Chillers Customer benefits Industry leading efficienties thanks to: • Falling film evaporator: superior performances with low refrigerant charge • New Trane control for optimal system reliability and human interface • Trane helical-rotary compressor - designed to perform, built to last • Optional Trane Adaptive Frequency TM Drive (AFD) for part load efficiency enhancement Main features • 4 efficiency levels: SE, HE, XE and new HSE fitted with Trane AFD with enhanced part load (ESEER) efficiencies • Low-speed, direct-drive semi-hermetic helical rotary compressor featuring only 3 moving parts, suction-gas- cooled motor • Fully modulating load control (15-100%) • Compact physical footprint - fits through standard double-width doors • Bolt-together construction for easy unit disassembly • Factory-mounted star-delta starter panel • Simplified piping - the only piping required is for the evaporator and condenser grooved pipe connections • Single power connection - reduced wiring costs Options • Insulation on evaporator, water boxes, suction line, motor housing • Fused or non-fused power disconnect switch • Under/over voltage protection Accessories • Outside air temperature sensor • Condenser valves Control • Ultimate control: UC800 • Easy to read 7-inch color touchscreen display • Industry leading algorithms • Open protocol design • Adaptive control • Feedforward adaptive control • Softloading (HSE) • Rapid Restart • SmartCom interface: LonTalk®, BACnet®, Modbus® communication interfaces • Energy metering RTHD evo Water-cooled packaged helical-rotary chiller Series R™ This description may not include all options and accessories available. For full technical information, visit www.trane.com/litweb or contact your local sales office.

Upload: vudiep

Post on 12-Feb-2019

221 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RTHDevo Water-cooled packaged helical-rotary chiller Series R™ · EER (1) 5.16 5.03 5.03 5.18 5.06 4.81 ESEER (1) 5.41 5.36 5.09 5.41 5.31 4.93 Eurovent class A B B A A B Sound

Chille

rs

Customer benefits

Industry leading efficienties thanks to:

• Falling film evaporator: superior performances with low

refrigerant charge

• New Trane control for optimal system reliability and

human interface

• Trane helical-rotary compressor - designed to perform,

built to last

• Optional Trane Adaptive FrequencyTM Drive (AFD) for part

load efficiency enhancement

Main features

• 4 efficiency levels: SE, HE, XE and new HSE fitted with

Trane AFD with enhanced part load (ESEER) efficiencies

• Low-speed, direct-drive semi-hermetic helical rotary

compressor featuring only 3 moving parts, suction-gas-

cooled motor

• Fully modulating load control (15-100%)

• Compact physical footprint - fits through standard

double-width doors

• Bolt-together construction for easy unit disassembly

• Factory-mounted star-delta starter panel

• Simplified piping - the only piping required is for the

evaporator and condenser grooved pipe connections

• Single power connection - reduced wiring costs

Options

• Insulation on evaporator, water boxes, suction line,

motor housing

• Fused or non-fused power disconnect switch

• Under/over voltage protection

Accessories

• Outside air temperature sensor

• Condenser valves

Control

• Ultimate control: UC800

• Easy to read 7-inch color touchscreen display

• Industry leading algorithms

• Open protocol design

• Adaptive control

• Feedforward adaptive control

• Softloading (HSE)

• Rapid Restart

• SmartCom interface: LonTalk®, BACnet®, Modbus®

communication interfaces

• Energy metering

RTHDevo

Water-cooled packaged

helical-rotary chiller

Series R™

This description may not include all options and accessories available. For full technical information, visit www.trane.com/litweb or contact your local sales office.

Page 2: RTHDevo Water-cooled packaged helical-rotary chiller Series R™ · EER (1) 5.16 5.03 5.03 5.18 5.06 4.81 ESEER (1) 5.41 5.36 5.09 5.41 5.31 4.93 Eurovent class A B B A A B Sound

Chille

rs

Condenser leaving water temperature (min./max.) (°C) 20 / +50

Evaporator leaving water temperature range (min./max.) (°C) -12 / +18

Power supply (V/Ph/Hz) 400/3/50

(1) At Eurovent conditions: evaporator 12/7°C and 0,0176m2K/kW, condenser 30/35°C and 0,44m2K/kW according to EN 14511

(2) At full load according to ISO9614

RTHD Standard Efficiency 225 250 300 325 350 375

Cooling capacity (1) (kW) 769 886 1050 1145 1216 1342

Total power input (1) (kW) 149 176 209 221 240 279

EER (1) 5.16 5.03 5.03 5.18 5.06 4.81

ESEER (1) 5.41 5.36 5.09 5.41 5.31 4.93

Eurovent class A B B A A B

Sound power level (2) (dBA) 98 98 97 97 97 101

Number of circuit(s) 1 1 1 1 1 1

Number of compressors per circuit 1 1 1 1 1 1

Dimensions and weights (operating)

