rural electric cooperativecorporation a …psc.ky.gov/pscscf/post case referenced...
TRANSCRIPT
April 25, 2016
RURAL ELECTRIC COOPERATIVE CORPORATION
A Touchstone Energy'^ Cooperative
Public Service Commission
P.O. Box 615
211 Sower Boulevard
Frankfort, Kentucky 40602-0615
RE: Administrative Case No. 2011-00450
RECEIVED
APR 2 S 2016
Public ServiceCommission
Enclosed is a paper copy of the 2015 electric distribution utility annual reliability report for Nolin RECC,as well as a copy of Nolin RECC's vegetation management program. Additionally, the enclosed flash diskcontains electronic copies of these files.
Please let us know if there are any questions or concerns.
Regards,
Devon Woosley ^System Engineer/ SCADA Administrator
Enclosures
UTILITY NAME:
REPORT PREPARED BY:
E-MAIL ADDRESS OF
PREPARER:
PHONE NUMBER OF
PREPARER:
CALENDAR YEAR OF
REPORT:
TMED:
FIRST DATE USED TO
DETERMINETMED:
LAST DATE USED TO
DETERMINETMED:
NUMBER OF MED IN
REPORT YEAR:
Kentucky Public Service Commission
Electric Distribution Utility Annual Reliability Report
SECTION 1: CONTACT INFORMATION
Nolin RECC
GDS Associates, Inc. D/B/A Hi-Line Engineering
770-425-8100
SECTION 2: REPORTING YEAR
2015
SECTION 3: MAJOR EVENT DAYS (MED)
9.34
1/1/2010
12/31/2014
NOTE: Per IEEE TMED should be calculated using the daily SAID! values for the five prior years. If five
years of data are not available, then utilities should use what is available until five years accumulated.
SECTION 4: SYSTEM RELIABILITY INFORMATION AND RESULTS
TOTAL
CUSTOMERS:34,658
System-wide Information
TOTAL CIRCUITS: 82
Notes:
5-YEAR AVERAGE (2010-2014)
SAIDI: 84.491
SAIFI: .906
5-YEAR AVERAGE (2010-2014)
SAIDI: 118.712SAIFI: 1.039
Excluding MED
REPORTING YEAR
SAIDI: 110.802
SAIFI: 1.118
Including MED
REPORTING YEAR
SAIDI: 110.802
SAIFI: 1.118
1) All duration indices (SAIDI) are to be reported in units of minutes.
2) Reports are due on the first business day of May of each year.
3) Reports cover the calendar year ending in the December before the reports are due.
4) IEEE 1366 (latest version) is used to define SAIDI, SAIFI, and TMED.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT#!:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
COLESBURG-1
COLESBURG 1
HARDIN - HALL & BARDSTOWN RD. - YOUNGER CREEK
COLESBURG-1
ELIZABETHTOWN, KY - YOUNGERS CREEK RD./ DEVERS RD.
41.11
398
January-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.10%
2.35%
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 50.02%
PUBLIC ACCIDENTS, OTHER 10.52%
SMALL ANIMALS OR BIRDS 0.00%
TREES 33.68%
WIND, HIGH WIND 0.00%
WEATHER 3.34%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUITS YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
75.36
249.50
0.79
2.70
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Review ROWconditions and vegetation management cycle.
SECTION 5: CIRCUIT REPORTING
fClRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #2:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
COLESBURG-2
COLESBURG 1
HARDIN - HALL & BARDSTOWN RD. - YOUNGER CREEK
COLESBURG-2
ELIZABETHTOWN, KY - BARDSTOWN RD./ MOUNTAIN VIEW
ESTATES RD.
13.35
187
January-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
0.00%
8. LISTOFOUTAGE(S);
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 99.22%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.78%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAID!):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BETAKEN
10.67
125.78
0.20
1.01
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #3:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
{COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
COLESBURG-4
COLESBURG 1
HARDIN - HALL & BARDSTOWN RD. - YOUNGER CREEK
COLESBURG-4
ELIZABETHTOWN, KY- LOWER COLESBURG RD/BATTLE
TRAINING RD, HAPPY HOLLOW RD
36.8
213
January-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
1.99%
0.12%
1.92%
8. USTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 70.37%
PUBLIC ACCIDENTS, OTHER 0.54%
SMALLANIMALS OR BIRDS 0.00%
TREES 20.68%
WIND, HIGH WIND 0.00%
WEATHER 4.38%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BETAKEN
43.21
177.36
0.62
2.08
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability Issues.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #4:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN);
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GEN ERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
ETOWN 1-4
ETOWN 1 2
HARDIN - WOODLAND DR. - E-TOWN
ETOWN 1-4
ELIZABETHTOWN, KY - E. NALLS RD.
2.25
52
May-14
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 100.00%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.Q0%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
8.98
45.00
0.34
1.00
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #5:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
ETOWN 1-5
ETOWN 1 2
HARDIN - WOODLAND DR. - E-TOWN
ETOWN 1-5
ELIZABETHTOWN, KY - BYPASS/ BANKVIEW RD./ DIXIE RD./FREEMAN LAKE PARK RD.
