S TEE L N T ERe HAN G E Steel I nterchange is an open forum for Modern Steel Con- struction readers to exch ange useful and practical prof essional idea s and information on all phases of steel building a nd bridge construction. Opinions and s uggestions ar e welcome on any sub- ject covered in this magazine. If you have a question or problem th at your fe llow readers might help you to solve, pl ease forward it to Modern Steel Construction. At the same time, feel free to respond to any of the questions that you have read here . Pl ease send th em to: Steel Interchange Modern Steel Cons truction One East Wacker Dr. , Suite 3100 Chicago, IL 60601-2001 Answers a nd/or qu es tion s should be cl early prese nt ed. E- mail submittals and/or e-mail a tt achments are wel come. Th e opinions expressed in Steel Interchange do not necessar- ily re present an official pos ition of th e American Ins titut e of Steel Cons truction, Inc. and have not been reviewed. It is recog- ni zed th at th e d es ign of str uctu res is within th e scope and experti se of a competent licen sed s tructural engineer, a rchitect or other li censed prof essional for the application of principles to a pa rticul ar s tructure. To order an AISC publication menti oned in thi s article, call AISC Publi cat ions at 800/644-2400. * * * * Questions and answers can now be e-mailedto: grubb@ aiscmail .com * * * * Question from May 1999: Are there any references on the mainte- nance of weathering steel wall panels or structural members? Can weathering steel be painted? A n excellent reference for weatheri ng stee l is at the Bethlehem Burns H arbor web site: www.bethsteel.com/divisions/burns/bhweathstl.html Weathering s te el can be pa int ed an d the above web site ha s some specific suggestion s. Harold Sprague, P.E. The Neenan Company Fort Collins, CO Question from June 1999: Anchor rods (A307 or A36 material) occa- sionally get knocked and bent prior to the installation of the structural steel columns. Are there any guidelines or provisions for bending the anchor rods back into position? Are there limits to the degree of bending that can be straightened? Michael D. Gregory, P.E. Teton Structural Engineers Idaho Falls, ID I t s ounds as if your anch or rods had an encoun ter with a DB Cat and lost! Co nsideratio n mu st be given to the degree of be nd , the radius of the bend, and the diame ter of th e anch or rod. A sh ar p 90 degree cold bend in a 1- 1/2 in. diameter rod is like- ly to produc e mol e cul ar d istortion an d small cracks. Str aightening, even wit h h eat, would like- ly re s ult in reduced st r engt h in such a case. On the other hand , a gradu al cold be nd of 20 degrees in a 1 in . diameter r od would probab ly not be a problem. Similar be nds are rout inely made in fab- ricating shops. Anchor rods with slight bend s or rods which are cast into concrete in a t ilted position can usually be straightened without heating using a pipe "hickey." Contract docu ments u sually stipulate th at contem- plated repairs to d efective or damaged column anchorage be reviewed by the structural en gineer of record or other competent person. AlSC Design Guide No.1, Column Base Plates, contains broad information on column base design and construc- tion . Dav id T. Ricker, P.E. Javelina Explorations Pay son, AZ Another response: A nch or rods are frequently impacted an d bent 1"'1.on highway structures in the State of Illinois. If the degree of bending is sub s tantial , a significant amount of cumulative fatigue damage can be sus- taine d by the anchor. Bending it backwards causes further fatigue damage . The larger the anchor rod, the smaller the angle of bending that is tolerab le. Also, the material composition of the anchor rod is important . For example , an ASTM A3 6 anchor rod can generally sustain greater slow- strain-rate plastic deformation at 70 d egrees F than an ASTM F1554 105 ksi anchor, although its impact energy or fracture toughness may be signif - icantly different. This is particularly important for anchor rods used in seismic areas or those subject to fluctuating loads. The general rules I have use d in forensic analysis is that any bend which cau sed tearing at the th read roots or more than 2 to 5% l ocal pl astic deformation probab ly su stai n s a nascent or precu rsor fatigue crack. To remedy the problem, the bent area is cut off, and reconnected with coupling nuts of equ ivalent section and strength . Use of thread-locking com- pounds and torquing requirements are preferred if any vibrations may be encountered, which is typi- cally the case for sign /s ignal structures and bridges. Christopher Hahin , P.E. Illinoi s Department of Transportation Springfield, IL Modern Steel Cons truction / August 1999 / 9

