Copper Development Association

Copper DevelopmentAssociation

 K Rating of Transformerssupplying Harmonic Rich Loads

www.cda.org.uk

Page 2: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 2/33

 

Copper Development Association

 Losses in Transformers

No-load loss (‘iron loss’)

 –  energy consumed in eddy current and hysteresis loss

 –  present 100% of the time

oad losses

!esisti"e loss (‘copper loss’)

 – dependent on s#uare of load current

 – important only during peak load periods

$ddy current loss

Page 3: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 3/33

 

Copper Development Association

 Distribution transformer efficiency standards

HD 428 (538)

Source: CENELEC 

Load Losses for Distribution Transformers No-Load Losses for Distribution Transformers

RATED

POWER 

OIL-FILLED (HD42! "P TO 24#$2! DR% T%PE

(HD&'!

OIL-FILLED (HD42! "P TO 24#$2! DR% T%PE

(HD&'!

LIT A LIT ) LIT * +2#$

PRI,AR% '!

LIT A LIT ) LIT * +2#$

PRI,AR% '!

#$A W W W W W W W W

&. +/+.. +/'&. 0& N1A +. +4& +2& N1A

100 1,750 2,150 1,475 2,000 320 260 210 440

+3. 2/'&. '/+.. 2/... 2/0.. 43. '0& '.. 3+.

2&. '/2&. 4/2.. 2/0&. '/&.. 3&. &'. 42& 2.

4.. 4/3.. 3/... '/&. 4/.. '. 0&. 3+. +/+&.

3'. 14+! 3/&.. /4.. &/4.. 0/'.. +/'.. +/.'. 3. +/&..

3'. 13 3/0&. /0.. &/3.. 0/3.. +/2.. 4. .. +/'0.

+... +./&.. +'/... /&.. +./... +/0.. +/4.. +/+.. 2/...

+3.. +0/... 2./... +4/... +4/... 2/3.. 2/2.. +/0.. 2/..

2&.. 23/&.. '2/... 22/... 2+/... '/.. '/2.. 2/&.. 4/'..

Page 4: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 4/33

 

Copper Development Association

Full load losses in a 100kV !"!# transformer

12%

88%

Winding

Magnetic

Total loss $ 1%&' ( 

Page 5: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 5/33

 

Copper Development Association

Full load losses in a 100kV !"!# transformer

79%

9%

12% Resistance

Magnetic

Eddy Current

Total loss $ 1%&' ( 

Page 6: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 6/33

 

Copper Development Association

ransformers supplying harmonic loads must &eappropriately de-rated.

•  'armonic currents &eing of higher fre#uency

cause increased magnetic losses in the core and

increased eddy current and skin effect losses in

the windings.

•  riple-n harmonic currents circulate in delta

windings increasing resisti"e losses operatingtemperature and reducing effecti"e load capacity.

 )ffect of harmonics on transformers

Page 7: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 7/33 

Copper Development Association

!urrent *a+eform for a typical ,ersonal !omputer 

Page 8: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 8/33 

Copper Development Association

 Harmonic profile of a typical ,ersonal !omputer 

Page 9: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 9/33 

Copper Development Association

Typical harmonic profile " si-"pulse controller 

)i* pulse &ridge - harmonic current

0

5

10

15

20

25

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

'armonic num&er

%

Page 10: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 10/33 

Copper Development Association

 .ncreased )ddy current losses in transformers

255

+5

25ef e5 5IPP

ma6

∑==

=

where+

P eh

is the total eddy current loss

P ef   is the eddy current loss at fundamental

fre#uencyh is the harmonic order 

I h

is the !, current at harmonic h as a

percentage of rated fundamental current

ncrease in eddy current loss can &e calculated &y+

Page 11: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 11/33 

Copper Development Association

 K"Rating of Transformers

wo rating or de-rating systems for transformers+-

•  merican system esta&lished &y / and

manufacturers specifies harmonic capa&ility of

transformer - known as K factor .

•  $uropean system de"eloped &y $ defines

de-rating factor for standard transformers -

known as factor K .

Page 12: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 12/33 

Copper Development Association

 K"Rating of Transformers " / ystem

255

+5

255I7 

ma6

∑==

=

where+

h is the harmonic order 

  I h is the !, current at h in per unit of rated load current

irst calculate the 2 factor of the load according to+

Page 13: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 13/33 

Copper Development Association

or this typical 3 load the 2 factor is 11.4

(ee $$ 1100-1556 for a worked e*ample)

 K"Rating of Transformers " / ystem

Page 14: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 14/33 

Copper Development Association

Full load losses in a 100kV !"!# transformer

1%!"%

#%

Resistance

Magnetic

Eddy Current

Total loss $ 23' ( 

Page 15: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 15/33 

Copper Development Association

 K"Rating of Transformers " / ystem

Ne*t select a transformer with a higher 2 rating+standard ratings are 7 5 18 60 80 70 and 90.

N: - for non 2-rated transformers+

he 2 factor descri&es the increase in eddy current

losses not total losses.