11.54
527
January-14
OUTAGE MINUTES (%OFTOTAL OUTAGE MINUTES):
0.00%
17.71%
0.12%
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 82.12%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.05%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
87.70
54.80
0.62
1.14
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #6:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
ETOWN 2-3
ETOWN 2 20
HARDIN - WOODLAND DR. - E-TOWN
ETOWN 2-3
ELIZABETHTOWN, KY - DEERFIELD HILLS RD./ RINEYVILLE RD.
7.34
298
JuIy-12
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
99.80%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.13%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
0.07%
0.00%
15.11
99.92
0.53
1.11
Feeder Inspection to identify equipment for maintenance
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDIAND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #42:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YV):
ETOWN 2-5
ETOWN 2 20
HARDIN - WOODLAND DR. - E-TOWN
ETOWN 2-5
ELIZABETHTOWN, KY - RING RD./ PEACH ORCHARD RD.
20.28
747
December-13
OUTAGE MINUTES {% OFTOTAL OUTAGE MINUTES):
0.00%
0.10%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
98.39%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BETAKEN
1.51%
0.00%
No History
74.76
No History
1.03
Identify new surge arrestor placement opportunities. Reviewovervoltage protection.
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEARAVERAGEl
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT#?:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT;
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
SOUTH BOUNDARY-3
SOUTH BOUNDARY 14
HARDIN - HWY 313 - RADCLIFF
SOUTH BOUNDARY-3
RADCLIFF, KY - SOUTH BOUNDARY RD (N. OF SUB.) / AUSTIN DR/ SHELBY AVE
22.55
768
April-15
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
31.96%
44.45%
0.32%
22.37%
0.00%
PUBLIC ACCIDENTS, OTHER 0.76%
SMALLANIMALS OR BIRDS 0.14%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
36.68
31.55
0.64
1.16
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
Feeder inspection to identify equipment for maintenance.
Nolin RECC to monitor contractor performance to insureoutage contribution issues have been corrected.
10
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIR EXCEEDING 5 YEAR AVERAGEl
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #8:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
SOUTH BOUNDARY-4
SOUTH BOUNDARY 14
HARDIN - HWY 313 - RADCLIFF
SOUTH BOUNDARY-4
RADCLIFF, KY - SOUTH BOUNDARY RD (N. OF SUB.)/ 7thARMORED DIVISION RD
3.02
239
Aprll-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
94.08% PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 1.44%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI);
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
3.83%
0.00%
0.00%
0.64%
20.56
19.64
0.30
0.98
Nolin RECC to monitor contractor performance to insure
outage contribution issues have been corrected.
11
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #9:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUITS YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
SOUTH BOUNDARY-5
SOUTH BOUNDARY 14
HARDIN - HWY 313 - RADCLIFF
SOUTH BOUNDARY-5
ELIZABETHTOWN, KY - BATTLE TRAINING RD.
13.98
242
January-15
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
49.65%
0.02%
2.12%
0.00%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.00%
TREES 47.66%
WIND, HIGH WIND Q.00%
WEATHER 0.55%
51.62
140.16
0.68
2.62
Feeder inspection to identify equipment for maintenance.Circuit was trimmed recently to remedy tree related outages.Nolin RECC to monitor this feeder to make sure ROW Issues
have been corrected.
12
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFl EXCEEDING 5 YEAR AVERAGEl
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #10: GLENDALE-1
GLENDALE3
HARDIN - E. GLENDALE HODGENVILLE RD - GLENDALE
GLENDALE-1
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YV):
GLENDALE, KY - W. GLENDALE HODGENVILLE RD / MUD SPLASH
RD/ANDOVER RD
9.54
194
November-14
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.41%
0.00%
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 51.98%
PUBLIC ACCIDENTS, OTHER 47.62%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
19.48
78.49
0.26
1.99
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Feeder inspectionwill identify areas for correction.
13
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #11:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
GLENDALE-2
GLENDALE3
HARDIN - E. GLENDALE HODGENVILLE RD - GLENDALE
GLENDALE-2
GLENDALE, KY - SPORTSMAN LAKE RD./ OVERALL PHILLIPS RD.
42.2
858
November-14
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
7.55%
1.69%
4.07%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 53.47%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.25%
TREES 32.97%
WIND, HIGH WIND 0.00%
WEATHER 0.01%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
84.35
76.31
0.93
1.26
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Review ROWconditions and vegetation management cycle.
14
SECTION 5: CIRCUIT REPORTING
fClRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE)
fCIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #12:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
GLENDALE-4
6LENDALE3
HARDIN - E. GLENDALE HODGENVILLE RD - GLENDALE
GLENDALE-4
GLENDALE, KY - ROUNDTOP RD./ LICOLN PKWY
54.31
474
February-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
10.76%
PUBLIC ACCIDENTS, OTHER 0.23%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
3.87%
0.51%
84.63%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
66.77
48.21
0.79
1.14
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
15
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #13:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
8. USTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI);
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
GLENDALE-5
GLENDALE3
HARDIN - E. GLENDALE HODGENVILLE RD - GLENDALE
GLENDALE-5
SONORA, KY - HWY 31W (SOUTH)/ NOLIN RD / SONORA NOUNRD
29.43
204
January-15
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
2.21%
16.63%
0.00%
68.45%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 8.17%
TREES 4.54%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
61.99
59.61
0.66
1.25
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
16
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
fCIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #14:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
8. LiSTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
HODGENVILLE-4
H0DGENVILLE4
LARUE - HWY 31E (NEAR WADDELL RD)- HODGENVILLE
HODGENVlLLE-4
HODGENVILLE, KY - OLD ELIZABETHTOWN RD./ CARTER
BROTHERS RD.
