Technical Specification Sheet Rev. 3, December, 2000 Document No. 149-359P25 Page 1 of 3 Room Relative Humidity and Relative Humidity & Temperature Sensor Description The Room Relative Humidity and Relative Humidity & Temperature Sensors monitor and transmit standard signals for humidity and temperature that can be used with a variety of building control systems including the APOGEE™ Automation System. These units are especially suited for commercial HVAC control applications. Three models are available – plain humidity sensing only, plain humidity and temperature sensing only, and humidity and temperature sensing in a full-featured version. All three models are available in either 5% accuracy, 2% accuracy, or 2% accuracy NIST (National Institute of Standards and Technology) certified versions. Both the standard 5% accuracy and 2% accuracy versions are calibrated using a NIST traceable calibration standard. The 2% accuracy NIST certified versions are also calibrated using a NIST traceable standard, however, an additional three- point humidity calibration check and one-point temperature calibration check is performed and documented on a calibration certificate included with the sensor. All units incorporate a bulk resistive polymer humidity-sensing element. The combination humidity and temperature units incorporate a 1K Ohm Platinum RTD temperature-sensing element. All units have a RJ-11 jack located on the bottom of the sensor where the EasyCal Plus Humidity Calibrator can be connected to check the operation of the humidity sensor and perform a one-point offset adjustment if necessary. Full-Featured Model The full-featured model offers a wide range of features and functionality that can be used with a variety of building control systems including the APOGEE Automation System. These features include: Liquid Crystal Display (LCD) : A two-line alphanumeric LCD allows simultaneous display of room temperature and relative humidity in degrees F or C. Relative humidity can also be displayed alone. Digital temperature set point adjustment : The sensor’s keypad allows error-free digital temperature set point adjustments in one-degree increments. Set point values momentarily display as changes are made. Override button : The flush mounted override button allows an occupant to change to an occupied control schedule during the unoccupied cycle for a predetermined time period. Display of operating mode : Graphic symbols are displayed in the LCD to indicate the controller’s operating mode. A “sun” indicates occupied mode operation and a “moon” indicates night mode operation.

Upload: vanliem

Post on 12-May-2018

406 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Room Relative Humidity and Relative Humidity & Temperature Sensor ·  · 2010-03-30Room Relative Humidity and Relative Humidity & Temperature Sensor ... (85 mm x 63 mm x 38 mm)

Technical Specification Sheet

Rev. 3, December, 2000

Document No. 149-359P25

Page 1 of 3

Room Relative Humidity and Relative Humidity & Temperature Sensor

Description

The Room Relative Humidity and Relative Humidity & Temperature Sensors monitor and transmit standard signals for humidity and temperature that can be used with a variety of building control systems including the APOGEE™ Automation System. These units are especially suited for commercial HVAC control applications. Three models are available – plain humidity sensing only, plain humidity and temperature sensing only, and humidity and temperature sensing in a full-featured version. All three models are available in either 5% accuracy, 2% accuracy, or 2% accuracy NIST (National Institute of Standards and Technology) certified versions.

Both the standard 5% accuracy and 2% accuracy versions are calibrated using a NIST traceable calibration standard. The 2% accuracy NIST certified versions are also calibrated using a NIST traceable standard, however, an additional three-point humidity calibration check and one-point temperature calibration check is performed and documented on a calibration certificate included with the sensor.

All units incorporate a bulk resistive polymer humidity-sensing element. The combination humidity and temperature units incorporate a 1K Ohm Platinum RTD temperature-sensing element.

All units have a RJ-11 jack located on the bottom of the sensor where the EasyCal Plus Humidity Calibrator can be connected to check the operation of the humidity sensor and perform a one-point offset adjustment if necessary.

Full-Featured Model

The full-featured model offers a wide range of features and functionality that can be used with a variety of building control systems including the APOGEE Automation System. These features include:

• Liquid Crystal Display (LCD): A two-line alphanumeric LCD allows simultaneous display of room temperature and relative humidity in degrees F or C. Relative humidity can also be displayed alone.