$ddy current losses at the fundamental are normally

around 10 % of the resisti"e losses so that a load 2factor of 11.4 would re#uire de-rating to ;0 % load.

Page 16: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 16/33 

Copper Development Association

 K"Rating of Transformers " )uropean ystem

n $urope the transformer de-rating factor is calculated

according to the formulae in : ;<61 3art 7. he factor2 is gi"en &y+

&8.

2

2

+

2

+

++

   

 

 

 

   

 

 

 

   

  

++=   ∑

=

+

 N n

n

nq

 I 

 I 

n I 

 I 

e

e

 K 

e is ratio of eddy current loss (90 '=) to resisti"e loss

n is the harmonic order 

# is dependent on winding type and fre#uencytypically 1.9 to 1.;

Page 17: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 17/33 

Copper Development Association

 K"Rating of Transformers " )uropean ystem

or the same 3 load the de-rating factor is ;<%

Page 18: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 18/33 

Copper Development Association

2 actor 

0

2

4

6

8

10

12

14

16

1 2 5 10 20 41

No of /nits (pairs)

   2    1

  a  c   t  o  r

 Harmonic Di+ersity " K Factor 

Page 19: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 19/33 

Copper Development Association

 K"Rating " !alculation soft*are

Page 20: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 20/33 

Copper Development Association

Full load losses in a 100kV !"!# transformer

1%!"%

#%

Resistance

Magnetic

Eddy Current

Total loss $ 23' ( 

Page 21: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 21/33

 

Copper Development Association

!  , 

 , t temp(orking 

 f  

k °17393.190

 

×

10

2

T time Life 

 yearsT time Life

 f 

 f k 

 , 

 ,  , t 

13.02402  3.8

10

 

 

×

 

 )ffect of additional losses on life"time

*here T is *orking temperature at rated fundamental po*er4 ,  f  44 , k  is the total

 po*er and T is the rated life"time in years

Page 22: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 22/33

 

Copper Development Association

&05 load losses in a 100kV !"!# transformer

39%51%

10%

Resistance

Magnetic

Eddy Current 

Total loss $ 21'% ( 

Page 23: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 23/33

 

Copper Development Association

!  , 

 , t temp(orking 

 f  

k °11528.190

 

×

10

2

T time Life 

 yearsT time Life

 f 

 f k 

 , 

 ,  , t 

72402  5.2

10

 

 

×

 

 )ffect of additional losses on life"time

*here T is *orking temperature at rated fundamental po*er4 ,  f  44 , k  is the total

 po*er and T is the rated life"time in years

Page 24: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 24/33

 

Copper Development Association

 K"Rating " !alculation soft*are

Page 25: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 25/33

 

Copper Development Association

 K"Rating " !alculation soft*are

Page 26: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 26/33

 

Copper Development Association

Full load losses in a 100kV !"!# transformer

!1%1%

8%

Resistance

Magnetic

Eddy Current

Total loss $ 2%0' ( 

Page 27: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 27/33

 

Copper Development Association

!  , 

 , t temp(orking 

 f  

k °13955.190

 

×

10

2

T time Life 

 yearsT time Life

 f 

 f k 

 , 

 ,  , t 

34.12402  9.4

10

 

 

×

 

 )ffect of additional losses on life"time

*here T is *orking temperature at rated fundamental po*er4 ,  f  44 , k  is the total

 po*er and T is the rated life"time in years

Page 28: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 28/33

 

Copper Development Association

 K"Rating " !alculation soft*are

Page 29: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 29/33

 

Copper Development Association

 K"Rating or De"rating6

‘2-rated’ transformers are designed to supply harmonic

loads &y +

•  using stranded conductors to reduce eddy current

losses

•  &ringing secondary winding star point connections

out separately to pro"ide a 800% neutral rating

Page 30: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 30/33

 

Copper Development Association

‘>e-rating’ a standard transformer has some

disad"antages+-

•  primary o"er-current protection may &e too high

to protect the secondary and too low to sur"i"e the

in-rush current•  future increases in loading must take the de-rating

fully into account

•  it is less efficient

•  the neutral star point is likely to &e rated at only100% of the phase current

 K"Rating or De"rating6

Page 31: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 31/33

 

Copper Development Association

ransformers supplying harmonic loads must &e

appropriately de-rated.

•  'armonic currents &eing of higher fre#uency

cause increased magnetic losses in the core and

increased eddy current and skin effect losses inthe windings.

•  riple-n harmonic currents circulate in delta

windings increasing resisti"e losses operatingtemperature and reducing effecti"e load capacity.

 )ffect of harmonics on transformers

Page 32: Rom8 Harmonic Derating

7/21/2019 Rom8 Harmonic Derating

http://slidepdf.com/reader/full/rom8-harmonic-derating 32/33

 

Copper Development Association

 )ffect of triple"n harmonics in transformers

riple-n harmonic currents circulate in delta windings -

they do not propagate &ack onto the supply network.

- &ut the transformer must &e specified and rated to

cope with the additional losses.