26.8
341
January-lS
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
1.25%
1.21%
0.65%
0.00%
PUBLIC ACCIDENTS, OTHER 96.90%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
31.79
48.16
0.57
0.33
Feeder inspection will identify areas for correction
17
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #15:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
HODGENVILLE-5
H0DGENVILLE4
LARUE - HWY 31E (NEAR WADDELL RD)- HODGENVILLE
HODGENVILLE-5
HODGENVILLE, KY - CARTER BROTHERS RD./ DAN DUNN RD.
61.58
437
September-14
OUTAGE MINUTES (%OFTOTAL OUTAGE MINUTES):
0.00%
0.00%
14.35%
0.28%
0.00%
PUBLIC ACCIDENTS, OTHER 44.70%
SMALLANIMALS OR BIRDS 0.00%
TREES 40.67%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
35.20
43.55
0.43
0.33
Feeder inspection will identify areas for correction. ReviewROW conditions and vegetation management cycle.
18
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #16:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFi):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BETAKEN
KARGLE-3
KARGLE 15
HARDIN - AUTO GLASS DR - ELIZABETHTOWN
KARGLE-3
ELIZABETHTOWN, KY - AUTO GLASS DR -AT AGC Automotive
Americas
0.01
N/A
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
0.00%
0.00%
PUBLIC ACCIDENTS, OTHER 100.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
No History
582.00
No History
1.00
Outage cause resolved with impacted customer on thisdedicated feeder.
19
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #17:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-VY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUITS YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
LOGSDON-3
LOGSDON 18
HARDIN- HILL ST (NEAR ETHAN CT) - VINE GROVE
LOGSDON-3
RADCLIFF, KY-W. CROCUS DR/ ELM RD/ N LOGSDON PKWY
15.02
1005
January-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
35.57%
5.86%
20.99%
0.00%
0.00%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALSOR BIRDS 25.22%
TREES 12.35%
WIND, HIGH WIND Q.00%
WEATHER 0.00%
25.48
28.25
0.32
0.65
Nolln RECC to monitor contractor performance to Insureoutage contribution Issues have been corrected. FeederInspection will Identify areas to mitigate animal caused
outages.
20
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #18: LOGSDON-4
LOGSDON 18
HARDIN - HILL ST (NEAR ETHAN CT) - VINE GROVE
LOGSDON-4
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
RADCLIFF, KY-VINELAND CENTER DR/, HILL ST A MANLEYAVE/AIRPORT RD
9.09
435
March-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
45.76%
PUBLIC ACCIDENTS, OTHER 54.24%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFl):
12. REPORTING YEAR (SAIFl):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
18.26
69.55
0.28
0.79
Feeder Inspection will identify areas for correction. Feeder
inspection will identify areas for correction.
21
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #19:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
L06SD0N-5
LOGSDON 18
HARDIN - HILL ST(NEAR ETHAN CT) - VINE GROVE
LOGSDON-5
RADCLIFF, KY-W. VINE ST./S. LOGSDON PKWY
7.3
513
March-15
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
90.12%
PUBLIC ACCIDENTS, OTHER 0.88%
SMALLANIMALS OR BIRDS 0.33%
TREES 1.92%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
6.39%
0.13%
0.24%
22.36
34.63
0.31
0.35
Feeder inspection to identify equipment for maintenance
22
SECTION 5: CIRCUIT REPORTING
{CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #20:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFl):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
MAGNOLIA-1
MAGNOLIAS
LARUE - NEW JACKSON HWY - MAGNOLIA
MAGNOLIA-1
MAGNOLIA, KY-JE JONES RD, MTSHERMAN, BAILEYX-ROADS,
MTTABOR RD, HWY 210, HWY 61.
107.19
980
January-16
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
29.67%
1.53%
0.00%
0.00%
PUBLIC ACCIDENTS, OTHER 2.57%
SMALLANIMALS OR BIRDS 44.52%
TREES 20.66%
WIND, HIGH WIND 1.06%
WEATHER 0.00%
126.48
159.53
1.33
2.31
Feeder inspection will identify areas to mitigate animalcaused outages. Feeder inspection to identify equipment for
maintenance.
23
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #21:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- VY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFl):
12. REPORTING YEAR (SAIFl):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
MAGNOLIA-4
MAGNOLIAS
LARUE - NEW JACKSON HWY - MAGNOLIA
MAGNOLIA-4
TANNER, KY - OAK HILL RD TO BRASHEARS RD, NEW JACKSON
HWY NORTH OF SUBSTATION, HAWKINS RD, SONORA RD,
SIBERIA RD, MURRIELTOWN RD.