• Digital temperature set point adjustment: The sensor’s keypad allows error-free digital temperature set point adjustments in one-degree increments. Set point values momentarily display as changes are made.

• Override button: The flush mounted override button allows an occupant to change to an occupied control schedule during the unoccupied cycle for a predetermined time period.

• Display of operating mode: Graphic symbols are displayed in the LCD to indicate the controller’s operating mode. A “sun” indicates occupied mode operation and a “moon” indicates night mode operation.

Page 2: Room Relative Humidity and Relative Humidity & Temperature Sensor ·  · 2010-03-30Room Relative Humidity and Relative Humidity & Temperature Sensor ... (85 mm x 63 mm x 38 mm)

Page 2 of 3 Siemens Building Technologies, Inc.

Specifications - Humidity Element

Operating range 0 to 100% RH

Accuracy at 77°F (25°C) ±5% or ±2% RH over 20-95% RH including hysteresis, linearity, and repeatability

Operating temperature 32 to 122°F (0 to 50°C)

Temperature effect Less than 0.06% per degree F (0.11% per degree C)

Output signal-RH only units 4-20 mA DC, 0-100% linear, proportional

Output signal-RH/T units 0-10 Vdc, 0-100% linear, proportional

Calibration requirements Annually (field calibration using the EasyCal Plus)

Polarity Protection Yes

Specifications – Temperature Element (for combination humidity & temperature units only)

Operating range 32 to 122°F (0 to 50°C)

RTD Calibration Point 32°F (0 °C)

Sensing Element 1K Platinum RTD

Output Signal 0-10 Vdc, 32 to 122°F (0 to 50°C) linear, proportional

Set point adjustment range 73°F ± 10°F (23°C ± 10°C)

Calibration requirements None required

General Specifications

Installation 750 feet (229 m) max. cable length using 18 to 22 AWG twisted pair shielded cable (overall shielded cable for Full-Featured Units), NEC Class 2

Connections Screw terminals

Cover dimensions 3-11/32" H x 2-1/2" W x 1-1/2" D (85 mm x 63 mm x 38 mm)

Color Desert beige or white

Voltage requirement 18 to 35 Vdc

Ordering Information

Description Accuracy % Certification Features Product Part Number

RH only 5 Plain Sensing 544-808

RH only 2 Plain Sensing 544-811

RH only 2 Included Plain Sensing 544-812

RH/T 5 Plain Sensing 544-814

RH/T 2 Plain Sensing 544-819

RH/T 2 Included Plain Sensing 544-820

RH/T 5 Full-Featured 544-818

RH/T 2 Full-Featured 544-822

RH/T 2 Included Full-Featured 544-823

Add letter suffix to indicate desired color: A=Desert Beige; B=White (e.g., 544-808A for Desert Beige).

Page 3: Room Relative Humidity and Relative Humidity & Temperature Sensor ·  · 2010-03-30Room Relative Humidity and Relative Humidity & Temperature Sensor ... (85 mm x 63 mm x 38 mm)

Information in this document is based on specifications believed correct at the time of publication. The right is reserved to make changes as design improvements are introduced. APOGEE is a trademark of Siemens Building Technologies, Inc. ©2000 Siemens Building Technologies, Inc.

Siemens Building Technologies, Inc. Landis Division 1000 Deerfield Parkway Buffalo Grove, IL 60089-4513

Printed in the U.S.A. (origin) Page 3 of 3

Accessories Ordering Information

Description Product Part Number

EasyCal Plus Humidity Calibrator 538-897

Single Adapter Base Kit (Beige) 544-782A

Double Adapter Base Kit (White) 544-783B

Double Adapter Base Kit (Beige) 544-783A

Extender Ring Kit (White) 544-785B

Extender Ring Kit (Beige) 544-785A

Non-Conduit Rough-In Kit 544-784

Sensor Power Supply Module (for MBC/RBC applications using the RH/T units) PTX6.4SPS

AI Point Termination Module (for MBC/RBC applications using the RH/T units) PTM6.2U10

AI Point Termination Modules (for MBC/RBC applications using the RH only units) PTM6.2I420