOLUTIONS AFTER INITIALENGAGEMENT OF SPRINKLER INLET THREADS WITHADAPTER FITTING OUTLET THREADS

SPRINKLER FITTING AND WATERWAY CENTERLINEMUST BE PERPENDICULAR TO ESCUTCHEONMOUNTING SURFACE

NOTES:

2.

1.

7/32" (6 mm)MINIMUM THREAD

ENGAGEMENT

FACE OFSPRINKLER

FITTING

SPRINKLERFITTING ANDWATERWAY

CENETRLINE

STYLE J OR KESCUTCHEON

CEILINGOR WALL

ESCUTCHEONMOUNTINGSURFACE

CLEARANCEHOLE

CEILINGOR WALL

COVERINGMATERIAL

FACE OFFRAMINGMEMBER

SPRINKLERBODY ENGAGEDBY ESCUTCHEON

PRONGS

ACPVC

PIPE FROMSYSTEM

CPVC SPRINKLERADAPTER FITTING

WITH ISO 228 G3/8"OUTLET THREADS

(REF. FIGURE 4)

Fitting Type

Fitting Size

Inches x ISO 228 Outlet Threads

A Inches (mm)

Pendent Horizontal Sidewall

Min. Max. Min. Max.

90° Elbow 1 x G3/87/8 (22)

1-1/4 (32)

1-1/8 (29)

1-1/2 (38)

Tee 1 x 1 x G3/8

FIGURE 6 RAVEN STUDIO SPRINKLERS

PENDENT AND HORIZONTAL SIDEWALL LOW-PROFILE CPVC ADAPTER FITTING INSTALLATION CRITERIA

Page 52: rociadores std tyco

TFP658Page 6 of 16

SOCKET ACCEPTS1/2" DRIVE

WRENCH PRONGSUNIQUELY SPACED TOENGAGE SPRINKLER

WRENCHING NOTCHES

RAVEN STUDIOSPRINKLER

"UP" INDICATESTOP OF HORIZONTAL

SIDEWALL SPRINKLERDEFLECTOR

WRENCH FLATACCOMMODATES

LEVEL IF NECESSARYFOR HORIZONTAL

SIDEWALL SPRINKLERINSTALLATION

USE WRENCHFOR SPRINKLERINSTALLATIONAND REMOVAL

CAP PRONGSUNIQUELY SPACED TOENGAGE SPRINKLER

WRENCHING NOTCHES

RAVEN STUDIOSPRINKLER

"UP" INDICATESTOP OF HORIZONTAL

SIDEWALL SPRINKLERDEFLECTOR

CAP FLATACCOMMODATES

LEVEL IF NECESSARYFOR HORIZONTAL

SIDEWALL SPRINKLERINSTALLATION

CENTERMARKING

POINTFINGER

GRIP

CAP IS FORSINGLE-USE ONLYDO NOT RE-USEAFTER PAINTING

USE CAP FORSPRINKLER

INSTALLATIONAND PROTECTIONWHILE PAINTING

FIGURE 8 RAVEN STUDIO SPRINKLERS

W-TYPE 25 WRENCH APPLICATION

FIGURE 7 RAVEN STUDIO SPRINKLERS

PAINT CAP APPLICATION

Page 53: rociadores std tyco

TFP658Page 7 of 16

ALLOW MINIMUM 2 HOUR CURE TIME BEFORE SYSTEM PRESSURETESTING

REFER TO PERMABOND LH056 TECHNICAL DATA SHEET FOR MOREINFORMATION, GO TO: www.permabond.com

APPLY SEALANT AROUND FIRST 4 (MINIMUM) SPRINKLER INLETTHREADS LEAVING FIRST THREAD FREE OF SEALANT

ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLERWATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENTFAILURE

USE ONLY PERMABOND LH056 SEALANT FOR SEALING SPRINKLERINLET THREAD CONNECTION IN CPVC PIPE SYSTEM

NOTES:

5.

6.

2.

4.

1.

3.

INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT

CPVC SPRINKLERHEAD ADAPTER FITTING,ISO 228 G3/8" THREAD

SPRINKLERINLET

THREADS

RAVEN STUDIO SPRINKLERWITH PAINT CAP ORW-TYPE 25 WRENCH

PERMABOND LH056SEALANT

APPLICATOR

CPVCPIPE FROM

SYSTEM

APPLY SEALANT AROUND FIRST 2-3 (MINIMUM) SPRINKLER INLETTHREADS

NOTES:

3.

1.

ALLOW MINIMUM 1 HOUR CURE TIME BEFORE SYSTEM PRESSURETESTING

REFER TO LOCTITE 243 TECHNICAL DATA SHEET FOR MOREINFORMATION, GO TO: www.loctite.com

ASSURE SEALANT AVOIDS CONTACT WITH INTERNAL SPRINKLERWATERWAY; FAILURE TO DO SO MAY RESULT IN EQUIPMENTFAILURE

INSTALL SPRINKLER IMMEDIATELY AFTER APPLYING SEALANT

6.

7.

5.

4.

2. DO NOT USE LOCTITE 243 SEALANT IN CPVC PIPE SYSTEMS

USE ONLY LOCTITE 243 SEALANT FOR SEALING SPRINKLERINLET THREAD CONNECTION IN STEEL PIPE SYSTEM

SPRINKLERINLET

THREADS

RAVEN STUDIO SPRINKLERWITH PAINT CAP ORW-TYPE 25 WRENCH

LOCTITE 243SEALANTBOTTLE

STEELPIPE FROM

SYSTEM

MALLEABLE OR CAST IRONSPRINKLER FITTING

WITH THREAD ADAPTER

FIGURE 10 RAVEN STUDIO SPRINKLERS

PERMABOND LH056 SEALANT APPLICATION — CPVC PIPE SYSTEM INSTALLATIONS

FIGURE 9 RAVEN STUDIO SPRINKLERS

LOCTITE 243 SEALANT APPLICATION — STEEL PIPE SYSTEM INSTALLATIONS

Page 54: rociadores std tyco

TFP658Page 8 of 16

SPRINKLERBODY STOP

CEILING OR WALLESCUTCHEON

MOUNTINGSURFACE

RAVEN STUDIO SPRINKLERWITH PAINT CAP ORW-TYPE 25 WRENCH

SPRINKLERFITTING WITH

THREADADAPTER

CLEARANCEHOLE

FINISHEDSURFACE

INSTALLATIONTOOL

FINISHEDSURFACE

INSTALLATIONTOOL

LIP OF SPRINKLER BODY, NOTBRASS SHOULDER, FLUSH AGAINSTSPRINKLER BODY STOP SURFACE

BASE

CPVC SPRINKLERADAPTER FITTING

WITH ISO 228 G3/8"OUTLET THREADS

RAVEN STUDIO SPRINKLERWITH PAINT CAP ORW-TYPE 25 WRENCH

SPRINKLERFITTING WITH

THREADADAPTER

ROUGH-ININSTALLATION TOOL

36" (0,9 m) BEAMACCOMMODATES

VARIETY OFFRAMING SPACINGS

FACE OFWALL ORCEILING

FRAMINGMEMBER

WIDE BASE OFBEAM FLUSH

AGAINST FACEOF FRAMING

MEMBERS

ADJUST TOSUIT FRAMINGSPACING AND

FITTINGLOCATION

LOCK UNLOCK

GAUGE

CARRIAGE

IMPERIAL SCALE(0 to 1-1/2")

METRIC SCALE(0 to 40 mm)

GAUGE LOCKHANDLE

LIP OF SPRINKLER BODY,NOT BRASS SHOULDER,

FLUSH AGAINST SPRINKLERBODY STOP SURFACE

ADJUST TOALIGN EDGEOF GAUGE

WITH MARKINGON IMPERIALOR METRIC

SCALE TO SUITTOTAL COVERING

MATERIALTHICKNESS

CPVC SPRINKLERADAPTER FITTING

WITH ISO 228 G3/8"OUTLET THREADS

FIGURE 11 RAVEN STUDIO SPRINKLERS

FINISHED SURFACE INSTALLATION TOOL APPLICATION

FIGURE 12 RAVEN STUDIO SPRINKLERS

ROUGH-IN INSTALLATION TOOL APPLICATION

Page 55: rociadores std tyco

TFP658Page 9 of 16

INSPECT WRENCHING NOTCH POSITIONS AFTERESCUTCHEON INSTALLATION TO VERIFY PROPERHORIZONTAL SIDEWALL SPRINKLER DEFLECTORORIENTATION

1.

NOTES:

2. FARTHEST-SPACED WRENCHING NOTCHLOCATED AT 12 O'CLOCK POSITION INDICATESPROPER DEFLECTOR ORIENTATION

STYLE J OR KESCUTCHEON

CLOSEST-SPACEDWRENCHING NOTCHES

FARTHEST-SPACEDWRENCHING NOTCH

ENCLOSEDHORIZONTAL

SIDEWALLDEFLECTOR

FACE OFFINISHEDCEILING

RAVENSTUDIO

HORIZONTALSIDEWALL

SPRINKLERSPRINKLERFITTING

THREADADAPTER

ESCUTCHEONMOUNTINGSURFACE

SPRINKLERFITTING ANDWATERWAY

CENTERLINE

12-7/16" (316 mm)4-7/16" (133 mm)

REFERENCE DIMENSION D = TOTAL CEILINGOR WALL COVERING MATERIAL THICKNESS(DRYWALL, PLYWOOD, ETC. PLUS TAPE,PLASTER, ETC.)

1.

NOTES:

CLEARANCEHOLE

DREF.

PLASTER,TAPE, ETC.

CEILINGOR WALL

COVERINGMATERIAL

CEILING OR WALLESCUTCHEON

MOUNTINGSURFACE

FIGURE 14 RAVEN STUDIO SPRINKLERS

TOTAL CEILING AND WALL COVERING MATERIAL THICKNESS

FIGURE 13 RAVEN STUDIO SPRINKLERS

HORIZONTAL SIDEWALL INSTALLATION CRITERIA

Page 56: rociadores std tyco

TFP658Page 10 of 16

Design CriteriaStandard Coverage CriteriaRAVEN Studio 5.6K Pendent and Hori-zontal Sidewall Sprinklers (TY1281 and TY1381) are intended for use in light hazard or ordinary hazard applica-tions as defined by NFPA 13, utilizing the density/area method for hydrauli-cally calculated systems, and with fire protection systems designed in accordance with the standard instal-lation rules recognized by the appli-cable listing or approval agency (e.g., UL Listing is based on NFPA 13 requirements).

RAVEN Studio Horizontal Sidewall Sprinklers (TY1381) must be installed with a deflector-to-ceiling distance of 4 to 12 inches (100 to 300 mm). To meet this requirement, the centerline of the sprinkler waterway must be located 4-7/16 to 12-7/16 inches (112,7 to 315,9 mm) below the ceiling (Ref. Figures 13 and 15).

Extended Coverage CriteriaRAVEN Studio 5.6K Pendent and Hori-zontal Sidewall Sprinklers (TY1282 and TY1382) must be installed in accor-dance with the flow rate criteria pro-vided in Table A. They must be installed and utilized in light hazard occupancies only under smooth, flat, horizontal ceil-ings as outlined in the applicable instal-lation standard recognized by the listing or approval agency (e.g., UL Listing is based on NFPA 13 requirements).

RAVEN Extended Coverage, Horizontal Sidewall Sprinklers (TY1382) must be installed with a deflector-to-ceiling dis-tance of 4 to 12 inches (100 to 300 mm). To meet this requirement, the center-line of the sprinkler waterway must be located 4-7/16 to 12-7/16 inches (112,7

to 315,9 mm) below the ceiling (Ref. Figures 13 and 15).