77.19
493
August-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
33.26%
23.51%
0.00%
2.06%
PUBLIC ACCIDENTS, OTHER 15.74%
SMALLANIMALS OR BIRDS 1.71%
TREES 23.73%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
35.21
75.15
0.59
0.70
Feeder inspection to identify equipment for maintenance.Circuit was trimmed recently to remedy tree related outages.Nolin RECC to monitor this feeder to make sure ROW issues
have been corrected.
24
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #43:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
RADCLIFF-2
RADCLIFF 10
HARDIN - HILL ST(NEAR W. LINCOLN TRAIL BLVD) - RADCLIFF
RADCLIFF-2
VINE GROVE, KY - KNOX AVE, WEST SIDE OF SAFARI TRL, RED
HILL RD TO GERONIMO CIR, DITTO LN.
22.04
422
Aprii-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
21.03%
PUBLIC ACCIDENTS, OTHER 68.07%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 10.57%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.32%
0.00%
0.00%
99.00
114.73
1.23
1.17
Feeder inspection will identify areas for correction
25
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #22:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA);
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
RINEYVILLE-3
RINEYVILLE21
HARDIN - OWSLEY RD - RINEYVILLE
RINEYVILLE-3
RINEYVILLE, KY - BERRYTOWN RD, RINEYVILLE BIG SPRINGS RD,RINEYVILLE SCHOOL RD.
20.19
449
December-15
OUTAG E MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.40%
0.00%
8. LISTOFOUTAGE{S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
95.75%
PUBLICACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 3.85%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAlDI):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
1.52
87.93
0.02
1.03
Feeder inspection will identify areas for correction
26
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #23:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
RINEYVILLE-4
RINEYVILLE21
HARDIN - OWSLEY RD - RINEYVILLE
RINEYVILLE-4
RINEYVILLE, KY - BERRYTOWN RD./ BLUE BALL RD., SALT RIVER
RD.
50.26
391
May-15
0UTAGE M1N UTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.45%
2.71%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
95.31%
PUBLIC ACCIDENTS, OTHER 0.17%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 1.37%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFl);
12. REPORTING YEAR (SAIFl):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
100.03
89.54
0.73
1.09
Feeder Inspection will Identify areas for correction
27
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #24:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES);
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
RINEYVILLE-5
RINEYVILLE21
HARDIN - OWSLEY RD - RINEYVILLE
RINEYVILLE-5
RINEVILLE, KY- OWSLEY RD, RINEYVILLE RD, HARGAN RD,
PICKERELLLN, BENNET RD, BLACKBURN RD
28.6
504
October-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
2.00%
0.22%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
42.58%
PUBLIC ACCIDENTS, OTHER 50.69%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 4.51%
9. CIRCUITS YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
61.68
197.28
0.34
2.76
Feeder Inspection will identify areas for correction. FeederInspection will identify areas for correction.
28
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #25:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
STEPHENSBURG-1
STEPHENSBURG 6
HARDIN-LEITCHFIELD RD-STEPHENSBURG
STEPHENSBURG-1
GLENDALE, KY - STAR MILLS EASTVIEW RD, BACON CREEK RD,
HWY 222, CECILIA SMITH MILL RD, PARTRIDGE WAY.
41.57
401
December-14
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.90%
0.54%
0.03%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 62.63%
PUBLIC ACCIDENTS, OTHER 0.08%
SMALLANIMALS OR BIRDS 0.00%
TREES 35.83%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUITS YEAR AVERAGE (SAIFl):
12. REPORTING YEAR (SAIFl):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
55.14
343.29
0.86
2.90
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
29
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #26:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER;
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY);
STEPHENSBURG-2
STEPHENSBURG 6
HARDIN-LEITCHFIELD RD-STEPHENSBURG
STEPHENSBURG-2
WHITE HILLS, KY - SONORA HARDIN SPRINGS RD.
46.37
259
December-14
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.10%
1.49%
0.10%
8. LIST0F0UTA6E(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 96.45%
PUBLIC ACCIDENTS, OTHER 0.13%
SMALLANIMALS OR BIRDS 0.14%
TREES 1.60%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAID!):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BETAKEN
64.42
215.24
1.12
2.07
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability Issues.
30
SECTION 5: CIRCUIT REPORTING
fCIRCUlTS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #27:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YV):
STEPHENSBURG-3
STEPHENSBURG 6
HARDIN-LEITCHFIELDRD-STEPHENSBURG
STEPHENSBURG-3
STEPHENSBERG, KY - LEITCHFIELD RD./ SONORA HARDINSPRINGS RD./ WEBB MILLS RD.
69.62
554
December-14
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
0.13%
11.23%
0.04%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 78.12%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.00%
TREES 10.47%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUITS YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
51.69
265.75
0.76
2.44
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
31
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #28:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
STEPHENSBURG-4
STEPHENSBURG 6
HARDIN-LEITCHFIELD RD-STEPHENSBURG
STEPHENSBURG-4
EASTVIEW, KY - SONORA HARDIN SPRINGS RD./ EASTVIEW RD.
74.89
573
December-14
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
0.00%
0.04%
1.48%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
17.42%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.77%
TREES 9.06%
WIND, HIGH WIND 0.00%
WEATHER 22.31%48.92%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI);
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
60.52
424.33
0.95
3.62
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Reviewsectionalizing on feeder to minimize number of customers
impacted by equipment operations.