Length (mm) 3290 3290 3290 3290 3290 3290

Width (mm) 1600 1600 1600 1600 1600 1600

Height (mm) 1940 1940 1940 1940 1940 1940

Clearance A (mm) 2510 2510 2510 2510 2510 2510

Clearance B (mm) 1000 1000 1000 1000 1000 1000

Weight (kg) 5891 6833 6335 6522 6553 6655

Electrical data

Maximum amps (A) 349 349 455 455 455 488

Start-up amps (A) 480 480 748 748 748 748

RTHD High Efficiency 150 175 225 250 300 350 375 400

Cooling capacity (1) (kW) 545 595 778 896 1074 1195 1278 1411

Total power input (1) (kW) 99 109 145 170 198 212 228 266

EER (1) 5.49 5.44 5.37 5.26 5.42 5.65 5.60 5.31

ESEER (1) 5.79 5.88 5.68 5.66 5.63 5.88 5.78 5.38

Eurovent class A A A A A A A A

Sound power level (2) (dBA) 98 98 98 98 97 97 97 101

Number of circuit(s) 1 1 1 1 1 1 1 1

Number of compressors per circuit 1 1 1 1 1 1 1 1

Dimensions and weights (operating)

Length (mm) 3170 3170 3290 3290 3290 3690 3690 3690

Width (mm) 1600 1600 1600 1600 1600 1600 1600 1600

Height (mm) 1850 1850 1940 1940 1940 1940 1940 1940

Clearance A (mm) 2530 2530 2510 2510 2510 2970 2970 2970

Clearance B (mm) 1000 1000 1000 1000 1000 1000 1000 1000

Weight (kg) 4361 4361 6030 6030 6612 7558 7589 7767

Electrical data

Maximum amps (A) 233 233 349 349 455 455 455 488

Start-up amps (A) 412 412 480 480 748 748 748 748

Page 3: RTHDevo Water-cooled packaged helical-rotary chiller Series R™ · EER (1) 5.16 5.03 5.03 5.18 5.06 4.81 ESEER (1) 5.41 5.36 5.09 5.41 5.31 4.93 Eurovent class A B B A A B Sound

Chille

rs

RTHD eXtra High Efficiency 150 175 225 275 325 350 375 425

Cooling capacity (1) (kW) 559 614 797 937 1119 1203 1294 1453

Total power input (1) (kW) 98 108 140 160 188 205 218 253

EER (1) 5.69 5.69 5.68 5.86 5.94 5.88 5.94 5.74

ESEER (1) 5.95 6.09 6.09 6.27 6.16 6.21 6.21 5.91

Eurovent class A A A A A A A A

Sound power level (2) (dBA) 98 98 98 98 97 97 97 101

Number of circuit(s) 1 1 1 1 1 1 1 1

Number of compressors per circuit 1 1 1 1 1 1 1 1

Dimensions and weights (operating)

Length (mm) 3640 3640 3290 3670 3850 3850 3850 3850

Width (mm) 1600 1600 1600 1600 1800 1800 1800 1800

Height (mm) 1850 1850 1940 1940 2035 2040 2040 2040

Clearance A (mm) 2990 2990 2510 2980 3130 3130 3130 3130

Clearance B (mm) 1000 1000 1000 1000 1000 1000 1000 1000

Weight (kg) 4756 4756 6355 6833 8951 9196 9384 9741

Electrical data

Maximum amps (A) 233 233 349 349 455 455 455 488

Start-up amps (A) 412 412 480 480 748 748 748 748

RTHD High Seasonal Efficiency 150 175 225 275 325 350 375 425

Cooling capacity (1) (kW) 559 614 797 937 1119 1203 1294 1453

Total power input (1) (kW) 102 111 145 165 195 211 225 261

EER (1) 5.51 5.51 5.50 5.68 5.75 5.69 5.75 5.56

ESEER (1) 7.14 7.20 7.32 7.61 7.71 7.52 7.94 7.83

Eurovent class A A A A A A A A

Sound power level (2) (dBA) 98 98 98 98 97 97 97 101

Number of circuit(s) 1 1 1 1 1 1 1 1

Number of compressors per circuit 1 1 1 1 1 1 1 1

Dimensions and weights (operating)

Length (mm) 3640 3640 3290 3670 3850 3850 3850 3850

Width (mm) 1850 1850 1970 1970 2040 2040 2040 2040

Height (mm) 1690 1690 1810 1810 2000 2000 2000 2000

Clearance A (mm) 2990 2990 2510 2980 3130 3130 3130 3130

Clearance B (mm) 1000 1000 1000 1000 1000 1000 1000 1000

Weight (kg) 4860 4860 6534 7012 9139 9384 9572 9929

Electrical data

Maximum amps (A) 218 218 314 314 421 421 421 452

Start-up amps (A) 11 11 16 16 21 21 21 23

Condenser leaving water temperature (min./max.) (°C) 20 / +50

Evaporator leaving water temperature range (min./max.) (°C) -12 / +18

Power supply (V/Ph/Hz) 400/3/50

(1) At Eurovent conditions: evaporator 12/7°C and 0,0176m2K/kW, condenser 30/35°C and 0,44m2K/kW according to EN 14511

(2) At full load according to ISO9614