OperationWater is prevented from flowing from the RAVEN Studio Sprinkler by means of a sealing assembly held in place by operating parts secured by a link assembly. The link assembly is com-prised of two link halves soldered together with an eutectic solder that melts when exposed to heat. When the link reaches its rated temperature, the link halves separate and release the operating parts and sealing assem-bly, allowing the deflector assembly to extend from the body and water to flow from the sprinkler.

Care and MaintenanceTYCO RAVEN Studio Sprinklers 5.6K Pendent and Horizontal Sidewall (HSW) Quick Response, Standard and Extended Coverage must be main-tained and serviced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection system from the proper authorities and notify all personnel who may be affect-ed by this action.

Service inspections should be made on a regular basis to detect possible damage or alterations to the sprin-kler and escutcheon. Inspections should include making certain that the escutcheon is held fast to the mount-ing surface. Damaged or altered sprin-klers are to be replaced immediately

to avoid personal injury and to prevent use for causing personal injury, as well as to maintain the sprinkler system in an operative condition.

Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modi-fied sprinklers must be replaced. Sprin-klers that have been exposed to cor-rosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid damage to the sprinklers before, during, and after installation. Sprin-klers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced.

Frequent visual inspections are recom-mended to be initially performed for sprinklers installed in potentially corro-sive atmospheres to verify the integrity of the materials of construction as they may be affected by the corrosive con-ditions present for a given installation.

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the approval agency and standards of any other authority having jurisdic-tion. Contact the installing contrac-tor or product manufacturer with any questions.

Sprinklers are recommended to be inspected, tested, and maintained by a qualified Inspection Service in accor-dance with local requirements and/or national codes.

5.6K Extended Coverage Pendent (TY1282)

Response Rating

Coverage Area Ft. x Ft. (m x m)

Minimum Flow(a)

gpm (lpm)

Minimum Pressure(b)

psi (bar)

Deflector-to-Ceiling Distance

Sprinkler Temperature Rating

°F (°C)

Minimum Spacing Ft. (m)

Quick 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) Flush Mounted 165 (74) 8 (2,4)

5.6K Extended Coverage Horizontal Sidewall (TY1382)

Response Rating

Coverage Area Ft. x Ft. (m x m)

Minimum Flow(a)

gpm (lpm)

Minimum Pressure(b)

psi (bar)

Deflector-to-Ceiling Distance(c)

Inches (mm)

Sprinkler Temperature Rating

°F (°C)

Lateral Minimum Spacing(d)

Ft. (m)

Quick 16 x 16 (4,9 x 4,9) 26 (98) 21.6 (1,49) 4 to 12 (100 to 300) 165 (74) 8 (2,4)

Notes:a. Requirement is based on minimum flow in gpm (lpm) from each sprinkler.b. Indicated residual pressures are based on the nominal K-factor.c. Centerline of the sprinkler waterway is located 7/16 inch (11,1 mm) below the deflector (Ref. Figure 15).d. Minimum spacing is for lateral distance between sprinklers located along a single wall; otherwise, adjacent sprinklers (i.e., sidewall sprinklers on an adjacent wall, on an op-

posite wall, or pendent sprinklers) must be located outside of the maximum listed protection area of the extended coverage sidewall sprinkler being utilized.

TABLE A RAVEN STUDIO SPRINKLERS

UL AND C-UL LISTING EXTENDED COVERAGE AREAS for LIGHT HAZARDS AND FLOW RATE CRITERIA

Page 57: rociadores std tyco

TFP658Page 11 of 16

PENDENT

HORIZONTAL SIDEWALL

9/16"(14 mm)

11/16"(17 mm)

7/16"(11 mm)

CENTERLINEOF SPRINKLER

WATERWAY

TOP OFDEFLECTOR

SPRINKLERDEFLECTOR ASSEMBLYIN OPERATED POSITION

SPRINKLERDEFLECTOR ASSEMBLYIN OPERATED POSITION

ESCUTCHEON

ESCUTCHEON

ESCUTCHEONMOUNTINGSURFACE

ESCUTCHEONMOUNTINGSURFACE

RAVEN STUDIOSPRINKLER

RAVEN STUDIOSPRINKLER

4" (102 mm)TO

12" (305 mm)

FACE OFFINISHED CEILING

FIGURE 15 RAVEN STUDIO SPRINKLERS

OPERATED CONDITION

Page 58: rociadores std tyco

TFP658Page 12 of 16

Step 1. Cut clearance hole through covering material (Ref. Figure 2, Dim. C).

Note: Location of hole centerline deter-mined by design location of sprinkler.

Step 2. Install sprinkler fitting with face located at proper distance from escutcheon mounting surface (Ref. Figures 5 or 6, Dim. A).

Note: Sprinkler fitting centerline must be perpendicular to escutcheon mounting surface.

Note: Fitting outlet: 1/2” NPT proceed to Step 3; ISO 228 G3/8” proceed to Step 4.

Step 5. Engage sprinkler wrench-ing notches by paint cap or wrench prongs (Ref. Figures 1, 7 and 8). Apply sealant to sprinkler inlet threads (steel pipe system installations Ref. Figure 9; CPVC pipe system installations Ref. Figure 10).

NOTICEAssure sealant avoids contact with internal waterway of sprinkler. Failure to do so may result in equipment failure.

Step 4. Remove shipping cap from sprinkler by pulling away from body along sprinkler centerline.

NOTICESprinkler with shipping cap attached to remain in original packaging until ready for installation. To avoid damage to link assembly, do not pull cap away from sprinkler at an angle.

Step 3. Apply TEFLON tape sealant to external threads of thread adapter and install into sprinkler fitting.

A leak-tight 1/2 inch NPT thread adapter joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm).

NOTICEHigher levels of torque will distort the thread adapter and cause leakage or impairment of the sprinkler.

Step 6. Grasping paint cap or wrench, align sprinkler inlet threads with outlet of thread adapter or CPVC sprinkler adapter fitting and rotate clockwise to initially engage threads.

InstallationPreferred Method: Finished Surface Procedure

In finished surface construction, TYCO Raven Studio 5.6 K-factor Pendent and Horizontal Sidewall Sprinklers must be installed in accordance with this section.

This procedure describes sprinkler installation in construction where ceiling or wall covering material — drywall, plywood, etc. — has been installed in advance.

Step 1

C

Step 2

A

Step 3

Step 6Step 4 Step 5

Page 59: rociadores std tyco

TFP658Page 13 of 16

Step 8. Grasp paint cap or wrench and rotate sprinkler clockwise until painted sprinkler body lip (not brass shoulder) is flush with tool sprinkler body stop (Ref. Figure 11). Remove installation tool.

Note: Proceed to Step 9 for horizontal sidewall sprinkler; proceed to Step 10 for pendent sprinkler.

Note: Allow time for sealant to set before proceeding to Step 10: 5 minutes for LOCTITE 243; 30 minutes for PERMABOND LH056.

Step 12. Remove and discard paint cap to complete installation.

Note: Paint cap is single-use only when painting. Do not re-use after painting.

Step 7. Place base of finished surface installation tool flush against escutch-eon mounting surface, positioning sprinkler body stop against sprinkler dust cap (Ref. Figures 1 and 11). Hold tool in place.

Note: Tool base must be held flush against framing members for proper sprinkler installation.

Step 11. Paint ceiling or wall to suit.

Note: Paint cap to remain attached while painting ceiling or wall.

Note: Install primed escutcheon for best painting results (refer to Ordering Procedure).

Step 10. Orient escutcheon base flange toward mounting surface, align-ing escutcheon centerline with sprin-kler centerline. Push escutcheon onto sprinkler, engaging body by prongs, until flange is flush against mounting surface.

Note: If ceiling or wall painting is not intended, remove paint cap to com-plete installation; If ceiling or wall painting is intended, proceed to Step 11.

Step 9. Orientation of paint cap or wrench “UP” indicator arrow must be in the 12 o’clock position (horizontal sidewall sprinkler only). Rotate sprinkler clockwise a maximum 1 full revolution to attain proper orientation. Remove wrench.

Note: Proper sprinkler orientation may also be verified by observing position of sprinkler wrenching notches (Ref. Figure 13).

Note: Allow time for sealant to set before proceeding to Step 10: 5 minutes for LOCTITE 243; 30 minutes for PERMABOND LH056.

Step 11 Step 12

Step 7 Step 8

Step 10

Step 9

Page 60: rociadores std tyco

TFP658Page 14 of 16

Step A. Determine Dim. D, covering material total thickness (Ref. Figure 14). Subtract Dim. D from Dim. A (Ref. Figures 5 or 6). Install sprinkler fitting, locating face at proper distance from face of framing members using calcu-lated value.

Note: Sprinkler fitting centerline must be perpendicular to escutcheon mounting surface.

Note: Adjust rough-in installation tool depth (Ref. Figure 12) to suit Dim. D.

Note: Fitting outlet: 1/2” NPT proceed to Step B; ISO 228 G3/8” proceed to Step C.

Step B. Apply TEFLON tape sealant to external threads of thread adapter and install into sprinkler fitting.

A leak-tight 1/2 inch NPT thread adapter joint should be obtained by applying a minimum-to-maximum torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm).

NOTICEHigher levels of torque will distort the thread adapter and cause leakage or impairment of the sprinkler.

Step E. Grasping paint cap or wrench, align sprinkler threads with thread adapter port and rotate clockwise to initially engage threads.

Step D. Engage sprinkler wrench-ing notches by paint cap or wrench prongs (Ref. Figures 1, 7 and 8). Apply sealant to sprinkler inlet threads (steel pipe system installations Ref. Figure 9; CPVC pipe system installations Ref. Figure 10).

NOTICEAssure sealant avoids contact with internal waterway of sprinkler. Failure to do so may result in equipment failure.

Step C. Remove shipping cap from sprinkler by pulling away from body along sprinkler centerline.

NOTICESprinkler with shipping cap attached to remain in original packaging until ready for installation. To avoid damage to link assembly, do not pull cap away from sprinkler at an angle.

Step F. Place rough-in installation tool base flush against framing members, positioning sprinkler body stop against sprinkler dust cap (Ref. Figures 1 and 12). Hold tool in place.

Note: Tool base must be held flush against framing members for proper sprinkler installation.

InstallationAlternate Method: Rough-in Procedure

In rough-in construction, TYCO Raven Studio 5.6 K-factor Pendent and Horizontal Sidewall Sprinklers must be installed in accordance with this section.

This procedure describes sprinkler installation in construction where ceiling or wall covering material — drywall, plywood, etc. — has not been installed in advance.

Step A

A - D

A

D

Step B Step C

Step FStep D Step E

Page 61: rociadores std tyco

TFP658Page 15 of 16

Step H. Orientation of paint cap or wrench “UP” indicator arrow must be in the 12 o’clock position (horizontal sidewall sprinkler only). Rotate sprinkler clockwise a maximum 1 full revolution to attain proper orientation. Remove wrench.

Note: Proper sprinkler orientation may also be verified by observing position of sprinkler wrenching notches (Ref. Figure 13).

Note: Allow time for sealant to set before proceeding to Step J: 5 minutes for LOCTITE 243; 30 minutes for PERM-ABOND LH056.

Step M. Remove and discard paint cap to complete installation.

Note: Paint cap is single-use only when painting. Do not re-use after painting.

Step G. Grasp paint cap or wrench and rotate sprinkler clockwise until painted sprinkler body lip (not brass shoulder) is flush with tool sprinkler body stop (Ref. Figure 12). Remove installation tool.

Note: Proceed to Step H for horizontal sidewall sprinkler; proceed to Step J for pendent sprinkler.

Note: Allow time for sealant to set before proceeding to Step J: 5 minutes for LOCTITE 243; 30 minutes for PERM-ABOND LH056.