32
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #29:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN);
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
STEPHENSBURG-5
STEPHENSBURG6
HARDIN-LEITCHFIELDRD-STEPHENSBURG
STEPHENSBURG-5
STEPHENSBURG, KY - EASTVIEW RD./ NACKE PIKE RD.
71.45
605
December-14
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
0.00%
4.83%
0.04%
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 89.16%
PUBLIC ACCIDENTS, OTHER 2.04%
SMALLANIMALS OR BIRDS 1.92%
TREES 0.17%
WIND, HIGH WIND 0.00%
WEATHER 1.83%
9. CIRCUITS YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
43.62
232.83
0.64
2.25
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability Issues.
33
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #30:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
THARP-3
THARP 12
HARDIN - ST. JOHN RD. - ETOWN
THARP-3
ELIZABETHTOWN, KY-SAINT JOHN RD./ RING RD.
2.43
13
May-lS
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
76.98%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 23.02%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
0.00%
0.00%
50.31
89.82
1.05
1.31
Feeder inspection to identify equipment for maintenance
34
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEARAVERAGE!
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #31:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
TUNNEL HILL 1-1
TUNNEL HILL 111
HARDIN - TUNNEL HILL RD. - E-TOWN
TUNNEL HILL 1-1
ELIZABETHTOWN, KY - DOLPHIN RD./ COMMERCE DR.
7.46
437
March-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
59.77%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
0.06%
40.17%
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
80.06
135.52
0.37
2.29
Feeder inspection to Identify equipment for maintenance.Feeder Inspection will Identify areas for correction.
35
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #32:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
TUNNEL HILL 1-2
TUNNEL HILL 111
HARDIN - TUNNEL HILL RD. - E-TOWN
TUNNEL HILL 1-2
ELIZABETHTOWN, KY - TUNNEL HILL RD, RING RD, BON AIRE DR
7.41
708
April-13
OUTAGE MINUTES (%OFTOTAL OUTAGE MINUTES):
0.00%
0.18%
0.04%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
99.64%
PUBLIC ACCIDENTS, OTHER 0.14%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
10.83
140.90
0.23
1.02
Feeder inspection will Identify areas for correction
36
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIF! EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #33: TUNNEL HILL 1-4
TUNNEL HILL 111
HARDIN - TUNNEL HILL RD. - E-TOWN
TUNNEL HILL 1-4
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-
ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
ELIZABETHTOWN, KY-TUNNEL HILL RD, RING RD, FINANCIAL DR
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
2.26
57
August-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
0.00%
0.00%
PUBLIC ACCIDENTS, OTHER 100.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
No History
4.06
No History
0.04
Feeder inspection will identify areas for correction
37
SECTION 5: CIRCUIT REPORTING
(CIRCUITSWITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #34:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN);3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI);
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
TUNNEL HILL 2-4
TUNNEL HILL 2 19
HARDIN - TUNNEL HILL RD. - E-TOWN
TUNNEL HILL 2-4
ELIZABETHTOWN, KY- OLD TUNNEL HILL RD, WOODEN LN,FELIX CT, TUNNEL HILL RD, BLUE GRASS RD
15.27
555
December-15
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
0.00%
1.67%
19.59%
11.56%
0.00%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 57.43%
TREES 9.75%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
60.59
20.18
0.44
0.46
Feeder Inspection will identify areas to mitigate animalcaused outages. Identify new surge arrestor placement
opportunities. Review overvoltage protection.
38
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGEl
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #35:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- VY):
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
UPTON-2
UPTON 7
HARDIN - MILERSTOWN RD. - UPTON
UPTON-2
UPTON, KY- MILLERSTOWN RD, AKERS SCHOOL RD, CASH RD,
FLINT HILL RD, RAIDER HOLLOW RD, WAX RD.
46.28
348
August-15
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.20%
0.39%
0.36%
0.00%
PUBLIC ACCIDENTS, OTHER 0.33%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.06%
WIND, HIGH WIND 98.67%
WEATHER 0.00%
32.61
113.47
0.65
0.98
Feeder inspection will Identify areas to mitigate wind causedoutages.
39
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEARAVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #36:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN);
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
VERTREES-1
VERTREES 8
HARDIN - SALT RIVER RD. - VERTREES
VERTREES-1
VERTREES, KY - HARDINSBURG RD./ CONSTANTINE RD.
45.32
339
Aprll-12
OUTAGE MINUTES {% OF TOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
23.25%
PUBLICACCIDENTS, OTHER O.Q3%
SMALL ANIMALS OR BIRDS 0.00%
TREES 22.37%
WIND, HIGH WIND 12.38%
WEATHER 1.00%
1.71%
2.09%
37.18%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI);
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
167.01
414.78
0.85
5.63
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Feeder inspectionto identify equipment for maintenance.
40
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #37:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
VERTREES-2
VERTREES8
HARDIN - SALT RIVER RD. - VERTREES
VERTREES-2
VERTREES, KY-SALT RIVER RD./SAINT JOHN RD.
