rp 15081208 design and cooling performance evaluation @ masharie accommodation-by getco
TRANSCRIPT
Cooling Performance
Evaluation of Design Compare to Actual Performance
along with before & after
Accommodation from Two blocksEach from Three Floors
Each Floor Cooled by: 3 FCU & 1 FAHU
SKM
SKM
FA
SKM
SKM
SKM
FA
SKM
Rooms Connected Unit No. F1
SKM
Riser DiagramOne ETS RoomOne Pump RMTwo Risers One for each Block
Design: ETS RM Consist of 2-PHXActual: No PHX-CH. W. Direct Connected
Total Water Flow: 248.2 gpm (As Per Schedule)
Total Water Flow: 165.5 gpm (As Per Drawing)
Temperature Air Flow Water Flow
Observation
27-29’C
85 cfm0.52 cfm/ft2
Water flow is LOW
Observation
Site Inspection
& After Cleaning
Typical Room Size: 163 ft2
DesignCondition
180 cfm
4.74 TMBH
0.4 TR
Using Manometer we found that ESP is Very Low, because FAN is not selected for High Static.
ESP: External Static Pressure Drop that ensure the ability to blow air out through long duct
Total Water Flow: 165.5 gpm (110 TR-As Per Drawing)
Reading-2 Reading-1
23040 l/h= 84.5 gpm =49.1 TR-45% of Total Load
12120 l/h= 44.4 gpm =26.8 TR24% of Total Load
Wrong Selection of Indoor Units
Reasons
Less Water FlowLoose Control
Ducting & Air Distribution
ال يوجد تكامل حقيقي بين
الخدمات المختلفة
MainReason
No Real Integration
between Services
Typical Room Size: 163 ft2Design Actual Best Practice
85 cfm180 cfm 336 cfm
Air Flow:Actual vs. Best Practice
Design Actual Best Practice
85 cfm180 cfm 336 cfm4.74 TMBH
0.4 TR
2.55 TMBH
0.21 TR
10.1 TMBH
0.84 TR
Variable vs. Constant Flow2-Way Valve 3-Way Valve
Variable Flow Constant Flow
Variable vs. Constant Flow2-Way Valve 3-Way Valve
Variable Flow-Open/Close Constant Flow
Variable vs. Constant Flow2-Way Valve Modulating CV
Open/Close Type Variable Flow
Variable vs. Constant FlowVariable Flow Constant Flow
Variable Frequency Drive Direct Pump
Chilled Water SystemCentral Controller – Main Manu
FCV-Flow Control Valves 1&2-Are Total Open 31%, While Accommodation is suffering from NO COOLING
FCV-160%
Open
FCV-22%
Open
First we have to Understand how DC Plant Maintaining CH. W. Delta-T and evaluate A/C Sys. Components, also the Logic of HVAC Controller.”
“” 2
5
What Does Implementation Look Like?
Enlarge FCU to AHU of 2400 cfm
Minimum Standard:2 cfm Per ft2
Design
Enlarge
Unit
180 cfm
Since available CH. W. Pipe: 1”Maximum Customize AHU: 2400 cfm, 11% better than existing 2166 cfm
Design Best Practice Best Possible
336 cfm180 cfm 200 cfm
Since available CH. W. Pipe: 1”Maximum Customize AHU can deliver: 60.1 TMBH of Cooling, 5.6% better than 56.9 TMBH
Design Best Practice Best Possible
336 cfm180 cfm 200 cfm4.74 TMBH
0.4 TR
10.1 TMBH
0.84 TR
0.5 TMBH
0.60 TR
ecoCool AHU equipped with two Blowers powered by Stronger Motors driven by adjustable Belts.