Step L. Paint ceiling or wall to suit.

Note: Paint cap to remain attached while painting ceiling or wall.

Note: Install primed escutcheon for best painting results (refer to Ordering Procedure).

Step K. Orient escutcheon base flange toward mounting surface, align-ing escutcheon centerline with sprin-kler centerline. Push escutcheon onto sprinkler, engaging body by prongs, until flange is flush against mounting surface.

Note: If ceiling or wall painting is not intended, remove paint cap to com-plete installation; If ceiling or wall painting is intended, proceed to Step L.

Step J. Hold covering material in its installed position and press against paint cap marking point. Cut clear-ance hole through covering material (Ref. Figure 2, Dim. C) using resulting mark as center point. Install covering material, assuring sprinkler is centered in clearance hole.

Note: Paint cap to remain attached for marking center point of covering mate-rial clearance hole.

NOTICEInstall only covering material having total thickness used in Step A.

Step L Step M

Step G Step H

Step K

C

Step J

Page 62: rociadores std tyco

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of the DuPont Corporation; LOCTITE is a trademark of Henkel Corporation; PERMABOND is a trademark of Permabond LLC

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP658Page 16 of 16

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product description and Part Number (P/N).

Note: Order all components separately. A complete assembly consists of sprin-kler, escutcheon, thread adapter and inlet thread sealant. Order installation tools and accessories as needed.

SprinklersSpecify: RAVEN Studio 5.6K Sprin-kler, (specifiy) SIN, (specify) coverage, (specify) orientation, (specify) finish, P/N (specify):Standard CoverageTY1281 – PendentWhite . . . . . . . . . . . . . . . . . . . . . . . 50-310-4-165 Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-310-9-165 Custom Color. . . . . . . . . . . . . . . . . 50-310-X-165

TY1381 – Horizontal SidewallWhite . . . . . . . . . . . . . . . . . . . . . . . 50-312-4-165 Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-312-9-165 Custom Color. . . . . . . . . . . . . . . . . 50-312-X-165

Extended CoverageTY1282 – PendentWhite . . . . . . . . . . . . . . . . . . . . . . . 50-311-4-165 Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-311-9-165 Custom Color. . . . . . . . . . . . . . . . . 50-311-X-165

TY1382 – Horizontal SidewallWhite . . . . . . . . . . . . . . . . . . . . . . . 50-318-4-165 Grey . . . . . . . . . . . . . . . . . . . . . . . . 50-318-9-165 Custom Color. . . . . . . . . . . . . . . . . 50-313-X-165

Style J Escutcheons (3 Inch Diameter)Specify: RAVEN Studio Sprinkler Escutcheon, Style J, 3 inch diameter, (specify) material, (specify) finish, P/N (specify):Carbon SteelWhite . . . . . . . . . . . . . . . . . . . . . . 56-306-4-010 Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-306-7-010 Chrome. . . . . . . . . . . . . . . . . . . . . 56-306-9-010 Primed White . . . . . . . . . . . . . . . . 56-306-0-004 Primed Grey . . . . . . . . . . . . . . . . . 56-306-0-007 Custom Color. . . . . . . . . . . . . . . . .56-306-X-010

Stainless SteelWhite . . . . . . . . . . . . . . . . . . . . . . .56-307-4-010 Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-307-7-010 Electropolish*. . . . . . . . . . . . . . . . .56-307-9-010 Primed White . . . . . . . . . . . . . . . . .56-307-0-004 Primed Grey . . . . . . . . . . . . . . . . . .56-307-0-007 Custom Color. . . . . . . . . . . . . . . . . 56-307-X-010

* Chrome-coated appearance

Style K Escutcheons (4 Inch Diameter)Specify: RAVEN Studio Sprinkler Escutcheon, Style K, 4 inch diameter, (specify) material, (specify) finish, P/N (specify):Carbon SteelWhite . . . . . . . . . . . . . . . . . . . . . . .56-308-4-010 Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-308-7-010 Chrome. . . . . . . . . . . . . . . . . . . . . .56-308-9-010 Primed White . . . . . . . . . . . . . . . . 56-308-0-004 Primed Grey . . . . . . . . . . . . . . . . . 56-308-0-007 Custom Color. . . . . . . . . . . . . . . . .56-308-X-010

Stainless SteelWhite . . . . . . . . . . . . . . . . . . . . . . 56-309-4-010 Grey . . . . . . . . . . . . . . . . . . . . . . . . 56-309-7-010 Electropolish*. . . . . . . . . . . . . . . . 56-309-9-010 Primed White . . . . . . . . . . . . . . . . 56-309-0-004 Primed Grey . . . . . . . . . . . . . . . . . 56-309-0-007 Custom Color. . . . . . . . . . . . . . . . .56-309-X-010

* Chrome-coated appearance

Note: Contact Tyco Customer Service at +1-800-558-5236 with any questions related to custom orders.

Thread AdaptersSpecify: RAVEN Studio Sprinkler Thread Adapter, Brass, (specify) size, P/N (specify): Short 3/4” (19 mm) . . . . . . . . . . . . . 91-310-0-075 Standard 1” (25 mm) . . . . . . . . . . . 91-310-0-100 Medium 1-1/2” (38 mm) . . . . . . . . . 91-310-0-150 Long 2” (50 mm). . . . . . . . . . . . . . .91-310-0-200

CPVC Sprinkler Adapter FittingsSpecify: CPVC Sprinkler Adapter Fitting, (specify type), (specify) size, P/N (specify):90° Elbow1” x ISO 228 G3/8”. . . . . . . . . . . . . . . . . . . 82198

Tee1” x 1” x ISO 228 G3/8” . . . . . . . . . . . . . . . 82251

Sprinkler Inlet Thread SealantSpecify: LOCTITE 243 Thread Sealant, 10 ml Bottle, P/N 91-310-1-243

Specify: PERMABOND LH056 Thread Sealant, 350 ml Container, P/N 33045

Note: PERMABOND LH056 thread sealant has a 12-month shelf life. Pur-chase of new container recommend-ed for each RAVEN Studio Sprinkler project.

Sprinkler Installation ToolsSpecify: RAVEN Studio Installation Tool, (specify type), P/N (specify):Finished Surface . . . . . . . . . . . . . .56-100-0-355 Rough-in . . . . . . . . . . . . . . . . . . . .56-100-0-365

Paint CapSpecify: RAVEN Studio Sprinkler Paint Cap, P/N 56-100-0-354

Sprinkler WrenchSpecify: W-Type 25 Sprinkler Wrench, P/N 56-314-1-001

Page 63: rociadores std tyco

Series TY-FRB – 5.6 K-factor Conventional (Old Style) Sprinklers Quick Response

Page 1 of 4 FEBRUARY 2015 TFP667

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently dam-age a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionThe TYCO Series TY-FRB, 5.6 K-fac-tor, Conventional Sprinklers, Quick Response described in this technical data sheet are quick response, stan-dard coverage, decorative 3 mm glass bulb type spray sprinklers. These sprin-klers are intended to be installed either pendent or upright, and in either posi-tion, they produce a spherical water discharge pattern with approximately 50% of the discharge directed upwards and approximately 50% of the dis-charge directed downwards.

Conventional sprinklers are gener-ally used with Ordinary and Extra High Hazard Class Systems, as defined by the automatic sprinkler system instal-lation rules of the country and author-ity having jurisdiction. The National Fire Protection Association (NFPA) permits the use of “Old Style Sprinklers” where special construction features require a unique water distribution; for the pro-tection of fur vaults; or, the replace-ment of similar sprinklers that had been installed prior to 1955.

NOTICEThe Series TY-FRB Sprinklers de-scribed herein must be installed and maintained in compliance with this doc-ument, as well as with the applicable standards of the National Fire Protec-tion Association, in addition to the stan-dards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Sprinkler Identification Numbers (SINs)TY363 TY3630 (LPCB Approved only)

Technical DataApprovalsUL and C-UL Listed VdS Approved LPCB Approved (TY3630 only)

Sprinklers with Polyester Finish are UL and C-UL Listed as Corrosion-Resis-tant Sprinklers.

Maximum Working Pressure175 psi (12,1 bar)

Discharge CoefficientK=5.6 gpm/psi1/2 (80,6 lpm/bar1/2)

Temperature Ratings135°F (57°C) 155°F (68°C) 175°F (79°C) 200°F (93°C) 286°F (141°C)

FinishesSprinkler: Refer to Table A.

Physical CharacteristicsFrame ....................................................... BronzeButton ............................................ Brass/CopperSealing Assembly ..........................Stainless Steel

w/TEFLONBulb ............................................................ GlassCompression Screw .................................. BronzeDeflector .................................................... Bronze

OperationThe glass bulb contains a fluid which expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, allowing the sprinkler to activate and water to flow.

Design CriteriaThe TYCO Series TY-FRB, 5.6 K-fac-tor, Conventional Sprinklers, Quick Response are intended for fire protec-tion systems designed in accordance with the standard installation rules rec-ognized by the applicable Listing or Approval agency (e.g., UL Listing is based on NFPA 13 requirements). The Series TY-FRB Conventional Sprinklers are only for non-recessed applications.

Page 64: rociadores std tyco

TFP667Page 2 of 4

InstallationThe TYCO Series TY-FRB, 5.6 K-fac-tor, Conventional Sprinklers, Quick Response must be installed in accor-dance with this section.

General InstructionsDo not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprin-kler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm) for the 135°F (57°C) to 3/32 inch (2,4 mm) for the 286°F (141°C) tem-perature ratings.

A leak-tight 1/2 inch NPT sprinkler joint should be obtained with a torque of 7 to 14 ft.-lbs. (9,5 to 19,0 Nm). Higher levels of torque may distort the sprinkler inlet and cause leakage or impairment of the sprinkler.

Step 1. With pipe thread sealant applied to the pipe threads, hand tighten the sprinkler into the sprinkler fitting.

Step 2. Tighten the sprinkler into the sprinkler fitting using only the W-Type 6 Sprinkler Wrench (Ref. Figure 2). With reference to Figure 1, the W-Type 6 Sprinkler Wrench is to be applied to the wrench flats.

Care and MaintenanceThe TYCO Series TY-FRB, 5.6 K-fac-tor, Conventional Sprinklers, Quick Response must be maintained and ser-viced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action.

Sprinklers which are found to be leak-ing or exhibiting visible signs of corro-sion must be replaced.

Automatic sprinklers must never be painted, plated, coated, or other-wise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush.

Care must be exercised to avoid dam-age to the sprinklers before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Refer to Installation Section.)

The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any other authorities

having jurisdiction. Contact the install-ing contractor or product manufacturer with any questions.

It is recommended that automatic sprinkler systems be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

CROSS SECTIONSHOWN UPRIGHT

SHOWNPENDENT

6 - De�ector

5 -4 -

CompressionScrew

Bulb

Components:

-23 -

1 -ButtonSealingAssembly

Frame

1-3/8"(34,9 mm)

2"(50,8 mm)

WRENCHFLATS

7/16" (11,1 mm)NOMINALMAKE-IN

ESCUTCHEON PLATESEATING SURFACE

1/2"NPT

2

1

3

*

Temperaturerating is indicatedon De�ector.

* 4

5

6

*

**

Pipe threadconnections perISO 7-1 can beprovided onspecial request.

**

WRENCH RECESS(USE ONLY

END "A")

FIGURE 1 SERIES TY-FRB CONVENTIONAL SPRINKLERS (TY363 & TY3630)

5.6 K-FACTOR, 1/2 INCH NPT, QUICK RESPONSE

FIGURE 2 W-TYPE 6

SPRINKLER WRENCH

Page 65: rociadores std tyco

TFP667Page 3 of 4

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for availability. When placing an order, indicate the full product name and Part Number (P/N).

