Cooling Performance

Evaluation of Design Compare to Actual Performance

along with before & after

Page 2: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Accommodation from Two blocksEach from Three Floors

Each Floor Cooled by: 3 FCU & 1 FAHU

SKM

SKM

FA

SKM

SKM

SKM

FA

SKM

Page 3: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Rooms Connected Unit No. F1

SKM

Page 4: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Riser DiagramOne ETS RoomOne Pump RMTwo Risers One for each Block

Page 5: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Design: ETS RM Consist of 2-PHXActual: No PHX-CH. W. Direct Connected

Page 6: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Total Water Flow: 248.2 gpm (As Per Schedule)

Total Water Flow: 165.5 gpm (As Per Drawing)

Page 9: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Site Inspection

Page 10: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

& After Cleaning

Page 11: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Typical Room Size: 163 ft2

DesignCondition

180 cfm

4.74 TMBH

0.4 TR

Page 12: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Using Manometer we found that ESP is Very Low, because FAN is not selected for High Static.

ESP: External Static Pressure Drop that ensure the ability to blow air out through long duct

Page 13: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Total Water Flow: 165.5 gpm (110 TR-As Per Drawing)

Reading-2 Reading-1

23040 l/h= 84.5 gpm =49.1 TR-45% of Total Load

12120 l/h= 44.4 gpm =26.8 TR24% of Total Load

Page 14: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Wrong Selection of Indoor Units

Reasons

Less Water FlowLoose Control

Ducting & Air Distribution

Page 15: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

ال يوجد تكامل حقيقي بين

الخدمات المختلفة

MainReason

No Real Integration

between Services

Page 16: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Typical Room Size: 163 ft2Design Actual Best Practice

85 cfm180 cfm 336 cfm

Page 17: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Air Flow:Actual vs. Best Practice

Design Actual Best Practice

85 cfm180 cfm 336 cfm4.74 TMBH

0.4 TR

2.55 TMBH

0.21 TR

10.1 TMBH

0.84 TR

Page 18: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Variable vs. Constant Flow2-Way Valve 3-Way Valve

Variable Flow Constant Flow

Page 19: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Variable vs. Constant Flow2-Way Valve 3-Way Valve

Variable Flow-Open/Close Constant Flow

Page 20: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Variable vs. Constant Flow2-Way Valve Modulating CV

Open/Close Type Variable Flow

Page 21: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Variable vs. Constant FlowVariable Flow Constant Flow

Variable Frequency Drive Direct Pump

Page 22: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Chilled Water SystemCentral Controller – Main Manu

Page 23: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

FCV-Flow Control Valves 1&2-Are Total Open 31%, While Accommodation is suffering from NO COOLING

FCV-160%

Open

FCV-22%

Open

Page 26: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

What Does Implementation Look Like?

Page 27: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Enlarge FCU to AHU of 2400 cfm

Minimum Standard:2 cfm Per ft2

Design

Enlarge

Unit

180 cfm

Page 28: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Since available CH. W. Pipe: 1”Maximum Customize AHU: 2400 cfm, 11% better than existing 2166 cfm

Design Best Practice Best Possible

336 cfm180 cfm 200 cfm

Page 29: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Since available CH. W. Pipe: 1”Maximum Customize AHU can deliver: 60.1 TMBH of Cooling, 5.6% better than 56.9 TMBH

Design Best Practice Best Possible

336 cfm180 cfm 200 cfm4.74 TMBH

0.4 TR

10.1 TMBH

0.84 TR

0.5 TMBH

0.60 TR

Page 30: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

ecoCool AHU equipped with two Blowers powered by Stronger Motors driven by adjustable Belts.

Increase ESP by Empower FAN Motors

Page 31: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

The New AHU from ecoCool is Dynamically Balanced Unit that over come both main reasons of less cooling:

• Less Chilled Water Flow.• More Air Flow

Page 32: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Total Water Flow: 165.5 gpm (110 TR-As Per Drawing)

Reading-1

12120 l/h= 44.4 gpm =26.8 TR24% of Total Load

Reading-3

23040 l/h= 148 gpm =89.9 TR-90% of Total Load

Page 33: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

By shifting Unit to corridor in order to reduce duct and the negative effect on Air Flow.