Increase ESP by Empower FAN Motors
The New AHU from ecoCool is Dynamically Balanced Unit that over come both main reasons of less cooling:
• Less Chilled Water Flow.• More Air Flow
Total Water Flow: 165.5 gpm (110 TR-As Per Drawing)
Reading-1
12120 l/h= 44.4 gpm =26.8 TR24% of Total Load
Reading-3
23040 l/h= 148 gpm =89.9 TR-90% of Total Load
By shifting Unit to corridor in order to reduce duct and the negative effect on Air Flow.
Reduce Long Duct
ecoCool
1) Connect VFD.2) Add new control to signal VFD.3) Utilize PICV benefits4) Shift the Make-up Pressurization Pump.
Convert to Dynamically Control Ch. W. Sys.
1d
Now VFD are disconnected and Pumps are connected directly
1d
Connect & Re-commission VFD to Control Variable CH. W. Flow
VFD Activated for Chilled Water Pumps
Now VFD Vary the Chilled Water
according to actual demand
2d
Exist signal to VFD from ETS
* Reducing CH. W. Flow inside the Building while trying to Maintain Delta-T .* Casing less cooling effect.* Reducing emiCool BTU-Meter-Bill.
2d
Add new control to signal VFD.
* Right Control Method.* With Right Signal.* At Right Location.
14
5.5
Shift Signal from before Load/BLD to after ensuring filling all indoor units
ETSRoom
Correct Signal Location to Control
VFD
After Correct Signal and Activate VFD, water is flowing
better and Cooling Improved in Air
Temperature
3d
Now CV-Open and Close Valve that Flod the Cooling Coil with more chilled water
3d
Utilize PICV/PICCV benefits
4d
Make-up Pressurization Pump @ GF
Pressurization Make-up Pump located at GF-Pumps Room and can’t function as per design.
4d
Shift the Make-up Pressurization Pump Must shift the
Make-up Pressurization Pump to maintain the minimum pressure at the weakest point.
Shifted to the Roof
14
5.5
Pressurization Pump is down: Not Functioning: Must Shift to Weakest Point
14
5.5
Control Signal: Must ensure the right flow @ weakest pointEV
Static Pressure is Monitored and Maintained at Fixed Level
Fixed Static
Pressure
Dynamic Pressure is Monitored and Maintained at Fixed Level
Self Balancing Dynamic Pressure
Our Solution is Molded in One Unit
Cool
Dynamically Balanced Solution
Replaced all the 24 AHUs with ecoCool
Activate Variable PumpsFix the Right Flow Signal
Replace 6 FAHUs
الخطوة
التالية
Shift Press. Pump to weakest point
ETS Control System is maintaining
around 6.2’C
all the time
Reading:09/5/2015
Reading:21/3/2015
But Chilled Water Flow in
Ltr/Hour (l/h)has been increased
by: 330%after correction
Reading:09/5/2015
Reading:21/3/2015
Most important that Cooling Capacity in
KWcdelivered the
building has been increased
by: 260%
Reading:12/5/2015
Reading:21/3/2015
Supply Air Temp.SAT
Room Temp.RMT
Corridor Zone Temp.
Some Temperature Readings in many
roomShowing
the improvement
Reading on: 25/07/2015
Low Static Pressure FCUvs.
High Static Pressure AHU
Convert to Dynamically Control Ch. W. Sys1) Connect VFD.2) Add new control to signal VFD.3) Utilize PICV benefits4) Shift Make-up Pressurization Pump.
Reduce Long
Duct by fixing
AHU at Corridor
when possible
Increase ESP
by Empower FAN Motors
From 0.75 kw to 1-kw
Enlarge FCU to AHU from
2230 to 2400 cfm
Summary Of Work Done
برمجة وتكامل حقيقي بين
أجهزة التكييف و منظومة التحكم
الذكية من إيميكوول
Make Real Integration
between you’re A/C Units and emiCool Smart
Controller
الخطوة التاليةNext Step
Also Pumps Status has been connected to
Central Control System
Reading:25/6/2015
Reading:21/3/2015
To benefit from our Integration Services:Consultancies.Corrections.