Sprinkler Assemblies with NPT Thread ConnectionsSpecify: Series TY-FRB Conventional Sprinkler, (specify) SIN, K=5.6, Quick Response, (specify) temperature rat-ing), (specify) finish, P/N (specify, refer to Table A)

Sprinkler WrenchSpecify: W-Type 6 Sprinkler Wrench, P/N 56-000-6-387

SPRINKLER FINISH

1 NATURAL BRASS

3 PURE WHITE (RAL9010)*** POLYESTER

4 SIGNAL WHITE (RAL9003) POLYESTER

9 CHROME PLATED

TEMPERATURE RATINGS

135 135°F (57°C)

155 155°F (68°C)

175 175°F (79°C)

200 200°F (93°C)

286 286°F (141°C)

P/N* 77 – XXX – X – XXX

SIN

373 5.6K CONVENTIONAL TY363

373 5.6K CONVENTIONAL TY3630**

Notes:* Use suffix “I” for ISO 7-1 connection (e.g., 77-373-4-175-I)** LPCB Approved Series TY-B Conventional Sprinkler as-

semblies only: Use suffix “L” for LPCB Approved assem-blies (e.g., 77-373-4-175-L or 77-373-4-175-IL for LPCB Approved and ISO 7-1 connection)

*** Eastern Hemisphere sales only

TABLE A PART NUMBER SELECTION

SERIES TY-FRB CONVENTIONAL SPRINKLERS

Page 66: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP667Page 4 of 4

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.TEFLON is trademark of The DuPont Corporation.

Page 67: rociadores std tyco

FASTFLEX Model YN25, YB25, and YB28 Flexible Sprinkler Hose Assembly Europe, Middle East, and Africa Only

Worldwide Contacts www.tyco-fire.com

Page 1 of 8 APRIL 2015 TFP720

Technical DataApprovalsUL ListedFM ApprovedVdS ApprovedLPCB Approved

(Specific details for laboratory approvals are given in Table A, and the approvals apply to the service conditions indicated in the applicable Design Criteria sections)

APSAD accepted per Table A

CSTB accepted for all models and assembly lengths

Inlet Connections (Ref. Figure 1)ISO 7-R 1 ISO 7-R 1 1/4

Outlet Connections (Ref. Figure 2)ISO 7-Rc 3/8 1/2 inch NPT 3/4 inch NPT

Nominal Assembly LengthsRef. Table A

Construction (Ref. Figure 1)The Inlet Nipple is mild steel, and the Flexible Hose is SS AISI 304. The connection at each end of the Flexible Hose utilizes a brass Slip Nut, NBR/CR o-ring, and Nylon W6 washer. The Sprinkler Reducer is mild steel. The Reducer Bracket, Bar Fixing Clamps, and Support Bar are pressed steel.

General DescriptionThe TYCO FASTFLEX Flexible Sprinkler Hose is a unique sprinkler drop assem-bly comprised of a branchline adapter nipple, stainless steel flexible hose with two slip nuts, sprinkler reducer, and lightweight ceiling bracket com-ponents. (Ref. Figure 1.)

The FASTFLEX Flexible Sprinkler Hose can be installed in false ceilings without cutting and threading pipes associ-ated with installing a drop, armover, and elbows. FASTFLEX makes it pos-sible to test and charge the system with water before the ceiling grid is installed. Once the ceiling grid is in position, the FASTFLEX hoses can be reshaped to suit the final sprinkler location without draining the system.

FASTFLEX Flexible Sprinkler Hose is installed quickly without large and expensive tools. Ideal projects are offices, schools, libraries, hospitals, and shopping complexes. FASTFLEX sprinkler hoses are for use on wet pipe, preaction, and dry pipe systems. The FASTFLEX hose can also be used in conjunction with ultra-low flow water mist nozzles following the design crite-ria outlined in this technical data sheet.

NOTICEThe FASTFLEX flexible sprinkler hoses described herein must be installed and maintained in compliance with this document and with the applicable standards recognized by the Approval agency, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the perfor-mance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Page 68: rociadores std tyco

TFP720Page 2 of 8

TYPICAL SPRINKLER

SEE FIGURE 2FOR DETAILS

(STRAIGHT SHOWN)

HOSE THREADEDSPRINKLER REDUCER

INLETNIPPLE

BRANCHLINE FITTING OUTLET

CLAMP WITH

CEILING

T-BARGRID

SCREW

BOLTSBUTTERFLY

FIXING

ISO 7-R 1 or

PIPE THREADEDEND

DROP-INCEILING PANEL

BOLTS

REDUCER

BUTTERFLYBRACKET WITH

SUPPORTBAR

600 mm

25 or 28 mm IDHOSE THREADED

END

ASSEMBLY

25 or 28 mm ID

BAR

ISO 7-R 1-1/4

25 mm ID BRAIDED

28 mm ID BRAIDED25 mm ID BRAIDED - FM

28 mm ID BRAIDED - FM

25 mm ID UNBRAIDEDWITH SLIP NUTS:FLEXIBLE HOSE

SPRINKLERREDUCER

(SEE FIGURE 2)

REDUCERBRACKET WITH

BUTTERFLYBOLTS

HOSETHREADEDSLIP NUT

CEILINGGRIDT-BAR

DROP-INCEILINGPANEL

SUPPORTBAR

SYSTEMBRANCHLINE

INLETNIPPLE

BRANCHLINEFITTING

(NOT INCLUDED)

BARFIXING

CLAMP WITHBUTTERFLY

BOLTS

SPRINKLER INSTALLEDIN ACCORDANCE WITH

MANUFACTURER'SINSTRUCTIONS

ISO 7-R 1 orISO 7-R 1-1/4THREADED

FITTINGOUTLET

FLEXIBLE HOSEWITH SLIP NUTS:

25 mm ID UNBRAIDED25 mm ID BRAIDED25 mm ID BRAIDED - FM28 mm ID BRAIDED28 mm ID BRAIDED - FM

FIGURE 1 FASTFLEX FLEXIBLE SPRINKLER HOSE

Page 69: rociadores std tyco

TFP720Page 3 of 8

370

(YB)

2370

33702770

2170167014701380870670

MODELSIZE

1500

31003700

25002700

18002000

70010001200

11901380

29803580

238018801680

258027903390

21902390

14901690

NOMINAL LENGTH mm

580

(YN or YB)L1

1080880

390

890690

L2(YN)

L2

SPRINKLER REDUCERS

HOSE ASSEMBLIES

BAR FIXING CLAMPS

MALE HOSE

OUTLET

STRAIGHT

AND BRACKET

120 mm

THREADED

25 or 28 mm ID

INLET

or 3/4" NPT1/2" NPT,

ISO 7-Rc 3/8,

FEMALE PIPETHREADED

WRENCH

FLATS

BRANCHLINEFITTING

TERMINATIONFERRULE

SPRINKLERREDUCER

HOSE

FLEXIBLEHOSE

NIPPLEINLET

140 mm

45 DEGREE

125 mm

125 mm

90 DEGREE

133 mm

L1

L2

NUTSLIP

FLATS

WRENCHAND BRACKET

25 or 28 mm ID

THREADEDMALE HOSE

INLET

OUTLETTHREADED

FEMALE PIPE

1/2" NPT,or 3/4" NPT

ISO 7-Rc 3/8, ISO 7-Rc 3/8,

FEMALE PIPETHREADED

or 3/4" NPT

OUTLET

1/2" NPT,

WRENCHAND BRACKET

FLATS

INLET

25 or 28 mm ID

THREADEDMALE HOSE

50 mm 90 mm

FIGURE 2 FASTFLEX FLEXIBLE SPRINKLER HOSE

NOMINAL DIMENSIONS

Page 70: rociadores std tyco

TFP720Page 4 of 8

LPCB - Design Criteria• Refer to Table A for Model, Nominal Assembly Length,

and Sprinkler Reducer combinations.

• Wet-pipe systems only.

• Maximum service pressure of 16 bar.

• Sprinklers with nominal K57, K80, or K115.

• Maximum ambient temperature of 148°C for YN25.

• Approved as a Type 2 hose of moderate flexibility in accordance with LPS 1261. They may be used in applications where little or no differential movement between the two ends is expected after installation (e.g., supply to single sprinklers in suspended ceilings).

• Approved for the following locations:

Assembly Length in

Millimeters

Pre-Calculated Town Mains

Pre-Calculated Pumps

Fully Hydraulically Calculated

Up to 700 Yes Yes Yes

Up to 1200 No Yes Yes

Up to 3700 No No Yes

• All pipe work supplying FASTFLEX in pre-calculated systems shall be sized as distribution mains.

• In suspended ceilings FASTFLEX must be installed in accordance with this data sheet.

• In suspended ceiling, sprinkler reducer must be connected to the ceiling support system with brackets supplied. For other applications the installer must supply brackets to ensure sprinkler is secure.

• Minimum bend radius of 55 mm.

• LPCB Friction Loss for YN25.

Assembly Length in

Millimeters

Number of 90° Bends

Equivalent Length* of DN25 Sch. 40 Pipe at

C=120 in Meters

700 2 8,9

1000 2 13,5

1200 2 11,9

1500 2 18,7

1800 3 24,7

2000 3 20,7

2500 3 21,7

2700 3 24,2

3100 3 25,9

3700 3 30,3* Add 2,3 meters when using a 45° or 90° sprinkler

reducer.

VdS - Design Criteria• Refer to Table A for Model, Nominal Assembly Length,

and Sprinkler Reducer combinations.

• Wet-pipe systems only.

• Maximum service pressure of 16 bar.

• Pendent sprinklers with nominal K57, K80, or K115.

• Maximum ambient temperature of 107°C for YB25 and YB28.

• Approved for use only in the following suspended ceilings:

Odenwald Systems- S3 & S15

Richter Systems- 11.1 - 11.5

Armstrong Systems- Board and Tegular with panel type “Prima Sahara”

API Systems- 15/38, 24/38, 24/60, 35/38, and 35/60 with panel type of a.m.

• VdS Friction Loss

• For compensation of pressure loss, the nominal assembly length is to be multiplied by 12. The resulting length will provide pressure drop in equivalent length DN20 (26,9 x 2,3 mm) seamless metal tube per DIN 2448.

• Add 2,3 m when using a 45° or 90° sprinkler reducer.

• Minimum bend radius of 55 mm.

• The tube assembly may not have more than one 90° bend or four 15° bends.

Page 71: rociadores std tyco

TFP720Page 5 of 8

FM - Design Criteria• Refer to Table A for Model, Nominal Assembly Length,

and Sprinkler Reducer combinations.

• Wet pipe, preaction, and dry pipe systems.

• Maximum service pressure of 12 bar.

• Sprinklers with a maximum K80 (K5.6) for 1/2 inch NPT or maximum K115 (K8.0) for 3/4 inch NPT.

• Maximum ambient temperature of 107°C for Model YB25 and YB28.

• Minimum ambient temperature of -40°C for Model YB25 and YB28 for use in dry pipe systems.

• These connections are designed for use in ceilings with grids that meet ASTM C 635 (Standard Specifi-cation for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings) and ASTM C 636 (Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels) refer-enced by IBC. The three structural classifications are the following: Intermediate-Duty Systems and Heavy-Duty Systems. These connections have been approved for use in all Intermediate-Duty and Heavy-Duty structural classifications.

• Minimum bend radius of 152 mm for Model YB28 or 203 mm for Model YB25.