Reduce Long Duct

ecoCool

Page 34: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

1) Connect VFD.2) Add new control to signal VFD.3) Utilize PICV benefits4) Shift the Make-up Pressurization Pump.

Convert to Dynamically Control Ch. W. Sys.

Page 35: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

1d

Now VFD are disconnected and Pumps are connected directly

Page 36: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

1d

Connect & Re-commission VFD to Control Variable CH. W. Flow

Page 37: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

VFD Activated for Chilled Water Pumps

Page 38: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Now VFD Vary the Chilled Water

according to actual demand

Page 39: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

2d

Exist signal to VFD from ETS

* Reducing CH. W. Flow inside the Building while trying to Maintain Delta-T .* Casing less cooling effect.* Reducing emiCool BTU-Meter-Bill.

Page 40: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

2d

Add new control to signal VFD.

* Right Control Method.* With Right Signal.* At Right Location.

Page 41: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

14

5.5

Shift Signal from before Load/BLD to after ensuring filling all indoor units

ETSRoom

Page 42: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Correct Signal Location to Control

VFD

Page 43: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

After Correct Signal and Activate VFD, water is flowing

better and Cooling Improved in Air

Temperature

Page 44: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

3d

Now CV-Open and Close Valve that Flod the Cooling Coil with more chilled water

Page 45: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

3d

Utilize PICV/PICCV benefits

Page 46: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

4d

Make-up Pressurization Pump @ GF

Pressurization Make-up Pump located at GF-Pumps Room and can’t function as per design.

Page 47: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

4d

Shift the Make-up Pressurization Pump Must shift the

Make-up Pressurization Pump to maintain the minimum pressure at the weakest point.

Shifted to the Roof

Page 48: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

14

5.5

Pressurization Pump is down: Not Functioning: Must Shift to Weakest Point

Page 49: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

14

5.5

Control Signal: Must ensure the right flow @ weakest pointEV

Page 50: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Static Pressure is Monitored and Maintained at Fixed Level

Fixed Static

Pressure

Page 51: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Dynamic Pressure is Monitored and Maintained at Fixed Level

Self Balancing Dynamic Pressure

Page 52: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Our Solution is Molded in One Unit

Cool

Dynamically Balanced Solution

Page 53: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Replaced all the 24 AHUs with ecoCool

Activate Variable PumpsFix the Right Flow Signal

Replace 6 FAHUs

الخطوة

التالية

Shift Press. Pump to weakest point

Page 54: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

ETS Control System is maintaining

around 6.2’C

all the time

Reading:09/5/2015

Reading:21/3/2015

Page 55: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

But Chilled Water Flow in

Ltr/Hour (l/h)has been increased

by: 330%after correction

Reading:09/5/2015

Reading:21/3/2015

Page 56: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Most important that Cooling Capacity in

KWcdelivered the

building has been increased

by: 260%

Reading:12/5/2015

Reading:21/3/2015

Page 57: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Supply Air Temp.SAT

Page 58: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Room Temp.RMT

Page 59: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Corridor Zone Temp.

Page 60: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Some Temperature Readings in many

roomShowing

the improvement

Reading on: 25/07/2015

Page 61: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Low Static Pressure FCUvs.

High Static Pressure AHU

Page 62: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco
Page 63: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Convert to Dynamically Control Ch. W. Sys1) Connect VFD.2) Add new control to signal VFD.3) Utilize PICV benefits4) Shift Make-up Pressurization Pump.

Reduce Long

Duct by fixing

AHU at Corridor

when possible

Increase ESP

by Empower FAN Motors

From 0.75 kw to 1-kw

Enlarge FCU to AHU from

2230 to 2400 cfm

Summary Of Work Done

Page 64: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

برمجة وتكامل حقيقي بين

أجهزة التكييف و منظومة التحكم

الذكية من إيميكوول

Make Real Integration

between you’re A/C Units and emiCool Smart

Controller

الخطوة التاليةNext Step

Page 65: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

Also Pumps Status has been connected to

Central Control System

Reading:25/6/2015

Reading:21/3/2015

Page 66: Rp 15081208 design and cooling performance evaluation  @ masharie accommodation-by getco

To benefit from our Integration Services:Consultancies.Corrections.