60.62
452
April-12
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.45%
5.40%
1.10%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 79.09%
PUBLIC ACCIDENTS, OTHER 0.08%
SMALLANIMALS OR BIRDS 6.34%
TREES 0.12%
WIND, HIGH WIND 0.00%
WEATHER 7.41%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI);
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
170.76
194.96
0.71
2.29
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
41
SECTION 5: CIRCUIT REPORTING
fCIRCUITS WITH SAIDI AND/OR SAIF! EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #38:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
VERTREES-4
VERTREES 8
HARDIN - SALT RIVER RD. - VERTREES
VERTREES-4
VERTREES, KY- HARDINSBURG RD./ LONG GROVE RD.
41.82
492
April-12
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
5.09%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
11.20%
PUBLIC ACCIDENTS, OTHER 47.61%
SMALLANIMALS OR BIRDS 0.07%
TREES 2.87%
WIND, HIGH WIND Q.00%
WEATHER 2.08%
0.04%
31.03%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
163.52
496.89
0.68
4.91
Feeder inspection will identify areas for correction. NolinRECC to work with EKPC to review remedies for
transmission/substation reliability issues.
42
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #39:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
VERTREES-5
VERTREES8
HARDIN - SALT RIVER RD. - VERTREES
VERTREES-5
EAST VIEW, KY - SALT RIVER RD., LAUREL RIDGE RD., SONORA
HARDIN SPRINGS RD., RIDGE TOP LN.
70.85
477
March-16
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.31%
2.29%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
10.09%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.08%
TREES 23.20%
WIND, HIGH WIND 0.00%
WEATHER 13.33%50.71%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFl):
12. REPORTING YEAR (SAIFl):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
167.78
304.06
1.18
2.59
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Circuit wastrimmed recently to remedy tree related outages. Nolin RECC
to monitor this feeder to make sure ROW issues have been
corrected.
43
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #40:
1. SUBSTATION NAME AND
NUMBER;
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
VINEGROVE-1
VINE GROVE 9
HARDIN - ROGERSVILLE RD. - VINE GROVE
VINEGROVE-1
VINE GROVE, KY- ROGERSVILLE RD., CRUME RD., DUGGIN
SWITCH RD., SAINT ANDREWS DR., FORTAVE.
25.19
534
May-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.27%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
59.28%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.15%
WIND, HIGH WIND Q.00%
WEATHER 6.64%
33.66%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
0.00%
136.38
138.86
1.64
2.02
Identify new surge arrester placement opportunities. Reviewovervoltage protection. Feeder inspection will Identify areas
for correction.
44
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #44:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- VY):
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
9. CIRCUIT 5 YEAR AVERAGE (SAIDl):
10. REPORTING YEAR (SAIDl):
11. CIRCUITS YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
VINEGROVE-7
VINE GROVE 9
HARDIN - ROGERSVILLE RD. - VINE GROVE
VINEGROVE-7
VINE GROVE, KY - DECKARD SCHOOL RD TO COUNTRY LN,
BURNS RD, DUGGIN SWITCH RD, VILLA RAY DR
16.85
285
Aprll-13
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
15.82%
0.00%
1.67%
0.00%
PUBLIC ACCIDENTS, OTHER 0.05%
SMALL ANIMALS OR BIRDS 0.00%
TREES 0.26%
WIND, HIGH WIND 0.00%
WEATHER 82.21%
134.06
134.78
1.23
0.52
Review sectlonalizing on feeder to minimize number of
customers impacted by equipment operations.
45
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDl AND/OR SAIFI EXCEEDING 5 YEAR AVERAGEl
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #45:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
WILLIAMS-1
WILLIAMS 16
HARDIN - BARDSTOWN RD. - E-TOWN
WILLIAMS-1
ELIZABETHTOWN, KY - BARDSTOWN RD./ LINCOLN RD.
30.43
816
December-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.50%
1.94%
0.06%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 94.49%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 2.75%
WIND, HIGH WIND 0.00%
WEATHER 0.27%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
49.94
298.45
0.69
1.12
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
46
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFl EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #46:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
W!LLIAMS-2
WILLIAMS 16
HARDIN - BARDSTOWN RD. - E-TOWN
WILLIAMS-2
ELIZABETHTOWN, KY-TO BARDSTOWN RD
0.21
December-13
OUTAGE MINUTES (% OF TOTAL OUTAGE MINUTES):
0.00%
0.00%
0.00%
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 100.00%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.00%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFl):
12. REPORTING YEAR (SAIFl):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
No History
282.00
No History
1.00
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
47
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MED)
CIRCUIT #41:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month- YY):
WILLlAMS-3
WILLIAMS 16
HARDIN - BARDSTOWN RD. - E-TOWN
WILLIAMS-3
ELIZABETHTOWN, KY - SPRINGFIELD RD, LOCUST GROVE RD,
MIDDLE CREEK RD, FORD HWY, VALLEY CREEK RD, MILLER RD,
HILLCREEK DR, BARDSTOWN RD
71.32
1124
December-13
OUTAGE MINUTES (% OFTOTAL OUTAGE MINUTES):
0.00%
8. LISTOFOUTAGE(S):
CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER
23.90%
PUBLIC ACCIDENTS, OTHER 2.45%
SMALLANIMALS OR BIRDS 12.74%
TREES 0.36%
WIND, HIGH WIND 0.00%
WEATHER 1.64%
0.49%
0.00%
58.42%
9. CIRCUIT 5 YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LISTOF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
68.40
482.73
0.78
3.15
Nolln RECC to work with EKPC to review remedies for
transmission/substation reliability issues. Feeder inspectionto identify equipment for maintenance.