• FM Friction Loss for YB25 and YB28:

Assembly Length in

Millimeters

Outlet (NPT)

Max Number

of 90° Bends

YB25 YB28Equivalent

Length of DN25 Sch. 40 Pipe

C=120 in Meters

Equivalent Length of DN25

Sch. 40 PipeC=120 in Meters

700 1/2 1 14,1 7,73/4 1 11,9 6,0

1000 1/2 1 16,4 12,23/4 1 13,8 10,4

1200 1/2 2 22,4 15,23/4 2 19,6 13,4

1500 1/2 3 27,4 17,63/4 3 26,4 16,1

1800 1/2 4 34,4 20,03/4 4 32,0 18,7

UL - Design Criteria• Refer to Table A for Model, Nominal Assembly Length,

and Sprinkler Reducer combinations.

• Wet-pipe systems only.

• The hose and fittings have limited flexibility and are intended for direct connection to sprinklers in accor-dance with NFPA 13, 13D, or 13R.

• Maximum service pressure of 13 bar.

• Sprinklers with a maximum K80 (K5.6) for 1/2 inch NPT or maximum K115 (K8.0) for 3/4 inch NPT.

• Maximum ambient temperature of 107°C for Model YB25 and YB28, or maximum ambient temperature of 148°C for Model YN25.

• These connections are designed for use in ceilings with grids that meet ASTM C 635 (Standard Specifi-cation for the Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-in Panel Ceilings) and ASTM C 636 (Standard Practice for Installation of Metal Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels) refer-enced by IBC. The three structural classifications are the following: Intermediate-Duty Systems and Heavy-Duty Systems. These connections have been approved for use in all Intermediate-Duty and Heavy-Duty structural classifications.

• Minimum bend radius of 76 mm.

Assembly Length in

Millimeters

Outlet (NPT)

Maximum Number

of 90° Bends*

YN25 and YB25 YB28

Equivalent Length of DN25 Sch. 40 Pipe at

C=120 in Meters

Equivalent Length of DN25 Sch. 40 Pipe at

C=120 in Meters

7001/2 2 6,7 3,0

3/4 2 8,5 4,9

10001/2 2 9,8 4,9

3/4 2 11,6 7,0

12001/2 2 12,5 6,1

3/4 2 14,6 7,6

15001/2 2 14,9 7,0

3/4 2 16,5 8,5

1800

1/22 18,3 7,9

3 20,4 9,8

3/42 20,4 10,1

3 22,6 11,6

* Information in this column indicates the maximum number of allow-able bends and that hoses are installed with at least one bend.

Page 72: rociadores std tyco

TFP720Page 6 of 8

Model TypeAssembly Length in

Millimeters

LPCB VdS FM UL* APSAD**

50 and 90 mm Bar Fixing

Clamp

50 and 90 mm Bar Fixing

Clamp

50 and 90 mm Bar Fixing

Clamp

50 mm Bar Fixing

Clamp

50 and 90 mm Bar Fixing

Clamp

Sprinkler Reducer Type

Sprinkler Reducer Type

Sprinkler Reducer Type

Sprinkler Reducer Type

Sprinkler Reducer Type

0° 45° 90° 0° 45° 90° 0° 45° 90° 0° 45° 90° 0° 45° 90°

YN25-700 Un-braided 700 x x x x x

YN25-1000 Un-braided 1000 x x x x x

YN25-1200 Un-braided 1200 x x x x x

YN25-1500 Un-braided 1500 x x x x x

YN25-1800 Un-braided 1800 x x x x

YN25-2000 Un-braided 2000 x x x

YN25-2500 Un-braided 2500 x x x

YN25-2700 Un-braided 2700 x x x

YN25-3100 Un-braided 3100 x x x

YN25-3700 Un-braided 3700 x x x

YB25-700 Braided 700 x x x x

YB25-1000 Braided 1000 x x x x

YB25-1200 Braided 1200 x x x x

YB25-1500 Braided 1500 x x x x

YB25-1800 Braided 1800 x x x x

YB25-2000 Braided 2000 x x x

YB25-2500 Braided 2500 x x x

YB25-700 Braided-FM 700 x

YB25-1000 Braided-FM 1000 x

YB25-1200 Braided-FM 1200 x

YB25-1500 Braided-FM 1500 x

YB25-1800 Braided-FM 1800 x

YB28-700 Braided 700 x x x x x

YB28-1000 Braided 1000 x x x x x

YB28-1200 Braided 1200 x x x x x

YB28-1500 Braided 1500 x x x x x

YB28-1800 Braided 1800 x x x x

YB28-2000 Braided 2000 x x x

YB28-2500 Braided 2500 x x x

YB28-700 Braided - FM 700 x

YB28-1000 Braided - FM 1000 x

YB28-1200 Braided - FM 1200 x

YB28-1500 Braided - FM 1500 x

YB28-1800 Braided - FM 1800 x

x Indicates Listed or Approved as applicable.* UL Listing is based on the use of the ISO 7-R 1 Inlet Connection.** Acceptance by APSAD is based on using the LPCB, VdS, FM Approved, or UL Listed Design Criteria as may be accept-

able to the authority having jurisdiction.

TABLE A FASTFLEX SPRINKLER HOSE ASSEMBLY

MODELS, ASSEMBLY LENGTHS, AND APPROVALS

Page 73: rociadores std tyco

TFP720Page 7 of 8

DO route the FASTFLEX Flexible Hose to permit entire draining either back into the branch-line or through the sprinkler reducer.

DO use the FASTFLEX Inlet Nipple with the direction of flow arrow properly oriented to avoid mismatched threads.

InstallationThe TYCO FASTFLEX Flexible Sprin-kler Hose as shown in Figure 1, must be installed in accordance with this section.

NOTICEFlexible Hoses are intended only to connect sprinklers directly to system piping (Ref. Figure 1). Flexible Hoses cannot be joined together to form longer hoses. Joining Flexible Hoses together creates an assembly with unknown performance that has not been accounted for in system calcula-tions or safe product performance.

Step 1. Review the Design Criteria section that applies to the Approval agency recognized by the authority having jurisdiction, as well as Figure 3 that provides installation guidance.

Step 2. Determine the approximate place where the sprinkler will be located. The Support Bar is 700 mm long and shall be mounted on the 600 mm width of the ceiling grid. The sprinkler should be located as close as possible to the center of the distance between ceiling grid T-bars.

Step 3. Slide the Reducer Bracket onto the Support Bar. Loosely attach the Reducer Bracket and the two Bar Fixing Clamps on the Support Bar and place the Bar Fixing Clamps such that the Support Bar crosses the location where the sprinkler will be located.

Step 4. Attach one end of the Flex-ible Hose onto the sprinkler reducer. Applying the wrench to the Slip Nut, and not to the Flexible Hose, tighten to a maximum torque of 35 Nm.

Step 5. Attach the Inlet Nipple on to the branch line. Ensure that the arrow is in the appropriate direction of flow to the sprinkler and to use pipe thread sealant at the connection to the branch line.

Attach one end of the Flexible Hose on to the Inlet Nipple. Applying the wrench to the Slip Nut, and not to the Flexible Hose, tighten to a maximum torque of 35 Nm. Do not twist the Flexible Hose.

Step 6. Bend the Flexible Hose into a curve(s) that locates the Sprinkler Reducer at the other end of the Flexible Hose in the area where the sprinkler will be located. The tube arc should not be twisted, and the arc should be as large and smooth as possible.

NOTICEFor minimum bend criteria, refer to the Design Criteria section that applies to the Approval agency recognized by the authority having jurisdiction.

A bend radius smaller than pro-vided by the minimum bend criteria may adversely effect the friction loss specifications stated by the approval laboratory.

For assembly lengths greater than 1800 mm the Flexible Hose shall be supported to the structure to ensure that the maximum unsupported length does not exceed 1800 mm. In these cases, it is recommended that the tube be secured to a fixed mounting point every 600 mm, in order to provide a more stable installation.

For installations per LPCB, all bends greater than 45° shall be fitted with a MRI55 Plastic Clip Minimum Radius Indicator (Ref. Figure 4).

Step 7. Insert the Sprinkler Reducer into the Reducer Bracket. Locate the Reducer Bracket and Sprinkler Reducer where the sprinkler will be, and loosely tighten the Butterfly Bolt on the Reducer Bracket.

Step 8. Attach the sprinkler to the Sprinkler Reducer. Put a wrench on the Sprinkler Reducer to counteract the tightening torque and prevent the Flex-ible Hose from twisting. Reference the sprinkler manufacturer’s sprinkler data sheet for appropriate sprinkler tighten-ing torque, sprinkler wrench, and other guidance.

Step 9. Verify that the Sprinkler Reducer is seated in the Reducer Bracket. Precisely locate the sprin-kler in all three axes in accordance with the sprinkler manufacturer’s data sheet. Tighten the Butterfly Bolts on the Bar Fixing Clamps and the Reducer Bracket. The tightening torque for the Bar Fixing Clamp fastener is 4,5 to 5,7 Nm, and the tightening torque for the Reducer Bracket fastener, is a minimum of 2,3 Nm.

Step 10. After tightening all the But-terfly Bolts, verify that the sprinkler is properly located in accordance with the manufacture’s instructions. If not, loosen the Butterfly Bolts and readjust as required.

PERMITTED NOT PERMITTEDNOT PERMITTED

ISO 7-R 1OR ISO 7-R 1 1/4THREADED END

MACHINE HOSETHREADED

END

BRANCHLINEFITTINGOUTLET

SLIPNUT

FLEXIBLEHOSE TO

SPRINKLER

INLETNIPPLE

FIGURE 3 FASTFLEX FLEXIBLE SPRINKLER HOSE

INSTALLATION GUIDANCE

Page 74: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP720Page 8 of 8

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.

Care and MaintenanceThe TYCO FASTFLEX Flexible Sprinkler Hose must be maintained and serviced in accordance with this section.

Before closing a fire protection system control valve for inspection or main-tenance work on the fire protection system that it controls, permission to shut down the effected fire protection system must first be obtained from the proper authorities and all person-nel who may be affected by this action must be notified.

After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni-toring proprietary and/or central station alarms.

The owner is responsible for the inspec-tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N).Flexible Hose AssemblyThe FASTFLEX Flexible Hose Assembly includes Flexible Hose, ISO 7-R 1 x Hose Thread Inlet Nipple, 1/2" NPT x Hose Thread Straight Sprin-kler Reducer, Reducer Bracket, Bar Fixing Clamps, and Support Bar.

Note: Refer to Table A for Model, Type, Length, Bar Fixing Clamp options, and Approval details.