Upload: vuongkiet

Post on 13-Mar-2018

217 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: S TEE L N T ERe HAN G E - AISC Home | American Institute ... TEE L N T ERe HAN G E Steel Interchange is an open forum for Modern Steel Con struction readers to exchange useful and

S TEE L N T ERe HAN G E Steel Interchange is an open forum for Modern Steel Con­

struction readers to exchange useful and practical professional ideas and information on all phases of steel building and bridge construction. Opinions and suggestions are welcome on any sub­ject covered in this magazine. If you have a question or problem that your fellow readers might help you to solve, please forward it to Modern Steel Construction. At the same time, feel free to respond to any of the questions that you have read here. Please send them to:

Steel Interchange Modern Steel Construction

One East Wacker Dr., Suite 3100 Chicago, IL 60601-2001

Answers and/or questions should be clearly presented. E­mail submittals and/or e-mail attachments are welcome.

The opinions expressed in S teel Interchange do not necessar­ily represent an official position of the American Institute of Steel Construction, Inc. and have not been reviewed. It is recog­nized that the design of st ructures is within the scope and expertise of a competent licensed structural engineer , architect or other licensed professional for the application of principles to a particular structure.

To order an AISC publication mentioned in this article, call AISC Publications at 800/644-2400.

* * * * Questions and answers can now be e-mailedto: [email protected] * * * *

Question from May 1999:

Are there any references on the mainte­nance of weathering steel wall panels o r structural members? Can weathering steel be painted?

An excellent reference for weathering steel is at the Bethlehem Burns Harbor web site:

www.bethsteel.com/divisions/burns/bhweathstl.html

Weathering steel can be painted and the above web site has some specific suggestions.

Harold Sprague, P.E. The Neenan Company Fort Collins, CO

Question from June 1999:

Anchor rods (A307 or A36 material) occa­sionally get knocked and bent prior to the installation of the structural steel columns. Are there any guidelines or provisions for bending the anchor rods back into position? Are there limits to the degree of bending that can be straightened?

Michael D. Gregory, P.E. Teton Structural Engineers Idaho Falls, ID

I t sounds as if your anchor rods had an encounter with a DB Cat and lost! Consideration must be

given to the degree of bend, the radius of the bend, and the diameter of the anchor rod. A sharp 90 degree cold bend in a 1-1/2 in. diameter rod is like­ly to produce molecula r distortion and small cracks. Straightening, even with heat, would like­ly result in reduced strength in such a case. On the other hand, a gradual cold bend of 20 degrees in a 1 in . diameter rod would probably not be a problem. Similar bends are routinely made in fab­ricating shops.

Anchor rods with slight bends or rods which are cast into concrete in a t ilted posit ion can usu ally be

straightened without heating using a pipe "h ickey." Contract documents usually stipulate that contem­plated repairs to defective or damaged colu mn anchorage be reviewed by the structural engineer of record or other competent person. AlSC Design Guide No.1, Column Base Plates, contains broad information on column base design and construc­tion.

David T. Ricker, P.E. Javelina Explorations Payson, AZ

Another response:

A nchor rods are frequently impacted and bent 1"'1.on highway structures in the State of Illinois. If the degree of bending is substantial, a significant amount of cumulative fatigue damage can be sus­tained by the anchor. Bending it backwards causes further fatigue damage. The larger the anchor rod, the smaller the angle of bending that is tolerable.