48
SECTION 5: CIRCUIT REPORTING
(CIRCUITS WITH SAIDI AND/OR SAIFI EXCEEDING 5 YEAR AVERAGE)
(CIRCUIT NUMBERS SHOULD BE REPORTED EXCLUDING MEDl
CIRCUIT #47:
1. SUBSTATION NAME AND
NUMBER:
2. SUBSTATION LOCATION
(COUNTY-ROAD-TOWN):
3. CIRCUIT NAME AND NUMBER:
4. CIRCUIT LOCATION (TOWN-ROAD-GENERAL AREA):
5. TOTAL CIRCUIT LENGTH (MILES):
6. CUSTOMER COUNT FOR THIS
CIRCUIT:
7. DATE OF LAST CIRCUIT TRIM
(Month-YY):
WILUAMS-4
WILLIAMS 16
HARDIN - BARDSTOWN RD. - E-TOWN
WILLIAMS-4
ELIZABETHTOWN, KY - BARDSTOWN RD, N. MULBERRY ST EAST
OF 1-65, BETH CT,
13.52
452
December-13
0UTAGE MIN UTES (%OFTOTAL OUTAG E MIN UTES):
0.00%
2.20%
2.58%
0.00%
8. LISTOFOUTAGE(S):CONTRACTOR
EQUIPMENT/ MATERIAL FAILURE
LIGHTNING
NO CAUSE CODE
POWER SUPPLIER 95.18%
PUBLIC ACCIDENTS, OTHER 0.00%
SMALLANIMALS OR BIRDS 0.04%
TREES 0.00%
WIND, HIGH WIND 0.00%
WEATHER 0.00%
9. CIRCUITS YEAR AVERAGE (SAIDI):
10. REPORTING YEAR (SAIDI):
11. CIRCUIT 5 YEAR AVERAGE (SAIFI):
12. REPORTING YEAR (SAIFI):
13. LIST OF CORRECTIVE ACTION, IF
ANY, TAKEN OR TO BE TAKEN
32.06
296.29
0.39
1.19
Nolin RECC to work with EKPC to review remedies for
transmission/substation reliability issues.
49
SECTION 6: VEGETATION MANAGEMENT PLAN REVIEW
INCLUDE CURRENT VEGETATION MANAGEMENT PLAN
See attached Vegetation Management Program 2-18-11 Nolin.PDF"
SECTION 7: UTILITY COMMENTS
50
Vegetation Management Program
Definitions of Terms Used in Standard
This section includes newly defined or revised terms used in this standard. New or reviseddefinitions, listed below, become approved when the standard is placed in operation. Whenthe standard becomes effective, these defined terms will be removed from the individualstandard and added to the Glossary.
Fire Risk: The likelihood that a fire will ignite or spread in a particular geographic area.
Flashover: An electrical discharge through air around or over the surface of insulation,between objects of different potential, caused by placing a voltage across the air space thatresults in the ionization of the air space.
IEEE: Institute of Electrical and Electronics Engineers, Inc.
Vegetation Inspection: The systematic examination of a distribution corridor to documentvegetation conditions.
Operating Voltage: The voltage level by which an electrical system is designated and towhich certain operating characteristics of the system are related; also, the effective (root-mean-square) potential difference between any two conductors or between a conductor andthe ground. The actual voltage of the circuit may vary somewhat above or below this value.
Rated Electrical Operating Conditions: The specified or reasonably anticipated conditionsunder which the electrical system or an individual electrical circuit is intend/designed tooperate.
Right-of-Way (ROW): A corridor of land on which electric lines may be located. Thedistribution owner may own the land in fee, own an easement, or have certain franchise,prescription, or license rights to construct and maintain lines.
Sustained Outage: The de-energized condition of a distribution line resulting from a fault ordisturbance following an unsuccessful automatic reclosing sequence and/or unsuccessfulmanual reclosing procedure.
Distribution Line: A system of structures, wires, insulators and associated hardware thatcarry electric energy from one point to another in an electric power system. Lines are operatedat relatively high voltages varying from 120 V up to 7.2 kV, and are capable of transmittingquantities of electricity over long distances.
Vegetation: All plant material, growing or not, living or dead.
Appendix A Page 1
Introduction
Purpose:
To improve the reliability of the electric distribution systems by preventing outages fromvegetation located on distribution rights-of-way (ROW) and minimizing outages fromvegetation located adjacent to ROW, maintaining clearances between distribution lines andvegetation on and along distribution ROW.
This standard is developed for all distribution lines operated at 7.2 kV and to any lowervoltage lines designated by the Nolin Rural Electric Cooperative Corporation (RECC) ascritical to the reliability of the electric system in the region.
Requirements:
1) Nolin RECC will periodically review, and keep current, the formal distributionvegetation management program. The review will include the evaluation of objectives,practices, approved procedures, work specifications, and evaluation of SAIDI, SAIFI,CAIDI, and CAIFI. The outage management system (OMS) will collect informationfrom the automated meter reading (AMR) system, supervisory control and dataacquisition (SCADA) and input from the on-duty dispatcher for evaluation.