Specify: Model (specify) FASTFLEX Flexible Sprinkler Hose Assembly, Type (specify), (specify) length, (specify) Bar Fixing Clamp, P/N (specify):Model YN25, Un-braided, 50 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2507001000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2510001200 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2512001500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2515001800 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2518002000 . . . . . . . . . . . . . . . . . . . . . . . . . . YN2520002500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2525002700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2527003100. . . . . . . . . . . . . . . . . . . . . . . . . . . . YN2531003700 . . . . . . . . . . . . . . . . . . . . . . . . . . . YN253700

Model YN25, Un-braided, 90 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . .YN250700C1000 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251000C1200 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251200C1500 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251500C1800 . . . . . . . . . . . . . . . . . . . . . . . . . . YN251800C2000 . . . . . . . . . . . . . . . . . . . . . . . . . .YN252000C2500 . . . . . . . . . . . . . . . . . . . . . . . . . .YN252500C2700 . . . . . . . . . . . . . . . . . . . . . . . . . . YN252700C3100. . . . . . . . . . . . . . . . . . . . . . . . . . . YN253100C3700 . . . . . . . . . . . . . . . . . . . . . . . . . .YN253700C

Model YB25, Braided, 50 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2507001000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2510001200 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2512001500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2515001800 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2518002000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2520002500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB252500

Model YB25, Braided, FM Approved 50 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . YB250700-F1000 . . . . . . . . . . . . . . . . . . . . . . . . . YB251000-F1200 . . . . . . . . . . . . . . . . . . . . . . . . . YB251200-F1500 . . . . . . . . . . . . . . . . . . . . . . . . . YB251500-F1800 . . . . . . . . . . . . . . . . . . . . . . . . . YB251800-F

Model YB28, Braided, 50 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2807001000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2810001200 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2812001500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2815001800 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2818002000 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB2820002500 . . . . . . . . . . . . . . . . . . . . . . . . . . . YB282500

Model YB28, Braided, FM Approved, 50 mm Clamps700 . . . . . . . . . . . . . . . . . . . . . . . . . . YB280700-F1000 . . . . . . . . . . . . . . . . . . . . . . . . . YB281000-F1200 . . . . . . . . . . . . . . . . . . . . . . . . . YB281200-F1500 . . . . . . . . . . . . . . . . . . . . . . . . . YB281500-F1800 . . . . . . . . . . . . . . . . . . . . . . . . . YB281800-F

Inlet NippleSpecify: (25 mm or 28 mm) hose thread FASTFLEX Inlet Nipple with (ISO 7-R 1 or ISO 7-R 1 1/4) inlet thread connec-tion, P/N (specify):

25 mm Hose Thread ISO 7-R 1 . . . . . . . . . . . . . . . . . . .HOSENIP25 ISO 7-R 1 1/4 . . . . . . . . . . . . . . HOSENIP25R

28 mm Hose Thread ISO 7-R 1 . . . . . . . . . . . . . . . . . . .HOSENIP28 ISO 7-R 1 1/4 . . . . . . . . . . . . . . HOSENIP28R

Sprinkler Reducer Specify: (Straight, 45 Degree, or 90 Degree) for (25 mm or 28 mm hose threads) FASTFLEX Sprinkler Reducer with (ISO 7-Rc 3/8, 1/2 inch NPT, or 3/4 inch NPT) outlet thread connection, P/N (specify):

Straight 25 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBR120 1/2 inch NPT . . . . . . . . . . . . . . . . . . . RBR120 3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBR120

28 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PBR28120 1/2 inch NPT . . . . . . . . . . . . . . . . . RBR28120 3/4 inch NPT . . . . . . . . . . . . . . . . . SBR28120

45 Degree 25 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR45 1/2 inch NPT . . . . . . . . . . . . . . . . . . .RBAR45 3/4 inch NPT . . . . . . . . . . . . . . . . . . . SBAR45

28 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . PB28AR45 1/2 inch NPT . . . . . . . . . . . . . . . . .RB28AR45 3/4 inch NPT . . . . . . . . . . . . . . . . .SB28AR45

90 Degree 25 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . . . . PBAR90 1/2 inch NPT . . . . . . . . . . . . . . . . . . .RBAR90 3/4 inch NPT . . . . . . . . . . . . . . . . . . .SBAR90

28 mm Hose Thread ISO 7-Rc 3/8 . . . . . . . . . . . . . . . . .PB28AR90 1/2 inch NPT . . . . . . . . . . . . . . . . .RB28AR90 3/4 inch NPT . . . . . . . . . . . . . . . . .SB28AR90

Bar Fixing ClampsSpecify: FASTFLEX (50 mm or 90 mm) Bar Fixing Clamps, P/N (specify):50 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . RBF58T90 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . RBF90T

Minimum Radius IndicatorSpecify: MRI55 Plastic Clip Minimum Radius Indicator of 55 mm to be attached to Sprinkler Hose YN25, P/N MRI55

Note: For installations per LPCB, all bends greater than 45° shall be fitted with a MRI55 Plastic Clip Minimum Radius Indicator. (Ref. Figure 4.)

FLEXIBLEHOSE

YN25

INDICATORRADIUS

MINIMUM

MRI55

FIGURE 4 MINIMUM RADIUS INDICATOR

MRI55

Page 75: rociadores std tyco

FASTFLEX Model FB Flexible Braided Hose

Page 1 of 6 MARCH 2015 TFP730

Worldwide Contacts www.tyco-fire.com

Technical DataApprovalsVdS Approved

(Approvals apply to the service conditions indicated in the Design Criteria sections.)

CSTB accepted for all models and assembly lengths.

Inlet Connections (Ref. Figure 1)ISO 7-R 1

Outlet Connections (Ref. Figure 3)1/2 inch NPT 3/4 inch NPT

Nominal Assembly Lengths Ref. Figure 3

Construction (Ref. Figure 1)The Inlet Nipple is mild steel, and the Flexible Hose is SS AISI 304. The Sprinkler Reducer is mild steel. The Reducer Bracket, Bar Fixing Clamps, and Support Bar are pressed steel.

Design CriteriaThe TYCO FASTFLEX Model FB Flex-ible Braided Hose is VdS Listed and used with pendent sprinklers. The fol-lowing paragraph provides the design criteria unique to VdS Approval listing.

VdS Listing Design Criteria• Wet-pipe systems only

• Minimum bend radius of 55 mm

• Maximum service pressure of 16 bar

• Pendent sprinklers with nominal K57, K80, or K115

• Maximum ambient temperature of 107°C

General DescriptionThe TYCO FASTFLEX Model FB Flex-ible Braided Hose is a unique sprinkler drop assembly comprised of a stain-less steel flexible hose a swivel inlet nipple, a sprinkler reducer, and light-weight ceiling bracket components. (Ref. Figure 1.)

The FASTFLEX Model FB Flexible Braided Hose can be installed in false ceilings without cutting and threading pipes associated with installing a drop, arm-over, and elbow. It provides easier maneuverability around ducts and trays in congested spaces and for unusual ceiling types and curved plasterboard ceilings. The FASTFLEX Model FB Flex-ible Braided Hose makes it possible to test and charge the system with water before the ceiling grid is installed. Once the ceiling grid is in position, the hoses can be reshaped to suit the final sprinkler location without draining the system.

The FASTFLEX Model FB Flexible Braided Hose hoses are for use on wet pipe sprinkler systems only.

NOTICEThe TYCO FASTFLEX Model FB Flex-ible Braided Hose described herein must be installed and maintained in compliance with this document and with the applicable standards rec-ognized by the Approval agency, in addition to the standards of any other authorities having jurisdiction. Failure to do so may impair the performance of these devices.

The owner is responsible for main-taining their fire protection system and devices in proper operating con-dition. Contact the installing contrac-tor or product manufacturer with any questions.

Approved Ceiling SystemsFASTFLEX Model FB Flexible Braided Hose assemblies are approved for installation above suspended ceiling systems having T-profile grid supports manufactured only by:

AMF Odenwald Richter Armstrong Rigips Knauf Chicago Metallic Durlum Geipel Gema Armstrong Suckow & Fischer USG Donn Daldrop & Dr. Huber Rockfon Pagos

NOTE: FASTFLEX Model FB Flex-ible Braided Hose assemblies are approved for installation with RBF38T Gypsum End Brackets in gypsum sus-pended ceiling systems having U-pro-file channel support construction.

VdS Friction LossFor compensation of pressure loss, the nominal assembly length is to be multiplied by 10. The resulting length will provide pressure drop in equivalent length DN25 (33,7 x 3,25 mm) metal tube per EN 10255.

Add 2,3 m when using a 90° sprinkler reducer.

Page 76: rociadores std tyco

TFP730Page 2 of 6

InstallationT-Bar Bracket Application

The TYCO FASTFLEX Model FB Flexible Braided Hose, as shown in Figure 1, must be installed in accor-dance with this section.

NOTICETYCO Model FB Flexible Braided Hoses are intended only to connect sprinklers directly to system piping (Ref. Figure 1). Model FB Flexible Braided Hoses cannot be joined together to form longer hoses. Joining flexible hoses together creates an assembly with unknown performance that has not been accounted for in system calcula-tions or safe product performance.

Step 1. Review the Design Criteria section that applies to the approval agency recognized by the authority having jurisdiction, as well as Figure 4 that provides Installation Guidance.

Step 2. Determine approximately where the sprinkler will be located.

Mount the End Brackets to the Support Bar then slide the End Brackets over the ceiling grid T-bars. The sprin-kler should be located as close to the center of the distance between the ceiling grid T-bars as possible.

Step 3. Hand-tighten the Wings Screws and the Hex Screws on the End Brack-ets securing the Support Bar.

Step 4. Attach the Swivel Inlet Nipple to the Branchline Fitting outlet. (Ref. Figure 1.) Apply the wrench directly to the Swivel Inlet Nipple and tighten to the maximum torque of 35 Nm.

Step 5. Attach the sprinkler to the Sprinkler Reducer. Place a wrench on the Sprinkler Reducer to counteract the tightening torque of the sprinkler and torque the sprinkler to the recom-mended torque setting. Refer to the sprinkler manufacturer’s sprinkler data sheet for appropriate sprinkler torque setting, sprinkler wrench, and other guidance.

Step 6. Bend the Flexible Braided Hose and place the Sprinkler Reducer to

where the sprinkler will be located. The hose arc should not be twisted, and the arc should be as large and smooth as possible. (Ref. Figures 3 and 4)

NOTICEFor minimum bend criteria, refer to the Design Criteria section that applies to the approval agency recognized by the authority having jurisdiction.

A bend radius smaller than pro-vided by the minimum bend criteria may adversely effect the friction loss specifications stated by the approval laboratory.

Step 7. Slide the Reducer Bracket over the Sprinkler Reducer end of the Flex-ible Braided Hose and clip over the Support Bar. Hand-tighten the fastener on the Reducer Bracket securing the Reducer Bracket to the Support Bar. Ensure that the Reducer Bracket fas-tener is secured to the flat surface of the Sprinkler Reducer.

Step 8. After tightening the Reducer Bracket fastener, verify that the sprin-

CEILINGGRIDT-BAR

DROP-INCEILINGPANEL

SUPPORTBAR

SYSTEMBRANCHLINE

SPRINKLER INSTALLEDIN ACCORDANCE WITH

MANUFACTURER'SINSTRUCTIONS

BRANCHLINEFITTING

(NOT INCLUDED)

REDUCERBRACKET WITHSOCKET HEAD

SCREW

INTEGRATEDHEX SPRINKLER

REDUCER

BRAIDEDJACKET

FLEXIBLEHOSE

BRANCHLINEFITTING

ISO 7-R 1THREADED

OUTLET

END BRACKETWITH WING

SCREW, HEXSCREW AND

LOCK WASHER

INTEGRATEDKNURLED AND

MALE THREADEDSWIVEL INLET

NIPPLE

600 mm

FIGURE 1 FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE

ASSEMBLY AND TYPICAL INSTALLATION

Page 77: rociadores std tyco

TFP730Page 3 of 6

kler is properly located in accordance with the manufacturer’s instructions. If not in the proper location, adjust its position as necessary.

Step 9. Once the sprinkler is in the proper location, torque all hardware as follows:

NOTE: The End Brackets Wing Screws must be tightened before tightening the Reducer Bracket to the Support Bar.

End Bracket Hex Screws . . . . . . . . . . 4,5 Nm (min)End Bracket Wing Screws . . . . . . . . 4,5 to 5,7 NmReducer Bracket Fastener . . . . . . . . . . . . . 2,3 Nm (min)

InstallationGypsum End Bracket Application

THE TYCO FASTFLEX Model FB Flex-ible Braided Hose gypsum ceiling installation, using the Gypsum End Bracket RBF38T as shown in Figure 2, must be installed in accordance with this section.

NOTICETYCO Model FB Flexible Braided Hoses are intended only to connect sprinklers directly to system piping (Ref. Figure 1). Model FB Flexible Braided Hoses cannot be joined together to form longer hoses. Joining flexible hoses together creates an assembly with unknown performance that has not been accounted for in system calcula-tions or safe product performance.