Also, the material composition of the anchor rod is important . For example , an ASTM A36 anchor rod can generally sustain greater slow­strain-rate plastic deformation at 70 degrees F than an ASTM F1554 105 ksi anchor, although its impact energy or fracture toughness may be signif­icantly different. This is particularly important for anchor rods used in seismic areas or those subject to fluctuating loads. The general rules I have used in forensic analysis is that any bend which caused tearing at the thread roots or more than 2 to 5% local p lastic deformation probably su stain s a nascent or precursor fatigue crack.

To remedy the problem, the bent area is cut off, and reconnected with coupling nuts of equ ivalent section and strength. Use of thread-locking com­pounds and torquing requirements are preferred if any vibrations may be encountered, which is typi­cally the case for sign/s ignal structures and bridges.

Christopher Hahin, P.E. Illinois Department of Transportation Springfield, IL

Modern Steel Construction / August 1999 / 9

Page 2: S TEE L N T ERe HAN G E - AISC Home | American Institute ... TEE L N T ERe HAN G E Steel Interchange is an open forum for Modern Steel Con struction readers to exchange useful and

S T 'E E L N T ERe HAN G E Question from June 1999:

Is there a publication or research paper which discusses the design of column base plate shear lugs made out of the standard W sections? In particular, should such shear lugs be designed for overall section bending and shear only due to the bearing pressure exerted against the concrete face, or should the effect of local flange or web bending be considered? Shear lugs are assumed to be confined in shear pockets by a non-shrink grout.

Mark Trojanowski, P.Eng. Hatch Mississauga, Ontario, Canada

II Thy consider using a wide flange section for a V V shear lug unless is is to use scraps from the

scrap bin? Think of the poor guy who has to cast the "H" shaped grooves in the top of the foundation and later has to pump or poke the grout into and around the positioned shear lug without allowing any skips or air pockets. There are better devices. AISC Design Guide No.1, Column Base Plates, contains basic information on column base design and construction. The use of heavy plate shear lugs in a crossing pattern should ease the question­er's concerns with wide flange section bending and local flange and web distortion resulting from shear forces.

David T. Ricker, P.E. Javelina Explorations Payson,AZ

I note that the AISC specification for com­posite members requires composite floor shear studs to extend up to 1.5 in. above the top of the deck.

How can a strength value be assigned to a stud that is short of this? While safe, it seems too conservative to say that the stud has no strength. LRFD Equation 13-1 considers stud length relative to deck height but is, as I understand it, designed to consider primarily the effects of narrow ribs. I will appreciate any discussion.

Alfred Hendrickson, P.E. Whitten & Borges, PC Billings, MT

The simplest, most direct way in which the ques­tion can be addressed is to conduct a series of

push-out tests on the particular configuration (deck type, stud length, etc.) in question. In lieu of this test data, an arbitrary reduction in the strength of the stud must be made. I have no data to support a particular number.

10 / Modern Steel Construction /August 1999

The strength reduction equation is used to account for the stud placed in steel deck, without regard to the issue of narrow or wide rib deck. Certainly the reduction is greater for "narrow" rib deck than it is for "wide" rib deck, however the equation is intended to be applicable to both.

As a side note, there will be a great deal of infor­mation coming forward in the next few months per­taining to the general behavior and design of weld­ed shear studs placed in steel deck . This information is the result of a significant number of push-out tests , beam tests and analytical study. However, the issue of studs less than 1.5 in. above the top of the deck was not considered. This value was maintained throughout the test program as a design minimum.

w. Samuel Easterling, Ph.D., P.E. Virginia Tech Blacksburg, VA

New Question Under what circumstances would one use a

cross sectional area other than gross area, of a threaded connector in tension? Or, when would one use the "tensile stress area" or "minimum root area" provided in the tables for Screw Threads, as contained in the AISC Manuals? How are these issues related to material properties or specification? Consid­er, as an example, a threaded rod in a tension splice.

Phil Pierce, P.E. Shumaker Consulting Engineering Vestal, NY