2) The plan defines a schedule for ROW vegetation inspections. This schedule will beflexible enough to adjust for changing conditions. The inspection schedule is based onthe anticipated growth of vegetation and any other environmental or operationalfactors that could impact the relationship of vegetation to the Nolin RECC'sdistribution lines.
3) Encourage public outreach to educate the public, in general, about the use andacceptance of vegetation management on rights-of-way.
4) Nolin RECC will, during initial installation, identify clearances between vegetationand any overhead, ungrounded supply conductors, taking into consideration the linevoltage, the effects of ambient temperature on conductor sag under maximum designloading, the configuration and insulated value of the line, and the effects of windvelocities on conductor sway. Specifically, Nolin RECC will establish clearances to beachieved at the time of vegetation management work to maintain a set of clearancesidentified to prevent flashover between vegetation and overhead-ungrounded supplyconductors. Nolin RECC shall determine appropriate clearance distances to beachieved at the time of distribution vegetation management work based upon:operating voltage, appropriate vegetation management techniques, fire risk, reasonablyanticipated tree and conductor movement, species types and growth rates, speciesfailure characteristics, local climate and rainfall patterns, line terrain and elevation,location of the vegetation within the span, and worker approach distance requirements.
Appendix A Page 2
5) Nolin RECC will determine specific radial clearances to be maintained betweenvegetation and conductors under all rated electrical operating conditions. Theseminimum clearance distances are necessary to prevent flashover between vegetationand conductors and may vary due to such factors as has been stated. Nolin RECCshall develop mitigation measures to achieve sufficient clearances for the protection ofthe distribution facilities when it identifies locations on the ROW where it is restricted
from attaining the clearances specified in this Requirement.
6) All personnel directly involved in the design and implementation of the VegetationManagement Program shall hold appropriate qualifications and training, as defined byNolin RECC, to perform their duties.
7) Nolin RECC shall establish a process for the communication of vegetation conditionsthat present an imminent threat of an outage to a distribution line. This is so actionmay be taken (temporary reduction in line's consumers, switching line out of service,etc.) until the threat is relieved.
8) Nolin RECC shall create and implement an annual plan for vegetation managementwork to ensure the reliability of the system. The plan shall describe the methods used,such as manual clearing, mechanical clearing, herbicide treatment, or other actions.The plan should be flexible enough to adjust to changing conditions, taking intoconsideration the anticipated growth of vegetation and other environmental factorsthat may have an impact on the reliability of the distribution systems. Adjustments tothe plan shall be documented as they occur. The plan should take into considerationthe time required to obtain permissions or permits from landowners or regulatoryauthorities. Each procedure for documenting and tracking the plarmed vegetationmanagement work and ensuring that the vegetation management work was completedaccording to work specifications.
Appendix A Page 3
Compliance to the Requirements
1. The overall 'Vegetation Management Plan' will be evaluated annually to establish theprogress of the plans' past year improvement against prior years. The comparison willinclude outage data of specific feeders, overall system outages, record keeping processof outage tickets, time response to outage lengths, comparison of funds to lines lengthsand type of work done, and AMR's blink reports. Each year the progress of the planwill be evaluated; deviations, deficiencies or improvements will be made for thefollowing year, and work procedures will be considered.
2. The inspection and right of clearing schedule will be 3 years in dense housing areas(approximately 14 consumers per mile), fast growing tree (locust, sycamore etc.) areasand in areas where trimming maybe limited (historic sites, national forest, andsensitive environmental areas). Other areas will be on the normal 5-year cycle.
3. An article describing the need for right of way maintenance, safety issues associatedwith live electric lines and trees, and proper tree selection for planting near electriclines will be mailed to all consumer's service address.
4. During System inspection, employees working on existing facilities will make calls tothe dispatcher about tree trimming or removal of trouble areas that may not complywith the RUS standard that is set forth in M1.30G "Right of wav clearing guide" and
standards set by the National Electrical Safety Code in Section 23. If no imminentdanger exists, the dispatcher will generate a Work Order Ticket for the correction ofthe problem.
5. Staking sheets will have notes associated for tree trimming or removal withdimensions from the centerline of the line construction. The notes will remain with
the staking sheets throughout the construction phase and final inspection of the jobs.The dimensions will comply with the RUS standard that is set forth in M1.30G '"'"Rightofway clearing guide^' and standards set in the National Electrical Safety Code inSection 23.
6. Employees will have annual training on the RUS standards and National ElectricalSafety Code relating to line construction and safety issues.
7. The dispatcher will be available 24 hours a day to take calls, make work order tickets,and dispatch employees for imminent danger of hazards to the public.
8. An overall system map will be color coded for work to be done each year. The mapwill be a base for planning and an estimate for budget numbers. The cost of variousmethods right of way control will be used as the land and environment dictate. Eachyear, during the planning period, an evaluation of outages and outages data will beused to set an estimated budget number. During the Budget planning, a dollar figurewill be set aside for the various methods of right of way control. The areas, as budgetpermits, will be designated as to method and length of lines to be done.
Appendix A Page 4