Step 1. Review the Design Criteria section that applies to the approval agency recognized by the authority having jurisdiction, as well as Figure 4 that provides Installation Guidance.

Step 2. Determine approximately where the sprinkler will be located. Set the Support Bar on the U-profile Support Channel, then mount the Gypsum End Bracket to the Support Bar. Hook the Gypsum End Bracket under the edge of the U-profile Support Channel. The sprinkler should be located as close to the center of the distance between the U-profile Support Channels as possible.

Step 3. Hand-tighten the Wing Screw on the Gypsum End Bracket securing it to the Support Bar.

Step 4. Attach the Swivel Inlet Nipple to the Branchline Fitting outlet. (Ref. Figure 1.) Apply the wrench directly to the Swivel Inlet Nipple and tighten to the maximum torque of 35 Nm.

Step 5. Attach the sprinkler to the Sprinkler Reducer. Place a wrench on the Sprinkler Reducer to counteract the tightening torque of the sprinkler and torque the sprinkler to the recom-mended torque setting. Refer to the sprinkler manufacturer’s sprinkler data sheet for appropriate sprinkler torque setting, sprinkler wrench, and other guidance.

Step 6. Bend the Flexible Braided Hose and place the Sprinkler Reducer to where the sprinkler will be located. The hose arc should not be twisted, and the arc should be as large and smooth as possible. (Ref. Figures 3 and 4)

NOTICEFor minimum bend criteria, refer to the Design Criteria section that applies to the approval agency recognized by the authority having jurisdiction.

A bend radius smaller than pro-vided by the minimum bend criteria may adversely effect the friction loss specifications stated by the approval laboratory.

Step 7. Slide the Reducer Bracket over the Sprinkler Reducer end of the Flex-ible Braided Hose and clip over the Support Bar. Hand-tighten the fastener on the Reducer Bracket securing the Reducer Bracket to the Support Bar. Ensure that the Reducer Bracket fas-tener is secured to the flat surface of the Sprinkler Reducer.

Step 8. After tightening the Reducer Bracket fastener, verify that the sprin-kler is properly located in accordance with the manufacturer’s instructions. If not in the proper location, adjust its position as necessary.

Step 9. Once the sprinkler is in the proper location, torque all hardware as follows:

NOTE: The Gypsum End Bracket Wing Screws must be tightened before tightening the Reducer Bracket to the Support Bar.

Gypsum End Bracket Wing Screws . . . . . . . . 4,5 to 5,7 NmReducer Bracket Fastener . . . . . . . . . . . . . 2,3 Nm (min)

GYPSUM CEILINGU-PROFILE SUPPORT

CHANNEL

RBF38TGYPSUM END

BRACKET WITHWING SCREW

SUPPORT BAR

FIGURE 2 FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE

GYPSUM CEILING INSTALLATION DETAIL

Page 78: rociadores std tyco

TFP730Page 4 of 6

Care and MaintenanceThe TYCO FASTFLEX Model FB Flex-ible Braided Hose must be maintained and serviced in accordance with this section.

Before closing a fire protection system control valve for inspection or main-tenance work on the fire protection system that it controls, permission to shut down the effected fire protection system must first be obtained from the proper authorities and all person-nel who may be affected by this action must be notified.

Inspection, testing, and maintenance must be performed as indicated below and in accordance with the local requirements and/or national codes. Any impairment must be immediately corrected.

The owner is responsible for the inspec-tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the authorities having jurisdiction. Contact the installing contractor or product manufacturer with any questions.

After placing a fire protection system in service, notify the proper authorities and advise those responsible for moni-toring proprietary and/or central station alarms.

Automatic sprinkler systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

Model TypeL

Nominal Length

Maximum Number of

Bends

FB25-700 Braided 700 mm 3

FB25-1000 Braided 1000 mm 3

FB25-1200 Braided 1200 mm 3

FB25-1500 Braided 1500 mm 4

FB25-2000 Braided 2000 mm 4

OUTERBRAIDEDJACKET

STRAIGHTSPRINKLERREDUCER

90°SPRINKLERREDUCER

INNERFLEXIBLE

HOSE

SWIVELINLET

NIPPLE

OUTERBRAIDEDJACKET

INNERFLEXIBLE

HOSE

SWIVELINLET

NIPPLE

ISO 7-R 1

180 mm

ISO 7-R 1

L

L

1/2" NPTor

3/4" NPT

1/2" NPTor

3/4" NPT

FIGURE 3 FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE ASSEMBLY

NOMINAL DIMENSIONS

Page 79: rociadores std tyco

TFP730Page 5 of 6

Route the Model FB Flexible Braided Hose to permit the water to drain back into the branchline or through the sprinkler reducer.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and Part Number (P/N).

Flexible Hose Assembly** The FASTFLEX Model FB Flexible Braided Hose Assemblies includes the following items:

- Flexible Braided Hose - Inlet Nipple, ISO 7-R 1 - Sprinkler Reducer, 1/2" or 3/4" NPT, Straight or Angled - Reducer Bracket - End Brackets - Support Bar

Specify: FASTFLEX Model FB Flex-ible Braided Hose Model (specify, Ref. Figure 3), (specified) length, and (specify size, 50 or 90 mm) Bar Fixing Clamps, P/N (specify):

With 1/2 inch Straight Reducer:700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBS12507001000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS12510001200 . . . . . . . . . . . . . . . . . . . . . . . . . FBS12512001500 . . . . . . . . . . . . . . . . . . . . . . . . . FBS12515002000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS1252000

With 1/2 inch Angled Reducer:700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBA12507001000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA12510001200 . . . . . . . . . . . . . . . . . . . . . . . . . FBA12512001500 . . . . . . . . . . . . . . . . . . . . . . . . . FBA12515002000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA1252000

With 3/4 inch Straight Reducer:700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBS32507001000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS32510001200 . . . . . . . . . . . . . . . . . . . . . . . . . FBS32512001500 . . . . . . . . . . . . . . . . . . . . . . . . . FBS32515002000 . . . . . . . . . . . . . . . . . . . . . . . . . FBS3252000

With 3/4 inch Angled Reducer:700 . . . . . . . . . . . . . . . . . . . . . . . . . . FBA32507001000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA32510001200 . . . . . . . . . . . . . . . . . . . . . . . . . FBA32512001500 . . . . . . . . . . . . . . . . . . . . . . . . . FBA32515002000 . . . . . . . . . . . . . . . . . . . . . . . . . FBA3252000End BracketSpecify: FASTFLEX End Bracket, P/N FENDBRA

Gypsum End BracketSpecify: Gypsum End Bracket, P/N RBF38T

Support BarSpecify: FASTFLEX Support Bar, (specify) length, P/N (specify):700 . . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR07001000 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR10001300 . . . . . . . . . . . . . . . . . . . . . . . FSUPBAR1300Reducer BracketSpecify: FASTFLEX Reducer Bracket, (specify) size, P/N (specify):1/2" . . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA0503/4" . . . . . . . . . . . . . . . . . . . . . . . . . FREDBRA075

NOT PERMITTEDPERMITTED NOT PERMITTEDPERMITTED

FIGURE 4 FASTFLEX MODEL FB FLEXIBLE BRAIDED HOSE

INSTALLATION GUIDANCE

Page 80: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP730Page 6 of 6

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.

Page 81: rociadores std tyco

Type MV-R Reverse Action and Type MV-T Tank TopOpen NozzlesMedium Velocity

Page 1 of 6 FEBRUARY 2015 TFP809

IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and com-ponents. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely.

Worldwide Contacts www.tyco-fire.com

General DescriptionThe Tyco Type MV-R Reverse Action and Type MV-T Tank Top Nozzles are open (non-automatic) spray nozzles designed for use in water spray fixed systems for fire protection of vessels or structures containing highly flammable liquids, gases and solids having flash-points of 66˚C (150˚F) and below. They are external deflector-type nozzles that discharge against the direction of the orifice in a uniformly filled spray pattern of medium velocity water droplets over a pre-determined area.

MV-R and MV-T nozzles are effective in covering exposed vertical, horizontal, curved, and irregular shaped surfaces in a cooling spray to prevent excessive absorption of heat from an external fire and possible structural damage or spread of fire to the protected equip-ment. They also promote vapor dilution and dispersion.

The Type MV-R Reverse Action Nozzle, designed specifically to protect spheri-cal vessels and bulk storage tanks, can be installed at any angle and dis-charges a 118˚ reverse angle conical spray pattern (refer to Graph A).

The Type MV-T Tank Top Nozzle, designed specifically to protect tank tops, is installed in only an upright ori-entation and discharges a wide-angle hemispherical spray pattern (refer to Graph B).

Type MV-R and MV-T nozzles having orifice diameters smaller than 9,5 mm (0.37 in.) are factory assembled with

an orifice insert and strainer. Strainers have 3,2 mm (0.13 in.) diameter holes. Nozzles equipped with strainers range in size from MV10 to MV30 (refer to Tables A and B).

It is recommended that the end user be consulted with respect to the suitabil-ity of the materials of construction and finish for any given corrosive environ-ment. The effects of ambient tempera-ture, concentration of chemicals, and gas/chemical velocity, should be con-sidered, at a minimum, along with the corrosive nature to which the Type MV Nozzles may be exposed.

NOTICEThe Tyco Type MV-R and MV-T Nozzles described herein must be installed and maintained in compliance with this doc-ument and with the applicable stan-dards of the National Fire Protection Association, in addition to the stan-dards of any authorities having juris-diction. Failure to do so may impair the performance of these devices.

The design of individual water spray fixed systems can vary considerably, depending on the characteristics and nature of the hazard, the basic purpose of the spraying system, the configura-tion of the hazard, and wind/draft con-ditions. Because of these variations, as well as the wide range of available nozzle spray characteristics, the design of water spray fixed systems for fire protection must only be performed by experienced designers who thoroughly understand the limitations as well as capabilities of such systems.

The owner is responsible for maintain-ing their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions.

Type MV-R

Type MV-T

Page 82: rociadores std tyco

TFP809Page 2 of 6

Technical DataApprovalsMV-R, UL Listed and FM Approved (refer to Table A) MV-T, UL Listed and FM Approved (refer to Table B)

Maximum Working Pressure12,1 bar (175 psi)

Discharge Coefficient MV-R, refer to Table A MV-T, refer to Table B

Thread Connection1/2 in. NPT

Physical CharacteristicsType MV-R and MV-T Nozzles are com-prised of components constructed from: Stainless Steel, Brass & Leaded Gunmetal LG2, Titanium, Aluminium Bronze, SMO254, or Zeron 100.

*

*

*

*

WRENCHINGAREA

11,1 mm (7/16")NOMINAL MAKE-IN

47,6 mm(1-7/8")

17,5 mm(11/16")

65,1 mm(2-9/16")

55,6 mm(2-3/16")

NOZZLES HAVINGORIFICES SMALLERTHAN 9,5 mm (0.37")DIAMETER INCLUDEORIFICE INSERT ANDSTRAINER

1/2" NPT

STRAINERWITH NOMINAL

3,2 mm (1/8") DIA.HOLES

ORIFICEINSERT

FRAME

SPLITTER

DEFLECTOR

K-FACTOR ANDAPPROVAL AGENCY

INDICATED ONFRAME ARM

MV ORIFICE SIZEAND REVERSE

ACTION CODE RINDICATED ONFRAME ARM

**

*

*

WRENCHINGAREA

11,1 mm (7/16")NOMINAL MAKE-IN

47,6 mm(1-7/8")

17,5 mm(11/16")

65,1 mm(2-9/16")

55,6 mm(2-3/16")

NOZZLES HAVINGORIFICES SMALLERTHAN 9,5 mm (0.37")DIAMETER INCLUDEORIFICE INSERT ANDSTRAINER

1/2" NPT

STRAINERWITH NOMINAL

3,2 mm (1/8") DIA.HOLES

ORIFICEINSERT

FRAME

SPLITTER

DEFLECTOR

K-FACTOR ANDAPPROVAL AGENCY

INDICATED ONFRAME ARM

MV ORIFICESIZE AND

TANK TOP CODE TINDICATED ONFRAME ARM

FIGURE 1 TYPE MV-R REVERSE ACTION NOZZLE

ASSEMBLY AND NOMINAL DIMENSIONS

FIGURE 2 TYPE MV-T TANK TOP

ASSEMBLY AND NOMINAL DIMENSIONS

Page 83: rociadores std tyco

TFP809Page 3 of 6

Orifice Size

Minimum Diameter

mm (Inches)

K-factor Listings/Approvals per Material

LPM/bar1/2 GPM/psi1/2 Stainless Steel Brass Titanium Aluminium

Bronze SMO254 Zeron 100

MV10R 5,15 (0.20) 17,3 1.2

1, 2 1, 2 1, 2 1, 2 1, 2 1, 2

MV12R 5,40 (0.21) 18,7 1.3

MV15R 6,35 (0.25) 25,9 1.8

MV18R 6,80 (0.27) 28,8 2.0

MV19R 7,15 (0.28) 31,7 2.2

MV21R 7,70 (0.30) 36,0 2.5

MV25R 8,35 (0.33) 41,8 2.9

MV26R 8,80 (0.34) 44,6 3.1

MV30R 9,00 (0.35) 49,0 3.4

MV34R 9,60 (0.38) 59,0 4.1

MV47R 11,20 (0.44) 79,2 5.5

MV57R 12,60 (0.50) 100,8 7.0

NOTES:1. UL Listed2. FM Approved

Orifice Size

Minimum Diameter

mm (Inches)

K-factor Listings/Approvals per Material

LPM/bar1/2 GPM/psi1/2 Stainless Steel Brass Titanium Aluminium

Bronze SMO254 Zeron 100

MV10T 5,15 (0.20) 17,3 1.2

1 1 1 1 1 1

MV12T 5,40 (0.21) 18,7 1.3

MV15T 6,35 (0.25) 25,9 1.8

MV18T 6,80 (0.27) 28,8 2.0

MV19T 7,15 (0.28) 31,7 2.2

MV21T 7,70 (0.30) 36,0 2.5

MV25T 8,35 (0.33) 41,8 2.9

MV26T 8,80 (0.34) 44,6 3.1

MV30T 9,00 (0.35) 49,0 3.4

MV34T 9,60 (0.38) 59,0 4.1

MV47T 11,20 (0.44) 79,2 5.5

MV57T 12,60 (0.50) 100,8 7.0

NOTES:1. UL Listed

TABLE A TYPE MV-R REVERSE ACTION NOZZLE

ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND LABORATORY LISTINGS AND APPROVALS

TABLE B TYPE MV-T TANK TOP NOZZLE

ORIFICE SIZES, DISCHARGE COEFFICIENTS, MATERIALS OF CONSTRUCTION, AND LABORATORY LISTINGS AND APPROVALS

Page 84: rociadores std tyco

TFP809Page 4 of 6

Design CriteriaNozzle PlacementWhere direct impingement of water spray onto all of the protected surface is required by the authority having juris-diction, Type MV-R and MV-R Nozzles are to be spaced and directed so that their spray patterns will completely cover the protected surface with the minimum required average density.

Both MV-R and MV-T nozzles must be installed at a maximum effective dis-tance of 0,75 m (2.5 ft.) from the pro-tected surface.

Type MV-R nozzles can be oriented at any angle on pipe sprigs (refer to Figure 3).

Type MV-T nozzles must be oriented in the upright position on pipe sprigs (refer to Figure 4).

Spray PatternsSpray patterns for MV-R and MV-T nozzles are shown in Graphs A and B and apply to discharge pressures of 1,4 (20 psi). Though the Maximum Working Pressure is 12,1 bar (175 psi), discharge pressures in excess of 4,1 bar (60 psi)

will result in a decrease in coverage area since the spray patterns tend to draw inwards at higher pressures.

Main Pipeline StrainersMain pipeline strainers per NFPA 15 are required for systems utilizing nozzles with a flow path less than 9,5 mm (0.37 in.) diameter (i.e., MV10 thru MV30, refer to Table A), and for any system where the water is likely to contain obstruc-tive material.

InstallationThe Tyco Type MV-R and MV-T Nozzles must be installed in accordance with this section.

General InstructionsA leak-tight 1/2 in. NPT sprinkler joint should be obtained by applying a mini-mum-to-maximum torque of 9,5 to 19,0 Nm (7 to 14 ft.-lbs.). Higher levels of torque can distort the nozzle Inlet with consequent impairment of the nozzle.

Step 1. With pipe-thread sealant applied to the pipe threads, hand-tighten the nozzle into the nozzle fitting.

Step 2. With reference to Figures 1 and 2, apply an appropriate size adjustable Crescent wrench to the wrenching area and tighten the nozzle into the nozzle fitting.

RADIAL DISTANCE FROMNOZZLE CENTERLINE, METERS

RADIAL DISTANCE FROMNOZZLE CENTERLINE, FEET

AX

IAL

DIS

TAN

CE

FR

OM

NO

ZZ

LE D

EFL

EC

TOR

, FE

ET

AX

IAL

DIS

TAN

CE

FR

OM

NO

ZZ

LE D

EFL

EC

TOR

, ME

TER

S

0,75

0,50

0,25

1,25 1,000

0,500,75 0,25 0 1 2

2

1

430

RADIAL DISTANCE FROMNOZZLE CENTERLINE, METERS

RADIAL DISTANCE FROMNOZZLE CENTERLINE, FEET

AX

IAL

DIS

TAN

CE

FR

OM

NO

ZZ

LE D

EFL

EC

TOR

, FE

ET

AX

IAL

DIS

TAN

CE

FR

OM

NO

ZZ

LE D

EFL

EC

TOR

, ME

TER

S 0,75

0,75

1,50

0,50

0,25

1,750

1,25 1,00 0,250,50 0 21 3

2

1

4 50

GRAPH A TYPE MV-R REVERSE ACTION NOZZLE

SPRAY PROFILE

GRAPH B TYPE MV-T TANK TOP NOZZLE

SPRAY PROFILE

Page 85: rociadores std tyco

TFP809Page 5 of 6

Care and MaintenanceThe Tyco Type MV-R and MV-T Nozzles must be maintained and serviced in accordance with this section.

Before closing a fire protection system main control valve for maintenance work on the fire protection system that it con-trols, obtain permission to shut down the affected fire protection system from the proper authorities and notify all per-

sonnel who may be affected by this action.

Type MV-R and MV-T Nozzles must never be painted, plated, coated or altered in any way after leaving the factory; otherwise, the spray perfor-mance may be impaired.

Exercise care to avoid damage to the nozzles, before, during, and after instal-lation. Replace nozzles damaged by dropping, striking, wrench twist/slip-page, or the like.

Frequent visual inspections are rec-ommended to be initially performed for nozzles installed in potentially cor-rosive atmospheres to verify the integ-rity of the materials of construction and finish as they may be affected by the corrosive conditions present for a given installation. Thereafter, annual inspec-tions per NFPA 25 are required.

Water spray fixed systems to fire pro-tection service require regularly sched-uled care and maintenance by trained personnel.

In addition to inspecting nozzles for proper spray performance during water flow trip tests of the system, it is rec-ommended that nozzles be periodically inspected for broken or missing parts, loading/obstructions, or other evidence of impaired protection. The inspec-tions should be scheduled weekly or as frequently as may be necessary, and corrective action must be taken to ensure that the nozzles will perform as intended in the event of a fire.

The owner is responsible for the inspec-tion, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Asso-ciation (e.g., NFPA 25), in addition to the standards of any authorities having jurisdiction. The installing contractor or sprinkler manufacturer should be con-tacted relative to any questions.

Water spray fixed systems are rec-ommended to be inspected, tested, and maintained by a qualified Inspec-tion Service in accordance with local requirements and/or national codes.

PROTECTEDSURFACE

SUPPLYPIPE

WATERDISCHARGE

TYPE MV-RREVERSE ACTION

NOZZLE(ORIENT AT

ANY ANGLE)

PIPESPRIG

PROTECTEDSURFACE

SUPPLYPIPE

WATERDISCHARGE

PIPESPRIG

TYPE MV-TTANK TOP NOZZLE(ORIENT UPRIGHT

ONLY)

FIGURE 3 TYPE MV-R REVERSE ACTION NOZZLE

TYPICAL INSTALLATION

FIGURE 4 TYPE MV-T TANK TOP NOZZLE

TYPICAL INSTALLATION

Page 86: rociadores std tyco

GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700

TFP809Page 6 of 6

Copyright © 2015 Tyco Fire Products, LP. All rights reserved.

Limited WarrantyFor warranty terms and conditions, visit www.tyco-fire.com.

Ordering ProcedureContact your local distributor for avail-ability. When placing an order, indicate the full product name and part number (P/N).

Type MV-R Reverse Action NozzlesSpecify: Type MV-R Reverse Action Nozzle, Open, Medium Velocity, orifice size (specify), material (specify), P/N (specify from Table C).

Type MV-T Tank Top NozzlesSpecify: Type MV-T Tank Top Nozzle, Open, Medium Velocity, orifice size (specify), material (specify), P/N (specify from Table D).

Orifice Size

Material

Stainless Steel

Brass & Leaded

Gunmetal LG2

Titanium Aluminium Bronze SMO254 Zeron 100

MV10R 28480 28383 28480T 28383AB 28480SMO 28480Z

MV12R 28481 28384 28481T 28384AB 28481SMO 28481Z

MV15R 28482 28385 28482T 28385AB 28482SMO 28482Z

MV18R 28483 28386 28483T 28386AB 28483SMO 28483Z

MV19R 28484 28387 28484T 28387AB 28484SMO 28484Z

MV21R 28485 28388 28485T 28388AB 28485SMO 28485Z

MV25R 28486 28389 28486T 28389AB 28486SMO 28486Z

MV26R 28487 28390 28487T 28390AB 28487SMO 28487Z

MV30R 28488 28391 28488T 28391AB 28488SMO 28488Z

MV34R 28489 28392 28489T 28392AB 28489SMO 28489Z

MV47R 28490 28393 28490T 28393AB 28490SMO 28490Z

MV57R 28491 28394 28491T 28394AB 28491SMO 28491Z

Orifice Size

Material

Stainless Steel

Brass & Leaded

Gunmetal LG2

Titanium Aluminium Bronze SMO254 Zeron 100

MV10T 28492 28285 28492T 28285AB 28492SMO 28492Z

MV12T 28493 28281 28493T 28281AB 28493SMO 28493Z

MV15T 28494 28282 28494T 28282AB 28494SMO 28494Z

MV18T 28495 28283 28495T 28283AB 28495SMO 28495Z

MV19T 28496 28286 28496T 28286AB 28496SMO 28496Z

MV21T 28497 28287 28497T 28287AB 28497SMO 28497Z

MV25T 28498 28288 28498T 28288AB 28498SMO 28498Z

MV26T 28499 28289 28499T 28289AB 28499SMO 28499Z

MV30T 28500 28290 28500T 28290AB 28500SMO 28500Z

MV34T 28501 28291 28501T 28291AB 28501SMO 28501Z

MV47T 28502 28292 28502T 28292AB 28502SMO 28502Z

MV57T 28503 28293 28503T 28293AB 28503SMO 28503Z

TABLE C TYPE MV-R REVERSE ACTION NOZZLE

PART NUMBERS

TABLE D TYPE MV-T TANK TOP NOZZLE

PART NUMBERS